Академический Документы
Профессиональный Документы
Культура Документы
uk
system particularly turbine blades in power plant at f requency below 47.5Hz. During normal operation of power system the amount of generation is equal to the amount of demand. Whenever the f aults occur, either the amount of generation is decreases or the amount of load is suddenly increases, the balance of power is violated and the f requency f alls at the predetermined threshold the portion of the load will be shed in a f ew steps to equalize the amount of demand and generation to prevent the system collapse. T he loads to be shed in this system are shed constant load f eeders and are not selected adaptively. In the other hand, these systems always drop the same load regardless of the location of disturbance. In this system loads are classif ied in three groups of non vital, semi vital and vital loads. T he system usually shed non vital load. Sometime in severe condition semi vital loads may also be shed. Although this kind of protection scheme is easy to implement, but it is suf f er in term of adaptability when various kind of f ault is experience. In the other hand, regardless of the severity of the disturbance, setting of the under f requency load shedding scheme is the same or constant. T his kind of scheme may be introduced over shedding or under shedding f or small disturbance or large disturbance respectively. In this project rate of change of f requency is proposed to enhance the adaptability of under f requency relays. By using this load shedding method, f ast reactions could be obtained f or major system f ailures. Adaptive under f requency load shedding (AUFLS) scheme can prevent complete system blackouts in the case of large or small disturbance. In other word, adaptive under f requency load shedding (AUFLS) scheme is specially designed to counter any kind of in coming disturbance applied. Rate of change of f requency, df /dt is the indicator to detect the magnitude of disturbance or f aults. T he rate of change of f requency df /dt is an instantaneous indicator of power imbalance and is presently used with the f requency f unction to provide a more selective or f aster operation. To make the rate of change of f requency df /dt as power def iciency indicator additional inf ormation about the system is required such as voltage, spinning reserve, load and etc. Such inf ormation may be communicated to the relay. T here are three types of the under f requency relays available f or load shedding scheme purpose. T hey are electromechanical relays, solid-state relays and digital relays. T he purpose of the under f requency relay is f or monitoring the f requency of an alternating current power line and protect the system by giving signal when ever the f requency drop below predetermine value f or a specif ic length interval. T he f requency of grid system must be maintain at 50Hz, if the f requency drop below nominal value the protection scheme must be initiated in order to maintain its generator on line even at low f requency. Frequency drop in power line may take several steps to measure. One of the methods is by using oscillator, the f requency which is substantially higher than the nominal f requency being measured, and counting the number of pulses f rom the oscillator during the period. When the line f requency decrease, the period will correspondingly increase, and theref ore a high number of oscillator output pulse will be obtained. It is no desired to detect under f requency condition which result in load shedding when an under f requency condition does not exist in f act, primarily because of the inconvenience may cause customer unsatisf ied. It is also because of the dif f iculty and duration taken to restore power to those customers. T he objective of the invention of under f requency relay is to provide method of detecting an under f requency condition on an alternating current power line including the step of sensing by means of electrical circuit. Af ter the power def icient has been cleared, the amount of the power generation and the power demand is approximately the same. T heref ore the f requency of the system will bring back to the acceptable level because the power imbalance is proportional to the f requency deviation. T hus, when the f requency is synchronous with the f requency of the grid system, the islanded locations will connected back to the grid in case of the f ault has been cleared.
1.1 OBJECTIVE:
AIM 1: To design adaptive under f requency load shedding scheme f or small Distributed Generation. AIM 2: To develop model to predict the rate of f requency (df /dt) decay during system disturbance.
understand well the method and design the algorithm. 3. Write program into C++ programming language based on the written algorithm. 4. Modeling simulation network by using Power System CAD (PSCAD) sof tware. Interf acing C code to the PSCAD sof tware. 5. Testing adaptive under f requency load shedding scheme in the simulation modeling. 6. T he result is studied f ro dif f erent power imbalance.
