Standard Technical Specifications for Electrical Works

POWER COMPENSATION
( Data Sheets )

11kV Capacitor Banks

FEWA STANDARD : D-POC-CAP-11 (Rev.0-2010)


________________________________________________________________________________________
4-DATA SHEET CAPACITOR BANK Page 1 of 25

POWER COMPENSATION 11kV Capacitor Banks

Table of Content
Page

1.00 2.00 A. B. C. D. E. F. G. H. I. J. K. L. #### N. 3.00 A. B. C. D. E. F. G. H. I. J.

GENERAL CONSTRUCTION DATA Capacitor Unit Capacitor Unit Bushings Series Reactors Contactor External Capacitor Stage HRC Fuses Capacitor Racks Surge Arresters Isolator / Grounding Switch (3-Position) Capacitor Bank Feeder Circuit Breaker Post Insulators Current Transformers Capacitor Bank Housing for outdoor type (if applicable) #REF! Wiring ELECTRICAL DATA Common for the Capacitor Bank Busbars Capacitor Units Capacitor Unit Bushings Series Reactors (de-tuning) Contactor External Capacitor Unit Fuses Surge Arresters Isolator / grounding switch (3-position) Post Insulators

4 4 4 6 6 6 7 8 8 8 9 9 10 10 14 16 16 16 17 17 18 18 19 19 20 20 20

_____________________________________________________________________________________________________________
4-DATA SHEET CAPACITOR BANK Page 2 of 25

POWER COMPENSATION 11kV Capacitor Banks

Table of Content
Page

K. L. M. 4.00 A. B. C. D. E. F. G. 5.00 6.00 7.00

Wiring Voltage and Current Transformers Capacitor Bank Feeder Circuit Breaker CONTROL & PROTECTION Common Features of numerical devices Reactive Power Regulator Unbalance Protection Relay Thermal Overload Protection Relay Over / Under Voltage Relay Overcurrent / Earhtfault Relay Control / Protection Cubicles TESTS LOSSES SUPPORTING DOCUMENTS

20 20 21 21 21 21 22 23 24 25 25 25 25 25

_____________________________________________________________________________________________________________
4-DATA SHEET CAPACITOR BANK Page 3 of 25

POWER COMPENSATION 11kV Capacitor Banks Sl. No. REQUIRED TENDERED

1.00
1.01 1.01.1 1.01.2 1.02

GENERAL
Manufacturer of complete Capacitor Bank name country of manufacturer Applicable standards
71-1, 2, 3, 4 60060-1 60549 IEEE Std. 18-2002 IEEE Std. 1036 IEEE Std. C37.19.00 IEC

1.03 1.03.1 1.03.2 1.03.3 1.03.3.1 1.03.3.2 1.04 1.05 1.06

Type test carried out date testing laboratory name country Maximum audible sound level at 2m distance Type Commercial operation time of offered capacitor years bank type
dB(A) 50 dd-mm-yy yes

2.00
A.
2.01 2.01.1 2.01.2 2.02

CONSTRUCTION DATA
Capacitor Unit Manufacturer name country of manufacturing Applicable standards Type test carried out date
dd-mm-yy yes IEC 60871-1 60871-4

2.03 2.03.1 2.03.2

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
4-DATA SHEET CAPACITOR BANK Page 4 of 25

POWER COMPENSATION 11kV Capacitor Banks Sl. No. REQUIRED TENDERED

2.03.3 2.03.3.1 2.03.3.2 2.04 2.05 2.05.1 2.05.2 2.05.3 2.06 2.07

testing laboratory name country Type Number of capacitors (elements) series parallel total Number of bushings Type of connector provided at capacitor unit terminals Type of internal fuse Minimum No. of elements in each unit Impregnant applicable standards impregnating medium brand name specification reference Container material type grade thickness degree of protection minimum rupturing pressure of container dimension length width height Discharge resistor (built-in)
mm mm mm yes mm IP kg/mm2 stainless steel non-PCB Min. 40 No. No. No. No. 2

2.08 2.09 2.10 2.10.1 2.10.2 2.10.3 2.10.4 2.11 2.11.1 2.11.1.1 2.11.1.2 2.11.1.3 2.11.1.4 2.11.2 2.11.3 2.11.3.1 2.11.3.2 2.11.3.3 2.12

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
4-DATA SHEET CAPACITOR BANK Page 5 of 25

POWER COMPENSATION 11kV Capacitor Banks Sl. No.


