Вы находитесь на странице: 1из 2

3.6/6 (7.

2) KV HXLP-AWA
High Voltage Cross-Linked Polyethylene Single Core Cable 3.6/6 (7.2) KV, Copper Conductor with Aluminum Wire Armor

Insulation Insulation Shield Conductor Binding Shield Tape Bedding

Sheath Black polyethylene (ST 7) (Optional: Polyvinyl chloride)


PE Sheath Aluminum Copper Copper Wire Tape Conductor

Application
Preferably used for urban networks. Exposed in aerial, direct burial, conduit, open tray and underground duct installation.

Detail Description or Construction


Conductor Compact round stranded copper Conductor Shield Semi-conducting tape and/or Semiconducting cross-linked polyethylene Insulation Cross-linked polyethylene Insulation Shield Semi-conducting cross-linked polyethylene Shield Copper tape shield Bedding Black polyethylene (Optional: Polyvinyl chloride) Armor Aluminum wire armor Binding Tape Polyester and/or Spunbond tape (Optional: Water blocking tape)

Standards / Testing Specications


IEC 60502-2.

Marking
3.6/6 (7.2) KV HXLP-AWA 1 X SIZE SQ.MM., PHELPS DODGE.

Installation
HXLP-AWA cable can be installed in aerial, direct burial, conduit, open tray and underground duct. It is recommended that the installation instructions indicated by the Local Electric Code, or any equivalent, be followed, so that the safe guarding of persons and the integrity of the product will not be affected by deciencies in the installation.

www.pdic.com

PDIC01098 | 10.27.04

3.6/6 (7.2) KV HXLP-AWA


High Voltage Cross-Linked Polyethylene Single Core Cable 3.6/6 (7.2) KV, Copper Conductor with Aluminum Wire Armor

Nominal Sectional Area mm

Minimum Number of Wires

Diameter of Conductor (approx) mm

Thickness of Insulation mm

Diameter Over Insulation (approx) mm

Armor Aluminum Wire Diameter mm

Diameter Over Armor (approx) mm

Thickness of Sheath

Overall Diameter (approx.) mm

Maximum DC. Resistance of Cdr. @ 20C / km

Minimum Insulation Resistance @ 20C M - km

Ampacities Direct Burial in Ground @ 30C Ambient** A

Allowable Ampacities in Free Air @ 40C Ambient A

Cable Weight (approx) kg / km

Standard Packing

mm

m / reel

10 16 25 35 50 70 95 120 150 185 240 300 400 500 630 800

7 7 7 7 7 18 18 18 18 34 34 34 55 55 81 81

3.7 4.7 5.9 6.9 8.0 9.7 11.4 12.9 14.2 16.0 18.4 20.5 23.4 26.6 30.0 33.9

2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.6 2.8 3.0 3.2 3.2 3.2

9.5 10.5 11.7 12.7 13.8 15.5 17.2 19.0 20.2 22.1 24.7 27.4 31.2 34.9 38.5 42.4

1.25 1.25 1.6 1.6 1.6 1.6 1.6 1.6 1.6 2.0 2.0 2.0 2.0 2.5 2.5 2.5

18.1 19.1 21.0 22.1 23.1 24.8 26.5 28.3 29.5 32.2 34.8 38.0 41.8 46.7 51.0 54.9

1.6 1.6 1.7 1.7 1.8 1.8 1.9 1.9 2.0 2.0 2.1 2.2 2.3 2.5 2.6 2.7

24 25 27 28 29 31 33 35 36 39 42 45 49 55 59 63

1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366 0.0283 0.0221

1199 1041 896 800 720 623 551 490 455 411 379 365 341 324 291 261

91 118 151 181 213 260 311 353 397 449 520 587 670 760 859 1026

98 127 167 201 240 299 368 421 480 549 642 735 862 960 1127 1274

537 621 801 925 1,085 1,342 1,653 1,947 2,262 2,752 3,392 4,141 5,099 6,456 8,034 9,853

1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 500 500 500 500 500 500

** Depth of laying in Ground = 1 m, Rho = 1.2C m/watt, Spacing of cable = 2 x cable overall diameter

www.pdic.com

PDIC01098 | 10.27.04

Вам также может понравиться