Вы находитесь на странице: 1из 31

Directional / non Directional

Overcurrent Protection
P120 Software Version 10 & Hardware Version 5

P121 Software Version 10 & Hardware Version 5

P122 Software Version 10 & Hardware Version 5

P123 Software Version 10 & Hardware Version 5

P125 Software Version 10 & Hardware Version 5

P126 Software Version 10 & Hardware Version 5

P127 Software Version 10 & Hardware Version 5

Technical Data Sheet


P12xy/EN TDS/B22

This document does not replace the Technical Manual.


Application and Scope
The MiCOM P12x relays are suitable for all the For easy adaptation to varying system operating
applications where overcurrent and earth-fault conditions two independent setting groups are
protection are required. provided.

The P12x relays can be used for a range of Flexible automation functions enable accurate co-
overcurrent applications from single phase/earth ordination with other devices.
fault applications, P120 (non directional), P125 Three earth fault sensitivity current inputs are
(directional) to three phase and earth fault available by ordering code.
applications, P123 (non directional), P127 1A and 5A dual rated CT inputs are available with
(directional). The P127 also includes voltage all MiCOM P12x relays using separate terminals.
protections and relevant functions and power Two line/phase voltage input ranges, 57-130V and
measurement. 220-480V, are available by ordering code.
The P12x relays provide a comprehensive suite of The auxiliary voltage for the power supply and the
overcurrent protection and automation features for digital inputs is a wide-range design, 24 to 60 Vdc
easy and flexible adaptation under different and 48 to 250 Vac/dc.
operating conditions. The P12x relays are housed in a robust 4U metal
case for panel or rack mounting with 20TE width
The typical applications are overhead lines, (P120, P121, P122, P123 and P125) or 30TE width
underground cables and backup for HV systems in (P126 and P127). To ease maintenance, the relay
insulated, solid, resistance and Petersen coil can be withdrawn from its case (draw out case).
earthed neutral systems, used in MV utility,
Industry, Transport, generator and transformer
schemes.

P120 P121 P122 P123 P125 P126 P127 Technical DataSheet 2 P12xy/EN TDS/B22
Functions overview

Functions Overview P120 P121 P122 P123 P125 P126 P127


67/50/51 Three phase directional non directional overcurrent X
50/51 Three-phase overcurrent X X X X
49 Thermal overload X X X X
37 Three-phase undercurrent X X X X
46 Negative pase sequence overcurrent X X X X
67N/50N/51N Earth fault directional non directional overcurrent X X X
50N/51N Earth fault (Single-phase) overcurrent X X X X
32N Earth fault Wattmetric / Ie*cosφ X X X
59N Residual overvoltage X X X
27/59 Phase/Line under/ overvoltage X
79 Autoreclose X X X
Switch on to fault (SOTF) X X X
CB control Local/ remote X X X X
Phase current rotation X X
50BF Circuit breaker failure detection X X X X
Circuit Breaker Maintenance and Trip Circuit Supervision X X X X
46BC Broken conductor detection I2/I1 X X X X
Cold load pick up X X X X
86 Output relay latching X X X X X X X
Blocking Logic X X X X X X X
Selective relay scheme logic X X X X
Relay maintenance mode X X X X X
Remote control of output relays X X
Setting groups 1 1 2 2 2 2 2
Programmable AND logic X X
VT supervision (VTS) and logic application X
Auxiliary timers X X X X X
Measurements X X X X X X X
Peak and rolling values X X X X
Power and Energy measurement X
Fault records X X X X
Elapsed time of protection starting X X X X
Event records X X X X
Disturbance recording X X X X
Binary inputs / output relays 2/4 2/4 3/6 5/8 4/6 7/8 7/8
AC current / voltage inputs 1/0 4/0 4/0 4/0 1/1 4/1 4/3
Modbus RTU X X X X X X X
IEC 60870-5-103 X X X X X X X
Courier X X X X
DNP3.0 X X X X
Setting software MiCOM S1 X X X X X X X

P120 P121 P122 P123 P125 P126 P127 Technical DataSheet 3 P12xy/EN TDS/B22
Control and display set the relay using a PC with the setting software
All functions including protection automation, MiCOM S1.
communication, LEDs, inputs and outputs can be The simple and powerful software interface
programmed and modified using the front panel provides the user easy configuration and access to
user interface. all measurements and stored information for
maintenance and post-fault analysis purposes.
The 2 line, 16 alphanumerical backlit LCD display
(available in a range of languages) provides the Password Protection
user with key information (faults, measurements, A four-character password is requested in order to
settings, etc.). prevent inadvertent or unauthorized change of
settings or trigger of control functions.
The default display can be selected by the user. It is
possible to show the phase or earth current value Self-Monitoring
by selecting Phase A, Phase B , Phase C, Earth N Comprehensive self-monitoring procedures within
(P126/7), or the four values simultaneously the devices ensure that internal hardware or
(P120/1/2/3). The P125 will be able to show the software errors are detected and do not cause
earth fault current only. malfunctions of the device. As the auxiliary voltage
is turned on, a functional test is carried out. Cyclic
The menus have a pull-down structure for easy use
self-monitoring tests are running during operation. If
and quick access to any data. test results deviate from the default value then the
Dedicated LEDs corresponding signal is entered into the non-volatile
monitoring signal memory. The result of the fault
4 LEDs indicate the state of the relay (Trip, Alarm, diagnosis determines whether a blocking of the
Warning, Healthy). protection and control unit will occur or whether a
Acknowledgement of alarm and trip LEDs can be warning only is issued.
easily performed locally or remotely.
Programmable LEDs
4 freely programmable LEDs are provided on all
models.
The user can assign independently each LED to
any programmable function or combination of
thresholds. Clear Key
Keypad Trip Led Read Key

A seven-button tactile keypad on the front panel Alarm Led


allows the user easy access to any data.
Communication RS485 Device fail
Power supply Cursor
All P12x series relays have a rear RS485 keys
communications port to communicate with Freely
Enter key
MODBUS, IEC 60870-5-103, Courier and DNP3 Programmable
protocols. (Courier & DNP3 are not available on Leds
P125, P126 and P127 relays). The relays can
communicate to the local monitoring system, or
remotely to the SCADA, settings, measurements RS232
and alarms, as well as fault, event and disturbance
records.
All communication parameters (relay address, data
rate, parity, etc.) can be set using the front panel
user interface.
Communication RS232
Main Functions
An RS232 front port is available in the MiCOM P12x The relays comprise a full suite of protection
series. functions as well as an automatic recloser and
It allows the user to download new firmware auxiliary functions;
(update, language changing,...) and also allows to Each function can be individually configured or
disabled suiting any particular application.

P120 P121 P122 P123 P125 P126 P127 Technical DataSheet 4 P12xy/EN TDS/B22
FUNCTIONAL OVERVIEW

AUXILIARY FUNCTIONS MEASUREMENTS Recording


Front port Rear port • SOTF (Switch on to fault) • Phase Current features
• CB local/Remote • Direct and inverse currents
Setting RS485 port. • Phase Current Rotation • Residual current Fault record
software S1 To setting software S1 • CB Monitoring • Residual voltage 5
to SCADA system • Cold Load Pick Up • Line and phase voltage
• Trip Circuit Supervision • Active and Reactive Power
• Blocking Logic • Active and Reactive Energy Event Recording
• Selective Scheme Logic • Autoreclose counters 75
• Relay maintenance Mode • CB mechanical operation
• Remote ctrl on output relays counter
• Programmable AND Logic • CB electrical operation Dist. Recording
counter
5 records of
• Auxiliary timers 3 sec.
27 59 79 86 • Peak and rolling demand
59N
• Self Monitoring

32N 50N
67 67N Iecos 50/51 51N 37 46 46BC 49 50BF

(Description of ANSI code nos. see Functions Overview)

Three-phase Overcurrent Protection (50/51)


Earth Fault Overcurrent Protection (50N/51N) Ith
Three independent stages are available for phase
and earth fault protection.
I>
Time

The first and second stage can be independently


t>
selected as definite time delay or inverse time delay I>>
with different types of curve (IEC, IEEE/ANSI, RI,
t>>
RECT), except for P120 and P121 where the I>>> t>>>
I<
second stage can only be set as definite time. I>>>> t>>>>
The third stage for the P122, P123, P126, P127 can
also be configured as peak detection with a definite Current
time delay only.
Each stage and related time delay can be Three-phase Directional Overcurrent (67)
programmed to provide maximum selectivity. The Each one of the three-phase overcurrent stages of
IDMT stages have definite or inverse time reset the P127 can be independently configured as
capability reducing clearance times when
directional protection with specific relay
intermittent faults happen.
characteristic angle (RCA) settings and boundaries.
In the P125, P126, P127 the 2nd and 3rd threshold
Each directional stage has instantaneous (start)
pick-up can suspend the 1st threshold output to
control selectivity. forward/reverse outputs available.
The MiCOM P12x relays have separate Directional Overcurrent Tripping Zone
instantaneous (start) and delayed (trip) outputs for
each stage. P126 & P127 can indicate the faulted
phase(s) by configuring output relays (first stage
only). The range of earth fault current sensitivity can
be selected by ordering code.
Tripping Characteristics

P120 P121 P122 P123 P125 P126 P127 Technical DataSheet 5 P12xy/EN TDS/B22
The first and second stage can be independently In addition to the residual current, the residual
select as definite time delay or inverse time delay voltage must be connected to a dedicated input or
with different types of curve (IEC, IEEE/ANSI, RI, internally calculated as a vector sum (P127 only) in
RECT). The third stage can be configured with order to make directional operation possible.
definite time delay only. The 2nd and 3rd threshold Each earth-fault directional stage measures the
pick-up can suspend the 1st threshold output to residual current, the residual voltage, and the angle
control selectivity between residual voltage and current.

