SITE ACCEPTANCE TEST RECORD

Contractor:

Date: 14-11-2012 to 20-11-2012


Contract No:

Description: Site:

LINE DIFFERENTIAL RELAY- TYPE 7SD522


230/ 115KV MAHASEN BSP
Panel/Bay Name:

31033077/00

=2DD/ 115KV ABUGHANIMA SS LINE SET-2 PANEL

1. RELAY CHARACTERISTICS
Panel Reference Manufacturer Type Relay model (MLFB) Firmware version Serial number Rated current Rated voltage Rated frequency Auxiliary voltage =2DD SIEMENS SIPROTEC 7SD522 7SD5225-5DB99-7HM6-OS2A V 04.7.07 BF 1112072666 5A 100 125Vac 50 / 60Hz 110-250Vdc

2. M ECHAN ICAL

CHECKS
Checking Visual inspection Conformity with drawings Connection conformity with drawing Case earthing connection Results OK OK OK OK

3. ELECTRICAL CHECKS
Checking Indications checked. Alarm contacts checked. Trip contacts checked. Reset of indications checked. Results OK OK OK OK

Tested by: NCC Name : VARUSAI MOHAMMED Signature:

Witnessed by: SEC-P&TD-E


Name: RAMZI

P a g e | 1 of
15

Signature:

NATIONAL CONTRACTING CO. LTD., T&D CENTER, P.O. BOX 90, AL-KHOBAR-31952, KSA

SITE ACCEPTANCE TEST RECORD


Contractor:

Date: 14-11-2012 to 20-11-2012


Contract No:

Description: Site:

LINE DIFFERENTIAL RELAY- TYPE 7SD522


230/ 115KV MAHASEN BSP
Panel/Bay Name:

31033077/00

=2DD/ 115KV ABUGHANIMA SS LINE SET-2 PANEL

4.OPERATIONAL MEASUREMENTS:
CTR : 1200 /5A Distance Protection = 1201=OFF. Applied : PTR :115000/115V

VPH - N = 66.4 V
PARAMETER

I PH = 5 AMP

V-I

= 30.

MEASURED VALUES IN THE RELAY S.N0 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. PRIMARY MEASUREMENT SECONDARY MEASUREMENT PERCENT %

IA IB IC Ia=5 0,Ib=10 180,Ic=0,3I0= 5A VA VB VC V A-B V B-C V C-A Va=46.39 0,Vb=66.39 180, Vc=0,3U0=20V S P Q FREQUENCY P.F

1200A 1200A 1200A 1200A 66KV 66KV 66KV 115KV 115KV 115KV 20KV 239MVA 239MW -0MVAR 60Hz 0.99

4.99A 4.99A 4.99A 4.99A 66.38V 66.38V 66.43V 114.99V 115V 115V 20V 60Hz 0.99

99.9 99.9 99.9 99.9 100.0 100.0 100.0 100.0 100.0 100.0 30.1 99.8 99.8 -0.1 100.0 -

5. DIRECTIONAL TEST:
PHASE DISTANCE: QUAD, EARTH DISTANCE: QUAD, ANGLE DIRECTION
FORWARD UNDEFINED REVERSE UNDEFINED

FROM 338.2 120.2 150 300.2

TO 120.1 149.9 300.1 338.1

Tested by: NCC Name : VARUSAI MOHAMMED Signature:

Witnessed by: SEC-P&TD-E


Name: RAMZI

P a g e | 2 of
15

Signature:

NATIONAL CONTRACTING CO. LTD., T&D CENTER, P.O. BOX 90, AL-KHOBAR-31952, KSA

SITE ACCEPTANCE TEST RECORD


Contractor:

Date: 14-11-2012 to 20-11-2012


Contract No:

Description: Site:

LINE DIFFERENTIAL RELAY- TYPE 7SD522


230/ 115KV MAHASEN BSP
Panel/Bay Name:

31033077/00

=2DD/ 115KV ABUGHANIMA SS LINE SET-2 PANEL

6. FAULT DETECTION TEST:


2910: FUSE FAILURE MONITOR=OFF, 2901: MEASUREMENT SUPERVISION=OFF. 1201: ALL ZONES OF DISTANCE = ON, 1) PHASE OVER CURRENT DETECTION - I ph > : 1202: I ph > for Distance Measurement & INJECT CURRENT IN PHASE TO PHASE.

