Академический Документы
Профессиональный Документы
Культура Документы
=
A
+ + =
1 2
1
0
)
2
cos( A | |
N
k
k k
t n
n
N
k
A e n i
t
t
(1)
where, t and A
0
are the primary time constant and the
magnitude oI an exponential component, A
k
and
k
are the
amplitude and the phase angle oI the kth harmonic component,
At is the sampling interval and N is the number oI samples per
cycle.
The phasor oI the Iundamental Irequency component is
calculated by the DFT as Iollows.
ac
DFT
th
DFT
N
n
n
N
f
DFT
I I e n i
N
I + = =
_
1
1
0
2
| |
2
t
(2)
where
1
1
1 | f th
DFT
e A I =
) 1 ( ) 1 (
2
2
0
N
f
N ac
DFT
Ee E A
N
I
t
=
t t
e E
A
=
Although the DFT is simple and easy to implement, the
output oI the DFT Ior the Iundamental Irequency
component,
DFT
I
, contains an error,
ac
DFT
I , due to the
exponentially decaying DC oIIset.
Equation (2) can be decomposed into the even-sample-set
DFT,
even
DFT
I , and the odd-sample-set DFT,
oaa
DFT
I , as Iollows.
_
=
1
0
2
| |
2
N
n
n
N
f
DFT
e n i
N
I
t
_ _
=
+
+ + =
1 2
0
) 1 2 (
2
1 2
0
2
2
| 1 2 |
2
| 2 |
2
N
n
n
N
f
N
n
n
N
f
e n i
N
e n i
N
t t
oaa
DFT
even
DFT
I I + = (3)
The even- and odd-sample-set DFTs can be rearranged as
Iollows.
_
=
1 2
0
2
2
| 2 |
2
N
n
n
N
f
even
DFT
e n i
N
I
t
2
2 0 1
) ( 1
1 2
2
1
1
N
f
N
f
Ee
E
A
N
e A
t
|
+ =
(4)
_
=
+
+ =
1 2
0
) 1 2 (
2
| 1 2 |
2
N
n
n
N
f
oaa
DFT
e n i
N
I
t
2
2 0
2
1
) ( 1
1 2
2
1
1
N
f
N
N
f
f
Ee
E
A Ee
N
e A
t
t
|
+ =
(5)
The even- and odd-sample-set DFTs have the same
Iundamental Irequency component, 2
1
1
| f
e A . This component
can be eliminated by subtracting (5) Irom (4).
) 1 ( ) 1 (
2
2
0
N
f
N oaa
DFT
even
DFT
Ee E A
N
I I
t
+ =
(6)
The DFT output oI the Iundamental Irequency component
due to the decaying DC component,
ac
DFT
I , in (2) can be
rewritten as Iollows.
( ) ) 1 ( ) 1 (
2 2
N
f
N
f
oaa
DFT
even
DFT
ac
DFT
Ee Ee I I I
t t
+ = (7)
where
) 2 cos( ) 2 sin( N K N K
K
E
Im Re
Im
t t
=
{ }
oaa
DFT
even
DFT Re
I I Re K =
{ }
oaa
DFT
even
DFT Im
I I Im K =
ThereIore, the accurate Iundamental Irequency component
phasor oI the input signal,
th
DFT
I
1
, can be obtained Irom
ac
DFT DFT
th
DFT
I I I =
1
(8)
B. Distance Relaying Algorithm
Fig. 1 shows a Ilowchart describing distance relaying
algorithm adopting a DFT-based modiIied phasor estimation
method. A distance relay is provided with voltage and current
signals Irom one end only oI the protected circuit, and is
expected to assess the location oI a Iault on the basis oI these
locally measured signals. Most distance relays discriminate
between load and Iault conditions by measuring both the
magnitude and angle oI the impedance presented to them. This
means that the distance relays estimate the phasors oI the
voltage and current signals to calculate the impedance.
3
lhpuls (Vollage, Currehl)
2hd Order Digilal Low-Pass Filler
New Fourier AIgorithm
START
Calculalihg Apparehl lmpedahce
Even/Odd 5ampIe 5et DFTs
CaIcuIating ( )
2nd Order DigitaI Low-Pass FiIter
Estimating and
CaIcuIating
odd
DF1
even
DF1
I I
z
At
e
dc
DF1
I
th
DF1
I
1
Fig. 1. Flowchart oI the proposed algorithm
A DFT is generally used to calculate the phasor oI the
Iundamental Irequency component in digital protective relays.
However, instead oI the conventional DFT, the new Fourier
algorithm is used Ior the distance relaying algorithm. A
subtraction process, such as (6), in the new Fourier algorithm
normally magniIies high Irequency noises in input signals.