The phase fault directional elements are internally Wattmetric/Ie*cos ϕ protection (32N)
polarised by quadrature phase-phase voltages. Two additional stages are configurable with
Wattmetric or Ie*cosϕ characteristics. The first
A synchronous polarising function is provided to stage can be set with a definite time or with various
ensure correct operation of the overcurrent IDMT curves as the 51N and 67N. The second
elements for close-up three phase faults where the stage is definite time only.
collapse of the polarising line voltages can occur.
The Pe threshold setting value is automatically
corrected selecting the rated Ie current.
The two-stages can be independently configured
with specific characteristic boundaries. The RCA
angle is common for the two stages.
Wattmetric characteristic

The absolute phase angle of line voltages is


measured every cycle and the last value is stored in
the relay memory.
The polarisation discrimination voltage value is 0.6V
(fixed value) for relays with a system voltage of 57
to 130V and 3V (fixed value) for relays with a UnderCurrent protection (37)
system voltage of 220 to 480V.
Over this value the directional relay uses standard MiCOM P122, P123, P126 & P127 relays provide a
polarisation (the measured voltage), under this definite time undercurrent protection.
value the synchronous polarisation (stored vector) This function allows typical applications such as
is used. loss of load or simple broken conductor detection.
The synchronous polarisation is maintained up to
the restoration of an input voltage value. For the P122 and P123 the undercurrent protection
If the input voltage loss persists longer than 5s the stage is conditioned to the status of the CB auxiliary
directional overcurrent protection is blocked. contact. The stage operates when the CB is closed
as indicated by a logic digital input energised via
Earth-fault Directional Overcurrent (67N) the 52a auxiliary contact of the CB.
Each of the three earth-fault stages of P125, P126
and P127 can be configured as directional Thermal overload
protection with specific characteristic angle (RCA). The thermal overload protection can be applied to
Each directional stage has instantaneous (start) prevent damage to the electrical plant equipment
forward/reverse outputs available. when operating at temperatures in excess of the
The first and second stage can be independently designed maximum withstand. A prolonged
select as definite time or inverse time delay with overloading causes excessive heating, which may
different type of curves (IEC, IEEE/ANSI, RI, result in premature deterioration of the insulation, or
RECT). The third stage can be configured with a in extreme cases, insulation failure.
definite time delay only. The 2nd and 3rd threshold The P122, P123, P126 and P127 relays incorporate
pick-up can suspend the 1st threshold output to a current based thermal replica, using load current
control selectivity to reproduce the heating and cooling of the

P120 P121 P122 P123 P125 P126 P127 Technical DataSheet 6 P12xy/EN TDS/B22
equipment to be protected. The thermal overload When the first or the second stages of the phase
element can be set with both alarm and trip stages. overcurrent protection are set to an IDMT curve, the
maximum setting recommended should be 2 times
The heating within any plant equipment, such as the nominal. When the earth fault elements are set
cables or transformers, is of resistive type (I²R x t). to an IDMT curve, the maximum setting
Thus, the quantity of heat generated is directly recommended should 1/20th of the neutral CT input
proportional to current squared (I²). rating.
The thermal time characteristic used in the relay is ⎛ K ⎞
t = T ∗⎜ + L⎟
⎜ (I IS )
based on current squared, integrated over time. α
−1 ⎟
The P122, P123, P126 and P127 automatically use ⎝ ⎠
the highest phase current as input information for Where:
the thermal model. t Operation time
K Factor (see table)
The mathematical formula applicable is: I Value of measured current
Is Value of the programmed threshold (pick-up value)
⎛ K2 -θ ⎞ α Factor (see table)
t Trip = Te ∗ ln ⎜ 2 ⎟ L ANSI/IEEE constant (zero for IEC and RECT curves)
⎜ K −θ ⎟ T Time multiplier setting from 0.025 to 1.5
⎝ Trip ⎠
Type of curve Standard K factor α factor L factor
Where:
Short time inverse AREVA 0.05 0.04 0
tTrip is the time to trip in seconds
Te is the thermal time constant of the equipment to be Standard inverse IEC 0.14 0.02 0
protected in seconds Very inverse IEC 13.5 1 0
K is the thermal overload calculated by Ieq/k, where Extremely inverse IEC 80 2 0
Ieq is the equivalent current corresponding to the
RMS value of the largest measured phase current Long time inverse AREVA 120 1 0
and k is a factor associated to the thermal state
Short time inverse C02 0.02394 0.02 0.01694
formula.
Moderately Inverse ANSI/IEEE 0.0515 0.02 0.114
θ is the actual thermal status,
Long time inverse C08 5.95 2 0.18
θTrip is the trip thermal state.
Very inverse ANSI/IEEE 19.61 2 0.491
An alarm stage, θ alarm, is provided for the initial thermal
status. Extremely inverse ANSI/IEEE 28.2 2 0.1217
Negative phase sequence overcurrent Rectifier protection RECT 45900 5.6 0
protection
The RI curve has the following definition:
Any unbalanced fault condition will produce
negative sequence current of some magnitude 1
t= K ∗
Thus, a negative phase sequence overcurrent 0 .236
element can operate for both phase-to-phase and
phase to earth faults.
0 .339 −
( )
I
Is
The MiCOM P122, P123, P126 & P127 relays K setting is from 0.10 to 10 in steps of 0.05.
include a programmable function specially designed
RXIDG CURVES (P122, P123)
to detect unbalanced load or fault conditions. The The first and second earth threshold can be selected with
three stages of negative sequence overcurrent dedicated RXIDG curves.
have the same setting ranges as the phase The curves available follow the following formula :
overcurrent. The first stage can be independently t = 5.8 – 1.35 * ln ( 1/ (k * Is/I))
select as a definite time or inverse time delay with
different types of curve (IEC, IEEE/ANSI, RI, where :
RECT). t = tripping time
The second and third stage can be configured with k = coefficient (from 0.3 to 1, by steps of 0.1)
IS = value of the programmed threshold (Pick-
a definite time delay only. up value)
IDMT trip and reset curves I = value of measured current
IEC, ANSI/IEEE trip curve
The minimum guaranteed value of the operating In order to be compliant with Netmanagement
current for all the curves with the inverse time specifications the relay has to have :
characteristic is 1.1Is (with a tolerance of ± 0.05Is).

P120 P121 P122 P123 P125 P126 P127 Technical DataSheet 7 P12xy/EN TDS/B22
- An earth current range 0.01 Ion to 8 Ion (corresponding Under / Over voltage protection (27/59)
to Cortec model number P12-B-X---X) Under-voltage conditions may occur on a power
- A rated current of 1A system for increased system loading, complete loss
- A core balanced CT with a ratio 25/1. of busbar voltage or for faults occurring on the
phases the power system.
Reset ANSI/IEEE curve
Over-voltage conditions generally happen in a loss
The equation is valid for 1.1 ≤ I/Is ≤ 20.
of load condition or during an earth fault condition
⎛ ⎞ where there may be an increase of the voltage
K
t = T ∗⎜ ⎟ magnitude in the healthy phases.
⎜ 1 − (I I )α ⎟
⎝ S ⎠ The P127 relay provides two independent under-
Where: voltage stages and two over-voltage stages. They
are definite time elements.
t: Reset time
K: Factor (see table) Each stage can be configured to operate in single-
I: Value of the measured current phase mode (OR mode) or three-phase mode (AND
Is : Value of the programmed threshold (pick-up value) mode). Both voltage protections operate on line
α: Factor (see table) voltage (phase to phase voltage) always.
T: Reset time multiplier (RTMS) setting between 0.025
and 3.2. Residual over voltage (59N)
P125, P126 and P127 provide an additional
Type of curve Standard K factor α factor residual over-voltage stage that can be used for
Short time inverse C02 2.261 2 generic earth fault detection, particularly in
Moderately inverse ANSI/IEEE 4.850 2 insulated neutral systems or as backup at the
Long time inverse C08 5.950 2 busbar level.
Very inverse ANSI/IEEE 21.600 2
The protection element has one programmable
Extremely Inverse ANSI/IEEE 29.100 2
stage with definite delay time.
Broken conductor detection (46BC) Autorecloser (79)
A typical unbalanced fault that can occur on the Most faults on overhead line networks are transient
system is an open circuit fault. This fault can arise in nature. A transient fault, such as an insulator
from a broken conductor, mal-operation of one of flashover, is a self-clearing non-damage fault. It can
the switchgear poles, or blowing of a fuse. be cleared by the immediate tripping of one or more
circuit breakers, and does not recur when the line is
re-energised. Lightning is the most common cause
of transient faults, other possible causes being
clashing conductors and wind blown debris.
The auto-recloser function is applied for
automatically reclosing of a switching device after it
has been opened due to operation of protection
where transient and non-permanent faults are
prevalent.
MiCOM P123, P126 and P127 relays include a 4-
shot auto-recloser. All the programmed protection
functions can independently start any of the shots
and the user can programme which functions are
allowed to trip after any of the shots. This makes
possible special reclosing cycles e.g. for co-
ordination with fuses in distribution systems with
teed transformers.
Dead and reclaim times are freely adjustable.
A counter stores the number of recloser commands.
This information is available locally or remotely.
Switch on to Fault protection
MiCOM P122/3 and P126/7 relays incorporate an
Some faults may be due to fault conditions not
element, which measures the ratio of negative to removed from the feeder after a reclosing cycle or
positive sequence current (I2/I1). This fully
manual tripping, or due to earthing clamps left on
programmable function allows more sensitivity and following maintenance works. In these cases, it may
stability than pure negative sequence be desirable to clear the fault condition in a faster
measurement.

