Cable Calculation Report

Project Reference: CCB - ALAOJI 504MW PP Job Number: RK-117-E-2020-2029


Document No: CCB-DBP-001 Created On : 08/10/2008 Rev Date :
Created By : ARNEL CORPUZ Modified By: Rev No:

Calculated in accordance with BS7671

Cable (E) Cbl_SM-1


Connection From: MDB-CCB-DBP/1/L1,L2,L3 To: DB-P1
Active Source: Source-1
Load Type: Distribution Board Design Current Ib (A): 37.1

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: MEM Memshield2 MCCB F Frame (MFH) (Fixed) Th/Mag
Rating In (A): 40 [a] Overload Setting Ir (A): 40 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 1 x 4 x 1c Size (mm2 ): 6 [a]
Neutral: 6 mm²[a] Length (m): 10
1 - In conduit in a thermally insulated wall Conduit: Plastic

Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]

3rd Harmonics (%) = 0.00 Ch = 1.00


CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 37.1
Device Rating In = 40 Overload Setting Ir = 40 _ Ib]
[Ir >
Min. Cable Capacity Iz = 40.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 40.0 _ Iz]
[It >

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 37.1 / 1.00 36.1 / 1.00 36.7 / 1.00 0.8
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 1.44 / 0.63 1.34 / 0.58 1.40 / 0.61 -----
Voltage Drop - From Source (V/%) 2.43 / 1.05 2.39 / 1.04 2.52 / 1.10 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 1.5 [a] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.16898 0.03926 0.15500 0.36294 0.69697 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
0.63
Adiabatic check (mm 2 ) CPC Section = Separate 1.5 Total = 1.5 Min. Section = 1.31

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 12.846 / 8.495 Load End: 5.206 / 2.240
Protective Device Breaking Capacity (kA): Icu: 45 Ics: 25

Adiabatic Check: CPD Energy Let-through (A²s): 41.71 x 103 Adiabatic Limit k²S² (A²s): 736.16 x 103

Project: D:\My Documents\ALAOJI\SERVICE BLDGS\CentralControlBldg\CCB-DBP.p17 Page 1 of 39 Printed on: 11/12/2008


Created using: 15.0.0(BS7671:2008) - Rockson Engineering Ltd Copyright © AMTECH Power Software Ltd 2008
Cable Calculation Report

Project Reference: CCB - ALAOJI 504MW PP Job Number: RK-117-E-2020-2029


Document No: CCB-DBP-001 Created On : 08/10/2008 Rev Date :
Created By : ARNEL CORPUZ Modified By: Rev No:

Calculated in accordance with BS7671

Cable (G) Cbl_SM-2


Connection From: MDB-CCB-DBP/2/L1,L2,L3 To: DB-P2
Active Source: Source-1
Load Type: Distribution Board Design Current Ib (A): 73.4

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: MEM Memshield2 MCCB F Frame (MFH) (Fixed) Th/Mag
Rating In (A): 80 [a] Overload Setting Ir (A): 80 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 1 x 4 x 1c Size (mm2 ): 25 [a]
Neutral: 25 mm²[a] Length (m): 10
1 - In conduit in a thermally insulated wall Conduit: Plastic

Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]

3rd Harmonics (%) = 0.00 Ch = 1.00


CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 73.4
Device Rating In = 80 Overload Setting Ir = 80 _ Ib]
[Ir >
Min. Cable Capacity Iz = 80.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 95.0 _ Iz]
[It >

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 67.4 / 1.00 71.0 / 1.00 73.4 / 1.00 5.2
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.52 / 0.23 0.61 / 0.27 0.66 / 0.29 -----
Voltage Drop - From Source (V/%) 1.51 / 0.65 1.66 / 0.72 1.78 / 0.77 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 2.5 [a] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.16898 0.00937 0.09500 0.27309 0.28750 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
0.84
Adiabatic check (mm 2 ) CPC Section = Separate 2.5 Total = 2.5 Min. Section = 1.31

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 12.846 / 8.495 Load End: 9.542 / 5.106
Protective Device Breaking Capacity (kA): Icu: 45 Ics: 25

Adiabatic Check: CPD Energy Let-through (A²s): 152.36 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: D:\My Documents\ALAOJI\SERVICE BLDGS\CentralControlBldg\CCB-DBP.p17 Page 2 of 39 Printed on: 11/12/2008


Created using: 15.0.0(BS7671:2008) - Rockson Engineering Ltd Copyright © AMTECH Power Software Ltd 2008
Cable Calculation Report

Project Reference: CCB - ALAOJI 504MW PP Job Number: RK-117-E-2020-2029


Document No: CCB-DBP-001 Created On : 08/10/2008 Rev Date :
Created By : ARNEL CORPUZ Modified By: Rev No:

Calculated in accordance with BS7671

Cable CKT P101


Connection From: DB-P1/1/L1 To: P101
Active Source: Source-1
Load Type: Lighting, radial circuits Design Current Ib (A): 4.0
Length to First Fitting (m): 5.00
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: MEM Memshield 2 MCB Type C (MCH) Th/Mag
Rating In (A): 10 [f] Overload Setting Ir (A): 10 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 1 x 2 x 1c Size (mm2 ): 2.5 [f]
Neutral: 2.5 mm²[a] Length (m): 24
1 - In conduit in a thermally insulated wall Conduit: Plastic

Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]

3rd Harmonics (%) = 0.00 Ch = 1.00


CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 6.9 V (to BS 7671:2008 Appendix 12)
Design Current Ib = 4.0
Device Rating In = 10 Overload Setting Ir = 10 _ Ib]
[Ir >
Min. Cable Capacity Iz = 10.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 26.0 _ Iz]
[It >

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 4.0 / 1.00 0.0 / 0.00 0.0 / 0.00 4.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.89 / 0.39 0.00 / 0.00 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 3.32 / 1.44 0.00 / 0.00 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 1 [a] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.36294 0.22800 0.55200 1.14275 2.30000 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 0.40
0.20
Adiabatic check (mm 2 ) CPC Section = Separate 1 Total = 1.0 Min. Section = 0.26

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 5.206 / 2.240 Load End: 0.577 / 0.412
Protective Device Breaking Capacity (kA): Icu: 10 Ics: 10

Adiabatic Check: CPD Energy Let-through (A²s): 1,350.00 Adiabatic Limit k²S² (A²s): 127.81 x 103

Project: D:\My Documents\ALAOJI\SERVICE BLDGS\CentralControlBldg\CCB-DBP.p17 Page 3 of 39 Printed on: 11/12/2008


Created using: 15.0.0(BS7671:2008) - Rockson Engineering Ltd Copyright © AMTECH Power Software Ltd 2008
Cable Calculation Report

Project Reference: CCB - ALAOJI 504MW PP Job Number: RK-117-E-2020-2029


Document No: CCB-DBP-001 Created On : 08/10/2008 Rev Date :
Created By : ARNEL CORPUZ Modified By: Rev No:

Calculated in accordance with BS7671

Cable CKT P102


Connection From: DB-P1/2/L1 To: P102
Active Source: Source-1
Load Type: Lighting, radial circuits Design Current Ib (A): 6.5
Length to First Fitting (m): 8.00
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: MEM Memshield 2 MCB Type C (MCH) Th/Mag
Rating In (A): 10 [f] Overload Setting Ir (A): 10 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 1 x 2 x 1c Size (mm2 ): 2.5 [f]
Neutral: 2.5 mm²[a] Length (m): 73
1 - In conduit in a thermally insulated wall Conduit: Plastic

Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]

3rd Harmonics (%) = 0.00 Ch = 1.00


CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 6.9 V (to BS 7671:2008 Appendix 12)
Design Current Ib = 6.5
Device Rating In = 10 Overload Setting Ir = 10 _ Ib]
[Ir >
Min. Cable Capacity Iz = 10.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 26.0 _ Iz]
[It >

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 6.5 / 1.00 0.0 / 0.00 0.0 / 0.00 6.5
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 4.12 / 1.79 0.00 / 0.00 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 6.55 / 2.85 0.00 / 0.00 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 1.5 [a] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.36294 0.69350 1.13150 2.18771 2.30000 Current (kA)

Disconnection time (s): From characteristic: 0.26 Maximum for circuit: 0.40
0.11
Adiabatic check (mm 2 ) CPC Section = Separate 1.5 Total = 1.5 Min. Section = 0.37

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 5.206 / 2.240 Load End: 0.204 / 0.154
Protective Device Breaking Capacity (kA): Icu: 10 Ics: 10

Adiabatic Check: CPD Energy Let-through (A²s): 1,350.00 Adiabatic Limit k²S² (A²s): 127.81 x 103

Project: D:\My Documents\ALAOJI\SERVICE BLDGS\CentralControlBldg\CCB-DBP.p17 Page 4 of 39 Printed on: 11/12/2008


Created using: 15.0.0(BS7671:2008) - Rockson Engineering Ltd Copyright © AMTECH Power Software Ltd 2008
Cable Calculation Report

Project Reference: CCB - ALAOJI 504MW PP Job Number: RK-117-E-2020-2029


Document No: CCB-DBP-001 Created On : 08/10/2008 Rev Date :
Created By : ARNEL CORPUZ Modified By: Rev No:

Calculated in accordance with BS7671

Cable CKT P103


Connection From: DB-P1/1/L2 To: P103
Active Source: Source-1
Load Type: Sockets BS 1363, 32A ring final circuit to sockets up to 100m² Design Current Ib (A): 7.8

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: MEM Memshield 2 MCB Type C (MCV) 15kA Th/Mag
Rating In (A): 32 [f] Overload Setting Ir (A): 32 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 2 x 2 x 1c Size (mm2 ): 4 [f]
Neutral: 4 mm²[a] Length (m): 37
1 - In conduit in a thermally insulated wall Conduit: Plastic

Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]

3rd Harmonics (%) = 0.00 Ch = 1.00


CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 11.5 V (to BS 7671:2008 Appendix 12)
Design Current Ib = 7.8
Device Rating In = 32 Overload Setting Ir = 32 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 35.0 _ Iz]
[It >

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 7.8 / 1.00 0.0 / 0.00 7.8
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 0.71 / 0.31 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 3.11 / 1.35 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 1 [a] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.36294 0.05550 0.21275 0.63107 0.71875 Current (kA)

Disconnection time (s): From characteristic: 0.09 Maximum for circuit: 0.40
0.36
Adiabatic check (mm 2 ) CPC Section = Separate 1 Total = 1.0 Min. Section = 0.31

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 5.206 / 2.240 Load End: 1.777 / 1.079
Protective Device Breaking Capacity (kA): Icu: 15 Ics: 7.5

Adiabatic Check: CPD Energy Let-through (A²s): 4,373.12 Adiabatic Limit k²S² (A²s): 327.18 x 103