related to the government of f ice. T his method is compared with the conventional load shedding which is shed the same location which can cause the importance of the load. Usually, the loads to be shed are chosen f rom the loads which have low degree of importance and the loads are not concentrated at any specif ic area. For the purpose of preserving the island, the amount of the load and supply must be equal. T he power demand and supply is calculated to determine the amount of load to shed and the value will be used to select which load will be shed based on the importance of the load. T he less importance of the load, the f irst load will be shed and vice versa. T he value of the rate of change of f requency is inf luence the value of the load to be shed. Because the large disturbance the large load is to shed. Af ter load is reduced the total load is also reduced then the demand is approximately equal to the power supply. T heref ore the f requency is bringing back to the nominal f requency, but slightly below the nominal level. T he power of the total load might be loss in a small quantity. Af ter the f ault has been cleared the islanding location and the grid will reconnect in the case the islanding location and the grid is synchronous in term of f requency.
ref erred as the portion of the transmission system that connects the high voltage substations through step-down transf ormers to the distribution substations. T here is no clear delineation between transmission and sub transmission voltage levels. T he sub transmission voltage level usually ranges f rom 69KV to 138KV. Some large industrial customers may be served f rom the sub transmissions f or maintaining the transmission line voltage.
SWING EQUATION:
Under normal operating conditions, the relative position of the rotor axis and the resultant magnetic f ield axis is f ixed. T he angle between the two is known as power angle or torque angle. Whenever disturbances occur rotor will accelerate or decelerate with respect to the synchronously rotating air gap (mmf ), and a relative motion begins. T he equation describing this relative motion begins. T he equation describing this relative motion is known as the swing equation. If , af ter this oscillatory period, the rotor locks back into synchronous speed, the generator will maintaining its stability. In the case of the disturbance does not involve any net change in power, the rotor return to its original position. if the disturbance is created by a change in generation, load, or in network conditions, the rotor comes to a new operating power angle relative to the synchronously revolving f ield.
Consider a synchronous generator developing an electromagnetic Te and running at the synchronous speed wsm. If T m is the driving mechanical torque, then under steady state operation with losses neglected we have T m=Te (1) A departure f rom steady state due to the disturbance result in an accelerating (T m>Te) or decelerating (T m<="" p=""> Ta=T m-Te (2) If J is the combined moment of inertia of the prime mover and generator, neglecting f rictional and damping torques, f rom laws of rotation we have J(dw/dt) = T m Te = Ta (3)
Where
J is the moment of inertia(kg-m2) w Is the angular velocity(rad/s) dw/dt is the angular acceleration(rad/s2) Ta is the resulting torque(N-m)
voltage to the desired value. T he f actors which contribute power generation at minimum cost are operating ef f iciencies, f uel cost and transmission losses. A program called dispatch was developed to f ind the optimal dispatch of generation f or an interconnected power system. T he optimal dispatch may be considered within the f ramework of Load Frequency Control (LFC). Digital computer is included in the control loop which scans the unit generation and tie- line f lows in direct digital control systems. T hese setting are compared with the optimal settings which are derived f rom solution of the optimal dispatch program. If the actual settings are deviate f rom optimal values, the computer will generates the raise/lower pulses which are not sent to the individual units. T he other program will also be considered in the tie-line power contracts between the areas. Parallel with the development of modern control theory, several concept are included in the automatic generator control (AGC) which is go beyond the simple tie line bias control. T he basic approach is the use of more extended mathematical models. T he automatic generator control (AGC) can also be used to include the representations of the dynamic area and the complete system as well. Other concepts of modern control theory are also can be employed, such as state estimation and optimal control with linear regulator utilizing constant f eedback gains. In addition to the structures which aim at the control of deterministic signal and disturbances, there are scheme which use stochastic control concepts. T he generator excitation system should be maintaining voltage and controlling f low of reactive power. For older system generator excitation may be provided through slip rings and brushes by means of dc generators mounted on the same shaf t as the rotor of the synchronous machine, but f or modern generator excitation systems usually use ac generators with rotating rectif iers and are known as brushless excitation. Basically, when ever power demands change, it may result in f requency change, whereas a change in reactive power will result a change in the voltage magnitude essentially. T he relationship between voltage and f requency controls is generally weak enough to justif y their analysis separately. Reactive power is draws f rom generator, capacitor and reactors. Field excitation will control the generator reactive power. In addition methods of improving the voltage prof ile on electric transmission systems are transf ormer load tap changers, switched capacitors, step regulators and static var control equipment. T he generator excitation control primarily using automatic voltage regulator (AVR) f or generator reactive power control. T he purpose of the automatic voltage regulator (AVR) is to hold the terminal voltage magnitude of a synchronous generator at a specif ied level. If the reactive power loads of the generator increase the terminal voltage magnitude will decrease. T he potential transf ormer will detect the voltage magnitude. Terminal voltage will rectif y and compared to the dc set point signal. T he exciter f ield will controlled by the amplif ied error signals to increase the exciter terminal voltage. T heref ore, the generator f ield current is increased and directly increase the generated emf . T he reactive power generation is established in a new equilibrium, and increase the terminal voltage to the desired value.