P120 P121 P122 P123 P125 P126 P127 Technical DataSheet 8 P12xy/EN TDS/B22
time, rather than waiting for the trip delay time DT combination of the selected elements (i.e. current or
or IDMT associated with the involved protection to voltage stages, thermal replica, etc).
elapse.
A typical application is to use a dedicated digital
Another condition where this function is particularly input to block the time delay settings of phase/earth
adapted is in case of manual close of the CB on an fault protection in a relay in response to the
existing fault. This can be considered as a phase/earth fault start condition of a downstream
particularly critical situation, since the overcurrent relay.
protection would not clear the fault until the set
This function allows the MiCOM relays to clear the
operate delay had elapsed.
fault fastly and correctly when used in a cascade
Hence for all these situations, it is desirable to clear scheme.
the fault in the fastest time possible.
The P123, P126 and P127 relays incorporate
configurable switch on to fault protection. It provides
an instantaneous trip during a settable time after
local or remote manual close or after automatic
reclose.
The SOTF function incorporates a fixed time
window of 500 ms during which the detection of the
fault is enabled.
Circuit breaker failure protection (50BF)
Following the inception of a fault, one or more main
protection devices will operate and issue a trip
output to the circuit breaker(s) associated with the
faulted circuit.
The circuit breaker failure protection verifies the
effective opening of the CB by a dedicated
undercurrent threshold isolating the fault and
preventing damage or further damage to the power
system.
The 50BF protection in the P122, P123, P126 and
P127 can be activated by trip of a generic
protection or/and external command by the relevant
digital input associated to the label Strt. tBF.
The Circuit breaker failure protection can also be
used to trip upstream circuit breakers.
The circuit breaker failure provides the possibility to
block the instantaneous I> and Ie> thresholds when
a 50BF signal is emitted. This allows more flexibility
in the fault localisation and isolation with blocking
schemes.
Phase current rotation
In some applications there is a need to match the
plant phase sequence with the connected relay
without changing the cabling. The P122 and P123
relays include the phase rotation feature that allows
the setting of the phases in clockwise or in anti-
clockwise rotation (ABC or ACB sequence).
Blocking logic
When the MiCOM P12x and P12y relays are used
in critical networks, management of protection
relays must take surrounding devices into
consideration.
Two blocking logic inputs can be configured
independently of each other to block any

P120 P121 P122 P123 P125 P126 P127 Technical DataSheet 9 P12xy/EN TDS/B22
Selective relay scheme logic
The P122/3 and P126/7 relays include selective Inputs and Outputs
relay scheme logic. The P12x relays include freely configurable digital
A dedicated digital input can temporarily alter the inputs and output relays for CB control and
time delay settings in response to the phase/earth signalling.
fault start condition of a downstream relay. This Each input can be configured as active high or
function allows the MiCOM relays to clear the fault active low and the supply type can be chosen as
fast and correctly when used in a cascade scheme. DC or AC at the order.
Any input can be configured for blocking, selective
Local/remote Control
logic, control, etc. by the label associated to the
In the P123, P125, P126 and P127 one logic input
specific function.
associated to the label LOCAL MODE is dedicated
to this feature. If this logic input is powered, all the Each instantaneous and delayed trip is assignable
remote communications (setting parameters, to any output relays and to the led on the front
control command....) will be forbidden to avoid a panel. To the trip relay (relay 1) only the delayed
mal-operation during a local operation. trip of the protections and some accessory function
are assignable.
The time synchronization via the network stays
active because there is no effect on the output
relays. Voltage controlled overcurrent 51V and Voltage
Transformer Supervision (VTS)
Circuit Breaker Monitoring and Supervision The logical functionality includes the possibility to
Circuit-breaker preventative maintenance is the provide the 51V function controlled by undervoltage
advanced function provided by the MiCOM P122, V< (27) and negative sequence overvoltage V2>
P123, P126 and P127 relays with adjustable closing (47).
and opening time measurements. All phase
currents (I or I2 ) are accumulated to inform about (U<ORV2>)&I>> ?
NO
the total interrupted fault current. 1
YES
V<
MiCOM P122 P123 P126 and P127 relays allow trip ≥1 BlocksI>>
circuit supervision via a specific input associated to ≥1 threshol
V2>
the label Trip Circ. The result of this monitoring can &
be viewed locally or remotely.
Cold Load Pick up
When a feeder is energised, the current levels that
flow for a period of time following energisation may (U<<ORV2>>)&I>>> ?
differ greatly from the normal load levels. NO
1
Consequently, overcurrent settings that have been
YES
applied to give short circuit protection may not be V<<
BlocksI>>>
suitable during this period. ≥1 threshol
≥1
V2>>
The Cold Load Pick-up (CLP) logic included in the &
P122, P123, P126 & P127 relays raises the settings VTS Blocks 51V .
of selected protection stages for a setting time of VTS YES

the tCL timer initiated via a dedicated logic input 0 NO


associated to the label Cold L PU.
This allows the protection settings to be set closer
VTSAlarm ?
to the load profile by automatically increasing VTSAlarm
YES
settings after energisation. VTS
NO

The 51 function is supervised by voltage


transformer supervision (VTS).
VTS logic: VTS = [(V2>0.3Vn) AND (I2<0.5In)] OR
[(V1<0.1Vn) AND (I>0.1In)]
Output relay latching (86)
Any outputs, including trip, can be latched. Reset of
the latched outputs is possible by logic input, front
panel operator interface or by remote
communication.
Cold-load characteristics

P120 P121 P122 P123 P125 P126 P127 Technical DataSheet 10 P12xy/EN TDS/B22
Peak demands with a 15-minute window are also
memorised.
Relay Maintenance mode All the measured and derived values can be
The P122, P123, P125, P126 and P127 incorporate displayed on the front panel LCD or transferred
the direct control of the output relays (without the locally or remotely on user request.
need to inject any current). This functionality allows For the complete list of the available measurements
the user to quickly verify the external wiring of the refer to the technical data in other part of this
relay output contacts. document.
Remote control on output relays
The P122 and P123 allow the direct control of 4 CB Protection start records
by selected output relays. The control can be Five protection start records are stored in the
performed by the software interface locally (S1) or MiCOM P122, P123, P126 & P127 relays.
by remote control (DCS system). Each instantaneous (start) record includes:
• instantaneous (start) time (date & duration)
Setting Groups • origin (phase & earth thresholds)
The P122, P123, P125, P126 and P127 relays have Start records give the user useful information for
two protection related setting groups. preventative maintenance of the electrical system.
Changes between the two groups are executed via
the front interface, a dedicated logic input or Event recording
through the communication port. 75 logic events are stored in the MiCOM P122,
To avoid any undesirable tripping, the setting group P123, P126 and P127 relays. Events include
change is only executed when none of the inputs/outputs, state changes, alarms and contact
protection functions are running except for the operations.
thermal overload function. If a setting group change All events are time-tagged to 1ms.
is received during any protection or automation
function, it is stored and executed after the last Fault records
timer has elapsed. Five faults are stored inside the relays. Each record
includes:
Programmable AND Logic • Fault indicators
MiCOM P126 and P127 relays incorporate four • Value of the available measurements for each
programmable AND logic equations. relay
The AND equations can match trip or start status of • Tripping time
the protection and automation functions so to have Fault indications help the user to clearly identify the
outputs conditioned. cause of the fault and monitor the P122, P123,
An operate and reset time is available for each AND P126 and P127 settings.
equation.
The output of each equation can be associated to Disturbance recording
any output relay including the trip relay. Current waveforms are captured by the P122,
P123, P126 and P127 relays. Up to 3 seconds of
Auxiliary timers
records are stored inside the relays for each fault
Auxiliary timers tAux1, tAux2, tAux3 (P122) plus
memorised in the relay. The disturbance recording
tAux4 (P123, P125, P126 and P127) associated
respectively to Aux1, Aux2, Aux3 and function is triggered either by any of the
Aux4 logic inputs can be applied for automation and programmed thresholds or by an external input, or
control in the electrical power systems. through the communications.
When the logic inputs labelled Aux 1…Aux 4 are All the logic and analogue information are stored in
energised, the relevant timer starts and when the memory and can be transferred to an external data
set time is elapsed the associated output relay trip. analyser by the front communication port or the rear
Each auxiliary timer can be associated to any port by an appropriate protocol.
output relay including the trip relay (RL1).
Measurements
MiCOM P120, P121, P122, P123, P125, P126 and
P127 relays continually monitor all of the available
analogue inputs. The relays display the values on the
LCD and store the measurements in memory.
The measured values are the true RMS up to the
10th harmonic with a 0.1% accuracy (nominal
conditions at 50 Hz).
The calculation of the average value for each phase
during a selectable rolling sub-period is also
available.

P120 P121 P122 P123 P125 P126 P127 Technical DataSheet 11 P12xy/EN TDS/B22
Device Identification, Ports
The front of the relay has two flaps. The upper flap
identifies the product name. It can be lifted to
access the product model number, serial number
and ratings.
Under the lower flap there is a 9 pin RS232 port
and a place for a backup battery that is no longer
needed (since hardware 5).
The RS232 port can be used for relay setting and
for software upgrade.

To prevent unauthorized users to open the lower


flap, the case can fit a security seal.
USB/RS232 power cable (MiCOM E2)
The external accessory MiCOM E2 is available on
demand.
The USB/RS232 cable is able to power the relay
from its front port. This allows the user to retrieve
data or modify parameters from the relay (using the
front HMI or MiCOM S1) even when the auxiliary
power supply of the relay is off or has failed.

