Вы находитесь на странице: 1из 2

Power cable, 0,6/1 kV, VDE tested halogen-free, without functionality

N2XH

Technical data
Power and control cable according to DIN VDE 0276 part 604, HD 604 S1 part 1 and part 5G Conductor resistance (at 208 C) according to VDE 0295 cl. 1 or 2 and IEC 60228 cl. 1 or 2 and HD 383 cl. 1 and cl. 2 Temperature range during installation 58 C to +508 C fixed installation 308 C to +908 C Permissible operating temperature at conductor +908 C Nominal voltage U0/U 0,6/1 kV Test voltage 4 kV Minimum bending radius single-core approx. 15 x cable 1 multi-core approx. 12 x cable 1 Tests Flame-test to VDE 0472 part 804, test method C, IEC 60332-3 and HD 405.3 Corrosiveness of combustion gases to VDE 0472 part 813, IEC 60754-2 and HD 602 Halogen-free to VDE 0472 part 815 and IEC 60754-1 Smoke density to VDE 0472 part 816, test method C, IEC 61034-1/61034-2, HD 606 and BS 7622 part 1 and 2
Part No. 53100 53101 53102 53103 53104 53105 53106 53107 53108 53109 53110 53111 53112 53113 53114 53115 53116 53117 53118 53119 53120 53121 53122 53123 53124 53125 53126 53127 53128 53129 53130 53131 53132 O O O O O O O O O O O O O O O O O O O O O No. of cores x cross-section mm2 1x4 1x6 1 x 10 1 x 16 1 x 25 1 x 35 1 x 50 1 x 70 1 x 95 1 x 120 1 x 150 1 x 185 1 x 240 1 x 300 2 x 1,5 2 x 2,5 2x4 2x6 2 x 10 2 x 16 2 x 25 3 x 1,5 3 x 2,5 3x4 3x6 3 x 10 3 x 16 3 x 25 3 x 35 3 x 50 3 x 70 3 x 95 3 x 120 re re re re rm rm rm rm rm rm rm rm rm rm re re re re re re rm re re re re re re rm rm rm rm rm rm Outer 1 ca. mm 8,0 9,0 9,0 10,0 11,0 12,0 15,0 17,0 19,0 21,0 23,0 25,0 28,0 30,0 12,0 12,2 13,2 14,1 16,2 17,8 21,0 13,0 14,0 15,0 16,0 18,0 20,0 21,8 24,9 25,2 29,2 32,0 34,9 Cop. weight kg / km 39 58 96 154 240 336 480 672 912 1152 1440 1776 2304 2880 29 48 77 115 192 307 480 43 72 115 173 288 461 720 1008 1440 2016 2736 3456

Cable structure
Plain Cu wire conductor, single or multiple-wire, according to DIN VDE 0295 cl. 1 or 2 and IEC 60228 cl. 1 or 2, HD 383 Halogen-free core insulation, crosslinked polyethylene compound 2XI1, to HD 604 S1 Colour coding of cores according to DIN VDE 0293 and HD 186 Green-yellow earth-core, 3 cores and above Cores stranded in layers (for multi-core cables) Overall filled inner sheath, covered by filling compound or wrapped tape Outer sheath of thermoplastic polyolefine compound HM4, to HD 604 S1, halogen-free Sheath colour black Advantages Halogen-free, no separation of corrosive or toxic gases Limited propagation of fire Low smoke development Caloric load values see page T 64

Application
Halogen-free power cables with enhanced characteristics in case of fire are used for applications where harm to human life and damage to property must be prevented in the event of fire, e. g. in industrial installations, communal establishments, hotels, airports, underground stations, railway stations, hospitals department stores, banks, schools theaters, multi-storey buildings, process control centres etc. Suitable for fixed installation in dry, damp or wet environments, in, above, on and beneath plaster as well as in masonary walls and in concrete. These cables are suitable for outdoor applications and in underground by using in conduits or tubes. Additionally valid also DIN VDE 0298 part 1 and 2. The materials used in manufacture are cadmium-free and contain no silicone and free from substances harmful to the wetting properties of lacquers
*) Note AWG sizes are approximate equivalent values. The actual cross-section is in mm2 see page T 15.

= The product is conformed with the EC Low-Voltage Directive 73/23/EEC and 93/68/EEC.
Weigth ca. kg / km 68 90 140 190 290 390 510 710 960 1200 1480 1910 2370 2970 185 220 275 335 450 620 930 220 280 350 420 600 770 1120 1550 1750 2450 3250 4000 AWGno.*) 12 10 8 6 4 2 1 2/0 3/0 4/0 MCM MCM MCM MCM 16 14 12 10 8 6 4 16 14 12 10 8 6 4 2 1 2/0 3/0 4/0 Part No. 53133 53134 53135 53136 53137 53138 53139 53140 53141 53142 53143 53144 53145 53146 53147 53148 53149 53150 53151 53152 53153 53154 53155 53156 53157 53158 53159 53160 53161 53162 53163 No. of cores x cross-section mm2 3 x 150 rm 3 x 185 rm 3 x 240 rm 3 x 50/25 rm 3 x 70/35 rm 3 x 95/50 rm 3 x 120/70 rm 3 x 150/70 rm 3 x 185/95 rm 3 x 240/120 rm 4 x 1,5 4 x 2,5 4x4 4x6 4 x 10 4 x 16 4 x 25 4 x 35 4 x 50 4 x 70 4 x 95 4 x 120 4 x 150 4 x 185 4 x 240 5 x 1,5 5 x 2,5 5x4 5x6 5 x 10 5 x 16 re re re re re re rm rm rm rm rm rm rm rm rm re re re re re re Outer 1 ca. mm 39,2 44,1 49,2 28,5 31,4 34,9 38,0 43,3 47,2 53,4 13,0 14,0 15,0 16,0 18,0 20,0 25,0 27,0 28,0 32,0 36,0 40,2 45,8 49,5 56,0 14,5 16,0 17,0 18,5 21,0 24,0 Cop. weight kg / km 4320 5328 6912 1680 2352 3216 4128 4992 6240 8064 58 96 154 230 384 614 960 1344 1920 2668 3648 4608 5760 7104 9216 72 120 192 288 480 768 Weigth ca. kg / km 5000 6150 8000 2100 2800 3750 4750 5750 7200 9300 235 290 370 470 670 930 1440 1890 2300 3200 4250 5350 6550 8100 10550 280 350 450 600 850 1200 AWGno.*)

