SmartPlant Electrical

Bus Load Configuration Examples for Bus Load Calculations

Version 2009.4 (6.0.4)

September 2011

DELE2-PE-200014A

Copyright
Copyright 2002-2011 Intergraph Corporation. All Rights Reserved. Including software, file formats, and audiovisual displays; may be used pursuant to applicable software license agreement; contains confidential and proprietary information of Intergraph and/or third parties which is protected by copyright law, trade secret law, and international treaty, and may not be provided or otherwise made available without proper authorization from Intergraph Corporation.

U.S. Government Restricted Rights Legend


Use, duplication, or disclosure by the government is subject to restrictions as set forth below. For civilian agencies: This was developed at private expense and is "restricted computer software" submitted with restricted rights in accordance with subparagraphs (a) through (d) of the Commercial Computer Software - Restricted Rights clause at 52.227-19 of the Federal Acquisition Regulations ("FAR") and its successors, and is unpublished and all rights are reserved under the copyright laws of the United States. For units of the Department of Defense ("DoD"): This is "commercial computer software" as defined at DFARS 252.227-7014 and the rights of the Government are as specified at DFARS 227.7202-3. Unpublished - rights reserved under the copyright laws of the United States. Intergraph Corporation P.O. Box 240000 Huntsville, AL 35813 Street address: 170 Graphics Drive, Madison, AL 35758

Terms of Use
Use of this software product is subject to the End User License Agreement and Limited Product Warranty ("EULA") delivered with this software product unless the licensee has a valid signed license for this software product with Intergraph Corporation. If the licensee has a valid signed license for this software product with Intergraph Corporation, the valid signed license shall take precedence and govern the use of this software product. Subject to the terms contained within the applicable license agreement, Intergraph Corporation gives licensee permission to print a reasonable number of copies of the documentation as defined in the applicable license agreement and delivered with the software product for licensee's internal, non-commercial use. The documentation may not be printed for resale or redistribution.

Warranties and Liabilities


All warranties given by Intergraph Corporation about equipment or software are set forth in the EULA provided with the software or applicable license for the software product signed by Intergraph Corporation, and nothing stated in, or implied by, this document or its contents shall be considered or deemed a modification or amendment of such warranties. Intergraph believes the information in this publication is accurate as of its publication date. The information and the software discussed in this document are subject to change without notice and are subject to applicable technical product descriptions. Intergraph Corporation is not responsible for any error that may appear in this document. The software discussed in this document is furnished under a license and may be used or copied only in accordance with the terms of this license. No responsibility is assumed by Intergraph for the use or reliability of software on equipment that is not supplied by Intergraph or its affiliated companies. THE USER OF THE SOFTWARE IS EXPECTED TO MAKE THE FINAL EVALUATION AS TO THE USEFULNESS OF THE SOFTWARE IN HIS OWN ENVIRONMENT. Intergraph is not responsible for the accuracy of delivered data including, but not limited to, catalog, reference and symbol data. Users should verify for themselves that the data is accurate and suitable for their project work.

Trademarks
Intergraph, the Intergraph logo, PDS, SmartPlant, SmartMarine, FrameWorks, I-Convert, I-Export, I-Sketch, IntelliShip, INtools, ISOGEN, MARIAN, SmartSketch, SPOOLGEN, SupportManager, and SupportModeler are trademarks or registered trademarks of Intergraph Corporation or its subsidiaries in the United States and other countries. Microsoft and Windows are registered trademarks of Microsoft Corporation. MicroStation is a registered trademark of Bentley Systems, Inc. Other brands and product names are trademarks of their respective owners.

Contents
Introduction ............................................................................................................................................................................................. 4 Configuration A: Single load, continuous operating mode .................................................................................................................... 5 Configuration A: Single load, intermittent operation mode ................................................................................................................... 6 Configuration A: Single load, standby operation mode.......................................................................................................................... 7 Configuration A: single load, spare operation mode .............................................................................................................................. 8 Configuration B: Load connected to a bus without a circuit .................................................................................................................. 9 Configuration C: Bus totals including converting equipment losses .................................................................................................... 10 Configuration C: Bus totals excluding converting equipment losses ................................................................................................... 11 Configuration C: Bus totals when converting equipment is defined as a load ..................................................................................... 12 Configuration D: Bus totals accounting for load coincidence factors .................................................................................................. 13 Configuration D: Bus totals accounting for bus coincidence factors ................................................................................................... 14 Configuration D: The effect of disconnected circuits on bus load total calculation............................................................................. 15 Configuration E: A bus with mixed loads............................................................................................................................................. 16 Configuration F: Coupled buses calculated independently .................................................................................................................. 17 Configuration F: Coupled buses with the Include coupled buses connected by couplers only option ............................................. 18 Configuration F: Coupled buses with the Include coupled buses connected by couplers and risers option ..................................... 19 Configuration G: Equipment connected to an alternative power source (the main feeder and alternative feeder are connected to the different buses).......................................................... 20 Configuration H: Loads connected in parallel ...................................................................................................................................... 21 Configuration I: Several loads connected by a junction box (the JB property 'Is Load' = 'False') ....................................................... 22 Configuration I: Several loads connected by a junction box (the JB property 'Is Load' = 'True') ........................................................ 23 Configuration J: Loads connected in a daisy-chain .............................................................................................................................. 24 Configuration K: A space heater connected to an auxiliary contact..................................................................................................... 25

Bus Load Configuration Examples

Introduction
This document contains examples of bus load configurations for bus load calculations. You should use this document when reading the Calculating Bus Load Summaries section in the SmartPlant Electrical Help or User Guide.

Bus Load Configuration Examples

Configuration A: Single load, continuous operating mode


Incomer R1-A IN Uncompensated Rated Consumed P Q P Q
KW KVAR KW KVAR

Bus Incom er

Connected Compensated Rated Consumed P Q P Q


KW KVAR KW KVAR

Continuous Intermittent Stand By Spare BUS-A

11.1

6.89

8.5

5.95

11.1

6.89

8.5

5.95

X 400 V Uncompensated Rated Consumed Q S P Q S P@F P@F


KW KVAR KVA

ZZ

1
Compensated P
KW

0.4

0.1

P
KW

Q 6.89 6.89 6.89

Rated S

KVAR KVA

KVAR KVA

P@F

I
A

P
KW

KVAR KVA

Consumed S P@F

I
A

Bus

Bus Run Bus Peak Continuous Intermittent Stand By Spare Feeder CKT-2 Uncompensated Consumed Rated P Q P Q
KW KVAR KW KVAR

11.1 11.1 11.1

6.89 6.89 6.89

13.065 0.85 8.5 13.065 0.85 8.5 8.5

5.95 5.95 5.95

10.376 0.82 11.1 10.376 0.82 11.1 11.1

13.065 0.85 18.8588.5 13.065 0.85 18.8588.5 8.5

5.95 5.95 5.95

10.376 0.82 14.976 10.376 0.82 14.976

Feeders

Connected Compensated Rated Consumed P Q P Q


KW KVAR KW KVAR

Feeder CKT-3 Uncompensated Rated Consumed P Q P Q


KW KVAR KW KVAR

Connected Compensated Rated Consumed P Q P Q


KW KVAR KW KVAR

Feeder CKT-4 Uncompensated Rated Consumed P Q P Q


KW KVAR KW KVAR

Connected Compensated Consumed Rated P Q P Q KW KVAR KW KVAR

Continuous 11.1 Intermittent Stand By Spare

6.89

8.5

5.95

11.1

6.89

8.5

5.95

Continuous X 19.9 A 1 Rated P Q S PF/Eff P KW KVAR KVA 0.85 KW 11.1 6.89 13.06 0.9 8.5 Rated Power: Brake Power: M-2 380 V

Y Z ZZ 0.5 0.1 0.05 Consumed Q S PF/Eff KVAR KVA 0.82 5.95 10.38 0.88 10 kW 7.5 kW

Note: The compensated bus load values are equal to uncompensated due to the X=1.0 multiplier.

