Вы находитесь на странице: 1из 10

`

PRODUCT RELEASE REVIEW


2006

50315.PRR0036
Page 1 of 10 Issue A 2 June 2006 CONFIDENTIAL
The information contained in this document is not to be communicated either directly or indirectly to any person not authorised to receive it.

PX40 PLATFORM - MICOM P540 CURRENT DIFFERENTIAL PHASE 2 P54XXXXXXXX320J PRODUCT RELEASE INCOPORATING SOFTWARE 32B

VOB Location: /var/www/apps/conversion/tmp/scratch_1/149298988.doc

RELEASE STATEMENT
This release is a special software release for Hydro Quebec. All models from the P546xxxxxxx320J product range, incorporating the P540 version 32B release of software shall be released to production. This release involves changes to the software. This release is required following Products Notice Risk Assessments 2006.004 & 2006.006.

See Lotus Notes database Products Release Review NROB-6QD9Y8 for approval signatures.

T&D
Automation & Information Systems - St Leonards Avenue Stafford ST17 4LX England Tel: +44 (0)1785 223251 Fax: +44 (0)1785 212232
AREVA T&D UK LTD. Registered Office: St Leonards Avenue Stafford ST17 4LX Registered in England: 4955841

50315.PRR0036
Page 2 of 10 Issue A 2 June 2006 Table of Contents

PRODUCT RELEASE REVIEW

1. PRODUCT RELEASE.................................................................................................................. 3 1.1. OVERVIEW............................................................................................................................... 3 1.2. SCOPE OF THE RELEASE......................................................................................................3 2. REFERENCES............................................................................................................................. 3 3. PRODUCT SAFETY.....................................................................................................................4 4. NATIONAL AND INTERNATIONAL LEGISLATION...................................................................4 5. FUNCTIONALITY AND PERFORMANCE...................................................................................4 6. EXTERNAL PRODUCT APPROVALS........................................................................................4 7. PRODUCTION AND DELIVERY..................................................................................................4 8. QUALITY ASSURANCE.............................................................................................................. 4 9. SUPPORT.................................................................................................................................... 4 10. RELEASE NOTES..................................................................................................................... 4 10.1. INVENTORY OF DOCUMENTATION.....................................................................................4 10.2. INVENTORY OF SOFTWARE ITEMS IN RELEASE...............................................................5 10.3. INVENTORY OF SOFTWARE COMPONENTS......................................................................5 10.4. SOFTWARE CHANGES IMPLEMENTED IN THIS VERSION................................................5 10.5. SOFTWARE DEFECTS/ISSUES CORRECTED IN THIS VERSION......................................6 10.6. INVENTORY OF HARDWARE ITEMS AND COMPONENTS IN RELEASE...........................7 10.7. HARDWARE CHANGES IMPLEMENTED IN THIS VERSION................................................7 10.8. HARDWARE DEFECTS/ISSUES CORRECTED IN THIS VERSION......................................7 10.9. OUTSTANDING HARDWARE DEFECTS/ISSUES IN THIS VERSION...................................7 10.10. DTS SYSTEM BASELINE.....................................................................................................7 11. OUTSTANDING SOFTWARE, HARDWARE & OTHER DEFECTS / RISK ASSESSMENT & MANAGEMENT PHILOSOPHY.....................................................................................8 12. OTHER COMMENTS.................................................................................................................9

PRODUCT RELEASE REVIEW

50315.PRR0036
Page 3 of 10 Issue A 2 June 2006

1.
1.1.

PRODUCT RELEASE
OVERVIEW This release covers P546xxxxxxx320J product range, incorporating the P540 software version 32B. This product release affects software only. Software 32B like 32A are special versions of P546 software for Hydro-Qebec. Software 32B is based on 32A, which was based on 30F, but including all the changes added to 30F to produce 30I as detailed in sections 10.4 & 10.5 and summarised below: Resolved a mal operation of the distance protection Resolved a problem relating to IRIG-B Improved DNP3 performance Fixed other bugs

This is an essential bug fix version required by Products Notice Risk Assessments 2006.004 & 2006.006. See section 12 for further information. 1.2. SCOPE OF THE RELEASE Models affected by this release: Model P541 P542 P543 P544 P545 P546 Courier Modbus Protocol IEC60870-5103 DNP3 UCA2 Not Available Not Available

The features of each of the protocol options are unchanged from previous release 32A software as described in service manual P54x/EN T/G42. Language Options The following language options are provided English/French/German/Spanish English/French/German/Russian

2.

REFERENCES
Ref A B Document Number PDP0003 9105 0422 Issue D D Document Name Product Release Product Release Px40 Software

50315.PRR0036
Page 4 of 10 Issue A 2 June 2006

PRODUCT RELEASE REVIEW

3.

PRODUCT SAFETY
As there are no hardware changes there is no impact on existing product safety requirements.

