Вы находитесь на странице: 1из 54

Variable Frequency Drives

Family Overview................................................................................................................................................4 S500E Series ....................................................................................................................................................5 E500 Series........................................................................................................................................................9 E700 Series......................................................................................................................................................13 F700 Series ......................................................................................................................................................19 A700 Series......................................................................................................................................................29 V500 Series......................................................................................................................................................40 Packaged Drives ............................................................................................................................................44 General Options ..............................................................................................................................................48

Stock Product: Stock product is product MEAU makes every effort to have on hand for immediate shipment. There may be instances when we are out of stock due to unexpected large requirements. All stock product will be indicated in this book by an S in the Stocked Item columns/rows. Non-Stock Product: Non-stock product is product supplied on an as-needed basis. Standard lead times of 12 16 weeks apply, product is non-returnable and non-cancelable. Product listed as non-stock may change to stock product subject to increases in sales and usage. All non-stock product will be indicated in this book by a dash in the Stocked Item columns/rows.

Mitsubishi Electric Automation

Variable Frequency Drives 3

VARIABLE FREQUENCY DRIVES

Variable Frequency Drives Family


Model Series Page Voltage Range (VAC) HP Range Constant Torque Variable Torque Open-Loop Flux Vector Real Sensorless Vector Control Algorithm Closed-Loop Vector Closed-Loop Speed Closed-Loop Torque Open-Loop Torque Closed-Loop Position Modbus RTU CC-Link DeviceNet Profibus-DP Modbus Plus Communication LonWorks SSCNETIII Metasys N2 Siemens FLN Ethernet I/P Modbus TCP I/P BacNET TP ControlNET Max Output Freq. Analog Inputs Analog Outputs Digital Inputs Digital Outputs Specifications Pulse Train Input Brake Transistor Brake Resistor DC Link Reactor EMC Filter Operator Interface Remote Mount Keypad Alarm History Option Option LED included FR-PU04 (LCD/Copy) Last 4 Option Option Option LED FR-PA02-02 FR-PU07 (LCD/Copy) or FR-PU04 (LCD) Last 4 Last 8 Option Option LED included All 1/2 HP 20 HP 120Hz 1: 0-5/10Vdc or 4-20mA 1: 0-5Vdc 5 (4 assignable) 1 transistor type (assignable) & 1 form C (assignable) 400Hz 400Hz 400Hz Option Option Option Option Option Option Option Option Option Option Option Option Option Option Option Option Option Option Option Option Option Option Option Option Option Option Option Option Option Option 400Hz 3: 0-5/10Vdc or 4-20mA 2: 0-10Vdc and 4-20mA 2: 0-10Vdc and FM Special Option Option Option Standard Option Option Option Standard Option Option Option Standard Standard 115 1/8 1 S500E 5 240 1/8 5 480 1/2 5 115 1/8 1 E500 9 600 1 10 240 1/8 20 E700 13 480 1/2 20 3/4 125 3/4 700 240 F700 19 480 A700 3/4 700 1 200 A700 29 480 1/4 700 1 800 Standard Standard Standard Standard Standard Standard Standard Standard Option Option Option Option 600 1 400 2 550

1: 0-5/10Vdc or 4-20mA 1: 0-5/10Vdc or 4-20mA 1: 0-5/10Vdc(600V) 1: FM (pulse train) (100V) 7 (4 assignable) 1: 0-10Vdc 7 (assignable)

12 (assignable) 5 transistor type (assignable) and 2 form C (assignable) Standard Up to 30 HP Up to 10 HP Option (Standard 100Hp and above) Standard Standard Up to 5 HP

2 transistor type 2 transistor type (assignable) & 1 form C (assignable) & 1 form C (assignable) (assignable)

FR-DU07 removeable (LED/Copy) FR-PU07 (LCD/Copy) or FR-PU04 (LCD) Last 8 Last 8

Standard Features: 1. RS-485 serial communications (Mitsubishi VFD protocol) 2. PID or PI control 3. Adjustable carrier frequency (Low Noise) upto 14.5KHz 4. Soft PWM 5. Packaged options available 6. Setup Software available 7. Line regenerative braking is available for using the FR-CV option 8. User selectable Sink (default) / Source I/O

S500E Series
Low Cost Sub-Micro VFD with Mitsubishi Electric Quality.
I I I I I I I I I I I I I

Simple to Use: The S500E is perfect for a wide range of applications Simple to Set Up: The digital setting dial with integrated display makes S500E configuration fast and easy Simple Operation: Control the S500E remotely or with built-in digital control Simple to Choose: Low cost and Mitsubishi Electric quality ensure solid solutions Capable of generating 150% torque at 5Hz 150% overload for 1 minute 14.5 kHz carrier frequency DIN Rail Mounting (option) 50C (122F ambient rating) Programmable I/O Adjustable torque boost DC Injection braking Fault history Stores last 4 alarms Can display operation frequency at occurence of last alarm

Voltage 115 208/230 460 1/8 1 Hp 1/8 5 Hp 1/2 5 Hp

FR-S520E 0.1 K NA
Symbol S510WE S520E S540E Voltage Class Single-phase 100V class Three-phase 200V class Three-phase 400V class Inverter capacity kW

Horsepower

S500E Series
Rating (CT & VT) Hp Output Current (Amps) IP20 Open Chassis Model Number Height mm (in) Dimensions Width mm (in) Depth mm (in) Weight kg (lb) Stocked Item

1-Phase 100 115VAC Input / 3-Phase 230VAC Output 1/8 1/4 1/2 1 0.8 1.4 2.5 4.1 FR-S510WE-0.1K-NA FR-S510WE-0.2K-NA FR-S510WE-0.4K-NA FR-S510WE-0.75K-NA 128 (5.04) 128 (5.04) 128 (5.04) 128 (5.04) 68 (2.68) 68 (2.68) 68 (2.68) 108 (4.25) 80.5 (3.17) 110.5 (4.35) 142.5 (5.61) 149.5 (5.89) 0.5 (1.1) 0.5 (1.1) 0.9 (2) 1.5 (3.3) S S S S

200 240VAC Input / 3-Phase Output 3-Phase Hp 1/8 1/4 1/2 1 2 3 5 Amp 0.8 1.4 2.5 4.1 7 10 16.5 Hp 1/20 1/8 1/4 1/2 3/4 1.0 2.0 1-Phase Amp 0.4 0.8 1.5 2.5 4 5 7 FR-S520E-0.1K-NA FR-S520E-0.2K-NA FR-S520E-0.4K-NA FR-S520E-0.75K-NA FR-S520E-1.5K-NA FR-S520E-2.2K-NA FR-S520E-3.7K-NA 128 (5.04) 128 (5.04) 128 (5.04) 128 (5.04) 128 (5.04) 128 (5.04) 128 (5.04) 68 (2.68) 68 (2.68) 68 (2.68) 68 (2.68) 108 (4.25) 108 (4.25) 170 (6.69) 80.5 (3.17) 80.5 (3.17) 112.5 (4.43) 132.5 (5.22) 135.5 (5.33) 135.5 (5.33) 142.5 (5.61) 0.5 (1.1) 0.5 (1.1) 0.8 (1.8) 0.9 (2) 1.5 (3.3) 1.5 (3.3) 2.1 (4.6) S S S S S S S

380 480VAC Input / Output 1/2 1 2 3 5 1.1 2.1 3.5 4.8 7.7 FR-S540E-0.4K-NA FR-S540E-0.75K-NA FR-S540E-1.5K-NA FR-S540E-2.2K-NA FR-S540E-3.7K-NA 128 (5.04) 128 (5.04) 128 (5.04) 128 (5.04) 128 (5.04) 108 (4.25) 108 (4.25) 108 (4.25) 108 (4.25) 108 (4.25) 129.5 (5.10) 129.5 (5.10) 135.5 (5.33) 155.5 (6.12) 165.5 (6.52) 1.5 (3.3) 1.5 (3.3) 1.5 (3.3) 1.6 (3.5) 1.7 (3.7) S S S S S

Mitsubishi Electric Automation

Variable Frequency Drives 5

VARIABLE FREQUENCY DRIVES

S500E General Specifications


Control System Output Frequency Range Frequency Setting Resolution Output Frequency Accuracy Analog Input Digital Input (Using Keypad) Analog Input Digital Input (Using Keypad) Algorithm Options V/F control Soft-PWM; Adjustable carrier frequency (2kHz -14.5kHz) 0.2 to 120Hz (starting frequency variable between 0 and 60Hz) 5VDC input: 0.2% of selected maximum frequency 10VDC, 4-20mADC input: 0.1% of selected maximum frequency <100Hz: 0.1Hz 100Hz: 1Hz 1% of maximum output frequency (25C 10C (77F 18F)) 0.5% of commanded output frequency Base frequency setting range: 0 - 120Hz Automatic Torque Boost function selectable 150% or more (at 6Hz) when automatic torque boost is selected 0, 0.1 to 999 sec (acceleration and deceleration set independently) Linear or S-pattern curves may be selected 0.1K, 0.2K150%, 0.4K, 0.75K100%, 1.5K50%, 2.2K, 3.7K20% Operation frequency (0 to 120Hz), operation time (0 to 10s), operation voltage (0 to 15%) 0 to 5VDC, 0 to 10VDC, 4 to 20mADC Entered from built-in digital setting dial Forward and reverse rotation, start signal Used to reset alarm output after alarm condition Up to 15 speeds can be defined Used to select second functions (acceleration time, deceleration time, torque boost, base frequency, electronic overcurrent protection) Instantaneous shut-off of inverter output (frequency, voltage) Used to select input of frequency setting signal 4 to 20mADC (terminal 4) Used to provide interface to external thermal relay Used to remotely switch the VFD between operation via the digital setting dial and external operation Control input holding circuit for 3-wire control applications Maximum/ minimum frequency setting, frequency jump operation, external thermal relay input selection, automatic restart operation after instantaneous power failure, forward/reverse rotation prevention, slip compensation, operation mode selection, PID control Running, up to frequency, frequency detection, overload alarm, zero current detection, output current detection, PID upper limit, PID lower limit, PID forward/reverse rotation, operation ready, minor fault and alarm, and 1 contact output (230VAC 0.3A, 30VDC 0.3A) can be selected Output Frequency or Motor Current selection Operating Status Alarm Definition Output voltage, output current, set frequency, running Alarm definition is displayed when protective function is activated. 4 alarm definitions are stored Power application (POWER), Alarm (ALARM) Overcurrent shut-off (during acceleration, deceleration, constant speed), regenerative overvoltage shut-off, undervoltage (*1), instantaneous power failure (*1), overload shut-off (electronic overcurrent protection), stall prevention, fin overheat, fan failure (*4), parameter error, PU disconnection, starting ground fault overcurrent protection -10C to +50C, 14F to 122F (non-freezing) 90%RH or less (non-condensing) -20C to +65C / -4F to 149F Indoors, no corrosive and flammable gases, oil mist, dust and dirt. Maximum 1000m (3280.80 ft.) above sea level for standard operation. After that derate by 3% for every extra 500m (1640.40 feet) up to 2500m (8202.00 feet) (91%)

Voltage/Frequency Characteristic Torque Boost Starting Torque Acceleration/ Deceleration Time Setting

Control Specifications

Braking Torque (*3) Freq. Setting Signal

Regenerative DC Braking Analog Input Digital Input

Input Signals

Start Signal Alarm Reset Multi-Speed Selection Second Function Selection Output Stop Current Input Selection Thermal Relay Input Digital OperationExternal Operation Switching 3-Wire Control Input

Operation Functions

One (1) Open-Collector and One (1) Form C Contact Outputs (User Definable)

One (1) Analog Outputs (0 to 5VDC, 1mA)

Display

Control Panel Display LED Display

Protective / Alarm Functions Ambient Temperature Ambient Humidity Storage Temperature (*2) Atmosphere Altitude, Vibration

Notes: 1. When undervoltage or instantaneous power failure has occurred, alarm display or alarm output is not provided but the inverter itself is protected. Overcurrent, regenerative overvoltage or other protection may be activated at power restoration according to the operating status (load size, etc.). 2. Temperature applicable for a short period in transit, etc. 3. The braking torque indicated is a short-duration average torque (which varies with motor loss) when the motor alone is decelerated from 60HZ in the shortest time and is not a continuous regenerative torque. When the motor is decelerated from the frequency higher than the base frequency, the average deceleration torque will reduce. 4. Provided only for forced-air models FR-S520E-1.5K-NA, FR-S520E-2.2K-NA and FR-S520E-3.7K-NA.

Environment

Output Signals

Use Pr. 180 to Pr. 183 for selection.

S500E Series Terminal Connection Diagram

Three-Phase 200V Power Input/Output Three-Phase 400V Power Input/Output

Notes: 1. The N/- terminal is not provided for the FR-S520E-0.1K to 0.75K-NA. 2. The PR terminal is provided for the FR-S520E-0.4K to 3.7K-NA. (not used) 3. You can switch the position of sink and source logic. 4. When the setting potentiometer is used frequently, use a 2W1k potentiometer.

5. The terminal functions change with input terminal function selection (Pr. 60 to Pr. 63). (RES, RL, RM, RH, RT, AU, STOP, MRS, OH, REX, JOG, X14, X16, (STR) signal selection) 6. The terminal function changes according to the setting of output terminal function selection (Pr. 64, Pr. 65). (RUN, SU, OL, FU, RY, Y12, Y13, FDN, FUP, RL, Y93, Y95, LF, ABC signal selection)

Single-phase 100V power input / three-phase 200V power output

Terminal Block Layout

Mitsubishi Electric Automation

Variable Frequency Drives 7

VARIABLE FREQUENCY DRIVES

S500E Series Options


Options and Accessories Model Number FR-E5T FR-E5T-14 IB(NA)0600027 FR-PU04 FR-CB201 FR-CB203 FR-CB205 FR-CONFIGURATOR SC-FRPC Description Mounting Adapter Mounting Adapter S500 Detailed Instruc. Manual Parameter Unit Remote Cable Remote Cable Remote Cable Programming and Diagnostic Software Serial Communications Cable Notes Allows mounting 2.2 & 3.75K S520E VFD in A024 hole pattern Allows mounting 1.5K, 2.2K & 3.7K S540E VFD in A044 hole pattern Download from www.meau.com Use with remote cable 1m cable 3m cable 5m cable Stocked Item S S S S S S

Input Radio Noise Filter


This filter is connected to the input of the drive and helps to reduce radiated noise in the radio frequencies.
Drive Voltage 208 230 460 Kit Model Number FR-BIF FR-BIF-H Leakage Current (mA) 4 4 Dimensions mm (in) L 58 (2.3) 58 (2.3) W 44 (1.8) 44 (1.8) D 42 (1.7) 42 (1.7) Stocked Item S

DIN Rail Mounting Attachment


This attachment allows the S500E Series inverter to mount on a 35mm DIN rail.
Model Number FR-UDA01 FR-UDA02 FR-UDA03 Drive Model S510WE 0.1K 0.4K 0.75K S520E 0.1K 0.75K 1.5K 2.2K 3.7K Stocked Item S S

Installation Interchange Attachment


This attachment allows the S500E Series inverter to be mounted using the installation holes from the previous series VFDs.
Model Number Installation Model S500E Series FR-S520E-0.1K-NA FR-E5T-10 FR-S520E-0.2K-NA FR-S520E-0.4K-NA FR-S520E-0.75K-NA FR-E5T-11 FR-E5T FR-S520E-0.75K-NA FR-S520E-1.5K-NA FR-S520E-2.2K-NA FR-S520E-3.7K-NA FR-S540E-1.5K-NA FR-E5T-14 FR-S540E-2.2K-NA FR-S540E-3.7K-NA FR-A024-0.2K-UL FR-A024-0.4K-UL FR-A024-0.75K-UL FR-A024-1.5K-UL FR-A024-2.2K-UL FR-A024-3.7K-UL FR-A044-1.5K-UL FR-A044-2.2K-UL FR-A044-3.7K-UL A0x4 Series Z024 Series FR-Z024-0.1K-UL FR-Z024-0.2K-UL FR-Z024-0.4K-UL FR-Z024-0.75K-UL FR-Z024-1.5K-UL FR-Z024-2.2K-UL FR-Z024-3.7K-UL Previous Model A200E Series S Stocked Item

S500E Series Watt Loss and Efficiency Data


120VAC 1-Phase Input / 240VAC 3-Phase Output HP-CT 1/8 1/4 1/2 1
Notes at right.

S500E Series Watt Loss and Efficiency Data


240VAC 3-Phase Input / Output HP-CT 1/8 1/4 1/2 1 2 3 5 Model Number FR-S520E-0.1K-NA FR-S520E-0.2K-NA FR-S520E-0.4K-NA FR-S520E-0.75K-NA FR-S520E-1.5K-NA FR-S520E-2.2K-NA FR-S520E-3.7K-NA Rated Watts Watts Loss Efficiency 100 200 400 750 1500 2200 3700 16 20 45 50 85 100 160 84% 90% 89% 93% 94% 95% 96%

Model Number FR-S510WE-0.1K-NA FR-S510WE-0.2K-NA FR-S510WE-0.4K-NA FR-S510WE-0.75K-NA

Rated Watts Watts Loss Efficiency 100 200 400 750 16 20 45 50 84% 90% 89% 93%

S500E Series Watt Loss and Efficiency Data


480VAC 3-Phase Input / Output HP-CT 1/2 1 2 3 5
Notes at right.

Model Number FR-S540E-0.4K-NA FR-S540E-0.75K-NA FR-S540E-1.5K-NA FR-S540E-4.4K-NA FR-S540E-3.7K-NA

Rated Watts Watts Loss Efficiency 400 750 1500 2200 3700 45 50 85 100 160 89% 93% 94% 95% 96%

General Notes: 1. The amount of heat generated by the inverter is based on one inverter connected to one motor of the same capacity. 2. The amount of heat generated in the above table is the amount of heat generated when the inverter is operated at it's rated current. 3. The amount of heat generated will decrease according to the motor load and usage (duty).

S540E EMC Filters


This attachment allows the VFD to be mounted onto the filter.
Model Number FFR-S540-8A-RF100 FFR-S540-13A-RF100 Installation Mode FR-S540E-0.4K 1.5K FR-S540E-2.2K 3.7K Stocked Item

E500 Series
The cost-effective variable speed control solution for general purpose applications.
I I I I I I I I I I I I I I

Up to 1 Hp at 115VAC Up to 10 Hp at 600VAC Advanced Magnetic Flux Vector Control Auto-tuning 50C maximum ambient temperature RS-485 serial communication (standard) Selectable cooling fan operation mode Built-in PID control Adjustable carrier frequency (0.7kHz to 14.5kHz) Optional keypad interface (FR-PA02-02)

Compatible with FR-PU04 user interface UL & cUL listed / CE marked Available configuration software for Windows 95 / 98 Open-network communication options I DeviceNet I CC-Link I Profibus DP (600V only) Brake Transistor

Voltage

FR-E510W 0.1 K NA
Symbol E510W E560 Voltage Class Single-phase 100V class Three-phase 600V class Inverter capacity kW

115 600

1/8 1 Hp 1 10 Hp Horsepower

E500 Selection
Rating (CT & VT) Hp Output Current Amps IP20 Open Chassis Model Number Height mm (in) Width mm (in) Dimensions Depth mm (in) Weight kg (lbs) Stocked Item

1-Phase 100 115VAC Input / 3-Phase 230VAC Output 1/8 1/4 1/2 1.0 1.0 2.0 3.0 5.0 7.5 10.0 0.8 1.5 3.0 5.0 1.7 2.7 4.0 6.1 9.0 12 FR-E510W-0.1K-NA FR-E510W-0.2K-NA FR-E510W-0.4K-NA FR-E510W-0.75K-NA FR-E560-0.75K-NA FR-E560-1.5K-NA FR-E560-2.2K-NA FR-E560-3.7K-NA FR-E560-5.5K-NA FR-E560-7.5K-NA 128 (5.0) 128 (5.0) 128 (5.0) 128 (5.0) 150 (5.9) 150 (5.9) 150 (5.9) 150 (5.9) 150 (5.9) 150 (5.9) 68 (2.7) 68 (2.7) 68 (2.7) 108 (4.3) 140 (5.5) 140 (5.5) 140 (5.5) 220 (8.7) 220 (8.7) 220 (8.7) 76 (3.0) 106 (4.2) 138 (5.5) 155 (6.1) 136 (5.4) 136 (5.4) 136 (5.4) 148 (5.8) 148 (5.8) 148 (5.8) 0.6 (1.4) 0.6 (1.4) 1.0 (2.2) 1.7 (3.8) 1.8 (4.0) 2.0 (4.7) 2.0 (4.7) 3.8 (8.4) 3.8 (8.4) 3.8 (8.4) S S S S S S S S S

3-Phase 575 600VAC Input / Output

Mitsubishi Electric Automation

Variable Frequency Drives 9

VARIABLE FREQUENCY DRIVES

E500 General Specifications


Control Method Output Frequency Range Frequency Control Analog Input Digital Input Analog Input Digital Input Voltage / Frequency Characteristics Starting Torque Torque Boost Acceleration / Deceleration Time Setting Braking Torque Regenerative DC Dynamic Brake Stall Prevention Operation Level Voltage Stall Prevention Operation Level Fast-Response Current Limit Level Frequency Setting Signal Starting Signal Alarm Reset Multi-Speed Selection Second Function Selection Output Stop Current Input Selection Start Signal Automatic Analog Input Digital Input Soft-PWM control / high carrier frequency PWM control can be selected. V / F control or general-purpose magnetic flux vector control can be selected. 0.2 to 400Hz (starting frequency variable between 0 and 60Hz) Across terminals 2-5: 1/500 of maximum set frequency (5VDC input), 1/1000 (10VDC, 4-20mADC input). 0.01Hz (less than 100Hz), 0.1Hz (100Hz or more) when digital setting is made using the control panel. Within 0.5% of maximum output frequency (25C 10C) / 59F to 95F. Within 0.01% of set output frequency when setting is made from control panel. Base frequency set as required between 0 and 400Hz. Constant torque or variable torque pattern can be selected. 150% or more (at 1Hz), 200% or more (at 3Hz) when general-purpose magnetic flux vector control or slip compensation is selected. Manual torque boost, 0 to 30% may be set. 0.01, 0.1 to 3600 sec. (accel. and decel. can be set individually), linear or S-pattern accel./decel. mode can be selected 0.1K, 0.2K...150% or more, 0.4K, 0.75K... 00% or more, 1.5K...50% or more, 2.2K, 3.7K, 5.5K, 7.5K ... 20% or more (*1) Operation frequency (0 to 120Hz), operation time (0 to 10 s), operation voltage (0 to 30%) variable. Operation current level can be set (0 to 200% variable), presence or absence can be selected. Operation level is fixed, presence or absence can be selected. Operation level is fixed, presence or absence can be selected. 0 to 5VDC, 0 to 10VDC, 4 to 20mADC. Entered from control panel (FR-PA02-02). Forward and reverse rotation, start signal automatic self-holding input (3-wire input) can be selected. Used to reset alarm output provided when protective function is activated. Up to 15 speeds can be selected. (Each speed can be set between 0 and 400Hz, running speed can be changed during operation from the control panel.)

Control Specifications

Frequency Precision

Instantaneous shut-off of inverter output (frequency, voltage). Used to select input of frequency setting signal 4 to 20mADC (terminal 4). Used to select start signal automatic self-holding input. (3-wire input) Thermal relay contact input for use when the inverter is stopped by the external thermal relay. Used to switch between PU operation and external operation from outside the inverter. Used to switch between V/F control and general-purpose magnetic flux vector from outside the inverter. Maximum/minimum frequency setting, frequency jump operation, external thermal relay input selection, automatic restart operation after instantaneous power failure, forward/reverse rotation prevention, slip comp., operation mode selection, off-line auto tuning function, PID control, computer link operation (RS-485). 2 open collector output signals can be selected from inverter running, up to frequency, frequency

Input Signals

Self-Holding Selection External Thermal Relay Input PU Operation-External Operation Switching V/F-General-Purpose Magnetic Flux Switching Operation Functions

Output Signals

Operation Status

detection, overload alarm, zero current detection, output current detection, PID upper limit, PID lower limit, PID forward/reverse rotation, operation ready, minor fault and alarm, and 1 contact output (230VAC 0.3A, 30VDC 0.3A) can be selected. 1 signal can be selected from output frequency, motor current and output voltage. Pulse train output (1440 pulses/second/full scale). Operating Status Alarm Definition Output voltage, output current, set frequency, running. Alarm definition is displayed when protective function is activated. 4 alarm definitions are stored. Power application (POWER) Overcurrent shut-off (during acceleration, deceleration, constant speed), regenerative overvoltage shut-off, undervoltage (*2) , instantaneous power failure (*2), overload shut-off (electronic overcurrent protection), brake transistor alarm, output short circuit, stall prevention, brake resistor overheat protection, fan overheat, fan failure (*4), parameter error, PU disconnection, ground fault protection. Constant torque: -10C to +50C (non-freezing) 14F to 122F 90%RH or less (non-condensing) -20C to +65C / -4F to 149F Indoors, no corrosive and flammable gases, oil mist, dust and dirt. Maximum 1000m (3300 ft.) above sea level for standard operation. After that derate by 3% for every extra 500m up to 2500m (91%). 5.9 m/s2 (0.6G max.) based on JIS C 0911.

For Meter

Display

Control Panel Display LED Display

Protective And Warning Functions

Ambient Temperature Ambient Humidity

Environment

Storage Temperature (*3 ) Atmosphere Altitude Vibration

Notes: 1. The braking torque indicated is a short-duration average torque (which varies with motor loss) when the motor alone is decelerated from 60Hz in the shortest time and is not a continuous regenerative torque. When the motor is decelerated from the frequency higher than the base frequency, the average deceleration torque will reduce. Since the inverter does not contain a brake resistor, use the optional brake resistor when regenerative energy is large. (The optional brake resistor cannot be used with 0.1K and 0.2K.) A brake unit (BU) may also be used. 2. When undervoltage or instantaneous power failure has occurred, alarm display or alarm output is not provided but the inverter itself is protected. Overcurrent, regenerative overvoltage or other protection may be activated at power restoration according to the operating status (load size, etc.). 3. Temperature applicable for a short period in transit, etc. 4. Not provided for the FR-E510W-0.1K to 0.75K which are not equipped with a cooling fan.