Although the DFT inherently has very robust characteristics
over the high-Irequency noises, the subtraction process aIter
the DFT can cause an error. This drawback can be easily
suppressed by a simple low-pass Iilter, like the second one in
the right-hand side oI the Ilowchart.
A ground distance relay calculates the apparent impedance
using the estimated phasors (J
app
and I
app
) as
( )
0 1 0
1 / I Z Z I
J
Z
L L app
app
app
+
=
(9)
where
1 L
Z and
0 L
Z
are the positive- and zero-sequence line
impedances, respectively, and
0
I
is the zero-sequence current
Irom the relaying point into the Iault.
III. SIMULATIONS OF THE DISTANCE RELAYING ALGORITHM
A. System Configuration
In this section, the perIormance evaluation Ior the proposed
distance relaying algorithm is described.
The current and voltage singles are generated by the EMTP.
The model system Ior the simulations is a 345 kV, 50 km
overhead transmission with sources at both ends, as shown in
Fig. 2. The transmission line parameters used in the
simulations are given in Table 1.
Fig. 2. Single-line diagram oI the model system
TABLE I
OVERHEAD TRANSMISSION LINE PARAMETERS
Sequence Parameter Value Units
Positive
&
Negative
R
1
, R
2
0.0345 O/km
L
1
, L
2
0.9724 mH/km
C
1
, C
2
0.0117 nF/km
Zero
R
0
0.2511 O/km
L
0
2.7058 mH/km
C
0
0.0045 nF/km
TABLE II
EQUIVALENT SOURCE PARAMETERS
Sequence S |GVA| X/R
Z
S0
5.00 5.00
Z
S1
10.00 3.00
Case 1 Case 2
Sequence S |GVA| X/R S |GVA| X/R
Z
R0
3.50 5.00 3.50 7.00
Z
R1
7.00 10.00 7.00 14.00
Zone 1 oI the distance relay was set to 80 oI the
transmission line impedance with no intentional time delay. A-
phase to ground Iaults with Iault resistances oI 0 O, 5 O, and
10 O were applied at a distance oI 41 km Irom the relaying
point, i.e., close-in Iaults Irom the end oI Zone 1. A Iault
inception angle oI 0 was considered Ior the maximum
magnitude oI the DC component.
The time constant and amplitude oI the decaying DC
component varies depending on the system conIiguration and
Iault conditions such as the Iault location, the Iault resistance,
and the Iault inception angle. The time constant oI the decay is
generally determined by the Iault resistance and the impedance
ratio (X/R, the ratio oI the inductive reactance to the
resistance) oI the system. As shown in Table II, diIIerent
impedance ratios oI the remote end source were used Ior Cases
1 and 2 to consider the eIIect oI the source impedance ratio on
the time constant.
B. Case Stuaies
Figs. 3 to 5 show the magnitude estimation results oI Iault
currents and the measured impedance trajectories designed by
the proposed technique Ior Case 1. For comparison, the results
obtained using the conventional DFT and PS-based DFT are
also shown in each Iigure.
4
0.5 1 1.5 2
4
6
8
10
M
a
g
n
i
t
u
d
e
[
k
A
]
Conventional DFT PS-based DFT Proposed DFT
time in cyeles after fault
(a) Magnitude estimation results oI a Iault current
0 5 10 15 20
0
5
10
15
20
R [O]
X
[ O
]
Conventional DFT PS-based DFT Proposed DFT
0 0.5 1 1.5 2 2.5
13.5
14
14.5
15
15.5
16
16.5
Lihe
lmpedahce
ehlarged view ol lhe doled reclahgle
Zohe 1
(b) Apparent impedance trajectories
Fig. 3. Test results Ior Case 1 (Iault resistance 0 O)
0.5 1 1.5 2
4
6
8
10
M
a
g
n
i
t
u
d
e
[
k
A
]
Conventional DFT PS-based DFT Proposed DFT
time in cyeles after fault
(a) Magnitude estimation results oI a Iault current
0 5 10 15 20
0
5
10
15
20
R [O]
X
[ O
]
Conventional DFT PS-based DFT Proposed DFT
7 7.5 8 8.5 9 9.5 10
13.5
14
14.5
15
15.5
16
16.5
Lihe
lmpedahce
ehlarged view ol lhe doled reclahgle
Zohe 1
(b) Apparent impedance trajectories
Fig. 4. Test results Ior Case 1 (Iault resistance 5 O)
0.5 1 1.5 2
4
6
8
10
M
a
g
n
i
t
u
d
e
[
k
A
]
Conventional DFT PS-based DFT Proposed DFT
time in cyeles after fault
(a) Magnitude estimation results oI a Iault current
0 5 10 15 20
0
5
10
15
20
R [O]
X
[ O
]
Conventional DFT PS-based DFT Proposed DFT
14 14.5 15 15.5 16 16.5 17
13.5
14
14.5
15
15.5
16
16.5
Lihe
lmpedahce
ehlarged view ol lhe doled reclahgle
Zohe 1
(b) Apparent impedance trajectories
Fig. 5. Test results Ior Case 1 (Iault resistance 10 O)
Fig. 3 shows the test results Ior an ideal a-g Iault at 41km
Irom the relaying point. For an ideal Iault the Iault current
Ilowing through a power line contains only one exponentially
decaying DC component which depends on the local source
impedance and the line impedance. Compared to the other
algorithms, the distance relay designed by the conventional
DFT shows not only the largest transient overshoot but also
the largest oscillatory response.