energy resource (DER) technologies more economically viable and energy ef f icient, power electronics based conversion systems need to be developed f or proper conditioning of the energy to be delivered to the current three phase power system. T hese power conversion systems (PCS) allow f or increased reliability, security and f ewer downtimes by incorporating intentional islands into the utility grid without having to add or replace the existing transmission system. When distributed generation (DG) and their local load (the island) are isolated f rom a larger grid. If the distributed generation or so called synchronous generator and its prime mover ( a turbine or a reciprocating engine) and the load of this small "island" that can be isolated f rom the grid and powered by this generator and it's prime mover is 25 MW. So, when this island and it's generator are isolated f rom the larger grid some load has to be shed (automatically disconnected) in order not to exceed the rating of the generator's prime mover. In this example, a total of 5 MW of load would have to be disconnected f rom the isolated island in order not to exceed the rating of the generators' prime mover if it were to be operated at rated f requency when isolated f rom a largergrid. In order f or a prime mover and it's generator to energize a load at a constant f requency the prime mover needs to be operated in that way that it is controlling f requency in response to changes in load. T his is usually called Isochronous Governor mode, or Isochronous Speed Control mode. And a prime mover and its generator can only produce power at rated f requency up to the rating of the synchronous generator's prime mover. When the generator connected to a larger grid in parallel with other generators and their prime movers the normal mode of operation f or the prime mover governor (control system) is Droop Speed Control mode, this is because some other "entity" is controlling the f requency of the grid. when connected to a larger grid in parallel with other generators and their prime movers a generator can only produce power up to the rating of its prime mover. So, when a prime mover and its generator are suddenly disconnected f rom a larger grid and are to be provide power to a local load (the island) independent of the grid, the prime mover's governor is usually switched to Isochronous Speed Control mode. If the load of this small island exceeds the rating of the generator's prime mover then some of the load must automatically be disconnected, and this is ref erred to as load shedding. Usually, there is a contact on the breaker that connects the island to the larger grid that serves to tell the prime mover governor to switch f rom Droop Speed Control mode to Isochronous Speed Control mode *and* to initiate load shedding to reduce the load below the generator prime mover's rating. Depending on how f ast the load is shed when the grid tie breaker opens and also depending on how f ast the prime mover's governor (control system) can react to the change in load, what usually happens if the island load is initially greater than the prime mover's rating is that the f requency will decrease. Once the load of the island has been reduced to at least the rating of the generator prime mover and the prime mover's governor has responded to the change in load, then the f requency should return to rated and remain at rated as long as the load of the island does not exceed the rating of the generator's prime mover. As long as the island load is not allowed to exceed the rating of the generator's prime mover it should be able to respond to any change in load and still maintain rated f requency. T hat is, the prime mover's control system (the governor) should be able to respond to any change in load up the rating of the prime mover and still be able to maintain f requency. T he generator produces power at a f requency that is proportional to the speed at which it's rotor is being turned by the prime mover (the turbine or reciprocating engine). When operating a small island of isolated load, the amount of load must be less than the rated power of the prime mover driving the synchronous generator, or else the f requency will not remain at rated value. It's not the generator which controlling f requency or the amount of load, but it's the control system (the governor) of the generator's prime mover which is controlling the f requency (when operating in Isochronous Speed Control mode) or the load (when operating in Droop Speed Control mode in parallel
with other generators and their prime movers). A generator is just a device f or converting torque (f rom a prime mover) into amperes. T hose amperes can then be transmitted over wires to motors which convert the amperes into torque. (Lighting is a way to convert amperes into heat, heat so hot that it produces light.) So, the load of a generator is proportional to the amount of torque being produced by it's prime mover. And that torque is a f unction of the energy which f lowing into the prime mover (usually f uel or steam or water or wind).
