Type MVAA
Auxiliary Relays
The type MVAA is a low burden auxiliary relay which can be used where a scheme demands several contacts for event recording, alarm initiation, contact logic arrangements, etc. The relay can be supplied fitted with normal duty contacts and/or with heavy duty blow-out contacts. MVAA relays are voltage operated attracted armature units of compact design with a positive action and a high degree of mechanical stability. Voltage is applied to the relay coils via an internal diode bridge which enables relays to be energized from ac or dc power supplies. Typical applications are for general contact multiplication, interlocking, and customizing the protection scheme to suit the substation.
MODELS AVAILABLE
There are five versions of the MVAA relay, each with a different type of contact reset mechanism.
> MVAA 11
Single element relay with self reset contacts. Two element version is type MVAA 21. MVAA12 Single element relay with a combination of self and hand reset contacts. Two element version is type MVAA 22. MVAA 13 Single element relay with hand reset contacts. Two element version is type MVAA 23 MVAA 14 Single element relay with electrical reset contacts. MVAA 15 Single element relay with hand and electrical reset contacts. The contacts can be reset either electrically or by hand.
>
>
> Customer Benefits Compact design Mechanically stable Hand, self and electrically reset versions available Wide voltage range Optional operation indicator >
T&D
CONTACTS
Normal duty make, break and changeover contacts and heavy duty magnetic blow-out contacts are available in various combinations. See tables 1, 2 and 3. Heavy duty magnetic blow-out contacts are recommended for breaking heavy or highly inductive dc loads. When these are fitted, the number of contacts available may be reduced. See table 3.
OPERATING TIMES The operating times are typically 12-25ms depending on the number of contacts and relay type.
CONTACTS COMBINATIONS
Relay type Contact combination code letter (cross reference to detailed contact combinations in Table 3) Case sizes
MVAA11 Breaking capacity curves for these contacts are shown in Figure 1. MVAA12 MVAA13* MVAA14* MVAA15*
OPERATION INDICATORS
Each relay element is supplied with an optional hand reset operation indicator. The indicator consists of a mask which on operation drops to expose a broad red strip positioned diagonally on a rectangular white background.
Q R S Q R Q R Q R
2 4 2 2 4 2 4 2 4
Table 1
Available contact combinations & case sizes for single element relays
Contact combination code letter (cross Case sizes
TECHNICAL DATA
RATINGS Standard coil ratings: 24/27V, 30/34V, 48/54V, 110/125V, 220/250V, ac or dc
Relay type
MVAA21 OPERATIVE RANGES Voltage rating (V) 24/27 30/34 48/54 110/125 220/250 Operating voltage range (V) 19.2 - 32.4 24.0 - 40.8 38.4 - 64.8 88.0 - 150.0 176.0 - 300.0 MVAA22 MVAA23* Table 2
P Q S Q
P Q S Q
2 4 4 4
Available contact combinations & case sizes for dual element relays
FREQUENCY
50/60Hz
WITHSTAND RATING The relay will withstand 120% of its maximum voltage rating continuously.
* Note. When the relays are required to cut-off their own supply voltage following operation, a special late acting contact must be used. This contact can be fitted on request and will be wired internally. The number of available output contacts shown in table 3 reduces by one when a cut-off contact is supplied.
2>3
Normal duty in any combination of make (M) or break (B) 4 6 3 1 8 4 2 6 (2-HR and 4-SR or 2-SR and 4-HR)
P Q
4 6 -
Contact type
Current
Make and carry continuously 1250VA with maxima of 5A and 300V 1250W with maxima of 5A and 300V 1250W with maxima of 5A and 300V
Make and carry for 3 seconds 7500VA with maxima of 30A and 300V 7500W with maxima of 30A and 300V 7500W with maxima of 30A and 300V
Break
Heavy duty
DC
1250VA with maxima of 5A and 300V 100W (resistive) 50W (inductive) with maxima of 5A and 300V See curves, Figure 1
100
w 00 10 0w 50 w 00 25 w 00 50
DURABILITY
0w 25
Loaded contact 10,000 operations minimum Unloaded contact 100,000 operations minimum
10
0w 10 w 50 w 25
RESISTIVE 1.0
45
4 holes 4.4
13 24
168
159
159
177
157 max.
32
212
25 min.
Reset
51
Flush mounting
All dimensions in mm
177
157 max.
Figure 2
Figure 3
CASES
Relays are supplied in size 2 or size 4 cases as indicated in the Technical Data section. See Figures 2 and 3 for outline dimensions.
NORTH AMERICA Tel.: +1 (610) 997 5100 / +1 (450) 923 7084 CENTRAL AMERICA Tel.: +52 (55) 1101 1038 SOUTH AMERICA Tel.: +55 (0) 11 3491 7240 BRITISH ISLES Tel.: +44 (0) 1785 77 24 06 FRANCE Tel.: +33 (0)4 67 20 55 76 MEDITERRANEAN & AFRICA Tel.: +33 (0) 4 67 20 55 41 SOUTH EAST AFRICA Tel.: +27 (011) 820 5037 NORTHERN & CENTRAL EUROPE Tel.: +49 69 6632 3333 NEAR & MIDDLE EST Tel.: +971 6 556 0559 INDIA Tel: +91 44 2264 0888 NORTH EAST & SOUTH EAST ASIA Tel.: +65 6843 3133 CHINA Tel.: +86 21 58 12 8822 PACIFIC Tel.: +61 (2) 96 45 07 33
AREVA Track Record Auxiliary Relays >> Over 180,000 MVAJ tripping relays delivered since launching in 1983 >> Over 150,000 MVAA auxiliary relays delivered since launching in 1983. >> Over 330,000 PRiMA auxiliaries delivered since launching in 1994 >> Underlines AREVA's commitment to the supply of quality electromechanical devices
AREVA is a worldwide expert in the energy field, with a strong industrial presence in over 40 countries. The group provides its clients with technological solutions for nuclear energy production and electricity transmission and distribution. AREVA also offers interconnect systems, principally in the telecommunications, computer and automotive markets. The 70,000 AREVA employees are thus committed to the major challenges of the 21st century: access to energy for everyone, preservation of the planet and responsibility toward future generations. T&D Worldwide Contact Centre Available 24h a day: +44 (0) 1785 25 00 70 contact.centre@areva-td.com http://www.areva-td.com/contactcentre/
Our policy is one of continuous development. Accordingly the design of our products may change at any time. Whilst every effort is made to produce up to date literature, this brochure should only be regarded as a guide and is intended for information purposes only. Its contents do not constitute an offer for sale or advise on the application of any product referred to in it. We cannot be held responsible for any reliance on any decisions taken on its contents without specific advice.
www.areva-td.com