Вы находитесь на странице: 1из 128

Instructions

95-8470-05

Eagle Quantum Fire and Gas Detection/Releasing System

Detector Electronics Corporation 6901 West 110th Street Minneapolis, Minnesota 55438 USA Tel: 952.941.5665 or 800.765.3473 Fax: 952.829.8750

10/01

95-8470-05

Table of Contents
Section I - System Overview SYSTEM DESCRIPTION .......................................................I-1 SYSTEM FEATURES ............................................................I-2 MAJOR COMPONENT DESCRIPTIONS ..............................I-2 Intelligent Field Devices on Local Operating Network/Signaling Line Circuit (LON/SLC) .......I-2 Local Control Unit (LCU) ..............................................I-2 Local Output Unit (LIOU)..............................................I-3 THEORY OF OPERATION ....................................................I-3 NETWORK OPERATION DURING A FAULT CONDITION...I-3 Multiple Wiring Faults ...................................................I-4 LON/SLC Ground Fault Detection and LCU Protection..............................................................I-4 Field Devices without Power ........................................I-4 Section II - Local Control Unit and Power Supplies OVERVIEW ...........................................................................II-1 Logic Controller ...........................................................II-1 Communication Gateway ............................................II-1 Isolation Module ..........................................................II-1 Optional LCU Versions................................................II-1 EQ2100CG COMMUNICATION GATEWAY ........................II-1 Features ......................................................................II-1 Description ..................................................................II-1 EQ2100LC LOGIC CONTROLLER.......................................II-5 Features ......................................................................II-5 Description ..................................................................II-5 EQ2100IM ISOLATION MODULE ........................................II-7 Features ......................................................................II-7 Description ..................................................................II-7 EQ21XXPS SERIES POWER SUPPLIES AND EQ2100PSM POWER SUPPLY MONITOR .........................II-8 Features ......................................................................II-8 Description ..................................................................II-8 EQ2100PSM ...............................................................II-8 EQ2200IDCGF ............................................................II-8 Section III - Local Output Unit OVERVIEW ..........................................................................III-1 Enclosure ...................................................................III-1 Fault LED and Reset Switch ......................................III-1 RELAY MODULE .................................................................III-1 Features .....................................................................III-1 Description .................................................................III-1 RELEASE MODULE ............................................................III-2 Features .....................................................................III-2 Description .................................................................III-2 SIGNAL AUDIBLE MODULE ...............................................III-3 Features .....................................................................III-3 Description .................................................................III-3 Section IV - Addressable Field Devices EQ2200IDC SERIES INITIATING DEVICE CIRCUIT .........IV-1 Description .................................................................IV-1 EQ2200UV UV FLAME DETECTOR ...................................IV-1 Description .................................................................IV-1 Software Selectable Options .....................................IV-2 EQ2200UVHT (Hi Temp) UV FLAME DETECTOR .............IV-4 Description .................................................................IV-4 EQ2200UVIR FLAME DETECTOR .....................................IV-4 Description .................................................................IV-4 Software Selectable Options .....................................IV-5 EQ2200DCU AND EQ2200DCUEX DIGITAL COMMUNICATION UNIT ...........................................IV-7 Description..................................................................IV-7 EQ2500ARM AGENT RELEASE MODULE .........................IV-9 Description..................................................................IV-9 EQ2500SAM SIGNAL AUDIBLE MODULE........................IV-10 Description................................................................IV-10 EQ2400NE NETWORK EXTENDER .................................IV-10 Description................................................................IV-10 General Application Information ...............................IV-11 Section V - Detector Application Information UV DETECTORS..................................................................V-1 Windows .....................................................................V-1 Obstructions................................................................V-1 Smoke.........................................................................V-1 Arc Welding ................................................................V-1 Common Environmental Conditions ...........................V-1 UV DETECTOR POSITIONING ...........................................V-2 UV/IR DETECTORS .............................................................V-2 False Alarm Sources ..................................................V-2 Factors Inhibiting Detector Response.........................V-3 UV/IR DETECTOR POSITIONING .......................................V-3 GAS DETECTOR POSITIONING .........................................V-3 CATALYTIC GAS SENSORS ...............................................V-4 Catalytic Sensor Operation .........................................V-4 Sensitivity Loss in Catalytic Combustible Gas Sensors ...............................................................V-6 Calibration Gas ...........................................................V-7 Section VI - General Wiring Requirements GENERAL INFORMATION .................................................VI-1 Power Wiring .............................................................VI-1 Network Wiring ..........................................................VI-2 Shield Grounding .......................................................VI-2 Junction Box Grounding ............................................VI-3 RS-485 Link Wiring ....................................................VI-3 Protection Against Moisture Damage ........................VI-3 Electrostatic Discharge ..............................................VI-3 DETERMINING POWER REQUIREMENTS .......................VI-3 EQ2110PS, EQ2130PS AND EQ2175PS .................VI-4 Backup Battery ..........................................................VI-4 Battery Charger .........................................................VI-5

Table of Contents Continued


Section VII System Wiring EQ2100PSM POWER SUPPLY MONITOR USED WITH EQ2110PS, EQ2130PS AND EQ2175PS POWER SUPPLIES............................................................VII-1 Wiring........................................................................VII-1 Startup ......................................................................VII-3 Measuring Battery Voltage and Charging Current ....VII-3 EQ2100LCU SERIES LOCAL CONTROL UNIT ................VII-4 EQ2100LIOU LOCAL OUTPUT UNIT ................................VII-7 Backplane Wiring ......................................................VII-7 RS485 Link Wiring ....................................................VII-7 Power Wiring ............................................................VII-7 RELAY MODULE................................................................VII-8 Wiring........................................................................VII-8 Switch Setting ...........................................................VII-8 RELEASE MODULE ...........................................................VII-9 Wiring........................................................................VII-9 Jumpers ....................................................................VII-9 Switch Setting ...........................................................VII-9 SIGNAL AUDIBLE MODULE ............................................VII-11 Wiring......................................................................VII-11 Jumpers/Switches...................................................VII-11 Address Switch Setting ...........................................VII-11 FIELD DEVICES ...............................................................VII-13 EQ2200IDC Series Initiating Device Circuit ............VII-13 EQ2200IDCGF Series Initiating Device Circuit Ground Fault ...................................................VII-14 EQ2200IDCSC Series Initiating Device Circuit Short Circuit .........................................VII-14 EQ2200UV UV Flame Detector ..............................VII-15 EQ2200UVHT High Temperature UV Detector.......VII-17 EQ2200UVIR UV/IR Flame Detector ......................VII-19 EQ2200DCU Digital Communication Unit used with Det-Tronics H2S/O2 Sensors or other Two-Wire 4 to 20 ma Devices............VII-22 Sensor Separation for DCU with H2S and O2 Sensors .....................................................VII-22 EQ2200DCU Digital Communication Unit used with PointWatch......................................VII-23 EQ2200DCUEX Digital Communication Unit used with Det-Tronics Combustible Gas Sensors...............................VII-24 EQ2500ARM Series Agent Release Module ..........VII-27 EQ2500SAM Series Signal Audible Module ...........VII-29 EQ2400NE Series Network Extender .....................VII-30 TYPICAL APPLICATIONS................................................VII-31 INSTALLATION CHECKLIST ...........................................VII-32 Section VIII Switch Setting GATEWAY .........................................................................VIII-1 LOGIC CONTROLLER ......................................................VIII-3 ISOLATION MODULE .......................................................VIII-3 LON/SLC DEVICE ADDRESS SWITCH SETTING ...........VIII-3 Section IX System Startup PRE-COMMISSIONING CHECKLIST .................................IX-1 STARTUP PROCEDURE ....................................................IX-2 CALIBRATION .....................................................................IX-2 Calibration Algorithm A For Manual Calibration of Universal DCU................................................IX-2 Calibration Algorithm C For Combustible Gas DCUs and Automatic Calibration of Universal DCUs....IX-4 Calibration Algorithm D For Universal DCUs with O2 Sensor...................................................IX-5 Calibration Algorithm G For DCUs with PointWatch ..IX-6 UV DETECTOR TEST .........................................................IX-7 Fire Alarm Test ..........................................................IX-7 False Alarm Test........................................................IX-7 UV/IR DETECTOR TEST ....................................................IX-7 Manual oi...................................................................IX-8 Automatic oi ..............................................................IX-8 Section X Specifications CERTIFICATIONS ................................................................X-1 EQ2100LCU LOCAL CONTROL UNIT.................................X-1 EQ2200IDC/IDCGF/IDCSC INITIATING DEVICE CIRCUIT X-3 EQ2200UV and EQ2200UVHT UV FLAME DETECTORS ..X-3 EQ2200UVIR UV/IR DETECTOR.........................................X-6 EQ2200DCU AND EQ2200DCUEX DIGITAL COMMUNICATION UNIT ......................................X-9 EQ2500ARM AGENT RELEASE MODULE .........................X-9 EQ2500SAM SIGNAL AUDIBLE MODULE ........................X-10 EQ2400NE NETWORK EXTENDER..................................X-10 EQ2100PSM POWER SUPPLY MONITOR .......................X-11 EQ2110PS, EQ2130PS AND EQ2175PS POWER SUPPLIES............................................................X-11 LIOU Local Output Unit.......................................................X-12 LIOU RELAY MODULE ......................................................X-12 LIOU RELEASE MODULE .................................................X-12 LIOU SIGNAL AUDIBLE MODULE ....................................X-12 COMBUSTIBLE GAS SENSOR .........................................X-13 ELECTROCHEMICAL SENSORS......................................X-13 POINTWATCH....................................................................X-13 Section XI System Maintenance ROUTINE MAINTENANCE .................................................XI-1 Manual Check of Output Devices ..............................XI-1 O-Ring Maintenance ..................................................XI-1 Flame Detector Maintenance.....................................XI-1 Gas Sensor Maintenance ..........................................XI-1 Batteries.....................................................................XI-2 TROUBLESHOOTING.........................................................XI-2 REPLACEMENT PARTS .....................................................XI-2 DEVICE REPAIR AND RETURN ........................................XI-3 ORDERING INFORMATION ...............................................XI-3

DET-TRONICS

INSTRUCTIONS

Eagle Quantum Fire and Gas Detection/Releasing System


IMPORTANT Be sure to read and understand the entire instruction manual before installing or operating the Eagle Quantum System. Only qualified personnel should install, maintain or operate the Eagle Quantum System. WARNING The hazardous area must be de-classified prior to removing a junction box cover or opening a detector assembly with power applied. CAUTION 1. The wiring procedures in this manual are intended to ensure proper functioning of the devices under normal conditions. However, because of the many variations in wiring codes and regulations, total compliance to these ordinances cannot be guaranteed. Be certain that all wiring complies with the NEC as well as all local ordinances. If in doubt, consult a qualified official before wiring the system. 2. Some Eagle Quantum devices contain semiconductor devices that are susceptible to damage by electrostatic discharge. An electrostatic charge can build up on the skin and discharge when an object is touched. Always observe the normal precautions for handling electrostatic sensitive devices, i.e. use of a wrist strap (if available) and proper grounding. 3. To prevent unwanted actuation, alarms and extinguishing devices must be secured prior to performing system tests.

Section I System Overview


SYSTEM DESCRIPTION
The Eagle Quantum System serves multiple roles in the monitoring and protection of hazardous areas. It is a fire detection and extinguishing agent release system combined with a hazardous gas monitoring system, integrated on a fault tolerant digital communication network. The Eagle Quantum system utilizes an advanced distributed architecture that is equally adept at monitoring analog process signals like combustible or toxic gas concentrations, and discrete contact closure type devices such as manual fire alarm call boxes and heat detectors, as well as Det-Tronics optical flame detection. This sensor information is then transmitted to the control unit to execute the fire suppression logic, to control agent release, signaling, and annunciation outputs, and to communicate with external operator interface systems for configuration and monitoring.

*oi

is Detector Electronics' Trademark for its patented Optical Integrity Systems, U.S. Patent 3,952,196, United Kingdom Patent 1,534,969, Canada Patent 1,059,598.

Detector Electronics Corporation 2001

10/01

95-8470-05

SYSTEM FEATURES
Deluge and pre-action release capability for fire suppression. Agent release capability for fire suppression. Up to 244 addressable field devices and 32,500 feet (10,000 meters) of wiring on the network. Supports up to 6 network extenders. Compatible with Det-Tronics flame and gas detectors. Accommodates a variety of third-party devices with 4 to 20 ma or dry contact type inputs. Fault tolerant communication loop. Non-volatile memory for alarm and calibration logging. Built in diagnostics. Programmable logic. Modbus RTU Master/Slave and Allen Bradley DF1 communication capability through two electrically isolated RS-232 serial ports. Up to 4 gateways and 4 logic controllers. Up to 75 amperes of alarm current per power supply.

FM Approved to ANSI/NFPA-72-1996 National Fire Alarm Code. See Figure A1 in Appendix A for installation requirements. FM, CSA, CENELEC and CE Mark Certifications. See Appendix A, B and C respectively for details and specific installation requirements.

MAJOR COMPONENT DESCRIPTIONS


The system consists of three basic components (see Figure I-1): INTELLIGENT FIELD DEVICES ON LOCAL OPERATING NETWORK/SIGNALING LINE CIRCUIT (LON/SLC) The LON/SLC is a fault tolerant, two wire, digital communication network, arranged in a loop starting and ending at the Local Control Unit. The LON/SLC supports up to 244 intelligent field devices spread over a distance of up to 32,500 feet (10,000 meters). The LON/SLC serves as the Signaling Line Circuit (SLC) for the fire detection/suppression aspects of the system. LOCAL CONTROL UNIT (LCU) The LCU functions as the heart of the Eagle Quantum system. The LCU contains three replaceable modules
FIRE DETECTION CONTACT CLOSURE DEVICE GAS DETECTION GAS SENSOR OR OTHER 4 TO 20 MA INPUT FIRE/GAS RESPONSE

POWER MONITORS

NETWORK EXTENDERS

FLAME DETECTORS

IDCs

DCUs

AGENT RELEASE MODULES

FIRE SUPRESSION

SIGNAL AUDIBLE MODULES


LON/SLC LON/SLC

VISUAL/ AUDIBLE INDICATORS

LOCAL CONTROL UNIT (LCU)

LOGIC CONTROLLER

GATEWAY

ISOLATION MODULE

OIS

PLC/DCS

AUDIBLE INDICATORS

LOCAL OUTPUT UNIT (LIOU)

VISUAL INDICATORS

FIRE SUPPRESSION
C1899

Figure I1Block Diagram of Eagle Quantum System

I2

that perform all the communication, command, and control functions for the system. It includes all the required operator interface controls for a fire alarm system (silence, acknowledge, reset, isolate), annunciation relays, a local information display, and communication interfaces for computer based configuration and monitoring of the system. LOCAL OUTPUT UNIT (LIOU) The LIOU consists of a rack controlled by the LCU that can hold up to six FenwalNet 2000 modules. These modules allow the control of Notification Appliance Circuits (NACs), fire suppression agent release (CO2, Halon, FM200) using supervised relays, as well as unsupervised relays for other needs.

If a Fire Alarm is detected by a Flame Detector or Initiating Device Circuit (IDC), the affected node will send a special Acknowledged Exception Report (AER) directly to the Logic Controller. The AER is transmitted as soon as an alarm is detected to maximize system performance. When the Logic Controller receives the AER, it sends the originating node a message acknowledging its receipt. If the node originating the AER does not receive an acknowledgement, it will retransmit the AER until it receives an acknowledgement. This exchange of messages is used to ensure that critical messages are received at all appropriate registers throughout the system. Once the Logic Controller receives a Fire Alarm message from a field device, fixed logic will activate built-in annunciation circuits, which consist of both a visible and audible alarm. The programmable logic will execute any specified voting, timing, and/or zone logic and subsequently activate the appropriate output circuits for Notification Appliance Circuits (NACs), agent release circuits, and unsupervised relay outputs. The faceplate of the Logic Controller has two pushbuttons. ACKNOWLEDGE will silence the built in audible alarm and illuminate the Acknowledge LED located on the faceplate next to the Acknowledge pushbutton. SILENCE will silence selected NACs in the field and illuminate the Silence LED located on the faceplate next to the Silence pushbutton. The Logic Controller also features a keyswitch to reset the system after the event is over.

THEORY OF OPERATION
During normal operation, each node on the network monitors its attached sensor or other input, determines if it has an alarm condition, analyzes its own health, checks network integrity, and then packages up this information for transmission to the communication gateway, located in the LCU. This Standard Periodic Report (SPR) contains 16 pieces of discrete information on the status of the node and, where applicable, also contains the analog value of its sensor. At the time of node configuration, the report rate of the SPR can be set to anywhere between 1 and 10 seconds. In the LCU the Communication Gateway collects all of the incoming SPRs from the field devices and puts the information into datatables. Datatables are organized areas of memory in the gateway that can be read by external host devices using one of the gateways serial ports. If any of the SPRs indicate an out of tolerance condition, the gateway will display this information on its integrated faceplate display. The gateway also has four programmable relays whose action can be programmed to events in the SPRs of the monitored nodes. In addition to SPRs, nodes used as a part of the fire detection and suppression system, such as fire detectors or Initiating Device Circuits (IDCs) interfaced with heat detectors, manual call points, etc. send a separate Standard Supervisory Report (SSR) to the Logic Controller, located in the Local Control Unit. The Logic Controller, which manages the fire suppression logic, uses these SSR messages to verify that the nodes used in the fire alarm and suppression logic are active and able to communicate. If the Logic Controller does not receive SSRs from a required node, it will annunciate a trouble condition.

NETWORK OPERATION DURING A FAULT CONDITION


The Eagle Quantum system utilizes a unique patented technique for detecting problems in the communication network wiring. This state-of-the-art feature minimizes the possibility of a communication breakdown in the event of a wiring fault in the communication loop and can also serve as an aid in troubleshooting. The communication network is constructed as a loop that starts and ends at a pair of communication ports located at the LCU. The nodes communicate with the LCU over the LON/SLC as shown in Figure I-2. Each field device node contains both the hardware and software necessary to isolate and re-route communication in the event of a network wiring fault. When a problem occurs somewhere within the network wiring, the communication gateway located in the LCU annunciates the fault, while the fault isolation circuitry in the affected nodes isolates the section of the network where the fault has occurred. Communication is

I3

95-8470

thereby ensured and will continue over the network. See Figure I-3. A single open or short on the LON/SLC will not affect system communication between the field devices and the gateway. System communication will continue until the wiring problem can be repaired. MULTIPLE WIRING FAULTS In the event of multiple wiring faults on the LON/SLC, the nodes between the faults will continue to function, but the faults will prevent them from communicating with the gateway. See Figure I-4. In this example, nodes 1 to 4 communicate using one gateway port (path A) and nodes 7 and 8 use the other gateway port (path B). Nodes 5 and 6 are unable to report to the gateway because they are isolated by the two wiring faults. LON/SLC GROUND FAULT DETECTION AND LCU PROTECTION The LCU contains an isolation module that checks the LON/SLC for ground faults. Should a ground fault be detected, it is indicated by an LED on the isolation modules faceplate. The isolation module also ensures communication with the field devices even if there is a LON/SLC short circuit directly adjacent to the LCU. FIELD DEVICES WITHOUT POWER All Eagle Quantum field devices are designed so that a pass-through circuit is created for the network wiring on a loss of power to the node. This ensures network integrity even when a node is down for service or has been damaged. The Communication Gateway in the LCU will report powered-down nodes as notcommunicating. IMPORTANT Since it is impossible to predict where a network fault might occur or exactly what effect it will have on actual system operation, it is important to diagnose and repair any fault as soon as possible after it is detected to ensure reliable system operation.

NODE 4 NODE 3

NODE 5 NODE 6

NODE 2

NODE 7

NODE 1

LCU

NODE 8
A1851

Figure I2Normal Communication over the Digital Highway

WIRING FAULT NODE 4 NODE 3 NODE 5 NODE 6

NODE 2

PATH A

PATH B

NODE 7

NODE 1

LCU

NODE 8
A1852

Figure I3Communication with a Single Wiring Fault on the Network

WIRING FAULTS NODE 4 NODE 3 NODE 5 NODE 6

NODE 2

PATH A

PATH B

NODE 7

NODE 1

LCU

NODE 8
A1853

Figure I4Communication with Multiple Wiring Faults on the Network

I4

Section II Local Control Unit (LCU) and Power Supplies


OVERVIEW
The Local Control Unit (LCU) is the heart of the Eagle Quantum system. External host devices such as PLCs or DCSs interface through the LCU, the fire detection and releasing logic resides in the LCU, control of the releasing, signaling, and annunciation outputs are handled by the LCU, and the Local Operating Network/Signaling Line Circuit (LON/SLC), through which all field devices communicate, starts and ends its loop at the LCU. Physically, the LCU consists of a three slot rack style enclosure that houses the Communication Gateway, Logic Controller, and Isolation Module. These three modules plug into the backplane and are secured with thumb screws. All external wiring is routed through conduit entries at the bottom and sides of the unit. The wiring terminals are protected by a removable cover. The LCU can be installed in Class I, Division 2 hazardous locations. Refer to Appendix A (FMRC) and Appendix B (CSA) for details. LOGIC CONTROLLER The Eagle Quantum Logic Controller uses seven microprocessors and parallel processing techniques to execute the logic used for fire suppression. Its wealth of logical operators allow for the easy development of nearly any imaginable type of cross-zone monitoring, voting, and timed operations that might be needed in a fire suppression system. The Logic Controller supports ANSI/NFPA 72 Class A, Style 7 communication with field devices. COMMUNICATION GATEWAY The Eagle Quantum Communication Gateway communicates through two serial links for configuration and monitoring. This allows for device configuration using a comprehensive set of Det-Tronics authored software tools. The monitoring is provided to the Operator Interface Station(s) (OIS) through Modbus or Allen-Bradley compatible protocols. The gateway also provides four programmable relays that can be used to annunciate conditions being monitored by the devices on the LON/SLC. ISOLATION MODULE The Isolation Module protects the integrity of the LON/SLC wiring by isolating shorts and monitoring for ground faults. It also provides electrical isolation for the two serial communication ports between the gateway and host devices.
II1

OPTIONAL LCU VERSIONS An optional EQ2101LCU is available with provisions for two 24 vdc power inputs. Two reliable and independent 24 vdc supplies, in accordance with ANSI/NFPA 72 section 1-5.2, must be supplied. If either of the supplies is missing or a wiring problem occurs, a trouble condition will be annunciated. Logic controllers can be added to the communication network to segment it into logical groups. Up to four logic controllers can be used on each network. Auxiliary gateways can be added to provide additional relays or serial port connections to PLCs or DCSs. Up to three auxiliary gateways can be added to the Quantum network. Gateways located outside the LCU can be turned off without disrupting LON/SLC communication with the LCU.

EQ2100CG COMMUNICATION GATEWAY


FEATURES Utilizes Modbus or Allen Bradley protocols Transformer isolation of network ports Four programmable relay outputs Three digit display and bar graph LEDs indicate relay status EMI/RFI hardened

DESCRIPTION The Eagle Quantum Communication Gateway is used in conjunction with Det-Tronics software to configure the system as well as to provide information on an ongoing basis to external systems such as PLCs and DCSs. It also provides local display and four programmable relay outputs. In addition, the gateway provides a heartbeat signal used to test for LON/SLC integrity, to provide time and date information to field devices, and to monitor for the continued presence of all configured field devices. The gateway receives and stores the current status and process variable information from all devices on the Local Operating Network/Signaling Line Circuit (LON/SLC) communication loop. It services all valid requests by Modbus RTU masters and/or Allen-Bradley DF1 masters that are received through its two host interface serial ports. When acting as a Modbus RTU master, the gateway will automatically transfer key process variable and status information to a default or user selected Modbus RTU slave address and register offset.
95-8470

DET-TRONICS

DEVICE ADDRESS
DIGITAL DISPLAY BAR GRAPH DISPLAY

RELAY 1 RELAY 1 LED RELAY 2 RELAY 2 LED RELAY 3 RELAY 3 LED RESET PUSHBUTTON RELAY 4

100 90 80 70 60 50 40 30 20 10 RELAY 4 LED FAULT LED

All three digits are on and the decimal point for each digit is also on. Up to 250 addresses are available (displayed 0.0.1. to 2.5.0.). DEVICE IDENTIFICATION CODE See Table II-1 for device identification codes. DEVICE PERCENT FULL SCALE/FAULT CODE/CALIBRATE The display follows the sensor input in percent of full scale up to 100% full scale. A negative sign is used to indicate a negative zero drift condition. See Table II-2 for the status codes used by the gateway display. A fault condition is indicated as FXX, with F indicating that a fault has occurred and XX identifying the type of fault that is detected. If a detector is being calibrated, the display will show CAL. BAR GRAPH The 20 segment bar graph tracks the input signal from the sensor, providing a 0 to 100% full scale reading of sensor input.
Table II1Device Identification Codes used by Gateway Digital Display

FAULT RESET EAGLE QUANTUM GATEWAY

B1884

Figure II1Gateway Faceplate

During normal operation the gateway produces a periodic (250 millisecond) heartbeat signal on the network, which is used by all field devices as a part of their network fault isolation routine. Every fourth heartbeat (1 second intervals) also includes a time and date message that is used by the field devices for logging calibration, alarm, and other events. The gateway has sufficient non-volatile memory to store configuration data for all networked field devices, which is downloaded to the gateway from the OIS. Faceplate Description The faceplate provides four relay LEDs and one fault LED, a digital display, a bar graph, and a reset pushbutton. See Figure II-1. DIGITAL DISPLAY The digital display is a three digit seven segment display. During normal operating conditions, the display indicates 000. When a system event occurs (alarm, fault or calibration) the display sequentially shows the device address, followed by device identification code, followed by device percent full scale/fault code/calibrate signal. Each indication is shown for 3/4 second, followed by a 1/4 second delay before going to the next indication. If more than one event should occur, the entire display (digital display and bar graph) will track the status of each address where activity is occurring by sequencing through each event by order of address.
II2

DISPLAY READING

DEVICE Gateway

IDC

UV Detector

UV/IR Detector Logic Controller

DCU

ARM SAM

Power Supply Monitor

T0026B

Table II2Status Codes used by Gateway Digital Display

Gateway

F10 F20 F30 F32 F40 F50 F51 F60 ALA Bytes F10 F11 F13 F14 F20 F60 A10 A01 A11 F10 F11 F13 F14 F20 F60 A10 A01 A11 F10 F11 F13 F14 F20 F60 A10 A01 A11 F10 F11 F12 F13 F20 F60 cps F10 F11 F20 F60 cps* * Can be F10 F17 F20 F60 ALA Bytes F10 F11 F20 F60 CAL nnn Sol F10 F11 F12 F20 F21 F60

Gateway Fault Not Communicating LON Fault Right Heartbeat Fault (Net Test Fault) Stuck Reset Switch Upper Transceiver Fault Lower Transceiver Fault Invalid Configuration or Unable to Configure Output Relay Active Bytes Remaining for Non-volatile Memory Write Fault Low Voltage Fault Input 1 Open Input 2 Open Not Communicating, Com 1 or Com 2 fault Invalid Configuration or Unable to Configure Input 1 is Active Input 2 is Active Both Inputs are Active Fault Low Voltage Fault Input 1 Open or Short Input 2 Open or Short Not Communicating, Com 1 or Com 2 fault Invalid Configuration or Unable to Configure Input 1 is Active Input 2 is Active Both Inputs are Active Fault Low Voltage Fault Ground Fault Input Open Not Communicating, Com 1 or Com 2 fault Invalid Configuration or Unable to Configure Ground Fault + Input is Active Input Active and Ground Fault + Fault Low Voltage Fault oi Fault 290 Volt Fault Not Communicating, Com 1 or Com 2 fault Invalid Configuration or Unable to Configure Counts Per Second, Displayed During Alarm and Pre-Alarm Fault Low Voltage Fault Not Communicating, Com 1 or Com 2 fault Invalid Configuration or Unable to Configure Counts Per Second, Displayed During Alarm either UV counts or IR counts, depending on the mode selected at the OIS. Trouble Ground fault Not Communicating, Upper Transceiver Fault or Lower Transceiver Fault Invalid Configuration or Unable to Configure Alarm Bytes Remaining for Non-volatile Memory Write Sensor Fault or Calibration Fault Low Voltage Fault Not Communicating, Com 1 or Com 2 fault Unconfigured, Invalid Configuration or Unable to Configure Calibration in Progress Process variable displayed as a % of the Calibrated Full Scale Reading Release display code Open Output Low Voltage Fault Low Auxiliary Voltage Fault Not Communicating, Com 1 or Com 2 fault Network Variable Input Fault Invalid Configuration or Unable to Configure
II3 95-8470

IDC

IDCSC

IDCGF

UV Detector

UV/IR Detector

Logic Controller

DCU

ARM

SAM

Table II2Status Codes used by Gateway Digital Display (Continued) Aud Signal Audible display code F11 Low Voltage Fault F12 Low Auxiliary Voltage Fault F13 Open/Short on Circuit 1 F14 Open/Short on Circuit 2 F20 Not Communicating, Com 1 or Com 2 fault F21 Network Variable Input Fault F60 Invalid Configuration or Unable to Configure

Power Supply Monitor

PS F10 F11 F12 F13 F14 F20 F60

Power Monitor display code AC Failed Low Voltage Fault Battery Fault Ground Fault Power Supply Fault Not Communicating, Com 1 or Com 2 Fault Invalid Configuration or Unable to Configure

The bar graph indicates 0 to 100% full scale, which corresponds to the 4 to 20 ma signal for all gas sensors except oxygen. The 4 to 20 ma signal from an oxygen sensor corresponds to 0 to 25% oxygen. Sensor output (measured in counts per second) is displayed for UV and UV/IR detectors. LEDS Five faceplate LEDs are provided for indicating the status of the gateway relays. When a relay is reset, the corresponding LED is also reset. RELAYS The communication gateway is provided with five relays. Four of the relays are general purpose relays. The fifth relay functions as a fault relay, responding only to gateway or LON network faults. The relays have form C contacts rated 5 amperes resistive at 30 vdc. The specific function of the four general purpose relays is programmable through Det-Tronics software. The relays are selectable for latching or non-latching operation and can be configured for normally energized or de-energized operation. CAUTION When the relays are used as gas alarm outputs in the non-latching mode, they must be connected to another device that will perform the latching function. RESET PUSHBUTTON The programmable relays can be reset by pressing the reset pushbutton or external reset (resetting all latching relays) or by a command from the EagleVision NT software (resetting individual relays). The reset function resets the relay, regardless of the status of the initiating device. This allows additional events to trigger the same relay, even though the first device may still be in a triggering mode.
II4

Automatic Diagnostics The gateway features self-testing circuitry that continuously checks for problems that could prevent proper system response. The gateway performs three forms of diagnostics: self-diagnostics, LON/SLC diagnostics, and device diagnostics. Self-diagnostic tests monitor the condition of the gateway. LON/SLC diagnostics check for shorts and opens in the LON/SLC wiring. In the event of a problem, the fault is annunciated in the gateway status word and the gateway fault relay is activated. For device diagnostics, the gateway provides a watchdog timer for each configured device on the loop. Each time the device reports to the gateway, the timer accumulator is reset to zero and the timer starts over. If a device does not respond before its watchdog timer expires, the gateway sets the not communicating bit in the status word for that device. Fault Tolerant Communication Fault tolerance is provided by constructing the LON/SLC as a loop that starts and ends at a pair of network communication ports on the gateway. If a fault occurs somewhere in the network wiring, fault isolation circuitry in the communication modules isolates the problem section of the network. When the gateway detects the fault, it is immediately annunciated. The gateway then reconfigures the network so data can be transmitted to all devices. This feature minimizes the possibility of a communication breakdown in the event of an open or short in the communication loop. A single open or short on the LON/SLC will not affect system communication performance. In the event of multiple opens or shorts, only those detectors between the opens and shorts will not be able to communicate with the LCU, even though they will continue to function.

DET-TRONICS
POWER ALARM TROUBLE POWER FAULT SUPERVISORY

The logic controller receives configuration information through the gateway by means of its serial connection to the operator interface system. Faceplate Description The faceplate has a key switch, two pushbutton switches, and nine LEDs. See Figure II-2. KEY SWITCH The key switch on the front panel of the logic controller is used to select from four operating modes Normal, Acknowledge & Silence Enable, Reset or Isolate. The key may be removed in the Normal or Isolate position. NOTE Always rotate the key switch slowly when selecting operating modes. Normal

ACKNOWLEGDE PUSHBUTTON SWITCHES SILENCE PROGRAM ISOLATE

EAGLE QUANTUM LOGIC CONTROLLER


NORMAL ACKNOWLEDGE & SILENCE ENABLE

KEY SWITCH

RESET ISOLATE

C1854

Figure II2Logic Controller Faceplate

In the normal mode, the controllers program is running and the outputs are enabled. Acknowledge & Silence Enable This mode enables the Acknowledge and Silence pushbuttons. NOTE The Acknowledge and Silence pushbuttons are inhibited when the key switch is in the Normal position. Reset

EQ2100LC LOGIC CONTROLLER


FEATURES Programmable logic LEDs indicate status conditions Alarm, Trouble and Supervisory SPDT relays EMI/RFI hardened

DESCRIPTION The logic controller provides the control function for the fire detection portion of the Eagle Quantum fire and gas safety system. It monitors messages from the devices on the loop that are configured to report to that controller (up to 120 in combination) and generates the appropriate output(s) in response to the input conditions. The logic controller supports ANSI/NFPA 72 Class A, Style 7 communication with the field devices. The logic controller uses fixed logic to control the faceplate display and onboard alarm, trouble and supervisory outputs per ANSI/NFPA 72. The logic controller also has programmable logic, which allows it to be customized to perform complex logic operations including voting and timing. It also communicates with the output modules located in the LIOU, controlling system functions such as alarm signaling, agent release and relay actuation. In the reset mode, normal operation is inhibited and a reset signal is sent to the LIOU and field output devices. This mode is also used for programming. In the program mode, normal operation is inhibited. This is the only mode that allows configuration information to be downloaded to the logic controller from the gateway. When the program mode is exited, configuration information is sent to the LIOU. NOTE If the key switch is left in the RESET position for more than a second or if the logic controller is in the Program mode, a Trouble condition will be indicated.

