Академический Документы
Профессиональный Документы
Культура Документы
Transformers are high value equipments Damage may lead to considerable operational losses Normally lead time of transformer procurement is high (6 to 12 months) Transformer failure may lead to damaging of adjoining equipments & infrastructure Transformer damage may cause human injury and/or fatality
Broad Categories
1. Electrical: Electrical protection is implemented by sensing current flowing through it, voltage and frequency Mechanical: Mech. protection is implemented by sensing operational parameters like oil pressure/ level, gas evolved, oil & winding temperature.
2.
Nowadays, Transformer Management Relays are used which take care for all protections.
Protection Philosophy
Conditions
Winding Phase-Phase, Phase-Ground faults Winding inter-turn faults Core insulation failure, shorted laminations Tank faults
Protection Philosophy
Internal Faults Differential (87T), overcurrent (51, 51N) Restricted ground fault protection (87RGF) Differential (87T), Buchholz relay, Differential (87T), Buchholz relay, sudden pressure relay Differential (87T), Buchholz relay and tankground protection External Faults
Overloads Overvoltage Frequency Overfluxing External system short circuits Frequency decay rate
Thermal (49) Overvoltage (59) Over & Under Frequency (81O, 81U) Volts/Hz (24) Time overcurrent (51, 51G), Instantaneous overcurrent (50, 50G) / Phase & Neutral Frequency decay rate (81U-R)
Over Fluxing
Transformer flux: Transformer flux is proportion to voltage and frequency Flux Voltage/frequency While designing transformer, the peak rated value of flux density is kept about 1.6 to 1.8 Tesla Saturation flux density of Core material, Cold Rolled Grain Oriented Silicone Steel (CRGOS) is about 1.9 to 2 Tesla. This corresponds to 1.1 times the rated value Operating any transformer above the rated flux will cause core overheating and severe damage Over-fluxing can be a result of; Overvoltage Low system frequency Over Fluxing Setting Example: The nominal volts per hertz ratio of the system, for 115V VT secondary and 50Hz frequency, is 2.3 V/Hz. Sample protection settings for V/f are: Pick up 1: 2.53 V/Hz; Delay 1: 65sec Pick up 2: 2.76 V/Hz; Delay 2: 8sec
Differential Protection
Differential Protection provides much better overall protection. The basic operating principle of the percent differential element can be described by the following diagram and its associated equations.
I r I restraint max( I1 , I 2 , I 3 ) I d I differential I1 I 2 I 3
%slope Id 100% Ir
Some factors resulting in flow of differential current even under balanced power in & power out conditions are: Magnetization inrush current; Current can be as high as 8 to 30 times the rated current Over Excitation; Concern in generator-transformer units & transmission lines with high capacitance, light load condition CT saturation; Flux beyond certain limit can cause CT saturation Mismatch between CTs Voltage control tap
Percent differential pickup = 0.1 to 0.2; Cannot be zero to allow mismatch due to tap changes Percent differential slope 1 = 20% to 30% Set to ensure sensitivity to internal faults at normal operating current levels, to allow mismatch during tap changing, to accommodate CT mismatch Percent differential knee point = 1xCT Set just above the maximum operating current level of the transformer Percent differential slope 2 = 90% Restraints currents above the knee point; ensures stability under heavy through fault conditions
140%
Irestraint (xCT)
Harmonic Inhibit level: 20% Inhibition of differential protection if the 2nd harmonic of the same phase exceeds the HARMONIC INHIBIT LEVEL set point. ENERGIZATION INHIBIT Instantaneous differential element: 5xCT Differential current above which the unrestrained differential element will pick up.
SETTING: Suppose ground resistance is 400A. For a winding fault point at 5% distance from the neutral we have the following settings Restricted ground fault pick up: 0.1xCT Restricted ground fault slope: 1% Restricted ground fault delay: 0.10sec
pickup
20 A 10% CT 200 A
20 A 1% 1618 A
slope
100
With ambient of 20 C. Hot spot rise of 78 C is design normal. A further rise of 6 C doubles rate of using life.
1.0 98 0.1 80 90 100 110 120 130 140 Hot spot temp. C
Other Protections
Buchholz relay Buchholz relay is a safety device mounted on some oil-filled transformers, equipped with an external overhead oil reservoir called a conservator. The Buchholz Relay is used as a protective device sensitive to the effects of dielectric failure inside the equipment. Whenever there is an internal fault in the transformer such as arcing or excessive heating, the transformer oil is decomposed in different hydrocarbon gases like H2, CO2 and CO. The gases will flow towards conservator and accumulate in the upper part the Buchholz Container which causes fall of oil level in it. This will cause actuation of float switch. Transformers without conservators are usually equipped with sudden pressure relays, which perform a similar function as the Buchholz relay.
Transformer Condition Monitoring ... Contd TRANSFORMER DISSOLVED GAS ANALYSIS (DGA)
DGA Limits and Interpretation
Status Condition1 Condition2 Condition3 Condition4 H2 Min 0 101 701 1801 Max 100 700 1800 0 121 401 1001 CH4 Min Max 120 400 1000 0 66 101 151 C2H6 Min Max 65 100 150 0 51 101 201 C2H4 Min Max 50 100 200 0 36 51 81 C2H2 Min Max 35 50 80 Min 0 351 571 1401 C0 Max 350 570 1400 TDCG Min 0 721 1921 4631 Max 720 1920 4630
Note: CO2 is not included in adding the numbers for analysis because it is not a combustible gas
Operating Procedure
Condition Condition1 Condition2 Condition3 Condition4 Operating Procedure Continue normal operation. Analyze individual gases. Exercise caution. Analyze individual gases to find cause. Determine load dependence. Exercise extreme caution. Analyze individual gases to find cause. Plan outage.Call manufacturer and other consultants for advice. Consider removal from service. Call manufacturer and other consultants for advice.
Gas Interpretation
Abnormal Gas for Cond 3&4 Hydrogen H2 Methane CH4 Ethane C2H6 Ethylene C2H4 Acetylene C2H2 Carbon Monoxide CO Carbon Dioxide CO2>15,000 Interpretation Corona, Arcing Sparking Local overheating Severe overheating Arcing Severe overheating Severe overheating
Thank You!