I ph> Setting
0.5 A

Pick up
0.508 A

3Io DETECTION:. ( set address 1509A : 3U0 and 3I0 , then inject morethan 5V in yellow phase , then vary current in R phase upto pickup)

3Io > Setting


0.5 A

Pick up
0.504

2) 3 Vo DETECTION:( set address 1509A: 3U0 and 3I0, then inject morethan 0.5 A

in Rphase, then vary voltage in yellow phase until pickup)

3Vo > Setting


5.0 V

Pick up
4.99 V

Tested by: NCC Name : VARUSAI MOHAMMED Signature:

Witnessed by: SEC-P&TD-E


Name: RAMZI

P a g e | 3 of
15

Signature:

NATIONAL CONTRACTING CO. LTD., T&D CENTER, P.O. BOX 90, AL-KHOBAR-31952, KSA

SITE ACCEPTANCE TEST RECORD


Contractor:

Date: 14-11-2012 to 20-11-2012


Contract No:

Description: Site:

LINE DIFFERENTIAL RELAY- TYPE 7SD522


230/ 115KV MAHASEN BSP
Panel/Bay Name:

31033077/00

=2DD/ 115KV ABUGHANIMA SS LINE SET-2 PANEL

4.2

Breaker Failure Phase Over Current. Phase A B C Current Setting (Amps) 2 2 2 Pickup Amps 2.000 2.000 1.999

4.3Breaker Failure Operating Times Stage 1 & 2 Set current = 1 A Set Time T1 1 1 (Secs) T2 2 2 T1 1.02 1.02 Measured (Secs) T2 2.04 2.03

Tested by: NCC Name : VARUSAI MOHAMMED Signature:

Witnessed by: SEC-P&TD-E


Name: RAMZI

P a g e | 4 of
15

Signature:

NATIONAL CONTRACTING CO. LTD., T&D CENTER, P.O. BOX 90, AL-KHOBAR-31952, KSA

SITE ACCEPTANCE TEST RECORD


Contractor:

Date: 14-11-2012 to 20-11-2012


Contract No:

Description: Site:

LINE DIFFERENTIAL RELAY- TYPE 7SD522


230/ 115KV OVER VOLTAGE V> measurement mode Ph-N STAGE 1 PHASE A B C APPLIED 3PH VOLTAGE 63.5V SETTING 70 PICK UP 69.94 69.99 69.95 MAHASEN BSP
Panel/Bay Name:

31033077/00

=2DD/ 115KV ABUGHANIMA SS LINE SET-2 PANEL

DROP OFF 68.59 68.64 68.55

STAGE 2 PHASE A B C APPLIED 3PH VOLTAGE 63.5V SETTING 80 PICK UP 79.98 79.97 79.90` DROP OFF 78.44 78.35 78.41

TIMING TEST V> PHASE A B C APPLIED 3PH VOLTAGE 63.5V SETTING V< 1 1sec V> 1 1.03 1.03 1.02 SETTING V< 1 0.5 sec V> 2 0.533 sec 0.526 sec 0.530 sec

Tested by: NCC Name : VARUSAI MOHAMMED Signature:

Witnessed by: SEC-P&TD-E


Name: RAMZI

P a g e | 5 of
15

Signature:

NATIONAL CONTRACTING CO. LTD., T&D CENTER, P.O. BOX 90, AL-KHOBAR-31952, KSA

SITE ACCEPTANCE TEST RECORD


Contractor:

Date: 14-11-2012 to 20-11-2012


Contract No:

Description: Site:

LINE DIFFERENTIAL RELAY- TYPE 7SD522


230/ 115KV MAHASEN BSP
Panel/Bay Name:

31033077/00

=2DD/ 115KV ABUGHANIMA SS LINE SET-2 PANEL

7. REACH TEST & TIMING TEST

Tested by: NCC Name : VARUSAI MOHAMMED Signature:

Witnessed by: SEC-P&TD-E


Name: RAMZI

P a g e | 6 of
15

Signature:

NATIONAL CONTRACTING CO. LTD., T&D CENTER, P.O. BOX 90, AL-KHOBAR-31952, KSA

SITE ACCEPTANCE TEST RECORD


Contractor:

Date: 14-11-2012 to 20-11-2012


Contract No:

Description: Site:

LINE DIFFERENTIAL RELAY- TYPE 7SD522


230/ 115KV MAHASEN BSP
Panel/Bay Name:

31033077/00

=2DD/ 115KV ABUGHANIMA SS LINE SET-2 PANEL


TYPE OF FAULTS TIME m sec

TIME sec

SETTING

ZON E
REVERSEZ5 FORWARDZ4 REVERSEZ3 FORWARDZ2 FORWARDZ1B FORWARDZ1

AXES A-N

B-N

C-N

A-B

B-C

C-A

ABC

1
0

R X R X R X R X R X R X R X R X FREJA TEST REPORTS ATTACHED

2.5 1.3
0.1

3.5 2
0.4

5 -3
1.0

-6 5
1.2

10
1.5

-5 -10 7 12

NON-DIRECTIONALZ6

2.0

-7 -12

Tested by: NCC Name : VARUSAI MOHAMMED Signature:

Witnessed by: SEC-P&TD-E


Name: RAMZI

P a g e | 7 of
15

Signature:

NATIONAL CONTRACTING CO. LTD., T&D CENTER, P.O. BOX 90, AL-KHOBAR-31952, KSA

SITE ACCEPTANCE TEST RECORD


Contractor:

Date: 14-11-2012 to 20-11-2012


Contract No:

Description: Site:

LINE DIFFERENTIAL RELAY- TYPE 7SD522


230/ 115KV MAHASEN BSP
Panel/Bay Name:

31033077/00

=2DD/ 115KV ABUGHANIMA SS LINE SET-2 PANEL

8. BACK UP OVER CURRENT TEST:


Tested by: NCC Name : VARUSAI MOHAMMED Signature: Witnessed by: SEC-P&TD-E
Name: RAMZI

P a g e | 8 of
15

Signature:

NATIONAL CONTRACTING CO. LTD., T&D CENTER, P.O. BOX 90, AL-KHOBAR-31952, KSA

SITE ACCEPTANCE TEST RECORD


Contractor:

Date: 14-11-2012 to 20-11-2012


Contract No:

Description: Site:

LINE DIFFERENTIAL RELAY- TYPE 7SD522


230/ 115KV MAHASEN BSP
Panel/Bay Name:

31033077/00

1201: Distance protection =OFF 1. DEFINITE TIME TEST Function I> Io > I >> I o >> Setting Current (A) 5.0 1 10.0 5.0 Time (sec) 1.0 2.0 0.0 0.0

=2DD/ 115KV ABUGHANIMA SS LINE SET-2 PANEL 2601: Backup O/C Protection =ON 7211: B/O O/C General Trip Measured Pickup values (A) A-N 5.002 0.99 10.0 5.001 B-N 5.003 0.99 10.0 5.001 C-N 5.002 0.998 10.0 4.998 Trip time @ 2xIs (sec) 1.03 2.03 0.031 0.028

2. INVERSE TIME TEST: Ip> = 5 A, Characteristics Phase A B C N A B C N A B C N A B C N T.M.S 0.1 Io> = 2.5 A Calculated time @ 2xIs (sec) 1.003 Measured time (sec) 0.998 0.998 0.998 0.999 2.69 2.69 2.69 2.70 2.67 2.66 2.66 2.67 23.98 23.95 23.95 24.05 % Error 0.498 0.498 0.498 0.398 0.370 0.370 0.370 0 0 0.374 0.374 0 0.083 0.208 0.208 0.208

Normal Inverse

Very Inverse

0.2

2.7

Extremely Inverse

0.1

2.67

Long time Inverse

0.2

24

9 . SOTF FUNTION:
Tested by: NCC Name : VARUSAI MOHAMMED Signature: Witnessed by: SEC-P&TD-E
Name: RAMZI

P a g e | 9 of
15

Signature:

NATIONAL CONTRACTING CO. LTD., T&D CENTER, P.O. BOX 90, AL-KHOBAR-31952, KSA

SITE ACCEPTANCE TEST RECORD


Contractor:

Date: 14-11-2012 to 20-11-2012


Contract No:

Description: Site:

LINE DIFFERENTIAL RELAY- TYPE 7SD522


230/ 115KV MAHASEN BSP
Panel/Bay Name:

31033077/00

=2DD/ 115KV ABUGHANIMA SS LINE SET-2 PANEL

9.1. SOTF SEPARATE FUNCTION: CB MANUAL CLOSE BINARY INPUT = 356.


ADDRESS NO 2404 = 12.5A, LED 09= 4295=SOTF TRIP SHOULD GLOW ON SOTF : OK (INJECT 2.1A.) MORE THAN THE SETTING ADDRESS 2404 W/O BINARY INPUT : NO TRIP (INJECT 2.1A.) MORE THAN THE SETTING ADDRESS 2404 + BINARY INPUT : TRIP@ 19.0 ms (INJECT 1.9A) LESS THAN THE SETTING ADDRESS 2404 + BINARY INPUT: NO TRIP