II5

95-8470

Isolate In the isolate mode, normal operation continues while the logic controller sends an isolate command to all the agent release outputs in the LIOU. The Isolate LED turns on in a steady state if all release outputs are isolated. The LED is off when none of the outputs are isolated and blinks if only some of the outputs are isolated. NOTE User logic is required to isolate LON based agent release modules. PUSHBUTTON SWITCHES Acknowledge Pressing the acknowledge pushbutton with Acknowledge/Silence enabled acknowledges the current status condition(s) and turns off the internal buzzer. Silence Pressing the silence pushbutton silences the selected signaling outputs in the LIOU. (The specific LIOU outputs that are affected by the silence button are selected at the time of system configuration.) NOTE Signaling devices connected to LON based Signal Audible Modules must be silenced via user logic. LEDS Nine faceplate LEDs are provided for indicating system status conditions. POWER (Green) Indicates that power is applied to the device. ALARM (Red) Indicates that the Fire Alarm relay is actuated. TROUBLE (Yellow) Illuminated when a trouble condition occurs in the wiring or devices associated with the fire system. (Trouble relay is active). All logic controller faults are latching and must be cleared by resetting with the key switch. Det-Tronics configuration software should be used to determine the specific problem.

POWER FAULT (Yellow) Indicates that a power supply fault has been detected. This could involve any of the following: ground fault low or missing AC input voltage 24 vdc power supply battery related fault power supply monitor IDCGF.

SUPERVISORY (Yellow) Follows the status of the Supervisory relay. ACKNOWLEDGE (Yellow) Illuminated when the acknowledge switch is pressed and remains lit until the unit is reset. SILENCE (Yellow) Illuminated when the silence switch is pressed and remains on until the unit is reset. PROGRAM (Yellow) Indicates that the logic controller is in the Reset/Program mode. ISOLATE (Yellow) Indicates that the logic controller is in the Isolate mode. Relays The Logic Controller has three relay outputs, responding to the following status conditions: Fire alarm (Activated when any device that is configured as a fire alarm input is active. This includes all flame detectors and IDCs that are configured as alarm type inputs.) Supervisory (Activated when a supervisory fault occurs at any LON device that is configured to report to the Logic Controller as a supervisory input.) Trouble (Normally energized). Activated when any of the following occurs: LIOU communication, wiring or other fault AC input failure Battery fault Power supply fault Invalid configuration LON fault LON device communication fault Gateway LON fault RAM fault.
II6

EQ2100IM ISOLATION MODULE


0.5 SEC 0.5 SEC 1.5 SEC

FEATURES
ALARM

Ground fault detection RS-232 isolation for data rates up to 19.2 Kbaud

0.5 SEC 5.0 SEC TROUBLE 0.1 SEC 0.1 SEC

LEDs indicate status conditions EMI/RFI hardened DESCRIPTION

2.0 SEC SUPERVISORY


A1855

Figure II3Tone Pattern for Logic Controller Buzzer

The Eagle Quantum Isolation Module (LON Isolator) protects the integrity of the communication network wiring by isolating shorts and monitoring for ground faults. The Isolation Module also provides electrical isolation for the two serial communication ports between the gateway and host devices. Visual Indicators LEDs on the front panel are provided for indicating status conditions. See Figure II-4 for LED locations and Table II-3A and II-3B for possible fault conditions.

The relays latch until the Logic Controller is reset. The relays have SPDT (Form C) contacts, rated 5 amperes resistive at 30 vdc. Terminals are provided on the LCU backplane for connecting EOL resistors. Buzzer The Logic Controller is furnished with an internal buzzer for signaling a change in status. The buzzer has four modes of operation: Off Alarm Trouble Supervisory.

DET-TRONICS
LON ISOLATOR

In the normal mode with no events occurring, the buzzer is off. If an alarm, trouble or supervisory event occurs, the appropriate tone is generated. In the event of multiple events, the order of priority is alarm, supervisory, then trouble. Refer to Figure II-3 for the tone patterns that identify each type of event. The buzzer can be silenced by pressing the ACKNOWLEDGE switch on the front panel (the key switch must be in the Acknowledge & Silence Enable position). If a second event occurs or if the original event stops and then returns, the buzzer will again turn on. NOTE If a trouble condition has been acknowledged and the condition exists for more than 24 hours, the buzzer will again sound.

GROUND FAULT POWER + POWER

GROUND FAULT COM 1 COM 2

EAGLE QUANTUM LON ISOLATOR

B1856

Figure II4Isolation Module Faceplate

II7

95-8470

Table II-3APower Supply Ground Fault

Power + ground fault occurs if: - Resistance of Power + to earth is <136K ohms. - DC voltage is below +19.0 vdc (with 26 vdc supply voltage). - Current >0.14 ma between + wire and earth. Power ground fault occurs if: - Resistance of Power to earth is <15K ohms. - DC voltage is below 4.9 vdc (with 26 vdc supply voltage). - Current >0.1 ma between wire and earth.
Table II-3BLON Ground Fault

resides on the communication loop (LON), any trouble condition related to system power will immediately be reported through the Local Control Unit. Status conditions being monitored include power supply failure, loss of AC power, loss of battery power, power ground fault, AC voltage, DC voltage and battery charging current levels. The output of the power supply monitor is a status message that is sent along the communication loop to the gateway and logic controller in the Local Control Unit (LCU). System response to the message is determined at the time of configuration. The power supply monitor supports ANSI/NFPA 72 Class A, Style 7 communication with the LCU. Enclosure The power supply monitor must be located in a controlled non-hazardous area and must be mounted in a suitable metallic nationally recognized test laboratory (NRTL) labeled NEMA rated enclosure. Fault Tolerant Network

COM 1 / COM 2 ground fault occurs if: - LON B wire resistance to earth is <4K ohms. - LON B wire DC voltage is below 4.0 vdc. - Current >1.0 ma between LON B wire and earth. OR - LON A wire resistance to earth is <2K ohms. - LON A wire DC voltage is below +2.0 vdc. - Current >1.0 ma between LON A wire and earth.
Note: Voltages are nominal and may vary slightly (voltages referenced to earth). Resistance/voltage levels between sides are different same readings indicate they are shorted together.

EQ21XXPS SERIES POWER SUPPLIES AND EQ2100PSM POWER SUPPLY MONITOR


FEATURES Monitors primary AC supply and battery integrity. Power supplies available with 10, 30 or 75 ampere output. Field addressable. Unique patented fault isolation. Utilizes state-of-the-art communication technology. Pass through communication circuitry on power loss. EMI hardened. FMRC approved and CSA certified for use in Eagle Quantum systems. DESCRIPTION These power supplies are available with 10, 30 or 75 ampere outputs. Input voltage is selectable for 120, 208 or 240 vac. Refer to Section X or Table VI-5 (Section VI) for power supply specifications. EQ2100PSM The EQ2100PSM Power Supply Monitor is used in conjunction with an EQ21xxPS power supply and backup batteries to provide power for the Eagle Quantum system. Since the power supply monitor

Like other Eagle Quantum network devices, the power supply monitor utilizes a unique patented technique for detecting network wiring problems. This feature minimizes the possibility of a communication breakdown in the event of a wiring fault and can also serve as an aid in troubleshooting. A single open or short on the network will not affect system communication between the field devices and the LCU. System communication will continue until the wiring problem can be repaired. Status LEDs The power supply monitor has three LEDs to provide a visual indication of status conditions: Green Red Yellow On when power is applied to the device. On (flashing) indicates a trouble condition. Used for factory diagnostic purposes.

EQ2200IDCGF The available EQ2200IDCGF Initiating Device Circuit Ground Fault Monitor responds to the presence of a ground fault within the power circuitry of the Eagle Quantum system. It provides a supervised dry contact input and ground fault monitoring circuitry for indicating a power supply trouble condition. It is intended for use with a third party power supply.

II8

Section III EQ2100LIOU Local Output Unit


OVERVIEW
The Local Output Unit (LIOU) consists of a six position card rack. Available modules include: Relay Module four independently programmable unsupervised relay contacts. Release Module one release circuit and three signaling circuits. Signal Audible Module four independently programmable signaling circuits. These modules can be installed in the rack in any position. The Local Control Unit (LCU) automatically reads the output modules type and address on powerup. It is recommended that modules performing like functions be inserted adjacent to each other to facilitate identification and field wiring runs. The assembly is controlled and supervised by the local control unit (using an RS-485 serial communication link) and must be mounted nearby (less than 20 feet). Up to four LIOUs can be controlled by the LCU, adding a maximum of 24 output modules to the system. When multiple LIOUs are used, the last one in the chain must be no more than 20 cable feet from the LCU. NOTE Input modules are not currently available for the LIOU. ENCLOSURE The LIOU must be located in a controlled nonhazardous area and must be mounted in a suitable metallic nationally recognized test laboratory (NRTL) labeled NEMA rated enclosure. FAULT LED AND RESET SWITCH Each card in the LIOU is furnished with a yellow fault LED and a Reset switch. During Normal operation, the LED is off. The yellow LED turns on when the Reset button is pressed or a fault occurs. Pressing the Reset button resets the microprocessor on the card, causing it to re-initialize. At this time, the Trouble light on the LCU is also turned on. If the Reset button is pressed with an output energized, the output is de-energized until the event that triggered the output re-occurs. (Outputs are event driven.)

The yellow LED also turns on if: An output fault occurs (signal audible and agent release modules only). The LED is reset automatically when the fault clears. A microprocessor fault occurs. The card is not configured. A loss of communication with the LCU occurs (RS485). If an output is on during a loss of communication, the output will remain in the current state and can only be reset using the reset switch on the Logic Controller.

RELAY MODULE
FEATURES Four independently programmable relays SPDT dry contacts Supervised module DESCRIPTION The relay module is a convenient and economical means of providing unsupervised output capability for the Eagle Quantum System. The module is located in the LIOU and provides four independently programmable relays for control of auxiliary functions such as fan shutdown and damper control. Each relay has SPDT contacts, rated 2 amperes at 30 vdc. The connection of the relay module to the system is supervised by the LCU. In the event of module removal, the system will display a trouble condition at the LCU. The relay module is housed and secured in the LIOU. A maximum of 8 relay modules can be installed in the system. NOTE It is not recommended to configure relay outputs as Normally Energized/Open on Alarm.

III-1

95-8470

RELEASE MODULE
FEATURES One programmable releasing output Three independently programmable signal circuit outputs (style Y wiring) FM200, FE-13, CO2, Halon, water mist, dry and wet chemical compatible, deluge and pre-action Programmable for initiators or solenoid type releasing devices for 90 sec., 10 min., 15 min., continuous. DESCRIPTION The release module is a convenient and economical means of providing signaling and agent release capability for the Eagle Quantum System. The release module is located in the LIOU and provides one programmable release circuit and three Style Y signaling circuits. The release circuit is compatible with all solenoid or initiator based Fenwal suppression systems. Used in conjunction with the Eagle Quantums programmable logic, each release circuit can be programmed for Single, Cross or Counting Zone Style initiation. Optional time delay, abort and manual release sequences allow the output to be programmed for use in unique applications.

Each signal circuit delivers up to 2 amperes at 24 vdc enough to meet the power requirements of todays ADA/UL 1971 Signaling Appliances. The three signal outputs are individually programmable to allow signaling of each phase of the release sequence. The agent release output circuit is rated for 24 vdc control devices. Each release output can supervise and activate up to two solenoid control heads. Tables III-1 and III-2 identify the devices that can be controlled by the releasing output. Refer to Section VII for specific wiring information. Each circuit on the release module is furnished with a self-restoring fuse to provide protection from short circuit conditions. The three signaling circuits are supervised for open and short circuit conditions. The release circuit is supervised for open circuit conditions. If a trouble condition occurs, it will be indicated at the LCU. The connection of the release module to the system is supervised by the LCU. In the event of module removal, the system will display a trouble condition at the LCU. The release module is housed and secured in the LIOU. A maximum of 8 release modules can be installed in the system.

Table III1Solenoid Compatibility with Release Module for Releasing Applications

Table III-2Solenoid Compatibility with Release Module for Deluge and Pre-Action Applications

Solenoids Fenwal part no. Fenwal part no. Fenwal part no. Fenwal part no. Fenwal part no. Fenwal part no. 486500-001 890181 897494 899175 895630-000 31-199932-004 Manufacturer Skinner ASCO ASCO Skinner Skinner Skinner Model LV2LBX25 8210A107 8210G207 73218BN4UNLVNOC111C2 73212BN4TNLVNOC322C2 71395SN2ENJ1NOH111C2
T0037B

III-2

SIGNAL AUDIBLE MODULE


FEATURES Four independently programmable indicating circuits NFPA Style Y or Z wiring 24 vdc power limited outputs Self-restoring output design Four optional coded outputs per circuit. DESCRIPTION The signal audible module provides four indicating circuits for controlling UL Listed 24 vdc polarized audible/visual indicating appliances. Each output circuit is independently programmable to allow annunciation of separate events. The outputs are UL Listed for power limited applications. The advanced circuitry design uses resettable fuses, eliminating the need to replace modules or components if the circuits are shorted or overloaded. As a result, downtime and maintenance costs are reduced. The signal audible module can support four NFPA Style Y or two Style Z field wiring circuits. Each output circuit is supervised for open and short circuit conditions. The outputs operate in the reverse polarity fashion when activated. Each output delivers up to 2 amperes at 24 vdc enough to meet the power requirements of todays ADA/UL 1971 signaling appliances.

The Signal Audible Module is located in the LIOU and is supervised by the LCU. In the event of module removal, the system displays a trouble condition at the LCU. The Eagle Quantum system supports up to eight signal audible modules, providing a maximum of 32 signal outputs per system. Each module provides auxiliary input terminals for additional 24 vdc signaling power where required. All four module outputs are synchronized for accurate activation of visual signaling appliances. The signal outputs are programmable for activation by the Eagle Quantums Logic Controller. Time delay and stepped signaling functions can also be accommodated. In release applications, signal outputs can be programmed to provide pre-release, release and post-release signaling. Each circuit is individually programmable for any one of the following coded outputs: 1. 2. 3. 4. Continuous sounding 60 Beats per minute 120 Beats per minute Temporal pattern.

The signal audible module is housed and secured in the LIOU. A maximum of eight signal audible modules can be installed in the system.

III-3

95-8470

Section IV Addressable Field Devices


EQ2200IDC SERIES INITIATING DEVICE CIRCUIT (IDC)
DESCRIPTION Three IDC models are available: The EQ2200IDC allows discrete inputs from smoke/heat detectors, manual call stations or other contact devices. The EQ2200IDCGF Initiating Device Circuit Ground Fault Monitor responds to the presence of a ground fault within the power circuitry of the Eagle Quantum system. It provides a supervised dry contact input and ground fault monitoring circuitry for indicating a power supply trouble condition. It is intended for use with a third party power supply. The EQ2200IDCSC Initiating Device Circuit Short Circuit (IDCSC) provides two supervised digital inputs for monitoring the system for shorts circuits. The IDCSC supports ANSI/NFPA 72 Class B Style C (3 state, open/short circuit) supervised input circuits. Inputs Each IDC accepts two dry contact inputs for use with devices such as relays, pushbuttons, key switches, etc. The IDC supports ANSI/NFPA 72 Class B Style B supervised input circuits (Class B Style C for IDCSC). Each circuit requires its own end of line (EOL) resistor for monitoring circuit continuity. Nominal resistance of the resistor is 10 k ohms. Inputs are software selectable in EagleVision NT to actuate the alarm, trouble, or supervisory relays on the LCU. Outputs The output of the device is a status message that is sent to the gateway and logic controller in the Local Control Unit along the LON/SLC. System response to the message is determined at the time of configuration. The IDC supports ANSI/NFPA 72 Class A, Style 7 communication with the LCU. A Standard Periodic Report (SPR) is sent to the gateway at the rate determined at the time of configuration. When programmed for response to a fire alarm condition, a special Acknowledged Exception Report (AER) is immediately sent to the Logic Controller.

Addressability Device identification is accomplished by setting switches on an eight position DIP switch (valid address range is 5 to 250). Status LEDs Three LEDs are located at the center of the communication module circuit board and are visible when the cover is removed. The green LED serves as a power-on indicator and is the only LED illuminated during normal operation (no faults or alarms occurring). The red LED is used to indicate an alarm or fault condition. The flashing rate of the red LED indicates the following conditions: On steady = Blinking = one of the inputs is active fault condition such as an open input circuit or not configured.

The amber LED is provided for factory diagnostic purposes and is not used by the customer. Illumination of the amber LED normally indicates a failure in the communication chip. Replacement of the communication module circuit board is required. Alarm Log The module tracks when either of its input circuits are activated and will store these changes in non-volatile memory. The time, date, and circuit number is stored for the last eight events. Enclosure The explosion-proof, water-tight NEMA/Type 4X enclosure is designed for use in a variety of hazardous locations.

EQ2200UV UV FLAME DETECTOR


DESCRIPTION The EQ2200UV Series UV Flame Detector contains a UV sensor module and control circuitry in an explosionproof, watertight enclosure. The detector is equipped with both automatic and manual optical integrity (oi) test capability. Detector status is indicated by red LEDs visible through the detectors viewing window. Table IV-1 indicates the condition of the LEDs for each detector status.

IV-1

95-8470

Table IV1EQ2200UV Detector Status/Indications

Status Normal with automatic oi selected Normal with manual oi selected Fault (General) Power supply fault oi fault UV being detected, but time delay not yet satisfied Fire

LEDs Blink every 5 seconds Blink every 10 seconds Off Off Off LEDs continue blinking On
T0005A

Output The output of the device is a status message that is sent to the gateway and logic controller in the Local Control Unit along the communication loop. System response to the message is determined at the time of configuration. The UV detector supports ANSI/NFPA 72 Class A, Style 7 communication with the LCU. A Standard Periodic Report (SPR) is sent to the gateway at the rate determined at the time of configuration. When programmed for response to a fire alarm condition, a special Acknowledged Exception Report (AER) is immediately sent to the Logic Controller. Addressability Device identification is accomplished by setting switches on an eight position DIP switch (valid address range is 5 to 250). Alarm Log Each detector maintains an alarm log in non-volatile memory. The time and date for the last eight alarms are logged. Terminal Wiring Board All external wiring is connected to screw terminal connectors on the terminal wiring board located inside the detector housing. Enclosure The explosion-proof NEMA/Type 4X enclosure is designed for use in a variety of hazardous locations. SOFTWARE SELECTABLE OPTIONS The following software selectable options are available through a PC running Det-Tronics configuration software.

Operating Mode The operating mode determines the type of logic that the UV flame detector will use for processing fire signals (either standard or arc rejection). ARC REJECTION MODE The arc rejection mode (recommended) enables the detector to prevent nuisance fire alarms caused by UV from short-duration electrical arcs or electrostatic discharge, while maintaining the ability to reliably detect the UV given off by a flame. The arc rejection mode is not recommended unless these false alarm sources are present within the application to be protected. Typical applications that benefit from arc rejection logic include electrostatic coating processes and uncontrolled environments where transient UV sources can be present, such as many typical outdoor applications. STANDARD MODE In the standard processing mode, the detector output (measured in counts per second) is compared to the fire threshold (the sensitivity setting as described below). If the radiant energy level from the fire exceeds the selected alarm threshold level, the time delay begins (if a time delay is selected). If the radiant energy level from the fire remains above the selected sensitivity level for the duration of the time delay, the fire alarm output is activated. In every application, it is crucial to ensure that the radiant ultraviolet energy level from the expected fire at the required distance from the detector will exceed the selected sensitivity level. Standard signal processing is recommended for controlled indoor applications only. The arc rejection algorithm examines the radiant energy level detected within a specified unit of time (timed gate). Detector output is determined by three variables: sensitivity level gate length number of consecutive gates required.
IV-2

Different combinations of these variables allow for various levels of transient arc rejection capability. There are four arc rejection levels (very high, high, medium, and low) that are selectable for each detector through the PC. Refer to Table IV-2. The proper arc rejection setting for a given application must be determined through testing. For indoor applications with known electrostatic energy fields within 15 feet of the detector, an arc rejection setting of very high or high is typical. For outdoor applications, medium or low arc rejection settings are typical. It is recommended that each detector be thoroughly tested at the programmed arc rejection setting within the ambient conditions that will be present during normal operation. This will help to ensure that the selected arc rejection setting is proper for the application. Sensitivity Whether the Standard or Arc Rejection mode is selected, the sensitivity setting must always be programmed. The selected sensitivity level determines the fire alarm threshold setpoint. The higher the sensitivity level, the greater the detection range, but the possibility of false alarms will be increased. Four sensitivity levels are selectable. Refer to Table IV-3. The sensitivity setting must be appropriate for the anticipated fire size at the required distance from the detector.

Time Delay Arc rejection mode If the fire signal meets the programmed arc rejection requirements, the time delay begins. A fire output is generated if the fire signal continues for the duration of the time delay. Standard mode A fire output is generated only if the fire signal exceeds the sensitivity setting for the entire duration of the programmed time delay. Automatic or Manual oi The o i system uses an internally generated UV test signal to determine the relative condition of the detector and its optical surfaces. If automatic o i testing is selected, the o i test is automatically performed once every minute. The automatic oi test does not generate an alarm output or interfere with normal detector operation. The manual oi test is initiated using a button on the point display screen at the PC. The manual oi test can be used in addition to automatic oi to verify correct system operation. Fire Output Latching When latching operation is selected, the fire alarm signal is cleared by removing input power for a minimum of 0.1 second.

Table IV2Arc Rejection Levels for UV Detector

Arc Rejection Level Very High High Medium Low * CPS = counts per second

Consecutive Gates 8 4 4 4

Gate Length 1/16 Second 1/16 Second 1/8 Second 1/4 Second

Sensitivity* Very High (8 CPS) Very High (8 CPS) Very High (8 CPS) Very High (8 CPS)

Min. Processing Time 0.5 Second 0.25 Second 0.5 Second 1.0 Second
T0006A

Table IV3Sensitivity Levels for UV Detector

Sensitivity Level Equivalents Sensitivity Level Selected Very High High Medium Low
IV-3

Nominal Fire Alarm Threshold In Counts per Second (CPS) 8 24 48 96


T0007A

95-8470

Fault Latching If the fault output is set for latching, the fault will not clear until it is corrected and the unit is reset. If a fire occurs, the unit will indicate a fire, over-riding the fault condition, i.e., the fault signal will clear if not latched. If a fault is still present after the fire has been extinguished, the unit will again indicate a fault until the problem has been corrected and the unit is reset.

EQ2200UVIR FLAME DETECTOR


DESCRIPTION The EQ2200UVIR Series Flame Detector is designed to provide reliable fire protection in applications where the use of either ultraviolet (UV) or infrared (IR) detectors alone can result in false alarms. When used alone, a UV detector can respond to sources of ultraviolet radiation besides fire, such as lightning, x-rays or arc welding. Likewise, an IR detector can respond to various hot objects, such as flickering or chopped radiation from electric heaters or exhaust manifolds. The microprocessor based EQ2200UVIR combines both a UV and a single frequency IR sensor in a single detector and requires simultaneous response of both sensors to generate a fire alarm. These two detecting elements monitor different portions of the radiation spectrum and have virtually no common sources of false alarms. This enables the detector to respond to a real fire while ignoring potential false alarm sources such as arc welding, x-rays, or hot vibrating objects. Microprocessor based circuitry located inside the detector junction box continuously monitors the two sensors, evaluating the signal(s) with fire and fault algorithms to determine the current status of the detector. When both sensors simultaneously detect the presence of fire, the microprocessor generates a fire signal, which is immediately sent over the LON/SLC to the logic controller in the Local Control Unit (LCU). The LEDs, visible through the UV sensor viewing window, are also immediately illuminated. In addition, a watchdog timer assures that the detectors operating program is running properly. Detector Output The output of the device is a status message that is sent to the gateway and logic controller in the LCU along the communication loop. System response to the message is determined at the time of configuration. The detector supports ANSI/NFPA 72 Class A, Style 7 communication with the LCU. Status Conditions

EQ2200UVHT HIGH TEMPERATURE UV FLAME DETECTOR


DESCRIPTION The EQ2200UVHT UV Flame Detector provides UV flame protection in continuous duty high temperature applications, such as turbine compartments, enclosures, generator rooms, etc. where ambient temperatures can continuously exceed +75C (+167F). The EQ2200UVHT is an electronic module assembly that is used in conjunction with a high temperature rated C7050B UV detector (with DE1888K3 high temperature rated UV sensor tube). The two devices are mounted in separate explosion-proof, watertight enclosures. The UV detector is rated for continuous duty in environments up to +125C (+257F). The electronic module is rated up to +75C (+167F). NOTE The electronic module cannot be located in the high temperature area. The UV detector and electronic module assembly can be separated up to 165 feet (50 meters) using high temperature rated 4 core shielded cable. NOTE In accordance with NFPA 72, the maximum separation distance is 20 feet (6 meters) using conduit or equivalent protection against mechanical damage. LED Detector status is indicated by a red LED that is visible through the viewing window on the cover of the electronic module junction box. Refer to the EQ2200UV UV Flame Detector section above for a description of features, operating characteristics and software selectable options of DetTronics Eagle Quantum UV detectors.

Detector status conditions include normal operation, fire, fault, UV only, and IR only. A fire alarm signal is generated when both UV and IR sensors are active. The fire alarm status has the highest priority and will override a fault condition.

IV-4

Addressability Device identification is accomplished by setting rocker switches on an eight position DIP switch (valid address range is 5 to 250). Alarm Log Each detector maintains an alarm log in non-volatile memory. The time and date for the last 8 alarms are logged. Enclosure The explosion-proof NEMA/Type 4X enclosure is available in either aluminum or stainless steel and is designed for use in a variety of hazardous locations. LEDs Detector status is indicated by a pair of red LEDs (illuminated simultaneously) that are visible through the viewing window of the UV sensor. Table IV-4 indicates the condition of the LEDs for each detector status. Automatic Diagnostics The microprocessor based detector is equipped with advanced fault detection and diagnostic capabilities. The LED indicators on the UV sensor module provide the user with visual annunciation of the problem area. In addition, the point display screen at the OIS provides a variety of information regarding detector status as well as the actual UV and IR signal levels present at the detector. Refer to Table IV-5 for a list of status conditions.

SOFTWARE SELECTABLE OPTIONS The following options are selectable through a PC running Det-Tronics configuration software: Processing Mode The UV portion of the detector offers a choice of two different types of logic that can be used for processing fire signals either standard or arc rejection. ARC REJECTION MODE The arc rejection mode (recommended) enables the detector to prevent nuisance fire alarms caused by short-duration electrical arcs or electrostatic discharge, while maintaining the ability to reliably detect a flame. The arc rejection mode is not recommended unless these false alarm sources are present within the application to be protected. Typical applications that benefit from arc rejection logic include any uncontrolled environments where transient radiation sources can be present, such as many typical outdoor applications. The arc rejection algorithm examines the radiant energy level detected within a specified unit of time (timed gate). The output of the detector is determined by three variables: sensitivity level gate length number of consecutive gates required. Different combinations of these variables allow for various levels of transient arc rejection capability. There are two arc rejection levels (medium and high) that are selectable for the detector through the OIS. The proper arc rejection setting for a given application must be determined through testing.

Table IV4EQ2200UVIR Detector Status/Indications

Detector Status Fault Automatic oi Manual oi UV only IR only Alarm

LED Off On for 0.25 second every 5 seconds On for 0.25 second every 10 seconds On for 50 milliseconds off for 500 milliseconds On for 200 milliseconds off for 500 milliseconds On steady
T0030

IV-5

95-8470

Table IV5Status Conditions of UV/IR Detector

Status Indication Low Voltage COM 1 COM 2 IR Alarm UV Alarm Not communicating

Possible Cause Power supply. Detector power wiring. LON wiring on COM 1 side of detector. Detector communication circuitry problem. LON wiring on COM 2 side of detector. Detector communication circuitry problem. IR radiation source within view of detector. UV radiation source within view of detector. Power supply or power wiring problem. LON wiring problem. Detector communication circuitry problem. Wrong DIP switch address setting. Inhibit activated at OIS. Configuration problem. Repeat configuration. Configuration problem. Repeat configuration. Defect in UV module. (See extended status.) Defect in IR module. (See extended status.) Detector in power-up time delay. Solution: Wait for detector to exit delay. Replace detector. Configuration problem. Repeat configuration. Power supply failure. Power or LON wiring problem. Electronic failure in detector. UV and IR radiation detected. UV viewing window or oi ring dirty. UV oi ring missing. Module missing. Install module. Dirty or broken contacts on module. Internal power problem. Replace detector terminal board. IR viewing window or oi ring dirty. IR oi ring missing. Module missing. Install module. Dirty or broken contacts on module.
T0031B

Inhibit active Unable to configure Invalid Configuration UV fault IR fault Power-up Auto configuration fault General fault

Fire alarm UV oi fault UV tube missing UV 290 volt fault IR oi fault IR missing module

IV-6

It is recommended that each detector be thoroughly tested at the programmed arc rejection setting within the ambient conditions that will be present during normal operation. This will help to ensure that the selected arc rejection setting is proper for the application. STANDARD MODE In the standard processing mode, the UV sensor output (measured in counts per second) is compared to the fire threshold (the sensitivity setting as described below). If the radiant energy level from the fire exceeds the selected alarm threshold level, the time delay begins (if a time delay is selected). If the radiant energy level from the fire remains above the selected sensitivity level for the duration of the time delay, a fire alarm signal is generated. In every application, it is crucial to ensure that the radiant energy level from the expected fire at the required distance from the detector will exceed the selected sensitivity level. Standard signal processing is recommended for controlled indoor applications only. Sensitivity Whether Arc Rejection or Standard mode is selected, the sensitivity setting must always be programmed. The selected sensitivity level determines the fire alarm threshold setpoint. The higher the sensitivity level, the greater the detection range, but the possibility of false alarms will be increased. Four sensitivity levels are selectable. (Sensitivity levels for UV and IR are selected separately.) The sensitivity setting must be appropriate for the anticipated fire size at the required distance from the detector. Refer to the Specifications section of this manual for additional information. Time Delay A time delay from 0 to 7 seconds is selectable. STANDARD MODE A fire output is generated only if the fire signal exceeds the sensitivity setting for the entire duration of the programmed time delay. ARC REJECTION MODE If the fire signal meets the programmed arc rejection requirements, the time delay begins. A fire output is generated if the fire signal continues for the duration of the time delay.

Automatic or Manual oi The EQ2200UVIR is equipped with the Optical Integrity (oi) feature. The oi test is performed on both the UV and IR sensors to check the cleanliness of the detector optics, as well as the proper functioning of the sensors and electronic components of the detector. If a problem should occur, it is quickly detected. The detector is user programmable (from a PC running Det-Tronics configuration software) for automatic o i testing. If automatic testing is selected, the oi test is automatically performed on each sensor. The rate for the UV sensor test is once per minute. The rate for the IR sensor is field selectable from once a minute to once every four hours. If a fault is detected, a trouble signal is sent to the LCU over the LON/SLC. A fault condition is indicated at the logic controller and the gateway and also by the LEDs on the detectors UV sensor. The automatic oi test does not generate an alarm output or interfere with normal detector operation. The manual oi test is initiated using a button on the point display screen at the OIS. A successful test is signaled by the OIS. The manual oi test can be used in addition to automatic o i to verify correct detector operation. NOTE The manual oi test does not generate an alarm output or actuate any system outputs. Fire Output Latching When latching operation is selected, the fire alarm signal is present until cleared by a reset command from the PC.

EQ2200DCU AND EQ2200DCUEX DIGITAL COMMUNICATION UNIT


DESCRIPTION The EQ2200 Series Digital Communication Unit (DCU) digitizes a 4 to 20 ma analog signal and transmits the value as the process variable portion of its Standard Periodic Report (SPR) to the Communication Gateway located in the LCU. All circuitry is housed in a single explosion-proof/watertight enclosure for use in the area of detection. Designed for use with the Eagle Quantum system, the DCU provides a unique technique for detecting and isolating opens or shorts in the Local Operating Network/Signaling Line Circuit (LON/SLC) wiring. This

IV-7

95-8470

fault isolation method allows for communication integrity in the event of a single wiring fault in the LON/SLC wiring. The DCU is approved for use with a variety of Detector Electronics sensors including catalytic combustible gas sensors, the PointWatch IR gas detector, as well as electrochemical sensors (hydrogen sulfide, carbon monoxide, chlorine, sulfur dioxide, and nitrogen dioxide). It will also accept any sensor with a linear 4 to 20 ma output signal and allows for one person nonintrusive calibration. Inputs The DCU features one 4 to 20 ma non-isolated input, with an input impedance of 200 ohms in series with a protection diode. (When used with a Det-Tronics catalytic combustible gas sensor, a separate transmitter board converts the millivolt output to a 4 to 20 ma signal.) The DCU also monitors its 24 vdc supply voltage and reports to the PC when requested. Output The Standard Periodic Report (SPR) is sent to the gateway at the rate determined at the time of configuration (from one to ten seconds). Calibration A magnetic reed switch, located on the terminal board, enables calibration of the sensor without opening the enclosure. The switch is activated by placing a calibration magnet at a specified location on the side of the enclosure. Once the calibration mode has been entered, the DCU steps the user through the process. For details, refer to the Calibration section of this manual. Addressability Device identification is accomplished by setting switches on an eight position DIP switch (valid address range is 5 to 250). Status LEDs Three LEDs are located at the center of the communication module circuit board and are visible through the window on the enclosure cover. The green LED serves as a power-on indicator and is illuminated whenever power is applied. During normal operation, only the green LED is illuminated.

The red LED is used to indicate a calibration, power-up, fault or alarm condition. The flashing rate of the red LED indicates the following conditions: Power-up = Calibration = Fault = Alarm = Pulsed at a 0.5 Hz rate Pulsed at a 1 Hz rate or on steady Pulsed at a 4 Hz rate Illuminated continuously.

NOTE If the communication module has not been configured, the red LED blinks at the 4 Hz rate. The amber LED is provided for factory diagnostic purposes and is not used in the system. Illumination of the amber LED normally indicates a failure in the communication chip. Replacement of the communication module circuit board is required. Calibration Log The DCU keeps a calibration log in non-volatile memory that can be used by the operator to evaluate the remaining life of some sensors. This log includes the zero, span, date and time for each successful calibration. An aborted calibration is indicated by zeros in the zero and span values. The calibration log is cleared when the sensor replacement switch is pressed and the calibration is successfully completed. The initial calibration is logged in position one, where it remains for the life of the sensor. If more than 8 calibrations are performed without the sensor replacement switch being pressed, the newest calibration data will replace the second oldest so that the initial calibration data can be saved. The old calibration data will be lost. This feature enables sensor sensitivity trending to aid in maintenance or troubleshooting. The analog value for the sensor is represented in raw analog to digital counts 0 to 4095, where 0 represents 0 ma and 4095 represents 24 ma. Alarm Log A log of low and high alarms is stored in each DCU. Time, date and alarm type are logged for each alarm event. A maximum of eight events can be stored. If more than eight events are logged, the oldest event will be overwritten.

