2) KV HXLP-AWA
High Voltage Cross-Linked Polyethylene Single Core Cable 3.6/6 (7.2) KV, Copper Conductor with Aluminum Wire Armor
Application
Preferably used for urban networks. Exposed in aerial, direct burial, conduit, open tray and underground duct installation.
Marking
3.6/6 (7.2) KV HXLP-AWA 1 X SIZE SQ.MM., PHELPS DODGE.
Installation
HXLP-AWA cable can be installed in aerial, direct burial, conduit, open tray and underground duct. It is recommended that the installation instructions indicated by the Local Electric Code, or any equivalent, be followed, so that the safe guarding of persons and the integrity of the product will not be affected by deciencies in the installation.
www.pdic.com
PDIC01098 | 10.27.04
Thickness of Insulation mm
Thickness of Sheath
Standard Packing
mm
m / reel
7 7 7 7 7 18 18 18 18 34 34 34 55 55 81 81
3.7 4.7 5.9 6.9 8.0 9.7 11.4 12.9 14.2 16.0 18.4 20.5 23.4 26.6 30.0 33.9
2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.6 2.8 3.0 3.2 3.2 3.2
9.5 10.5 11.7 12.7 13.8 15.5 17.2 19.0 20.2 22.1 24.7 27.4 31.2 34.9 38.5 42.4
1.25 1.25 1.6 1.6 1.6 1.6 1.6 1.6 1.6 2.0 2.0 2.0 2.0 2.5 2.5 2.5
18.1 19.1 21.0 22.1 23.1 24.8 26.5 28.3 29.5 32.2 34.8 38.0 41.8 46.7 51.0 54.9
1.6 1.6 1.7 1.7 1.8 1.8 1.9 1.9 2.0 2.0 2.1 2.2 2.3 2.5 2.6 2.7
24 25 27 28 29 31 33 35 36 39 42 45 49 55 59 63
1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366 0.0283 0.0221
1199 1041 896 800 720 623 551 490 455 411 379 365 341 324 291 261
91 118 151 181 213 260 311 353 397 449 520 587 670 760 859 1026
98 127 167 201 240 299 368 421 480 549 642 735 862 960 1127 1274
537 621 801 925 1,085 1,342 1,653 1,947 2,262 2,752 3,392 4,141 5,099 6,456 8,034 9,853
1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 500 500 500 500 500 500
** Depth of laying in Ground = 1 m, Rho = 1.2C m/watt, Spacing of cable = 2 x cable overall diameter
www.pdic.com
PDIC01098 | 10.27.04