additional load by increasing their power output when the grid f requency decreases. Whenever a machine which is to have 5% droop speed control will normally reach rated output when the speed ref erence reaches approximately 105% of rated speed. A machine with 4% droop will reach its rated power when the speed ref erence is 104%. T he power produced by the generator heavy duty gas turbine operating on most f uels is generally directly proportional to the f uel f low rate. T he rate of f uel injected is directly proportional to the f uel stroke ref erence (FSR), which is a ref erence f or the opening of the f uel control valve and/or the f uel f low rate through the control valve. T he purpose of droop speed control primarily is to allow a prime mover and its generator to smoothly and stably share in supplying the load of a grid while operating in parallel with other prime movers and their generators. T he secondary purpose of droop speed control is to help to maintain grid f requency when it varies f rom desired. When the grid f requency decreases because of the power imbalance (generally the amount of load is greater than generation), hence droop speed control increases the output to try to help support the local load at particular time. T he amount of generation must be balance with the amount of the load. Droop speed control is ref erred to as proportional control. T he amount of power produced is directly proportional to the error between the turbine speed ref erence and actual speed. T his is explaining that how the f uel is controlled during parallel operation with other prime movers and generator connected to a grid supplying a load. Prime movers mostly uses something similar, it is not only f or stable control of f uel f low f rom no load to rated load based on simple parameters, but it is also usef ul when trying to maintain load on a grid when the grid f requency is not at the rated output. T he speed error will decrease when ever the grid f requency increases above rated. Droop speed control does not try to make the actual speed of generator equal to the speed ref erence. It is based on the f act that there will be an error because under normal circumstances the grid f requency is stable at 100% and theref ore, the actual turbine speed is stable at 100%, and the amount of f uel f low is proportional to the error of speed which is dif f erent of actual speed and ref erence speed. A machine which have 4% droop setting in generally new and clean conditions being operated at ambient temperatures less than nameplate rated will usually reach exhaust temperature control or Base Load at T NR greater than 104% and the load will be greater than nameplate rated value. Generally f or every 1% change in T NR the unit power output will increase by approximately 25% of rated power output and this value is corresponding to the 4% droop speed control. In the case of a machine is not new or in other word in dirty compressor, high inlet f ilter dif f erential pressure and increased tolerances in the axial compressor and/or turbine sections, will not be as ef f icient and the change in load f or the change in T NR will be slightly depending on the severity of the condition less than specif ied values. A machine with 4% droop speed control might have only 23% increases power output and 1% change in speed error. T heref ore, with unclean condition the machine will not be able to achieve optimal result. Droop speed control is only part of the change in the power output relative to the speed error, and that portion is related to rated power output not actual power output under less than rated conditions. T he desired rated power output of the machine is only achieve if the machine in new and clean condition. T he main purpose of the droop speed control is to control prime mover governor to allow a prime mover and its generator to smoothly and stably share in supplying the load of a grid wile operating in parallel with other prime movers and their generators.
f requency is bring back to the acceptable level rapidly without introducing under shedding or over shedding. Large Disturbance: this diagram shows that the sharp drop of the f requency indicate that the islanding experience large disturbance. Medium Disturbance: this diagram shows that the f requency drop is slightly f aster and it is classif ied as medium disturbance because the f requency does not f all as f ast as in large disturbance. Small Disturbance: this diagram shows that the f requency drop is slower than the medium disturbance and this kind of disturbance is classif ied as small disturbance. T he rate of the f requency change is calculated by determine the value of the slope of f requency drop, the equation is shown below. T he short time interval, will give more accurate value. In the other word t2 and t1 must be in the short duration to get accurate value. s1 is representing the small disturbance which is the slope is bigger because the f requency is f all slowly. s2 is representing the slightly greater f rom small disturbance, which is the slope is slightly smaller than the small disturbance. s3 is representing the medium disturbance which is the slope is quite small because the f requency is drop quite f aster. s4 is representing the slightly greater f rom medium disturbance, which is the slope is slightly smaller than the medium disturbance. s5 is representing the large disturbance which is the slop is very small because the f requency is drop rapidly.
