Вы находитесь на странице: 1из 201

Rels e Contatores de Estado Slido

SIRIUS
Coletnea de dados tcnicos (product data sheet)
Agosto/2012
SSR - 3RF21
22,5 mm
Ponto Zero
SSR - 3RF20
45 mm
Ponto Zero
SSR - 3RF22
45 mm
Ponto Zero
Trifsico
Controle 2 fases
SSR - 3RF22
45 mm
Ponto Zero
Trifsico
Controle 3 fases
SSC - 3RF23
Ponto Zero
Monofsico
SSC - 3RF23
Instantneo
Monofsico
SSC - 3RF24
Ponto Zero
Trifsico
Controle 2 fases
SSC - 3RF24
Ponto Zero
Trifsico
Controle 3 fases
Monitor carga
Bsico
Mdulo
Conversor
SSC - 3RF34
Instantneo
Trifsico
Para motores
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS Solid-State Switching Devices 3RF20... Solid-State Relays
Subject to changes 07/2010 Page 1/7
http://www.siemens.com/solid-state-switching-devices
Main Characteristics:
LED display
Plug-in control terminal
Degree of protection IP 20
Easy replacement of existing relays
Zero-point switching

Standards / Approvals:
DIN EN 60947-4-3
UL 508 / CSA
CE
C-Tick


Ordering Key:
3RF20 20 - 1 A A 0 2
Max.
load current
Connection
technology
Switching
function
Controlled
phases
Control
voltage
Operating
voltage
45 mm solid
state relay
without
heat sink
20 = 20 A
30 = 30 A
50 = 50 A
70 = 70 A
90 = 88 A
1 = Screw connection A = Zero-point
switching

A = Single-phase 0 = 24 V DC
2 = 110 - 230 V AC
4 = 4 - 30 V DC

2 = 24 - 230 V
4 = 48 - 460 V
5 = 48 - 600 V
6 = 48 - 600 V
Not all possible versions are available ex stock.

Main Circuit
1
:
I
max
I
e
IEC 947-4-3 I
e
UL/CSA
Power
loss
Min. load
current
Max. leakage
current
Type A
With Rthha
/ 40 C
A
With Rthha
/ 40 C
A
With Rthha
/ 50 C
With I
max

W
A mA
3RF2020-. 20 2.0 K/W 20 1.7 K/W 20 1.3 K/W 28.5 0.1 10
3RF2030-. 30 1.1 K/W 30 0.79 K/W 30 0.56 K/W 44 0.5 10
3RF2050-. 50 0.68 K/W 50 0.48 K/W 50 0.33 K/W 66 0.5 10
3RF2070-. 70 0.40 K/W 50 0.77 K/W 50 0.60 K/W 94 0.5 10
3RF2090-. 88 0.33 K/W 50 0.94 K/W 50 0.85 K/W 118 0.5 10

Type 3RF20. . - . AA. 2 3RF20. . - . AA. 4 3RF20. . - . AA. 5
3RF20. . -
. AA. 6
Rated operating voltage U
e
V 24 ... 230 48 ... 460 48 ... 600 48 ... 600
Voltage range V 20 ... 253 40 ... 506 40 ... 660 40 ... 660
Rated frequency Hz 50/60 10 %
Rated insulation voltage U
i
V 600
Rated impulse withstand voltage U
imp
kV 6
Blocking voltage V 800 1200 1200 1600
Slew rate V/s 1000









1
The current I
max
provides information about the performance of the solid-state relays. The actual permitted rated
operating current I
e
can be smaller depending on the connection method and cooling conditions. The spring-
loaded terminals version can be used for a rated current of up to approx. 20 A with one conductor and up to
approx. 40 A with two conductor on each terminal.
VOLTAR
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS Solid-State Switching Devices 3RF20... Solid-State Relays
Subject to changes 07/2010 Page 2/7
http://www.siemens.com/solid-state-switching-devices

Rated impulse
withstand strength Itsm
I
2
t value
Type A A
2
s
3RF2020- . 200 200
3RF2030- . AA. 2 300 450
3RF2030- . AA. 4 300 450
3RF2030- . AA. 6 400 800
3RF2050-. 600 1800
3RF2070- . AA. 2 1200 7200
3RF2070- . AA. 4 1200 7200
3RF2070- . AA. 6 1150 6600
3RF2090- . 1150 6600

Control Circuit A1-A2:
Type 3RF20. . - . AA0. 3RF20. . - . AA2. 3RF20. . - . AA4.
Control voltage U
s
V 24 DC (EN 61131-2) 110 ... 230 AC 4 ... 30 DC
Max. control voltage U
s
V 30 253 30
Typical operating current mA 20 15 20
Response voltage V 15 90 4
Drop-out voltage V 5 40 1
Rated frequency
of the control supply voltage
Hz -- 50/60 10 % --
Switching times ON delay ms
1 + Max. one
half-wave
40 + Max. one
half-wave
1 + Max. one
half-wave
OFF delay ms
1 + Max. one
half-wave
40 + Max. one
half-wave
1 + Max. one
half-wave


General Data:
Ambient temperature
During operation, derating as of 40 C C -25 ... 60
During storage C -55 ... 80
Mounting altitude m 0 ... 1000; at > 1000 m, please contact our Technical Assistance
Impact resistance acc. to DIN IEC 68 g/ms 15/11
Vibration resistance g 2
Degree of protection IP20
Electromagnetic compatibility
(EMC)

Interference emission
o Conducted interference voltage
IEC 60 947-4-3
Class A for industrial applications
2

o Radiated, high-frequency
interference voltage IEC 60 947-4-3
Class B for residential/office/commercial applications
Interference resistance
o Electrostatic discharge acc. to
IEC 61 000-4-2 (corresponds
to severity 3)
kV Contact discharge 4; air discharge 8; performance criterion 2
o Induced HF fields acc. to
IEC 61 000-4-6
MHz 0.15 ... 80; 140 dBV; performance criterion 1
o Burst acc. to IEC 61 000-4-4 kV 2/5.0 kHz; performance criterion 2
o Surge acc. to IEC 61 000-4-5 kV Phase-to-ground 2; phase-to-phase 1; performance criterion 2
Dielectric Strength 50/60 Hz
(Input, Output / Base)
V rms 4000


2
Attention!
This product was constructed as a EMC Class A device. The use of this product in residential applications could
lead to radio interferences. In such an application, additional filtering may be required.
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS Solid-State Switching Devices 3RF20... Solid-State Relays
Type 3RF20. . - 1.
Connection, main contacts Screw connection
Conductor cross-section
o Solid mm
2
2 x (1.5 ... 2.5); 2 x (2.5 ... 6)
o Finely stranded with end sleeve mm
2
2 x (1.5 ... 2.5); 2 x (2.5 ... 6); 1 x 10
o Finely stranded w/o end sleeve mm
2
-
o Solid or stranded AWG 2 x (14 ... 10)
Stripping length mm 10
Terminal screw M 4
Nm 2 ... 2.5 o Tightening torque
D 5...6 mm / PZ 2
lb.in 18 ... 22

Type 3RF20. . - 1.
Connection, auxiliary/control contacts Screw connection
Conductor-cross section with or
without end sleeve
mm
mm
AWG
1 x (0.5 ... 2.5)
2 x (0.5 ... 1.0)
20 ... 12
Stripping length mm 7
Terminal screw M 3
Nm 0.5 ... 0.6 o Tightening torque
D 3.5 / PZ 1
lb.in 4.5 ... 5.3

Subject to changes 07/2010 Page 3/7
http://www.siemens.com/solid-state-switching-devices
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS Solid-State Switching Devices 3RF20... Solid-State Relays
Subject to changes 07/2010 Page 4/7
http://www.siemens.com/solid-state-switching-devices

Type Semiconductor protection fuse
Full-range fuse Partial-range fuse
LV HRC design Cylindrical
design
LV HRC
design
Cylindrical design
3

gR/SITOR gR/Neozed aR/SITOR aR/SITOR
3NE1 5SE1 3NE8 3NC1 0 3NC1 4 3NC2 2
10 x 38 14 x 51 22 x 58
3RF2020- . 2 3NE1814-0 5SE 1325 3NE 8015-1 3NC1032 3NC1430 3NC2225
3RF2020- . 4 3NE1813-0
5
5SE 1320 3NE 8015-1 3NC1016
5
3NC1425 3NC2220
3RF2020- . 5
4
3NE1813-0
5
5SE 1320 3NE 8015-1 3NC1016
5
3NC1425 3NC2220
3RF2030- . 2 3NE1815-0
5
5SE 1335 3NE 8003-1 3NC1032 3NC1440 3NC2240
3RF2030- . 4 3NE1815-0
5
5SE 1325
5
3NE 8003-1 3NC1025
5
3NC1430 3NC2232
3RF2030- . 6 3NE1815-0
5
-- 3NE 8003-1 3NC1032 3NC1440 3NC2240
3RF2050- . 2 3NE1817-0 5SE 1350 3NE 8017-1 -- 3NC1450 3NC2263
3RF2050- . 4 3NE1802-0
5
5SE 1335
5
3NE 8017-1 -- 3NC1450 3NC2250
3RF2050- . 5
4
3NE1802-0
5
5SE 1335
5
3NE 8017-1 -- 3NC1450 3NC2250
3RF2050- . 6 3NE1803-0
5
-- 3NE 8017-1 -- 3NC1450 3NC2250
3RF2070- . 2
6
3NE1820-0 5SE 1363
5
3NE 8020-1 -- -- 3NC2200
3RF2070- . 4
6
3NE1020-2 5SE 1363
5
3NE 8020-1 -- -- 3NC2280
3RF2070- . 5
64
3NE1020-2 -- 3NE 8020-1 -- -- 3NC2280
3RF2070- . 6
6
3NE1020-2 -- 3NE 8020-1 -- -- 3NC2280
3RF2090- . 2
6
3NE1021-2 -- 3NE 8021-1 -- -- 3NC2200
3RF2090- . 4
6
3NE1021-2 -- 3NE 8021-1 -- -- 3NC2280
5

3RF2090- . 5
64
3NE1021-2 -- 3NE 8021-1 -- -- 3NC2280
5

3RF2090- . 6
6
3NE1817-0
5
-- 3NE 8021-1 -- -- 3NC2280
5


Typ Line protection fuse
LV HRC design
5
Cylindrical design
5
DIAZED
gG gG gG gG fast
3NA 3NW 3NW 3NW 5SB
10 x 38 mm 14 x 51 mm 22 x 58 mm
3RF2020- . 2 3NA6803 3NW6001-1 3NW6101-1 -- 5SB171
3RF2020- . 4 3NA6801 -- 3NW6101-1 -- 5SB141
5

3RF2020- . 5
4
3NA6801 -- 3NW6101-1 -- 5SB141
5

3RF2030- . 2 3NA6803 -- 3NW6103-1 -- 5SB311
3RF2030- . 4 3NA6803 -- 3NW6101-1 -- 5SB171
5

3RF2030- . 6 3NA6803-6 -- -- -- --
3RF2050- . 2 3NA6810 -- 3NW6107-1 3NW6207-1
3RF2050- . 4 3NA6807 -- -- 3NW6205-1 5SB311
5

3RF2050- . 5
4
3NA6807 -- -- 3NW6205-1 5SB311
5

3RF2050- . 6 3NA6807-6 -- -- -- --
3RF2070- . 2
6
3NA6817 -- -- 3NW6217-1 5SB331
5

3RF2070- . 4
6
3NA6812 -- -- 3NW6212-1 5SB331
5

3RF2070- . 5
64
3NA6812 -- -- 3NW6212-1 --
3RF2070- . 6
6
3NA6812-6 -- -- -- --
3RF2090- . 2
6
3NA6817 -- -- 3NW6217-1 --
3RF2090- . 4
6
3NA6812 -- -- 3NW6212-1 --
3RF2090- . 5
64
3NA6812 -- -- 3NW6212-1 --
3RF2090- . 6
6
3NA6812-6 -- -- -- --

Accessories:

No accessories are available for the 3RF20 solid state relays.

3
Max. allowable fuse; with smaller fuses the load reversal stability can be limited.
4
Use in applications with max 506V.
5
These fuses have a lower rated current than the solid state relays.
6
Protection against short circuit with m.c.b. (See catalog LV1 - chapter Solid-State Switching Devices)
Fused Design with Semiconductor Protection:
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS Solid-State Switching Devices 3RF20... Solid-State Relays

Characteristic Curves:

3RF2020-

Ambient temperature Ta in C
Device current Ie in A
1,3 K/W
1,6 K/W
2 K/W
2,5 K/W
3,2 K/W
4 K/W
6 K/W
8 K/W
12 K/W
5 K/W
2 6 10 14 18 22
P
o
w
e
r

l
o
s
s

P
M

i
n

W
0
5
10
15
20
25
30
35
40
0 10 20 30 40 50 60
Min. thickness of the heat sink the relay is mounted to
4 mm





















3RF2030-

0
10
20
30
40
50
60
0 10 20 30 40 50 60
0,65 K/W
0,85 K/W
1,1K/W
1,5 K/W
2,1K/W
3 K/W
5 K/W
7 K/W
10 K/W
4 K/W
6 10 14 18 22 26 30 34
P
o
w
e
r

l
o
s
s

P
M

i
n

W
Ambient temperature Ta in C Device current Ie in A
Min. thickness of the heat sink the relay is mounted to
4 mm 5 mm
Subject to changes 07/2010 Page 5/7
http://www.siemens.com/solid-state-switching-devices
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS Solid-State Switching Devices 3RF20... Solid-State Relays
3RF2050-

0
10
20
30
40
50
60
70
80
90
0 10 20 30 40 50 60
0,4 K/W
0,53 K/W
0,68 K/W
0,85 K/W
1,1K/W
1,5 K/W
3 K/W
5 K/W
10 K/W
2 K/W
5 10 15 20 25 30 35 40 45 50 55 60
P
o
w
e
r

l
o
s
s

P
M

i
n

W
Ambient temperature Ta in C Device current Ie in A
Min. thickness of the heat sink the relay is mounted to
4 mm 5 mm 8 mm


















3RF2070-

3 K/W
0,4 K/W
5 K/W
0,22 K/W
0,3 K/W
0,55 K/W
0,75 K/W
1K/W
2 K/W
1,5 K/W
10 20 30 40 50 60 70 80
P
o
w
e
r

l
o
s
s

P
M

i
n

W

0
20
40
60
80
100
120
0 10 20 30 40 50 60
Ambient temperature Ta in C Device current Ie in A
Min. thickness of the heat sink the relay is mounted to
4 mm 5 mm 8 mm 10 mm


















3RF2090-
10 20 30 40 50 60 70 80 90
M
o
d
u
l
e

p
o
w
e
r

l
o
s
s

P
M

i
0
20
40
60
80
100
120
0 10 20 30 40 50 60
0,24 K/W
0,3 K/W
0,39 K/W
0,5 K/W
0,65 K/W
0,85 K/W
1,6 K/W
2,5 K/W
4 K/W
1,1K/W
Ambient temperature Ta in C Device current Ie in A
Min. thickness of the heat sink the relay is mounted to
4 mm 5 mm 8 mm 10 mm

Subject to changes 07/2010 Page 6/7
http://www.siemens.com/solid-state-switching-devices
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS Solid-State Switching Devices 3RF20... Solid-State Relays

Dimension Drawings:


Subject to changes 07/2010 Page 7/7
http://www.siemens.com/solid-state-switching-devices













Dimensions in mm (in)


Device / Example Circuit Diagram:

3RF20. . - . AA0. 3RF20. . - . AA2.
Us = 24 V DC Us = 110 ... 230 V DC

1/N/PE 50 Hz 230 V
1 L
2 T
A2 ~
A1 ~
N
PE
L
F1
K1
R
S1
ON /OFF
F2

1/N/PE 50 Hz 230 V
1 L
2 T
A2 -
A1 +
N
PE
L
F1
K1
R
S1
ON /OFF
L -
L +
DC 24 V
F2
F1 Main circuit fuse
(semiconductor protection
recommended)
F2 Control circuit fuse
K1 3RF2 solid state relay
R Load resistance
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS Solid-State Switching Devices
3RF21..-AA. Zero-point Switching Solid-State Relays
Subject to changes 08/2011 Page 1/7
http://www.siemens.com/solid-state-switching-devices
Main Characteristics:
Space-saving, width of only 22.5 mm
LED display
Various connection technologies
Plug-in control terminal
Degree of protection IP 20
Zero-point switching

Standards / Approvals:
DIN EN 60947-4-3
UL 508 / CSA
CE
C-Tick

Ordering Key:
3RF21 20 - 1 A A 0 2
Max.
load current
Connection
technology
Switching
function
Controlled
phases
Control
voltage
Operating
voltage
Solid state
relay without
heat sink
20 = 20 A
30 = 30 A
50 = 50 A
70 = 70 A
90 = 88 A
1 = Screw connection
2 = Spring-loaded
3 = Ring cable
connection M5
A = Zero-point
switching

A = Single-phase 0 = 24 V DC
2 = 110 - 230 V AC
4 = 4 - 30 V DC

2 = 24 - 230 V
4 = 48 - 460 V
5 = 48 - 600 V
6 = 48 - 600 V
Not all possible versions are available ex stock.

Main Circuit
1
:
Imax Ie IEC 947-4-3 Ie UL/CSA
Power
loss
Min. load
current
Max. reverse
current
Type A
With Rthha
/ 40 C
A
With Rthha
/ 40 C
A
With Rthha
/ 50 C
With Imax
W
A mA
3RF2120-. 20 2.0 K/W 20 1.7 K/W 20 1.3 K/W 28.5 0.1 10
3RF2130-1. 30 1.1 K/W 30 0.79 K/W 30 0.56 K/W 44 0.5 10
3RF2150-1. 50 0.68 K/W 50 0.48 K/W 50 0.33 K/W 66 0.5 10
3RF2150-2. 20 2.60 K/W 20 2.90 K/W
3RF2150-3. 50 0.48 K/W 50 0.33 K/W
3RF2170-1. 70 0.40 K/W 50 0.77 K/W 50 0.60 K/W 94 0.5 10
3RF2190-1. 88 0.33 K/W 50 0.94 K/W 50 0.85 K/W 118 0.5 10
3RF2190-2. 20 2.80 K/W 20 3.50 K/W
3RF2190-3. 88 0.22 K/W 83 0.19 K/W

Type 3RF21. . - . AA. 2 3RF21. . - . AA. 4 3RF21. . - . AA. 5 3RF21. . - . AA. 6
Rated operating voltage Ue V 24 ... 230 48 ... 460 48 ... 600 48 ... 600
Voltage range V 20 ... 253 40 506 40 660 40 660
Rated frequency Hz 50/60 10 %
Rated insulation voltage Ui V 600
Rated impulse withstand voltage U
imp
kV 6
Blocking voltage V 800 1200 1200 1600
Slew rate V/s 1000


1
The current Imax provides information about the performance of the solid-state relays. The actual permitted rated
operating current Ie can be smaller depending on the connection method and cooling conditions. The spring-
loaded terminals version can be used for a rated current of up to approx. 20 A with one conductor and up to
approx. 40 A with two conductor on each terminal.
VOLTAR
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS Solid-State Switching Devices
3RF21..-AA. Zero-point Switching Solid-State Relays
Subject to changes 08/2011 Page 2/7
http://www.siemens.com/solid-state-switching-devices

Rated impulse withstand strength Itsm I
2
t value
Type A A
2
s
3RF2120- . 200 200
3RF2130- . AA. 2 300 450
3RF2130- . AA. 4 300 450
3RF2130- . AA. 6 400 800
3RF2150-. 600 1800
3RF2170- . AA. 2 1200 7200
3RF2170- . AA. 4 1200 7200
3RF2170- . AA. 6 1150 6600
3RF2190- . 1150 6600

Control Circuit A1-A2:
Type 3RF21. . - . AA0. 3RF21. . - . AA2. 3RF21. . - . AA4.
Control voltage Us V 24 DC (EN 61131-2) 110 ... 230 AC 4 ... 30 DC
Max. control voltage Us V 30 253 30
Typical operating current mA 20 ( <10
2
) 15 20
Response voltage V 15 90 4
Drop-out voltage V 5 40 1
Rated frequency
of the control supply voltage
Hz -- 50/60 10 % --
Switching times ON delay ms 1 + max. one half-wave 40 + max. one half-wave 1 + max. one half-wave
OFF delay ms 1 + max. one half-wave 40 + max. one half-wave 1 + max. one half-wave

General Data:
Ambient temperature
During operation, derating as of 40 C C -25 ... 60
During storage C -55 ... 80
Mounting altitude m 0 ... 1000; at > 1000 m, please contact our Technical Assistance
Impact resistance acc. to DIN IEC 68 g/ms 15/11
Vibration resistance g 2
Degree of protection IP20
Electromagnetic compatibility (EMC)
Interference emission
o Conducted interference voltage
IEC 60 947-4-3
Class A for industrial applications
3

o Radiated, high-frequency
interference voltage IEC 60 947-4-3
Class B for residential/office/commercial applications
Interference resistance
o Electrostatic discharge acc. to
IEC 61 000-4-2 (corresponds
to severity 3)
kV Contact discharge 4; air discharge 8; performance criterion 2
o Induced HF fields acc. to
IEC 61 000-4-6
MHz 0.15 ... 80; 140 dBV; performance criterion 1
o Burst acc. to IEC 61 000-4-4 kV 2/5.0 kHz; performance criterion 2
o Surge acc. to IEC 61 000-4-5 kV Phase-to-ground 2; phase-to-phase 1; performance criterion 2
Dielectric Strength 50/60 Hz
(Input, Output / Base)
V rms 4000


2
Only Low Power consumption Versions 3RF21..-.AA..-0KN0
3
Attention!
This product was constructed as a EMC Class A device. The use of this product in residential applications could
lead to radio interferences. In such an application, additional filtering may be required.
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS Solid-State Switching Devices
3RF21..-AA. Zero-point Switching Solid-State Relays
Subject to changes 08/2011 Page 3/7
http://www.siemens.com/solid-state-switching-devices

Type 3RF21. . - 1. 3RF21. . - 2. 3RF21. . - 3.
Connection, main contacts Screw connection Spring-loaded connection Ring cable connection
Conductor cross-section
o Solid mm
2

2 x (1.5 ... 2.5),
2 x (2.5 ... 6)
2x (0.5 ... 2.5)
o Finely stranded with end sleeve mm
2

2 x (1.5 ... 2.5),
2 x (2.5 ... 6), 1 x 10
2x (0.5 ... 1.5)
o Finely stranded w/o end sleeve mm
2
2x (0.5 ... 2.5)
o Solid or stranded AWG 2 x (14 ... 10) 2 x (18 ... 14)
Stripping length mm 10 10
Terminal screw M 4 - M 5
Nm 2 ... 2.5 - 2 ... 2.5 o Tightening torque
D 5...6 mm / PZ 2
lb.in 18 ... 22 - 18 ... 22
Cable lug DIN - - DIN 46234 5-2.5 ... 5-25
4
JIS - - JIS C 2805 R 2-5 14-5

Type 3RF21. . - 1. 3RF21. . - 2. 3RF21. . - 3.
Connection, auxiliary/control contacts Screw connection
Spring-loaded
connection
Ring cable connection
Conductor cross-section with or
without end sleeve
mm
mm
AWG
1 x (0.5 ... 2.5)
2 x (0.5 ... 1.0)
20 ... 12
0.5 ... 2.5

20 ... 12
1 x (0.5 ... 2.5)
2 x (0.5 ... 1.0)
20 ... 12
Stripping length mm 7 10 7
Terminal screw M 3 - M 3
Nm 0.5 ... 0.6 - 0.5 ... 0.6 o Tightening torque
D 3.5 / PZ 1
lb.in 4.5 ... 5.3 - 4.5 ... 5.3


Type Semiconductor protection fuse
Full-range fuse Partial-range fuse
LV HBC design Cylindrical design LV HBC design Cylindrical design
5

gR/gS/SITOR gR/Neozed aR/gR/SITOR aR/SITOR
3NE1 5SE1 3NE8 3NC1 0 3NC1 4 3NC2 2
10 x 38 14 x 51 22 x 58
3RF2120- . 2 3NE1814-0 5SE 1325 3NE 8015-1 3NC1032 3NC1430 3NC2225
3RF2120- . 4 3NE1813-0
6
5SE 1320 3NE 8015-1 3NC1016
6
3NC1420 3NC2220
3RF2120- . 5
7
3NE1813-0
6
5SE 1320 3NE 8015-1 3NC1016
6
3NC1420 3NC2220
3RF2130- . 2 3NE1815-0
6
5SE 1335 3NE 8003-1 3NC1032 3NC1440 3NC2240
3RF2130- . 4 3NE1815-0
6
5SE 1325
6
3NE 8003-1 3NC1025
6
3NC1430 3NC2232
3RF2130- . 5
7
3NE1815-0
6
5SE 1325
6
3NE 8003-1 3NC1025
6
3NC1430 3NC2232
3RF2130- . 6 3NE1815-0
6
-- 3NE 8003-1 3NC1032 3NC1440 3NC2240
3RF2150- . 2 3NE1817-0 5SE 1350 3NE 8017-1 -- 3NC1450 3NC2263
3RF2150- . 4 3NE1802-0
6
5SE 1335
6
3NE 8017-1 -- 3NC1450 3NC2250
3RF2150- . 5
7
3NE1802-0
6
5SE 1335
6
3NE 8017-1 -- 3NC1450 3NC2250
3RF2150- . 6 3NE1803-0
6
-- 3NE 8017-1 -- 3NC1450 3NC2250
3RF2170- . 2
8
3NE1820-0 5SE 1363
6
3NE 8020-1 -- -- 3NC2200
3RF2170- . 4
8
3NE1020-2 5SE 1363
6
3NE 8020-1 -- -- 3NC2280
3RF2170- . 5
87
3NE1020-2 -- 3NE 8020-1 -- -- 3NC2280
3RF2170- . 6
8
3NE1020-2 -- 3NE 8020-1 -- -- 3NC2280
3RF2190- . 2
8
3NE1021-2 -- 3NE 8021-1 -- -- 3NC2200
3RF2190- . 4
8
3NE1021-2 -- 3NE 8021-1 -- -- 3NC2280
6

3RF2190- . 5
87
3NE1021-2 -- 3NE 8021-1 -- -- 3NC2280
6

3RF2190- . 6
8
3NE1817-0
6
-- 3NE 8021-1 -- -- 3NC2280
6


4
Maximum breadth of the Cable lug 12 mm!
5
Max. allowable fuse; with smaller fuses the load reversal stability can be limited.
6
These fuses have a lower rated current than the solid state relays.
7
Use in applications with max 506V.
8
Protection against short circuit with m.c.b. (See catalog LV1 - chapter Solid-State Switching Devices)
Fused Design with Semiconductor Protection
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS Solid-State Switching Devices
3RF21..-AA. Zero-point Switching Solid-State Relays
Subject to changes 08/2011 Page 4/7
http://www.siemens.com/solid-state-switching-devices

Typ Line protection fuse
LV HRC design
6
Cylindrical design
6
Neozed
6
DIAZED
6

gG gG gG gG gG fast
3NA 3NW 3NW 3NW 5SE2 5SB
10 x 38 mm 14 x 51 mm 22 x 58 mm
3RF2120- . 2 3NA6803 3NW6001-1 3NW6101-1 -- 5SE2306 5SB141
3RF2120- . 4 3NA6801 -- 3NW6101-1 -- 5SE2306 5SB141
3RF2120- . 5
7
3NA6801 -- 3NW6101-1 -- 5SE2306 5SB141
3RF2130- . 2 3NA6803 -- 3NW6103-1 -- 5SE2313-2A 5SB171
3RF2130- . 4 3NA6803 -- 3NW6101-1 -- 5SE2313-2A 5SB171
3RF2130- . 5
7
3NA6803 -- 3NW6101-1 -- 5SE2313-2A 5SB171
3RF2130- . 6 3NA6803-6 -- -- -- -- --
3RF2150- . 2 3NA6810 -- 3NW6107-1 3NW6207-1 5SE2320 5SB311
3RF2150- . 4 3NA6807 -- -- 3NW6205-1 5SE2320 5SB311
3RF2150- . 5
7
3NA6807 -- -- 3NW6205-1 5SE2320 5SB311
3RF2150- . 6 3NA6807-6 -- -- -- -- --
3RF2170- . 2
8
3NA6817 -- -- 3NW6217-1 5SE2335 5SB331
3RF2170- . 4
8
3NA6812 -- -- 3NW6212-1 5SE2335 5SB331
3RF2170- . 5
78
3NA6812 -- -- 3NW6212-1 5SE2335 5SB331
3RF2170- . 6
8
3NA6812-6 -- -- -- -- --
3RF2190- . 2
8
3NA6817 -- -- 3NW6217-1 5SE2335 5SB331
3RF2190- . 4
8
3NA6812 -- -- 3NW6212-1 5SE2335 5SB331
3RF2190- . 5
78
3NA6812 -- -- 3NW6212-1 5SE2335 5SB331
3RF2190- . 6
8
3NA6812-6 -- -- -- -- --





Accessories:
Function module Order No. Applicable for the
following types
Versions
Converter 3RF2900-0EA18 3RF21. . - . AA0.
3RF21. . - . AA4.
Us = 24 V AC/DC
Load monitoring Basic 3RF29. . -0FA08 3RF21. . - 1AA0.
3RF21. . - 1AA4.
Screw connection
Us = 24 V DC
Load monitoring Extended
9
3RF29. . - 0GA. . 3RF21. . - 1. Screw connection
3RF21. . - 3. Ring cable connection
Terminal cover
10
3RF2900-3PA88 3RF21. . - 1. Screw connection
3RF21. . - 3. Ring cable connection


9
For the exact allocation of the function modules, please refer to the LV 1 Catalog.
10
The terminal cover can be easily adjusted for screw connection applications.
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS Solid-State Switching Devices
3RF21..-AA. Zero-point Switching Solid-State Relays
Subject to changes 08/2011 Page 5/7
http://www.siemens.com/solid-state-switching-devices

Characteristic Curves:

3RF2120-




















3RF2130-





















3RF2150-














Ambient temperature Ta in C
Device current Ie in A
1,3 K/W
1,6 K/W
2 K/W
2,5 K/W
3,2 K/W
4 K/W
6 K/W
8 K/W
12 K/W
5 K/W
2 6 10 14 18 22
P
o
w
e
r

l
o
s
s

P
M

i
n

W
0
5
10
15
20
25
30
35
40
0 10 20 30 40 50 60
Min. thickness of the heat sink the relay is mounted to
4 mm
0
10
20
30
40
50
60
0 10 20 30 40 50 60
0,65 K/W
0,85 K/W
1,1K/W
1,5 K/W
2,1K/W
3 K/W
5 K/W
7 K/W
10 K/W
4 K/W
6 10 14 18 22 26 30 34
P
o
w
e
r

l
o
s
s

P
M

i
n

W
Ambient temperature Ta in C Device current Ie in A
Min. thickness of the heat sink the relay is mounted to
4 mm 5 mm
0
10
20
30
40
50
60
70
80
90
0 10 20 30 40 50 60
0,4 K/W
0,53 K/W
0,68 K/W
0,85 K/W
1,1K/W
1,5 K/W
3 K/W
5 K/W
10 K/W
2 K/W
5 10 15 20 25 30 35 40 45 50 55 60
P
o
w
e
r

l
o
s
s

P
M

i
n

W
Ambient temperature Ta in C Device current Ie in A
Min. thickness of the heat sink the relay is mounted to
4 mm 5 mm 8 mm
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS Solid-State Switching Devices
3RF21..-AA. Zero-point Switching Solid-State Relays
Subject to changes 08/2011 Page 6/7
http://www.siemens.com/solid-state-switching-devices





3RF2170-



















RF2190-




















Dimension Drawings:
3 K/W
0,4 K/W
5 K/W
0,22 K/W
0,3 K/W
0,55 K/W
0,75 K/W
1K/W
2 K/W
1,5 K/W
10 20 30 40 50 60 70 80
P
o
w
e
r

l
o
s
s

P
M

i
n

W

0
20
40
60
80
100
120
0 10 20 30 40 50 60
Ambient temperature Ta in C Device current Ie in A
Min. thickness of the heat sink the relay is mounted to
4 mm 5 mm 8 mm 10 mm
10 20 30 40 50 60 70 80 90
P
o
w
e
r

l
o
s
s

P
M

i
n

W
0
20
40
60
80
100
120
0 10 20 30 40 50 60
0,24 K/W
0,3 K/W
0,39 K/W
0,5 K/W
0,65 K/W
0,85 K/W
1,6 K/W
2,5 K/W
4 K/W
1,1K/W
Ambient temperature Ta in C Device current Ie in A
Min. thickness of the heat sink the relay is mounted to
4 mm 5 mm 8 mm 10 mm
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS Solid-State Switching Devices
3RF21..-AA. Zero-point Switching Solid-State Relays
Subject to changes 08/2011 Page 7/7
http://www.siemens.com/solid-state-switching-devices



Device / Example Circuit Diagram:

3RF21. . - . AA0. 3RF21. . - . AA2.
Us = 24 V DC Us = 110 ... 230 V AC

1/N/PE 50 Hz 230 V
1 L
2 T
A2 ~
A1 ~
N
PE
L
F1
K1
R
S1
ON /OFF
F2

1/N/PE 50 Hz 230 V
1 L
2 T
A2 -
A1 +
N
PE
L
F1
K1
R
S1
ON /OFF
L -
L +
DC 24 V
F2
F1 Main circuit fuse
(semiconductor protection
recommended)
F2 Control circuit fuse
K1 3RF2 solid state relay
R Load resistance
Screw
connection
Spring-loaded
connection
All other dimensions as
with screw connection
Ring cable
connection
All other dimensions as
with screw connection
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF22..-.AB. Zero-point Switching 3-phase Solid State Relays
Main Characteristics:
2-phase control
Space-saving, width of only 45 mm
LED display
Various connection technologies
Plug-in control terminal
Degree of protection IP 20
Standards / Approvals:
DIN EN 60947-4-3
UL 508 / CSA
1

CE / C-Tick
Ordering Key:
3RF22 30 - 1 A B 4 5
Max.
load current
Connection
technology
Switching
function
Controlled
phases
Control
voltage
Operating
voltage
Solid state
relay without
heat sink
30 = 30 A
55 = 55 A
1 = Screw connection
2 = Spring-loaded
3 = Ring cable
connection M5
A = Zero-point
switching

B = 2-phase 3 = 110 VAC
4 = 4 - 30 VDC

5 = 48 - 600 V

Not all possible versions are available ex stock.

Main Circuit
2
:
I
max
I
e
IEC 947-4-3 I
e
UL/CSA
Power
loss
Min.load
current
Max. leakage
current
Type A
With Rthha
/ 40 C
A
With Rthha
/ 40 C
A
With Rthha
/ 50 C
With I
max

W
A mA
3RF2230-. 30 0,57 K/W 30 0,57 K/W 30 0,44 K/W 81 0,5 10
3RF2230-2. 20 1,36 K/W 20 1,15 K/W
3RF2255-. 55 0,18 K/W 55 0,18 K/W 55 0,12 K/W 151
3RF2255-2. 20 1,83 K/W 20 1,58 K/W

Type 3RF22. . - . AB. 5
Rated operating voltage U
e
V 48 ... 600
Voltage range V 40 ... 660
Rated frequency Hz 50/60 10 %
Rated insulation voltage U
i
V 600
Rated impulse withstand voltage U
imp
kV 6
Blocking voltage V 1200
Slew rate V/s 1000

Rated impulse withstand strength Itsm I
2
t value
Type A A
2
s
3RF2230- . 300 450
3RF2255-. 600 1800

Control Circuit A1-A2:
Type 3RF22. . - . AB3. 3RF22. . - . AB4.
Control voltage U
s
V AC 110 DC 4 ... 30
Max. control voltage U
s
V 121 30
Typical operating current mA 15 30
Response voltage V 90 4
Drop-out voltage V < 40 1
Switching times ON delay ms 40 + max. one half-wave 1 + max. one half-wave
OFF delay ms 40 + max. one half-wave 1 + max. one half-wave


1
Use overvoltage protection device; max cut-off-voltage 6.000 V; min energy handling capability 100 J
2
The current I
max
provides information about the performance of the solid-state relays. The actual permitted rated operating current I
e

can be smaller depending on the connection method and cooling conditions. The spring-loaded terminals version can be used for a
rated current of up to approx. 20 A with one conductor and up to approx. 40 A with two conductor on each terminal.
Subject to changes 08/2010 Page 1/5
http://www.siemens.com/solid-state-switching-devices
VOLTAR
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF22..-.AB. Zero-point Switching 3-phase Solid State Relays
Subject to changes 08/2010 Page 2/5
http://www.siemens.com/solid-state-switching-devices

General Data:
Ambient temperature
During operation, derating as of 40 C C -25 ... 60
During storage C -55 ... 80
Mounting altitude m 0 ... 1000; at > 1000 m, please contact our Technical Assistance
Impact resistance acc. to DIN IEC 68 g/ms 15/11
Vibration resistance g 2
Degree of protection IP20
Electromagnetic compatibility
Interference emission
o Conducted interference voltage
IEC 60 947-4-3
Class A for industrial applications
3

Interference resistance
o Electrostatic discharge acc. to
IEC 61 000-4-2 (corresponds
to severity 3)
kV Contact discharge 4; air discharge 8; performance criterion 2
o Induced HF fields acc. to
IEC 61 000-4-6
MHz 0.15 ... 80; 140 dBV; performance criterion 1
o Burst acc. to IEC 61 000-4-4 kV 2/5.0 kHz; performance criterion 2
o Surge acc. to IEC 61 000-4-5 kV Phase-to-ground 2; phase-to-phase 1; performance criterion 2
Dielectric Strength 50/60 Hz
(Input, Output / Base)
V rms 4000

Type 3RF22. . - 1. 3RF22. . - 2. 3RF22. . - 3.
Connection, main contacts Screw connection
Spring-loaded
connection
Ring cable connection
Conductor cross-section
o Solid mm
2

2 x (1,5 ... 2,5),
2 x (2,5 ... 6)
2x (0,5 ... 2,5)
o Finely stranded with end sleeve mm
2

2 x (1,5 ... 2,5),
2 x (2,5 ... 6), 1 x 10
2x (0,5 ... 1,5)
o Finely stranded w/o end sleeve mm
2
2x (0,5 ... 2,5)
o Solid or stranded AWG 2 x (14 ... 10) 2 x (18 ... 14)
Stripping length mm 10 10
Terminal screw M 4 - M 5
Nm 2 ... 2,5 - 2 ... 2,5 o Tightening torque
D 5...6 mm / PZ 2
lb.in 18 ... 22 - 18 ... 22
Cable lug DIN - - DIN 46234 5-2,5 ... 5-25
JIS - - JIS C 2805 R 2-5 14-5
Connection, auxiliary/control
contacts

Conductor cross-section with or
without end sleeve
mm
mm
AWG
1 x (0,5 ... 2,5)
2 x (0,5 ... 1,0)
20 ... 12
0,5 ... 2,5

20 ... 12
1 x (0,5 ... 2,5)
2 x (0,5 ... 1,0)
20 ... 12
Stripping length mm 7 10 7
Terminal screw M 3 - M 3
Nm 0,5 ... 0,6 - 0,5 ... 0,6 o Tightening torque
D 3.5 / PZ 1
lb.in 4,5 ... 5,3 - 4,5 ... 5,3


3
Attention!
This product was constructed as an EMC Class A device. The use of this product in residential applications could
lead to radio interferences. In such an application, additional filtering may be required.
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF22..-.AB. Zero-point Switching 3-phase Solid State Relays

Type Semiconductor protection fuse
Full-range fuse Partial-range fuse
LV HBC
design
cylindrical
design
LV HBC
design
cylindrical design
gR/SITOR gR/Neozed
4
aR/SITOR aR/SITOR
3NE1 5SE1 3NE8 3NC1 0 3NC1 4 3NC2 2
10 x 38 14 x 51 22 x 58
Maximum operation voltage U
e
460V (+10%)
3RF2230- 3NE1814-0
5
5SE1325
5
3NE 8003-1 3NC1032 3NC1430 3NC2232
3RF2255- 3NE1802-0
5
5SE1350
5
3NE 8018-1 -- 3NC1450 3NC2263
Maximum operation voltage U
e
600 V (+10%)
3RF2230- 3NE1814-0 -- 3NE 8003-1 3NC1025 3NC1430 3NC2232
3RF2255- 3NE1803-0 -- 3NE 8018-1 -- 3NC1450 3NC2250
Fused Design with Semiconductor Protection:


Type Line protection fuse
LV HBC design cylindrical design DIAZED
gG gG gG gG fast
3NA 3NW 3NW 3NW 5SB
10 x 38 mm 14 x 51 mm 22 x 58 mm
Maximum operation voltage U
e
460V (+10%)
3RF2230- 3NA3803-6
5
-- 3NW6101-1
5
3NW6205-1
5
5SB171
5

3RF2255- 3NA3807-6
5
-- -- -- 5SB311
5

Maximum operation voltage U
e
600 V (+10%)
3RF2230- 3NA3803-6
5
-- -- -- --
3RF2255- 3NA3805-6
5
-- -- -- --


Accessories:
Function module Order No. Applicable for the
following types
Versions
Converter 3RF2900-0EA18 3RF22. . - . AB4. Us = AC/DC 24 V
























4
Operation voltage only up to 400V!
Subject to changes 08/2010 Page 3/5
5
These fuses have a lower rated current than the solid state relay.
http://www.siemens.com/solid-state-switching-devices
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF22..-.AB. Zero-point Switching 3-phase Solid State Relays


Characteristic Curves:

3RF2230-
Rthha
0
20
40
60
80
100
0 10 20 30 40 50 60
0,35 K/W
0,45 K/W
0,56 K/W
0,75 K/W
1 K/W
1,3 K/W
1,7 K/W
2,2 K/W
3 K/W
4 K/W
5 K/W
7 K/W
10 K/W
4 8 12 16 20 24 28 32 36
3 mm 5 mm
Min. thickness of the heat sink the relay is mounted to
Ta in C
P
M

i
n

W
Ie in A


3RF2255-
Rthha
0
20
40
60
80
100
120
140
160
0 10 20 30 40 50 60
0,13 K/W
0,18 K/W
0,25 K/W
0,37 K/W
0,55 K/W
0,8 K/W
1,2 K/W
2 K/W
3 K/W
4 K/W
5 K/W
7 K/W
10 K/W
5 15 25 35 45 55
3 mm 5 mm
Min. thickness of the heat sink the relay is mounted to
Ie in A Ta in C
P
M

i
n

W


















Subject to changes 08/2010 Page 4/5
http://www.siemens.com/solid-state-switching-devices
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF22..-.AB. Zero-point Switching 3-phase Solid State Relays
Dimension Drawings
6
:

Screw
connection
Spring-loaded
connection
Ring cable
connection
Device / Example Circuit Diagram:



Subject to changes 08/2010 Page 5/5
6
Dimensions in mm (in)
http://www.siemens.com/solid-state-switching-devices
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF22..-.AB. Zero-point Switching 3-phase Solid State Relays
Main Characteristics:
2-phase control
Space-saving, width of only 45 mm
LED display
Various connection technologies
Plug-in control terminal
Degree of protection IP 20
Standards / Approvals:
DIN EN 60947-4-3
UL 508 / CSA
1

CE / C-Tick
Ordering Key:
3RF22 30 - 1 A B 4 5
Max.
load current
Connection
technology
Switching
function
Controlled
phases
Control
voltage
Operating
voltage
Solid state
relay without
heat sink
30 = 30 A
55 = 55 A
1 = Screw connection
2 = Spring-loaded
3 = Ring cable
connection M5
A = Zero-point
switching

B = 2-phase 3 = 110 VAC
4 = 4 - 30 VDC

5 = 48 - 600 V

Not all possible versions are available ex stock.