Project: D:\My Documents\ALAOJI\SERVICE BLDGS\CentralControlBldg\CCB-DBP.p17 Page 5 of 39 Printed on: 11/12/2008


Created using: 15.0.0(BS7671:2008) - Rockson Engineering Ltd Copyright © AMTECH Power Software Ltd 2008
Cable Calculation Report

Project Reference: CCB - ALAOJI 504MW PP Job Number: RK-117-E-2020-2029


Document No: CCB-DBP-001 Created On : 08/10/2008 Rev Date :
Created By : ARNEL CORPUZ Modified By: Rev No:

Calculated in accordance with BS7671

Cable CKT P104


Connection From: DB-P1/2/L2 To: P104
Active Source: Source-1
Load Type: Lighting, radial circuits Design Current Ib (A): 4.3
Length to First Fitting (m): 5.00
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: MEM Memshield 2 MCB Type C (MCH) Th/Mag
Rating In (A): 10 [f] Overload Setting Ir (A): 10 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 1 x 2 x 1c Size (mm2 ): 2.5 [f]
Neutral: 2.5 mm²[a] Length (m): 57
1 - In conduit in a thermally insulated wall Conduit: Plastic

Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]

3rd Harmonics (%) = 0.00 Ch = 1.00


CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 6.9 V (to BS 7671:2008 Appendix 12)
Design Current Ib = 4.3
Device Rating In = 10 Overload Setting Ir = 10 _ Ib]
[Ir >
Min. Cable Capacity Iz = 10.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 26.0 _ Iz]
[It >

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 4.3 / 1.00 0.0 / 0.00 4.3
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 2.08 / 0.90 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 4.47 / 1.94 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 1 [a] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.36294 0.54150 1.31100 2.21521 2.30000 Current (kA)

Disconnection time (s): From characteristic: 0.29 Maximum for circuit: 0.40
0.10
Adiabatic check (mm 2 ) CPC Section = Separate 1 Total = 1.0 Min. Section = 0.39

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 5.206 / 2.240 Load End: 0.259 / 0.194
Protective Device Breaking Capacity (kA): Icu: 10 Ics: 10

Adiabatic Check: CPD Energy Let-through (A²s): 1,350.00 Adiabatic Limit k²S² (A²s): 127.81 x 103

Project: D:\My Documents\ALAOJI\SERVICE BLDGS\CentralControlBldg\CCB-DBP.p17 Page 6 of 39 Printed on: 11/12/2008


Created using: 15.0.0(BS7671:2008) - Rockson Engineering Ltd Copyright © AMTECH Power Software Ltd 2008
Cable Calculation Report

Project Reference: CCB - ALAOJI 504MW PP Job Number: RK-117-E-2020-2029


Document No: CCB-DBP-001 Created On : 08/10/2008 Rev Date :
Created By : ARNEL CORPUZ Modified By: Rev No:

Calculated in accordance with BS7671

Cable CKT P106


Connection From: DB-P1/2/L3 To: P106
Active Source: Source-1
Load Type: Lighting, radial circuits Design Current Ib (A): 2.6
Length to First Fitting (m): 9.00
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: MEM Memshield 2 MCB Type C (MCH) Th/Mag
Rating In (A): 10 [f] Overload Setting Ir (A): 10 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 1 x 2 x 1c Size (mm2 ): 2.5 [f]
Neutral: 2.5 mm²[a] Length (m): 40
1 - In conduit in a thermally insulated wall Conduit: Plastic

Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]

3rd Harmonics (%) = 0.00 Ch = 1.00


CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 6.9 V (to BS 7671:2008 Appendix 12)
Design Current Ib = 2.6
Device Rating In = 10 Overload Setting Ir = 10 _ Ib]
[Ir >
Min. Cable Capacity Iz = 10.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 26.0 _ Iz]
[It >

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 0.0 / 0.00 2.6 / 1.00 2.6
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 0.00 / 0.00 1.00 / 0.44 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 0.00 / 0.00 3.52 / 1.53 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 1 [a] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.36294 0.38000 0.92000 1.66273 2.30000 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 0.40
0.14
Adiabatic check (mm 2 ) CPC Section = Separate 1 Total = 1.0 Min. Section = 0.26

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 5.206 / 2.240 Load End: 0.362 / 0.267
Protective Device Breaking Capacity (kA): Icu: 10 Ics: 10

Adiabatic Check: CPD Energy Let-through (A²s): 1,350.00 Adiabatic Limit k²S² (A²s): 127.81 x 103

Project: D:\My Documents\ALAOJI\SERVICE BLDGS\CentralControlBldg\CCB-DBP.p17 Page 7 of 39 Printed on: 11/12/2008


Created using: 15.0.0(BS7671:2008) - Rockson Engineering Ltd Copyright © AMTECH Power Software Ltd 2008
Cable Calculation Report

Project Reference: CCB - ALAOJI 504MW PP Job Number: RK-117-E-2020-2029


Document No: CCB-DBP-001 Created On : 08/10/2008 Rev Date :
Created By : ARNEL CORPUZ Modified By: Rev No:

Calculated in accordance with BS7671

Cable CKT P107


Connection From: DB-P1/3/L1 To: P107
Active Source: Source-1
Load Type: Sockets BS 1363, 32A ring final circuit to sockets up to 100m² Design Current Ib (A): 2.6

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: MEM Memshield 2 MCB Type C (MCH) Th/Mag
Rating In (A): 32 [f] Overload Setting Ir (A): 32 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 2 x 2 x 1c Size (mm2 ): 4 [f]
Neutral: 4 mm²[a] Length (m): 29
1 - In conduit in a thermally insulated wall Conduit: Plastic

Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]

3rd Harmonics (%) = 0.00 Ch = 1.00


CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 11.5 V (to BS 7671:2008 Appendix 12)
Design Current Ib = 2.6
Device Rating In = 32 Overload Setting Ir = 32 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 35.0 _ Iz]
[It >

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 2.6 / 1.00 0.0 / 0.00 0.0 / 0.00 2.6
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.18 / 0.08 0.00 / 0.00 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 2.61 / 1.14 0.00 / 0.00 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 1 [a] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.36294 0.04350 0.16675 0.57309 0.71875 Current (kA)

Disconnection time (s): From characteristic: 0.03 Maximum for circuit: 0.40
0.40
Adiabatic check (mm 2 ) CPC Section = Separate 1 Total = 1.0 Min. Section = 0.31

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 5.206 / 2.240 Load End: 2.076 / 1.215
Protective Device Breaking Capacity (kA): Icu: 10 Ics: 10

Adiabatic Check: CPD Energy Let-through (A²s): 4,932.67 Adiabatic Limit k²S² (A²s): 327.18 x 103

Project: D:\My Documents\ALAOJI\SERVICE BLDGS\CentralControlBldg\CCB-DBP.p17 Page 8 of 39 Printed on: 11/12/2008


Created using: 15.0.0(BS7671:2008) - Rockson Engineering Ltd Copyright © AMTECH Power Software Ltd 2008
Cable Calculation Report

Project Reference: CCB - ALAOJI 504MW PP Job Number: RK-117-E-2020-2029


Document No: CCB-DBP-001 Created On : 08/10/2008 Rev Date :
Created By : ARNEL CORPUZ Modified By: Rev No:

Calculated in accordance with BS7671

Cable CKT P108


Connection From: DB-P1/4/L1 To: P108
Active Source: Source-1
Load Type: Sockets BS EN 60309-2, 20A radial circuit Design Current Ib (A): 12.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: MEM Memshield 2 MCB Type C (MCH) Th/Mag
Rating In (A): 20 [f] Overload Setting Ir (A): 20 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 1 x 2 x 1c Size (mm2 ): 4 [f]
Neutral: 4 mm²[a] Length (m): 24
1 - In conduit in a thermally insulated wall Conduit: Plastic

Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]

3rd Harmonics (%) = 0.00 Ch = 1.00


CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 11.5 V (to BS 7671:2008 Appendix 12)
Design Current Ib = 12.0
Device Rating In = 20 Overload Setting Ir = 20 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 35.0 _ Iz]
[It >

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 12.0 / 1.00 0.0 / 0.00 0.0 / 0.00 12.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 2.88 / 1.25 0.00 / 0.00 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 5.31 / 2.31 0.00 / 0.00 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 1 [a] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.36294 0.14400 0.55200 1.05876 1.15000 Current (kA)

Disconnection time (s): From characteristic: 0.19 Maximum for circuit: 0.40
0.22
Adiabatic check (mm 2 ) CPC Section = Separate 1 Total = 1.0 Min. Section = 0.67

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 5.206 / 2.240 Load End: 0.860 / 0.590
Protective Device Breaking Capacity (kA): Icu: 10 Ics: 10

Adiabatic Check: CPD Energy Let-through (A²s): 2,041.07 Adiabatic Limit k²S² (A²s): 327.18 x 103

Project: D:\My Documents\ALAOJI\SERVICE BLDGS\CentralControlBldg\CCB-DBP.p17 Page 9 of 39 Printed on: 11/12/2008


Created using: 15.0.0(BS7671:2008) - Rockson Engineering Ltd Copyright © AMTECH Power Software Ltd 2008
Cable Calculation Report

Project Reference: CCB - ALAOJI 504MW PP Job Number: RK-117-E-2020-2029


Document No: CCB-DBP-001 Created On : 08/10/2008 Rev Date :
Created By : ARNEL CORPUZ Modified By: Rev No:

Calculated in accordance with BS7671

Cable CKT P109


Connection From: DB-P1/3/L2 To: P109
Active Source: Source-1
Load Type: Sockets BS EN 60309-2, 20A radial circuit Design Current Ib (A): 12.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: MEM Memshield 2 MCB Type C (MCH) Th/Mag
Rating In (A): 20 [f] Overload Setting Ir (A): 20 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 1 x 2 x 1c Size (mm2 ): 4 [f]
Neutral: 4 mm²[a] Length (m): 13
1 - In conduit in a thermally insulated wall Conduit: Plastic

Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]

3rd Harmonics (%) = 0.00 Ch = 1.00


CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 11.5 V (to BS 7671:2008 Appendix 12)
Design Current Ib = 12.0
Device Rating In = 20 Overload Setting Ir = 20 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 35.0 _ Iz]
[It >

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 12.0 / 1.00 0.0 / 0.00 12.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 1.56 / 0.68 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 3.95 / 1.72 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 1 [a] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.36294 0.07800 0.29900 0.73980 1.15000 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 0.40
0.31
Adiabatic check (mm 2 ) CPC Section = Separate 1 Total = 1.0 Min. Section = 0.29