9.2. SOTF WITH DISTANCE PROTECTION: (1232 = ZONE PICK UP)


( SOTF TRIP LED ASSIGNED . BUT ZONE TRIP TIME WILL BE BYPASSED) SOTF WITH IN Z1 REACH SOTF WITH Z2 REACH SOTF WITH Z3 REACH SOTF WITH Z4 REACH SOTF WITH Z5 REACH SOTF WITH Z6 REACH T W/O SOTF = T WITH SOTF = T W/O SOTF T WITH SOTF T W/O SOTF T WITH SOTF T W/O SOTF T WITH SOTF T W/O SOTF T WITH SOTF T W/O SOTF T WITH SOTF = = = = = = = = = = 14.9 ms 15.6 ms 438.6 ms 34.8 ms 0.814 sec 14.3 ms 1.23 sec 35.3 ms 1.54 sec 35.5 ms 2.04 sec 35.1 ms

10. VT MCB TRIP :


ZONE 1: WITH OUT VT MCB TRIP WITH VT MCB TRIP : DISTANCE TRIPPED ZONE-1 : DISTANCE BLOCKED

Tested by: NCC Name : VARUSAI MOHAMMED Signature:

Witnessed by: SEC-P&TD-E


Name: RAMZI

P a g e | 10 of 15

Signature:

NATIONAL CONTRACTING CO. LTD., T&D CENTER, P.O. BOX 90, AL-KHOBAR-31952, KSA

SITE ACCEPTANCE TEST RECORD


Contractor:

Date: 14-11-2012 to 20-11-2012


Contract No:

Description: Site:

LINE DIFFERENTIAL RELAY- TYPE 7SD522


230/ 115KV MAHASEN BSP
Panel/Bay Name:

31033077/00

=2DD/ 115KV ABUGHANIMA SS LINE SET-2 PANEL : DISTANCE TRIPPRD ZONE-1B : DISTANCE BLOCKED : DISTANCE TRIPPED ZONE-2 : DISTANCE BLOCKED : DISTANCE TRIPPED ZONE-3 : DISTANCE BLOCKED : DISTANCE TRIPPED ZONE-4 : DISTANCE BLOCKED : DISTANCE TRIPPED ZONE-5 : DISTANCE BLOCKED : DISTANCE TRIPPED ZONE-6 : DISTANCE BLOCKED

ZONE 1B ZONE 2: ZONE 3: ZONE 4: ZONE 5: ZONE 6:

WITH OUT VT MCB TRIP WITH VT MCB TRIP WITH OUT VT MCB TRIP WITH VT MCB TRIP WITH OUT VT MCB TRIP WITH VT MCB TRIP WITH OUT VT MCB TRIP WITH VT MCB TRIP WITH OUT VT MCB TRIP WITH VT MCB TRIP WITH OUT VT MCB TRIP WITH VT MCB TRIP

11. FUSE FAIL MONITOR:


A) 170: LED 12 = FUSE FAILURE, 2916A:=0 sec 2910: ON, 2911: 1PHASE SETTING=30V, 2912: 3PHASE CURRENT = 0.5A. Vrn = 31v,Vyn=Vbn=60V, SLOWLY DECREASE RN VOLTAGE & CHECK AT WHICH VOLTAGE FUSE FAIL LED APPEARS @ 29.80 V B) 2913: 3 PHASE SETTING=5V, 168: LED 14 = VOLTAGE ABSENT DISTANCE BLOCKED SPONTANEOUS INDICATION APPEARS ON FUSE FAILURE OPERATION. Vyn=Vbn=60V, 3 PHASE CURRENT = 0.5A. SLOWLY DECREASE 3 PHASE VOLTAGE & CHECK AT WHICH VOLTAGE FUSE FAIL LED APPEARS @ 5.01 V Vrn =

12. DISTANCE TELEPROTECTION SCHEME CHECK:


A A)PERMISSIVE UNDER REACH (PUTT) 4056: LED 13 =SIGNAL SEND, 4054: LED 14 =SIGNAL RECEIVES, 4006: CARRIER RECEIVE BI, 3850: TRIP WITH TELE PROTECTION SCHEME SEND LOGIC CS = Z1 FAULT : OK TRIP LOGIC TRIP = Z1B FAULT + CR : OK TRIP TIME MEASURED : 14.3 ms NO TRIP LOGIC= Z1B FAULT + NO CR : OK