Main Circuit
2
:
I
max
I
e
IEC 947-4-3 I
e
UL/CSA
Power
loss
Min.load
current
Max. leakage
current
Type A
With Rthha
/ 40 C
A
With Rthha
/ 40 C
A
With Rthha
/ 50 C
With I
max

W
A mA
3RF2230-. 30 0,57 K/W 30 0,57 K/W 30 0,44 K/W 81 0,5 10
3RF2230-2. 20 1,36 K/W 20 1,15 K/W
3RF2255-. 55 0,18 K/W 55 0,18 K/W 55 0,12 K/W 151
3RF2255-2. 20 1,83 K/W 20 1,58 K/W

Type 3RF22. . - . AB. 5
Rated operating voltage U
e
V 48 ... 600
Voltage range V 40 ... 660
Rated frequency Hz 50/60 10 %
Rated insulation voltage U
i
V 600
Rated impulse withstand voltage U
imp
kV 6
Blocking voltage V 1200
Slew rate V/s 1000

Rated impulse withstand strength Itsm I
2
t value
Type A A
2
s
3RF2230- . 300 450
3RF2255-. 600 1800

Control Circuit A1-A2:
Type 3RF22. . - . AB3. 3RF22. . - . AB4.
Control voltage U
s
V AC 110 DC 4 ... 30
Max. control voltage U
s
V 121 30
Typical operating current mA 15 30
Response voltage V 90 4
Drop-out voltage V < 40 1
Switching times ON delay ms 40 + max. one half-wave 1 + max. one half-wave
OFF delay ms 40 + max. one half-wave 1 + max. one half-wave


1
Use overvoltage protection device; max cut-off-voltage 6.000 V; min energy handling capability 100 J
2
The current I
max
provides information about the performance of the solid-state relays. The actual permitted rated operating current I
e

can be smaller depending on the connection method and cooling conditions. The spring-loaded terminals version can be used for a
rated current of up to approx. 20 A with one conductor and up to approx. 40 A with two conductor on each terminal.
Subject to changes 08/2010 Page 1/5
http://www.siemens.com/solid-state-switching-devices
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF22..-.AB. Zero-point Switching 3-phase Solid State Relays
Subject to changes 08/2010 Page 2/5
http://www.siemens.com/solid-state-switching-devices

General Data:
Ambient temperature
During operation, derating as of 40 C C -25 ... 60
During storage C -55 ... 80
Mounting altitude m 0 ... 1000; at > 1000 m, please contact our Technical Assistance
Impact resistance acc. to DIN IEC 68 g/ms 15/11
Vibration resistance g 2
Degree of protection IP20
Electromagnetic compatibility
Interference emission
o Conducted interference voltage
IEC 60 947-4-3
Class A for industrial applications
3

Interference resistance
o Electrostatic discharge acc. to
IEC 61 000-4-2 (corresponds
to severity 3)
kV Contact discharge 4; air discharge 8; performance criterion 2
o Induced HF fields acc. to
IEC 61 000-4-6
MHz 0.15 ... 80; 140 dBV; performance criterion 1
o Burst acc. to IEC 61 000-4-4 kV 2/5.0 kHz; performance criterion 2
o Surge acc. to IEC 61 000-4-5 kV Phase-to-ground 2; phase-to-phase 1; performance criterion 2
Dielectric Strength 50/60 Hz
(Input, Output / Base)
V rms 4000

Type 3RF22. . - 1. 3RF22. . - 2. 3RF22. . - 3.
Connection, main contacts Screw connection
Spring-loaded
connection
Ring cable connection
Conductor cross-section
o Solid mm
2

2 x (1,5 ... 2,5),
2 x (2,5 ... 6)
2x (0,5 ... 2,5)
o Finely stranded with end sleeve mm
2

2 x (1,5 ... 2,5),
2 x (2,5 ... 6), 1 x 10
2x (0,5 ... 1,5)
o Finely stranded w/o end sleeve mm
2
2x (0,5 ... 2,5)
o Solid or stranded AWG 2 x (14 ... 10) 2 x (18 ... 14)
Stripping length mm 10 10
Terminal screw M 4 - M 5
Nm 2 ... 2,5 - 2 ... 2,5 o Tightening torque
D 5...6 mm / PZ 2
lb.in 18 ... 22 - 18 ... 22
Cable lug DIN - - DIN 46234 5-2,5 ... 5-25
JIS - - JIS C 2805 R 2-5 14-5
Connection, auxiliary/control
contacts

Conductor cross-section with or
without end sleeve
mm
mm
AWG
1 x (0,5 ... 2,5)
2 x (0,5 ... 1,0)
20 ... 12
0,5 ... 2,5

20 ... 12
1 x (0,5 ... 2,5)
2 x (0,5 ... 1,0)
20 ... 12
Stripping length mm 7 10 7
Terminal screw M 3 - M 3
Nm 0,5 ... 0,6 - 0,5 ... 0,6 o Tightening torque
D 3.5 / PZ 1
lb.in 4,5 ... 5,3 - 4,5 ... 5,3


3
Attention!
This product was constructed as an EMC Class A device. The use of this product in residential applications could
lead to radio interferences. In such an application, additional filtering may be required.
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF22..-.AB. Zero-point Switching 3-phase Solid State Relays

Type Semiconductor protection fuse
Full-range fuse Partial-range fuse
LV HBC
design
cylindrical
design
LV HBC
design
cylindrical design
gR/SITOR gR/Neozed
4
aR/SITOR aR/SITOR
3NE1 5SE1 3NE8 3NC1 0 3NC1 4 3NC2 2
10 x 38 14 x 51 22 x 58
Maximum operation voltage U
e
460V (+10%)
3RF2230- 3NE1814-0
5
5SE1325
5
3NE 8003-1 3NC1032 3NC1430 3NC2232
3RF2255- 3NE1802-0
5
5SE1350
5
3NE 8018-1 -- 3NC1450 3NC2263
Maximum operation voltage U
e
600 V (+10%)
3RF2230- 3NE1814-0 -- 3NE 8003-1 3NC1025 3NC1430 3NC2232
3RF2255- 3NE1803-0 -- 3NE 8018-1 -- 3NC1450 3NC2250
Fused Design with Semiconductor Protection:


Type Line protection fuse
LV HBC design cylindrical design DIAZED
gG gG gG gG fast
3NA 3NW 3NW 3NW 5SB
10 x 38 mm 14 x 51 mm 22 x 58 mm
Maximum operation voltage U
e
460V (+10%)
3RF2230- 3NA3803-6
5
-- 3NW6101-1
5
3NW6205-1
5
5SB171
5

3RF2255- 3NA3807-6
5
-- -- -- 5SB311
5

Maximum operation voltage U
e
600 V (+10%)
3RF2230- 3NA3803-6
5
-- -- -- --
3RF2255- 3NA3805-6
5
-- -- -- --


Accessories:
Function module Order No. Applicable for the
following types
Versions
Converter 3RF2900-0EA18 3RF22. . - . AB4. Us = AC/DC 24 V
























4
Operation voltage only up to 400V!
Subject to changes 08/2010 Page 3/5
5
These fuses have a lower rated current than the solid state relay.
http://www.siemens.com/solid-state-switching-devices
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF22..-.AB. Zero-point Switching 3-phase Solid State Relays


Characteristic Curves:

3RF2230-
Rthha
0
20
40
60
80
100
0 10 20 30 40 50 60
0,35 K/W
0,45 K/W
0,56 K/W
0,75 K/W
1 K/W
1,3 K/W
1,7 K/W
2,2 K/W
3 K/W
4 K/W
5 K/W
7 K/W
10 K/W
4 8 12 16 20 24 28 32 36
3 mm 5 mm
Min. thickness of the heat sink the relay is mounted to
Ta in C
P
M

i
n

W
Ie in A


3RF2255-
Rthha
0
20
40
60
80
100
120
140
160
0 10 20 30 40 50 60
0,13 K/W
0,18 K/W
0,25 K/W
0,37 K/W
0,55 K/W
0,8 K/W
1,2 K/W
2 K/W
3 K/W
4 K/W
5 K/W
7 K/W
10 K/W
5 15 25 35 45 55
3 mm 5 mm
Min. thickness of the heat sink the relay is mounted to
Ie in A Ta in C
P
M

i
n

W


















Subject to changes 08/2010 Page 4/5
http://www.siemens.com/solid-state-switching-devices
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF22..-.AB. Zero-point Switching 3-phase Solid State Relays
Dimension Drawings
6
:

Screw
connection
Spring-loaded
connection
Ring cable
connection
Device / Example Circuit Diagram:



Subject to changes 08/2010 Page 5/5
6
Dimensions in mm (in)
http://www.siemens.com/solid-state-switching-devices
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF22..-.AB. Zero-point Switching 3-phase Solid State Relays
Main Characteristics:
2-phase control
Space-saving, width of only 45 mm
LED display
Various connection technologies
Plug-in control terminal
Degree of protection IP 20
Standards / Approvals:
DIN EN 60947-4-3
UL 508 / CSA
1

CE / C-Tick
Ordering Key:
3RF22 30 - 1 A B 4 5
Max.
load current
Connection
technology
Switching
function
Controlled
phases
Control
voltage
Operating
voltage
Solid state
relay without
heat sink
30 = 30 A
55 = 55 A
1 = Screw connection
2 = Spring-loaded
3 = Ring cable
connection M5
A = Zero-point
switching

B = 2-phase 3 = 110 VAC
4 = 4 - 30 VDC

5 = 48 - 600 V

Not all possible versions are available ex stock.

Main Circuit
2
:
I
max
I
e
IEC 947-4-3 I
e
UL/CSA
Power
loss
Min.load
current
Max. leakage
current
Type A
With Rthha
/ 40 C
A
With Rthha
/ 40 C
A
With Rthha
/ 50 C
With I
max

W
A mA
3RF2230-. 30 0,57 K/W 30 0,57 K/W 30 0,44 K/W 81 0,5 10
3RF2230-2. 20 1,36 K/W 20 1,15 K/W
3RF2255-. 55 0,18 K/W 55 0,18 K/W 55 0,12 K/W 151
3RF2255-2. 20 1,83 K/W 20 1,58 K/W

Type 3RF22. . - . AB. 5
Rated operating voltage U
e
V 48 ... 600
Voltage range V 40 ... 660
Rated frequency Hz 50/60 10 %
Rated insulation voltage U
i
V 600
Rated impulse withstand voltage U
imp
kV 6
Blocking voltage V 1200
Slew rate V/s 1000

Rated impulse withstand strength Itsm I
2
t value
Type A A
2
s
3RF2230- . 300 450
3RF2255-. 600 1800

Control Circuit A1-A2:
Type 3RF22. . - . AB3. 3RF22. . - . AB4.
Control voltage U
s
V AC 110 DC 4 ... 30
Max. control voltage U
s
V 121 30
Typical operating current mA 15 30
Response voltage V 90 4
Drop-out voltage V < 40 1
Switching times ON delay ms 40 + max. one half-wave 1 + max. one half-wave
OFF delay ms 40 + max. one half-wave 1 + max. one half-wave


1
Use overvoltage protection device; max cut-off-voltage 6.000 V; min energy handling capability 100 J
2
The current I
max
provides information about the performance of the solid-state relays. The actual permitted rated operating current I
e

can be smaller depending on the connection method and cooling conditions. The spring-loaded terminals version can be used for a
rated current of up to approx. 20 A with one conductor and up to approx. 40 A with two conductor on each terminal.
Subject to changes 08/2010 Page 1/5
http://www.siemens.com/solid-state-switching-devices
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF22..-.AB. Zero-point Switching 3-phase Solid State Relays
Subject to changes 08/2010 Page 2/5
http://www.siemens.com/solid-state-switching-devices

General Data:
Ambient temperature
During operation, derating as of 40 C C -25 ... 60
During storage C -55 ... 80
Mounting altitude m 0 ... 1000; at > 1000 m, please contact our Technical Assistance
Impact resistance acc. to DIN IEC 68 g/ms 15/11
Vibration resistance g 2
Degree of protection IP20
Electromagnetic compatibility
Interference emission
o Conducted interference voltage
IEC 60 947-4-3
Class A for industrial applications
3

Interference resistance
o Electrostatic discharge acc. to
IEC 61 000-4-2 (corresponds
to severity 3)
kV Contact discharge 4; air discharge 8; performance criterion 2
o Induced HF fields acc. to
IEC 61 000-4-6
MHz 0.15 ... 80; 140 dBV; performance criterion 1
o Burst acc. to IEC 61 000-4-4 kV 2/5.0 kHz; performance criterion 2
o Surge acc. to IEC 61 000-4-5 kV Phase-to-ground 2; phase-to-phase 1; performance criterion 2
Dielectric Strength 50/60 Hz
(Input, Output / Base)
V rms 4000

Type 3RF22. . - 1. 3RF22. . - 2. 3RF22. . - 3.
Connection, main contacts Screw connection
Spring-loaded
connection
Ring cable connection
Conductor cross-section
o Solid mm
2

2 x (1,5 ... 2,5),
2 x (2,5 ... 6)
2x (0,5 ... 2,5)
o Finely stranded with end sleeve mm
2

2 x (1,5 ... 2,5),
2 x (2,5 ... 6), 1 x 10
2x (0,5 ... 1,5)
o Finely stranded w/o end sleeve mm
2
2x (0,5 ... 2,5)
o Solid or stranded AWG 2 x (14 ... 10) 2 x (18 ... 14)
Stripping length mm 10 10
Terminal screw M 4 - M 5
Nm 2 ... 2,5 - 2 ... 2,5 o Tightening torque
D 5...6 mm / PZ 2
lb.in 18 ... 22 - 18 ... 22
Cable lug DIN - - DIN 46234 5-2,5 ... 5-25
JIS - - JIS C 2805 R 2-5 14-5
Connection, auxiliary/control
contacts

Conductor cross-section with or
without end sleeve
mm
mm
AWG
1 x (0,5 ... 2,5)
2 x (0,5 ... 1,0)
20 ... 12
0,5 ... 2,5

20 ... 12
1 x (0,5 ... 2,5)
2 x (0,5 ... 1,0)
20 ... 12
Stripping length mm 7 10 7
Terminal screw M 3 - M 3
Nm 0,5 ... 0,6 - 0,5 ... 0,6 o Tightening torque
D 3.5 / PZ 1
lb.in 4,5 ... 5,3 - 4,5 ... 5,3


3
Attention!
This product was constructed as an EMC Class A device. The use of this product in residential applications could
lead to radio interferences. In such an application, additional filtering may be required.
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF22..-.AB. Zero-point Switching 3-phase Solid State Relays

Type Semiconductor protection fuse
Full-range fuse Partial-range fuse
LV HBC
design
cylindrical
design
LV HBC
design
cylindrical design
gR/SITOR gR/Neozed
4
aR/SITOR aR/SITOR
3NE1 5SE1 3NE8 3NC1 0 3NC1 4 3NC2 2
10 x 38 14 x 51 22 x 58
Maximum operation voltage U
e
460V (+10%)
3RF2230- 3NE1814-0
5
5SE1325
5
3NE 8003-1 3NC1032 3NC1430 3NC2232
3RF2255- 3NE1802-0
5
5SE1350
5
3NE 8018-1 -- 3NC1450 3NC2263
Maximum operation voltage U
e
600 V (+10%)
3RF2230- 3NE1814-0 -- 3NE 8003-1 3NC1025 3NC1430 3NC2232
3RF2255- 3NE1803-0 -- 3NE 8018-1 -- 3NC1450 3NC2250
Fused Design with Semiconductor Protection:


Type Line protection fuse
LV HBC design cylindrical design DIAZED
gG gG gG gG fast
3NA 3NW 3NW 3NW 5SB
10 x 38 mm 14 x 51 mm 22 x 58 mm
Maximum operation voltage U
e
460V (+10%)
3RF2230- 3NA3803-6
5
-- 3NW6101-1
5
3NW6205-1
5
5SB171
5

3RF2255- 3NA3807-6
5
-- -- -- 5SB311
5

Maximum operation voltage U
e
600 V (+10%)
3RF2230- 3NA3803-6
5
-- -- -- --
3RF2255- 3NA3805-6
5
-- -- -- --


Accessories:
Function module Order No. Applicable for the
following types
Versions
Converter 3RF2900-0EA18 3RF22. . - . AB4. Us = AC/DC 24 V
























4
Operation voltage only up to 400V!
Subject to changes 08/2010 Page 3/5
5
These fuses have a lower rated current than the solid state relay.
http://www.siemens.com/solid-state-switching-devices
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF22..-.AB. Zero-point Switching 3-phase Solid State Relays


Characteristic Curves:

3RF2230-
Rthha
0
20
40
60
80
100
0 10 20 30 40 50 60
0,35 K/W
0,45 K/W
0,56 K/W
0,75 K/W
1 K/W
1,3 K/W
1,7 K/W
2,2 K/W
3 K/W
4 K/W
5 K/W
7 K/W
10 K/W
4 8 12 16 20 24 28 32 36
3 mm 5 mm
Min. thickness of the heat sink the relay is mounted to
Ta in C
P
M

i
n

W
Ie in A


3RF2255-
Rthha
0
20
40
60
80
100
120
140
160
0 10 20 30 40 50 60
0,13 K/W
0,18 K/W
0,25 K/W
0,37 K/W
0,55 K/W
0,8 K/W
1,2 K/W
2 K/W
3 K/W
4 K/W
5 K/W
7 K/W
10 K/W
5 15 25 35 45 55
3 mm 5 mm
Min. thickness of the heat sink the relay is mounted to
Ie in A Ta in C
P
M

i
n

W


















Subject to changes 08/2010 Page 4/5
http://www.siemens.com/solid-state-switching-devices
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF22..-.AB. Zero-point Switching 3-phase Solid State Relays
Dimension Drawings
6
:

Screw
connection
Spring-loaded
connection
Ring cable
connection
Device / Example Circuit Diagram:



Subject to changes 08/2010 Page 5/5
6
Dimensions in mm (in)
http://www.siemens.com/solid-state-switching-devices
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF22..-.AB. Zero-point Switching 3-phase Solid State Relays
Main Characteristics:
2-phase control
Space-saving, width of only 45 mm
LED display
Various connection technologies
Plug-in control terminal
Degree of protection IP 20
Standards / Approvals:
DIN EN 60947-4-3
UL 508 / CSA
1

CE / C-Tick
Ordering Key:
3RF22 30 - 1 A B 4 5
Max.
load current
Connection
technology
Switching
function
Controlled
phases
Control
voltage
Operating
voltage
Solid state
relay without
heat sink
30 = 30 A
55 = 55 A
1 = Screw connection
2 = Spring-loaded
3 = Ring cable
connection M5
A = Zero-point
switching

B = 2-phase 3 = 110 VAC
4 = 4 - 30 VDC

5 = 48 - 600 V

Not all possible versions are available ex stock.

Main Circuit
2
:
I
max
I
e
IEC 947-4-3 I
e
UL/CSA
Power
loss
Min.load
current
Max. leakage
current
Type A
With Rthha
/ 40 C
A
With Rthha
/ 40 C
A
With Rthha
/ 50 C
With I
max

W
A mA
3RF2230-. 30 0,57 K/W 30 0,57 K/W 30 0,44 K/W 81 0,5 10
3RF2230-2. 20 1,36 K/W 20 1,15 K/W
3RF2255-. 55 0,18 K/W 55 0,18 K/W 55 0,12 K/W 151
3RF2255-2. 20 1,83 K/W 20 1,58 K/W

Type 3RF22. . - . AB. 5
Rated operating voltage U
e
V 48 ... 600
Voltage range V 40 ... 660
Rated frequency Hz 50/60 10 %
Rated insulation voltage U
i
V 600
Rated impulse withstand voltage U
imp
kV 6
Blocking voltage V 1200
Slew rate V/s 1000

Rated impulse withstand strength Itsm I
2
t value
Type A A
2
s
3RF2230- . 300 450
3RF2255-. 600 1800

Control Circuit A1-A2:
Type 3RF22. . - . AB3. 3RF22. . - . AB4.
Control voltage U
s
V AC 110 DC 4 ... 30
Max. control voltage U
s
V 121 30
Typical operating current mA 15 30
Response voltage V 90 4
Drop-out voltage V < 40 1
Switching times ON delay ms 40 + max. one half-wave 1 + max. one half-wave
OFF delay ms 40 + max. one half-wave 1 + max. one half-wave


1
Use overvoltage protection device; max cut-off-voltage 6.000 V; min energy handling capability 100 J
2
The current I
max
provides information about the performance of the solid-state relays. The actual permitted rated operating current I
e

can be smaller depending on the connection method and cooling conditions. The spring-loaded terminals version can be used for a
rated current of up to approx. 20 A with one conductor and up to approx. 40 A with two conductor on each terminal.
Subject to changes 08/2010 Page 1/5
http://www.siemens.com/solid-state-switching-devices
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF22..-.AB. Zero-point Switching 3-phase Solid State Relays
Subject to changes 08/2010 Page 2/5
http://www.siemens.com/solid-state-switching-devices

General Data:
Ambient temperature
During operation, derating as of 40 C C -25 ... 60
During storage C -55 ... 80
Mounting altitude m 0 ... 1000; at > 1000 m, please contact our Technical Assistance
Impact resistance acc. to DIN IEC 68 g/ms 15/11
Vibration resistance g 2
Degree of protection IP20
Electromagnetic compatibility
Interference emission
o Conducted interference voltage
IEC 60 947-4-3
Class A for industrial applications
3

Interference resistance
o Electrostatic discharge acc. to
IEC 61 000-4-2 (corresponds
to severity 3)
kV Contact discharge 4; air discharge 8; performance criterion 2
o Induced HF fields acc. to
IEC 61 000-4-6
MHz 0.15 ... 80; 140 dBV; performance criterion 1
o Burst acc. to IEC 61 000-4-4 kV 2/5.0 kHz; performance criterion 2
o Surge acc. to IEC 61 000-4-5 kV Phase-to-ground 2; phase-to-phase 1; performance criterion 2
Dielectric Strength 50/60 Hz
(Input, Output / Base)
V rms 4000

Type 3RF22. . - 1. 3RF22. . - 2. 3RF22. . - 3.
Connection, main contacts Screw connection
Spring-loaded
connection
Ring cable connection
Conductor cross-section
o Solid mm
2

2 x (1,5 ... 2,5),
2 x (2,5 ... 6)
2x (0,5 ... 2,5)
o Finely stranded with end sleeve mm
2

2 x (1,5 ... 2,5),
2 x (2,5 ... 6), 1 x 10
2x (0,5 ... 1,5)
o Finely stranded w/o end sleeve mm
2
2x (0,5 ... 2,5)
o Solid or stranded AWG 2 x (14 ... 10) 2 x (18 ... 14)
Stripping length mm 10 10
Terminal screw M 4 - M 5
Nm 2 ... 2,5 - 2 ... 2,5 o Tightening torque
D 5...6 mm / PZ 2
lb.in 18 ... 22 - 18 ... 22
Cable lug DIN - - DIN 46234 5-2,5 ... 5-25
JIS - - JIS C 2805 R 2-5 14-5
Connection, auxiliary/control
contacts

Conductor cross-section with or
without end sleeve
mm
mm
AWG
1 x (0,5 ... 2,5)
2 x (0,5 ... 1,0)
20 ... 12
0,5 ... 2,5

20 ... 12
1 x (0,5 ... 2,5)
2 x (0,5 ... 1,0)
20 ... 12
Stripping length mm 7 10 7
Terminal screw M 3 - M 3
Nm 0,5 ... 0,6 - 0,5 ... 0,6 o Tightening torque
D 3.5 / PZ 1
lb.in 4,5 ... 5,3 - 4,5 ... 5,3


3
Attention!
This product was constructed as an EMC Class A device. The use of this product in residential applications could
lead to radio interferences. In such an application, additional filtering may be required.
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF22..-.AB. Zero-point Switching 3-phase Solid State Relays

Type Semiconductor protection fuse
Full-range fuse Partial-range fuse
LV HBC
design
cylindrical
design
LV HBC
design
cylindrical design
gR/SITOR gR/Neozed
4
aR/SITOR aR/SITOR
3NE1 5SE1 3NE8 3NC1 0 3NC1 4 3NC2 2
10 x 38 14 x 51 22 x 58
Maximum operation voltage U
e
460V (+10%)
3RF2230- 3NE1814-0
5
5SE1325
5
3NE 8003-1 3NC1032 3NC1430 3NC2232
3RF2255- 3NE1802-0
5
5SE1350
5
3NE 8018-1 -- 3NC1450 3NC2263
Maximum operation voltage U
e
600 V (+10%)
3RF2230- 3NE1814-0 -- 3NE 8003-1 3NC1025 3NC1430 3NC2232
3RF2255- 3NE1803-0 -- 3NE 8018-1 -- 3NC1450 3NC2250
Fused Design with Semiconductor Protection:


Type Line protection fuse
LV HBC design cylindrical design DIAZED
gG gG gG gG fast
3NA 3NW 3NW 3NW 5SB
10 x 38 mm 14 x 51 mm 22 x 58 mm
Maximum operation voltage U
e
460V (+10%)
3RF2230- 3NA3803-6
5
-- 3NW6101-1
5
3NW6205-1
5
5SB171
5

3RF2255- 3NA3807-6
5
-- -- -- 5SB311
5

Maximum operation voltage U
e
600 V (+10%)
3RF2230- 3NA3803-6
5
-- -- -- --
3RF2255- 3NA3805-6
5
-- -- -- --


Accessories:
Function module Order No. Applicable for the
following types
Versions
Converter 3RF2900-0EA18 3RF22. . - . AB4. Us = AC/DC 24 V
























4
Operation voltage only up to 400V!
Subject to changes 08/2010 Page 3/5
5
These fuses have a lower rated current than the solid state relay.
http://www.siemens.com/solid-state-switching-devices
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF22..-.AB. Zero-point Switching 3-phase Solid State Relays


Characteristic Curves:

3RF2230-
Rthha
0
20
40
60
80
100
0 10 20 30 40 50 60
0,35 K/W
0,45 K/W
0,56 K/W
0,75 K/W
1 K/W
1,3 K/W
1,7 K/W
2,2 K/W
3 K/W
4 K/W
5 K/W
7 K/W
10 K/W
4 8 12 16 20 24 28 32 36
3 mm 5 mm
Min. thickness of the heat sink the relay is mounted to
Ta in C
P
M

i
n

W
Ie in A


3RF2255-
Rthha
0
20
40
60
80
100
120
140
160
0 10 20 30 40 50 60
0,13 K/W
0,18 K/W
0,25 K/W
0,37 K/W
0,55 K/W
0,8 K/W
1,2 K/W
2 K/W
3 K/W
4 K/W
5 K/W
7 K/W
10 K/W
5 15 25 35 45 55
3 mm 5 mm
Min. thickness of the heat sink the relay is mounted to
Ie in A Ta in C
P
M

i
n

W


















Subject to changes 08/2010 Page 4/5
http://www.siemens.com/solid-state-switching-devices
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF22..-.AB. Zero-point Switching 3-phase Solid State Relays
Dimension Drawings
6
:

Screw
connection
Spring-loaded
connection
Ring cable
connection
Device / Example Circuit Diagram:



Subject to changes 08/2010 Page 5/5
6
Dimensions in mm (in)
http://www.siemens.com/solid-state-switching-devices
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF22..-AC. Zero-point Switching 3-phase Solid State Relays

Subject to changes 08/2010 Page 1/5
Main Characteristics:
3-phase control
Space-saving, width of only 45 mm
LED display
Various connection technologies
Plug-in control terminal
Degree of protection IP 20
Standards / Approvals:
DIN EN 60947-4-3
UL 508 / CSA
1

CE / C-Tick
Ordering Key:
3RF22 30 - 1 A C 4 5
Max.
load current
Connection
technology
Switching
function
Controlled
phases
Control
voltage
Operating
voltage
Solid state
relay without
heat sink
30 = 30 A
55 = 55 A
1 = Screw connection
2 = Spring-loaded
3 = Ring cable
connection M5
A = Zero-point
switching

C = 3-phase 3 = 110 VAC
4 = 4 - 30 VDC

5 = 48 - 600 V

Not all possible versions are available ex stock.

Main Circuit
2
:
I
max
I
e
IEC 947-4-3 I
e
UL/CSA
Power
loss
Min. load
current
Max. leakage
current
Type A
With Rthha
/ 40 C
A
With Rthha
/ 40 C
A
With Rthha
/ 50 C
With I
max

W
A mA
3RF2230-. 30 0,33 K/W 30 0,33 K/W 30 0,25 K/W 122 0,5 10
3RF2230-2. 20 0,86 K/W 20 0,72 K/W
3RF2255-. 55 0,09 K/W 55 0,09 K/W 55 0,05 K/W 226
3RF2255-2. 20 1,19 K/W 20 1,02 K/W

Type 3RF22. . - . AC. 5
Rated operating voltage U
e
V 48 ... 600
Voltage range V 40 ... 660
Rated frequency Hz 50/60 10 %
Rated insulation voltage U
i
V 600
Rated impulse withstand voltage U
imp
kV 6
Blocking voltage V 1200
Slew rate V/s 1000

Rated impulse withstand strength Itsm I
2
t value
Type A A
2
s
3RF2230- . 300 450
3RF2255-. 600 1800

Control Circuit A1-A2:
Type 3RF22. . - . AC3. 3RF22. . - . AC4.
Control voltage U
s
V AC 110 DC 4 ... 30
Max. control voltage U
s
V 121 30
Typical operating current mA 15 30
Response voltage V 90 4
Drop-out voltage V < 40 1
Switching times ON delay ms 40 + max. one half-wave 1 + max. one half-wave
OFF delay ms 40 + max. one half-wave 1 + max. one half-wave

1
Use overvoltage protection device; max cut-off-voltage 6.000 V; min energy handling capability 100 J
2
The current I
max
provides information about the performance of the solid-state relays. The actual permitted rated operating current I
e

can be smaller depending on the connection method and cooling conditions. The spring-loaded terminals version can be used for a
rated current of up to approx. 20 A with one conductor and up to approx. 40 A with two conductor on each terminal.
http://www.siemens.com/solid-state-switching-devices
VOLTAR
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF22..-AC. Zero-point Switching 3-phase Solid State Relays

Subject to changes 08/2010 Page 2/5
http://www.siemens.com/solid-state-switching-devices
General Data:
Ambient temperature
During operation, derating as of 40 C C -25 ... 60
During storage C -55 ... 80
Mounting altitude m 0 ... 1000; at > 1000 m, please contact our Technical Assistance
Impact resistance acc. to DIN IEC 68 g/ms 15/11
Vibration resistance g 2
Degree of protection IP20
Electromagnetic compatibility
(


Interference emission
o Conducted interference voltage
IEC 60 947-4-3

Class A for industrial applications
3

Interference resistance
o Electrostatic discharge acc. to
IEC 61 000-4-2 (corresponds
to severity 3)

kV Contact discharge 4; air discharge 8; performance criterion 2
o Induced HF fields acc. to
IEC 61 000-4-6

MHz 0.15 ... 80; 140 dBV; performance criterion 1
o Burst acc. to IEC 61 000-4-4 kV 2/5.0 kHz; performance criterion 2
o Surge acc. to IEC 61 000-4-5 kV Phase-to-ground 2; phase-to-phase 1; performance criterion 2
Dielectric Strength 50/60 Hz
(Input, Output / Base)

V rms 4000


Type 3RF22. . - 1. 3RF22. . - 2. 3RF22. . - 3.
Connection, main contacts Screw connection
Spring-loaded
connection
Ring cable connection
Conductor cross-section
o Solid mm
2

2 x (1,5 ... 2,5),
2 x (2,5 ... 6)
2x (0,5 ... 2,5)
o Finely stranded with end sleeve mm
2

2 x (1,5 ... 2,5),
2 x (2,5 ... 6), 1 x 10
2x (0,5 ... 1,5)
o Finely stranded w/o end sleeve mm
2
2x (0,5 ... 2,5)
o Solid or stranded AWG 2 x (14 ... 10) 2 x (18 ... 14)
Stripping length mm 10 10
Terminal screw M 4 - M 5
Nm 2 ... 2,5 - 2 ... 2,5 o Tightening torque
D 5...6 mm / PZ 2
lb.in 18 ... 22 - 18 ... 22
Cable lug DIN - - DIN 46234 5-2,5 ... 5-25
JIS - - JIS C 2805 R 2-5 14-5
Connection, auxiliary/control
contacts

Conductor cross-section with or
without end sleeve
mm
mm
AWG
1 x (0,5 ... 2,5)
2 x (0,5 ... 1,0)
20 ... 12
0,5 ... 2,5

20 ... 12
1 x (0,5 ... 2,5)
2 x (0,5 ... 1,0)
20 ... 12
Stripping length mm 7 10 7
Terminal screw M 3 - M 3
Nm 0,5 ... 0,6 - 0,5 ... 0,6 o Tightening torque
D 3.5 / PZ 1
lb.in 4,5 ... 5,3 - 4,5 ... 5,3


3
Attention!
This product was constructed as an EMC Class A device. The use of this product in residential applications could
lead to radio interferences. In such an application, additional filtering may be required.
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF22..-AC. Zero-point Switching 3-phase Solid State Relays

Subject to changes 08/2010 Page 3/5

Type Semiconductor protection fuse
Full-range fuse Partial-range fuse
LV HBC
design
cylindrical
design
LV HBC
design
cylindrical design
gR/SITOR gR/Neozed
4
aR/SITOR aR/SITOR
3NE1 5SE1 3NE8 3NC1 0 3NC1 4 3NC2 2
10 x 38 14 x 51 22 x 58
Maximum operation voltage U
e
460V (+10%)
3RF2230- 3NE1814-0
5
5SE1325
5
3NE 8003-1 3NC1032 3NC1430 3NC2232
3RF2255- 3NE1802-0
5
5SE1350
5
3NE 8018-1 -- 3NC1450 3NC2263
Maximum operation voltage U
e
600 V (+10%)
3RF2230- 3NE1814-0
5
-- 3NE 8003-1 3NC1025
5
3NC1430 3NC2232
3RF2255- 3NE1803-0
5
-- 3NE 8018-1 -- 3NC1450
5
3NC2250
5

Fused Design with Semiconductor Protection:

Type Line protection fuse
LV HBC design cylindrical design DIAZED
gG gG gG gG fast
3NA 3NW 3NW 3NW 5SB
10 x 38 mm 14 x 51 mm 22 x 58 mm
Maximum operation voltage U
e
460V (+10%)
3RF2230- 3NA3803-6
5
-- 3NW6101-1
5
3NW6205-1
5
5SB171
5

3RF2255- 3NA3807-6
5
-- -- -- 5SB311
5

Maximum operation voltage U
e
600 V (+10%)
3RF2230- 3NA3803-6
5
-- -- -- --
3RF2255- 3NA3805-6
5
-- -- -- --


Accessories:
Function module Order No. Applicable for the
following types
Versions
Converter 3RF2900-0EA18 3RF22. . - . AC4. Us = AC/DC 24 V


4
Operation voltage only up to 400V!
5
These fuses have a lower rated current than the solid state relay.
http://www.siemens.com/solid-state-switching-devices
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF22..-AC. Zero-point Switching 3-phase Solid State Relays

Subject to changes 08/2010 Page 4/5

Characteristic Curves:

3RF2230-
4 8 12 16 20 24 28 32 36
Rthha
0
20
40
60
80
100
120
140
160
0 10 20 30 40 50 60
0,26 K/W
0,33 K/W
0,44 K/W
0,62 K/W
0,9 K/W
1,3 K/W
1,7 K/W
2,2 K/W
3 K/W
4 K/W
5 K/W
7 K/W
10 K/W
3 mm 5 mm
Min. thickness of the heat sink the relay is mounted to
Ie in A
P
M

i
n

W
Ta in C


3RF2255-
5 15 25 35 45 55
Rthha
0
50
100
150
200
250
0 10 20 30 40 50 60
0,06 K/W
0,09 K/W
0,15 K/W
0,25 K/W
0,4 K/W
0,6 K/W
0,8 K/W
1,1 K/W
1,5 K/W
2 K/W
3 K/W
4 K/W
6 K/W
3 mm 5 mm
Min. thickness of the heat sink the relay is mounted to
Ie in A
P
M
i
n
W
Ta in C


http://www.siemens.com/solid-state-switching-devices
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF22..-AC. Zero-point Switching 3-phase Solid State Relays

Subject to changes 08/2010 Page 5/5

Dimension Drawings
6
:

Screw
connection
Spring-loaded
connection
Ring cable
connection
http://www.siemens.com/solid-state-switching-devices
Device / Example Circuit Diagram:



6
Dimensions in mm (in)
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF22..-AC. Zero-point Switching 3-phase Solid State Relays

Subject to changes 08/2010 Page 1/5
Main Characteristics:
3-phase control
Space-saving, width of only 45 mm
LED display
Various connection technologies
Plug-in control terminal
Degree of protection IP 20
Standards / Approvals:
DIN EN 60947-4-3
UL 508 / CSA
1

CE / C-Tick
Ordering Key:
3RF22 30 - 1 A C 4 5
Max.
load current
Connection
technology
Switching
function
Controlled
phases
Control
voltage
Operating
voltage
Solid state
relay without
heat sink
30 = 30 A
55 = 55 A
1 = Screw connection
2 = Spring-loaded
3 = Ring cable
connection M5
A = Zero-point
switching

C = 3-phase 3 = 110 VAC
4 = 4 - 30 VDC

5 = 48 - 600 V

Not all possible versions are available ex stock.