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 5.206 / 2.240 Load End: 1.399 / 0.891
Protective Device Breaking Capacity (kA): Icu: 10 Ics: 10

Adiabatic Check: CPD Energy Let-through (A²s): 3,186.04 Adiabatic Limit k²S² (A²s): 327.18 x 103

Project: D:\My Documents\ALAOJI\SERVICE BLDGS\CentralControlBldg\CCB-DBP.p17 Page 10 of 39 Printed on: 11/12/2008


Created using: 15.0.0(BS7671:2008) - Rockson Engineering Ltd Copyright © AMTECH Power Software Ltd 2008
Cable Calculation Report

Project Reference: CCB - ALAOJI 504MW PP Job Number: RK-117-E-2020-2029


Document No: CCB-DBP-001 Created On : 08/10/2008 Rev Date :
Created By : ARNEL CORPUZ Modified By: Rev No:

Calculated in accordance with BS7671

Cable CKT P110


Connection From: DB-P1/4/L2 To: P110
Active Source: Source-1
Load Type: Sockets BS EN 60309-2, 20A radial circuit Design Current Ib (A): 12.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: MEM Memshield 2 MCB Type C (MCH) Th/Mag
Rating In (A): 20 [f] Overload Setting Ir (A): 20 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 1 x 2 x 1c Size (mm2 ): 4 [f]
Neutral: 4 mm²[a] Length (m): 19
1 - In conduit in a thermally insulated wall Conduit: Plastic

Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]

3rd Harmonics (%) = 0.00 Ch = 1.00


CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 11.5 V (to BS 7671:2008 Appendix 12)
Design Current Ib = 12.0
Device Rating In = 20 Overload Setting Ir = 20 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 35.0 _ Iz]
[It >

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 12.0 / 1.00 0.0 / 0.00 12.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 2.28 / 0.99 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 4.68 / 2.03 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 1 [a] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.36294 0.11400 0.43700 0.91377 1.15000 Current (kA)

Disconnection time (s): From characteristic: 0.05 Maximum for circuit: 0.40
0.25
Adiabatic check (mm 2 ) CPC Section = Separate 1 Total = 1.0 Min. Section = 0.29

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 5.206 / 2.240 Load End: 1.043 / 0.697
Protective Device Breaking Capacity (kA): Icu: 10 Ics: 10

Adiabatic Check: CPD Energy Let-through (A²s): 2,448.19 Adiabatic Limit k²S² (A²s): 327.18 x 103

Project: D:\My Documents\ALAOJI\SERVICE BLDGS\CentralControlBldg\CCB-DBP.p17 Page 11 of 39 Printed on: 11/12/2008


Created using: 15.0.0(BS7671:2008) - Rockson Engineering Ltd Copyright © AMTECH Power Software Ltd 2008
Cable Calculation Report

Project Reference: CCB - ALAOJI 504MW PP Job Number: RK-117-E-2020-2029


Document No: CCB-DBP-001 Created On : 08/10/2008 Rev Date :
Created By : ARNEL CORPUZ Modified By: Rev No:

Calculated in accordance with BS7671

Cable CKT P111


Connection From: DB-P1/3/L3 To: P111
Active Source: Source-1
Load Type: Lighting, radial circuits Design Current Ib (A): 4.0
Length to First Fitting (m): 11.00
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: MEM Memshield 2 MCB Type C (MCH) Th/Mag
Rating In (A): 10 [f] Overload Setting Ir (A): 10 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 1 x 2 x 1c Size (mm2 ): 2.5 [f]
Neutral: 2.5 mm²[a] Length (m): 38
1 - In conduit in a thermally insulated wall Conduit: Plastic

Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]

3rd Harmonics (%) = 0.00 Ch = 1.00


CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 6.9 V (to BS 7671:2008 Appendix 12)
Design Current Ib = 4.0
Device Rating In = 10 Overload Setting Ir = 10 _ Ib]
[Ir >
Min. Cable Capacity Iz = 10.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 26.0 _ Iz]
[It >

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 0.0 / 0.00 4.0 / 1.00 4.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 0.00 / 0.00 1.51 / 0.65 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 0.00 / 0.00 4.03 / 1.75 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 1 [a] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.36294 0.36100 0.87400 1.59773 2.30000 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 0.40
0.14
Adiabatic check (mm 2 ) CPC Section = Separate 1 Total = 1.0 Min. Section = 0.26

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 5.206 / 2.240 Load End: 0.379 / 0.279
Protective Device Breaking Capacity (kA): Icu: 10 Ics: 10

Adiabatic Check: CPD Energy Let-through (A²s): 1,350.00 Adiabatic Limit k²S² (A²s): 127.81 x 103

Project: D:\My Documents\ALAOJI\SERVICE BLDGS\CentralControlBldg\CCB-DBP.p17 Page 12 of 39 Printed on: 11/12/2008


Created using: 15.0.0(BS7671:2008) - Rockson Engineering Ltd Copyright © AMTECH Power Software Ltd 2008
Cable Calculation Report

Project Reference: CCB - ALAOJI 504MW PP Job Number: RK-117-E-2020-2029


Document No: CCB-DBP-001 Created On : 08/10/2008 Rev Date :
Created By : ARNEL CORPUZ Modified By: Rev No:

Calculated in accordance with BS7671

Cable CKT P112


Connection From: DB-P1/4/L3 To: P112
Active Source: Source-1
Load Type: Sockets BS EN 60309-2, 20A radial circuit Design Current Ib (A): 12.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: MEM Memshield 2 MCB Type C (MCH) Th/Mag
Rating In (A): 20 [f] Overload Setting Ir (A): 20 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 1 x 2 x 1c Size (mm2 ): 4 [f]
Neutral: 4 mm²[a] Length (m): 13
1 - In conduit in a thermally insulated wall Conduit: Plastic

Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]

3rd Harmonics (%) = 0.00 Ch = 1.00


CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 11.5 V (to BS 7671:2008 Appendix 12)
Design Current Ib = 12.0
Device Rating In = 20 Overload Setting Ir = 20 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 35.0 _ Iz]
[It >

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 0.0 / 0.00 12.0 / 1.00 12.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 0.00 / 0.00 1.56 / 0.68 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 0.00 / 0.00 4.09 / 1.78 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 1 [a] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.36294 0.07800 0.29900 0.73980 1.15000 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 0.40
0.31
Adiabatic check (mm 2 ) CPC Section = Separate 1 Total = 1.0 Min. Section = 0.29

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 5.206 / 2.240 Load End: 1.399 / 0.891
Protective Device Breaking Capacity (kA): Icu: 10 Ics: 10

Adiabatic Check: CPD Energy Let-through (A²s): 3,186.04 Adiabatic Limit k²S² (A²s): 327.18 x 103

Project: D:\My Documents\ALAOJI\SERVICE BLDGS\CentralControlBldg\CCB-DBP.p17 Page 13 of 39 Printed on: 11/12/2008


Created using: 15.0.0(BS7671:2008) - Rockson Engineering Ltd Copyright © AMTECH Power Software Ltd 2008
Cable Calculation Report

Project Reference: CCB - ALAOJI 504MW PP Job Number: RK-117-E-2020-2029


Document No: CCB-DBP-001 Created On : 08/10/2008 Rev Date :
Created By : ARNEL CORPUZ Modified By: Rev No:

Calculated in accordance with BS7671

Cable CKT P113


Connection From: DB-P1/5/L1 To: P113
Active Source: Source-1
Load Type: Sockets BS EN 60309-2, 20A radial circuit Design Current Ib (A): 12.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: MEM Memshield 2 MCB Type C (MCH) Th/Mag
Rating In (A): 20 [f] Overload Setting Ir (A): 20 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 1 x 2 x 1c Size (mm2 ): 4 [f]
Neutral: 4 mm²[a] Length (m): 19
1 - In conduit in a thermally insulated wall Conduit: Plastic

Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]

3rd Harmonics (%) = 0.00 Ch = 1.00


CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 11.5 V (to BS 7671:2008 Appendix 12)
Design Current Ib = 12.0
Device Rating In = 20 Overload Setting Ir = 20 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 35.0 _ Iz]
[It >

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 12.0 / 1.00 0.0 / 0.00 0.0 / 0.00 12.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 2.28 / 0.99 0.00 / 0.00 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 4.71 / 2.05 0.00 / 0.00 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 1 [a] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.36294 0.11400 0.43700 0.91377 1.15000 Current (kA)

Disconnection time (s): From characteristic: 0.05 Maximum for circuit: 0.40
0.25
Adiabatic check (mm 2 ) CPC Section = Separate 1 Total = 1.0 Min. Section = 0.29

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 5.206 / 2.240 Load End: 1.043 / 0.697
Protective Device Breaking Capacity (kA): Icu: 10 Ics: 10

Adiabatic Check: CPD Energy Let-through (A²s): 2,448.19 Adiabatic Limit k²S² (A²s): 327.18 x 103

Project: D:\My Documents\ALAOJI\SERVICE BLDGS\CentralControlBldg\CCB-DBP.p17 Page 14 of 39 Printed on: 11/12/2008


Created using: 15.0.0(BS7671:2008) - Rockson Engineering Ltd Copyright © AMTECH Power Software Ltd 2008
Cable Calculation Report

Project Reference: CCB - ALAOJI 504MW PP Job Number: RK-117-E-2020-2029


Document No: CCB-DBP-001 Created On : 08/10/2008 Rev Date :
Created By : ARNEL CORPUZ Modified By: Rev No:

Calculated in accordance with BS7671

Cable CKT P117


Connection From: DB-P1/5/L3 To: P117
Active Source: Source-1
Load Type: Sockets BS EN 60309-2, 20A radial circuit Design Current Ib (A): 12.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: MEM Memshield 2 MCB Type C (MCH) Th/Mag
Rating In (A): 20 [f] Overload Setting Ir (A): 20 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 1 x 2 x 1c Size (mm2 ): 4 [f]
Neutral: 4 mm²[a] Length (m): 21
1 - In conduit in a thermally insulated wall Conduit: Plastic

Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]

3rd Harmonics (%) = 0.00 Ch = 1.00


CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 11.5 V (to BS 7671:2008 Appendix 12)
Design Current Ib = 12.0
Device Rating In = 20 Overload Setting Ir = 20 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 35.0 _ Iz]
[It >

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 0.0 / 0.00 12.0 / 1.00 12.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 0.00 / 0.00 2.52 / 1.10 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 0.00 / 0.00 5.05 / 2.19 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 1 [a] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.36294 0.12600 0.48300 0.97177 1.15000 Current (kA)

Disconnection time (s): From characteristic: 0.09 Maximum for circuit: 0.40
0.24
Adiabatic check (mm 2 ) CPC Section = Separate 1 Total = 1.0 Min. Section = 0.29