2.12.1 2.13

REQUIRED type Total weight of complete unit capacitor including all fitting and impregnating medium
kg

TENDERED

2.14

Commercial operation time of offered capacitor u years


* approximate data will be finalised at detailed engineering stage

B.
2.15 2.15.1 2.15.2 2.16

Capacitor Unit Bushings Manufacturer name country of manufacturing Applicable standards


IEC 60137

2.17 2.17.1 2.17.2 2.17.3 2.17.3.1 2.17.3.2 2.18 2.19 2.20 2.21 2.22

Type test carried out date testing laboratory name country Type Catalogue number Material Creepage distance Commercial operation time of offered unit bushings Series Reactors
mm/kV years composite 31 dd-mm-yy yes

C.

as per requirement specified in standard

D.
2.23 2.23.1 2.23.2 2.24

Contactor Manufacturer name country of manufacturing Applicable standards


IEC 60265-1 + 60470

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
4-DATA SHEET CAPACITOR BANK Page 6 of 25

POWER COMPENSATION 11kV Capacitor Banks Sl. No. REQUIRED TENDERED

2.25 2.25.1 2.25.2 2.25.3 2.25.3.1 2.25.3.2 2.26 2.27 2.28 2.28.1 2.29 2.29.1 2.29.2 2.30 2.30.1 2.30.2 2.30.3 2.31 2.32

Type test carried out date testing laboratory name country Type Catalogue number Interrupting medium vacuum Auxiliary contacts normally open (NO) when contactor is closed No. normally close (NC) when contactor is closed No. Operating mechanism power consumption closing (d.c.) holding (d.c.) tripping (d.c.) Position indicator Commercial operation time of offered contactor years External Capacitor Stage HRC Fuses Manufacturer name country of manufacturing Applicable standards Type test carried out date testing laboratory name
dd-mm-yy yes IEC for capacitor bank +60282 W W W yes 4 4 yes/no dd-mm-yy yes

E.
2.33 2.33.1 2.33.2 2.34

2.35 2.35.1 2.35.2 2.35.3 2.35.3.1

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
4-DATA SHEET CAPACITOR BANK Page 7 of 25

POWER COMPENSATION 11kV Capacitor Banks Sl. No.


2.35.3.2 2.36 2.37 2.38 2.39 2.40

REQUIRED country Type Catalogue number Visual indicating when blown Weight Commercial operation time of offered fuses Capacitor Racks Number of racks Number of capacitor units connected in parallel per phase Mounting of capacitor units horizontal vertical Center line between capacitor units Dimension length width height Center line between capacitor racks Surge Arresters
mm mm mm mm mm yes/no yes/no No. No. kg years yes

TENDERED

F.
2.41 2.42

2.43 2.43.1 2.43.2 2.44 2.45 2.45.1 2.45.2 2.45.3 2.46

G.

as per requirement specified in standard

H.
2.47 2.47.1 2.47.2 2.48 2.49 2.49.1

Isolator / Grounding Switch (3-Position) Manufacturer name country of manufacturing Applicable standards Operating facilities hand
yes IEC 60129

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
4-DATA SHEET CAPACITOR BANK Page 8 of 25

POWER COMPENSATION 11kV Capacitor Banks Sl. No.


2.49.2 2.50 2.50.1 2.50.2 2.51 2.51.1 2.51.2 2.51.3 2.52 2.53

REQUIRED motor Auxiliary switch contacts normally open (NO) when isolator is closed normally close (NC) when isolator is closed Dimension length width height Weight Commercial operation time of offered isolator / grounding switch Capacitor Bank Feeder Circuit Breaker
mm mm mm kg years No. No. 4 4 yes

TENDERED

I.

as per requirement specified in standard

J.
2.54 2.54.1 2.54.2 2.55 2.56 2.56.1 2.56.2 2.56.3 2.56.3.1 2.56.3.2 2.57 2.58 2.59 2.60

Post Insulators Manufacturer name country of manufacturing Applicable standards Type test carried out date testing laboratory name country Type Catalogue number Material Creepage distance
composite dd-mm-yy yes IEC

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
4-DATA SHEET CAPACITOR BANK Page 9 of 25

POWER COMPENSATION 11kV Capacitor Banks Sl. No.