4.

NATIONAL AND INTERNATIONAL LEGISLATION


The requirements for the EU are covered in the existing TCF 50331.3711.001 The existing Declaration of Conformity (DOC) DOCR 0150 is valid. There are no additional requirements for non EU markets.

5.

FUNCTIONALITY AND PERFORMANCE


P540 relays have passed all tests required as agreed with Certification and documented in the change control 50315.C0138. All models / protocols shown in the table in section 1.2 have passed the build verify tests described in 50315.3210.014C. A 48-hour burn in has been completed on one relay with no failures.

6.

EXTERNAL PRODUCT APPROVALS


Software 32A & 32B, has been developed specifically for Hydro Quebec and is subject to their homologation process.

7.

PRODUCTION AND DELIVERY


This is a maintenance release of software. New model numbers are not required. No changes are required to the production test bench.

8.

QUALITY ASSURANCE
All documents and software files have been placed under configuration management using the clearcase system as described in documentation plan 50315.2050.001 and section 10.2 of this document.

9.

SUPPORT
The changes do not affect the service manuals These changes do not affect the MiCOM S1 support files issued for version 31A. Note these support files are in English and French languages only. An electronic Defect Tracking System is used for reporting and resolving defects. The existing development team will supply maintenance within R&D.

10.
10.1. 10.1.1.

RELEASE NOTES
INVENTORY OF DOCUMENTATION Development Documentation See change control 50315.C0138 Product Literature Service manuals are:

10.1.2.

PRODUCT RELEASE REVIEW

50315.PRR0036
Page 5 of 10 Issue A 2 June 2006

10.2.

P54x EN T/H53 P54x EN O/H53

INVENTORY OF SOFTWARE ITEMS IN RELEASE See 50304.SR0081 for further details.

10.3.

INVENTORY OF SOFTWARE COMPONENTS COMPONENT Courier library MODBUS library IEC870 library DNP3 library System Services Px40 Platform UCA2 library UCA2 library UCA2 library CAA P540 main board P540 C Diff * VOB REFERENCE 50222\courier 50222\modbus 50222\iec870 50222\ 50222\DNP3 50300L1 50300PL 50300PL\lib\mvl\ \50300PL\lib\uca2\ \50300PL\lib\vxworks 50300PR 50304B 50304CD RELEASE IDENTIFIER C1.4 MODBUS_B1.3 A1.0 Px40custom\V2.32F V2.32 CPU2_B2.4 D2.4* MMSLITE_V4.21B MODTOOL_V2.3C VXWORKS_V5.4 D3.3** H1.1 F1.5 NEW?

See 50304B\build2\config.txt Issue32B for the ClearCase configuration spec. All files as label except:
50300PL\DEV\pl\SRC\copro.c /main/50309.c0901\2 50300PL\DEV\pl\INC\copro.h /main/50309.c0901\1

**

All files as label except:


50300PR\DEV\pr\SRC\ar_singlepole.c ...\P443_Phase1\14 50300PR\DEV\pr\SRC\vts.c ...\50300PR.C0080\2 50300PR\DEV\pr\INC\vts.h ...\50300PR.C0080\2 50300PR\DEV\pr\SRC\poledead.c ...\50300PR.C0103\1 50300PR\DEV\pr\INC\poledead.h ...\50300PR.C0103\1

10.4.

SOFTWARE CHANGES IMPLEMENTED IN THIS VERSION CHANGE C0946 C0955 SUMMARY Remove duplicate font table that is amount to a saving of 1028 32-bit words of memory. Updates to DNP to provide compatibility with C264 interframe gap

50315.PRR0036
Page 6 of 10 Issue A 2 June 2006 CHANGE C0964 C0976 50315.C0137 SUMMARY

PRODUCT RELEASE REVIEW

Addition of S1_LANG: and S1_MODEL_1: entries to extracted LNG files, plus change of FILESOURCE from ALSTOM to READONLY Modifications to Modbus to allow individual register access. Improvements to the Distance protection

10.5.