10

Use Pr. 180 to Pr. 183 for selection.

Used to select second functions (accel. time, decel. time, torque boost, freq., electronic overcurrent protection).

E500 Series Terminal Connection Diagram

Notes: 1. Use 0.5W, 1k potentiometer. For heavier duty applications, use a 2W, 1k potentiometer. 2. 0.1kW and 0.2kW rated models do not contain braking transistor. 3. Terminals SD and SE are electrically isolated. 4. Terminals SD and 5 are not electrically isolated. Do not connect them to each other or to ground. 5. To avoid damage to the VFD, do not allow a short circuit between terminals PC and SD. 6. Sink/Source selectable I/O. Sink type is factory default.

Single-phase 100V power input / three-phase 200V power output

Terminal Block Layout


100V class *AM for the 600V class inverter. 600V class

Mitsubishi Electric Automation

Variable Frequency Drives 11

VARIABLE FREQUENCY DRIVES

E500 Series Options


Model Number FR-PA02-02 FR-E5P FR-DU04 FR-PU04 FR-E5ND FR-E5NP FR-E5NC FR-E5NL FR-CB201 FR-CB203 FR-CB205 IB(NA)66866 SH(NA)3193 IB(NA)0600003 IB(NA)0600006 IB(NA)0600007 IB(NA)0600204 FR-CONFIGURATOR SC-FRPC Description Keypad for E500 VFD Keypad Panel Mounting Adapter LED Parameter Unit LCD Parameter Unit E540, E560 DeviceNet Interface E540, E560 Profibus DP Interface E540, E560 CC-Link Interface E540, E560 LonWorks Interface Remote cable Remote Cable Remote Cable FR-E520/E540/E510W Instruction Manual FR-A500 / E500 Technical Manual FR-E5NC, CC-Link Instruction Manual FR-E5ND, DeviceNet Instruction Manual FR-E5NP, Profibus Instruction Manual FR-E560 Instruction Manual Programming and Diagnostic Software Serial Communication Cable Only available for download. Notes For mounting on E500 VFD Also used with A500(L). Also used with A500(L). Plug-in Option. Not for use with E520 or E510W. Plug-in Option. Not for use with E520 or E510W. Plug-in Option. Not for use with E520 or E510W. Plug-in Option. Not for use with E520 or E510W. 1m cable 3m cable 5m cable For use only on FR-PA02-02 and FR-CB20I Stocked Item S S S S S S S S S S

Dynamic Braking
All Mitsubishi Electric VFDs have some inherent braking capability. During controlled deceleration, motor regenerative losses are dissipated in the motor, wire, and VFD circuitry. The built-in DC injection braking allows for low speed braking and stopping. When the above capabilities are inadequate for an application, it is necessary to add a power transistor brake unit and resistor unit in series across the DC bus. Motor regeneration causes the DC bus voltage to increase, and when the voltage exceeds a specified threshold, the transistor turns on to pass current through the resistor. Motor kinetic energy is converted to heat energy. VFD overcurrent and overvoltage protective circuits are active at all times, and will fault-trip the VFD if the brake size is inadequate. Two main factors must be considered when sizing the brake, the effective duty cycle (%ED) and the short time duty rating. The effective duty cycle is increased when an external resistor is added. It is preferable to profile the effective duty cycle of the units of time. With this information, the short time duty is known and the %ED can be calculated, as shown in the below example. %ED = Braking time / total time for complete operating cycle x 100 Example: Complete cycle is: 5 sec: Acceleration time to reach set speed 60 sec: Run time at set speed 3 sec: Deceleration time to come to a complete stop 12 sec: Time period motor remains stopped %ED = 3 / (5 + 60 + 3 + 12) * 100 = 3.6% The tables shown assume 100% brake torque, when brake torque is represented by its percentage to the rated torque of the applied motor. Torque (kg.m) = 974 * Power (kW) / Speed (rpm).
Dynamic Braking Unit for 230VAC Braking Torque = 100% Braking Unit Model No. (*3) Not Necessary Weight kg / lbs Resistor Kit Model No. FR-ABR-0.4K N/A FR-ABR-0.75K S 0.4 / 0.9 100 150 1 0.75K 10% Stocked Item S Weight Resistance kg / lbs (Ohms) 0.2 / 0.5 200 Rated (W) 80 Motor (Hp) 0.5 Drive Model E510W 0.4K %ED 10% FR-ABR-0.4K to 0.75K

Products are UL listed.

Line Noise Filter


Provides a toroid for line noise reduction.
Drive Hp 0.5 5 0.5 75 Kit Model Number Dimensions mm (in) L W 22.5 (0.89) 31.5 (1.24) D 65 (2.56) 83 (3.27) Stocked Item S S

DIN Rail Mounting Attachment


This attachment allows the E500 Series inverter to mount on a 35mm DIN rail.
Model Number FR-UDA01 FR-UDA02 Drive Model E510W 0.1K 0.4K 0.75K Stocked Item S S

FR-BSF01 110 (4.33) FR-BLF 180 (7.07)

12

E700 Series
The cost-effective variable speed control solution for general purpose applications.
I I

I I I I

Available in 240V and 480V up to 20HP Advanced Magnetic Flux Vector Control for improved starting torque and smooth low speed motor operation Auto-tuning allows improved performance using virtually any manufacturers motor All capacities include built-in brake chopper USB communications allow fast commissioning and troubleshooting Standard RS485 serial communications supporting Modbus RTU

I I I I I I I I

Sink / Source selectable I/O Supports remote I/O function via network Built-in PID Control Delivers rated current at 50C and 14.5kHz carrier frequency with minimal de-rating 200% overload for 3 seconds 0 to 10V analog output CC-Link, DeviceNet, Profibus-DP, LonWorks Standard 5 year warranty

FR-E720 175 NA
Voltage 208/230 Inverter capacity Amperage/10 (175 = 17.5A output) 460 Horsepower 1/8 20 Hp 1/2 20 Hp Symbol E720 E740 Voltage Class Three-phase 200V class Three-phase 400V class

E700 Selection
Output Amps HP Model Number Dimensions in inches (mm) Height Width Depth Weight Lbs (kg) Stocked Item

3-Phase 200~240VAC Input & Output 0.8 1.5 3 5 8 11 17.5 24 33 47 60 1/8 1/4 1/2 1 2 3 5 7 1/2 10 15 20 FR-E720-008-NA FR-E720-015-NA FR-E720-030-NA FR-E720-050-NA FR-E720-080-NA FR-E720-110-NA FR-E720-175-NA FR-E720-240-NA FR-E720-330-NA FR-E720-470-NA FR-E720-600-NA 5.0 (128) 5.0 (128) 5.0 (128) 5.0 (128) 5.0 (128) 10.3 (260) 2.7 (68) 2.7 (68) 2.7 (68) 4.3 (108) 6.7 (170) 7.1 (180) 3.2 (81) 4.5 (113) 5.3 (133) 5.4 (136) 5.7 (143) 6.5 (165) 1.1 (0.5) 1.6 (0.7) 2.2 (1.0) 3.1 (1.4) 3.8 (1.7) 9.5 (4.3) S S S S S S S S S S S

10.3 (260)

8.7 (220)

7.5 (190)

19.9 (9)

3-Phase 380~480VAC Input & Output 1.6 2.6 4 6 9.5 12 17 23 30 1/2 1 2 3 5 7 1/2 10 15 20 FR-E740-016-NA FR-E740-026-NA FR-E740-040-NA FR-E740-060-NA FR-E740-095-NA FR-E740-120-NA FR-E740-170-NA FR-E740-230-NA FR-E740-300-NA 5.9 (150) 8.7 (220) 5.8 (147) 7.1 (3.2) 5.9 (150) 5.5 (140) 5.4 (135) 4.2 (1.9) 5.9 (150) 5.5 (140) 4.5 (114) 3.1 (1.4) S S S S S S S S S

10.3 (260)

8.7 (220)

7.5 (190)

19.9 (9)

Mitsubishi Electric Automation

Variable Frequency Drives 13

E700 General Specifications VARIABLE FREQUENCY DRIVES


Control Method Output Frequency Range Frequency Setting Resolution Frequency Accuracy Analog Input Digital Input Analog Input Digital Input Soft-PWM control/high carrier frequency PWM control (V/F control, advanced magnetic flux vector control, general-purpose magnetic flux vector control, optimum excitation control can be selected) 0.2 to 400Hz 0.06Hz/60Hz (terminal2, 4: 0 to 10V/10bit) 0.12Hz/60Hz (terminal2, 4: 0 to 5V/9bit) 0.06Hz/60Hz (terminal4: 4 to 20mA/10bit) 0.01Hz Within 0.5% of the max. output frequency (25C 10C) Within 0.01% of the set output frequency Base frequency can be set from 0 to 400Hz Constant torque/variable torque pattern can be selected 200% or more (at 0.5Hz) when advanced magnetic flux vector control is set (3.7K or less) Manual torque boost 0.01 to 360s, 0.1 to 3600s (acceleration and deceleration can be set individually), linear or S-pattern acceleration/deceleration mode can be selected. Operation frequency (0 to 120Hz), operation time (0 to 10s), operation voltage (0 to 30%) variable Operation current level can be set (0 to 200% adjustable), whether to use the function or not can be selected Two points Terminal 2: 0 to 10V, 0 to 5V can be selected Terminal 4: 0 to 10V, 0 to 5V, 4 to 20mA can be selected Entered from operation panel and parameter unit Forward and reverse rotation or start signal automatic self-holding input (3-wire input) can be selected. Seven points You can select from among multi-speed selection, remote setting, stop-on contact selection, second function selection, terminal 4 input selection, JOG operation selection, PID control valid terminal, brake opening completion signal, external thermal input, PU-external operation switchover, V/F switchover, output stop, start self-holding selection, forward rotation, reverse rotation command, inverter reset, PU-NET operation switchover, external-NET operation switchover, command source switchover, inverter operation enable signal, and PU operation external interlock Maximum/minimum frequency setting, frequency jump operation, external thermal relay input selection, automatic restart after instantaneous power failure operation, forward/reverse rotation prevention, remote setting, ibrake sequence, second function, multi-speed operation, stop-on contact control, droop control, regeneration avoidance, slip compensation, operation mode selection, offline auto tuning function, PID control, computer link operation (RS-485) Open Collector Output Relay Output Two points One point You can select from among inverter operation, up-to-frequency, overload alarm, output frequency detection, regenerative brake prealarm, electronic thermal relay function prealarm, inverter operation ready, output current detection, zero current detection, PID lower limit, PID upper limit, PID forward/reverse rotation output, brake opening request, fan alarm*2, heatsink overheat pre-alarm, deceleration at an instantaneous power failure, PID control activated, during retry, life alarm, current average value monitor, remote output, alarm output, fault output, fault output 3, and maintenance timer alarm Analog Output 0 to 10VDC: one point You can select from among output frequency, motor current (steady), output voltage, frequency setting, motor torque, converter output voltage, regenerative brake duty, electronic thermal relay function load factor, output current peak value, converter output voltage peak value, reference voltage output, motor load factor, PID set point, PID measured value, output power 0 to 10VDC You can select from among output frequency, motor current (steady), output voltage, frequency setting, cumulative energization time, actual operation time, motor torque, converter output voltage, regenerative brake duty, electronic thermal relay function load factor, outOperating Status put current peak value, converter output voltage peak value, motor load factor, PID set point, PID measured value, PID deviation, inverter I/O terminal monitor, I/O terminal option monitor, output power, cumulative power, motor thermal load factor, and inverter thermal load factor. Fault Definition Additional Display By The Parameter Unit (FR-PU04/FRPU07) Only Fault definition is displayed when the fault occurs and the past 8 fault definitions (output voltage/current/frequency/cumulative energization time right before the fault occurs) are stored

Control Specifications

Voltage/Frequency Characteristics StartingTorque Torque Boost Acceleration/DecelerationTime Setting DC Injection Brake Stall Prevention Operation Level Frequency Setting Signal Start Signal Analog Input Digital Input

Input Signal

Operation Specifications

Operational Functions

Output Signal Points

Output Signal Indication

Operating Status

For Meter Output Points For Meter

Operation Panel Parameter Unit (FR-PU07)

Operating Status Not used Fault Definition Interactive Guidance Output voltage/current/frequency/cumulative energization time immediately before the fault occurs Function (help) for operation guide Protective functions Overcurrent during acceleration, overcurrent during constant speed, overcurrent during deceleration, overvoltage during acceleration, overvoltage during constant speed, overvoltage during deceleration, inverter protection thermal operation, motor protection thermal operation, heatsink overheat, input phase failure, output side earth (ground) fault overcurrent at start (*4), output phase failure, external thermal relay operation (*4), option fault, parameter error, internal board fault, PU disconnection, retry count excess (*4), CPU fault, brake transistor alarm, inrush resistance overheat, communication error, analog input error, USB communication error, brake sequence error 4 to 7 (*4) Warning functions Fan alarm (*2), overcurrent stall prevention, overvoltage stall prevention, PU stop, parameter write error, regenerative brake prealarm (*4), electronic thermal relay function prealarm, maintenance output (*4), undervoltage -10C to +50C (14F to 122F) (non-freezing) (*3) 90%RH maximum (non-condensing) -20C to +65C (-4F to 149F) Indoors (without corrosive gas, flammable gas, oil mist, dust and dirt etc.) Maximum 1000m (3280.80 feet) above sea level, 5.9m/s2 or less

Protective/Warning Function

Ambient Temperature Environment Ambient Humidity Storage Temperature (*1) Atmosphere Altitude/Vibration

14

Notes: 1. Temperatures applicable for a short time, e.g. in transit. 2. As the FR-E720-050 or less, FR-E740-026 or less is not provided with the cooling fan, this alarm does not function. 3. When using the inverters at the ambient temperature of 40C (104F) or less, the inverters can be installed closely attached (0cm clearance). 4. This protective function does not function in the initial status.

E700 Series Terminal Connection Diagram


Three-phase 200V power input Three-phase 400V power input
Sink logic Main circuit terminal Control circuit terminal
Brake unit (Option)

*6 A brake transistor is not built-in to the FR-E720-008 and 015. *7 Brake resistor (FR-ABR, MRS, MYS type) Install a thermal relay to prevent an overheat and burnout of the brake resistor. (The brake resistor can not be connected to the FR-E720-008 and 015.)

*1 Earth (Ground) Jumper P1 R/L1 S/L2 T/L3 Earth (Ground) P/+


Inrush current limit circuit

*1. DC reactor (FR-HEL)


When connecting a DC reactor, remove the jumper across P1-P/+

*7 PR N/*6

MCCB Three-phase AC power supply

MC

U V W

Motor IM

Main circuit Control circuit

Earth (Ground)

Standard control temirnal block


Control input signals (No voltage input allowed) Forward Terminal functions vary rotation start with the input terminal Reverse assignment (Pr. 178 to rotation start Pr. 184) High speed Multi-speed selection Middle speed *2 When using terminals PCLow SD as a 24VDC power speed
supply, take care not to short across terminals PC-SD.

STF STR RH RM RL MRS


SOURCE SINK

C B A Relay output (Fault output)

Relay output Terminal functions vary by Pr. 192 A,B,C terminal function selection

Open collector output RUN Running FU Terminal functions vary with the output terminal assignment (Pr. 190 and Pr. 191)

Output stop Reset

RES SD PC *2

Frequency detection Open collector output common Sink/source common

Contact input common 24VDC power supply (Common for external power supply transistor) Frequency setting signals (Analog)
*3 Terminal input specifications Frequency can be changed by analog setting input specifications potentiometer switchover (Pr. 73). *4 Terminal input specifications can be changed by analog input specifications switchover (Pr. 267). Set the voltage/current input switch in the "V" position to select voltage input (0 to 5V/0 to10V) and "I" (initial value) to select current input (4 to 20mA).

SE
24V

3 2

10(+5V) 2 0 to 5VDC *3 (0 to 10VDC) 5(Analog common)

AM 5 PU connector

(+) (-)

Analog signal output (0 to 10VDC)

1/2W1k *5

Terminal 4 (+) input (Current (-) input)

4 4 to 20mADC 0 to 5VDC 0 to 10VDC *4

USB connector

*5 It is recommended to use 2W1k when the frequency setting signal is changed frequently.

Voltage/current input switch *4

Connector for plug-in option connection

Option connector

Terminal Block Layout


Terminal screw size M3: (Terminal A, B, C) M2: (Other than the above)
10 2 5 4 RUN FU SE

AM RL RM RH MRS RES SD PC STF STR SD SD

Mitsubishi Electric Automation

Variable Frequency Drives 15

VARIABLE FREQUENCY DRIVES

E700 Series Plug-In Options


Model Number FR-A7NC E KIT FR-A7ND E KIT FR-A7NP E KIT FR-A7NL E KIT FR-A7AX E KIT FR-A7AY E KIT FR-A7AR E KIT Description CC-Link Network Option DeviceNet Network Option Profibus-DP Network Option LonWorks Network Option Additional 16-bit Digital Input Additional Analog & Digital Output Additional Relay Output Stocked Item S S S S S S S

E700 Series External Options


Model Number FR-PU07 FR-PU07-BB FR-CB20 I SC-FRPC FR-ABR- I I K Description Alpha-Numeric multi-language keypad Battery powered Alpha-Numeric multi-language keypad Keypad extension cable Serial communications cable External brake resistor Stocked Item S S S S S FR-CB201 FR-CB203 FR-CB203

Note: I I represents drive kW rating

E700 Dynamic Braking


All Mitsubishi Electric VFDs have some inherent braking capability. During controlled deceleration, motor regenerative losses are dissipated in the motor, wire, and VFD circuitry. The built-in DC injection braking allows for low speed braking and stopping. When the above capabilities are inadequate for an application, it is necessary to add a power transistor brake unit and resistor unit in series across the DC bus. Motor regeneration causes the DC bus voltage to increase, and when the voltage exceeds a specified threshold, the transistor turns on to pass current through the resistor. Motor kinetic energy is converted to heat energy. VFD overcurrent and overvoltage protective circuits are active at all times, and will fault-trip the VFD if the brake size is inadequate. Two main factors must be considered when sizing the brake, the effective duty cycle (%ED) and the short time duty rating. The effective duty cycle is increased when an external resistor is added. It is preferable to profile the effective duty cycle of the units of time. With this information, the short time duty is known and the %ED can be calculated, as shown in the below example. %ED = Braking time / total time for complete operating cycle *100 Example: Complete cycle is: 5 sec: Acceleration time to reach set speed 60 sec: Run time at set speed 3 sec: Deceleration time to come to a complete stop 12 sec: Time period motor remains stopped %ED = 3 / (5 + 60 + 3 + 12) * 100 = 3.6% The tables shown assume 100% brake torque, when brake torque is represented by its percentage to the rated torque of the applied motor. Torque (kg.m) = 974 * Power (kW) / Speed (rpm).

Dynamic Braking Unit For 230VAC Braking Torque = 100%


Resistor Kit Model Number FR-ABR-0.4K FR-ABR-0.75K FR-ABR-2.2K FR-ABR-3.7K FR-ABR-5.5K FR-ABR-7.5K FR-ABR-11K FR-ABR-15K (2 resistors in parallel) Weight kg / lbs 0.2 / 0.5 0.4 / 0.9 0.5 / 1.1 0.8 / 1.8 1.3 / 2.9 2.2 / 4.9 3.4 (7.5) 2.4 (5.3) x 2 Resistance (Ohms) 200 100 60 40 25 20 13 18/2 Rated (W) 80 150 250 300 500 800 Motor (Hp) 1/2 1 3 5 7.5 10 15 20 Drive Model E720 030 050 080/110 175 240 330 470 600 % ED 10% 10% 10% 10% 10% 10% 6% 6% Stocked Item S S S S S S S S

Dynamic Braking Unit For 460-480VAC Braking Torque = 100%


Resistor Kit Model Number FR-ABR-H0.4K FR-ABR-H0.75K FR-ABR-H1.5K FR-ABR-H2.2K FR-ABR-H3.7K FR-ABR-H5.5K FR-ABR-H7.5K FR-ABR-H11K FR-ABR-H15K (2 resistors in series) Weight kg / lbs 0.2 / 0.5 0.2 / 0.5 0.4 / 0.9 0.5 / 1.1 0.8 / 1.8 1.3 / 2.9 2.2 / 4.9 3.2 (7.1) 2.4 (5.3) x2 Resistance (Ohms) 1200 700 350 250 150 110 75 52 18 x 2 Drive Model Rated (W) 60 80 150 250 300 500 800 1000 1600 Motor (Hp) 0.5 1 2 3 5 7.5 10 15 20 E740 016 026 040 060 095 120 170 230 030 % ED 10% 10% 10% 10% 10% 10% 10% 6% 6% Stocked Item S S S S S S S S S

16

Brake Resistors
Brake Resistor Model

Dimensions (mm) W FR-ABR-0.4K


A1 d1 A1

FR-ABR-0.4K to 7.5K, H0.4K to H7.5K


W W1 1 W2 500 +20 0
B1

W1 125 200 225 200 320 385 100 125 200 225 200 320 385

W2 100 175 200 175 295 360 75 100 175 200 175 295 360

D 40 40 50 61 61 80 40 40 40 50 61 61 80

H 21 21 26 33 33 40 21 21 21 26 33 33 40

140 215 240 215 335 400 115 140 215 240 215 335 400

FR-ABR-0.75K 200 V Class 400V Class FR-ABR-2.2K FR-ABR-3.7K FR-ABR-5.5K FR-ABR-7.5K FR-ABR-H0.4K FR-ABR-H0.75K FR-ABR-H1.5K FR-ABR-H2.2K FR-ABR-H3.7K FR-ABR-H5.5K FR-ABR-H7.5K

5.3

A2
Glass-braided cable 2.0mm2 white

d2 A2
H

FR-ABR-11K, 15K, 22K, H11K, H15K, H22K


W W1 1 W2 700+20 0

2.5

B2

Dimensions (mm) Brake Resistor Model W


B1

W1 125 200 225 100 125 385

W2 100 175 200 75 100 360

D 40 40 50 40 40 80

H 21 21 26 21 21 40

A1 d1 A1

200 V Class

FR-ABR-11K FR-ABR-15K FR-ABR-22K FR-ABR-H11K FR-ABR-H15K FR-ABR-H22K

140 215 240 115 140 400

80.5 1 5.3

A2
Glass-braided cable 2.0mm2 white

d2 A2

B2

100
50

Input Radio Noise Filter


This filter is connected to the input of the drive and helps to reduce radiated noise in the radio frequencies.
Drive Voltage 208 230 460 Kit Model Number FR-BIF FR-BIF-H Leakage Current (mA) 4 4 Dimensions mm (in) L 58 (2.3) 58 (2.3) W 44 (1.8) 44 (1.8) D 42 (1.7) 42 (1.7) Stocked Item S

2.5

Line Noise Filter


Provides a toroid for line noise reduction.
Drive Hp 0.5 5 0.5 75 Kit Model Number Dimensions mm (in) L W 22.5 (0.89) 31.5 (1.24) D 65 (2.56) 83 (3.27) Stocked Item S S

E740 EMC Filters


This attachment allows the VFD to be mounted onto the filter.
Model Number FFR-E540-4.5A-SF1 FFR-E540-15A-SF1 FFR-E540-27A-SF1 Drive Model FR-008-050 FR-080-175 FR-240-330 Stocked Item S

FR-BSF01 110 (4.33) FR-BLF 180 (7.07)

DIN Rail Mounting Attachment


This attachment allows the E700 Series inverter to mount on a 35mm DIN rail.
Model Number FR-UDA01 FR-UDA02 FR-UDA03 Drive Model E720 0080-050 080-110 175 Stocked Item S S

400V Class

Mitsubishi Electric Automation

Variable Frequency Drives 17

VARIABLE FREQUENCY DRIVES

Installation Interchange Attachment


This attachment allows the E700 Series inverter to be mounted using the installation holes from the previous series VFDs.
Model Number Installation Model E700 Series E720-008 FR-E5T-10 E720-015 E720-030 E720-050 FR-E5T-11 FR-E5T FR-E5T-02 Direct Attachment E720-050 E720-080 E720-110 E720-175 E720-240 E720-330 E740-016 E740-026 E740-040 FR-E5T-14 E740-060 E740-095 Direct Replacement Previous Model E500 Series A0x4 Series FR-A024-0.1K-UL FR-A024-0.2K-UL FR-A024-0.4K-UL FR-A024-0.75K-UL FR-A024-1.5K-UL FR-A024-2.2K-UL FR-A024-3.7K-UL FR-A044-0.4K-UL FR-A044-0.75K-UL FR-A044-1.5K-UL FR-A044-2.2K-UL FR-A044-3.7K-UL Z024 Series FR-Z024-0.1K-UL FR-Z024-0.2K-UL FR-Z024-0.4K-UL FR-Z024-0.75K-UL FR-Z024-1.5K-UL FR-Z024-2.2K-UL FR-Z024-3.7K-UL A200E Series FR-A220E-5.5K-UL FR-A220E-7.5K-UL S Stocked Item

E700 Installation Interchange Attachment


This attachment allows the E700 Series inverter to be mounted at a 90 angle so that the depth is reduced to 80 mm.
Model Number FR-E5T-L Installation Model E700 Series E720-030 E720-050 E500 Series Direct Replacement Previous Model A0x4 Series FR-A024-0.4K-UL FR-A024-0.75K-UL Z024 Series FR-Z024-0.4K-UL Stocked item

E700 Series Watt Loss and Efficiency Data


240VAC 3-Phase Input HP-CT 1/8 1/4 1/2 1 2 3 5 7.5 10 15 20 Model Number FR-E720-008-NA FR-E720-015-NA FR-E720-030-NA FR-E720-050-NA FR-E720-080-NA FR-F720-110-NA FR-E720-175-NA FR-E720-240-NA FR-F720-330-NA FR-E720-470-NA FR-E720-600-NA Rated Watts 100 200 400 750 1500 2200 3700 5500 7500 11000 15000 Watts Loss 14 20 32 50 80 100 160 290 380 520 600 Efficiency 86% 90% 92% 93% 95% 95% 96% 95% 95% 95% 96% Model Number FR-E740-016-NA FR-E740-026-NA FR-E740-040-NA FR-E740-060-NA FR-E740-095-NA FR-E740-120-NA FR-E740-170-NA FR-E740-230-NA FR-E740-300-NA 480VAC 3-Phase Input Rated Watts 400 750 1500 2200 3700 5500 7500 11000 15000 Watts Loss 45 50 85 100 160 310 420 560 640 Efficiency 89% 93% 94% 95% 96% 94% 94% 95% 96%

Notes: 1. The amount of heat generated by the inverter is based on one inverter connected to one motor of the same capacity. 2. The amount of heat generated in the above table is the amount of heat generated when the inverter is operated at its rated current. 3. The amount of heat generated will decrease according to the motor load and usage (duty).

