SECTION II: INST ALL ATION AND MAINTEN ANCE

II.8.4

TABLE OF ALARMS

The dis play on the control panel displ ays the alarms, with referenc e to the following table. Alarms are r eset by pressing the ALARM key on the control panel once the cause has been identified and eliminated.

Typ e of alarm AL:002 Antifreez e alarm

Possible cause Set-point s et too l ow Insufficient water fl ow Insufficient water fl ow Presenc e of air in the water s ystem Intercept val ves clos ed The circulati ng pump (if present) does not run Water circuit filter obstructed

Cut-in Chec k set-point and res et Chec k and adj ust if nec essar y Restore the correct water flow Bleed Open val ves See Troubl eshooting s ection Chec k and cl ean if necess ar y Indicates that the low pressur e s witch has been activated: the alar m is res et manually from the keyboard. Note: the alar m will be automatic ally res et 3 ti mes in the region of an hour and will then need to be reset manuall y. When this alarm is triggered the AL:021 and AL:022 signals are acti vated simultaneousl y. If the alarm persists refer to Troubles hooting section. Indicates that the high press ure s witch has been activated: r eset the press ure s witch manuall y by firmly pressing the button on the pressure s witc h itself. Then res et the alar m manuall y fr om the keyboard. If the alarm persists refer to Troubles hooting section. Chec k and r eplac e the fan if necess ary Indicates that following the AL: 005 alarm the pump may be faulty. T he alarm is r eset manuall y from the keyboard. Note: the alar m will be automatic ally res et 3 ti mes in the region of an hour and will then need to be reset manuall y. Replace the sensor Insert terminal into connector B1 Replace the sensor Insert terminal into connector B5 Replace the sensor Insert terminal into connector B4 Replace the transducer Insert tr ansducer into c onnector B6 This alarm does not i ndicate a malfunction but onl y signals that the number of wor king hours of the pump has exc eeded the set val ue. T he unit continues to operate as nor mal. Contac t an authorised s er vice c entre for maintenanc e inter vention. Press the ALARM key to deacti vate the signal. This alarm does not i ndicate a malfunction but onl y signals that the number of wor king hours of the c ompressor has exceeded the set value. T he unit c ontinues to operate as nor mal. Contac t an authorised s er vice c entre for maintenanc e inter vention. Press the ALARM key to deacti vate the signal. Indicates that the cloc k card ( accessor y) is faulty: cut off and resume the unit's power. If the alar m persists, contact an authorised ser vice c entr e and the cl oc k card will be replaced. T he alarms are reset automaticall y. Indicates that L1-L2-L3 phas e s equenc e allinterruttore gener ale is inc orrect. Cut the unit off, adj ust the s equence and resume power. T he alarms are res et automaticall y. Indicates that the general power s uppl y voltage (in volt) is outside the set range. Chec k power line. The al arms are reset automaticall y.

AL:005 Alar m for water differential pressur e switch on condenser/evaporator

AL:010 Lo w pr essur e alarm

AL:012 High pressur e switch alarm

AL:020 Fan ther mal protection activation alarm AL:21 Alarm pump 1 AL:22 Alarm pump 2 AL:030 Inlet water temper ature sensor alarm (ST1) AL:034 Temp erature sen sor alarm: evaporator outlet water (ST2) AL:033 Temp erature sen sor alarm: buffer tank outlet water (ST4) AL:035 Pr essure tr ansducer alarm

Short-circuited fan

Sens or faulty Sens or detac hed from connector B1 Sens or faulty Sens or detac hed from connector B5 Faulty sensor Sens or detac hed from connector B4 Transduc er faulty Transduc er detac hed from connector B6

AL:040 Pump 1 m aintenan ce signal AL:046 Pump 2 m aintenan ce signal

AL:041 Compressor 1 m aintenan ce signal AL:042 Compressor 2 m aintenan ce signal

AL:055 Clock card alarm

AL:056 Ph ase sequence alarm

AL:057 Min/max voltage alarm