Harmonic Misconceptions

Conrad St. Pierre - Electric Power Consultants, LLC There have been many harmonic articles in trade magazines and the problems that can occur because of them. Due to limited space and the technical level of the readers, many simplifying generalizations are made. These generalizations become the rule, because they are repeated articles after an article, without explanation or technical detail. These rules can be misapplied and point to harmonics as the culprit when they are not. The following are samples of these rules, which are true for some conditions but not true for all conditions. The reason for some of these rules will be explained. The maximum amount of a harmonic current from a three-phase drive is 1/(harmonic order). That is, the maximum 5th harmonic is 1/5 or 20% of the fundamental. This is a theoretical rule that applies for the following particular set of conditions. 1. The drive is a properly operating 6-pulse full-wave bridge drive operating at full-load with a step wave output. The 12-pulse rectifier bridge drive will have greatly reduced harmonics. The DC bus voltage or current is constant. - meaning it has sufficient inductance or capacitance. The source impedance is low.

2. 3.

A good exception to this rule is a PWM (pulse width modulated) drive witha constant magnitude varying pulse width output. These drives can have the 5th harmonic current up to 80% of the fundamental current with a low series or internal reactance. The 5th harmonic current decreases to approximately 22% with a higher series or internal impedance. The percent harmonic current also dependents upon the impedance being on the input ac or dc portion of the converter. Figure 1 shows the change in harmonics on a PWM drive when external impedance is added.
100.0

Percent Fundamental Current

80.0

5th
60.0

7th 11th 13th 17th

40.0

20.0

19th
0.0

0.1

10

Percent Impedance (Source plus Reactor or Transformer)

Fig. 1 - PWM Drive Harmonic Content

ELECTRIC POWER CONSULTANTS , LLC - 1821 Curry Road ! Schenectady, NY

12306 ! Ph 518-356-9665

Triplex harmonics do not flow through a wye-delta transformers. The fact is that triplex harmonic currents can flow through and do flow through wye-delta transformers. The amount that flows depends on the phase angle and magnitude of the currents in each of the three phases. For example, 100% of the third harmonic current would pass through the transformer if they were equal in magnitude and displaced 120o from each other. This flow of current would be just like a balanced three-phase 60 Hertz current as shown in Fig 2. On the other extreme, if the third harmonic current produced is in phase with the third harmonic currents in the other two phases, the third harmonic current will add in the neutral of a wye connected transformer. Most of third harmonic currents in a 60-Hz system are the latter. The third harmonic current in the wye legs of a transformer will circulate in the delta winding to balance the amp-turns. Figure 3 shows this condition. This misconception is caused by the generalization that all third harmonics behave similarly to fundamental frequency zero-sequence currents. A 60-Hertz three-phase system can have positive, negative and zero sequence currents when the phases are not balanced. Likewise, the third harmonic currents can have positive, negative and zero sequence currents. When the third harmonic current in each phase is balanced and displaced by 120o, the current is positive sequence. When the third harmonic currents are balanced and inphase with each other, the current is zero sequence. In most three phase systems the third harmonic current produced are closer to being in-phase, but with a slight unbalanced in magnitude and phase angle. Therefore, most of the third harmonic current will flow in the transformer neutral and the remainder through the transformer.

1.0

1.0

0.0

0.0

-1.0

TIME

-1.0

TIME

1.0

1.0

0.0

0.0

-1.0

-1.0

TIME

TIME

1.0

1.0

0.0 1.0

0.0

-1.0

-1.0

TIME

0.0

TIME

-1.0

TIME

Fig. 2 - Out-of-Phase Third Harmonic Current Flow


(Displaced by 120 degrees)

ELECTRIC POWER CONSULTANTS , LLC - 1821 Curry Road ! Schenectady, NY

12306 ! Ph 518-356-9665

1.0

1.0

0.0

0.0

-1.0

TIME

-1.0 TIME

1.0

1.0

0.0

0.0

-1.0

-1.0

TIME

TIME

1.0

1.0

0.0

1.0

0.0

-1.0

TIME

0.0

-1.0

TIME

-1.0

TIME

Fig. 3 - In-of-Phase Third Harmonic Current Flow


(Displaced by 0 degrees)