IV-8

Enclosure The explosion-proof, watertight NEMA/Type 4X enclosure is designed for use in a variety of hazardous locations. The cover is furnished with a window to allow the operator to view the three status indicator LEDs on the communication module PC board. Terminal Wiring Board All external wiring is connected to screw terminal connectors on the terminal wiring board located inside the junction box.

Each output is rated at 2 amperes. Auxiliary input terminals are provided for additional 24 vdc output power where needed. Solenoids/Initiators The releasing output devices listed in Table IV-6 are recommended for use with the Agent Release Module. The solenoids listed in Table IV-7 are compatible with the Agent Release Module for deluge and pre-action applications. Addressability

EQ2500ARM AGENT RELEASE MODULE


DESCRIPTION The EQ2500ARM Series Agent Release Module (ARM) is located on the LON/SLC and provides agent release capability for the Eagle Quantum system. The device is controlled by programmable logic in the Logic Controller and can be programmed for Single, Cross or Counting Zone Style initiation. Optional time delay, abort and manual release sequences allow the output to be programmed for use in unique applications. The Agent Release Module can monitor and control two output devices (rated for 24 vdc), which are programmed and energized together. The release circuits are compatible with a variety of solenoid or initiator (squib) based suppression systems. The release circuit is supervised for open circuit conditions. If a trouble condition occurs (open circuit or solenoid supply voltage less than 19 volts), it will be indicated at the LCU.

Device identification is accomplished by setting switches on an eight position DIP switch (valid address range is 5 to 250). Status LEDs Three LEDs located at the center of the circuit board provide a visual indication of device status conditions. Green On steady when power is applied to the device. Red Blinking at a 4 Hz rate with the LED on 50%, off 50% of the time indicates a local trouble condition such as an open output circuit or low solenoid supply voltage. Blinking at a 1 Hz rate with the LED on 5%, off 95% of the time indicates an isolate condition. Blinking at a 1 Hz rate with the LED on 95%, off 5% of the time indicates release and isolate. Yellow On indicates a malfunction in the electronic circuitry. Replace the module.

Table IV-6Recommended Releasing Output Devices for Agent Release Module

Manufacturer Fenwal Fenwal Fenwal Fenwal Fenwal Fenwal

Model 890181
(2.4 A. max., 10 , momentary)

Table IV-7Solenoid Compatibility with Agent Release Module for Deluge and Pre-Action Applications

899175
(2.4 A. max., 10.8 , momentary)

Manufacturer Skinner ASCO ASCO Skinner Skinner Skinner

Model LV2LBX25 8210A107 8210G207 73218BN4UNLVNOC111C2 73212BN4TNLVNOC322C2 71395SN2ENJ1NOH111C2


T0037B

895630-000
(2 A. max., 12 , momentary)

897494
(1.5 A. max., 15.9 , continuous)

486500-001
(240 ma max., 103 , momentary)

31-199932-004
(2.4 A. max., 10 , momentary)

IV-9

95-8470

Alarm Log Time and date are logged each time that a release occurs. Data for the last eight events is stored in nonvolatile memory. Terminal Wiring Board

Status LEDs Three LEDs located at the center of the circuit board provide a visual indication of device status conditions. Green On when power is applied to the device. Red On steady indicates an active condition. Blinking indicates a local trouble condition such as an open or shorted output circuit or low output supply voltage. Yellow On indicates a malfunction in the electronic circuitry. Replace the module. Alarm Log Time and date are logged each time that a fire alarm occurs. Data for the last eight events is stored in nonvolatile memory. Terminal Wiring Board All external wiring is connected to screw terminal connectors on the terminal wiring board located inside the device enclosure.

All external wiring is connected to screw terminal connectors on the terminal wiring board located inside the device enclosure.

EQ2500SAM SIGNAL AUDIBLE MODULE


DESCRIPTION The EQ2500SAM Series Signal Audible Module (SAM) provides two indicating circuits for controlling UL Listed 24 vdc polarized audible/visual indicating appliances. The device is located on the LON/SLC and is controlled by programmable logic in the Eagle Quantums Logic Controller. Each output circuit is independently programmable to allow annunciation of separate events. In release applications, signal outputs can be programmed to provide signaling for pre-release, release or postrelease. Each output can be individually activated for any one of the following pre-defined coded outputs: 1. 2. 3. 4. Continuous until reset 60 beats per minute 120 beats per minute Temporal pattern.

EQ2400NE NETWORK EXTENDER


DESCRIPTION The EQ2400NE Series Network Extender expands the capabilities of the Eagle Quantum system by allowing additional nodes as well as additional wiring to be added to the LON/SLC (communication loop). Without a network extender, the communication network is limited to 60 nodes on a 2000 meter loop. Each network extender, however, increases the capacity of the loop by up to 40 nodes and 2000 meters of wiring, up to a maximum of 244 field nodes and 10,000 meters of wiring. Network extender circuitry supports communication in both directions. If a network wiring fault should occur, uninterrupted communication can continue in the opposite direction. LEDs The network extenders electronic module is furnished with three LEDs (one green and two yellow) for indicating device status.

The outputs operate in the reverse polarity fashion when activated. Each output is rated at 2 amperes. Auxiliary input terminals are provided for additional 24 vdc signaling power where required. The output circuits are supervised for open and short circuit conditions. If a wiring fault occurs, a trouble condition will be indicated at the LCU. Addressability Device identification is accomplished by setting switches on an eight position DIP switch (valid address range is 5 to 250).

IV-10

The green LED indicates that power is applied and flashes to indicate that messages are being transferred over the network. The two yellow LEDs correspond to the two communication transceivers and are illuminated to indicate that an internal fault has been detected. Enclosure The network extenders electronic circuitry is mounted inside an explosion-proof, water-tight enclosure for installation in hazardous locations. The enclosure is available with up to six 3/4 inch NPT or 25 mm conduit entries. GENERAL APPLICATION INFORMATION System Capacity The basic Eagle Quantum system supports a communication loop consisting of up to 60 detection nodes and up to 2000 meters of connecting wiring. Adding a network extender to the loop allows it to be expanded by up to 40 nodes with an additional 2000 meters of wiring. Up to 6 network extenders can be utilized in a single system, supporting up to 244 field nodes and up to 10,000 meters of wiring. To ensure optimum performance, it is important to distribute the network extenders along the loop so that there are no more than 40 detection nodes or 2000 meters of wiring on either side of a network extender. See Figure IV-1. Response Time vs. System Size When designing a system, it is important to realize that increasing the number of nodes on the communication loop can result in an increase in the amount of time required for a status change message from a detection node to reach the host computer. The gateway requires a finite length of time to process each bit of information that is transferred along the communication network. As the number of nodes increases, so does the amount of data that is being processed as well as the time required for processing the data. As a result, the update time for each node should be increased to accommodate the extra traffic for a large system (one second minimum for each 50 nodes).

If the fastest possible communication response time is an important criteria for a large system, it is recommended that the number of nodes on an individual loop be kept as small as practical. Consider using multiple loops with fewer nodes per loop rather than one large loop.

60 NODE LOOP

RIGHT

LCU

100 NODE LOOP

NE

WRONG

50 NODES

50 NODES

LCU

100 NODE LOOP

NE

40 NODES

NE

RIGHT
30 NODES 30 NODES

LCU

NOTES:

1.

2.

3.

BASIC LOOP WITHOUT A NETWORK EXTENDER CANNOT EXCEED 60 NODES AND 2000 METERS OF WIRE. NO MORE THAN 40 NODES AND 2000 METERS OF WIRE BETWEEN NETWORK EXTENDERS OR BETWEEN A NETWORK EXTENDER AND THE LCU. NO MORE THAN 244 FIELD NODES AND 10,000 METERS OF WIRE ON THE LOOP.
A1946

Figure IV-1Eagle Quantum Communication Loops

IV-11

95-8470

Section V Detector Application Information


UV DETECTORS
In applying any type detector, it is important can prevent the device also to know what other the device to respond. WINDOWS Glass and plexiglas windows significantly attenuate UV radiation and must not be located between the detector and a potential flame source. If the window cannot be eliminated or the detector location changed, contact Detector Electronics for recommendations regarding window materials that will not attenuate UV radiation. OBSTRUCTIONS For an ultraviolet detector, dust, dirt and other films, UV absorbing gases or vapors as well as physical obstructions must not be allowed to come between the detector and the protected hazard (see Table V-1). SMOKE Smoke will absorb UV radiation, and if accumulations of dense smoke can be expected to precede the presence of flame, then ultraviolet detectors that are used in enclosed areas should be mounted on the wall approximately 3 feet (1 meter) from the ceiling where the accumulation of smoke is reduced. ARC WELDING Electric arc welding is a source of intense ultraviolet radiation, and care must be taken to ensure that arc welding is not performed in the protected area without securing the fire detection system. UV radiation from arc welding readily scatters and can deflect across significant distances, even when direct obstructions exist. Any open door or window can allow nuisance UV radiation from arc welding to enter an enclosed area. When x-rays or radioactive substances are present in the area being protected, the UV system must be disabled until those sources are removed. COMMON ENVIRONMENTAL CONDITIONS The detector is not affected by environmental conditions such as wind, rain or extremes of temperature and of sensing device as a fire to know of any conditions that from responding to a fire, and sources besides fire will cause

pressure. It is also insensitive to the ultraviolet component of solar radiation. UV radiation generated by periodic lightning or sparks in the area can be effectively ignored by the detector using the arc rejection feature or time delay. UV detectors should not be positioned so that their cone of vision can scan the horizon. Rather, they should be directed down over the designated hazardous area to reduce the likelihood of picking up UV radiation from distant sources.

Table V-1UV and IR Absorbing Gases and Vapors

The following is a partial list of compounds that exhibit significant UV absorption characteristics. These are also usually hazardous vapors. While generally of little consequence in small amounts, these gases can restrict UV detection if they are in the atmosphere in heavy concentrations. It should also be determined whether or not large amounts of these gases may be released as a result of a fire-causing occurrence. Acetaldehyde Acetone Acrylonitrile Ethyl Acrylate Methyl Acrylate Ethanol Ammonia Aniline Benzene 1,3 Butadiene 2Butanone Butylamine Chlorobenzene 1-Chloro-1-Nitropropane Chloroprene Cumene Cyclopentadiene O-Dichlorobenzene P-Dichlorobenzene Methyl Methacrylate Alpha-Methylstyrene Naphthalene Nitroethane Nitrobenzene Nitromethane 1-Nitropropane 2-Nitropropane 2-Pentanone Phenol Phenyl Clycide Ether Pyridine Hydrogen Sulfide Styrene Tetrachloroethylene Toluene Trichloroethylene Vinyl Toluene Xylene

If UV-absorbing gases may be a factor in a given application, precautionary measures should be taken. Detectors can be placed closer to the potential hazard area, and/or the sensitivity of the detection system can be increased. Contact the factory for further details. Substances such as methane, propane, butane, hexane, camphor and octane are not UV absorbing. Absorption of infrared radiation in the range of 4.2 to 4.7 microns is not a significant problem with most organic vapors, with the exception of those compounds that have triple bonds such as acetylene, nitriles, silane, or isocyanates. Carbon dioxide concentrations higher than normally present in the atmosphere can also cause substantial loss of fire detection sensitivity.

V-1

95-8470

UV DETECTOR POSITIONING
Detectors should be positioned to provide the best unobstructed view of the area to be protected. The following factors should be taken into consideration: Identify all high risk fire ignition sources. Be sure that enough detectors are used to adequately cover the hazardous area. For fastest response time, locate the detector as close as possible to the anticipated fire source. The central axis of the detectors cone of vision provides the highest sensitivity. Be sure that the unit is easily accessible for cleaning and other periodic servicing. Particular attention should be paid to potential false alarm sources within the cone of vision of the detector. For outdoor applications, the detector should be aimed downward at least 10 to 20 degrees to prevent it from scanning the horizon. This minimizes response to distant UV sources outside the protected area. See Figure 1. Dense fog, rain or ice will absorb UV radiation and reduce the sensitivity of the detector. If smoke is expected before flame, it is recommended that smoke or other additional detectors be used in conjunction with the UV detector. If possible, fire tests should be conducted to verify correct detector positioning and coverage.
CENTER AXIS OF DETECTOR FIELD OF VIEW CENTER AXIS OF DETECTOR FIELD OF VIEW

INCORRECT

B1974

CORRECT NOTE: DETECTOR MUST ALWAYS BE AIMED DOWNWARD AT LEAST 10 TO 20 DEGREES.

Figure 1Detector Orientation Relative to Horizon

Any object having a temperature greater than 0 Kelvin (273C) emits infrared radiation. The hotter the object, the greater the intensity of the emitted radiation. The closer the infrared source is to the detector, the greater the potential for a false alarm. The IR sensor can respond to IR radiation sources that can meet the amplitude and flicker requirements of the detector such as vibrating hot objects. Although the detector is designed to reduce false actuations, certain combinations of ambient radiation must be avoided. For example, if IR radiation with an intensity that exceeds the fire threshold of the IR sensor should reach the detector as a flickering signal, and if at the same time an electric arc welding signal also reaches the detector, an alarm output will be generated. NOTE Radiation generated by false alarm sources such as periodic lightning or sparks in the area can be effectively ignored by the detector using the arc rejection feature or time delay. Arc Welding Electric arc welding is a source of intense ultraviolet radiation. UV radiation from arc welding readily scatters and can deflect across significant distances, even when direct obstructions exist. Any open door or window can allow nuisance UV radiation from arc welding to enter an enclosed area.

UV/IR DETECTORS
FALSE ALARM SOURCES UV: The UV sensor is insensitive to the ultraviolet component of solar radiation. However, it will respond to sources of UV besides fire, such as electric arc welding, lightning, high voltage corona, x-rays and gamma radiation. IR: The detector has been designed to ignore steady state infrared sources that do not have a flicker frequency characteristic of a fire, however, it should be noted that if these steady state infrared sources are hot enough to emit adequate amounts of infrared radiation in the response range of the IR sensor and if this radiation becomes interrupted from the view of the detector in a pattern characteristic of a flickering flame, the IR sensor can respond.

V-2

The UV/IR detector does not respond to arc welding beyond 10 feet from the detector. However, a UV only signal will be generated in response to the intense UV radiation generated by the arc welding, and at distances closer than 10 feet the heated metal from the welding can become a false alarm source for the IR sensor. FACTORS INHIBITING DETECTOR RESPONSE Windows Glass and Plexiglas windows significantly attenuate radiation and must not be located between the detector and a potential flame source. If the window cannot be eliminated or the detector location changed, contact Detector Electronics for recommendations regarding window materials that will not attenuate radiation. Obstructions Radiation must be able to reach the detector in order for it to respond. Care must be taken to keep physical obstructions out of the line of view of the detector. In addition, UV or IR absorbing gases or vapors must not be allowed to accumulate between the detector and the protected hazard. See Table V-1 for a list of these substances. Smoke Smoke will absorb radiation. If accumulations of dense smoke can be expected to precede the presence of a flame, then detectors that are used in enclosed areas should be mounted on the wall approximately 3 feet (1 meter) from the ceiling where the accumulation of smoke is reduced. Detector Viewing Windows It is important to keep the detector viewing windows as free of contaminants as possible in order to maintain maximum sensitivity. Commonly encountered substances that can significantly attenuate UV and/or IR radiation include, but are certainly not limited to, the following: Silicones Oils and greases Ice buildup Dust and dirt buildup Paint overspray.

UV/IR DETECTOR POSITIONING


IMPORTANT Detectors should not be positioned so that their cone of vision can scan the horizon. Rather, they should be directed down over the designated hazardous area to reduce the likelihood of picking up radiation from distant sources. See Figure 1. Detectors should be located in positions best suited for covering the area to be protected. Whenever practical, they should be placed where they will be easily accessible for cleaning and other periodic servicing. Particular attention should also be paid to potential false alarm sources within the cone of vision of the detector, such as distant arc welding, or the rotating blades of a fan or surface vibration of an IR source, which could allow a flickering IR signal to reach the detector. Rain or ice can absorb radiation, which can reduce the capability of the detector. For outdoor applications, aim the detector downward to minimize the buildup of water or ice on the detector viewing windows and to prevent the cone of vision from scanning the horizon. This minimizes response to distant radiation sources outside the protected area.

GAS DETECTOR POSITIONING


The sensor must be properly located to enable it to provide maximum protection. The formula for determining the most effective number and placement of sensors varies depending on the conditions at the job site. The individual performing the installation must rely on experience and common sense to determine the quantity of sensors and the best sensor locations to adequately protect the area. The following factors should be considered for every installation: 1. What kind of gas is to be detected? If it is lighter than air (acetylene, hydrogen, methane, etc.), place the sensor above the potential source. Place the sensor close to the floor for gases that are heavier than air (benzene, butane, butylene, propane, hexane, pentane, etc.) or for vapors resulting from flammable liquid spills. However, note that air currents can cause a gas that is heavier than air to rise. In addition, if the gas is hotter than ambient air, it could also rise. How rapidly will the gas diffuse into the air? Select a location for the sensor as close as practical to the anticipated source of a gas leak.

2.

V-3

95-8470

3.

Ventilation characteristics of the immediate area must also be considered. Movement of air will cause gas to accumulate more heavily in one area than another. The sensor should be placed in the area where the most concentrated accumulation of gas is anticipated. Also consider the fact that many ventilation systems do not operate continuously. The sensor should be pointed down to prevent the buildup of moisture or contaminants on the filter and to ensure proper operation. For PointWatch, refer to instruction manual 95-8440. The sensor must be accessible for testing and calibration. The use of the Sensor Separation Kit will be required in some installations. Catalytic sensors should be located where they are safe from potential sources of contamination that can poison the sensing element. Exposure to excessive heat or vibration can result in premature failure of any electronic device and should be avoided if possible. Shielding the device from intense sunlight will reduce solar heating and can increase the life of the unit.

When a sensor is exposed to a different or new environment, calibration should be checked frequently to determine the proper interval between periodic calibrations. Before performing calibration, the operator should examine the sensor filter (flame arrester) to be sure that it is not missing or damaged. If the filter is defective or missing, it must be replaced. In some cases, an exposed sensing element can act as an ignition source. It should also be noted that a dirty cover can significantly reduce the sensitivity of the sensor. CATALYTIC SENSOR OPERATION The sensing element used in the combustible gas sensor consists of a pair of elements. One is an active catalytic sensing element, and the other is inactive and acts as a temperature compensating reference element. Both elements are composed of a wire coil encased in ceramic. The active element has a catalytic coating applied to its surface, however, the reference element is glazed so that it does not react to the presence of a combustible gas/air mixture. The pair is computer matched to have the same electrical resistance. In the presence of a combustible gas/air mixture, the resistance of the active sensing element increases in proportion to the concentration of gas at the sensor. The change in resistance of the active sensing element, relative to that of the reference element, is used to determine the actual level of combustible gas present at the sensor. Both elements operate at a high temperature and are enclosed by a porous stainless steel cup (flame arrester). See Figure V-2. This cup allows the diffusion of gas to and from the sensing element, but prevents the ignition of the atmosphere outside the sensor should the combustible gas concentration exceed its LFL. A barrier is placed between the element pair to prevent thermal interaction and to prevent the transfer of catalytic material from the active element to the surface of the reference element. All catalytic type sensors require oxygen to detect combustible gases. The sensor response will decrease if enough combustible gas displaces the normal oxygen present in air. The sensor should not be used where the oxygen level is less than 10%. See Figure V-3. Figure V-4 shows the response of a typical sensor to various levels of combustible gas. Note that a reading of 40% LFL will be given at 2.0% methane (40% LFL) and

4.

5.

6.

7.

For additional information on determining quantity and placement for sensors in a specific application, refer to Instrument Society of America (ISA) Transaction Volume 20, Number 2, titled The Use of Combustible Detectors in Protecting Facilities from Flammable Hazards.

CATALYTIC GAS SENSORS


CAUTION Exposure to a high level of gas can have an adverse effect on the sensitivity of catalytic sensing elements. If the level of gas at the sensor should reach 100% LFL, it is important that it be tested and recalibrated if required. In some cases, it may be necessary to replace the sensor. If an over-range condition should occur, the user must exercise caution, since a highly explosive condition could exist. The hazardous area should be checked with a portable detection instrument to determine the actual level of combustible gas present. For best calibration results, allow a new sensor to operate for several hours to ensure a stable output before performing calibration. For the highest degree of accuracy, perform a second calibration after 24 hours.

V-4

WHT

RED

CAUTION It is possible for the display to drop to a low % LFL reading after going into high alarm and still have an unsafe level of combustible gas present. Therefore, precautions should be taken to ensure that the combustible gas has been cleared before classifying the area as safe.

ACTIVE ELEMENT FLAME ARRESTER

BLK

also at 80.0% methane, well above the upper flammable limit of methane. Although gas levels above the upper flammable limit will not propagate a flame, it stands to reason that somewhere between the leak and clear air there will be a flammable mixture.

REFERENCE ELEMENT THERMAL BARRIER


B1124

Figure V2Catalytic Combustible Gas Sensor

90% LFL METHANE IN STANDARD AIR 100 4.5% METHANE

90

80

70 50% LFL METHANE IN STANDARD AIR 60 2.5% METHANE

CONTROLLER DISPLAY READING (%LFL)

50

40

30

20

10

0 0
B1126

10

15

20

30

40

50

60

70

80

90

100

PERCENT OF OXYGEN IN MIXTURE (BY VOLUME)

Figure V3Effect of Oxygen Enriched and Deficient Atmosphere on the Response of a Typical Catalytic Sensor

V-5

95-8470

180

160

140

120

DISPLAY READING (%LFL)

100

80 LOWER FLAMMABLE LIMIT (100% LFL) 60

40

UPPER FLAMMABLE LIMIT

20

0 0 5 10 15 20 30 40 50 60 70 80 90 100
B1125

PERCENT OF METHANE (BY VOLUME)

Figure V4Typical Response of Catalytic Sensor to All Possible Mixtures of Methane and Air

SENSITIVITY LOSS IN CATALYTIC COMBUSTIBLE GAS SENSORS There are a variety of factors that can cause a decrease in the sensitivity of catalytic type combustible gas sensors. Interfering or contaminating substances that can adversely affect the response of the sensor to combustible gases are as follows: A. Materials that can clog the pores of the sintered metal flame arrestor and reduce the gas diffusion rate to the sensor are: 1. Dirt and oil. A dust cover should be installed to protect the flame arrester whenever these conditions exist. The dust cover can be cleaned as part of routine maintenance. This can be accomplished using an organic solvent and an ultrasonic bath. 2. Corrosive products. This occurs when substances such as Cl 2 (Chlorine) or HCl are present. A dust cover provides some protection. The dust cover should be replaced as part of routine maintenance. 3. Flame arrester clogged as a result of painting or house cleaning.

The routine maintenance procedure should include covering the sensor with a plastic bag when painting or cleaning. The bag should be removed as soon as possible when the procedure is complete. 4. Polymer formation in the flame arrester. This can occur where monomer vapors such as 1-3 butadiene, styrene, isoprene, etc. are present. B. Substances that cover or tie up the active sites on the catalytic surface of the active sensing element. This occurs in the presence of volatile metal organics, gases, or vapors of hydrides, and volatile compounds containing phosphorous, boron, silicone, etc. Examples: RTV silicone sealants Silicone oils and greases Tetraethyl lead Phosphine Diborane Silane Trimethyl chlorsilane Hydrogen fluoride Boron trifluoride Phosphate esters

V-6

C. Materials that remove the catalytic metals from the active element of the sensor. Some substances react with the catalytic metal forming a volatile compound. This erodes the metal from the surface. With sufficient exposure, most or all of the metal catalyst can be removed from the surface of the active element of the sensor. Halogens and compounds containing halogen are materials of this nature. Examples: Chlorine Bromine Iodine Hydrogen Chloride, Bromide or Iodide Organic halides: Trichloroethylene Dichlorobenzene Vinyl chloride Freons Halon 1301 (Bromotrifluoromethane). A brief exposure to one of these materials can temporarily increase the sensitivity of the sensor. This results because the surface of the active element is increased due to etching. Prolonged exposure continues the etching process until the sensitivity of the sensor is degraded, resulting in shortened sensor life. D. Exposure to high concentrations of combustible gases. Exposure of the sensor to high concentrations of combustible gases for extended periods of time can introduce stress to the sensing element and seriously affect its performance. After exposure to a high concentration of combustible gas, recalibration should be performed and, if necessary, the sensor should be replaced. The degree of damage to the sensor is determined by a combination of the type of contaminant, its concentration in the atmosphere, and the length of time the sensor is exposed. When a sensor has been exposed to a contaminant or a high level of combustible gas, it should be calibrated at the time, followed by an additional calibration a few days later to determine whether a significant shift in sensitivity has occurred. E. A combination of accessories such as rain shields and dust covers is not recommended and can result in slow response to a gas leak.

CALIBRATION GAS Before calibrating a sensor, check the label on the calibration gas cylinder to ensure that the correct gas type and concentration are being used. If a different gas type is being used for calibration, refer to DetTronics Technical Note No. GTN01 for K-Factor information (Det-Tronics form number 99-1068-02).

V-7

95-8470

Section VI General Wiring Requirements


GENERAL INFORMATION
WARNING Do not open any junction box or device enclosure when power is applied without first de-classifying the hazardous area. CAUTION Any deviation from the recommended wiring practices can compromise system operation. Consult the factory if different wire types or methods are being considered. NOTE All wiring must be marked per NFPA 70 Article 760. NOTE Specific installation requirements may differ depending on local installation practices and compliance with third party certifications. For local installation practices, consult the local authority having jurisdiction. For compliance with third party certifications, consult the appropriate appendix in this manual for additional specific installation requirements.

POWER WIRING The input voltage at the field devices must be 18 vdc minimum to ensure proper operation of the devices. Therefore, it is important to consider both the size (gauge) of the power wiring and the wiring distance from the power supply. As the wiring distance increases, larger diameter wire is required to maintain a minimum of 18 vdc at the device. Refer to Table VI-1 to determine the minimum wire size needed to prevent excessive voltage drop from power supply to device for a given current load. To use Table VI-1, first determine the total current load for the circuit and the maximum allowable voltage drop. Then look under the appropriate Amp Load column to determine the minimum wire size that will not allow the voltage drop to exceed the maximum allowable. For example: What wire size is required to power ten DCUs at a distance of 100 feet from the power supply, assuming a 24 VDC power supply and a minimum of 18 VDC needed to power the DCUs? Maximum allowable voltage drop is 6 VDC. (24 18 = 6)

Table VI-1Voltage Drop Per Pair in Volts DC per 100 Feet from Power Supply to Device

AWG 22 20 18 16 14 12 10 8 6 4 1 1/0

1 AMP LOAD 3.3 2.1 1.5 1.0 0.6 0.4 0.2 0.2 0.1 0.1 0.0 0.0

2 AMP LOAD 6.6 4.1 3.1 2.0 1.2 0.8 0.5 0.3 0.2 0.1 0.1 0.0

3 AMP LOAD 9.9 6.2 4.6 2.9 1.9 1.2 0.7 0.5 0.3 0.2 0.1 0.1

4 AMP LOAD 13.2 8.3 6.2 3.9 2.5 1.5 1.0 0.6 0.4 0.2 0.1 0.1

5 AMP LOAD 16.5 10.4 7.7 4.9 3.1 1.9 1.2 0.8 0.5 0.3 0.2 0.1

NOTES: This table is for reference only and does not replace good engineering practice. Use Ohms Law when designing the power distribution system. Voltage drop and wiring distance are proportional. Consult factory for assistance with system wiring requirements.

VI-1

95-8470

A combustible gas DCU draws approximately 500 mA at startup, therefore, the total current load is 5 amps. (10 units x 500 mA = 5 amps) Refer to the 5 Amp Load column in the table. Since the maximum allowable voltage drop is 6 volts, 16 AWG (or larger) wire is required. IMPORTANT To ensure proper operation of field devices, the voltage input to the device (measured at the device) must be within the range indicated for that device in the Specifications section of this manual.

Table VI3Communication Loop Wiring Cable

Cable Type

Maximum Length Feet Meters 2000 2000 1370 900

Belden 8719 Belden 85231 Level IV, 22 AWG JY (St) 2x2x0.8

6500 6500 4500 3000

Be sure that selected cable meets all job specifications. If necessary, consult factory for further suggested cable types.

NETWORK WIRING All devices on the LON/SLC are wired in a loop that starts and ends at the LCU. To ensure proper operation, the LON/SLC should be wired using high speed communication grade cable. Cable meeting the specifications listed in Table VI-2 is suitable for distances up to 2000 meters. Any of the cable types listed in Table VI-3 can be used for wiring the LON/SLC for the distances indicated. If no network extenders are used, the distances listed are for the entire loop. If network extenders are used, the distances listed are for the wiring length between network extenders or

between a network extender and the LCU. The use of other cable types can degrade system operation. For optimum fault isolation performance, the maximum LON/SLC wiring length should not exceed 1600 feet (500 meters). SHIELD GROUNDING Two shield ground terminals are provided inside the junction box of each field device and also at the LCU. Connect the shield ends to the terminals provided (not to each other) inside the junction box. CAUTION Insulate the shields to prevent shorting to the device housing or to any other conductor.

Table VI-2Specifications for LON Wiring Cable

Minimum DC Resistance, each conductor DC Resistance Unbalanced Mutual Capacitance Characteristic Impedance Attenuation 20 kHz 64 kHz 78 kHz 156 kHz 256 kHz 512 kHz 772 kHz 1000 kHz Propagation Delay 92 14

Typical 14.7

Maximum 15.5 5% 55.9

Units ohm/km

Condition 20 C per ASTM D 4566 20 C per ASTM D 4566

nF/km ohm dB/km

per ASTM D 4566 64 kHz to 1 MHz, per ASTM D 4566 20 C per ASTM D 4566

100

108 1.3 1.9 2.2 3 4.8 8.1 11.3 13.7 5.6

nsec/m

78 kHz
T0049B

Length: 6,500 feet/2000 meters maximum (basic loop or between Network Extenders). Type: Single twisted pair. Wire Gauge: 16 AWG, stranded (19 x 29), tinned copper with overall shield. Cables meeting these specifications are good for up to 2000 meters.

VI-2

JUNCTION BOX GROUNDING Junction boxes should be electrically connected to earth ground. RS-485 LINK WIRING

In applications where the wiring cable is installed in conduit, the use of watertight conduit seals, drains, breathers, or equivalent is recommended to prevent damage to electrical connections caused by condensation within the conduit. ELECTROSTATIC DISCHARGE

The RS-485 link connecting the LCU and LIOU requires termination at both ends. The LCU provides termination for the beginning of the RS-485 link. All other devices, except for the device at the end of the line, shall have their termination resistor removed. The LIOU uses a termination resistor that must be removed if it is not at the end of the line. All devices sharing a common RS-485 link must have a common power return. PROTECTION AGAINST MOISTURE DAMAGE Moisture can have a detrimental effect on the performance of electronic devices. Therefore, it is important to take proper precautions during installation to ensure that moisture will not come in contact with the electrical connections or components of the system.

Many system electronic modules contain semiconductor devices that are susceptible to damage by electrostatic discharge. An electrostatic charge can build up on the skin and discharge when an object is touched. Therefore, use caution when handling, taking care not to touch the terminals or electronic components. For more information on proper handling, refer to Service Memo form 75-1005.

DETERMINING POWER REQUIREMENTS


Tables VI-4 and VI-5 are provided for calculating the total current requirements for those parts of the system requiring battery backup.

Table VI4Standby Current Requirements at 24 vdc

Device Type LCU Release Module Signal Audible Relay Module P. S. Monitor IDC/IDCGF/IDCSC UV Detector UV/IR Detector DCUEX DCU with H2S DCU with PointWatch ARM SAM Network Extender Power Supply Other

Number of Devices 1 X X X X X X X X X X X X X X X X

Standby Current 0.300 0.070 0.033 0.020 0.060 0.055 0.100 0.100 0.145 0.060 0.300 0.075 0.060 0.090 0.300 = = = = = = = = = = = = = = = = =

Total Current for Device Type 0.300

TOTAL STANDBY CURRENT FOR SYSTEM (IN AMPERES)

T0012B

VI-3

95-8470

Table VI5Alarm Current Requirements at 24 vdc

Device Type LCU Release Module Signal Audible Relay Module P. S. Monitor IDC/IDCGF/IDCSC UV Detector UV/IR Detector DCUEX DCU with H2S DCU with PointWatch ARM SAM Network Extender Power Supply Other

Number of Devices 1 X X X X X X X X X X X X X X X X

Alarm Current 0.340 0.165 0.120 0.090 0.060 0.090 0.120 0.120 0.160 0.075 0.320 0.120 0.120 0.090 0.300 = = = = = = = = = = = = = = = = + + =

Total Current for Device Type 0.340

Total Solenoid Load Total Signaling Load TOTAL ALARM CURRENT FOR SYSTEM (IN AMPERES)

T0013B

EQ2110PS, EQ2130PS AND EQ2175PS Refer to Table VI-6 for Power Supply ratings. BACKUP BATTERY Refer to Table VI-7 or VI-8 to calculate the minimum size of the backup battery (in amp hours). Select a sealed lead-acid battery with an adequate amp hour rating.

NOTE Connect two batteries in series for 24 volts. Be sure that the battery enclosure is adequately ventilated.

Table VI-6EQ21xxPS Power Supply Specifications

Characteristic EQ2110PS Input Voltage Input Current Input Frequency Supply Rating Maximum Alarm Current Maximum Standby Current Recharge Current Maximum Battery Capacity Maximum Deluge Standby Current 120 vac 4 Amps 60 Hz 10 Amps 10 Amps 3.33 Amps 6.67 Amps 100 AmpHours 1 Amp
VI-4

Power Supply EQ2130PS 120/208/240 vac 11/6/6 Amps 60 or 50 Hz 30 Amps 30 Amps 10 Amps 20 Amps 300 AmpHours 3 Amps EQ2175PS 120/208/240 vac 24/15/12 Amps 60 or 50 Hz 75 Amps 75 Amps 25 Amps 50 Amps 750 AmpHours 7.5 Amps

Table VI7Backup Battery Requirements for Automatic Release of Extinguishing Systems Except Deluge

Standby Current X

Standby Time* = 24 Hours

Standby Amp Hours

Alarm Current X

5 Minute Alarm Time* = 0.083 Hours

Alarm Amp Hours

Sum of Standby and Alarm Amp Hours Multiply by 1.1 (10% Safety Factor) Total Battery Amp Hour Requirement
* FM MINIMUM REQUIREMENT FOR EXTINGUISHING SYSTEMS IS 24 HOURS STANDBY TIME AND 5 MINUTES ALARM TIME.