Case
For all MiCOM P12x the units have a draw out
metal 4U case high.
The width is 20TE for the P120 P121 P122 P123
P125, 30TE for the P126 and P127.
All CTs inputs are short-circuited if the active unit is
withdrawn from the case. This feature allows a
quick and easy replacement of the unit in case of
failure, without the need to rewire the relay.
All P12x relays can be panel or rack mounted.
Wiring
External connections are made via MIDOS type
terminal blocks.
Each connection includes two 6.35mm Fast on and
one M4 screw fixing.
The wiring for all the MiCOM P120, P121, P122,
P123, P125, P126 and P127 relays is standard to
provide maximum compatibility.

P120 P121 P122 P123 P125 P126 P127 Technical DataSheet 12 P12xy/EN TDS/B22
Technical Data Compliance with European Commission Low Voltage
Directive. Compliance is demonstrated by reference to
General Data
generic safety standards:
Design EN61010-1: 1993/A2: 1995
Case Height: 4U (177mm) EN60950: 1992/A11: 1997
MiCOM P120 /1/2/3/5 20 TE
MiCOM P126/7 30 TE
Weight:
P120/1/2/3/5 approx. 3.0 Kg
P126/7approx. 4.0 Kg
Mounting
Rack or flush mounting
Connections
Rear (double fast on + M4 screw per connection)
Full draw-out with automatic CT shorting in the case of
the relay

Enclosure protection
Dust IP50 (whole case), Front IP 52, Back IP 10
Dimensions
See dimensions diagram.
PC Interface
DIN 41652 connector (X6),
type D-Sub, 9-pin.

Environmental Conditions
Recommended Ambient temperature range
Per IEC 60068-2-1 : 1993
Operating temperature range:
-25°C to 55°C (or 13°F to 131°F)
-25°C to 70° (*) (or 13°F to 158°F(*))
Storage and transit:
-25°C to 70°C (or 13°F to 158°F)
(*) The upper limit is permissible for a single 6 hour
duration within any 24 hour period.

Ambient Humidity Range


Per IEC 60068-2-78: 2001
56 days at 93% relative humidity and +40 °C
Per IEC 60068-2-30: 1980:
Damp heat cyclic, six (12 + 12) hour cycles, 93% RH,
+25 to +55 °C
Solar Radiation
Avoid exposure of the front panel to direct solar radiation.

MECHANICAL ENVIRONMENT
Vibration Test
IEC 60255-21-1: 1998, class 2.

Shock and Bump Test


IEC 60255-21-2: 1998, class 1.and 2

Seismic Test
IEC 60255-21-3: 1993, Class 2.

PRODUCT SAFETY

72/23/EEC

P120 P121 P122 P123 P125 P126 P127 Technical DataSheet 13 P12xy/EN TDS/B22
Type Tests
Insulation
Per IEC 60255-5: 2000,
Insulation resistance > 100MΩ at 500Vdc
(Using only electronic/brushless insulation tester).

High Voltage (Dielectric) Withstand


(i) Per IEC 60255-5: 2000, 2 kV rms AC, 1 minute:
Between all case terminals connected together, and the
case earth, and between all terminals of independent
circuits (RS232 ports excepted).
1kV rms AC for 1 minute, across open watchdog
contacts.
1,5kV rms AC for 1 minute, across open contacts of
changeover output relays.

Impulse Voltage Withstand Test


Per IEC 60255-5: 2000
1.2 / 50 µs, peak value: 5 kV, 0.5J
Between all terminals, and all terminals and case earth.

Electromagnetic Compatibility (EMC)

1 MHz Burst Disturbance Test


IEC 61000-4-12, Class 3

Immunity to Electrostatic Discharge


Per IEC 60255-22-2: 1996, Class 3 and 4
Electrical Fast Transient bursts
IEC 60255-22-4 class 4.
IEC 61000-4-4 class 4.

Immunity to Radiated Electromagnetic field


IEC60255-22-3 class 3.
IEC61000-4-3 class 3.

Surge Immunity Test


IEC 61000-4-5, class 4.

Immunity to Conducted Disturbances Induced


by Radio Frequency Fields
4 IEC 61000-4-6, class 3.

Power Frequency Magnetic Field Immunity


IEC 61000-4-8, class 5.
EMC compliance
89/336/EEC
93/31/EEC
Compliance with European Commission EMC Directive.
Generic standards were used to establish conformity:
EN50081-2: 1994
EN60952-2: 1995

P120 P121 P122 P123 P125 P126 P127 Technical DataSheet 14 P12xy/EN TDS/B22
Ratings
AC Measuring Inputs PC Interface
Nominal frequency: 50 and 60 Hz (settable) Transmission rate: 19200 baud (fixed)
Operating range: from 45 Hz to 65 Hz Parity: None
Frame: 8 bit
AC Current
Stop bit: 1 bit
Nominal current (In): 1A and 5A dual rated
Earth nominal current 1A and 5A dual rated Communication Interface
Nominal burden per phase: < 0.025 VA (1A) Communication interface rear port:
< 0.3 VA (5A) RS 485 2kV-isolation hardware support common mode
Nominal burden per earth: < 0.08 VA (1A) Output Relays
< 0.42 VA (5A) Contact relay: Dry contact Ag Ni
Continuous withstand: 4 In Make current: Max. 30A and carry for 3s
for 2 s: 40 In Carry capacity: 5A continuous
for 1 s: 100 In Rated Voltage: 250Vac
AC Voltage Breaking characteristic:
Voltage input range Un 57 to 130V Breaking capacity AC: 1500 VA resistive
Measuring range 0 to 260V 1500 VA inductive (P.F. = 0.5)
Burden per phase: 0.08W at 100/√3 V 220 Vac, 5A (cos ϕ = 0.6)
Continuous withstand: 260V ph-ph Breaking capacity DC:
10 seconds 300V ph-ph 135 Vdc, 0.3A (L/R = 30 ms)
Voltage input range Un 220 to 480V 250 Vdc, 50W resistive or
Measuring range 0 to 960V 25W inductive (L/R=40ms)
Burden per phase: 0.55W at 480V Operation time: <7ms
Continuous withstand: 960V ph-ph Durability:
10 seconds: 1300V ph-ph Loaded contact 10000 operation minimum
Unloaded contact 100000 operation minimum
Power Supply
Nominal auxiliary
24-60Vdc; Logical Inputs
48-250Vdc / 48-250 Vac
voltage Vx
Type: optically insulated
DC ± 20% of Vx
Operating range
AC – 20%, +10% of Vx Burden: 2.3 mA per input
Aux Supply ripple Up to 12% Recognition time (DC): < 5ms
Stored energy time ≥50 ms for interruption of Vx
Burden Stand by: <3W DC or <8 VA The tolerance on the auxiliary voltage variations for the
P120/1/2/3/4/5 Max: <5W DC or <12 VA logic inputs is ±20% for DC voltage and −20%, +10% for
Stand by: <3W DC or <8 VA AC voltage.
Burden P126
Max: <6W DC or <14 VA
Stand by: <3W DC or <8VA (**) Logic input recognition time for ENA assessment.
Burden P127 Dedicated filtering on 24 samples (15 ms at 50 Hz).
Max: <6W DC or <14VA