Conduit Kits
Model Number Description FR-E7FN-01 FR-E7FN-02 FR-E7FN-03 FR-E7FN-04 FR-E7FN-05 FR-E7FN-06 FR-E7FN-07 FR-E7FN-08 FR-E7FN-09 FR-E7FN-10 Conduit kit for E720-008/015 Conduit kit for E720-030 Conduit kit for E720-050 Conduit kit for E720-080/110 Conduit kit for E740-016/026 Conduit kit for E740-040/060/090 Conduit kit for E720-175 Conduit kit for E740-120/170 Conduit kit for E720-240/330 Conduit kit for E720-470/600 E740-230/300 Stocked Item S S S S S S S S S S

E700 Heatsink Extension Kits


Model Number FR-E7CN-02 FR-E7CN-03 FR-E7CN-04 FR-E7CN-05 FR-E7CN-06 FR-E7CN-07 FR-E7CN-08 FR-E7CN-09 FR-A7CN02 Description Heatsink Extension kit for E720-030 Heatsink Extension kit for E720-050 Heatsink Extension kit for E720-080/110 Heatsink Extension kit for E740-016/026 Heatsink Extension kit for E740-040/060/090 Heatsink Extension kit for E720-175 Heatsink Extension kit for E740-120/170 Heatsink Extension kit for E720-240/330 Heatsink Extension kit for E720-470/600 E740-230/300 Stocked Item S S S S S S S S S

E700 Demonstration Unit


Model Number VFD-MICRO-DEMO VFD-MOTOR-DEMO Description Includes E720 1HP, pre-wired digital input switches, led outputs and speed potentiometer Includes 1/2HP motor with quick connection to VFD-MICRO-DEMO Stocked Item S S

18

F700 Series
The truly fantastic specifications of the F700, make this VFD from Mitsubishi Electric an absolute must for your drive systems.
I

I I I I I

NEMA 1 UL Type 1 Enclosure Designs: Drive can be mounted as a stand-alone unit where required. (Plenum rated) Ease of Programming: Taken to new levels with the new DU07 programming dial and FR-Configurator programming software Built-in EMC filter: Conforms to EN61800-3 2nd environmental Energy Savings: Optimum Excitation Control The popular setting dial makes operation easy Control terminals can be used over a network as remote I/O An operation panel can be installed on the front cover and is detachable (Cable connector option is required)

I I I I I I I I I

PU/EXT (operation mode) switchover key is available RS-485 communications as standard Mitsubishi or Modbus RTU protocol Windmill start: Catch a reverse spinning load Regeneration avoidance PID sleep mode Pre-soak mode 3 user programmable skip frequencies Remote I/O capability: All the drive I/O can be read or controlled over a network UL Listed for single phase input

Voltage 208/230 480 3/4 200 Hp 3/4 800 Hp

Horsepower

F700 Ratings 200-240V Class


Input: 1 Phase/3 Phase - Output Voltage: 3 Phase 200-240V at 60Hz Voltage Tolerance: 170-264V at 60Hz Available Braking Torque: 15% Torque Continuous SLD (40C) 110% OL / 1min 120% OL / 3 sec Hp (*1) 1 2 3 5 7.5 10 15 20 25 30 40 50/60 60 75 40 50/60 60 75 100/125 150 200 FLA 4.6 7.7 10.5 16.7 25 34 49 63 77 93 125 154 187 233 125 154 187 233 316 380 475 LD 120% OL / 1min 150% OL / 3 sec Hp (*1) 1 2 3 5 7.5 10 15 20 25 30 40 50 60 75 40 50 60 75 100 125 150 FLA 4.2 7 9.6 15.2 23 31 45 58 70 85 114 140 170 212 114 140 170 212 288 346 432 FR-F720-00046-NA FR-F720-00077-NA FR-F720-00105-NA FR-F720-00167-NA FR-F720-00250-NA FR-F720-00340-NA FR-F720-00490-NA FR-F720-00630-NA FR-F720-00770-NA FR-F720-00930-NA FR-F720-01250-NA FR-F720-01540-NA FR-F720-01870-NA FR-F720-02330-NA FR-F720-01250-NAN1 FR-F720-01540-NAN1 FR-F720-01870-NAN1 FR-F720-02330-NAN1 FR-F720-03160-NA FR-F720-03800-NA FR-F720-04750-NA A B C C C D D E F F F G H H F G H H K K K IP00 (*2) NEMA 1 Forced Air Cooled UL Type 1 Plenum Rated Self Cooling S S S S S S S S S S S IP00 (*2) S S S S S Model Number (*4) Frame Size Cooling Method Protective Rating Stocked item

Notes: See next page.

Mitsubishi Electric Automation

Variable Frequency Drives 19

VARIABLE FREQUENCY DRIVES

F700 Ratings 480V Class


Input: 1 Phase/ 3 Phase Output Voltage: 3 Phase 380-480V at 50/60Hz Voltage Tolerance: 323-528V at 50/60Hz Available Braking Torque: 15% Torque Continuous SLD (40C) 110% OL / 1min 120% OL / 3 sec Hp (*1) 1 2 3 5 7.5 10 15 20 25 30 40 50/60 60 75 50/60 60 75 FLA 2.3 3.8 5.2 8.3 12.6 17 25 31 38 47 62 77 93 116 77 93 116 LD 120% OL / 1min Model Number (*4) 150% OL / 3 sec Hp (*1) 1 2 3 5 7.5 10 15 20 25 30 40 50 60 75 50 60 75 FLA 2.1 3.5 4.8 7.6 11.5 16 23 29 35 43 57 70 85 106 70 85 106 FR-F740-00023-NA FR-F740-00038-NA FR-F740-00052-NA FR-F740-00083-NA FR-F740-00126-NA FR-F740-00170-NA FR-F740-00250-NA FR-F740-00310-NA FR-F740-00380-NA FR-F740-00470-NA FR-F740-00620-NA FR-F740-00770-NA FR-F740-00930-NA FR-F740-01160-NA FR-F740-00770-NAN1 FR-F740-00930-NAN1 FR-F740-01160-NAN1 C C C C C D D E E F F G H H G H H NEMA 1 Forced Air Cooled IP00 (*3) UL Type 1 Plenum rated Self Cooling S S S S S S S S S S S S S S Frame Size Cooling Method Protective Rating Stocked Item

Input: 1 Phase / 3 Phase Output Voltage: 3 Phase 380-480V at 50/60Hz Voltage Tolerance: 323-550V at 50/60Hz Available Braking Torque: 15% Torque Continuous DC Link Choke is Included With The VFD SLD (40C) 110% OL / 1min 120% OL / 3 sec Hp (*1) 100/150 150 200 250 300 350 400 450 500 550 650 700 800 900 1000 FLA 180 216 260 325 361 432 481 547 610 683 770 866 962 1094 1212 LD 120% OL / 1min 150% OL / 3 sec Hp (*1) 100 150 150 200 250 300 350 400 450 500 550 650 700 800 900 FLA 144 180 216 260 325 361 432 481 547 610 683 770 866 962 1094 FR-F740-01800-NA FR-F740-02160-NA FR-F740-02600-NA FR-F740-03250-NA FR-F740-03610-NA FR-F740-04320-NA FR-F740-04810-NA FR-F740-05470-NA FR-F740-06100-NA FR-F740-06830-NA FR-F740-07700-NA FR-F740-08660-NA FR-F740-09620-NA FR-F740-10940-NA FR-F740-12120-NA H J J K K L L M M M N N P P P IP00 Forced Air Cooled IP00 (*3) S S S S S S S S S S S S S Model Number (*4) Frame Size Fan Protective Rating Stocked Item

Notes: 1. Motor ratings shown are intended as guidelines only based on 4 pole standard induction motors. 2. NEMA 1 conduit adapter option required for types 01250 04750. See page 24. 3. NEMA 1 conduit adapter option required for types 00770 06830. See page 24. 4. For single phase input, derate output current by 40% (Models up to F720-03800-NA, F740-04810-NA.)

20

F700 General Specifications


Control System Output Frequency Range Frequency Setting Resolution Frequency Accuracy Analog Input Digital Input Analog Input Digital Input High carrier frequency PWM control (V/F control)/optimum excitation control/simple magnetic flux vector control 0.5 to 400Hz 0.015Hz/0 to 60Hz (terminal 2, 4: 0 to 10V/12bit); 0.03Hz/0 to 60Hz (terminal 2, 4: 0 to 5V/11bit, 0 to 20mA/approx. 11bit, terminal 1: -10V to +10V/11bit); 0.06Hz/0 to 60Hz (terminal 1: 0 to 5V/10bit) 0.01Hz Within 0.2% of the max. output frequency (25C 10C) Within 0.01% of the set output frequency Base frequency can be set from 0 to 400Hz. Constant torque/variable torque pattern or adjustable 5 points V/F can be selected 120% (3Hz) when set to simple magnetic flux vector control and slip compensation 0 to 3600s (acceleration and deceleration can be set individually), linear or S-pattern acceleration/deceleration mode can be selected. Operation frequency (0 to 120Hz), operation time (0 to 10s), operation voltage (0 to 30%) variable Operation current level can be set (0 to 150% adjustable), whether to use the function or not can be selected Terminal 2, 4: 0 to 10V, 0 to 5V, 4 to 20mA can be selected. Terminal 1: -10 to +10V, -5 to 5V can be selected. Four-digit BCD or 16-bit binary using the setting dial of the operation panel (when used with the option FR-A7AX) Available individually for forward and reverse rotation. Start signal automatic self-holding input (3-wire input) can be selected. Select any twelve signals using Pr.178 to Pr.189 (input terminal function selection) from among multi-speed selection, second function selection, terminal 4 input selection, JOG operation selection, selection of automatic restart after instantaneous power failure, external thermal relay input, HC connection (inverter operation enable signal), HC connection (instantaneous power failure detection), PU operation/external interlock signal , PID control enable terminal, PU operation, external operation switchover, output stop, start self-holding selection, forward rotation command, reverse rotation command, inverter reset, PTC thermistor input, PID forward reverse operation switchover, PU-NET operation switchover, NET-external operation switchover, command source switchover. Max. and min. frequency settings, frequency jump operation, external thermal relay input selection, polarity reversible operation, automatic restart after instantaneous power failure operation, continuous operation at an instantaneous power failure, commercial power supply-inverter switchover operation, forward/reverse rotation prevention, operation mode selection, PID control, computer link operation (RS-485). Select any seven signals using Pr.190 to Pr.196 (output terminal function selection) from among inverter running, up-to-speed, instantaneous power failure/undervoltage, overload warning, output frequency detection, second output frequency detection, electronic thermal relay function pre-alarm, PU operation mode, inverter operation ready, output current detection, zero current detection, PID lower limit, PID upper limit, PID forward rotation reverse rotation output, commercial power supply-inverter switchover MC1, commercial power supply-inverter switchover MC2, commercial power supply-inverter switchover MC3, fan fault output, heatsink overheat pre-alarm, inverter running start command on, deceleration at an instantaneous power failure, PID control activated, during retry, during PID output suspension, life alarm, input MC stop signal, power savings average value update timing, current average monitor, alarm output 2, maintenance timer alarm, remote output, minor failure output, alarm output. Open collector output (5 points), relay output (2 points) and alarm code of the inverter can be output (4 bit) from the open collector. Select any seven signals using Pr. 313 to Pr. 319 (extension output terminal function selection) from among control circuit capacitor life, main circuit capacitor life, cooling fan life, inrush current limit circuit life. Select from output frequency, motor current (steady or peak value), output voltage, frequency setting value, running speed, converter output voltage (steady or peak value), electronic thermal relay function load factor, input power, output power, load meter, reference voltage output, motor load factor, energy saving effect, PID set value, PID process value using Pr. 54 CA terminal function selection (analog current output) and Pr. 158 AM terminal function selection (analog output). Output frequency, motor current (steady or peak value), output voltage, alarm indication, frequency setting, running speed, converter output voltage (steady or peak value), electronic thermal load factor, input voltage, output voltage, road meter, cumulative energization time, actual operation time, motor load factor, cumulative energization power, power saving effect, cumulative saving power, PID set point, PID process value, PID deviation value, inverter I/O terminal monitor, input terminal option monitor (*1), output terminal option monitor (*1), option fitting status monitor (*2), terminal assignment status (*2) Alarm definition is displayed when the protective function is activated, the output voltage/current/frequency/cumulative energization time right before the protection function was activated and the past 8 alarm definitions are stored. Operation guide/troubleshooting with a help function. (*2) Overcurrent during acceleration, overcurrent during constant speed, overcurrent during deceleration, overvoltage during acceleration, overvoltage during constant speed, overvoltage during deceleration, inverter protection thermal operation, heatsink overheat, instantaneous power failure occurrence, undervoltage, input phase failure, motor overload, output side earth (ground) fault overcurrent, output phase failure, external thermal relay operation, PTC thermistor operation, option alarm, parameter error, PU disconnection, retry count excess, CPU alarm, power supply short for operation panel, 24VDC power output short, output current detection value over, inrush resistance overheat, communication alarm (inverter), analog input alarm, internal circuit alarm (15V power supply), fan fault, overcurrent stall prevention, overvoltage stall prevention, electronic thermal prealarm, PU stop, maintenance timer alarm (*1), parameter write error, copy operation error, operation panel lock. -10C to +50C (non-freezing) 90% RH or less (non-condensing) -20C to +65C Indoors (without corrosive gas, flammable gas, oil mist, dust and dirt, etc.) Maximum 1000m above sea level, 5.9m/s2 or less (conforms to JIS C 0040)

Control Specifications

Voltage/Frequency Characteristics Starting Torque Acceleration/Deceleration Time Setting DC Injection Brake Stall Prevention Operation Level Frequency Setting Signal Start Signal Analog Input Digital Input

Input Signals

Operation Specifications

Operational Functions

Output Signals

Operating Status

When Used With The FR-A7AY (Option)

Analog Output

Parameter Unit (FR-DU07/ FR-PU04)

Operating Status

Display

Alarm Definition Interactive Guidance

Protective/Warning Function

Ambient Temperature Environment Ambient Humidity Storage Temperature (*3) Atmosphere Altitude, Vibration

Notes: 1. Can be displayed only on the operation panel (FR-DU07). 2. Can be displayed only on the parameter unit (FR-PU04/FR-PU07). 3. Temperature applicable for a short period in transit, etc.

Mitsubishi Electric Automation

Variable Frequency Drives 21

VARIABLE FREQUENCY DRIVES

F700 Series Terminal Connection Diagram

F700 Control Terminal Layout


RL SE

A1 RM

B1 RH SU

C1 RT IPF

A2 AU OL

B2

C2

10E

10 SD

2 CA

4 AM CS 1 PC

STOP MRS FU SD SD

RES STF

RUN

STR

JOG

22

F700 Factory Supplied DC Link Chokes


Standard With VFD FR-F700 Series FR-F740-01800-NA FR-F740-02160-NA FR-F740-02600-NA FR-F740-03250-NA FR-F740-03610-NA FR-F740-04320-NA FR-F740-04810-NA FR-F740-05470-NA FR-F740-06100-NA FR-F740-06830-NA FR-F740-07700-NA FR-F740-08660-NA FR-F740-09620-NA FR-F740-10940-NA FR-F740-12120-NA DC Link Model Number FR-HEL-H90K FR-HEL-H110K FR-HEL-H132K FR-HEL-H160K FR-HEL-H185K FR-HEL-H220K FR-HEL-H250K FR-HEL-H280K FR-HEL-H315K FR-HEL-H355K FR-HEL-H400K FR-HEL-H450K FR-HEL-H500K FR-HEL-H560K FR-HEL-H630K mH 0.3 0.246 0.204 0.171 0.148 0.124 0.109 0.098 0.087 0.077 0.069 0.061 0.055 0.049 0.044 Amps 191 233 281 335 389 462 524 585 658 742 836 940 1045 1170 1317 Watt Loss 130 130 140 140 170 230 240 270 300 360 360 450 450 470 500 Height 13.4 (340) 13.4 (340) 15.9 (405) 15.9 (405) 15.9 (405) 15.9 (405) 17.3 (440) 17.3 (440) 19.5 (495) 19.5 (495) 19.7 (500) 19.7 (500) 17.8 (455) 18.1 (460) 18.1 (460) Dimensions inches (mm) Width 5.9 (150) 5.9 (150) 6.9 (175) 6.9 (175) 6.9 (175) 6.9 (175) 7.5 (190) 7.5 (190) 8.3 (210) 8.3 (210) 8.7 (220) 8.7 (220) 8.5 (215) 8.5 (215) 8.5 (215) Depth 7.5 (190) 7.7 (195) 7.9 (200) 8 (205) 9.4 (240) 9.4 (240) 9.8 (250) 10 (255) 9.8 (250) 9.8 (250) 9.8 (250) 10.6 (270) 13.6 (345) 14.2 (360) 14.2 (360) Approx. Weight lb (kg) 20 (44) 22 (48) 26 (57) 28 (62) 29 (64) 30 (66) 35 (77) 38 (84) 42 (92) 46 (101) 50 (110) 57 (125) 67 (1147) 85 (187) 95 (209)

F700 Frame Size


Frame Size A B C D E F G H J K L M N P Dimensions inches (mm) Height 10.2 (260) 10.2 (260) 10.2 (260) 10.2 (260) 11.8 (300) 15.8 (400) 21.7 (550) 21.7 (550) 27.6 (700) 29.1 (740) 39.8 (1010) 39.8 (1010) 52.4 (1330) 62.2 (1580) Width 4.3 (110) 4.3 (110) 5.9 (150) 8.7 (220) 8.7 (220) 9.8 (250) 12.8 (325) 17.1 (435) 18.3 (465) 18.3 (465) 19.6 (498) 26.8 (680) 31.1 (790) 39.2 (995) Depth 4.3 (110) 4.9 (125) 5.5 (140) 6.7 (170) 7.5 (190) 7.5 (190) 7.7 (195) 9.8 (250) 9.8 (250) 14.2 (360) 15 (380) 15 (380) 17.3 (440) 17.3 (440) Weight Without Reactor lbs (kg) 4.2 (1.9) 5 (2.3) 9.3 (4.2) 17.7 (8) 19.4 (8.8) 32.6 (14.8) 77.1 (35) 134.4 (61) 134.4 (61) 244.5 (111) 378.9 (172) 385 (175) 572 (260) 814 (370)

Mitsubishi Electric Automation

Variable Frequency Drives 23

VARIABLE FREQUENCY DRIVES

F700 Series Options


Conduit Attachments
Model Number FR-A7FN05 FR-A7FN06 FR-A7FN07 FR-A7FN-10 (*2) FR-A7FN-11 (*2) FR-A7FN-12 (*2) FR-A7FN-13 (*2) FR-A7FN-14 (*2) Drive Model F720 (*1) 01250 01540 01870, 02330 03160, 03800, 04750 F740 (*1) 00770 00930, 01160 01800 02160, 02600 03250, 03610 04320, 04810 05470, 06100, 06830 Stocked Item S S S S S S S

Instruction Manuals
Description FR-F700 Installation Manual Contains instructions for installer and parameter list. (Included with VFD, plus CD with all versions of VFD and option manuals.) FR-F700 Basic Manual Contains wiring details, VFD layout drawings, alarm definitions and parameter list. FR-F700 Applied Manual Contains wiring details, VFD layout drawings, alarm definitions and complete parameter list with definitions and setting examples. FR-PU07 Manual Contains complete instruction sets and screen definitions.
Manuals available for download at www.meau.com

Model Number IB(NA)0600218

Stocked Item

IB(NA)0600216

IB(NA)0600217

Notes: 1. For FR-F700s smaller than listed above, they are UL Type 1, and conduit attachment is standard. 2. Mounting hardware included for standard DC chokes which ship with VFD.

IB(NA)0600240

External Heatsink Attachment


Model Number FR-A7CN01 FR-A7CN02 FR-A7CN03 FR-A7CN04 FR-A7CN05 FR-A7CN06 FR-A7CN07 FR-A7CN08 FR-A7CN09 FR-A7CN10 01870, 02330 Drive Model F720 00105 to 00250 00340, 00490 00630 00770 to 01250 01540 00770 00930, 01160, 01800 02160 02600 03250, 03610 F740 00023 to 00126 00170, 00250 00310, 00380 00470, 00620 Stocked Item S S S S S S S

Parameter Units / Parameter Copy Units


Parameter units are used for operator control, reading and writing parameters, and drive monitoring. Parameter Copy Units also read the drive parameter settings and copy them into non-volatile memory, and can write them into other drives.
Model Number FR-CB201 FR-CB203 FR-CB205 FR-DU07 Description Extension cable straight plugs on both ends 1 meter. Extension cable straight plugs on both ends 3 meters. Extension cable straight plugs on both ends 5 meters. Control Panel for F700 LCD Multi-lingual Parameter Copy Unit (English, French, Spanish, German, Italian, Swedish, Finnish, Japanese) for operator control, parameter read/write and monitoring. Stores settings in non-volatile memory. Built-in parameter copy capability. (F/A700 based) FR-DU07 panel mounting adapter LCD Multi-lingual Parameter Copy Unit (English, French, Spanish, German, Italian, Swedish, Finnish, Japanese) for operator control, parameter read/write and monitoring. Serial Communication Cable Battery Powered PU07 Stocked Item S S S S

FR-PU07

FR-ADP

Option Cards
Model No. Relay Output 12 Bit Digital Input Function Digital Output Ext. Analog Output BiPolar Analog Input High Res Analog Input Motor Thermistor Communication CC-Link DeviceNet LonWorks Profibus DP FR-A7NC FR-A7ND FR-A7NL FR-A7NP S S S S FR-A7AZ FR-A7AR FR-A7AX FR-A7AY Stocked Item S S S

FR-PU04

SC-FRPC FR-PU07-BB

S S

Building Management Options


Model Number /Network Type Stock Item Ethernet I/P Modbus TCP/IP BacNET IP Metasys N2 Siemens FLN Modbus RTU BacNET MSTP FR-A7N-ETH (*1, *2) S X X X FR-A7N-XLT (*1, *2) S ETH-200 (*1, *3, *4) X X XLTR-200 (*1, *3)

X X X X

X X

F700 Demonstration Unit


Model Number VFD-F700-DEMO VFD-MOTOR-DEMO Description Includes F720 1HP, pre-wired digital input switches, LED outputs, speed potentiometer and analog meter Includes 1/2HP motor with quick connection to VFD-F700-DEMO Stocked Item S S

Notes: 1. For additional information visit www.iccdesigns.com 2. Physically mounts within VFD and powered by VFD 3. Communication to multiple VFD's is possible 4. Mounted and powered external to VFD

Software
Model Number FR-Configurator Description Programming and diagnostic software Stocked Item S

24

F700 Parameter Unit/Cable Reference List


VFD Model FR-DU04 FR-PA02 Parameter FR-PA02-02 Unit FR-PU04 FR-DU07 FR-PU07 Software FR-CONFIGURATOR E500 2a 1/2b 1/2b 2a A700 F700 2a S500E 2a 2b 2b 2a
Extension cables 1 = Direct mount 2 = FR-CB201, FR-CB203, FR-CB205 Where 1, 3, 5 indicate length in meters 3 = SC-FRPC Notes: a = Will not mount directly on drives cover cable required. b = To remote mount on the enclosure panel, an extension cable and gender change adapter (FR-E5P for E500, SD-54258-8811 for F700) are required. c = Included standard with VFD.

2a 1c / 2 b 1/2b 3

Dynamic Braking Options


Select the brake unit according to the motor capacity. To obtain braking torque greater than 200%, use a larger inverter capacity. Up to 10 FR-BU2 brake units can be connected in parallel for increased braking capacity.