Bus Load Configuration Examples

Loads

Configuration A: Single load, intermittent operation mode


Incomer R1-D IN Uncompensated Rated Consumed P Q P Q
KW KVAR KW KVAR

Bus Incom er

Connected Compensated Rated Consumed P Q P Q


KW KVAR KW KVAR

Continious Intermittent Stand By Spare BUS-D

11.1

6.9

8.5

5.9

5.55

3.45

4.25

2.95 X Y Z ZZ

P
KW

KVAR KVA

400 V Uncompensated Rated Consumed Q S P Q S PF@ PF@


KW KVAR KVA

1
Compensated P
KW

Q 3.45 3.45 3.45

Rated S 6.535 6.535

KVAR KVA

PF@

I
A

P
KW

KVAR KVA

Consumed S PF@ 5.173 5.173

I
A

Bus

Bus Run Bus Peak Continious Intermittent Stand By Spare Feeder CKT-2 Uncompensated Consumed Rated P Q P Q
KW KVAR KW KVAR

11.1 11.1 11.1

6.9 6.9 6.9

13.07 13.07

0.85 8.5 0.85 8.5 8.5

5.9 5.9 5.9

10.347 0.82 5.55 10.347 0.82 5.55 5.55

0.85 9.432 4.25 0.85 9.432 4.25 4.25

2.95 2.95 2.95

0.82 7.467 0.82 7.467

Feeders

Connected Compensated Rated Consumed P Q P Q


KW KVAR KW KVAR

Feeder CKT-3 Uncompensated Rated Consumed P Q P Q


KW KVAR KW KVAR

Disconnected Compensated Rated Consumed P Q P Q


KW KVAR KW KVAR

Feeder CKT-4 Uncompensated Rated Consumed P Q P Q


KW KVAR KW KVAR

Connected Compensated Consumed Rated P Q P Q


KW KVAR KW KVAR

Continious Intermittent 11.1 Stand By Spare

6.9

8.5

5.9

5.55

3.45

4.25

2.95

M-5 380 V

Loads

P
KW

KVAR KVA

Intermittent X 19.9 A 1 Rated Q S P PF@ 13.1 0.85 8.5 Rated Power: Brake Power:

KW

Y Z ZZ 0.5 0.1 0.05 Consumed Q S PF@


KVAR KVA

X Rated Q S
KVAR KVA

ZZ Rated Q S
KVAR KVA

ZZ

P
KW

PF@

P
KW

Consumed Q S
KVAR KVA

PF@

P
KW

PF@

P
KW

Consumed Q S
KVAR KVA

PF@

11.1

6.9

5.9 10.3 10 kW 7.5 kW

0.82 Rated Power: Brake Power: Rated Power: Brake Power:

Note: The compensated bus load values are 50% of the uncompensated values (multiplied by the Y = 0.5 factor).

Bus Load Configuration Examples

Configuration A: Single load, standby operation mode


Incomer R1-B IN Uncompensated Consumed Rated P Q P Q
KW KVAR KW KVAR

Bus Incom er

Connected Compensated Consumed Rated P Q P Q


KW KVAR KW KVAR

Continious Intermittent Stand By Spare BUS-B

11.1

6.9

8.5

5.9

1.11

0.69

0.85

0.59 X Y Z ZZ

P
KW

KVAR KVA

400 V Uncompensated Rated Consumed Q S P Q S PF@ PF@


KW KVAR KVA

1
Compensated P
KW

Rated S

KVAR KVA

PF@

I
A

P
KW

KVAR KVA

Consumed S PF@ 1.035

I
A

Bus

Bus Run Bus Peak Continious Intermittent Stand By Spare Feeder CKT-2 Uncompensated Consumed Rated P Q P Q
KW KVAR KW KVAR

11.1

6.9

13.07

0.85 8.5

5.9

10.347 0.82 1.11

0.69

1.307

0.85 1.886 0.85

0.59

0.82 1.494

11.1

6.9

8.5

5.9

1.11

0.69

0.85

0.59

Feeders

Connected Compensated Consumed Rated P Q P Q KW KVAR KW KVAR

Feeder CKT-3 Uncompensated Rated Consumed P Q P Q


KW KVAR KW KVAR

Connected Compensated Rated Consumed P Q P Q


KW KVAR KW KVAR

Feeder CKT-4 Uncompensated Rated Consumed P Q P Q


KW KVAR KW KVAR

Connected Compensated Consumed Rated P Q P Q KW KVAR KW KVAR

Continious Intermittent Stand By 11.1 Spare

6.9

8.5

5.9

1.11

0.69

0.85

0.59

M-3 380 V

Loads

P
KW

KVAR KVA

Standby X 19.9 A 1 Rated Q S P PF@ 13.1 0.85 8.5 Rated Power: Brake Power:

KW

Y Z ZZ 0.5 0.1 0.05 Consumed Q S PF@


KVAR KVA

X Rated Q S
KVAR KVA

ZZ Rated Q S
KVAR KVA

ZZ

P
KW

PF@

P
KW

Consumed Q S
KVAR KVA

PF@

P
KW

PF@

P
KW

Consumed Q S
KVAR KVA

PF@

11.1

6.9

5.9 10.3 10 kW 7.5 kW

0.82 Rated Power: Brake Power: Rated Power: Brake Power:

Note: The compensated bus load values are 10% of the uncompensated values (multiplied by the Z = 0.1 factor).

Bus Load Configuration Examples

Configuration A: single load, spare operation mode


Incomer R1-C IN Uncompensated Rated Consumed P Q P Q
KW KVAR KW

Bus Incom er

Connected Compensated Rated Consumed P Q P Q


KVAR KW KVAR

KVAR KW

Continuous Intermittent Stand By Spare

BUS-C

P
KW

KVAR KVA

11.1 6.9 8.5 5.9 400 V Uncompensated Consumed Rated Q S P Q S P P@F P@F
KW KVAR KVA

0.555 0.345 0.425 0.295

ZZ

1
Compensated Q Rated S P@F I
A

P
KW

KW

KVAR KVA

KVAR KVA

Consumed S P@F

I
A

Bus

Bus Run Bus Peak Continuous Intermittent Stand By Spare Feeder CKT-45 Uncompensated Consumed Rated P Q P Q
KW KVAR KW

11.1

6.9

13.07

0.85 8.5

5.9

10.347 0.82 0.555 0.345 0.653

0.85 0.943 0.425 0.295 0.517

0.82 0.746

11.1 -

6.9

8.5

5.9

0.555 0.345 Connected Compensated Rated Consumed P Q P Q KVAR KW KVAR

0.425 0.295 Feeder CKT-47 Uncompensated Rated Consumed P Q P Q


KW KVAR KW

Feeders

Connected Compensated Rated Consumed P Q P Q


KVAR KW KVAR

Feeder CKT-46 Uncompensated Rated Consumed P Q P Q


KW KVAR KW

Connected Compensated Rated Consumed P Q P Q KVAR KW KVAR

KVAR KW

KVAR KW

KVAR KW

Continuous Intermittent Stand By Spare 11.1

6.9

8.5

5.9 Spare 19.9 A

0.555 0.345 0.425 0.295 X

Y Z ZZ 0.5 0.1 0.05 Rated Consumed Q S PF/Eff P Q S PF/Eff P KW KVAR KVA 0.85 KW KVAR KVA 0.82 11.1 6.9 13.1 0.9 8.5 5.9 10.3 0.88 Rated Power: 10 kW Brake Power: 7.5 kW 1

M-9 380 V

Note: The compensated bus load values are 5% of the uncompensated values (multiplied by the ZZ = 0.05 factor). Bus Load Configuration Examples 8

Loads

Configuration B: Load connected to a bus without a circuit


Incomer R1-A IN Uncompensated Rated Consumed P Q P Q
KW KVAR KW KVAR

Bus Incomer

Connected Compensated Rated Consumed P Q P Q KW KVAR KW KVAR

Continuous Intermittent Stand By Spare BUS-A

11.1

6.89

8.5

5.95

11.1

6.89

8.5

5.95

X 400 V Uncompensated Rated Consumed Q S P Q S PF@ PF@


KW KVAR KVA

ZZ

1
Compensated P
KW

0.4

0.1

P
KW

Q 6.89 6.89 6.89

Rated S

KVAR KVA

KVAR KVA

PF@

I
A

P
KW

KVAR KVA

Consumed S PF@

I
A

Bus

Bus Run Bus Peak Continuous Intermittent Stand By Spare

11.1 11.1 11.1

6.89 6.89 6.89

13.065 0.85 8.5 13.065 0.85 8.5 8.5

5.95 5.95 5.95

10.376 0.82 11.1 10.376 0.82 11.1 11.1

13.065 0.85 18.8588.5 13.065 0.85 18.8588.5 8.5

5.95 5.95 5.95

10.376 0.82 14.976 10.376 0.82 14.976

Feeders

Feeder CKT-3 Uncompensated Rated Consumed P Q P Q


KW KVAR KW KVAR

Connected Compensated Rated Consumed P Q P Q


KW KVAR KW KVAR

Feeder CKT-4 Uncompensated Consumed Rated P Q P Q


KW KVAR KW KVAR

Connected Compensated Rated Consumed P Q P Q


KW KVAR KW KVAR

Continuous Intermittent Stand By Spare Continuous X 19.9 A 1 Rated P Q S PF/Eff P KW KVAR KVA 0.85 KW 11.1 6.89 13.06 0.9 8.5 Rated Power: Brake Power: M-100 380 V Y Z ZZ 0.5 0.1 0.05 Consumed Q S PF/Eff KVAR KVA 0.82 5.95 10.38 0.88 10 kW 7.5 kW

Note: Load values are summarized on the bus even if there is no circuit equipment between the load and the bus.