= X
T0014A

Table VI-8Backup Battery Requirements for Deluge and Pre-Action Applications

Standby Current X

Standby Time* = 90 Hours

Standby Amp Hours

Alarm Current X

10 Minute Alarm Time* = 0.166 Hours

Alarm Amp Hours

Sum of Standby and Alarm Amp Hours Multiply by 1.1 (10% Safety Factor) Total Battery Amp Hour Requirement
* FM MINIMUM REQUIREMENT FOR DELUGE SYSTEMS IS 90 HOURS STANDBY TIME AND 10 MINUTES ALARM TIME.

= X
T0040A

BATTERY CHARGER Use the following formula to calculate the minimum battery charger size: Minimum = Alarm Current + Total Amp Hours Charge Rate 48

CAUTION Care should be taken when considering the final voltage at the device during AC power loss. With loss of AC power, the device voltage will drop over time as the batteries lose their charge. If extended periods of AC power loss are to be expected, either consider a heavier wire gauge than indicated in Table VI-1, or specify batteries with higher amphour ratings.

VI-5

95-8470

Section VII System Wiring


NOTE Specific installation requirements may differ depending on local installation practices and compliance with third party certifications. For local installation practices, consult the local authority having jurisdiction. For compliance with third party certifications, consult the appropriate appendix in this manual for additional specific installation requirements.

EQ2100PSM POWER SUPPLY MONITOR USED WITH EQ2110PS, EQ2130PS AND EQ2175PS POWER SUPPLIES
WIRING 1. Mount the power supply monitor in a Nationally Recognized Test Laboratory (NRTL) labeled enclosure. Refer to the Specifications section for mounting dimensions. NOTE Power supplies require unrestricted air flow for proper cooling. 2. Securely mount the cabinet. The cabinet should be electrically connected to earth ground. Connect the external wiring to the appropriate points as described below. Refer to Figure VII-1 for terminal block locations and Figures VII-2 and VII-3 for terminal identification.

3.

J1: POWER AND LON WIRING

LON ADDRESS SWITCHES

J3: AC INPUT

TERMINAL NO. 1

SWITCH NO. 1
+ +
+ +

1
+ + +

1
+

YELLOW LED RED LED GREEN LED

TERMINAL NO. 1

A1949

TERMINAL NO. 1 J2: CURRENT TEST POINTS TERMINAL "C" TERMINAL "B"

Figure VII-1Location of Terminals, LEDs and Switches on the Power Supply Monitor

VII-1

95-8470

WARNING Do not connect or disconnect wires with power applied. 4. Connect the 24 vdc power wires and the LON network cable to the appropriate points on J1, the Power & LON Wiring terminal block. See Figure VII2. Communication network connections: Connect to COM 2 terminals of the next device on the loop, A to A and B to B. Communication network connections: Connect to COM 1 terminals of the previous device on the loop, A to A and B to B. Connect the "+" terminal to the positive side of the 24 vdc power source. (Both "+" terminals are connected internally.) Connect the "-" terminal to the negative side of the 24 vdc power source. (Both "-" terminals are connected internally.) 6.

Connect the shield to the designated "shield" terminal. (The two shield terminals are connected internally.) Do not ground any shield at the monitor / power distribution cabinet. Insulate the shields to prevent shorting to the device housing or any other conductor. 5. Connect a two wire cable between the AC input of the power supply and terminals 1 and 4 on J3, the AC input terminal block on the power supply monitor. See Figure VII-3. Connect the B terminal on the power supply monitor to the negative () side of the backup battery. Connect a correctly sized circuit breaker or disconnect switch in the battery circuit as shown in Figure VII-4. If a circuit breaker is used, it must be rated between 150% and 250% of the total load. Connect the C terminal on the power supply monitor to the negative () side of the power supply. Wire the power distribution circuit breakers to the output of the power supply. Circuit breaker ratings must be between 150% and 250% of the full load rating. Check all field wiring to ensure that the proper connections have been made.

COM 1 -

COM 2 -

24 VDC -

7.

8.

9.
1 SHIELD

COM 1

SHIELD

10. Set the LON address for the power supply monitor. Refer to Figure VII-1 for rocker switch location. Refer to LON/SLC Device Address Switch Setting in the Switch Setting section (Section VIII) of the Eagle Quantum system manual (form number 958470) for complete information regarding the switch setting procedure. 11. Connect the mounting frame to chassis (earth) ground.

24 VDC

SHIELD 1 AC INPUT 120 / 240 VAC

10

A 2 NOT USED

11

COM 2 3 NOT USED

12

SHIELD 4
A1947 A1950

AC INPUT 120 / 240 VAC

Figure VII-2J1: Power and LON Wiring Terminal

Figure VII-3J3: AC Input Terminal

VII-2

POWER SUPPLY MONITOR

1 AC MONITOR 4

C B

12 11 10 9 8 7 6 5 4 3 2 1

H N G 24 VDC OUTPUT

+ POWER DIST CKT #1 + POWER DIST CKT #2 + POWER DIST CKT #3

AC BREAKER

DC BREAKER

+ POWER DIST CKT #4 BATTERY CIRCUIT BREAKER

POWER SUPPLY NRTL CABINET

12 VDC

12 VDC

C1951

BACKUP BATTERIES

NOTES 1. AC INPUT SELECTABLE (THROUGH THE OIS) FOR 120 / 208 / 240 VAC. 2. BATTERY SIZE CALCULATED BASED ON SYSTEM LOAD. 3. CIRCUIT BREAKER RATINGS MUST BE BETWEEN 150% AND 250% OF FULL LOAD RATING. 4. REMOVAL OF TERMINAL PLUG WITH POWER APPLIED TO TERMINALS B AND C WILL DAMAGE THE POWER SUPPLY MONITOR.

Figure VII-4A Typical Application Wiring Connections for a Power Supply Monitor, Power Supply and Backup Batteries

STARTUP Turn on the power supply and allow the voltage to stabilize at 27 volts before closing the circuit to the battery. MEASURING BATTERY VOLTAGE AND CHARGING CURRENT Measure the battery voltage at terminals 3 and 4 of terminal block J2.

To measure the battery charging current, connect a digital voltmeter to terminals 1 and 2 of terminal block J2. See Figure VII-5. The voltmeter will read 1 millivolt (0.001 volt) for each 2 amperes of current. Current in Amperes = Meter reading in millivolts x 2 Example: A reading of 50 millivolts indicates a charging current of 100 amperes.

CURRENT SENSE

CURRENT SENSE

BATTERY

4
A1952

BATTERY +

Figure VII-5J2: Current Test Points VII-3 95-8470

EQ2100LCU SERIES LOCAL CONTROL UNIT


All external wiring to the LCU is connected to the terminal blocks that are an integral part of the LCU backplane, extending below the card rack. To access the terminals, the cover must be removed. The terminals are arranged in three rows and numbered from left to right. Row A is closest to the bottom of the board, row B in the center, and row C on top. See Figure VII-6 for wiring terminal identification. Terminals 1 to 3 Logic controller relay contacts:

NOTE EOL terminals are provided to allow convenient installation of EOL resistors. Installing an EOL resistor at terminals 1D and 1E or 2D and 2E places it across the normally open and common contacts of the alarm and supervisory relays. Note that the Trouble relay is energized during normal operation, therefore the EOL resistor goes across the normally closed contacts at 3D and 3E. To insert the resistor lead into the terminal, depress the orange lever. Terminals 4 to 6 DC Power. (EQ2101LCU only) Two separate 24 vdc power supplies with common ground are required. Connect terminals A4 and B4 to one supply and A5 and B5 to the other. A trouble condition is indicated if either supply is missing. Connect terminals A6 and B6 (AUX OUT) to the auxiliary terminals on the LIOU. This is typically used for powering solenoids, horns, strobes, etc. Row A terminals = () Row B terminals = (+)

Terminals A1 (NO), = B1 (COM), = C1 (NC), = Alarm relay 1D and 1E = EOL Terminals A2 (NO), = B2 (COM), = C2 (NC), = Supervisory relay 2D and 2E = EOL

Terminals A3 (NO), = B3 (COM), = C3 (NC), = Trouble relay 3D and 3E = EOL.

P7

TROUBLE

ALARM EOL

SUPER

GATEWAY RELAYS FAULT P2 P1

LON/SLC

MAIN 24V

GND FLT

AUX 24V

A RS-485 B CHASSIS EARTH

DC2

DC1

ROW D

3E 3D 2E 2D 1E 1D

K1

K2

K3

K4

INPUT 3

INPUT 2

INPUT 1

SHIELD

R+ RXD COM TXD T+ RXD COM TXD

RESET

NC

NC

ROW C

14

15

16

17

18

COM2

COM

COM

ROW B

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

1 NO

COM1

NO

ROW A

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

TO OIS GATEWAY RELAY CONTACTS RESET GATEWAY RELAYS UNSUPERVISED INPUTS TO LOGIC CONTROLLER RS-485 TO LIOU CHASSIS (EARTH) GND 24 VDC TO STANDARD LCU RACK USED WITH EQ2101 RACK ONLY, SEE TEXT
D1859

TO COMMUNICATION NETWORK

LOGIC CONTROLLER RELAY CONTACTS

Figure VII6Wiring Terminals on the LCU

VII-4

Terminal 7

System power. When used with the standard LCU rack (EQ2100LCU), terminals A7 and B7 are power input terminals for supplying the 24 vdc power from the power supply to the LCU. When used with the optional LCU rack (EQ2101LCU), terminals A7 and B7 are power output terminals for supplying isolated power with ground fault monitoring from the LCU to the main power terminals on the LIOU and field devices. Output current must not exceed 2.8 amperes. A7 terminal = () B7 terminal = (+)

contacts etc. Wire the contacts between the A and B terminals. These inputs can be used in the programmable logic. Terminal 13 Remote reset. Connect a normally open, momentary closure switch between terminals A13 and B13 to reset the gateway relays from a remote location when the relays are programmed for latching operation. Terminals 14 to 18 Gateway relay contacts.

Terminal 8

Ground fault monitor. Terminal B8 (ground fault monitor) must be connected to A8 (chassis ground) to ensure proper functioning of the ground fault monitoring circuitry.

Terminals A14 (NO), = B14 (COM), = C14 (NC), = Relay K1 Terminals A15 (NO), = B15 (COM), = C15 (NC), = Relay K2 Terminals A16 (NO), = B16 (COM), = C16 (NC), = Relay K3 Terminals A17 (NO), = B17 (COM), = C17 (NC), = Relay K4 Terminals A18 (NO), = B18 (COM), = C18 (NC), = Fault relay Terminals 19 to 22 RS-232 serial communication ports. These two serial ports are electrically isolated from each other and from the system. A19 = Port 2 common (COM). Connects to common of the other device. B19 = Port 2 transmit (TXD). Connects to receive of the other device. B20 = Port 2 receive (RXD). Connects to transmit of the other device.

IMPORTANT The chassis ground stud must be connected to earth ground. Terminal 9 RS-485 link. Connect to the power supply or LIOU rack RS485 terminals. Be sure to observe polarity: Connect A9 terminal to the RS485 A terminal of the next device on the link. Connect B9 terminal to the RS-485 B terminal of the next device on the link. All devices sharing a common RS-485 link must have a common system power return. Terminals 10 to 12 Three unsupervised inputs to the Logic Controller. These inputs are typically used for contact inputs such as switches, pushbuttons, relay

VII-5

95-8470

NOTE Connection to Port 2 can also be made using the 9-pin (DB9) connector P7. Pin 2 = TXD = B19 Pin 3 = RXD = B20 Pin 5 = COM = A19 WARNING Do not plug or unplug the connector unless the area is known to be non-hazardous. A20 = (T+) Not used. A21 = Port 1 common (COM). Connects to common of the other device. B21 = Port 1 transmit (TXD). Connects to receive of the other device. B22 = Port 1 receive (RXD). Connects to transmit of the other device. A22 = (R+) Not used. Terminals 23 to 25 LON/SLC signaling circuit terminals, with separate shield connections. The LON/SLC is polarity sensitive due to ground fault monitoring. A23 = shield connection for COM 1 A24 = B side of signaling circuit for COM 1 A25 = A side of signaling circuit for COM 1 B23 = shield connection for COM 2 B24 = B side of signaling circuit for COM 2 B25 = A side of signaling circuit for COM 2

NOTE B23 is connected directly to chassis ground. A23 is connected to chassis ground through a filter network. IMPORTANT When installing the three modules in the LCU rack, the Logic Controller must be in the left hand position, the Gateway in the center position, and the LON Isolator in the right hand position.

VII-6

EQ2100LIOU LOCAL OUTPUT UNIT


CAUTION All personnel installing or servicing the LIOU must wear a grounding strap to avoid generating static electricity that can destroy or damage integrated circuits. The circuit boards are shipped in antistatic plastic bags and should be kept in these bags until the time of installation. If the circuit boards are removed from the rack, they should be replaced in the appropriate bags. Never pack the boards in styrofoam or plastic pellets. CAUTION LIOU modules must not be installed or removed in a powered-up system. Always disconnect both AC and battery power before installing the modules. BACKPLANE WIRING Power and communication wiring to the LIOU is connected to the terminal block on the LIOU backplane. See Figure VII-7. RS-485 LINK WIRING The assembly is controlled and supervised by the Local Control Unit (LCU) using an RS-485 serial communication link. Up to four LIOUs can be controlled by the LCU adding a maximum of 24 output modules to the system. The RS-485 link connecting the LCU and LIOU requires termination at both ends. The LCU provides termination for the beginning of the RS-485 link. If the LIOU is not the last unit in the line, termination resistor R1 must be removed. See Figure VII-7 for location. Two sets of RS-485 terminals are provided to allow daisy-chained wiring. A terminals are connected to A terminals and B terminals to B terminals of the next device on the link. RS-485 A Connect one terminal to A of the previous device on the link and the other terminal to A of the next device on the link.

POWER WIRING Main Power () Connect to the () terminal of the system power terminals on the EQ2101LCU (terminal A7).

CAUTION Do not connect a breaker or other disconnect device to power minus () with RS-485 connected. Doing so will damage the RS-485 circuitry. Main Power (+): Connect to the (+) terminal of the system power terminals on the EQ2101LCU (terminal B7).

Auxiliary Power Input (): Connect to the () auxiliary terminal of the EQ2101LCU (terminal A6). Auxiliary Power Input (+): Connect to the (+) auxiliary terminal of the EQ2101LCU (terminal B6). Auxiliary Power Output: J3, J4, J5 These terminals are provided to distribute 24 vdc auxiliary power to the auxiliary power terminals on the release and signal audible modules. Maximum total current must not exceed 8 amperes. Connect to earth ground.

Chassis Ground: Module Wiring

Wiring to the external devices that are controlled by the LIOU modules is connected to the terminal strip on the corresponding module.

RS-485 TERMINATION RESISTOR P1 P2 P3 P4 P5 P6


AUX POWER

RS-485 B

Connect one terminal to B of the previous device on the link and the other terminal to B of the next device on the link.

J3 J4 J5

+
B A

+
RS-485 MAIN AUX

All devices sharing a common RS-485 link must have a common power return.
B1860

Figure VII-7Wiring Terminals on LIOU Backplane

VII-7

95-8470

RELAY MODULE
WIRING Refer to Figure VII-8 for identification of relay wiring terminals. SWITCH SETTING Each relay module must be assigned a unique address (1 to 8) using switch assemblies S1 and S2 on the relay module circuit board. See Figure VII-9 for the location of switches on the circuit board. Refer to Table VII-1 to determine the correct switch positions for the desired address. Note that switch S1-1 is not used.
RESET SWITCH ON 1 2 1 2
A1862

S3

TROUBLE LED

DS1 S2 S1

MODULE ADDRESS SWITCHES

1 2 3 4 5 6 7 8 9 10 11 12 NOTES: 1. ALL RELAY OUTPUTS ARE SHOWN IN NORMAL STANDBY CONDITION. 2. ALL CONTACTS ARE THE DRY CONTACT TYPE. 3. OUTPUTS OF ALL RELAYS ARE NOT SUPERVISED. 4. RATINGS ARE 2A MAXIMUM AT 24 VDC; 1A AT 120 VAC. 5. THE MAXIMUM NUMBER OF BOARDS PER SYSTEM IS EIGHT. 6. THE MAXIMUM WIRE SIZE IS 12 AWG, ONE WIRE PER TERMINAL. K4 K3 K2 12 RELAY MODULE K1 TB1

Figure VII9Location of Switches on Relay Module

Table VII1Switch Positions for Relay Module Addresses


B1861

Figure VII8Wiring Terminals for Relay Module

Module Address 1 2 3 4 5 6 7 8

Switch Position S12 S21 S22 ON ON ON ON OFF OFF OFF OFF ON ON OFF OFF ON ON OFF OFF ON OFF ON OFF ON OFF ON OFF
T0016A

VII-8

RELEASE MODULE
WIRING Refer to Figure VII-10 for identification of wiring terminals. To ensure adequate operating voltage for the output device, the maximum wiring length from the power source to the output device must not exceed the values shown in Table VII-2 for automatic release applications or Table VII-3 for deluge and pre-action applications. (For solenoids, this wire length includes both the wiring from the power supply to the agent release module and the wiring from the module to the solenoid. For squibs, use only the wire length from the power supply to the module, since the resistance of the wire from the module to the squib is included when determining the value of the compensating resistor.) JUMPERS When the auxiliary power input is used, jumpers W1 and W2 must be cut. See Figure VII-11 for the locations of jumpers and switches on the circuit board.

SWITCH SETTING Each release module in the LIOU must be assigned a unique address (1 to 8). This is accomplished using switches S3-2, S4-1 and S4-2 on the release module circuit board. Refer to Table VII-4 to determine the correct switch positions for the desired address. Switches S1 and S3-1 must be set for solenoid or explosive initiator (squib). Refer to Table VII-5 for switch positions.

RELEASE SOLENOIDS
TB1 1 2 3 4 5 6 7 8 9 10 11 12 3 4 5 RELEASE CIRCUITS 6

+ + + + + +

AUXILIARY POWER

+ +
ONE SOLENOID SEE NOTE 3.

SIGNAL CIRCUITS

TB1 3 4 5 6

+ +

SOLENOID ONE SEE NOTE 3. SOLENOID TWO

SIGNAL CIRCUITS
TB1 7 8 9 10 11 12
B1863

INITIATOR RELEASE
TB1 3

NOTES: 1. USED TO COMPENSATE FOR 10 OHMS MAXIMUM CIRCUIT RESISTANCE. 1. RESISTOR MUST BE RATED AT 1 WATT MINIMUM. 2. MAXIMUM NUMBER OF INITIATORS PER CIRCUIT IS 12. 2. EACH CIRCUIT MUST NOT EXCEED 10 OHMS INCLUDING CABLE RESISTANCE. 3. USE A 1200 OHM RESISTOR AS A LOAD FOR TEST PURPOSES. 4. POLARITY SHOWN IS FOR ACTIVATED CONDITION. POLARITY IS REVERSED DURING MONITORING CONDITION.

CKT #1

10K EOL 4 5

+ +

SEE NOTE 1.

+ + +
CKT #3 10K EOL CKT #2 10K EOL

SEE NOTE 2.

Figure VII-10Wiring Terminals for Release Module

VII-9

95-8470

ON S4 S3 DS1 1 2 1 2

RESET SWITCH TROUBLE LED

S2

MODULE ADDRESS ASSIGNMENT

Table VII-2Maximum Wiring Length for Release Applications


J1

Device

Maximum Wire Length in Feet 12 AWG 14 AWG 16 AWG 18 AWG

S1 SQB SOL

W1

890181* 899175* 895630-000* 897494* 486500-001* 31-199932-004* Squib

150 150 150 190 1500 150 190 190

100 100 100 120 1000 100 120 120

60 60 60 75 600 60 75 75
T0028B

1 W2

TB1

400

12 RELEASE MODULE
A1864

2 Amp Load
*Fenwal Solenoid

Figure VII11Location of Switches and Jumpers on Release Module

Table VII-3Maximum Wiring Length for FM Approved Solenoids for Deluge and Pre-Action Applications

Solenoids Manufacturer Skinner ASCO ASCO Skinner Skinner Skinner Model LV2LBX25 8210A107 8210G207 73218BN4UNLVNOC111C2 73212BN4TNLVNOC322C2 71395SN2ENJ1NOH111C2

Maximum Wire Length in Feet (Meters) 12 AWG 800 (244) 520 (158) 825 (251) 860 (262) 400 (122) 860 (262) 14 AWG 500 (152) 325 (99) 520 (158) 540 (165) 250 (76) 540 (165) 16 AWG 310 (94) 200 (61) 325 (99) 340 (104) 160 (49) 340 (104) 18 AWG 200 (61) 130 (40) 205 (62) 215 (66) 100 (30) 215 (66)
T0041B

Table VII-4Switch Positions for Release Module Addresses

Table VII-5Switch Positions for Solenoid/Explosive Initiator

Module Address 1 2 3 4 5 6 7 8

Switch Position S32 S41 S42 ON ON ON ON OFF OFF OFF OFF ON ON OFF OFF ON ON OFF OFF ON OFF ON OFF ON OFF ON OFF
T0017A

Switch S1 Position Assignments S1 SOL SQB Single Solenoid X X Dual Solenoid X Explosive Initiators X

Switch S31 Position Assignments OFF ON


VII-10

Solenoids Explosive Initiator


T0018A

SIGNAL AUDIBLE MODULE


WIRING The signal audible module can support NFPA style Y or style Z field wiring. Refer to Figures VII-12 through VII15 and determine which of the wiring styles will be used. EOL resistor value is 10K ohms. NOTE Polarity shown is for activated condition. Polarity is reversed for monitoring condition. To ensure adequate operating voltage for the signaling device, the maximum wiring length from the power source to the output device must not exceed the values shown in Table VII-6. (This wire length includes both the wiring from the power supply to the signal audible module and the wiring from the module to the signaling device.) JUMPERS/SWITCHES Note that each wiring diagram is accompanied by its corresponding jumper/switch setting table. This table shows the correct positions for jumper plugs W1 through W8 and switches SW2-1 and SW3-2. For jumper plugs W1 through W8, ON = jumper installed, OFF = jumper removed. When the auxiliary power input is used, jumpers W9 and W10 must be cut. See Figure VII-16 for the locations of jumpers and switches on the circuit board.
AUXILIARY POWER

TB1

+24VDC
RET

1 2

10K EOL 10K EOL + + 10K EOL

5 CIRCUIT 1 6 CIRCUIT 2 7 8 9

10 11 + 12 +

CIRCUIT 3

W1 OFF ON

W2 ON

W3 ON

JUMPERS W4 W5 OFF OFF

W6 OFF

W7 OFF

W8 ON

SWITCHES SW21 SW32 ON OFF


C1866

Figure VII13Two Style Y and One Style Z Circuits for Signal Audible Module

TB1

+24VDC
AUXILIARY POWER RET

1 2

10K EOL + + 10K EOL

5 6 CIRCUIT 1 7 8 9

10 11 + +12

CIRCUIT 3

ADDRESS SWITCH SETTING Each signal audible module must be assigned a unique address (1 to 8). This is accomplished using switches SW2-2, SW1-1 and SW1-2 on the signal audible module circuit board. Refer to Table VII-7 to determine the correct switch positions for the desired address.
TB1 JUMPERS W4 W5 ON OFF

W1 OFF

W2 OFF

W3 OFF

W6 OFF

W7 OFF

W8 ON

SWITCHES SW21 SW32 OFF OFF


C1867

Figure VII14Two Style Z Circuits for Signal Audible Module

+24VDC
AUXILIARY POWER RET

1 2 AUXILIARY POWER

TB1

+24VDC
RET

1 2

10K EOL + + 10K EOL 10K EOL

5 6 CIRCUIT 1 7 10K EOL 8 9 CIRCUIT 3 CIRCUIT 4 10K EOL 10K EOL 10 11 + 12 + 10K EOL + + 5 CIRCUIT 1 6 CIRCUIT 2 7 8 9 CIRCUIT 3 CIRCUIT 4

10 11 + +12

W1 OFF

W2 OFF

W3 OFF

JUMPERS W4 W5 ON ON

W6 ON

W7 ON

W8 OFF

SWITCHES SW21 SW32 OFF ON


C1865

W1 OFF ON

W2 ON

W3 ON

JUMPERS W4 W5 OFF ON

W6 ON

W7 ON

W8 OFF

SWITCHES SW21 SW32 ON ON


C1868

Figure VII12One Style Z and Two Style Y Circuits for Signal Audible Module VII-11

Figure VII15Four Style Y Circuits for Signal Audible Module 95-8470

Table VII6Maximum Wiring Length from Nominal 24 VDC Power Source to Signaling Device

Maximum Wire Length in Feet (Meters) 12 AWG 14 AWG 16 AWG (4 mm2)* (2.5 mm2)* (1.5 mm2)* One 2 Ampere Load Two 2 Ampere Loads 190 (58) 95 (29) 120 (37) 60 (18) 75 (23) 35 (11)
T0029A

* Approximate Metric Equivalent.

SIGNAL AUDIBLE MODULE

W11 U1
MICROCONTROLLER WITH EPROM

RESET SWITCH TROUBLE LED

SW4 DS1

ON SW1 SW2 SW3 1 2 1 2 1 2 J1

MODULE ADDRESS ASSIGNMENT

W3

W4 W9

W1

W10

W2

TB1

W5

W6 12 W7 W8

A1869

Figure VII16Location of Switches and Jumpers on Signal Audible Module

Table VII7Switch Positions for Signal Audible Module Addresses

Module Address 1 2 3 4 5 6 7 8

Switch Position SW22 SW11 SW12 ON ON ON ON OFF OFF OFF OFF ON ON OFF OFF ON ON OFF OFF ON OFF ON OFF ON OFF ON OFF
T0019A

VII-12

FIELD DEVICES
EQ2200IDC SERIES INITIATING DEVICE CIRCUIT
GND

2.

Connect external system wiring to the appropriate terminals on the terminal block inside the junction box. See Figure VII-17 for terminal block location and Figure VII-18 for terminal identification. The input to the IDC consists of one or more normally open switches (momentary pushbuttons are not recommended), with a 10K ohm, 1/4 watt EOL resistor in parallel across the last switch. An EOL resistor must be installed on both IDC inputs (including unused inputs). Wiring impedance must not exceed 500 ohms. Check the wiring to ensure proper connections.

1.

Remove the cover from the junction box.

10

WARNING The hazardous area must be de-classified prior to removing a junction box cover with power applied.

11 12

Figure VII17IDC Terminal Wiring Board Mounted in Six-Port Junction Box

13 14

A1870

3. 4.

IDC

MANUAL PULL STATION OR OTHER CONTACT DEVICE

1 EOL (10K)

Set the node address for the device. Refer to Device Address Switch Setting in the Switch Setting section (Section VIII) of this manual for complete information regarding the switch setting procedure. Install the communication module inside the junction box. Be sure that the keyed ribbon cable is properly connected. Inspect the junction box O-ring to be sure that it is in good condition and properly installed. Lubricate the O-ring and the threads of the junction box cover with a thin coat of an appropriate grease to ease installation and ensure a watertight enclosure. The recommended lubricant is a silicone free grease, available from Det-Tronics. Place the cover on the junction box. Tighten only until snug. Do not over tighten.

CIRCUIT 1

+
CIRCUIT 2

3 EOL (10K)

5.

A COM 2 B

6.

7 COM SHIELD 8

14

13

24 VDC

A COM 1 B

12

10

11

+
A1871

Figure VII18Terminal Configuration for Initiating Device Circuit

VII-13

95-8470

EQ2200IDCGF SERIES INITIATING DEVICE CIRCUIT GROUND FAULT


+
3

RELAY CONTACT FOR MONITORING BATTERY. CONTACT OPENS WITH BATTERY TROUBLE CONDITION. 68K OHM RESISTOR

1.

Securely mount the aluminum enclosure. The enclosure should be electrically connected to earth ground. Connect the external wiring to the appropriate points on the terminal block. See Figure VII-17 for terminal block location and Figure VII-19A for terminal identification. Check all field wiring to ensure that the proper connections have been made. Install the communication module inside the junction box. Be sure that the keyed ribbon cable is properly connected.

INPUT

A COM 2

RELAY CONTACT FOR MONITORING AC POWER. CONTACT CLOSES ON LOSS OF AC POWER.

2.

7 COM SHIELD 8

14

13

24 VDC

3.

A COM 1 B

12

10

11

+
B1922

4.

NOTE: ENCLOSURE AND/OR MOUNTING BRACKET MUST BE CONNECTED TO EARTH GROUND.

5.

Set the node address for the device. Refer to LON/SLC Device Address Switch Setting in the Switch Setting section (Section VIII). Inspect the enclosure O-ring to be sure that it is in good condition and properly installed. Lubricate the O-ring and the threads of the enclosure cover to ease both installation and future removal of the cover. The recommended lubricant is a silicone free grease available from Detector Electronics. If the installation uses catalytic type combustible gas sensors, it is imperative that lubricants containing silicone not be used, since they will cause irreversible damage to the sensor. Place the cover on the enclosure. Tighten only until snug. Do not over tighten.

Figure VII-19AEQ2200IDCGF Wiring Terminal

6.

EQ2200IDCSC SERIES INITIATING DEVICE CIRCUIT SHORT CIRCUIT The EQ2200IDCSC Initiating Device Circuit Short Circuit (IDCSC) provides two supervised digital inputs for use with dry contact inputs from devices such as relays, pushbuttons, key switches, etc. The IDCSC supports ANSI/NFPA 72 Class B Style C (3 state, open/short circuit) supervised input circuits. Each circuit uses its own end of line (EOL) resistor for monitoring circuit continuity and a series resistor for each contact. 1. Remove the cover from the junction box. Remove the communication module from the junction box. Connect external system wiring to the appropriate terminals on the terminal block inside the junction box. See Figure VII-17 for terminal block location and Figure VII-19B for terminal identification. The input to the IDCSC consists of one or more normally open switches, with a 10K ohm, 1/4 watt EOL resistor in parallel across the last switch. An EOL resistor must be installed on both IDCSC inputs (including unused inputs). Wiring impedance must not exceed 500 ohms. A 3.3K ohm resistor must be installed in series with each switch. Check the wiring to ensure proper connections.

Device Configuration 2. When configuring the EQ2200IDCGF, its device type should be configured as an initiating device circuit (IDC). Both inputs must be configured for a trouble condition. Circuit 1 Open indicates a 24 VDC ground fault condition. Active indicates a +24 VDC ground fault condition. Active indicates a loss of AC input power. Open indicates a loss of battery power.

Circuit 2

3.

VII-14

4.

Set the node address for the device. Refer to Device Address Switch Setting in the Switch Setting section (Section VIII) of this manual for complete information regarding the switch setting procedure. Install the communication module inside the junction box. Be sure that the keyed ribbon cable is properly connected. Inspect the junction box O-ring to be sure that it is in good condition and properly installed. Lubricate the O-ring and the threads of the junction box cover with a thin coat of an appropriate grease to ease installation and ensure a watertight enclosure. The recommended lubricant is a silicone free grease, available from Det-Tronics. Place the cover on the junction box. Tighten only until snug. Do not over tighten.

EQ2200UV UV FLAME DETECTOR 1. Remove the sensor housing from the bulkhead (turn counterclockwise). Install the sensor module and replace the sensor housing. See Figure VII-20. NOTE If the detector is equipped with a cover locking device, it must be loosened using a 5/32 hexagonal (Allen) wrench (see Figure VII-21). 2. Mount the swivel mounting bracket using 1/4 inch (M6) screws with a length of at least 1 inch (25 mm). The mounting surface should be free of vibration. Allow adequate space around the swivel to facilitate aiming and wiring of the detector. Armored flexible conduit should be used for the final 3 feet (one meter) of the cable run to allow for aiming and alignment of the detector. Attach the detector to the swivel mounting bracket. Remove the rear housing from the bulkhead. Connect the wires to the appropriate screw terminals on the terminal block. See Figure VII-22. Connect the cable shields to the terminals provided. Set the rocker switches on the DIP switch assembly on the electronic module for the desired address. Refer to Device Address Switch Setting in the Switch Setting section of this manual for complete information regarding the switch setting procedure. Install the electronic module, ensuring that the connector is aligned correctly. Tighten the three captive screws that hold the electronic module in place. See Figures VII-20 and VII-23. Replace the rear housing and hand tighten to ensure proper sealing. See Figures VII-20 and VII-21. Aim the detector at the potential hazard and tighten the nut.

5.

6.

3. 4. 5.
MANUAL PULL STATION OR OTHER CONTACT DEVICE IDCSC

+
CIRCUIT 1

1 EOL (10K) 3.3 K 3.3 K

6.

+
CIRCUIT 2

3 EOL (10K)

3.3 K

A COM 2 B

7.

7 COM SHIELDS 8

14

8.
24 VDC

13

A COM 1 B

12

9.

10

11

+
A2076

Figure VII-19BTerminal Identification for EQ2200IDCSC

10. Check the viewing window surface (Figure VII-24) and ensure that: A) the oi source (UV test lamp opening) is located on top B) the split in the oi reflective ring is not aligned with the UV test lamp opening on the detector module C) the split in the oi ring is directed downward to prevent a buildup of contaminants between the oi ring and the viewing window.

VII-15

95-8470

CONDUIT ENTRY BULKHEAD SENSOR MODULE

SENSOR HOUSING

REAR HOUSING

ELECTRONIC MODULE O-RING CONDUIT ENTRY O-RING

oi RING

DETECTOR WINDOW

A1840

Figure VII20EQ2200UV Detector Assembly

REAR HOUSING

BLIND HOLE

SCREW

COVER LOCKING CLAMP

CATCH

CATCH SCREW

COVER LOCKING ASSEMBLY

STRAP

BARREL

LENS CAP

A1841

Figure VII21Optional Cover Locking Devices on UV Detector

VII-16

11. Clean the viewing window and oi ring using the procedure described in the Maintenance section.
+
24 VDC COM 1

12. Install any optional accessories (such as air shields).

1 2 5 6 7

COM 2

9 10

EQ2200UVHT HIGH TEMPERATURE UV FLAME DETECTOR WARNING Do not open any junction box or device enclosure when power is applied without first de-classifying the hazardous area.
A1873

TERMINALS 1 AND 2 24 VDC POWER SUPPLY (+) TERMINALS 3 AND 4 POWER SUPPLY () TERMINAL 5 COM 1 A TERMINAL 6 COM 1 B TERMINAL 7 SHIELD TERMINAL 8 COM 2 A TERMINAL 9 COM 2 B TERMINAL 10 SHIELD

Electronic Module Assembly


Figure VII22EQ2200UV Detector Wiring Terminals

MOUNTING SCREWS

1. Mount the device on a solid surface that is free of vibration. 2. Remove the cover from the junction box.

ADDRESS SWITCHES

3. Loosen the three captive screws that hold the electronic module to the terminal wiring board and remove the module. See Figure VII-25. 4. Loosen (do not remove) the two captive screws that secure the terminal wiring board inside the junction box, and remove the terminal wiring board. See Figure VII-26. (The terminal blocks are located on the bottom side of the terminal wiring board.) 5. Connect the UV detector wires to the appropriate points on the P3 terminal. Connect the 24 vdc power wires and the communication network cable to the appropriate points on the P2 terminal. See Figure VII-27 for terminal identification. Note that the plug-in terminals can be removed to facilitate wiring.