CHAPTER3: METHODOLOGY 3.1 INTRODUCTION ADAPTIVE UNDER FREQUENCY LOAD SHEDDING SCHEME
T he method that employed in this project is adaptive LD df /dt characteristic scheme. In this method the amount of load to be shed is a f unction of df /dt variable. T he load to be shed in based on the value of the df /dt. Because rate of change of f requency of the system will determine the magnitude of the disturbance, hence load to be shed is proportional to the value of the df /dt. Adaptive LD df /dt is very powerf ul characteristic to achieve proper load shedding. Whenever large disturbance occur, this scheme will shed large load and in the case of small disturbance occur, small load will be shed and the same cases f or medium disturbance. In other word, this load shedding scheme will introduce proper load shedding and enhancing the power system reliability without introducing large loss. T his type of scheme is designed several times f or dif f erent levels of df /dt. T he adaptive Under Frequency Load Shedding Scheme is specially designed to encounter f or any level of disturbance, with its related df /dt, minimum f requency of the system does not f all to the below a certain value. T his method is designed f or each value of df /dt a suitable value of LD is calculated where LD is the amount of the load to be shed.
In the adaptive under f requency load shedding scheme, the load will be shedding simultaneously based on the magnitude of the disturbance and it will result f aster recovery of f requency decline. Compared to the conventional load shedding, the take a f ew step to shed load and it will result under shedding or over shedding because they shed constantly regardless what kind of the disturbance it is applied. Hence it will result slower f requency recovery. In adaptive under f requency load shedding scheme, the main powerf ul tool is the rate of f requency change df /dt variable, so the load to be shed is programmed based on the several range of the df /dt value. 3. DET ERMINAT ION OF T HE AMOUNT OF LOAD T O BE SHED: T he f irst step is to calculate the amount of load to be shed to maintain f requency above minimum permissible f requency f or maximum expected overload. Total amount of load to be shed is calculated by the f ollowing equation: Where LD = total load that must be shed L = expected overload f = minimum permissible f requency d = load reduction f actor f n = nominal f requency (50Hz) T he value of the load must be shed is included in the several range of the rate of the f requency change. Because LD value is proportional to the value of the rate of f requency change. T he disturbance is large if the value of the rate of f requency change is large and directly the load to be shed is also large. T heref ore, the value of large load to be shed is included in the large value of df /dt interval. Adaptive under f requency load shedding scheme will be shed the load simultaneously or lump sum based of the magnitude of the disturbance. Compare to the conventional under f requency load shedding scheme, the load to be shed is divide into several percentage and shed f ollowing several steps. T his method will lead to the under shedding or over shedding. LD df /dt CHARACT ERIST IC SCHEME: T his characteristic scheme is very important part in adaptive under f requency load shedding scheme. T his part will distinguish between the conventional and adaptive under f requency load shedding scheme. In this method the amount of the to be shed is in the f unction of the df /dt. T he characteristic of LD df /dt is shown below. From the diagram, this method indicates that the load to be shed is in a f unction of df /dt. If the smallest the value of the df /dt the larger the load is to be shed. For example, Df 2 is large disturbance and its value is smaller, the load to be shed is LD3 which indicate that the largest load is to be shed. T his correlation is explaining that when the large disturbance occur, the f requency decline is very f ast which result the smaller value of df /dt and this indicate that the larger value of load must be shed to prevent excess f requency decline. In the case of Df 1, the load to be shed is LD2, this indicate when medium magnitude of disturbance occur, the medium value of load is to be shed. T he same case f or the small disturbance.