Harmonic currents can cause an induction motor to run backwards. Besides running backwards, it is commonly said that motors will overheat due to the additional horsepower required to overcome the harmonic "torque fight. - a term used to describe the backward torque on the motor. This misconception comes from the fact that the 5th harmonic currents have negative sequence characteristics. By using the simple equivalent circuit for an induction motor shown in Figure 4, the torque due to a 5th and 7th harmonic voltage can easily be quantified.
S

XS

R S = 0.003 PU X S = 0.08 PU RM XM R R R = 0.01 PU X R = 0.08 PU R M = 20 XM = 5 SLIP = 0.01 PU

SLIP

Fig. 4 - Induction Motor Equivalent Circuit

Figure 5 shows the per unit torque for an induction motor subject to 10%, 5th and 8.5%, 7th harmonic voltages caused by adjacent SCR controlled drives. The harmonic voltage will result in 12% 5th and 6% 7th harmonic current in the motor based on rated current or the total rms current being 101% of rated. The ELECTRIC POWER CONSULTANTS , LLC - 1821 Curry Road ! Schenectady, NY

12306 ! Ph 518-356-9665

negative torque of the 5th harmonic at approximately rated speed is approximately 0.003% of the fundamental torque, (Trq . I2*RR/s = 0.122*0.01/6 = 0.00003). Also, the 0.00001% forward torque produced by the 7th harmonic will cancel a potion of the backward torque produced by the 5th harmonic voltage. Clearly, the motor with this very low negative torque will not run backwards. The additional fundamental current required to supply the "torque fight" phenomenon is insignificant, but the increase in eddy currents and hysteresis losses within the motor due to harmonics are not. Many IEEE papers have quantitatively addressed this temperature rise and they appear to indicate a greater possibility of motor overheating due to unbalanced voltage rather than from harmonics currents.
4.0

Per Unit Torque

3.0 2.0

Fundamental Torque

7th Harmonic Torque 1.0 0.0 -1.0

-6

-5

-4

-3

-2

-1

Per Unit Speed (Base 60 Hz)


5th Harmonic Torque -2.0 -3.0 -4.0

Fig. 5 - Induction Motor Torque

Harmonic filters are always required when VSD (Variable Speed Drives) are used. Several factors should be considered before a harmonic filter is installed. If the amount of drives is small (<15%) compared to the system loading, it is likely that a filter will not needed to help control harmonics. Generally, as the ratio of the short circuit kVA to drive kVA increases, the need for harmonic filters decreases further. Bus loads and drives at a low load may require capacitors for an improved power factor at the utility metering point to avoid demand or power factor penalties. The location of the capacitors compared to the location of the drives is important. Increasing the impedance between them, reduces the possibility of adverse resonance due to the drives. Therefore, impedance between the capacitor and drive reduces the need for harmonic filters. Not all resonance conditions caused by the addition of capacitors are problems. If the system resonance is at a harmonic not produced by drive, then filters may not be required.

ELECTRIC POWER CONSULTANTS , LLC - 1821 Curry Road ! Schenectady, NY

12306 ! Ph 518-356-9665

Harmonic filters trap harmonics. A properly designed filter presents a low impedance current path at its design frequency. For example, when 5th harmonic currents are present on the same bus with a 5th harmonic filter, the amount of 5th harmonic current in the filter is inversely proportion to all connecting impedances. Since a 5th harmonic filter is designed to have low impedance near the 5th harmonic, most the 5th harmonic currents will flow in the filter. Other harmonic currents can also flow in a 5th harmonic filter. Since the filter impedance at the other harmonics is higher, a smaller portion of the non-5th harmonic currents also flow in the 5th harmonic filter. The filter does not trap harmonics, but it provides a low impedance return path for the harmonic current to flow. The closer the filter is tuned to the source of the harmonics, the less disruptive the harmonics will be. Harmonics must follow Kirchhoff's voltage and current laws and are not trapped and disappear in free space.