P120 P121 P122 P123 P125 P126 P127 Technical DataSheet 15 P12xy/EN TDS/B22
Protections functions Ue>, Ue>>, Ue>>> for 57 to 130V version:
1V to 260V in steps of 0.1V
Settings Ue>, Ue>>, Ue>>> for 220 to 480V version:
Phase overcurrent [67/50/51]
4V to 960V in steps of 0.5V
(P120, P121, P122, P123, P125, P126, P127)
Earth fault current trip delay time:
Range 0.1 to 40 In
DT for tIe>, tIe>>, tIe>>> 0 to 150 s in steps of 0.01s
I>: 0.1 to 25 In
IDMT for Ie> and Ie>> (except for P120, P121)
I>>: 0.5 to 40 In
IEC, ANSI/IEEE, RI and RECT curve
I>>>: 0.5 to 40 In
TMS 0.025 to 1.5 in steps of 0.025
Setting Step 0.01In
Reset time for DT on Ie>,Ie>>: (P120/1/2/3)
If I> or I>> are set to IDMT operation, the maximum
0 to 600 sec in steps of 0.01In
recommended setting should be 2x In to give a full
Reset time for IDMT for P120/1 only
operating curve.
tIe> , tIe>> fixed 50 ms
P127 in directional mode Reset time for P122 & P123
Relay characteristic angle RCA-Torque angle for each tIe>, tIe>> with IEC curve:
stage 0° to 359° 0.04 to 100s in steps of 0.01s
Trip zone for each stage ±10° to ±170° tIe>, tIe>> with ANSI/IEEE curve:
Trip delay time RTMS: 0.025 to 3.2 in steps of 0.025
DT for: tI>, tI>>, tI>>> 0 to 150 s in steps of 0.01s DT: 0.04 to 100 s in steps of 0.01s
IDMT for I> and I>> (except P120, P121) Reset time for P125, P126 & P127
IEC, ANSI/IEEE, RI and RECT curve tIe>, tIe>> with IEC curve:
TMS 0.025 to 1.5 in steps of 0.025 0 to 100 s in steps of 0.01s
Reset time for DT on I>,I>>: (P120/1/2/3) tIe>, tIe>> with ANSI/IEEE curve:
0 to 600 sec in steps of 0.01In RTMS: 0.025 to 3.2 in steps of 0.025
Reset time for IDMT for P120/1 only DT: 0 to 100 s in steps of 0.01s
tI> , tI>> fixed 50 ms For the range 0.002 to 1Ien, RXIDG curves are available
Reset time for P122 & P123 on the P122 & P123 only.
tI>, tI>> with IEC curve: Wattmetric /Iecos earth fault [32N] (P125, P126, P127)
0.04 to 100s in steps of 0.01s The setting value has to be multiplied by Ien for 32N only
tI>, tI>> with ANSI/IEEE curve: (I.e. Ien=5A Pe>: 2.00 x 5 W. your setting is 10W)
0.04 to 100 s in steps of 0.01s
RTMS: 0.025 to 3.2 in steps of 0.025 Range:
Reset time for P126 & P127 0.1 to 40 Ien
tI>, tI>> with IEC curve: voltage range 57 to 130V
0 to 100 s in steps of 0.01s Pe>, Pe>> 10 to 800 W
tI>, tI>> with ANSI/IEEE curve: Setting Step: 1W
RTMS: 0.025 to 3.2 in steps of 0.025 voltage range 220 to 480V
DT: 0.00 to 100s in steps of 0.01s Pe>, Pe>> 40 to 3200 W
Setting Step: 5W
Earth fault overcurrent [67N/50N/51N] Ie cos> 0.1 to 25 Ien
(P120, P121, P122, P123, P125, P126, P127) Iecos>> 0.5 to 40 Ien
Range: 0.1 to 40 Ien Setting Step: 0.01 Ien
0.1 to 40 Ien
Ie> from 0.1 to 25 Ien Range:
Ie>>, Ie>>> from 0.5 to 40 Ien 0.01 to 8 Ien
Setting Step: 0.01Ien voltage range 57 to 130V
If Ie> or Ie>> are set to IDMT operation, the maximum Pe>, Pe>> 1 to 160 W
recommended setting should be 2x In to give a full Setting Step: 0.1 W
operating curve. voltage range 220 to 480V
Pe>, Pe>> 4 to 640 W
Range: 0.01 to 8 Ien Setting Step: 0.5 W
Ie> from 0.01 to 1 Ien Ie cos> 0.01 to 1 Ien
Ie>>, Ie>>> from 0.01 to 8 Ien Iecos>> 0.01 to 8 Ien
Setting Step: 0.005 Ien Setting Step: 0.005 Ien
If Ie> or Ie>> are set to IDMT operation, the maximum
recommended setting should be 0.4x In to give a full Range:
operating curve. 0.002 to 1 Ien
voltage range 57 to 130V
Range:0.002 to 1 Ien Pe>, Pe>> from 0.2 to 20 W
Ie>, Ie>>, Ie>>> from 0.002 to 1 Ien Setting Step: 0.02 W
Setting steps 0.001 Ien voltage range 220 to 480V
If Ie> or Ie>> are set to IDMT operation, the maximum Pe>, Pe>> from 1.0 to 80 W
recommended setting should be 0.05x In to give a full Setting Step: 0.01 W
operating curve. Ie cos> from 0.002 to 1 Ien
P125/6/7 directional mode Iecos>> from 0.002 to 1 Ien
Relay characteristic angle RCA-Torque angle for each Setting Step: 0.001 Ien
stage 0° to 359° Relay characteristic angle RCA-Torque angle for each of
Trip zone for each stage ±10° to ±170° the Pe/Iecos elements 0° to 359°
Setting step 1°

P120 P121 P122 P123 P125 P126 P127 Technical DataSheet 16 P12xy/EN TDS/B22
Trip Zone : +/- 80° Phase/line over voltage [59] (P127)
DT for: tPe>, tPe>>, Iecos>, Iecos>> 0 to 150 s Nominal Voltage range 57 – 130V
IDMT for Pe> and Iecos> U> AND/OR/OFF
IEC, ANSI/IEEE, RI and RECT curve U> 2 to 260V in steps of 0.1V
TMS 0.025 to 1.5 in steps of 0.025 U>> AND/OR/OFF
Reset time U>> 2 to 260V in steps of 0.1V
tIPe>, tIecos> with IEC curve: Nominal Voltage range 220 – 480V
0 to 100 s in steps of 0.01s U> AND/OR/OFF
tIPe>, tIecos> with ANSI/IEEE curve: U> 10 to 720V in steps of 0.5V
RTMS: 0.025 to 3.2 in steps of 0.025 U>> AND/OR/OFF
DT: 0 to 100 s in steps of 0.01s U>> 10 to 960V in steps of 0.5V
DT for tU>, tU>> 0 to 600 s in steps of 0.01
Negative Sequence [46] (P122, P123, P126, P127) The setting OR / AND in the stages means:
P126 & P127: OR: trip by start of one or two or three phase
I2> 0.1 to 25 In AND: trip by start of three phases.
I2>> 0.5 to 40 In
Residual over voltage [59N] (P125, P126, P127)
I2>>> 0.5 to 40 In
Nominal Voltage range 57 – 130V
Setting Step 0.01In
Ue>>>> 1 to 260V in steps of 0.1V
P122 & P123:
Nominal Voltage range 220 – 480V
I2> 0.1 to 40 In
Ue>>>> 5 to 960V in steps of 0.5V
I2>> 0.1 to 40 In
DT for t Ue>>>> 0 to 600 s in steps of 0.01
Setting Step 0.01In
If I2> is set to IDMT operation, the maximum Autoreclose [79] (P123, P126, P127)
recommended setting should be 2x In to give a full Autoreclose settings
operating curve. Ext CB Fail? NO YES
DT for: tI2>, tI2>>, tI2>>> 0 to 150 s in steps of 0.01s Ext CB Fail Time 000.01 ms 600, 00 sec 0.01 sec
IDMT for I2> Ext Block? NO YES
IEC, ANSI/IEEE, RI and RECT curve tD1 000.01 sec 300, 00 sec 0.01 sec
TMS 0.025 to 1.5 in steps of 0.025 tD2 000.01 sec 300, 00 sec 0.01 sec
Reset time P122, P123, P126, P127 tD3 000.01 sec 600, 00 sec 0.01 sec
tI2> with IEC curve: tD4 000.01 sec 600, 00 sec 0.01 sec
0.04 to 100 s in steps of 0.01s Reclaim Time tR 000.02 sec 600, 00 sec 0.01 sec
tI2> with ANSI/IEEE curve: Inhibit Time tI 000.02 sec 600, 00 sec 0.01 sec
RTMS: 0.025 to 3.2 in steps of 0.025 Phase Cycles 0 4 1
DT: 0.04 to 100 s in steps of 0.01s E/Gnd Cycles 0 4 1
Thermal Overload element [49]) Cycles 4321 4321
0/1/2
(P122, P123, P126, P127) tI> 0000 2222
Iθ> 0.1 to 3.2 In steps of 0.01In Cycles 4321 4321
0/1/2
Te 1 to 200mn in steps of 1mn tI>> 0000 2222
K 1 to 1.5 in steps of 0.01 Cycles 4321 4321
0/1/2
θ Trip 50% to 200% in steps of 1% tI>>> 0000 2222
θ Alarm 50% to 200% in steps of 1% Cycles 4321 4321
0/1/2
tIe> 0000 2222
Three phase undercurrent [37] Cycles 4321 4321
0/1/2
(P122, P123, P126, P127) tIe>> 0000 2222
I< (P122 P123) 0.02 to 1 In steps of 0.01 Cycles 4321 4321
I< (P126 P127) 0.1 to 1 In steps of 0.01 0/1/2
tIe>>> 0000 2222
DT for: tI< 0 to 150 s in steps of 0.01s Cycles (P126/7) 4321 4321
0/1/2
tPe/Iecos>, 0000 2222
Phase/line under voltage [27] (P127)
Cycles (P126/7) 4321 4321
Nominal Voltage range 57 – 130V 0/1/2
tPe/Iecos>> 0000 2222
U< AND/OR/OFF
U< 2 to 260V in steps of 0.1V Cycles 4321 4321
0/1/2
U<< AND/OR/OFF tAux1 0000 2222
U<< 2 to 260V in steps of 0.1V Cycles 4321 4321
0/1/2
Nominal Voltage range 220 – 480V tAux2 0000 2222
U< AND/OR/OFF The settings 0, 1 and 2 means:
U< 10 to 480V in steps of 0.5V 0 = means that any trip of the threshold is considered a
U<< AND/OR/OFF final trip. The autoreclose is not initiated.
U<< 10 to 480V in steps of 0.5V 1 = trip on threshold pick up, followed by the programmed
DT for tU<, tU<< 0 to 600 s in steps of 0.01 reclosing activity
Setting OR / AND in the stage means: 2 = no trip on threshold pick up, whatever has been set in
OR: trip by start of one or two or three phase the any trip control menu. With this setting after the
AND: trip by start of three phases. Reclaim time is expired, the autoreclose is ready for a
new sequence.
The recloser runs for 4 reclosing cycles

