Академический Документы
Профессиональный Документы
Культура Документы
START-UP CONTROL
There are two basic methods used for controlling the start-up of a chilled water system: 1. The most common method is manual initiation. With this method, the facility operating staff makes the decision to start the system on the basis of the time of year, outdoor temperature, and/or the number of hot complaints received from building occupants. This method is widely used in northern climates that have more distinctly separate heating and cooling seasons. 2. Outdoor temperature can be the trigger for starting a chilled water system, particularly if airside economizer systems are used in the facility. When airside economizer control is applied to building air-handling systems, outdoor air will satisfy imposed cooling requirements when the temperature is at or below the required air-handling units discharge temperature setpoint, usually about 55F. This temperature, then, may be set as the change-over temperature and the chilled water system is operated only when the outdoor temperature rises above this setpoint. Atypical scheme would be to start the chillers when the outdoor temperature rises to 60F and to stop them when the outdoor temperature falls to 55F.
Starting a chilled water system means, first of all, starting the chilled waterdistribution pumps. After that, the chiller will start upon initiation by its factory controls if the chilled water supply temperature is above its setpoint condition. For air-cooled chillers, the condenser fan(s) will start as required to maintain the correct condensing pressure. But, for water-cooled chillers, via hard-wired or software interlock, the factory chiller controls will start the condenser water pump and, then, if flow of both chilled water and condenser water is proven by flow switches (preferably, differential pressure type), the chiller will start.
71
72
Aside from the flow switches, every chiller is factory-equipped with basic operating safety controls to protect the refrigeration machine from damage due to any of the following conditions: 1. Low refrigerant temperature 2. Low chilled water temperature 3. High condensing pressure 4. Low oil pressure
In the event that any of these conditions exists, the chiller will shut down and require manual investigation and reset before operation can resume. For rotary compressor chillers, there are typically two additional safety cutouts: 1. High motor winding temperature 2. Motor overload (high amps)
CAPACITY CONTROL
Modern water chillers are normally provided with digital electronic controls designed and integrated by the chiller manufacturer. In addition to the operating safety elements outlined in the previous section, these controls are used to provide capacity control based on maintaining a supply chilled water temperature setpoint.
73
onstant, the seal pressure is modulated, allowing more or less refrigerc ant to bypass around the seals, loading or unloading the scrolls. Rotary screw compressors. Since the rotary screw compressor is a positivedisplacement compressor, suction throttling can reduce the refrigerant gas flow into the compressor. A modulating control method is desirable to produce essentially infinite capacity adjustment between the minimum and maximum flow rates and capacities. A slide valve is a hot-gas bypass control valve with a sliding action arranged parallel to the rotor bores and located at the high-pressure discharge of the compressor. The valve is then modulated to return a variable portion of the discharge gas back to the compressor suction. This valve, in addition to controlling capacity, also adjusts the location of the compressor discharge port as the load changes. This axial discharge port then provides good part load performance without reducing full-load efficiency. Centrifugal compressors. Historically, refrigerant gas flow into a centrifugal compressor has been controlled by adjustable inlet guide vanes, or preswirl or prerotation vanes, just as with a centrifugal fan. These vanes are arranged radially at the inlet to the compressor impeller and can be opened and closed by an external operator. Since each vane rotates around an axial shaft, they affect the direction of the flow entering the impeller. When the inlet vanes are fully open, gas enters the impeller at 90 to the impeller. However, as the inlet vanes begin to close, flow enters the impeller at an increasing angle in the direction of the radial flow along the impeller blades. This preswirl condition reduces the ability of the impeller to impart kinetic energy to the refrigerant gas, thus reducing the flow rate. Inlet vanes do not produce a pressure drop or throttling to reduce refrigerant flow through the centrifugal compressor. A minimum volumetric rate flow through a centrifugal compressor is required for stable operation. If the volumetric flow rates fall below this minimum, the compressor will become unstable and surge. When this happens, the refrigerant flows alternatively backward and forward through the compressor, producing noise and poor operation. Extended operation under surge conditions will cause mechanical damage to the compressor. The surge envelope will vary from compressor to compressor but usually occurs when the volumetric flow rate is reduced by 4060%. To prevent surge from occurring, internal hot-gas bypass may be used to allow capacity to be reduced while maintaining sufficient gas flow through the compressor. (This condition, along with increasing windage losses and motor inefficiencies, accounts for the part-load performance characteristics shown in Figure 1.7.) In recent years, capacity control of centrifugal chillers by speed control has been applied. Here, a large variable frequency drive is applied to the chiller motor and the motor speed modulated to control capacity. Generally,
74
speed control improves efficiency over inlet vane control down to about 55% of rated capacity; whole inlet vane control is more efficient below 55% of rated capacity. Compressor speed is directly related to capacity, but the pressure (lift) produced by the compressor is a function of the square of the speed. This may produce unsatisfactory operation and surge, requiring the use of hot gas bypass, as the chiller unloads under speed control. Adding speed control significantly increases the price of the chiller and this option must be carefully evaluated to determine if this concept is cost effective for a given cooling load profile.