B) PERMISSIVE OVER REACH (POTT) Tested by: NCC Name : VARUSAI MOHAMMED Signature: Witnessed by: SEC-P&TD-E
Name: RAMZI

P a g e | 11 of 15

Signature:

NATIONAL CONTRACTING CO. LTD., T&D CENTER, P.O. BOX 90, AL-KHOBAR-31952, KSA

SITE ACCEPTANCE TEST RECORD


Contractor:

Date: 14-11-2012 to 20-11-2012


Contract No:

Description: Site:

LINE DIFFERENTIAL RELAY- TYPE 7SD522


230/ 115KV C MAHASEN BSP
Panel/Bay Name:

31033077/00

=2DD/ 115KV ABUGHANIMA SS LINE SET-2 PANEL 4056: LED 13 =SIGNAL SEND, 4054: LED 14 =SIGNAL RECEIVE, D 4006: CARRIER RECEIVE BI, 3850: TRIP WITH TELE PROTECTION SCHEME, E SEND LOGIC = Z1B FAULT : OK TRIP LOGIC = Z1B FAULT+CR : OK TRIP TIME MEASURED : 23.2 ms

WEAK INFEED =2501: ECHO ONLY


ECHO SEND SIGNAL IMMEDIATE WHEN CB OPEN & CR, ECHO SEND SIGNAL AFTER TIME DELAY WHEN CB CLOSED & CR : : OK OK

WEAK INFEED = 2501: ECHO & TRIP ONLY (WHEN CB CLOSES)


WHEN CB CLOSED +CR+ UNDER VOLTAGE CONDITIONS ARE SATISFIED V<25V. ECHO SENDS SIGNAL & TRIP AFTER TIME DELAY : OK WHEN CB CLOSED +CR+ UNDER VOLTAGE CONDITIONS NOT SATISFIED V>25V. ECHO SENDS SIGNAL ONLY AFTERTIME DELAY : OK

C) BLOCKING SCHEME
SEND LOGIC CS = Z3 FAULT (REVERSE) : OK TRIP LOGIC = Z1B FAULT+ NO CR : OK TRIP TIME MEASURED : 23.4 ms NO TRIP LOGIC= Z1B FAULT+ CR : OK

D) DIRECT TRANSFER TRIP


TRIP OUTPUT = 4435, ALSO PUTT SCHEME TO BE SELECTED TO SEND SIGNAL IN ZONE - 1. SEND LOGIC CS = (Z1) FAULTTRIP+CS : OK TRIPLOGIC CR = TRIP ; OK

13. POWER SWING SCHEME 1. 2. ALL ZONE BLOCKING CHECKED : OK Z1,Z1B BLOCKING CHECKED : OK

14.

FAULT LOCATOR CHECK:

Default Setting:

Tested by: NCC Name : VARUSAI MOHAMMED Signature:

Witnessed by: SEC-P&TD-E


Name: RAMZI

P a g e | 12 of 15

Signature:

NATIONAL CONTRACTING CO. LTD., T&D CENTER, P.O. BOX 90, AL-KHOBAR-31952, KSA

SITE ACCEPTANCE TEST RECORD


Contractor:

Date: 14-11-2012 to 20-11-2012


Contract No:

Description: Site:

LINE DIFFERENTIAL RELAY- TYPE 7SD522


230/ 115KV Reactance (X) Line Length RE/RL MAHASEN BSP 0.03 Ohms / Km 100 Km XE/XL =1.0
Panel/Bay Name:

31033077/00

=2DD/ 115KV ABUGHANIMA SS LINE SET-2 PANEL

= = = 1.0

Percentage of length
50 75 100

X Value Injected
1.500 2.250 3.00

Measured values in display (km) RN


50.2 75.3 100.3

YN
50.1 75.3 100.4

BN
50.1 75.2 100.4

RY
50.1 75.2 100.1

YB
50.1 75.2 100.3

BR
50.2 75.3 100.1

RYB
50.2 75.2 100.2

15.