P120 P121 P122 P123 P125 P126 P127 Technical DataSheet 17 P12xy/EN TDS/B22
Automation and accessory functions CB supervision and control (P122, P123, P126, P127)
Trip command Trip circuit supervision
Each one of the protection function outputs (after a time CB supervision time
delay, e.g. tI>), auxiliary timers, and logic equations can t SUP 0.1 to 10 s in steps of 0.01 s
be assigned to the trip command (relay 1).
CB open/close supervision time
Latch functions CB open sup. time 0.05 to 1 s in step of 0.01 s
Each of the protection function outputs (after a time CB close sup. time 0.05 to 1 s in step of 0.01 s
delay, e.g. tI>), auxiliary timers and CB fail can be latched
CB trip operations stages
in P120, P121, P122, and P123.
CB trip mechanical operations 0 to 50000 in steps of 1
Latch output relays CB trip electrical operations Σan
The output relays that can be latched are as follows: 0 to 4000 Exp6 in steps 1 E6
P120: latching relays not available CB trip electrical operations exp n: 1 to 2 in steps of 1
P121: relay 2 to 4
P122: relay 2 to 6 CB open time and close time control
P123: relay 2 to 8 CB open control time 0 to 5 s in step of 0.01 s
P125: relay 1 to 6 CB close control time 0 to 5 s in step of 0.01 s
P126, P127: relay 1 to 8
Auxiliary timers (P122, P123, P125, P126, P127)
Circuit breaker failure detection [50BF] (P122, P123, tAux1, tAux2, t Aux3, t Aux4:
P126, P127) 0 to 200 s in steps of 0.01 s
I< CB 0.02 to 1In in steps of 0.01In
Programmable AND logic (P126, P127)
t BF (P126, P127) 0 to 10 s in steps of 0.01 s For each equation there is:
t BF (P122, P123) 0.03 to 10 s in steps of 0.01 s T operate 0 to 600 s in steps of 0.01 s
Block on I> Yes/No
t Reset 0 to 600 s in steps of 0.01 s
Block on Ie> Yes/No
Disturbance Recording (P122, P123, P126, P127)
Blocking logic (P120 P121 P122. P123, P125, P126, Pre-time 0 to 3 s in steps of 0.1s
P127) Post -time 0 to 3 s in steps of 0.1s
The follow stages locked by a digital input associated to Pre-time + Post-time = 3 sec. maximum
the label Blk. Log1/2 are for the P12x : Trigger for disturbance ON Inst. or ON Trip
I>. I>>, I>>>, Ie>, Ie>>, Ie>>>, I2>, I2>>, Thermal θ, Start on digital input labelled as Strt dist.
Brkn. Cond., t Aux1, t Aux2, tAux3, tAux4.
In addition for the P125/6/7 are : Time peak value (P122, P123, P126, P127)
tPe/Iecos> , tPe/Iecos>, tI<, I2>>>, tUe>>>>. Windows time 5min, 10min, 15min, 30min, or 60min
For the P127 only: tU>, tU>>, tU<, tU<<.
Rolling demand (P122, P123, P126, P127)
Selective scheme logic (P122. P123, P126, P127) Sub period 1 to 60 mn in steps of 1 mn
The involved stages are: Num sub period 1 to 24 in steps of 1
tI>, tI>>, tI>>>, tIe>, tIe>>, tIe>>>.
t sel: 0 to 150 s in steps of 0.01 s Configuration parameters
Broken conductor (46BC) (P122, P123, P126, P127) VT connections (P127)
Ratio I2/I1 20% to 100% in steps of 1% 3 phase to neutral (UA, UB, UC) 3Vpn
t BC 0 to 14400 s in steps of 1 s Ue is calculated: Ue = (UA+UB+UC)/3
2 phase to neutral and residual voltage (UA,UB,Ur)
Cold load pick up (P122, P123, P126, P127) 2Vpn + Vr
Level (P126 P127) 100% to 500% in steps of 1% 2 phase to phase and residual voltage (UAB,UBC,Ur)
Level (P122 P123) 20% to 500% in steps of 1% 2Vpp + Vr
t CL 0.1to 3600 s in steps of 0.1 s VT connections (P125, P126)
The involved stages are: Residual voltage Vr
I>, I>>, I>>>
Ie>, Ie>>, Ie>>> Display (P125, P126, P127)
I2>, I2>>, I2>>> Default display IA or IB or IC or IN
I2>>>: in P126 P127 only Display (P120, P121)
t Therm. Default display A or B or C or N
L1 or L2 or L3 or E
Voltage controlled overcurrent [51V] (P127) R or S or T or G
Voltage range: 57 to 130V Display (P122, P123)
Block of I>> = (U< OR V2>) & I>> A or B or C or N or IA, IB,IC,IN
V2 > 3V to 200V in steps of 0.1V L1 or L2 or L3 or E or L1, L2, L3, E
Block of I>>> (U<ORV2>)&I>>> R or S or T or G or R, S, T, G
V2 >> 3V to 200V in steps of 0.1V
Voltage range: 220 to 480V
V2 >, V2>> 20V to 720V in steps of 0.5V
Voltage transformer supervision [VTS] (P127)
VTS blocks 51V Yes/No
VTS Alarm Yes/No

P120 P121 P122 P123 P125 P126 P127 Technical DataSheet 18 P12xy/EN TDS/B22
Transformer Ratio Measurement range
Phase CTs IA, IB, IC with Sec. max 40 In x CT prim. max 9999:
Primary : 0 to 9999 A 0 to 400 kA by step of 0.01 A
Secondary 1A or 5 A UA,UB,UC (Un = 57..130 V) with Sec max 260 x VT prim.
Earth CTs Max 1 MV / VT sec. min 57:
Primary : 0 to 9999 A 0 to 4.56 MV by step of 0.01 V
Secondary 1A or 5 A UA,UB,UC (Un = 220...480 V) with Sec max 960:
Phase Voltage VTs 0 to 960 V by step of 0.01 V
P127 Ordering code A (57 to 130V) UAB,UBC,UCA (Un = 57..130 V) with 2 x VA, VB or VC
Primary nominal (phase to phase) 0.10 to 1000.00 kV
max if angle = 180°between 2 phases:
Secondary (phase to phase) 57 to 130V
P127 Ordering code B (220 to 480V) 0 to 9.12 MV by step of 0.01 V
Direct input (phase to phase) 220 to 480 V UAB,UBC,UCA (Un = 220..480 V) with 2 x VA, VB or VC
Residual Voltage VTs max if angle = 180°between 2 phases:
P125, P126, P127 Ordering code A (57 to 130V) 0 to 1.92 kV by step of 0.01 V
Primary 0.10 to 1000.00 kV Ie (0.1 to 40 Ien) with Sec. max 40 Ien x CT prim. max
Secondary 57 to 130V
9999: 0 to 400 kA by step of 0.01A
P125, P126, P127 Ordering code B (220 to 480V)
Direct input 220 to 480 V Ie (0.01 to 8 Ien) with Sec. max 8 Ien x CT prim. max
9999 0 to 80 kA by step of 0.01A
Other configurations Ie (0.002 to 1 Ien) with Sec. max 1 Ien x CT prim. max
Phase rotation (P122 P123) 9999 0 to 10 kA by step of 0.01A
Phase rotation P122 P123: A-B-C or A-C-B Ue (Uen = 57..130 V) with Sec max 260 x VT prim. Max
1 MV / VT sec. min 57 0 to 4.56 MV by step of 0.01 V
Group select (P122, P123, P125, P126, P127)
Change Group on Input labeled: change set Ue (Uen = 220...480 V) with Sec max 960:
EDGE or LEVEL 0 to 960 V by step of 0.01 V
Setting Group 1 or 2 Pe Power (0.1 to 40 Ien, Uen = 57..130 V) with (Ie max
400 kA x Ue max 4.56 MV) 0 to 1824 GW by step of 1 W
Alarms (P122, P123, P125, P126, P127) Pe Power (0.01 to 8 Ien, Uen = 57..130 V) with Ie max
Inst. Self-reset ? Yes or No
Reset led on fault ? Yes or No 80 kA x Ue max 4.56 MV 0 to 365 GW by step of 1 W
Alarm Battery? Yes or No Pe Power (0.002 to 1 Ien, Uen = 57..130 V) with Ie max
10 kA x Ue max 4.56 MV 0 to 45.6 GW by step of 1 W
Digital Inputs configuration
Pe Power (0.1 to 40 Ien, Uen = 220..480 V) with Ie max
Each of the digital inputs can be set as:
Active high (rising edge/high level) 400 kA x Ue max 960 V 0 to 384 MW by step of 1 W
or Active low (falling edge/low level) Pe Power (0.01 to 8 Ien, Uen = 220..480 V) with Ie max
P120 and P121 have two inputs. 80 kA x Ue max 960 V 0 to 76.8 MW by step of 1 W
P122 has three inputs. Pe Power (0.002 to 1 Ien, Uen = 220..480 V) with Ie max
P123 has five inputs. 10 kA x Ue max 960 V 0 to 7.7 MW by step of 1 W
P125 has four inputs. Angle Ie^Ue 0° to 359°
P126 and P127 have seven inputs.
Active Power 0 to 9999 GW
The voltage for digital inputs is DC or AC selectable, Reactive Power 0 to 9999 GVar
depending from the model; see ordering code tables. Power factor 0 to 1
Active Energy Power 0 to 4200 GWh
Relay Maintenance mode
Reactive Energy Power 0 to 4200 Gvarh
Relays maintenance mode P122 P123 P125 P126
P127 Further:
P122 P125 relays 65W(*)4321 I1, I2, Ratio I2/I1,Thermal status (resettable)
P123 P126 P127 Relays 8765W(*)4321
(*) watch dog relay Max & Average (resettable)
Max IA Rms, Max IB Rms, Max IC Rms
Average IA Rms, Average IB Rms, Average IC Rms
Recloser operations counters (resettable)
Total Recloses, Cycle 1, Cycle 2, Cycle 3, Cycle 4
Total Trip & Lockout

P120 P121 P122 P123 P125 P126 P127 Technical DataSheet 19 P12xy/EN TDS/B22
Communication Courier
P120 P121 P122. P123
ModBus protocol Relay Address 1 to 255
P120 P121 P122. P123, P125, P126, P127
Baud Rate:
300, 600, 1200, 2400, 4800, 9600, 19200, 38400 bd CT/VT requirement
Parity Even/Odd/None Phase inputs Typical 5VA 5P10
Stop Bits 1 or 2 Earth inputs Core balanced CT or residual
R4elay Address 1 to 255 Phase input Typical Protection VT
Residual voltage input
IEC 60870-5-103 Residual voltage input Typical protection VT or Open Delta VT
P120 P121 P122. P123, P125, P126, P127
Baud Rate
300, 600, 1200, 2400, 4800, 9600, 19200, 38400 bd
Relay Address 1 to 255
DNP3.0
P120 P121 P122. P123
Baud Rate:
300, 600, 1200, 2400, 4800, 9600, 19200, 38400 bd
Parity Even/Odd/None
Stop Bits 1 or 2
Relay Address 1 to 255