Main Circuit
2
:
I
max
I
e
IEC 947-4-3 I
e
UL/CSA
Power
loss
Min. load
current
Max. leakage
current
Type A
With Rthha
/ 40 C
A
With Rthha
/ 40 C
A
With Rthha
/ 50 C
With I
max

W
A mA
3RF2230-. 30 0,33 K/W 30 0,33 K/W 30 0,25 K/W 122 0,5 10
3RF2230-2. 20 0,86 K/W 20 0,72 K/W
3RF2255-. 55 0,09 K/W 55 0,09 K/W 55 0,05 K/W 226
3RF2255-2. 20 1,19 K/W 20 1,02 K/W

Type 3RF22. . - . AC. 5
Rated operating voltage U
e
V 48 ... 600
Voltage range V 40 ... 660
Rated frequency Hz 50/60 10 %
Rated insulation voltage U
i
V 600
Rated impulse withstand voltage U
imp
kV 6
Blocking voltage V 1200
Slew rate V/s 1000

Rated impulse withstand strength Itsm I
2
t value
Type A A
2
s
3RF2230- . 300 450
3RF2255-. 600 1800

Control Circuit A1-A2:
Type 3RF22. . - . AC3. 3RF22. . - . AC4.
Control voltage U
s
V AC 110 DC 4 ... 30
Max. control voltage U
s
V 121 30
Typical operating current mA 15 30
Response voltage V 90 4
Drop-out voltage V < 40 1
Switching times ON delay ms 40 + max. one half-wave 1 + max. one half-wave
OFF delay ms 40 + max. one half-wave 1 + max. one half-wave

1
Use overvoltage protection device; max cut-off-voltage 6.000 V; min energy handling capability 100 J
2
The current I
max
provides information about the performance of the solid-state relays. The actual permitted rated operating current I
e

can be smaller depending on the connection method and cooling conditions. The spring-loaded terminals version can be used for a
rated current of up to approx. 20 A with one conductor and up to approx. 40 A with two conductor on each terminal.
http://www.siemens.com/solid-state-switching-devices
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF22..-AC. Zero-point Switching 3-phase Solid State Relays

Subject to changes 08/2010 Page 2/5
http://www.siemens.com/solid-state-switching-devices
General Data:
Ambient temperature
During operation, derating as of 40 C C -25 ... 60
During storage C -55 ... 80
Mounting altitude m 0 ... 1000; at > 1000 m, please contact our Technical Assistance
Impact resistance acc. to DIN IEC 68 g/ms 15/11
Vibration resistance g 2
Degree of protection IP20
Electromagnetic compatibility
(


Interference emission
o Conducted interference voltage
IEC 60 947-4-3

Class A for industrial applications
3

Interference resistance
o Electrostatic discharge acc. to
IEC 61 000-4-2 (corresponds
to severity 3)

kV Contact discharge 4; air discharge 8; performance criterion 2
o Induced HF fields acc. to
IEC 61 000-4-6

MHz 0.15 ... 80; 140 dBV; performance criterion 1
o Burst acc. to IEC 61 000-4-4 kV 2/5.0 kHz; performance criterion 2
o Surge acc. to IEC 61 000-4-5 kV Phase-to-ground 2; phase-to-phase 1; performance criterion 2
Dielectric Strength 50/60 Hz
(Input, Output / Base)

V rms 4000


Type 3RF22. . - 1. 3RF22. . - 2. 3RF22. . - 3.
Connection, main contacts Screw connection
Spring-loaded
connection
Ring cable connection
Conductor cross-section
o Solid mm
2

2 x (1,5 ... 2,5),
2 x (2,5 ... 6)
2x (0,5 ... 2,5)
o Finely stranded with end sleeve mm
2

2 x (1,5 ... 2,5),
2 x (2,5 ... 6), 1 x 10
2x (0,5 ... 1,5)
o Finely stranded w/o end sleeve mm
2
2x (0,5 ... 2,5)
o Solid or stranded AWG 2 x (14 ... 10) 2 x (18 ... 14)
Stripping length mm 10 10
Terminal screw M 4 - M 5
Nm 2 ... 2,5 - 2 ... 2,5 o Tightening torque
D 5...6 mm / PZ 2
lb.in 18 ... 22 - 18 ... 22
Cable lug DIN - - DIN 46234 5-2,5 ... 5-25
JIS - - JIS C 2805 R 2-5 14-5
Connection, auxiliary/control
contacts

Conductor cross-section with or
without end sleeve
mm
mm
AWG
1 x (0,5 ... 2,5)
2 x (0,5 ... 1,0)
20 ... 12
0,5 ... 2,5

20 ... 12
1 x (0,5 ... 2,5)
2 x (0,5 ... 1,0)
20 ... 12
Stripping length mm 7 10 7
Terminal screw M 3 - M 3
Nm 0,5 ... 0,6 - 0,5 ... 0,6 o Tightening torque
D 3.5 / PZ 1
lb.in 4,5 ... 5,3 - 4,5 ... 5,3


3
Attention!
This product was constructed as an EMC Class A device. The use of this product in residential applications could
lead to radio interferences. In such an application, additional filtering may be required.
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF22..-AC. Zero-point Switching 3-phase Solid State Relays

Subject to changes 08/2010 Page 3/5

Type Semiconductor protection fuse
Full-range fuse Partial-range fuse
LV HBC
design
cylindrical
design
LV HBC
design
cylindrical design
gR/SITOR gR/Neozed
4
aR/SITOR aR/SITOR
3NE1 5SE1 3NE8 3NC1 0 3NC1 4 3NC2 2
10 x 38 14 x 51 22 x 58
Maximum operation voltage U
e
460V (+10%)
3RF2230- 3NE1814-0
5
5SE1325
5
3NE 8003-1 3NC1032 3NC1430 3NC2232
3RF2255- 3NE1802-0
5
5SE1350
5
3NE 8018-1 -- 3NC1450 3NC2263
Maximum operation voltage U
e
600 V (+10%)
3RF2230- 3NE1814-0
5
-- 3NE 8003-1 3NC1025
5
3NC1430 3NC2232
3RF2255- 3NE1803-0
5
-- 3NE 8018-1 -- 3NC1450
5
3NC2250
5

Fused Design with Semiconductor Protection:

Type Line protection fuse
LV HBC design cylindrical design DIAZED
gG gG gG gG fast
3NA 3NW 3NW 3NW 5SB
10 x 38 mm 14 x 51 mm 22 x 58 mm
Maximum operation voltage U
e
460V (+10%)
3RF2230- 3NA3803-6
5
-- 3NW6101-1
5
3NW6205-1
5
5SB171
5

3RF2255- 3NA3807-6
5
-- -- -- 5SB311
5

Maximum operation voltage U
e
600 V (+10%)
3RF2230- 3NA3803-6
5
-- -- -- --
3RF2255- 3NA3805-6
5
-- -- -- --


Accessories:
Function module Order No. Applicable for the
following types
Versions
Converter 3RF2900-0EA18 3RF22. . - . AC4. Us = AC/DC 24 V


4
Operation voltage only up to 400V!
5
These fuses have a lower rated current than the solid state relay.
http://www.siemens.com/solid-state-switching-devices
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF22..-AC. Zero-point Switching 3-phase Solid State Relays

Subject to changes 08/2010 Page 4/5

Characteristic Curves:

3RF2230-
4 8 12 16 20 24 28 32 36
Rthha
0
20
40
60
80
100
120
140
160
0 10 20 30 40 50 60
0,26 K/W
0,33 K/W
0,44 K/W
0,62 K/W
0,9 K/W
1,3 K/W
1,7 K/W
2,2 K/W
3 K/W
4 K/W
5 K/W
7 K/W
10 K/W
3 mm 5 mm
Min. thickness of the heat sink the relay is mounted to
Ie in A
P
M

i
n

W
Ta in C


3RF2255-
5 15 25 35 45 55
Rthha
0
50
100
150
200
250
0 10 20 30 40 50 60
0,06 K/W
0,09 K/W
0,15 K/W
0,25 K/W
0,4 K/W
0,6 K/W
0,8 K/W
1,1 K/W
1,5 K/W
2 K/W
3 K/W
4 K/W
6 K/W
3 mm 5 mm
Min. thickness of the heat sink the relay is mounted to
Ie in A
P
M
i
n
W
Ta in C


http://www.siemens.com/solid-state-switching-devices
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF22..-AC. Zero-point Switching 3-phase Solid State Relays

Subject to changes 08/2010 Page 5/5

Dimension Drawings
6
:

Screw
connection
Spring-loaded
connection
Ring cable
connection
http://www.siemens.com/solid-state-switching-devices
Device / Example Circuit Diagram:



6
Dimensions in mm (in)
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF22..-AC. Zero-point Switching 3-phase Solid State Relays

Subject to changes 08/2010 Page 1/5
Main Characteristics:
3-phase control
Space-saving, width of only 45 mm
LED display
Various connection technologies
Plug-in control terminal
Degree of protection IP 20
Standards / Approvals:
DIN EN 60947-4-3
UL 508 / CSA
1

CE / C-Tick
Ordering Key:
3RF22 30 - 1 A C 4 5
Max.
load current
Connection
technology
Switching
function
Controlled
phases
Control
voltage
Operating
voltage
Solid state
relay without
heat sink
30 = 30 A
55 = 55 A
1 = Screw connection
2 = Spring-loaded
3 = Ring cable
connection M5
A = Zero-point
switching

C = 3-phase 3 = 110 VAC
4 = 4 - 30 VDC

5 = 48 - 600 V

Not all possible versions are available ex stock.

Main Circuit
2
:
I
max
I
e
IEC 947-4-3 I
e
UL/CSA
Power
loss
Min. load
current
Max. leakage
current
Type A
With Rthha
/ 40 C
A
With Rthha
/ 40 C
A
With Rthha
/ 50 C
With I
max

W
A mA
3RF2230-. 30 0,33 K/W 30 0,33 K/W 30 0,25 K/W 122 0,5 10
3RF2230-2. 20 0,86 K/W 20 0,72 K/W
3RF2255-. 55 0,09 K/W 55 0,09 K/W 55 0,05 K/W 226
3RF2255-2. 20 1,19 K/W 20 1,02 K/W

Type 3RF22. . - . AC. 5
Rated operating voltage U
e
V 48 ... 600
Voltage range V 40 ... 660
Rated frequency Hz 50/60 10 %
Rated insulation voltage U
i
V 600
Rated impulse withstand voltage U
imp
kV 6
Blocking voltage V 1200
Slew rate V/s 1000

Rated impulse withstand strength Itsm I
2
t value
Type A A
2
s
3RF2230- . 300 450
3RF2255-. 600 1800

Control Circuit A1-A2:
Type 3RF22. . - . AC3. 3RF22. . - . AC4.
Control voltage U
s
V AC 110 DC 4 ... 30
Max. control voltage U
s
V 121 30
Typical operating current mA 15 30
Response voltage V 90 4
Drop-out voltage V < 40 1
Switching times ON delay ms 40 + max. one half-wave 1 + max. one half-wave
OFF delay ms 40 + max. one half-wave 1 + max. one half-wave

1
Use overvoltage protection device; max cut-off-voltage 6.000 V; min energy handling capability 100 J
2
The current I
max
provides information about the performance of the solid-state relays. The actual permitted rated operating current I
e

can be smaller depending on the connection method and cooling conditions. The spring-loaded terminals version can be used for a
rated current of up to approx. 20 A with one conductor and up to approx. 40 A with two conductor on each terminal.
http://www.siemens.com/solid-state-switching-devices
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF22..-AC. Zero-point Switching 3-phase Solid State Relays

Subject to changes 08/2010 Page 2/5
http://www.siemens.com/solid-state-switching-devices
General Data:
Ambient temperature
During operation, derating as of 40 C C -25 ... 60
During storage C -55 ... 80
Mounting altitude m 0 ... 1000; at > 1000 m, please contact our Technical Assistance
Impact resistance acc. to DIN IEC 68 g/ms 15/11
Vibration resistance g 2
Degree of protection IP20
Electromagnetic compatibility
(


Interference emission
o Conducted interference voltage
IEC 60 947-4-3

Class A for industrial applications
3

Interference resistance
o Electrostatic discharge acc. to
IEC 61 000-4-2 (corresponds
to severity 3)

kV Contact discharge 4; air discharge 8; performance criterion 2
o Induced HF fields acc. to
IEC 61 000-4-6

MHz 0.15 ... 80; 140 dBV; performance criterion 1
o Burst acc. to IEC 61 000-4-4 kV 2/5.0 kHz; performance criterion 2
o Surge acc. to IEC 61 000-4-5 kV Phase-to-ground 2; phase-to-phase 1; performance criterion 2
Dielectric Strength 50/60 Hz
(Input, Output / Base)

V rms 4000


Type 3RF22. . - 1. 3RF22. . - 2. 3RF22. . - 3.
Connection, main contacts Screw connection
Spring-loaded
connection
Ring cable connection
Conductor cross-section
o Solid mm
2

2 x (1,5 ... 2,5),
2 x (2,5 ... 6)
2x (0,5 ... 2,5)
o Finely stranded with end sleeve mm
2

2 x (1,5 ... 2,5),
2 x (2,5 ... 6), 1 x 10
2x (0,5 ... 1,5)
o Finely stranded w/o end sleeve mm
2
2x (0,5 ... 2,5)
o Solid or stranded AWG 2 x (14 ... 10) 2 x (18 ... 14)
Stripping length mm 10 10
Terminal screw M 4 - M 5
Nm 2 ... 2,5 - 2 ... 2,5 o Tightening torque
D 5...6 mm / PZ 2
lb.in 18 ... 22 - 18 ... 22
Cable lug DIN - - DIN 46234 5-2,5 ... 5-25
JIS - - JIS C 2805 R 2-5 14-5
Connection, auxiliary/control
contacts

Conductor cross-section with or
without end sleeve
mm
mm
AWG
1 x (0,5 ... 2,5)
2 x (0,5 ... 1,0)
20 ... 12
0,5 ... 2,5

20 ... 12
1 x (0,5 ... 2,5)
2 x (0,5 ... 1,0)
20 ... 12
Stripping length mm 7 10 7
Terminal screw M 3 - M 3
Nm 0,5 ... 0,6 - 0,5 ... 0,6 o Tightening torque
D 3.5 / PZ 1
lb.in 4,5 ... 5,3 - 4,5 ... 5,3


3
Attention!
This product was constructed as an EMC Class A device. The use of this product in residential applications could
lead to radio interferences. In such an application, additional filtering may be required.
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF22..-AC. Zero-point Switching 3-phase Solid State Relays

Subject to changes 08/2010 Page 3/5

Type Semiconductor protection fuse
Full-range fuse Partial-range fuse
LV HBC
design
cylindrical
design
LV HBC
design
cylindrical design
gR/SITOR gR/Neozed
4
aR/SITOR aR/SITOR
3NE1 5SE1 3NE8 3NC1 0 3NC1 4 3NC2 2
10 x 38 14 x 51 22 x 58
Maximum operation voltage U
e
460V (+10%)
3RF2230- 3NE1814-0
5
5SE1325
5
3NE 8003-1 3NC1032 3NC1430 3NC2232
3RF2255- 3NE1802-0
5
5SE1350
5
3NE 8018-1 -- 3NC1450 3NC2263
Maximum operation voltage U
e
600 V (+10%)
3RF2230- 3NE1814-0
5
-- 3NE 8003-1 3NC1025
5
3NC1430 3NC2232
3RF2255- 3NE1803-0
5
-- 3NE 8018-1 -- 3NC1450
5
3NC2250
5

Fused Design with Semiconductor Protection:

Type Line protection fuse
LV HBC design cylindrical design DIAZED
gG gG gG gG fast
3NA 3NW 3NW 3NW 5SB
10 x 38 mm 14 x 51 mm 22 x 58 mm
Maximum operation voltage U
e
460V (+10%)
3RF2230- 3NA3803-6
5
-- 3NW6101-1
5
3NW6205-1
5
5SB171
5

3RF2255- 3NA3807-6
5
-- -- -- 5SB311
5

Maximum operation voltage U
e
600 V (+10%)
3RF2230- 3NA3803-6
5
-- -- -- --
3RF2255- 3NA3805-6
5
-- -- -- --


Accessories:
Function module Order No. Applicable for the
following types
Versions
Converter 3RF2900-0EA18 3RF22. . - . AC4. Us = AC/DC 24 V


4
Operation voltage only up to 400V!
5
These fuses have a lower rated current than the solid state relay.
http://www.siemens.com/solid-state-switching-devices
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF22..-AC. Zero-point Switching 3-phase Solid State Relays

Subject to changes 08/2010 Page 4/5

Characteristic Curves:

3RF2230-
4 8 12 16 20 24 28 32 36
Rthha
0
20
40
60
80
100
120
140
160
0 10 20 30 40 50 60
0,26 K/W
0,33 K/W
0,44 K/W
0,62 K/W
0,9 K/W
1,3 K/W
1,7 K/W
2,2 K/W
3 K/W
4 K/W
5 K/W
7 K/W
10 K/W
3 mm 5 mm
Min. thickness of the heat sink the relay is mounted to
Ie in A
P
M

i
n

W
Ta in C


3RF2255-
5 15 25 35 45 55
Rthha
0
50
100
150
200
250
0 10 20 30 40 50 60
0,06 K/W
0,09 K/W
0,15 K/W
0,25 K/W
0,4 K/W
0,6 K/W
0,8 K/W
1,1 K/W
1,5 K/W
2 K/W
3 K/W
4 K/W
6 K/W
3 mm 5 mm
Min. thickness of the heat sink the relay is mounted to
Ie in A
P
M
i
n
W
Ta in C


http://www.siemens.com/solid-state-switching-devices
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF22..-AC. Zero-point Switching 3-phase Solid State Relays

Subject to changes 08/2010 Page 5/5

Dimension Drawings
6
:

Screw
connection
Spring-loaded
connection
Ring cable
connection
http://www.siemens.com/solid-state-switching-devices
Device / Example Circuit Diagram:



6
Dimensions in mm (in)
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF22..-AC. Zero-point Switching 3-phase Solid State Relays

Subject to changes 08/2010 Page 1/5
Main Characteristics:
3-phase control
Space-saving, width of only 45 mm
LED display
Various connection technologies
Plug-in control terminal
Degree of protection IP 20
Standards / Approvals:
DIN EN 60947-4-3
UL 508 / CSA
1

CE / C-Tick
Ordering Key:
3RF22 30 - 1 A C 4 5
Max.
load current
Connection
technology
Switching
function
Controlled
phases
Control
voltage
Operating
voltage
Solid state
relay without
heat sink
30 = 30 A
55 = 55 A
1 = Screw connection
2 = Spring-loaded
3 = Ring cable
connection M5
A = Zero-point
switching

C = 3-phase 3 = 110 VAC
4 = 4 - 30 VDC

5 = 48 - 600 V

Not all possible versions are available ex stock.

Main Circuit
2
:
I
max
I
e
IEC 947-4-3 I
e
UL/CSA
Power
loss
Min. load
current
Max. leakage
current
Type A
With Rthha
/ 40 C
A
With Rthha
/ 40 C
A
With Rthha
/ 50 C
With I
max

W
A mA
3RF2230-. 30 0,33 K/W 30 0,33 K/W 30 0,25 K/W 122 0,5 10
3RF2230-2. 20 0,86 K/W 20 0,72 K/W
3RF2255-. 55 0,09 K/W 55 0,09 K/W 55 0,05 K/W 226
3RF2255-2. 20 1,19 K/W 20 1,02 K/W

Type 3RF22. . - . AC. 5
Rated operating voltage U
e
V 48 ... 600
Voltage range V 40 ... 660
Rated frequency Hz 50/60 10 %
Rated insulation voltage U
i
V 600
Rated impulse withstand voltage U
imp
kV 6
Blocking voltage V 1200
Slew rate V/s 1000

Rated impulse withstand strength Itsm I
2
t value
Type A A
2
s
3RF2230- . 300 450
3RF2255-. 600 1800

Control Circuit A1-A2:
Type 3RF22. . - . AC3. 3RF22. . - . AC4.
Control voltage U
s
V AC 110 DC 4 ... 30
Max. control voltage U
s
V 121 30
Typical operating current mA 15 30
Response voltage V 90 4
Drop-out voltage V < 40 1
Switching times ON delay ms 40 + max. one half-wave 1 + max. one half-wave
OFF delay ms 40 + max. one half-wave 1 + max. one half-wave

1
Use overvoltage protection device; max cut-off-voltage 6.000 V; min energy handling capability 100 J
2
The current I
max
provides information about the performance of the solid-state relays. The actual permitted rated operating current I
e

can be smaller depending on the connection method and cooling conditions. The spring-loaded terminals version can be used for a
rated current of up to approx. 20 A with one conductor and up to approx. 40 A with two conductor on each terminal.
http://www.siemens.com/solid-state-switching-devices
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF22..-AC. Zero-point Switching 3-phase Solid State Relays

Subject to changes 08/2010 Page 2/5
http://www.siemens.com/solid-state-switching-devices
General Data:
Ambient temperature
During operation, derating as of 40 C C -25 ... 60
During storage C -55 ... 80
Mounting altitude m 0 ... 1000; at > 1000 m, please contact our Technical Assistance
Impact resistance acc. to DIN IEC 68 g/ms 15/11
Vibration resistance g 2
Degree of protection IP20
Electromagnetic compatibility
(


Interference emission
o Conducted interference voltage
IEC 60 947-4-3

Class A for industrial applications
3

Interference resistance
o Electrostatic discharge acc. to
IEC 61 000-4-2 (corresponds
to severity 3)

kV Contact discharge 4; air discharge 8; performance criterion 2
o Induced HF fields acc. to
IEC 61 000-4-6

MHz 0.15 ... 80; 140 dBV; performance criterion 1
o Burst acc. to IEC 61 000-4-4 kV 2/5.0 kHz; performance criterion 2
o Surge acc. to IEC 61 000-4-5 kV Phase-to-ground 2; phase-to-phase 1; performance criterion 2
Dielectric Strength 50/60 Hz
(Input, Output / Base)

V rms 4000


Type 3RF22. . - 1. 3RF22. . - 2. 3RF22. . - 3.
Connection, main contacts Screw connection
Spring-loaded
connection
Ring cable connection
Conductor cross-section
o Solid mm
2

2 x (1,5 ... 2,5),
2 x (2,5 ... 6)
2x (0,5 ... 2,5)
o Finely stranded with end sleeve mm
2

2 x (1,5 ... 2,5),
2 x (2,5 ... 6), 1 x 10
2x (0,5 ... 1,5)
o Finely stranded w/o end sleeve mm
2
2x (0,5 ... 2,5)
o Solid or stranded AWG 2 x (14 ... 10) 2 x (18 ... 14)
Stripping length mm 10 10
Terminal screw M 4 - M 5
Nm 2 ... 2,5 - 2 ... 2,5 o Tightening torque
D 5...6 mm / PZ 2
lb.in 18 ... 22 - 18 ... 22
Cable lug DIN - - DIN 46234 5-2,5 ... 5-25
JIS - - JIS C 2805 R 2-5 14-5
Connection, auxiliary/control
contacts

Conductor cross-section with or
without end sleeve
mm
mm
AWG
1 x (0,5 ... 2,5)
2 x (0,5 ... 1,0)
20 ... 12
0,5 ... 2,5

20 ... 12
1 x (0,5 ... 2,5)
2 x (0,5 ... 1,0)
20 ... 12
Stripping length mm 7 10 7
Terminal screw M 3 - M 3
Nm 0,5 ... 0,6 - 0,5 ... 0,6 o Tightening torque
D 3.5 / PZ 1
lb.in 4,5 ... 5,3 - 4,5 ... 5,3


3
Attention!
This product was constructed as an EMC Class A device. The use of this product in residential applications could
lead to radio interferences. In such an application, additional filtering may be required.
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF22..-AC. Zero-point Switching 3-phase Solid State Relays

Subject to changes 08/2010 Page 3/5

Type Semiconductor protection fuse
Full-range fuse Partial-range fuse
LV HBC
design
cylindrical
design
LV HBC
design
cylindrical design
gR/SITOR gR/Neozed
4
aR/SITOR aR/SITOR
3NE1 5SE1 3NE8 3NC1 0 3NC1 4 3NC2 2
10 x 38 14 x 51 22 x 58
Maximum operation voltage U
e
460V (+10%)
3RF2230- 3NE1814-0
5
5SE1325
5
3NE 8003-1 3NC1032 3NC1430 3NC2232
3RF2255- 3NE1802-0
5
5SE1350
5
3NE 8018-1 -- 3NC1450 3NC2263
Maximum operation voltage U
e
600 V (+10%)
3RF2230- 3NE1814-0
5
-- 3NE 8003-1 3NC1025
5
3NC1430 3NC2232
3RF2255- 3NE1803-0
5
-- 3NE 8018-1 -- 3NC1450
5
3NC2250
5

Fused Design with Semiconductor Protection:

Type Line protection fuse
LV HBC design cylindrical design DIAZED
gG gG gG gG fast
3NA 3NW 3NW 3NW 5SB
10 x 38 mm 14 x 51 mm 22 x 58 mm
Maximum operation voltage U
e
460V (+10%)
3RF2230- 3NA3803-6
5
-- 3NW6101-1
5
3NW6205-1
5
5SB171
5

3RF2255- 3NA3807-6
5
-- -- -- 5SB311
5

Maximum operation voltage U
e
600 V (+10%)
3RF2230- 3NA3803-6
5
-- -- -- --
3RF2255- 3NA3805-6
5
-- -- -- --


Accessories:
Function module Order No. Applicable for the
following types
Versions
Converter 3RF2900-0EA18 3RF22. . - . AC4. Us = AC/DC 24 V


4
Operation voltage only up to 400V!
5
These fuses have a lower rated current than the solid state relay.
http://www.siemens.com/solid-state-switching-devices
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF22..-AC. Zero-point Switching 3-phase Solid State Relays

Subject to changes 08/2010 Page 4/5

Characteristic Curves:

3RF2230-
4 8 12 16 20 24 28 32 36
Rthha
0
20
40
60
80
100
120
140
160
0 10 20 30 40 50 60
0,26 K/W
0,33 K/W
0,44 K/W
0,62 K/W
0,9 K/W
1,3 K/W
1,7 K/W
2,2 K/W
3 K/W
4 K/W
5 K/W
7 K/W
10 K/W
3 mm 5 mm
Min. thickness of the heat sink the relay is mounted to
Ie in A
P
M

i
n

W
Ta in C


3RF2255-
5 15 25 35 45 55
Rthha
0
50
100
150
200
250
0 10 20 30 40 50 60
0,06 K/W
0,09 K/W
0,15 K/W
0,25 K/W
0,4 K/W
0,6 K/W
0,8 K/W
1,1 K/W
1,5 K/W
2 K/W
3 K/W
4 K/W
6 K/W
3 mm 5 mm
Min. thickness of the heat sink the relay is mounted to
Ie in A
P
M
i
n
W
Ta in C


http://www.siemens.com/solid-state-switching-devices
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF22..-AC. Zero-point Switching 3-phase Solid State Relays

Subject to changes 08/2010 Page 5/5

Dimension Drawings
6
:

Screw
connection
Spring-loaded
connection
Ring cable
connection
http://www.siemens.com/solid-state-switching-devices
Device / Example Circuit Diagram:



6
Dimensions in mm (in)
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS Solid-state Switching Devices
3RF23..-.AA.. Zero-Point Switching Solid State Contactors
Subject to changes 08/2011 Page 1/9
http://www.siemens.com/solid-state-switching-devices
Main Characteristics:
Zero-point switching
LED display
Various connection technologies
Plug-in control terminal
Degree of protection IP 20
Insulated mounting foot

Standards / Approvals:
DIN EN 60947-4-3
UL 508 / CSA
CE
C-Tick

Ordering Key:
3RF23 10 - 1 A A 0 2
Max.
load current
Connection
technology
Switching
function
Controlled
phases
Control voltage Operating
voltage
Solid state
contactor
with heat sink
10 = 10.5 A
20 = 20 A
30 = 30 A
40 = 40 A
50 = 50 A
70 = 70 A
90 = 88 A
1 = Screw connection
2 = Spring-loaded
connection
3 = Ring cable
connection M5
A = Zero-point
switching

A = Single-phase 0 = 24 V DC
1 = 24 V AC/DC
2 = 110 - 230 V AC
4 = 4 - 30 V DC
2 = 24 - 230 V
4 = 48 - 460 V
5 = 48 - 600 V
6 = 48 - 600 V
Not all possible versions are available ex stock!

Main Circuit:
Type 3RF23. . - . AA. 2 3RF23. . - . AA. 4 3RF23. . - . AA. 5 3RF23. . - . AA. 6
Rated operating voltage Ue V 24 ... 230 48 ... 460 48 ... 600 48 ... 600
Voltage range V 20 ... 253 40 ... 506 40 ... 660 40 ... 660
Rated frequency Hz 50/60 10 %
Rated insulation voltage Ui V 600
Rated impulse withstand voltage Uimp kV 6
Blocking voltage V 800 1200 1200 1600
Slew rate V/s 1000

Type current AC-51
1
Imax at 40C
Ie acc. to
IEC947-4-3 at
40C
Ie UL/CSA
at 50C
Power loss
with Imax
Min. load
current
Max. reverse
current
Type A A A W A mA
3RF2310- . AA. 10.5 7.5 9.6 11 0.1 10
3RF2320- . AA. 20 13.2 17.6 20 0.5 10
3RF2330- 1AA. 30 22 27 33 0.5 10
3RF2330- 3AA. 30 22 27 33 0.5 10
3RF2340- 1AA. 40 33 36 44 0.5 10
3RF2340- 3AA. 40 33 36 44 0.5 10
3RF2350- 1AA. 50 36 45 54 0.5 10
3RF2350- 3AA. 50 36 45 54 0.5 10
3RF2370- 3AA. 70 70 62 83 0.5 10
3RF2390- 3AA. 88 88 83 117 0.5 10



1
The type current provides information about the performance of the solid-state relays. The actual permitted rated
operating current Ie can be smaller depending on the connection method and cooling conditions.
VOLTAR
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS Solid-state Switching Devices
3RF23..-.AA.. Zero-Point Switching Solid State Contactors
Subject to changes 08/2011 Page 2/9
http://www.siemens.com/solid-state-switching-devices
















Control Circuit A1-A2:
Type 3RF23. . - . AA0. 3RF23. . - . AA1. 3RF23. . - . AA2. 3RF23. . - . AA4.
Control voltage Us V
DC 24
acc. to EN 61131-2
AC/DC 24 AC 110 ... 230 DC 4 ... 30
Max. control voltage Us V 30 AC 26,5 DC 30 253 30
Typical operating current mA 20 ( 6,5
2
) 20 20 15 20
Response voltage V 15 AC 14 DC 15 90 4
Drop-out voltage V 5 5 5 40 1
Rated frequency
of the control supply voltage
Hz --
50/60
10 %
-- 50/60 10 % --
Switching times ON delay ms
1 + Max. one
half-wave
40 + Max. one
half-wave
1 + Max. one
half-wave
OFF delay ms
1 + Max. one
half-wave
10 + Max. one hw.
15 + Max. one Hw
40 + Max. one
half-wave
1 + Max. one
half-wave

General Data:
Ambient temperature
During operation C -25 ... 60
During storage C -55 ... 80
Mounting altitude m 0 ... 1000; at > 1000 m, please contact our Technical Assistance
Impact resistance acc. to DIN IEC 68 g/ms 15/11
Vibration resistance g 2
Degree of protection IP20
Electromagnetic compatibility (EMC)
Interference emission
o Conducted interference voltage
IEC 60 947-4-3
Class A for industrial applications
3

o Radiated, high-frequency
interference voltage IEC 60 947-4-3
Class B for residential/office/commercial applications
Interference resistance
o Electrostatic discharge acc. to
IEC 61 000-4-2 (corresponds
to severity 3)
kV Contact discharge 4; air discharge 8; performance criterion 2
o Induced HF fields acc. to
IEC 61 000-4-6
MHz 0.15 ... 80; 140 dBV; performance criterion 1
o Burst acc. to IEC 61 000-4-4 kV 2/5.0 kHz; performance criterion 2
o Surge acc. to IEC 61 000-4-5 kV Phase-to-ground 2; phase-to-phase 1; performance criterion 2
Dielectric Strength 50/60 Hz
(Input, Output / Base)
V rms 4000

2
Only Low Power consumption versions 3RF23..-.AA..-0KN0
3
Attention!
This product was constructed as a EMC Class A device. The use of this product in residential applications could lead
to radio interferences. In such an application, additional filtering may be required.

Rated impulse
withstand strength Itsm
I
2
t value
Type A A
2
s
3RF2310- . AA. 2 200 200
3RF2310- . AA. 4 200 200
3RF2310- . AA. 6 400 800
3RF2320- . A. 600 1800
3RF2330- . A. 600 1800
3RF2340- . AA. 2 1200 7200
3RF2340- . AA. 4 1200 7200
3RF2340- . AA. 6 1150 6600
3RF2350- . A. 1150 6600
3RF2370- . A. 1150 6600
3RF2390- . A. 1150 6600
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS Solid-state Switching Devices
3RF23..-.AA.. Zero-Point Switching Solid State Contactors
Subject to changes 08/2011 Page 3/9
http://www.siemens.com/solid-state-switching-devices


Type 3RF23. . - 1. 3RF23. . - 2. 3RF23. . - 3.
Connection, main contacts Screw connection
Spring-loaded
connection
Ring cable connection
Conductor cross-section
o Solid mm
2

2 x (1.5 ... 2.5),
2 x (2.5 ... 6)
2x (0.5 ... 2.5)
o Finely stranded with end sleeve mm
2

2 x (1.5 ... 2.5),
2 x (2.5 ... 6), 1 x 10
2x (0.5 ... 1.5)
o Finely stranded w/o end sleeve mm
2
2x (0.5 ... 2.5)
o Solid or stranded AWG 2 x (14 ... 10) 2 x (18 ... 14)
Stripping length mm 10 10
Terminal screw M 4 - M 5
Nm 2 ... 2.5 - 2 ... 2.5 o Tightening torque
D 5...6 mm / PZ 2
lb.in 18 ... 22 - 18 ... 22
Cable lug DIN - - DIN 46234 5-2.5 ... 5-25
4

JIS - - JIS C 2805 R 2-5 14-5
Connection, control contacts
Conductor cross-section with or
without end sleeve
mm
mm
AWG
1 x (0.5 ... 2.5)
2 x (0.5 ... 1.0)
20 ... 12
0.5 ... 2.5

20 ... 12
1 x (0.5 ... 2.5)
2 x (0.5 ... 1.0)
20 ... 12
Stripping length mm 7 10 7
Terminal screw M 3 - M 3
Nm 0.5 ... 0.6 - 0.5 ... 0.6 o Tightening torque
D 3.5 / PZ 1
lb.in 4.5 ... 5.3 - 4.5 ... 5.3


4
Maximum breadth of the Cable lug 12 mm!
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS Solid-state Switching Devices
3RF23..-.AA.. Zero-Point Switching Solid State Contactors
Subject to changes 08/2011 Page 4/9
http://www.siemens.com/solid-state-switching-devices

Type Semiconductor protection fuse
Full-range fuse Partial-range fuse

LV HBC
design
Cylindrical
design
LV HBC
design
Cylindrical design
5

gR/gS/SITOR gR/Neozed aR/gR/SITOR aR/SITOR
3NE1 5SE1 3NE8 3NC1 0 3NC1 4 3NC2 2
10 x 38 14 x 51 22 x 58
3RF2310- . AA. 2 3NE1813-0 5SE 1316 3NE 8015-1 3NC1020 3NC1430 3NC2225
3RF2310- . AA. 4 3NE1813-0 5SE 1316 3NE 8015-1 3NC1016 3NC1420 3NC2220
3RF2310- . AA. 6 3NE1813-0 5SE 1316 3NE 8015-1 3NC1032 3NC1440 3NC2240
3RF2320- . AA. 2 3NE1814-0 5SE 1325 3NE 8015-1 3NC1032 3NC1450 3NC2263
3RF2320- . AA. 4 3NE1814-0 5SE 1325 3NE 8015-1 3NC1032 3NC1450 3NC2263
3RF2320- . AA. 6 3NE1814-0 5SE 1325 3NE 8015-1 3NC1032 3NC1450 3NC2250
3RF2330- . AA. 2 3NE1803-0 5SE 1335 3NE 8003-1 3NC1032 3NC1450 3NC2263
3RF2330- . AA. 4 3NE1803-0 5SE 1335 3NE 8003-1 3NC1032 3NC1450 3NC2263
3RF2330- . AA. 6 3NE1803-0 5SE 1335 3NE 8003-1 3NC1032 3NC1450 3NC2250
3RF2340- . AA. 2 3NE1802-0 5SE 1350 3NE 8017-1 -- 3NC1450 3NC2200
3RF2340- . AA. 4 3NE1802-0 5SE 1350 3NE 8017-1 -- 3NC1450 3NC2280
3RF2340- . AA. 6 3NE1802-0 5SE 1350 3NE 8017-1 -- 3NC1450 3NC2280
3RF2350- . AA. 2 3NE1817-0 5SE 1363 3NE 8018-1 -- 3NC1450 3NC2200
3RF2350- . AA. 4 3NE1817-0 5SE 1363 3NE 8018-1 -- 3NC1450 3NC2280
3RF2350- . AA. 6 3NE1817-0 5SE 1363 3NE 8018-1 -- 3NC1450 3NC2280
3RF2370- . AA. 2 3NE1820-0 -- 3NE 8020-1 -- -- 3NC2200
3RF2370- . AA. 4 3NE1020-2 -- 3NE 8020-1 -- -- 3NC2280
3RF2370- . AA. 5
7
3NE1020-2 -- 3NE 8020-1 -- -- 3NC2280
3RF2370- . AA. 6 3NE1020-2 -- 3NE 8020-1 -- -- 3NC2280
3RF2390- . AA. 2 3NE1021-2 -- 3NE 8021-1 -- -- 3NC2200
3RF2390- . AA. 4 3NE1021-2 -- 3NE 8021-1 -- -- 3NC2280
6

3RF2390- . AA. 5
7
3NE1021-2 -- 3NE 8021-1 -- -- 3NC2280
6

3RF2390- . AA. 6 3NE1020-2
6
-- 3NE 8021-1 -- -- 3NC2280
6



5
Max. allowable fuse; with smaller fuses the load reversal stability can be limited.
6
These fuses have a lower rated current than the solid state contactors.
Fused Design with Semiconductor Protection
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS Solid-state Switching Devices
3RF23..-.AA.. Zero-Point Switching Solid State Contactors
Subject to changes 08/2011 Page 5/9
http://www.siemens.com/solid-state-switching-devices

Typ Line fuse protection
LV HBC design Cylindrical design Neozed DIAZED
gG gG gG gG gG fast
3NA 3NW 3NW 3NW 5SE2 5SB
10 x 38 mm 14 x 51 mm 22 x 58 mm
3RF2310- . AA. 2 3NA6803 3NW6001-1
6
3NW6101-1
6
-- 5SE2306
6
5SB141
3RF2310- . AA. 4 3NA6801 3NW6001-1
6
3NW6101-1
6
-- 5SE2306
6
5SB141
3RF2310- . AA. 5
7
3NA6801 3NW6001-1
6
3NW6101-1
6
-- 5SE2306
6
5SB141
3RF2310- . AA. 6 3NA6803-6 -- -- -- -- --
3RF2320- . AA. 2 3NA6807 3NW6007-1 3NW6107-1 3NW6207-1 5SE2320 5SB171
3RF2320- . AA. 4 3NA6807 3NW6005-1
6
3NW6105-1
6
3NW6205-1
6
5SE2320 5SB171
3RF2320- . AA. 5
7
3NA6807 3NW6005-1
6
3NW6105-1
6
3NW6205-1
6
5SE2320 5SB171
3RF2320- . AA. 6 3NA6807-6 -- -- -- -- --
3RF2330- . AA. 2 3NA6810
6
-- 3NW6107-1
6
3NW6207-1
6
5SE2320
6
5SB311
3RF2330- . AA. 4 3NA6807
6
-- 3NW6105-1
6
3NW6205-1
6
5SE2320
6
5SB311
3RF2330- . AA. 5
7
3NA6807
6
-- 3NW6105-1
6
3NW6205-1
6
5SE2320
6
5SB311
3RF2330- . AA. 6 3NA6807-6
6
-- -- -- -- --
3RF2340- . AA. 2 3NA6817 -- 3NW6117-1 3NW6217-1 5SE2335
6
5SB321
3RF2340- . AA. 4 3NA6812
6
-- 3NW6112-1
6
3NW6212-1
6
5SE2335
6
5SB321
3RF2340- . AA. 5
7
3NA6812
6
-- 3NW6112-1
6
3NW6212-1
6
5SE2335
6
5SB321
3RF2340- . AA. 6 -- -- -- -- -- --
3RF2350- . AA. 2 -- -- -- 3NW6217-1
6
5SE2335
6
5SB321
3RF2350- . AA. 4 -- -- -- -- 5SE2335
6
5SB321
3RF2350- . AA. 5
7
-- -- -- -- 5SE2335
6
5SB321
3RF2350- . AA. 6 -- -- -- -- -- --
3RF2370- . AA. 2 -- -- -- -- 5SE2335
6
5SB331
6

3RF2370- . AA. 4 -- -- -- -- 5SE2335
6
5SB321
6

3RF2370- . AA. 5
7
-- -- -- -- 5SE2335
6
5SB321
6

3RF2370- . AA. 6 -- -- -- -- -- --
3RF2390- . AA. 2 -- -- -- -- 5SE2335
6
5SB331
6

3RF2390- . AA. 4 -- -- -- -- 5SE2335
6
5SB321
6

3RF2390- . AA. 5
7
-- -- -- -- 5SE2335
6
5SB321
6

3RF2390- . AA. 6 -- -- -- -- -- --


Accessories
Function module Order No. Applicable for Versions
Converter 3RF2900-0EA18 3RF23. . - . AA0.
3RF23. . - . AA4.
Us = 24 V DC
Load monitoring Basic 3RF29. . -0FA08 3RF23. . - 1AA0.
3RF23. . - 1AA4.
Screw connection,
Us = 24 V DC
Load monitoring Extended
8
3RF29. . - 0GA. . 3RF23. . - 1. Screw connection
3RF23. . - 3. Ring cable connection
Power regulator
9
3RF29. . - 0HA. . 3RF23. . - 1AA. Screw connection
3RF23. . - 3AA. Ring cable connection
Power controllerr
9
3RF29. . - 0KA. . 3RF23. . - 1AA. Screw connection
3RF23. . - 3AA. Ring cable connection
Terminal cover
10
3RF2900-3PA88 3RF23. . - 1. Screw connection
3RF23. . - 3. Ring cable connection


7
Use at main voltage Ue up to 506 V.

8
For the exact allocation of the function modules, please refer to the IC 10 Catalog.
9
Use of Power controller or regulator is possible for the full-wave control mode. The phase angle control mode is
recommended only for the combination with instantaneous switching devices.
10
The terminal covers can be easily adjusted for screw connection applications.
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS Solid-state Switching Devices
3RF23..-.AA.. Zero-Point Switching Solid State Contactors
Subject to changes 08/2011 Page 6/9
http://www.siemens.com/solid-state-switching-devices
Legend
I
e
Current
P Power loss
T
a
Ambient temperature
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
0 1 2 3 4 5 6 7 8 9 101112
I [A]
P

[
W
]
0
2
4
6
8
10
12
14
0 10 20 30 40 50 60
Ta [C]
I

[
A
]

Characteristic Curves
3RF2310-.