BULKHEAD

A1895

Figure VII23Electronic Module Mounted Inside Bulkhead

oi RING

LOOSEN THREE SCREWS TO REMOVE ELECTRONIC MODULE

UV TEST LAMP* OPENING

ELECTRONIC MODULE

TERMINAL WIRING BOARD

SPLIT IN oi RING (MUST BE POSITIONED ON THE DOWNWARD SIDE OF UNIT WHEN MOUNTED) LEDs
A1992

* UV TEST LAMP OPENING MUST NOT BE ALIGNED WITH SPLIT IN oi RING

B1891

Figure VII-25Electronic Module Installed on Terminal Wiring Board Figure VII24Viewing Window of UV Detector

VII-17

95-8470

LOOSEN TWO SCREWS TO REMOVE TERMINAL WIRING BOARD

P2 1 SHIELD

COM 1

SHIELD

+
24 VDC

6 UV FLAME DETECTOR TERMINAL BLOCK A

A1993

P3 1

+
SHIELD

Figure VII-26 Terminal Wiring Board with Electronic Module Removed

10

NOTE Terminals 4 and 9 (shield) are connected internally, as are terminals 5 and 8 (24 vdc +) and terminals 6 and 7 (24 vdc ). 6. Re-install the terminal wiring board inside the junction box. 7. Set the rocker switches on the DIP switch assembly on the electronic module for the desired address. Refer to LON/SLC Device Address Switch Setting in the Switch Setting section of this manual for complete information regarding the switch setting procedure. 8. Re-install the electronic module, ensuring that the connector is aligned correctly. Tighten the three captive screws that hold the electronic module in place. 9. Replace the junction box cover and hand tighten to ensure proper sealing. UV Flame Detector WIRING REQUIREMENTS Wiring to the UV detector must be between 12 and 18 AWG with a minimum voltage rating of 600 volts rms and a minimum temperature rating of 125C. The use of shielded cable is highly recommended to provide maximum protection from RFI/EMI interference. 1. Mount the Swivel Mounting Bracket using 1/4 inch (M6) screws with a length of at least 1 inch (25 mm). The mounting surface should be free of vibration. Allow adequate space around the swivel to facilitate

4 5

11

COM 2

12

SHIELD

A1989

Figure VII-27 EQ2200UVHT Wiring Terminal

aiming and wiring of the detector. Armored flexible conduit should be used for the final 3 feet (one meter) of the cable run to allow for aiming and alignment of the detector. 2. Attach the detector to the Swivel Mounting Bracket. 3. Disassemble the detector enclosure by turning the housing cover counterclockwise. See Figure VII-28. NOTE If the detector is equipped with a cover locking device, it must be loosened using a hexagonal (Allen) wrench. 4. Connect the wires to the appropriate screw terminals on the detector terminal block. See Figure VII-27 for terminal identification. Do not ground the shield to the detector housing. (Tape off the shield and leave it disconnected.) 5. Remove the UV sensor tube module from its shipping package. When handling the sensor tube module, be careful not to touch the sensor tube, since oil from the skin can attenuate UV radiation, reducing the sensitivity of the tube. 6. Using the index pin as a guide, install the sensor module on the detector terminal block.

VII-18

7. Re-assemble the detector housing. If the detectors are equipped with cover locking devices, loosen the clamp sufficiently so that the catch can be seated in the blind hole provided on the terminal cap. The clamp must then be fastened securely around the detector barrel by tightening with the proper tool. 8. Clean the viewing window and o i ring using the procedure described in the Maintenance section. 9. Check the viewing window surface (Figure VII-24) and ensure that: A) The oi source (UV test lamp opening) is located on top. B) The split in the oi reflective ring is not aligned with the UV test lamp opening on the detector module. C) The split in the oi ring is directed downward to prevent a buildup of contaminants between the oi ring and the viewing window. 10. Aim the detector at the potential hazard and tighten the nut on the swivel mounting bracket. 11. Install any optional accessories (such as air shields).

EQ2200UVIR UV/IR FLAME DETECTOR 1. Mount and wire the detector. A. Mount the detector and mounting bracket assembly on the wall or ceiling. Observe the following guidelines: The mounting surface should be free of excessive heat and vibration. Allow adequate space around the swivel to facilitate aiming and wiring of the detector. Armored flexible conduit should be used for the final 3 feet (one meter) of the cable run to allow for aiming and alignment of the detector. Position the conduit below the detector and orient the detector with the conduit entry at the bottom or either side of the detector (never at the top). This will prevent condensation in the conduit from entering the detector junction box. B. Remove the junction box cover. C. Connect the leadwires to the appropriate screw terminals on the terminal block inside the junction box. See Figures VII-29 and VII-30 for location of the terminal block and Figure VII-31 for terminal identification. Connect the shield of the power cable to earth ground at the power source. Connect the shields for the LON/SLC cable as indicated. Do not ground the shields at the detector housing.

TERMINAL BLOCK

INDEX PIN

UV SENSOR TUBE MODULE

A1994

HOUSING COVER

Figure VII-28High Temperature UV Detector

VII-19

95-8470

JUNCTION BOX

JUNCTION BOX COVER IR CONNECTOR PLUG IR SENSOR MODULE

oi TEST LAMP (2)

O-RING IR SENSOR HOUSING UV TERMINAL BLOCK IR oi RING BANANA PLUG

UV SENSOR MODULE oi TEST LAMP LED (2)

O-RING

UV SENSOR HOUSING

A1913

UV oi RING

Figure VII29UV/IR Detector Parts Identification

GROUND SCREW

"D" CONNECTOR

A1912

TERMINAL BLOCK

LON/SLC ADDRESS SWITCHES SERVICE SWITCH * LED **

NOTES: ** SERVICE SWITCH NOT FOR USE IN THE FIELD. NOTES: ** ILLUMINATION OF LED INDICATES AN ELECTRONIC MALFUNCTION.

Figure VII30UV/IR Detector Junction Box with Cover Removed

VII-20

2.
1

Set the rocker switches. A. Set the rocker switches on the DIP switch assembly for the desired LON/SLC address. Refer to LON/SLC Device Address Switch Setting in Section VIII Switch Setting. B. Re-install the junction box cover. The six screws must be tight to ensure the explosionproof and watertight integrity of the junction box.

+
POWER

COM 1

3.

Complete the installation. A. Aim the detector at the potential hazard.

SHIELD

COM 2

B. Inspect and clean (if necessary) the detector viewing windows and oi rings by following the instructions in the Maintenance section of this manual. C. Check the detector viewing windows (Figure VII-32) and ensure that: the oi test lamps are located at the top or side of the sensor module (when viewed from the front) the opening in the oi ring is at the bottom. This will ensure proper operation of the oi system and also minimize the accumulation of moisture and contaminants between the oi ring and the viewing window. D. Install any optional accessories (such as air shields).

SHIELD
A1914

10

Figure VII31EQ2200UVIR Detector Wiring Terminals

*oi TEST LAMPS AT TOP OR SIDE

oi TEST LAMP
LED (2)

UV SENSOR HOUSING

oi RING OPENING DOWN

*oi TEST LAMP


(2) LED (2) IR SENSOR HOUSING

DETECTOR MUST BE ORIENTED WITH CABLE/CONDUIT ENTRY AT BOTTOM (PREFERRED) OR SIDE TO ELIMINATE DRAINAGE INTO JUNCTION BOX.
H1327

Figure VII32Front View of the UV/IR Detector

VII-21

95-8470

EQ2200DCU DIGITAL COMMUNICATION UNIT USED WITH DET-TRONICS H2S/O2 SENSORS OR OTHER TWO-WIRE 4 TO 20 MA DEVICES Determine the best mounting locations for the detectors. Whenever practical, detectors should be placed where they are easily accessible for calibration. WARNING Do not apply power to the system with the cover removed unless the area has been verified to be free of combustible gases or vapors. The DCU utilizes the following: 1. A terminal wiring board mounted at the bottom of the junction box.

COMMUNICATION MODULE

STANDOFFS (4)

TERMINAL WIRING BOARD

A1571

2.

A communication module mounted above the terminal wiring board using the standoffs provided. See Figure VII-33.

Figure VII33Printed Circuit Boards in Universal DCU

Assembly and Wiring Procedure Attach the sensor to the DCU enclosure. Do not overtighten. If a sensor separation kit is being used, attach the sensor to the separation kit junction box and wire the device as described in the Sensor Separation section. CAUTION The sensor threads can be coated with an appropriate grease to ease installation. Also lubricate the cover threads. (See Ordering Information for part number). Connect the external wiring to the appropriate terminals on the DCU terminal wiring board. Refer to Figure VII34 for terminal identification. See Figure VII-35 for an example of a Det-Tronics electrochemical sensor connected to a DCU. Attach the communication module to the standoffs as shown in Figure VII-33. Connect the ribbon cable from the terminal wiring board to the communication module. Set the address for the device. Refer to Device Address Switch Setting in the Switch Setting section of this manual for complete information regarding the switch setting procedure. Check the wiring to ensure proper connections, then pour the conduit seals and allow them to dry (if conduit is being used). NOTE Before placing the cover back on the enclosure following completion of assembly and wiring, inspect the enclosure O-ring to be sure that it is in good condition and properly installed. Lubricate the O-ring and the threads of the cover with a thin coat of an appropriate grease to ease installation. Refer to the Ordering Information section for the part number of the recommended grease (available from Detector Electronics). If the installation uses catalytic type combustible gas sensors, it is imperative that lubricants containing silicone NOT be used, since they will cause irreversible damage to the sensor. Place the cover on the enclosure. Tighten only until snug. Do not over tighten.

SENSOR SEPARATION FOR DCU WITH H2S AND O2 SENSORS Since the transmitter for the electrochemical sensor is already mounted within the sensor housing, simply mount the entire sensor assembly to the sensor separation kit junction box and wire it to terminals 2 and 4 inside the DCU, the same as a regular (without sensor separation) installation. Connect the shield to the ground terminal in the DCU junction box. Refer to Table VII-8 for separation distance limitations for H2S and O2 sensors.

VII-22

EQ2200DCU DIGITAL COMMUNICATION UNIT USED WITH POINTWATCH


POINTWATCH CALIBRATE 1

4 TO 20 MA IN

Determine the best mounting locations for the detectors. Whenever practical, detectors should be placed where they are easily accessible for calibration. WARNING Do not apply power to the system with the cover removed unless the area has been verified to be free of combustible gases and vapors. The DCU utilizes the following:
14

SENSOR POWER

A COM 2 B

7 COM SHIELD 8

1.

A terminal wiring board mounted at the bottom of the junction box. A communication module mounted above the terminal wiring board using the standoffs provided. See Figure VII-33.

13

24 VDC

2.

A COM 1 B
A1726

12

10

11

Assembly and Wiring Procedure


Figure VII34Wiring Configuration for DCU
DCU H2S/TOXIC/O2

POINTWATCH CALIBRATE

Attach the PointWatch to the DCU enclosure. Do not over-tighten. If a sensor separation kit is being used, attach the sensor to the separation kit junction box and wire the device as described in the Sensor Separation section. Refer to the PointWatch instruction manual (form number 95-8440) for complete installation and application information. Refer to Figure VII-36 when wiring a PointWatch IR gas detector and a DCU. The wiring code for PointWatch is: Red = Black = White = Yellow = Green = + (24 vdc) (common) 4 to 20 ma signal Calibration input Chassis ground

4 TO 20 MA IN

BLACK

SENSOR POWER

RED

GREEN

A COM 2 B

7 COM SHIELD 8

14

13

24 VDC

A COM 1 B
A1875

12

10

11

Set the address for the device. Refer to Device Address Switch Setting in the Switch Setting section of this manual for complete information regarding the switch setting procedure.

Figure VII35Electrochemical Sensor Connected to DCU

Table VII8 Maximum Separation Distances Electrochemical Sensor to DCU

Wire Size (AWG) 18 16

Maximum Wiring Distance Feet 5700 9000 Meters 1750 2800


T0020A

VII-23

95-8470

DCU

POINTWATCH

POINTWATCH CALIBRATE

YELLOW

EQ2200DCUEX DIGITAL COMMUNICATION UNIT USED WITH DET-TRONICS COMBUSTIBLE GAS SENSORS Determine the best mounting locations for the detectors. Whenever practical, detectors should be placed where they are easily accessible for calibration. Always orient the junction box with the sensor pointing down. WARNING Do not apply power to the system with the cover removed unless the area has been verified to be free of combustible gases or vapors. The DCUEX uses the following: 1. The terminal wiring board is mounted at the bottom of the junction box. The transmitter board is mounted above the terminal wiring board. The communication module is mounted above the transmitter board.

4 TO 20 MA IN

WHITE

SENSOR POWER

BLACK

RED

A COM 2 B

GREEN

7 COM SHIELD 8

14

13

24 VDC

A COM 1 B
A1876

12

2.

10

11

3.
Figure VII36PointWatch Connected to DCU

Sensor Separation for DCU with PointWatch Shielded four wire cable is recommended for connecting the detector junction box to the DCU. Cable with a foil shield is recommended. The shield of the cable should be open at the detector junction box and connected to earth ground at the DCU junction box. Refer to Table VI-1 to determine the maximum allowable wiring from the PointWatch to the power supply (through the DCU). NOTE To ensure proper operation, it is essential to maintain a minimum of 18 vdc (including ripple) at the PointWatch detector.

The boards are connected to each other using the standoffs provided. See Figure VII-37. NOTE Be sure to note correct orientation of the transmitter board. If the transmitter board is rotated 180 from proper orientation, the device will not operate correctly a LON communication fault will result. See Figure VII37. Assembly and Wiring Procedure Connect the external wiring to the appropriate terminals on the DCU terminal wiring board. See Figure VII-38. Attach the sensor to the DCU enclosure. Do not overtighten. If a sensor separation kit is being used, attach the sensor to the separation kit junction box and wire the device as described below.

VII-24

COMMUNICATION MODULE

SWITCHES ON SAME SIDE (RIGHT)

TRANSMITTER BOARD

TERMINAL WIRING BOARD

CAUTION The sensor threads can be coated with an appropriate grease to ease both the initial installation and future replacement of the sensor. Detector Electronics offers a silicone free grease that is especially suited for use with catalytic type combustible gas sensors (see Ordering Information for part number). The use of other lubricants is not recommended, since some materials can cause irreversible damage to the sensing element. SILICONE based lubricants or compounds must NEVER be used. Screw the transmitter board to the standoffs as shown in Figure VII-37. Connect the sensor plug to the transmitter board. Attach the communication module to the standoffs mounted on the transmitter board. Connect the ribbon cable from the terminal wiring board to the communication module. Set the address for the device. Refer to Device Address Switch Setting in the Switch Setting section of this manual for complete information regarding the switch setting procedure.

CORRECT ORIENTATION OF TRANSMITTER BOARD

COMMUNICATION MODULE

SWITCHES ON OPPOSITE SIDES (WRONG)

TRANSMITTER BOARD

TERMINAL WIRING BOARD

G N O R W

DCU TERMINAL BOARD

DCU TRANSMITTER BOARD1 (MIDDLE BOARD)

POINTWATCH CALIBRATE

INCORRECT ORIENTATION OF TRANSMITTER BOARD

4 TO 20 MA IN

SIG

SENSOR POWER

2 4

A COMMUNICATION MODULE COM 2 B

7 TRANSMITTER BOARD COM SHIELD 8

14

13

24 VDC

STANDOFFS (4) COM 1 TERMINAL WIRING BOARD


B1877

12

10

11

B1570

NOTES: 1 Catalytic Combustible Gas Sensor Plugs into Connector Pins on the Middle Board inside the Junction Box. 2 Connections Wired at the Factory.

Figure VII37Printed Circuit Boards in Combustible Gas DCU

Figure VII38DCU Transmitter Board Connected to Terminal Wiring Board

VII-25

95-8470

Sensor Separation with DCUEX


+
GR N

If the installation requires mounting the sensor in a different location than the DCUEX, observe the following guidelines. When separating a combustible gas sensor from the DCUEX, two options exist: 1. Preferred Method

+
ELECTROCHEMICAL SENSOR
GR
SPARE CAL 4-20 RET +24

N
CHASSIS CAL 4-20 RET +24

Mount the transmitter PC board inside the sensor separation junction box. This assembly can be separated from the DCUEX by up to 1000 feet using three conductor 18 AWG shielded cable. (Regardless of separation distance, operating voltage at the transmitter MUST be at least 18 vdc to ensure proper operation.) See Figure VII-39. Assemble the DCUEX without the transmitter board similar to the DCU as shown in Figure VII-33. Plug the sensor into P2 on the transmitter board. Use a three conductor 18 AWG shielded cable to connect P1 on the transmitter board to terminals 2, 3 and 4 on the DCU terminal board (see Figure VII-39). Connect the shield to the ground terminal in the DCUEX junction box. 2. Alternate Method. If the transmitter board must be mounted separate from the sensor (high temperature applications, etc.), separate the sensor only, leaving the transmitter PC board inside the DCUEX enclosure. When using this installation option, see Table VII-9 for maximum wiring distances.
TRANSMITTER BOARD
GND

POINTWATCH

P1

+
4 TO 20

P2

NOTE: ALWAYS ORIENT JUNCTION BOX WITH CATALYTIC SENSOR POINTING DOWN.
SENSOR
B1878

Mount the sensor directly to the separation kit junction box. Use three conductor shielded cable for the connection between the terminal block in the separation kit junction box and P1 on the transmitter board. A plug with screw terminals is provided for connecting the cable to P1 on the transmitter board. Observe the wiring color code. Connect the shield to the ground terminal in the DCUEX junction box.

CATALYTIC SENSOR

Figure VII39Sensor Separation Kits

Table VII9Maximum Separation Distances Combustible Gas Sensor to DCU (Alternate Method)

Wire Size 18 AWG (1.0 mm2)* 16 AWG (1.5 mm2)* 14 AWG (2.5 mm2)* 12 AWG (4.0 mm2)*

Maximum Separation Distance Feet Meters 40 60 100 150 12 18 30 45

*Approximate Metric Equivalent.

VII-26

EQ2500ARM SERIES AGENT RELEASE MODULE Wiring To ensure adequate operating voltage for the output device, the maximum wiring length from the power source to the output device must not exceed the values shown in Table VII-10 for automatic release applications or Table VII-11 for deluge and pre-action applications. (For solenoids, this wire length includes both the wiring from the power supply to the agent release module and the wiring from the module to the solenoid. For squibs, use only the wire length from the power supply to the module, since the resistance of the wire from the module to the squib is included when determining the value of the compensating resistor.) Refer to Figure VII-40 for identification of wiring terminals. Terminals 1 to 4 Output terminals Connect a single solenoid between terminals 1 and 4. Connect dual solenoids between terminals 1 and 2, and between terminals 3 and 4. NOTE For testing purposes, a load resistor of 1200 to 1500 ohms @ 1 watt can be placed across terminals 1 and 4. When using an explosive initiator, connect the resistor between terminals 1 and 2 and the initiator between terminals 3 and 4, as shown in Figure VII-40. CAUTION Do not intermix different types of initiators in the release circuit.

Table VII10Maximum Wiring Length for Release Applications

Device

Maximum Wire Length in Feet 12 AWG 14 AWG 16 AWG 18 AWG

890181* 899175* 895630-000* 897494* 486500-001* 31-199932-004* Squib 2 Amp Load


*Fenwal Solenoid

150 150 150 190 1500 150 190 190

100 100 100 120 1000 100 120 120

60 60 60 75 600 60 75 75
T0028B

400

Terminals 5 to 10

LON/SLC signaling circuit terminals Be sure to observe polarity when wiring the LON/SLC.

5 A side of signaling circuit for COM 2 6 B side of signaling circuit for COM 2 7 and 8 shield connection 9 A side of signaling circuit for COM 1 10 B side of signaling circuit for COM 1

Table VII-11Maximum Wiring Length for FM Approved Solenoids for Deluge and Pre-Action Applications

Solenoids Manufacturer Skinner ASCO ASCO Skinner Skinner Skinner Model LV2LBX25 8210A107 8210G207 73218BN4UNLVNOC111C2 73212BN4TNLVNOC322C2 71395SN2ENJ1NOH111C2

Maximum Wire Length in Feet (Meters) 12 AWG 800 (244) 520 (158) 825 (251) 860 (262) 400 (122) 860 (262) 14 AWG 500 (152) 325 (99) 520 (158) 540 (165) 250 (76) 540 (165) 16 AWG 310 (94) 200 (61) 325 (99) 340 (104) 160 (49) 340 (104) 18 AWG 200 (61) 130 (40) 205 (62) 215 (66) 100 (30) 215 (66)
T0041B

VII-27

95-8470

Terminals 11 to 14

24 vdc power input Connect the module power supply to terminals 12 and 13. If an auxiliary output supply is used for powering solenoids, it should be connected to terminals 11 and 14.

Jumpers Terminals 13 and 14 are connected by jumper JP2 and terminals 11 and 12 are connected by jumper JP3. These two jumpers (JP2 and JP3) must be cut if an auxiliary output power supply is being used. See Figure VII-41 for the locations of jumpers on the circuit board. When an explosive initiator is being used, jumper JP1 must be cut. If a solenoid is used, the jumper must remain in.

SINGLE SOLENOID

DUAL SOLENOIDS

Address Switch Setting


1 2

A COM 2 B

Each device on the LON/SLC must be assigned a unique address. This is accomplished by setting DIP switches on the release module circuit board. The valid address range is from 5 to 250. For complete information on address switch setting, refer to LON/SLC Device Address Switch Setting in Section VIII. For convenience in determining the correct positions for address switches, refer to the table Address Switch Settings at the back of this manual.
14

7 COM SHIELD 8

13

24 VDC

A COM 1 B

12

10

11

+
JP1 JP2 JP3

EXPLOSIVE INITIATOR OPTION

1 2 3 4 5 6 7 8 9 10

1 SEE NOTE 2. 2
A1902

Figure VII41Agent Release Module Wiring Terminals and Jumpers

4 NOTES: 1. JUMPER JP1 MUST BE REMOVED IF EXPLOSIVE INITIATOR IS USED. 2. RESISTOR IS USED TO COMPENSATE FOR 10 OHMS CIRCUIT RESISTANCE. RESISTOR MUST BE RATED 1 WATT MINIMUM (WIRE-WOUND RESISTOR PREFERRED). WHEN MEASURING THE TOTAL RELEASE CIRCUIT RESISTANCE, USE AN OHM METER WITH A CURRENT OUTPUT OF 10 MA MAXIMUM. 3. MAXIMUM NUMBER OF EXPLOSIVE INITIATORS PER CIRCUIT IS 12. EACH CIRCUIT MUST NOT EXCEED 10 OHMS INCLUDING CABLE RESISTANCE.

B1900

Figure VII40Wiring Configuration for Agent Release Module

VII-28

11 12 13 14

NOTE: TERMINALS 12 AND 13 ARE FOR MODULE POWER SUPPLY. TERMINALS 11 AND 14 ARE FOR AUXILIARY OUTPUT POWER SUPPLY. JUMPERS JP2 AND JP3 MUST BE REMOVED IF AN AUXILIARY POWER SUPPLY IS USED.

EQ2500SAM SERIES SIGNAL AUDIBLE MODULE Wiring To ensure adequate operating voltage for the signaling device, the maximum wiring length from the power source to the output device must not exceed the values shown in Table VII-12. (This wire length includes both the wiring from the power supply to the signal audible module and the wiring from the module to the signaling device.) Refer to Figure VII-42 for identification of wiring terminals.

Table VII12Maximum Wiring Length from Nominal 24 VDC Power Source to Signaling Device

Maximum Wire Length in Feet (Meters) 12 AWG 14 AWG 16 AWG (4 mm2)* (2.5 mm2)* (1.5 mm2)* One 2 Ampere Load Two 2 Ampere Loads 190 (58) 95 (29) 120 (37) 60 (18) 75 (23) 35 (11)
T0029A

* Approximate Metric Equivalent.

1 10K EOL

Terminals 1 to 4

Output terminals Connect the first output device between terminals 1 and 2, and the second between terminals 3 and 4. Polarity shown in Figure VII-42 is for monitoring condition, polarity is reversed when activated. Each circuit must have a 10 kohm EOL resistor.

OUTPUT 1*

+
OUTPUT 2*

3 10K EOL

A COM 2 B

7 COM SHIELD 8

14

13

24 VDC

Terminals 5 to 10

LON/SLC signaling circuit terminals


COM 1

12

Be sure to observe polarity when wiring the LON/SLC.


*

10

11

+
B1901

5 A side of signaling circuit for COM 2 6 B side of signaling circuit for COM 2 7 and 8 shield connection 9 A side of signaling circuit for COM 1 10 B side of signaling circuit for COM 1 Terminals 11 to 14 24 vdc power input Connect the module power supply to terminals 12 and 13. If an auxiliary output supply is used for powering signaling devices, it should be connected to terminals 11 and 14.

POLARITY SHOWN IS FOR MONITORING CONDITION, POLARITY IS REVERSED WHEN ACTIVATED.

NOTE: TERMINALS 12 AND 13 ARE FOR MODULE POWER SUPPLY. TERMINALS 11 AND 14 ARE FOR AUXILIARY OUTPUT POWER SUPPLY. JUMPERS JP1 AND JP2 MUST BE REMOVED IF AN AUXILIARY POWER SUPPLY IS USED.

Figure VII42Wiring Configuration for Signal Audible Module

Jumpers Terminals 13 and 14 are connected by jumper JP2 and terminals 11 and 12 are connected by jumper JP1. These two jumpers (JP1 and JP2) must be cut if an auxiliary output power supply is being used. See Figure VII-43 for the locations of jumpers on the circuit board.

VII-29

95-8470

EQ2400NE SERIES NETWORK EXTENDER 1.


JP1 JP2

Securely mount the aluminum enclosure. Remove the cover from the network extender enclosure. Connect the 24 vdc power lead wires and the communication network cable to the appropriate points on the terminal block. See Figure VII-44A for terminal location within the junction box and Figure VII-44B for terminal identification. Refer to Table VII13 to determine maximum wiring length.
TERMINAL NO. 1

2.

1 2 3 4 5 6 7 8 9 10

Figure VII43Signal Audible Module Wiring Terminals and Jumpers

Address Switch Setting Each device on the LON/SLC must be assigned a unique address. This is accomplished by setting DIP switches on the modules circuit board. The valid address range is from 5 to 250. For complete information on address switch setting, refer to LON/SLC Device Address Switch Setting in Section VIII. For convenience in determining the correct positions for address switches, refer to the table Address Switch Settings at the back of this manual.
1 12

11 12 13 14

3.

B1903

A2021

Figure VII-44ANetwork Extender Wiring Terminal Location

SHIELD

COM 1

SHIELD

24 VDC

SHIELD

10

11

COM 2

12

SHIELD

A1947

Figure VII-44BNetwork Extender Wiring Terminal Identification

VII-30

COM 1 -

Communication network connections: Connect to COM 2 terminals of the next device on the loop, A to A and B to B. Communication network connections: Connect to COM 1 terminals of the previous device on the loop, A to A and B to B. Connect the "+" terminal to the positive side of the 24 vdc power source. (Both "+" terminals are connected internally.) Connect the "-" terminal to the negative side of the 24 vdc power source. (Both "-" terminals are connected internally.)

TYPICAL APPLICATIONS
Figure VII-45 shows a power supply monitor wired on a LON between a UV detector and a DCU. Figure VII-46 illustrates the power and communication wiring for a UV detector, an IDC and a DCU, connected to a standard LCU (EQ2100LCU) and an LIOU. Figure VII-47 illustrates the power and communication wiring for a UV detector, an IDC and a DCU, connected to the optional LCU (EQ2101LCU) and an LIOU. Figure VII-48 shows the power and communication wiring for a UV/IR detector, an EQ2500SAM and an EQ2500ARM, connected to a standard LCU (EQ2100LCU) and an LIOU. Figure VII-49 shows a network extender wired between a UV detector and a DCU. Figure VII-50 shows a high temperature UV detector wired between a standard UV detector and a DCU.

COM 2 -

24 VDC -

4.

Connect the shields to the two designated "shield" terminals. The two shield terminals are connected internally to ensure shield continuity. Do not ground either shield at the network extender enclosure. Insulate the shields to prevent shorting to the device housing or any other conductor. Check all field wiring to ensure that the proper connections have been made. Inspect the enclosure O-ring to be sure that it is in good condition and properly installed. Lubricate the O-ring and the threads of the enclosure cover to ease both installation and future removal of the cover. The recommended lubricant is a silicone free grease available from Detector Electronics. If the installation uses catalytic type combustible gas sensors, it is imperative that lubricants containing silicone not be used, since they will cause irreversible damage to the sensor. Place the cover on the enclosure. Tighten only until snug. Do not over tighten.

5.

6.

Table VII-13Maximum Wiring Length from Nominal 24 vdc Power Source to Network Extender

Wire Size 18 AWG (1.0 mm2)* 16 AWG (1.5 mm2)* 14 AWG (2.5 mm2)*

Maximum Wiring Distance Feet Meters 2200 3500 5600 650 750 1700

* Approximate Metric Equivalent.

VII-31

95-8470

INSTALLATION CHECKLIST
The following checklist is provided as a means of double checking the system to be sure that all phases of system installation are complete and have been performed correctly. 1. Junction boxes are mounted securely and detectors are pointing in the proper direction. All cable shields are properly insulated and grounded. All junction box covers are tightly installed. Explosion-proof and watertight electrical fittings have been installed at all junction box entries as required for the hazardous location.

5. 6.

Sensor and LON/SLC wiring is correct. Power wiring is installed and power source is operational. External loads are properly connected and EOL resistors are installed. DIP switches are set correctly. Record this information for future reference. Devices are properly installed in the mounting racks.

7.

8.

2.

9.

3. 4.