Accuracy
Element Deviation Trigger Reset Time deviation
Phase overcurrent elements ± 2% DT: Is ± 2% 0.95 Is ±2% ±2% +20…50ms
P120/1/2/3/6/7 IDMT: 1.1Is ±2% 1.05 Is ±2% ±5% +20…50ms

Relay characteristic angle RCA ≤ 3°


(RCA-Torque angle) P125/6/7
Trip zone P125/6/7 ≤ 3°
Earth fault overcurrent elements ± 2% DT: Ies ± 2% 0.95 Ies ±2% ±2% +20…50ms
P121/2/3/6/7 IDMT: 1.1Ies ±2% 1.05 Ies ±2% ±5% +20…50ms
Wattmetric earth fault elements ±4% ± error on cosϕ DT: Pes 0.95 Pes ±2% +30…50ms
P125/6/7 ± accuracy ± accuracy ±5% +30…50ms
IDMT: 1.1Pes 1.05 Pes
± accuracy ± accuracy
IeCosϕ ±2% ± error on cosϕ DT: IeCos ± accuracy 0.95 IeCos ± accuracy ±2% +30…50ms
earth fault overcurrent elements IDMT: 1.1 IeCos ± accuracy 1.05 IeCos ± accuracy ±5% +30…50ms
P125/6/7
Negative sequence phase ± 2% DT: I2s ± 2% 0.95 I2s ±2% ±2% +20…50ms
overcurrent elements IDMT: 1.1I2s ±2% 1.05 I2s ±2% ±5% +20…50ms
P122/3/6/7
Phase undercurrent element ± 2% DT: I< ± 2% 1.05 I< ±2% ±2% +20…50ms
P122/3/6/7
Broken conductor ± 3% DT: I2/I1 ± 3% 0.95 I2/I1 ±3% ±2% +20…50ms
P122/3/6/7
Thermal overload ± 3% IDMT: Iθ> ± 3% 0.97 Iθ>±3% ±5% +20…50ms (ref.
P122/3/6/7 IEC 60255-8)
Overvoltage ± 2% DT: Us ± 2% 0.95 Us ±2% ±2% +20…40ms
P127
Undervoltage ± 2% DT: Us ± 2% 1.05 Us ±2% ±2% +20…40ms
P127
Derived residual overvoltage ± 2% DT: Urs ± 2% 0.95 Urs ±2% ±2% +20…40ms
P125/6/7 or 1V
Auxiliary Timers ±2% +10...20 ms
Timers of logic functions ±2% +10...20 ms
Autoreclosing Timers ±2% +10...20 ms

P120 P121 P122 P123 P125 P126 P127 Technical DataSheet 20 P12xy/EN TDS/B22
Dimension

case 20 TE

39 39
97 26 26

All dimensions
in mm
168 158

Panel cut-out
Flush mounting fiwing details

4 holes Ø 3.4 49.5 49.5 4 holes Ø 4.4 (M4 screw)


103 25.1 226
MiCOM P121

IA = 214.50A
Trip

Alarm C
Equip.fail

Auxiliary
supply 177 151.2 max.
AUX. 1

AUX. 2

AUX. 3

AUX. 4

Flush mounting
P0001ENa

case 30 TE

Figure Dimensional drawings

P120 P121 P122 P123 P125 P126 P127 Technical DataSheet 21 P12xy/EN TDS/B22
Alternative : The earth current input is connected to the sommation of the three phase CTs. The current inputs are connected to 3 phase CTs + a core balanced CT.
P2 P1 P2 P1 P2 P1 37
A A 33 35
S2 S1 S2 S1 Auxiliary + WD Watch dog (4)
B B 36
voltage
}
C C _ 6
S2 S1 34
49 49 4
Programmable tripping
P121 RL1
2
} output
1A 1A
50 50 12
51 51 10
RL2 Programmable output
1A 1A P121 8
}
A only
Wiring Connections

52 52 16
53 53 RL3 Programmable output
14 }
1A 1A 20
54 54 RL4 18 Programmable output
55 55 }
C B
1A 1A
Phase rotation
56 56
41 P121 41

P120 P121 P122 P123 P125 P126 P127 Technical DataSheet


5A 5A
42 42
43 43
P121
Typical application diagram P120 P121

5A 5A
only
44 44
45 45

5A 5A
46 46
47 47
5A 5A MiCOM
48 48

+ P120/121
Programmable 22
L1

22
input { 24 Case earth connection
-
Alternative (P121 only): Connection to 2 phases CTs + a core balanced CT. +
Programmable 26
input L2
P2 P1 P2 P1 { 28
A -
S2 S1 Case earth
B 29
Communication
C 30 cable shield
S2 S1 1 2 29 30 *
49
3 4 31 32
1A 31 _ RS 485
5 6 33 34
50 Port communication
7 8 35 36
51
9 10 37 38 32 }
1A +
11 12 39 40 ( : terminating resistor for the
52 13 14 41 42 *
53 last relay to be connected
15 16 43 44 between 30-32)
1A
17 18 45 46
54
55 19 20 47 48
21 22 49 50
1A
23 24 51 52
56 Nota :
41 25 26 53 54
(1) (a) CT shorting links make before (b) and (c) disconnect
5A 27 28 55 56

42
43 (b) Short terminals break before (c)
Module terminal blocks
5A (c) Long terminals
viewed from rear
44 (d)
45 (with integral case earth link) Pins terminals (pcb type)

5A (2) CT connection are typical only


46
47
(3) Earth terminals are typical only
5A (4) The MICOM P120/P121 relays are shown with supply off.

48

P0045ENb

P12xy/EN TDS/B22
Alternative : The earth current input is connected to the sommation of the three phase CTs. The current inputs are connected to 3 phase CTs + a core balanced CT.
P2 P1 P2 P1 P2 P1 37
A A 33 35
S2 S1 S2 S1 Auxiliary + Watch dog (4)
B B WD 36
}
voltage
C C
{ _ 6
S2 S1 34
49 49 4
Programmable tripping
RL1 output
2 }
1A 1A
50 50 12
51 51 10
RL2 Programmable output
8
1A
A
1A
}
52 52 16
53 53 RL3 Programmable output
14 }
1A 1A 20
54 54 RL4 18 Programmable output
55 55
B 3
}
1A C 1A
Phase rotation RL5 1 } Programmable output
56 56
41 41 7
RL6 5 Programmable output
5A 5A }

P120 P121 P122 P123 P125 P126 P127 Technical DataSheet


9
42 42
43 43 RL7 11 Programmable output
5A 5A 13
}
Typical application diagram P122 P123

44 44 RL8 15 Programmable output


45 45
}
5A 5A P123 only
46 46
47 47
5A 5A MiCOM
48 48

+ P122/123
Programmable 22
L1

23
input { 24 Case earth connection
-
Alternative : Connection to 2 phases CTs + a core balanced CT. +
Programmable 26
input L2
P2 P1 P2 P1 { 28
A -
+
S2 S1 Case earth Programmable 17
B L3 29
input { 19 Communication
C - cable shield
S2 S1 1 2 29 30 + 30
49 Programmable 21 *
3 4 31 32 input L4
1A
{ 23 31 _
5 6 33 34 - RS 485
+
50 Programmable 25 Port communication
7 8 35 36
51 input L5
9 10 37 38 { 27 32 }
1A - +
11 12 39 40 ( : terminating resistor for the
52 13 14 41 42 *
53 P123 only last relay to be connected
15 16 43 44 between 30-32)
1A
17 18 45 46
54
55 19 20 47 48
21 22 49 50
1A
23 24 51 52
56 Nota :
41 25 26 53 54
(1) (a) CT shorting links make before (b) and (c) disconnect
5A 27 28 55 56

42
43 (b) Short terminals break before (c)
Module terminal blocks
5A (c) Long terminals
viewed from rear
44 (d)
45 (with integral case earth link) Pins terminals (pcb type)

5A (2) CT connection are typical only


46
47 (3) Earth terminals are typical only
5A (4) The MICOM P122/P123 relays are shown with supply off.

48

P0046ENb

P12xy/EN TDS/B22
Typical application diagram P125

35
C B Watch Dog
Phase rotation ~/+ 33 WD 37
36
Auxiliary Voltage 4
A B C Programmable tripping output
~/_ 34 RL1 6
2
10
Trip direction

P1 55 RL2 12
Programmable output
S1 8
1A 14
56 32N 50N 51N RL Programmable output
16
47 18
RL4 Programmable output
67N 59N 20
5A
48 3
RL5 Programmable output
1
7
RL6 Programmable output
5

22

MiCOM
A da
Programmable input L1
24
26
Programmable input L2

P125
B 28
17
Programmable input L3
19
21
C 39 Programmable input L4
23

N dn 40

Case earth connection


29 Communication cable shield
*
30 Terminal RS485

_ 31
RS485
Communication Port
+ 32
* terminating resistor for the last
relay to be connected between 30-32

P0074ENb

P120 P121 P122 P123 P125 P126 P127 Technical DataSheet 24 P12xy/EN TDS/B22
Typical application diagram P126

C B
Phase rotation
35
A B C 37
~/+ 33 WD
36
Auxiliary Voltage 4
~/_ 34
P1 RL1 6
49 2
S1 10
1A 50 51 32N
50 RL2 12
P1 51 8
14
S1 51N RL
1A 67N 50N 16
52 18
53 RL4
P1 20
37 46 49
S1 3
1A RL5
1
54
59N 79 BC
Trip direction

7
55 RL6
P1 5
S1 9
1A 50BF TCS RL7
56 11
13
41 RL8
15
5A 22
42
24 Programmable input L1
43
26
5A Programmable input L2
44 28
17
45
Programmable input L3
19
5A 21
46
Programmable input L4