Upper curves:
I
max
thermal limit current
Lower curves:
Rated current Ie
acc. to
DIN EN 60947-4-3
(maximum temperature rise
at heat sink 50 K)

Continuous lines:
Stand-alone mounting
Dashed lines:
Side-by-side mounting

3RF2320-.


















3RF2330-.


















0
2
4
6
8
10
12
14
16
18
20
22
24
26
0 4 8 12 16 20 24
I [A]
P

[
W
]
0
5
10
15
20
25
30
0 10 20 30 40 50 60
Ta [C]
I

[
A
]
0
4
8
12
16
20
24
28
32
36
40
44
0 4 8 12 16 20 24 28 32 36
I [A]
P

[
W
]
0
5
10
15
20
25
30
35
40
0 10 20 30 40 50 60
Ta [C]
I

[
A
]
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS Solid-state Switching Devices
3RF23..-.AA.. Zero-Point Switching Solid State Contactors
Subject to changes 08/2011 Page 7/9
http://www.siemens.com/solid-state-switching-devices
Legend
I
e
Current
P Power loss
T
a
Ambient temperature
0
4
8
12
16
20
24
28
32
36
40
44
48
52
56
0 5 10 15 20 25 30 35 40 45
I [A]
P

[
W
]
0
10
20
30
40
50
60
0 10 20 30 40 50 60
Ta [C]
I

[
A
]
0
10
20
30
40
50
60
70
0 10 20 30 40 50 60
I [A]
P

[
W
]
0
10
20
30
40
50
60
70
0 10 20 30 40 50 60
Ta [C]
I

[
A
]
3RF2340-.
11


Upper curves:
I
max
thermal limit current
Lower curves:
Rated current Ie
acc. to
DIN EN 60947-4-3 (maximum
temperature rise at heat sink
50 K)



3RF2350-.
11



















3RF2370-.
11


















11
Identical current / temperature curves for stand-alone and side-by-side mounting
0
10
20
30
40
50
60
70
80
90
100
110
0 10 20 30 40 50 60 70 80
I [A]
P

[
W
]
0
10
20
30
40
50
60
70
80
90
0 10 20 30 40 50 60
Ta [C]
I

[
A
]
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS Solid-state Switching Devices
3RF23..-.AA.. Zero-Point Switching Solid State Contactors
Subject to changes 08/2011 Page 8/9
http://www.siemens.com/solid-state-switching-devices
0
10
20
30
40
50
60
70
80
90
100
110
120
0 10 20 30 40 50 60 70 80 90
I [A]
P

[
W
]
0
10
20
30
40
50
60
70
80
90
100
0 10 20 30 40 50 60
Ta [C]
I

[
A
]
3RF2390-.
11


Curve:
I
max
thermal limit current
and
rated current Ie
acc. to DIN EN 60947-
4-3 (maximum
temperature rise at heat
sink 50 K)










Mounting Instructions
12
:














Dimension Drawings
12
:



12
Dimensions in mm, (in);
Stand-alone mounting, Characteristic curves show derating for side-by-side mounting
3
R
F
2
3
1
0
,

3
R
F
2
3
2
0
3
R
F
2
3
3
0
3
R
F
2
3
1
0
,

3
R
F
2
3
2
0
3
R
F
2
3
3
0
>
2
0

(
0
,
8
)
>
2
0

(
0
,
8
)
>
2
0

(
0
,
8
)
>50 (2)
>70 (2,75)
10
10
3
R
F
2
3
4
0
,

3
R
F
2
3
5
0
3
R
F
2
3
7
0
,

3
R
F
2
3
9
0
3
R
F
2
3
4
0
,

3
R
F
2
3
5
0
3
R
F
2
3
7
0
,

3
R
F
2
3
9
0
>
2
0

(
0
,
8
)
>
2
0

(
0
,
8
)
>50 (2)
>70 (2,75)
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS Solid-state Switching Devices
3RF23..-.AA.. Zero-Point Switching Solid State Contactors
Subject to changes 08/2011 Page 9/9
http://www.siemens.com/solid-state-switching-devices

Device / Example Circuit Diagram:

3RF23. . - . AA0. 3RF23. . - . AA2.
Us = 24 V DC Us = 110 ... 230 V AC



F1 Main circuit fuse
(Semiconductor protection recommended)
F2 Control circuit fuse
K1 3RF2 solid state contactor
R Load resistance

1/N/PE 50 Hz 230 V
N
PE
L
F1
K1
R
S1
ON /OFF
F2
1 L
2 T
A2 ~
A1 ~
PE
1/N/PE 50 Hz 230 V
N
PE
L
F1
K1
R
S1
ON /OFF
L -
L +
DC 24 V
F2
1 L
2 T
A2 -
A1 +
PE
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS Solid-state Switching Devices
3RF23..-.BA.. Instantaneous-Switching Solid State Contactors
Subject to changes 08/2011 Page 1/9
http://www.siemens.com/solid-state-switching-devices
Main Characteristics:
Instantaneous switching
LED display
Various connection technologies
Plug-in control terminal
Degree of protection IP 20
Insulated mounting foot

Standards / Approvals:
DIN EN 60947-4-3
UL 508 / CSA
CE
C-Tick

Ordering Key:
3RF23 10 - 1 B A 0 2
Max. load
current
Connection
technology
Switching
function
Controlled
phases
Control
voltage
Operating
voltage
Solid state
contactor
with heat sink
10 = 10.5 A
20 = 20 A
30 = 30 A
40 = 40 A
50 = 50 A
70 = 70 A
90 = 88 A
1 = Screw connection
3 = Ring cable
connection M5
B = Instantaneous
switching
A = Single-phase 0 = 24 V DC
2 = 110 - 230 V AC
4 = 4 - 30 V DC


2 = 24 - 230 V
4 = 48 - 460 V
6 = 48 - 600 V
Not all possible versions are available ex stock.

Main Circuit:
Type current AC-51
1

IAC-51 / Imax
at 40C
Ie IEC947-4-3
at 40C
Ie UL/CSA
at 50C
IAC-15 *
at 40C
IAC-53 **
at 40C
Power loss with
Imax
Min. load
current
Max.
reverse
current
Type A A A A A W A mA
3RF2310-1B. 10.5 7.5 9.6 6 7 11 0.1 10
3RF2320-1B. 20 13.2 17.6 12 15 20 0.5 10
3RF2330-1B. 30 22 27 15 18 33 0.5 10
3RF2340-1B. 40 33 36 20 24 44 0.5 10
3RF2350-1B. 50 36 45 25 31 54 0.5 10
3RF2370- 1B. 50 50 50 27,5 34 53 0,5 10
3RF2370- 3B. 70 70 62 27,5 34 83 0,5 10
3RF2390- 1B. 50 50 50 30 37 53 0,5 10
3RF2390- 3B. 88 88 80 30 37 117 0,5 10
* I
AC-15
Parameter: max. 1200 starts/h, 50 % ON duration, 10-fold inrush current for 60 msec.
** I
AC-53
Parameter for three-phase applications in three-phase networks:
Max. 1200 starts/h, 50 % ON duration, 6-fold inrush current for 100 msec.

Type 3RF23. . - . BA. 2 3RF23. . - . BA. 4 3RF23. . - . BA. 6
Rated operating voltage Ue V 24 ... 230 48 ... 460 48 ... 600
Voltage range V 20 ... 253 40 ... 506 40 ... 660
Rated frequency Hz 50/60 10 %
Rated insulation voltage Ui V 600
Rated impulse withstand voltage Uimp kV 6
Blocking voltage V 800 1200 1600
Slew rate V/s 1000

1
The type current provides information about the performance of the solid-state relays. The actual permitted
rated operating current Ie can be smaller depending on the connection method and cooling conditions.
VOLTAR
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS Solid-state Switching Devices
3RF23..-.BA.. Instantaneous-Switching Solid State Contactors
Subject to changes 08/2011 Page 2/9
http://www.siemens.com/solid-state-switching-devices
















Control Circuit:
Type 3RF23. . - . BA0. 3RF23. . - . BA2. 3RF23. . - . BA4.
Control voltage Us V 24 acc. to EN 61131-2 110 ... 230 4 ... 30 DC
Max. control voltage Us V 30 253 30
Typical operating current mA 20 15 20
Response voltage V 15 90 4
Drop-out voltage V 5 40 1
Rated frequency
of the control supply voltage
Hz 50/60 10 % --
Switching times ON delay ms 1 40 1
OFF delay ms 1 + Max. one half-wave
40 + Max. one half-
wave
1 + Max. one
half-wave

General Data:
Ambient temperature
During operation C -25 ... 60
During storage C -55 ... 80
Mounting altitude m 0 ... 1000; at > 1000 m, please contact our Technical Assistance
Impact resistance acc. to DIN IEC 68 g/ms 15/11
Vibration resistance g 2
Degree of protection IP20
Electromagnetic compatibility (EMC)
Interference emission
o Conducted interference voltage
IEC 60 947-4-3
Class A for industrial applications
2

o Radiated, high-frequency
interference voltage IEC 60 947-4-3
Class B for residential/office/commercial applications
Interference resistance
o Electrostatic discharge acc. to
IEC 61 000-4-2 (corresponds
to severity 3)
kV Contact discharge 4; air discharge 8; performance criterion 2
o Induced HF fields acc. to
IEC 61 000-4-6
MHz 0.15 ... 80; 140 dBV; performance criterion 1
o Burst acc. to IEC 61 000-4-4 kV 2/5.0 kHz; performance criterion 2
o Surge acc. to IEC 61 000-4-5 kV Phase-to-ground 2; phase-to-phase 1; performance criterion 2
Dielectric Strength 50/60 Hz
(Input, Output / Base)
V rms 4000


2
Attention!
This product was constructed as an EMC Class A device. The use of this product in residential applications could lead to
radio interferences. In such an application, additional filtering may be required.

Rated impulse
withstand strength Itsm
I
2
t value
Type A A
2
s
3RF2310- . BA. 2 200 200
3RF2310- . BA. 4 200 200
3RF2310- . BA. 6 400 800
3RF2320- . B. 600 1800
3RF2330- . B. 600 1800
3RF2340- . BA. 2 1200 7200
3RF2340- . BA. 4 1200 7200
3RF2340- . BA. 6 1150 6600
3RF2350- . B. 1150 6600
3RF2370- . B. 1150 6600
3RF2390- . B. 1150 6600
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS Solid-state Switching Devices
3RF23..-.BA.. Instantaneous-Switching Solid State Contactors
Subject to changes 08/2011 Page 3/9
http://www.siemens.com/solid-state-switching-devices

Type 3RF23. . - 1. 3RF23. . - 3.
Connection, main contacts Screw connection Ring cable connection
Conductor cross-section
o Solid mm
2

2 x (1.5 ... 2.5),
2 x (2.5 ... 6)

o Finely stranded with end sleeve mm
2

2 x (1.5 ... 2.5),
2 x (2.5 ... 6), 1 x 10

o Finely stranded w/o end sleeve mm
2

o Solid or stranded AWG 2 x (14 ... 10)
Stripping length mm 10
Terminal screw M 4 M 5
Nm 2 ... 2.5 2 ... 2.5 o Tightening torque
D 5...6 mm / PZ 2
lb.in 18 ... 22 18 ... 22
Cable lug DIN - DIN 46234 5-2.5 ... 5-25
3

JIS - JIS C 2805 R 2-5 14-5
Connection,
auxiliary/control contacts

Conductor cross-section with or
without end sleeve
mm
mm
AWG
1 x (0.5 ... 2.5)
2 x (0.5 ... 1.0)
20 ... 12
1 x (0.5 ... 2.5)
2 x (0.5 ... 1.0)
20 ... 12
Stripping length mm 7 7
Terminal screw M 3 M 3
Nm 0.5 ... 0.6 0.5 ... 0.6 o Tightening torque
D 3.5 / PZ 1
lb.in 4.5 ... 5.3 4.5 ... 5.3


3
Maximum breadth of the Cable lug 12 mm!
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS Solid-state Switching Devices
3RF23..-.BA.. Instantaneous-Switching Solid State Contactors
Subject to changes 08/2011 Page 4/9
http://www.siemens.com/solid-state-switching-devices


Type Semiconductor protection fuse
Full-range fuse Back-up fuse
LV HBC
design
Cylindrical
design
LV HBC
design
Cylindrical design
4

gR/gS/SITOR gR/Neozed aR/gR/SITOR aR/SITOR
3NE1 5SE1 3NE8 3NC1 0 3NC1 4 3NC2 2
10 x 38 14 x 51 22 x 58
3RF2310- . BA. 2 3NE1813-0 5SE 1316 3NE 8015-1 3NC1020 3NC1430 3NC2225
3RF2310- . BA. 4 3NE1813-0 5SE 1316 3NE 8015-1 3NC1016 3NC1420 3NC2220
3RF2310- . BA. 6 3NE1813-0 5SE 1316 3NE 8015-1 3NC1032 3NC1440 3NC2240
3RF2320- . BA. 2 3NE1814-0 5SE 1325 3NE 8015-1 3NC1032 3NC1450 3NC2263
3RF2320- . BA. 4 3NE1814-0 5SE 1325 3NE 8015-1 3NC1032 3NC1450 3NC2263
3RF2320- . BA. 6 3NE1814-0 5SE 1325 3NE 8015-1 3NC1032 3NC1450 3NC2250
3RF2330- . BA. 2 3NE1803-0 5SE 1335 3NE 8003-1 3NC1032 3NC1450 3NC2263
3RF2330- . BA. 4 3NE1803-0 5SE 1335 3NE 8003-1 3NC1032 3NC1450 3NC2263
3RF2330- . BA. 6 3NE1803-0 5SE 1335 3NE 8003-1 3NC1032 3NC1450 3NC2250
3RF2340- . BA. 2 3NE1802-0 5SE 1350 3NE 8017-1 -- 3NC1450 3NC2200
3RF2340- . BA. 4 3NE1802-0 5SE 1350 3NE 8017-1 -- 3NC1450 3NC2280
3RF2340- . BA. 6 3NE1802-0 5SE 1350 3NE 8017-1 -- 3NC1450 3NC2280
3RF2350- . BA. 2 3NE1817-0 5SE 1363 3NE 8018-1 -- 3NC1450 3NC2200
3RF2350- . BA. 4 3NE1817-0 5SE 1363 3NE 8018-1 -- 3NC1450 3NC2280
3RF2350- . BA. 6 3NE1817-0 5SE 1363 3NE 8018-1 -- 3NC1450 3NC2280
3RF2370- . BA. 2 3NE1820-0 -- 3NE 8020-1 -- -- 3NC2200
3RF2370- . BA. 4 3NE1020-2 -- 3NE 8020-1 -- -- 3NC2280
3RF2370- . BA. 5
6
3NE1020-2 -- 3NE 8020-1 -- -- 3NC2280
3RF2370- . BA. 6 3NE1020-2 -- 3NE 8020-1 -- -- 3NC2280
3RF2390- . BA. 2 3NE1021-2 -- 3NE 8021-1 -- -- 3NC2200
3RF2390- . BA. 4 3NE1021-2 -- 3NE 8021-1 -- -- 3NC2280
5

3RF2390- . BA. 5
6
3NE1021-2 -- 3NE 8021-1 -- -- 3NC2280
5

3RF2390- . BA. 6 3NE1020-2
5
-- 3NE 8021-1 -- -- 3NC2280
5



4
Max. allowable fuse; with smaller fuses the load reversal stability can be limited.
5
These fuses have a lower rated current than the solid state contactors.
Fused Design with Semiconductor Protection
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS Solid-state Switching Devices
3RF23..-.BA.. Instantaneous-Switching Solid State Contactors
Subject to changes 08/2011 Page 5/9
http://www.siemens.com/solid-state-switching-devices

Typ Line fuse protection
LV HBC design Cylindrical design Neozed DIAZED
gG gG gG gG gG fast
3NA 3NW 3NW 3NW 5SE2 5SB
10 x 38 mm 14 x 51 mm 22 x 58 mm
3RF2310- . BA. 2 3NA6803 3NW6001-1
5
3NW6101-1
5
-- 5SE2306
5
5SB141
3RF2310- . BA. 4 3NA6801 3NW6001-1
5
3NW6101-1
5
-- 5SE2306
5
5SB141
3RF2310- . BA. 5
6
3NA6801 3NW6001-1
5
3NW6101-1
5
-- 5SE2306
5
5SB141
3RF2310- . BA. 6 3NA6803-6 -- -- -- -- --
3RF2320- . BA. 2 3NA6807 3NW6007-1 3NW6107-1 3NW6207-1 5SE2320 5SB171
3RF2320- . BA. 4 3NA6807 3NW6005-1
5
3NW6105-1
5
3NW6205-1
5
5SE2320 5SB171
3RF2320- . BA. 5
6
3NA6807 3NW6005-1
5
3NW6105-1
5
3NW6205-1
5
5SE2320 5SB171
3RF2320- . BA. 6 3NA6807-6 -- -- -- -- --
3RF2330- . BA. 2 3NA6810
5
-- 3NW6107-1
5
3NW6207-1
5
5SE2320
5
5SB311
3RF2330- . BA. 4 3NA6807
5
-- 3NW6105-1
5
3NW6205-1
5
5SE2320
5
5SB311
3RF2330- . BA. 5
6
3NA6807
5
-- 3NW6105-1
5
3NW6205-1
5
5SE2320
5
5SB311
3RF2330- . BA. 6 3NA6807-6
5
-- -- -- -- --
3RF2340- . BA. 2 3NA6817 -- 3NW6117-1 3NW6217-1 5SE2335
5
5SB321
3RF2340- . BA. 4 3NA6812
5
-- 3NW6112-1
5
3NW6212-1
5
5SE2335
5
5SB321
3RF2340- . BA. 5
6
3NA6812
5
-- 3NW6112-1
5
3NW6212-1
5
5SE2335
5
5SB321
3RF2340- . BA. 6 -- -- -- -- -- --
3RF2350- . BA. 2 -- -- -- 3NW6217-1
5
5SE2335
5
5SB321
3RF2350- . BA. 4 -- -- -- -- 5SE2335
5
5SB321
3RF2350- . BA. 5
6
-- -- -- -- 5SE2335
5
5SB321
3RF2350- . BA. 6 -- -- -- -- -- --
3RF2370- . BA. 2 -- -- -- -- 5SE2335
5
5SB331
5

3RF2370- . BA. 4 -- -- -- -- 5SE2335
5
5SB321
5

3RF2370- . BA. 5
6
-- -- -- -- 5SE2335
5
5SB321
5

3RF2370- . BA. 6 -- -- -- -- -- --
3RF2390- . BA. 2 -- -- -- -- 5SE2335
5
5SB331
5

3RF2390- . BA. 4 -- -- -- -- 5SE2335
5
5SB321
5

3RF2390- . BA. 5
6
-- -- -- -- 5SE2335
5
5SB321
5

3RF2390- . BA. 6 -- -- -- -- -- --


Accessories
Function module Order No. Applicable for Versions
Converter 3RF2900-0EA18 3RF23. . - . BA0. Us = 24 V DC
Load monitoring Basic 3RF29. . - 0FA08 3RF23. . - 1BA0. Screw connection,
Us = 24 V DC
Load monitoring Extended
7
3RF29. . - 0GA. . 3RF23. . - 1. Screw connection
3RF23. . - 3. Ring cable connection
Power regulator 3RF29. . - 0HA. . 3RF23. . - 1BA. Screw connection
3RF23. . - 3BA. Ring cable connection
Power controller 3RF29. . - 0KA. . 3RF23. . - 1BA. Screw connection
3RF23. . - 3BA. Ring cable connection
Terminal cover
8
3RF2900-3PA88 3RF23. . - 1. Screw connection
3RF23. . - 3. Ring cable connection

6
Use at main voltage Ue up to 506 V.

7
For the exact allocation of the function modules, please refer to the IC 10 Catalog.
8
The terminal cover can be easily adjusted for screw connection applications.
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS Solid-state Switching Devices
3RF23..-.BA.. Instantaneous-Switching Solid State Contactors
Subject to changes 08/2011 Page 6/9
http://www.siemens.com/solid-state-switching-devices
Legend
I
e
Current
P Power loss
T
a
Ambient temperature
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
0 1 2 3 4 5 6 7 8 9 101112
I [A]
P

[
W
]
0
2
4
6
8
10
12
14
0 10 20 30 40 50 60
Ta [C]
I

[
A
]

Characteristic Curves
3RF2310-.

Upper curves:
I
max
thermal limit current
Lower curves:
Rated current Ie
acc. to
DIN EN 60947-4-3 (maximum
temperature rise at heat sink
50 K)

Continuous lines:
Stand-alone mounting
Dashed lines:
Side-by-side mounting

3RF2320-.


















3RF2330-.


















0
2
4
6
8
10
12
14
16
18
20
22
24
26
0 4 8 12 16 20 24
I [A]
P

[
W
]
0
5
10
15
20
25
30
0 10 20 30 40 50 60
Ta [C]
I

[
A
]
0
4
8
12
16
20
24
28
32
36
40
44
0 4 8 12 16 20 24 28 32 36
I [A]
P

[
W
]
0
5
10
15
20
25
30
35
40
0 10 20 30 40 50 60
Ta [C]
I

[
A
]
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS Solid-state Switching Devices
3RF23..-.BA.. Instantaneous-Switching Solid State Contactors
Subject to changes 08/2011 Page 7/9
http://www.siemens.com/solid-state-switching-devices
Legend
I
e
Current
P Power loss
T
a
Ambient temperature
0
4
8
12
16
20
24
28
32
36
40
44
48
52
56
0 5 10 15 20 25 30 35 40 45
I [A]
P

[
W
]
0
10
20
30
40
50
60
0 10 20 30 40 50 60
Ta [C]
I

[
A
]
0
10
20
30
40
50
60
70
0 10 20 30 40 50 60
I [A]
P

[
W
]
0
10
20
30
40
50
60
70
0 10 20 30 40 50 60
Ta [C]
I

[
A
]
3RF2340-.
9


Upper curves:
I
max
thermal limit current
Lower curves:
Rated current Ie
acc. to
DIN EN 60947-4-3 (maximum
temperature rise at heat sink 50
K)



3RF2350-.
9



















3RF2370-.
9


















9
Identical current / temperature curves for stand-alone and side-by-side mounting
0
10
20
30
40
50
60
70
80
90
100
110
0 10 20 30 40 50 60 70 80
I [A]
P

[
W
]
0
10
20
30
40
50
60
70
80
90
0 10 20 30 40 50 60
Ta [C]
I

[
A
]
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS Solid-state Switching Devices
3RF23..-.BA.. Instantaneous-Switching Solid State Contactors
Subject to changes 08/2011 Page 8/9
http://www.siemens.com/solid-state-switching-devices
0
10
20
30
40
50
60
70
80
90
100
110
120
0 10 20 30 40 50 60 70 80 90
I [A]
P

[
W
]
0
10
20
30
40
50
60
70
80
90
100
0 10 20 30 40 50 60
Ta [C]
I

[
A
]
3RF2390-.
9


Curve:
I
max
thermal limit current
and
rated current Ie
acc. to DIN EN 60947-4-3
(maximum temperature
rise at heat sink 50 K)



























Dimension Drawings
10
:



10
Dimensions in mm, (in);
Stand-alone mounting, characteristic curves show derating for side-by-side mounting
Mounting Instructions
10
:
3
R
F
2
3
1
0
,

3
R
F
2
3
2
0
3
R
F
2
3
3
0
3
R
F
2
3
1
0
,

3
R
F
2
3
2
0
3
R
F
2
3
3
0
>
2
0

(
0
,
8
)
>
2
0

(
0
,
8
)
>
2
0

(
0
,
8
)
>50 (2)
>70 (2,75)
10
10
3
R
F
2
3
4
0
,

3
R
F
2
3
5
0
3
R
F
2
3
7
0
,

3
R
F
2
3
9
0
3
R
F
2
3
4
0
,

3
R
F
2
3
5
0
3
R
F
2
3
7
0
,

3
R
F
2
3
9
0
>
2
0

(
0
,
8
)
>
2
0

(
0
,
8
)
>50 (2)
>70 (2,75)
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS Solid-state Switching Devices
3RF23..-.BA.. Instantaneous-Switching Solid State Contactors
Subject to changes 08/2011 Page 9/9
http://www.siemens.com/solid-state-switching-devices

Device / Example Circuit Diagram:

3RF23. . - . BA0. 3RF23. . - . BA2.
Us = DC 24 V Us = AC 110 ... 230 V



F1 Main circuit fuse
(semiconductor protection recommended)
F2 Control circuit fuse
K1 3RF2 solid state contactor
R Load resistance

1/N/PE 50 Hz 230 V
N
PE
L
F1
K1
R
S1
ON /OFF
F2
1 L
2 T
A2 ~
A1 ~
PE
1/N/PE 50 Hz 230 V
N
PE
L
F1
K1
R
S1
ON /OFF
L -
L +
DC 24 V
F2
1 L
2 T
A2 -
A1 +
PE
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF24..-.AB.. Zero-Point Switching Solid State Contactors
Main Characteristics:
Two-phase controlled
Zero switching
LED display
Various connection technologies
Plug-in control terminal
Degree of protection IP 20
Insulated mounting foot
Standards / Approvals:
DIN EN 60947-4-3
UL 508 / CSA
1

CE
C-Tick

Ordering Key:
3RF24 10 - 1 A B 4 5
Max.
load current
Connection
technology
Switching
function
Controlled
phases
Control voltage Operating
voltage
3-phase solid
state contactor
with heat sink
10 = 10,5 A
20 = 22 A
30 = 30 A
40 = 40 A
50 = 50 A
1 = Screw connection
2 = Spring-loaded
connection
3 = Ring cable
connection M5
A = Zero-point
switching

B = two-phase 3 = 110 VAC
4 = 4 - 30 VDC
5 = 190 - 230 VAC

5 = 48 - 600 V
Not all possible versions are available ex stock!

Main Circuit:
Values for 40 C
ambient temperature!
I
AC-51

I
e
acc. to
IEC947-4-3
Ie [50C]
UL/CSA
Power loss
with I
AC-51

Min. load
current
Max. leakage
current
Type A A A W A mA
3RF2410- . AB. 10,5 7 7 23 0,1 10
3RF2420- . AB. 22 15 15 44 0,5
3RF2430- . AB. 30 22 22 61
3RF2440- . AB. 40 30 30 80
3RF2450- . AB. 50 38 38 107

Type 3RF24. . - . AB. 5
Rated operating voltage U
e
V 48 ... 600
Voltage range V 40 ... 660
Rated frequency Hz 50/60 10 %
Rated insulation voltage U
i
V 600
Rated impulse withstand voltage U
imp
kV 6
Slew rate V/s 1000
Rated impulse withstand strength Itsm I
2
t value Blocking voltage
Type A A
2
s V
3RF2410- . AB. 200 200 1200
3RF2420- . AB. 600 1800 1200
3RF2430- . AB. 1200 7200 1200
3RF2440- . AB. 1150 6600 1600
3RF2450- . AB. 1150 6600 1600

Subject to changes 08/2010 Page 1/7
1
Use overvoltage protection device; max cut-off-voltage 6.000 V; min energy handling capability 100 J
http://www.siemens.com/solid-state-switching-devices
VOLTAR
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF24..-.AB.. Zero-Point Switching Solid State Contactors
Subject to changes 08/2010 Page 2/7
http://www.siemens.com/solid-state-switching-devices

Control Circuit A1-A2:
Type 3RF24. . - . AB3. 3RF24. . - . AB4. 3RF24. . - . AB5.
Control voltage U
s
V AC 110 DC 4 ... 30 AC 190 ... 230
Max. control voltage U
s
V 121 30 253
Typical operating current mA 15 30 15
Response voltage V 90 4 180
Drop-out voltage V < 40 <1 <40
Rated frequency
of the control supply voltage
Hz 50/60 10 % -- 50/60 10 %
Switching times ON delay ms 40 + Max. one half-wave 1 + Max. one half-wave 40 + Max. one half-wave
OFF delay ms 40 + Max. one half-wave 1 + Max. one half-wave 40 + Max. one half-wave

General Data:
Ambient temperature
During operation C -25 ... 60
During storage C -55 ... 80
Mounting altitude m 0 ... 1000; at > 1000 m, please contact our Technical Assistance
Impact resistance acc. to DIN IEC 68 g/ms 15/11
Vibration resistance g 2
Degree of protection IP20
Electromagnetic compatibility (EMC)
Interference emission
o Conducted interference voltage
IEC 60 947-4-3
Class A for industrial applications
2

Interference resistance
o Electrostatic discharge acc. to
IEC 61 000-4-2 (corresponds
to severity 3)
kV Contact discharge 4; air discharge 8; performance criterion 2
o Induced HF fields acc. to
IEC 61 000-4-6
MHz 0.15 ... 80; 140 dBV; performance criterion 1
o Burst acc. to IEC 61 000-4-4 kV 2/5.0 kHz; performance criterion 2
o Surge acc. to IEC 61 000-4-5 kV Phase-to-ground 2; phase-to-phase 1; performance criterion 2
Dielectric Strength 50/60 Hz
(Input, Output / Base)
V rms 4000



2
Attention!
This product was constructed as an EMC Class A device. The use of this product in residential applications could lead
to radio interferences. In such an application, additional filtering may be required.
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF24..-.AB.. Zero-Point Switching Solid State Contactors

Type 3RF24. . - 1. 3RF24. . - 2. 3RF24. . - 3.
Connection, main contacts Screw connection
Spring-loaded
connection
Ring cable connection
Conductor cross-section
o Solid mm
2

2 x (1.5 ... 2.5),
2 x (2.5 ... 6)
2x (0.5 ... 2.5)
o Finely stranded with end sleeve mm
2

2 x (1.5 ... 2.5),
2 x (2.5 ... 6), 1 x 10
2x (0.5 ... 1.5)
o Finely stranded w/o end sleeve mm
2
2x (0.5 ... 2.5)
o Solid or stranded AWG 2 x (14 ... 10) 2 x (18 ... 14)
Stripping length mm 10 10
Terminal screw M 4 - M 5
Nm 2 ... 2.5 - 2 ... 2.5 o Tightening torque
D 5...6 mm / PZ 2
lb.in 18 ... 22 - 18 ... 22
Cable lug DIN - - DIN 46234 5-2.5 ... 5-25
JIS - - JIS C 2805 R 2-5 14-5
Connection, control contacts
Conductor cross-section with or
without end sleeve
mm
mm
AWG
1 x (0.5 ... 2.5)
2 x (0.5 ... 1.0)
20 ... 12
0.5 ... 2.5

20 ... 12
1 x (0.5 ... 2.5)
2 x (0.5 ... 1.0)
20 ... 12
Stripping length mm 7 10 7
Terminal screw M 3 - M 3
Nm 0.5 ... 0.6 - 0.5 ... 0.6 o Tightening torque
D 3.5 / PZ 1
lb.in 4.5 ... 5.3 - 4.5 ... 5.3

Type Semiconductor protection fuse
Full-range fuse Back-up fuse
LV HBC
design
Cylindrical
design
LV HBC
design
Cylindrical design
3

gR/SITOR gR/Neozed
4
aR/SITOR aR/SITOR
3NE1 5SE1 3NE8 3NC1 0 3NC1 4 3NC2 2
10 x 38 14 x 51 22 x 58
Maximum operation voltage U
e
460 V (+10%)
3RF2410- . AB. 3NE1813-0 5SE 1310 3NE 8015-1 3NC1020 3NC1415 3NC2220
3RF2420- . AB. 3NE1814-0 5SE 1320 3NE 8015-1 3NC1032 3NC1450 3NC2263
3RF2430- . AB. 3NE1803-0 5SE 1335 3NE 8003-1 3NC1032 3NC1450 3NC2200
3RF2440- . AB. 3NE1802-0 5SE 1350 3NE 8017-1 -- 3NC1450 3NC2200
3RF2450- . AB. 3NE1817-0 5SE 1350 3NE 8018-1 -- 3NC1450 3NC2200
Maximum operation voltage U
e
600 V (+10%)
3RF2410- . AB. 3NE1813-0 -- 3NE 8015-1 3NC1016 3NC1420 3NC2220
3RF2420- . AB. 3NE1814-0 -- 3NE 8015-1 3NC1032 3NC1450 3NC2250
3RF2430- . AB. 3NE1803-0 -- 3NE 8003-1 3NC1032 3NC1450 3NC2280
3RF2440- . AB. 3NE1802-0 -- 3NE 8017-1 -- 3NC1450 3NC2280
3RF2450- . AB. 3NE1817-0 -- 3NE 8018-1 -- 3NC1450 3NC2280
Fused Design with Semiconductor Protection

Type Line protection fuse
LV HBC design Cylindrical design DIAZED
gG 3NA gG 3NW gG 3NW gG 3NW fast 5SB
10 x 38 mm 14 x 51 mm 22 x 58 mm
Maximum operation voltage

460 V (+10%)
3RF2410- . AB. 3NA3801
5
3NW6001-1
5
3NW6101-1
5
-- 5SB131
5

3RF2420- . AB. 3NA3805
5
3NW6005-1
5
3NW6105-1
5
3NW6205-1
5
5SB181
3RF2430- . AB. 3NA3812 -- 3NW6112-1 -- 5SB311
3RF2440- . AB. 3NA3812
5
-- 3NW6112-1
5
3NW6210-1
5
5SB321
3RF2450- . AB. 3NA3812
5
-- -- 3NW6210-1
5
5SB321
5



3
Max. allowable fuse; with smaller fuses the load reversal stability can be limited.
4
Operating voltage only up to 400V!
Subject to changes 08/2010 Page 3/7
5
These fuses have a lower rated current than the solid state contactors.
http://www.siemens.com/solid-state-switching-devices
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF24..-.AB.. Zero-Point Switching Solid State Contactors
Accessories
Function module Order No. Applicable for Versions
Converter 3RF2900-0EA18 3RF24. . - . AB4. Us = DC 24 V



Characteristic Curves

3RF2410-.

0
2
4
6
8
10
12
14
16
18
20
22
24
26
0 2 4 6 8 10 12
Ie in A
P
o
w
e
r

l
o
s
s

i
n

W
0
2
4
6
8
10
12
0 20 40 60
Ambient temperature Ta in C
I
e

i
n

A

Upper curves:
I
max
thermal limit current
Middle curves:
Rated current I
e
acc. to UL
Lower curves:
Rated current I
e

acc. to
DIN EN 60947-4-3

Continuous lines:
Stand-alone mounting
Dashed lines:
Side-by-side mounting




3RF2420-.


















0
5
10
15
20
25
0 20 40 60
Ambient temperature Ta in C
I
e

i
n

A
0
5
10
15
20
25
30
35
40
45
50
0 4 8 12 16 20 24
Ie in A
P
o
w
e
r

l
o
s
s

i
n

W
Subject to changes 08/2010 Page 4/7
http://www.siemens.com/solid-state-switching-devices
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF24..-.AB.. Zero-Point Switching Solid State Contactors
3RF2430-.


















0
5
10
15
20
25
30
35
40
0 20 40 60
Ambient temperature Ta in C
I
e

i
n

A
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
0 6 12 18 24 30 36
Ie in A
P
o
w
e
r

l
o
s
s

i
n

W
3RF2440-.
6


0
5
10
15
20
25
30
35
40
45
50
0 20 40 60
Ambient temperature Ta in C
I
e

i
n

A
0
10
20
30
40
50
60
70
80
90
100
110
0 8 16 24 32 40 48
Ie in A
P
o
w
e
r

l
o
s
s

i
n

W

Upper curves:
I
max
thermal limit current
Middle curves:
Rated current I
e
acc. to UL
Lower curves:
Rated current I
e

acc. to
DIN EN 60947-4-3

For:
Stand-alone and side-by-
side mounting






3RF2450-.
6




















0
5
10
15
20
25
30
35
40
45
50
55
60
0 20 40 60
Ambient temperature Ta in C
I
e

i
n

A
0
20
40
60
80
100
120
0 10 20 30 40 50
Ie in A
P
o
w
e
r

l
o
s
s

i
n

W
Subject to changes 08/2010 Page 5/7
http://www.siemens.com/solid-state-switching-devices

6
Identical current/temperature curves for Stand-alone and side by side mounting.
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF24..-.AB.. Zero-Point Switching Solid State Contactors


Mounting Instructions:
7


Device / Example Circuit Diagram:


Subject to changes 08/2010 Page 6/7
http://www.siemens.com/solid-state-switching-devices

7
Dimensions in mm, (in);
Stand-alone mounting, Characteristic Curves shows derating for Side-by-side mounting
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF24..-.AB.. Zero-Point Switching Solid State Contactors

Dimension Drawings
8
:



Subject to changes 08/2010 Page 7/7
8
Dimensions in mm, (in)
http://www.siemens.com/solid-state-switching-devices
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF24..-.AB.. Zero-Point Switching Solid State Contactors
Main Characteristics:
Two-phase controlled
Zero switching
LED display
Various connection technologies
Plug-in control terminal
Degree of protection IP 20
Insulated mounting foot
Standards / Approvals:
DIN EN 60947-4-3
UL 508 / CSA
1

CE
C-Tick

Ordering Key:
3RF24 10 - 1 A B 4 5
Max.
load current
Connection
technology
Switching
function
Controlled
phases
Control voltage Operating
voltage
3-phase solid
state contactor
with heat sink
10 = 10,5 A
20 = 22 A
30 = 30 A
40 = 40 A
50 = 50 A
1 = Screw connection
2 = Spring-loaded
connection
3 = Ring cable
connection M5
A = Zero-point
switching

B = two-phase 3 = 110 VAC
4 = 4 - 30 VDC
5 = 190 - 230 VAC

5 = 48 - 600 V
Not all possible versions are available ex stock!