75
Again, consider a system with a 44F supply chilled water temperature, a 12F range, and three equally sized chillers arranged in a primarysecondary configuration. At full cooling load the flow rates in the primary and secondary loops are exactly equal and the temperature in the return section of the primary loop is equal to the return temperature from the secondary loop, 56F. However, as the cooling load falls, the secondary flow rate decreases. Since the primary loop flow rate now exceeds the secondary loop flow rate, chilled water from the supply side of primary loop mixes with return water from the secondary loop to produce a reduced temperature in the return side of the primary loop. When this temperature falls to 52F, one chiller can be stopped since the reduced return water temperature indicates that the cooling load has declined by one-third. When a chiller is stopped, the flow rate in the primary loop is reduced by one-third and now again equals the secondary flow rate. Blending is eliminated and the temperature in the return side of the primary loop returns to 56F. If the cooling load continues to fall, the temperature in the return side of the primary loop will again begin to fall as blending is reinitiated. When it falls to 50F, the second chiller can be stopped. As the cooling load increases, the flow in the secondary loop will begin to exceed the flow in the primary loop. Under these conditions, the temperature in the primary loop will rise to above 56F, which indicates that a chiller must be started. The general algorithm for control of chiller sequencing in a primary secondary system made up of any number of equally sized chiller modules (a chiller and a primary chilled water pump) can be stated as follows: T1=Tc+Td
where T1=the secondary loop chilled water temperature setpoint Tc=the system supply chilled water temperature setpoint Td=the system design temperature range If (Tr+0.5), where Tr is the primary loop return water temperature, is greater than T1 for at least 30min, start a chiller. T2=Td/N, where T2 is the range assigned to each on N equally sized chillers. If (Tr0.5) is less than (T1T2) for at least 30min, stop a chiller. 3. Sequencing chillers in a variable primary configuration is relatively complex. Each chiller must be equipped with a high-quality flow meter that is used to measure flow through each chiller evaporator. Again, consider a system with a 44F supply chilled water temperature, a 12F range, and three equally sized chillers. At full load, all chillers operate at full flow, chilled water is supplied to the coils at 44F, and the return temperature is 56F.
76
As the cooling load falls, the pump speed on each chiller reduces to deliver less flow and maintain the return water temperature setpoint of 56F. Once the flow through all three chillers is reduced to 67% of design flow, one chiller and pump can be stopped. Once the flow through the remaining chillers is reduced to 50% of design flow, the second chiller can be stopped. As cooling load increases, the chillers can be started at these same flow conditions.
