Phu My- Ho Chi Minh City (Phu My - Nha Be - Phu Lam) 500 kV Transmission Line Project package#1 substation works

Circuit-Breaker technical description

Written by Name Date Visa Modifi cation Rev01 Zanata

Approved by Larger 28/05/04

HV300977 rev01

Package #1 : TECHNICAL SCHEDULES

B.1

550 kV CIRCUIT BREAKER


Name of Manufacturer Country of origin Quantity ________ Nuova Magrini Galileo S.p.A _______________________________Italy For Phu My S/S For Nha Be S/S For Phu Lam S/S Type of circuit breaker Manufacturer's designation Manufacturing standards Number of phases Rated frequency Rated voltage Rated continuous current to IEC 62271-100 Rated insulation level (a) Power frequency withstand voltage,(to earth/across open breaker poles) dry, 1 minute kV (b) Lightning impulse withstand voltage (to earth/across open breaker poles) (c) Switching impulse withstand voltage (to earth/across open breaker poles) (+450) (d) Maximum permissible switching overvoltage kV Rated short-circuit breaking current (Three phase) : (a) Symmetrical breaking current (b) Asymmetrical breaking current (Single phase) : (d) Symmetrical breaking current (e) Asymmetrical breaking current Short circuit making current (a) One second (b) Three seconds Resistor Values (a) Opening-per phase Ohms _____________ / kA rms kA rms kA peak kA rms kA rms ____________ 50 ____________ 62 ___________ 125 ____________ 50 ____________ 50 kA rms kA rms ____________ 50 ____________ 62 ____________ 50 ___________ 858 kV 1175/900 kV __________ 1550 _______ 620/800 Hz kV A set(s) set(s) set(s) ____________ 15 _____________ 8 _____________ 1 ___ SF6 PUFFER __ 550 MHMe-2Y __ IEC 62271-100 _____________ 3 ____________ 50 ___________ 550 __________ 3150

(c) Maximum dc component as a percentage of (a) %

Short-time withstand currents in accordance with IEC 56

HV300977 rev01

Package #1 : TECHNICAL SCHEDULES

(b) Closing-per phase Resistor operating time (a) Closing pre-insertion time - Rated operation duty cycle

Ohms ms

_____________ / _____________ / 0-0,3S-CO-3min-CO

Number of successive auto-reclosing operations without derating (under normal service condition) First-phase-to-clear factor (a) Peak Uc (b) Rate of rise of restriking voltage kV peak kV/s kA A A A ______ O-CO-CO ___________ 1,3 ___________ 817 _____________ 2 __________ 12,5 ___________ 500 ___________ 500 ___________ 400 RESTRIKE FREE ms ms ____________ 20 ____________ 65 ____________ 22 _____________ 3 ___________ 300 ___________ 300 ____________ 40
ELECTROPNEUMATIC

Rated transient recovery voltage at rated short circuit breaking current

Rated out-of-phase switching capability to IEC 56 (a) Line charging current (b) Cable charging current (c) Capacitor current (d) Number of restrikes

Rated capacitance current switching capabilities to IEC 56:

Operating time in accordance with IEC 56 (a) Opening time (b) Closing time

(c) Maximum arcing time during current interruption ms (3 phase) (e) Minimum time for auto reclosing (dead time) Single phase Three phase last phase to clear (a) Closing (b) Opening Operating power consumption: (a) Trip coils current voltage (b) Closing coil current A A V ms ms ms ms

(d) Maximum difference in opening time between first and last phase to open

(f) Total break time (i.e. time from trip coil energisation to arc extinction in Circuit breaker operating mechanism type: (Hydraulic, Spring or Pneumatic) _ ELECTROPNEUMATIC

________ 1,8/0,9 _______ 110/220 ________ 1,8/0,9

HV300977 rev01

Package #1 : TECHNICAL SCHEDULES

voltage (c) Operating motor power voltage (d) Heater current Total estimated mass of circuit breaker unit: (a) One pole (b) Three pole Mass of largest single component Quantity of gas in circuit breaker (a) Volume at normal pressure (b) Mass Gas leakage per annum Interrupting gas pressure: (absolute value) (a) Maximum (b) Normal (c) Minimum (d) Alarm Loss of SF6 (e) Trip and lockout -

V kW V A kg kg kg m3 kg % bar bar bar bar bar

_______ 110/220 __________ 1500 ________ 400-3? ___________ 3,1 ____ 2910/2870 ____ 8900/8770 _____ 2500/2000 ______ 1,78/1,59 _________ 81/72 __________ <0,5 _____________ 7 _____________ 7 ___________ 6,5 ___________ 6,6 ___________ 6,5 _____________ 2

Number of close-open operations possible without recharging Number of operations before interrupter maintenance required (a) at rated short circuit current (b) at rated current ____________ 20 __________ 2000 ____________ 20

Number of years equipment of identical design has been in service Number of breaks in series per pole Maximum loading to be used for foundation/floor design (a) Vertical shock-load during operation at opening and at closing (b) Steady loading kg kg kg __________ 8000 __________ 4000 _____ 8900/8770 ____ 7,5 at 100 A __________ 32C __________ 4740 _________ >3840 _____________ 2

Voltage drop across main contacts of one pole mV K mm mm

Temperature rise of main contacts on continuous operation at rated current, and at ambient temperature 40C Minimum clearance (a) between phases (b) between live parts and earth

HV300977 rev01

Package #1 : TECHNICAL SCHEDULES

Insulator creepage distance

mm

___ 17050/ 13750

The type test certificate and/or report which has been carried out in accordance with the requirement of IEC 56 shall be submitted with the this Tender.