Bus Load Configuration Examples

Loads

Configuration C: Bus totals including converting equipment losses


Bus Incomer
Incomer R1-F IN Uncompensated Rated Consumed P Q P Q
KW KVAR KW KVAR

Connected Compensated Rated Consumed P Q P Q KW KVAR KW KVAR

Continuous Intermittent Stand By Spare BUS-F

1.0 11.1

1.0 6.9

1.0 8.5

1.0 5.9

1.0 1.11

1.0 0.69

1.0 0.85

1.0 0.59 X Y Z ZZ

P
KW

400 V Uncompensated Rated Consumed Q S P Q S PF@ PF@


KW KVAR KVA

1
Compensated P
KW

0.4

0.1

Q 1 1.69 1.0 0.69

Rated S PF@ 1.414 0.71 2.703 0.78

I
A

P
KW

Consumed PF@ S 1.414 0.71 2.439 0.76

I
A

KVAR KVA

KVAR KVA

KVAR KVA

Bus

Bus Run Bus Peak Continuous Intermittent Stand By Spare Feeder CKT-50 Uncompensated Rated Consumed P Q P Q
KW KVAR KW KVAR

1 12.1 1.0 11.1

1 7.9 1.0 6.9

1.414 0.71 14.4510.84

1 9.5 1.0 8.5

1 6.9 1.0 5.9

1.414 0.71 11.7410.81

1 2.11 1.0 1.11

2.0 3.9

1 1.85 1.0 0.85

1 1.59 1.0 0.59

2.0 3.5

Feeders

Connected Compensated Rated Consumed P Q P Q KW KVAR KW KVAR

Feeder CKT-51 Uncompensated Consumed Rated P Q P Q


KW KVAR KW KVAR

Connected Compensated Rated Consumed P Q P Q KW KVAR KW KVAR

Feeder CKT-52 Uncompensated Rated Consumed P Q P Q


KW KVAR KW KVAR

Connected Compensated Rated Consumed P Q P Q KW KVAR KW KVAR

Continuous 1.0 Intermittent Stand By 11.1 Spare

1.0 6.9

1.0 8.5

1.0 5.9

1.0 1.11

1.0 0.69

1.0 0.85

1.0 0.59

KW

Continuous X VFD-2 Y Z ZZ Is Load 1 0.5 0.1 0.05 FALSE Resistive Losses Reactive Losses 1 kW 1 KVAR Rated Consumed P Q S P Q S PF@ Eff
KVAR KVA KW KVAR KVA

Converting

2 M-10 380 V

8.2

1.5

5.2 ZZ 0.05
PF/Eff

Standby Y Z X 19.9 A 1 0.5 0.1 Rated Consumed P Q S P Q S PF/Eff KW KVAR KVA KW KVAR KVA 0.85 11.1 6.9 13.1 0.9 8.5 5.9 10.3 Motor Rated Power: 10 kW Brake Power: 7.5 kW

Loads

0.82 0.88

Bus Load Configuration Examples

10

Configuration C: Bus totals excluding converting equipment losses


Incomer R1-F IN Uncompensated Consumed Rated P Q P Q
KW KVAR KW KVAR

Bus Incomer

Connected Compensated Rated Consumed P Q P Q


KW KVAR KW KVAR

Continuous Intermittent Stand By Spare BUS-F

11.1

6.9

8.5

5.9

1.11

0.69

0.85

0.59 X Y Z ZZ

P
KW

400 V Uncompensated Rated Consumed PF@ PF@ Q S P Q S


KW KVAR KVA

1
Compensated P
KW

0.4

0.1

Rated PF@ S

I
A

P
KW

Consumed S PF@

I
A

KVAR KVA

KVAR KVA

KVAR KVA

Bus

Bus Run Bus Peak Continuous Intermittent Stand By Spare Feeder CKT-50 Uncompensated Rated Consumed P Q P Q
KW KVAR KW KVAR

11.1

6.9

13.07 0.85

8.5

5.9

10.3470.82

1.11

0.69

1.307 0.85

1.8

0.85

0.59

1.035 0.82

1.4

11.1

6.9

8.5

5.9

1.11

0.69

0.85

0.59

Feeders

Connected Compensated Rated Consumed P Q P Q


KW KVAR KW KVAR

Feeder CKT-51 Uncompensated Rated Consumed P Q P Q


KW KVAR KW KVAR

Connected Compensated Consumed Rated P Q P Q KW KVAR KW KVAR

Feeder CKT-52 Uncompensated Rated Consumed P Q P Q


KW KVAR KW KVAR

Connected Compensated Rated Consumed P Q P Q


KW KVAR KW KVAR

Continuous Intermittent Stand By 11.1 Spare

6.9

8.5

5.9

1.11

0.69

0.85

0.59

KW

Continuous X VFD-2 Y Z ZZ 1 0.5 0.1 0.05 Is Load FALSE Reactive Losses Resistive Losses 1 kW 1 KVAR Rated Consumed P Q S P Q S PF@ Eff
KVAR KVA KW KVAR KVA

Converting

2 M-10 380 V

8.2

1.5

5.2 ZZ 0.05
PF/Eff

Standby X Y Z 1 0.5 0.1 19.9 A Rated Consumed P Q S P Q S PF/Eff KW KVAR KVA KW KVAR KVA 0.85 11.1 6.9 13.1 0.9 8.5 5.9 10.3 Motor Rated Power: 10 kW Brake Power: 7.5 kW

Loads

0.82 0.88

Bus Load Configuration Examples

11

Configuration C: Bus totals when converting equipment is defined as a load


Incomer R1-F IN Uncompensated Rated Consumed P Q P Q
KW KVAR KW KVAR

Bus Incom er

Connected Compensated Rated Consumed P Q P Q KW KVAR KW KVAR

Continuous Intermittent Stand By Spare BUS-F

1.5

1.5

X 400 V Uncompensated Rated Consumed Q S P Q S PF@ PF@


KW KVAR KVA

ZZ

1
Compensated P
KW

0.4

0.1

P
KW

Q 3 3 2

Rated S PF@ 9.487 0.95 9.487 0.95

I
A

P
KW

Q 2.5 2.5 1.5

Consumed S PF@ 6.5 6.5 0.92 0.92

I
A

KVAR KVA

KVAR KVA

KVAR KVA

Bus

Bus Run Bus Peak Continuous Intermittent Stand By Spare Feeder CKT-50 Uncompensated Rated Consumed P Q P Q
KW KVAR KW KVAR

9 9 8

3 3 2

9.487 0.95 9.487 0.95

6 6 5

2.5 2.5 1.5

6.5 6.5

0.92 0.92

9 9 8

13.6 13.6

6 6 5

9.3 9.3

Feeders

Connected Compensated Rated Consumed P Q P Q


KW KVAR KW KVAR

Feeder CKT-51 Uncompensated Consumed Rated P Q P Q


KW KVAR KW KVAR

Connected Compensated Consumed Rated P Q P Q KW KVAR KW KVAR

Feeder CKT-52 Uncompensated Rated Consumed P Q P Q


KW KVAR KW KVAR

Connected Compensated Consumed Rated P Q P Q


KW KVAR KW KVAR

Continuous 8 Intermittent Stand By Spare

1.5

1.5

KW

Continuous X VFD-2 Y Z ZZ Is Load 1 0.5 0.1 0.05 TRUE Reactive Losses Resistive Losses 1 kW 1 KVAR Rated Consumed P Q S P Q S PF@ Eff
KVAR KVA KW KVAR KVA

Converting

2 M-10 380 V

8.2

1.5

5.2 Y Z ZZ 0.5 0.1 0.05 Consumed Q S PF/Eff KVAR KVA 0.82 5.9 10.3 0.88 10 kW 7.5 kW

Standby X 19.9 A 1 Rated P Q S PF/Eff P KW KVAR KVA 0.85 KW 11.1 6.9 13.1 0.9 8.5 Motor Rated Power: Brake Power:

Bus Load Configuration Examples

Loads

12

Configuration D: Bus totals accounting for load coincidence factors


Incomer R1-E IN Uncompensated Rated Consumed P Q P Q
KW KVAR KW KVAR

Bus Incom er

Connected Compensated Rated Consumed P Q P Q


KW KVAR KW KVAR

Continuous Intermittent Stand By Spare BUS-E

1.11 1.11 1.11

0.69 0.69 0.69

0.9 0.9 0.9

0.62 0.62 0.62

1.11 0.69 0.9 0.62 0.444 0.276 0.36 0.248 0.166 0.104 0.135 0.093 X Y Z ZZ

P
KW

KVAR KVA

400 V Uncompensated Rated Consumed Q S P Q S P@F P@F


KW KVAR KVA

1
Compensated P
KW

0.4

0.1

Rated S

KVAR KVA

P@F

I
A

P
KW

KVAR KVA

Consumed S P@F

I
A

Bus

Bus Run Bus Peak Continuous Intermittent Stand By Spare Feeder CKT-2 Uncompensated Rated Consumed P Q P Q
KW KVAR KW KVAR

2.22 3.33 1.11 1.11 1.11

1.38 2.07 0.69 0.69 0.69

2.614 3.921

0.85 1.8 0.85 2.7 0.9 0.9 0.9

1.24 1.86 0.62 0.62 0.62

2.186 3.279

0.82 1.554 0.966 1.83 0.82 1.721 1.07 2.026 1.11 0.69 0.444 0.276 0.166 0.104

0.85 2.641 1.26 0.868 1.53 0.85 2.924 1.395 0.961 1.694 0.9 0.62 0.36 0.248 0.135 0.093