A harmonic load must meet harmonic standard IEEE-519. IEEE Standard 519, "IEEE Recommended Practices and Requirements for Harmonic Control in Electrical Power System" pertains only to the point of common coupling (PCC), generally the utility metering point. The only place where IEEE-519 is required to be met is at the PCC. The standard does not provide guidelines for harmonic distortion within the user facilities. What the standard does, is to provide an acceptable level of harmonic distortion at the PCC. The user and utility share in this responsibility. The utility must supply a relatively clean voltage to the user and the user must limit the amount of harmonic current flowing from their loads back into the utility. Individual drives or loads do not need to meet IEEE-519. In addition, IEEE-519 voltage distortion limits do not apply within the users' facility. However, the user can specify harmonic current and voltage distortion limits of equipment specified from manufactures. For equipment manufactures to meet a specified criteria, the following information has to be provided to the manufacture. a. b. c. d. e. Single-line diagrams, the operating conditions, the location of any capacitors, the bus short-circuit impedance Other drives and harmonic load information.

The neutral current in a 3 phase, 4 wire system is limited to 173% third harmonic. Because of the mix of loads in a facility this "rule" is generally true. Lets take an extreme example of 15 kVA 480/208-120 volt transformer serving personal computers that have a measured current wave shape and harmonic content as shown in Fig. 6. In addition, lets assume each phase has 5 kVA (41.6 A) of load connected line to neutral and the third harmonic in-phase with each other. Of the total load, the fundamental current in Fig. 6 is 1.03/1.57 = 0.656 (27.3A) of the total current, the third 0.8615 times the fundamental or 23.5A. Because the third harmonics are in-phase with each other, the neutral will carry three times the phase third harmonic current or 70.5 A. This is 258% (100*70.5/27.3) of the fundamental and 169% (100*70.5/41.6) of the total phase current. As with any percentage, the reference base needs to be provided.

ELECTRIC POWER CONSULTANTS , LLC - 1821 Curry Road ! Schenectady, NY

12306 ! Ph 518-356-9665

Harmonic 1 3 5 7 9 11 13 15 17 19

Percent Fundamental Current 100.00 86.15 63.76 38.12 15.82 3.47 6.73 6.85 3.97 2.48 1.57A 1.03A

RMS Fundamental

Fig. 6 - Personal Computer Current Wave Shape

Pulsed Width Modulation (PWM) drives produce no harmonics problems. All equipment that uses electronic control power circuits will produce harmonics when connected to an ac power system. PWM drives are no exception. By themselves, they generally produce more harmonics than other types of drives. As stated above, they can produce high percentage of harmonic currents. While the percentage of harmonic current at light loads can be higher at full load, the current is small and therefore the actual harmonic amps are also small. To help reduce the amount of harmonic current some manufactures add isolation transformers or series ac or dc reactors to the drives. The added impedance causes a greater voltage drop to the motor and to compensate for it the drive controller has to conduct for a longer period which lowers the harmonic content. Total harmonic current distortion remains above 20%. Figure 7 is current waveform and harmonic content of a PWM drive with and without the added impedance. While a small single drive may not cause a problem, a large number PWM drives can. Isolation transformers stop harmonics. Placing an isolation transformer in series with a drive does not stop harmonics. If the drives produce harmonic currents that have the characteristics of positive and negative currents, Kirchhoff's law says they have to flow through the transformer and they do. By the careful selection of delta-wye and delta-delta isolation transformers, the total amount of harmonic currents in a system can be reduced. Having an equal kVA mix of delta-wye and delta-delta transformers can provide some of the benefits of a 12 pulse system. The 5th and 7th harmonic currents will partially be reduced by cancellation. The triplex harmonics will be reduced because they will generally circulate the transformer delta winding and in the transformer wye-connected neutral back to the drive. On PWM type drives, a reactor can be used in place of the delta-delta transformer to help lower harmonics. Cost determines the selection of a reactor or ELECTRIC POWER CONSULTANTS , LLC - 1821 Curry Road ! Schenectady, NY
12306 ! Ph 518-356-9665

isolation transformer. One benefit of the isolation transformers or source side reactors is the reduction of commutation notches. If commutation notches are not a problem, then the delta-delta or series reactors are not needed at all. On non-PWM drives, the same benefits of cancellation can be obtained by having half the drive kVA directly connected to the system and the other half on delta-wye isolation transformers. The above discussions presented several reasons why some harmonic 'truths' exist. Usually they are generally true but there are exceptions.

Fig. 7 - Full Load Current in PWM Drive

Myth1.wpd

ELECTRIC POWER CONSULTANTS , LLC - 1821 Curry Road ! Schenectady, NY

12306 ! Ph 518-356-9665