4.3.6 Air Outlets. 4.3.6.1 General.

Air supplied to any space shall not contain flammable vapors, flyings, or dust in quantities and concentrations that would introduce a hazardous condition. 4.3.6.2 Construction of Air Outlets. 4.3.6.2.1 Air outlets shall be constructed of noncombustible material, except under the conditions of 4.3.6.2.2. 4.3.6.2.2 Air outlets shall be permitted to be constructed of a material that has a maximum flame spread index of 25 and a maximum smoke developed index of 50. 4.3.6.3 Location of Air Outlets. 4.3.6.3.1 Air outlets shall be located at least 76 mm (3 in.) above the floor, unless provisions have been made to prevent dirt and dust accumulations from entering the system. 4.3.6.3.2 Where located less than 2.13 m (7 ft) above the floor, outlet openings shall be protected by a grille or screen having openings through which a 12.7 mm ( in.) sphere cannot pass.