MiCOM
23
47
25
5A Programmable input L5
27
48

P126
58
Programmable input L6
A da 60
57
Programmable input L7
59

B
Case earth connection
29 Communication cable shield
30
C 73 Terminal RS485
_ 31
RS485
N dn 74 Communication
+ 32

P0075ENb

P120 P121 P122 P123 P125 P126 P127 Technical DataSheet 25 P12xy/EN TDS/B22
Typical application diagram P127

C B 35
Phase rotation
37
~/+ 33 WD
36
A B C Auxiliary Voltage 4
~/_ 34
RL1 6
P1 49 2
S1 10
1A
50
50 51 67 RL2 12
P1 51 8
14
S1 RL
1A 32N 50N 51N 16
52 18
53 RL4
P1 20
S1
67N 37 46
3
1A RL5
54 1
Trip direction

49 79 BC 7
55 RL6
P1 5
S1
9
1A 50BF TCS RL7
56 11
41 13
RL8
15
5A 59 59N 27
22
42
43 24
Programmable input L1
26
5A Programmable input L2
44 28
45 17
Programmable input L3
19
5A 21
46 Programmable input L4

MiCOM
47 23
25
5A Programmable input L5
27
48

P127
58
A a Programmable input L6
69 60
57
Programmable input L7
70 59

B b 71
Case earth connection
29 Communication cable shield
72 *
30
C c 73 Terminal RS485
_ 31
RS485
N n 74 Communication
+ 32
* terminating resistor for the last
Internal reconstruction voltage Ue relay to be connected between 30-32

Two phase-neutral plus Open Delta Two phase to phase plus


connection Open Delta connection
A B C A B C
A da a 69
A da a 69

70
70
B b 71
B b 71

72
n 72
C c
C 73

N dn n
N dn 74

73
Internal reconstruction voltage UC
74

Internal reconstruction voltage UCA


P0076ENb

P120 P121 P122 P123 P125 P126 P127 Technical DataSheet 26 P12xy/EN TDS/B22
Guide Form Specification MiCOM P125 P126 P127
MiCOM P120 P121 P122 P123 Phase and earth numerical directional non
Phase and earth numerical overcurrent relay in directional overcurrent relay in drawout 4U metal
drawout 4U metal case. case.
The following functions are available: The following functions are available:
ƒ 3 independent phase stages (instantaneous and ƒ Directional / non Directional Phase Overcurrent
tine-delayed) 50/51 Directional / non Directional earth fault
ƒ 3 independent earth stages (instantaneous and overcurrent relay in drawout 4U metal case.
time-delayed) 50N/51N ƒ The following functions are available :
ƒ Tripping curves type IEC (short time inverse, ƒ 3 independent phase thresholds (instantaneous
standard inverse, very inverse, extremely and delayed) 67/50/51
inverse, long time inverse) and IEEE/ANSI (short ƒ 3 independent earth fault
time inverse, moderately inverse, inverse, very thresholds (instantaneous and
inverse, extremely inverse) delayed) 67N/50N/51N
ƒ RXIDG curves ƒ 2 Wattmetric Pe/Iecos earth fault thresholds 32N
ƒ Rectifier curve ƒ Tripping curves type IEC (short time inverse,
ƒ Negative sequence overcurrent - 46 standard inverse, very inverse, extremely
ƒ Undercurrent - 37 inverse, long time inverse) IEEE/ANSI (short
time inverse, moderately inverse, inverse, very
ƒ Thermal overload - 49 inverse, extremely inverse), RI and RECT
ƒ Output relay latching - 86 ƒ 3 Negative phase sequence overcurrent
ƒ Broken conductor detection thresholds 46
ƒ 4 shot autorecloser - 79 ƒ Undercurrent - 37
ƒ Circuit breaker failure detection - 50 BF ƒ 2 Thermal overload thresholds 49
ƒ Circuit breaker monitoring ƒ 2 Phase Overvoltage thresholds 59
ƒ Trip circuit supervision ƒ 2 Phase Undervoltage thresholds 27
The relay provides complete measurements and ƒ 1 Residual Overvoltage thresholds 59N
recording functions including: ƒ Output relay latching 86
ƒ True RMS values ƒ Broken conductor detection
ƒ Event recorder with the last 75 events, 1ms ƒ 4 shot auto-recloser 79
time-tagged.
ƒ Circuit breaker failure detection 50 BF
ƒ Fault recorder with the last 5 faults
ƒ Circuit breaker monitoring
ƒ Instantaneous recorder with the last 5
instantaneous starts ƒ Trip circuit supervision
ƒ Disturbance recorder with storage of 5 records The relay provides complete measurements and
for 3 seconds each recording functions including:
User interface includes: ƒ True RMS values
ƒ A 32-character backlit display ƒ Event recorder with the last 75 events,
1ms time stamped.
ƒ Programmable LEDs
ƒ Fault recorder with the last 5 faults
ƒ A front panel EIA RS232 for local settings
ƒ Instantaneous recorder with the last 5
ƒ A EIA RS485 rear port compatible with instantaneous starts
MODBUS, Courier, IEC 60870-5-103, or DNP3.0
ƒ Disturbance recorder with storage of 5 records
ƒ An easy to use PC setting software for 3 seconds each
User interface includes:
ƒ A 32 characters backlit display
ƒ Programmable LEDs
ƒ A front panel RS232 for local settings
ƒ A RS485 rear port compatible with MODBUS
and IEC60870-5-103
ƒ An easy to use PC setting software.

P120 P121 P122 P123 P125 P126 P127 Technical DataSheet 27 P12xy/EN TDS/B22
Ordering Information P120 P121 P122 P123

P12x Overcurrent protection P12 0 0 A *

Variant
Earth or Single Phase Overcurrent 0
3 Phase and Earth Overcurrent 1
Advanced - 3 Phase and Earth Overcurrent 2
Expert - 3 Phase and Earth Overcurrent 3
Earth current input
0.1 - 40 IN, nom A
0.01 - 8 IN, nom B
0.002 - 0.8 IN, nom C
Auxiliary voltage Digital input voltage
24 - 60 Vdc 24 - 60 Vdc A
48 - 250 Vdc / 48 - 240 Vac 24 - 250 Vdc / 48 - 250 Vac F
48 - 250 Vdc / 48 - 240 Vac 105 - 145 Vdc (special application) - not yet available H
48 - 250 Vdc / 48 - 240 Vac 24 - 250 Vdc (ac immune) - not yet available T
1)
48 - 250 Vdc / 48 - 240 Vac 110 Vdc -30% / +20% (special application) V
1)
48 - 250 Vdc / 48 - 240 Vac 220 Vdc -30% / +20% (special application) W
Communication interface
Modbus 1
Courier 2
IEC 60870-5-103 / VDEW 3
DNP3.0 4
Language
French 0
English / American 1
Spanish 2
German 3
Italian 4
Russian 5
Polish 6
Portuguese (not yet available for P120, P121, P122 or P123) 7
Dutch (not yet available for P120) 8
Czech (not yet available for P120) A
Hungarian (not yet available for P120) B
Greek (not yet available for P120) C
Turkish (Available for all variants EXCEPT P120) E
Chinese (Only available with Phase 2 Hardware with graphical display and NOT P120) D
Hardware Platform
AREVA Look & Feel Phase 1 1
AREVA Look & Feel Phase 2 2
Latest Major & Minor Software release (2 digits) A *

NOTE: 1) Options V and W are only available when ordering through China manufacturing unit

P120 P121 P122 P123 P125 P126 P127 Technical DataSheet 28 P12xy/EN TDS/B22
Ordering Information P125 P126 P127

P12y Overcurrent protection P12 0 A *

Variant
Directionnal/Non-directional (E/F) Overcurrent relay 5
Three Phase Overcurrent & Directionnal/Non-directional earth fault relay 6
Directionnal/Non-directional Three Phase Overcurrent & 7
Directionnal/Non-directional earth fault relay
Earth current input
0.1 - 40 IN, nom A
0.01 - 8 IN, nom B
0.002 - 1 IN, nom C
Voltage inputs
57 – 130 V A
220 – 480 V B
Auxiliary voltage Digital input voltage
24 - 60 Vdc 24 - 250 Vdc / 24 - 240 Vac A
48 - 250 Vdc / 48 - 240 Vac 24 - 250 Vdc / 24 - 240 Vac F
48 - 250 Vdc / 48 - 240 Vac 105 - 145 Vdc (special application) - not yet available H
48 - 250 Vdc / 48 - 240 Vac 24 - 250 Vdc (ac immune) - not yet available T
1)
48 - 250 Vdc / 48 - 240 Vac 110 Vdc -30% / +20% (special application) V
1)
48 - 250 Vdc / 48 - 240 Vac 220 Vdc -30% / +20% (special application) W
Communication interface
Modbus 1
IEC 60870-5-103 / VDEW 3
DNP3.0 - not yet available 4
Language
French 0
English / American 1
Spanish 2
German 3
Italian 4
Russian 5
Polish 6
Portuguese 7
Dutch 8
Czech A
Hungarian B
Hardware Platform
AREVA Look & Feel Phase 1 1
AREVA Look & Feel Phase 2 2
Latest Major & Minor Software release (2 digits) A *

NOTE: 1) Options V and W are only available when ordering through China manufacturing unit

P120 P121 P122 P123 P125 P126 P127 Technical DataSheet 29 P12xy/EN TDS/B22
P120 P121 P122 P123 P125 P126 P127 Technical DataSheet 30 P12xy/EN TDS/B22
T&D Worldwide Contact Centre
Available 24h a day: +44 (0) 1785 25 00 70
contact.centre@areva-td.com
www.areva-td.com

Вам также может понравиться