%ED or Time at Short-Time Rating When Braking Torque is 100%


Brake Unit Model No. FR-BU2-1.5K FR-BU2-3.7K FR-BU2-7.5K FR-BU2-15K FR-BU2-30K FR-BU2-55K FR-BU2-H7.5K 460V FR-BU2-H15K FR-BU2-H30K FR-BU2-H55K Stocked Item S S S S S S S S S Stocked Item S S S S S S S S Brake Resistor Model No. BU-1500-TEIKOUKI BU-3700-TEIKOUKI BU-7.5K-TEIKOUKI FR-BR-15K-UL FR-BR-30K-UL FR-BR-55K-UL 2 x BU-3700-TEIKOUKI FR-BR-H15K-UL FR-BR-H30K-UL FR-BR-H55K-UL Brake Resistor Model No. MT-BR5-H75K 2 x MT-BR5-H75K 3 x MT-BR5-H75K 4 x MT-BR5-H75K 5 x MT-BR5-H75K 6 x MT-BR5-H75K 7 x MT-BR5-H75K 8 x MT-BR5-H75K Stocked Item S S S S S Stocked Item Motor Capacity (HP) 1 30 s. 2 30 s. 3 30 s. 30 s. 5 30 s. 30 s. 7.5 80% 80% 10 40% 40% 15 15% 65% 15% 65% 20 10% 30% 10% 30% 25 25% 90% 25% 90% 30 15% 60% 15% 60% 40 10% 30% 10% 30% 50 20% 20% 60 15% 15% 75 10% 10%

230V

Brake Unit Model No. FR-BU2-H75K 2 x FR-BU2-H75K 3 x FR-BU2-H75K 4 x FR-BU2-H75K 5 x FR-BU2-H75K 6 x FR-BU2-H75K 7 x FR-BU2-H75K 8 x FR-BU2-H75K

Motor Capacity (HP) 100 10% 40% 90% 125 5% 25% 60% 95% 150 15% 40% 70% 200 10% 20% 40% 60% 90% 250 5% 14% 25% 40% 55% 80% 300 10% 15% 25% 40% 55% 70% 350 5% 13% 20% 25% 40% 50% 400 5% 10% 15% 25% 35% 45% 450 5% 12% 15% 20% 30% 500 5% 10% 14% 15% 25% 600 5% 10% 13% 15% 700 5% 5% 10% 13% 800 5% 5% 10%

460V

Mitsubishi Electric Automation

Variable Frequency Drives 25

VARIABLE FREQUENCY DRIVES

Braking Torque (%) at Short-Time Rating of 30 Sec. for 5HP and Less Braking Torque (%) at Short-Time Rating of 15 Sec. for 7.5HP and Larger
Brake Unit Model No. FR-BU2-1.5K FR-BU2-3.7K FR-BU2-7.5K FR-BU2-15K FR-BU2-30K FR-BU2-55K FR-BU2-H15K FR-BU2-H30K FR-BU2-H55K Stocked Item S S S S S S S S Brake Resistor Model No. BU-1500-TEIKOUKI BU-3700-TEIKOUKI BU-7.5K-TEIKOUKI FR-BR-15K-UL FR-BR-30K-UL FR-BR-55K-UL FR-BR-H15K-UL FR-BR-H30K-UL FR-BR-H55K-UL Stocked Item S S S S S Motor Capacity (HP) 1 2 3 5 7.5 100% 50% 100% 50% 50% 100% 100% 10 15 20 25 30 40 50 60 75

230V

280% 200% 120% 100% 80% 70%

460V

260% 180% 160% 130% 100% 80% 300% 250% 180% 150% 280% 200% 120% 100% 80% 70% 260% 180% 160% 130% 100% 80% 300% 250% 180% 150%

70% 120% 100% 70% 120% 100%

Brake Unit Model No. FR-BU2-H75K 2 x FR-BU2-H75K 3 x FR-BU2-H75K 4 x FR-BU2-H75K 5 x FR-BU2-H75K 6 x FR-BU2-H75K 7 x FR-BU2-H75K 8 x FR-BU2-H75K

Stocked Item S S S S S S S S

Brake Resistor Model No. MT-BR5-H75K 2 x MT-BR5-H75K 3 x MT-BR5-H75K 4 x MT-BR5-H75K 5 x MT-BR5-H75K 6 x MT-BR5-H75K 7 x MT-BR5-H75K 8 x MT-BR5-H75K

Stocked Item

Motor Capacity (HP) 100 100% 200% 300% 125 80% 165% 250% 300% 150 65% 135% 200% 270% 300% 200 50% 100% 150% 200% 250% 300% 250 40% 80% 120% 160% 200% 240% 280% 300 30% 65% 100% 135% 170% 200% 235% 270% 350 28% 55% 85% 115% 140% 170% 200% 230% 400 26% 53% 80% 105% 130% 160% 185% 210% 450 22% 44% 65% 85% 110% 130% 155% 175% 500 20% 40% 60% 80% 100% 120% 140% 160% 600 33% 50% 65% 83% 100% 115% 130% 700 28% 43% 55% 70% 85% 100% 110% 800 25% 37% 50% 62% 75% 85% 100%

460V

Dynamic Braking Unit & Resistor Specifications


Brake Unit Model No. FR-BU2-1.5K FR-BU2-3.7K 230V FR-BU2-7.5K FR-BU2-15K FR-BU2-30K FR-BU2-55K FR-BU2-H7.5K FR-BU2-H15K 460V FR-BU2-H30K FR-BU2-H55K FR-BU2-H75K Stocked Item S S S S S S S S S S Brake Resistor Model No. BU-1500-TEIKOUKI BU-3700-TEIKOUKI BU-7.5K-TEIKOUKI FR-BR-15K-UL FR-BR-30K-UL FR-BR-55K-UL 2 x BU-3700-TEIKOUKI FR-BR-H15K-UL FR-BR-H30K-UL FR-BR-H55K-UL MT-BR5-H75K Stocked Item S S S S S Weight kg / lbs n/a n/a n/a 15 / 33 30 / 66 70 / 154 n/a 15 / 33 30 / 66 70 / 154 70 / 154 Resistance (Ohms) 50 30 20 8 4 2 60 32 16 8 6.5 Rated (Watts) 300 900 1800 4000 8000 16000 1800 4000 8000 16000 30000 Continuous Permissible Power (Watts) 100 300 600 990 1990 3910 600 990 1990 3910 7500

26

F700 Dynamic Braking Units and Resistors UFS Series


I I I I I

A more economical solution to regenerative braking applications. UL and cUL listing for the brake units Internal Form-C relay Adjustable DC bus brake turn-on voltage Configurable master / slave brake configuration. Allows connection of up to 5 brake units (1 master / 4 slaves)

240V Series
Braking Torque 100% For 15 Secs. Electrical Data HP kW Brake Unit Brake Resistor Continuous Permissible Power (W) Resistance (Overall) Continuous Current (Amps) 7.5 5.5 10 7.5 15 11 UFS22J 20 15 Motor Capacity 25 30 18.5 22 40 30 60 75 45 55 2 x UFS40J 2 x RUFC40J 2ea x UFS40J 4000W 2ea x RUFC40J 3.75ohms 29.2A 50 37

RUFC15J RUFC22J UFS22J 1500W RUFC15J 24ohms RUFC22J 12ohms 7A 10A

UFS40J RUFC40J UFS40J 2000W RUFC40J 7.5ohms 14.6A

460V Series
Motor Capacity Braking Torque 100% For 15 Secs. Electrical Data HP kW Brake Unit Brake Resistor Continuous Permissible Power (W) Resistance (Overall) Continuous Current (Amps) RUFC15/480 44ohms 6A RUFC15/480 7.5 5.5 10 7.5 15 11 UFS22 RUFC22/480 UFS22 2000W RUFC22/480 27ohms 7.7A 25 18.5 30 22 40 30 50 37 60 45 UFS40 RUFC40/480 UFS40 4000W RUFC40/480 15ohms 14.6 75 55

Motor Capacity Braking Torque 100% For 15 Secs. Electrical Data HP kW Brake Unit Brake Resistor Continuous Permissible Power (W) Resistance (Overall) Continuous Current (Amps) 100 75 125 90 UFS110 RUFC110/480 UFS110 8000W RUFC110/480 6.8ohms 30.7A 150 110 175 132 215 160 300 220 2 X UFS110 2 X RUFC110/480 2 x UFS110 16000W 2 x RUFC110/480 3.4ohms 61.4A 375 280

Dimensions
Model Number mm UFS20J UFS40J 240V RUFC15J RUFC22J RUFC40J UFS22 UFS40 UFS110 480V RUFC15/480 RUFC22/480 RUFC40/480 RUFC110/480 310 365 2 x 365 4 x 365 12.2 14.4 2 x 14.4 4 x 14.4 250 9.8 250 240 310 365 Height inches 9.8 9.5 12.2 14.4 100 107 100 2 x 100 4 x 100 3.9 4.2 3.9 2 x 3.9 4 x 3.9 175 195 75 2 x 75 4 x 75 6.9 7.7 3 2x3 4x3 100 3.9 75 3 mm Width inches mm 175 Depth inches 6.9 Approximate Weight kg 2.5 2.8 3.5 4.3 2.5 3.9 3.5 4.2 8.7 17.3 lbs 5.5 6.2 7.7 9.5 5.5 8.6 7.7 9.3 19.2 38.1 S S S S S S S S S S S S Stocked Item

Mitsubishi Electric Automation

Variable Frequency Drives 27

VARIABLE FREQUENCY DRIVES

F700 VFD Efficiency Values


240VAC 3-Phase Input Model Number FR-F720-00046-NA FR-F720-00077-NA FR-F720-00105-NA FR-F720-00167-NA FR-F720-00250-NA FR-F720-00340-NA FR-F720-00490-NA FR-F720-00630-NA FR-F720-00770-NA FR-F720-00930-NA FR-F720-01250-NA FR-F720-01540-NA FR-F720-01870-NA FR-F720-02330-NA Rated Watts 750 1500 2200 3700 5500 7500 11000 15000 18500 22000 30000 37000 45000 55000 Watts Loss Efficiency Watts Loss Efficiency SLD SLD LD LD 70 110 140 210 300 370 590 660 910 1050 1540 1490 1680 2210 91% 93% 94% 94% 95% 95% 95% 96% 95% 95% 95% 96% 96% 96% 60 100 130 190 260 340 530 580 810 940 1370 1320 1490 1950 92% 93% 94% 95% 95% 95% 95% 96% 96% 96% 95% 96% 97% 96% Model Number FR-F740-00023-NA FR-F740-00038-NA FR-F740-00052-NA FR-F740-00083-NA FR-F740-00126-NA FR-F740-00170-NA FR-F740-00250-NA FR-F740-00310-NA FR-F740-00380-NA FR-F740-00470-NA FR-F740-00620-NA FR-F740-00770-NA FR-F740-00930-NA FR-F740-01160-NA FR-F740-01800-NA FR-F740-02160-NA FR-F740-02600-NA FR-F740-03250-NA FR-F740-03610-NA FR-F740-04320-NA FR-F740-04810-NA FR-F740-05470-NA FR-F740-06100-NA FR-F740-06830-NA FR-F740-07700-NA FR-F740-08660-NA FR-F740-09620-NA FR-F740-10940-NA FR-F740-12120-NA 480VAC 3-Phase Input Rated Watts 750 1500 2200 3700 5500 7500 11000 15000 18500 22000 30000 37000 45000 55000 75000 90000 110000 132000 160000 185000 220000 250000 280000 315000 355000 400000 450000 500000 560000 Watts Loss Efficiency Watts Loss Efficiency SLD SLD LD LD 60 80 100 160 190 240 340 390 490 580 810 1000 1170 1510 2700 3300 3960 4800 5550 6600 7500 8400 9450 10650 12000 13500 15000 16800 18900 92% 95% 95% 96% 97% 97% 97% 97% 97% 97% 97% 97% 97% 97% 96% 96% 96% 96% 97% 96% 97% 97% 97% 97% 97% 97% 97% 97% 97% 50 80 90 140 180 220 310 350 440 520 710 930 1030 1320 2250 2700 3300 3960 4800 5550 6600 7500 8400 9450 10650 12000 13500 15000 16800 93% 95% 96% 96% 97% 97% 97% 98% 98% 98% 98% 97% 98% 98% 97% 97% 97% 97% 97% 97% 97% 97% 97% 97% 97% 97% 97% 97% 97%

General Notes: The amount of heat generated by the inverter is based on one inverter connected to one motor of the same capacity. The amount of heat generated in the above table is the amount of heat generated when the inverter is operated at its rated current. The amount of heat generated will decrease according to the motor load and usage (duty).

28

A700 Series
Mitsubishi Electrics RSV technology gives you class-leading power, control and flexibility.
I I I I

I I I

Wide Speed Range: 200:1 operating range is possible even when the drive is used open loop PLC Feature: A700 programmability provides true intelligence inside the drive a simple solution for complex applications Easy Gain Tuning: Compensates automatically for changes in load inertia to ensure smooth and consistent operation Fast Response: Up to 300 radians / second speed response means lightning fast reaction to sudden load changes USB Port: Allows simple connection to the new FRConfigurator Software for quick and easy commissioning Power Down Braking: Keeps the motor under control even if the supply power is lost Remote I / O Capability: All of the drive I/O can be read or controlled over a network

I I

Brake Transistor Circuit: Included in all sizes up to 30 Hp Integral Radio Filter: Limits Radio Noise emissions to meet EU Directive all sizes of drive Speed Control: with or without torque limit allows 200:1 Speed range, driving or overhauling Open Loop Torque Control: including torque at zero speed UL Listed for single-phase input

Voltage 240 480 600 3/4 200 Hp 3/4 800 Hp 1 500 Hp

A700 Ratings 240V Class


Output voltage: 3 phase 200-240V at 60Hz Voltage Tolerance 170-264V at 60Hz
ND (50C) 150% OL / 1 min 200% OL / 3 sec Hp (*1) 1/2 1 2 3 5 7.5 10 1/2 1 2 3 5 7.5 10 15 20 25 30 40 50 60 75 FLA 3 5 8 11 17.5 24 33 3 5 8 11 17.5 24 33 46 61 76 90 115 145 175 215 HD (50C) 200% OL / 1 min 250% OL / 3 sec Hp (*1) 1/4 1/2 1 2 3 5 7.5 1/4 1/2 1 2 3 5 7.5 10 15 20 25 30 40 50 60 FLA 1.5 3 5 8 11 17.5 24 1.5 3 5 8 11 17.5 24 33 46 61 76 90 115 145 175 LD (50C) 120% OL / 1 min 150% OL / 3 sec Hp (*1) 1 2 3 5 7.5 10 15 1 2 3 5 7.5 10 15 20 25 30 40 50 60 75 100 FLA 4.2 6.5 9.6 15.2 24 31 45 4.2 6.5 9.6 15.2 24 31 45 58 70 85 114 140 170 212 288 SLD (40C) 110% OL / 1 min 120% OL / 3 sec Hp (*1) 1 2 3 5 7.5 10 15 1 2 3 5 7.5 10 15 20 25 30 40 50/60 60 75 100/125 FLA 4.6 7.1 10.5 16.7 25 34 49 4.6 7.1 10.5 16.7 25 34 49 63 77 93 125 154 187 233 316 FR-A720-00030-NA FR-A720-00050-NA FR-A720-00080-NA FR-A720-00110-NA FR-A720-00175-NA FR-A720-00240-NA FR-A720-00330-NA FR-A720-00030-N4 FR-A720-00050-N4 FR-A720-00080-N4 FR-A720-00110-N4 FR-A720-00175-N4 FR-A720-00240-N4 FR-A720-00330-N4 FR-A720-00460-NA FR-A720-00610-NA FR-A720-00760-NA FR-A720-00900-NA FR-A720-01150-NA FR-A720-01450-NA FR-A720-01750-NA FR-A720-02150-NA A B C C C D D A (*5) B (*5) C (*5) C (*5) C (*5) D (*5) D (*5) E F F F G H H JA Forced Air Cooling Self Cooling Forced Air Cooling Self Cooling Model Number (*6) Frame Size Cooling Method

Horsepower

Regenerative Protective Braking Torque / Rating Max Value (Permissible Duty) 150% torque / 3% ED NEMA 1 (*2) 100% torque / 3% ED 100% torque / 2% ED 150% torque / 3% ED 100% torque / 3% ED 100% torque / 2% ED 20% torque / continuous (brake transistor included)

Stocked Item S S S S S S S S S S S S

UL Type 1 Plenum Rated

IP00 (*3)

20% torque / continuous

S S S

A700 Ratings 240V Class


Output voltage: 3 phase 200-240V at 60Hz Voltage Tolerance 170-264V at 60Hz DC Link Choke is included with the VFD
ND (50C) 150% OL / 1 min 200% OL / 3 sec Hp FLA 100 125 288 346 HD (50C) 200% OL / 1 min 250% OL / 3 sec Hp FLA 75 100 215 288 LD (50C) 120% OL / 1 min 150% OL / 3 sec Hp FLA 125 150 346 432 SLD (40C) 110% OL / 1 min 120% OL / 3 sec Hp FLA 150 200 380 475 Model Number (*7) Frame Size K K Cooling Method Forced Air Cooling Protective Rating Regenerative Braking Torque / Max Value (Permissible Duty) 10% torque / continuous Stocked Item

FR-A720-02880-NA FR-A720-03460-NA

IP00 (*3)

Notes: See next page.

Mitsubishi Electric Automation

Variable Frequency Drives 29

VARIABLE FREQUENCY DRIVES

A700 Ratings 480V Class


Output voltage: 3 phase 380-480V at 60Hz Voltage Tolerance 323-528V at 60Hz.
ND (50C) 150% OL / 1 min 200% OL / 3 sec Hp (*1) 1/2 1 2 3 5 7.5 10 1/2 1 2 3 5 7.5 10 15 20 25 30 40 50 60 75 FLA 1.5 2.5 4 6 9 12 17 1.5 2.5 4 6 9 12 17 23 31 38 44 57 71 86 110 HD (50C) 200% OL / 1 min 250% OL / 3 sec Hp (*1) 1/4 1/2 1 2 3 5 7.5 1/4 1/2 1 2 3 5 7.5 10 15 20 25 30 40 50 60 FLA 0.8 1.5 2.5 4 6 9 12 0.8 1.5 25 4 6 9 12 17 23 31 38 44 57 71 86 LD (50C) 120% OL / 1 min 150% OL / 3 sec Hp (*1) 1 2 3 5 7.5 10 15 1 2 3 5 7.5 10 15 20 25 30 40 50 60 75 100 FLA 2.1 3.5 4.8 7.6 11.5 16 23 2.1 3.5 4.8 7.6 11.5 16 23 29 35 43 57 70 85 106 144 SLD (40C) 110% OL / 1 min 120% OL / 3 sec Hp (*1) 1 2 3 5 7.5 10 15 1 2 3 5 7.5 10 15 20 25 30 40 50/60 60 75 100/150 FLA 2.3 3.8 5.2 8.3 12.6 17 25 2.3 3.8 5.2 8.3 12.6 17 25 31 38 47 62 77 93 116 180 FR-A740-00015-NA FR-A740-00025-NA FR-A740-00040-NA FR-A740-00060-NA FR-A740-00090-NA FR-A740-00120-NA FR-A740-00170-NA FR-A740-00015-N4 FR-A740-00025-N4 FR-A740-00040-N4 FR-A740-00060-N4 FR-A740-00090-N4 FR-A740-00120-N4 FR-A740-00170-N4 FR-A740-00230-NA FR-A740-00310-NA FR-A740-00380-NA FR-A740-00440-NA FR-A740-00570-NA FR-A740-00710-NA FR-A740-00860-NA FR-A740-01100-NA C C C C C D D C (*5) C (*5) C (*5) C (*5) C (*5) D (*5) D (*5) E E F F JA H H H IP00 (*4) 20% torque / continuous Forced Air Cooling UL Type 1 Plenum Rated 20% torque / continuous (brake transistor included) 100% torque / 2% ED Self Cooling Forced Air Cooling NEMA 1 (*2) 100% torque / 2% ED Self Cooling Model Number (*6) Frame Size Cooling Method Protective Rating Regenerative Braking Torque / Max Value (Permissible Duty)

Stocked Item

S S S S S S S S S S S S S S S

Notes: See below.

A700 Ratings 480V Class


Output voltage: 3 phase 380-480V at 60Hz Voltage Tolerance 323-528V at 60Hz DC Link Choke is included with the VFD.
ND (50C) 150% OL / 1 min 200% OL / 3 sec Hp (*1) 100 150 150 200 250 300 350 400 450 500 550 650 700 800 FLA 144 180 216 260 325 361 432 481 547 610 683 770 866 962 HD (50C) 200% OL / 1 min 250% OL / 3 sec Hp (*1) 75 100 150 150 200 250 300 350 400 450 500 550 650 700 FLA 110 144 180 216 260 325 361 432 481 547 610 683 770 866 LD (50C) 120% OL / 1 min 150% OL / 3 sec Hp (*1) 150 150 200 250 300 350 400 450 500 550 650 700 800 900 FLA 180 216 260 325 361 432 481 547 610 683 770 866 962 1094 SLD (40C) 110% OL / 1 min Model Number (*6) 120% OL / 3 sec Hp (*1) 150 200 250 300 350 400 450 500 550 650 700 800 900 1000 FLA 216 260 325 361 432 481 547 610 683 770 866 962 1094 1212 FR-A740-01440-NA FR-A740-01800-NA FR-A740-02160-NA FR-A740-02600-NA FR-A740-03250-NA FR-A740-03610-NA FR-A740-04320-NA FR-A740-04810-NA FR-A740-05470-NA FR-A740-06100-NA FR-A740-06830-NA FR-A740-07700-NA FR-A740-08660-NA FR-A740-09620-NA J J K K L L M M M N N P P P IP00 Forced Air Cooling 10% torque / continuous IP00 (*4) Frame Size Cooling Method Protective Rating Regenerative Braking Torque / Max Value (Permissible Duty)

Stocked Item

S S S S S S S S S

Notes: 1. Motor ratings shown are intended as guidelines only - based on 4 pole standard inductions motors. 2. UL Type 1 version drives are available replace -NA suffix with -N4. 3. Conduit adapter option required for types 01150 03460. See page 34. 4. Conduit adapter option required for types 00570 05470. See page 34. 5. Depth is slightly extended to meet UL Type 1 requirements. 6. For single phase input, derate output current by 40% (Models up to FR-A720-02880-NA and FR-A740-03610-NA)

30

A700 Ratings 600V Class


Output voltage: 3 phase 525-600V at 60Hz - Voltage Tolerance 472-660V at 60Hz
ND (40C) 150% OL / 1 min 200% OL / 3 sec. HP (*1) 1 3 5 10 20 30 50 75 FLA 1.7 4.0 6.1 12 22 33 55 84 HD (40C) 200% OL / 1 min 250% OL / 3 sec. 280% OL / 0.5 sec. HP (*1) 1/2 2 3 7 1/2 10 20 40 60 FLA 1.0 2.7 4.0 9.0 16 24 41 63 LD (40C) 120% OL / 1 min 150% OL / 3 sec. HP (*1) 1 1/2 3 5 10 25 40 60 100 FLA 2.5 5.6 8.2 16 27 41 62 99 (*2) SLD (40C) (30C for 00040 or less) 110% OL / 1 min 120% OL / 3 sec. HP (*1) 2 5 7 1/2 15 30 40 60 100 FLA 2.7 6.1 9.0 17 32 45 68 108 (*2) FR-A760-00017-NA FR-A760-00040-NA FR-A760-00061-NA FR-A760-00120-NA FR-A760-00220-NA FR-A760-00330-NA FR-A760-00550-NA FR-A760-00840-NA D E F H Forced air cooling C Self cooling UL Type 1 (*3) 100% torque / 2% ED Option S S S S S S S Model Number Frame Size Cooling Method Protective Rating Regenerative Braking Torque / DC Link Stocked Max Value Reactor Item (Permissible Duty)

20% torque / UL Type 1 continuous (brake transistor included) IP00 (*4) 20% torque / continuous

ND (50C) 150% OL / 1 min 200% OL / 3 sec. HP (*1) 100 125 150 200 250 300 400 FLA 104 131 152 221 255 304 402

HD (40C) 200% OL / 1 min 250% OL / 3 sec. 280% OL / 0.5 sec. HP (*1) 75 100 125 150 200 250 300 FLA 84 104 131 152 202 255 304

LD (50C) 120% OL / 1 min 150% OL / 3 sec. HP (*1) 125 150 200 250 300 400 500 FLA 131 152 221 255 304 402 496

SLD (40C) 110% OL / 1 min 120% OL / 3 sec. HP (*1) 150 150 250 300 350 450 550 FLA 144 167 243 289 336 442 545 FR-A760-01040-NA FR-A760-01310-NA FR-A760-01520-NA FR-A760-02210-NA FR-A760-02550-NA FR-A760-03040-NA FR-A760-04020-NA L M N IP00 J Forced air cooling IP00 (*4) Model Number Frame Size Cooling Method Protective Rating

Regenerative Braking Torque / DC Link Stocked Max Value Reactor Item (Permissible Duty) S S 20% torque / continuous S Standard S S

Notes: 1. Motor ratings shown are intended as guidelines only - based on 4 pole standard induction motors. 2. To utilize these ratings, DC Link reactor is required. 3. These models supplied with an externally connected brake resistor. When the external brake resistor is used, protective rating is open type (NEMA1). 4. Conduit adapter option required for types 00550-03040. See page 34.

