Вы находитесь на странице: 1из 8

High voltage engineering, Network protection

Power transformer protection


Overcurrent protection
ƒ overcurrent relay
ƒ instantaneous tripping in high-voltage side faults
ƒ delayed tripping in low-voltage side faults
ƒ inrush current (switching current surge)
has to be taken into account
ƒ differential relay
Earth fault protection
ƒ earthed network
ƒ overcurrent relaying
ƒ measurement and time delay of the neutral point current
ƒ differential current relay
ƒ neutral isolated network; measurement of zero-sequence voltage
(delay)

J.Partanen 1
www.ee.lut.fi/fi/lab/sahkomarkkina/

Network protection, Power transformer protection

Winding and interturn fault protection

In an interturn fault, there occur high currents in the


turns experiencing an interturn short circuit. However,
only small current changes can be seen outside
the transformer.

Buchholz gas relay


ƒ also insulation failures

Differential relay
ƒ faster than gas relay

J.Partanen 2
www.ee.lut.fi/fi/lab/sahkomarkkina/
Network protection, Power transformer protection

Overload protection

ƒ measurement of the oil temperature


ƒ time delay with respect to the temperature rise of the winding
ƒ winding temperature indicator
ƒ resistance element that passes a current proportional to the
load current

Overvoltage protection

> 10 % overvoltage damages the transformer (saturation)


U/f control

J.Partanen 3
www.ee.lut.fi/fi/lab/sahkomarkkina/

Network protection, Power transformer protection

Transformer differential protection


The protection has to be stable and sensitive:
Operation:
ƒ in faults inside the protection zone
ƒ when switching against a fault in the protection zone
ƒ when the transformer is overexcited
May not operate:
ƒ when switching a transformer to the grid (no fault)
ƒ when the voltage is restored to normal after clearing an external
fault
ƒ in faults outside the protection zone
ƒ when switching a parallel transformer to the grid
ƒ when switching a transformer against a fault outside the
protection zone

J.Partanen 4
www.ee.lut.fi/fi/lab/sahkomarkkina/
Network protection, Power transformer protection

P1 P2 110/20 kV P2 P1

J.Partanen 5
www.ee.lut.fi/fi/lab/sahkomarkkina/

Network protection, Power transformer protection

Transformer differential protection

Problems to be solved:
ƒ saturation of current transformers
ƒ transformer inrush current
ƒ transformer overexcitation
ƒ compensation of the vector group of the transformer
ƒ stabilization of the operation
ƒ no-load current
ƒ on-load tap changer

J.Partanen 6
www.ee.lut.fi/fi/lab/sahkomarkkina/
Network protection, Power transformer protection

Inrush current in the transformer


The iron core of the transformer saturates strongly
when, under certain conditions, the transformer is
connected to the network

The inrush current may reach a value of 10–20 x In, 500


x I0
ƒ depends on the transformer and the instant at which
the transformer is switched out (disconnected) from
the network
ƒ occurs always at some phase
ƒ dampens in 0.1–30 s
J.Partanen 7
www.ee.lut.fi/fi/lab/sahkomarkkina/

Network protection, Power transformer protection

The switching current includes plenty of harmonics;


compared with the excitation current of the normal
state, there occurs also some 2nd harmonic.
ƒ blocking based on the ratio I2/In (does not always work)
ƒ blocking based on the curve form of the differential current
Transformer Supply to the Supply to the Time in which the
power MVA high-voltage low-voltage current decreases to
side winding side winding half / s
1 7⋅îN 12⋅îN 0.1–0.2
5 5⋅îN 9⋅îN 0.2–0.5
10 4⋅îN 8⋅îN 0.5–1.0
50 3,5⋅îN 7,5⋅îN 1.2–7.2

Measured values of the transformer inrush current.