Fault resistance is usually small in the case oI inter-phase
Iaults. On the other hand, ground Iaults may introduce high
resistance in the Iault loop. The most common Iaults on
overhead lines are ground Iaults that are caused by Ilashover
oI an insulator. The Iault loop Ior ground Iaults includes tower
impedance, tower Iooting resistance, and arc resistance. Tower
Iooting resistance can vary Irom less than one ohm to several
hundred ohms.
For high-resistance ground Iaults, the time constant oI the
decay is very small, sometimes less than halI oI the
Iundamental Irequency cycle. In such cases, decaying DC
components do not cause errors that are taken into
consideration in calculating the phasor. However, in the case
oI Iaults with a Iault resistance oI less than ten ohms, DC
components heavily inIluence the accuracy and the
convergence speed oI the estimation oI a phasor. Furthermore,
the current relaying signal contains two exponentially decaying
DC oIIsets that depend on not only the local source impedance
but also on the remote source impedance Ior a Iault with a Iault
resistance.
5
0.5 1 1.5 2
4
6
8
10
M
a
g
n
i
t
u
d
e
[
k
A
]
Conventional DFT PS-based DFT Proposed DFT
time in cyeles after fault
(a) Magnitude estimation results oI a Iault current
0 5 10 15 20
0
5
10
15
20
R [O]
X
[ O
]
Conventional DFT PS-based DFT Proposed DFT
7 7.5 8 8.5 9 9.5 10
13.5
14
14.5
15
15.5
16
16.5
Lihe
lmpedahce
ehlarged view ol lhe doled reclahgle
Zohe 1
(b) Apparent impedance trajectories
Fig. 6. Test results Ior Case 2 (Iault resistance 5 O)
0.5 1 1.5 2
4
6
8
10
M
a
g
n
i
t
u
d
e
[
k
A
]
Conventional DFT PS-based DFT Proposed DFT
time in cyeles after fault
(a) Magnitude estimation results oI a Iault current
0 5 10 15 20
0
5
10
15
20
R [O]
X
[ O
]
Conventional DFT PS-based DFT Proposed DFT
14 14.5 15 15.5 16 16.5 17
13.5
14
14.5
15
15.5
16
16.5
Lihe
lmpedahce
ehlarged view ol lhe doled reclahgle
Zohe 1
(b) Apparent impedance trajectories
Fig. 7. Test results Ior Case 2 (Iault resistance 10 O)
Figs. 4 and 5 show test results Ior the Iault with a Iault
resistance. In this case, as shown in Figs. 4 (a) and 5 (a), there
is overshoot in the output oI the PS-based method because it
cannot completely remove the adverse inIluence oI the DC
oIIsets when the input signal contains two exponentially
decaying DC components with diIIerent time constants. Thus,
the measured impedance using a PS-based method had about a
46 transient overreach and showed an oscillatory response
Ior the Iault with a Iault resistance as shown in Figs. 4(b) and
5(b).
The proposed method completely eliminated the DC oIIsets
because it estimated an exponentially decaying DC oIIset
with an approximately equivalent time constant. ThereIore,
the measured impedance using the proposed method reached
the desired impedance value without an oscillatory response.
The transient overreach oI the measured impedance using the
proposed method was less than 1 .
Figs. 6 and 7 show the magnitude estimation results oI Iault
currents and the measured impedance trajectories Ior Case 2.
The transient overreach oI the apparent impedances using a
PS-based method increased compared with Case 1 because the
increased impedance ratio oI the remote source aIIected the
time constants oI the DC components, i.e., one oI the time
constants that mainly depends on the local source ratio was
almost equal to that oI Case 1, and the other time constant that
greatly depends on the remote source ratio becomes much
smaller than that oI Case 1.