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 5.206 / 2.240 Load End: 0.961 / 0.650
Protective Device Breaking Capacity (kA): Icu: 10 Ics: 10

Adiabatic Check: CPD Energy Let-through (A²s): 2,268.81 Adiabatic Limit k²S² (A²s): 327.18 x 103

Project: D:\My Documents\ALAOJI\SERVICE BLDGS\CentralControlBldg\CCB-DBP.p17 Page 15 of 39 Printed on: 11/12/2008


Created using: 15.0.0(BS7671:2008) - Rockson Engineering Ltd Copyright © AMTECH Power Software Ltd 2008
Cable Calculation Report

Project Reference: CCB - ALAOJI 504MW PP Job Number: RK-117-E-2020-2029


Document No: CCB-DBP-001 Created On : 08/10/2008 Rev Date :
Created By : ARNEL CORPUZ Modified By: Rev No:

Calculated in accordance with BS7671

Cable CKT P201


Connection From: DB-P2/1/L1 To: P201
Active Source: Source-1
Load Type: Sockets BS 1363, 32A ring final circuit to sockets up to 100m² Design Current Ib (A): 7.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: MEM Memshield 2 MCB Type C (MCV) 15kA Th/Mag
Rating In (A): 32 [f] Overload Setting Ir (A): 32 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 2 x 2 x 1c Size (mm2 ): 4 [f]
Neutral: 4 mm²[a] Length (m): 65
1 - In conduit in a thermally insulated wall Conduit: Plastic

Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]

3rd Harmonics (%) = 0.00 Ch = 1.00


CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 11.5 V (to BS 7671:2008 Appendix 12)
Design Current Ib = 7.0
Device Rating In = 32 Overload Setting Ir = 32 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 35.0 _ Iz]
[It >

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 7.0 / 1.00 0.0 / 0.00 0.0 / 0.00 7.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 1.11 / 0.48 0.00 / 0.00 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 2.62 / 1.14 0.00 / 0.00 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 1.5 [a] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.27309 0.09750 0.25188 0.62221 0.71875 Current (kA)

Disconnection time (s): From characteristic: 0.08 Maximum for circuit: 0.40
0.37
Adiabatic check (mm 2 ) CPC Section = Separate 1.5 Total = 1.5 Min. Section = 0.31

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 9.542 / 5.106 Load End: 1.341 / 0.969
Protective Device Breaking Capacity (kA): Icu: 15 Ics: 7.5

Adiabatic Check: CPD Energy Let-through (A²s): 3,923.69 Adiabatic Limit k²S² (A²s): 327.18 x 103

Project: D:\My Documents\ALAOJI\SERVICE BLDGS\CentralControlBldg\CCB-DBP.p17 Page 16 of 39 Printed on: 11/12/2008


Created using: 15.0.0(BS7671:2008) - Rockson Engineering Ltd Copyright © AMTECH Power Software Ltd 2008
Cable Calculation Report

Project Reference: CCB - ALAOJI 504MW PP Job Number: RK-117-E-2020-2029


Document No: CCB-DBP-001 Created On : 08/10/2008 Rev Date :
Created By : ARNEL CORPUZ Modified By: Rev No:

Calculated in accordance with BS7671

Cable CKT P202


Connection From: DB-P2/2/L1 To: P202
Active Source: Source-1
Load Type: Sockets BS 1363, 32A ring final circuit to sockets up to 100m² Design Current Ib (A): 9.6

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: MEM Memshield 2 MCB Type C (MCV) 15kA Th/Mag
Rating In (A): 32 [f] Overload Setting Ir (A): 32 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 2 x 2 x 1c Size (mm2 ): 4 [f]
Neutral: 4 mm²[a] Length (m): 56
1 - In conduit in a thermally insulated wall Conduit: Plastic

Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]

3rd Harmonics (%) = 0.00 Ch = 1.00


CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 11.5 V (to BS 7671:2008 Appendix 12)
Design Current Ib = 9.6
Device Rating In = 32 Overload Setting Ir = 32 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 35.0 _ Iz]
[It >

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 9.6 / 1.00 0.0 / 0.00 0.0 / 0.00 9.6
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 1.33 / 0.58 0.00 / 0.00 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 2.83 / 1.23 0.00 / 0.00 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 1.5 [a] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.27309 0.08400 0.21700 0.57386 0.71875 Current (kA)

Disconnection time (s): From characteristic: 0.03 Maximum for circuit: 0.40
0.40
Adiabatic check (mm 2 ) CPC Section = Separate 1.5 Total = 1.5 Min. Section = 0.31

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 9.542 / 5.106 Load End: 1.528 / 1.093
Protective Device Breaking Capacity (kA): Icu: 15 Ics: 7.5

Adiabatic Check: CPD Energy Let-through (A²s): 4,432.16 Adiabatic Limit k²S² (A²s): 327.18 x 103

Project: D:\My Documents\ALAOJI\SERVICE BLDGS\CentralControlBldg\CCB-DBP.p17 Page 17 of 39 Printed on: 11/12/2008


Created using: 15.0.0(BS7671:2008) - Rockson Engineering Ltd Copyright © AMTECH Power Software Ltd 2008
Cable Calculation Report

Project Reference: CCB - ALAOJI 504MW PP Job Number: RK-117-E-2020-2029


Document No: CCB-DBP-001 Created On : 08/10/2008 Rev Date :
Created By : ARNEL CORPUZ Modified By: Rev No:

Calculated in accordance with BS7671

Cable CKT P203


Connection From: DB-P2/1/L2 To: P203
Active Source: Source-1
Load Type: Sockets BS 1363, 32A ring final circuit to sockets up to 100m² Design Current Ib (A): 5.2

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: MEM Memshield 2 MCB Type C (MCV) 15kA Th/Mag
Rating In (A): 32 [f] Overload Setting Ir (A): 32 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 2 x 2 x 1c Size (mm2 ): 4 [f]
Neutral: 4 mm²[a] Length (m): 57
1 - In conduit in a thermally insulated wall Conduit: Plastic

Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]

3rd Harmonics (%) = 0.00 Ch = 1.00


CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 11.5 V (to BS 7671:2008 Appendix 12)
Design Current Ib = 5.2
Device Rating In = 32 Overload Setting Ir = 32 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 35.0 _ Iz]
[It >

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 5.2 / 1.00 0.0 / 0.00 5.2
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 0.73 / 0.32 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 2.39 / 1.04 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 1.5 [a] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.27309 0.08550 0.22088 0.57923 0.71875 Current (kA)

Disconnection time (s): From characteristic: 0.04 Maximum for circuit: 0.40
0.40
Adiabatic check (mm 2 ) CPC Section = Separate 1.5 Total = 1.5 Min. Section = 0.31

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 9.542 / 5.106 Load End: 1.505 / 1.078
Protective Device Breaking Capacity (kA): Icu: 15 Ics: 7.5

Adiabatic Check: CPD Energy Let-through (A²s): 4,369.34 Adiabatic Limit k²S² (A²s): 327.18 x 103

Project: D:\My Documents\ALAOJI\SERVICE BLDGS\CentralControlBldg\CCB-DBP.p17 Page 18 of 39 Printed on: 11/12/2008


Created using: 15.0.0(BS7671:2008) - Rockson Engineering Ltd Copyright © AMTECH Power Software Ltd 2008
Cable Calculation Report

Project Reference: CCB - ALAOJI 504MW PP Job Number: RK-117-E-2020-2029


Document No: CCB-DBP-001 Created On : 08/10/2008 Rev Date :
Created By : ARNEL CORPUZ Modified By: Rev No:

Calculated in accordance with BS7671

Cable CKT P204


Connection From: DB-P2/2/L2 To: P204
Active Source: Source-1
Load Type: Sockets BS 1363, 32A ring final circuit to sockets up to 100m² Design Current Ib (A): 7.8

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: MEM Memshield 2 MCB Type C (MCV) 15kA Th/Mag
Rating In (A): 32 [f] Overload Setting Ir (A): 32 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 2 x 2 x 1c Size (mm2 ): 4 [f]
Neutral: 4 mm²[a] Length (m): 33
1 - In conduit in a thermally insulated wall Conduit: Plastic

Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]

3rd Harmonics (%) = 0.00 Ch = 1.00


CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 11.5 V (to BS 7671:2008 Appendix 12)
Design Current Ib = 7.8
Device Rating In = 32 Overload Setting Ir = 32 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 35.0 _ Iz]
[It >

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 7.8 / 1.00 0.0 / 0.00 7.8
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 0.64 / 0.28 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 2.30 / 1.00 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 1 [a] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.27309 0.04950 0.18975 0.51213 0.71875 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 0.40
0.45
Adiabatic check (mm 2 ) CPC Section = Separate 1 Total = 1.0 Min. Section = 0.31

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 9.542 / 5.106 Load End: 2.370 / 1.623
Protective Device Breaking Capacity (kA): Icu: 15 Ics: 7.5

Adiabatic Check: CPD Energy Let-through (A²s): 6,812.49 Adiabatic Limit k²S² (A²s): 327.18 x 103

Project: D:\My Documents\ALAOJI\SERVICE BLDGS\CentralControlBldg\CCB-DBP.p17 Page 19 of 39 Printed on: 11/12/2008


Created using: 15.0.0(BS7671:2008) - Rockson Engineering Ltd Copyright © AMTECH Power Software Ltd 2008
Cable Calculation Report

Project Reference: CCB - ALAOJI 504MW PP Job Number: RK-117-E-2020-2029


Document No: CCB-DBP-001 Created On : 08/10/2008 Rev Date :
Created By : ARNEL CORPUZ Modified By: Rev No:

Calculated in accordance with BS7671

Cable CKT P205


Connection From: DB-P2/1/L3 To: P205
Active Source: Source-1
Load Type: Sockets BS 1363, 32A ring final circuit to sockets up to 100m² Design Current Ib (A): 5.2

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: MEM Memshield 2 MCB Type C (MCV) 15kA Th/Mag
Rating In (A): 32 [f] Overload Setting Ir (A): 32 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 2 x 2 x 1c Size (mm2 ): 4 [f]
Neutral: 4 mm²[a] Length (m): 51
1 - In conduit in a thermally insulated wall Conduit: Plastic

Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]

3rd Harmonics (%) = 0.00 Ch = 1.00


CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 11.5 V (to BS 7671:2008 Appendix 12)
Design Current Ib = 5.2
Device Rating In = 32 Overload Setting Ir = 32 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 35.0 _ Iz]
[It >

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 0.0 / 0.00 5.2 / 1.00 5.2
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 0.00 / 0.00 0.65 / 0.28 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 0.00 / 0.00 2.43 / 1.06 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 1 [a] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.27309 0.07650 0.29325 0.64258 0.71875 Current (kA)