3.2.1 ALGORITHM
1. START 2. Insert values of Generation power, pg Frequency, f
Power load1, pload1 Power load2, pload2 Power load3, pload3 Power load4, pload4 Power load5, pload5 Power load6, pload6 Power load7, pload7 Power load8, pload8 Power load9, pload9 3. Calculate value of total power load, pt Total power load, pt = power load4, pload4 + power load5, pload5 + power load6, pload6 + power load7, pload7 + power load8, pload8 + power load9, pload9 Or Total power load, pt =pload4+pload5+pload6+pload7+pload8+pload9 Pload1 = pload4+pload5 Pload2=pload6 +pload7 Pload3 =pload8+pload9 4. Calculate expected overload, L or 5. Calculate d and LD 6. Calculate rate of f requency change, df /dt 7. Set several range of rate of change of f requency change, df /dt df /dt=s1=-0.0001 f or small disturbance which is large value of rate f requency drop df /dt=s2 =-0.002 f or slightly bigger than smaller disturbance which is slightly less than s1 f /dt=s3=-0.004 f or medium disturbance which is medium value of rate of f requency drop df /dt=s4=-0.005 f or slightly large than medium disturbance which is slightly smaller than s3 df /dt=s5=-0.007 f or large disturbance which is give smaller value of rate f requency change T he rate of f requency change is divided into several range if s2< df /dt< p=""> <> if s3< df /dt< p=""> <> if s4< df /dt< p=""> <> if s5< df /dt< p=""> <> if df /dt>s5 8. T he value of the load to be shed, LD is compared to the load which is selected to shed. If the load
to be shed is less or equal to the value of the selected load, the corresponding breaker of the load will be tripped. If LD<= selected load then the breaker will trip(sl) 9. Breaker trip. If logic 1 is send to the breaker, the breaker will be trip if logic 0 is send the breaker will close. In the PsCAD sof tware when the breaker close(load energize) the breaker is colored red while when the breaker trip(load not energize) the breaker is colored green. BRK=1(OPEN) GREEN BRK=0(CLOSE) RED 10. EXIT
WHAT IS PSCAD
PSCAD (Power Systems CAD) is a powerf ul and f lexible graphical user interf ace to the worldrenowned, EMT DC solution engine. PSCAD enables the user to schematically construct a circuit, run a simulation, analyze the results, and manage the data in a completely integrated, graphical environment. Online plotting f unctions, controls and meters are also included, so that the user can alter system parameters during a simulation run, and view the results directly. PSCAD comes complete with a library of pre-programmed and tested models, ranging f rom simple passive elements and control f unctions, to more complex models, such as electric machines, FACT S devices, transmission lines and cables. If a particular model does not exist, PSCAD provides the f lexibility of building custom models, either by assembling them graphically using existing models, or by utilising an intuitively designed Design Editor. T he f ollowing are some common models f ound in systems studied using PSCAD: Resistors, inductors, capacitors Mutually coupled windings, such as transf ormers Frequency dependent transmission lines and cables (including the most accurate time domain line model in the world!) Current and voltage sources Switches and breakers Protection and relaying Diodes, thyristors and GT Os Analog and digital control f unctions AC and DC machines, exciters, governors, stabilizers and inertial models Meters and measuring f unctions Generic DC and AC controls HVDC, SVC, and other FACT S controllers Wind source, turbines and governors PSCAD, and its simulation engine EMT DC, have enjoyed close to 30 years of development, inspired by ideas and suggestions by its ever strengthening, worldwide user base. T his development philosophy has helped to establish PSCAD as one of the most powerf ul and intuitive CAD sof tware packages available.
2. CREAT E NEW COMPONENT -New component is created to determine how many input and output we desire to do. Usually the lef t hand side is input and right hand side is the output. 3. CALL C SUBROUT INE - T he way we call c subroutine is by call c code f rom the c code f ile through the new component script. Write header in the c code f ile like f ollowing header And call c code through the new component script T heref ore, anything program written in the c code f ile will be read by calling through new component script. T he f low of operation is shown below.
be displayed by using graph f rame or control panel. Next step is take the data or storing the data to be use.