77
temperature or humidity sensors remain above the maximum required zone temperature or humidity level, reduce chilled water temperature by 0.2F and monitor system for another 15min. Continue this process until all temperature sensors return to within their required temperature or humidity range and then return to Step 3.
where M =mass flow rate (lbm/min) C =specific heat of the fluid (Btu/lbF) T =temperature of the fluids, hot (Th) and cold (Tc), respectively (F) d A =differential area of the coil under study (ft2) Integrating this equation over the entire area of the coil yields Q= UA ( TD i TDo ) ln ( TD i / TDo )
where TD=ThTc at the inlet (i) and outlet (o) conditions, respectively. The temperature term (TDiTDo)/ln(TDi/TDo) is called the logarithmic mean tem perature difference (LMTD). Since U is defined by the design of the coil and the materials used in construction, which is fairly consistent between manufacturers, the basic performance of any coil is defined by the coil surface area and the temperatures required, or LMTD. If large temperature differences are available, as for most heating applications, the required coil area is small. For small temperature differences, as for chilled water systems, the coil area is large.
78
Water coil surface area is defined by the number of rows of tubes and the pacing, or density, of the fins (in terms of fins/in. of coil width). Thus, a heating s coil may have 1 or 2 rows and 810 fins/in., but a cooling coil will have 68 rows and up to 16fins/in. The capacity of any water coil is controlled by modulating the flow of liquid through the coil. However, as flow is reduced, the capacity of the coil is not reduced linearly. To compensate for this nonlinearity, equal percentage characteristic control valves are utilized, resulting in a linear relationship between coil capacity and valve stroke or percent open, as shown in Figure 4.1. These control valves must be selected on the basis of the maximum design flow through the coil and a wide open pressure drop equal to or greater than the pressure drop through the coil. Additionally, the valves must be rated for tight shutoff against the maximum system pressure that is developed, which, for variable flow systems, is the pump cutoff pressure, the pressure the pump will develop at zero flow. As load is reduced at a cooling coil, the control valve throttles flow to the coil to match flow capacity to the coil load as follows: 1. Secondary chilled water pumps in a primarysecondary configuration can reduce their flow rate by either increasing head (forcing a flow reduction along the pump curve) or decreasing pump speed. The second method is more efficient and produces significant energy savings compared to the first. Thus, except for very small systems (<10hp), VFDs are used to modulate pump speed in response to flow needs (see the section Variable Flow Pumping in Chapter 3). Accurate control of pump speed, and thus flow rate, is critical.
0% Stem travel 100% 100%
100%
Heat transfer
Control valve
0%
0%
Design flow
0% 100%
FIGURE 4.1 Coil capacity control with equal percentage control valve.
Coil capacity
79
When variable flow chilled water systems were introduced in the early 1980s, pressure control was typically used. A pressure sensor, located sufficiently downstream from the pump to be sensitive to control valve action, can respond to the pressure increase produced by throttling control valves by reducing the pump speed and, consequently, flow rate and pressure. But, it quickly became obvious that pressure control represented an attempt to respond to a symptom rather than to the disease. While pressure changes with flow changes, the change is not linear (pressure changes as the square of flow), multiple valves of different sizes may have different pressure/flow relationships, and the resulting pressure change in a larger system may have not real relationship to the cooling load. The basis of design for a primarysecondary system is to maintain a fixed chilled water supply temperature and a fixed temperature range in the secondary loop. If, by chiller capacity control and proper sequencing of chillers, the chilled water supply temperature is maintained at setpoint, the design range can be used to establish a return chilled water temperature setpoint to control pump speed. Any variation in the return chilled water temperature must result in an opposite linear change in the chilled water flow rate. 2. Variable flow control in a variable flow primary configuration is essentially the same as for the secondary pumps in a primarysecondary configuration. As the pump speed is reduced, both flow rate and pressure are reduced. Ultimately, the available pressure at reduced flow rates may not be sufficient to ensure water flow to the more remote coils and, thus, these coils are starved and they fail to cool at all. To prevent this problem, one or more differential pressure sensors must be installed across the most remote flow circuit(s) and a minimum pressure setpoint determined for each circuit. Then, as the pump speed is reduced, if the pressure falls below the required setpoint in any circuit, further reduction of pump speed in inhibited. At this point, the system essentially becomes constantflow. For variable primary flow systems, there is also a minimum flow requirement through the chiller, equal to 3fps or about 2530% of design flow. A bypass control valve must be modulated open when the flow rate through the last operating chiller is reduced to its minimum level, as indicated by the chiller flow meter.