10. Proper ventilation is provided (if needed) to prevent equipment over-heating. Proceed to System Startup.

EQ2200UV

EQ2100PSM

EQ2200DCU

TO POWER DISTRIBUTION TERMINALS

3 4

9 10

COM 2 12 11 10 9 SHIELD B A SHIELD 8 + 7 6 5 + 4 SHIELD 3 2 B A 1 SHIELD 1 2 3 4 5

14 13 12 11 6 7 8 9 10

TO PREVIOUS LON DEVICE

G
B1953

Figure VII-45A Typical Application LON Connections for a Power Supply Monitor Wired Between a UV Detector and a DCU

VII-32

+ + SHIELD A B COM 1 TO NEXT LON DEVICE

SHIELD

POINTWATCH CALIBRATE 4 TO 20 MA IN POWER + SENSOR A B COM 2 COM 1

24 VDC 1 2

A B SHIELD 5 6 7 COM 1

24 VOLTS DC

24 VDC

COM 2

EQ2100LCU
COM2

EQ2200UV

EQ2200IDC

EQ2200DCU
TO GAS DETECTOR POWER SUPPLY

COM1 24 VOLTS DC COM 1 8 9 COM 2 14 1 2 3 4 5 6 7 8 9 10 1 2 3 13 12 11 4 5 6 10 14 7 13 8

A 25 24 VDC 1 2 A 5 B SHIELD 6 7

24 VOLTS DC

B 24

+
3 4

SHIELD 23

12 9

11 10

22

P1

21

20

P2

RXD + RXD COM TXD TXD + RXD COM TXD

SHIELD

SHIELD

SHIELD

SHIELD

19 COM 2 COM 1

SENSOR

FAULT

4 TO 20 MA IN

CIRCUIT 1

CIRCUIT 2

18

K4

17

K3

POINTWATCH CALIBRATE

16

K2

GATEWAY RELAYS

15 NO

K1

NC

14

COM

RESET 13

INPUT 1 12

INPUT 2 11

VII-33
BATTERY CKT BREAKER NO ROW A C BUS BAR B 12 11 10 9 B A SHIELD SHIELD 8 + 7 6 5 + 4 SHIELD

INPUT 3 10

RS-485

A B CHASSIS GND FLT EARTH

EQ2100LIOU
B J3 J1 A

MAIN 24V

AUX 24V

RS-485

DC1

AUX POWER

DC2

+ + + +

MAIN AUX

TROUBLE

SUPER

ALARM

3E 3D 2E 2D 1E 1D

NC

COM

ROW C

ROW B 3 B 2 A 1 SHIELD

J1

+
24 VOLT BATTERY BACKUP

J3
SYSTEM POWER SUPPLY 1 2 3 H N A C LINE 4

C1879

95-8470

POWER SUPPLY MONITOR

Figure VII46A Typical System Field Devices Connected to EQ2100LCU (Standard)

+
A B COM 1 J4 J5

+ +


A B

+ +
A B COM 2 POWER J2

+ +


A B

+
24 VDC COM 2 COM 1

EQ2101LCU
COM2

EQ2200UV

EQ2200IDC

EQ2200DCU

COM1 24 VOLTS DC COM 1 8 9 COM 2 14 1 2 3 4 5 6 7 8 9 10 1 2 3 13 12 11 4 5 6 10 14 7

TO GAS DETECTOR POWER SUPPLY 24 VOLTS DC 24 VDC 1 2 A 5 B SHIELD 6 7

A 25

B 24

+
3 4

SHIELD 23

13 8

12 9

11 10

22

P1

21

20

P2

RXD + RXD COM TXD TXD + RXD COM TXD

SHIELD

SHIELD

SHIELD

SHIELD

19 COM 2 COM 1

SENSOR

FAULT

4 TO 20 MA IN

CIRCUIT 1

CIRCUIT 2

18

K4

17

K3

POINTWATCH CALIBRATE

16

K2

GATEWAY RELAYS

15

K1 NO

NC

14

COM

RESET 13

INPUT 1 12

TWO 24VOLT DC POWER SUPPLIES PER NFPA 72

VII-34
NO ROW A

INPUT 2 11

INPUT 3 10

RS-485

A B CHASSIS GND FLT EARTH

EQ2100LIOU
B J3 J1 A

MAIN 24V

AUX 24V

6 RS-485

DC1

AUX POWER

DC2

+ + + +

MAIN AUX

TROUBLE

SUPER

ALARM

3E 3D 2E 2D 1E 1D

NC

COM

ROW C

ROW B

B1880

Figure VII47A Typical System Field Devices Connected to EQ2101LCU (Optional)

+
B A B COM 1 J4 J5

+ +

+ +
A B COM 2 POWER J2

+ +


A B

EQ2100LCU

EQ2200UVIR

EQ2500SAM

EQ2500ARM

COM2

COM1 24 VOLTS DC SINGLE SOLENOID 24 VOLTS DC

A 25 COM 1 COM 2

B 24 DUAL SOLENOIDS 14 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 13 12 11 6 14 7 13

SHIELD 23

SHIELD

SHIELD

12 8 9

11 10

22 1 2 3 4 5 6 7 8 9 10

P1

21

20

P2

RXD + RXD COM TXD TXD + RXD COM TXD

SHIELD

SHIELD

SHIELD

SHIELD

19 COM 2 COM 1

FAULT

OUTPUT 1

OUTPUT 2

18

K4

17

K3

16

K2

GATEWAY RELAYS

15

K1

NC

14

NO

COM

RESET 13

INPUT 1 12

INPUT 2 11

INPUT 3 10

RS-485

A B CHASSIS GND FLT EARTH

EQ2100LIOU
B J3 J1 A

MAIN 24V

AUX 24V

RS-485

DC1

AUX POWER

DC2

+ + + +

MAIN AUX

TROUBLE

SUPER BATTERY CKT BREAKER

ALARM

3E 3D 2E 2D 1E 1D

NC

NO

COM

ROW C

ROW A

ROW B C BUS BAR B 12 11 10 9 B A SHIELD SHIELD 8 + 7 6 5 + 4 SHIELD 3 B 2 A 1 SHIELD

+
24 VOLT BATTERY BACKUP

J3
SYSTEM POWER SUPPLY 1 2 3 H N A C LINE 4

C1910

95-8470

POWER SUPPLY MONITOR

Figure VII48A Typical System UV/IR Detector, EQ2500SAM and EQ2500ARM Connected to a Standard EQ2100LCU

+
A B COM 1 J4 J5


A B

+ + +
A B COM 2 J2

+ + +
COM 1


A B

+
A B A B

+ + +

VII-35
COM 2

24 VDC

EQ2100LCU
COM2 TO GAS DETECTOR POWER SUPPLY 24 VOLTS DC COM 1 8 9 COM 2 12 11 10 9 8 7 6 5 B A 4 3 2 1 1 2 3 4 5 6 10 14 7 13 8 12 9 11 10 24 VDC 1 2 A 5 B SHIELD 6 7

EQ2200UV

EQ2401NE

EQ2200DCU

COM1

A 25

B 24

+
3 4

SHIELD 23

22

P1

21

SHIELD

SHIELD

SHIELD

SHIELD

20

P2 24 VDC COM 2 COM 1

RXD + RXD COM TXD TXD + RXD COM TXD

SHIELD

SHIELD

19

SENSOR

FAULT

4 TO 20 MA IN

18

K4

17

K3

POINTWATCH CALIBRATE

16

K2

GATEWAY RELAYS

15 NO

K1

NC

14

COM

RESET 13

INPUT 1 12

INPUT 2 11

VII-36
NO BATTERY CKT BREAKER C BUS BAR B 12 11 10 9 B A SHIELD SHIELD 8 + 7 6 5 + 4 SHIELD 3 B 2 A

INPUT 3 10

RS-485

A B CHASSIS GND FLT EARTH

EQ2100LIOU
B J3 J1 A

MAIN 24V

AUX 24V

RS-485

DC1

AUX POWER

DC2

+ + + +

MAIN AUX

TROUBLE

SUPER

ALARM

3E 3D 2E 2D 1E 1D

NC

COM

ROW C

ROW A

ROW B 1 SHIELD

+
24 VOLT BATTERY BACKUP

J3
SYSTEM POWER SUPPLY 1 2 3 H N A C LINE 4

C1940

POWER SUPPLY MONITOR

Figure VII-49A Typical System - Network Extender Wired Between UV Detector and DCU

+
A B COM 1 J4 J5


B J2 A

POWER

A COM 2

+ +

24 VDC

COM 2

COM 1

EQ2200UVHT EQ2200UV
D C B A

EQ2100LCU
COM2

EQ2200DCU
TO GAS DETECTOR POWER SUPPLY 24 VOLTS DC COM 1 8 9 COM 2 12 11 10 9 8 7 6 5 B A 4 3 2 1 1 2 3 4 5 6 10 5 1 14 7 13 8 12 9 11 10 4 3 2

COM1

A 25 24 VDC 1 2 A 5 B SHIELD 6 7

B 24

+
3 4

SHIELD 23

22

P1

21

SHIELD

SHIELD

SHIELD

SHIELD

20 24 VDC

P2 COM 2 COM 1

RXD + RXD COM TXD TXD + RXD COM TXD

SHIELD

SHIELD

19

SENSOR

FAULT

4 TO 20 MA IN

18

K4

17

K3

POINTWATCH CALIBRATE

16

K2

GATEWAY RELAYS

15 NO

K1

NC

14

COM

RESET 13

INPUT 1 12

INPUT 2 11

VII-37
BATTERY CKT BREAKER NO ROW A C BUS BAR B 12 11 10 9 B A SHIELD SHIELD

INPUT 3 10

RS-485

A B CHASSIS GND FLT EARTH

EQ2100LIOU
B J3 J1 A

MAIN 24V

AUX 24V

RS-485

DC1

AUX POWER

DC2

+ + + +

MAIN AUX

TROUBLE

SUPER

ALARM

3E 3D 2E 2D 1E 1D

NC

COM 8 + 7 6 5 + 4 SHIELD 3 B 2 A 1 SHIELD

ROW C

ROW B

J3
SYSTEM POWER SUPPLY 1 2 3 H N A C LINE 4

POWER SUPPLY MONITOR

24 VDC

24 VOLT BATTERY BACKUP

B1990

Figure 50A Typical System EQ2200UVHT Wired Between a Standard UV Detector and a DCU

+
A B COM 1 J4 J5

+ +


B COM 2 COM 1 A

POWER J2

A COM 2

+ +

95-8470

Section VIII Switch Setting


GATEWAY
The gateway contains four 8-position DIP switch assemblies that are used for: Selecting serial port 1 software parameters Setting the gateway Modbus/Allen Bradley address Selecting gateway relay operation (latching/nonlatching) Setting the gateway type and address. Refer to Figure VIII-1 to identify the function of the DIP switches. Refer to Figure VIII-2 to locate the DIP switch assemblies on the side of the gateway.

S5 Hardware Serial Port Configuration Verify that S5 switches are set as follows: 1 Open 2 Closed 3 Closed 4 Open 5 and 6 Closed 7 and 8 Open. S6 Software Serial Port Configuration for Port 1 1, 2, and 3 Determine the desired baud rate, then refer to Table VIII-1 for the proper switch settings. (19,200 is recommended and cannot be exceeded in the LCU.) 4 Parity enable. Open = no parity. Closed = parity enabled. 5 Parity type. Open = odd. Closed = even. 6 Stop bits. Open = 1 stop bit. Closed = 2 stop bits.

S8 LON CONFIGURATION 1 2 3 4 5 6 7 8 CLOSED OPEN NON-LATCHING GATEWAY RELAYS SELECT CONFIGURATION PORT PORT 2 OPERATION PORT 1 OPERATION GATEWAY ADDRESS BIT 1 (MSB) GATEWAY ADDRESS BIT 0 (LSB) S7 MODBUS ADDRESS 1 2 3 4 5 6 7 8 MODBUS ADDRESS BIT 7 (MSB) MODBUS ADDRESS BIT 6 MODBUS ADDRESS BIT 5 MODBUS ADDRESS BIT 4 MODBUS ADDRESS BIT 3 MODBUS ADDRESS BIT 2 MODBUS ADDRESS BIT 1 MODBUS ADDRESS BIT 0 (LSB) S6 SOFTWARE SERIAL PORT CONFIGURATION (CHANNEL 1 ONLY) 1 2 3 4 5 6 7 8 OPEN NUMBER OF DATA BITS (OFF = 7, ON = 8) NUMBER OF STOP BITS (OFF = 1, ON = 2) PARITY TYPE (OFF = ODD, ON = EVEN) PARITY ENABLE (OFF = NO PARITY, ON = PARITY ENABLED) BAUD RATE BIT 2 (MSB) 0 = 1200 BAUD RATE BIT 1 1 = 2400 BAUD RATE BIT 0 (LSB) 2 = 9600 3 = 19200 S5 HARDWARE SERIAL PORT CONFIGURATION 1 2 3 4 5 6 7 8 OPEN OPEN CLOSED CLOSED OPEN CLOSED CLOSED OPEN

OPEN = OFF CLOSED = ON

C1888

Figure VIII1Gateway DIP Switch Assignments

A1546

S5 S6

S7

S8

Figure VIII2Gateway DIP Switch Location

VIII-1

95-8470

7 Data bits. Closed = 8 data bits (required for Modbus or Allen Bradley communication). Open = 7 data bits (not recommended). 8 Open. NOTE Serial port 2 is fixed at 9600 baud, one stop bit and even parity.

Table VIII1Baud Rate Selection - Switches S6-1, S6-2, S6-3

BAUD RATE 1,200 2,400 9,600 19,200 Op = Open Cl = Closed

SWITCH POSITIONS 1 2 3 Op Cl Op Cl Op Op Cl Cl Op Op Op Op
T0022B

Table VIII2Gateway Address Switch Settings

S7 Port 1: Modbus/Allen Bradley Address


Gateway Address S8-1 Op Cl Op Cl S8-2 Op Op Cl Cl
T0023A

Set switches to match the required slave address. 0 is not a valid address. Refer to Address Switch Settings in the Appendix. S8 Network Configuration

1 2 3 4 Op = Open

1 and 2 Gateway LON/SLC address. See Table VIII-2. Gateway address 1 is recommended. 3 Port 1 operation: Open = Modbus RTU Slave Closed = Allen Bradley DF1 Slave 4 Port 2 operation: Open = Modbus RTU Slave Closed = Modbus RTU Master (to PLC) 5 Select configuration port: Open = Port 1 Closed = Port 2 6 Relay Operation. Open = Latching Closed = Non-latching. 7 Reserved. Leave switch Open 8 Gateway type. Open = Reserved Closed = Main gateway.

Cl = Closed

VIII-2

LOGIC CONTROLLER
The logic controller contains three 8-position DIP switch assemblies that are used for: Serial port configuration Communication parameters Setting the LON/SLC address. S5 Hardware Serial Port Configuration Verify that S5 switches are set as follows: 1 Closed 2 Open 3 Open 4 Closed 5 Open 6 Open 7 Closed 8 Open. S6 Diagnostic Serial Port Configuration Diagnostic serial port is intended for factory use only. Switch settings will not affect normal operation. S7 LON/SLC Address Set switches for the LON/SLC address. Valid addresses are from 5 to 247, and must be an odd number. If an address outside this range is selected, the address will default to 5. S7-1 = LSB, S7-8 = MSB.

LON/SLC DEVICE ADDRESS SWITCH SETTING


Each individual device on the LON/SLC must be assigned a unique address. Addresses 1 to 4 are reserved for gateway use. Address 1 is for the main gateway. Valid addresses for field devices are from 5 to 250. If the address is set to zero or an address above 250, the communication module will ignore the switch setting. Duplicated addresses are not automatically detected. All modules with the same address will report on that address. The status word will show the latest update, which could be from any of the reporting modules at that address. NOTE Logic controllers utilize two consecutive LON/SLC addresses, the first of which must be an odd number, i. e. a Logic Controller with an address of 7 will occupy both 7 and 8 on the LON/SLC. Selection of the node address for field devices is accomplished by setting rocker switches on a DIP switch assembly. (Note that only the first eight of the 12 switches are used for selecting the address.) The address number is binary encoded with rocker switch No. 1 on the 8 position switch assembly being the LSB (least significant bit). Each rocker switch has a specific binary value, as shown in Figure VIII-3. The node address is equal to the added value of all closed rocker switches. All open switches are ignored. For example: for node No. 5, close rocker switches 1 and 3 (binary values 1 + 4); for node No. 25, close rocker switches 1, 4 and 5 (binary values 1 + 8 + 16). Power must be cycled before the new address will take effect. For your convenience in setting the address switches, refer to the table Address Switch Settings at the back of this manual. After setting the address switches, record the address number and device type on the Address Identification Chart provided with this manual. Post the chart in a convenient location near the LCU.

ISOLATION MODULE
A slide switch (SW1), located on the top edge of the module, controls the 24 volt ground fault monitor function. On = Enabled Off = Disabled Determine the type of LCU being used (Refer to the label on the LCU mounting cage.) Set SW1 as follows: Off EQ2100LCU On EQ2101LCU

OPEN BINARY VALUE 1 2 4 8 16 32 64 128

OPEN

LEAVE IN OPEN POSITION OPEN = OFF CLOSED = ON


A1557

NODE ADDRESS EQUALS THE ADDED VALUE OF ALL CLOSED ROCKER SWITCHES

Figure VIII3Field Device Address Switches

VIII-3

95-8470

Section IX System Startup


PRE-COMMISSIONING CHECKLIST
GENERAL Insulate all shields to prevent shorting to the device housing or to any other conductor. Place alarm/release output in Bypass/Isolate when servicing devices. Maintain a log book containing the type and serial numbers of devices as well as the location and date of installation. Maintain a log of maintenance activities. Observe normal precautions for handling electrostatic sensitive devices. LON Rocker switches for each LON device must be set to the desired address prior to power-up. Test the loop with no power applied and all communication modules removed. DC resistance should be equal on A and B. Check polarity on A and B (no rolls). COM 1 connects to COM 2 ; COM 2 connects to COM 1. A connects to A and B to B. Measure voltage. A to chassis ground measures approximately +7.5 vdc. B to ground measures approximately 7.5 vdc. Measure signal (400 mv P-P min.). Check fault tolerance by introducing a short and an open.

The last device requires an EOL resistor. All devices sharing a common RS-485 link must have a common system power return.

LIOU Verify correct jumper positions and switch settings. Never disconnect the circuit ground between the LIOU and the LCU. Check signal circuits for correct polarity. Check for correct installation of EOL resistors.

POWER SUPPLIES AND POWER MONITORS Verify all earth ground connections as specified in the wiring instructions. Verify correct ac power to supply. Check power distribution to ensure that all devices are receiving power. Check power trouble indicator by introducing a short and an open.

FLAME DETECTORS Check for potential false alarm sources. Check detector aiming and ensure that mounting brackets are tight. Check for objects that can block the detectors view. Detectors can be checked for proper response using the test described in this manual.

DCUs LCU Verify correct switch positions. All configuration data must be downloaded to the device and written to the EPROM after any change is made. Changes to the logic controller also require downloading via the key switch. Chassis ground stud must be connected to earth ground. Check RS-485 connections and polarity. Check modules for correct orientation. Check for the presence of contaminants or poisoning agents. Device should be oriented with the sensor pointing down.

IDCs Check for correct installation of EOL resistors.

IX-1

95-8470

ARMs Check jumpers.

CALIBRATION
To ensure optimum performance, calibration must be performed on a regularly scheduled basis. Since each application is different, the length of time between regularly scheduled recalibrations can vary from one installation to the next. In general, the more frequently a system is checked, the greater the reliability. IMPORTANT 4 to 20 ma devices not manufactured by DetTronics must be pre-calibrated. To ensure adequate protection, calibration must be performed on a regularly scheduled basis. NOTE The calibration will be aborted and the detector will revert back to the previous calibration values if the calibration is not completed within 12 minutes. The red LED will blink. The calibration will be logged as aborted. NOTE The Sensor Replacement calibration procedure must be used for the initial calibration of a new sensor. The Routine Calibration procedure can then be used for all subsequent calibrations. NOTE Some calibration procedures require the operator to activate the reed switch located on a circuit board inside the junction box. See Figure IX-1 for the location of the reed switch. To activate the reed switch, hold the calibration magnet against the side of the junction box near the switch location approximately one inch above the mounting surface. (Do not open the junction box.) Hold the calibration magnet in place for about 4 seconds to initiate steps of the calibration procedure. CALIBRATION ALGORITHM A FOR MANUAL CALIBRATION OF UNIVERSAL DCU

SAMs Check signal circuits for correct polarity. Check for correct installation of EOL resistors. Check jumpers.

STARTUP PROCEDURE
1. Output loads that are controlled by the system should be secured (remove power from all output devices) to prevent actuation. Check all system wiring for proper connection. Before installing devices in the mounting racks, inspect them to verify that they have not been physically damaged in shipment. Check the rocker switches for proper programming, then slide the device fully into the mounting rack. Apply power to the system. NOTE To prevent the network modules from going into a fault isolation condition, apply power to the LCU prior to applying power to the network devices. 5. Program the system for the desired operation using Det-Tronics configuration software. Refer to software manual, form number 95-8479-02. Download configuration data to all devices. NOTE After system configuration has been completed, the entire system should be tested for proper operation to ensure that configuration was performed properly. 6. 7. Calibrate the sensors. Ensure that all trouble and alarm conditions have been cleared and the LCU reset, then remove mechanical blocking devices (if used) and restore power to the output loads.

2. 3.

4.

Normal Calibration 1. Activate the reed switch. The red LED blinks at a 2 Hz rate while the reed switch is closed. After the reed switch has been closed for 3 seconds, the calibrate LED on the communication module flashes at a 1 Hz rate, indicating that it is ready for the zero input. Apply the zero input (4 ma).

2.

3.

IX-2

13. The calibration is complete. The calibrate LED turns off. If the calibration is not completed within 12 minutes, the previous calibration values are restored and the calibration is logged as aborted. The calibrate LED flashes at a 4 Hz rate.
10

GND

11 12 7 8 9 13 14

Sensor Replacement WARNING The hazardous area must be de-classified prior to removing a junction box cover with power applied. 1. Open the junction box cover and press the sensor replacement switch. The calibrate LED on the communication module flashes at a 1 Hz rate, indicating it is ready for the zero input. Replace the sensor and apply the zero input (4 ma). Activate the reed switch. The red LED blinks at a 2 Hz rate for 3 seconds while the reed switch is closed. The communication module records the uncalibrated value in position one of the calibration log and calibrates the zero value. The calibrate LED goes on steady. Apply the calibration gas. The calibrate LED blinks at a 1 Hz rate when the input increases. Activate the reed switch. The red LED blinks at a 2 Hz rate for 3 seconds while the reed switch is closed. The communication module records the uncalibrated value in the first register of the calibration log and calibrates the span value.

SW1

MAGNETIC REED SWITCH *

A1881

2.

TO ACTIVATE THE MAGNETIC REED SWITCH, HOLD THE CALIBRATION MAGNET AGAINST THE SIDE OF THE ENCLOSURE AT THE LOCATION OF THE REED SWITCH, APPROXIMATELY ONE INCH ABOVE THE MOUNTING SURFACE.

Figure IX1DCU Terminal Wiring Board Mounted in Six-Port Junction Box

3. 4.

4.

Activate the reed switch. The red LED will blink at a 2 Hz rate for 3 seconds while the reed switch is closed. After the reed switch has been closed for 3 seconds, the communication module records the uncalibrated value in the calibration log and calibrates the zero value. The calibrate LED goes on steady. Apply the calibration gas. The calibrate LED blinks at a 1 Hz rate when the input increases. Activate the reed switch. The red LED blinks at a 2 Hz rate while the reed switch is closed. The communication module records the uncalibrated value in the calibration log and calibrates the span value after the reed switch is on for 3 seconds.

5.

5.

6. 7.

6. 7.

8.

8.

9.

9.

10. The calibrate LED goes on steady. 11. Remove the span gas and return the analog input to normal. 12. Activate the reed switch. The red LED blinks at a 2 Hz rate for 3 seconds while the reed switch is closed. 13. The calibration is complete. The calibrate LED turns off.

10. The calibrate LED goes on steady. 11. Remove the span gas and return the analog input to normal. 12. Activate the reed switch. The red LED blinks at a 2 Hz rate for 3 seconds while the reed switch is closed.

IX-3

95-8470

Pressing the sensor replacement switch aborts the calibration and starts over. Resetting the communication module will abort sensor replacement.

Sensor Replacement Combustible Gas NOTE When replacing a sensor, compare part numbers to be sure that the correct replacement sensor is being used. WARNING The hazardous area must be de-classified prior to removing a junction box cover with power applied. 1. 2. Remove the cover from the DCU enclosure. Press the sensor replacement switch on the communication module for about 1 second. The calibrate LED on the communication module blinks at a 1 Hz rate, indicating that it is ready for the zero input. NOTE Pressing the sensor replacement switch prevents the communication module from generating a fault signal when the input drops to zero due to removing the sensor. In addition, the calibration will not be aborted if the calibration procedure is not completed within 12 minutes. 3. Place the calibration switch on the transmitter board in the calibrate position. Replace the sensor. Connect a volt meter to the test points on the transmitter board. Connect the + lead to TP1 (red). Connect the lead to TP2 (black). Wait at least 5 minutes for the sensor output to stabilize, then adjust R2 for a reading of 0.40 vdc (4 ma) on the meter. NOTE Do not make adjustments to R1 when calibrating the sensor. 7. Place the calibrate switch on the transmitter board in the normal position. Activate the reed switch for 4 seconds. The red LED blinks at a 2 Hz rate for 3 seconds while the reed switch is activated. The communication module records the uncalibrated value in position one of the calibration log and calibrates the zero value. The calibrate LED goes on steady. Place the calibration switch on the transmitter board in the calibrate position.

CALIBRATION ALGORITHM C FOR COMBUSTIBLE GAS DCUs AND AUTOMATIC CALIBRATION OF UNIVERSAL DCUs NOTE After exposure of the H 2 S sensor to high concentrations of gas, it is recommended that it be exposed to fresh air for at least 30 minutes and then re-calibrated. Routine Calibration 1. 2. Apply the zero gas. Activate the reed switch for at least 4 seconds. The red LED blinks at a 2 Hz rate for 3 seconds while the reed switch is activated. The calibrate LED on the communication module blinks at a 1 Hz rate, indicating it is ready for the zero input. Wait until the calibrate LED goes on steady (approximately 4 seconds). The communication module records the uncalibrated value in the calibration log and calibrates the zero value during this time. Apply the calibration gas. The calibrate LED blinks at a 1 Hz rate when the sensor detects gas. When the sensor input has been stable for 30 seconds, the communication module records the uncalibrated value in the calibration log and calibrates the span value. The calibrate LED goes on steady. Remove the calibration gas. The communication module waits until the sensor input drops below 4% full scale. 6.

3.

4.

4. 5.

5.

6.

7. 8. 9.

8.

10. The calibration is complete. The calibrate LED turns off. NOTE If the calibration is not completed within 12 minutes, the calibration will be aborted and the detector will revert back to the previous calibration values. The red LED will blink at a 4 Hz rate. The calibration will be logged as aborted.
IX-4

9.

10. Apply the calibration gas and wait for the output to stabilize. 11. With 50% LFL calibration gas applied to the sensor, adjust R3 for a reading of 1.2 vdc (12 ma) on the meter. 12. Place the calibrate switch on the transmitter board in the normal position. The red LED blinks at a 1 Hz rate. 13. Activate the reed switch. The red LED blinks at a 2 Hz rate for 3 seconds while the reed switch is activated. 14. The communication module records the uncalibrated value in the first register of the calibration log and calibrates the span value. The calibrate LED goes on steady. 15. Remove the calibration gas and place the cover back on the DCU enclosure. 16. The communication module waits until the analog value drops below 4% full scale. The calibration is complete. The calibrate LED turns off. Pressing the sensor replacement switch aborts the calibration and starts over. Sensor Replacement Toxic Gas NOTE When replacing a sensor, compare part numbers to be sure that the correct replacement sensor is being used. WARNING The hazardous area must be de-classified prior to removing a junction box cover with power applied. 1. 2. Remove the cover from the DCU enclosure. Press the sensor replacement switch on the communication module for about 1 second. The calibrate LED on the communication module blinks at a 1 Hz rate, indicating that it is ready for the zero input. NOTE Pressing the sensor replacement switch prevents the communication module from generating a fault signal when the input drops to zero due to removing the sensor. In addition, the calibration will not be aborted if the calibration procedure is not completed within 12 minutes.

3. 4.

Replace the sensor. Wait at least 5 minutes for the sensor output to stabilize. Activate the reed switch. The red LED blinks at a 2 Hz rate for 3 seconds while the reed switch is activated. The communication module records the uncalibrated value in position one of the calibration log and calibrates the zero value. The calibrate LED goes on steady. Apply the calibration gas. The calibrate LED blinks at a 1 Hz rate when the input increases. Activate the reed switch. The red LED blinks at a 2 Hz rate for 3 seconds while the reed switch is activated. The communication module records the uncalibrated value in the first register of the calibration log and calibrates the span value. The calibrate LED goes on steady. Remove the calibration gas and place the cover back on the DCU enclosure.

5.

6.

7.

8.

9.

10. The communication module waits until the analog value drops below 4% full scale. The calibration is complete. The calibrate LED turns off. Pressing the sensor replacement switch aborts the calibration and starts over.

CALIBRATION ALGORITHM D FOR UNIVERSAL DCUs WITH O2 SENSOR Normal Calibration 1. 2. Apply clean air (20.9% oxygen). Activate the reed switch for at least 4 seconds. The red LED blinks at a 2 Hz rate for 3 seconds while the reed switch is closed. The calibrate LED blinks at a 1 Hz rate, indicating that calibration has begun. The communication module waits 3 seconds. The communication module records the uncalibrated value in the calibration log and calibrates the span value. The calibrate LED goes on steady.

3.

4. 5.

6.

IX-5

95-8470

7. 8.

The communication module waits 3 seconds. The calibration is complete. The calibrate LED turns off.

CALIBRATION ALGORITHM G FOR DCUs WITH POINTWATCH Routine Calibration 1. 2. Apply the zero gas. Activate the reed switch for at least 4 seconds. The red LED blinks at a 2 Hz rate for 3 seconds while the reed switch is activated. The calibrate LED on the communication module blinks at a 1 Hz rate, indicating it is ready for the zero input. When a steady zero reading is obtained, the communication module records the uncalibrated value in the calibration log and calibrates the zero value during this time. The LED turns on steady. Apply the calibration gas. The calibrate LED blinks at a 1 Hz rate when the sensor detects gas. When the sensor input has been stable for 30 seconds, the communication module records the uncalibrated value in the calibration log and calibrates the span value. The calibrate LED goes on steady. Remove the calibration gas. The communication module waits until the sensor input drops below 4% full scale.

Sensor Replacement WARNING The hazardous area must be de-classified prior to removing a junction box cover with power applied. 1. Open the junction box cover and press the sensor replacement switch. The calibrate LED on the communication module blinks at a 1 Hz rate, indicating that it is ready for the zero input. Replace the sensor and set the sensor switch (located on the sensor cell) to zero. Activate the reed switch. The red LED blinks at a 2 Hz rate for 3 seconds while the reed switch is closed. The communication module records the uncalibrated value in position one of the calibration log and calibrates the zero value. The calibrate LED is on steady. Set the zero switch on the sensor to normal. Apply clean air (20.9% oxygen) to set the sensor analog span value. The calibrate LED blinks at a 1 Hz rate when the input goes high. Activate the reed switch. The red LED blinks at a 2 Hz rate for 3 seconds while the reed switch is closed. The communication module records the uncalibrated value in the first register of the calibration log and calibrates the span value.

3.

2.

4.

3.

4.

5.

6.

5.

7. 8. 9.

6.

7.

8.

10. The calibration is complete. The calibrate LED turns off. NOTE If the calibration is not completed within 12 minutes, the calibration will be aborted and the detector will revert back to the previous calibration values. The red LED will blink at a 4 Hz rate. The calibration will be logged as aborted. Sensor Replacement WARNING The hazardous area must be de-classified prior to removing a junction box cover with power applied. 1. Remove power from the DCU and the PointWatch unit. Replace the PointWatch. Apply power, then press the sensor replacement switch on the communication module for about 1 second. Allow at least 10 minutes for the sensor to warm up.

9.

10. The calibration is complete. The calibrate LED turns off. Pressing the sensor replacement switch aborts the calibration and starts over.

IX-6

NOTE Pressing the sensor replacement switch prevents the communication module from generating a fault signal when the input drops to zero. In addition, the calibration will not be aborted if the calibration procedure is not completed within 12 minutes. 2. 3. Apply zero gas. The calibrate LED on the communication module blinks at a 1 Hz rate, indicating that it is ready for the zero input. Continue from step 4 of the PointWatch routine calibration procedure described above.

FALSE ALARM TEST 1. 2. Disable all alarm response equipment. Allow the system to monitor the protected area for a period of time with all the normal operations in the area taking place. If the detector responds (indicating a fire when no fire has occurred), check the area to see if UV sources are present. If possible, remove the sources, or reposition the detectors so that the sources fall outside of the detectors cone of vision. If problems still occur, adjust the time delay, sensitivity or arc rejection settings. The model U7656 Hand-Held UV Monitor is available from Detector Electronics for conveniently scanning the protected area and pin-pointing the exact source of UV radiation. 3. 4. Recycle power and test again as described above. Once the correct settings are obtained, turn on all alarm and extinguishing equipment that is connected to the system. Record all switch settings for future reference.

4.

UV DETECTOR TEST
CAUTION To prevent unwanted actuation, alarm and extinguishing devices must be disconnected prior to performing detection system tests.

FIRE ALARM TEST 1. Disable any extinguishing equipment that is connected to the system. Apply input power to the system. Allow a one second power-up delay. Hold a UV source (W8066) within the cone of vision of the detector at a distance relative to the selected detection range. Verify that an alarm condition is indicated at the LCU. Reset the alarm indication using the key switch on the LCU. Lack of response may indicate reduced sensitivity due to contamination on the viewing window, a damaged sensor, or electronic circuitry or wiring problems. Refer to Troubleshooting for additional information. 4. 5. Repeat this test for each fire detector in the system. Verify that all detectors are properly aimed at the area to be protected. Enable extinguishing equipment when the test is complete.

UV/IR DETECTOR TEST


IMPORTANT Disable any extinguishing equipment that is connected to the system to prevent unwanted actuation. The detector can be tested by shining a UV/IR test lamp (W867 or W8067) into the detector viewing windows or by a live fire. (Refer to the test lamp manual for specific instructions regarding proper use of the device.) This will cause the detector to go into an alarm condition the LEDs on the UV sensor will be on steady and the LCU will indicate an alarm condition. If latching operation is selected, the detector will remain in this condition until it is reset at the OIS. If non-latching operation is selected, the detector will return to normal operation as soon as the test is terminated (the test lamp or fire source is removed). If a fire signal was not generated and the LEDs indicate response by only one sensor, the other sensor has failed to respond. Check the cleanliness of the viewing window and repeat the test. If the sensor fails to respond again, replace the sensor module. If the sensor still does not respond, replace the detector.

2.

3.

6.

IX-7

95-8470

If a fire signal was not generated and the LEDs indicate response by neither sensor, both sensors have failed to respond. Check input power and external wiring. Check the cleanliness of both viewing windows. If the detector still does not respond: If using a test lamp, check the battery, window, etc. to be sure that the test lamp is working properly. If the detector still does not respond, replace the detector. MANUAL oi

IR Fault To correct an IR oi fault, clean the viewing window and oi ring of the IR sensor, and also check the module and oi ring opening for proper orientation. If the fault does not clear (fault reoccurs), a faulty sensor or electrical problem is indicated. Check the connection of the connector plug on the IR module. Also check the condition of the wires. Repair or replace if needed. If the problem persists, replace the IR sensor module. If the problem still persists, replace the detector. General Fault

When manual oi is selected, the automatically initiated oi test is disabled. Regardless of the o i selection, internal diagnostic circuitry will respond to failures such as a loss of input power or to certain electronic failures. These failures will be indicated at the LCU and also by the detectors LEDs. If such a failure occurs, check the operation of the power source and the continuity of the detector wiring. If the detector appears to be dead with power applied, it must be returned to the factory for repair. AUTOMATIC oi The Automatic oi feature (if selected) tests the detector at the selected interval (once per minute for UV and from once a minute to once every four hours for IR), checking the cleanliness of the optical surfaces, sensor sensitivity, and proper functioning of the electronic circuitry. If a problem is detected for three consecutive automatic oi tests, a fault signal is generated at the LCU (also indicated by the UV sensor LEDs). If the detector passes three subsequent automatic oi tests, the fault signal will be cleared UV Fault To correct a UV oi fault, clean the viewing window and oi ring of the UV sensor, and also check the oi ring opening for proper orientation. If the fault does not clear (or fault reoccurs), a faulty sensor or electrical problem is indicated. First replace the UV sensor module. If the problem persists, replace the detector.

If a general fault is indicated, check input power to the detector as well as continuity of system wiring. Also check the detector viewing windows for contamination such as paint overspray, snow, etc. that could simultaneously affect both sensors. Since simultaneous failure of both sensor modules is unlikely, the problem is most likely caused by loss of input power or failure of the detectors electronic circuitry. Background Radiation Background radiation as such does not cause a problem with the detector in most applications, unless both UV and flickering IR non-fire radiation sources occur simultaneously. If a UV or IR background radiation indication occurs: Determine its cause. The presence of background radiation could indicate a problem in the protected area. For example, background IR could be caused by overheating equipment. Determine whether or not repositioning the detector could eliminate response to the background radiation without reducing coverage of the hazardous area.

IX-8

Section X Specifications
CERTIFICATIONS
FMRC Approval See Appendix A. CSA Certification See Appendix B. CENELEC and CE Mark See Appendix C.

I/O PORTS The LCU provides two electrically isolated RS-232 serial ports, port 1 and port 2, both of which can be active simultaneously. Port 1 can be configured as either a Modbus RTU slave, or an Allen Bradley DF1 slave. Port 2 can be either a Modbus RTU slave or master.

EQ2100LCU LOCAL CONTROL UNIT


INPUT VOLTAGE 18 to 30 vdc. 10% overvoltage will not cause damage to the equipment. INPUT CURRENT EQ2100LCU: 0.4 ampere maximum. EQ2101LCU: 12 amperes maximum. OUTPUT CURRENT (EQ2101LCU ONLY) System: 2.8 amperes maximum (ground fault monitored) 1.8 amperes standby current 2.8 amperes alarm current Auxiliary: 8.0 amperes maximum (input power to LIOU auxiliary). RELAY OUTPUT RATING 5 amperes resistive at 30 vdc.