Sources oI supply having diIIerent impedance ratios might
not only aIIect the time constants oI the DC oIIsets, but may
also change the apparent impedance seen by a distance relay
whenever a resistance is present in the Iault path. II X/R oI the
local source is greater than that oI the remote source, the Iault
resistance appears as an impedance with an inductive
reactance. II X/R oI the local source is less than that oI the
remote source, the Iault resistance appears as an impedance
with a capacitive reactance |6|, |7|. The more the impedance
ratio oI the local source diIIers Irom that oI the remote source,
the more the reactance eIIect may be increased. In the case oI
the model system used in this study, the Iault resistance
appears as an impedance with an capacitive reactance. For this
reason, the measured impedance trajectory using a PS-based
method overreached the boundary oI the Zone 1 even when the
Iault resistance was 5 O, as shown in Fig. 6(b). The transient
over-reach reduces the sensitivity oI the relays and may also
increase the operation time because the measured impedance
keeps on moving in and out oI the relay operation region.
The proposed algorithm was not aIIected by system and
Iault conditions. ThereIore, the output oI the proposed method
was stable, and showed superior results. These simulation
results demonstrate the superiority oI the proposed algorithm
in a distance relay design.
6
IV. CONCLUSIONS
A distance relaying algorithm using a DFT-based modiIied
phasor estimation method to eliminate the adverse inIluence oI
exponentially decaying DC oIIsets was described. The
proposed phasor estimation method used an even-sample-set
DFT and an odd-sample-set DFT to reduce the length oI the
data window to only one cycle. The error due to DC oIIsets on
the DFT was calculated and eliminated using the outputs oI
even- and odd-sample-set DFTs so that the phasor oI the
Iundamental component could be accurately estimated.
A perIormance evaluation showed that the proposed
algorithm was not aIIected by system and Iault conditions and
the output was stable without an oscillatory response, unlike
some other algorithms. Thus, the evaluation results indicate
that adopting the proposed algorithm in a distance relay can
eIIectively suppress the adverse inIluence oI DC oIIsets in a
relaying signal.
V. REFERENCES
|1| G. Benmouyal, 'Removal oI DC oIIset in current waveIorms using
digital mimic Iiltering, IEEE Trans. Power Delivery, vol. 10, no. 2, pp.
621630, April 1995.
|2| Jyh-Cherng Gu and Sun-Li Yu, 'Removal oI DC oIIset in current and
voltage signals using a novel Fourier Iilter algorithm, IEEE Trans.
Power Delivery, vol. 15, no. 1, pp. 7379, Jan. 2000.
|3| Soon-Ryul Nam, Sang-Hee Kang and Jong-Keun Park, 'An Analytic
Method Ior Measuring Accurate Fundamental Frequency Components,
IEEE Trans. Power Delivery, vol. 17, no. 2, pp. 405-411, April 2002.
|4| Yong Guo, M. Kezunovic, and Deshu Chen, 'SimpliIied algorithms Ior
removal oI the eIIect oI exponentially decaying DC oIIset on the Fourier
algorithm, IEEE Trans. Power Delivery, vol. 18, no. 3, pp. 711717,
July 2003.
|5| Dong-Gyu Lee, Sang-Hee Kang, Soon-Ryul Nam, 'New ModiIied
Fourier Algorithm to Eliminate the EIIect oI the DC oIIset on Phasor
Estimation Using DFT, 2008 IEEE PES Transmission ana Distribution
Conference ana Exposition, April 2008.
|6| IEEE Guiae for Protective Relay applications to Transmission Lines,
IEEE Standard C37.113-1999.
|7| V. Cook, Analysis of Distance Protection, Research Studies Press, 1985,
pp. 9294.
VI. BIOGRAPHIES
Dong-Gyu Lee received the B.S. and M.S. degrees Irom Myongji University,
Korea, in 2002 and 2004, respectively. He is now studying Ior his Ph.D.
degree at Myongji University. He has been with Next-generation Power
Technology Center, Korea, since 2002. His main research interests are power
system protection.
Ye-1un Oh is now studying Ior his B.S. degree at Myongji University and
has been with the Next-generation Power Technology Center in Korea since
2009. His main research interests are power system protection.
Sang-Hee Kang is a proIessor at Myongji University, Korea. He received the
B.S., M.S. and Ph.D. degrees Irom Seoul National University, Korea, in 1985,
1987, and 1993, respectively. He was a visiting Iellow and a visiting scholar
at the University oI Bath, United Kingdom, in 1991 and 1999, and he has
been with Next-generation Power Technology Center, Korea, since 2001. He
was an honorary academic visitor at the University oI Manchester, UK, in
2007. His main research interests are the development oI digital protection
systems Ior power systems using digital signal processing techniques.
Byung M. Han received the B.S degree in Electrical Engineering Irom the
Seoul National University, Korea, in 1976, and the M.S and Ph.D. degrees
Irom Arizona State University in 1988 and 1992, respectively. He was with
Westinghouse Electric Corporation as a Senior Research Engineer in the
Science & Technology Center. Currently, he is a proIessor at the Department
oI Electrical Engineering, Myoungji University, Korea. His research interests
include power converters Ior power system applications, Ilexible AC
transmission systems, high-voltage DC transmission, custom power devices,
and distributed generation.