2.60.1 2.60.2 2.61 2.61.1 2.61.2 2.61.3 2.63 2.64

REQUIRED Installations in indoor housing (IP 43) Installations in outddor housing (IP 54) Strength cantilever tensile compression Weight Commercial operation time of offered post insulators Current Transformers
N N N kg years mm/kV mm/kV 42 31

TENDERED

K.

as per requirement specified in standard

L.
2.65 2.65.1 2.65.2 2.66 2.67 2.67.1 2.67.1.1 2.67.1.2 2.67.2 2.67.2.1 2.67.2.2 2.67.2.3 2.67.2.4 2.67.3 2.67.3.1 2.67.3.1.1

Capacitor Bank Housing for outdoor type (if applicable) Manufacturer name country of manufacturing Applicable standards Construction material details base plate / corner posts material minimum thickness walls / doors material applicable standards minimum thickness K-value roof (double sheet) upper and lower side material
ALU-ZINC BS mm W/m2 0 ALU-ZINC 729 2 0.56 hot-dip galvanised steel sheet mm 3 IEC

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
4-DATA SHEET CAPACITOR BANK Page 10 of 25

POWER COMPENSATION 11kV Capacitor Banks Sl. No.


2.67.3.1.2 2.67.3.1.3 2.67.3.1.4 2.67.4 2.67.4.1 2.67.4.2 2.67.4.3 2.68 2.69 2.69.1

REQUIRED applicable standards minimum thickness K-value partitions (if applicable) material applicable standards minimum thickness Protection against accumulation of water on roof Degree of protection switchgear compartment
IP 54 Outdoor, 43 - Indoor BS mm yes ALU-ZINC BS mm W/m2 K 729 2 0.41

TENDERED

2.70 2.70.1 2.70.1.1 2.70.1.2 2.70.1.3 2.70.1.4 2.70.1.5 2.70.1.6 2.71 2.71.1 2.71.1.1 2.71.1.2 2.71.1.3 2.72 2.73 2.74 2.74.1 2.75

Lighting normal type number power voltage MCB protection door switch provided Sockets single-phase type number voltage Vermin proof Access doors for each compartment Door stopper at all doors gas-spring type Door fixings to fix the door panel during maintenance
yes/no yes No. v 1 240 yes/no yes No. W Vac bulk head 1 100 240 yes yes yes

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
4-DATA SHEET CAPACITOR BANK Page 11 of 25

POWER COMPENSATION 11kV Capacitor Banks Sl. No.


2.76 2.76.1

REQUIRED Corrosion protection details material outside type minimum thickness color inside type minimum thickness color Earthing arrangement earthing bar material minimum cross-section dimension width height interconnection between compartments, etc. material minimum cross-section number of connections for external earthing copper rods at housing external earthing devices material minimum number cross-section of each copper rod Danger sign details (at each housing door) material grade
stainless steel 1.4301 (V2A) No. mm2 copper rods 2 stranded copper conductor mm2 No. 70 2 mm2 copper 240 m RAL 40 m RAL 100 7032 powder paint polymer resin base

TENDERED

2.76.2 2.76.2.1 2.76.2.2 2.76.2.3 2.76.3 2.76.3.1 2.76.3.2 2.76.3.3 2.77 2.77.1 2.77.1.1 2.77.1.2 2.77.1.3 2.77.1.3.1 2.77.1.3.2 2.77.2 2.77.2.1

2.77.2.2 2.77.3 2.77.4 2.77.5 2.77.5.1 2.77.5.1.1 2.77.5.1.2 2.78 2.78.1 2.78.1.1

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
4-DATA SHEET CAPACITOR BANK Page 12 of 25

POWER COMPENSATION 11kV Capacitor Banks Sl. No.