Mitsubishi Electric Automation

Variable Frequency Drives 31

VARIABLE FREQUENCY DRIVES

A700 Terminal Connection Diagram

A700 Control Terminal Layout


RL SE

A1 RM

B1 RH SU

C1 RT IPF

A2 AU OL

B2

C2

10E

10 SD

2 FM

4 AM CS 1 PC

STOP MRS FU SD SD

RES STF

RUN

STR

JOG

32

A700 General Specifications


Control Method Output Frequency Range Frequency Setting Resolution Frequency Accuracy Analog Input Soft-PWM control/high carrier frequency PWM control (selectable from among V/F control, advanced magnetic flux vector control and real sensorless vector control) /
vector control (when used with option FR-A7AP) (*1)

0.2 to 400Hz 0.015Hz/0 to 60Hz (terminal 2, 4: 0 to 10V/12 bit); 0.03Hz/0 to 60Hz (terminal 2, 4: 0 to 5V/11 bit, 0 to 20mA/about 11 bit, terminal 1: 0 to 10V/12 bit) 0.06Hz/0 to 60Hz (terminal 1: 0 to 5V/11 bit) 0.01Hz Within 0.2% of the max. output frequency (25C 10C) Within 0.01% of the set output frequency Base frequency can be set from 0 to 400Hz Constant torque/variable torque pattern or adjustable 5 points V/F can be selected 200% 0.3Hz (up to frame size C), 150% 0.3Hz (Frame Size D and above) (under real sensorless vector control or vector control) Manual torque boost 0 to 3600s (acceleration and deceleration can be set individually), linear or S-pattern acceleration/deceleration mode, backlash measures acceleration/deceleration can be selected. Operation frequency (0 to 120Hz), operation time (0 to 10s), operation voltage (0 to 30%) variable Operation current level can be set (0 to 220% adjustable), whether to use the function or not can be selected Torque limit value can be set (0 to 400% variable) Terminal 2: 4: 0 to 10V, 0 to 5V, 4 to 20mA can be selected Terminal 1:-10 to +10V, -5 to +5V can be selected Input using the setting dial of the operation panel or parameter unit. Four-digit BCD or 16 bit binary (when used with option FR-A7AX) Forward and reverse rotation or start signal automatic self-holding input (3-wire input) can be selected. Select any twelve signals using Pr. 178 to Pr. 189 (input terminal function selection) from among multi speed selection, remote setting, stop-on-contact, second function selection, third function selection, terminal 4 input selection, JOG operation selection, selection of automatic restart after instantaneous power failure, flying start, external thermal relay input, inverter operation enable signal (FR-HC/FR-CV connection), FR-HC connection (instantaneous power failure detection), PU operation/external inter lock signal, external DC injection brake operation start, PID control enable terminal, brake opening completion signal, PU operation/external operation switchover, load pattern selection forward rotation reverse rotation boost, V/F switching, load torque high-speed frequency, S-pattern acceleration/deceleration C switchover, pre-excitation, output stop, start self-holding selection, control mode changing, torque limit selection, start-time tuning start external input, torque bias selection 1, 2 (*1), P/PI control switchover, forward rotation command, reverse rotation command, inverter reset, PTC thermistor input, PID forward reverse operation switchover, PU-NET operation switchover, NET-external operation switchover, and command source switchover, conditional position pulse train sign (*1), conditional position droop pulse clear (*1). 100kpps Maximum/minimum frequency setting, frequency jump operation, external thermal relay input selection, polarity reversible operation, automatic restart after instantaneous power failure operation, commercial power supply-inverter switchover operation, forward/reverse rotation prevention, remote setting, brake sequence, second function, third function, multi-speed operation, original operation continuation at instantaneous power failure, stop-on-contact control, load torque high speed frequency control, droop control, regeneration avoidance, slip compensation, operation mode selection, offline auto tuning function, online auto tuning function, PID control, computer link operation (RS-485), motor end orientation (*1), machine end orientation (*1), pre-excitation, notch filter, machine analyzer (*1), easy gain tuning, speed feed forward, and torque bias (*1) Select any signals using Pr. 190 to Pr. 196 (output terminal function selection) from among inverter running, up-to-frequency, instantaneous power failure/undervoltage, overload warning, output frequency (speed) detection, second output frequency (speed) detection, third output frequency (speed) detection, regenerative brake prealarm, electronic thermal relay function pre-alarm, PU operation mode, inverter operation ready, output current detection, zero current detection, PID lower limit, PID upper limit, PID forward rotation reverse rotation output, commercial power supply-inverter switchover MC1, commercial power supply-inverter switchover MC2, commercial power supplyinverter switchover MC3, orientation completion (*1), brake opening request, fan fault output, heatsink overheat pre-alarm , inverter running/start command on, deceleration at an instantaneous power failure, PID control activated, during retry, PID output interruption, life alarm, alarm output 1, 2, 3 (power-off signal), power savings average value update timing, current average monitor, maintenance timer alarm, remote output, forward rotation output (*1), reverse rotation output (*1), low speed output, torque detection, regenerative status output (*1), start-time tuning completion, in-position completion (*1), minor failure output and alarm output. Open collector output (5 points), relay output (2 points) and alarm code of the inverter can be output (4 bit) from the open collector.

Digital Input Analog Input Digital Input Voltage / Frequency Characteristics Starting Torque Torque Boost Acceleration / Deceleration Time Setting DC Injection Brake Stall Prevention Operation Level Torque Limit Level Analog Input Frequency Setting Signal Digital Input Start Signal Operation Specifications

Input Signal

Pulse Train Input

Operational Functions

Output Signals

Operating Status

When used with In addition to the above, select any signals using Pr. 313 to Pr. 319 (extension output terminal function selection) from among control circuit capacitor life, main circuit capacitor the FR-A7AY, FRlife, cooling fan life, inrush current limit circuit life (only positive logic can be set for extension terminals of the FR-A7AR). A7AR (optional) Pulse Train Input 500kpps Pulse / Analog Output Select any signals using Pr. 54 FM terminal function selection (pulse train output) and Pr. 158 AM terminal function selection (analog output) from among output frequency, motor current (steady or peak value), output voltage, frequency setting, operation speed, motor torque, converter output voltage (steady or peak value), electronic thermal relay function load factor, input power, output power, load meter, motor excitation current, reference voltage output, motor load factor, power saving effect, regenerative brake duty, PID set point, PID measured value, motor output, torque command, torque current command, and torque monitor.

PU (FR-DU07 / FR-PU07 / FR-PU04)

Output frequency, motor current (steady or peak value), output voltage, frequency setting, running speed,motor torque, overload, converter output voltage (steady or peak value), electronic thermal relay function load factor, input power, output power, load meter, motor excitation current, cumulative energization time, actual operation time, motor load factor, cumulative power, energy saving effect, cumulative saving power, regenerative brake duty, PID set point, PID measured value, PID deviation, inverter I/O terminal monitor, input terminal option monitor (*2), output terminal option monitor (*2), option fitting status (*3), terminal assignment status (*3), torque command, torque current command, feed back pulse (*1), motor output Alarm definition is displayed when the protective function is activated, the output voltage/current/frequency/cumulative energization time right before the protection function was Alarm Definition activated and past 8 alarm definitions are stored. Interactive Operation guide/trouble shooting with a help function (*3) Guidance Operating Status Overcurrent during acceleration, overcurrent during constant speed, overcurrent during deceleration, overvoltage during acceleration, overvoltage during constant speed, overvoltage during deceleration, inverter protection thermal operation, motor protection thermal operation, heatsink overheat, instantaneous power failure occurrence, undervoltage, input phase failure, motor overload, output side earth (ground) fault overcurrent, output short circuit, main circuit element overheat, output phase failure, external thermal relay operation, PTC thermistor operation, option alarm, parameter error, PU disconnection, retry count excess, CPU alarm, operation panel power supply short circuit, 24VDC power output short circuit, output current detection value excess, inrush current limit circuit alarm, communication alarm (inverter), USB error, opposite rotation deceleration error, analog input error, fan fault, overcurrent stall prevention, overvoltage stall prevention, regenerative brake prealarm, electronic thermal relay function prealarm, PU stop, maintenance timer alarm (*2), brake transistor alarm, parameter write error, copy operation error, operation panel lock, parameter copy alarm, speed limit indication, encoder no-signal (*1), speed deviation large (*1), overspeed (*1), position error large (*1), encoder phase error (*1) -10C to +50C (non-freezing) 90%RH maximum (non-condensing) -20C to +65C Indoors (without corrosive gas, flammable gas, oil mist, dust and dirt etc.) Maximum 1000m above sea level, 0.6 G or less (*5) (conforms to JIS C 60068-2-6)

Indication Environment

Protective / Warning Function

Ambient Temperature Ambient Humidity Storage Temperature (*4) Atmosphere Altitude / Vibration

Notes: 1. Available only when the option (FR-A7AP) is mounted 2. Can be displayed only on the operation panel (FR-DU07). 3. Can be displayed only on the parameter unit (FR-PU07/FR-PU04). 4. Temperature applicable for a short period in transit, etc. 5. 2.9m/s2 or less for the FR-A740-03250 or more.

Mitsubishi Electric Automation

Variable Frequency Drives 33

VARIABLE FREQUENCY DRIVES

A700 Options

Function/Options
Model No. 120VAC Control Input Analog I/O Encoder Feedback Relay Output Function 12 Bit Digital Input Digital Output Ext. Analog Output BiPolar Analog Input High Res Analog Input Motor Thermistor CC-Link Communiction ControlNET (*1) DeviceNet EtherNET IP (*1) LonWorks Profibus DP SSCNET III FR-A7NC FR-A7NCN FR-A7ND FR-A7NE FR-A7NL FR-A7NP FR-A7NS S S S S S S S FR-A7AZ FR-A7AC FR-A7AN FR-A7AP FR-A7AR FR-A7AX FR-A7AY Stocked item S S S S S S

Instruction Manuals
Description Model Number FR-A700 Installation Manual Contains instructions for installer and parameter list. (Included with VFD, plus CD with all versions of IB(NA)0600254 VFD and option manuals.) FR-A700 Basic Manual Contains wiring details, VFD layout drawings, alarm definitions and parameter list. FR-A700 Applied Manual Contains wiring details, VFD layout drawings, alarm definitions and complete parameter list with definitions and setting examples. FR-A700 PLC Programming Manual Contains complete instruction sets for PLC feature. FR-PU07 Manual Contains complete instruction sets and screen definitions.
Manuals available for download at www.meau.com

IB(NA)0600225

IB(NA)0600255

IB(NA)0600262 IB(NA)0600240

Building Management Options


Gateway Communication Network Type/ Model No. Ethernet I/P Modbus TCP/IP Metasys N2 Siemens FLN BacNET MSTP BacNET IP Modbus RTU Stocked Item FR-A7N-ETH (*1, *2) x x x s FR-A7N-XLT (*1, *2) x x x x s ETH-200 (*1, *3, *4) x x XLTR-200 (*1, *3, *4) x x

Note: Notify factory at time of order so that firmware support can be verified.

External Heatsink Attachment


Drive Model A720 00080 to 00175 00240, 00330 00460 00610 to 00900 01150 01450, 01750 A740 00025 to 00090 00120, 00170 00230, 00310 00380, 00440 00570 00710 to 01100 01440 01800 02160, 02600 A760 00017, 00040, 00061 00120 00220 00330 00550, 00840 01040, 01310, 01520 Model Number FR-A7CN01 FR-A7CN02 FR-A7CN03 FR-A7CN04 FR-A7CN05 FR-A7CN06 FR-A7CN07 FR-A7CN08 FR-A7CN09 FR-A7CN10 FR-A7CN11 Stocked Item S S S S S S S

Notes: 1. For additional information visit www.iccdesigns.com 2. Physically mounts within VFD and powered by VFD 3. Communication to multiple VFDs is possible 4. Mounted and powered external to VFD

Conduit Attachments
Model Number FR-A7FN05 Drive Model A720 (*1, *2) 00900 01150 01450, 01750 02880, 03460 A740 (*1, *2) 00770 00930, 01160 01440, 01800 02160, 2600 03250, 03610 04320, 04810, 05470 A760 (*2) 00550, 00840 01040, 01310, 01520 02210, 02550 03040 Stocked Item S S S S S S

02150

Software
Model Number FR-Configurator Description Programming and diagnostic software Stocked Item S

FR-A7FN06 FR-A7FN07 FR-A7FN-11 (*3) FR-A7FN-12 (*3) FR-A7FN-13 (*3)

F700 Demonstration Unit


Model Number VFD-A700DEMO VFD-MOTORENC-DEMO Description Includes A720 1/2HP, pre-wired digital input switches, LED outputs, two potentiometers, analog meter and encoder option Includes 1/2HP motor and encoder with quick connections to VFDA700-DEMO Stocked Item S S

FR-A7FN-14 (*3)

Notes: 1. FR-A720-00460 to 00760 & FR-A740-00230 to 00440 are UL Type 1: the conduit adapter is included as standard. 2. FR-A700 smaller than listed above, the UL Type 1 version (conduit adapter standard) is a special type: Change from suffix -NA to -N4. 3. Mounting hardware included for standard DC chokes which ship with VFD.

34

Factory Supplied DC Link Chokes


Standard With VFD Drive Model FR-A740-01440-NA FR-A740-01880-NA FR-A740-02160-NA FR-A740-02600-NA FR-A740-03250-NA FR-A740-03610-NA FR-A740-04320-NA FR-A740-04810-NA FR-A740-05470-NA FR-A740-06100-NA FR-A740-06830-NA FR-A740-07700-NA FR-A740-08660-NA FR-A740-09620-NA DC Link Model No. FR-HEL-H110K FR-HEL-H132K FR-HEL-H160K FR-HEL-H185K FR-HEL-H220K FR-HEL-H250K FR-HEL-H280K FR-HEL-H315K FR-HEL-H355K FR-HEL-H400K FR-HEL-H450K FR-HEL-H500K FR-HEL-H560K FR-HEL-H630K mH 0.246 0.204 0.171 0.148 0.124 0.109 0.098 0.087 0.077 0.069 0.061 0.055 0.049 0.044 Amps 233 281 335 389 462 524 585 658 742 836 940 1045 1170 1317 Height 13.4 (340) 15.9 (405) 15.9 (405) 15.9 (405) 15.9 (405) 17.3 (440) 17.3 (440) 19.5 (495) 19.5 (495) 19.7 (500) 19.7 (500) 17.8 (455) 18.1 (460) 18.1 (460) Dimensions inches (mm) Width 5.9 (150) 6.9 (175) 6.9 (175) 6.9 (175) 6.9 (175) 7.5 (190) 7.5 (190) 8.3 (210) 8.3 (210) 8.7 (220) 8.7 (220) 8.5 (215) 8.5 (215) 8.5 (215) Depth 7.7 (195) 7.9 (200) 8 (205) 9.4 (240) 9.4 (240) 9.8 (250) 10 (255) 9.8 (250) 9.8 (250) 9.8 (250) 10.6 (270) 13.6 (345) 14.2 (360) 14.2 (360) Approx Weight lb (kg) 22 (48) 26 (57) 28 (62) 29 (64) 30 (66) 35 (77) 38 (84) 42 (92) 46 (101) 50 (110) 57 (125) 67 (147) 85 (187) 95 (209)

A700 Frame Size


Drive Height x Width x Depth Frame Size Height A B C D E F G H J JA K L M N P 10.2 (260) 10.2 (260) 10.2 (260) 10.2 (260) 11.8 (300) 15.8 (400) 21.7 (550) 21.7 (550) 27.6 (700) 24.4 (620) 29.1 (740) 39.8 (1010) 39.8 (1010) 52.4 (1330) 62.2 (1580) Dimensions inches (mm) Width 4.3 (110) 4.3 (110) 5.9 (150) 8.7 (220) 8.7 (220) 9.8 (250) 12.8 (325) 17.1 (435) 18.3 (465) 18.3 (465) 18.3 (465) 19.6 (498) 26.8 (680) 31.1 (790) 39.2 (995) Depth 4.3 (110) 4.9 (125) 5.5 (140) 6.7 (170) 7.5 (190) 7.5 (190) 7.7 (195) 9.8 (250) 9.8 (250) 11.8 (300) 14.2 (360) 15 (380) 15 (380) 17.3 (440) 17.3 (440) Weight Without Reactor lbs (kg) 4.2 (1.9) 5 (2.3) 9.3 (4.2) 17.7 (8) 19.4 (8.8) 32.6 (14.8) 77.1 (35) 134.4 (61) 134.4 (61) 176.2 (80) 244.5 (111) 378.9 (172) 385 (175) 572 (260) 814 (370)

Parameter Units / Parameter Copy Units


Parameter units are used for operator control, reading and writing parameters, and drive monitoring. Parameter Copy Units also read the drive parameter settings and copy them into non-volatile memory, and can write them into other drives.
Model Number FR-CB201 FR-CB203 FR-CB205 FR-DU07 Description Extension cable straight plugs on both ends 1 meter. Extension cable straight plugs on both ends 3 meters. Extension cable straight plugs on both ends 5 meters. Control Panel for A700 LCD Multi-lingual Parameter Copy Unit (English, French, Spanish, German, Italian, Swedish, Finnish, Japanese) for operator control, parameter read/write and monitoring. Stores settings in non-volatile memory. Built-in parameter copy capability. (F/A700 based) FR-DU07 panel mounting adapter LCD Multi-lingual Parameter Copy Unit (English, French, Spanish, German, Italian, Swedish, Finnish, Japanese) for operator control, parameter read/write and monitoring. Serial Communication Cable Battery Powered PU07 Stocked Item S S S S

FR-PU07

FR-ADP FR-PU04 SC-FRPC FR-PU07-BB

S S S S

Mitsubishi Electric Automation

Variable Frequency Drives 35

VARIABLE FREQUENCY DRIVES

A700 Dynamic Braking


All Mitsubishi Electric VFDs have some inherent braking capability. During controlled deceleration, motor regenerative losses are dissipated in the motor, wire, and VFD circuitry. The built-in DC injection braking allows for low speed braking and stopping. When the above capabilities are inadequate for an application, it is necessary to add a power transistor brake unit and resistor unit in series across the DC bus. Motor regeneration causes the DC bus voltage to increase, and when the voltage exceeds a specified threshold, the transistor turns on to pass current through the resistor. Motor kinetic energy is converted to heat energy. VFD overcurrent and overvoltage protective circuits are active at all times, and will fault-trip the VFD if the brake size is inadequate. Two main factors must be considered when sizing the brake, the effective duty cycle (%ED) and the short time duty rating. The effective duty cycle is increased when an external resistor is added. It is preferable to profile the effective duty cycle of the units of time. With this information, the short time duty is known and the %ED can be calculated, as shown in the below example. %ED = Braking time / total time for complete operating cycle x 100 Example: Complete cycle is: 5 sec: Acceleration time to reach set speed 60 sec: Run time at set speed 3 sec: Deceleration time to come to a complete stop 12 sec: Time period motor remains stopped
Instruction Manual Model FR-BU/BR-C Model Number IB(NA)66403 Stocked Item

%ED = 3 / (5 + 60 + 3 + 12) * 100 = 3.6% The tables shown assume 100% brake torque, when brake torque is represented by its percentage to the rated torque of the applied motor. Torque (kg.m) = 974 * Power (kW) / Speed (rpm).

Dynamic Braking Unit For 230VAC Braking Torque = 100%


Resistor Kit Model Number FR-ABR-0.4K FR-ABR-0.75K FR-ABR-2.2K FR-ABR-3.7K FR-ABR-5.5K FR-ABR-7.5K FR-ABR-11K FR-ABR-15K (2 resistors in parallel) FR-ABR-22K (2 resistors in parallel) Stocked Item S S S S S S S S S Weight kg / lbs 0.2 / 0.5 0.4 / 0.9 0.5 / 1.1 0.8 / 1.8 1.3 / 2.9 2.2 / 4.9 3.4 (7.5) 2.4 (5.3) x2 3.3 (6.6) x2 Resistance (Ohms) 200 100 60 40 25 20 13 18/2 13/2 Rated (W) 80 150 250 300 500 800 Motor (Hp) 1/2 1 2/3 5 7.5 10 15 20 25 30 Drive Model A720 00030 00050 00080/00110 00175 00240 00330 00460 00610 00760 00900 % ED 10% 10% 10% 10% 10% 10% 6% 6% 6% 6%

Dynamic Braking Unit For 460-480VAC Braking Torque = 100%


Drive Model Resistor Kit Model Number FR-ABR-H0.4K FR-ABR-H0.75K FR-ABR-H1.5K FR-ABR-H2.2K FR-ABR-H3.7K FR-ABR-H5.5K FR-ABR-H7.5K FR-ABR-H11K FR-ABR-H15K (2 resistors in series) FR-ABR-H22K (2 resistors in parallel) Stocked Item S S S S S S S S S S Weight kg / lbs 0.2 / 0.5 0.2 / 0.5 0.4 / 0.9 0.5 / 1.1 0.8 / 1.8 1.3 / 2.9 2.2 / 4.9 3.2 (7.1) 2.4 (5.3) x2 3.3 (6.6) x2 Resistance (Ohms) 1200 700 350 250 150 110 75 52 18 x 2 52 / 2 Rated (W) 60 80 150 250 300 500 800 1000 1600 Motor (Hp) 0.5 1 2 3 5 7.5 10 15 20 25 30 A740 00015 00025 00040 00060 00090 00120 00170 00230 00310 00380 00440 % ED 10% 10% 10% 10% 10% 10% 10% 6% 6% 6% 6%

Dynamic Braking Unit For 600VAC Braking Torque = 100%


Braking Unit Model Number Stocked Item Weight kg / lbs Resistor Kit Model Number FR-BR-C3.7K (*2) S 5 / 11 FR-BR-C7.5K (*2) Stocked Item Weight kg / lbs 10 / 22 15 / 33 Resistance (Ohms) 200 100 Rated (W) 1200 2400 Motor (Hp) 3 5 5 7.5 10 10 15 20 25 30 25 30 40 50 60 75 Drive Model A760 % ED 00040 30 00061 10 00061 40 20 00120 10 00120 85 40 00220 20 15 00330 10 90 00330 60 30 00550 20 15 00840 10

FR-BU-C7.5K (*2)

FR-BU-C22K (*2)

5 / 11

FR-BR-C22K (*2)

30 / 66

31

4800

FR-BU-C55K (*2)

9 / 20

FR-BR-C55K (*2)

70 / 300

13

9600

Note: 1. The FR-A720-00030 to 00460 and FR-A740-00015 to 00230 have a built-in braking transistor. 2.FR-BU-C

and FR-BR-C

are CSA listed.

36

Dynamic Braking Options


Select the brake unit according to the motor capacity. To obtain braking torque greater than 200%, use a larger inverter capacity. Up to 10 FR-BU2 brake units can be connected in parallel for increased braking capacity.

%ED or Time at Short-Time Rating When Braking Torque is 100%


Brake Unit Model Number FR-BU2-1.5K FR-BU2-3.7K FR-BU2-7.5K FR-BU2-15K FR-BU2-30K FR-BU2-55K FR-BU2-H7.5K 460V FR-BU2-H15K FR-BU2-H30K FR-BU2-H55K Stocked Item S S S S S S S S S Stocked Item S S S S S S S S Brake Resistor Model Number BU-1500-TEIKOUKI BU-3700-TEIKOUKI BU-7.5K-TEIKOUKI FR-BR-15K-UL FR-BR-30K-UL FR-BR-55K-UL 2 x BU-3700-TEIKOUKI FR-BR-H15K-UL FR-BR-H30K-UL FR-BR-H55K-UL Brake Resistor Model Number MT-BR5-H75K 2 x MT-BR5-H75K 3 x MT-BR5-H75K 4 x MT-BR5-H75K 5 x MT-BR5-H75K 6 x MT-BR5-H75K 7 x MT-BR5-H75K 8 x MT-BR5-H75K Stocked Item S S S S S Stocked Item Motor Capacity (HP) 1 30 s. 2 30 s. 3 30 s. 30 s. 5 30 s. 30 s. 7.5 80% 80% 10 40% 40% 15 15% 65% 15% 65% 20 10% 30% 10% 30% 25 25% 90% 25% 90% 30 15% 60% 15% 60% 40 10% 30% 10% 30% 50 20% 20% 60 15% 15% 75 10% 10%

230V

Brake Unit Model Number FR-BU2-H75K 2 x FR-BU2-H75K 3 x FR-BU2-H75K 4 x FR-BU2-H75K 5 x FR-BU2-H75K 6 x FR-BU2-H75K 7 x FR-BU2-H75K 8 x FR-BU2-H75K

Motor Capacity (HP) 100 10% 40% 90% 125 5% 25% 60% 95% 150 15% 40% 70% 200 10% 20% 40% 60% 90% 250 5% 14% 25% 40% 55% 80% 300 10% 15% 25% 40% 55% 70% 350 5% 13% 20% 25% 40% 50% 400 5% 10% 15% 25% 35% 45% 450 5% 12% 15% 20% 30% 500 5% 10% 14% 15% 25% 600 5% 10% 13% 15% 700 5% 5% 10% 13% 800 5% 5% 10%

460V

Braking Torque (%) at Short-Time Rating of 30 Sec. for 5HP and Less Braking Torque (%) at Short-Time Rating of 15 Sec. for 7.5HP and Larger
Brake Unit Model Number FR-BU2-1.5K FR-BU2-3.7K FR-BU2-7.5K FR-BU2-15K FR-BU2-30K FR-BU2-55K FR-BU2-H15K FR-BU2-H30K FR-BU2-H55K Stocked Stocked Brake Resistor Model Number Item Item S S S S S S S S BU-1500-TEIKOUKI BU-3700-TEIKOUKI BU-7.5K-TEIKOUKI FR-BR-15K-UL FR-BR-30K-UL FR-BR-55K-UL FR-BR-H15K-UL FR-BR-H30K-UL FR-BR-H55K-UL S S S S S Motor Capacity (HP) 1 2 3 5 100% 50% 100% 50% 50% 100% 100% 7.5 10 15 20 25 80% 30 70% 40 50 60 75

230V

280% 200% 120% 100%

460V

260% 180% 160% 130% 100% 80% 70% 300% 250% 180% 150% 120% 100% 280% 200% 120% 100% 80% 70% 260% 180% 160% 130% 100% 80% 70% 300% 250% 180% 150% 120% 100%

Brake Unit Model Number FR-BU2-H75K 2 x FR-BU2-H75K 3 x FR-BU2-H75K 4 x FR-BU2-H75K 5 x FR-BU2-H75K 6 x FR-BU2-H75K 7 x FR-BU2-H75K 8 x FR-BU2-H75K

Stocked Item S

Brake Resistor Model Number MT-BR5-H75K 2 x MT-BR5-H75K 3 x MT-BR5-H75K 4 x MT-BR5-H75K 5 x MT-BR5-H75K 6 x MT-BR5-H75K 7 x MT-BR5-H75K 8 x MT-BR5-H75K

Stocked Item

Motor Capacity (HP) 100 100% 200% 300% 125 80% 165% 250% 300% 150 65% 135% 200% 270% 300% 200 50% 100% 150% 200% 250% 300% 250 40% 80% 120% 160% 200% 240% 280% 300 30% 65% 100% 135% 170% 200% 235% 270% 350 28% 55% 85% 115% 140% 170% 200% 230% 400 26% 53% 80% 105% 130% 160% 185% 210% 450 22% 44% 65% 85% 110% 130% 155% 175% 500 20% 40% 60% 80% 100% 120% 140% 160% 600 33% 50% 65% 83% 100% 115% 130% 700 28% 43% 55% 70% 85% 100% 110% 800 25% 37% 50% 62% 75% 85% 100%