B.2

245 kV Circuit Breaker


Name of Manufacturer Country of origin Quantity Type of circuit breaker Manufacturer's designation Manufacturing standards Number of phases Rated frequency Rated voltage Rated continuous current Hz kV A ___________ Nuova Magrini Galileo S.p.A. _____________________________ ITALY for Nha Be S/S sets _____________ 2 _ PUFFER TYPE _____ SB6m 245 __ IEC 62271-100 _____________ 3 ____________ 50 ___________ 245 __________ 3150 ___________ 460 __________ 1050

Rated insulation level (a) Power frequency withstand voltage, dry, 1 minutekV (b) Lightning impulse withstand voltage kV

Rated short-circuit breaking current: (Three phase) : (a) Symmetrical breaking current (b) Asymmetrical breaking current kA rms kA rms kA peak kA rms kA rms ____________ 40 ____________ 46 ____________ 40 ___________ 100 ____________ 40 ____________ 40
_0-0,3S-CO-3min-CO

(c) Maximum dc component as a percentage of (a) % Short circuit making current (a) One second (b) Three seconds Rated operation duty cycle normal service condition) First-phase-to-clear factor (a) Peak Uc (b) Rate of rise of restriking voltage Rated out-of-phase switching capability to IEC 56 kV peak kV/s kA Short-time withstand currents in accordance with IEC 56

Number of successive auto-reclosing operations without derating (under ______ 0-CO-CO ___________ 1,5 ___________ 420 _____________ 2 ____________ 10

Rated transient recovery voltage at rated short circuit breaking current

Rated capacitance current switching capabilities to IEC 56:

HV300977 rev01

Package #1 : TECHNICAL SCHEDULES

(a) Line charging current (b) Cable charging current (c) Capacitor current (d) Number of restrikes Operating time in accordance with IEC 56 (a) Opening time (b) Closing time

A A A

___________ 125 ___________ 250 ___________ 400 RESTRIKE FREE

ms ms

____________ 30 ____________ 65 ____________ 22 _____________ 3 ___________ 300 ____________ 50 _________ spring _________ spring

(c) Maximum arcing time during current interruption ms (3 phase) (e) Minimum time for auto reclosing (dead time) Three Phase last phase to clear) (a) Closing (b) Opening Operating power consumption: (a) Trip coils current voltage (b) Closing coil current voltage (c) Operating motor power voltage (d) Heater current Total estimated mass of circuit breaker unit: (a) One pole (b) Three pole Mass of largest single component Quantity of gas in circuit breaker (a) Volume at normal pressure (b) Mass Gas leakage per annum Interrupting gas pressure: (absolute value) (a) Maximum bar m3 kg % kg kg kg kW V A kW V kW V ms ms ms

(d) Maximum difference in opening time between first and last phase to open

(f) Total break time (i.e. time from trip coil energisation to arc extinction in Circuit breaker operating mechanism type: (Hydraulic/Spring etc.)

_________ 0,300 ___________ 110 _________ 0,300 ___________ 110 _______ 0,270X3 ________ 230-1? ___________ 1,5 _________ 1050 _________ 3250 ___________ 800 __________ 0.55 ____________ 24 __________ <0,5 _____________ 7

HV300977 rev01

Package #1 : TECHNICAL SCHEDULES

(b) Normal (c) Minimum (d) Alarm Loss of SF6 (e) Trip and lockout -

bar bar bar bar

_____________ 7 ___________ 6,4 ___________ 6,7 ___________ 6,4 ______________

Number of close-open operations possible without recharging ___________ 1 Number of operations before interrupter maintenance required (a) at rated short circuit current (b) at rated current ____________ 20 __________ 2000 _____________ 1

Number of years equipment of identical design has been in service Number of breaks in series per pole Maximum loading to be used for foundation/floor design (a) Vertical shock-load during operation at open _______3000 kg and at close ________ 2000 kg (b) Steady loading kg mV K mm mm mm __________ 3250 ______4 at 100 A __________ 49C __________ 2810 __________ 1734 _________ >6125 _____________ 1

Voltage drop across main contacts of one pole and at ambient temperature 40C Minimum clearance (a) between phases (b) between live parts and earth

Temperature rise of main contacts on continuous operation at rated current,

Insulator creepage distance

The type test certificate and/or report which has been carried out in accordance with the requirement of IEC 56 shall be submitted with the this Tender.