2.78.2 2.78.3 2.78.4 2.78.4.1 2.78.4.2 2.78.5 2.78.5.1 2.78.5.2 2.78.6 2.78.6.1 2.78.6.1.1 2.78.7 2.79 2.79.1 2.79.1.1 2.79.2 2.79.3 2.79.4 2.79.4.1 2.79.4.2 2.79.5 2.79.5.1 2.79.5.2 2.79.6 2.79.6.1 2.79.6.1.1 2.79.7 2.80 2.80.1 2.80.1.1 2.80.2 2.80.2.1

REQUIRED width height letters quality of paint height of letters colors background letters fixing bolts material grade numbers Identification sign details (at housing) material grade width height letters quality of paint height of letters colors background letters fixing bolts material grade numbers Lifting devices details housing number roof number
4 4 No. stainless steel 1.4301 (V2A) 1 red sun light proof, no fading mm 100 mm mm stainless steel 1.4301 (V2A) No. stainless steel 1.4301 (V2A) red sun light proof, no fading mm 100 mm mm

TENDERED

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
4-DATA SHEET CAPACITOR BANK Page 13 of 25

POWER COMPENSATION 11kV Capacitor Banks Sl. No.


2.81 2.81.1 2.82 2.82.1

REQUIRED Cable protection 11 kV underground cable protection box Stainless steel used for handles, hinges, signs, bolts, nuts, etc. grade Wiring Material stranded copper wires for cross-sections >2.5mm2 else solid copper wires
copper 1.4301 (V2A) yes yes

TENDERED

N.
2.83

2.84 2.84.1 2.84.2 2.84.3 2.84.4 2.84.5

Cross-sections power circuits (min) control circuits CT circuits (min) VT circuits (min) other wiring
mm2 mm2 mm2 mm2 mm2 1.5 1.0 2.5 1.5 1.5

3.00
A.
3.01 3.02 3.03 3.04 3.05 3.06 3.07 3.08 3.09 3.09.1 3.09.2 3.10

ELECTRICAL DATA
Common for the Capacitor Bank Rated voltage Permissible overvoltage (continuous) Nominal operating voltage Rated current Permissible continuous current Rated output at 400C ambient temperature Permissible maximum output Frequency Lightning impulse withstand voltage indoor type outdoor type Power frequency withstand test voltage # suitable for 12kV maximum system voltage * stage contactors and fuses are rated 12kV
kVpeak kVpeak kVrms 75 95 38 kV % kV A % MVAr % Hz 1.3 x Irated 3 x 1.2 135 50 12 1.1 x Urated 11

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
4-DATA SHEET CAPACITOR BANK Page 14 of 25

POWER COMPENSATION 11kV Capacitor Banks Sl. No.


3.11 3.12 3.13 3.14 3.15

REQUIRED Rated short-circuit current Rated reactance (per phase) Nominal capacitance Maximum permitted tolerance (%)
kA/3se F % 31.5

TENDERED

Maximum dielectric stress permitted by the design for capacitor bank Total losses Variation of losses due to temperature variation over an ambient temperature range from 0C to +50C Variation of capacitance due to temperature variation over an ambient temperature range from 0C to +50C Self inductance of Control circuits voltage Auxiliary circuits rated voltage Busbars Rated current carrying capacity at max. 50C Rated current carrying capacity at 40C
A A kW Dwg No.

3.16 3.17

3.18

Dwg No.

3.19 3.20 3.21

mH Vdc Vac 110 230/400

B.
3.22

C.
3.23 3.24 3.25 3.26 3.27 3.28 3.28.1 3.28.1.1 3.28.1.2 3.28.2 3.29 3.30

Capacitor Units Rated current Rated output Nominal capacitance Maximum permitted tolerance (%)
A kVAr F %

Maximum dielectric stress permitted by the design Insulation level of each unit capacitor lightning impulse level outdoor indoor power frequency withstand voltage Total losses Variation of losses due to temperature variation over an ambient temperature range from 0C to +50C
kV kVpeak kVpeak kV W Dwg. No. 95 75 38

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
4-DATA SHEET CAPACITOR BANK Page 15 of 25

POWER COMPENSATION 11kV Capacitor Banks Sl. No.


3.31

REQUIRED Variation of capacitance due to temperature variation over an ambient temperature range from 0C to +50C Maximum surface temperature of unit capacitor container Internal temperature of unit capacitor mean max hot spot Self inductance of Natural frequency of unit capacitor Resistance of discharge resistor Time required for capacitor-unit internal discharge devices alone (without the aid of external discharge paths) to discharge the capacitor per phase voltage from rated voltage to 75 V Tolerance of rated capacity at rated V and Hz Max. operating capacity Max. operating voltage (including harmonics) Max. operating current (including harmonics) Capacitor Unit Bushings Impulse withstand voltage Power frequency withstand voltage dry wet Series Reactors (de-tuning)
kV1min kV10s as per requirement specified in standard C C mH kHz k minutes <10

TENDERED

Dwg. No.