Main Circuit:
Values for 40 C
ambient temperature!
I
AC-51

I
e
acc. to
IEC947-4-3
Ie [50C]
UL/CSA
Power loss
with I
AC-51

Min. load
current
Max. leakage
current
Type A A A W A mA
3RF2410- . AB. 10,5 7 7 23 0,1 10
3RF2420- . AB. 22 15 15 44 0,5
3RF2430- . AB. 30 22 22 61
3RF2440- . AB. 40 30 30 80
3RF2450- . AB. 50 38 38 107

Type 3RF24. . - . AB. 5
Rated operating voltage U
e
V 48 ... 600
Voltage range V 40 ... 660
Rated frequency Hz 50/60 10 %
Rated insulation voltage U
i
V 600
Rated impulse withstand voltage U
imp
kV 6
Slew rate V/s 1000
Rated impulse withstand strength Itsm I
2
t value Blocking voltage
Type A A
2
s V
3RF2410- . AB. 200 200 1200
3RF2420- . AB. 600 1800 1200
3RF2430- . AB. 1200 7200 1200
3RF2440- . AB. 1150 6600 1600
3RF2450- . AB. 1150 6600 1600

Subject to changes 08/2010 Page 1/7
1
Use overvoltage protection device; max cut-off-voltage 6.000 V; min energy handling capability 100 J
http://www.siemens.com/solid-state-switching-devices
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF24..-.AB.. Zero-Point Switching Solid State Contactors
Subject to changes 08/2010 Page 2/7
http://www.siemens.com/solid-state-switching-devices

Control Circuit A1-A2:
Type 3RF24. . - . AB3. 3RF24. . - . AB4. 3RF24. . - . AB5.
Control voltage U
s
V AC 110 DC 4 ... 30 AC 190 ... 230
Max. control voltage U
s
V 121 30 253
Typical operating current mA 15 30 15
Response voltage V 90 4 180
Drop-out voltage V < 40 <1 <40
Rated frequency
of the control supply voltage
Hz 50/60 10 % -- 50/60 10 %
Switching times ON delay ms 40 + Max. one half-wave 1 + Max. one half-wave 40 + Max. one half-wave
OFF delay ms 40 + Max. one half-wave 1 + Max. one half-wave 40 + Max. one half-wave

General Data:
Ambient temperature
During operation C -25 ... 60
During storage C -55 ... 80
Mounting altitude m 0 ... 1000; at > 1000 m, please contact our Technical Assistance
Impact resistance acc. to DIN IEC 68 g/ms 15/11
Vibration resistance g 2
Degree of protection IP20
Electromagnetic compatibility (EMC)
Interference emission
o Conducted interference voltage
IEC 60 947-4-3
Class A for industrial applications
2

Interference resistance
o Electrostatic discharge acc. to
IEC 61 000-4-2 (corresponds
to severity 3)
kV Contact discharge 4; air discharge 8; performance criterion 2
o Induced HF fields acc. to
IEC 61 000-4-6
MHz 0.15 ... 80; 140 dBV; performance criterion 1
o Burst acc. to IEC 61 000-4-4 kV 2/5.0 kHz; performance criterion 2
o Surge acc. to IEC 61 000-4-5 kV Phase-to-ground 2; phase-to-phase 1; performance criterion 2
Dielectric Strength 50/60 Hz
(Input, Output / Base)
V rms 4000



2
Attention!
This product was constructed as an EMC Class A device. The use of this product in residential applications could lead
to radio interferences. In such an application, additional filtering may be required.
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF24..-.AB.. Zero-Point Switching Solid State Contactors

Type 3RF24. . - 1. 3RF24. . - 2. 3RF24. . - 3.
Connection, main contacts Screw connection
Spring-loaded
connection
Ring cable connection
Conductor cross-section
o Solid mm
2

2 x (1.5 ... 2.5),
2 x (2.5 ... 6)
2x (0.5 ... 2.5)
o Finely stranded with end sleeve mm
2

2 x (1.5 ... 2.5),
2 x (2.5 ... 6), 1 x 10
2x (0.5 ... 1.5)
o Finely stranded w/o end sleeve mm
2
2x (0.5 ... 2.5)
o Solid or stranded AWG 2 x (14 ... 10) 2 x (18 ... 14)
Stripping length mm 10 10
Terminal screw M 4 - M 5
Nm 2 ... 2.5 - 2 ... 2.5 o Tightening torque
D 5...6 mm / PZ 2
lb.in 18 ... 22 - 18 ... 22
Cable lug DIN - - DIN 46234 5-2.5 ... 5-25
JIS - - JIS C 2805 R 2-5 14-5
Connection, control contacts
Conductor cross-section with or
without end sleeve
mm
mm
AWG
1 x (0.5 ... 2.5)
2 x (0.5 ... 1.0)
20 ... 12
0.5 ... 2.5

20 ... 12
1 x (0.5 ... 2.5)
2 x (0.5 ... 1.0)
20 ... 12
Stripping length mm 7 10 7
Terminal screw M 3 - M 3
Nm 0.5 ... 0.6 - 0.5 ... 0.6 o Tightening torque
D 3.5 / PZ 1
lb.in 4.5 ... 5.3 - 4.5 ... 5.3

Type Semiconductor protection fuse
Full-range fuse Back-up fuse
LV HBC
design
Cylindrical
design
LV HBC
design
Cylindrical design
3

gR/SITOR gR/Neozed
4
aR/SITOR aR/SITOR
3NE1 5SE1 3NE8 3NC1 0 3NC1 4 3NC2 2
10 x 38 14 x 51 22 x 58
Maximum operation voltage U
e
460 V (+10%)
3RF2410- . AB. 3NE1813-0 5SE 1310 3NE 8015-1 3NC1020 3NC1415 3NC2220
3RF2420- . AB. 3NE1814-0 5SE 1320 3NE 8015-1 3NC1032 3NC1450 3NC2263
3RF2430- . AB. 3NE1803-0 5SE 1335 3NE 8003-1 3NC1032 3NC1450 3NC2200
3RF2440- . AB. 3NE1802-0 5SE 1350 3NE 8017-1 -- 3NC1450 3NC2200
3RF2450- . AB. 3NE1817-0 5SE 1350 3NE 8018-1 -- 3NC1450 3NC2200
Maximum operation voltage U
e
600 V (+10%)
3RF2410- . AB. 3NE1813-0 -- 3NE 8015-1 3NC1016 3NC1420 3NC2220
3RF2420- . AB. 3NE1814-0 -- 3NE 8015-1 3NC1032 3NC1450 3NC2250
3RF2430- . AB. 3NE1803-0 -- 3NE 8003-1 3NC1032 3NC1450 3NC2280
3RF2440- . AB. 3NE1802-0 -- 3NE 8017-1 -- 3NC1450 3NC2280
3RF2450- . AB. 3NE1817-0 -- 3NE 8018-1 -- 3NC1450 3NC2280
Fused Design with Semiconductor Protection

Type Line protection fuse
LV HBC design Cylindrical design DIAZED
gG 3NA gG 3NW gG 3NW gG 3NW fast 5SB
10 x 38 mm 14 x 51 mm 22 x 58 mm
Maximum operation voltage

460 V (+10%)
3RF2410- . AB. 3NA3801
5
3NW6001-1
5
3NW6101-1
5
-- 5SB131
5

3RF2420- . AB. 3NA3805
5
3NW6005-1
5
3NW6105-1
5
3NW6205-1
5
5SB181
3RF2430- . AB. 3NA3812 -- 3NW6112-1 -- 5SB311
3RF2440- . AB. 3NA3812
5
-- 3NW6112-1
5
3NW6210-1
5
5SB321
3RF2450- . AB. 3NA3812
5
-- -- 3NW6210-1
5
5SB321
5



3
Max. allowable fuse; with smaller fuses the load reversal stability can be limited.
4
Operating voltage only up to 400V!
Subject to changes 08/2010 Page 3/7
5
These fuses have a lower rated current than the solid state contactors.
http://www.siemens.com/solid-state-switching-devices
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF24..-.AB.. Zero-Point Switching Solid State Contactors
Accessories
Function module Order No. Applicable for Versions
Converter 3RF2900-0EA18 3RF24. . - . AB4. Us = DC 24 V



Characteristic Curves

3RF2410-.

0
2
4
6
8
10
12
14
16
18
20
22
24
26
0 2 4 6 8 10 12
Ie in A
P
o
w
e
r

l
o
s
s

i
n

W
0
2
4
6
8
10
12
0 20 40 60
Ambient temperature Ta in C
I
e

i
n

A

Upper curves:
I
max
thermal limit current
Middle curves:
Rated current I
e
acc. to UL
Lower curves:
Rated current I
e

acc. to
DIN EN 60947-4-3

Continuous lines:
Stand-alone mounting
Dashed lines:
Side-by-side mounting




3RF2420-.


















0
5
10
15
20
25
0 20 40 60
Ambient temperature Ta in C
I
e

i
n

A
0
5
10
15
20
25
30
35
40
45
50
0 4 8 12 16 20 24
Ie in A
P
o
w
e
r

l
o
s
s

i
n

W
Subject to changes 08/2010 Page 4/7
http://www.siemens.com/solid-state-switching-devices
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF24..-.AB.. Zero-Point Switching Solid State Contactors
3RF2430-.


















0
5
10
15
20
25
30
35
40
0 20 40 60
Ambient temperature Ta in C
I
e

i
n

A
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
0 6 12 18 24 30 36
Ie in A
P
o
w
e
r

l
o
s
s

i
n

W
3RF2440-.
6


0
5
10
15
20
25
30
35
40
45
50
0 20 40 60
Ambient temperature Ta in C
I
e

i
n

A
0
10
20
30
40
50
60
70
80
90
100
110
0 8 16 24 32 40 48
Ie in A
P
o
w
e
r

l
o
s
s

i
n

W

Upper curves:
I
max
thermal limit current
Middle curves:
Rated current I
e
acc. to UL
Lower curves:
Rated current I
e

acc. to
DIN EN 60947-4-3

For:
Stand-alone and side-by-
side mounting






3RF2450-.
6




















0
5
10
15
20
25
30
35
40
45
50
55
60
0 20 40 60
Ambient temperature Ta in C
I
e

i
n

A
0
20
40
60
80
100
120
0 10 20 30 40 50
Ie in A
P
o
w
e
r

l
o
s
s

i
n

W
Subject to changes 08/2010 Page 5/7
http://www.siemens.com/solid-state-switching-devices

6
Identical current/temperature curves for Stand-alone and side by side mounting.
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF24..-.AB.. Zero-Point Switching Solid State Contactors


Mounting Instructions:
7


Device / Example Circuit Diagram:


Subject to changes 08/2010 Page 6/7
http://www.siemens.com/solid-state-switching-devices

7
Dimensions in mm, (in);
Stand-alone mounting, Characteristic Curves shows derating for Side-by-side mounting
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF24..-.AB.. Zero-Point Switching Solid State Contactors

Dimension Drawings
8
:



Subject to changes 08/2010 Page 7/7
8
Dimensions in mm, (in)
http://www.siemens.com/solid-state-switching-devices
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF24..-.AB.. Zero-Point Switching Solid State Contactors
Main Characteristics:
Two-phase controlled
Zero switching
LED display
Various connection technologies
Plug-in control terminal
Degree of protection IP 20
Insulated mounting foot
Standards / Approvals:
DIN EN 60947-4-3
UL 508 / CSA
1

CE
C-Tick

Ordering Key:
3RF24 10 - 1 A B 4 5
Max.
load current
Connection
technology
Switching
function
Controlled
phases
Control voltage Operating
voltage
3-phase solid
state contactor
with heat sink
10 = 10,5 A
20 = 22 A
30 = 30 A
40 = 40 A
50 = 50 A
1 = Screw connection
2 = Spring-loaded
connection
3 = Ring cable
connection M5
A = Zero-point
switching

B = two-phase 3 = 110 VAC
4 = 4 - 30 VDC
5 = 190 - 230 VAC

5 = 48 - 600 V
Not all possible versions are available ex stock!

Main Circuit:
Values for 40 C
ambient temperature!
I
AC-51

I
e
acc. to
IEC947-4-3
Ie [50C]
UL/CSA
Power loss
with I
AC-51

Min. load
current
Max. leakage
current
Type A A A W A mA
3RF2410- . AB. 10,5 7 7 23 0,1 10
3RF2420- . AB. 22 15 15 44 0,5
3RF2430- . AB. 30 22 22 61
3RF2440- . AB. 40 30 30 80
3RF2450- . AB. 50 38 38 107

Type 3RF24. . - . AB. 5
Rated operating voltage U
e
V 48 ... 600
Voltage range V 40 ... 660
Rated frequency Hz 50/60 10 %
Rated insulation voltage U
i
V 600
Rated impulse withstand voltage U
imp
kV 6
Slew rate V/s 1000
Rated impulse withstand strength Itsm I
2
t value Blocking voltage
Type A A
2
s V
3RF2410- . AB. 200 200 1200
3RF2420- . AB. 600 1800 1200
3RF2430- . AB. 1200 7200 1200
3RF2440- . AB. 1150 6600 1600
3RF2450- . AB. 1150 6600 1600

Subject to changes 08/2010 Page 1/7
1
Use overvoltage protection device; max cut-off-voltage 6.000 V; min energy handling capability 100 J
http://www.siemens.com/solid-state-switching-devices
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF24..-.AB.. Zero-Point Switching Solid State Contactors
Subject to changes 08/2010 Page 2/7
http://www.siemens.com/solid-state-switching-devices

Control Circuit A1-A2:
Type 3RF24. . - . AB3. 3RF24. . - . AB4. 3RF24. . - . AB5.
Control voltage U
s
V AC 110 DC 4 ... 30 AC 190 ... 230
Max. control voltage U
s
V 121 30 253
Typical operating current mA 15 30 15
Response voltage V 90 4 180
Drop-out voltage V < 40 <1 <40
Rated frequency
of the control supply voltage
Hz 50/60 10 % -- 50/60 10 %
Switching times ON delay ms 40 + Max. one half-wave 1 + Max. one half-wave 40 + Max. one half-wave
OFF delay ms 40 + Max. one half-wave 1 + Max. one half-wave 40 + Max. one half-wave

General Data:
Ambient temperature
During operation C -25 ... 60
During storage C -55 ... 80
Mounting altitude m 0 ... 1000; at > 1000 m, please contact our Technical Assistance
Impact resistance acc. to DIN IEC 68 g/ms 15/11
Vibration resistance g 2
Degree of protection IP20
Electromagnetic compatibility (EMC)
Interference emission
o Conducted interference voltage
IEC 60 947-4-3
Class A for industrial applications
2

Interference resistance
o Electrostatic discharge acc. to
IEC 61 000-4-2 (corresponds
to severity 3)
kV Contact discharge 4; air discharge 8; performance criterion 2
o Induced HF fields acc. to
IEC 61 000-4-6
MHz 0.15 ... 80; 140 dBV; performance criterion 1
o Burst acc. to IEC 61 000-4-4 kV 2/5.0 kHz; performance criterion 2
o Surge acc. to IEC 61 000-4-5 kV Phase-to-ground 2; phase-to-phase 1; performance criterion 2
Dielectric Strength 50/60 Hz
(Input, Output / Base)
V rms 4000



2
Attention!
This product was constructed as an EMC Class A device. The use of this product in residential applications could lead
to radio interferences. In such an application, additional filtering may be required.
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF24..-.AB.. Zero-Point Switching Solid State Contactors

Type 3RF24. . - 1. 3RF24. . - 2. 3RF24. . - 3.
Connection, main contacts Screw connection
Spring-loaded
connection
Ring cable connection
Conductor cross-section
o Solid mm
2

2 x (1.5 ... 2.5),
2 x (2.5 ... 6)
2x (0.5 ... 2.5)
o Finely stranded with end sleeve mm
2

2 x (1.5 ... 2.5),
2 x (2.5 ... 6), 1 x 10
2x (0.5 ... 1.5)
o Finely stranded w/o end sleeve mm
2
2x (0.5 ... 2.5)
o Solid or stranded AWG 2 x (14 ... 10) 2 x (18 ... 14)
Stripping length mm 10 10
Terminal screw M 4 - M 5
Nm 2 ... 2.5 - 2 ... 2.5 o Tightening torque
D 5...6 mm / PZ 2
lb.in 18 ... 22 - 18 ... 22
Cable lug DIN - - DIN 46234 5-2.5 ... 5-25
JIS - - JIS C 2805 R 2-5 14-5
Connection, control contacts
Conductor cross-section with or
without end sleeve
mm
mm
AWG
1 x (0.5 ... 2.5)
2 x (0.5 ... 1.0)
20 ... 12
0.5 ... 2.5

20 ... 12
1 x (0.5 ... 2.5)
2 x (0.5 ... 1.0)
20 ... 12
Stripping length mm 7 10 7
Terminal screw M 3 - M 3
Nm 0.5 ... 0.6 - 0.5 ... 0.6 o Tightening torque
D 3.5 / PZ 1
lb.in 4.5 ... 5.3 - 4.5 ... 5.3

Type Semiconductor protection fuse
Full-range fuse Back-up fuse
LV HBC
design
Cylindrical
design
LV HBC
design
Cylindrical design
3

gR/SITOR gR/Neozed
4
aR/SITOR aR/SITOR
3NE1 5SE1 3NE8 3NC1 0 3NC1 4 3NC2 2
10 x 38 14 x 51 22 x 58
Maximum operation voltage U
e
460 V (+10%)
3RF2410- . AB. 3NE1813-0 5SE 1310 3NE 8015-1 3NC1020 3NC1415 3NC2220
3RF2420- . AB. 3NE1814-0 5SE 1320 3NE 8015-1 3NC1032 3NC1450 3NC2263
3RF2430- . AB. 3NE1803-0 5SE 1335 3NE 8003-1 3NC1032 3NC1450 3NC2200
3RF2440- . AB. 3NE1802-0 5SE 1350 3NE 8017-1 -- 3NC1450 3NC2200
3RF2450- . AB. 3NE1817-0 5SE 1350 3NE 8018-1 -- 3NC1450 3NC2200
Maximum operation voltage U
e
600 V (+10%)
3RF2410- . AB. 3NE1813-0 -- 3NE 8015-1 3NC1016 3NC1420 3NC2220
3RF2420- . AB. 3NE1814-0 -- 3NE 8015-1 3NC1032 3NC1450 3NC2250
3RF2430- . AB. 3NE1803-0 -- 3NE 8003-1 3NC1032 3NC1450 3NC2280
3RF2440- . AB. 3NE1802-0 -- 3NE 8017-1 -- 3NC1450 3NC2280
3RF2450- . AB. 3NE1817-0 -- 3NE 8018-1 -- 3NC1450 3NC2280
Fused Design with Semiconductor Protection

Type Line protection fuse
LV HBC design Cylindrical design DIAZED
gG 3NA gG 3NW gG 3NW gG 3NW fast 5SB
10 x 38 mm 14 x 51 mm 22 x 58 mm
Maximum operation voltage

460 V (+10%)
3RF2410- . AB. 3NA3801
5
3NW6001-1
5
3NW6101-1
5
-- 5SB131
5

3RF2420- . AB. 3NA3805
5
3NW6005-1
5
3NW6105-1
5
3NW6205-1
5
5SB181
3RF2430- . AB. 3NA3812 -- 3NW6112-1 -- 5SB311
3RF2440- . AB. 3NA3812
5
-- 3NW6112-1
5
3NW6210-1
5
5SB321
3RF2450- . AB. 3NA3812
5
-- -- 3NW6210-1
5
5SB321
5



3
Max. allowable fuse; with smaller fuses the load reversal stability can be limited.
4
Operating voltage only up to 400V!
Subject to changes 08/2010 Page 3/7
5
These fuses have a lower rated current than the solid state contactors.
http://www.siemens.com/solid-state-switching-devices
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF24..-.AB.. Zero-Point Switching Solid State Contactors
Accessories
Function module Order No. Applicable for Versions
Converter 3RF2900-0EA18 3RF24. . - . AB4. Us = DC 24 V



Characteristic Curves

3RF2410-.

0
2
4
6
8
10
12
14
16
18
20
22
24
26
0 2 4 6 8 10 12
Ie in A
P
o
w
e
r

l
o
s
s

i
n

W
0
2
4
6
8
10
12
0 20 40 60
Ambient temperature Ta in C
I
e

i
n

A

Upper curves:
I
max
thermal limit current
Middle curves:
Rated current I
e
acc. to UL
Lower curves:
Rated current I
e

acc. to
DIN EN 60947-4-3

Continuous lines:
Stand-alone mounting
Dashed lines:
Side-by-side mounting




3RF2420-.


















0
5
10
15
20
25
0 20 40 60
Ambient temperature Ta in C
I
e

i
n

A
0
5
10
15
20
25
30
35
40
45
50
0 4 8 12 16 20 24
Ie in A
P
o
w
e
r

l
o
s
s

i
n

W
Subject to changes 08/2010 Page 4/7
http://www.siemens.com/solid-state-switching-devices
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF24..-.AB.. Zero-Point Switching Solid State Contactors
3RF2430-.


















0
5
10
15
20
25
30
35
40
0 20 40 60
Ambient temperature Ta in C
I
e

i
n

A
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
0 6 12 18 24 30 36
Ie in A
P
o
w
e
r

l
o
s
s

i
n

W
3RF2440-.
6


0
5
10
15
20
25
30
35
40
45
50
0 20 40 60
Ambient temperature Ta in C
I
e

i
n

A
0
10
20
30
40
50
60
70
80
90
100
110
0 8 16 24 32 40 48
Ie in A
P
o
w
e
r

l
o
s
s

i
n

W

Upper curves:
I
max
thermal limit current
Middle curves:
Rated current I
e
acc. to UL
Lower curves:
Rated current I
e

acc. to
DIN EN 60947-4-3

For:
Stand-alone and side-by-
side mounting






3RF2450-.
6




















0
5
10
15
20
25
30
35
40
45
50
55
60
0 20 40 60
Ambient temperature Ta in C
I
e

i
n

A
0
20
40
60
80
100
120
0 10 20 30 40 50
Ie in A
P
o
w
e
r

l
o
s
s

i
n

W
Subject to changes 08/2010 Page 5/7
http://www.siemens.com/solid-state-switching-devices

6
Identical current/temperature curves for Stand-alone and side by side mounting.
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF24..-.AB.. Zero-Point Switching Solid State Contactors


Mounting Instructions:
7


Device / Example Circuit Diagram:


Subject to changes 08/2010 Page 6/7
http://www.siemens.com/solid-state-switching-devices

7
Dimensions in mm, (in);
Stand-alone mounting, Characteristic Curves shows derating for Side-by-side mounting
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF24..-.AB.. Zero-Point Switching Solid State Contactors

Dimension Drawings
8
:



Subject to changes 08/2010 Page 7/7
8
Dimensions in mm, (in)
http://www.siemens.com/solid-state-switching-devices
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF24..-.AB.. Zero-Point Switching Solid State Contactors
Main Characteristics:
Two-phase controlled
Zero switching
LED display
Various connection technologies
Plug-in control terminal
Degree of protection IP 20
Insulated mounting foot
Standards / Approvals:
DIN EN 60947-4-3
UL 508 / CSA
1

CE
C-Tick

Ordering Key:
3RF24 10 - 1 A B 4 5
Max.
load current
Connection
technology
Switching
function
Controlled
phases
Control voltage Operating
voltage
3-phase solid
state contactor
with heat sink
10 = 10,5 A
20 = 22 A
30 = 30 A
40 = 40 A
50 = 50 A
1 = Screw connection
2 = Spring-loaded
connection
3 = Ring cable
connection M5
A = Zero-point
switching

B = two-phase 3 = 110 VAC
4 = 4 - 30 VDC
5 = 190 - 230 VAC

5 = 48 - 600 V
Not all possible versions are available ex stock!

Main Circuit:
Values for 40 C
ambient temperature!
I
AC-51

I
e
acc. to
IEC947-4-3
Ie [50C]
UL/CSA
Power loss
with I
AC-51

Min. load
current
Max. leakage
current
Type A A A W A mA
3RF2410- . AB. 10,5 7 7 23 0,1 10
3RF2420- . AB. 22 15 15 44 0,5
3RF2430- . AB. 30 22 22 61
3RF2440- . AB. 40 30 30 80
3RF2450- . AB. 50 38 38 107

Type 3RF24. . - . AB. 5
Rated operating voltage U
e
V 48 ... 600
Voltage range V 40 ... 660
Rated frequency Hz 50/60 10 %
Rated insulation voltage U
i
V 600
Rated impulse withstand voltage U
imp
kV 6
Slew rate V/s 1000
Rated impulse withstand strength Itsm I
2
t value Blocking voltage
Type A A
2
s V
3RF2410- . AB. 200 200 1200
3RF2420- . AB. 600 1800 1200
3RF2430- . AB. 1200 7200 1200
3RF2440- . AB. 1150 6600 1600
3RF2450- . AB. 1150 6600 1600

Subject to changes 08/2010 Page 1/7
1
Use overvoltage protection device; max cut-off-voltage 6.000 V; min energy handling capability 100 J
http://www.siemens.com/solid-state-switching-devices
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF24..-.AB.. Zero-Point Switching Solid State Contactors
Subject to changes 08/2010 Page 2/7
http://www.siemens.com/solid-state-switching-devices

Control Circuit A1-A2:
Type 3RF24. . - . AB3. 3RF24. . - . AB4. 3RF24. . - . AB5.
Control voltage U
s
V AC 110 DC 4 ... 30 AC 190 ... 230
Max. control voltage U
s
V 121 30 253
Typical operating current mA 15 30 15
Response voltage V 90 4 180
Drop-out voltage V < 40 <1 <40
Rated frequency
of the control supply voltage
Hz 50/60 10 % -- 50/60 10 %
Switching times ON delay ms 40 + Max. one half-wave 1 + Max. one half-wave 40 + Max. one half-wave
OFF delay ms 40 + Max. one half-wave 1 + Max. one half-wave 40 + Max. one half-wave

General Data:
Ambient temperature
During operation C -25 ... 60
During storage C -55 ... 80
Mounting altitude m 0 ... 1000; at > 1000 m, please contact our Technical Assistance
Impact resistance acc. to DIN IEC 68 g/ms 15/11
Vibration resistance g 2
Degree of protection IP20
Electromagnetic compatibility (EMC)
Interference emission
o Conducted interference voltage
IEC 60 947-4-3
Class A for industrial applications
2

Interference resistance
o Electrostatic discharge acc. to
IEC 61 000-4-2 (corresponds
to severity 3)
kV Contact discharge 4; air discharge 8; performance criterion 2
o Induced HF fields acc. to
IEC 61 000-4-6
MHz 0.15 ... 80; 140 dBV; performance criterion 1
o Burst acc. to IEC 61 000-4-4 kV 2/5.0 kHz; performance criterion 2
o Surge acc. to IEC 61 000-4-5 kV Phase-to-ground 2; phase-to-phase 1; performance criterion 2
Dielectric Strength 50/60 Hz
(Input, Output / Base)
V rms 4000



2
Attention!
This product was constructed as an EMC Class A device. The use of this product in residential applications could lead
to radio interferences. In such an application, additional filtering may be required.
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF24..-.AB.. Zero-Point Switching Solid State Contactors

Type 3RF24. . - 1. 3RF24. . - 2. 3RF24. . - 3.
Connection, main contacts Screw connection
Spring-loaded
connection
Ring cable connection
Conductor cross-section
o Solid mm
2

2 x (1.5 ... 2.5),
2 x (2.5 ... 6)
2x (0.5 ... 2.5)
o Finely stranded with end sleeve mm
2

2 x (1.5 ... 2.5),
2 x (2.5 ... 6), 1 x 10
2x (0.5 ... 1.5)
o Finely stranded w/o end sleeve mm
2
2x (0.5 ... 2.5)
o Solid or stranded AWG 2 x (14 ... 10) 2 x (18 ... 14)
Stripping length mm 10 10
Terminal screw M 4 - M 5
Nm 2 ... 2.5 - 2 ... 2.5 o Tightening torque
D 5...6 mm / PZ 2
lb.in 18 ... 22 - 18 ... 22
Cable lug DIN - - DIN 46234 5-2.5 ... 5-25
JIS - - JIS C 2805 R 2-5 14-5
Connection, control contacts
Conductor cross-section with or
without end sleeve
mm
mm
AWG
1 x (0.5 ... 2.5)
2 x (0.5 ... 1.0)
20 ... 12
0.5 ... 2.5

20 ... 12
1 x (0.5 ... 2.5)
2 x (0.5 ... 1.0)
20 ... 12
Stripping length mm 7 10 7
Terminal screw M 3 - M 3
Nm 0.5 ... 0.6 - 0.5 ... 0.6 o Tightening torque
D 3.5 / PZ 1
lb.in 4.5 ... 5.3 - 4.5 ... 5.3

Type Semiconductor protection fuse
Full-range fuse Back-up fuse
LV HBC
design
Cylindrical
design
LV HBC
design
Cylindrical design
3

gR/SITOR gR/Neozed
4
aR/SITOR aR/SITOR
3NE1 5SE1 3NE8 3NC1 0 3NC1 4 3NC2 2
10 x 38 14 x 51 22 x 58
Maximum operation voltage U
e
460 V (+10%)
3RF2410- . AB. 3NE1813-0 5SE 1310 3NE 8015-1 3NC1020 3NC1415 3NC2220
3RF2420- . AB. 3NE1814-0 5SE 1320 3NE 8015-1 3NC1032 3NC1450 3NC2263
3RF2430- . AB. 3NE1803-0 5SE 1335 3NE 8003-1 3NC1032 3NC1450 3NC2200
3RF2440- . AB. 3NE1802-0 5SE 1350 3NE 8017-1 -- 3NC1450 3NC2200
3RF2450- . AB. 3NE1817-0 5SE 1350 3NE 8018-1 -- 3NC1450 3NC2200
Maximum operation voltage U
e
600 V (+10%)
3RF2410- . AB. 3NE1813-0 -- 3NE 8015-1 3NC1016 3NC1420 3NC2220
3RF2420- . AB. 3NE1814-0 -- 3NE 8015-1 3NC1032 3NC1450 3NC2250
3RF2430- . AB. 3NE1803-0 -- 3NE 8003-1 3NC1032 3NC1450 3NC2280
3RF2440- . AB. 3NE1802-0 -- 3NE 8017-1 -- 3NC1450 3NC2280
3RF2450- . AB. 3NE1817-0 -- 3NE 8018-1 -- 3NC1450 3NC2280
Fused Design with Semiconductor Protection

Type Line protection fuse
LV HBC design Cylindrical design DIAZED
gG 3NA gG 3NW gG 3NW gG 3NW fast 5SB
10 x 38 mm 14 x 51 mm 22 x 58 mm
Maximum operation voltage

460 V (+10%)
3RF2410- . AB. 3NA3801
5
3NW6001-1
5
3NW6101-1
5
-- 5SB131
5

3RF2420- . AB. 3NA3805
5
3NW6005-1
5
3NW6105-1
5
3NW6205-1
5
5SB181
3RF2430- . AB. 3NA3812 -- 3NW6112-1 -- 5SB311
3RF2440- . AB. 3NA3812
5
-- 3NW6112-1
5
3NW6210-1
5
5SB321
3RF2450- . AB. 3NA3812
5
-- -- 3NW6210-1
5
5SB321
5



3
Max. allowable fuse; with smaller fuses the load reversal stability can be limited.
4
Operating voltage only up to 400V!
Subject to changes 08/2010 Page 3/7
5
These fuses have a lower rated current than the solid state contactors.
http://www.siemens.com/solid-state-switching-devices
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF24..-.AB.. Zero-Point Switching Solid State Contactors
Accessories
Function module Order No. Applicable for Versions
Converter 3RF2900-0EA18 3RF24. . - . AB4. Us = DC 24 V



Characteristic Curves

3RF2410-.

0
2
4
6
8
10
12
14
16
18
20
22
24
26
0 2 4 6 8 10 12
Ie in A
P
o
w
e
r

l
o
s
s

i
n

W
0
2
4
6
8
10
12
0 20 40 60
Ambient temperature Ta in C
I
e

i
n

A

Upper curves:
I
max
thermal limit current
Middle curves:
Rated current I
e
acc. to UL
Lower curves:
Rated current I
e

acc. to
DIN EN 60947-4-3

Continuous lines:
Stand-alone mounting
Dashed lines:
Side-by-side mounting




3RF2420-.


















0
5
10
15
20
25
0 20 40 60
Ambient temperature Ta in C
I
e

i
n

A
0
5
10
15
20
25
30
35
40
45
50
0 4 8 12 16 20 24
Ie in A
P
o
w
e
r

l
o
s
s

i
n

W
Subject to changes 08/2010 Page 4/7
http://www.siemens.com/solid-state-switching-devices
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF24..-.AB.. Zero-Point Switching Solid State Contactors
3RF2430-.


















0
5
10
15
20
25
30
35
40
0 20 40 60
Ambient temperature Ta in C
I
e

i
n

A
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
0 6 12 18 24 30 36
Ie in A
P
o
w
e
r

l
o
s
s

i
n

W
3RF2440-.
6


0
5
10
15
20
25
30
35
40
45
50
0 20 40 60
Ambient temperature Ta in C
I
e

i
n

A
0
10
20
30
40
50
60
70
80
90
100
110
0 8 16 24 32 40 48
Ie in A
P
o
w
e
r

l
o
s
s

i
n

W

Upper curves:
I
max
thermal limit current
Middle curves:
Rated current I
e
acc. to UL
Lower curves:
Rated current I
e

acc. to
DIN EN 60947-4-3

For:
Stand-alone and side-by-
side mounting






3RF2450-.
6




















0
5
10
15
20
25
30
35
40
45
50
55
60
0 20 40 60
Ambient temperature Ta in C
I
e

i
n

A
0
20
40
60
80
100
120
0 10 20 30 40 50
Ie in A
P
o
w
e
r

l
o
s
s

i
n

W
Subject to changes 08/2010 Page 5/7
http://www.siemens.com/solid-state-switching-devices

6
Identical current/temperature curves for Stand-alone and side by side mounting.
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF24..-.AB.. Zero-Point Switching Solid State Contactors


Mounting Instructions:
7


Device / Example Circuit Diagram:


Subject to changes 08/2010 Page 6/7
http://www.siemens.com/solid-state-switching-devices

7
Dimensions in mm, (in);
Stand-alone mounting, Characteristic Curves shows derating for Side-by-side mounting
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF24..-.AB.. Zero-Point Switching Solid State Contactors

Dimension Drawings
8
:



Subject to changes 08/2010 Page 7/7
8
Dimensions in mm, (in)
http://www.siemens.com/solid-state-switching-devices
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF24..-.AC.. Zero-Point Switching Solid State Contactors

Subject to changes 08/2010 Page 1/7
Main Characteristics:
Three-phase controlled
Zero switching
LED display
Various connection technologies
Plug-in control terminal
Degree of protection IP 20
Insulated mounting foot

Standards / Approvals:
DIN EN 60947-4-3
UL 508 / CSA
1

CE
C-Tick

Ordering Key:
3RF24 10 - 1 A C 4 5
Max.
load current
Connection
technology
Switching
function
Controlled
phases
Control voltage Operating
voltage
3-phase solid
state contactor
with heat sink
10 = 10,5 A
20 = 22 A
30 = 30 A
40 = 40 A
50 = 50 A
1 = Screw connection
2 = Spring-loaded
connection
3 = Ring cable
connection M5
A = Zero-point
switching

C = three-phase 3 = 110 VAC
4 = 4 - 30 VDC
5 = 190 - 230 VAC

5 = 48 - 600 V
Not all possible versions are available ex stock!

Main Circuit:
Values for 40 C
ambient temperature!
I
AC-51

I
e
acc. to
IEC947-4-3
Ie [50C]
UL/CSA
Power loss
with I
AC-51

Min. load
current
Max. leakage
current
Type A A A W A mA
3RF2410- . AC. 10,5 7 7 31 0,1 10
3RF2420- . AC. 22 15 15 66 0,5
3RF2430- . AC. 30 22 22 91
3RF2440- . AC. 40 30 30 121
3RF2450- . AC. 50 38 38 160

Type 3RF24. . - . AC. 5
Rated operating voltage U
e
V 48 ... 600
Voltage range V 40 ... 660
Rated frequency Hz 50/60 10 %
Rated insulation voltage U
i
V 600
Rated impulse withstand voltage U
imp
kV 6
Slew rate V/s 1000
Rated impulse withstand strength Itsm I
2
t value Blocking voltage
Type A A
2
s V
3RF2410- . AC. 300 450 1200
3RF2420- . AC. 600 1800 1200
3RF2430- . AC. 1200 7200 1200
3RF2440- . AC. 1150 6600 1600
3RF2450- . AC. 1150 6600 1600

1
Use overvoltage protection device; max cut-off-voltage 6.000 V; min energy handling capability 100 J
http://www.siemens.com/solid-state-switching-devices
VOLTAR
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF24..-.AC.. Zero-Point Switching Solid State Contactors

Subject to changes 08/2010 Page 2/7
http://www.siemens.com/solid-state-switching-devices

Control Circuit A1-A2:
Type 3RF24. . - . AC3. 3RF24. . - . AC4. 3RF24. . - . AC5.
Control voltage U
s
V AC 110 DC 4 ... 30 AC 190 ... 230
Max. control voltage U
s
V 121 30 253
Typical operating current mA 15 30 15
Response voltage V 90 4 180
Drop-out voltage V <40 <1 <40
Rated frequency
of the control supply voltage
Hz 50/60 10 % -- 50/60 10 %
Switching times ON delay ms 40 + Max. one half-wave 1 + Max. one half-wave 40 + Max. one half-wave
OFF delay ms 40 + Max. one half-wave 1 + Max. one half-wave 40 + Max. one half-wave

General Data:
Ambient temperature
During operation C -25 ... 60
During storage C -55 ... 80
Mounting altitude m 0 ... 1000; at > 1000 m, please contact our Technical Assistance
Impact resistance acc. to DIN IEC 68 g/ms 15/11
Vibration resistance g 2
Degree of protection IP20
Electromagnetic compatibility (EMC)
Interference emission
o Conducted interference voltage
IEC 60 947-4-3
Class A for industrial applications
2

Interference resistance
o Electrostatic discharge acc. to
IEC 61 000-4-2 (corresponds
to severity 3)
kV Contact discharge 4; air discharge 8; performance criterion 2
o Induced HF fields acc. to
IEC 61 000-4-6
MHz 0.15 ... 80; 140 dBV; performance criterion 1
o Burst acc. to IEC 61 000-4-4 kV 2/5.0 kHz; performance criterion 2
o Surge acc. to IEC 61 000-4-5 kV Phase-to-ground 2; phase-to-phase 1; performance criterion 2
Dielectric Strength 50/60 Hz
(Input, Output / Base)
V rms 4000


2
Attention!
This product was constructed as an EMC Class A device. The use of this product in residential applications could lead
to radio interferences. In such an application, additional filtering may be required.
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF24..-.AC.. Zero-Point Switching Solid State Contactors

Subject to changes 08/2010 Page 3/7

Type 3RF24. . - 1. 3RF24. . - 2. 3RF24. . - 3.
Connection, main contacts Screw connection
Spring-loaded
connection
Ring cable connection
Conductor cross-section
o Solid mm
2

2 x (1.5 ... 2.5),
2 x (2.5 ... 6)
2x (0.5 ... 2.5)
o Finely stranded with end sleeve mm
2

2 x (1.5 ... 2.5),
2 x (2.5 ... 6), 1 x 10
2x (0.5 ... 1.5)
o Finely stranded w/o end sleeve mm
2
2x (0.5 ... 2.5)
o Solid or stranded AWG 2 x (14 ... 10) 2 x (18 ... 14)
Stripping length mm 10 10
Terminal screw M 4 - M 5
Nm 2 ... 2.5 - 2 ... 2.5 o Tightening torque
D 5...6 mm / PZ 2
lb.in 18 ... 22 - 18 ... 22
Cable lug DIN - - DIN 46234 5-2.5 ... 5-25
JIS - - JIS C 2805 R 2-5 14-5
Connection, control contacts
Conductor cross-section with or
without end sleeve
mm
mm
AWG
1 x (0.5 ... 2.5)
2 x (0.5 ... 1.0)
20 ... 12
0.5 ... 2.5

20 ... 12
1 x (0.5 ... 2.5)
2 x (0.5 ... 1.0)
20 ... 12
Stripping length mm 7 10 7
Terminal screw M 3 - M 3
Nm 0.5 ... 0.6 - 0.5 ... 0.6 o Tightening torque
D 3.5 / PZ 1
lb.in 4.5 ... 5.3 - 4.5 ... 5.3

Type Semiconductor protection fuse
Full-range fuse Partial-range fuse
LV HBC design Cylindrical design LV HBC design Cylindrical design
3

gR/SITOR gR/Neozed
4
aR/SITOR aR/SITOR
3NE1 5SE1 3NE8 3NC1 0 3NC1 4 3NC2 2
10 x 38 14 x 51 22 x 58
Maximum operation voltage U
e
460 V (+10%)
3RF2410- . AC. 3NE1813-0 5SE 1310 3NE 8015-1 3NC1032 3NC1430 3NC2232
3RF2420- . AC. 3NE1814-0 5SE 1320 3NE 8015-1 3NC1032 3NC1450 3NC2263
3RF2430- . AC. 3NE1803-0 5SE 1335 3NE 8003-1 3NC1032 3NC1450 3NC2200
3RF2440- . AC. 3NE1802-0 5SE 1350 3NE 8017-1 -- 3NC1450 3NC2200
3RF2450- . AC. 3NE1817-0 5SE 1350 3NE 8018-1 -- 3NC1450 3NC2200
Maximum operation voltage U
e
600 V (+10%)
3RF2410- . AC. 3NE1813-0 -- 3NE 8015-1 3NC1025 3NC1430 3NC2220
3RF2420- . AC. 3NE1814-0 -- 3NE 8015-1 3NC1032 3NC1450 3NC2250
3RF2430- . AC. 3NE1803-0 -- 3NE 8003-1 3NC1032 3NC1450 3NC2280
3RF2440- . AC. 3NE1802-0 -- 3NE 8017-1 -- 3NC1450 3NC2280
3RF2450- . AC. 3NE1817-0 -- 3NE 8018-1 -- 3NC1450 3NC2280
Fused Design with Semiconductor Protection

Type Line protection fuse
LV HBC design Cylindrical design DIAZED
gG gG gG gG fast
3NA 3NW 3NW 3NW 5SB
10 x 38 mm 14 x 51 mm 22 x 58 mm
Maximum operation voltage

460 V (+10%)
3RF2410- . AC. 3NA3803 3NW6001-1
5
3NW6101-1
5
-- 5SB161
3RF2420- . AC. 3NA3805
5
3NW6005-1
5
3NW6105-1
5
3NW6205-1
5
5SB181
3RF2430- . AC. 3NA3812 -- 3NW6112-1 -- 5SB311
3RF2440- . AC. 3NA3812
5
-- 3NW6112-1
5
3NW6210-1
5
5SB321
3RF2450- . AC. 3NA3812
5
-- -- 3NW6210-1
5
5SB321
5



3
Max. allowable fuse; with smaller fuses the load reversal stability can be limited.
4
Operating voltage only up to 400V!
5
These fuses have a lower rated current than the solid state contactors.
http://www.siemens.com/solid-state-switching-devices
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF24..-.AC.. Zero-Point Switching Solid State Contactors

Subject to changes 08/2010 Page 4/7

Accessories
Function module Order No. Applicable for Versions
Converter 3RF2900-0EA18 3RF24. . - . AC4. Us = DC 24 V


Characteristic Curves

3RF2410-.

Upper curves:
0
2
4
6
8
10
12
0 10 20 30 40 50 60
Ambient temperature Ta in C
I
e

i
n

A
0
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
0 2 4 6 8 10 1
Ie in A
P
o
w
e
r

l
o
s
s

i
n

W
2
I
max
thermal limit current
Middle curves:
Rated current I
e
acc. to UL
Lower curves:
Rated current Ie
acc. to
DIN EN 60947-4-3

Continuous lines:
Stand-alone mounting
Dashed lines:
Side-by-side mounting







3RF2420-.



















