Академический Документы
Профессиональный Документы
Культура Документы
125REOZT
Diesel
208-480 V
Ratings Range
Standby: Prime: kW kVA kW kVA 60 Hz 92--130 92--163 83--115 83--144
RATINGS: All three-phase units are rated at 0.8 power factor. All single-phase units are rated at 1.0 power factor. Standby Ratings: The standby rating is applicable to varying loads for the duration of a power outage. There is no overload capability for this rating. Prime Power Ratings: At varying load, the number of generator set operating hours is unlimited. A 10% overload capacity is available for one hour in twelve. Ratings are in accordance with ISO-8528-1 and ISO-3046-1. For limited running time and continuous ratings, consult the factory. Obtain technical information bulletin (TIB-101) for ratings guidelines, complete ratings definitions, and site condition derates. The generator set manufacturer reserves the right to change the design or specifications without notice and without any obligation or liability whatsoever. G5-567 (125REOZT) 6/12h
Alternator Specifications
D NEMA-MG21, UTE NF C51.111, VDE 0530, BS 4999, CSA standards compliance for temperature rise and motor starting. D Self-ventilated and dripproof construction. D Vacuum-impregnated windings with fungus-resistant epoxy varnish for dependability and long life. D Superior voltage waveform from a two-thirds pitch stator and skewed rotor.
Specifications Manufacturer Type Exciter type Leads: quantity, type Voltage regulator Insulation: Material Bearing: quantity, type Coupling Voltage regulation, no-load to full-load Direct axis subtransient reactance (Xd), % Alternator Leroy Somer 4-Pole, Rotating-Field Shunt 12, Reconnectable Solid State, R230 NEMA MG1 Class H 1, Sealed Direct 1% 7.9
Application Data
Engine
Engine Specifications Manufacturer Engine model Engine type Cylinder arrangement Displacement, L (cu. in.) Bore and stroke, mm (in.) Compression ratio Piston speed, m/min. (ft./min.) Rated rpm Max. power at rated rpm, kWm (BHP) Valve material: Intake Exhaust Governor type Frequency regulation, no-load to full-load Frequency regulation, steady state Air cleaner type, all models Chromium-Silicon Steel Stainless Steel Electronic ISO 5% 2.5% Dry John Deere 6068HFS82 4-Cycle, Turbocharged 6 Inline 6.8 (415) 106 x 127 (4.2 x 5.0) 19:1 457 (1500) 1800 147 (197)
Engine Electrical
Engine Electrical System Battery charging alternator: Ground (negative/positive) Volts (DC) Starter motor rated voltage (DC) Battery, recommended cold cranking amps (CCA): Quantity, CCA rating each Battery voltage (DC) One, 680 12 Negative 12 12
Fuel
Fuel System Max. fuel flow, Lph (gph) Fuel prime pump Recommended fuel Fuel tank capacity, L (gal.) 89.8 (23.7) Manual #2 Diesel 868 (229)
Lubrication
Lubricating System Type Oil pan capacity, L (qt.) Oil pan capacity with filter, L (qt.) Full Pressure 32 (34) 33 (34.9)
Application Data
Operation Requirements
Fuel Consumption Diesel, Lph (gph) at % load 100% (of the prime rating) 75% (of the prime rating) 50% (of the prime rating) Prime Rating 33.74 29.41 21.76 (8.9) (7.8) (5.7)
Controllers
Decision-Makerr 1000
Standard Features D LCD display panel D User buttons for start, stop, and menu scroll and selection D Emergency stop button D On/off key switch D LED indication for status D Panel-mounted battery fuse D Panel lights LCD Panel Features D Three lines of text and graphic display D Icons for quick identification of system status Functions D View and adjust system operation parameters D View system faults Viewable/Selectable Parameters (may require optional module) D Mode of operation D Battery voltage D Frequency D Time delay countdown D Hourmeter D Engine speed D Fuel level (%) D Coolant temperature D Oil pressure D Voltage: phase, phase-to-neutral, total voltage D Current Viewable Faults D Overspeed D Overcrank D Low fuel level D Coolant temperature D Oil pressure D Battery charger D Frequency meter, ammeter, voltmeter D Emergency stop
KOHLER CO., Kohler, Wisconsin 53044 USA Phone 920-457-4441, Fax 920-459-1646 For the nearest sales and service outlet in the US and Canada, phone 1-800-544-2444 KohlerPower.com
Kohler Power Systems, EMEA Headquarters ZI Senia 122 12, rue des Hauts Flouviers 94517 Thiais Cedex, France Phone (33) 1 41 735500, Fax (33) 1 41 735501
Kohler Power Systems Asia Pacific Headquarters 7 Jurong Pier Road Singapore 619159 Phone (65) 6264-6422, Fax (65) 6264-6455
Distribution Panel
Receptacles
D D D
Two 20-amp 120 V, 1 phase, GFCI duplex Two 50-amp 120/240 V twistlock (shore power) Individual receptacle circuit breakers
Main bus connection studs enclosed behind a lockable access door for easy access and operator safety Strain relief to prevent cables from being pulled free from bus connections
Available Accessories
- Battery Charger, Equalize/Float Type - Bottle Jack - Cable Rack (bolt on) - Fire Extinguisher - Lunette Eye - Remote Start Connections - Spare Tire - Trailer (includes utility tool box)
Note: This drawing is provided for reference only and should not be used for planning installation. Contact your local distributor for more detailed information.
DISTRIBUTED BY:
2008, 2009, 2010, 2012 by Kohler Co. All rights reserved. G5-567 (125REOZT) 6/12h