0.82 2.208 0.82 2.445

Feeders

Connected Compensated Consumed Rated P Q P Q KW KVAR KW KVAR

Feeder CKT-3 Uncompensated Rated Consumed P Q P Q


KW KVAR KW KVAR

Connected Compensated Rated Consumed P Q P Q KW KVAR KW KVAR

Feeder CKT-4 Uncompensated Rated Consumed P Q P Q


KW KVAR KW KVAR

Connected Compensated Consumed Rated P Q P Q KW KVAR KW KVAR

Continuous 1.11 Intermittent Stand By Spare

0.69

0.9

0.62

1.11

0.69

0.9

0.62 1.11 0.69 0.9 0.62 0.444 0.276 0.36 0.248 1.11 0.69 0.9 0.62 0.166 0.104 0.135 0.093

M-6 380 V

Loads

P
KW

KVAR KVA

Continuous X 1 2.0 A Rated Q S P P@F

KW

Y Z ZZ 0.5 0.1 0.05 Consumed Q S P@F


KVAR KVA

M-7 380 V P
KW

KVAR KVA

Intermittent X 2.0 A 1 Rated Q S P P@F

KW

Y Z ZZ 0.4 0.2 0.1 Consumed Q S P@F


KVAR KVA

M-8 380 V P
KW

KVAR KVA

Standby X 2.0 A 1 Rated Q S P P@F

KW

Y Z ZZ 0.7 0.15 0.05 Consumed Q S P@F


KVAR KVA

1.11

0.69

1.31 0.85 0.90 0.62 1.09 Rated Power: 1 kW Brake Power: 0.8 kW

0.83

1.11

0.69

1.31 0.85 0.90 0.62 1.09 Rated Power: 1 kW Brake Power: 0.8 kW

0.83

1.11

0.69

1.31 0.85 0.90 0.62 1.09 Rated Power: 1 kW Brake Power: 0.8 kW

0.83

Note: The bus coincidence factors do not affect the calculation in this example.

Bus Load Configuration Examples

13

Configuration D: Bus totals accounting for bus coincidence factors


Incomer R1-E IN Uncompensated Rated Consumed P Q P Q
KW KVAR KW KVAR

Bus Incomer

Connected Compensated Rated Consumed P Q P Q


KW KVAR KW KVAR

Continuous Intermittent Stand By Spare BUS-E

1.11 1.11 1.11

0.69 0.69 0.69

0.9 0.9 0.9

0.62 0.62 0.62

1.11 0.69 0.9 0.444 0.276 0.36 0.111 0.069 0.09

0.62 0.248 0.062 X Y Z ZZ

P
KW

KVAR KVA

400 V Uncompensated Consumed Rated Q S P Q S P@F P@F


KW KVAR KVA

1
Compensated P
KW

0.4

0.1

Rated S

KVAR KVA

P@F

I
A

P
KW

KVAR KVA

Consumed S P@F

I
A

Bus

Bus Run Bus Peak Continuous Intermittent Stand By Spare Feeder CKT-2 Uncompensated Rated Consumed P Q P Q
KW KVAR KW KVAR

2.22 3.33 1.11 1.11 1.11

1.38 2.07 0.69 0.69 0.69

2.614 3.921

0.85 1.8 0.85 2.7 0.9 0.9 0.9

1.24 1.86 0.62 0.62 0.62

2.186 3.279

0.82 1.554 0.966 1.83 0.82 1.665 1.035 1.96 1.11 0.69 0.444 0.276 0.111 0.069

0.85 2.641 1.26 0.85 2.829 1.35 0.9 0.36 0.09

0.868 1.53 0.93 1.639 0.62 0.248 0.062

0.82 2.208 0.82 2.366

Feeders

Connected Compensated Rated Consumed P Q P Q KW KVAR KW KVAR

Feeder CKT-3 Uncompensated Consumed Rated P Q P Q


KW KVAR KW KVAR

Connected Compensated Rated Consumed P Q P Q


KW KVAR KW KVAR

Feeder CKT-4 Uncompensated Rated Consumed P Q P Q


KW KVAR KW KVAR

Connected Compensated Rated Consumed P Q P Q KW KVAR KW KVAR

Continuous 1.11 Intermittent Stand By Spare

0.69

0.9

0.62

1.11

0.69

0.9

0.62 1.11 0.69 0.9 0.62 0.444 0.276 0.36 0.248 1.11 0.69 0.9 0.62 0.111 0.069 0.09 0.062

M-6 380 V

Loads

P
KW

KVAR KVA

Continuous X 2.0 A 1 Rated Q S P P@F

KW

Z ZZ Y 0.5 0.1 0.05 Consumed Q S P@F


KVAR KVA

M-7 380 V P
KW

KVAR KVA

Intermittent X 2.0 A 1 Rated Q S P P@F

KW

Y Z ZZ 0.6 0.2 0.1 Consumed Q S P@F


KVAR KVA

M-8 380 V P
KW

KVAR KVA

Standby X 2.0 A 1 Rated Q S P P@F

KW

Y Z ZZ 0.7 0.2 0.05 Consumed Q S P@F


KVAR KVA

1.11

0.69

1.31 0.85 0.90 0.62 1.09 Rated Power: 1 kW Brake Power: 0.8 kW

0.83

1.11

0.69

1.31 0.85 0.90 0.62 1.09 Rated Power: 1 kW Brake Power: 0.8 kW

0.83

1.11

0.69

1.31 0.85 0.90 0.62 1.09 Rated Power: 1 kW Brake Power: 0.8 kW

0.83

Note: The load coincidence factors do not affect the calculation in this example.

Bus Load Configuration Examples

14

Configuration D: The effect of disconnected circuits on bus load total calculation


Incomer R1-E IN Uncompensated Rated Consumed P Q P Q
KW KVAR KW KVAR

Bus Incom er

Connected Compensated Rated Consumed P Q P Q


KW KVAR KW KVAR

Continuous Intermittent Stand By Spare BUS-E

1.1

0.69

0.9

0.62

0.11

0.069 0.09

0.062 X Y Z ZZ

P
KW

KVAR KVA

400 V Uncompensated Consumed Rated Q S P Q S PF@ PF@


KW KVAR KVA

1
Compensated P
KW

0.4

0.1

Rated S

KVAR KVA

PF@

I
A

P
KW

KVAR KVA

Consumed S PF@

I
A

Bus

Bus Run Bus Peak Continuous Intermittent Stand By Spare Feeder CKT-2 Uncompensated Consumed Rated P Q P Q
KW KVAR KW KVAR

1.1

0.69

1.298

0.85 0.9

0.62

1.093

0.82 0.11

0.069 0.13

0.85 0.188 0.09

0.062 0.109

0.83 0.157

1.1

0.69

0.9

0.62

0.11

0.069

0.09

0.062

Feeders

Disconnected Compensated Rated Consumed P Q P Q


KW KVAR KW KVAR

Feeder CKT-3 Uncompensated Rated Consumed P Q P Q


KW KVAR KW KVAR

Disconnected Compensated Rated Consumed P Q P Q


KW KVAR KW KVAR

Feeder CKT-4 Uncompensated Consumed Rated P Q P Q


KW KVAR KW KVAR

Connected Compensated Rated Consumed P Q P Q


KW KVAR KW KVAR

Continuous Intermittent Stand By Spare M-6 380 V Continuous X 1 2.0 A Rated Q S P PF@ 1.30 0.85 0.9 Rated Power: Brake Power: Y Z ZZ 0.5 0.1 0.05 Consumed Q S PF@
KVAR KVA

1.1

0.69

0.9

0.62

0.11

0.069 0.09

0.062

M-7 380 V P
KW

Loads

P
KW

KVAR KVA

KW

KVAR KVA

Intermittent X 2.0 A 1 Rated Q S P PF@ 1.30 0.85 0.9 Rated Power: Brake Power:

KW

Y Z ZZ 0.5 0.1 0.05 Consumed Q S PF@


KVAR KVA

M-8 380 V P
KW

KVAR KVA

Standby X 2.0 A 1 Rated Q S P PF@ 1.30 0.85 0.9 Rated Power: Brake Power:

KW

Y Z ZZ 0.5 0.1 0.05 Consumed Q S PF@


KVAR KVA

1.1

0.69

0.62 1.09 1 kW 0.8 kW

0.83

1.1

0.69

0.62 1.09 1 kW 0.8 kW

0.83

1.1

0.69

0.62 1.09 1 kW 0.8 kW

0.83

Note: The circuit in "Disconnected" mode breaks the plant drill-down workflow. The load data below the disconnected circuit is not rolled up. As a result, the calculation of the bus totals above that circuit doesn't take in account the loads connected below the circuit.

