Auto-transformer

for use in Reduce Voltage Motor Starter

Design:
Insulation class:
Max. room temp:
Protection class:

Dry type as per IEC 76


Class E to class H, depend on the size.
40C
IP00 open type, for installation into
IP20.
Moisture protection: Completely immerse in resin varnish and
oven cured.
Connection:
Open star-point connection.
Capacity:
Starting duty cycle is 6-8 starts per hour.
Over-temp.
A normally closed thermostat is included.
Protection:
Below specification with 415V 50Hz 3phase power supply.
Motor 415V 50Hz

Full load
current

Thermoprotection

Transfomer
tappings.

Max. Starting
times. =>70%

Max. Starting
times. =>60%

Design
type

Insulation
class

KW

HP

Sec.

Sec.

Amp
6.5

% - Un

3.75

Yes

70%

12

5.5

7.5

11

Yes

70%

12

7.5

10

14

Yes

70%

12

11

15

21

Yes

70%

14

11 (3T)

15 (3T)

21

Yes

55, 65 & 75%

14

15

20

28

Yes

55, 65 & 75%

10

16

18.5

25

35

Yes

55, 65 & 75%

11

17

22.5

30

40

Yes

55, 65 & 75%

12

19

30

40

55

Yes

55, 65 & 75%

14

22

37.5

50

66

Yes

55, 65 & 75%

16

26

45

60

80

Yes

55, 65 & 75%

18

29

56

75

100

Yes

55, 65 & 75%

21

34

66

88

120

Yes

55, 65 & 75%

24

38

80

107

140

Yes

55, 65 & 75%

27

45

A/B

94

125

165

Yes

55, 65 & 75%

30

45

A/B

110

150

200

Yes

55, 65 & 75%

30

45

132

175

230

Yes

55, 65 & 75%

30

45

150

200

260

Yes

55, 65 & 75%

30

45

185

250

325

Yes

55, 65 & 75%

30

45

225

300

385

Yes

55, 65 & 75%

30

45

260

350

450

Yes

55, 65 & 75%

30

45

300

400

520

Yes

55, 65 & 75%

30

45

335

450

580

Yes

55, 65 & 75%

30

45

375

500

650

Yes

55, 65 & 75%

30

45

450

600

Yes

55, 65 & 75%

30

45

550

750

780
950

Yes

55, 65 & 75%

30

45

** Special requirement: We can design and fabricate these type of transformer according to conditions needed.

Inter Win Engineering Sdn. Bhd. 495888-U


14, Jln BK 1/18, Tmn Perindustrian Puchong, Bdr Kinrara,
47100 Puchong, Selangor D.E. Malaysia.
Phone:603-8075-9032 & 016-3367585
Fax:603-8075-3170, E-mail: cbyip@tm.net.my
Hand phone: 019-3367585 (Benny Chan)

4 holes

Auto-transformer for use in Reduce Voltage Motor Starter

13

11

TYPE X

22

B
TYPE Y

Dimension for: Side Mounting


Motor Power
5.5 kW
7.5 kW
11kW S/T
11 kW 3/T
15 kW
18.5 kW
22 kW
30 kW
37.5 kW
45 kW
56 kW
66 kW
80 kW
94 kW

A
227
227
227
227
227
227
227
248
248
255
255
320
320
320

B
235
235
235
235
235
235
235
256
256
256
256
332
332
332

C
100
115
130
130
140
150
160
140
150
165
175
190
200
205

D
138
138
138
138
138
138
138
160
160
160
160
200
200
200

E
205
205
205
205
205
205
205
226
226
226
226
295
295
295

Connection
connector
connector
connector
10mm T. Blocks
10mm T. Blocks
10mm T. Blocks
10mm T. Blocks
10mm T. Blocks
16mm T. Blocks
16mm T. Blocks
25mm T. Blocks
25mm T. Blocks
35mm T. Blocks
35mm T. Blocks

Holes
X
X
X
X
X
X
X
X
X
X
X
Y
Y
Y

Weight (Kg)
6.00
7.50
10.00
10.00
12.50
14.50
16.00
18.00
21.00
24.00
28.00
35.00
40.00
46.00

Dimension for: Floor Mounting


Motor Power
80kW

A
315

B
305

C
180

D
113

E
170

Connection
Bolt & Nut

Holes
X

Weight - Kg
40.00

94kW

330

305

220

120

170

Bolt & Nut

46

110kW

360

305

240

130

170

Bolt & Nut

51.00

132kW

360

305

260

140

170

Bolt & Nut

60.00

150kW

360

305

260

150

170

Bolt & Nut

70.00

185kW

400

446

280

155

280

Bolt & Nut

90.00

225kW

440

446

260

170

280

Bolt & Nut

110.00

260kW

460

446

280

185

280

Bolt & Nut

120.00

300kW

460

446

315

210

280

Bolt & Nut

145.00

335kW

460

446

335

235

280

Bolt & Nut

160.00

375kW

520

510

335

235

344

Bolt & Nut

175.00

450kW

520

510

360

265

344

Bolt & Nut

190.00

550kW

520

510

400

265

344

Bolt & Nut

225

** Specification suhject to change without prior notice.**