3.32

3.33 3.33.1 3.33.2 3.34 3.35 3.36 3.37

3.38 3.39 3.40 3.41

% of rated KVAr % of rated KVAr % of rated KVAr % of rated KVAr

D.
3.42 3.43 3.43.1 3.43.2

E.

F.
3.44 3.45

Contactor Rated voltage Operating voltage


kV kV 12 11

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
4-DATA SHEET CAPACITOR BANK Page 16 of 25

POWER COMPENSATION 11kV Capacitor Banks Sl. No.


3.46 3.47 3.48 3.49 3.50 3.50.1 3.50.1.1 3.50.1.2 3.51 3.51.1 3.51.1.1 3.51.1.2 3.52 3.52.1

REQUIRED Rated current at 40C Rated current at 50C Rated breaking current capacity Breaking time Closing time number of switchings with rated current with rated short circuit breaking current Rated supply voltage of operating mechanism coil allowable variation of voltage power consumption at normal voltage Auxiliary switches rated voltage External Capacitor Unit Fuses Rated current of the fuse link
A Vac 230 Vdc % W 110 No. No. 100,000 100 A A kA mS mS

TENDERED

G.
3.53 3.54 3.55 3.56 3.57 3.57.1 3.57.2 3.58

Max. continuous current capability of the fuse linkA Rated capacity breaking current Rated inductive breaking current Max. I2 t values which the fuse can withstand for: 5 discharges 100 discharges Max. available capacitor energy which the fuse kJ can withstand at 1.5 times of rated voltage without bursting Minimum pre-arcing I2 t (under substantially adiabate conditions) Maximum total clearing I2 t inductive power frequency current capacitive power frequency current Cold resistance of the fuse link
A A

3.59

3.60 3.60.1 3.60.2 3.61

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
4-DATA SHEET CAPACITOR BANK Page 17 of 25

POWER COMPENSATION 11kV Capacitor Banks Sl. No.


3.61.1 3.62

REQUIRED tolerances Time-current characteristic curve attached Surge Arresters


yes as per requirement specified in standard

TENDERED

H.

I.
3.63 3.63.1 3.63.2 3.64 3.64.1 3.64.2

Isolator / grounding switch (3-position) Remote operation closing time with motor drive opening time with motor drive Motor drive power rated voltage Post Insulators Critical-Impulse flashover, positive Power frequency withstand voltage Wiring Power frequency withstand voltage Voltage and Current Transformers
kVac-1m 3 kVcrest kVrms W Vdc 110 s s yes

J.
3.65 3.66

K.
3.67

L.

as per requirement specified in standard

M.

Capacitor Bank Feeder Circuit Breaker

as per requirement specified in standard

4.00
A.

CONTROL & PROTECTION


Common Features of numerical devices
as per requirement specified in standard

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
4-DATA SHEET CAPACITOR BANK Page 18 of 25

POWER COMPENSATION 11kV Capacitor Banks Sl. No. REQUIRED TENDERED

B.
4.01 4.01.1 4.01.2 4.02 4.03 4.04 4.05 4.05.1 4.05.2 4.05.3 4.05.3.1 4.05.3.2 4.06 4.06.1 4.06.2 4.06.3 4.06.4 4.06.5 4.06.6 4.06.7 4.06.8 4.06.9 4.06.10 4.06.11 4.06.12 4.06.13

Reactive Power Regulator Manufacturer name country of manufacturing Applicable standards Type Type number Type test carried out date testing laboratory name country Technical Data Rated Current Rated Frequency Supply Voltage Scan Rate Regulation steps Setting Range Memory Capacity Over Compensation Monitoring Manual Mode Self Monitoring Solternal Interface Connection to SCMS Type of Protocol to SCMS Unbalance Protection Relay
cos phi kB RAM A Hz V DC kHz dd-mm-yy yes/no IEC numerical

1 50 110

min 4

yes yes yes RS232 yes IEC

C.