Bus Load Configuration Examples

15

Configuration E: A bus with mixed loads


Bus Incom er
Incomer SW-C IN Uncompensated Rated Consumed P Q P Q
KW KVAR KW KVAR

Connected Compensated Consumed Rated P Q P Q


KW KVAR KW KVAR

Continuous Intermittent Stand By Spare SW-C

16.5 16.5 49.9 16.5

7.02 7.02 27.68 7.02

8.9 8.9 30.5 8.9

8.26 8.26 25.74 8.26

16.5 8.25 4.99 0.825

7.02 3.51 2.768 0.351

8.9 4.45 3.05 0.445

8.26 4.13 2.574 0.413

ZZ

P
KW

KVAR KVA

3300 V Uncompensated Rated Consumed Q S P Q S PF@ PF@


KW KVAR KVA

1
Compensated P
KW

Rated S

KVAR KVA

PF@

I
A

P
KW

KVAR KVA

Consumed S PF@

I
A

Bus

Bus Run Bus Peak Continuous Intermittent Stand By Spare Feeder CKT-46 Uncompensated Rated Consumed P Q P Q
KW KVAR KW KVAR

37.5 19.04 42.057 0.89 22.3 103.9 53.74 116.97 0.89 61.7 16.5 16.5 49.9 16.5 7.02 7.02 27.68 7.02 8.9 8.9 30.5 8.9

21.52 30.99 0.72 29.25 15.53 33.117 0.88 5.794 17.85 17.39 24.921 0.72 4.36 55.52 83.002 0.74 35.06518.64939.716 0.88 6.948 21.34520.37729.51 0.72 5.163 8.26 8.26 25.74 8.26 16.5 8.25 4.99 0.825 7.02 3.51 2.768 0.351 Connected Compensated Rated Consumed P Q P Q
KW KVAR KW KVAR

8.9 4.45 3.05 0.445

8.26 4.13 2.574 0.413 Feeder CKT-51 Uncompensated Rated Consumed P Q P Q


KW KVAR KW KVAR

Feeders

Connected Compensated Rated Consumed P Q P Q


KW KVAR KW KVAR

Feeder CKT-50 Uncompensated Consumed Rated P Q P Q


KW KVAR KW KVAR

Connected Compensated Rated Consumed P Q P Q KW KVAR KW KVAR

Continuous Intermittent Stand By Spare

18.5 16.5 16.5 16.5

10.02 7.02 7.02 7.02

10.9 8.9 8.9 8.9

11.26 8.26 8.26 8.26

18.5 8.25 1.65 0.825

10.02 3.51 0.702 0.351

10.9 4.45 0.89 0.445

11.26 4.13 0.826 0.413

2.5 16.7

2.5

2 8.74

2.5 1.67

2.5

2 0.874 16.7 10.33 10.8 8.74 1.67 1.033 1.08 0.874

10.33 10.8

1.033 1.08

KW

Continuous X Y Z ZZ T-10 1 Is Load FALSE Reactive Losses Resistive Losses 2 kW 3 kVAR Rated Consumed P Q S P Q S PF@ Eff
KVAR KVA KW KVAR KVA

KW

Intermittent X VFD-3 Y Z ZZ 1 0.6 0.15 0.1 Is Load FALSE Resistive Losses Reactive Losses 2.5 kW 2 KVAR Consumed Rated P Q S P Q S PF@ Eff
KVAR KVA KW KVAR KVA

Converting

100

12

100.7 50

7 -

50.5 Connected Compensated Rated Consumed P Q P Q


KW KVAR KW KVAR

50

12 M-14 3300 V

51.4

30

31.3 Standby X Y Z 1 0.5 0.1 29.8 A Rated Consumed P Q S PF/Eff P Q S KW KVAR KVA 0.85 KW KVAR KVA 16.7 10.33 19.64 0.9 10.8 8.74 13.89 Rated Power: 15 kW Brake Power: 9 kW M-13 380 V ZZ 0.05

Loads

Incomer I IN1 Uncompensated Rated Consumed P Q P Q


KW KVAR KW KVAR

16.5 16.5 16.5 16.5

7.02 7.02 7.02 7.02

8.9 8.9 8.9 8.9

8.26 8.26 8.26 8.26

16.5 8.25 1.65

7.02 8.9 3.51 4.45 0.702 0.89

8.26 4.13 0.826

Standby X Y Z ZZ 1 0.5 0.1 0.05 3.4 A Consumed Rated P Q S PF/Eff P Q S PF/Eff KW KVAR KVA 0.85 KW KVAR KVA 0.78 16.7 10.33 19.64 0.9 10.8 8.74 13.89 0.83 Rated Power: Motor Rated Power: Brake Power: otor 2::Brake Power:

PF/Eff
0.78 0.83

0.825 0.351 0.445 0.413

Bus Load Configuration Examples

16

Configuration F: Coupled buses calculated independently


Incomer Connected G IN1 Uncompensated Compensated Rated Consumed Rated Consumed P Q P Q P Q P Q
KW KVA KW KVA KW KVA KW KVA

Bus Incom er

Incomer Connected H IN1 Uncompensated Compensated Rated Consumed Rated Consumed P Q P Q P Q P Q


KW KVA KW KVA KW KVA KW KVA

Continuous Intermittent Stand By Spare BUS-G

1.11 0.69 0.9

0.62 1.11 0.69 0.9

0.62 1.11 0.69 0.9 X Y Z ZZ BUS-H 400 V Uncompensated Consumed Rated Q S P Q S PF@ PF@
KW KVA KVA

0.62 0.1660.1040.1350.093 X Y Z ZZ

KW KVA KVA

400 V Uncompensated Rated Consumed Q S P Q S PF@ PF@


KW KVA KVA

1
Compensated P Rated Q S PF@ I
A

0.4 0.1 0
Consumed Q S PF@

1
Compensated P Rated Q S PF@ I
A

0.4 0.1 0
Consumed Q S PF@

I
A

I
A

KW KVA KVA

KW KVA KVA

KW KVA KVA

KW KVA KVA

KW KVA KVA

Bus

Bus Run 1.11 0.69 1.307 0.85 0.9 Bus Peak 1.11 0.69 1.307 0.85 0.9 Continuous 1.11 0.69 Intermittent Stand By Spare 0.9

0.62 1.093 0.82 1.11 0.69 1.307 0.85 1.8860.9 0.62 1.093 0.82 1.11 0.69 1.307 0.85 1.8860.9 0.62 1.11 0.69 0.9

0.62 1.093 0.82 1.578 0.62 1.093 0.82 1.578 0.62

1.11 0.69 1.307 0.85 0.9

0.62 1.093 0.82 0.1660.1040.196 0.85 0.2830.1350.0930.164 0.82 0.237

1.11 0.69

0.9

0.62

0.1660.104

0.1350.093

Feeders

Feeder Connected G-FED1 Uncompensated Compensated Rated Consumed Rated Consumed P Q P Q P Q P Q


KW KVA KW KVA KW KVA KW KVA

Connected G-H Coupler Coupler Compensated Uncompensated Rated Consumed Rated Consumed P Q P Q P Q P Q
KW KVA KW KVA KW KVA KW KVA

Connected G-H Riser Bus Riser Compensated Uncompensated Rated Consumed Rated Consumed P Q P Q P Q P Q
KW KVA KW KVA KW KVA KW KVA

Feeder Connected H-FED1 Uncompensated Compensated Rated Consumed Rated Consumed P Q P Q P Q P Q


KW KVA KW KVA KW KVA KW KVA

Continuous 1.11 0.69 0.9 Intermittent Stand By Spare

0.62 1.11 0.69 0.9

0.62 1.11 0.69 0.9 0.62 0.1660.1040.1350.093

Y Z ZZ M-10 Continuous X 2.0 A 1 0.7 0.2 0.1 380 V Rated Consumed Q S PF@/Eff P Q S PF@ P KW KVA KVA 0.9 KW KVA KVA 0.8 1.11 0.69 1.31 0.9 0.90 0.62 1.09 0.9 Rated Power: 1 kW Brake Power: 0.8 kW

Standby X Y Z ZZ M-11 0.7 0.2 0.1 380 V 2.0 A 1 Rated Consumed P Q S PF@ P Q S PF@/Eff KW KVA KVA 0.9 KW KVA KVA 0.8 1.11 0.69 1.31 0.9 0.90 0.62 1.09 0.9 Rated Power: 1 kW Brake Power: 0.8 kW

Notes: Each bus is calculated independently and has no effect on the adjacent bus. The coupler and riser load values are not entered by the software. Bus Load Configuration Examples 17

Loads

Configuration F: Coupled buses with the Include coupled buses connected by couplers only option
Connected Incomer G IN1 Compensated Uncompensated Rated Consumed Rated Consumed P Q P Q P Q P Q
KW KVA KW KVA KW KVA KW KVA

Bus Incomer

Connected Incomer H IN1 Uncompensated Compensated Rated Consumed Rated Consumed P Q P Q P Q P Q