SOFTWARE DEFECTS/ISSUES CORRECTED IN THIS VERSION DEFECT PCL980 PCS2417 PCS2419 PCS2422 PCS2434 PCS2440 PCS2450 PCS2451 PCS2483 PCS2486 PCS2489 PCS2493 PCS2497 SUMMARY When long disturbance file are recorded ( Extended mode) several splited files can be created Maximum frame size for FT1.2 frames in the Phase 2 CPU VDEW driver is incorrect. Incorrect Time and Data stamp when 'Comm2 H/W Fail' alarm is raised Incorrect 'Comm2 H/W Fail' event logging. Phase 2 Flash Driver: Allocated memory is not initialised at startup. Relay reboots with errorcode 0x04100001 if a Courier Get strings command is issued for cell B21C, the block transfer mode cell. The error message for the coprocessor application image transfer reports an FPGA transfer error. Relay Healthy LED not extinguished on self-test failure In P546 IEEE C3794 alarms are incorrectly mapped in DNP3 in the documentation Distance & C Diff starts are coded as ASDU1 instead of ASDU2 in CS103 Incorrect character bitmap in Phase 2 CPU UI for character code 92 "\" backslash Uncompressed Disturbance Recorder does not trap out of range sample values. An attempt to set the data cell [04 20] Thermal State returns 'Local Access in Progress'. It should return 'Remote Access Denied' CS103 - The relay can incorrectly retransmit frames due to a repeated request message. Reset Indications via front port results in a CS103 message with a remote COT indicated Incorrect address returned for DNP3.0 link layer requests German & Spanish text for external loopback is same as internal loopback IRIG-B Status changes status between "Signal Healthy" and "Card Failed" even though the IRIG-B source is healthy. Status of LEDs is stored to non-volatile memory for all changes.

PCS2502 PCS2519 PCS2529 PCS2552 PCS2559 PCS2564

PRODUCT RELEASE REVIEW

50315.PRR0036
Page 7 of 10 Issue A 2 June 2006

DEFECT PCS2567 PCS2573 PCS2597 PCS2585

SUMMARY Multiple settings changes can cause relay reboot due to RCUR2 message queue When relay is powered up, IRIG-B reports card fail until signal applied.
Selection of (Overcurrent, Earth fault and SEF) IEEE IDMT Reset Curves causes relay to reboot

Uncompressed Disturbance record Pre-trigger is calculated incorrectly

10.6.

INVENTORY OF HARDWARE ITEMS AND COMPONENTS IN RELEASE This software runs in relays with design suffix J. The hardware has not changed and the inventory is detailed in the Technical Construction File 50300.3711.001.

10.7.

HARDWARE CHANGES IMPLEMENTED IN THIS VERSION Change ID Summary None

10.8.

HARDWARE DEFECTS/ISSUES CORRECTED IN THIS VERSION Defect ID Summary None

10.9.

OUTSTANDING HARDWARE DEFECTS/ISSUES IN THIS VERSION Defect ID Summary None

10.10.

DTS SYSTEM BASELINE A record of the current DTS ID counters is required so that defects identified after this release can be unambiguously identified. Date 22-5-2006 Time 14:30 PCL 1037 PCS 2617 PCP 23

Page 8 of 10 Issue A 2 June 2006

50315.PRR0036

11.

OUTSTANDING SOFTWARE, HARDWARE & OTHER DEFECTS / RISK ASSESSMENT & MANAGEMENT PHILOSOPHY
No Defect Description Of Defect / Risk Effect Of Defect / Risk Impact / Likelihood / Risk Factor 2/2/ Acceptable Risk Management

PCS2230

DNP3 CROB (Object 12) Operation is not compliant with DNP3 TB2000-002 and the level 2 test procedure Disruption of the analogue input sampling process; resulting in incorrect analogue values being used by the protection algorithms Section 11.5 of the Courier User Manual (R6512 Issue F) specifies that: "Entering an incorrect password at any time will result in the password level being reset." Modbus inactivity timer does not reset password if events are being extracted Russian text in relay not reviewed

The relay may produce a spurious error message if a DNP3 master station resends a command Self checking will detect this condition and reboot the relay, which will clear the condition Password protection does not perform as the specification says

Assist customers reporting problem Fix when dnp3 enhancements incorporated in later versions Assist customers reporting problem

PCS2367

2/2/ Acceptable

PCS2441

1/2/ Acceptable

Include fix when available

PCS2452

Password protection does not perform as it should while modbus is polling for events Russian customers may find errors with Russian text in relay Possible incorrect occurrence of flashing alarm Courier should return an error code no data

1/2/ Acceptable 2/2/ Acceptable 1/1/Acceptable

Include fix when available

PRODUCT RELEASE REVIEW

5 6 PCS2521

Russian text can be corrected with S1 Text Editor Assist customers reporting problem

"Standing Alarm LED starts to flash with no new Alarms shown." Ch2 Rx & Tx Prop delays when GPS is failed display 1.0s when read over courier

PCS2523

1/1/Acceptable

Assist customers reporting problem

Note: Shaded areas indicate defects added since the last release

PRODUCT RELEASE REVIEW

50315.PRR0036
Page 9 of 10 Issue A 2 June 2006

12.

OTHER COMMENTS

50315.PRR0036
Page 10 of 10 Issue A 2 June 2006

PRODUCT RELEASE REVIEW

REVIEW HISTORY
Issue A Name N Robinson S Potts B Caunce S Richards P Horton Position P540 Team Leader R&D Manager Certification Manager Marketing Manager Marketing

VERSION CONTROL
Issue A Author(s) N Robinson Reason for change First Issue Date 2/6/2006