Disconnection time (s): From characteristic: 0.11 Maximum for circuit: 0.40
0.36
Adiabatic check (mm 2 ) CPC Section = Separate 1 Total = 1.0 Min. Section = 0.84

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 9.542 / 5.106 Load End: 1.656 / 1.177
Protective Device Breaking Capacity (kA): Icu: 15 Ics: 7.5

Adiabatic Check: CPD Energy Let-through (A²s): 4,774.94 Adiabatic Limit k²S² (A²s): 327.18 x 103

Project: D:\My Documents\ALAOJI\SERVICE BLDGS\CentralControlBldg\CCB-DBP.p17 Page 20 of 39 Printed on: 11/12/2008


Created using: 15.0.0(BS7671:2008) - Rockson Engineering Ltd Copyright © AMTECH Power Software Ltd 2008
Cable Calculation Report

Project Reference: CCB - ALAOJI 504MW PP Job Number: RK-117-E-2020-2029


Document No: CCB-DBP-001 Created On : 08/10/2008 Rev Date :
Created By : ARNEL CORPUZ Modified By: Rev No:

Calculated in accordance with BS7671

Cable CKT P206


Connection From: DB-P2/2/L3 To: P206
Active Source: Source-1
Load Type: Sockets BS 1363, 32A ring final circuit to sockets up to 100m² Design Current Ib (A): 5.2

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: MEM Memshield 2 MCB Type C (MCV) 15kA Th/Mag
Rating In (A): 32 [f] Overload Setting Ir (A): 32 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 2 x 2 x 1c Size (mm2 ): 4 [f]
Neutral: 4 mm²[a] Length (m): 72
1 - In conduit in a thermally insulated wall Conduit: Plastic

Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]

3rd Harmonics (%) = 0.00 Ch = 1.00


CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 11.5 V (to BS 7671:2008 Appendix 12)
Design Current Ib = 5.2
Device Rating In = 32 Overload Setting Ir = 32 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 35.0 _ Iz]
[It >

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 0.0 / 0.00 5.2 / 1.00 5.2
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 0.00 / 0.00 0.92 / 0.40 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 0.00 / 0.00 2.70 / 1.17 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 1.5 [a] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.27309 0.10800 0.27900 0.65983 0.71875 Current (kA)

Disconnection time (s): From characteristic: 0.15 Maximum for circuit: 0.40
0.35
Adiabatic check (mm 2 ) CPC Section = Separate 1.5 Total = 1.5 Min. Section = 0.95

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 9.542 / 5.106 Load End: 1.224 / 0.891
Protective Device Breaking Capacity (kA): Icu: 15 Ics: 7.5

Adiabatic Check: CPD Energy Let-through (A²s): 3,601.34 Adiabatic Limit k²S² (A²s): 327.18 x 103

Project: D:\My Documents\ALAOJI\SERVICE BLDGS\CentralControlBldg\CCB-DBP.p17 Page 21 of 39 Printed on: 11/12/2008


Created using: 15.0.0(BS7671:2008) - Rockson Engineering Ltd Copyright © AMTECH Power Software Ltd 2008
Cable Calculation Report

Project Reference: CCB - ALAOJI 504MW PP Job Number: RK-117-E-2020-2029


Document No: CCB-DBP-001 Created On : 08/10/2008 Rev Date :
Created By : ARNEL CORPUZ Modified By: Rev No:

Calculated in accordance with BS7671

Cable CKT P207


Connection From: DB-P2/3/L1 To: P207
Active Source: Source-1
Load Type: Lighting, radial circuits Design Current Ib (A): 7.9
Length to First Fitting (m): 33.00
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: MEM Memshield 2 MCB Type C (MCV) 15kA Th/Mag
Rating In (A): 10 [f] Overload Setting Ir (A): 10 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 1 x 2 x 1c Size (mm2 ): 2.5 [f]
Neutral: 2.5 mm²[a] Length (m): 116
1 - In conduit in a thermally insulated wall Conduit: Plastic

Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]

3rd Harmonics (%) = 0.00 Ch = 1.00


CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 11.5 V (User defined)
Design Current Ib = 7.9
Device Rating In = 10 Overload Setting Ir = 10 [Ir >
_ Ib]
Min. Cable Capacity Iz = 10.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 26.0 _ Iz]
[It >

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 7.9 / 1.00 0.0 / 0.00 0.0 / 0.00 7.9
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 9.30 / 4.05 0.00 / 0.00 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 10.81 / 4.70 0.00 / 0.00 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 4 [a] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.27309 1.10200 0.69600 2.07070 2.30000 Current (kA)

Disconnection time (s): From characteristic: 0.16 Maximum for circuit: 0.40
0.11
Adiabatic check (mm 2 ) CPC Section = Separate 4 Total = 4.0 Min. Section = 0.31

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 9.542 / 5.106 Load End: 0.132 / 0.102
Protective Device Breaking Capacity (kA): Icu: 15 Ics: 7.5

Adiabatic Check: Max. disconnection time (s) = (k²S²/I²): 12.28 Actual disconnection time (s) = 0.33

Project: D:\My Documents\ALAOJI\SERVICE BLDGS\CentralControlBldg\CCB-DBP.p17 Page 22 of 39 Printed on: 11/12/2008


Created using: 15.0.0(BS7671:2008) - Rockson Engineering Ltd Copyright © AMTECH Power Software Ltd 2008
Cable Calculation Report

Project Reference: CCB - ALAOJI 504MW PP Job Number: RK-117-E-2020-2029


Document No: CCB-DBP-001 Created On : 08/10/2008 Rev Date :
Created By : ARNEL CORPUZ Modified By: Rev No:

Calculated in accordance with BS7671

Cable CKT P208


Connection From: DB-P2/4/L1 To: P208
Active Source: Source-1
Load Type: Lighting, radial circuits Design Current Ib (A): 11.0
Length to First Fitting (m): 25.00
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: MEM Memshield 2 MCB Type C (MCV) 15kA Th/Mag
Rating In (A): 16 [f] Overload Setting Ir (A): 16 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 1 x 2 x 1c Size (mm2 ): 2.5 [f]
Neutral: 2.5 mm²[a] Length (m): 72
1 - In conduit in a thermally insulated wall Conduit: Plastic

Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]

3rd Harmonics (%) = 0.00 Ch = 1.00


CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 11.5 V (User defined)
Design Current Ib = 11.0
Device Rating In = 16 Overload Setting Ir = 16 [Ir >
_ Ib]
Min. Cable Capacity Iz = 16.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 26.0 _ Iz]
[It >

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 11.0 / 1.00 0.0 / 0.00 0.0 / 0.00 11.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 8.58 / 3.73 0.00 / 0.00 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 10.08 / 4.38 0.00 / 0.00 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 4 [a] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.27309 0.68400 0.43200 1.38873 1.39394 Current (kA)

Disconnection time (s): From characteristic: 0.39 Maximum for circuit: 0.40
0.17
Adiabatic check (mm 2 ) CPC Section = Separate 4 Total = 4.0 Min. Section = 0.72

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 9.542 / 5.106 Load End: 0.212 / 0.163
Protective Device Breaking Capacity (kA): Icu: 15 Ics: 7.5

Adiabatic Check: Max. disconnection time (s) = (k²S²/I²): 4.81 Actual disconnection time (s) = 0.43

Project: D:\My Documents\ALAOJI\SERVICE BLDGS\CentralControlBldg\CCB-DBP.p17 Page 23 of 39 Printed on: 11/12/2008


Created using: 15.0.0(BS7671:2008) - Rockson Engineering Ltd Copyright © AMTECH Power Software Ltd 2008
Cable Calculation Report

Project Reference: CCB - ALAOJI 504MW PP Job Number: RK-117-E-2020-2029


Document No: CCB-DBP-001 Created On : 08/10/2008 Rev Date :
Created By : ARNEL CORPUZ Modified By: Rev No:

Calculated in accordance with BS7671

Cable CKT P209


Connection From: DB-P2/3/L2 To: P209
Active Source: Source-1
Load Type: Lighting, radial circuits Design Current Ib (A): 4.8
Length to First Fitting (m): 19.00
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: MEM Memshield 2 MCB Type C (MCV) 15kA Th/Mag
Rating In (A): 10 [f] Overload Setting Ir (A): 10 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 1 x 2 x 1c Size (mm2 ): 2.5 [f]
Neutral: 2.5 mm²[a] Length (m): 68
1 - In conduit in a thermally insulated wall Conduit: Plastic

Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]

3rd Harmonics (%) = 0.00 Ch = 1.00


CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 6.9 V (to BS 7671:2008 Appendix 12)
Design Current Ib = 4.8
Device Rating In = 10 Overload Setting Ir = 10 _ Ib]
[Ir >
Min. Cable Capacity Iz = 10.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 26.0 _ Iz]
[It >

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 4.8 / 1.00 0.0 / 0.00 4.8
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 3.26 / 1.42 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 4.93 / 2.14 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 1.5 [a] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.27309 0.64600 1.05400 1.97271 2.30000 Current (kA)

Disconnection time (s): From characteristic: 0.11 Maximum for circuit: 0.40
0.12
Adiabatic check (mm 2 ) CPC Section = Separate 1.5 Total = 1.5 Min. Section = 0.26

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 9.542 / 5.106 Load End: 0.224 / 0.172
Protective Device Breaking Capacity (kA): Icu: 15 Ics: 7.5

Adiabatic Check: CPD Energy Let-through (A²s): 1,350.00 Adiabatic Limit k²S² (A²s): 127.81 x 103

Project: D:\My Documents\ALAOJI\SERVICE BLDGS\CentralControlBldg\CCB-DBP.p17 Page 24 of 39 Printed on: 11/12/2008


Created using: 15.0.0(BS7671:2008) - Rockson Engineering Ltd Copyright © AMTECH Power Software Ltd 2008
Cable Calculation Report

Project Reference: CCB - ALAOJI 504MW PP Job Number: RK-117-E-2020-2029


Document No: CCB-DBP-001 Created On : 08/10/2008 Rev Date :
Created By : ARNEL CORPUZ Modified By: Rev No:

Calculated in accordance with BS7671

Cable CKT P210


Connection From: DB-P2/4/L2 To: P210
Active Source: Source-1
Load Type: Lighting, radial circuits Design Current Ib (A): 9.2
Length to First Fitting (m): 24.00
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: MEM Memshield 2 MCB Type C (MCV) 15kA Th/Mag
Rating In (A): 16 [f] Overload Setting Ir (A): 16 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 1 x 2 x 1c Size (mm2 ): 2.5 [f]
Neutral: 2.5 mm²[a] Length (m): 33
1 - In conduit in a thermally insulated wall Conduit: Plastic

Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]

3rd Harmonics (%) = 0.00 Ch = 1.00


CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 6.9 V (to BS 7671:2008 Appendix 12)
Design Current Ib = 9.2
Device Rating In = 16 Overload Setting Ir = 16 _ Ib]
[Ir >
Min. Cable Capacity Iz = 16.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 26.0 _ Iz]
[It >

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 9.2 / 1.00 0.0 / 0.00 9.2
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 4.17 / 1.81 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 5.84 / 2.54 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 1 [a] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.27309 0.31350 0.75900 1.34524 1.39394 Current (kA)

Disconnection time (s): From characteristic: 0.31 Maximum for circuit: 0.40
0.17
Adiabatic check (mm 2 ) CPC Section = Separate 1 Total = 1.0 Min. Section = 0.67

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 9.542 / 5.106 Load End: 0.452 / 0.344
Protective Device Breaking Capacity (kA): Icu: 15 Ics: 7.5

Adiabatic Check: CPD Energy Let-through (A²s): 1,600.00 Adiabatic Limit k²S² (A²s): 127.81 x 103

Project: D:\My Documents\ALAOJI\SERVICE BLDGS\CentralControlBldg\CCB-DBP.p17 Page 25 of 39 Printed on: 11/12/2008


Created using: 15.0.0(BS7671:2008) - Rockson Engineering Ltd Copyright © AMTECH Power Software Ltd 2008
Cable Calculation Report

Project Reference: CCB - ALAOJI 504MW PP Job Number: RK-117-E-2020-2029


Document No: CCB-DBP-001 Created On : 08/10/2008 Rev Date :
Created By : ARNEL CORPUZ Modified By: Rev No:

Calculated in accordance with BS7671

Cable CKT P211


Connection From: DB-P2/3/L3 To: P211
Active Source: Source-1
Load Type: Lighting, radial circuits Design Current Ib (A): 5.3
Length to First Fitting (m): 22.00
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: MEM Memshield 2 MCB Type C (MCV) 15kA Th/Mag
Rating In (A): 10 [f] Overload Setting Ir (A): 10 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 1 x 2 x 1c Size (mm2 ): 2.5 [f]
Neutral: 2.5 mm²[a] Length (m): 76
1 - In conduit in a thermally insulated wall Conduit: Plastic

Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]

3rd Harmonics (%) = 0.00 Ch = 1.00


CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 6.9 V (to BS 7671:2008 Appendix 12)
Design Current Ib = 5.3
Device Rating In = 10 Overload Setting Ir = 10 _ Ib]
[Ir >
Min. Cable Capacity Iz = 10.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 26.0 _ Iz]
[It >

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 0.0 / 0.00 5.3 / 1.00 5.3
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 0.00 / 0.00 4.03 / 1.75 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 0.00 / 0.00 5.81 / 2.53 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 1.5 [a] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.27309 0.72200 1.17800 2.17270 2.30000 Current (kA)

Disconnection time (s): From characteristic: 0.24 Maximum for circuit: 0.40
0.11
Adiabatic check (mm 2 ) CPC Section = Separate 1.5 Total = 1.5 Min. Section = 0.37

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 9.542 / 5.106 Load End: 0.201 / 0.155
Protective Device Breaking Capacity (kA): Icu: 15 Ics: 7.5

Adiabatic Check: CPD Energy Let-through (A²s): 1,350.00 Adiabatic Limit k²S² (A²s): 127.81 x 103

Project: D:\My Documents\ALAOJI\SERVICE BLDGS\CentralControlBldg\CCB-DBP.p17 Page 26 of 39 Printed on: 11/12/2008


Created using: 15.0.0(BS7671:2008) - Rockson Engineering Ltd Copyright © AMTECH Power Software Ltd 2008
Cable Calculation Report

Project Reference: CCB - ALAOJI 504MW PP Job Number: RK-117-E-2020-2029


Document No: CCB-DBP-001 Created On : 08/10/2008 Rev Date :
Created By : ARNEL CORPUZ Modified By: Rev No:

Calculated in accordance with BS7671

Cable CKT P212


Connection From: DB-P2/4/L3 To: P212
Active Source: Source-1
Load Type: Sockets BS EN 60309-2, 20A radial circuit Design Current Ib (A): 12.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: MEM Memshield 2 MCB Type C (MCV) 15kA Th/Mag
Rating In (A): 20 [f] Overload Setting Ir (A): 20 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 1 x 2 x 1c Size (mm2 ): 4 [f]
Neutral: 4 mm²[a] Length (m): 27
1 - In conduit in a thermally insulated wall Conduit: Plastic

Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]

3rd Harmonics (%) = 0.00 Ch = 1.00


CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 11.5 V (to BS 7671:2008 Appendix 12)
Design Current Ib = 12.0
Device Rating In = 20 Overload Setting Ir = 20 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 35.0 _ Iz]
[It >

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 0.0 / 0.00 12.0 / 1.00 12.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 0.00 / 0.00 3.24 / 1.41 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 0.00 / 0.00 5.02 / 2.18 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 1 [a] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.27309 0.16200 0.62100 1.05576 1.15000 Current (kA)

Disconnection time (s): From characteristic: 0.19 Maximum for circuit: 0.40
0.22
Adiabatic check (mm 2 ) CPC Section = Separate 1 Total = 1.0 Min. Section = 0.66

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 9.542 / 5.106 Load End: 0.845 / 0.628
Protective Device Breaking Capacity (kA): Icu: 15 Ics: 7.5

Adiabatic Check: CPD Energy Let-through (A²s): 2,187.36 Adiabatic Limit k²S² (A²s): 327.18 x 103

Project: D:\My Documents\ALAOJI\SERVICE BLDGS\CentralControlBldg\CCB-DBP.p17 Page 27 of 39 Printed on: 11/12/2008


Created using: 15.0.0(BS7671:2008) - Rockson Engineering Ltd Copyright © AMTECH Power Software Ltd 2008
Cable Calculation Report

Project Reference: CCB - ALAOJI 504MW PP Job Number: RK-117-E-2020-2029


Document No: CCB-DBP-001 Created On : 08/10/2008 Rev Date :
Created By : ARNEL CORPUZ Modified By: Rev No:

Calculated in accordance with BS7671

Cable CKT P213


Connection From: DB-P2/5/L1 To: P213
Active Source: Source-1
Load Type: Sockets BS EN 60309-2, 20A radial circuit Design Current Ib (A): 12.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: MEM Memshield 2 MCB Type C (MCV) 15kA Th/Mag
Rating In (A): 20 [f] Overload Setting Ir (A): 20 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 1 x 2 x 1c Size (mm2 ): 4 [f]
Neutral: 4 mm²[a] Length (m): 41
1 - In conduit in a thermally insulated wall Conduit: Plastic

Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]

3rd Harmonics (%) = 0.00 Ch = 1.00


CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 11.5 V (to BS 7671:2008 Appendix 12)
Design Current Ib = 12.0
Device Rating In = 20 Overload Setting Ir = 20 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 35.0 _ Iz]
[It >

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 12.0 / 1.00 0.0 / 0.00 0.0 / 0.00 12.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 4.93 / 2.14 0.00 / 0.00 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 6.43 / 2.80 0.00 / 0.00 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 2.5 [a] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.27309 0.24600 0.38950 0.90828 1.15000 Current (kA)

Disconnection time (s): From characteristic: 0.05 Maximum for circuit: 0.40
0.25
Adiabatic check (mm 2 ) CPC Section = Separate 2.5 Total = 2.5 Min. Section = 0.29

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 9.542 / 5.106 Load End: 0.571 / 0.431
Protective Device Breaking Capacity (kA): Icu: 15 Ics: 7.5

Adiabatic Check: CPD Energy Let-through (A²s): 1,700.00 Adiabatic Limit k²S² (A²s): 327.18 x 103

Project: D:\My Documents\ALAOJI\SERVICE BLDGS\CentralControlBldg\CCB-DBP.p17 Page 28 of 39 Printed on: 11/12/2008


Created using: 15.0.0(BS7671:2008) - Rockson Engineering Ltd Copyright © AMTECH Power Software Ltd 2008
Cable Calculation Report

Project Reference: CCB - ALAOJI 504MW PP Job Number: RK-117-E-2020-2029


Document No: CCB-DBP-001 Created On : 08/10/2008 Rev Date :
Created By : ARNEL CORPUZ Modified By: Rev No:

Calculated in accordance with BS7671

Cable CKT P214


Connection From: DB-P2/6/L1 To: P214
Active Source: Source-1
Load Type: Sockets BS EN 60309-2, 20A radial circuit Design Current Ib (A): 12.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: MEM Memshield 2 MCB Type C (MCV) 15kA Th/Mag
Rating In (A): 20 [f] Overload Setting Ir (A): 20 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 1 x 2 x 1c Size (mm2 ): 4 [f]
Neutral: 4 mm²[a] Length (m): 32
1 - In conduit in a thermally insulated wall Conduit: Plastic

Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]

3rd Harmonics (%) = 0.00 Ch = 1.00


CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 11.5 V (to BS 7671:2008 Appendix 12)
Design Current Ib = 12.0
Device Rating In = 20 Overload Setting Ir = 20 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 35.0 _ Iz]
[It >

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 12.0 / 1.00 0.0 / 0.00 0.0 / 0.00 12.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 3.85 / 1.67 0.00 / 0.00 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 5.35 / 2.33 0.00 / 0.00 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 1.5 [a] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.27309 0.19200 0.49600 0.96077 1.15000 Current (kA)

Disconnection time (s): From characteristic: 0.08 Maximum for circuit: 0.40
0.24
Adiabatic check (mm 2 ) CPC Section = Separate 1.5 Total = 1.5 Min. Section = 0.29

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 9.542 / 5.106 Load End: 0.721 / 0.540
Protective Device Breaking Capacity (kA): Icu: 15 Ics: 7.5

Adiabatic Check: CPD Energy Let-through (A²s): 1,851.45 Adiabatic Limit k²S² (A²s): 327.18 x 103

Project: D:\My Documents\ALAOJI\SERVICE BLDGS\CentralControlBldg\CCB-DBP.p17 Page 29 of 39 Printed on: 11/12/2008


Created using: 15.0.0(BS7671:2008) - Rockson Engineering Ltd Copyright © AMTECH Power Software Ltd 2008
Cable Calculation Report

Project Reference: CCB - ALAOJI 504MW PP Job Number: RK-117-E-2020-2029


Document No: CCB-DBP-001 Created On : 08/10/2008 Rev Date :
Created By : ARNEL CORPUZ Modified By: Rev No:

Calculated in accordance with BS7671

Cable CKT P215


Connection From: DB-P2/5/L2 To: P215
Active Source: Source-1
Load Type: Sockets BS EN 60309-2, 20A radial circuit Design Current Ib (A): 12.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: MEM Memshield 2 MCB Type C (MCV) 15kA Th/Mag
Rating In (A): 20 [f] Overload Setting Ir (A): 20 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 1 x 2 x 1c Size (mm2 ): 4 [f]
Neutral: 4 mm²[a] Length (m): 43
1 - In conduit in a thermally insulated wall Conduit: Plastic

Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]

3rd Harmonics (%) = 0.00 Ch = 1.00


CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 11.5 V (to BS 7671:2008 Appendix 12)
Design Current Ib = 12.0
Device Rating In = 20 Overload Setting Ir = 20 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 35.0 _ Iz]
[It >

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 12.0 / 1.00 0.0 / 0.00 12.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 5.17 / 2.25 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 6.83 / 2.97 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 2.5 [a] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.27309 0.25800 0.40850 0.93927 1.15000 Current (kA)

Disconnection time (s): From characteristic: 0.07 Maximum for circuit: 0.40
0.24
Adiabatic check (mm 2 ) CPC Section = Separate 2.5 Total = 2.5 Min. Section = 0.29

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 9.542 / 5.106 Load End: 0.545 / 0.412
Protective Device Breaking Capacity (kA): Icu: 15 Ics: 7.5

Adiabatic Check: CPD Energy Let-through (A²s): 1,700.00 Adiabatic Limit k²S² (A²s): 327.18 x 103

Project: D:\My Documents\ALAOJI\SERVICE BLDGS\CentralControlBldg\CCB-DBP.p17 Page 30 of 39 Printed on: 11/12/2008


Created using: 15.0.0(BS7671:2008) - Rockson Engineering Ltd Copyright © AMTECH Power Software Ltd 2008
Cable Calculation Report

Project Reference: CCB - ALAOJI 504MW PP Job Number: RK-117-E-2020-2029


Document No: CCB-DBP-001 Created On : 08/10/2008 Rev Date :
Created By : ARNEL CORPUZ Modified By: Rev No:

Calculated in accordance with BS7671

Cable CKT P216


Connection From: DB-P2/6/L2 To: P216
Active Source: Source-1
Load Type: Lighting, radial circuits Design Current Ib (A): 7.9
Length to First Fitting (m): 24.00
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: MEM Memshield 2 MCB Type C (MCV) 15kA Th/Mag
Rating In (A): 16 [f] Overload Setting Ir (A): 16 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 1 x 2 x 1c Size (mm2 ): 2.5 [f]
Neutral: 2.5 mm²[a] Length (m): 50
1 - In conduit in a thermally insulated wall Conduit: Plastic

Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]

3rd Harmonics (%) = 0.00 Ch = 1.00


CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 6.9 V (to BS 7671:2008 Appendix 12)
Design Current Ib = 7.9
Device Rating In = 16 Overload Setting Ir = 16 _ Ib]
[Ir >
Min. Cable Capacity Iz = 16.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 26.0 _ Iz]
[It >

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 7.9 / 1.00 0.0 / 0.00 7.9
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 4.60 / 2.00 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 6.27 / 2.72 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 2.5 [a] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.27309 0.47500 0.47500 1.22274 1.39394 Current (kA)

Disconnection time (s): From characteristic: 0.16 Maximum for circuit: 0.40
0.19
Adiabatic check (mm 2 ) CPC Section = Separate 2.5 Total = 2.5 Min. Section = 0.52

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 9.542 / 5.106 Load End: 0.302 / 0.232
Protective Device Breaking Capacity (kA): Icu: 15 Ics: 7.5

Adiabatic Check: CPD Energy Let-through (A²s): 1,600.00 Adiabatic Limit k²S² (A²s): 127.81 x 103

Project: D:\My Documents\ALAOJI\SERVICE BLDGS\CentralControlBldg\CCB-DBP.p17 Page 31 of 39 Printed on: 11/12/2008


Created using: 15.0.0(BS7671:2008) - Rockson Engineering Ltd Copyright © AMTECH Power Software Ltd 2008
Cable Calculation Report

Project Reference: CCB - ALAOJI 504MW PP Job Number: RK-117-E-2020-2029


Document No: CCB-DBP-001 Created On : 08/10/2008 Rev Date :
Created By : ARNEL CORPUZ Modified By: Rev No:

Calculated in accordance with BS7671

Cable CKT P217


Connection From: DB-P2/5/L3 To: P217
Active Source: Source-1
Load Type: Sockets BS EN 60309-2, 20A radial circuit Design Current Ib (A): 12.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: MEM Memshield 2 MCB Type C (MCV) 15kA Th/Mag
Rating In (A): 20 [f] Overload Setting Ir (A): 20 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 1 x 2 x 1c Size (mm2 ): 4 [f]
Neutral: 4 mm²[a] Length (m): 51
1 - In conduit in a thermally insulated wall Conduit: Plastic

Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]

3rd Harmonics (%) = 0.00 Ch = 1.00


CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 11.5 V (to BS 7671:2008 Appendix 12)
Design Current Ib = 12.0
Device Rating In = 20 Overload Setting Ir = 20 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 35.0 _ Iz]
[It >

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 0.0 / 0.00 12.0 / 1.00 12.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 0.00 / 0.00 6.13 / 2.66 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 0.00 / 0.00 7.91 / 3.44 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 2.5 [a] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.27309 0.30600 0.48450 1.06326 1.15000 Current (kA)

Disconnection time (s): From characteristic: 0.20 Maximum for circuit: 0.40
0.22
Adiabatic check (mm 2 ) CPC Section = Separate 2.5 Total = 2.5 Min. Section = 0.68

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 9.542 / 5.106 Load End: 0.463 / 0.352
Protective Device Breaking Capacity (kA): Icu: 15 Ics: 7.5

Adiabatic Check: CPD Energy Let-through (A²s): 1,700.00 Adiabatic Limit k²S² (A²s): 327.18 x 103

Project: D:\My Documents\ALAOJI\SERVICE BLDGS\CentralControlBldg\CCB-DBP.p17 Page 32 of 39 Printed on: 11/12/2008


Created using: 15.0.0(BS7671:2008) - Rockson Engineering Ltd Copyright © AMTECH Power Software Ltd 2008
Cable Calculation Report

Project Reference: CCB - ALAOJI 504MW PP Job Number: RK-117-E-2020-2029


Document No: CCB-DBP-001 Created On : 08/10/2008 Rev Date :
Created By : ARNEL CORPUZ Modified By: Rev No:

Calculated in accordance with BS7671

Cable CKT P218


Connection From: DB-P2/6/L3 To: P218
Active Source: Source-1
Load Type: Sockets BS EN 60309-2, 20A radial circuit Design Current Ib (A): 12.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: MEM Memshield 2 MCB Type C (MCV) 15kA Th/Mag
Rating In (A): 20 [f] Overload Setting Ir (A): 20 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 1 x 2 x 1c Size (mm2 ): 4 [f]
Neutral: 4 mm²[a] Length (m): 65
1 - In conduit in a thermally insulated wall Conduit: Plastic

Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]

3rd Harmonics (%) = 0.00 Ch = 1.00


CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 11.5 V (to BS 7671:2008 Appendix 12)
Design Current Ib = 12.0
Device Rating In = 20 Overload Setting Ir = 20 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 35.0 _ Iz]
[It >

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 0.0 / 0.00 12.0 / 1.00 12.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 0.00 / 0.00 7.81 / 3.40 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 0.00 / 0.00 9.59 / 4.17 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 4 [a] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.27309 0.39000 0.39000 1.05276 1.15000 Current (kA)

Disconnection time (s): From characteristic: 0.19 Maximum for circuit: 0.40
0.22
Adiabatic check (mm 2 ) CPC Section = Separate 4 Total = 4.0 Min. Section = 0.66

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 9.542 / 5.106 Load End: 0.366 / 0.280
Protective Device Breaking Capacity (kA): Icu: 15 Ics: 7.5

Adiabatic Check: CPD Energy Let-through (A²s): 1,700.00 Adiabatic Limit k²S² (A²s): 327.18 x 103

Project: D:\My Documents\ALAOJI\SERVICE BLDGS\CentralControlBldg\CCB-DBP.p17 Page 33 of 39 Printed on: 11/12/2008


Created using: 15.0.0(BS7671:2008) - Rockson Engineering Ltd Copyright © AMTECH Power Software Ltd 2008
Cable Calculation Report

Project Reference: CCB - ALAOJI 504MW PP Job Number: RK-117-E-2020-2029


Document No: CCB-DBP-001 Created On : 08/10/2008 Rev Date :
Created By : ARNEL CORPUZ Modified By: Rev No:

Calculated in accordance with BS7671

Cable CKT P220


Connection From: DB-P2/8/L1 To: P220
Active Source: Source-1
Load Type: Lighting, radial circuits Design Current Ib (A): 7.9
Length to First Fitting (m): 33.00
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: MEM Memshield 2 MCB Type C (MCV) 15kA Th/Mag
Rating In (A): 10 [f] Overload Setting Ir (A): 10 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 1 x 2 x 1c Size (mm2 ): 2.5 [f]
Neutral: 2.5 mm²[a] Length (m): 116
4 - In conduit on a wooden/masonry wall Conduit: Plastic

Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]

3rd Harmonics (%) = 0.00 Ch = 1.00


CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 11.5 V (User defined)
Design Current Ib = 7.9
Device Rating In = 10 Overload Setting Ir = 10 [Ir >
_ Ib]
Min. Cable Capacity Iz = 10.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 31.0 _ Iz]
[It >

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 7.9 / 1.00 0.0 / 0.00 0.0 / 0.00 7.9
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 9.25 / 4.02 0.00 / 0.00 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 10.75 / 4.67 0.00 / 0.00 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 4 [a] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.27309 1.10200 0.69600 2.07070 2.30000 Current (kA)

Disconnection time (s): From characteristic: 0.16 Maximum for circuit: 0.40
0.11
Adiabatic check (mm 2 ) CPC Section = Separate 4 Total = 4.0 Min. Section = 0.31

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 9.542 / 5.106 Load End: 0.132 / 0.102
Protective Device Breaking Capacity (kA): Icu: 15 Ics: 7.5

Adiabatic Check: Max. disconnection time (s) = (k²S²/I²): 12.28 Actual disconnection time (s) = 0.33

Project: D:\My Documents\ALAOJI\SERVICE BLDGS\CentralControlBldg\CCB-DBP.p17 Page 34 of 39 Printed on: 11/12/2008


Created using: 15.0.0(BS7671:2008) - Rockson Engineering Ltd Copyright © AMTECH Power Software Ltd 2008
Cable Calculation Report