J.Partanen 8
www.ee.lut.fi/fi/lab/sahkomarkkina/
Network protection, Power transformer protection

Transformer overexcitation
Voltage rise of the transformer supply (load drop)

Φ ∼ U/f, voltage rise causes an increase in the excitation


current; an increase in harmonics in the differential current

Identification from the 5th current harmonic

Detection from the current curve form:


During the cycle, there are two periods, during which the
differential current is of the magnitude of the normal
excitation current.

J.Partanen 9
www.ee.lut.fi/fi/lab/sahkomarkkina/

Network protection, Power transformer protection

The transformer excitation current and the current harmonics in overvoltage


situation. The rated power of the transformer is 60 MVA and the rated
voltage 78 kV. The transformer core material is grain-oriented steel. In the
table below, U is voltage, Un rated voltage, Im transformer excitation current,
In transformer rated current, I1f fundamental harmonic of the excitation
current, I3f 3rd harmonic and I5f 5th harmonic.

U Im I1 f I3 f I5 f
/% /% /% /% /%
Un In Im I1 f I1 f
100 <1 93 34 24
110 2 76 67 48
120 8 72 76 54
130 25 76 73 44
140 46 80 68 32
150 70 84 62 22

J.Partanen 10
www.ee.lut.fi/fi/lab/sahkomarkkina/
Network protection, Power transformer protection

Current transformer saturation

DC component
ƒ there are plenty of 2nd and 3rd harmonics in the secondary
current
High primary current
ƒ only odd harmonics

In faults outside the protection zone, the current transformers of


the primary and secondary may saturate at different time instants
Æ differential current

Calculation of differential current right after the instant at which the


polarity (sign) of the current changes removes the above problem.

J.Partanen 11
www.ee.lut.fi/fi/lab/sahkomarkkina/

Protection technology, instrument transformers


Saturation of the current transformer

Excitation curve of the iron core


ƒ non-linear and saturating
ƒ knee-point voltage

Saturates
ƒ at a high sinusoidal overcurrent
ƒ as a result of the DC component of the primary current
ƒ as an effect of remanence

J.Partanen 12
www.ee.lut.fi/fi/lab/sahkomarkkina/
Protection technology, instrument transformers
Saturation of the current transformer
Magnetic flux density / T

Time / ms

Magnetic flux density of the core of a current transformer, when there is a high
short-circuit current including a DC component in the primary
(Bs ≈ 2.1 T and

J.Partanen 13
www.ee.lut.fi/fi/lab/sahkomarkkina/

Protection technology, instrument transformers


Saturation of the current transformer
Current / A

Primary current

Secondary current

Time / ms

Primary and secondary current of a current transformer saturated by a large DC


component. The primary current is referred to the secondary of the current
transformer.

J.Partanen 14
www.ee.lut.fi/fi/lab/sahkomarkkina/
Network protection, Power transformer protection

Vector group compensation

Numerical relays: mathematical algorithms

Yd and Dy compensation
ƒ subtraction of phase currents
ƒ problems in inrush current (phase shift ≠ 120°) and when the
current transformers are saturating
ƒ Delaying of samples
ƒ small delay

J.Partanen 15
www.ee.lut.fi/fi/lab/sahkomarkkina/

Network protection, Power transformer protection

Vector group compensation by delaying the samples of the phase current and by changing
the polarity (sign reversal). In the table, NS is the number of samples during one cycle. The
factor –1 corresponds to the 180° phase shift of the phase current.
Primary current Secondary current
Clock Delay Factor Delay Factor
reading
0 0 1 0 1
1 (1/12) · NS 1 0 1
2 (2/12) · NS 1 0 1
(3) (3/12) · NS (1) (0) (1)
4 0 -1 (2/12) · NS 1
5 0 -1 (1/12) · NS 1
6 0 -1 0 1
7 (1/12) · NS 1 0 -1
8 (2/12) · NS 1 0 -1
(9) (0) (1) ((3/12) · NS) (1)
10 0 1 (2/12) · NS 1
11 0 1 (1/12) · NS 1
J.Partanen 16
www.ee.lut.fi/fi/lab/sahkomarkkina/

Вам также может понравиться