EARTHFAULT DIRECTIONAL ELEMENT :

Setting: 131: Definite time 132: Directional Comparison Pick Up


3164 : Min. Zero seq. voltage 3Uo for polarizing = 5V 3141 : 3Io pick up= 0.25A

Alpha() angle set = 338


Measurements:
Min.3Uo for polarizing 3Io pickup ( ) angle measured ( ) angle measured = = = = 4.96 V 0.249 A 338.4 121.3

Beta()angle set = 122

15.1)

DEF TELEPROTECTION SCHEME:

DIRECTIONAL COMPARISON SCHEME


Sending logic = E/F Forward Fault Tripping time with CR = 30.4 ms Tripping Time w/o CR = 1.23 sec OK address 3147 = 1.2 sec

BLOCKING SCHEME
Sending logic =E/F Reverse Fault Tripping Time with CR = 1.23 sec Tripping Time w/o CR = 31.3 ms OK

16. DIFFERENTIAL PROTECTION (87L): Tested by: NCC Name : VARUSAI MOHAMMED Signature: Witnessed by: SEC-P&TD-E
Name: RAMZI

P a g e | 13 of 15

Signature:

NATIONAL CONTRACTING CO. LTD., T&D CENTER, P.O. BOX 90, AL-KHOBAR-31952, KSA

SITE ACCEPTANCE TEST RECORD


Contractor:

Date: 14-11-2012 to 20-11-2012


Contract No:

Description: Site:

LINE DIFFERENTIAL RELAY- TYPE 7SD522


230/ 115KV MAHASEN BSP
Panel/Bay Name:

31033077/00

=2DD/ 115KV ABUGHANIMA SS LINE SET-2 PANEL

NOTE: The Sensitivity and timing tests are conduct with DIFF.TEST Mode: ON -From HMI Display go to control menu. Tagging/ Diff test Mode: ON or by Digsi. I-DIFF> add (1210) Equation for Pickup Current: Irest/INB =set Idiff>/INB + permissible local CT error *I / IN1 + permissible remote CT error *I / IN2 + System error I = Actual current flowing INB = the nominal operational current as parameterized IN1 = the primary nominal current of the local current transformer IN2 = the primary nominal current of the current transformer of the remote end System error = Error due to frequency, synchronization and delay time difference errors = 1 2% of the current. As per manual page No. 548 Data for equation CT error =3% and system error =1%

16.1

Testing of 2* I-DIFF> trip threshold

Tested by: NCC Name : VARUSAI MOHAMMED Signature:

Witnessed by: SEC-P&TD-E


Name: RAMZI

P a g e | 14 of 15

Signature:

NATIONAL CONTRACTING CO. LTD., T&D CENTER, P.O. BOX 90, AL-KHOBAR-31952, KSA

SITE ACCEPTANCE TEST RECORD


Contractor:

Date: 14-11-2012 to 20-11-2012


Contract No:

Description: Site:

LINE DIFFERENTIAL RELAY- TYPE 7SD522


230/ 115KV PHASE MAHASEN BSP SETTING IDIFF (A) 1.0 1.5 2.0 2.5 1.0 1.5 2.0 2.5 1.0 1.5 2.0 2.5
Panel/Bay Name:

31033077/00

=2DD/ 115KV ABUGHANIMA SS LINE SET-2 PANEL Expected Pickup value(A) 1.042 1.563 2.083 2.604 1.042 1.563 2.083 2.604 1.042 1.563 2.083 2.604 Measured Pick Up Value (A) 1.068 1.588 2.099 2.628 1.068 1.588 2.099 2.624 1.065 1.589 2.098 2.618 Limits A 0.989 1.094 1.484 1.641 1.978 2.187 2.473 2.734 0.989 1.094 1.484 1.641 1.978 2.187 2.473 2.734 0.989 1.094 1.484 1.641 1.978 2.187 2.473 2.734

>

For determining pick up current the injection is gradually. Tolerance 5% of setting

16.1.1 Timing test I-DIFF> set = 2.5A Injected current PHASE I-DIFF> * 2 (A) R Y B 5.0 5.0 5.0 1134= current flow or manual close BI T-DELAY Measured I-DIFF> Remarks Time (ms) Setting (ms)
0.5 1.0 1.5 0.5 1.0 1.5 0.5 1.0 1.5 615.1 1110 1610 618.0 1120 1620 614 1120 1620 OK OK OK OK OK OK OK OK OK

NOTE: seal in time for all closers = 0.01sec min value ( Address : 1132A) Trip time expected = set time+0.01 sec

16.1.2 Under Switch on Condition:

Tested by: NCC Name : VARUSAI MOHAMMED Signature:

