Вы находитесь на странице: 1из 6

This workbook contains some worksheets that can calculate various psychrometric properties of air given a few basic

inputs.
By: Osiyo53

The accuracy of the results are based upon ASHRAE formulas and will be adequate for HVAC system work. I put this workbook together for my oldest grandson who'd learned a little about psychrometrics in a science class. But was having trouble grasping the concepts. Well, he knew old grandpa used to be a HVAC tech, so he asked if I could help him to better understand the subject. The worksheets are nothing fancy but they're useable. The workbook is free for anyone to use in any way they wish. And may be modified if desired. Just turn off Protection. Click shaded box below to jump to a worksheet. Single Point (Wet Bulb) Mixing Problem (Wet Bulb) Single Point (Relative Hum) Mixing Problem (Relative Hum)

Change - Add/Remove Heat

Single Point(WB)

Psychrometric Calculations
Inputs Dry Bulb Temperature Wet Bulb Temperature Altitude Outputs Atmospheric Pressure Vapor Press. at saturation Vapor Pressure Dew Point Temperature Relative Humidity Humidity Ratio Enthalpy Specific Volume 75.0 F 60.0 F 1,000.0 Ft.

28.86 0.875 0.371 50.6 42.4 0.0081 26.9 14.15

In. Hg In. Hg In. Hg F Percent lbw/lba Btu/lb CuFt/lb

14.17 psi 0.43 psi 0.18 psi

56.7 grains/lb

Page 2

Single Point(RH)

Psychrometric Calculations
Inputs Dry Bulb Temperature Relative Humidity Altitude Outputs Atmospheric Pressure Vapor Press. at saturation Vapor Pressure Dew Point Temperature Wet Bulb Temperature Humidity Ratio Enthalpy Specific Volume 75.0 F 42.4 Percent 1,000.0 Ft.

28.86 0.875 0.371 50.6 60.2 0.0082 27.0 14.15

In. Hg In. Hg In. Hg F F lbw/lba Btu/lb CuFt/lb

14.17 psi 0.43 psi 0.18 psi

57.7 grains/lb

Page 3

Mixing Problem(WB)

Psychrometric Calculations
Inputs Air Flow Rate Dry Bulb Temperature Wet Bulb Temperature Altitude Outputs Atmospheric Pressure Vapor Press. at saturation Vapor Pressure Dew Point Temperature Relative Humidity Humidity Ratio Enthalpy Specific Volume Mass Flow Rate, dry air Mass Flow Rate, water vapor Mass Flow Rate, moist air Air Stream 1 6,000 cfm 75.0 F 63.9 F 1,000.0 Ft. Mixing Problem Air Stream 2 4,000 cfm 60.0 F 46.4 F Mixed Air 10,000 cfm 69.0 F 57.5 F

28.86 0.875 0.488 58.1 55.7 0.0107 74.8 29.7 14.21 422.256 4.514 426.770

In. Hg In. Hg In. Hg F Percent lbw/lba grains/lb Btu/lb CuFt/lb lb/min lb/min lb/min

0.522 0.179 31.9 34.4 0.0039 27.2 18.6 13.66 292.770 1.139 293.910

In. Hg In. Hg F Percent lbw/lba grains/lb Btu/lb CuFt/lb lb/min lb/min lb/min

0.714 0.361 49.9 50.6 0.0079 55.4 25.2 13.99 715.026 5.653 720.679

In. Hg In. Hg F Percent lbw/lba grains/lb Btu/lb CuFt/lb lb/min lb/min lb/min

Page 4

Mixing Problem(RH)

Psychrometric Calculations
Inputs Air Flow Rate Dry Bulb Temperature Relative Humidity Altitude Outputs Atmospheric Pressure Vapor Press. at saturation Vapor Pressure Dew Point Temperature Wet Bulb Temperature Humidity Ratio Enthalpy Specific Volume Mass Flow Rate, dry air Mass Flow Rate, water vapor Mass Flow Rate, moist air Mixing Problem Air Stream 1 Air Stream 2 6,000 cfm 4,000 cfm 75.0 F 60.0 F 55.0 Percent 34.0 Percent 1,000.0 Ft. Mixed Air 10,000 cfm 69.0 F 49.5 Percent

28.86 0.875 0.481 57.7 63.9 0.0107 74.9 29.7 14.21 422.256 4.517 426.772

In. Hg In. Hg In. Hg F F lbw/lba grains/lb Btu/lb CuFt/lb lb/min lb/min lb/min

0.522 0.177 31.6 46.4 0.0039 27.2 18.6 13.66 292.770 1.140 293.910

In. Hg In. Hg F F lbw/lba grains/lb Btu/lb CuFt/lb lb/min lb/min lb/min

0.714 0.353 49.3 57.2 0.0079 55.5 25.0 13.98 715.026 5.656 720.682

In. Hg In. Hg F F lbw/lba grains/lb Btu/lb CuFt/lb lb/min lb/min lb/min

Page 5

Change

Psychrometric Calculations
Inputs Air Flow Rate Dry Bulb Temperature Relative Humidity Altitude Outputs Atmospheric Pressure Vapor Press. at saturation Vapor Pressure Dew Point Temperature Wet Bulb Temperature Humidity Ratio Enthalpy Specific Volume Mass Flow Rate, dry air Mass Flow Rate, water vapor Mass Flow Rate, moist air Dry Air Pressure Dry Air Density Vapor Density Moist Air Density BTU/Hr Total Removed ---BTU/Hr Sensible Removed ---BTU/Hr Latent Removed Tons of cooling Sensible Heat Ratio (SHR) Condensate lb/min Condensate lb/hr Heat/Moisture Added or Removed Air Stream In Air Stream Out 15,000.0 cfm 14,507.5 cfm 72.0 F 55.0 F 50.0 Percent 85.0 Percent 1,000.0 Ft. Change 492.5 cfm 17.0 F 35.0 Percent Less Less Increase

28.860 14.175 0.791 0.389 0.396 0.194 52.31 60.00 0.0088 61.4 26.86 14.087 1,064.821 9.333 1,074.154 13.980 0.0710 0.0006 0.0716 310,768.9 264,836.9 45,932.0 25.90 0.85 0.41 24.64

In. Hg psia In. Hg psia In. Hg psia F F lbw/lba grains/lb Btu/lb CuFt/lb lb/min lb/min lb/min psia lb/CuFt lb/CuFt lb/CuFt

0.436 0.214 0.370 0.182 50.53 52.40 0.0081 56.7 21.99 13.621 1,101.203 8.923 1,110.126 13.993 0.0734 0.0006 0.0740

In. Hg psia In. Hg psia F F lbw/lba grains/lb Btu/lb CuFt/lb lb/min lb/min lb/min psia lb/CuFt lb/CuFt lb/CuFt

0.355 0.175 0.025 0.012 1.78 7.60 0.0007 4.6 4.87 0.465 36.382 0.411 35.971 0.012 0.0024 0.0000 0.0024

In. Hg psia In. Hg psia F F lbw/lba grains/lb Btu/lb CuFt/lb lb/min lb/min lb/min psia lb/CuFt lb/CuFt lb/CuFt

Less Less Less Less Less Less Less Less Less Less Increase Less Increase Increase Increase Less Increase

Page 6