Phu My- Ho Chi Minh City (Phu My - Nha Be - Phu Lam) 500 kV Transmission Line Project package#1 substation works
HV300977 rev01
B.1
HV300977 rev01
(b) Closing-per phase Resistor operating time (a) Closing pre-insertion time - Rated operation duty cycle
Ohms ms
Number of successive auto-reclosing operations without derating (under normal service condition) First-phase-to-clear factor (a) Peak Uc (b) Rate of rise of restriking voltage kV peak kV/s kA A A A ______ O-CO-CO ___________ 1,3 ___________ 817 _____________ 2 __________ 12,5 ___________ 500 ___________ 500 ___________ 400 RESTRIKE FREE ms ms ____________ 20 ____________ 65 ____________ 22 _____________ 3 ___________ 300 ___________ 300 ____________ 40
ELECTROPNEUMATIC
Rated out-of-phase switching capability to IEC 56 (a) Line charging current (b) Cable charging current (c) Capacitor current (d) Number of restrikes
Operating time in accordance with IEC 56 (a) Opening time (b) Closing time
(c) Maximum arcing time during current interruption ms (3 phase) (e) Minimum time for auto reclosing (dead time) Single phase Three phase last phase to clear (a) Closing (b) Opening Operating power consumption: (a) Trip coils current voltage (b) Closing coil current A A V ms ms ms ms
(d) Maximum difference in opening time between first and last phase to open
(f) Total break time (i.e. time from trip coil energisation to arc extinction in Circuit breaker operating mechanism type: (Hydraulic, Spring or Pneumatic) _ ELECTROPNEUMATIC
HV300977 rev01
voltage (c) Operating motor power voltage (d) Heater current Total estimated mass of circuit breaker unit: (a) One pole (b) Three pole Mass of largest single component Quantity of gas in circuit breaker (a) Volume at normal pressure (b) Mass Gas leakage per annum Interrupting gas pressure: (absolute value) (a) Maximum (b) Normal (c) Minimum (d) Alarm Loss of SF6 (e) Trip and lockout -
_______ 110/220 __________ 1500 ________ 400-3? ___________ 3,1 ____ 2910/2870 ____ 8900/8770 _____ 2500/2000 ______ 1,78/1,59 _________ 81/72 __________ <0,5 _____________ 7 _____________ 7 ___________ 6,5 ___________ 6,6 ___________ 6,5 _____________ 2
Number of close-open operations possible without recharging Number of operations before interrupter maintenance required (a) at rated short circuit current (b) at rated current ____________ 20 __________ 2000 ____________ 20
Number of years equipment of identical design has been in service Number of breaks in series per pole Maximum loading to be used for foundation/floor design (a) Vertical shock-load during operation at opening and at closing (b) Steady loading kg kg kg __________ 8000 __________ 4000 _____ 8900/8770 ____ 7,5 at 100 A __________ 32C __________ 4740 _________ >3840 _____________ 2
Temperature rise of main contacts on continuous operation at rated current, and at ambient temperature 40C Minimum clearance (a) between phases (b) between live parts and earth
HV300977 rev01
mm
The type test certificate and/or report which has been carried out in accordance with the requirement of IEC 56 shall be submitted with the this Tender.
B.2
Rated insulation level (a) Power frequency withstand voltage, dry, 1 minutekV (b) Lightning impulse withstand voltage kV
Rated short-circuit breaking current: (Three phase) : (a) Symmetrical breaking current (b) Asymmetrical breaking current kA rms kA rms kA peak kA rms kA rms ____________ 40 ____________ 46 ____________ 40 ___________ 100 ____________ 40 ____________ 40
_0-0,3S-CO-3min-CO
(c) Maximum dc component as a percentage of (a) % Short circuit making current (a) One second (b) Three seconds Rated operation duty cycle normal service condition) First-phase-to-clear factor (a) Peak Uc (b) Rate of rise of restriking voltage Rated out-of-phase switching capability to IEC 56 kV peak kV/s kA Short-time withstand currents in accordance with IEC 56
Number of successive auto-reclosing operations without derating (under ______ 0-CO-CO ___________ 1,5 ___________ 420 _____________ 2 ____________ 10
HV300977 rev01
(a) Line charging current (b) Cable charging current (c) Capacitor current (d) Number of restrikes Operating time in accordance with IEC 56 (a) Opening time (b) Closing time
A A A
ms ms
____________ 30 ____________ 65 ____________ 22 _____________ 3 ___________ 300 ____________ 50 _________ spring _________ spring
(c) Maximum arcing time during current interruption ms (3 phase) (e) Minimum time for auto reclosing (dead time) Three Phase last phase to clear) (a) Closing (b) Opening Operating power consumption: (a) Trip coils current voltage (b) Closing coil current voltage (c) Operating motor power voltage (d) Heater current Total estimated mass of circuit breaker unit: (a) One pole (b) Three pole Mass of largest single component Quantity of gas in circuit breaker (a) Volume at normal pressure (b) Mass Gas leakage per annum Interrupting gas pressure: (absolute value) (a) Maximum bar m3 kg % kg kg kg kW V A kW V kW V ms ms ms
(d) Maximum difference in opening time between first and last phase to open
(f) Total break time (i.e. time from trip coil energisation to arc extinction in Circuit breaker operating mechanism type: (Hydraulic/Spring etc.)
_________ 0,300 ___________ 110 _________ 0,300 ___________ 110 _______ 0,270X3 ________ 230-1? ___________ 1,5 _________ 1050 _________ 3250 ___________ 800 __________ 0.55 ____________ 24 __________ <0,5 _____________ 7
HV300977 rev01
(b) Normal (c) Minimum (d) Alarm Loss of SF6 (e) Trip and lockout -
Number of close-open operations possible without recharging ___________ 1 Number of operations before interrupter maintenance required (a) at rated short circuit current (b) at rated current ____________ 20 __________ 2000 _____________ 1
Number of years equipment of identical design has been in service Number of breaks in series per pole Maximum loading to be used for foundation/floor design (a) Vertical shock-load during operation at open _______3000 kg and at close ________ 2000 kg (b) Steady loading kg mV K mm mm mm __________ 3250 ______4 at 100 A __________ 49C __________ 2810 __________ 1734 _________ >6125 _____________ 1
Voltage drop across main contacts of one pole and at ambient temperature 40C Minimum clearance (a) between phases (b) between live parts and earth
The type test certificate and/or report which has been carried out in accordance with the requirement of IEC 56 shall be submitted with the this Tender.
HV300977 rev01