Two 78.5 kb LON/SLC ports provide the start and end of the communication loop for the detection devices. The wiring is transformer coupled to protect the transceivers. The LON/SLC is monitored for ground faults. TEMPERATURE RANGE Operating: +32F to +140F (0C to +60C). Storage: 67F to +185F (55C to +85C). HUMIDITY RANGE 0 to 95% RH, non-condensing. VIBRATION Meets MIL SPEC 810C, method 514.2, curve AW. DIMENSIONS See Figure X-1A for dimensions of the standard LCU mounting configuration. The LCU can also be housed in a 19 inch mounting rack (000840-xxx), with any combination of up to 4 logic controllers, 4 gateways and one isolation module. See Figure X-1B for dimensions.

9.24 (23.5)

1.48 (3.8)

10.86 (27.6) 10.26 (26.1)

4.00 (10.2)

6.97 (17.7)

12.25 (31.1)

6.50 (16.5)

8.68 (22.0)
A1882

Figure X1ADimensions of LCU in Inches (Centimeters)

X-1

95-8470

TERMINAL STRIP REAR

13.2 (33.5)

FRONT

7.0 (17.7)

4.0 (10.2)

FRONT

19.0 (48.3)

DET-TRONICS
POWER ALARM TROUBLE POWER FAULT SUPERVISORY

DET-TRONICS

DET-TRONICS
LON INSOLATOR

GROUND FAULT RELAY 1 100 90 80 70 60 50 40 30 20 10 POWER + POWER

ACKNOWLEGDE RELAY 2

GROUND FAULT COM 1 COM 2

SILENCE PROGRAM ISOLATE

RELAY 3 RELAY 4

FAULT RESET EAGLE QUANTUM LOGIC CONTROLLER


NORMAL ACKNOWLEDGE & SILENCE ENABLE

EAGLE QUANTUM GATEWAY

EAGLE QUANTUM LON ISOLATOR

RESET ISOLATE

B2044

SLOT 1

SLOT 2

SLOT 3

SLOT 4

SLOT 5

SLOT 6

SLOT 7

SLOT 8

Figure X1BDimensions of Model 000840-XXX LCU in Inches (Centimeters)

X-2

EQ2200IDC/IDCGF/IDCSC INITIATING DEVICE CIRCUIT


INPUT VOLTAGE 24 vdc nominal, 18 to 30 vdc. 10% overvoltage will not cause damage to the equipment. INPUT POWER 4.0 watts maximum. INPUTS Two supervised non-incendive digital inputs (sealed or unsealed switch or relay contacts). 10 kohm EOL resistors are required. OUTPUTS Digital communication, transformer isolated (78.5 kbps). TEMPERATURE RANGE Operating: 40F to +167F (40C to +75C). Storage: -67F to +185F (55C to +85C). HUMIDITY RANGE 0 to 95% RH, non-condensing. VIBRATION Meets MIL SPEC 810C, method 514.2, curve AW. DIMENSIONS See Figure X-2.
0.28 (0.71) 4.7 (11.8) 3.4 (8.6)

EQ2200UV and EQ2200UVHT UV FLAME DETECTORS


INPUT VOLTAGE 24 vdc nominal, 18 to 30 vdc. 10% overvoltage will not cause damage to the equipment. INPUT POWER 2.0 watts typical, 4.0 watts maximum during oi test. TEMPERATURE RANGE EQ2200UV Operating: Storage: 40F to +167F (40C to +75C). 67F to +185F (55C to +85C).

EQ2200UVHT Electronic Module: 40F to +167F (40C to +75C). UV Detector: 40F to +257F (40C to +125C). Storage: 67F to +185F (55C to +85C). HUMIDITY RANGE 0 to 95% relative humidity, can withstand 100% condensing humidity for short periods of time. SPECTRAL SENSITIVITY RANGE UV radiation over the wavelength of 1850 to 2450 angstroms (solar blind). CONE OF VISION The detector has a 90 degree cone of vision with the highest sensitivity lying along its central axis. See Figure X-3.

5.2 (13.2)

2.7 (6.8)

100% REPRESENTS THE MAXIMUM DETECTION DISTANCE FOR A GIVEN FIRE. THE SENSITIVITY INCREASES AS THE ANGLE OF INCIDENCE DECREASES. 0 15 30 100 90 80 45 70 45 15 30

0.32 (0.81) OVAL SLOT MOUNTING (TYPICAL FOUR PLACES) DETECTION DISTANCE (PERCENT)

60 50 40 30 20 10
D573

6.6 (16.8)

Figure X3Cone of Vision of UV Detector


1.28 (3.25)
B2045

Figure X2Dimensions of Tall Cover Junction Box in Inches (Centimeters) X-3 95-8470

FLAME SENSITIVITY The detector has four adjustable sensitivity settings plus transient arc rejection capabilities. RESPONSE TIME The detector is selectable for a 0 to 7 second time delay. OUTPUTS Digital communication, transformer isolated (78.5 kbps).

5/16-18 UNC

DETECTOR LOCK NUT

1 3/8 INCH GLAND NUT USED TO ROTATE SWIVEL/DETECTOR ASSEMBLY TO DESIRED POSITION 2.5 (6.4)

MOUNTING BASE

SEPARATION DISTANCE (EQ2200UVHT only) Maximum separation distance between the UV detector and the electronic module is 165 feet (50 meters). VIBRATION Meets MIL SPEC 810C, method 514.2, curve AW. DIMENSIONS See Figures X-4A and X 4B for the standard UV detector. For the high temperature UV detector, see Figures X-5A and X-5B (UV detector) and Figure X-6 (electronic module).
2.5 (6.4) DIA. 2.0 (5.08) DIA.

2.5 (6.4)

120 2 (2)

A1986

0.25 (0.64) DIA. (3)

DETECTOR SCREWS ONTO SWIVEL MOUNT HERE 3/4 INCH NUT USED TO SECURE DETECTOR TO SWIVEL MOUNT 1/2 INCH NUT USED TO ADJUST ELBOW TO DESIRED ANGLE

Figure X5AQ9001B Swivel Mounting Bracket Dimensions in Inches (Centimeters)

5.25 (13.3)

1/2 INCH NPT OR 20 MM

4.75 (12.06)

1-3/8 INCH NUT USED TO ROTATE SWIVEL/DETECTOR ASSEMBLY TO DESIRED POSITION

2.5 (6.35)

MOUNTING BASE 2.5 (6.4)


A1987

Figure X5BUV Detector Dimensions in Inches (Centimeters)


120 2 (2)

2.0 (5.0) DIA.


A1886

0.25 (.64) (3) 2.5 (6.4) DIA.

Figure X4ADimensions of Optional Swivel Assembly in Inches (Centimeters)

X-4

COVER LOCKING CLAMPS (BASEEFA) 9 (228.6)

5 (127)

4 (101.6)

2.5 (63.5)

4.375 (111.1)

CONDUIT/CABLE ENTRY (2)


A1844

4.5 (114.3)

Figure X4BDimensions of EQ2200UV Detector in Inches (Millimeters)

0.28 (0.71)

4.66 (11.8) 3.39 (8.6)

5.20 (13.21)

2.69 (6.83)

0.32 (0.81) OVAL SLOT MOUNTING (TYPICAL FOUR PLACES)

6.62 (16.8)

1.28 (3.25)
A1887

Figure X6 EQ2200UVHT Junction Box Dimensions in Inches (Centimeters)

X-5

95-8470

EQ2200UVIR UV/IR DETECTOR


INPUT VOLTAGE 24 vdc nominal, 18 to 30 Vdc. 10% overvoltage will not cause damage to the equipment.
45

100% REPRESENTS THE MAXIMUM DETECTION DISTANCE FOR A GIVEN FIRE. THE SENSITIVITY INCREASES AS THE ANGLE OF INCIDENCE DECREASES. 0 15 30 100 90 80 45 70 60 DETECTION DISTANCE (PERCENT) 50 40 30 20 15 30

INPUT POWER 2.0 watts nominal, 5.0 watts maximum during oi test. TEMPERATURE RANGE Operating: 40F to +167F (40C to +75C). Storage: 40F to +185F (40C to +85C). HUMIDITY RANGE 0 to 95% RH. Can withstand 100% condensing humidity for short periods of time. SPECTRAL SENSITIVITY RANGE UV: 0.185 to 0.245 microns (solar blind). IR: 4.45 microns (solar blind). Figure X-7 illustrates the spectral response range of the UV and IR sensors. CONE OF VISION 90 degree cone of vision using gasoline fuel (1 sq. ft). 80 degree cone of vision using methane fuel (30 inch). See Figure X-8. FLAME SENSITIVITY Refer to Tables X-1 and X-2 for typical detector response characteristics. CAUTION The detector is extremely sensitive when the very high setting is utilized. While this setting is required to reliably detect certain types of fires, care must be taken to minimize the possibility of false alarms.

10
D573

Figure X8Cone of Vision of UV/IR Detector

RESPONSE TIME Selectable for a 0 to 7 second time delay. Fastest response time is 0.5 second. OUTPUTS Digital communication, transformer isolated (78.5 k bps). VIBRATION Meets MIL SPEC 810C, method 514.2, curve AW. ENCLOSURE MATERIAL Copper-free aluminum (red) or 316 stainless steel, with stainless steel mounting bracket. DIMENSIONS See Figures X-9 and X-10.

ULTRAVIOLET 100 75 ATMOSPHERIC TRANSMISSION 50 25 0 0.1 0.2 0.3 0.4

VISIBLE

INFRARED

0.5

0.6 0.7 0.8 0.9 1.0

1.5

2.0

3.0

4.0

5.0

WAVELENGTH (MICRONS) ULTRAVIOLET SENSOR RESPONSE SOLAR RADIATION REACHING THE EARTH INFRARED SENSOR RESPONSE
A1070

Figure X7Sensitivity Range of UV/IR Detector

X-6

Table X1UV/IR Detector Maximum Response Distances in Feet

Sensitivity UV Standard Low Medium High Very High Low Low Medium Medium High High Very High Very High Low Medium High Very High

Arc Rejection

30 inch Methane 40 60 80 100

1 Ft x 1 Ft Gasoline 30 45 65 100 30 30 40 40 50 50 65 65 65 75 90 100

1 Ft x 1 Ft Methanol 15 20 35 55 10 10 15 15 25 25 50 50 40 45 55 60

UV Arc Rejection

Medium High Medium High Medium High Medium High

35 35 55 55 60 65 85 85 40 55 65 90

IR

Typical response time less than 5 seconds. NOTE: Sensitivity level determines maximum response distance and is selected for UV and IR sensors individually (selected through the configuration software). The maximum response distance for the UV/IR detector is the lesser of the two.

Table X2Recommended Settings for JP-4, 5, 8 Fires

Fuel JP4 JP5 JP8 JP4 JP5 JP8

Size 3 Ft x 3 Ft 3 Ft x 3 Ft 3 Ft x 3 Ft 2 Ft x 2 Ft 2 Ft x 2 Ft 2 Ft x 2 Ft

Distance 150 Ft. 150 Ft. 150 Ft. 100 Ft. 100 Ft. 100 Ft.

UV Very High High Very High High High High

IR High High Medium Medium Medium Medium

Typical response time less than 5 seconds.

X-7

95-8470

JUNCTION BOX MOUNTING BRACKET (ATTACHES WITH TWO ENCLOSED FLATHEAD SCREWS) 3/4 INCH NUT USED TO SECURE DETECTOR BRACKET TO SWIVEL MOUNT 1/2 INCH NUT USED TO ADJUST ELBOW TO DESIRED ANGLE

5-1/4 INCHES (133 MM)

1-3/8 INCH NUT USED TO ROTATE SWIVEL/DETECTOR ASSEMBLY TO DESIRED POSITION

MOUNTING BASE 2-1/2 INCHES (64 MM)

B1303

120 2 (2)

2.00 (50.8 MM) DIA. 21/2 (64 MM) DIA.

0.25 (6.4 MM) DIA. (3)


B1303

Figure X9Q9001G Swivel Mounting Bracket Dimensions

3.38 (85.8 MM)

7.11 (181 MM)

2.5 DIA. (64 MM)

7.81 (198 MM) 5.25 (133 MM)

C1047

CONDUIT ENTRY 3/4 NPT OR 25 MM

Figure X10UV/IR Detector Dimensions in Inches (Millimeters)

X-8

EQ2200DCU AND EQ2200DCUEX DIGITAL COMMUNICATION UNIT


INPUT VOLTAGE 24 vdc nominal, 18 to 30 vdc. 10% overvoltage will not cause damage to the equipment. POWER CONSUMPTION DCU with toxic gas sensor/transmitter: 95 ma maximum. DCU with transmitter and combustible gas sensor: 180 ma maximum during normal operation, 500 ma during startup. INPUTS 4 to 20 ma analog signal. Non-intrusive calibration. OUTPUTS Digital communication, transformer isolated (78.5 kbps). TEMPERATURE RANGE Operating: 40F to +167F (40C to +75C). Storage: 67F to +185F (55C to +85C). HUMIDITY RANGE 0 to 95% RH, non-condensing. VIBRATION Meets MIL SPEC 810C, method 514.2, curve AW. DIMENSIONS See Figure X-2.

EQ2500ARM AGENT RELEASE MODULE


RELEASE OUTPUT RATING 2 amperes at 30 vdc maximum. SUPERVISORY CURRENT 2.0 ma, 1.0 ma each circuit. INPUT VOLTAGE 24 vdc nominal. INPUT CURRENT Standby: 75 ma maximum at 24 vdc. Alarm: 120 ma maximum at 24 vdc. STATUS OUTPUTS Digital communication, transformer isolated (78.5 kbps). TEMPERATURE RANGE Operating: 40F to +167F (40C to +75C). Storage: 67F to +185F (55C to +85C). HUMIDITY RANGE 5 to 95% RH, non-condensing. VIBRATION Meets MIL SPEC 810C, method 514.2, curve AW. DIMENSIONS See Figure X-2.

X-9

95-8470

EQ2500SAM SIGNAL AUDIBLE MODULE


OUTPUT RATING 2 amperes at 30 vdc maximum. RESPONSE TIME Output relay actuates in <0.1 second after acknowledging an alarm command message. SUPERVISORY CURRENT 3.0 ma 2.0ma, each circuit. EOL RESISTORS 10 kohm 2 kohm. Each circuit must have an EOL resistor. INPUT VOLTAGE 24 vdc nominal. INPUT CURRENT (Excluding Output Current) Standby: 60 ma maximum at 24 vdc. Alarm: 120 ma maximum at 24 vdc. STATUS OUTPUT Digital communication, transformer isolated (78.5 kbps). TEMPERATURE RANGE Operating: 40F to +167F (40C to +75C). Storage: 67F to +185F (55C to +85C). HUMIDITY RANGE 5 to 95% RH, non-condensing.

EQ2400NE NETWORK EXTENDER


INPUT VOLTAGE 18 to 30 Vdc. POWER CONSUMPTION 2.2 watts nominal at 24 vdc, 2.7 watts maximum. INPUTS/OUTPUTS Digital, transformer isolated (78.5k Baud). TEMPERATURE RANGE Operating: -40F to +167F (-40C to +75C) Storage: -67F to +185F (-55C to +85C). HUMIDITY 5 to 95% RH at 70C. DIMENSIONS See Figure X-11.
0.28 (0.71) 3.39 (8.6) 4.66 (11.8)

5.20 (13.21)

2.69 (6.83)

VIBRATION Meets MIL SPEC 810C, method 514.2, curve AW. DIMENSIONS See Figure X-2.

0.32 (0.81) OVAL SLOT MOUNTING (TYPICAL FOUR PLACES)

3.7 (9.4)

1.28 (3.25)
A1883

Figure X11Dimensions of Short Cover Junction Box in Inches (Centimeters)

X-10

EQ2100PSM POWER SUPPLY MONITOR


INPUT VOLTAGE 24 vdc nominal, 18 to 30 Vdc. POWER CONSUMPTION 2.0 watts maximum. MEASUREMENT RANGE AC Voltage: DC Battery Charging Current:

EQ2110PS, EQ2130PS AND EQ2175PS POWER SUPPLIES


INPUT VOLTAGE Selectable for 120, 208 or 240 vac input power, 10%. INPUT FREQUENCY 60 Hz 5% standard, 50 Hz 5% optional. INPUT CURRENT EQ2110PS: 4 amps at 120 VAC (60 Hz) EQ2130PS: 11 / 6 / 6 amps at 120 / 208 / 240 VAC* EQ2175PS: 24 / 15 / 12 amps at 120 / 208 / 240 VAC*. *Specify 50 Hz or 60 Hz. OUTPUT CURRENT EQ2110PS: 10 amperes at 24 VDC EQ2130PS: 30 amperes at 24 VDC EQ2175PS: 75 amperes at 24 VDC. POWER CONSUMPTION EQ2110PS: 46 Watts EQ2130PS: 140 Watts EQ2175PS: 349 Watts. TEMPERATURE RANGE Operating: +32F to +122F (0C to +50C) Storage: -40F to +185F (-40C to +85C).

240 vac maximum. 75 amperes maximum.

OUTPUT Digital communication, transformer isolated (78.5 k bps). TEMPERATURE RANGE Operating: +32F to +122F (0C to +50C) Storage: -67F to +185F (-55C to +85C). HUMIDITY RANGE 5 to 95% RH, non-condensing. DIMENSIONS See Figure X-12.

9 (22.9) 8.5 (21.6)

HUMIDITY RANGE 5 to 95% RH, non-condensing. DIMENSIONS in Inches (Centimeters) Width EQ2110PS: 19 (48.3) EQ2130PS: 19 (48.3) EQ2175PS: 19 (48.3)

J1

J3

2.25 (5.7) 4 (10.2)

Height 7 (17.8) 14 (35.6) 14 (35.6)

Depth 15 (38.1) 15 (38.1) 15 (38.1)

2.5 (6.4)

NOTE Power supplies are designed for mounting in a standard 19 inch rack. Optional mounting hardware is available for floor or wall mount applications.
A2038

Figure X12Dimensions of Power Supply Monitor in Inches (Centimeters)

X-11

95-8470

LIOU (Local Output Unit)


INPUT VOLTAGE 24 vdc nominal. INPUT POWER 30 watts maximum. MODULES PER SYSTEM 24 maximum. TEMPERATURE RATING Operating: +32F to +120F (0C to +50C). Storage: 67F to +185F (55C to +85C). HUMIDITY RANGE 0 to 95% RH, non-condensing. VIBRATION Meets FMRC Class number 3260 requirements. DIMENSIONS See Figures X-13 and X-14.

LIOU RELEASE MODULE


RELEASE OUTPUT RATING 2 amperes at 24 vdc. SUPERVISORY CURRENT 2.5 ma, each circuit. SIGNAL OUTPUT RATING 2 amperes at 24 vdc. MODULES PER SYSTEM 8 maximum. OUTPUTS PER SYSTEM 32 maximum.

LIOU SIGNAL AUDIBLE MODULE


OUTPUT RATING 2 amperes at 24 vdc WIRING STYLES NFPA Four Style Y or Two Style Z circuits.

LIOU RELAY MODULE


CONTACT RATING 2 amperes at 24 vdc. MODULES PER SYSTEM 8 maximum. OUTPUTS PER SYSTEM 32 maximum. MODULES PER SYSTEM 8 maximum. OUTPUTS PER SYSTEM 32 maximum.
10.25 (26) 9.6 (24.4)

12.0 (30.5)

6.0 (15.2)

14.25 (36.2)

13.6 (34.6)

16.0 (40.6)

A1695

Figure X13Dimensions of LIOU Enclosure in Inches


A2037

Figure X14Dimensions of LIOU Mounting Plate in Inches (Centimeters)

X-12

COMBUSTIBLE GAS SENSOR


Refer to the Combustible Gas Sensor Specification Data sheet, form 90-1041, for specifications.

ELECTROCHEMICAL SENSORS
Refer to the Electrochemical Gas Sensor Specification Data sheet, form 90-1079, for specifications. Electrochemical sensors available from Det-Tronics include Hydrogen Sulfide, Oxygen, Carbon Monoxide, Chlorine, Sulfur Dioxide, and Nitrogen Dioxide.

POINTWATCH
Refer to the PointWatch manual, form 95-8440, for PointWatch specifications.

X-13

95-8470

Section XI System Maintenance


ROUTINE MAINTENANCE
To ensure reliable protection, it is important to check and calibrate the system on a regularly scheduled basis. The frequency of these checks is determined by the requirements of the particular installation. MANUAL CHECK OF OUTPUT DEVICES It is important that response devices be checked initially when the system is installed, as well as periodically during the on-going maintenance program. CAUTION Be sure to secure all output devices that are actuated by the system to prevent unwanted activation of this equipment, and remember to place these same output devices back into service when the checkout is complete. O-RING MAINTENANCE WARNING The hazardous area must be de-classified prior to removing a junction box cover with power applied. A rubber O-ring is used to ensure that the junction box cover will seal tightly and provide protection against water ingress. Periodically the enclosure should be opened and the O-ring should be inspected for breaks, cracks and dryness. To test the ring, remove it from the enclosure and stretch it slightly. If cracks are visible, it should be replaced. If it feels dry, a thin coating of lubricant should be applied. When re-installing the ring, be sure that it is properly seated in the groove on the housing. It is imperative that this O-ring be properly installed and in good condition. Failure to properly maintain it can allow water to enter the enclosure and cause premature failure. A coating of lubricant should also be applied to the threads on the cover before reassembling the enclosure. This will both lubricate the threads and help to prevent moisture from entering the enclosure. CAUTION The O-rings should be lubricated with a silicone free grease. The use of other lubricants is not recommended, since they can adversely affect the performance of some sensors. Under no circumstances should a lubricant or compound containing silicone be used on systems using catalytic type combustible gas sensors.

FLAME DETECTOR MAINTENANCE The flame detector requires no periodic calibration. However, to maintain maximum sensitivity, the viewing window must be kept clean at all times. To clean the optical surfaces, remove the oi ring from the detector by gently squeezing the tabs together and then pulling out. Clean the viewing window and the back side of the oi ring using a clean cloth or tissue and Det-Tronics window cleaning solution. Avoid the use of commercial glass cleaners, since many of them can leave a UV absorbing residue on the surface. Avoid leaving fingerprints on the reflective surface of the o i ring. Re-install the ring so that the opening is positioned downward. NOTE If corrosive contaminants in the atmosphere cause the reflective rings to deteriorate to the extent that it is no longer possible to restore them to their original condition, they must be replaced. To ensure the watertight integrity of the detector, the Orings must be maintained following the guidelines described above. GAS SENSOR MAINTENANCE All gas sensors must be calibrated on a regularly scheduled basis, typically every 90 days for catalytic and electrochemical sensors and annually for PointWatch. Catalytic sensors have a finite lifespan. If a successful calibration cannot be performed, replace the sensor and recalibrate following the procedure described in the Calibration section. Exposure of the sensor to high concentrations of combustible gases for extended periods of time can introduce stress to the sensing element and seriously affect its performance. After exposure to a high concentration of combustible gas, recalibration should be performed and, if necessary, the sensor should be replaced. Electrochemical sensors have a finite lifespan. If a successful calibration cannot be performed, inspect the hydrophobic filter. If the filter is plugged, replace it and recalibrate the sensor. If the filter is in good condition, replace the sensor. Recalibrate following the procedure described in the Calibration section. If the PointWatch fails calibration, refer to the PointWatch manual. NOTE Compare part numbers to be sure that the correct replacement sensor is being used.
XI-1 95-8470

BATTERIES Batteries must be replaced every 48 months, or sooner if required by local codes. Only sealed batteries are to be used.

for proper wiring, programming and calibration. If it is determined that the problem is caused by an electronic defect, the device must be returned to the factory for repair. NOTE When replacing a device, be sure that the rocker switches on the replacement are set the same as the original. Remove power before removing or plugging in the replacement unit. When a DCU, IDC or flame detector is replaced, the point must be re-configured. If the auto-configure feature is enabled, configuration is done automatically.

TROUBLESHOOTING
Table XI-1 is intended to serve as an aid in locating the cause of a system malfunction. If the problem cannot be corrected, contact the factory for assistance.

REPLACEMENT PARTS
Eagle devices are not designed to be repaired in the field. If a problem should develop, first carefully check

Table XI-1Troubleshooting Guide

Symptom Gateway Green Power LED is off. Gateway Fault LED is on and F30 is displayed.

Possible Cause Power wiring is wrong. An open in the LON wiring. This can also be caused by a device that has isolated a short on the LON. Press the Gateway reset switch after the LON is repaired to clear the fault. The external or faceplate reset switch is held closed. A fault was detected on one of the LON communication boards. Replace the gateway. The gateway was not configured using the OIS software. Wrong communication parameters (check the gateway DIP switches), or communication wiring. See Logic Controller table (Table II-3). Power related fault. A field device programmed as a supervisory input is active. This is caused by a problem with the field device input. Check for wiring or sensor faults. The field device is not reporting or communication fault. Check power and LON wiring. Check that the device address is set properly. The device configuration needs to be downloaded using the OIS software. Dirty viewing window. oi ring dirty, misaligned or missing. Input voltage too low. Internal high voltage out of tolerance. Open, shorted or incorrect wiring. Device not configured. Dirty viewing window. Insufficient supply voltage. Open, shorted or incorrect wiring. Defect in UV module. Defect in electronic module.
T0025B

Gateway Fault LED is on and F40 is displayed. Gateway Fault LED is on and F50 or F51 is displayed. Gateway Fault LED is on and F60 is displayed. No communication with the host computer. Logic Controller Fault LED is on. Logic Controller Power Fault LED is on. Logic Controller Supervisory LED is on. The Gateway displays F10 for a field device. The Gateway displays F20 for a field device.

The Gateway displays F60 for a field device. UV Detector LEDs not blinking.

UV Detector does not respond to fire stimuli or to manual oi test.

XI-2

DEVICE REPAIR AND RETURN


Prior to returning devices or components, contact the nearest local Detector Electronics office so that a Service Order number can be assigned. A written statement describing the malfunction must accompany the returned device or component to expedite finding the cause of the failure. Pack the unit or component properly. Use sufficient packing material in addition to an antistatic bag or aluminum-backed cardboard as protection from electrostatic discharge. Return all equipment transportation prepaid to the factory in Minneapolis.

Table XI-2Combustible Gas Sensors


OS Number
CGSS1A6C2R1X

Part Number
006824-001

Replaces
225006-004 225957-002 226530-003 226531-003 226931-005 226931-006 226999-011 226999-012 225006-003 226530-005 226531-004 226931-007 226931-008 226999-008 226999-020 226999-014 226999-021 226999-015

Threads Wire Length


3/4 inch 6 inch

CGSS1A3C2R1X

006824-005

3/4 inch

30 inch

CGSS1C6C2R1X

006824-003

20 mm

6 inch

CGSS1C3C2R1X

006824-007

20 mm

30 inch
T0043A

ORDERING INFORMATION
POWER SUPPLIES When ordering, please specify: LCU Part Number 006814-001 Description EQ2100LCU Local Control Unit for use with EQ21XXPS Series Power Supplies. LCU Replacement Parts: 006570-001 EQ2100CG Communication Gateway 006566-001 EQ2100LC Logic Controller 006558-001 EQ2100IM Isolation Module 006668-001 EQ2100MR Mounting Rack LIOU Part Number 006641-xxx 102844-001 102843-001 102842-001 LON DEVICES Part Number 006608-xxx 006943-xxx 007257-xxx 006600-xxx 007082-xxx 006861-xxx 006607-xxx 006733-xxx 006738-xxx 006941-xxx Description EQ22XXIDC Initiating Device Circuit EQ22XXIDCGF Ground Fault Monitor EQ22XXIDCSC Initiating Device Circuit Short Circuit EQ22XXUV UV Flame Detector EQ22XXUVHT High Temperature UV Flame Detector EQ22XXUVIR UV/IR Flame Detector EQ22XXDCU Digital Communication Unit (specify gas) EQ25XXARM Agent Release Module EQ25XXSAM Signal Audible Module EQ24XXNE Network Extender
XI-3

Part Number 006979-001 000604-013 000604-014 000604-015

Description EQ2100PSM Power Supply Monitor EQ2110PS Power Supply (10 amps) EQ2130PS Power Supply (30 amps) EQ2175PS Power Supply (75 amps)

COMBUSTIBLE GAS SENSORS See Table XI-2. H2S SENSOR Part Number 004539-009 005434-001 Description Explosion-Proof H2S Sensor Housing Electrochemical H2S Sensing Element Assembly

Description EQ2100LIOU Local Input/Output Unit Relay Module Release Module Signal Audible Module

Other toxic gas sensors available. Consult the factory. ACCESSORIES Part Number 102868-001 102740-001 226365-113 226365-104 006414-001 226349-001 225312-001 226190-001 226354-001 Description Silicone Free Grease Calibration Magnet Sensor Separation Kit for Catalytic Sensors Sensor Separation Kit for Electrochemical Sensors Sensor Separation Kit for PointWatch Sensor Rain Shield Sensor Dust Cover (Stainless Steel) Sensor Dust Cover (Porex) Splash Guard

Other accessories are available. Consult the factory.

95-8470

CALIBRATION KITS COMBUSTIBLE GAS Part Number 225130-001 225130-002 225130-003 225130-004 225130-005 225130-006 225130-007 225130-008 Gas Methane (50% LFL) Ethane (50% LFL) Ethylene (50% LFL) Propane (50% LFL) Hydrogen (50% LFL) Methane (20% LFL) Methane (25% LFL) Methane (35% LFL)

Accessories and Replacement Parts Part Number 004273-002 004483-001 004404-005 003240-202 006598-001 002507-001 002519-001 107427-040 107427-004 Description Q1113 Air Shield Assembly W8066 UV Test Lamp Swivel Mount Sensor Module Electronic Module Window cleaner kit oi Ring O-Ring (large) O-Ring (small)

REPLACEMENT CYLINDERS UV DETECTOR High Temperature Part Number 226166-001 226166-002 226166-003 226166-004 226166-005 226166-006 226166-007 226166-008 226166-009 Gas Methane (50% LFL) Ethane (50% LFL) Ethylene (50% LFL) Propane (50% LFL) Hydrogen (50% LFL) Air (0% LFL) Methane (20% LFL) Methane (25% LFL) Methane (35% LFL) 007082-xxx 006899-xxx EQ22XXUVHT Hi Temp UV Flame Detector Electronic Module Assembly C7050B Hi Temp UV Detector

One electronic module assembly and one high temperature UV detector are required for each detection point. Both units must be ordered separately. Specify material (aluminum or stainless steel) and conduit entry size (3/4 inch NPT or 25/20 MM) for each. Accessories and Replacement Parts Part Number 006598-002 003240-221 107427-004 002099-003 004404-002 Description Electronic Module DE1888K3 UV Sensor Module O-Ring for UV Detector Mounting Bracket (Aluminum) Mounting Bracket (Stainless Steel)

REPLACEMENT PARTS FOR CALIBRATION KIT Part Number 162552-001 101678-007 004976-001 225777-001 Description Regulator 3 foot hose Standard calibration cup Modified calibration cup (for sensor separation)

H2S CALIBRATION KIT 227115-001 H 2 S Calibration Kit (for electrochemical sensors only) includes regulator, hose, calibration cup, and two cylinders of calibration gas.

UV/IR DETECTOR 006861-xxx EQ22XXUVIR UV/IR Flame Detector

Accessories and Replacement Parts Part Number 004404-001 004273-002 004000-003 002519-001 003525-001 107427-004 DE1888B2 DE5600-002 001680-001 003996-001 Description Q9001G Swivel Mount Assembly Q1113 Air Shield Assembly (two per detector) W867 Explosion-proof UV/IR Test Lamp oi ring for UV detector oi ring for IR detector O-rings for UV and IR detectors (two O-rings per detector) UV sensor module with LEDs IR module with LEDs (standard sensitivity) Window Cleaner (six bottles) UV/IR Window Maintenance Kit, consisting of 2 bottles of cleaner, 4 UV rings, 4 IR rings Silicone Free Grease

REPLACEMENT PARTS H2S Part Number 005434-001 004532-002 107427-034 107427-004 227117-001 Description Electrochemical Sensing Element Assembly for H2S Sensor Hydrophobic Filter for H2S Sensor O-ring (for Hydrophobic Filter) O-ring (for Sensor Housing) Gas Bottle for 227115-001 Calibration Kit - 50 ppm

UV DETECTOR 006600-xxx EQ22XXUV UV Flame Detector

102868-001
XI-4

APPENDIX A

FACTORY MUTUAL RESEARCH CORPORATION (FMRC) APPROVAL DESCRIPTION


The Eagle Quantum Fire and Gas Detection/Releasing System (reference Figure A1) has the following FMRC approved configurations:

MODEL EQ2100LCU SERIES LOCAL CONTROL UNIT (Up to four EQ2100LC, four EQ2100CG and one EQ2100IM for maximum system.) Nonincendive for Class I, Division 2, Groups A, B, C, and D; temperature code T4A Hazardous (Classified) Locations per FM 3611. Operating Temperature Limits 0C to +60C. Storage Temperature Limits 55C to +85C. Relative Humidity Range: 5 to 95% RH. National Fire Alarm Code Performance verified per ANSI/NFPA 72-1996. Combustible Gas Performance verified for 0 to 100% LFL methane-in-air atmospheres per FM 6320. H2S Toxic Gas Performance verified 0 to 20, 50 or 100 ppm per FMRC requirements. NOTE FMRC Approval allows the presence and operation of serial communications software in the LCU Gateway (MODBUS or Allen Bradley protocols, etc.), however, the communications functions are not included in the Approval.

MODEL EQ2100LCUPS LOCAL CONTROL UNIT POWER SUPPLY AND MODEL EQ2175PS, EQ2130PS, AND EQ2110PS POWER SUPPLIES WITH MODEL EQ2100PSM SERIES POWER SUPPLY MONITOR Ordinary Locations verified per FM 3820. Operating Temperature Limits 0C to +50C. Storage Temperature Limits 55C to +85C. Relative Humidity Range: 5 to 95% RH. National Fire Alarm Code Performance verified per ANSI/NFPA 72-1996.