KW KVA KW KVA KW KVA KW KVA

Continuous Intermittent Stand By Spare BUS-G

1.11 0.69 0.9 1.11 0.69 0.9 400 V Uncompensated Rated Consumed Q S P Q S PF PF
KW KVA KVA

0.62 1.11 0.69 0.9

0.62 1.11 0.69 0.9 X Y Z ZZ BUS-H 400 V Uncompensated Rated Consumed Q S P Q S PF PF


KW KVA KVA

0.62 0.1660.1040.1350.093

0.62 0.1660.1040.1350.093 X Y Z ZZ

1
Compensated P Rated Q S PF I
A

0.4 0.1 0
Consumed Q S PF

1
Compensated P Rated Q S PF I
A

0.4 0.1 0
Consumed Q S PF

I
A

I
A

KW KVA KVA

KW KVA KVA

KW KVA KVA

KW KVA KVA

KW KVA KVA

KW KVA KVA

Bus

Bus Run 1.11 0.69 1.307 0.85 0.9 Bus Peak 2.22 1.38 2.614 0.85 1.8 Continuous 1.11 0.69 Intermittent Stand By 1.11 0.69 Spare 0.9 0.9

0.62 1.093 0.82 1.11 0.69 1.307 0.85 1.8860.9 0.62 1.093 0.82 1.578 1.24 2.186 0.82 1.2770.7941.503 0.85 2.1691.0350.7131.257 0.82 1.814 0.62 0.62 1.11 0.69 0.1660.104 0.9 0.62

1.11 0.69 1.307 0.85 0.9

0.62 1.093 0.82 0.1660.1040.196 0.85 0.2830.1350.0930.164 0.82 0.237

0.1350.093

1.11 0.69

0.9

0.62

0.1660.104

0.1350.093

Feeders

Feeder Connected G-FED1 Uncompensated Compensated Rated Consumed Rated Consumed P Q P Q P Q P Q


KW KVA KW KVA KW KVA KW KVA

Connected G-H Coupler Coupler Compensated Uncompensated Rated Consumed Rated Consumed P Q P Q P Q P Q
KW KVA KW KVA KW KVA KW KVA

Connected G-H Riser Bus Riser Compensated Uncompensated Rated Consumed Rated Consumed P Q P Q P Q P Q
KW KVA KW KVA KW KVA KW KVA

Feeder Connected H-FED1 Uncompensated Compensated Rated Consumed Rated Consumed P Q P Q P Q P Q


KW KVA KW KVA KW KVA KW KVA

Continuous 1.11 0.69 0.9 Intermittent Stand By Spare

0.62 1.11 0.69 0.9

0.62 1.11 0.69 0.9 0.62 0.1660.1040.1350.093 1.11 0.69 0.9 0.62 0.1660.1040.1350.093

M-10 Continuous X Z ZZ Y 0.7 0.2 0.1 380 V 2.0 A 1 Rated Consumed P Q S PF/E P Q S PF/Eff KW KVA KVA 0.9 KW KVA KVA 0.8 1.11 0.69 1.31 0.9 0.90 0.62 1.09 0.9 Rated Power: 1 kW Brake Power: 0.8 kW

Standby X Y Z ZZ M-11 0.7 0.2 0.1 380 V 2.0 A 1 Rated Consumed P Q S PF/E P Q S PF/E KW KVA KVA 0.9 KW KVA KVA 0.8 1.11 0.69 1.31 0.9 0.90 0.62 1.09 0.9 Rated Power: 1 kW Brake Power: 0.8 kW

Notes:

Loads

Bus G, which powers all the loads (directly and through a coupler), summarizes all the system loads. Bus H, powered by Bus G (through a riser), summarizes only the down flow loads. The incomer circuit of Bus G displays the total loads of the whole system. The values of the riser circuit of the powered bus are not entered by the software.

Bus Load Configuration Examples

18

Configuration F: Coupled buses with the Include coupled buses connected by couplers and risers option
Incomer Connected G IN1 Uncompensated Compensated Rated Consumed Rated Consumed P Q P Q P Q P Q
KW KVA KW KVA KW KVA KW KVA

Bus Incomer

Connected Incomer H IN1 Uncompensated Compensated Rated Consumed Rated Consumed P Q P Q P Q P Q


KW KVA KW KVA KW KVA KW KVA

Continuous Intermittent Stand By Spare BUS-G

1.11 0.69 0.9 1.11 0.69 0.9 400 V Uncompensated Consumed Rated Q S P Q S PF PF
KW KVA KVA

0.62 1.11 0.69 0.9

0.62

1.11 0.69 0.9 1.11 0.69 0.9 X Y Z ZZ BUS-H 400 V Uncompensated Rated Consumed Q S P Q S PF PF
KW KVA KVA

0.62 1.11 0.69 0.9

0.62

0.62 0.1660.1040.1350.093

0.62 0.1660.1040.1350.093 X Y Z ZZ

1
Compensated P Rated Q S PF I
A

0.4 0.1 0
Consumed Q S PF

1
Compensated P Rated Q S PF I
A

0.4 0.1 0
Consumed Q S PF

I
A

I
A

KW KVA KVA

KW KVA KVA

KW KVA KVA

KW KVA KVA

KW KVA KVA

KW KVA KVA

Bus

Bus Run 1.11 0.69 1.307 0.85 0.9 Bus Peak 2.22 1.38 2.614 0.85 1.8 Continuous 1.11 0.69 Intermittent Stand By 1.11 0.69 Spare 0.9 0.9

0.62 1.093 0.82 1.11 0.69 1.307 0.85 1.8860.9 0.62 1.093 0.82 1.578 1.24 2.186 0.82 1.2770.7941.503 0.85 2.1691.0350.7131.257 0.82 1.814 0.62 0.62 1.11 0.69 0.1660.104 0.9 0.62

1.11 0.69 1.307 0.85 0.9 2.22 1.38 2.614 0.85 1.8 1.11 0.69 1.11 0.69 0.9 0.9

0.62 1.093 0.82 1.11 0.69 1.307 0.85 1.8860.9 0.62 1.093 0.82 1.578 1.24 2.186 0.82 1.2770.7941.503 0.85 2.1691.0350.7131.257 0.82 1.814 0.62 0.62 1.11 0.69 0.1660.104 0.9 0.62

0.1350.093

0.1350.093

Feeders

Feeder Connected G-FED1 Uncompensated Compensated Rated Consumed Rated Consumed P Q P Q P Q P Q


KW KVA KW KVA KW KVA KW KVA

Connected G-H Coupler Coupler Uncompensated Compensated Rated Consumed Rated Consumed P Q P Q P Q P Q
KW KVA KW KVA KW KVA KW KVA

Connected G-H Riser Bus Riser Uncompensated Compensated Rated Consumed Rated Consumed P Q P Q P Q P Q
KW KVA KW KVA KW KVA KW KVA

Connected Feeder H-FED1 Uncompensated Compensated Rated Consumed Rated Consumed P Q P Q P Q P Q


KW KVA KW KVA KW KVA KW KVA

Continuous 1.11 0.69 0.9 Intermittent Stand By Spare

0.62 1.11 0.69 0.9

0.62 1.11 0.69 0.9 0.62 0.1660.1040.1350.093

1.11 0.69 0.9

0.62 1.11 0.69 0.9

0.62 1.11 0.69 0.9 0.62 0.1660.1040.1350.093

M-10 Continuous X Z ZZ Y 380 V 2.0 A 1 0.7 0.2 0.1 Rated Consumed Q S PF/Eff P Q S PF/E P KW KVA KVA 0.9 KW KVA KVA 0.8 1.11 0.69 1.31 0.9 0.90 0.62 1.09 0.9 Rated Power: 1 kW Brake Power: 0.8 kW

Standby X Y Z ZZ M-11 380 V 2.0 A 1 0.7 0.2 0.1 Rated Consumed P Q S PF/E P Q S PF/E KW KVA KVA 0.9 KW KVA KVA 0.8 1.11 0.69 1.31 0.9 0.90 0.62 1.09 0.9 Rated Power: 1 kW Brake Power: 0.8 kW

Notes: Both buses display exactly the same total loads. They are equal to the sum of all the system loads. The coupler and riser circuits display the total loads from the adjacent buses for each bus.