0
5
10
15
20
25
0 10 20 30 40 50 60
Ambient temperature Ta in C
I
e

i
n

A
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
0 4 8 12 16 20 24
Ie in A
P
o
w
e
r

l
o
s
s

i
n

W
http://www.siemens.com/solid-state-switching-devices
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF24..-.AC.. Zero-Point Switching Solid State Contactors

Subject to changes 08/2010 Page 5/7
3RF2430-.
6

0
5
10
15
20
25
30
35
40
0 10 20 30 40 50 60
Ambient temperature Ta in C
I
e

i
n

A
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
85
90
95
100
105
110
115
0 6 12 18 24 30 36
Ie in A
P
o
w
e
r

l
o
s
s

i
n

W
Upper curves:
I
max
thermal limit current
Middle curves:
Rated current I
e
acc. to UL
Lower curves:
Rated current Ie
acc. to
DIN EN 60947-4-3

Stand-alone and side-by-
side mounting







3RF2440-.
6


















0
5
10
15
20
25
30
35
40
45
50
0 10 20 30 40 50 60
Ambient temperature Ta in C
I
e

i
n

A
0
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150
160
0 8 16 24 32 40 48
Ie in A
P
o
w
e
r

l
o
s
s

i
n

W
3RF2450-.
6


















http://www.siemens.com/solid-state-switching-devices

0
10
20
30
40
50
60
0 10 20 30 40 50 60
Ambient temperature Ta in C
I
e

i
n

A
0
20
40
60
80
100
120
140
160
180
200
0 10 20 30 40 50
Ie in A
P
o
w
e
r

l
o
s
s

i
n

W

6
Identical current/temperature curves for Stand-alone and side by side mounting.
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF24..-.AC.. Zero-Point Switching Solid State Contactors

Subject to changes 08/2010 Page 6/7
Mounting Instructions
7
:


Device / Example Circuit Diagram:


7
Dimensions in mm, (in);
Stand alone mounting, Characteristic Curves shows derating for Side-by-side mounting
http://www.siemens.com/solid-state-switching-devices
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF24..-.AC.. Zero-Point Switching Solid State Contactors

Subject to changes 08/2010 Page 7/7

Dimension Drawings
8
:


8
Dimensions in mm, (in)
http://www.siemens.com/solid-state-switching-devices
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF24..-.AC.. Zero-Point Switching Solid State Contactors

Subject to changes 08/2010 Page 1/7
Main Characteristics:
Three-phase controlled
Zero switching
LED display
Various connection technologies
Plug-in control terminal
Degree of protection IP 20
Insulated mounting foot

Standards / Approvals:
DIN EN 60947-4-3
UL 508 / CSA
1

CE
C-Tick

Ordering Key:
3RF24 10 - 1 A C 4 5
Max.
load current
Connection
technology
Switching
function
Controlled
phases
Control voltage Operating
voltage
3-phase solid
state contactor
with heat sink
10 = 10,5 A
20 = 22 A
30 = 30 A
40 = 40 A
50 = 50 A
1 = Screw connection
2 = Spring-loaded
connection
3 = Ring cable
connection M5
A = Zero-point
switching

C = three-phase 3 = 110 VAC
4 = 4 - 30 VDC
5 = 190 - 230 VAC

5 = 48 - 600 V
Not all possible versions are available ex stock!

Main Circuit:
Values for 40 C
ambient temperature!
I
AC-51

I
e
acc. to
IEC947-4-3
Ie [50C]
UL/CSA
Power loss
with I
AC-51

Min. load
current
Max. leakage
current
Type A A A W A mA
3RF2410- . AC. 10,5 7 7 31 0,1 10
3RF2420- . AC. 22 15 15 66 0,5
3RF2430- . AC. 30 22 22 91
3RF2440- . AC. 40 30 30 121
3RF2450- . AC. 50 38 38 160

Type 3RF24. . - . AC. 5
Rated operating voltage U
e
V 48 ... 600
Voltage range V 40 ... 660
Rated frequency Hz 50/60 10 %
Rated insulation voltage U
i
V 600
Rated impulse withstand voltage U
imp
kV 6
Slew rate V/s 1000
Rated impulse withstand strength Itsm I
2
t value Blocking voltage
Type A A
2
s V
3RF2410- . AC. 300 450 1200
3RF2420- . AC. 600 1800 1200
3RF2430- . AC. 1200 7200 1200
3RF2440- . AC. 1150 6600 1600
3RF2450- . AC. 1150 6600 1600

1
Use overvoltage protection device; max cut-off-voltage 6.000 V; min energy handling capability 100 J
http://www.siemens.com/solid-state-switching-devices
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF24..-.AC.. Zero-Point Switching Solid State Contactors

Subject to changes 08/2010 Page 2/7
http://www.siemens.com/solid-state-switching-devices

Control Circuit A1-A2:
Type 3RF24. . - . AC3. 3RF24. . - . AC4. 3RF24. . - . AC5.
Control voltage U
s
V AC 110 DC 4 ... 30 AC 190 ... 230
Max. control voltage U
s
V 121 30 253
Typical operating current mA 15 30 15
Response voltage V 90 4 180
Drop-out voltage V <40 <1 <40
Rated frequency
of the control supply voltage
Hz 50/60 10 % -- 50/60 10 %
Switching times ON delay ms 40 + Max. one half-wave 1 + Max. one half-wave 40 + Max. one half-wave
OFF delay ms 40 + Max. one half-wave 1 + Max. one half-wave 40 + Max. one half-wave

General Data:
Ambient temperature
During operation C -25 ... 60
During storage C -55 ... 80
Mounting altitude m 0 ... 1000; at > 1000 m, please contact our Technical Assistance
Impact resistance acc. to DIN IEC 68 g/ms 15/11
Vibration resistance g 2
Degree of protection IP20
Electromagnetic compatibility (EMC)
Interference emission
o Conducted interference voltage
IEC 60 947-4-3
Class A for industrial applications
2

Interference resistance
o Electrostatic discharge acc. to
IEC 61 000-4-2 (corresponds
to severity 3)
kV Contact discharge 4; air discharge 8; performance criterion 2
o Induced HF fields acc. to
IEC 61 000-4-6
MHz 0.15 ... 80; 140 dBV; performance criterion 1
o Burst acc. to IEC 61 000-4-4 kV 2/5.0 kHz; performance criterion 2
o Surge acc. to IEC 61 000-4-5 kV Phase-to-ground 2; phase-to-phase 1; performance criterion 2
Dielectric Strength 50/60 Hz
(Input, Output / Base)
V rms 4000


2
Attention!
This product was constructed as an EMC Class A device. The use of this product in residential applications could lead
to radio interferences. In such an application, additional filtering may be required.
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF24..-.AC.. Zero-Point Switching Solid State Contactors

Subject to changes 08/2010 Page 3/7

Type 3RF24. . - 1. 3RF24. . - 2. 3RF24. . - 3.
Connection, main contacts Screw connection
Spring-loaded
connection
Ring cable connection
Conductor cross-section
o Solid mm
2

2 x (1.5 ... 2.5),
2 x (2.5 ... 6)
2x (0.5 ... 2.5)
o Finely stranded with end sleeve mm
2

2 x (1.5 ... 2.5),
2 x (2.5 ... 6), 1 x 10
2x (0.5 ... 1.5)
o Finely stranded w/o end sleeve mm
2
2x (0.5 ... 2.5)
o Solid or stranded AWG 2 x (14 ... 10) 2 x (18 ... 14)
Stripping length mm 10 10
Terminal screw M 4 - M 5
Nm 2 ... 2.5 - 2 ... 2.5 o Tightening torque
D 5...6 mm / PZ 2
lb.in 18 ... 22 - 18 ... 22
Cable lug DIN - - DIN 46234 5-2.5 ... 5-25
JIS - - JIS C 2805 R 2-5 14-5
Connection, control contacts
Conductor cross-section with or
without end sleeve
mm
mm
AWG
1 x (0.5 ... 2.5)
2 x (0.5 ... 1.0)
20 ... 12
0.5 ... 2.5

20 ... 12
1 x (0.5 ... 2.5)
2 x (0.5 ... 1.0)
20 ... 12
Stripping length mm 7 10 7
Terminal screw M 3 - M 3
Nm 0.5 ... 0.6 - 0.5 ... 0.6 o Tightening torque
D 3.5 / PZ 1
lb.in 4.5 ... 5.3 - 4.5 ... 5.3

Type Semiconductor protection fuse
Full-range fuse Partial-range fuse
LV HBC design Cylindrical design LV HBC design Cylindrical design
3

gR/SITOR gR/Neozed
4
aR/SITOR aR/SITOR
3NE1 5SE1 3NE8 3NC1 0 3NC1 4 3NC2 2
10 x 38 14 x 51 22 x 58
Maximum operation voltage U
e
460 V (+10%)
3RF2410- . AC. 3NE1813-0 5SE 1310 3NE 8015-1 3NC1032 3NC1430 3NC2232
3RF2420- . AC. 3NE1814-0 5SE 1320 3NE 8015-1 3NC1032 3NC1450 3NC2263
3RF2430- . AC. 3NE1803-0 5SE 1335 3NE 8003-1 3NC1032 3NC1450 3NC2200
3RF2440- . AC. 3NE1802-0 5SE 1350 3NE 8017-1 -- 3NC1450 3NC2200
3RF2450- . AC. 3NE1817-0 5SE 1350 3NE 8018-1 -- 3NC1450 3NC2200
Maximum operation voltage U
e
600 V (+10%)
3RF2410- . AC. 3NE1813-0 -- 3NE 8015-1 3NC1025 3NC1430 3NC2220
3RF2420- . AC. 3NE1814-0 -- 3NE 8015-1 3NC1032 3NC1450 3NC2250
3RF2430- . AC. 3NE1803-0 -- 3NE 8003-1 3NC1032 3NC1450 3NC2280
3RF2440- . AC. 3NE1802-0 -- 3NE 8017-1 -- 3NC1450 3NC2280
3RF2450- . AC. 3NE1817-0 -- 3NE 8018-1 -- 3NC1450 3NC2280
Fused Design with Semiconductor Protection

Type Line protection fuse
LV HBC design Cylindrical design DIAZED
gG gG gG gG fast
3NA 3NW 3NW 3NW 5SB
10 x 38 mm 14 x 51 mm 22 x 58 mm
Maximum operation voltage

460 V (+10%)
3RF2410- . AC. 3NA3803 3NW6001-1
5
3NW6101-1
5
-- 5SB161
3RF2420- . AC. 3NA3805
5
3NW6005-1
5
3NW6105-1
5
3NW6205-1
5
5SB181
3RF2430- . AC. 3NA3812 -- 3NW6112-1 -- 5SB311
3RF2440- . AC. 3NA3812
5
-- 3NW6112-1
5
3NW6210-1
5
5SB321
3RF2450- . AC. 3NA3812
5
-- -- 3NW6210-1
5
5SB321
5



3
Max. allowable fuse; with smaller fuses the load reversal stability can be limited.
4
Operating voltage only up to 400V!
5
These fuses have a lower rated current than the solid state contactors.
http://www.siemens.com/solid-state-switching-devices
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF24..-.AC.. Zero-Point Switching Solid State Contactors

Subject to changes 08/2010 Page 4/7

Accessories
Function module Order No. Applicable for Versions
Converter 3RF2900-0EA18 3RF24. . - . AC4. Us = DC 24 V


Characteristic Curves

3RF2410-.

Upper curves:
0
2
4
6
8
10
12
0 10 20 30 40 50 60
Ambient temperature Ta in C
I
e

i
n

A
0
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
0 2 4 6 8 10 1
Ie in A
P
o
w
e
r

l
o
s
s

i
n

W
2
I
max
thermal limit current
Middle curves:
Rated current I
e
acc. to UL
Lower curves:
Rated current Ie
acc. to
DIN EN 60947-4-3

Continuous lines:
Stand-alone mounting
Dashed lines:
Side-by-side mounting







3RF2420-.



















0
5
10
15
20
25
0 10 20 30 40 50 60
Ambient temperature Ta in C
I
e

i
n

A
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
0 4 8 12 16 20 24
Ie in A
P
o
w
e
r

l
o
s
s

i
n

W
http://www.siemens.com/solid-state-switching-devices
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF24..-.AC.. Zero-Point Switching Solid State Contactors

Subject to changes 08/2010 Page 5/7
3RF2430-.
6

0
5
10
15
20
25
30
35
40
0 10 20 30 40 50 60
Ambient temperature Ta in C
I
e

i
n

A
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
85
90
95
100
105
110
115
0 6 12 18 24 30 36
Ie in A
P
o
w
e
r

l
o
s
s

i
n

W
Upper curves:
I
max
thermal limit current
Middle curves:
Rated current I
e
acc. to UL
Lower curves:
Rated current Ie
acc. to
DIN EN 60947-4-3

Stand-alone and side-by-
side mounting







3RF2440-.
6


















0
5
10
15
20
25
30
35
40
45
50
0 10 20 30 40 50 60
Ambient temperature Ta in C
I
e

i
n

A
0
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150
160
0 8 16 24 32 40 48
Ie in A
P
o
w
e
r

l
o
s
s

i
n

W
3RF2450-.
6


















http://www.siemens.com/solid-state-switching-devices

0
10
20
30
40
50
60
0 10 20 30 40 50 60
Ambient temperature Ta in C
I
e

i
n

A
0
20
40
60
80
100
120
140
160
180
200
0 10 20 30 40 50
Ie in A
P
o
w
e
r

l
o
s
s

i
n

W

6
Identical current/temperature curves for Stand-alone and side by side mounting.
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF24..-.AC.. Zero-Point Switching Solid State Contactors

Subject to changes 08/2010 Page 6/7
Mounting Instructions
7
:


Device / Example Circuit Diagram:


7
Dimensions in mm, (in);
Stand alone mounting, Characteristic Curves shows derating for Side-by-side mounting
http://www.siemens.com/solid-state-switching-devices
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF24..-.AC.. Zero-Point Switching Solid State Contactors

Subject to changes 08/2010 Page 7/7

Dimension Drawings
8
:


8
Dimensions in mm, (in)
http://www.siemens.com/solid-state-switching-devices
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF24..-.AC.. Zero-Point Switching Solid State Contactors

Subject to changes 08/2010 Page 1/7
Main Characteristics:
Three-phase controlled
Zero switching
LED display
Various connection technologies
Plug-in control terminal
Degree of protection IP 20
Insulated mounting foot

Standards / Approvals:
DIN EN 60947-4-3
UL 508 / CSA
1

CE
C-Tick

Ordering Key:
3RF24 10 - 1 A C 4 5
Max.
load current
Connection
technology
Switching
function
Controlled
phases
Control voltage Operating
voltage
3-phase solid
state contactor
with heat sink
10 = 10,5 A
20 = 22 A
30 = 30 A
40 = 40 A
50 = 50 A
1 = Screw connection
2 = Spring-loaded
connection
3 = Ring cable
connection M5
A = Zero-point
switching

C = three-phase 3 = 110 VAC
4 = 4 - 30 VDC
5 = 190 - 230 VAC

5 = 48 - 600 V
Not all possible versions are available ex stock!

Main Circuit:
Values for 40 C
ambient temperature!
I
AC-51

I
e
acc. to
IEC947-4-3
Ie [50C]
UL/CSA
Power loss
with I
AC-51

Min. load
current
Max. leakage
current
Type A A A W A mA
3RF2410- . AC. 10,5 7 7 31 0,1 10
3RF2420- . AC. 22 15 15 66 0,5
3RF2430- . AC. 30 22 22 91
3RF2440- . AC. 40 30 30 121
3RF2450- . AC. 50 38 38 160

Type 3RF24. . - . AC. 5
Rated operating voltage U
e
V 48 ... 600
Voltage range V 40 ... 660
Rated frequency Hz 50/60 10 %
Rated insulation voltage U
i
V 600
Rated impulse withstand voltage U
imp
kV 6
Slew rate V/s 1000
Rated impulse withstand strength Itsm I
2
t value Blocking voltage
Type A A
2
s V
3RF2410- . AC. 300 450 1200
3RF2420- . AC. 600 1800 1200
3RF2430- . AC. 1200 7200 1200
3RF2440- . AC. 1150 6600 1600
3RF2450- . AC. 1150 6600 1600

1
Use overvoltage protection device; max cut-off-voltage 6.000 V; min energy handling capability 100 J
http://www.siemens.com/solid-state-switching-devices
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF24..-.AC.. Zero-Point Switching Solid State Contactors

Subject to changes 08/2010 Page 2/7
http://www.siemens.com/solid-state-switching-devices

Control Circuit A1-A2:
Type 3RF24. . - . AC3. 3RF24. . - . AC4. 3RF24. . - . AC5.
Control voltage U
s
V AC 110 DC 4 ... 30 AC 190 ... 230
Max. control voltage U
s
V 121 30 253
Typical operating current mA 15 30 15
Response voltage V 90 4 180
Drop-out voltage V <40 <1 <40
Rated frequency
of the control supply voltage
Hz 50/60 10 % -- 50/60 10 %
Switching times ON delay ms 40 + Max. one half-wave 1 + Max. one half-wave 40 + Max. one half-wave
OFF delay ms 40 + Max. one half-wave 1 + Max. one half-wave 40 + Max. one half-wave

General Data:
Ambient temperature
During operation C -25 ... 60
During storage C -55 ... 80
Mounting altitude m 0 ... 1000; at > 1000 m, please contact our Technical Assistance
Impact resistance acc. to DIN IEC 68 g/ms 15/11
Vibration resistance g 2
Degree of protection IP20
Electromagnetic compatibility (EMC)
Interference emission
o Conducted interference voltage
IEC 60 947-4-3
Class A for industrial applications
2

Interference resistance
o Electrostatic discharge acc. to
IEC 61 000-4-2 (corresponds
to severity 3)
kV Contact discharge 4; air discharge 8; performance criterion 2
o Induced HF fields acc. to
IEC 61 000-4-6
MHz 0.15 ... 80; 140 dBV; performance criterion 1
o Burst acc. to IEC 61 000-4-4 kV 2/5.0 kHz; performance criterion 2
o Surge acc. to IEC 61 000-4-5 kV Phase-to-ground 2; phase-to-phase 1; performance criterion 2
Dielectric Strength 50/60 Hz
(Input, Output / Base)
V rms 4000


2
Attention!
This product was constructed as an EMC Class A device. The use of this product in residential applications could lead
to radio interferences. In such an application, additional filtering may be required.
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF24..-.AC.. Zero-Point Switching Solid State Contactors

Subject to changes 08/2010 Page 3/7

Type 3RF24. . - 1. 3RF24. . - 2. 3RF24. . - 3.
Connection, main contacts Screw connection
Spring-loaded
connection
Ring cable connection
Conductor cross-section
o Solid mm
2

2 x (1.5 ... 2.5),
2 x (2.5 ... 6)
2x (0.5 ... 2.5)
o Finely stranded with end sleeve mm
2

2 x (1.5 ... 2.5),
2 x (2.5 ... 6), 1 x 10
2x (0.5 ... 1.5)
o Finely stranded w/o end sleeve mm
2
2x (0.5 ... 2.5)
o Solid or stranded AWG 2 x (14 ... 10) 2 x (18 ... 14)
Stripping length mm 10 10
Terminal screw M 4 - M 5
Nm 2 ... 2.5 - 2 ... 2.5 o Tightening torque
D 5...6 mm / PZ 2
lb.in 18 ... 22 - 18 ... 22
Cable lug DIN - - DIN 46234 5-2.5 ... 5-25
JIS - - JIS C 2805 R 2-5 14-5
Connection, control contacts
Conductor cross-section with or
without end sleeve
mm
mm
AWG
1 x (0.5 ... 2.5)
2 x (0.5 ... 1.0)
20 ... 12
0.5 ... 2.5

20 ... 12
1 x (0.5 ... 2.5)
2 x (0.5 ... 1.0)
20 ... 12
Stripping length mm 7 10 7
Terminal screw M 3 - M 3
Nm 0.5 ... 0.6 - 0.5 ... 0.6 o Tightening torque
D 3.5 / PZ 1
lb.in 4.5 ... 5.3 - 4.5 ... 5.3

Type Semiconductor protection fuse
Full-range fuse Partial-range fuse
LV HBC design Cylindrical design LV HBC design Cylindrical design
3

gR/SITOR gR/Neozed
4
aR/SITOR aR/SITOR
3NE1 5SE1 3NE8 3NC1 0 3NC1 4 3NC2 2
10 x 38 14 x 51 22 x 58
Maximum operation voltage U
e
460 V (+10%)
3RF2410- . AC. 3NE1813-0 5SE 1310 3NE 8015-1 3NC1032 3NC1430 3NC2232
3RF2420- . AC. 3NE1814-0 5SE 1320 3NE 8015-1 3NC1032 3NC1450 3NC2263
3RF2430- . AC. 3NE1803-0 5SE 1335 3NE 8003-1 3NC1032 3NC1450 3NC2200
3RF2440- . AC. 3NE1802-0 5SE 1350 3NE 8017-1 -- 3NC1450 3NC2200
3RF2450- . AC. 3NE1817-0 5SE 1350 3NE 8018-1 -- 3NC1450 3NC2200
Maximum operation voltage U
e
600 V (+10%)
3RF2410- . AC. 3NE1813-0 -- 3NE 8015-1 3NC1025 3NC1430 3NC2220
3RF2420- . AC. 3NE1814-0 -- 3NE 8015-1 3NC1032 3NC1450 3NC2250
3RF2430- . AC. 3NE1803-0 -- 3NE 8003-1 3NC1032 3NC1450 3NC2280
3RF2440- . AC. 3NE1802-0 -- 3NE 8017-1 -- 3NC1450 3NC2280
3RF2450- . AC. 3NE1817-0 -- 3NE 8018-1 -- 3NC1450 3NC2280
Fused Design with Semiconductor Protection

Type Line protection fuse
LV HBC design Cylindrical design DIAZED
gG gG gG gG fast
3NA 3NW 3NW 3NW 5SB
10 x 38 mm 14 x 51 mm 22 x 58 mm
Maximum operation voltage

460 V (+10%)
3RF2410- . AC. 3NA3803 3NW6001-1
5
3NW6101-1
5
-- 5SB161
3RF2420- . AC. 3NA3805
5
3NW6005-1
5
3NW6105-1
5
3NW6205-1
5
5SB181
3RF2430- . AC. 3NA3812 -- 3NW6112-1 -- 5SB311
3RF2440- . AC. 3NA3812
5
-- 3NW6112-1
5
3NW6210-1
5
5SB321
3RF2450- . AC. 3NA3812
5
-- -- 3NW6210-1
5
5SB321
5



3
Max. allowable fuse; with smaller fuses the load reversal stability can be limited.
4
Operating voltage only up to 400V!
5
These fuses have a lower rated current than the solid state contactors.
http://www.siemens.com/solid-state-switching-devices
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF24..-.AC.. Zero-Point Switching Solid State Contactors

Subject to changes 08/2010 Page 4/7

Accessories
Function module Order No. Applicable for Versions
Converter 3RF2900-0EA18 3RF24. . - . AC4. Us = DC 24 V


Characteristic Curves

3RF2410-.

Upper curves:
0
2
4
6
8
10
12
0 10 20 30 40 50 60
Ambient temperature Ta in C
I
e

i
n

A
0
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
0 2 4 6 8 10 1
Ie in A
P
o
w
e
r

l
o
s
s

i
n

W
2
I
max
thermal limit current
Middle curves:
Rated current I
e
acc. to UL
Lower curves:
Rated current Ie
acc. to
DIN EN 60947-4-3

Continuous lines:
Stand-alone mounting
Dashed lines:
Side-by-side mounting







3RF2420-.



















0
5
10
15
20
25
0 10 20 30 40 50 60
Ambient temperature Ta in C
I
e

i
n

A
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
0 4 8 12 16 20 24
Ie in A
P
o
w
e
r

l
o
s
s

i
n

W
http://www.siemens.com/solid-state-switching-devices
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF24..-.AC.. Zero-Point Switching Solid State Contactors

Subject to changes 08/2010 Page 5/7
3RF2430-.
6

0
5
10
15
20
25
30
35
40
0 10 20 30 40 50 60
Ambient temperature Ta in C
I
e

i
n

A
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
85
90
95
100
105
110
115
0 6 12 18 24 30 36
Ie in A
P
o
w
e
r

l
o
s
s

i
n

W
Upper curves:
I
max
thermal limit current
Middle curves:
Rated current I
e
acc. to UL
Lower curves:
Rated current Ie
acc. to
DIN EN 60947-4-3

Stand-alone and side-by-
side mounting







3RF2440-.
6


















0
5
10
15
20
25
30
35
40
45
50
0 10 20 30 40 50 60
Ambient temperature Ta in C
I
e

i
n

A
0
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150
160
0 8 16 24 32 40 48
Ie in A
P
o
w
e
r

l
o
s
s

i
n

W
3RF2450-.
6


















http://www.siemens.com/solid-state-switching-devices

0
10
20
30
40
50
60
0 10 20 30 40 50 60
Ambient temperature Ta in C
I
e

i
n

A
0
20
40
60
80
100
120
140
160
180
200
0 10 20 30 40 50
Ie in A
P
o
w
e
r

l
o
s
s

i
n

W

6
Identical current/temperature curves for Stand-alone and side by side mounting.
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF24..-.AC.. Zero-Point Switching Solid State Contactors

Subject to changes 08/2010 Page 6/7
Mounting Instructions
7
:


Device / Example Circuit Diagram:


7
Dimensions in mm, (in);
Stand alone mounting, Characteristic Curves shows derating for Side-by-side mounting
http://www.siemens.com/solid-state-switching-devices
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF24..-.AC.. Zero-Point Switching Solid State Contactors

Subject to changes 08/2010 Page 7/7

Dimension Drawings
8
:


8
Dimensions in mm, (in)
http://www.siemens.com/solid-state-switching-devices
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF24..-.AC.. Zero-Point Switching Solid State Contactors

Subject to changes 08/2010 Page 1/7
Main Characteristics:
Three-phase controlled
Zero switching
LED display
Various connection technologies
Plug-in control terminal
Degree of protection IP 20
Insulated mounting foot

Standards / Approvals:
DIN EN 60947-4-3
UL 508 / CSA
1

CE
C-Tick

Ordering Key:
3RF24 10 - 1 A C 4 5
Max.
load current
Connection
technology
Switching
function
Controlled
phases
Control voltage Operating
voltage
3-phase solid
state contactor
with heat sink
10 = 10,5 A
20 = 22 A
30 = 30 A
40 = 40 A
50 = 50 A
1 = Screw connection
2 = Spring-loaded
connection
3 = Ring cable
connection M5
A = Zero-point
switching

C = three-phase 3 = 110 VAC
4 = 4 - 30 VDC
5 = 190 - 230 VAC

5 = 48 - 600 V
Not all possible versions are available ex stock!

Main Circuit:
Values for 40 C
ambient temperature!
I
AC-51

I
e
acc. to
IEC947-4-3
Ie [50C]
UL/CSA
Power loss
with I
AC-51

Min. load
current
Max. leakage
current
Type A A A W A mA
3RF2410- . AC. 10,5 7 7 31 0,1 10
3RF2420- . AC. 22 15 15 66 0,5
3RF2430- . AC. 30 22 22 91
3RF2440- . AC. 40 30 30 121
3RF2450- . AC. 50 38 38 160

Type 3RF24. . - . AC. 5
Rated operating voltage U
e
V 48 ... 600
Voltage range V 40 ... 660
Rated frequency Hz 50/60 10 %
Rated insulation voltage U
i
V 600
Rated impulse withstand voltage U
imp
kV 6
Slew rate V/s 1000
Rated impulse withstand strength Itsm I
2
t value Blocking voltage
Type A A
2
s V
3RF2410- . AC. 300 450 1200
3RF2420- . AC. 600 1800 1200
3RF2430- . AC. 1200 7200 1200
3RF2440- . AC. 1150 6600 1600
3RF2450- . AC. 1150 6600 1600

1
Use overvoltage protection device; max cut-off-voltage 6.000 V; min energy handling capability 100 J
http://www.siemens.com/solid-state-switching-devices
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF24..-.AC.. Zero-Point Switching Solid State Contactors

Subject to changes 08/2010 Page 2/7
http://www.siemens.com/solid-state-switching-devices

Control Circuit A1-A2:
Type 3RF24. . - . AC3. 3RF24. . - . AC4. 3RF24. . - . AC5.
Control voltage U
s
V AC 110 DC 4 ... 30 AC 190 ... 230
Max. control voltage U
s
V 121 30 253
Typical operating current mA 15 30 15
Response voltage V 90 4 180
Drop-out voltage V <40 <1 <40
Rated frequency
of the control supply voltage
Hz 50/60 10 % -- 50/60 10 %
Switching times ON delay ms 40 + Max. one half-wave 1 + Max. one half-wave 40 + Max. one half-wave
OFF delay ms 40 + Max. one half-wave 1 + Max. one half-wave 40 + Max. one half-wave

General Data:
Ambient temperature
During operation C -25 ... 60
During storage C -55 ... 80
Mounting altitude m 0 ... 1000; at > 1000 m, please contact our Technical Assistance
Impact resistance acc. to DIN IEC 68 g/ms 15/11
Vibration resistance g 2
Degree of protection IP20
Electromagnetic compatibility (EMC)
Interference emission
o Conducted interference voltage
IEC 60 947-4-3
Class A for industrial applications
2

Interference resistance
o Electrostatic discharge acc. to
IEC 61 000-4-2 (corresponds
to severity 3)
kV Contact discharge 4; air discharge 8; performance criterion 2
o Induced HF fields acc. to
IEC 61 000-4-6
MHz 0.15 ... 80; 140 dBV; performance criterion 1
o Burst acc. to IEC 61 000-4-4 kV 2/5.0 kHz; performance criterion 2
o Surge acc. to IEC 61 000-4-5 kV Phase-to-ground 2; phase-to-phase 1; performance criterion 2
Dielectric Strength 50/60 Hz
(Input, Output / Base)
V rms 4000


2
Attention!
This product was constructed as an EMC Class A device. The use of this product in residential applications could lead
to radio interferences. In such an application, additional filtering may be required.
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF24..-.AC.. Zero-Point Switching Solid State Contactors

Subject to changes 08/2010 Page 3/7

Type 3RF24. . - 1. 3RF24. . - 2. 3RF24. . - 3.
Connection, main contacts Screw connection
Spring-loaded
connection
Ring cable connection
Conductor cross-section
o Solid mm
2

2 x (1.5 ... 2.5),
2 x (2.5 ... 6)
2x (0.5 ... 2.5)
o Finely stranded with end sleeve mm
2

2 x (1.5 ... 2.5),
2 x (2.5 ... 6), 1 x 10
2x (0.5 ... 1.5)
o Finely stranded w/o end sleeve mm
2
2x (0.5 ... 2.5)
o Solid or stranded AWG 2 x (14 ... 10) 2 x (18 ... 14)
Stripping length mm 10 10
Terminal screw M 4 - M 5
Nm 2 ... 2.5 - 2 ... 2.5 o Tightening torque
D 5...6 mm / PZ 2
lb.in 18 ... 22 - 18 ... 22
Cable lug DIN - - DIN 46234 5-2.5 ... 5-25
JIS - - JIS C 2805 R 2-5 14-5
Connection, control contacts
Conductor cross-section with or
without end sleeve
mm
mm
AWG
1 x (0.5 ... 2.5)
2 x (0.5 ... 1.0)
20 ... 12
0.5 ... 2.5

20 ... 12
1 x (0.5 ... 2.5)
2 x (0.5 ... 1.0)
20 ... 12
Stripping length mm 7 10 7
Terminal screw M 3 - M 3
Nm 0.5 ... 0.6 - 0.5 ... 0.6 o Tightening torque
D 3.5 / PZ 1
lb.in 4.5 ... 5.3 - 4.5 ... 5.3

Type Semiconductor protection fuse
Full-range fuse Partial-range fuse
LV HBC design Cylindrical design LV HBC design Cylindrical design
3

gR/SITOR gR/Neozed
4
aR/SITOR aR/SITOR
3NE1 5SE1 3NE8 3NC1 0 3NC1 4 3NC2 2
10 x 38 14 x 51 22 x 58
Maximum operation voltage U
e
460 V (+10%)
3RF2410- . AC. 3NE1813-0 5SE 1310 3NE 8015-1 3NC1032 3NC1430 3NC2232
3RF2420- . AC. 3NE1814-0 5SE 1320 3NE 8015-1 3NC1032 3NC1450 3NC2263
3RF2430- . AC. 3NE1803-0 5SE 1335 3NE 8003-1 3NC1032 3NC1450 3NC2200
3RF2440- . AC. 3NE1802-0 5SE 1350 3NE 8017-1 -- 3NC1450 3NC2200
3RF2450- . AC. 3NE1817-0 5SE 1350 3NE 8018-1 -- 3NC1450 3NC2200
Maximum operation voltage U
e
600 V (+10%)
3RF2410- . AC. 3NE1813-0 -- 3NE 8015-1 3NC1025 3NC1430 3NC2220
3RF2420- . AC. 3NE1814-0 -- 3NE 8015-1 3NC1032 3NC1450 3NC2250
3RF2430- . AC. 3NE1803-0 -- 3NE 8003-1 3NC1032 3NC1450 3NC2280
3RF2440- . AC. 3NE1802-0 -- 3NE 8017-1 -- 3NC1450 3NC2280
3RF2450- . AC. 3NE1817-0 -- 3NE 8018-1 -- 3NC1450 3NC2280
Fused Design with Semiconductor Protection

Type Line protection fuse
LV HBC design Cylindrical design DIAZED
gG gG gG gG fast
3NA 3NW 3NW 3NW 5SB
10 x 38 mm 14 x 51 mm 22 x 58 mm
Maximum operation voltage

460 V (+10%)
3RF2410- . AC. 3NA3803 3NW6001-1
5
3NW6101-1
5
-- 5SB161
3RF2420- . AC. 3NA3805
5
3NW6005-1
5
3NW6105-1
5
3NW6205-1
5
5SB181
3RF2430- . AC. 3NA3812 -- 3NW6112-1 -- 5SB311
3RF2440- . AC. 3NA3812
5
-- 3NW6112-1
5
3NW6210-1
5
5SB321
3RF2450- . AC. 3NA3812
5
-- -- 3NW6210-1
5
5SB321
5



3
Max. allowable fuse; with smaller fuses the load reversal stability can be limited.
4
Operating voltage only up to 400V!
5
These fuses have a lower rated current than the solid state contactors.
http://www.siemens.com/solid-state-switching-devices
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF24..-.AC.. Zero-Point Switching Solid State Contactors

Subject to changes 08/2010 Page 4/7

Accessories
Function module Order No. Applicable for Versions
Converter 3RF2900-0EA18 3RF24. . - . AC4. Us = DC 24 V


Characteristic Curves

3RF2410-.

Upper curves:
0
2
4
6
8
10
12
0 10 20 30 40 50 60
Ambient temperature Ta in C
I
e

i
n

A
0
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
0 2 4 6 8 10 1
Ie in A
P
o
w
e
r

l
o
s
s

i
n

W
2
I
max
thermal limit current
Middle curves:
Rated current I
e
acc. to UL
Lower curves:
Rated current Ie
acc. to
DIN EN 60947-4-3

Continuous lines:
Stand-alone mounting
Dashed lines:
Side-by-side mounting







3RF2420-.



















0
5
10
15
20
25
0 10 20 30 40 50 60
Ambient temperature Ta in C
I
e

i
n

A
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
0 4 8 12 16 20 24
Ie in A
P
o
w
e
r

l
o
s
s

i
n

W
http://www.siemens.com/solid-state-switching-devices
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF24..-.AC.. Zero-Point Switching Solid State Contactors

Subject to changes 08/2010 Page 5/7
3RF2430-.
6

0
5
10
15
20
25
30
35
40
0 10 20 30 40 50 60
Ambient temperature Ta in C
I
e

i
n

A
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
85
90
95
100
105
110
115
0 6 12 18 24 30 36
Ie in A
P
o
w
e
r

l
o
s
s

i
n

W
Upper curves:
I
max
thermal limit current
Middle curves:
Rated current I
e
acc. to UL
Lower curves:
Rated current Ie
acc. to
DIN EN 60947-4-3

Stand-alone and side-by-
side mounting







3RF2440-.
6


















0
5
10
15
20
25
30
35
40
45
50
0 10 20 30 40 50 60
Ambient temperature Ta in C
I
e

i
n

A
0
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150
160
0 8 16 24 32 40 48
Ie in A
P
o
w
e
r

l
o
s
s

i
n

W
3RF2450-.
6


















http://www.siemens.com/solid-state-switching-devices

0
10
20
30
40
50
60
0 10 20 30 40 50 60
Ambient temperature Ta in C
I
e

i
n

A
0
20
40
60
80
100
120
140
160
180
200
0 10 20 30 40 50
Ie in A
P
o
w
e
r

l
o
s
s

i
n

W

6
Identical current/temperature curves for Stand-alone and side by side mounting.
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF24..-.AC.. Zero-Point Switching Solid State Contactors

Subject to changes 08/2010 Page 6/7
Mounting Instructions
7
:


Device / Example Circuit Diagram:


7
Dimensions in mm, (in);
Stand alone mounting, Characteristic Curves shows derating for Side-by-side mounting
http://www.siemens.com/solid-state-switching-devices
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS 3RF24..-.AC.. Zero-Point Switching Solid State Contactors

Subject to changes 08/2010 Page 7/7

Dimension Drawings
8
:


8
Dimensions in mm, (in)
http://www.siemens.com/solid-state-switching-devices
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS Solid-state Switching Devices
3RF29..-0FA08 Load Monitoring Basic Function Module
Main Characteristics:
Applicable on 3RF21 and 3RF23 devices
No additional space requirements
Partial load monitoring for up to 6 loads
Network and thyristor monitoring
Plug-in control terminal
Degree of protection IP 20

Standards / Approvals:
DIN EN 60947-4-3
UL 508 / CSA
CE
C-Tick

Product Description:
Operation and monitoring of up to 6 heating elements with constant resistance at a 3RF21 solid state relay or
a 3RF23 solid state contactor.
This module permanently measures the current strength. This value is then continuously compared to a
reference value (TEACH) which has once been stored during commissioning. If the current drops by 1/6
of the reference value, however, by at least the value of the min. partial load current, the module detects a
partial load fault.
Moreover, the function module monitors thyristor faults and network failures.
In cases of failure, the failure is signaled to the control via the OUT contact (NO contact) after a delay time of
100 msec and indicated via the FAULT LED at the function module.

Ordering Key:
3RF29 06 - 0 F A 0 8
Max. load
current
Connection
technology
Switching
function
Controlled
phases
Control
voltage
Operating
voltage
Function
module for
3RF21 and
3RF23
06 = 6 A
20 = 22 A
0 = Not relevant

F = Load monitoring
Basic
A = Single-phase 0 = 24 V DC 8 = Not relevant

Main Circuit:
Type 3RF2906-0FA08 3RF2920-0FA08 3RF2920-0FA08
Current detection
Product version
1
to *E02* ex *E03*
Rated operating current I
e
A 6 20 20
TEACH range A 0,25 ... 6 4 ... 22 0,65 ... 22
Measuring range A 0 ... 6,6 0 ... 22 0 ... 22
Min. partial load current A 0,25 0,65 0,65
Number of partial loads 1 6 1 6 1 6


Partial load monitoring response threshold in dependence of the sum current












For example: 3RF2920-0FA08 ex *E03*

The characteristic curve shows the load
change (Y axis) required for a partial load
fault in dependence of the teach current (X
axis).
3,9 A 20 A Teach current
P
a
r
t
i
a
l

l
o
a
d

c
u
r
r
e
n
d
r
e
s
p
o
n
s
e

t
h
r
e
s
h
o
l
d
0,65 A
3,33 A
0,65 A
1 to 6 max. 6 partial loads
1
The product version are on the package on the label and at the top of the device.
Subject to changes 07/2010 Page 1/4
http://www.siemens.com/solid-state-switching-devices
VOLTAR
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS Solid-state Switching Devices
3RF29..-0FA08 Load Monitoring Basic Function Module
Subject to changes 07/2010 Page 2/4
http://www.siemens.com/solid-state-switching-devices

Control Circuit A1-A2:
Type 3RF29..-0FA08
Rated control supply voltage U
s
V 24 DC
Current input mA < 25
Max. control supply voltage V 30 DC
Min. control supply voltage V 18 DC

Control Input IN:
Type 3RF29..-0FA08
Max. rated operating voltage U
c
V 30 DC
Operating current mA < 15
Response voltage U
c
V 12
Pickup current mA > 2
Drop-out voltage V 5

Fault Signaling Output OUT:
Type 3RF29..-0FA08
Output voltage V 15 ...30 DC
Max. output current mA 50

General Data:
Ambient temperature
During operation C -25 ... 60
During storage C -55 ... 80
Mounting altitude m 0 ... 1000; at > 1000 m, please contact our Technical Assistance
Impact resistance acc. to DIN IEC 68 g/ms 15/11
Vibration resistance g 2
Degree of protection IP20
Electromagnetic compatibility (EMC)
Interference emission
o Conducted interference voltage
IEC 60 947-4-3
Class A for industrial applications
2

o Radiated, high-frequency
interference voltage IEC 60 947-4-3
Class B for residential/office/commercial applications
Interference resistance
o Electrostatic discharge acc. to
IEC 61 000-4-2 (corresponds to severity 3)
kV Contact discharge 4; air discharge 8; performance criterion 2
o Induced HF fields acc. to
IEC 61 000-4-6
MHz 0.15 ... 80; 140 dBV; performance criterion 1
o Burst acc. to IEC 61 000-4-4 kV 2/5.0 kHz; performance criterion 2
o Surge acc. to IEC 61 000-4-5 kV Phase-to-ground 2; phase-to-phase 1; performance criterion 2

Type Screw connection
Connection, auxiliary/control contacts
Conductor cross-section with or
without end sleeve
mm
mm
AWG
1 x (0.5 ... 2.5)
2 x (0.5 ... 1.0)
20 ... 12
Stripping length mm 7
Terminal screw M 3
Nm 0.5 ... 0.6 o Tightening torque
D 3.5 / PZ 1
lb.in 4.5 ... 5.3
Current transformer hole diameter mm 7

2
Attention!
This product was constructed as a EMC Class A device. The use of this product in residential applications could lead
to radio interferences. In such an application, additional filtering may be required.
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS Solid-state Switching Devices
3RF29..-0FA08 Load Monitoring Basic Function Module

Allocation to the Solid State Switching Devices:
Applicable for
the following types
Order No. Control voltage Connection technology
Solid state relays 3RF21. . - 1. A0.
3RF21. . - 1. A4.
Us = 24 V DC
Us = 4...30 V DC
Screw connection
Solid state contactors 3RF23. . - 1. A0.
3RF23. . - 1. A4.
Us = 24 V DC
Us = 4...30 V DC
Screw connection
Accessories Order No.
Sealable caps 3RF2900-0RA88

Mounting:
The module can be mounted onto all 3RF21 solid state relays and 3RF23 solid state contactors with a
control voltage of 24 V DC. After disconnection of the control terminal from the solid state switching device
and disconnection of the line to the load from the 2T terminal, the Basic load monitoring can be snapped on.
All connections to the basic device are realized thereby. Caution: The guide at the transformer must be
inserted into the groove of the solid state switching device! The control terminal of the solid state relay or
contactor is plugged into the function modules A1-A2 terminal. The line to the load must be routed through
the transformer (D 7.0 mm) and reconnected to the solid state switching device.
For dismounting, the load monitoring must be manually withdrawn from the basic device in vertical direction.