460V

Mitsubishi Electric Automation

Variable Frequency Drives 37

VARIABLE FREQUENCY DRIVES

Dynamic Braking Unit & Resistor Specifications


Brake Unit Model Number FR-BU2-1.5K FR-BU2-3.7K FR-BU2-7.5K FR-BU2-15K FR-BU2-30K FR-BU2-55K FR-BU2-H7.5K FR-BU2-H15K FR-BU2-H30K FR-BU2-H55K FR-BU2-H75K Stocked Item S S S S S S S S S S Brake Resistor Model Number BU-1500-TEIKOUKI BU-3700-TEIKOUKI BU-7.5K-TEIKOUKI FR-BR-15K-UL FR-BR-30K-UL FR-BR-55K-UL 2 x BU-3700-TEIKOUKI FR-BR-H15K-UL FR-BR-H30K-UL FR-BR-H55K-UL MT-BR5-H75K Stocked Item S S S S S Weight kg / lbs n/a n/a n/a 15 / 33 30 / 66 70 / 154 n/a 15 / 33 30 / 66 70 / 154 70 / 154 Resistance (Ohms) 50 30 20 8 4 2 60 32 16 8 6.5 Continuous Rated (Watts) Permissible Power (Watts) 300 900 1800 4000 8000 16000 1800 4000 8000 16000 30000 100 300 600 990 1990 3910 600 990 1990 3910 7500

230V

460V

A700 Dynamic Braking Units and Resistors UFS Series


I I I I I

A more economical solution to regenerative braking applications. UL and cUL listing for the brake units Internal Form-C relay Adjustable DC bus brake turn-on voltage Configurable master / slave brake configuration. Allows connection of up to 5 brake units (1 master / 4 slaves)

240V Series
Braking Torque 100% for 15 secs. Electrical Data Hp kW Brake Unit Brake Resistor Continuous Permissible Power (W) Resistance (Overall) Continuous Current (Amps) 7.5 5.5 10 7.5 15 11 UFS22J 20 15 Motor Capacity 25 30 18.5 22 40 30 50 37 60 75 45 55 2 x UFS40J 2 x RUFC40J 2ea x UFS40J 4000W 2ea x RUFC40J 3.75ohms 29.2A

RUFC15J RUFC22J UFS22J 1500W RUFC15J 24ohms RUFC22J 12ohms 7A 10A

UFS40J RUFC40J UFS40J 2000W RUFC40J 7.5ohms 14.6A

460V Series
Braking Torque 100% for 15 secs. Electrical Data Hp kW Brake Unit Brake Resistor Continuous Permissible Power (W) Resistance (Overall) Continuous Current (Amps) 7.5 5.5 10 7.5 15 11 UFS22 RUFC15/480 RUFC15/480 44ohms 6A RUFC22/480 UFS22 2000W RUFC22/480 27ohms 7.7A 25 18.5 Motor Capacity 30 22 40 30 50 37 60 75 45 55 UFS40 RUFC40/480 UFS40 4000W RUFC40/480 15ohms 14.6A

Braking Torque 100% for 15 secs. Electrical Data

Hp kW Brake Unit Brake Resistor Continuous Permissible Power (W) Resistance (Overall) Continuous Current (Amps)

100 75

125 90

150 110

Motor Capacity 175 132

215 160

UFS110 RUFC110/480 UFS110 8000W RUFC110/480 6.8ohms 30.7A

300 375 220 280 2 X UFS110 2 X RUFC110/480 2 x UFS110 16000W 2 x RUFC110/480 3.4ohms 61.4A

38

Dimensions
Model Number mm UFS20J UFS40J RUFC15J RUFC22J RUFC40J UFS22 UFS40 UFS110 RUFC15/480 RUFC22/480 RUFC40/480 RUFC110/480 250 240 310 365 250 310 365 2 x 365 4 x 365 Height inches 9.8 9.5 12.2 14.4 9.8 12.2 14.4 2 x 14.4 4 x 14.4 100 3.9 75 3 mm Width inches mm 175 Depth inches 6.9 Approximate Weight kg 2.5 2.8 3.5 4.3 2.5 3.9 3.5 4.2 8.7 17.3 lbs 5.5 6.2 7.7 9.5 5.5 8.6 7.7 9.3 19.2 38.1 Stocked Item S S S S S S S S S S S S

240V

100 107 100 2 x 100 4 x 100

3.9 4.2 3.9 2 x 3.9 4 x 3.9

175 195 75 2 x 75 4 x 75

6.9 7.7 3 2x3 4x3

480V

A700 VFD Efficiency Values ND Rating Based


240VAC 3-Phase Input Rated Watts 400 750 1500 2200 3700 5500 7500 11000 15000 18500 22000 30000 37000 45000 55000 Watts Loss 50 70 110 140 190 260 360 520 670 770 940 1050 1270 1610 1880 480VAC 3-Phase Input Rated Watts 400 750 1500 2200 3700 5500 7500 11000 15000 18500 22000 30000 37000 45000 55000 75000 90000 Watts Loss 50 65 75 100 150 200 250 300 400 550 650 800 1100 1300 1550 1900 2400 2500 3000 4000 4200 5000 5500 6500 7000 8000 9000 Factory Supplied DC Choke Watts Loss 130 130 140 140 170 230 240 270 300 360 360 450 450 470 600VAC 3-Phase Input Rated Watts 750 2200 3700 7500 15000 22000 37000 55000 75000 90000 111000 132000 185000 220000 280000 355000 400000 Watts Loss 40 70 110 160 260 410 650 940 1500 1800 2200 2600 3200 3700 4800 6000 7500 Factory Supplied DC Choke Watts Loss 100 120 140 180 200 230 310 340 390

Model Number

Efficiency

Model Number

Efficiency

Model Number

Efficiency

FR-A720-00030-NA FR-A720-00050-NA FR-A720-00080-NA FR-A720-00110-NA FR-A720-00175-NA FR-A720-00240-NA FR-A720-00330-NA FR-A720-00460-NA FR-A720-00610-NA FR-A720-00760-NA FR-A720-00900-NA FR-A720-01150-NA FR-A720-01450-NA FR-A720-01750-NA FR-A720-02150-NA

88% 91% 93% 94% 95% 95% 95% 95% 96% 96% 96% 97% 97% 96% 97%

FR-A740-00015-NA FR-A740-00025-NA FR-A740-00040-NA FR-A740-00060-NA FR-A740-00090-NA FR-A740-00120-NA FR-A740-00170-NA FR-A740-00230-NA FR-A740-00310-NA FR-A740-00380-NA FR-A740-00440-NA FR-A740-00570-NA FR-A740-00710-NA FR-A740-00860-NA FR-A740-01100-NA FR-A740-01440-NA FR-A740-01800-NA

88% 91% 95% 95% 96% 96% 97% 97% 97% 97% 97% 97% 97% 97% 97% 97% 97% 98% 98% 98% 98% 98% 98% 98% 98% 98% 98% 98% 98%

FR-A760-00017-NA FR-A760-00040-NA FR-A760-00061-NA FR-A760-00120-NA FR-A760-00220-NA FR-A760-00330-NA FR-A760-00550-NA FR-A760-00840-NA FR-A760-01040-NA FR-A760-01310-NA FR-A760-01520-NA FR-A760-02210-NA FR-A760-02550-NA FR-A760-03040-NA FR-A760-04020-NA FR-A760-04960-NA FR-A760-05890-NA

95% 97% 97% 98% 98% 98% 98% 98% 98% 98% 98% 98% 98% 98% 98% 98% 98%

FR-A740-02160-NA 110000 FR-A740-02600-NA 132000 FR-A740-03250-NA 160000 FR-A740-03160-NA 185000 FR-A740-04320-NA 220000 FR-A740-04810-NA 250000 FR-A740-05470-NA 280000 FR-A740-06100-NA 315000 FR-A740-06830-NA 355000 FR-A740-07700-NA 400000

FR-A740-08660-NA 450000 10500 FR-A740-09620-NA 500000 11500

Notes: 1. The amount of heat generated by the inverter is based on one inverter connected to one motor of the same capacity. 2. The amount of heat generated in the above table is the amount of heat generated when the inverter is operated at its rated current. 3. The amount of heat generated will decrease according to the motor load and usage (duty).

Mitsubishi Electric Automation

Variable Frequency Drives 39

VARIABLE FREQUENCY DRIVES

V500 Series
Variable Frequency Drives True, Closed Loop Vector Control

This series achieves high precision and fast response that exceeds the performance of conventional general-purpose inverters. They can be used in specialized applications such as line control and elevators.
By incorporating our original all-digital vector control, high starting torque and high speed response have been made possible for both velocity and torque control modes.
I I I I I I I I I I I

2 to 75 Horsepower at 240V 2 to 75 Horsepower at 480V 100% continuous torque at Zero speed Auto Tuning to other manufacturers constant torque motor with encoder Easy to use Parameter Unit

4-Quadrant torque control standard Multiple parameters for tailoring to a wide variety of applications Simple positioning included as standard DC Link Reactor standard (V500L) Peripheral devices such as power regenerative converter (FR-CV, FR-RC, MT-RC) available Communications options: DeviceNet, Profibus DP, CC-Link, Modbus Plus, SSCNet

Constant Torque Hp 2 3 5 7.5 10 15 20 25 30 40 50 60 75 Output Amps 9.0 13.0 20.0 28.5 37.5 54 72.8 88 103.5 126.5 166.8 198.0 264.0

Model Number

Stocked Item

Constant Torque Hp 2 3 5 7.5 10 15 20 25 30 40 50 60 75 Output Amps 4.5 6.5 10.0 14.5 18.5 27.5 35.5 44.0 51.8 67.0 86.0 99.0 132.0

Model Number

Stocked Item

3-Phase 240VAC Input / Output FR-V520-1.5K-NA FR-V520-2.2K-NA FR-V520-3.7K-NA FR-V520-5.5K-NA FR-V520-7.5K-NA FR-V520-11K-NA FR-V520-15K-NA FR-V520-18.5K-NA FR-V520-22K-NA FR-V520-30K-NA FR-V520-37K-NA FR-V520-45K-NA FR-V520-55K-NA S S S S

3-Phase 480VAC Input / Output FR-V540-1.5K-NA FR-V540-2.2K-NA FR-V540-3.7K-NA FR-V540-5.5K-NA FR-V540-7.5K-NA FR-V540-11K-NA FR-V540-15K-NA FR-V540-18.5K-NA FR-V540-22K-NA FR-V540-30K-NA FR-V540-37K-NA FR-V540-45K-NA FR-V540-55K-NA S S S S S S S

V500 Ratings 240V Class 1.5K 55K


Model FR-V520K-NA 1.5
2 9.0

2.2
3 13.0

3.7
5 20.0

5.5

7.5

11

15

18.5

22

30

37

45

55
75 264.0

Horsepower Rating (Hp) Rated Current (A) Overload Current Rating (*1) Output Voltage (*2) Max. Time Regenerative Breaking Torque Tolerable Work Rate Rated Input, AC Volt. and Frequency Tolerable AC Voltage Fluctuation Power Tolerable Frequency Fluctuation Supply Amount of Instantaneous Voltage Drop that can be Withstood Supply (kVA) (*3) Protective Structure (JEM 1030) Cooling Method Approximate Weight kg lbs mm inches mm inches mm inches

7.5 10 15 20 25 30 40 50 60 28.5 37.5 54.0 72.8 88.0 103.5 126.5 166.0 198.0 150% 60 sec., 200% 0.5 sec. (inverse time characteristics) 3-Phase 200-220V 50 Hz, 200-230V 60 Hz 3-Phase 200-220V 50 Hz, 200-240V 60 Hz 100%/5 sec. 20% (*5) 2% ED (*5) 3-Phase 200-220 V 50 Hz, 200-240V 60 Hz 170-242V 50 Hz, 200-264V 60 Hz Continuous (*5) 3-Phase 200-220 V 50 Hz, 200-230V 60 Hz

3% ED (*5)

170-242V 50 Hz, 170-253V 60 Hz 5% When operated at or above 165 V continuously and voltage falls from rated voltage to under 165 V, 15 ms of continuous operation 5.0 6.5 10 14 19 23 33 39 48 57 77 90 123 Enclosed type (IP20) (*4) Forced air cooling 3.5 7.7 150 5.9 260 10.2 163 6.4 3.5 7.7 150 5.9 260 10.2 163 6.4 6 13.2 220 8.7 260 10.2 193 7.6 6 13.2 220 8.7 260 10.2 193 7.6 6 13.2 250 9.9 400 15.8 218 8.6 14 30.8 250 9.9 400 15.8 218 8.6 14 30.8 250 9.9 400 15.8 218 8.6 21 46.2 250 9.9 400 15.8 218 8.6 30 66 340 13.4 550 21.7 195 7.7 40 88 450 17.7 550 21.7 250 9.9 40 88 450 17.7 550 21.7 250 9.9 55 121 480 18.9 700 27.6 250 9.9 58 128 480 18.9 700 27.6 270 10.6 Open type (IP00)

Width

Height

Depth
Notes: See next page.

40

V500 Ratings 480V Class 1.5K 55K


Model FR-V540K-NA 1.5 2 4.5 2.2 3 6.5 3.7 5 10.0 5.5 7.5 11 15 18.5 22 30 40 67.0 37 50 86.0 45 60 99.0 55 75 132.0 Horsepower Rating (Hp) Rated Current (A) Overload Current Rating (*1) Output Voltage (*2) Max. Time Regenerative Breaking Torque Tolerable Work Rate Rated Input, AC Volt. and Frequency Tolerable AC Voltage Fluctuation Power Tolerable Frequency Fluctuation Supply Amount of Instantaneous Voltage Drop that can be Withstood Supply (kVA) (*3) Protective Structure (JEM 1030) Cooling System Approximate Weight kg lbs mm inches mm inches mm inches 3.5 7.7 150 5.9 260 10.2 163 6.4 3.5 7.7 150 5.9 260 10.2 163 6.4 6 13.2 220 8.7 260 10.2 193 7.6 6 13.2 220 8.7 260 10.2 193 7.6 14 30.8 250 9.9 400 15.8 218 8.6 14 30.8 250 9.9 400 15.8 218 8.6 5.0 6.5 7.5 10 15 20 25 30 14.5 18.5 27.5 35.5 44.0 51.8 150% 60 sec., 200% 0.5 sec. (inverse time characteristics) 3-Phase 380-480V 50 Hz/60 Hz 20% (*5) 100% / 5 sec. 2% ED (*5) 3-Phase 380-480 V 50 Hz/60 Hz 323-528V 50 Hz/60 Hz 5% When operated at or above 320 V continuously and voltage falls from rated voltage to under 320 V, 15 ms of continuous operation 10.2 14 19 23 33 39 48 57 77 90 123 Enclosed type (IP20) (*4) Forced air cooling 14 30.8 250 9.9 400 15.8 218 8.6 14 30.8 250 9.9 400 15.8 218 8.6 30 66 340 13.4 550 21.7 195 7.7 35 77 450 17.7 550 21.7 250 9.9 35 77 450 17.7 550 21.7 250 9.9 36 79 480 18.9 700 27.6 250 9.9 65 143 480 18.9 700 27.6 270 10.6 Open type (IP00) FR-V540-1.5K-NA FR-V540-2.2K-NA FR-V540-3.7K-NA FR-V540-5.5K-NA FR-V540-7.5K-NA FR-V540-11K-NA FR-V540-15K-NA FR-V540-18.5KNA FR-V540-22K-NA FR-V540-30K-NA FR-V540-37K-NA FR-V540-45K-NA FR-V540-55K-NA Continuous (*5)

Width

Height

Depth

Notes: 1. The overload current % value indicates the percentage to the inverters rated output current. For repeated duty, allow time for the inventer and motor to return to or below the temperature when at 100% load. 2. The maximum output voltage cannot exceed the power supply voltage. The maximum output voltage can be set below the power supply voltage. 3. The power capacity will vary according to the power supply side impedance (including input reactor and power lines) value. 4. When the wiring cover for the network option is removed and built-in options are installed, the protective structure will become open type (IP00). 5. For inverter capacities 1.5K to 15K, using the optional high-duty brake resistor (FR-ABR) will provide 100% torque/10% ED.

Dedicated Options V500 Series


Model Number FR-PU04V FR-V5AP FR-V5AX FR-V5AY FR-V5AM FR-V5NS FR-V5NE FR-V5AH T-TRC50 Description Parameter unit used for operation control, reading and writing parameters, drive monitoring, parameter copy and multi-language Pulse train input for advanced position control. Differential line receiver: 500kpps, open collector 200kpps 6 additional multi-function digital inputs and high resolution analog input (16-bit) 3 additional multi-function digital outputs and encoder pulse ratio output (differential or open collector output) When used with additional encoder, machine side orientation can be performed SSCNET motion control network operation Ethernet option for inverter setup and monitoring using LAN 3-digit BCD or 12-bit binary code input for high accuracy speed control Memory option used with setup software (FR-SW1-SETUP-WE) to analyze internal inverter trace data Installation Manual IB(NA)0600079 IB(NA)0600087 IB(NA)0600083 IB(NA)0600085 IB(NA)0600089 IB(NA)0600106E IB(NA)0600108E IB(NA)0600110E Contact MEAU Stocked Item S S S

SSCNET II Cables
Model Number FR-V5NSCBL005 FR-V5NSCBL01 FR-V5NSCBL05 FR-V5NSCBL10 FR-V5NSCBL20 Length 0.5 meter 1 meter 5 meters 10 meters 20 meters Description Connection of Q172CPU to FR-V5NS, FR-V5NS to FR-V5NS Stocked Item S S S

Instruction Manuals
Model FR-V520 FR-V540 FR-V560 FR-V500L Basic Detailed Basic Detailed Basic Detailed Model Number IB(NA)06000064 IB(NA)06000065 IB(NA)0600134 IB(NA)0600135 IB-T7311 IB-T7312

Mitsubishi Electric Automation

Variable Frequency Drives 41

VARIABLE FREQUENCY DRIVES

V500 General Specifications


Control System Control Mode Analog Input Frequency Control Resolution Digital Input Acceleration / Deceleration Time Acceleration / Deceleration Pattern Torque Restriction Level Soft- PWM control or high carrier frequency sine-wave PWM control can be selected. Vector control or V/F control can be selected. Speed control, torque control, position control 0.03% of maximum set speed 0.003% against maximum settings (0.1 rpm units for minimum setting) 0 to 3600 sec (0.1 second increments) Linear, S pattern (3 types) or backlash compensation acceleration/deceleration can be selected Torque restriction value can be set (0 to 400% variable) Terminal No. Setting Range Speed Control Torque Control 0 to 10V (resolution 0.03%) Main speed setting Speed restriction 2 Speed restriction compensation, Auxiliary speed setting, 0 to 10V (resolution 0.05%) magnetic flux command magnetic flux command, 1 regenerative torque restriction driving side speed restriction Torque restriction 3 0 to 10V (resolution 0.05%) Torque command (Torque bias) Speed restriction (at this time, terminal Main speed setting (in this case, 0 to 10V (resolution 0.003%) 6 terminals 1 and 2 are invalid) 2 is invalid) / Torque command (at Torque restriction this time, terminal 3 is valid) 3 fixed function terminals Forward rotation command, alarm reset, external thermal relay Selection can be made from reverse rotation command, multi-speed setting (max. 15 speeds), remote 5 multi-function terminals setting, jog operation, second function selection, third function selection, output stop, three-wire control, pre-excitation, control mode switchover, torque restriction selection, S pattern switchover, PID control terminal, orientation command, brake opening completion signal, PU operation/external operation switchover, torque bias selection 1, torque bias selection 2, P control selection, servo on, HC 6 multi-function terminals connection, PU/external interlock, external DC brake start, and commanded position selection. 1 Form C Relay Selection con be made from inverter running, up to speed, instantaneous power failure (undervoltage) (230VAC 0.3A, 30VDC 0.3A) speed detection, second speed detection, third speed detection, PU operation mode, overload alarm, regenerative brake pre-alarm, electronic thermal relay pre-alarm, output current detection, zero current 3 multi-function terminals detection, PID lower limit, PID upper limit, PID forward /reverse output, operation ready, operation ready 2. brake opening request, fan fault output, fin overheat pre-alarm, orientation in-position, forward 3 multi-function terminals 1 multi-function terminal rotation output, reverse rotation output, low speed output, torque detection, regenerative status output, minor fault output, alarm output, maintenance timer output, remote output, speed detection, in-position 7 multi-function terminals and trace status 0 to 10V, 12 bits x 1CH Selection can be made from speed, output current, output voltage, preset speed, output frequency, 0 to 10V, 12 bits x 1CH motor torque, converter output voltage, regenerative brake duty, electronic thermal relay load factor, 0 to 10V, 10 bits x 1CH output current peak value, converter output voltage peak value, load meter, motor exciting current, 0 to 20mA, 10 bits x 1CH motor output, reference voltage A phase, B phase, Z phase, (A and B phases can be divided) Open collector/differential line driver Maximum/minimum speed setting, speed jump, external thermal relay input selection, polarity reversible operation, override function, automatic restart operation after instantaneous power failure, forward/reverse operation prevention, operation mode selection, offline auto tuning function, online auto tuning function, easy gain tuning, computer link operation, remote setting, brake sequence, second function, third function, multi-speed operation, coasting to stop, power failure stop, PID control, speed feed forward, model adaptive speed control, master/slave, torque bias, 12-bit digital command (FR-A5AX option), pulse train input (FR-A5AP option), motor thermistor interface (FR-V5AX option), and simple positioning Selection can be made from speed, output current, output voltage, preset speed, output frequency, motor torque, converter output voltage, regenerative brake duty, electronic thermal relay load factor, output current peak value, converter output voltage, peak value, input terminal status (PU04V), load meter, motor exciting current, position pulse, cumulative energization time, actual operation time, motor load factor, torque command, torque current command, feedback pulse, motor output, trace status Alarm definition is displayed when protective function is activated. 8 past alarm definitions are stored. (Only 4 alarm definitions are stored in the DU04-1) Overcurrent shut-off (acceleration, deceleration, constant speed), regenerative overvoltage shut-off (acceleration, deceleration, constant speed), undervoltage, instantaneous power failure, overload shut-off (electronic thermal relay), brake transistor alarm, earth (ground) fault current, power output short circuit, stall prevention, external thermal relay, fin overheat, fan fault, option alarm, parameter error, PU disconnection, encoder no-signal, large speed deviation, overspeed large position error, CPU error, encoder phase error, output phase loss excessive retries, brake sequence error -10C to +50C (Non-freezing) / 14F to 122F 90% RH or less (Noncondensing) -20C to +65C / -4F to 149F For indoor use; no corrosive gasses, flammable gasses, oil mist, dust or dirt present 1000m above sea level. Contact factory for higher altitude deratings. 5.9 m/s2 (0.6G max.) based on JIS C 0911

Control Specs. Input Signal Environment Display Environment

Analog Setting Signal

With Option FR-V5AX

Contact Signal

With Option (FR-V5AX) Contact Signal Open Collector Signal With Option (FR-V5AY) With Option (FR-V5AM) With Option (FR-A5AY) Analog Output With Option (FR-A5AY) Encoder Pulse Output Option (FR-V5AY)

Operational Functions

Parameter Unit (FR-DU04-1/FR-PU04V) Alarm Definition

Protective Functions

Ambient Temperature Ambient Humidity Storage Temperature (*1) Atmosphere Attitude Vibration

Notes: 1. Temperature that can be applied for short times, such as in transit.

42

V500 Series Terminal Connection Diagram

Notes: 1. Terminal PR is provided on the 15kW and smaller capacities, and terminal PX is provided on the 5.5kW and smaller capacities. 2. When using FR-ABR with the 5.5kW or smaller capacity, remove this jumper. 3. Remove this jumper when using FR-BEL for 55kW and smaller capacities. DC link reactor included with 75kW and larger. 4. The converters life will be shortened by repeated in-rush currents when the power is turned ON, so do not turn the power ON and OFF frequently. 5. Prepare a 10V external power supply for terminals 1 and 3. 6. When using a motor without a thermal protector, set Pr.876 Thermal protector input to 0 and set Pr.9 (Pr.452) "Electronic thermal (2nd electronic thermal). 7. The terminal functions can be changed with the input terminal function selection (Pr.180 to Pr.183, Pr.187) 8. The terminal functions can be changed with the output terminal function selection (Pr.190 to Pr.192, Pr.195) 9. Change the connector according to the encoder power supply specifications. 10. The sink logic and source logic will change when the connector is changed. 11. Use of the 2W1kW is recommended when the settings are changed frequently. 12. Always ground the inverter and motor.

Mitsubishi Electric Automation

Variable Frequency Drives 43

VARIABLE FREQUENCY DRIVES

Packaged Variable Frequency Drives


Now you can get the complete package from Mitsubishi Electric we develop, engineer, manufacture and service AC variable frequency drive packages. Our packaged drives come to your facility with As Built documentation, pre-tested and ready for installation and wiring.

Fast lead times and convenient: Sourcing a complete system from a single responsible manufacturer eliminates the delays and other problems associated with dealing with multiple vendors. Space saving design: A custom enclosure with double layer construction is designed and built for optimum compactness. Wide range of options: An extensive array of options and components are available to meet your exact application requirements. Easy-to-use documentation: Thorough As-built documentation makes servicing and troubleshooting simple. Only the products and optional items ordered per your specifications are shown in the drawings. Fast, economical and ready for installation: All internal wiring is complete and the drives package comes to you ready for field wiring and operation. Package options include: circuit breaker, fused disconnect, parameter units, door mounted pilot devices, factory plug-in options, reactors AC input, DC link, and AC output, automatic / manual bypass, brake units, brake resistors, isolation transformers, RF filters for European directive compliance, output sine wave filter, output contactor, motor overload relay, blower starter, line regenerative braking, auxiliary power, remote pilot devices. Available in three different NEMA type enclosures.