A-1

95-8470

MODEL EQ2100LIOU LOCAL INPUT/OUTPUT UNIT Ordinary Locations verified per FM 3820. Operating Temperature Limits 0C to +50C. Storage Temperature Limits 55C to +85C. Humidity Range: 5 to 95% RH. National Fire Alarm Code Performance verified per ANSI/NFPA 72-1996. Approved for use with the following automatic deluge and pre-action solenoids: Manufacturer Skinner ASCO ASCO Skinner Skinner Skinner Model LV2LBX25 8210A107 8210G207 73218BN4UNLVNOC111C2 73212BN4TNLVNOC322C2 71395SN2ENJ1NOH111C2

MODEL EQ2200IDC SERIES INITIATING DEVICE CIRCUIT AND MODEL EQ2200IDCGF SERIES INITIATING DEVICE CIRCUIT GROUND FAULT Explosion-proof for Class I, Division 1, Groups B, C, and D Hazardous (Classified) Locations per FM 3615. Dust ignition-proof for Class II, Division 1, Groups E, F, and G, Class III Hazardous (Classified) Locations per FM 3615. Non-incendive for Class I, Div. 2, Groups A, B, C, and D; Class II, Div. 2, Groups F and G; Class III; Temperature Code T4A Hazardous (Classified) Locations per FM 3611. EQ22EMIDC and EQ22EMIDCGF non-incendive for Class I, Div. 2, Groups A, B, C and D; Temperature Code T4A Hazardous (Classified) Locations per FM 3611. Enclosure Rating NEMA Type 4X per ANSI/NEMA 250. Operating Temperature Limits 40C to +75C. Storage Temperature Limits 55C to +85C. Relative Humidity Range: 5 to 95% RH. National Fire Alarm Code Performance verified per ANSI/NFPA 72-1996. The Model EQ2200IDC Series must be used in conjunction with any FMRC Approved device providing relay contact closure.

A-2

MODEL EQ2200UV & EQ2200UVHT with C7050B SERIES UV FLAME DETECTORS Explosion-proof for Class I, Division 1, Groups B, C, and D Hazardous (Classified) Locations per FM 3615. Dust ignition-proof for Class II, Division 1, Groups E, F, and G, Class III Hazardous (Classified) Locations per FM 3615. Non-incendive for Class I, Div. 2, Groups A, B, C, and D; Class II, Div. 2, Groups F and G; Class III; Temperature Code T4A Hazardous (Classified) Locations per FM 3611. Enclosure Rating NEMA Type 4X per ANSI/NEMA 250. Operating Temperature Limits 40C to +75C for EQ2200UV and EQ2200UVHT; -40C to +125C for C7050B. Storage Temperature Limits 55C to +85C. Relative Humidity Range: 5 to 95% RH. National Fire Alarm Code Performance verified per ANSI/NFPA 72-1996. Automatic Fire Alarm Signaling Performance verified per FM 3260. A Model EQ2200UV with B2 Module was verified to comply with the following performance criteria:

Response Characteristics SENSITIVITY Very High Very High Very High FUEL Gasoline Diesel Natural Gas SIZE 1 ft x 1 ft (0.3 m x 0.3 m) 1 ft x 1 ft (0.3 m x 0.3 m) 30 inch plume DISTANCE 90 ft (27.4 m) 65 ft (19.8 m) 80 ft (24.4 m)

Response Time Typical 5 seconds maximum.

Field of View 45 to +45 off centerline in vertical and horizontal planes.

False Alarm Immunity Detector does not respond to the following: Direct sunlight Indirect (reflected) sunlight Two 34 watt fluorescent lights at 3 feet (0.9 m) 100 watt incandescent light at 3 feet (0.9 m) 75 watt Phillips Far Spot incandescent light at 3 feet (0.9 m) 250 watt infrared heat lamp at 3 feet (0.9 m) 300 watt incandescent clear light at 3 feet (0.9 m) 500 watt Phillips quartz halogen light at 3 feet (0.9 m) 6000 watt infrared heater at 3 feet (0.9 m).

A-3

95-8470

UV Arc Rejection Short duration electrical arcs

Mounting Q9001L swivel mount for EQ2200UV; Q9001B swivel mount for C7050B.

MODEL EQ2200UVIR SERIES UV/IR FLAME DETECTOR Explosionproof for Class I, Division 1, Groups B, C, & D Hazardous (Classified) Locations per FM 3615. Dust-ignitionproof for Class II, Division 1, Groups E, F, & G, Class III Hazardous (Classified) Locations per FM 3615. Non-incendive for Class I, Division 2, Groups A, B, C and D; Class II, Division 2, Groups F and G; Class III; Temperature Code T4A Hazardous (Classified) Locations per FM 3611. Enclosure Rating NEMA Type 4X per ANSI/NEMA 250. Operating Temperature Limits 40C to +75C. Storage Temperature Limits 55C to +85C. Relative Humidity Range: 5 to 95% RH. National Fire Alarm Code Performance verified per ANSI/NFPA 72-1996. Automatic Fire Alarm Signaling Performance verified per FM 3260. A Model EQ2200UVIR with UV Module DE1888B2 and IR Module DE5600-002 was verified to comply with the following performance criteria:

A-4

Response Characteristics Fuel Gasoline Gasoline Gasoline Gasoline Methane Methane Methane Methane Propane Propane Methanol Methanol JP4 JP5 JP8 Size 1 Sq. Ft. 1 Sq. Ft. 1 Sq. Ft. 1 Sq. Ft. 30 inch 30 inch 30 inch 30 inch 30 inch 30 inch 1 Sq. Ft. 1 Sq. Ft. 4 Sq. Ft. 4 Sq. Ft. 4 Sq. Ft. Distance 100 Ft. 80 Ft. 65 Ft. 65 Ft. 90 Ft. 90 Ft. 40 Ft. 40 Ft. 30 Ft. 30 Ft. 40 Ft. 40 Ft. 100 Ft. 100 Ft. 100 Ft. UV Setting Very High (Standard) Very High (Arc Rej.) High (Standard) Very High (Arc Rej.) Very High (Standard) Very High (Arc Rej.) Low (Standard) Medium (Arc Rej.) Medium (Standard) Medium (Arc Rej.) High (Standard) Very High (Arc Rej.) High (Standard) High (Standard) High (Standard) IR Setting Very High Very High Medium Medium Very High Very High Low Low Medium Medium Low Low Medium Medium Medium

Response Time Typical 5 seconds maximum.

Field of View 45 to +45 off centerline in vertical and horizontal planes using gasoline fuel (1 sq. ft.). 40 to +40 off centerline in vertical and horizontal planes using methane fuel (30 inch).

A-5

95-8470

False Alarm Immunity Detector does not respond to the following: Direct sunlight A 150 watt incandescent light at 2 feet (0.6 m) Two 60 watt fluorescent bulbs at 2 feet (0.6 m) A 500 watt halogen lamp at 4 feet (1.2 m) The radiation produced by a Miller Dial-Arc 250-P arcwelder at 10 feet (3m), set at 50 amperes with 1/8 inch Type 601 welding rod. Vibration immunity for vertical displacement of 0.02 inch (0.5 mm) at a frequency of 10 to 30 Hz for 4 hours. Radio frequency interference (RFI) immunity at 12 inches to 155 MHz and 450 MHz with radiation power levels of 5.0 watts.

Mounting Model Q9001G Swivel Mounting Bracket.

MODEL EQ2200DCU SERIES DIGITAL COMMUNICATION UNITS Explosion-proof for Class I, Division 1, Groups B, C and D Hazardous (Classified) Locations per FM 3615. Dust ignition-proof for Class II, Division 1, Groups E, F, and G, Class III Hazardous (Classified) Locations per FM 3615 (For use with Sensor Separation Kit). Non-incendive for Class I, Div. 2, Groups A, B, C, and D; Temperature Code T4A Hazardous (Classified) Locations per FM 3611. Non-incendive for Class II, Div. 2, Groups F and G; Class III; Temperature Code T4A Hazardous (Classified) Locations per FM 3611. (For use with sensor separation kit.) EQ22EMDCU non-incendive for Class I, Div. 2, Groups A, B, C and D; Temperature Code T4A Hazardous (Classified) Locations per FM 3611. Enclosure Rating NEMA Type 4X per ANSI/NEMA 250 (For use with Sensor Separation Kit). Operating Temperature Limits 40C to +75C. Storage Temperature Limits 55C to +85C. Relative Humidity Range: 5 to 95% RH. Combustible gas performance verified with any FMRC Approved stand alone linear 4 to 20 mA device per FM 6310/6320. Accuracy: 3% LFL from 0 to 50% LFL, 5% LFL from 51% to 100% LFL. Toxic gas performance verified 0 to 100 ppm per FMRC requirements. Accuracy: 2 ppm from 0 to 20 ppm, 10% of concentration from 21 to 100 ppm. Models C7064E4012 and C7064E5012 Hydrogen Sulfide (H2S) Sensors Explosion-proof for Class I, Div. 1, Groups C and D Hazardous (Classified) Locations per FM 3615. Model C7064E5014 Hydrogen Sulfide (H2S) Sensors Explosion-proof for Class I, Div. 1, Groups B, C and D Hazardous (Classified) Locations per FM 3615. Operating temperature limits are 40C to +40C.

A-6

NOTE Sensor cross sensitivity has not been verified by FMRC. NOTE FMRC Approval of the 4 to 20 ma input does not include or imply approval of the gas detection apparatus such as sensors, transmitters, or devices connected to the system. In order to maintain FMRC Approval of the system, all 4 to 20 ma gas detection instruments connected to the input must also be FMRC Approved.

MODEL EQ2200DCUEX SERIES DIGITAL COMMUNICATION UNIT WITH MODEL CGS SERIES COMBUSTIBLE GAS SENSOR Explosion-proof for Class I, Division 1, Groups B, C, and D Hazardous (Classified) Locations per FM 3615. Dust ignition-proof for Class II, Division 1, Groups E, F, and G, Class III Hazardous (Classified) Locations per FM 3615. (For use with Sensor Separation Kit) Non-incendive for Class I, Div. 2, Groups A, B, C, and D; Temperature Code T4A Hazardous (Classified) Locations per FM 3611. Non-incendive for Class II, Div. 2, Groups F and G; Class III; Temperature Code T4A Hazardous (Classified) Locations per FM 3611. (For use with sensor separation kit.) EQ22EMDCUEX non-incendive for Class I, Div. 2, Groups A, B, C and D; Temperature Code T4A Hazardous (Classified) Locations per FM 3611. Enclosure Rating NEMA Type 4X per ANSI/NEMA 250 (For use with Sensor Separation Kit). Operating Temperature Limits 40C to +75C. Storage Temperature Limits 55C to +85C. Relative Humidity Range: 5 to 95% RH. Performance verified for 0 to 100% LFL methane-in-air atmospheres per FM 6310/6320. Accuracy: 3% LFL from 0 to 50% LFL, 5% LFL from 51% to 100% LFL.

NOTE The high temperature characteristic has NOT been FMRC verified above 75C. NOTE Detector Electronics combustible gas detection K factors are not FMRC verified. SENSOR SEPARATION KIT 226365-106 226365-113 226365-104 Combustible, Aluminum, 3/4 inch NPT, 4 Position Connector Combustible, Aluminum, 3/4 inch NPT, Wiring Harness Toxic, Aluminum, 3/4 inch NPT

Explosion-proof for Class I, Division 1, Groups B, C, and D Hazardous (Classified) Locations per FM 3615. NOTE Ensure sensor hazardous (classified) location rating is applicable for the intended use.

A-7

95-8470

MODEL EQ2500ARM SERIES AGENT RELEASE MODULE Explosion-proof for Class I, Division 1, Groups B, C, and D Hazardous (Classified) Locations per FM 3615. Dust ignition-proof for Class II, Div. 1, Groups E, F, and G, Class III Hazardous (Classified) Locations per FM 3615. Non-incendive for Class I, Div. 2, Groups A, B, C, and D; Class II, Div. 2, Groups F and G; Class III; Temperature Code T4A Hazardous (Classified) Locations per FM 3611. EQ25EMARM non-incendive for Class I, Div. 2, Groups A, B, C and D; Temperature Code T4A Hazardous (Classified) Locations per FM 3611. Enclosure Rating NEMA Type 4X per ANSI/NEMA 250. Operating Temperature Limits 40C to +75C. Storage Temperature Limits 55C to +85C. Relative Humidity Range: 5 to 95% RH. National Fire Alarm Code Performance verified per ANSI/NFPA 72-1996. Approved for use with the following automatic deluge and pre-action solenoids: Manufacturer Skinner ASCO ASCO Skinner Skinner Skinner Model LV2LBX25 8210A107 8210G207 73218BN4UNLVNOC111C2 73212BN4TNLVNOC322C2 71395SN2ENJ1NOH111C2

MODEL EQ2500SAM SERIES SIGNAL AUDIBLE MODULE Explosion-proof for Class I, Division 1, Groups B, C, and D Hazardous (Classified) Locations per FM 3615. Dust ignition-proof for Class II, Div. 1, Groups E, F, and G, Class III Hazardous (Classified) Locations per FM 3615. Non-incendive for Class I, Div. 2, Groups A, B, C, and D; Class II, Div. 2, Groups F and G; Class III; Temperature Code T4A Hazardous (Classified) Locations per FM 3611. EQ25EMSAM non-incendive for Class I, Div. 2, Groups A, B, C and D; Temperature Code T4A Hazardous (Classified) Locations per FM 3611. Enclosure Rating NEMA Type 4X per ANSI/NEMA 250. Operating Temperature Limits 40C to +75C. Storage Temperature Limits 55C to +85C. Relative Humidity Range: 5 to 95% RH. National Fire Alarm Code Performance verified per ANSI/NFPA 72-1996.

A-8

MODEL EQ2400NE SERIES NETWORK EXTENDER Explosion-proof for Class I, Division 1, Groups B, C, & D Hazardous (Classified) Locations per FM 3615. Dust ignition-proof for Class II, Div. 1, Groups E, F, & G, Class III Hazardous (Classified) Locations per FM 3615. Non-incendive for Class I, Div. 2, Groups A, B, C and D; Class II, Div. 2, Groups F and G; Class III; Temperature Code T4A Hazardous (Classified) Locations per FM 3611. EQ24EMNE non-incendive for Class I, Div. 2, Groups A, B, C and D; Temperature Code T4A Hazardous (Classified) Locations per FM 3611. Enclosure Rating NEMA / Type 4X per ANSI/NEMA 250. Operating Temperature Limits -40C to +75C. Storage Temperature Limits -55C to +85C. Relative Humidity Range: 5 to 95% RH. National Fire Alarm Code Performance verified per ANSI/NFPA 72-1996 and gas performance verified per FM 6310/6320.

OPTIONS
An optional EQ2101LCU with EQ2101MR Mounting Rack is available with provisions for two 24 vdc power inputs. The customer must supply two reliable and independent 24 vdc supplies in accordance with ANSI/NFPA 72-1996 section 1-5.2. If either of the supplies is missing due to a broken wire, a trouble condition will be annunciated. Operator Interface Station (OIS)

NOTE Metric straight thread types are for use in non-North American applications.

CALIBRATION

Calibration of the above listed sensors has been FMRC verified using the respective EQ2200DCU and EQ2200DCUEX Series with the Det-Tronics 225130-001 (50% LFL methane) and 227115-001 H2S Calibration Kits. The EQ2200DCU Series can be used with any FMRC Approved 4 to 20 ma device.

A-9

95-8470

A-10 Figure A1

APPENDIX B

CANADIAN STANDARDS ASSOCIATION (CSA) APPROVAL DESCRIPTION]


The Eagle Quantum Fire and Gas Detection/Suppression System (reference Figure B1) has the following CSA approved configurations:

MODEL EQ2100LCU SERIES LOCAL CONTROL UNIT (Up to four EQ2100LCU, four EQ2100CG and one EQ2100IM for maximum system.) Class I, Division 2, Groups A, B, C, and D; Temperature Code T4A Hazardous Locations per CSA C22.2 #213. Operating Temperature Limits 0C to +60C. Storage Temperature Limits 55C to +85C. Relative Humidity Range: 5 to 95% RH. Combustible Gas Performance verified for 0 to 100% LFL methane-in-air atmospheres per CSA C22.2 #152.

MODEL EQ2100LCUPS LOCAL CONTROL UNIT POWER SUPPLY AND MODEL EQ2175PS, EQ2130PS AND EQ2110PS POWER SUPPLIES WITH MODEL EQ2100PSM SERIES POWER SUPPLY MONITOR Ordinary Locations verified per CSA C22.2 #142. Operating Temperature Limits 0C to +50C. Storage Temperature Limits 55C to +85C. Relative Humidity Range: 5 to 95% RH.

MODEL EQ2100LIOU LOCAL INPUT/OUTPUT UNIT Ordinary Locations verified per CSA C22.2 #142. Operating Temperature Limits 0C to +50C. Storage Temperature Limits 55C to +85C. Relative Humidity Range: 5 to 95% RH.

B-1

95-8470

MODEL EQ2200IDC SERIES INITIATING DEVICE CIRCUIT AND MODEL EQ2200IDCGF SERIES INITIATING DEVICE CIRCUIT GROUND FAULT Explosion-proof for Class I, Division 1, Groups B, C, and D Hazardous Locations per CSA C22.2 #30. Dust ignition-proof for Class II, Division 1, Groups E, F, and G, Class III Hazardous Locations per CSA C22.2 #25. Non-incendive for Class I, Div. 2, Groups A, B, C, and D; Class II, Div. 2, Groups F and G; Class III; Temperature Code T4A Hazardous Locations per CSA C22.2 #213. EQ22EMIDC AND EQ22EMIDCGF non-incendive for Class I, Div. 2, Groups A, B, C, and D; Temperature Code T4A Hazardous Locations per CSA C22.2 #213. Enclosure Rating Type 4X per CSA C22.2 #94. Operating Temperature Limits 40C to +75C. Storage Temperature Limits 55C to +85C. Relative Humidity Range: 5 to 95% RH. The Model EQ2200IDC Series must be used in conjunction with any CSA certified device providing relay contact closure.

MODEL EQ2200UV SERIES UV FLAME DETECTOR: Explosion-proof for Class I, Division 1, Groups B, C and D Hazardous Locations per CSA C22.2 #30. Dust-ignitionproof for Class II, Division 1, Groups E, F, and G, Class III Hazardous Locations per CSA C22.2 #25. Non-incendive for Class I, Div. 2, Groups A, B, C, and D; Class II, Div. 2, Groups F and G; Class III; Temperature Code T4A Hazardous Locations per CSA C22.2 #213. Enclosure Rating Type 4X per CSA C22.2 #94. Operating Temperature Limits 40C to +75C. Storage Temperature Limits 55C to +85C. Relative Humidity Range: 5 to 95% RH. Optional Q9001L Swivel Mount.

MODEL EQ2200UVHT SERIES HIGH TEMPERATURE UV FLAME DETECTOR Explosion-proof for Class I, Division 1, Groups B, C and D Hazardous Locations per CSA C22.2 #30. Dust-ignitionproof for Class II, Division 1, Groups E, F, and G, Class III Hazardous Locations per CSA C22.2 #25. Non-incendive for Class I, Div. 2, Groups A, B, C, and D; Class II, Div. 2, Groups F and G; Class III; Temperature Code T4A Hazardous Locations per CSA C22.2 #213. Enclosure Rating Type 4X per CSA C22.2 #94. Operating Temperature Limits 40C to +75C for electronic module, 40C to +125C for UV detector. Storage Temperature Limits 55C to +85C. Relative Humidity Range: 5 to 95% RH. Optional Q9001B Swivel Mount for UV detector.

B-2

MODEL EQ2200UVIR SERIES UV/IR FLAME DETECTOR Explosionproof for Class I, Division 1, Groups B, C and D Hazardous Locations per CSA C22.2 #30. Dust-ignitionproof for Class II, Division 1, Groups E, F, and G, Class III Hazardous Locations per CSA C22.2 #25. Non-incendive for Class I, Division 2, Groups A, B, C and D; Class II, Division 2, Groups F and G; Class III; Temperature Code T4A Hazardous Locations per CSA C22.2 #213. Enclosure Rating Type 4X per CSA C22.2 #94. Operating Temperature Limits 40C to +75C. Storage Temperature Limits 55C to +85C. Relative Humidity Range: 5 to 95% RH. Optional Q9001G Swivel Mount.

MODEL EQ2200DCU SERIES DIGITAL COMMUNICATION UNITS Explosion-proof for Class I, Division 1, Groups B, C and D Hazardous Locations per CSA C22.2 #30. Dust ignition-proof for Class II, Division 1, Groups E, F, and G, Class III Hazardous Locations per CSA C22.2 #25 (For use with Sensor Separation Kit). Non-incendive for Class I, Div. 2, Groups A, B, C, and D; Temperature Code T4A Hazardous Locations per CSA C22.2 #213. Non-incendive for Class II, Div. 2, Groups F and G; Class III; Temperature Code T4A Hazardous Locations per CSA C22.2 #213 (For use with sensor separation kit.) EQ22EMDCU non-incendive for Class I, Div. 2, Groups A, B, C, and D; Temperature Code T4A Hazardous Locations per CSA C22.2 #213. Enclosure Rating Type 4X per CSA C22.2 #94 (For use with Sensor Separation Kit). Operating Temperature Limits 40C to +75C. Storage Temperature Limits 55C to +85C. Relative Humidity Range: 5 to 95% RH. Combustible gas performance verified with any CSA Certified stand alone linear 4 to 20 mA device per CSA C22.2 #152. Accuracy 3% LFL from 0 to 50% LFL, 5% LFL from 51% to 100% LFL.

B-3

95-8470

MODEL EQ2200DCUEX SERIES DIGITAL COMMUNICATION UNIT WITH MODEL CGS SERIES COMBUSTIBLE GAS SENSOR Explosion-proof for Class I, Division 1, Groups B, C, and D Hazardous Locations per CSA C22.2 #30. Dust ignition-proof for Class II, Division 1, Groups E, F, and G, Class III Hazardous Locations per CSA C22.2 #25 (For use with Sensor Separation Kit). Non-incendive for Class I, Div. 2, Groups A, B, C, and D; Temperature Code T4A Hazardous Locations per CSA C22.2 #213. Non-incendive for Class II, Div. 2, Groups F and G; Class III; Temperature Code T4A Hazardous Locations per CSA C22.2 #213 (For use with sensor separation kit.) EQ22EMDCUEX non-incendive for Class I, Div. 2, Groups A, B, C, and D; Temperature Code T4A Hazardous Locations per CSA C22.2 #213. Enclosure Rating Type 4X per CSA C22.2 #94 (For use with Sensor Separation Kit). Operating Temperature Limits 40C to +75C. Storage Temperature Limits 55C to +85C. Relative Humidity Range: 5 to 95% RH. Verified for 0 to 100% LFL methane-in-air atmospheres per CSA C22.2 #152. Accuracy: 3% LFL from 0 to 50% LFL, 5% LFL from 51% to 100% LFL.

NOTE The high temperature characteristic has NOT been CSA verified above 75C.

SENSOR SEPARATION KITS 226365-106 226365-113 226365-104 Combustible, Aluminum, 3/4 inch NPT, 4 Position Connector Combustible, Aluminum, 3/4 inch NPT, Wiring Harness Toxic, Aluminum, 3/4 inch NPT

Explosion-proof for Class I, Division 1, Groups B, C, and D Hazardous Locations per CSA C22.2 #30. NOTE Ensure sensor hazardous (classified) location rating is applicable for the intended use.

MODEL EQ2500ARM SERIES AGENT RELEASE MODULE Explosion-proof for Class I, Division 1, Groups B, C, and D Hazardous Locations per CSA C22.2 #30. Dust ignition-proof for Class II, Division 1, Groups E, F, and G, Class III Hazardous Locations per CSA C22.2 #25. Non-incendive for Class I, Div. 2, Groups A, B, C, and D; Class II, Div. 2, Groups F and G; Class III; Temperature Code T4A Hazardous Locations per CSA C22.2 #213. EQ25EMARM non-incendive for Class I, Div. 2, Groups A, B, C and D; Temperature Code T4A Hazardous Locations per CSA C22.2 #213. Enclosure Rating NEMA Type 4X per CSA C22.2 #94. Operating Temperature Limits 40C to +75C. Storage Temperature Limits 55C to +85C. Relative Humidity Range: 5 to 95% RH.

B-4

MODEL EQ2500SAM SERIES SIGNAL AUDIBLE MODULE Explosion-proof for Class I, Division 1, Groups B, C, and D Hazardous Locations per CSA C22.2 #30. Dust ignition-proof for Class II, Division 1, Groups E, F, and G, Class III Hazardous Locations per CSA C22.2 #25. Non-incendive for Class I, Div. 2, Groups A, B, C, and D; Class II, Div. 2, Groups F and G; Class III; Temperature Code T4A Hazardous Locations per CSA C22.2 #213. EQ25EMSAM non-incendive for Class I, Div. 2, Groups A, B, C, and D; Temperature Code T4A Hazardous Locations per CSA C22.2 #213. Enclosure Rating NEMA Type 4X per CSA C22.2 #94. Operating Temperature Limits 40C to +75C. Storage Temperature Limits 55C to +85C. Relative Humidity Range: 5 to 95% RH.

MODEL EQ2400NE SERIES NETWORK EXTENDER Explosion-proof for Class I, Division 1, Groups B, C, & D Hazardous Locations per CSA C22.2 #30. Dust ignition-proof for Class II, Div. 1, Groups E, F, & G, Class III Hazardous Locations per CSA C22.2 #25. Non-incendive for Class I, Div.2, Groups A, B, C and D; Class II, Div. 2, Groups F and G; Class III; Temperature Code T4A Hazardous Locations per CSA C22.2 #213. EQ24EMNE non-incendive for Class I, Div. 2, Groups A, B, C, and D; Temperature Code T4A Hazardous Locations per CSA C22.2 #213. Enclosure Rating NEMA / Type 4X per CSA C22.2 #94. Operating Temperature Limits -40C to +75C. Storage Temperature Limits -55C to +85C. Relative Humidity Range: 5 to 95% RH. Gas performance verified per CSA C22.2 #152.

OPTIONS
Operator Interface Station (OIS) NOTE Metric straight thread types are for use in non-North American applications.

CALIBRATION
Calibration of the above listed sensors has been CSA verified using the respective EQ2200DCU and EQ2200DCUEX Series with Det-Tronics 225130-001 (50% LFL methane) and 227115-001 H2S Calibration Kits. The Model EQ2200DCU Series can be used with any CSA certified stand alone 4 to 20 ma linear device.

B-5

95-8470

B-6 Figure B1

APPENDIX C
CE MARK
The Eagle Quantum Fire and Gas Detection/Suppression System was tested and found to be compliant with EN50081-2 and EN50082-2 when wired in conduit or with armoured instrument cable with individual screened twisted pairs and galvanized steel wire armour. All screen drains shall be terminated to the chassis except for the LON/SLC screen drains, which are terminated at LCU terminals 23 A and B and the LON/SLC screen termination in each field device. Communication wiring between the Local Control Unit (LCU), Local Input/Output Unit (LIOU) and Local Control Unit Power Supply (LCUPS) shall be limited to a maximum of 3 meters for each section.

CENELEC CERTIFICATION
INITIATING DEVICE CIRCUIT (IDC and IDCGF), DIGITAL COMMUNICATION UNIT (DCU) AGENT RELEASE MODULE (ARM), SIGNAL AUDIBLE MODULE (SAM), NETWORK EXTENDER (NE): EEx d IIC T4 (Tamb = 60C to +75C) EEx d IIC T5 (Tamb = 60C to +65C) EEx d IIC T6 (Tamb = 60C to +50C) IP66. Special Conditions for Safe Use To obviate the risk of hotspots and capacitor energy storage, the enclosure must not be opened, even when isolated, when a flammable atmosphere is present. Cable glands or the conduit entries to be used with this apparatus shall be EEx d approved by a notified body, relevant to the threads found with the enclosure where they are to be fixed. As guards do not protect the transparent windows of the devices, care shall be exercised during installation, positioning the face of the apparatus in order to prevent damage. UV FLAME DETECTOR: Standard Temperature Version EEx d IIB +H2 T6 (Tamb = 40C to +75C). IP66. Extended Temperature Version EEx d IIB +H2 T6 (Tamb = 40C to +75C) EEx d IIB +H2 T4 (Tamb = 40C to +125C) IP66. Special Conditions for Safe Use of UV Detector The detector contains capacitors that could be an ignition source if the enclosure is opened within a hazardous area. The enclosure must not be opened, even when isolated, when a flammable atmosphere is present. The cable must only be connected to the enclosure by a flameproof cable entry device certified to EN 50 018. If only one cable entry is used, any other entries must be closed by a certified flameproof stopping plug. The flame detector can be delivered in two versions, one for ambient temperatures up to +75C, and one for temperatures up to +125C. The label will indicate the actual maximum allowable ambient temperature.

C-1

95-8470

EQ2200UVHT SERIES UV FLAME DETECTOR Electronic Module EEx d IIC T4 (Tamb = 60C to +75C) EEx d IIC T5 (Tamb = 60C to +65C) EEx d IIC T6 (Tamb = 60C to +50C) IP66. UV Detector EEx d IIB +H2 T4 (Tamb = 55C to +125C) EEx d IIB +H2 T5 (Tamb = 55C to +90C) EEx d IIB +H2 T6 (Tamb = 55C to +75C) IP66. Special Conditions for Safe Use of UV Detector The cable entry temperature may rise 10C above the ambient temperature and cable shall be suitable for that temperature. The flame detector shall be electrically connected by means of a flame-proof cable gland or stopping box certified to EN 50018. The fused silica lens in this unit is liable to be damabed by impact. The unit should be installed in such a manner as to protect the lens from mechanical damage. UV/IR FLAME DETECTOR: Standard Temperature Version EEx d IIB +H2 T6 (Tamb = 40C to +75C). EEx d IIB +H2 T5 (Tamb = 40C to +90C). IP66. Extended Temperature Version EEx d IIB +H2 T6 (Tamb = 55C to +75C) EEx d IIB +H2 T5 (Tamb = 55C to +90C) EEx d IIB +H2 T4 (Tamb = 55C to +125C) IP66. Special Conditions for Safe Use of UV/IR Detector The UV detector module contains a fused silica window, which can be damaged by impact. The detector should be installed in such a manner as to prevent the window from receiving mechanical damage. CATALYTIC COMBUSTIBLE GAS SENSOR EEx d IIC T4 (Tamb = 55C to +105C). Special Conditions for Safe Use of Catalytic Gas Sensor The sensor can withstand repeated exposures to +125C for periods up to 12 hours. It is recommended that the sensor be replaced after a maximum of 500 hours of exposure to the +125C temperature conditions.

C-2

APPENDIX D

D-1

95-8470

Node Address 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70

1 X O X O X O X O X O X O X O X O X O X O X O X O X O X O X O X O X O X O X O X O X O X O X O X O X O X O X O X O X O X O X O X O X O X O X O

2 O X X O O X X O O X X O O X X O O X X O O X X O O X X O O X X O O X X O O X X O O X X O O X X O O X X O O X X O O X X O O X X O O X X O O X

Rocker Switch 3 4 5 6 O O O X X X X O O O O X X X X O O O O X X X X O O O O X X X X O O O O X X X X O O O O X X X X O O O O X X X X O O O O X X X X O O O O X X X O O O O O O O X X X X X X X X O O O O O O O O X X X X X X X X O O O O O O O O X X X X X X X X O O O O O O O O X X X X X X X X O O O O O O O O O O O O O O O O O O O O O O X X X X X X X X X X X X X X X X O O O O O O O O O O O O O O O O X X X X X X X X X X X X X X X X O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X O O O O O O O

Rocker Switch Table Node Address 7 8


O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O X X X X X X X O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 137 138 139 140

1 X O X O X O X O X O X O X O X O X O X O X O X O X O X O X O X O X O X O X O X O X O X O X O X O X O X O X O X O X O X O X O X O X O X O X O

2 X O O X X O O X X O O X X O O X X O O X X O O X X O O X X O O X X O O X X O O X X O O X X O O X X O O X X O O X X O O X X O O X X O O X X O

3 X O O O O X X X X O O O O X X X X O O O O X X X X O O O O X X X X O O O O X X X X O O O O X X X X O O O O X X X X O O O O X X X X O O O O X

Rocker Switch 4 5 6 O X X X X X X X X O O O O O O O O X X X X X X X X O O O O O O O O X X X X X X X X O O O O O O O O X X X X X X X X O O O O O O O O X X X X X O O O O O O O O O X X X X X X X X X X X X X X X X O O O O O O O O O O O O O O O O X X X X X X X X X X X X X X X X O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X O O O O O O O O O O O O O

7 X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X O O O O O O O O O O O O O

8 O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O X X X X X X X X X X X X X

D-2

Node Address 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187 188 189 190 191 192 193 194 195 196 197 198 199 200 201 202 203 204 205 206 207 208 209 210

1 X O X O X O X O X O X O X O X O X O X O X O X O X O X O X O X O X O X O X O X O X O X O X O X O X O X O X O X O X O X O X O X O X O X O X O

2 O X X O O X X O O X X O O X X O O X X O O X X O O X X O O X X O O X X O O X X O O X X O O X X O O X X O O X X O O X X O O X X O O X X O O X

Rocker Switch 3 4 5 6 X X X O O O O X X X X O O O O X X X X O O O O X X X X O O O O X X X X O O O O X X X X O O O O X X X X O O O O X X X X O O O O X X X X O O O X X X O O O O O O O O X X X X X X X X O O O O O O O O X X X X X X X X O O O O O O O O X X X X X X X X O O O O O O O O X X X X X X X X O O O O O O X X X X X X X X X X X X X X X X O O O O O O O O O O O O O O O O X X X X X X X X X X X X X X X X O O O O O O O O O O O O O O O O X X X O O O O O O O O O O O O O O O O O O O X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X O O O O O O O O O O O O O O O O O O O

Rocker Switch Table Node Address 7 8


O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X 211 212 213 214 215 216 217 218 219 220 221 222 223 224 225 226 227 228 229 230 231 232 233 234 235 236 237 238 239 240 241 242 243 244 245 246 247 248 249 250

1 X O X O X O X O X O X O X O X O X O X O X O X O X O X O X O X O X O X O X O X O

2 X O O X X O O X X O O X X O O X X O O X X O O X X O O X X O O X X O O X X O O X

3 O X X X X O O O O X X X X O O O O X X X X O O O O X X X X O O O O X X X X O O O

Rocker Switch 4 5 6 O O O O O X X X X X X X X O O O O O O O O X X X X X X X X O O O O O O O O X X X X X X X X X X X X X X X X O O O O O O O O O O O O O O O O X X X X X X X X X X X O O O O O O O O O O O O O X X X X X X X X X X X X X X X X X X X X X X X X X X X

7 X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X

8 X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X

O = OPEN X = CLOSED

D-3

95-8470

LON is a registered trademark of Echelon Corporation. Modbus is a registered trademark of Modicon Inc.

Вам также может понравиться