Вы находитесь на странице: 1из 1

12LV01-BE-Eq-S-001

rev.2
rev.0

2012.07.10
2012.06.07

Heating Coil & Boiler Capacity Requirement Calculation Sheet


(t 1 - T1 )
W CP
q =
ln
(t - T )

U A
2
1

U:OWNER'S INPUT

Calculating (Heating Time Required)


BT063

Vessel Q'ty

AT041/
AT042

AT043/
AT044

MT151

MT051

MT01

MT02

MT03

MT04

CB01

CB02

CORE 2500

DI-P(SJ)

I-455

SJ10W30MB

SS7KAI

SL20W40MA

SL20W40MB

nos for estimation

2.9
60.0
0.9000

3.9
100.0
0.9895

2.8
40.0
0.8660

2.8
40.0
0.9760

4.4
150.0
0.8652

3.9
100.0
0.8658

2.9
50.0
0.8601

1.9
25.0
0.8830

1.9
25.0
0.8824

1.9
20.0
0.8902

1.7
10.0
0.8956

1.7
10.0
0.8651

1.7
10.0
0.8601

2.7
3.0
1.0000

54,000
0.433
27
130
150
10
60

98,950
0.413
36
130
150
10
60

34,640
0.441
18
130
150
10
60

39,040
0.416
19
130
150
10
60

129,780
0.441
44
130
150
10
60

86,580
0.441
33
130
150
10
60

43,005
0.443
23
130
150
10
60

22,075
0.437
17
130
150
10
60

22,060
0.437
17
130
150
10
60

17,804
0.435
14
130
150
10
60

8,956
0.434
8
130
150
10
60

8,651
0.441
7
130
150
10
60

8,601
0.443
7
130
150
10
60

3,000
0.411
10
20
150
10
60

V Tank Volume
Sg Specific Gravity
W Tank Volume

m3
--kg

Cp
A
U
t1
T1
T2

kcal/(kg deg.)
m2
kcal/(m2 hr deg.)
deg.
deg.
deg.

SJ 1-W30Hi Temp A
MA

Drum
Heater

nos/Unit

hr

SJ10W30
DI-P(SJ)
MA

MT101

Gear HE 90S

Heating Time Required

Specific Heat
Coil Surface Area
Overall Coefficient
Steam Temp.
Oil Initial Temp.
Oil Target Temp.

AT101

SS7KAI
1

CALCULATION
INPUT
INPUT
CALCULATION
CALCULATION
CALCULATION
INPUT
INPUT
INPUT
INPUT

Calculating A(Heating Coil Surface Area)


9.1 CALCULATION

A Coil Surface Area

m2

26.5

34.7

17.3

18.4

43.3

32.5

21.6

16.4

16.4

13.2

6.6

6.5

6.5

Heating Time Required

hrs

4.5

2.0

2.0

2.0

3.0

180

234

120

127

290

219

148

114

114

93

50

49

49

66

145

188

96

102

233

176

119

91

91

75

40

39

39

53

98

128

65

69

158

120

81

62

62

51

27

27

27

36

Taken

Heating Coil Length L(m)


1-1/2B
2B
3B

d Coil Size

Adopt

Steam Consumption(kg/Hr)
Specific Heat/ Oil
Heat Requirement
Steam Consumption/Vessel
Steam Consumption/Vessel
Steam Consumption/Unit

kcal/(kg deg.)
kcal
kg/Hr
m3/Hr
kg/Hr

0.45
2,226,375

0.45
779,400

0.45
878,400

0.45
2,920,050

0.45
1,948,050

0.45
967,613

0.45
496,688

0.45
496,350

0.45
400,590

0.45
201,510

0.45
194,648

0.45
193,523

0.45
67,500

802

1102

514

580

1285

964

639

492

491

397

199

193

192

45

219

301

141

158

351

263

174

134

134

108

55

53

52

12

802

1102

514

580

1285

964

639

492

491

397

199

193

192

45

7,894
789
200
8,883
75
6,662

kg/Hr
kg/Hr
kg/Hr
kg/Hr
%
kg/Hr

Vessel Consumption0.1(Dicision by arrangement)

Boiler Capacity
1st Stage

7 Ton/Hr

OWNER'S INPUT
* Steam required quantity of Additive Storage Tank are estimated for 1 Tank of each item.

(2/2)

Vessel Consumption: 1st Stage


Steam Trace Consumption: 1st Stage
ISO Tank Warm-up :ISO Tank x 2 Units
Total Consumption: 1st Stage
Consumption Ratio (% )
Boiler Capacity Requirement: 1st Stage

0.45
1,215,000