I I I

I I

For model numbers, pricing and availability, please contact your local Mitsubishi Electric representative.

44

Packaged drives are built-to-order and pre-wired with a variety of optional accessories from which to choose

1. Input Impedance: Input Reactors or Isolation Transformers provide impedance. Both can be provided in separate NEMA 1 enclosures; reactors can also be mounted inside the drive enclosure. 2. Input Protection: Fuses, Fused Disconnects, and Circuit Breakers are used to protect the drive from overcurrent. 3. Control Transformer: 115VAC control power for contactors, pilot devices, general control. 4. Power Supplies: 24VDC for control and pilot devices, 5VDC for encoder feedback. 5. Drives Available: All Mitsubishi Electric drives are available to be packaged. 6. Automatic Bypass: Allows the motor to be started and run across the line. This mode is initiated when the selector switch in manual, or when the drive is in auto and the drive has a fault. See items 8 and 10. 7. Blower Motor Starter: Provides a fused motor starter and overload for the blower motor which cools a constant torque, variable speed motor. 8. Motor Output Contactor: This is a standard with bypass. 9. Enclosure: NEMA 1, NEMA 12 and NEMA 12 ventilated enclosures are available. 10. Isolating Disconnect: Standard with bypass is a drive isolating disconnect. This allows the drive to be isolated from power while the motor is running across the line. 11. Input Line Filter: These devices help to reduce line noise (conducted and radiated) that is created by the drive. 12. Parameter Units: These keypads are used for operator control, reading and writing parameters, and drive monitoring. They can be installed on the drive, or mounted on the door of the enclosure. 13. Loading Parameter Settings: A customers parameter settings can be factory loaded and documented. 14. DC Link Reactor: The DC Link Reactor improves power factor and helps reduce the input current. 15. Dynamic Braking: Separated braking resistors and braking control units can be mounted and wired. 16. Plug-in Options: Mitsubishi VFDs feature a wide choice of plug-in regulator and interface options. 17. Output Line Conditioning: Output reactors and output filters are available to reduce the voltage spikes that can stress motor insulation. 18. Operator Control Stations: NEMA 12 operator stations featuring various combinations of start, stop, and other pilot devices with speed potentiometers. 19. Documentation: Wiring, interconnection, weight and dimensions are included. Data books and electronic formats are optional. 20. Output Overload: These are standard with bypass. Overloads are required when operating multiple motors from a common VFD.

Mitsubishi Electric Automation

Variable Frequency Drives 45

VARIABLE FREQUENCY DRIVES

FR-F700 based VFD Complete Bypass System NEMA 1 - Circuit Breaker, 3 Contactor Bypass, Input Reactor
Base System Includes:
I I I I I I I I I I I I I I I I I I I

NEMA 1 construction Pow-R-Gate bypass controller with LCD display 3 contactor bypass with TEST mode Auto/manual bypass field selectable Damper end switch input & damper actuator output E-Stop string w/ provisions for 3 sets of N.C. contacts Catch a spinning load / windmill start activated Adjustable overload relay, class 20 equivalent Parameter unit cover mounted Input circuit breaker, UL 489 Type Control transformer, fused primary & secondary

Terminal blocks for control connections RS-485, Modbus RTU Communication EMI/RFI Filter standard within VFD Complete standard Mitsubishi testing AutoCAD documentation packet Instruction manuals for VFD and controller UL / cUL 508 Available options: Output line reactor, RFI filter, harmonic filter, DC link reactor, input options, well bulb sensors, transducers, pressure sensors 2 year warranty

F1C208V05HM30

Symbol 208V 460V

Voltage Class 3 phase 60Hz input voltage 3 phase 60Hz input voltage Output HP 3-phase 60Hz

Symbol 3 5

Input Line Reactor Impedance 3% 5%

Standard Product with Circuit Breaker & 3 Contactor Bypass VFD System HP 1 2 3 5 7.5 10 15 20 25 30 40 50 60 75 100 125 150 200 KW 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90 90 132

208V Based VFD System Panel Size Model Number F1C208V01HM30 F1C208V02HM30 F1C208V03HM30 F1C208V05HM30 F1C208V07HM30 F1C208V10HM30 F1C208V15HM30 F1C208V20HM30 F1C208V25HM30 F1C208V30HM30 F1C208V40HM30 F1C208V50HM30 F1C208V60HM30 Stk. Item S S S S S S S S S S Amps 4.2 7 9.6 15.2 23 31 45 58 70 85 114 140 170 A A A A B B C D D D E E E

460V Based VFD System Panel Size Model Number F1C460V01HM30 F1C460V02HM30 F1C460V03HM30 F1C460V05HM30 F1C460V07HM30 F1C460V10HM30 F1C460V15HM30 F1C460V20HM30 F1C460V25HM30 F1C460V30HM30 F1C460V40HM30 F1C460V50HM30 F1C460V60HM30 F1C460V75HM30 F1C460V100HM30 F1C460V125HM30 F1C460V150HM30 F1C460V200HM30 Stk. Item S S S S S S S S S S S S S Amps 2.1 3.5 4.8 7.6 11.5 16 23 29 35 43 57 70 85 106 144 180 180 260 A A A A B B C C C C D D D D E E E Floor mount NEMA 12

Panel A B C D E Floor Mount

lbs 85 105 120 150 210 850

H (in) 32 40 44 52 68 78

W (in) 12 16 17 25 27 47.25

D (in) 8.2 10.2 10.2 12.6 18 20

46

FR-F700 Based VFD Complete Outdoor Enclosure NEMA 3R Circuit Breaker, 3 Contactor Bypass, Input Reactor
Base System Includes:
I I I I I I I I I I I I I I I I I I

NEMA 3R construction with rain hood and sun shield, designed for -10C to +40C air in direct sunlight Thermostatically controlled enclosure heating/cooling Clear gasketed weatherproof entry door for Pow-R-Gate bypass controller with LCD display Screened entrance and exits for cooling air 3 contactor bypass with TEST mode Auto/manual bypass field selectable Adjustable overload relay Parameter unit VFD mounted Input circuit breaker with door interlocked handle Control transformer, fused primary & secondary

Terminal blocks for control connections RS-485, Modbus RTU communication EMI/RFI filter standard within VFD Complete standard Mitsubishi testing AutoCAD documentation packet Instruction manuals for VFD and controller UL / cUL 508 Available options: Output line reactor, RFI filter, harmonic filter, DC link reactor, input options, well bulb sensors, transducers, pressure sensors 2 year warranty

F3C208V005HM3

Symbol 208V 460V

Voltage Class 3 phase 60Hz input voltage 3 phase 60Hz input voltage Output HP 3-phase 60Hz

Symbol 3 5

Input Line Reactor Impedance 3% 5%

Standard Product with Circuit Breaker & 3 Contactor Bypass VFD System HP 1 2 3 5 7.5 10 15 20 25 30 40 50 60 75 100 125 150 200 KW 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90 90 132

208V Based VFD system

Panel Size Amps 4.2 7 9.6 15.2 23 31 45 58 70 85 114 140 170 3A 3A 3A 3A 3B 3B 3B 3D 3D 3D 3D 3E 3E

460V Based VFD system

Panel Size Amps 2.1 3.5 4.8 7.6 11.5 16 23 29 35 43 57 70 85 106 144 180 180 260 3A 3A 3A 3A 3A 3A 3B 3B 3B 3D 3D 3E 3E 3E 3F 3F 3F 3F

Model Number F3C208V001HM3 F3C208V002HM3 F3C208V003HM3 F3C208V005HM3 F3C208V007HM3 F3C208V010HM3 F3C208V015HM3 F3C208V020HM3 F3C208V025HM3 F3C208V030HM3 F3C208V040HM3 F3C208V050HM3 F3C208V060HM3

Stk. Item S S S S S S S S

Model Number F3C460V001HM3 F3C460V002HM3 F3C460V003HM3 F3C460V005HM3 F3C460V007HM3 F3C460V010HM3 F3C460V015HM3 F3C460V020HM3 F3C460V025HM3 F3C460V030HM3 F3C460V040HM3 F3C460V050HM3 F3C460V060HM3 F3C460V075HM3 F3C460V100HM3 F3C460V125HM3 F3C460V150HM3 F3C460V200HM3

Stk. Item S S S S S S S S S S S

Panel 3A 3B 3C 3D 3E 3F

lbs 170 225 250 300 420 850

H (in) 28 34 34 42.03 54.11 7.58

W (in) 24.38 24.38 30.38 30.38 36.28 37.88

D (in) 15.4 15.4 15.4 20.97 20.97 22

Mitsubishi Electric Automation

Variable Frequency Drives 47

VARIABLE FREQUENCY DRIVES

General Options
RFI Filters
Model No. RF3-0006-4 RF3-0010-4 RF3-0018-4 RF3-0025-4 RF3-0033-4 RF3-0050-4 RF3-0070-4 RF3-0090-4 RF3-0130-4 RF3-0150-4 RF3-0330-4 RF3-0006-6 RF3-0010-6 RF3-0018-6 RF3-0025-6 RF3-0033-6 RF3-0050-6 RF3-0070-6 RF3-0090-6 RF3-0130-6 RF3-0150-6 RF3-0330-6 Filter Amps RMS 6 10 18 25 33 50 70 90 130 150 330 6 10 18 25 33 50 70 90 130 150 330 208V Hp With >3% Reactor 1-1.5 Hp 2 Hp 35 Hp 7.5 Hp 10 Hp 15 Hp 20 Hp 25 Hp 3040 Hp 50 Hp 60100 Hp 208V Hp* Without Reactor 1 Hp 1.5 Hp 2-3 Hp 5 Hp 7.5 Hp 10 Hp 15 Hp 20 Hp 2530 Hp 4075 Hp 240V Hp* With >3% Reactor 11.5 Hp 23 Hp 5 Hp 7.5 Hp 10 Hp 15 Hp 20 Hp 2530 Hp 40 Hp 50 Hp 60125 Hp 240V Hp* Without Reactor 1 Hp 1.52 Hp 3 Hp 5 Hp 7.5 Hp 10 Hp 15 Hp 20 Hp 2530 Hp 40 Hp 50100 Hp 480V Hp* With >3% Reactor 13 Hp 5 Hp 7.510 Hp 15 Hp 20 Hp 25-30 Hp 4050 Hp 60 Hp 75100 Hp 125250 Hp 480V Hp* Without Reactor 12 Hp 35 Hp 7.5 Hp 10 Hp 15 Hp 2025 Hp 30 Hp 4050 Hp 60 Hp 75 Hp 100200 Hp 600V Hp* With >3% Reactor 13 Hp 57.5 Hp 1015 Hp 20 Hp 2530 Hp 40 Hp 5060 Hp 75 Hp 100125 Hp 150 Hp 200300 Hp 600V Hp* Without Reactor 13 Hp 5 Hp 7.510 Hp 15 Hp 20 Hp 2530 Hp 4050 Hp 60 Hp 75100 Hp 125200 Hp Stocked Item

* Hp Based on NEC motor current ratings

RFI Filter Electrical Data


Model No. RF3-0006-4 RF3-0010-4 RF3-0018-4 RF3-0025-4 RF3-0033-4 RF3-0050-4 RF3-0070-4 RF3-0090-4 RF3-0130-4 RF3-0150-4 RF3-0330-4 RF3-0006-6 RF3-0010-6 RF3-0018-6 RF3-0025-6 RF3-0033-6 RF3-0050-6 RF3-0070-6 RF3-0090-6 RF3-0130-6 RF3-0150-6 RF3-0330-6 Dissipation Watts 3.5 4.2 11 11 16 16 19 18 25 28 40 3.5 4.2 11 11 16 16 19 19 28 28 40 Leakage Current mA 1.5 1.4 1.5 2.8 3.7 4.8 4.4 6.4 8.6 9.8 6 1.5 1.5 4.9 4.9 6.5 9.9 9.9 9.9 14.1 14.1 9.9 A Fig. in A A A A B B B B B B C C C C C B B B B B B C 7 7 9 9 10.7 12.3 12.3 12.6 12.6 13.1 15.2 7.2 7.2 9.2 9.2 10.7 12.3 12.3 12.3 13.1 13.1 15.2 mm 179 179 229 229 272 312 312 319 319 334 386 183 183 233 233 272 312 312 312 334 334 386 in 1.8 1.8 2.2 2.2 2.9 3.7 3.7 5 5 5 10.2 1.8 1.8 2.2 2.2 2.9 3.7 3.7 3.7 5 5 10.2 mm 45 45 55 55 74 93 93 126 126 126 260 45 45 55 55 74 93 93 93 126 126 260 in 3.1 3.1 4.5 4.5 6.3 7.5 7.5 8.8 8.8 8.8 4.6 3.1 3.1 4.5 4.5 6.3 7.5 7.5 7.5 8.8 8.8 4.6 mm 79 79 114 114 161 190 190 224 224 224 116 79 79 114 114 161 190 190 190 224 224 116 in 6.57 6.57 8.54 8.54 10.16 11.73 11.73 11.73 11.73 11.73 4.72 6.57 6.57 8.54 8.54 10.16 11.73 11.73 11.73 11.73 11.73 4.72 mm 167 167 217 217 258 298 298 298 298 298 120 167 167 217 217 258 298 298 298 298 298 120 in 1.26 1.26 1.65 1.65 2.36 3.11 3.11 4.41 4.41 4.41 9.25 1.26 1.26 1.65 1.65 2.36 3.11 3.11 3.11 4.41 4.41 9.25 mm 32 32 42 42 60 79 79 112 112 112 235 32 32 42 42 60 79 79 79 112 112 235 A B B C C D D E E Weight (lb.) 1.4 1.5 2.4 2.9 6 8.2 9.3 13.5 13.5 19.6 24.3 1.4 1.5 2.4 2.9 6 8.2 9.3 9.3 19.6 19.6 24.3 Mass (kg) 0.65 0.7 1.1 1.3 2.7 3.7 4.2 6.1 6.1 8.9 11 0.65 0.7 1.1 1.3 2.7 3.7 4.2 4.2 8.9 8.9 11

For additional information visit http://www.mtecorp.com/rfiemi.html

Figure A

Figure B

Figure C

48

Line / Load Reactors


Input or Output Reactors Open Type Model No. MRL-00101 MRL-00102 MRL-00103 MRL-00104 MRL-00201 MRL-00202 MRL-00203 MRL-00204 MRL-00401 MRL-00402 MRL-00403 MRL-00404 MRL-00801 MRL-00802 MRL-00803 MRL-00804 MRL-01201 MRL-01202 MRL-01203 MRL-01801 MRL-01802 MRL-01803 MRL-02501 MRL-02502 MRL-02503 MRL-03501 MRL-03502 MRL-03503 MRL-04501 MRL-04502 MRL-04503 MRL-05501 MRL-05502 MRL-05503 MRL-08001 MRL-08002 MRL-08003 MRL-10001 MRL-10002 MRL-10003 MRL-13001 MRL-13002 MRL-13003 MRL-16001 MRL-16002 MRL-16003 MRL-20001B14 MRL-20002B14 MRL-20003B14 MRL-25001B14 MRL-25002B14 MRL-25003B14 MRL-32001B14 MRL-32002B14 MRL-32003B14 MRL-40001B14 MRL-40002B14 MRL-40003B14 MRL-50001 MRL-50002 MRL-50003 MRL-60001 MRL-60002 MRL-60003 MRL-75001 MRL-75002 MRL-75003 MRL-85001 MRL-85002 MRL-85003 MRL-100001 MRL-100002 MRL-100003 Stocked Item S S S S S S S S S S S S S S S S S NEMA 1 Type Model No. MRL-00111 MRL-00112 MRL-00113 MRL-00114 MRL-00211 MRL-00212 MRL-00213 MRL-00214 MRL-00411 MRL-00412 MRL-00413 MRL-00414 MRL-00811 MRL-00812 MRL-00813 MRL-00814 MRL-01211 MRL-01212 MRL-01213 MRL-01811 MRL-01812 MRL-01813 MRL-02511 MRL-02512 MRL-02513 MRL-03511 MRL-03512 MRL-03513 MRL-04511 MRL-04512 MRL-04513 MRL-05511 MRL-05512 MRL-05513 MRL-08011 MRL-08012 MRL-08013 MRL-10011 MRL-10012 MRL-10013 MRL-13011 MRL-13012 MRL-13013 MRL-16011 MRL-16012 MRL-16013 MRL-20011B14 MRL-20012B14 MRL-20013B14 MRL-25011B14 MRL-25012B14 MRL-25013B14 MRL-32011B14 MRL-32012B14 MRL-32013B14 MRL-40011B14 MRL-40012B14 MRL-40013B14 MRL-50011 MRL-50012 MRL-50013 MRL-60011 MRL-60012 MRL-60013 MRL-75011 MRL-75012 MRL-75013 MRL-85011 MRL-85012 MRL-85013 MRL-100011 MRL-100012 MRL-100013 Stocked Item 208-240V 1//4Hp @ 3%, 1/3-3/4Hp @ 5% 1/4Hp @ 5% 1/3-3/4Hp @ 3% 1Hp @ 3% 1Hp @ 5% 1.5-2Hp @ 3% 1.5-2Hp @ 5% 3Hp @ 3% 3Hp @ 5% 5Hp @ 3% 5Hp @ 5% 7.5Hp @ 3% 7.5Hp @ 5% 10Hp @ 3% 10Hp @ 5% 15Hp @ 3% 15Hp @ 5% 20Hp @ 3% 20Hp @ 5% 25-30Hp @ 3% 25-30Hp @ 5% 40Hp @ 3% 40Hp @ 5% 50Hp @ 3% 50Hp @ 5% 60Hp @ 3% 60Hp @ 5% 75Hp @ 3% 75Hp @ 5% 100Hp @ 3% 100Hp @ 5% 125Hp @ 3% 125Hp @ 5% 150Hp @ 3% 150Hp @ 5% 200Hp @ 3% 200Hp @ 5% 3 Phase Voltage Class 480V 1/4-1/3Hp @ 5% 1/4-1/3Hp @ 3%, 1/2Hp @ 5% 1/4-1/2Hp @ 1.5%. 1/2Hp @ 3% 3/4-1.5Hp @ 3% 3/4-1.5Hp @ 5% 3/4-1.5Hp @ 5% 2-3Hp @ 1.5% 2-3Hp @ 3% 2-3Hp @ 5% 5Hp @ 1.5% 5Hp @ 3% 5Hp @ 5% 7.5Hp @ 1.5% 7.5Hp @ 3% 7.5Hp @ 5% 10Hp @ 1.5% 10Hp @ 3% 10Hp @ 5% 15Hp @ 1.5% 15Hp @ 3% 15Hp @ 5% 20-25Hp @ 1.5% 20-25Hp @ 3% 20-25Hp @ 5% 30Hp @ 1.5% 30Hp @ 3% 30Hp @ 5% 40Hp @ 1.5% 40Hp @ 3% 40Hp @ 5% 50-60Hp @ 1.5% 50-60Hp @ 3% 50-60Hp @ 5% 75Hp @ 1.5% 75Hp @ 3% 75Hp @ 5% 100Hp @ 1.5% 100Hp @ 3% 100Hp @ 5% 125Hp @ 1.5% 125Hp @ 3% 125Hp @ 5% 150Hp @ 1.5% 150Hp @ 3% 150Hp @ 5% 200Hp @ 1.5% 200Hp @ 3% 200Hp @ 5% 250Hp @ 1.5% 250Hp @ 3% 250Hp @ 5% 300Hp @ 1.5% 300Hp @ 3% 300Hp @ 5% 350-400Hp @ 1.5% 350-400Hp @ 3% 350-400Hp @ 5% 500Hp @ 1.5% 500Hp @ 3% 500Hp @ 5% 600Hp @ 1.5% 600Hp @ 3% 600Hp @ 5% 700Hp @ 1.5% 700Hp @ 3% 700Hp @ 5% 800Hp @ 1.5% 800Hp @ 3% 800Hp @ 5% 600V 1/4-1/3Hp @ 5% 1/4-1/3Hp @ 3%, 1/2Hp @ 5% 1/4-1/3Hp @ 1.5%. 1/2Hp @ 3% 1/2Hp @ 1.5% 3/4-1.5Hp @ 1.5% 3/4-1.5Hp @ 3% 3/4-1.5Hp @ 5% 2-3Hp @ 1.5% 2-3Hp @ 3% 2-3Hp @ 5% 7.5Hp @ 1.5% 5Hp @ 1.5%, 7.5Hp @ 3% 5Hp @ 3%, 7.5Hp @ 5% 5Hp @ 5% 10Hp @ 1.5% 10Hp @ 3% 10Hp @ 5% 15Hp @ 1.5% 15Hp @ 3% 15Hp @ 5% 20-25Hp @ 1.5% 20-25Hp @ 3% 20-25Hp @ 5% 30Hp @ 1.5% 30Hp @ 3% 30Hp @ 5% 40Hp @ 1.5% 40Hp @ 3% 40Hp @ 5% 50Hp @ 1.5% 50Hp @ 3% 50Hp @ 5% 60-75Hp @ 1.5% 60-75 Hp @ 3% 60-75 Hp @ 5% 100Hp @ 1.5% 100Hp @ 3% 100Hp @ 5% 125Hp @ 1.5% 125Hp @ 3% 125Hp @ 5% 150Hp @ 1.5% 150Hp @ 3% 150Hp @ 5% 200Hp @ 1.5% 200Hp @ 3% 200Hp @ 5% 250Hp @ 1.5% 250Hp @ 3% 250Hp @ 5% 300Hp @ 1.5% 300Hp @ 3% 300Hp @ 5% 350-400Hp @ 1.5% 350-400Hp @ 3% 350-400Hp @ 5% 500Hp @ 1.5% 500Hp @ 3% 500Hp @ 5% 600Hp @ 1.5% 600Hp @ 3% 600Hp @ 5% 700Hp @ 1.5% 700Hp @ 3% 700Hp @ 5% 800Hp @ 1.5% 800Hp @ 3% 800Hp @ 5%

Mitsubishi Electric Automation

Variable Frequency Drives 49

VARIABLE FREQUENCY DRIVES

Line / Load Reactor Electrical Data


Model Number MRL-00201 MRL-00202 MRL-00203 MRL-00204 MRL-00401 MRL-00402 MRL-00403 MRL-00404 MRL-00801 MRL-00802 MRL-00803 MRL-00804 MRL-01201 MRL-01202 MRL-01203 MRL-01801 MRL-01802 MRL-01803 MRL-02501 MRL-02502 MRL-02503 MRL-03501 MRL-03502 MRL-03503 MRL-04501 MRL-04502 MRL-04503 MRL-05501 MRL-05502 MRL-05503 MRL-08001 MRL-08002 MRL-08003 MRL-10001 MRL-10002 MRL-10003 MRL-13001 MRL-13002 MRL-13003 MRL-16001 MRL-16002 MRL-16003 MRL-20001B14 MRL-20002B14 MRL-20003B14 MRL-25001B14 MRL-25002B14 MRL-25003B14 MRL-32001B14 MRL-32002B14 MRL-32003B14 MRL-40001B14 MRL-40002B14 MRL-40003B14 MRL-50001 MRL-50002 MRL-50003 MRL-60001 MRL-60002 MRL-60003 MRL-75001 MRL-75002 MRL-75003 MRL-85001 MRL-85002 MRL-85003 MRL-90001 MRL-90002 MRL-90003 MRL-100001 MRL-100002 MRL-100003 Watts Loss 8 12 16 11 15 20 20 21 20 29 26 28 26 31 41 36 43 43 48 52 61 49 54 54 54 62 65 64 67 71 82 86 96 94 84 108 108 180 128 116 149 138 124 168 146 154 231 219 224 264 351 231 333 293 266 340 422 307 414 406 427 630 552 798 930 1133 860 1020 1365 940 1090 1500 Wire Range (AWG) 22 14 22 14 22 14 22 14 22 14 22 14 22 14 22 14 22 14 22 14 22 14 22 14 22 5 22 5 22 5 22 5 22 5 22 5 22 5 22 5 22 5 22 5 22 5 18 4 18 4 18 4 18 4 6 0 6 0 6 0 6 0 6 0 6 0 6 0 6 0 6 0 2 0000 2 0000 2 0000 2 0000 2 0000 2 0000 Copper Tab Copper Tab Copper Tab Copper Tab Copper Tab Copper Tab Copper Tab Copper Tab Copper Tab Copper Tab Copper Tab Copper Tab Copper Tab Copper Tab Copper Tab Copper Tab Copper Tab Copper Tab Copper Tab Copper Tab Copper Tab Copper tab Copper tab Copper tab Copper tab Copper tab Copper tab Copper tab Copper tab Copper tab Terminal Torque (in / lbs) 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 16 16 16 16 16 16 16 16 16 16 16 20 20 20 20 6-4(45) & 2-0(50) 6-4(45) & 2-0(50) 6-4(45) & 2-0(50) 6-4(45) & 2-0(50) 6-4(45) & 2-0(50) 6-4(45) & 2-0(50) 6-4(45) & 2-0(50) 6-4(45) & 2-0(50) 6-4(45) & 2-0(50) 150 150 150 150 150 150 Not Applicable Not Applicable Not Applicable Not Applicable Not Applicable Not Applicable Not Applicable Not Applicable Not Applicable Not Applicable Not Applicable Not Applicable Not Applicable Not Applicable Not Applicable Not Applicable Not Applicable Not Applicable Not Applicable Not Applicable Not Applicable Not Applicable Not Applicable Not Applicable Not Applicable Not Applicable Not Applicable Not Applicable Not Applicable Not Applicable Ind. mH 12 20 32 6 3 6.5 9 12 1.5 3 5 7.5 1.25 2.5 4.2 0.8 1.5 2.5 0.5 1.2 1.8 0.4 0.8 1.2 0.3 0.7 1.2 0.25 0.5 0.85 0.2 0.4 0.7 0.15 0.3 0.45 0.1 0.2 0.3 0.075 0.15 0.23 0.055 0.11 0.185 0.045 0.09 0.15 0.04 0.075 0.125 0.03 0.06 0.105 0.025 0.05 0.085 0.02 0.04 0.065 0.015 0.029 0.048 0.015 0.027 0.042 0.013 0.025 0.04 0.011 0.022 0.038 Fund Amps 2 2 2 2 4 4 4 4 8 8 8 8 12 12 12 18 18 18 25 25 25 35 35 35 45 45 45 55 55 55 80 80 80 100 100 100 130 130 130 160 160 160 200 200 200 250 250 250 320 320 320 400 400 400 500 500 500 600 600 600 750 750 750 850 850 850 900 900 900 1000 1000 1000 Max Amps 3 3 3 3 6 6 6 6 12 12 12 12 18 18 18 27 27 27 37.5 37.5 37.5 52.5 52.5 52.5 67.5 67.5 67.5 82.5 82.5 82.5 120 120 120 150 150 150 195 195 195 240 240 240 300 300 300 375 375 375 480 480 480 600 600 600 750 750 750 900 900 900 1125 1125 1125 1063 1063 1063 1125 1125 1125 1250 1250 1250