Project Reference: CCB - ALAOJI 504MW PP Job Number: RK-117-E-2020-2029


Document No: CCB-DBP-001 Created On : 08/10/2008 Rev Date :
Created By : ARNEL CORPUZ Modified By: Rev No:

Calculated in accordance with BS7671

Cable CKT P221


Connection From: DB-P2/7/L2 To: P221
Active Source: Source-1
Load Type: Sockets BS EN 60309-2, 20A radial circuit Design Current Ib (A): 12.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: MEM Memshield 2 MCB Type C (MCV) 15kA Th/Mag
Rating In (A): 20 [f] Overload Setting Ir (A): 20 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 1 x 2 x 1c Size (mm2 ): 4 [f]
Neutral: 4 mm²[a] Length (m): 54
1 - In conduit in a thermally insulated wall Conduit: Plastic

Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]

3rd Harmonics (%) = 0.00 Ch = 1.00


CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 11.5 V (User defined)
Design Current Ib = 12.0
Device Rating In = 20 Overload Setting Ir = 20 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 35.0 _ Iz]
[It >

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 12.0 / 1.00 0.0 / 0.00 12.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 6.49 / 2.82 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 8.15 / 3.55 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 2.5 [a] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.27309 0.32400 0.51300 1.10975 1.15000 Current (kA)

Disconnection time (s): From characteristic: 0.29 Maximum for circuit: 0.40
0.21
Adiabatic check (mm 2 ) CPC Section = Separate 2.5 Total = 2.5 Min. Section = 0.79

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 9.542 / 5.106 Load End: 0.438 / 0.333
Protective Device Breaking Capacity (kA): Icu: 15 Ics: 7.5

Adiabatic Check: CPD Energy Let-through (A²s): 1,700.00 Adiabatic Limit k²S² (A²s): 327.18 x 103

Project: D:\My Documents\ALAOJI\SERVICE BLDGS\CentralControlBldg\CCB-DBP.p17 Page 35 of 39 Printed on: 11/12/2008


Created using: 15.0.0(BS7671:2008) - Rockson Engineering Ltd Copyright © AMTECH Power Software Ltd 2008
Cable Calculation Report

Project Reference: CCB - ALAOJI 504MW PP Job Number: RK-117-E-2020-2029


Document No: CCB-DBP-001 Created On : 08/10/2008 Rev Date :
Created By : ARNEL CORPUZ Modified By: Rev No:

Calculated in accordance with BS7671

Cable CKT P222


Connection From: DB-P2/8/L2 To: P222
Active Source: Source-1
Load Type: Sockets BS EN 60309-2, 20A radial circuit Design Current Ib (A): 12.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: MEM Memshield 2 MCB Type C (MCV) 15kA Th/Mag
Rating In (A): 20 [f] Overload Setting Ir (A): 20 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 1 x 2 x 1c Size (mm2 ): 4 [f]
Neutral: 4 mm²[a] Length (m): 46
1 - In conduit in a thermally insulated wall Conduit: Plastic

Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]

3rd Harmonics (%) = 0.00 Ch = 1.00


CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 11.5 V (to BS 7671:2008 Appendix 12)
Design Current Ib = 12.0
Device Rating In = 20 Overload Setting Ir = 20 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 35.0 _ Iz]
[It >

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 12.0 / 1.00 0.0 / 0.00 12.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 5.53 / 2.40 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 7.19 / 3.13 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 2.5 [a] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.27309 0.27600 0.43700 0.98577 1.15000 Current (kA)

Disconnection time (s): From characteristic: 0.10 Maximum for circuit: 0.40
0.23
Adiabatic check (mm 2 ) CPC Section = Separate 2.5 Total = 2.5 Min. Section = 0.53

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 9.542 / 5.106 Load End: 0.511 / 0.387
Protective Device Breaking Capacity (kA): Icu: 15 Ics: 7.5

Adiabatic Check: CPD Energy Let-through (A²s): 1,700.00 Adiabatic Limit k²S² (A²s): 327.18 x 103

Project: D:\My Documents\ALAOJI\SERVICE BLDGS\CentralControlBldg\CCB-DBP.p17 Page 36 of 39 Printed on: 11/12/2008


Created using: 15.0.0(BS7671:2008) - Rockson Engineering Ltd Copyright © AMTECH Power Software Ltd 2008
Cable Calculation Report

Project Reference: CCB - ALAOJI 504MW PP Job Number: RK-117-E-2020-2029


Document No: CCB-DBP-001 Created On : 08/10/2008 Rev Date :
Created By : ARNEL CORPUZ Modified By: Rev No:

Calculated in accordance with BS7671

Cable CKT P223


Connection From: DB-P2/7/L3 To: P223
Active Source: Source-1
Load Type: Sockets BS EN 60309-2, 20A radial circuit Design Current Ib (A): 12.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: MEM Memshield 2 MCB Type C (MCV) 15kA Th/Mag
Rating In (A): 20 [f] Overload Setting Ir (A): 20 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 1 x 2 x 1c Size (mm2 ): 4 [f]
Neutral: 4 mm²[a] Length (m): 46
1 - In conduit in a thermally insulated wall Conduit: Plastic

Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]

3rd Harmonics (%) = 0.00 Ch = 1.00


CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 11.5 V (to BS 7671:2008 Appendix 12)
Design Current Ib = 12.0
Device Rating In = 20 Overload Setting Ir = 20 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 35.0 _ Iz]
[It >

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 0.0 / 0.00 12.0 / 1.00 12.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 0.00 / 0.00 5.53 / 2.40 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 0.00 / 0.00 7.31 / 3.18 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 2.5 [a] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.27309 0.27600 0.43700 0.98577 1.15000 Current (kA)

Disconnection time (s): From characteristic: 0.10 Maximum for circuit: 0.40
0.23
Adiabatic check (mm 2 ) CPC Section = Separate 2.5 Total = 2.5 Min. Section = 0.53

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 9.542 / 5.106 Load End: 0.511 / 0.387
Protective Device Breaking Capacity (kA): Icu: 15 Ics: 7.5

Adiabatic Check: CPD Energy Let-through (A²s): 1,700.00 Adiabatic Limit k²S² (A²s): 327.18 x 103

Project: D:\My Documents\ALAOJI\SERVICE BLDGS\CentralControlBldg\CCB-DBP.p17 Page 37 of 39 Printed on: 11/12/2008


Created using: 15.0.0(BS7671:2008) - Rockson Engineering Ltd Copyright © AMTECH Power Software Ltd 2008
Cable Calculation Report

Project Reference: CCB - ALAOJI 504MW PP Job Number: RK-117-E-2020-2029


Document No: CCB-DBP-001 Created On : 08/10/2008 Rev Date :
Created By : ARNEL CORPUZ Modified By: Rev No:

Calculated in accordance with BS7671

Cable CKT P224


Connection From: DB-P2/8/L3 To: P224
Active Source: Source-1
Load Type: Lighting, radial circuits Design Current Ib (A): 9.7
Length to First Fitting (m): 46.00
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: MEM Memshield 2 MCB Type C (MCV) 15kA Th/Mag
Rating In (A): 16 [f] Overload Setting Ir (A): 16 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 1 x 2 x 1c Size (mm2 ): 2.5 [f]
Neutral: 2.5 mm²[a] Length (m): 64
1 - In conduit in a thermally insulated wall Conduit: Plastic

Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]

3rd Harmonics (%) = 0.00 Ch = 1.00


CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 11.5 V (User defined)
Design Current Ib = 9.7
Device Rating In = 16 Overload Setting Ir = 16 [Ir >
_ Ib]
Min. Cable Capacity Iz = 16.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 26.0 _ Iz]
[It >

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 0.0 / 0.00 9.7 / 1.00 9.7
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 0.00 / 0.00 8.46 / 3.68 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 0.00 / 0.00 10.24 / 4.45 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 4 [a] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.27309 0.60800 0.38400 1.26474 1.39394 Current (kA)

Disconnection time (s): From characteristic: 0.20 Maximum for circuit: 0.40
0.18
Adiabatic check (mm 2 ) CPC Section = Separate 4 Total = 4.0 Min. Section = 0.57

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 9.542 / 5.106 Load End: 0.237 / 0.183
Protective Device Breaking Capacity (kA): Icu: 15 Ics: 7.5

Adiabatic Check: Max. disconnection time (s) = (k²S²/I²): 3.82 Actual disconnection time (s) = 0.19

Project: D:\My Documents\ALAOJI\SERVICE BLDGS\CentralControlBldg\CCB-DBP.p17 Page 38 of 39 Printed on: 11/12/2008


Created using: 15.0.0(BS7671:2008) - Rockson Engineering Ltd Copyright © AMTECH Power Software Ltd 2008
Cable Calculation Report

Project Reference: CCB - ALAOJI 504MW PP Job Number: RK-117-E-2020-2029


Document No: CCB-DBP-001 Created On : 08/10/2008 Rev Date :
Created By : ARNEL CORPUZ Modified By: Rev No:

Calculated in accordance with BS7671

Cable CKTP105
Connection From: DB-P1/1/L3 To: P105
Active Source: Source-1
Load Type: Sockets BS 1363, 32A ring final circuit to sockets up to 100m² Design Current Ib (A): 6.1

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: MEM Memshield 2 MCB Type C (MCH) Th/Mag
Rating In (A): 32 [f] Overload Setting Ir (A): 32 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 2 x 2 x 1c Size (mm2 ): 4 [f]
Neutral: 4 mm²[a] Length (m): 46
1 - In conduit in a thermally insulated wall Conduit: Plastic

Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]

3rd Harmonics (%) = 0.00 Ch = 1.00


CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 11.5 V (to BS 7671:2008 Appendix 12)
Design Current Ib = 6.1
Device Rating In = 32 Overload Setting Ir = 32 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 35.0 _ Iz]
[It >

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 0.0 / 0.00 6.1 / 1.00 6.1
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 0.00 / 0.00 0.69 / 0.30 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 0.00 / 0.00 3.21 / 1.40 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 1.5 [a] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.36294 0.06900 0.17825 0.61008 0.71875 Current (kA)

Disconnection time (s): From characteristic: 0.06 Maximum for circuit: 0.40
0.38
Adiabatic check (mm 2 ) CPC Section = Separate 1.5 Total = 1.5 Min. Section = 0.31

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 5.206 / 2.240 Load End: 1.529 / 0.958
Protective Device Breaking Capacity (kA): Icu: 10 Ics: 10

Adiabatic Check: CPD Energy Let-through (A²s): 3,876.76 Adiabatic Limit k²S² (A²s): 327.18 x 103

Project: D:\My Documents\ALAOJI\SERVICE BLDGS\CentralControlBldg\CCB-DBP.p17 Page 39 of 39 Printed on: 11/12/2008