Witnessed by: SEC-P&TD-E


Name: RAMZI

P a g e | 15 of 15

Signature:

NATIONAL CONTRACTING CO. LTD., T&D CENTER, P.O. BOX 90, AL-KHOBAR-31952, KSA

SITE ACCEPTANCE TEST RECORD


Contractor:

Date: 14-11-2012 to 20-11-2012


Contract No:

Description: Site:

LINE DIFFERENTIAL RELAY- TYPE 7SD522


230/ 115KV MAHASEN BSP
Panel/Bay Name:

31033077/00

=2DD/ 115KV ABUGHANIMA SS LINE SET-2 PANEL

PHASE

I-DIFF> SWITCH ON (A)


1.0 1.5 2.0 2.5 1.0 1.5 2.0 2.5 1.0 1.5 2.0 2.5

Expected pick up value (A)


0.989 1.094 1.484 1.641 1.978 2.187 2.473 2.734 0.989 1.094 1.484 1.641 1.978 2.187 2.473 2.734 0.989 1.094 1.484 1.641 1.978 2.187 2.473 2.734

Measured Pick Up Value (A)


1.070 1.592 2.099 2.628 1.071 1.590 2.095 2.626 1.061 1.591 2.100 2.620

Operating Time (ms) Setting=0.0


26.8 25.6 26.6 29.1 26.5 29.5 28.9 25.3 25.1 25.5 29.8 26.8

*Note : Timing taken at pickup value 16.1.3 For seal in time effect on tripping

CASE ONE: 1210 (I-DIFF>: pick up value) = 1.5 A 1213 (I-DIF>SWITCH ON pick up value) = 5.0 A 1134 (Line Closure) = manual close BI 1132 (seal in time after all closures) = 0.1 sec 1130 (pole open current threshold) less than (add.1210) = 0.5A Manual close BI in state 1 for time more than address. 1132 after that inject current as per tables below in state 2 (*) inject current in between setting of (I-DIFF> and I-DIF>SWITCH ON)

Setting I-DIFF> 1.5A Time

R-N

Injected current ( 2Amps ) Y-N B-N 294.9msec 300.8msec

298.7msec

This time is the summation of time in add.1217 plus add.1150 (0.3 sec).
Tested by: NCC Name : VARUSAI MOHAMMED Signature: Witnessed by: SEC-P&TD-E
Name: RAMZI

P a g e | 16 of 15

Signature:

NATIONAL CONTRACTING CO. LTD., T&D CENTER, P.O. BOX 90, AL-KHOBAR-31952, KSA

SITE ACCEPTANCE TEST RECORD


Contractor:

Date: 14-11-2012 to 20-11-2012


Contract No:

Description: Site:

LINE DIFFERENTIAL RELAY- TYPE 7SD522


230/ 115KV MAHASEN BSP
Panel/Bay Name:

31033077/00

=2DD/ 115KV ABUGHANIMA SS LINE SET-2 PANEL

(**)Inject current more than I-DIF>SWITCH ON condition Setting I-DIFF> under switch on condition Time Injected current ( 5.5 Amps) R-N 25.9 msec Y-N 27.4 msec B-N 27.0 msec

The time measured is the time in add 1217(0.0 sec)

a.

I-DIFF>>add (1233)
PHASE I-DIFF>> (A) Measured Pick Up Value (A) Operating Time (ms) Remarks OK OK OK OK OK OK OK OK OK OK OK OK

4 5 6 7 4 5 6 7 4 5 6 7

4.002 4.998 5.991 6.994 4.000 4.998 5.987 7.000 4.000 4.999 5.997 6.996

20.6 22.8 20.6 20.4 20.3 20.9 22.3 20.9 22.1 22.5 22.0 22.0

For determining pick up current, the injection is not gradually

Tested by: NCC Name : VARUSAI MOHAMMED Signature:

Witnessed by: SEC-P&TD-E


Name: RAMZI

P a g e | 17 of 15

Signature:

NATIONAL CONTRACTING CO. LTD., T&D CENTER, P.O. BOX 90, AL-KHOBAR-31952, KSA

SITE ACCEPTANCE TEST RECORD


Contractor:

Date: 14-11-2012 to 20-11-2012


Contract No:

Description: Site:

LINE DIFFERENTIAL RELAY- TYPE 7SD522


230/ 115KV MAHASEN BSP
Panel/Bay Name:

31033077/00

=2DD/ 115KV ABUGHANIMA SS LINE SET-2 PANEL

b.

