Tender No.

22071 - District Cooling Singapore Technical Data - Brine Chiller 1 (Base Chiller)

1 Chiller 28C-51309, brine outlet at 4.1C, 3868 kW

make refrigerant Operating Conditions refrigeration capacity chilled brine temperature cooling water temperature power at motor shaft COP at different load conditions 100 % 75 % 50 % 25 % Evaporator, type chilled fluid flow fate entering / leaving temprature pressure drop maximal permanent operating pressure fouling factor number of passes type of tubes / wall thickness dimension of tubes, x length materiel: - tubes - shell - tube end plate isolation Condensator, type cooling fluid flow rate (including water for oilcooler) temperature of fluid entering / leaving pressure drop maximal permanent operating pressure fouling factor number of passes type of tubes / wall thickness dimension of tubes, x length materiel: - tubes - shell - tube end plate isolation kW C C kW -

Axima (SULZER) R134a 3868 4.1 30.0 756 4.90 4.99 4.55 3.03 horizontal shell & tube water, 25% Glycol 887 8.1 / 4.1 0.72 10 0.000044 2 B3 / 0.71 3/4" x 5 SF-Cu P295GH P295GH yes horizontal shell & tube water 589 30.0/ 36.8 0.69 10 0.000088 2 CLF / 0.80 3/4" x 5 SF-C P295GH P295GH no

m3/h C bar bar eff. m2K/W - / mm "/m yes/no -

m3/h C bar bar eff. m2K/W - / mm "/m yes/no

g:\ab_turbo\angebot_e\brief_e\2002rub\fernklte singapur\22071 tech daten1.doc / 15.11.02/RUB

Page 1/3

Tender No. 22071 - District Cooling Singapore Technical Data - Brine Chiller 1 (Base Chiller)

1 Chiller 28C-51309, brine outlet at 4.1C, 3868 kW

Compressor, type number type speed suction volume power at motor shaft regulation of refigaration capacity Main Drive Motor number type output on shaft supply voltage speed supply frequency mounting protection degree hazardous area insulation class temperature rise cooling Oil Pump motor-rating voltage / frequecy Oil Cooler type cooling medium Oil Heater power voltage / frequecy

min-1 m3/s %

Uniturbo 28CX 1 centrifugal, single stage 14845 1.618 756 100 to 25

kW V rpm Hz K

1 squirrel cage 800 6600 2960 50 IM 1001 (B3) IP23 safe area F 80 air cooled

kW V / Hz kW V / Hz

5.5 3 x 400 / 50 plate type cooling water 2 x 0.6 2 x 400 / 50

g:\ab_turbo\angebot_e\brief_e\2002rub\fernklte singapur\22071 tech daten1.doc / 15.11.02/RUB

Page 2/3

Tender No. 22071 - District Cooling Singapore Technical Data - Brine Chiller 1 (Base Chiller)

1 Chiller 28C-51309, brine outlet at 4.1C, 3868 kW

Commande voltage / frequency Dimensions length x width x height weight shipping weight service weight charge of refrigerant

V / Hz m kg kg kg

220 / 50 6.2 x 3.0 x 4.1 ca. 22'000 ca. 26'000 1980

g:\ab_turbo\angebot_e\brief_e\2002rub\fernklte singapur\22071 tech daten1.doc / 15.11.02/RUB

Page 3/3