FDT software presentation

Arjan ten Broeke, Services EMEA

Features SprinkFDT
Calculate

the time to trip the dry valve and the time to deliver water towards the open sprinkler(s). UL listed and FM approved program of this type as defined by NFPA 13, chapter 7.2.3.6. files electronically and let the AHJ review the calculation using the free viewer. can be used to calculate dry and pre-action systems information: www.sprinkcad.com

1st

Send

Software

Additional

confidential

According BS EN12845
11.2.2 Size of installations The net volume of the pipework downstream of the control valve set shall not exceed that shown in Table 18, unless a calculation and test shows that the maximum time between a sprinkler opening and water discharging is less than 60 s.

confidential

According BS EN12845
11.1.3 Size of installations The maximum area controlled by a single wet alarm valve, including any sprinklers in a subsidiary extension, shall not exceed that shown in Table 17.

confidential

Fluid Delivery Time


Water delivery time is primarily determined by: The configuration and volume of the piping network System air pressure at the time of accelerator trip Number and orifice size of open sprinkler(s) Water supply characteristics

confidential

Example Dry system: Calculation of a dry system

confidential

Example Dry system: Purpose


To meet up with the required Fluid Delivery Time according the standard (EN12845, NFPA13, FM, VdS). Predict the Fluid Delivery Time in the engineering phase. To reduce the amount dry alarm valves, feed connections, shut off valves, air maintenance devices and ITCs.

confidential

Example Dry system: Design parameters


Standard: BS EN12845 Hazard class: HHS System type: Dry Required density: 12,5 mm/min Area of operation: 325 m2 Total area: 90 x 80 = 7200 m2 Distance between sprinklers: 3 meter Distance between branch lines: 2,5 meter Area per sprinkler: 7,5 m2 Number of sprinklers: 960 pieces

confidential

Example Dry system: Steps


Steps:
1.Determine 2.Design

the design parameters

the system the diameters

3.Determined 4.Calculate 5.If

the demanding remote area

necessary adjust the diameters of the system and recalculate a suitable pump the Fluid Delivery Time for the most demanding sprinkler

6.Select

7.Calculate 8.

If necessary redesign and calculate the system to have the water delivered within 60 seconds and that the hydraulic demand is within the pump curve

confidential

Example Dry system: Conclusion and results


FDT

calculation proves and allows a dry system with a volume of dm3 to be supplied with one Dry Pipe Valve. According table 18 of the EN12845 this system should be supplied with 3 Dry Pipe Valves. The SprinkFDT calculation saves the installation of 2 additional dry alarm valves, 2 shutoff valves and the feed connections to the different systems. Instead of 3 feed connections only 1. system requires an Inspection Test Connection. This can be reduced from 3 to 1 one. Saves 2 test connections. system requires an air maintenance device. So you will save 2 devices.

Every

Every

10

confidential

Example Dry system: Conclusion and results


Total Save Save

savings over 12.000,-. time required for inspection and testing. on maintenance due to less components.

11

confidential

Any Questions?

confidential

Thank You