Bus Load Configuration Examples

Loads

19

Configuration G: Equipment connected to an alternative power source (the main feeder and alternative feeder are connected to the different buses)
Incomer CKT-55 Uncompensated Rated Consumed P Q P Q
KW KVAR KW

Bu s In co m er

Connected Compensated Rated Consumed P Q P Q KVAR KW KVAR

Incomer CKT-59 Uncompensated Rated Consumed P Q P Q


KW KVAR KW

Connected Compensated Rated Consumed P Q P Q KVAR KW KVAR

KVAR KW

KVAR KW

Continuous Intermittent Stand By Spare BUS-14

11.11 6.89 8.52 5.95 11.11 6.89 8.52 5.95

X 400 V Uncompensated Consumed Rated Q S P Q S PF


KW KVAR KVA

ZZ

X BUS-15 400 V Uncompensated Consumed Rated Q S P Q S PF


KW KVAR KVA

ZZ

1
Compensated PF P
KW

0.4

0.1

1
Compensated PF P
KW

0.4

0.1

P
KW

Rated S

KVAR KVA

KVAR KVA

PF

I
A

P
KW

KVAR KVA

Consumed Q S PF

I
A

P
KW

Rated S

KVAR KVA

KVAR KVA

PF

I
A

P
KW

KVAR KVA

Consumed S PF

I
A

Bu s

Bus Run 11.11 6.89 13.073 0.85 8.52 5.95 10.392 0.82 11.11 6.89 13.073 0.85 18.8698.52 5.95 10.392 0.82 15 Bus Peak 11.11 6.89 13.073 0.85 8.52 5.95 10.392 0.82 11.11 6.89 13.073 0.85 18.8698.52 5.95 10.392 0.82 15 Continuous 11.11 6.89 Intermittent Stand By Spare Feeder CKT-56 Uncompensated Rated Consumed P Q P Q
KW KVAR KW

8.52 5.95

11.11 6.89

8.52 5.95

F eed ers

Connected Compensated Rated Consumed P Q P Q KVAR KW KVAR

Feeder CKT-60 Uncompensated Rated Consumed P Q P Q


KW KVAR KW

Disconnected Compensated Rated Consumed P Q P Q KVAR KW KVAR

KVAR KW

KVAR KW

Continuous 11.11 6.89 8.52 5.95 11.11 6.89 8.52 5.95 Intermittent Stand By Spare main power source Continuous X 19.9 A 1 Rated P Q S PF/Eff P KW KVAR KVA 0.85 KW 11.11 6.89 13.07 0.9 8.52 Rated Power: Brake Power: M-12 380 V alternative power source Y Z ZZ 0.5 0.1 0.05 Consumed Q S PF/Eff KVAR KVA 0.82 5.95 10.39 0.88 10 kW 7.5 kW

Bus Load Configuration Examples

L o ad s

20

Configuration H: Loads connected in parallel


PAR1-IN Incomer Uncompensated Consumed Rated P Q P Q
KW KVAR KW KVAR

Bus Incomer

Connected Compensated Consumed Rated P Q P Q KW KVAR KW KVAR

Continuous Intermittent Stand By Spare BUS-A

33.3

20.67 25.5

17.85 33.3

20.67 25.5

17.85

X 400 V Uncompensated Rated Consumed Q S P Q S PF@


KVA KW KVAR KVA

ZZ

1
Compensated PF@ P
KW

0.4

0.1

P
KW

Q
KVAR

Rated S
KVA

KVAR

PF@

I
A

P
KW

KVAR

Consumed S PF@
KVA

I
A

Bus

Bus Run Bus Peak Continuous Intermittent Stand By Spare AM-010/FD Feeder Uncompensated Consumed Rated P Q P Q
KW KVAR KW KVAR

33.3 33.3 33.3

20.67 39.194 0.85 25.5 20.67 39.194 0.85 25.5 20.67 25.5

17.85 31.127 0.82 33.3 17.85 31.127 0.82 33.3 17.85 33.3

20.67 39.194 0.85 56.572 25.5 20.67 39.194 0.85 56.572 25.5 20.67 25.5

17.85 31.127 0.82 44.928 17.85 31.127 0.82 44.928 17.85

Feeders

Connected Compensated Consumed Rated P Q P Q KW KVAR KW KVAR

CKT-4 Feeder Uncompensated Rated Consumed P Q P Q


KW KVAR KW KVAR

Connected Compensated Rated Consumed P Q P Q


KW KVAR KW KVAR

CKT-5 Feeder Uncompensated Rated Consumed P Q P Q


KW KVAR KW KVAR

Connected Compensated Consumed Rated P Q P Q KW KVAR KW KVAR

Continuous 33.3 Intermittent Stand By Spare

20.67 25.5

17.85 33.3

20.67 25.5

17.85

Loads

X 101-AM-10 Continuous 380 V 19.9 A 1 Rated P Q S P PF@


KW KVAR KVA

KW

Y Z ZZ 0.5 0.1 0.05 Consumed Q S PF@


KVAR KVA

101-AM-10 Continuous X 380 V 19.9 A 1 Rated P Q S P PF@


KW KVAR KVA

KW

Y Z ZZ 0.5 0.1 0.05 Consumed Q S PF@


KVAR KVA

101-AM-12 Continuous X 19.9 A 380 V 1 Rated P Q S P PF@


KW KVAR KVA

KW

Y Z ZZ 0.5 0.1 0.05 Consumed Q S PF@


KVAR KVA

11.1

6.89

13.06 0.85 8.5 Rated Power: Consumed Power:

5.95 10.38 0.82 10 kW 7.5 kW

11.1

6.89

13.06 0.85 8.5 Rated Power: Consumed Power:

5.95 10.38 0.82 10 kW 7.5 kW

11.1

6.89

13.06 0.85 8.5 Rated Power: Consumed Power:

5.95 10.38 0.82 10 kW 7.5 kW

Bus Load Configuration Examples

21

Configuration I: Several loads connected by a junction box (the JB property 'Is Load' = 'False')
Incomer MCC-L IN1 Uncompensated Consumed Rated P Q P Q
KW KVAR KW

Bus Incom er

Connected Compensated Consumed Rated P Q P Q


KVAR KW KVAR

KVAR KW

Continuous Intermittent Stand By Spare BUS-L

33.3

20.7

25.5

17.9

33.3

20.7

25.5

17.9

X 400 V Uncompensated Rated Consumed Q S P Q S PF@ PF@


KW KVAR KVA

ZZ

1
Compensated P
KW

0.4

0.1

P
KW

Rated S

KVAR KVA

KVAR KVA

PF@

I
A

P
KW

KVAR KVA

Consumed S PF@

I
A

Bus

Bus Run Bus Peak Continuous Intermittent Stand By Spare Feeder CKT-60 Uncompensated Rated Consumed P Q P Q
KW KVAR KW

33.3 33.3 33.3

20.67 39.194 0.85 25.5 20.67 39.194 0.85 25.5 20.67 25.5

17.85 31.127 0.82 33.3 17.85 31.127 0.82 33.3 17.85 33.3

20.67 39.194 0.85 56.57225.5 20.67 39.194 0.85 56.57225.5 20.67 25.5

17.85 31.127 0.82 44.928 17.85 31.127 0.82 44.928 17.85

Feeders

Connected Compensated Consumed Rated P Q P Q KVAR KW KVAR

Feeder CKT-61 Uncompensated Rated Consumed P Q P Q


KW KVAR KW

Connected Compensated Rated Consumed P Q P Q


KVAR KW KVAR

Feeder CKT-83 Uncompensated Consumed Rated P Q P Q


KW KVAR KW

Connected Compensated Rated Consumed P Q P Q


KVAR KW KVAR

KVAR KW

KVAR KW

KVAR KW

Continuous Intermittent Stand By Spare

33.3

20.67 25.5

17.85 33.3

20.67 25.5

17.85

JB-3

Is Load: False

M-23 380 V

Loads

P
KW

KVAR KVA

Continuous X 19.9 A 1 Rated Q S P PF@ 13.06 0.85 8.5 Rated Power: Brake Power:

KW

Y Z ZZ 0.5 0.1 0.05 Consumed Q S PF@


KVAR KVA

M-24 380 V P
KW

KVAR KVA

Continuous X 19.9 A 1 Rated Q S P PF@ 13.06 0.85 8.5 Rated Power: Brake Power:

KW

Y Z ZZ 0.5 0.1 0.05 Consumed Q S PF@


KVAR KVA

M-25 380 V P
KW

KVAR KVA

Continuous X 1 19.9 A Rated Q S P PF@ 13.06 0.85 8.5 Rated Power: Brake Power:

KW

Y Z ZZ 0.5 0.1 0.05 Consumed Q S PF@


KVAR KVA

11.1

6.89

5.95 10.38 0.82 10 kW 7.5 kW

11.1

6.89

5.95 10.38 0.82 10 kW 7.5 kW

11.1

6.89

5.95 10.38 0.82 10 kW 7.5 kW

Notes: A JB device is used to split the power between the loads. You can use a local panel for the same purpose. The "Is Load" property of the JB is set to "False". Bus Load Configuration Examples 22

Configuration I: Several loads connected by a junction box (the JB property 'Is Load' = 'True')
Incomer MCC-L IN1 Uncompensated Rated Consumed P Q P Q
KW KVAR KW KVAR

Bus Incomer

Connected Compensated Rated Consumed P Q P Q


KW KVAR KW KVAR

Continuous Intermittent Stand By Spare BUS-L

22

20

8.8

1.6 X Y Z ZZ

P
KW

KVAR KVA

400 V Uncompensated Consumed Rated Q S P Q S PF@ PF@


KW KVAR KVA

1
Compensated P
KW

0.4

0.1

Q 2.00 2.00 2.00

Rated S 9.02 9.02

KVAR KVA

PF@

I
A

P
KW

KVAR KVA

Consumed S PF@ 8.16 8.16

I
A

Bus

Bus Run Bus Peak Continuous Intermittent Stand By Spare Feeder CKT-60 Uncompensated Rated Consumed P Q P Q
KW KVAR KW KVAR