Commissioning:
When the supply voltage (A1-A2) is first applied, the two INPUT and ON LEDs flash alternately as no
TEACH process has yet been carried out. The fault signal output is not set thereby. The function module can
be taught in the controlled or uncontrolled state.
Press the TEACH pushbutton for at least 3 seconds. After this time, the load monitoring detects the current
flowing through the solid state relay or contactor and stores it as a set point value. The correct completion of
the TEACH process is indicated by a simultaneous continuous illumination of the two LEDs.
The TEACH process can be repeated at any time.
With the supply voltage applied, the TEACH button can be pressed shortly, maximally 1 second, for test
purposes. For this time, the solid state switching device switches through and you can thereby test the
arrangement.

Function Diagram:



1) Partial Load Fault
2) Thyristor Fault
3) Supply Fault
Subject to changes 07/2010 Page 3/4
http://www.siemens.com/solid-state-switching-devices
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS Solid-state Switching Devices
3RF29..-0FA08 Load Monitoring Basic Function Module


Subject to changes 07/2010 Page 4/4
http://www.siemens.com/solid-state-switching-devices
1 L
2 T
A2 -
A1 +
PE
1/N/PE 50 Hz 230 V
N
PE
L
R1 R2 R3 R4 R5 R6
A1 +
A2 -
IN
OUT
I<
1)
2)
K1
F1
L +
D in
D out
L -
L -
L +
DC 24 V
A1
3)
Dimension Drawing: Device Circuit Diagram:















A1 +
A2 -
IN
OUT
I<
1)
2)


3RF29..-0FA08
U
s
= 24 V DC






Example Circuit Diagram:

A1 Control (PLC)
F1 Miniature circuit-breaker
main circuit
K1 3RF23 solid state contactor
with plugged-on load
monitoring module
R1-6 Load resistances

1) Internal connection to the
solid state relay or contactor
2) Straight-through transformer

Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS Solid-state Switching Devices
3RF2900-0EA18 Converter Function Module
Main Characteristics:
Applicable on all 3RF21, 3RF22, 3RF23 and 3RF24 devices
No additional space requirements
LED display
Linear conversion
Plug-in control terminals
Degree of protection IP 20

Standards / Approvals:
DIN EN 60947-4-3
UL 508 / CSA
CE
C-Tick

Product Description:
With this module, analog control signals are converted into a pulse-width modulated digital signal.
The strength of the analog input voltage is converted into an ON and an OFF switching time within
a fixed period duration of approx. 1 second, e.g.: 3 V correspond to 0.3 s ON and 0.7 s OFF. The
conversion is realized linearly between a range of 0.3 and 9.6 V.
Below a value of 0.3 V, the connected solid state switching devices is not actuated, above 9.6 V, it
is permanently switched on.
The module could be used together with all 3RF21, 3RF22 solid state relays and 3RF23, 3RF24
solid state contactors with a control voltage of DC 24 V, AC/DC 24 V or DC 4 to 30 V.
In combination with the converter module it is possible to control all semiconductor-switch gear
with a DC control voltage also on a AC 24 V control voltage!

Ordering Key:
3RF29 00 - 0 E A 1 8
Max. load
current
Connection
technology
Switching
function
Controlled
phases
Control
voltage
Operating
voltage
Function
module for
3RF21,22 and
3RF23,24
00 = Without 0 = Not relevant

E = Converter A = Single-phase 1 = 24 V AC/DC 8 = Without


Main Circuit:
The function module has not contact with the main circuit!


Control Circuit A1-A2:
Type 3RF2900-0EA18
Rated control supply voltage U
s
V 24 AC/DC
Current input mA < 25
Max. control supply voltage V 26.5 AC 30 DC
Min. control supply voltage V 20.5 AC 18 DC
Rated frequency of the control supply voltage Hz 50/60 10 %


Control Input 0-10 V:
Type 3RF2900-0EA18
Analog input V 0 ... 10
Permissible range V -1 ... 11
Input resistance kOhm 100
Period duration, typical s 1


Subject to changes 07/2010 Page 1/4
http://www.siemens.com/solid-state-switching-devices
VOLTAR
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS Solid-state Switching Devices
3RF2900-0EA18 Converter Function Module
Subject to changes 07/2010 Page 2/4
http://www.siemens.com/solid-state-switching-devices


General Data:
Ambient temperature
During operation C -25 ... 60
During storage C -55 ... 80
Mounting altitude m 0 ... 1000; at > 1000 m, please contact our Technical Assistance
Impact resistance acc. to DIN IEC 68 g/ms 15/11
Vibration resistance g 2
Degree of protection IP20
Electromagnetic Compatibility (EMC)
Interference emission
o Conducted interference voltage
IEC 60 947-4-3
Class A for industrial applications
1

o Radiated, high-frequency
interference voltage IEC 60 947-4-3
Class B for residential/office/commercial applications
Interference resistance
o Electrostatic discharge acc. to
IEC 61 000-4-2 (corresponds
to severity 3)
kV Contact discharge 4; air discharge 8; performance criterion 2
o Induced HF fields acc. to
IEC 61 000-4-6
MHz 0.15 ... 80; 140 dBV; performance criterion 1
o Burst acc. to IEC 61 000-4-4 kV 2/5.0 kHz; performance criterion 2
o Surge acc. to IEC 61 000-4-5 kV Phase-to-ground 2; phase-to-phase 1; performance criterion 2

Type Screw connection
Connection, auxiliary/control contacts
Conductor cross-section with or
without end sleeve
mm
mm
AWG
1 x (0.5 ... 2.5)
2 x (0.5 ... 1.0)
20 ... 12
Stripping length mm 7
Terminal screw M 3
Nm 0.5 ... 0.6 o Tightening torque
D 3.5 / PZ 1
lb.in 4.5 ... 5.3

Allocation to Solid State Switching Devices:
Applicable for
the following types
Order No. Control voltage Connection technology
Solid state relays 3RF21. . - . . A0.
3RF21. . - . . A1.
3RF21. . - . . A4.
3RF22. . - . A. 4.
Us = 24 V DC
Us = 24 V AC/DC
Us = 4...30 V DC
Us = 4...30 V DC
Screw, spring-loaded and
ring cable connection
Solid state contactors 3RF23. . - . . A0.
3RF23. . - . . A1.
3RF23. . - . . A4.
3RF24. . - . A. 4.
3RF24. . - . A. 5.
Us = 24 V DC
Us = 24 V AC/DC
Us = 4...30 V DC
Us = 4...30 V DC
Us = 230 V AC
Screw, spring-loaded and
ring cable connection

Mounting:
The module can be mounted onto all 3RF21, 3RF22 solid state relays and 3RF23, 3RF24 solid
state contactors with a control voltage of 24 V AC/DC. After disconnection of the A1-A2 control
terminal from the solid state switching devices, the converter can be snapped on. All connections
to the basic device are realized thereby. The control terminal of the solid state relay or contactor is
plugged into the function modules A1-A2 terminal.
For dismounting, the converter must be manually withdrawn from the device in a vertical direction.

1
Attention!
This product was constructed as a EMC Class A device. The use of this product in residential applications
could lead to radio interferences. In such an application, additional filtering may be required.
Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS Solid-state Switching Devices
3RF2900-0EA18 Converter Function Module

Commissioning:
Apply a control voltage of 24 V AC/DC to terminal A1-A2. As soon as the voltage at the analog
input exceeds 0.3 V, the converter switches the solid state switching device ON and OFF in
accordance with the analog input voltage. For switch-off, the analog voltage must be reduced to
below 0.3 V or the supply voltage must be disconnected.

Characteristic analog input 0 10 V:

Subject to changes 07/2010 Page 3/4
http://www.siemens.com/solid-state-switching-devices




Below a value of 0.3 V,
the connected solid state
switching devices is not
actuated, above 9.6 V, it is
permanently switched on.









Characteristic Curve:
> 9,6 V
C
o
n
t
r
o
l

m
e
t
h
o
d
0 %
100 %
< 0,3 V
Analog input 0 - 10 V
5,0 V
50 %

























9,6 V
0,3 V

Siemens AG Low-Voltage Controls and Distribution Data Sheet
SIRIUS Solid-state Switching Devices
3RF2900-0EA18 Converter Function Module
Subject to changes 07/2010 Page 4/4
http://www.siemens.com/solid-state-switching-devices
Dimension Drawings: Device Circuit Diagram:



A1 ~
+
A2 ~
-
0V -
10V +
1)













3RF2900-0EA18
Us = 24 V AC/DC










Example Circuit Diagram

1/N/PE 50 Hz 230 V
1 L
2 T
A2 -
A1 +
N
PE
L
F1
K1
R
S1
ON /OFF
F2

A1 ~
+
A2 ~
-
0V -
10V +
1)
A1
0V -
10V +
L ~
-
L ~
+
AC / DC 24 V

A1 Temperature controller
with analog output
F1 Main circuit fuse
(semiconductor protection
recommended)
F2 Control circuit fuse
K1 3RF2 solid state relay with
plugged-on converter module
R Load resistance
S1 ON-/OFF-switch

1) Internal connection to the
solid state switching device
Solid-state switching devices
SIRIUS Innovations
SIRIUS 3RF34 Solid-state switching devices -
Overview of technical data
Product Information 11/2011
Industrial Controls
Answers for industry.
VOLTAR

SIRIUS 3RF34 solid-state switching
devices - Overview of technical data

___________________
___________________
___________________
___________________
___________________
___________________
___________________

Industrial Controls
Solid-state switching devices
SIRIUS 3RF34 solid-state switching
devices - Overview of technical data
Product Information


11/2011

Introduction

1

Safety notes

2

Product description

3

Application planning

4

Technical data

5

Circuit diagrams

6

Dimension drawings
(dimensions in mm)

7


Legal information

Legal information
Warning notice system
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent
damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert
symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are
graded according to the degree of danger.
DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.
WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.
CAUTION
with a safety alert symbol, indicates that minor personal injury can result if proper precautions are not taken.
CAUTION
without a safety alert symbol, indicates that property damage can result if proper precautions are not taken.
NOTICE
indicates that an unintended result or situation can occur if the relevant information is not taken into account.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will
be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to
property damage.
Qualified Personnel
The product/system described in this documentation may be operated only by personnel qualified for the specific
task in accordance with the relevant documentation, in particular its warning notices and safety instructions.
Qualified personnel are those who, based on their training and experience, are capable of identifying risks and
avoiding potential hazards when working with these products/systems.
Proper use of Siemens products
Note the following:
WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical
documentation. If products and components from other manufacturers are used, these must be recommended
or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and
maintenance are required to ensure that the products operate safely and without any problems. The permissible
ambient conditions must be complied with. The information in the relevant documentation must be observed.
Trademarks
All names identified by are registered trademarks of Siemens AG. The remaining trademarks in this publication
may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software
described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the
information in this publication is reviewed regularly and any necessary corrections are included in subsequent
editions.

Siemens AG
Industry Sector
Postfach 48 48
90026 NRNBERG
GERMANY

11/2011 Technical data subject to change
Copyright Siemens AG 2011.
All rights reserved

SIRIUS 3RF34 solid-state switching devices - Overview of technical data
Product Information, 11/2011 5
Table of contents

1 Introduction................................................................................................................................................ 7
2 Safety notes............................................................................................................................................... 9
2.1 Standards.....................................................................................................................................11
3 Product description.................................................................................................................................. 13
3.1 Device versions............................................................................................................................13
3.2 Solid-state switching devices.......................................................................................................15
3.3 Device labels................................................................................................................................17
4 Application planning................................................................................................................................. 21
4.1 Applications..................................................................................................................................21
4.2 Application planning.....................................................................................................................22
4.3 Application environment...............................................................................................................24
4.4 Short-circuit protection.................................................................................................................25
4.4.1 Mounting accessories for the load feeder conforming to IEC......................................................25
4.4.1.1 3RF34 solid-state contactors - coordination 1 and 2 conforming to IEC (fused design) .............25
4.4.1.2 3RF34 solid-state reversing contactors - coordination 1 and 2 conforming to IEC (fused
design) .........................................................................................................................................27
4.4.2 Mounting accessories for the load feeder conforming to UL .......................................................29
4.4.2.1 SCCR short-circuit current ratings ...............................................................................................29
4.4.2.2 Fuses ...........................................................................................................................................30
5 Technical data ......................................................................................................................................... 33
5.1 General data ................................................................................................................................33
5.2 Conductor cross-sections for solid-state contactors....................................................................35
5.3 Conductor cross-sections for solid-state reversing contactors....................................................36
5.4 Solid-state contactors 3RF34, 3-phase, screw connection .........................................................37
5.5 Solid-state contactors 3RF34, 3-phase, spring-loaded terminals................................................38
5.6 Solid-state contactors - fuseless design with CLASS 10 motor starter protector ........................39
5.7 Solid-state contactors - fused design with 3RB30 overload relay ...............................................40
5.8 Solid-state contactors - main circuit, 2-phase controlled.............................................................41
5.9 Solid-state contactors with control circuit.....................................................................................41
5.10 Solid-state reversing contactor with integration of four current paths to form a single
reversing circuit ............................................................................................................................42
5.11 Solid-state contactors - fuseless design with CLASS 10 motor starter protector ........................42
5.12 Solid-state contactor - fused design with 3RB30 overload relay .................................................43
5.13 Solid-state reversing contactor - main circuit, 2-phase controlled...............................................43
Table of contents

SIRIUS 3RF34 solid-state switching devices - Overview of technical data
6 Product Information, 11/2011
5.14 Solid-state reversing contactor with control circuit...................................................................... 44
5.15 Characteristics - switching frequency/load.................................................................................. 45
5.15.1 Characteristics for the solid-state contactor................................................................................ 45
5.15.2 Characteristics for the solid-state reversing contactor................................................................ 50
6 Circuit diagrams....................................................................................................................................... 55
7 Dimension drawings (dimensions in mm) ................................................................................................ 59
7.1 Solid-state switching devices ...................................................................................................... 59
7.2 Link module for motor starter protector....................................................................................... 60
Index........................................................................................................................................................ 61

SIRIUS 3RF34 solid-state switching devices - Overview of technical data
Product Information, 11/2011 7
Introduction 1

Required basic knowledge
To understand these operating instructions you should have a general knowledge of
automation engineering and low-voltage switchgear.
Recycling and disposal
These devices can be recycled thanks to their low pollutant content. For environmentally-
friendly recycling and disposal of your electronic waste, please contact a company certified
for the disposal of electronic waste.
Up-to-the-minute information
You can obtain further assistance by calling the following numbers:
Technical Assistance:
Telephone: +49 (0) 911-895-5900 (8 a.m. to 5 p.m. CET)
Fax: +49 (0) 911-895-5907
or on the Internet at:
E-mail: (mailto:technical-assistance@siemens.com)
Internet: (www.siemens.com/industrial-controls/technical-assistance)
Introduction

SIRIUS 3RF34 solid-state switching devices - Overview of technical data
8 Product Information, 11/2011

SIRIUS 3RF34 solid-state switching devices - Overview of technical data
Product Information, 11/2011 9
Safety notes 2

Correct usage

NOTICE
Radio frequency interference in residential areas
This product is a Class A device. Its use in residential areas can cause radio frequency
interference.
In this case, the user can be held liable for taking additional measures to attenuate such
interference.

Safety measures

CAUTION
Inter-phase short circuit due to overvoltage on solid-state reversing contactors
In the event of a short circuit, the switching devices in the load feeder can put persons and
property at risk.
For fused configurations, the protective device has to be replaced following a short circuit.
To reduce the risk of an inter-phase short circuit due to overvoltage, we recommend
connecting a 3TX7 462-3L type varistor between L1 and L3. We recommend a fused
design with semiconductor protection to provide short-circuit protection.

NOTICE
Inter-phase short circuit with solid-state reversing contactors in automatic mode
If the primary voltage is applied at the solid-state reversing contactors at the same time as
the control voltage is switched on, the integrated RC surge suppressor may respond in
some cases. If it does, dependent on actuation, two thyristors in the reversing circuit may
activate, thereby producing an inter-phase short circuit.
To be sure of avoiding this response, once the primary voltage has been applied, a delay of
40 ms should be allowed to elapse before the control inputs are activated.

Safety notes

SIRIUS 3RF34 solid-state switching devices - Overview of technical data
10 Product Information, 11/2011
CAUTION
Electromagnetic interference on the solid-state reversing contactors
Star-connected three-phase motors (particularly <1 kW) with electromechanical contactors
can cause significant electromagnetic interference. Such interference can cause solid-state
reversing contactors being used in the vicinity to malfunction.
Provision should be made for appropriate EMC surge suppressors on the sources of
interference.


Safety notes
2.1 Standards
SIRIUS 3RF34 solid-state switching devices - Overview of technical data
Product Information, 11/2011 11
2.1 Standards
Standards and approvals
IEC 60947-4-2
UL 508, CSA for North America
1)

CE mark for Europe
C-Tick approval for Australia
CCC for China
1)
Please note: Use overvoltage protection device;
max. cut-off-voltage 6000 V;
min. energy handling capability 100J.
Applicable standards
The product meets the requirements of the following standards:
Table 2- 1 Applied standards (product)
Applications Standard
Device standard DIN IEC 60947-4-2
Terminal designations/Terminal markings DIN EN 50011
Degree of protection IP20 DIN IEC 0529
Vibration resistance DIN IEC 60068-2-6
Shock resistance DIN IEC 60068-2-27
EMC standard DIN IEC 60947-4-2; DIN IEC 61000-4-2;
DIN IEC 61000-4-6; DIN IEC 61000-4-4;
DIN IEC 61000-4-5
Resistance to extreme climates DIN IEC 60068-2-61 (sequence of tests),
DIN IEC 60068-2-30 (damp heat),
DIN IEC 60068-2-2 (dry heat),
DIN IEC 60068-2-1 (cold),
DIN IEC 60068-2-14 (temperature change)


Safety notes
2.1 Standards
SIRIUS 3RF34 solid-state switching devices - Overview of technical data
12 Product Information, 11/2011

SIRIUS 3RF34 solid-state switching devices - Overview of technical data
Product Information, 11/2011 13
Product description 3
3.1 Device versions
Solid-state switching devices are primarily used in single-phase applications, which have to
meet the following requirements:
Very high switching frequencies (> 1000 switching operations per hour)
Resistive loads

The SIRIUS modular system features single- and three-phase solid-state contactors and
solid-state relays for the frequent switching of resistive loads. Three-phase solid-state
contactors and solid-state reversing contactors are available for switching motorized loads.
Standardized function modules for various applications complete the range of SIRIUS solid-
state switching devices.
The solid-state contactor and solid-state reversing contactor versions listed in this manual
are intended specifically for operation on three-phase motors up to 7.5 kW.
Overview
These 2-phase controlled instantaneous switching solid-state switching devices are operated
in two mounting widths in an insulating enclosure:
In 45 mm width
Up to 5.2 A as solid-state contactor (motor contactor) or
Up to 5.4 A as solid-state reversing contactor and
In 90 mm width
Up to 16 A as solid-state contactor or
Up to 7.4 A as solid-state reversing contactor
This means that it is possible to operate motors up to 7.5 kW.
The solid-state contactors and solid-state reversing contactors for screw-type connection can
be connected directly to a motor starter protector with a 3RA2921-1BA00 link module. Direct
mounting of a 3RB30/3RB31 solid-state overload relay and, in some cases, a 3RR2 current
monitoring relay, is also possible. This provides a time-saving way of implementing rapid-
switching motor feeders with and without fuses.
Product description
3.1 Device versions
SIRIUS 3RF34 solid-state switching devices - Overview of technical data
14 Product Information, 11/2011
Versions
The following table provides an overview of the versions of the 3RF34 instantaneous
switching solid-state contactors for switching motors.
Table 3- 1 Versions of solid-state switching devices
Characteristic Versions
Version Solid-state contactor Solid-state reversing contactor
Description Complete devices in insulated enclosures for
frequent switching on and switching off of
AC drives.
Compact design of the reversing circuit for
frequent switching on and switching off of AC
drives with continuous reversal of the
direction of rotation
Order numbers 3RF34..-.BB.. 3RF34..-.BD..
Size S0
Width (motor power
1)
/max.
rated operational current)
45 mm (motors up to 2.2 kW, 5.2 A)
90 mm (motors up to 7.5 kW, 16 A)
45 mm (motors up to 2.2 kW, 5.4 A)
90 mm (motors up to 3.0 kW, 7.4 A)
Number of poles 3 3
Connection system Screw-type and spring-loaded terminals Screw-type
Rated operating voltage Up to 600 V Up to 480 V
Rated control supply
voltage
24 V DC and 110 to 230 V AC
Switching delay
ON-delay
OFF-delay

1 ms (24 V DC), 5 ms (110 to 230 V AC)
1 ms (24 V DC), 30 ms (110 to 230 V AC)
plus up to one half-wave

5 ms (24 V DC), 20 ms (110 to 230 V AC)
5 ms (24 V DC), 10 ms (110 to 230 V AC)
plus up to one half-wave
Interlock time 60 to 100 ms (24 V DC), 50 to 100 ms (110 to 230 V AC)
Enclosure Insulated (no grounding required)
Control connections Screw-type connection system and spring-
loaded connection system, removable
terminal for auxiliary circuit wiring
(2 contacts)
Screw-type connection system, removable
terminal for auxiliary circuit wiring (3 contacts)
1)
Rating data relates to 400 V line voltage
Product description
3.2 Solid-state switching devices
SIRIUS 3RF34 solid-state switching devices - Overview of technical data
Product Information, 11/2011 15
3.2 Solid-state switching devices
Operator controls and equipment
Solid-state contactor
1
2
3
4
1
2
5 5
3
4

Operator control/Equipment Function
1 Solid-state contactor Frequent switching on and switching off of AC drives
2 Screw-type connection
system/Spring-loaded
connection system
Main circuit terminals infeed/line side
3 LED The yellow LED lights up when the control voltage is
applied.
4 Plug-in control connection
(2 terminals)
Removable terminals for the control circuit
5 Screw-type connection
system/Spring-loaded
connection system
Main circuit terminals outgoing feeder motor/load side
Figure 3-1 Solid-state contactor overview - Screw-type connection system and spring-loaded
connection system
Product description
3.2 Solid-state switching devices
SIRIUS 3RF34 solid-state switching devices - Overview of technical data
16 Product Information, 11/2011
Solid-state reversing contactor
1
2
5
3
4

Operator control/Equipment Function
1 Solid-state contactor Frequent switching on and switching off of AC drives
2 Screw-type connection system Main circuit terminals infeed/line side
3 LEDs The left-hand LED lights up yellow when counterclockwise
rotation is activated (control voltage applied at terminal A1
and A2).
The right-hand LED lights up yellow when clockwise rotation
is activated (control voltage applied at terminal A3 and A2).
4 Plug-in control connection
(3 terminals)
Removable terminals for the control circuit
5 Screw-type connection system Main circuit terminals outgoing feeder motor/load side
Figure 3-2 Solid-state reversing contactor overview - Screw-type connection system
Product description
3.3 Device labels
SIRIUS 3RF34 solid-state switching devices - Overview of technical data
Product Information, 11/2011 17
3.3 Device labels
Device labels
1L1 3L2 5L3
2T1 4T2 6T3
SIRIUS
24V
+
A1
DC
-
A2
3
R
F
3
4
.
.
-
1
B
B
.
.
G
/
0
9
0
5
0
6




*
E
0
1
*
2
5
1
4
7
3
6

1 Labeling to identify the main circuit terminals infeed/line side
2 SIRIUS (device group)
3 Production date/Product version
4 Labeling to identify the main circuit terminals outgoing feeder motor/load side
5 Order designation
6 Labeling to identify the control circuit terminals and indication of the control voltage
(See also the diagrams below, "Labeling on solid-state contactors, zoom view".)
7 Circuit diagram
Figure 3-3 Labeling to identify solid-state contactors with screw-type connection system

Product description
3.3 Device labels
SIRIUS 3RF34 solid-state switching devices - Overview of technical data
18 Product Information, 11/2011
24V
+
A1
DC
-
A2
1L 1 3L 2 5L 3
1L 1 3L 2 5L 3
SIRIUS
3
R
F
3
4
.
.
-
2
B
B
.
.
G
/
0
9
0
5
0
6




*
E
0
1
*
2
5
1
4
7
3
6

1 Labeling to identify the main circuit terminals infeed/line side
2 SIRIUS (device group)
3 Production date/Product version
4 Labeling to identify the main circuit terminals outgoing feeder motor/load side
5 Order designation
6 Labeling to identify the control circuit terminals and indication of the control voltage
(See also the diagrams below, "Labeling on solid-state contactors, zoom view".)
7 Circuit diagram
Figure 3-4 Labeling to identify solid-state contactors with spring-loaded terminals

110-230V AC
A1 A2

Figure 3-5 Labeling on solid-state contactors with AC control voltage, zoom view

24V
+
A1
DC
-
A2

Figure 3-6 Labeling on solid-state contactors with DC control voltage, zoom view

Product description
3.3 Device labels
SIRIUS 3RF34 solid-state switching devices - Overview of technical data
Product Information, 11/2011 19
1L1 3L2 5L3
SIRIUS

+
A1

+
A3

-
A2
3
R
F
3
4
.
.
-
1
B
D
.
.
G
/
0
9
0
5
0
6




*
E
0
1
*
24V DC
2T1 4T2 6T3
2
5
1
4
7
3
6

1 Labeling to identify the main circuit terminals infeed/line side
2 SIRIUS (device group)
3 Production date/Product version
4 Labeling to identify the main circuit terminals outgoing feeder motor/load side
5 Order designation
6 Labeling to identify the control circuit terminals and indication of the control voltage
(See also the diagrams below, "Labeling on solid-state reversing contactors, zoom view".)
7 Circuit diagram
Figure 3-7 Labeling to identify solid-state reversing contactors with screw connection

110-230V AC
A1 A2 A3

Figure 3-8 Labeling on solid-state reversing contactors with AC control voltage, zoom view


+
A1

+
A3

-
A2
24V DC

Figure 3-9 Labeling on solid-state reversing contactors with DC control voltage, zoom view
Product description
3.3 Device labels
SIRIUS 3RF34 solid-state switching devices - Overview of technical data
20 Product Information, 11/2011

SIRIUS 3RF34 solid-state switching devices - Overview of technical data
Product Information, 11/2011 21
Application planning 4
4.1 Applications
Solid-state switching devices for switching motors
The solid-state contactors for the wear-free and noiseless switching of motors are designed
for the frequent switching on and switching off of AC drives up to 7.5 kW as well as for
reversing up to 3.0 kW. The devices are fully insulated and can be mounted directly on motor
starter protectors and overload relays or SIRIUS current monitoring relays, which makes
them really easy to integrate into motor feeders.
These 3-phase solid-state contactors are equipped with a 2-phase control which is
particularly suitable for typical motor circuits without a connection to the neutral conductor.
The integration of four current paths to form a single reversing circuit, accommodated in one
enclosure, makes the solid-state reversing contactor a particularly compact solution. Unlike
conventional systems which require two contactors, width can be reduced by up to 50% with
the 3-phase solid-state reversing contactors. Devices with a width of 45 mm cover motors up
to 2.2 kW and those with a width of 90 mm cover motors up to 3 kW.
Integration in the SIRIUS modular system facilitates connection to a SIRIUS motor starter
protector via a link module or to a 3RB30/3RB31 solid-state overload relay or a 3RR2 current
monitoring relay without additional steps. As a result, fuseless or fused motor feeders can be
implemented quickly and easily.
Main features:
Insulated enclosure with integrated heat sink
Degree of protection IP20
Integrated mounting foot for snapping on a DIN rail or mounting on a support plate
Variety of connection systems
Plug-in control connection
LED to indicate control voltage

Application planning
4.2 Application planning
SIRIUS 3RF34 solid-state switching devices - Overview of technical data
22 Product Information, 11/2011
4.2 Application planning
Notes about integration into load feeders
Thanks to their industrial connection system and type of design, SIRIUS solid-state switching
devices can be integrated into load feeders very easily.
However, particular attention must be paid to the circumstances of installation and ambient
conditions, as the performance of the solid-state switching devices is very much dependent
on these. Each design will impose certain restrictions which have to be taken into account.
Detailed information about minimum clearances can be found in the chapter titled Technical
data (Page 33), as well as in the product data sheets.
Despite the rugged nature of the power semiconductors used, solid-state switching devices
are sensitive to short circuits in the load feeder. Consequently, special precautions have to
be taken against irreparable damage as appropriate for the type of design.
The use of SITOR semiconductor fuses is generally recommended. These fuses provide
protection against irreparable damage in the event of a short circuit even in applications
where full use is being made of solid-state contactors.
Alternatively, in the case of a lower load, protection can also be provided by standard fuses
or miniature circuit breakers. This protection is achieved by overdimensioning the solid-state
switching devices accordingly. The technical data and the product data sheets contain
information about protection based on semiconductor fuses only as well as on the use of
SIRIUS devices with conventional protective devices.
Solid-state motor and reversing contactors can easily be combined with 3RV motor starter
protectors and circuit breakers, 3RB3 solid-state overload relays and 3RR2 current
monitoring relays from the SIRIUS modular system. As a result, fuseless and fused motor
feeders can be implemented easily and without taking up too much space.

Note
Running star-connected three-phase motors (particularly with power ratings < 1 kW) with
electromechanical contactors can cause significant electromagnetic interference. Such
interference, which exceeds permissible limit values, can cause solid-state switching devices
operating in the vicinity to malfunction.
In the case of high levels of electromagnetic interference we recommend equipping motors
up to 5.5 kW which are controlled using 3RT20 1 electromechanical contactors with EMC
surge suppressors. 3-phase RC interference suppression modules like the 3RT29 16-1PA1
(up to 400 V) provide the best filtering effect. Corresponding modules for the contactors are
listed in the product chapter titled "Contactors and contactor assemblies", under
"Accessories". Varistor interference suppression modules should not be used, as they are
not capable of filtering out rapid transients to the required extent.

Application planning
4.2 Application planning
SIRIUS 3RF34 solid-state switching devices - Overview of technical data
Product Information, 11/2011 23
Selecting solid-state contactors
Solid-state contactors are selected on the basis of the line, the load, and the ambient
conditions.
The following procedure is recommended:
Determine the rated current of the load and the line voltage.
Select a solid-state contactor with a rated current which is higher than or at least equal to
the load.
Check the maximum permissible switching frequency based on the characteristic curves.
To do this, you must know the starting current, the start time, and the motorized load
during the operating phase.
If the permissible switching frequency is below the required switching frequency, it can
only be increased by overdimensioning the motor.
Alternatively, the correct device size can be determined by entering the line data, the
motor data, the application, and the ambient conditions in the "Selection of solid-state
contactors for switching motors (https://eb.automation.siemens.com/spicecad/dc-web-
app/main/index.jsf)" tool on the Internet.
Load feeders
There is no such thing as a typical design for a load feeder with solid-state relays or solid-
state contactors. Rather, the variety of connection systems and control voltages support
universal possible applications. SIRIUS solid-state relays and solid-state contactors can be
installed in either fuseless or fused feeders.

Application planning
4.3 Application environment
SIRIUS 3RF34 solid-state switching devices - Overview of technical data
24 Product Information, 11/2011
4.3 Application environment
General operating conditions
The following table lists the general operating conditions under which the product may be
operated.
Table 4- 1 General operating conditions
Operating conditions Value
Degree of protection IP20
Ambient temperature during operation - 25 to 60 C
Installation altitude 0 to 1000 m;
at > 1,000 m seek advice from Technical Assistance
(www.siemens.com/industrial-controls/technical-
assistance)
Shock resistance 15 g/11 ms; acc. to DIN IEC 68-2-27
Vibration resistance 2 g; acc. to DIN IEC 68-2-6
EMC conditions Acc. to DIN IEC 60947-4-2, DIN IEC 61000-4-2,
DIN IEC 61000-4-4, DIN IEC 61000-4-5, and
DIN IEC 61000-4-6,
Insulation strength 50/60 Hz 4,000 Vrms
Types of coordination
Standard DIN EN 60947-4-1 (VDE 0660 Part 102) or IEC 60947-4-1 distinguishes between
two types of coordination (type of coordination), which are referred to as coordination type
"1" and coordination type "2". The short circuit that needs to be dealt with is cleared reliably
and safely with both types of coordination; the only differences are in the extent of the
damage sustained by the device following a short circuit.
Type of coordination 1
It is permissible for the fuseless load feeder to be incapable of functioning after each short-
circuit disconnection. Damage to the contactor and the overload release is also permissible.
For 3RA2, the motor starter protector alone always achieves type of coordination "2".
Type of coordination 2
After short-circuit disconnection, there must be no damage to the overload release or to any
other part. The 3RA2 fuseless load feeder can resume operation without any parts having to
be repaired or replaced. Welding of the contactor contacts only is permitted if these can be
separated easily without significant deformation.
Application planning
4.4 Short-circuit protection
SIRIUS 3RF34 solid-state switching devices - Overview of technical data
Product Information, 11/2011 25
4.4 Short-circuit protection
4.4.1 Mounting accessories for the load feeder conforming to IEC
4.4.1.1 3RF34 solid-state contactors - coordination 1 and 2 conforming to IEC (fused design)
Combining 3RF34 solid-state contactors, type of coordination 1 (type 1), with 3RB3 overload relays
3RF34 solid-state contactors can be combined with the following 3RB3 overload relays in
conformance with type of coordination 1 (type 1):
Table 4- 2 Order designations for 3RB3 overload relays
Overload relay Solid-state contactor Maximum permissible fuse links at
400 V; operating class gG
Order
designation
Adjustment range Order designation Rated
current
Order
designation
Rated current
3RB3.2.-N.. 0.32 to 1.25 A 3RF3405-xBByz 4 A
3RB3.2.-P.. 1 to 4 A 3RF3405-xBByz 4 A
3RB3.2.-S.. 3 to 12 A 3RF3405-xBByz 4 A
3NW6210-1
3NA6810-6
25 A
3RB3.2.-N.. 0.32 to 1.25 A 3RF3410-xBByz 7.8 A
3RB3.2.-P.. 1 to 4 A 3RF3410-xBByz 7.8 A
3RB3.2.-S.. 3 to 12 A 3RF3410-xBByz 7.8 A
3RB3.2.-Q.. 6 to 25 A 3RF3410-xBByz 7.8 A
3NW6217-1
3NA6817-6
40 A
3RB3.2.-N.. 0.32 to 1.25 A 3RF3412-xBByz 9.5 A
3RB3.2.-P.. 1 to 4 A 3RF3412-xBByz 9.5 A
3RB3.2.-S.. 3 to 12 A 3RF3412-xBByz 9.5 A
3RB3.2.-Q.. 6 to 25 A 3RF3412-xBByz 9.5 A
3NW6117-1
3NA6817-6
40 A
3RB3.2.-N.. 0.32 to 1.25 A 3RF3416-xBByz 11 A
3RB3.2.-P.. 1 to 4 A 3RF3416-xBByz 11 A
3RB3.2.-S.. 3 to 12 A 3RF3416-xBByz 11 A
3RB3.2.-Q.. 6 to 25 A 3RF3416-xBByz 11 A
3NW6117-1
3NA6817-6
40 A


Application planning
4.4 Short-circuit protection
SIRIUS 3RF34 solid-state switching devices - Overview of technical data
26 Product Information, 11/2011
Table 4- 3 Supplements to order numbers:
x = type of connection system

1 = screw connection
2 = spring-loaded terminals
y = type of control voltage

0 = 24 V DC acc. to EN 61131-2
2 = 110 to 230 AC
z = type of rated control voltage

4 = 48 to 480 V
6 = 48 to 600 V
Combining 3RF34 solid-state contactors, type of coordination 2 (type 2), with 3RB3 overload relays
3RF34 solid-state contactors can be combined with the following 3RB3 overload relays in
conformance with type of coordination 2 (type 2):
Table 4- 4 Order designations for 3RB3 overload relays
Overload relay Solid-state contactor Maximum permissible fuse links at 400 V
Order
designation
Adjustment
range
Order
designation
Rated
current
Order
designation
Rated
current
Operating class
3RB3.2.-N.. 0.32 to 1.25 A 3RF3405-xBByz 4 A 3NA3801-6
5SB2 31
6 A gG
3RB3.2.-P.. 1 to 4 A 3RF3405-xBByz 4 A 3NC1020 20 A aR
3RB3.2.-S.. 3 to 12 A 3RF3405-xBByz 4 A 3NC1020 20 A aR
3RB3.2.-N.. 0.32 to 1.25 A 3RF3410-xBByz 7.8 A 3NA3801-6
5SB2 31
6 A gG
3RB3.2.-P.. 1 to 4 A 3RF3410-xBByz 7.8 A 3NE1802-0
3NE8020-1
3NW6205-1
40 A
80 A
16 A
gR
aR
aR
3RB3.2.-S.. 3 to 12 A 3RF3410-xBByz 7.8 A 3NE1802-0
3NE8020-1
3NW6205-1
40 A
80 A
16 A
gR
aR
aR
3RB3.2.-Q.. 6 to 25 A 3RF3410-xBByz 7.8 A 3NE1802-0
3NE8020-1
3NW6205-1
40 A
80 A
16 A
gR
aR
aR
3RB3.2.-N.. 0.32 to 1.25 A 3RF3412-xBByz 9.5 A 3NA3801-6
5SB2 31
6 A gG
3RB3.2.-P.. 1 to 4 A 3RF3412-xBByz 9.5 A 3NA3807-6
5SB2 71
20 A gG
3RB3.2.-S.. 3 to 12 A 3RF3412-xBByz 9.5 A 3NE1818-0
3NC2200
63 A
100 A
gR
aR
3RB3.2.-Q.. 6 to 25 A 3RF3412-xBByz 9.5 A 3NE1818-0
3NC2200
63 A
100 A
gR
aR
3RB3.2.-N.. 0.32 to 1.25 A 3RF3416-xBByz 11 A 3NA3801-6
5SB2 31
6 A gG
3RB3.2.-P.. 1 to 4 A 3RF3416-xBByz 11 A 3NA3807-6
5SB2 71
20 A gG
3RB3.2.-S.. 3 to 12 A 3RF3416-xBByz 11 A 3NA3812 32 A gG
3RB3.2.-Q.. 6 to 25 A 3RF3416-xBByz 11 A 3NA3812 32 A gG
Application planning
4.4 Short-circuit protection
SIRIUS 3RF34 solid-state switching devices - Overview of technical data
Product Information, 11/2011 27

Table 4- 5 Supplements to order numbers:
x = type of connection system

1 = screw connection
2 = spring-loaded terminals
y = type of control voltage

0 = 24 V DC acc. to EN 61131-2
2 = 110 to 230 AC
z = type of rated control voltage

4 = 48 to 480 V
6 = 48 to 600 V


Note
For details of the fuseless design (coordination of motor starter protectors), see Technical
data (Page 33).