I-DIF>>SWITCHON add (1235)


PHASE I-DIF>> SWITCHON (A) 4 5 6 7 4 5 6 7 4 5 6 7 Measured Pick Up Value (A) 3.999 4.996 5.998 6.961 3.998 4.996 5.994 6.994 3.999 4.998 5.980 6.985 Operating Time (ms) 20.6 28.1 20.8 20.4 30.4 20.7 22.1 21.5 22.3 30.0 28.1 21.8 Remarks OK OK OK OK OK OK OK OK OK OK OK OK

16.1.4 Inrush Restraint Current: (second harmonic blocked test) -choose add.2301 (Inrush Restraint) = ON -choose add.2302 (2nd harmonic in % of fundamental) = 15 % -choose add.2303 (cross block) = NO
a.

Inject one phase current (1A-60HZ and 0.22A-120HZ) the relay will not trip because of Second harmonic inrush block.

Tested by: NCC Name : VARUSAI MOHAMMED Signature:

Witnessed by: SEC-P&TD-E


Name: RAMZI

P a g e | 18 of 15

Signature:

NATIONAL CONTRACTING CO. LTD., T&D CENTER, P.O. BOX 90, AL-KHOBAR-31952, KSA

SITE ACCEPTANCE TEST RECORD


Contractor:

Date: 14-11-2012 to 20-11-2012


Contract No:

Description: Site:

LINE DIFFERENTIAL RELAY- TYPE 7SD522


230/ 115KV MAHASEN BSP
Panel/Bay Name:

31033077/00

=2DD/ 115KV ABUGHANIMA SS LINE SET-2 PANEL

2nd harmonic setting 15%

Non block 15.26%

Block value 15.28%

- 2303 (cross block) = YES - 2310 (time for cross block with 2nd harmonic) = 2.0 sec b. Inject one phase current (1A-60HZ and 0.22 A-120HZ) and another phase by (1A-60HZ). the relay will trip after the summation of time in (add.2310+add.1217) By cross blocking with2nd harmonic. Cross block set time 2 sec Actual time 2.03 sec Checked
OK

If Cross block setting is (no) so the tripping will be blocked only if the faulted phase has 2nd harmonic but if the another phase is the faulted phase without 2nd harmonic fault and healthy phase has 2nd harmonic then the tripping will not blocked and tripping will be blocked if the setting of cross block changed to yes so the tripping blocking happen for time 2310.
16.1.5 CHARGING CURRENT COMPENSATION : I C = 3.63 . 10 -6 . UN . FN . CB' . S Where :I C :- Charging current to be calculated in ( A ) primary . UN :- Nominal voltage of the network in ( KV ) primary . FN :- Nominal frequency of the network . CB' :- Per unit line length capacitance of the line in nF/km or nF/mile . S :- Length of the line in km or miles .

* Charging current is checked in secondary values . PHASE Current ( A ) Voltage ( V ) Calculated ICH ( % ) Measured ICH ( % )

R Y B

0.00 0.00 0.00

66.40 66.40 66.40

1.25 1.25 1.25

1.2 1.2 1.2

Tested by: NCC Name : VARUSAI MOHAMMED Signature:

Witnessed by: SEC-P&TD-E


Name: RAMZI

P a g e | 19 of 15

Signature:

NATIONAL CONTRACTING CO. LTD., T&D CENTER, P.O. BOX 90, AL-KHOBAR-31952, KSA

SITE ACCEPTANCE TEST RECORD


Contractor:

Date: 14-11-2012 to 20-11-2012


Contract No:

Description: Site:

LINE DIFFERENTIAL RELAY- TYPE 7SD522


230/ 115KV MAHASEN BSP
Panel/Bay Name:

31033077/00

=2DD/ 115KV ABUGHANIMA SS LINE SET-2 PANEL

17. ADDITIONAL CHECKS:


` 17.1 All binary inputs checked 17.2. All binary outputs checked 17.3 All LED checked 17.4 Disturbance report verified .. .. .. .. OK OK OK OK

Tested by: NCC Name : VARUSAI MOHAMMED Signature:

Witnessed by: SEC-P&TD-E


Name: RAMZI

P a g e | 20 of 15

Signature:

NATIONAL CONTRACTING CO. LTD., T&D CENTER, P.O. BOX 90, AL-KHOBAR-31952, KSA