CHAPTER4: 4.1 CASE 1(For 0.9 p.u of power generat ion) DISCUSSION
In this case power generation is 4.09MVA and the power load is 5.25MW. T he power generated is 0.9 f rom the rated power. T here is imbalance of power exist and some load has to be shed to match with the power generated. T he expected overload, L is calculated and the value is 0.2934 which is indicate that the loss of 23 percent of total generation. T he load to be shed is 1.1623MW which indicate that this amount of power must be shed to bring back the f requency to nominal. T his amount is the minimum number of load must be shed. From the f requency graph, there is slope exist and it is indicate that there is power imbalance. For this case the rate of f requency change measured is -0.0003 Hz/s which is mean the f requency is drop -0.0003Hz in a second. T his value is not critical yet and hence it is consider as a small disturbance. T heref ore, this value of f requency change is f all at the f irst interval which is between -0.001 and -0.0001. if the load
shedding is not initiate the f requency drop at 45Hz which cause turbine blade damage. And by initiate load shedding scheme the f requency drop at 49.6Hz which is in the saf e mode. T he appropriate load to be shed is properly chosen. Because the priority load can not be shed, in this modeling network, the priority load is load 6 which is the larger load in this network. To choose load to be shed, the power imbalance is calculated and we got 1.19MW. T his number of load must be shed either equal or slightly equal. For this case the closer load is power load1 which have 1.2MW. T heref ore, power load1, load4 and load5 are shed by tripping breaker 2, 5, and 6 respectively. All the loads to be shed are shed simultaneously by tripping the breaker at the same time setting. T heref ore, the f requency will recover f aster and bring back to the acceptable level. So, the remain power load is 4.05MW which is approximately equal to the power generation which is 4.09MW. Hence, the f requency is bringing back to the nominal value. Network diagram shows that the corresponding load is shed. T he breaker is trip by give signal logic 1 to the breaker. Figure of 4.10, 4.11 and 4.12 shows the behavior of f requency when without load shedding, with load shedding and comparison between them respectively. T he f requency without load shedding f inish at slightly below load shedding f requency because the f requency can not bring back to nominal due to generator trip. Load shedding succeed to bring the f requency rise at 49.6Hz to prevent f rom total blackout. Figure 4.13 illustrate simulation model af ter load shedding.
match with the power generated. T he expected overload, L is calculated and the value is 0.6629 which is indicate that the loss of 40 percent of total generation. T he load to be shed is 2.02MW which indicate that this amount of power must be shed to bring back the f requency to nominal. T his amount is the minimum number of load must be shed. From the f requency graph, there is slope exist and it is indicate that there is power imbalance. For this case the rate of f requency change measured is -0.00409 Hz/s which is mean the f requency is drop -0.00409Hz in a second. T his value is critical and hence it is consider as a medium disturbance. T heref ore, this value of f requency change is f all at the third interval which is between -0.005 and -0.004. if the load shedding is not initiated the f requency is drop at 38Hz which cause the turbine blade damage. And by initiate load shedding scheme the f requency will drop at 48.2Hz which is in the saf e mode. T he appropriate load to be shed is properly chosen. Because the priority load can not be shed, in this modeling network, the priority load is load 6 which is the larger load in this network. To choose load to be shed, the power imbalance is calculated and we got 2.093MW. T his number of load must be shed either equal or slightly equal. For this case the closer load is total of power load1 and power load3 which have 1.2MW and 1.05MW respectively. T heref ore, power load1, load4, load5, load3, load8 and load9 are shed by tripping breaker 2, 4, 5, 6, 9 and 10 respectively. All the loads to be shed are shed simultaneously by tripping the breaker at the same time setting. T heref ore, the f requency will recover f aster and bring back to the acceptable level. So, the remain power load is 3.0MW which is approximately equal to the power generation which is 3.157MW. Hence, the f requency is bringing back to the nominal value. Network diagram shows that the corresponding load is shed. T he breaker is trip by give signal logic 1 to the breaker. Figure 4.30, 4.31, 4.32 shows the behavior of f requency when without load shedding, load shedding and comparison between them respectively. For this case, f requency with load shedding is slightly odd, because the gap between load shed and power generation is large which 0.157MW is. so the behavior of graph is inf luence by the response of the generator. Fortunately the f requency is still can be bring back to acceptable level. Figure 4.33 illustrate simulation model af ter load shedding.
border of the saf e mode which is 47.5Hz. af ter load shedding the f requency is bring back to the acceptable level. Figure 4.43 illustrate the simulation model af ter load shedding.