4.4.1.2 3RF34 solid-state reversing contactors - coordination 1 and 2 conforming to IEC (fused
design)
Combining 3RF34 solid-state reversing contactors, type of coordination 1 (type 1), with 3RB3
overload relays
3RF34 solid-state reversing contactors can be combined with the following 3RB3 overload
relays in conformance with type of coordination 1 (type 1):
Table 4- 6 Order designations for 3RB3 overload relays
Overload relay Solid-state reversing contactor Maximum permissible fuse links at 400 V,
operating class gG
Order
designation
Adjustment
range
Order
designation
Rated
current
Order
designation
Rated
current
3RB3.2.-N.. 0.32 to 1.25 A 3RF3403-xBDyz 3.8 A
3RB3.2.-P.. 1 to 4 A 3RF3403-xBDyz 3.8 A
3RB3.2.-S.. 3 to 12 A 3RF3403-xBDyz 3.8 A
3NW6210-1
3NA6810-6
25 A
3RB3.2.-N.. 0.32 to 1.25 A 3RF3405-xBDyz 5.4 A
3RB3.2.-P.. 1 to 4 A 3RF3405-xBDyz 5.4 A
3RB3.2.-S.. 3 to 12 A 3RF3405-xBDyz 5.4 A
3NW6217-1
3NA6817-6
40 A
3RB3.2.-N.. 0.32 to 1.25 A 3RF3410-xBDyz 7.4 A
3RB3.2.-P.. 1 to 4 A 3RF3410-xBDyz 7.4 A
3RB3.2.-S.. 3 to 12 A 3RF3410-xBDyz 7.4 A
3RB3.2.-Q.. 6 to 25 A 3RF3410-xBDyz 7.4 A
3NW6117-1
3NA6817-6
40 A


Application planning
4.4 Short-circuit protection
SIRIUS 3RF34 solid-state switching devices - Overview of technical data
28 Product Information, 11/2011
Table 4- 7 Supplements to order numbers:
x = type of connection system

1 = screw connection
2 = spring-loaded terminals
y = type of control voltage

0 = 24 V DC acc. to EN 61131-2
2 = 110 to 230 AC
z = type of rated control voltage

4 = 48 to 480 V
6 = 48 to 600 V
Combining 3RF34 solid-state reversing contactors, type of coordination 2 (type 2), with 3RB3
overload relays
3RF34 solid-state reversing contactors can be combined with the following 3RB3 overload
relays in conformance with type of coordination 2 (type 2):
Table 4- 8 Order designations for 3RB3 overload relays
Overload relay Solid-state reversing contactor Maximum permissible fuse links at 400 V
Order
designation
Adjustment
range
Order
designation
Rated
current
Order
designation
Rated
current
Operating class
3RB3.2.-N.. 0.32 to 1.25 A 3RF3403-xBDyz 3.8 A 3NA3801-6
5SB2 31
6 A gG
3RB3.2.-P.. 1 to 4 A 3RF3403-xBDyz 3.8 A 3NC1020 20 A aR
3RB3.2.-S.. 3 to 12 A 3RF3403-xBDyz 3.8 A 3NC1020 20 A aR
3RB3.2.-N.. 0.32 to 1.25 A 3RF3405-xBDyz 5.4 A 3NA3801-6
5SB2 31
6 A gG
3RB3.2.-P.. 1 to 4 A 3RF3405-xBDyz 5.4 A 3NE1802-0
3NE8020-1
40 A
80 A
gR
aR
3RB3.2.-S.. 3 to 12 A 3RF3405-xBDyz 5.4 A 3NE1802-0
3NE8020-1
40 A
80 A
gR
aR
3RB3.2.-N.. 0.32 to 1.25 A 3RF3410-xBDyz 7.4 A 3NA3801-6
5SB2 31
6 A gG
3RB3.2.-P.. 1 to 4 A 3RF3410-xBDyz 7.4 A 3NE1802-0
3NE8020-1
40 A
80 A
gR
aR
3RB3.2.-S.. 3 to 12 A 3RF3410-xBDyz 7.4 A 3NE1802-0
3NE8020-1
40 A
80 A
gR
aR
3RB3.2.-Q.. 6 to 25 A 3RF3410-xBDyz 7.4 A 3NE1802-0
3NE8020-1
40 A
80 A
gR
aR

Application planning
4.4 Short-circuit protection
SIRIUS 3RF34 solid-state switching devices - Overview of technical data
Product Information, 11/2011 29
Table 4- 9 Supplements to order numbers:
x = type of connection system

1 = screw connection
2 = spring-loaded terminals
y = type of control voltage

0 = 24 V DC acc. to EN 61131-2
2 = 110 to 230 AC
z = type of rated control voltage

4 = 48 to 480 V
6 = 48 to 600 V


Note
For details of the fuseless design (coordination of motor starter protectors), see Technical
data (Page 33).

4.4.2 Mounting accessories for the load feeder conforming to UL
4.4.2.1 SCCR short-circuit current ratings
SCCR short-circuit current ratings
The SCCR (Short Circuit Current Rating) indicates the maximum permissible short-circuit
current for a switching device. A higher value can only be achieved in combination with
protection devices such as fuses or circuit breakers.
This rating is required for mounting accessories in control cabinets conforming to
UL 508A. The switching device or switchgear assembly with the lowest value specifies
the value for the entire control cabinet.
A low value makes engineering the supply voltage for the control cabinet difficult.
3RF3 solid-state switching devices have a standard short-circuit value of 5 kA conforming
to UL 508.
Tests with a short-circuit value of 65 kA (High Capacity Short Circuit Current Ratings)
have also been carried out. The UL reports include details of possible combinations with
Class CC and Class J fuses, as well as with a number of circuit breakers.
Application planning
4.4 Short-circuit protection
SIRIUS 3RF34 solid-state switching devices - Overview of technical data
30 Product Information, 11/2011
4.4.2.2 Fuses
Fuse ratings for solid-state contactors
Table 4- 10 Fuses for protecting against high short-circuit currents
Fuses
3RF34 Max. size [A] Class Type Current [kA] Voltage [V]
3RF3405-.BB 25 J TD 65 480
3RF3405-.BB 45 J TD 65 600
3RF3410-.BB 45 J TD 65 480
3RF3410-.BB 45 J TD 65 600
3RF3412-.BB 45 J TD 65 480
3RF3412-.BB 50 J TD 65 600
3RF3416-.BB 50 J TD 65 480
3RF3416-.BB 50 J TD 65 600
Fuse ratings for solid-state reversing contactors
Table 4- 11 Fuses for protecting against high short-circuit currents
Fuses
3RF34 Max. size [A] Class Type Current [kA] Voltage [V]
3RF3403-.BD 45 J TD 65 480
3RF3405-.BD 45 J TD 65 480
3RF3410-.BD 45 J TD 65 480
Circuit breakers for protecting against high short-circuit currents
Table 4- 12 Circuit breaker ratings for solid-state contactors
Fuses
3RF34 Max. size [A] Type Current [kA] Voltage [V]
3RF3405-.BB 4 3RV1721 50 480
3RF3405-.BB 4 3RV1721 10 600
3RF3410-.BB 8 3RV1721 5 600
3RF3412-.BB 8 3RV1721 5 600
3RF3416-.BB 8 3RV1721 5 600
3RF3416-.BB 10 3RV1721 5 600

Application planning
4.4 Short-circuit protection
SIRIUS 3RF34 solid-state switching devices - Overview of technical data
Product Information, 11/2011 31
Table 4- 13 Circuit breaker ratings for solid-state reversing contactors
Fuses
3RF34 Max. size [A] Type Current [kA] Voltage [V]
3RF3403-.BD 4 3RV1721 50 480
3RF3405-.BD 5 3RV1721 30 480
3RF3410-.BD 8 3RV1721 5 480


NOTICE
Short-circuit currents
Short-circuit currents can result in material damage.
When combining solid-state switching devices and overload relays the device with the
lowest rated value is decisive as regards short-circuit fuse protection.

Semiconductor fuses
SITOR fuses can be used as an alternative to UL fuses. Here too, the relevant data has
been included in the UL reports. Protection of the semiconductors is much better when
SITOR semiconductor fuses are used (comparable with type of coordination type 2).
The following applies to UL applications:
SITOR fuses are not feeder protective devices but only "special purpose fuses".
Table 4- 14 Fuse protection with semiconductor fuses
Fuse
3RF34 Max. size [A] Type Current [kA] Voltage [V]
3RF3405-.BB 16 3NE1813-0 65 480
3RF3405-.BB 32 3NE4101 65 480
3RF3405-.BB 25 3NE8715-1 65 480
3RF3405-.BB 25 3NE8015-1 65 480
3RF3405-.BB 35 3NE1803-0 65 600
3RF3405-.BB 50 3NE4117 65 600
3RF3405-.BB 50 3NE8717-1 65 600
3RF3405-.BB 63 3NE8018-1 65 600
3RF3410-.BB 35 3NE1803-0 65 600
3RF3410-.BB 50 3NE4117 65 600
3RF3410-.BB 50 3NE8717-1 65 600
3RF3410-.BB 63 3NE8018-1 65 600
3RF3412-.BB 63 3NE1818-0 65 480
3RF3412-.BB 50 3NE1817-0 65 600
3RF3412-.BB 50 3NE4117 65 600
Application planning
4.4 Short-circuit protection
SIRIUS 3RF34 solid-state switching devices - Overview of technical data
32 Product Information, 11/2011
Fuse
3RF34 Max. size [A] Type Current [kA] Voltage [V]
3RF3412-.BB 50 3NE8717-1 65 600
3RF3412-.BB 63 3NE8018-1 65 600
3RF3412-.BB 80 3NE1020-2 65 600
3RF3416-.BB 63 3NE1818-0 65 480
3RF3416-.BB 50 3NE1817-0 65 600
3RF3416-.BB 50 3NE4117 65 600
3RF3416-.BB 50 3NE8717-1 65 600
3RF3416-.BB 63 3NE8018-1 65 600
3RF3416-.BB 80 3NE1020-2 65 600
3RF3403-.BD 35 3NE1803-0 65 480
3RF3403-.BD 50 3NE4117 65 480
3RF3403-.BD 50 3NE8717-1 65 480
3RF3403-.BD 63 3NE8018-1 65 480
3RF3405-.BD 35 3NE1803-0 65 480
3RF3405-.BD 50 3NE4117 65 480
3RF3405-.BD 50 3NE8717-1 65 480
3RF3405-.BD 63 3NE8018-1 65 480
3RF3410-.BD 35 3NE1803-0 65 480
3RF3410-.BD 50 3NE4117 65 480
3RF3410-.BD 50 3NE8717-1 65 480
3RF3410-.BD 63 3NE8018-1 65 480

SIRIUS 3RF34 solid-state switching devices - Overview of technical data
Product Information, 11/2011 33
Technical data 5
5.1 General data
Table 5- 1 Solid-state switching devices - General data
General data
Ambient temperature
Operation, derating as of 40 C C - 25 to + 60
Storage C - 55 to + 80
Installation altitude m 0 to 1000;
at > 1,000 m seek advice from Technical Assistance
(www.siemens.com/industrial-controls/technical-
assistance)
Shock resistance according to DIN IEC 60068-2-27 g/ms 15/11
Vibration resistance; acc. to DIN IEC 60068-2-6 g 2
Degree of protection IP20
Electromagnetic compatibility (EMC)
Emitted interference acc. to DIN IEC 60947-4-2
- Conducted interference Class A for industrial environments
1)

- Emitted high-frequency interference
voltage
Class A for industrial environments
Immunity
2)

- Electrostatic discharge acc. to
DIN IEC 61000-4-2 (corresponds to
severity 3)
kV Contact discharge: 4; air discharge: 8; behavior criterion 2
- Induced conducted RF fields
acc. to DIN IEC 61000-4-6
MHz 0.15 to 80, 140 dBV, behavior criterion 1
- High-frequency, electromagnetic
fields acc. to DIN IEC 61000-4-3
MHz 80 to 3,000; test level 10 V/m; behavior criterion 1
- Burst acc. to DIN IEC 61000-4-4 kV 2/5.0 kHz; behavior criterion 1
- Surge acc. to DIN IEC 61000-4-5
3)
kV Conductor - protective conductor 2; conductor - conductor:
1; behavior criterion 2
Connection type

Solid-state contactor Screw-type and spring-loaded

Solid-state reversing contactor Screw-type connection system
Technical data
5.1 General data
SIRIUS 3RF34 solid-state switching devices - Overview of technical data
34 Product Information, 11/2011
General data
Permissible mounting position
10
10 10
10

Insulation strength at 50/60 Hz
(main/control circuit to floor)
V rms 4000
1)
These products are Class A products. Their use in residential areas can cause radio frequency interference. In this
case, the user can be held liable for taking additional measures to attenuate such interference.
2)
Running star-connected three-phase motors (particularly < 1 kW) with electromechanical contactors can cause
significant electromagnetic interference. Such interference can cause solid-state reversing contactors being used in the
vicinity to malfunction. Provision should be made for appropriate EMC surge suppressors on the sources of interference.
Suitable surge suppressors are described in Chapter 6 of Catalog IC10.
3)
For solid-state reversing contactors, the following applies: To maintain the values a 3TX7 462-3L surge suppressor (see
Catalog IC10) should be used between phases L1 and L3, as close as possible to the reversing contactor.
Technical data
5.2 Conductor cross-sections for solid-state contactors
SIRIUS 3RF34 solid-state switching devices - Overview of technical data
Product Information, 11/2011 35
5.2 Conductor cross-sections for solid-state contactors
Conductor cross-sections for solid-state contactors
Table 5- 2 Connection of main contacts with screw-type connection system or spring-loaded connection system
Connection, main contacts Screw connection Spring-loaded
connection
Conductor cross-section
Solid
mm 2 x (1.5 to 2.5), 2 x (1.5 to 6) 2 x (0.5 to 2.5)
Finely stranded with end sleeve
mm 2 x (1.5 to 2.5), 2 x (1.5 to 6) 2 x (0.5 to 1.5)
Finely stranded without end sleeve
mm 1 x 10 2 x (0.5 to 2.5)
Solid or stranded
AWG 2 x (14 to 10) 2 x (18 to 14)
Stripped length mm 10 10
Connection screw M4
Tightening torque Nm 2 to 2.5
D 5 to 6 mm/PZ 2 Ib in 18 to 22

Table 5- 3 Connection of main contacts and control contacts with screw-type connection system or spring-loaded
connection system
Connection, auxiliary contacts, and control
contacts
Screw connection Spring-loaded
connection
Conductor cross-section with end sleeve mm 1 x (0.5 to 2.5), 0.5 to 2.5
Conductor cross-section without end sleeve mm 2 x (0.5 to 1.0)
AWG 20 to 12 20 to 12
Stripped length mm 7 10
Connection screw M3
Tightening torque Nm 0.5 to 0.6
D 3.5/PZ 1 Ib in 4.5 to 5.3
Technical data
5.3 Conductor cross-sections for solid-state reversing contactors
SIRIUS 3RF34 solid-state switching devices - Overview of technical data
36 Product Information, 11/2011
5.3 Conductor cross-sections for solid-state reversing contactors
Conductor cross-sections for solid-state reversing contactors
Table 5- 4 Connection of main terminals with screw-type connection system
Connection, main contacts Screw-type connection system
Conductor cross-section
Solid
mm 2 x (1.5 to 2.5), 2 x (1.5 to 6)
Finely stranded with end sleeve
mm 2 x (1.5 to 2.5), 2 x (1.5 to 6)
Finely stranded without end sleeve
mm 1 x 10
Solid or stranded
AWG 2 x (14 to 10)
Stripped length mm 10
Connection screw M4
Tightening torque Nm 2 to 2.5
D 5 to 6 mm/PZ 2 Ib.in 18 to 22

Table 5- 5 Connection of main contacts and control contacts with screw-type connection system
Connection, auxiliary contacts, and control
contacts
Screw-type connection system
Conductor cross-section with end sleeve mm 1 x (0.5 to 2.5)
Conductor cross-section without end sleeve mm 2 x (0.5 to 1.0)
AWG 20 to 12
Stripped length mm 7
Connection screw M3
Tightening torque Nm 0.5 to 0.6
D 3.5/PZ 1 Ib.in 4.5 to 5.3
Technical data
5.4 Solid-state contactors 3RF34, 3-phase, screw connection
SIRIUS 3RF34 solid-state switching devices - Overview of technical data
Product Information, 11/2011 37
5.4 Solid-state contactors 3RF34, 3-phase, screw connection
Solid-state contactors - instantaneous switching - 2-phase controlled
Table 5- 6 Rated operational voltage Ue 48 to 480 V
3RF3405-
1BB04
3RF3410-
1BB04
3RF3412-
1BB04
3RF3416-
1BB04
Connection type Screw connection
Rated operational current Ie A 5.2 9.2 12.5 16
Rated power at Ie and Ue 400 V kW 2.2 4.0 5.5 7.5
Rated control supply voltage Us V DC 24 acc to. EN 61131-2
Weight approx. kg 0.250 0.380 0.380 0.380

Table 5- 7 Rated operational voltage Ue 48 to 480 V
3RF3405-
1BB24
3RF3410-
1BB24
3RF3412-
1BB24
3RF3416-
1BB24
Connection type Screw connection
Rated operational current Ie A 5.2 9.2 12.5 16
Rated power at Ie and Ue 400 V kW 2.2 4.0 5.5 7.5
Rated control supply voltage Us V AC 110 to 230
Weight approx. kg 0.250 0.380 0.380 0.380

Table 5- 8 Rated operational voltage Ue 48 to 600 V, blocking voltage 1,600 V
3RF3405-
1BB06
3RF3410-
1BB06
3RF3412-
1BB06
3RF3416-
1BB06
Connection type Screw connection
Rated operational current Ie A 5.2 9.2 12.5 16
Rated power at Ie and Ue 400 V kW 2.2 4.0 5.5 7.5
Rated control supply voltage Us V DC 24 acc to. EN 61131-2
Weight approx. kg 0.250 0.380 0.380 0.380

Table 5- 9 Rated operational voltage Ue 48 to 600 V, blocking voltage 1,600 V
3RF3405-
1BB26
3RF3410-
1BB26
3RF3412-
1BB26
3RF3416-
1BB26
Connection type Screw connection
Rated operational current Ie A 5.2 9.2 12.5 16
Rated power at Ie and Ue 400 V kW 2.2 4.0 5.5 7.5
Rated control supply voltage Us V AC 110 to 230
Weight approx. kg 0.250 0.380 0.380 0.380
Technical data
5.5 Solid-state contactors 3RF34, 3-phase, spring-loaded terminals
SIRIUS 3RF34 solid-state switching devices - Overview of technical data
38 Product Information, 11/2011
5.5 Solid-state contactors 3RF34, 3-phase, spring-loaded terminals
Solid-state contactors - instantaneous switching - 2-phase controlled
Table 5- 10 Rated operational voltage Ue 48 to 480 V
3RF3405-
1BB04
3RF3410-
1BB04
3RF3412-
1BB04
3RF3416-
1BB04
Connection type Spring-loaded terminals
Rated operational current Ie A 5.2 9.2 12.5 16
Rated power at Ie and Ue 400 V kW 2.2 4.0 5.5 7.5
Rated control supply voltage Us V 24 DC acc. to EN 61131-2
Weight approx. kg 0.250 0.380 0.380 0.380

Table 5- 11 Rated operational voltage Ue 48 to 480 V
3RF3405-
1BB24
3RF3410-
1BB24
3RF3412-
1BB24
3RF3416-
1BB24
Connection type Spring-loaded terminals
Rated operational current Ie A 5.2 9.2 12.5 16
Rated power at Ie and Ue 400 V kW 2.2 4.0 5.5 7.5
Rated control supply voltage Us V 110 to 230 AC
Weight approx. kg 0.250 0.380 0.380 0.380

Table 5- 12 Rated operational voltage Ue 48 to 600 V, blocking voltage 1,600 V
3RF3405-
1BB06
3RF3410-
1BB06
3RF3412-
1BB06
3RF3416-
1BB06
Connection type Spring-loaded terminals
Rated operational current Ie A 5.2 9.2 12.5 16
Rated power at Ie and Ue 400 V kW 2.2 4.0 5.5 7.5
Rated control supply voltage Us V 24 DC acc. to EN 61131-2
Weight approx. kg 0.250 0.380 0.380 0.380

Table 5- 13 Rated operational voltage Ue 48 to 600 V, blocking voltage 1,600 V
3RF3405-
1BB26
3RF3410-
1BB26
3RF3412-
1BB26
3RF3416-
1BB26
Connection type Spring-loaded terminals
Rated operational current Ie A 5.2 9.2 12.5 16
Rated power at Ie and Ue 400 V kW 2.2 4.0 5.5 7.5
Rated control supply voltage Us V 110 to 230 AC
Weight approx. kg 0.250 0.380 0.380 0.380
Technical data
5.6 Solid-state contactors - fuseless design with CLASS 10 motor starter protector
SIRIUS 3RF34 solid-state switching devices - Overview of technical data
Product Information, 11/2011 39
5.6 Solid-state contactors - fuseless design with CLASS 10 motor
starter protector
Fuseless design with CLASS 10 motor starter protector
Table 5- 14 Main circuit
Order no. 3RF3405-.BB.. 3RF3410-.BB.. 3RF3412-.BB.. 3RF3416-.BB..
Rated operational current IAC-53
1)
acc. to IEC 60947-4-2
At 40 C A 5.2 (4.5)
2)
9.2 12.5 16
At 50 A 4.6 (4.0)
2)
8.4 11.5 14
At 60 C A 4.2 (3.5)
2
7.6 10.5 12.5
Power loss at IAC-53 at 40 C W 10 (8)
2)
16 22 28
Short-circuit protection with type of coordination "1" at operational voltage Ue up to 440 V
Motor starter protector Type 3RV2011-1GA10 3RV2011-1JA10 3RV2011-1KA10 3RV2011-4AA10
Iq kA 50 5 5 3
1)
Use overvoltage protection device; max. cut-off-voltage 6,000 V; min. energy handling capability 100 J
2)
The reduced values in brackets apply in the case of a directly mounted motor starter protector combined with side-by-
side mounting.
Technical data
5.7 Solid-state contactors - fused design with 3RB30 overload relay
SIRIUS 3RF34 solid-state switching devices - Overview of technical data
40 Product Information, 11/2011
5.7 Solid-state contactors - fused design with 3RB30 overload relay
Fused design with directly mounted 3RB30 overload relay
Table 5- 15 Main circuit
Order no. 3RF3405-.BB.4 3RF3405-.BB.6 3RF3410-.BB..
Rated operational current IAC-53
1)
acc. to IEC 60947-4-2
At 40 C A 4 (3.5)
2)
4 (3.5)
2)
7.8
UL/CSA at 50 C A 3.6 (3.2)
2)
3.6 (3.2)
2)
7
At 60 C A 3.2 (2.9)
2
3.2 (2.9)
2
6.2
Power loss at IAC-53 at 40 C W 7 (6)
2)
7 (6)
2)
13
Minimum load current A 0.1 0.5 0.5
Max. leakage current mA 10 10 10
Rated peak withstand current Itsm A 200 600 600
I
2
t value A
2
s 200 1800 1800

Table 5- 16 Main circuit
Order no. 3RF3412-.BB.4 3RF3412-.BB.6 3RF3416-.BB..
Rated operational current IAC-53
1)
acc. to IEC 60947-4-2
At 40 C A 9.5 9.5 11
UL/CSA at 50 C A 8.5 8.5 10
At 60 C A 7.6 7.6 9
Power loss at IAC-53 at 40 C W 16 16 18
Minimum load current A 0.5 0.5 0.5
Max. leakage current mA 10 10 10
Rated peak withstand current Itsm A 1200 1150 1150
I
2
t value A
2
s 7200 6600 6600
1)
Use overvoltage protection device; max. cut-off-voltage 6,000 V; min. energy handling capability 100 J
2)
The reduced values in brackets apply in the case of a directly mounted motor starter protector combined with side-by-
side mounting.
Technical data
5.8 Solid-state contactors - main circuit, 2-phase controlled
SIRIUS 3RF34 solid-state switching devices - Overview of technical data
Product Information, 11/2011 41
5.8 Solid-state contactors - main circuit, 2-phase controlled
Solid-state contactor, 2-phase controlled
Table 5- 17 Main circuit
Order no. 3RF34..- BB.4 3RF34..- BB.6
Controlled phases 2-phase 2-phase
Rated operational voltage Ue
Operating range V 40 ... 506 40 ... 660
Rated frequency Hz 50 / 60 10 % 50 / 60 10 %
Rated insulation voltage Us V 600 600
Rated impulse withstand voltage Uimp kV 6 6
Blocking voltage V 1200 1600
Voltage gradient V/s 1000 1000
5.9 Solid-state contactors with control circuit
Solid-state contactor with control circuit
Table 5- 18 Control circuit A1 - A2:
Order no. 3RF34..- BB0. 3RF34..- BB2.
Method of operation DC operation AC operation
Rated control supply voltage Us V DC 24 acc to. EN 61131-2 AC 110 to 230
Rated control supply voltage, max. Us V DC 30 AC 253
Rated frequency of control supply voltage Hz 50 / 60 10 %
Typical actuating current mA 20 15
Response voltage V 15 90
Drop-out voltage V 5 < 40
Switching times
ON-delay
ms 1 5
OFF-delay
ms 1 + max. one half-wave 30 + max. one half-wave
Technical data
5.10 Solid-state reversing contactor with integration of four current paths to form a single reversing circuit
SIRIUS 3RF34 solid-state switching devices - Overview of technical data
42 Product Information, 11/2011
5.10 Solid-state reversing contactor with integration of four current paths
to form a single reversing circuit
Solid-state reversing contactor - instantaneous switching - 2-phase controlled - screw connection
Table 5- 19 Rated operational voltage Ue 48 to 480 V
Order no. 3RF34 03-1BD04 3RF34 05-1BD04 3RF34 10-1BD04
Rated operational current Ie A 3.8 5.4 7.4
Rated power at Ie and Ue 400 V kW 1.5 2.2 3.0
Rated control supply voltage Us V DC 24 acc to. EN 61131-2
Weight per PU approx. kg 0.280 0.280 0.410

Table 5- 20 Rated operational voltage Ue 48 to 480 V
Order no. 3RF34 03-1BD24 3RF34 05-1BD24 3RF34 10-1BD24
Rated operational current Ie A 3.8 5.4 7.4
Rated power at Ie and Ue 400 V kW 1.5 2.2 3.0
Rated control supply voltage Us V AC 110 to 230
Weight per PU approx. kg 0.280 0.280 0.410
5.11 Solid-state contactors - fuseless design with CLASS 10 motor
starter protector
Fuseless design with CLASS 10 motor starter protector
Table 5- 21 Main circuit
Order no. 3RF34 03-.BD.4 3RF34 05-.BD.4 3RF34 10-.BD.4
Rated operational current IAC-53
1)
acc. to IEC 60947-4-2
at 40 C A 3.8 (3.4) 5.4 (4.8) 7.4
UL/CSA at 50 C A 3.5 (3.1) 5 (4.3) 6.8
at 60 C A 3.2 (2.8) 4.6 (3.8) 6.2
Power loss at IAC-53 at 40 C W 7 (6) 9 (8) 13
Short-circuit protection with type of coordination "1" at operational voltage Ue up to 440 V
Motor starter protector Type 3RV20 11-1FA10 3RV20 11-1GA10 3RV20 11-1JA10
Iq kA 50 50 10
1)
The reduced values in brackets apply in the case of a directly mounted motor starter protector combined with side-by-
side mounting.
2)
To reduce the risk of an inter-phase short circuit due to overvoltage, we recommend connecting a 3TX7 462-3L type
varistor between phases L1 and L3, as close as possible to the switching device. We recommend a design with
semiconductor protection to provide short-circuit protection.
Technical data
5.12 Solid-state contactor - fused design with 3RB30 overload relay
SIRIUS 3RF34 solid-state switching devices - Overview of technical data
Product Information, 11/2011 43
5.12 Solid-state contactor - fused design with 3RB30 overload relay
Fused design with directly mounted 3RB30 overload relay
Table 5- 22 Main circuit
Order no. 3RF34 03-.BD.4 3RF34 05-.BD.4 3RF34 10-.BD.4
Rated operational current IAC-53
1)
acc. to IEC 60947-4-2
At 40 C A 3.8 (3.4) 5.4 (4.8) 7.4
UL/CSA at 50 C A 3.5 (3.1) 5 (4.3) 6.8
At 60 C A 3.2 (2.8) 4.6 (3.8) 6.2
Power loss at IAC-53 at 40 C W 7 (6) 9 (8) 13
Minimum load current A 0.5 0.5 0.5
Max. leakage current mA 10 10 10
Rated peak withstand current Itsm A 600 600 600
I
2
t value A
2
s 1800 1800 1800
1)
The reduced values in brackets apply in the case of a directly mounted motor starter protector combined with side-by-
side mounting.
2)
To reduce the risk of an inter-phase short circuit due to overvoltage, we recommend connecting a 3TX7 462-3L type
varistor between phases L1 and L3, as close as possible to the switching device. We recommend a design with
semiconductor protection to provide short-circuit protection.
5.13 Solid-state reversing contactor - main circuit, 2-phase controlled
Solid-state reversing contactor, 2-phase controlled
Table 5- 23 Main circuit
Order no. 3RF34..- BD.4
Controlled phases 2-phase
Rated operational voltage
Operating range Ue V 40 ... 506
Rated frequency Hz 50 / 60 10 %
Rated insulation voltage Us V 600
Rated impulse withstand voltage Uimp kV 6
Blocking voltage V 1200
Voltage gradient V/s 1000
Technical data
5.14 Solid-state reversing contactor with control circuit
SIRIUS 3RF34 solid-state switching devices - Overview of technical data
44 Product Information, 11/2011
5.14 Solid-state reversing contactor with control circuit
Solid-state reversing contactor with control circuit
Table 5- 24 Control circuit A1 - A2:
Order no. 3RF34..- BD0. 3RF34..- BD2.
Method of operation DC operation AC operation
Rated control supply voltage Us V DC 24 acc to. EN 61131-2 AC 110 to 230
Rated control supply voltage, max. Us V DC 30 AC 253
Rated frequency of control supply voltage Hz 50 / 60 10 %
Typical actuating current mA 20 15
Response voltage V 15 90
Drop-out voltage V 5 < 40
Switching times
ON-delay
ms 5 20
OFF-delay
ms 5 + max. one half-wave 10 + max. one half-wave
Locking time
ms 60 - 100 50 - 100
Technical data
5.15 Characteristics - switching frequency/load
SIRIUS 3RF34 solid-state switching devices - Overview of technical data
Product Information, 11/2011 45
5.15 Characteristics - switching frequency/load
5.15.1 Characteristics for the solid-state contactor
Switching frequency characteristic for the solid-state contactor
Motor's operating data
I
a
I
e
t
a
t
b
I
b
t
ED
N
S
B
0
_
0
1
8
1
5
a
tp
t
s

Ia Motor's direct starting current
Ie Motor's rated operational current
Ib Motor's operational current
ta Motor's start time
tb Operating time
tp Idle time
tED ON period
ts Operating cycle
ED [%] = 100%
t
s
t
ED

Figure 5-1 Switching frequency characteristics - load diagram

Technical data
5.15 Characteristics - switching frequency/load
SIRIUS 3RF34 solid-state switching devices - Overview of technical data
46 Product Information, 11/2011
1
2
3
4
5
6
7
la/le = 7,2 lb/le = 1
10
100
1000
10000
0,01 0,1 1 10 100 1000 tED [s]
z

[
1
/
h
]

1 ta = 0.05 s
2 ta = 0.1 s
3 ta = 0.2 s
4 ta = 0.4 s
5 ta = 0.8 s
6 ta = 1.6 s
7 ta = 3.2 s
Figure 5-2 Maximum permissible switching frequency z depending on the starting time ta and the ON period tED for
motors with a starting current of 4 to 7.2 times the rated current and with full load
1)


Technical data
5.15 Characteristics - switching frequency/load
SIRIUS 3RF34 solid-state switching devices - Overview of technical data
Product Information, 11/2011 47
1
2
3
4
5
6
7
la/le = 7,2 lb/le = 0,6
10
100
1000
10000
0,01 0,1 1 10 100 1000 tED [s]
z

[
1
/
h
]

1 ta = 0.05 s
2 ta = 0.1 s
3 ta = 0.2 s
4 ta = 0.4 s
5 ta = 0.8 s
6 ta = 1.6 s
7 ta = 3.2 s
Figure 5-3 Maximum permissible switching frequency z depending on the starting time ta and the ON period tED for
motors with a starting current of 4 to 7.2 times the rated current and 60% load
1)

1)
The dashed curves apply to the high currents during operation with a motor starter
protector.

Technical data
5.15 Characteristics - switching frequency/load
SIRIUS 3RF34 solid-state switching devices - Overview of technical data
48 Product Information, 11/2011
1
2
3
4
5
6
7
la/le = 4 lb/le = 1
10
100
1000
10000
0,01 0,1 1 10 100 1000 tED [s]
z

[
1
/
h
]

1 ta = 0.05 s
2 ta = 0.1 s
3 ta = 0.2 s
4 ta = 0.4 s
5 ta = 0.8 s
6 ta = 1.6 s
7 ta = 3.2 s
Figure 5-4 Maximum permissible switching frequency z depending on the starting time ta and the ON period tED for
motors with a starting current of up to 4 times the rated current and with full load

Technical data
5.15 Characteristics - switching frequency/load
SIRIUS 3RF34 solid-state switching devices - Overview of technical data
Product Information, 11/2011 49
1
2
3
4
5
6
7
la/le = 4 lb/le = 0,6
10
100
1000
10000
0,01 0,1 1 10 100 1000 tED [s]
z

[
1
/
h
]

1 ta = 0.05 s
2 ta = 0.1 s
3 ta = 0.2 s
4 ta = 0.4 s
5 ta = 0.8 s
6 ta = 1.6 s
7 ta = 3.2 s
Figure 5-5 Maximum permissible switching frequency z depending on the starting time ta and the ON period tED for
motors with a starting current of up to 4 times the rated current and 60% load
Technical data
5.15 Characteristics - switching frequency/load
SIRIUS 3RF34 solid-state switching devices - Overview of technical data
50 Product Information, 11/2011
5.15.2 Characteristics for the solid-state reversing contactor
Switching frequency characteristic for the solid-state reversing contactor
Motor's operating data
I
a
I
e
t
a
t
b
I
b
t
ED
N
S
B
0
_
0
1
8
1
5
a
tp
t
s

Ia Direct-on-line starting current
Ie Rated operational current
Ib Operating current
ta Start time
ta Operating time
tp Idle time
tED ON period
ts Operating cycle
ED [%] = 100%
t
s
t
ED

Figure 5-6 Switching frequency characteristics - load diagram

Technical data
5.15 Characteristics - switching frequency/load
SIRIUS 3RF34 solid-state switching devices - Overview of technical data
Product Information, 11/2011 51
1
2
3
4
5
6
7
la/le = 7,2 lb/le = 1
10
100
1000
10000
0,01 0,1 1 10 100 1000 tED [s]
z

[
1
/
h
]

1 ta = 0.05 s
2 ta = 0.1 s
3 ta = 0.2 s
4 ta = 0.4 s
5 ta = 0.8 s
6 ta = 1.6 s
7 ta = 3.2 s
Figure 5-7 Maximum permissible switching frequency z depending on the starting time ta and the ON period tED for
motors with a starting current of 4 to 7.2 times the rated current and with full load

Technical data
5.15 Characteristics - switching frequency/load
SIRIUS 3RF34 solid-state switching devices - Overview of technical data
52 Product Information, 11/2011
1
2
3
4
5
6
7
la/le = 7,2 lb/le = 0,6
10
100
1000
10000
0,01 0,1 1 10 100 1000 tED [s]
z

[
1
/
h
]

1 ta = 0.05 s
2 ta = 0.1 s
3 ta = 0.2 s
4 ta = 0.4 s
5 ta = 0.8 s
6 ta = 1.6 s
7 ta = 3.2 s
Figure 5-8 Maximum permissible switching frequency z depending on the starting time ta and the ON period tED for
motors with a starting current of 4 to 7.2 times the rated current and 60% load

Technical data
5.15 Characteristics - switching frequency/load
SIRIUS 3RF34 solid-state switching devices - Overview of technical data
Product Information, 11/2011 53
1
2
3
4
5
6
7
la/le = 4 lb/le = 1
10
100
1000
10000
0,01 0,1 1 10 100 1000 tED [s]
z

[
1
/
h
]

1 ta = 0.05 s
2 ta = 0.1 s
3 ta = 0.2 s
4 ta = 0.4 s
5 ta = 0.8 s
6 ta = 1.6 s
7 ta = 3.2 s
Figure 5-9 Maximum permissible switching frequency z depending on the starting time ta and the ON period tED for
motors with a starting current of up to 4 times the rated current and with full load

Technical data
5.15 Characteristics - switching frequency/load
SIRIUS 3RF34 solid-state switching devices - Overview of technical data
54 Product Information, 11/2011
1
2
3
4
5
6
7
la/le = 4 lb/le = 0,6
10
100
1000
10000
0,01 0,1 1 10 100 1000 tED [s]
z

[
1
/
h
]

1 ta = 0.05 s
2 ta = 0.1 s
3 ta = 0.2 s
4 ta = 0.4 s
5 ta = 0.8 s
6 ta = 1.6 s
7 ta = 3.2 s
Figure 5-10 Maximum permissible switching frequency z depending on the starting time ta and the ON period tED for
motors with a starting current of up to 4 times the rated current and 60% load

SIRIUS 3RF34 solid-state switching devices - Overview of technical data
Product Information, 11/2011 55
Circuit diagrams 6

3RF34 solid-state switching devices
3RF34..-.BB2.
1/L1 5/L3
2/T1 6/T3
3/L2
4/T2
A1~ A2~

Figure 6-1 Solid-state contactor, 3-phase, AC control voltage

3RF34..-.BD2.
1/L1 3/L2 5/L3
2/T1 4/T2 6/T3
A1~A2~A3~

Figure 6-2 Solid-state reversing contactor, 3-phase, AC control voltage

3RF34..-.BB0.
1/L1 5/L3
2/T1 6/T3
3/L2
4/T2
A1+ A2-

Figure 6-3 Solid-state contactor, 3-phase, DC control voltage

Circuit diagrams

SIRIUS 3RF34 solid-state switching devices - Overview of technical data
56 Product Information, 11/2011
3RF34..-.BD0.
1/L1 3/L2 5/L3
2/T1 4/T2 6/T3
A1+A2- A3+

Figure 6-4 Solid-state reversing contactor, 3-phase, DC control voltage
Example circuit diagrams
The figures below show the example circuit diagrams for the solid-state contactors and solid-
state reversing contactors
Example circuit diagram for the solid-state contactor for motorized loads
U
"On"
3/N/PE 50Hz 230/400 V
L1
L2
L3
N
PE
Q1
R1
DC 24 V
L+
L-
F4
F1 F2 F3
L1 1 L2 3 L3
A1 +
A2 -
5
T3 6 T2 4 T1 2
M1
M
S1

F1 - 3 Main circuit fuses (solid-state contactor recommended)
F4 Control circuit fuse
Q1 3RF34 solid-state contactor for motorized loads
M1 Motor
R1 Varistor 3TX7 462-3L (recommended to maintain "surge" immunity)
S1 "ON" switch
Figure 6-5 Example circuit diagram: Fused motor feeder with solid-state contactor for motorized
loads with DC control circuit
Circuit diagrams

SIRIUS 3RF34 solid-state switching devices - Overview of technical data
Product Information, 11/2011 57
Example circuit diagram for the solid-state reversing contactor
U
"Right"
"Left"
3/N/PE 50 Hz 230/400V
L1
L2
L3
N
PE
T3
A3~
A2~
A1~
6
L3 5 L2
F1
Q1
R1
F2 F3
3 L1 1
T2 4 T1
M1
M
2
F4
S2
S1

F1 - 3 Main circuit fuses (solid-state contactor recommended)
F4 Control circuit fuse
Q1 3RF34 solid-state reversing contactor
M1 Motor
R1 Varistor 3TX7 462-3L (recommended to maintain "surge" immunity)
S1 "Left" switch
S2 "Right" switch
Figure 6-6 Example circuit diagram: Fused motor feeder with solid-state reversing contactor with AC
control circuit

Circuit diagrams

SIRIUS 3RF34 solid-state switching devices - Overview of technical data
58 Product Information, 11/2011

SIRIUS 3RF34 solid-state switching devices - Overview of technical data
Product Information, 11/2011 59
Dimension drawings (dimensions in mm) 7


Note
All dimensions are specified in mm.

7.1 Solid-state switching devices
Solid-state contactor
4.3 61.5
81.9
96.5
4
7
.
5
1
4
.
5
14.4

4
.8
83,5
8
5
x
3
5
45
9
5
6
9
40 45
45
90

Figure 7-1 Solid-state contactor
Dimension drawings (dimensions in mm)
7.2 Link module for motor starter protector
SIRIUS 3RF34 solid-state switching devices - Overview of technical data
60 Product Information, 11/2011
Solid-state reversing contactor
4.3 61.5
93.7
109.4
28.8
1
4
.
5
4
7
.
5

4
.8
97
45
6
9
9
5
40 45
45
90
8
5
x
3
5

Figure 7-2 Solid-state reversing contactor

7.2 Link module for motor starter protector
Accessories
Link module 3RA2921-1BA00 for 3RV20 motor starter protector
2
0
.
7
4
3
.
1
72.9
14.4 14.4
44.8

Figure 7-3 Link module for motor starter protector

SIRIUS 3RF34 solid-state switching devices - Overview of technical data
Product Information, 11/2011 61
Index

A
Ambient temperature
Solid-state switching devices, 24
Applications
Solid-state switching devices, 21
B
Basic knowledge, 7
C
Characteristics - switching frequency/load
Solid-state contactor, 45
Solid-state reversing contactor, 50
Connection methods
Solid-state switching devices, 14
D
Device versions
Solid-state switching devices, 13
Disposal, 7
E
Electromagnetic interference
Solid-state switching devices, 22
Equipment features
Solid-state contactor, 15
Solid-state reversing contactor, 16
Example circuit diagrams
Solid-state switching devices, 56, 57
F
Fuses
Solid-state switching devices, 30
I
Internal circuit diagrams
Solid-state switching devices, 55
L
Load feeders
Solid-state switching devices, 22, 23
R
Recycling, 7
S
Safety instructions
Solid-state switching devices, 9
Selection
Solid-state switching devices, 23
Short-circuit current
Solid-state switching devices, 31
Short-circuit protection
Solid-state contactor, 25, 26
Solid-state reversing contactor, 27, 28
Solid-state switching devices, 25
SITOR semiconductor fuses
Solid-state switching devices, 22, 31
Solid-state contactors, 13, 14, 21
Solid-state reversing contactors, 13, 14, 21
Solid-state switching devices
Instantaneous switching, 13, 14
Standards
Solid-state switching devices, 11
Switching
Motorized load, 13, 21
Resistive load, 13
T
Technical Assistance, 7
Types of coordination, 24
U
UL
Solid-state switching devices, 29, 31

Index

SIRIUS 3RF34 solid-state switching devices - Overview of technical data
62 Product Information, 11/2011


Siemens AG
Industry Sector
Postfach 23 55
90713 FUERTH
GERMANY
Subject to change without prior notice
Siemens AG 2011
www.siemens.com/automation
Service & Support
Download catalogs and information material:
www.siemens.com/industrial-controls/catalogs
Newsletter always up to date:
www.siemens.com/industrial-controls/newsletter
E-business in the Industry Mall:
www.siemens.com/industrial-controls/mall
Online-Support:
www.siemens.com/industrial-controls/support
Contact for all technical information:
Technical Assistance
Tel.: +49 (911) 895-5900
e-mail: technical-assistance@siemens.com
www.siemens.com/industrial-controls/technical-assistance