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
4-DATA SHEET CAPACITOR BANK Page 19 of 25

POWER COMPENSATION 11kV Capacitor Banks Sl. No. REQUIRED TENDERED

4.07 4.07.1 4.07.2 4.08 4.09 4.10 4.11 4.11.1 4.11.2 4.11.3 4.11.3.1 4.11.3.2 4.12 4.12.1 4.12.1.1 4.12.1.2 4.12.1.3 4.12.1.4 4.12.2 4.12.3 4.12.4 4.12.4.1 4.12.4.2 4.12.4.3 4.12.5 4.12.6 4.12.7 4.12.7.1 4.12.7.2 4.12.7.3

Manufacturer name country of manufacturing Applicable standards Type Type number Type test carried out date testing laboratory name country Technical Data DC Infeed rated voltage DC/DC converter included allowable tolerances power consumption Rated current Protection class of relay housing Settings unbalance current range number of stages accuracy Overload limit of unbalance input Operation delay Output contact rating continuous current making current breaking current
A A A A A 2 1 52 110 yes +10/-15 ddmmyes/no IEC numerical

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
4-DATA SHEET CAPACITOR BANK Page 20 of 25

POWER COMPENSATION 11kV Capacitor Banks Sl. No.


4.12.8 4.12.9 4.12.10

REQUIRED Solternal Interface Connection to SCMS Type of Protocol to SCMS Thermal Overload Protection Relay Manufacturer name country of manufacturing Applicable standards Type Type number Type test carried out date testing laboratory name country Technical Data DC Infeed rated voltage DC/DC converter included allowable tolerances power consumption Rated current Protection class of relay housing Settings setting range number of stages required operating time Over / Under Voltage Relay A
2 1 52 110 yes +10/-15 dd-mm-yy yes/no IEC numerical

TENDERED

RS232 yes IEC

D.
4.13 4.13.1 4.13.2 4.14 4.15 4.16 4.17 4.17.1 4.17.2 4.17.3 4.17.3.1 4.17.3.2 4.18 4.18.1 4.18.1.1 4.18.1.2 4.18.1.3 4.18.1.4 4.18.2 4.18.3 4.19 4.19.1 4.19.2 4.19.3

E.

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
4-DATA SHEET CAPACITOR BANK Page 21 of 25

POWER COMPENSATION 11kV Capacitor Banks Sl. No.


4.20 4.20.1 4.20.2 4.21 4.22 4.23 4.24 4.24.1 4.24.2 4.24.3 4.24.3.1 4.24.3.2 4.25 4.25.1 4.25.1.1 4.25.1.2 4.25.1.3 4.25.1.4 4.25.2 4.26 4.26.1 4.26.2 4.26.3 4.26.4 4.26.5 4.26.6

REQUIRED Manufacturer name country of manufacturing Applicable standards Type Type number Type test carried out date testing laboratory name country Technical Data DC Infeed rated voltage DC/DC converter included allowable tolerances power consumption Protection class of relay housing Settings setting range operating time No. of stages required Solternal Interface Connection to SCMS Type of Protocol to SCMS Overcurrent / Earhtfault Relay
2 52 110 yes +10/-15 dd-mm-yy yes/no IEC numerical

TENDERED

+/-V

RS232 yes IEC


as per requirement specified in standard

F.

G.

Control / Protection Cubicles

as per requirement

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
4-DATA SHEET CAPACITOR BANK Page 22 of 25

POWER COMPENSATION 11kV Capacitor Banks Sl. No. REQUIRED TENDERED

5.00

TESTS
as per IEC60871 (1-4)

5.01 5.01.1 5.01.2

Capacitor Unit routine tests Insulation resistance


2.25 Urated yes

5.01.3

thermal stability test

yes

6.00
6.01

LOSSES
Guaranteed steady-state loss of capacitor bank at 250 C ambient temperature Dielectric losses Discharge resistor losses
W/kVar W/kVar

6.01.1 6.01.2

7.00
7.01 7.02 7.03 7.04 7.05

SUPPORTING DOCUMENTS
Type test reports enclosed ? List of minimum testing facilities enclosed ? Technical literature enclosed ? Relevant drawing enclosed ? Quality assurance plan (QAP) enclosed ?
yes yes yes yes yes

* Notes: Parameterisation of CPR1 protection relays and BLR CM06 PF controller is available from SCMS workstation via MODBUS RTU/TCP Gateway. Recording of control and protection events of the capacitor bank is available to SCMS via volt free signals converted to IEC 61850 communication protocol via BCU/ RTU /I-O box