CHAPTER 5: CONCLUSION
Adaptive under f requency load shedding scheme is designed in this project to prevent f rom extreme f requency drop which might cause turbine blade damage and cause total blackout in power system. T he Adaptive LD-df /dt Characteristic scheme is applied f or this project. T his characteristic is very powerf ul to prevent f rom under shed or over shed which may cause large loss. Figure 4.44 shows the summary of Adaptive LD-df /dt Characteristic scheme. T his method is proven by changing the power imbalance between power generation and power load. T he power imbalance is represented as disturbance, the greater the imbalance between power generation and power load the greater disturbance exist. T he rate of f requency change is used as an indicator to determine the severity of the disturbance and theref ore predetermine action can be taken. T he instantaneous of f requency change is taken to predict the power imbalance inside the system. Simulation model is developing to predict the outcome of the scheme. T he algorithm is written in the sequence to properly shed the appropriate load. T he rate of f requency change can predict the disturbance. Simulation modeling shows the network af ter and bef ore the load shedding is initiated. When the load shedding is not applied the f requency is drop at 35Hz f or the worst case which cause damage turbine blade and cause total blackout. Whenever, Adaptive UFLS is applied , T he result is load to be shed is corresponding to the severity of the disturbance and load to be shed is shed simultaneously which result f aster f requency rise.
REFERENCES
1. (URL-http://en.wikipedia.org/wiki/Distributed_Generation), 17/11/2009a 2. (URL-http://www.dh.history.vt.edu/ch3/islanding.html), 17/11/2009b 3. (URL-http://en.wikipedia.org/wiki/Demand_Respond), 15/03/2010 4. (URL-http://f reepatentsonline.com/3993984.pdf .html), 16/03/2010 5. H. Saadat (2009) . Power System Analysis . 2nd Ed. Mc Graw Hill. Milwaukee Scholl of Engineering. 6. H.seyedi, M. Sanaye-Pasand (2009) . Design of New Load Shedding Special Protection Schemes f or a double Area Power System . American Journal of Applied Sciences 6(2):317-327. 7. IEEE Std C37.117 (2007) . IEEE Guide f or the Application of Protective Relays Used f or Abnormal Frequency Load Shedding and Restoration. IEEE Power Engineering Society. 8. L. Z hang, J. Z hong (2006) .UFLS Design by Using f and Integrating df /dt. T he University of Hong Kong. 9. V.V. Terzija (2006). Adaptive Under f requency Load Shedding Based on the Magnitude of the Disturbance Estimation. Senior Member, IEEE. 10. M. Parniani, Member, IEEE, and A.Nasri (2006). SCADA Based Under Frequency Load Shedding Integrated with Rate of Frequency Decline. Department of Electrical Engineering Sharif University of technology Tehran, Iran. 11. M. Sanaye Pasand, H.Seyedi. New Centralized Adaptive Under Frequency Load Shedding Algorithms. Senior Member, IEEE. 12. J.G. T hompson . Adaptive load shedding f or isolated power systems. B.Fox, Phd, CEng, MIEE. 13. V. Terzija. M. Kayikcitnei. D. Cai (2009), POWER IMBALNCE EST IMAT ION IN DIST RIBUT ION NET WORKS WIT H RENEWABLE ENERGY RESOURCES. 20th International Conf erence on
electricity Distribution. 8 -11. 14. V.V.Terzija (2006). Adaptive Underf requency Load Shedding Based on the Magnitude of the Disturbance Estimation. Senior member, IEEE. VOL. 21, NO. 3. 15. H.seyedi, M. Sanaye-Pasand. M.R Dadashzadeh. Design and Simulation of an Adaptive Load Shedding Algorithm using a Real Network. Senior Member, IEEE.
Share/download essay:
Request the removal of this essay...