For additional information visit http://www.mtecorp.com/lineload.html

50

Sine Wave dV/dT Filters (2-8kHz Carrier Frequency)


460VAC Open Motor HP 1.5 2 3 5 7.5 10 15 20 25 30 40 50 60 75 100 125 150 200 250 300 350 400 450 500 600 Filter Rating Amps Model No. Stocked Item NEMA 1* Model No. Stocked Item

9 12 17 22 27 35 45 55 65 80 110 130 160 200 250 305 365 415 515 600 720

SWAP0009D SWAP0012D SWAP0017D SWAP0022D SWAP0027D SWAP0035D SWAP0045D SWAP0055D SWAP0065D SWAP0080D SWAP0110D SWAP0130D SWAP0160D SWAP0200D SWAP0250D SWAP0305D SWAP0365D SWAP0415D SWAP0515D SWAP0600D SWAP0720D

SWAGA0009D SWAGA0012D SWAGA0017D SWAGB0022D SWAGB0027D SWAGB0035D SWAGB0045D SWAGB0055D SWAGB0065D SWAGC0080D SWAGC0110D SWAGC0130D SWAGC0160D SWAGD0200D SWAGD0250D SWAGD0305D SWAGD0365D SWAGD0415D SWAGD0515D SWAGE0600D SWAGE0720D

* Note: Some enclosures meet NEMA 2. For more information, visit www.mtecorp.com

DC Chokes
Model No. DCA000204 DCA000402 DCA000403 DCA000404 DCA000902 DCA000903 DCA000904 DCA001202 DCA001203 DCA001204 DCA001802 DCA001803 DCA001804 DCA001805 DCA002503 DCA002505 DCA003201 DCA003202 DCA003203 DCA004002 DCA004003 DCA004004 DCA005001 DCA005003 DCA005004 DCA006201 DCA008002 DCA008005 DCA009202 DCA009203 DCA011002 DCA011003 DCA012502 DCA015002 DCA015004 DCA020002 208V 1/4hp @ 5% 1/2hp @ 3% & 3/4-1hp@ 5% 1/2hp @ 5% 1.5hp @ 3% 1.5 & 2hp @ 5% 2hp @ 3% 3hp @ 5% 3hp@3% & 5hp@5% 240V 1/4hp @ 5% 1/2hp @ 3% & 3/4-1hp@ 5% 1/2hp @ 5% 1.5 & 2hp @ 3% 1.5 & 2hp @ 5% 3hp @ 3% 3hp @ 5% 7.5hp @ 3 & 5% 5hp @ 3% 5hp @ 5% 10hp @ 3% 7.5hp @ 3% 7.5hp @ 3 & 5% 15hp @ 3% 15hp @ 5% 20hp @ 3% 20hp @ 5% 25hp @ 3% 25hp @ 5% 10hp @ 3% 10hp @ 5% 480V 1/2hp @ 3% &1/2-1hp@ 5% 2hp @ 3% 1.5hp @ 3% 1.5hp @ 5% & 2hp @5% 3 & 5hp @ 3% 3 & 5hp @ 5% 600V 3/4-1hp @ 3&5% Stocked Item

1.5hp & 2hp @ 3%& 5%

3 & 5hp @ 3 & 5%

15hp @ 3 & 5%

7.5hp @ 3% 7.5hp @ 5% 10hp @ 3% 10hp @ 5%

7.5hp @ 3% 7.5hp @ 5% 10hp @ 3% 10hp @ 5% 15hp @ 3%

20 & 25hp @ 3 & 5% 30hp @ 3% 30hp @ 5% 40hp @ 3% 40hp @ 5%

15hp @ 5% 30hp @ 5% 15hp @ 3% 20hp @ 3% 50hp @ 5% 60hp @ 3% 60hp @ 5% 30hp @ 5% 40hp @ 5% 50hp @ 5% 60hp @ 5% 30hp @ 5% 40hp @ 3% 100hp @ 5% 60hp @ 5%

60hp @ 5% 75hp @ 3 & 5%

Mitsubishi Electric Automation

Variable Frequency Drives 51

VARIABLE FREQUENCY DRIVES

DC Choke Electrical Data


Model No. DCA000204 DCA000402 DCA000403 DCA000404 DCA000902 DCA000903 DCA000904 DCA001201 DCA001202 DCA001203 DCA001204 DCA001801 DCA001802 DCA001803 DCA001804 DCA001805 DCA002503 DCA002504 DCA002505 DCA003201 DCA003202 DCA003203 DCA004001 DCA004002 DCA004003 DCA004004 DCA005001 DCA005003 DCA005004 DCA006201 DCA006202 DCA008002 DCA008005 DCA009201 DCA009202 DCA009203 DCA011002 DCA011003 DCA012502 DCA015002 DCA015004 DCA020002 DC Amps 2 4 4 4 9 9 9 12 12 12 12 18 18 18 18 18 25 25 25 32 32 32 40 40 40 40 50 50 50 62 62 80 80 92 92 92 110 110 125 150 150 200 mH 50 12 15 25 3.22 7.5 11.5 1 1 4 6 0.65 1.375 2.75 3.75 6 1.275 1.75 4 0.85 1.62 2.68 0.5 0.75 1 2 0.625 1.35 2 0.32 0.61 0.4 1.25 0.2 0.6 1 0.3 0.45 0.22 0.22 0.65 0.21 Watts 5 5 6 9 7 11 16 5 7 11 14 5 9 16 17 20 13 13 16 11 14 21 14 15 17 29 18 21 30 17 20 25 19 34 48 38 45 27 36 50 Lug Size 22-14 22-14 22-14 18-4 22-14 18-4 18-4 22-14 18-4 18-4 18-4 18-4 18-4 18-4 18-4 18-4 18-4 18-4 18-4 18-4 18-4 18-4 18-4 18-4 18-4 18-4 18-4 18-4 6-0 6-0 6-0 6-0 6-0 6-0 6-0 6-0 6-0 6-0 6-0 2-0000 2-0000 2-0000 Torque 4.5 4.5 4.5 20 4.5 20 20 4.5 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 6-4(45) &2-0 6-4(45) &2-0 6-4(45) &2-0 6-4(45) & 2-0(50) 6-4(45) & 2-0(50) 6-4(45) & 2-0(50) 6-4(45) & 2-0(50) 6-4(45) & 2-0(50) 6-4(45) & 2-0(50) 6-4(45) & 2-0(50) 6-4(45) & 2-0(50) 150 150 150 Unit Weight (lbs) 2 2 2 4 2 4 7 1 2 4 7 2 4 7 8 13 7 5 13 5 10 14 5 7 8 21 8 15 25 8 14 14 35 10 23 32 22 22 23 23 52 39

For additional information, visit http://www.mtecorp.com/dclink.html

Matrix Harmonic Filters, 5% THID 480V, 60Hz, Variable Torque Loads


Filter Max Motor Open Panel Load Motor HP NEC Amps Amps Model No. (*) 6 3 4.8 MDP0006D 8 5 7.6 MDP0008D 11 7.5 11 MDP0011D 14 10 14 MDP0014D 21 15 21 MDP0021D 27 20 27 MDP0027D 34 25 34 MDP0034D 44 30 40 MDP0044D 52 40 52 MDP0052D 66 50 65 MDP0066D 83 60 77 MDP0083D 103 75 96 MDP0103D 128 100 124 MDP0128D 165 125 156 MDP0165D 208 150 180 MDP0208D 240 200 240 MDP0240D 320 250 302 MDP0320D 403 300 361 MDP0403D 482 400 477 MDP0482D 636 500 590 MDP0636D 786 600 708 MDP0786D Filter Style Gen. Purpose NEMA 2 Gen. Purpose NEMA 3R Model No. (*) Model No. (*) MDG0006D MDW0006C MDG0008D MDW0008C MDG0011D MDW0011C MDG0014D MDW0014C MDG0021D MDW0021C MDG0027D MDW0027C MDG0034D MDW0034C MDG0044D MDW0044C MDG0052D MDW0052C MDG0066D MDW0066C MDG0083D MDW0083C MDG0103D MDW0103C MDG0128D MDW0128C MDG0165D MDW0165C MDG0208D MDW0208C MDG0240D MDW0240C MDG0320D MDW0320C MDG0403D MDW0403C MDG0482D MDW0482C MDG0636D MDW0636C MDG0786D MDW0786C

3 Phase Circuit Breaker


Amps 15A 20A 25A 30A 40A 50A 60A 70A 80A 90A 100A 125A 150A 175A 200A 225A 250A 400A 600A 800A NEMA 1 Enclosed Model No. (*) T1N015TL1 T1N020TL1 T1N025TL1 T1N030TL1 T1N040TL1 T1N050TL1 T1N060TL1 T1N070TL1 T1N080TL1 T1N090TL1 T1N100TL1 T3N125TL1 T3N150TL1 T3N175TL1 T3N200TL1 T3N225TL1 T4N250BL1 T5N400BL1 S6N600BL1 S6N800BL1 NEMA 3R Enclosed Model No. (*) T1N015TL3 T1N020TL3 T1N025TL3 T1N030TL3 T1N040TL3 T1N060TL3 T1N070TL3 T1N080TL3 T1N090TL3 T1N100TL3 T3N125TL3 T3N150TL3 T3N175TL3 T3N200TL3 T3N225TL3 T4N250BL3 T5N400BL3 S6N600BL3 S6N800BL3

* Non-stock. For use with bypass systems contactor option 010 or 011 is additionally required. For additional information, visit http://www.mtecorp.com/matrix.html

* Non-stock. For additional information, visit http://www.abb-control.com/products/lv023-molded_casebreakers.htm

52

Micro MAX AC Inverter Duty Motor


1000:1 Constant Torque (TENV) 20:1 Constant Torque (TEFC)

Designed for direct replacement of PMDC or any other variable speed application where up to a 1000:1 constant torque speed range is required. Typical uses include: machine tools, conveyors, packaging machines, batching machines and printing equipment.
I I I I I I I I I I

Replaces 90 and 180 volt PMDC motors when used with AC variable frequency drives Constant torque operation from 0 to base speed (TENV ratings) Constant torque operation from 1/20 speed to base speed (TEFC ratings) Constant horsepower to twice base speed (RPM) Class H insulation with CR200 magnetic wire

Continuous duty at 40C ambient Quick Connect terminal board as noted Top mounted conduit box with pigtail leads (TEFC and 1.5Hp TENV) UL recognized and CSA certified Three year warranty

C-Face with Rigid Base


Hp 1/8 1/4 1/3 1/2 RPM 1800 1800 1800 1800 1800 1800 1800 1800 1800 1800 1800 1800 1800 1800 1800 1800 1800 1800 1800 1800 1800 1800 1800 1800 1800 1800 1800 Volts 230 230 230 230 230/460 575 230 230/460 575 230 230/460 575 230 230/460 575 230 230/460 575 230 230/460 575 230/460 575 230/460 575 230/460 575 Encl. TENV TENV TENV TENV TENV TENV TEFC TEFC TEFC TEFC TEFC TEFC TENV TENV TENV TEFC TEFC TEFC TEFC TEFC TEFC TEFC TEFC TEFC TEFC TEFC TEFC Frame 56C 56C 56C 56C 56C 56C 56C 56C 56C 56C 56C 56C 145TC 145TC 145TC 145TC 145TC 145TC 182TC 182TC 182TC 184TC 184TC 213TC 213TC 215TC 215TC Catalog No. Y605 * Y500 * Y502 * Y504 * Y360 * Y361 * Y506 * Y362 * Y363 Y508 * Y364 * Y365 * Y522 * Y366 * Y367 * Y523 * Y368 * Y369 * Y998 Y999 * Y270 Y372 * Y373 Y994 * Y995 Y996 * Y997 F.L.A. 1.0 1.0 1.2 1.8 1.8/0.9 0.7 2.8 2.8/1.4 1.1 3.2 3.2/1.6 1.3 4.8 4.8/2.4 1.9 5.8 5.8/2.9 2.3 8.4 8.4/4.2 3.5 13.4/6.7 5.4 21.4/10.7 8.5 28.0/14.0 11.2 Weight 18 18 18 20 20 20 23 23 23 28 28 28 49 49 49 50 50 50 70 70 70 88 88 125 125 135 135 Notes N, Q N, Q N, Q N, Q N N, Q

3/4

1 1/2

N, 6 N, 6 N, 6 6 6 6

5 7 1/2 10

6 6

* Marathon Motors stock item. For additional information visit www.marathonelectric.com/motors/search.asp

C-Face Footless
Hp 1/8 1/4 1/3 1/2 RPM 1800 1800 1800 1800 1800 1800 1800 1800 1800 1800 1800 1800 Volts 230 230 230 230 230/460 575 230 230/460 575 230 230/460 575 Encl. TENV TENV TENV TENV TENV TENV TEFC TEFC TEFC TEFC TEFC TEFC Frame 56C 56C 56C 56C 56C 56C 56C 56C 56C 56C 56C 56C Catalog No. Y606 * Y501 * Y503 * Y505 * Y374 * Y375 * Y507 * Y376 * Y377 Y521 * Y378 * Y379 * F.L.A. 1.0 1.0 1.2 1.8 1.8/0.9 0.7 2.8 2.8/1.4 1.1 3.2 3.2/1.6 1.3 Weight 17 17 17 19 19 19 23 23 23 27 27 27 Notes N, Q N, Q N, Q N, Q N N, Q

3/4

* Marathon Motors stock item. Notes: N: Totally Enclosed Non Ventilated; Q: Quick Connect terminal board; 6: Bolt-on, removable base for footless mounting option. For additional information visit www.marathonelectric.com/motors/search.asp

Mitsubishi Electric Automation

Variable Frequency Drives 53

VARIABLE FREQUENCY DRIVES

Black MAX Vector Duty


1000:1 Constant Torque

Designed for inverter or vector duty applications where up to a 1000:1 constant torque speed range is required. Typical uses include: material handling, machine tools, conveyors, crane & hoist, metal processing and other industrial machinery installed in dusty or dirty environments.
I I I I I I

Class F MAX GUARD insulation system Constant torque operation from 0 to base speed on vector drive Constant horsepower to twice base speed (RPM) Continuous duty at 40C ambient Optimized for operation with IGBT inverter (NEMA Design A) Class F N/C thermostats

I I I I I I

Ball bearing Removable Base on some models as noted F1 standard, field reversible to F2 (except where noted) Encoder and brake provisions included on opposite drive end (maximum 10 lb-ft brake) UL recognized and CSA certified Three year warranty

Totally Enclosed Non-Ventilated, C-Face with Rigid Base


Hp 1/4 1/2 RPM 1800 1800 1800 1800 1800 1800 1200 1800 1800 1800 1200 1800 1800 1200 1800 1800 1200 1800 1800 1200 1800 1800 1200 1800 1800 1800 1800 1800 1800 1800 Volts 230/460 230/460 575 230/460 575 230/460 230/460 230/460 230/460 575 230/460 230/460 575 230/460 230/460 575 230/460 230/460 575 230/460 230/460 575 230/460 230/460 575 230/460 575 230/460 575 230/460 Frame 56C 56C 56C 56C 56C 143TC 145TC 145TC 145TC 145TC 184TC 182TC 182TC 213TC 184TC 184TC 215TC 213TC 213TC 254TC 215TC 215TC 256TC 254TC 254TC 256TC 256TC 284TC 284TC 286TC Catalog No. Y592 * Y534 * Y555 * Y535 * Y556 * Y536 * Y537 * Y538 * Y551 * Y557 * Y540 * Y541 * Y558 * Y542 * Y543 * Y559 * Y544 * Y545 * Y560 * Y546 * Y547 * Y561 * Y548 * Y549 * Y562 * Y552 * Y563 * Y553 * Y567 * Y393 * F.L.A. 1.2/0.6 1.6/0.8 0.6 3.0/1.5 1.2 3.0/1.5 3.8/1.9 4.8/2.4 6.0/3.0 2.4 6.6/3.3 8.4/4.2 3.4 9.4/4.7 14.0/7.0 5.4 15.4/7.7 21.0/10.5 8.4 22.0/11.0 27.0/13.5 10.8 28.0/14.0 40.0/20.0 16.0 50.0/25.0 20.0 62.0/31.0 24.8 80.0/40.0 Weight 19 28 28 39 40 43 49 50 70 70 88 93 98 118 103 103 128 146 150 209 159 159 275 250 250 320 320 525 525 575 Notes N, S, 13 N, S, 6, 13 N, S, 6, 13 N, S, 6, 13 N, S, 6, 13 N, S, 6, 13 N, S, 6, 13 N, S, 6, 13 N N N, AL N, AL N, AL N, AL N, AL N, AL N, AL N, AL N, AL N, AL N, AL N, AL N, AL N, AL, I N, AL, I N, I N, I N, I N, I N, I

1 1 1/2 2

7 1/2

10 15 20 25 30

* Marathon Motors stock item. Shaded areas are cast iron frames. Notes: AL: Aluminum Frame Construction; N: Totally Enclosed Non-Ventilated; I: Intermittent duty from 90-120Hz operation; S: Steel Frame Construction; 6: Bolt-on, removable base for footless mounting option; 13: F1 Mounting only, cannot modify to F2. For additional information visit www.marathonelectric.com/motors/search.asp

Black MAX Vector Duty: Encoders through Mod Center


Brand Model HS25A HS35A Avtron HS35M M3 M56 Dynapar BEI HS35 HS35 PPR 1024 2048 1024 2048 1024 2048 1024 1024 1024 2048 1024 2048 Catalog No. A746* A747* A736* A739* A742* A744 A753* A793* A772* A776* A779* A780* Notes Optical Hollow Shaft, MS connector Optical Hollow Shaft, MS connector Magnetic Hollow Shaft, EPIC connector Optical Hollow Shaft, EPIC connector Magnetic Modular Style, EPIC connector Shaft mount, 5-26VDC, with 10 pin connector Shaft mount, 5-26VDC, with 10 pin connector

54

* Marathon Motors stock item. For additional information visit www.marathonelectric.com/motors/search.asp

Blue MAX 2000 Vector Duty


2000:1 Constant Torque

Designed for inverter or vector duty applications where up to a 2000:1 constant torque speed range is required. Typical uses include: material handling, machine tools, conveyors, crane & hoist, metal processing, test stands, pumps, compressors, textile processing and other industrial machinery installed in dusty or dirty environments where cast iron construction is required.
I I I I I I I I

Class H MAX GUARD insulation system Constant torque operation from 0 to base speed on vector drive, including TEFC (on V/Hz drives, TEFC motors are limited to 20:1 Constant Torque) Constant horsepower to twice base speed (143-254 frame); 1.5 times base (all others) Continuous duty at 40C ambient Optimized for operation with IGBT inverter (NEMA Design A) C-Face foot mount through 100 Hp as noted Class F N/C thermostats Ball bearing (roller bearing available 360 frame and larger)

I I I I I I I

Cast iron frame and brackets Patented fracket design (TEBC enclosure) B temperature rise on Blower-Cooled motors F1 standard, field reversible to F2 Encoder and brake provisions included on opposite drive end UL recognized and CSA certified Three year warranty

Totally Enclosed Rigid Base, and C-Face with Rigid Base


Hp 1 1 1/2 2 3 5 7 1/2 10 RPM 1800 1800 1800 1800 1800 1800 1800 1800 1800 1800 1800 1200 1800 1800 1200 1800 1800 1200 1800 1800 1200 1800 1800 1200 1800 1800 1200 Volts 230/460 230/460 230/460 230/460 230/460 230/460 230/460 230/460 230/460 230/460 230/460 230/460 230/460 230/460 230/460 230/460 230/460 230/460 230/460 230/460 230/460 230/460 230/460 230/460 230/460 230/460 230/460 Encl. TENV TENV TENV TENV TENV TEFC TENV TEFC TENV TEFC TENV TEBC TEFC TENV TEBC TEFC TEBC TEBC TEFC TEBC TEBC TEFC TEBC TEBC TEFC TEBC TEBC Frame 143TC 145TC 145TC 182TC 184TC 213TC 213TC 215TC 215TC 254TC 254TC 284TC 256TC 256TC 286TC 284T 284TC 324TC 286T 286TC 326TC 324T 324TC 364TC 326T 326TC 365TC Catalog No. Y525 * Y590 * Y526 * Y527 * Y564 * Y595 * Y565 * Y596 * Y566 * Y597 * Y509 * Y395 * Y598 * Y510 * Y582 Y569 * Y511 * Y583 * Y570 * Y512 * Y584 * Y571 * Y513 * Y585 * Y572 * Y514 * Y586 F.L.A. 3.0/1.5 4.6/2.3 6.0/3.0 8.0/4.0 13.4/6.7 19.4/9.7 21.0/10.5 25.4/12.7 26.0/13.0 37.0/18.5 40.4/20.2 40.0/20.0 52.0/26.0 50.0/25.0 52.4/26.2 63.0/31.5 63.0/31.5 67.0/33.5 77.0/38.5 74.0/37.0 82.0/41.0 100/50.0 100/50.0 104/52.0 121/60.5 120/60.0 130/65.0 Weight 61 68 70 110 117 191 180 211 290 339 350 480 375 380 500 492 500 620 594 520 686 540 620 1050 540 640 1100 Notes NEMA Design B

NEMA Design B

15

20

NEMA Design B

25

NEMA Design B

30

NEMA Design B

40

50

* Marathon Motors stock item. Note: B: NEMA Design B. For additional information visit www.marathonelectric.com/motors/search.asp

Mitsubishi Electric Automation

Variable Frequency Drives 55

VARIABLE FREQUENCY DRIVES

Totally Enclosed Rigid Base, and C-Face with Rigid Base (continued)
Hp 60 RPM 1800 1800 1200 1800 1800 1200 1800 1800 1200 1800 1800 1800 1800 1800 1800 1800 1800 1800 1800 1800 Volts 230/460 230/460 230/460 230/460 230/460 230/460 230/460 230/460 230/460 460 460 460 460 460 460 460 460 460 460 460 Encl. TEFC TEBC TEBC TEFC TEBC TEBC TEFC TEBV TEBC TEFC TEBC TEFC TEBC TEFC TEBC TEFC TEBC TEFC TEBC TEBC Frame 364T 364TC 404TC 365T 365TC 405TC 405T 405TC 444TC 444T 444T 445T 445T 445T 445T 449T 449T 449T 449T 449T Catalog No. Y573 * Y515 * Y587 * Y574 * Y516 * Y588 * Y575 * Y517 * Y589 * Y576 * Y518 * Y577 * Y519 * Y578 * Y520 * Y579 Y531 * Y580 Y532 * Y533 * F.L.A. 147/73.5 147/73.5 142/71.0 184/92.0 180/90.0 180/90.0 230/115 230/115 250/125 143 138 170 170 230 230 295 295 330 327 385 Weight 965 1062 1380 1006 1106 1450 1308 1429 2150 2062 2110 2246 2321 2404 2457 2800 2880 2890 2950 3075 Notes

75

NEMA Design B

100

125 150 200 250 300 350

NEMA Design B

20:1

* Marathon Motors stock item. Note: B: NEMA Design B. For additional information visit www.marathonelectric.com/motors/search.asp

Blue MAX 2000 Vector Duty / Encoders Through Mod Center


Encl. Brand Model HS25A HS35A Avtron HS35M TENV M3 M56 Dynapar BEI HS35 HS35 HS35A Avtron TEFC Dynapar BEI HS35M M3 HS35 HS35 HS35A Avtron TEBC Dynapar BEI HS35M M56 HS35 HS35 PPR 1024 2048 1024 2048 1024 2048 1024 1024 1024 2048 1024 2048 1024 2048 1024 2048 1024 1024 2048 1024 2048 1024 2048 1024 2048 1024 1024 2048 1024 2048 Catalog No. A746* A747* A736* A739* A742* A744 A753* A793* A772* A776* A779* A780* A737* A740 A742* A744 A754* A774* A777* A783* A784* A738* A741* A743* A745 A794* A775* A778* A781* A782* A801* Notes Optical Hollow Shaft, MS connector Optical Hollow Shaft, MS connector Magnetic Hollow Shaft, EPIC connector Optical Hollow Shaft, EPIC connector Magnetic Modular Style, EPIC connector Shaft mount, 5-26VDC, with 10 pin connector Shaft mount, 5-26VDC, with 10 pin connector Optical Hollow Shaft, MS connector Magnetic Hollow Shaft, EPIC connector Optical Hollow Shaft, EPIC connector Shaft mount, 5-26VDC, with 10 pin connector Shaft mount, 5-26VDC, with 10 pin connector Optical Hollow Shaft, MS connector Magnetic Hollow Shaft, EPIC connector Magnetic Modular Style, EPIC connector Shaft mount, 5-26VDC, with 10 pin connector Shaft mount, 5-26VDC, with 10 pin connector Encoder Conduit box

* Marathon Motors stock item. For additional information visit www.marathonelectric.com/motors/search.asp

56