300 MCM 350 MCM 500 MCM 1 2/0 3/0 4/0 300 MCM 350 MCM 500 MCM 16 14 12 10 8 6 4 2 1 2/0 3/0 4/0 300 MCM 350 MCM 500 MCM 16 14 12 10 8 6 Continuation "

300 350 500 600

rm = round conductor, multiple-wire, re = round conductor, single-wire

G 11

Power cable, 0,6/1 kV, VDE tested halogen-free, without functionality

N2XH

Technical data
Power and control cable according to DIN VDE 0276 part 604, HD 604 S1 part 1 and part 5G Conductor resistance (at 208 C) according to VDE 0295 cl. 1 or 2 and IEC 60228 cl. 1 or 2 and HD 383 cl. 1 and cl. 2 Temperature range during installation 58 C to +508 C fixed installation 308 C to +908 C Permissible operating temperature at conductor +908 C Nominal voltage U0/U 0,6/1 kV Test voltage 4 kV Minimum bending radius single-core approx. 15 x cable 1 multi-core approx. 12 x cable 1 Tests Flame-test to VDE 0472 part 804, test method C, IEC 60332-3 and HD 405.3 Corrosiveness of combustion gases to VDE 0472 part 813, IEC 60754-2 and HD 602 Halogen-free to VDE 0472 part 815 and IEC 60754-1 Smoke density to VDE 0472 part 816, test method C, IEC 61034-1/61034-2, HD 606 and BS 7622 part 1 and 2
Part No. 53164 53165 53166 53167 53168 53169 53170 No. of cores x cross-section mm2 7 x 1,5 10 x 1,5 12 x 1,5 14 x 1,5 19 x 1,5 24 x 1,5 30 x 1,5 re re re re re re re Outer 1 ca. mm 15,5 18,5 19,0 20,0 22,0 25,0 26,0 Cop. weight kg / km 101 144 173 202 274 346 432

Cable structure
Plain Cu wire conductor, single or multiple-wire, according to DIN VDE 0295 cl. 1 or 2 and IEC 60228 cl. 1 or 2, HD 383 Halogen-free core insulation, crosslinked polyethylene compound 2XI1, to HD 604 S1 Colour coding of cores according to DIN VDE 0293 and HD 186 Green-yellow earth-core, 3 cores and above Cores stranded in layers (for multi-core cables) Overall filled inner sheath, covered by filling compound or wrapped tape Outer sheath of thermoplastic polyolefine compound HM4, to HD 604 S1, halogen-free Sheath colour black Advantages Halogen-free, no separation of corrosive or toxic gases Limited propagation of fire Low smoke development Caloric load values see page T 64
Weigth ca. kg / km 350 480 520 550 700 850 950 AWGno.*) 16 16 16 16 16 16 16 Part No. 53171 53172 53173 53174 53175 53176 53177 53178 53179 No. of cores x cross-section mm2 7 x 2,5 10 x 2,5 12 x 2,5 14 x 2,5 19 x 2,5 24 x 2,5 30 x 2,5 7x4 12 x 4 re re re re re re re re re

Application
Halogen-free power cables with enhanced characteristics in case of fire are used for applications where harm to human life and damage to property must be prevented in the event of fire, e. g. in industrial installations, communal establishments, hotels, airports, underground stations, railway stations, hospitals department stores, banks, schools theaters, multi-storey buildings, process control centres etc. Suitable for fixed installation in dry, damp or wet environments, in, above, on and beneath plaster as well as in masonary walls and in concrete. These cables are suitable for outdoor applications and in underground by using in conduits or tubes. Additionally valid also DIN VDE 0298 part 1 and 2.

The materials used in manufacture are cadmium-free and contain no silicone and free from substances harmful to the wetting properties of lacquers
Outer 1 ca. mm 17,0 20,5 21,0 22,0 24,0 27,0 28,0 17,2 21,2 Cop. weight kg / km 168 240 288 336 456 576 720 269 461 Weigth ca. kg / km 370 500 560 630 800 990 1180 530 800 AWGno.*) 14 14 14 14 14 14 14 12 12

= The product is conformed with the EC Low-Voltage Directive 73/23/EEC and 93/68/EEC.

re = round conductor, single-wire rm = round conductor, multiple-wire *) Note AWG sizes are approximate equivalent values. The actual cross-section is in mm2 see page T 15.