22.00 5.00 22.00 5.00 22.00 5.00

22.56 22.56

0.98 20.00 4.00 0.98 20.00 4.00 20.00 4.00

20.40 20.40

0.98 8.80 0.98 8.80 8.80

0.98 13.03 8.00 0.98 13.03 8.00 8.00

1.60 1.60 1.60

0.98 11.8 0.98 11.8

Feeders

Connected Compensated Rated Consumed P Q P Q KW KVAR KW KVAR

Feeder CKT-61 Uncompensated Rated Consumed P Q P Q


KW KVAR KW KVAR

Connected Compensated Rated Consumed P Q P Q KW KVAR KW KVAR

Feeder CKT-83 Uncompensated Rated Consumed P Q P Q


KW KVAR KW KVAR

Connected Compensated Consumed Rated P Q P Q KW KVAR KW KVAR

Continuous Intermittent Stand By Spare

22

20

8.8

1.6

Rated 22 kW 5 kVAR Cons 20 kW 4 kVAR

JB

Is Load: True Intermittent Y=0.4

M-23 380 V

Loads

P
KW

KVAR KVA

Continuous X 19.9 A 1 Rated Q S P PF@ 13.06 0.85 8.5 Rated Power: Brake Power:

KW

Y Z ZZ 0.5 0.1 0.05 Consumed Q S PF@


KVAR KVA

M-24 380 V P
KW

KVAR KVA

Continuous X 19.9 A 1 Rated Q S P PF@ 13.06 0.85 8.5 Rated Power: Brake Power:

KW

Y Z ZZ 0.5 0.1 0.05 Consumed Q S PF@


KVAR KVA

M-25 380 V P
KW

KVAR KVA

Continuous X 19.9 A 1 Rated Q S P PF@ 13.06 0.85 8.5 Rated Power: Brake Power:

KW

Y Z ZZ 0.5 0.1 0.05 Consumed Q S PF@


KVAR KVA

11.1

6.89

5.95 10.38 0.82 10 kW 7.5 kW

11.1

6.89

5.95 10.38 0.82 10 kW 7.5 kW

11.1

6.89

5.95 10.38 0.82 10 kW 7.5 kW

Bus Load Configuration Examples

23

Configuration J: Loads connected in a daisy-chain


Incomer MCC-M IN1 Uncompensated Consumed Rated P Q P Q
KW KVAR KW KVAR

Bus Incomer

Connected Compensated Consumed Rated P Q P Q


KW KVAR KW KVAR

Continuous Intermittent Stand By Spare BUS-M

33.3

20.67 25.5

17.85 33.3

20.67 25.5

17.85

X 400 V Uncompensated Rated Consumed Q S P Q S PF@ PF@


KW KVAR KVA

ZZ

1
Compensated P
KW

0.4

0.1

P
KW

Rated S

KVAR KVA

KVAR KVA

PF@

I
A

P
KW

KVAR KVA

Consumed S PF@

I
A

Bus

Bus Run Bus Peak Continuous Intermittent Stand By Spare Feeder CKT-60 Uncompensated Consumed Rated P Q P Q
KW KVAR KW KVAR

33.3 33.3 33.3

20.67 39.194 0.85 25.5 20.67 39.194 0.85 25.5 20.67 25.5

17.85 31.127 0.82 33.3 17.85 31.127 0.82 33.3 17.85 33.3

20.67 39.194 0.85 56.57225.5 20.67 39.194 0.85 56.57225.5 20.67 25.5

17.85 31.127 0.82 44.928 17.85 31.127 0.82 44.928 17.85

Feeders

Connected Compensated Consumed Rated P Q P Q


KW KVAR KW KVAR

Feeder CKT-61 Uncompensated Rated Consumed P Q P Q


KW KVAR KW KVAR

Connected Compensated Rated Consumed P Q P Q


KW KVAR KW KVAR

Feeder CKT-83 Uncompensated Rated Consumed P Q P Q


KW KVAR KW KVAR

Connected Compensated Consumed Rated P Q P Q


KW KVAR KW KVAR

Continuous 33.3 Intermittent Stand By Spare

20.67 25.5

17.85 33.3

20.67 25.5

17.85

Loads

KW

Continuous X LAMP-1 1 380 V 19.9 A Rated P Q S P PF@


KVAR KVA

KW

Y Z ZZ 0.5 0.1 0.05 Consumed Q S PF@


KVAR KVA

KW

Continuous X LAMP-2 1 380 V 19.9 A Rated P Q S P PF@


KVAR KVA

KW

Y Z ZZ 0.5 0.1 0.05 Consumed Q S PF@


KVAR KVA

KW

Continuous LAMP-3 X 380 V 19.9 A 1 Rated P Q S P PF@


KVAR KVA

KW

Y Z ZZ 0.5 0.1 0.05 Consumed Q S PF@


KVAR KVA

11.1

6.89

13.06 0.85 8.5 Rated Power: Consumed Power:

5.95 10.38 0.82 10 kW 7.5 kW

11.1

6.89

13.06 0.85 8.5 Rated Power: Consumed Power:

5.95 10.38 0.82 10 kW 7.5 kW

11.1

6.89

13.06 0.85 8.5 Rated Power: Consumed Power:

5.95 10.38 0.82 10 kW 7.5 kW

Bus Load Configuration Examples

24

Configuration K: A space heater connected to an auxiliary contact


Incomer AUX3_IN Uncompensated Rated Consumed P Q P Q
KW KVAR KW

Bus Incom er

Connected Compensated Rated Consumed P Q P Q KVAR KW KVAR

Incomer AUX4_IN Uncompensated Consumed Rated P Q P Q


KW KVAR KW

Connected Compensated Rated Consumed P Q P Q KVAR KW KVAR

KVAR KW

KVAR KW

Continuous Intermittent Stand By Spare ABC 380V

11.11 5.38 8.82 5.47 11.11 5.38 8.82 5.47 1.11 0.54 0.53 0.17 0.11 0.05 0.05 0.01 X 400 V Uncompensated Rated Consumed Q S P Q S PF
KW KVAR KVA

ZZ

X AUX 120V 120 V Uncompensated Rated Consumed Q S P Q S PF


KW KVAR KVA

ZZ

1
Compensated PF P
KW

0.4

0.1

1
Compensated PF 0.9 P
KW

0.4

0.1

P
KW

Rated S

KVAR KVA

KVAR KVA

PF

I
A

P
KW

KVAR KVA

Consumed Q S PF 10.3 0.8 10.3 0.8

I
A

P
KW

Rated S

KVAR KVA

KVAR KVA

PF 0.9

I
A

P
KW

KVAR KVA

Consumed S PF 0.0 0.9

I
A

Bus

Bus Run 11.1 5.3 Bus Peak 11.1 5.3 Continuous 11.1 5.3 Intermittent Stand By Spare

12.3 0.9 12.3 0.9

8.8 8.8 8.8

5.4 5.4 5.4

10.3 0.8 10.3 0.8

11.1 5.3 11.1 5.3 11.1 5.3

12.3 0.9 12.3 0.9

17.8 8.8 17.8 8.8 8.8

5.4 5.4 5.4

14.9 14.9

1.1

0.5

1.2

0.9

0.5

0.1

0.5

0.1

0.0

0.1

0.1

0.0

0.0

0.0

1.1

0.5

0.5

0.1

0.1

0.0

0.0

0.0

Feeders

Feeder AM-004/FD Uncompensated Rated Consumed P Q P Q


KW KVAR KW

Connected Compensated Rated Consumed P Q P Q


KVAR KW KVAR

Feeder HTR-4/FD Uncompensated Rated Consumed P Q P Q


KW KVAR KW

Connected Compensated Rated Consumed P Q P Q KVAR KW KVAR

KVAR KW

KVAR KW

Continuous 11.11 5.38 8.82 5.47 11.11 5.38 8.82 5.47 Intermittent Stand By Spare 101-AM-004 Continuous X 380 V 18.8 A 1 Rated P Q S PF/Eff P KW KVAR KVA 0.9 KW 11.11 5.38 12.34 0.9 8.82 Rated Power: Brake Power: Y Z ZZ 0.5 0.1 0.05 Consumed Q S PF/Eff KVAR KVA 0.85 5.47 10.38 0.85 10 kW 7.5 kW HTR-4 120 V

Auxiliary Contact For Motor Heater 1.11 0.54 0.53 0.17 0.11 0.05 0.05 0.01

Standby X 10.3 A 1 Rated P Q S PF/Eff P KW KVAR KVA 0.9 KW 1.11 0.54 1.23 0.9 0.53 Rated Power: Consumed Power:

Y Z ZZ 0.5 0.1 0.05 Consumed Q S PF/Eff KVAR KVA 0.95 0.17 0.56 0.95 1 kW 0.53 kW

Bus Load Configuration Examples