Вы находитесь на странице: 1из 1

MASON INDUSTRIES, Inc.

Manufacturers of Vibration Control Products


NY Mailing Address: PO Box 410, Smithtown, NY 11787

CERTIFIED FOR

TYPE

350 Rabro Drive Hauppauge, NY 11788 631/348-0282 FAX 631/348-0279 Info@Mason-Ind.com

2101 W. Crescent Ave., Suite D Anaheim, CA 92801 714/535-2727 FAX 714/535-5738 Info@MasonAnaheim.com

: CUSTOMER : CUSTOMER P.O. : MASON M.I. : DWG. NO. :


JOB NAME

Neoprene Jack-Up Assembly Housing 1336

FSN

Rubber Plug, to keep concrete out during pour. Remove Plug after concrete has set. Screw Adjusting Screw into Housing. rubber Whisker protrudes after pour.

1336 Housing Castings are color coded

Floating Floor Grout holes flush after floor is raised

Rebar or Mesh as required. See structural drawings

Steel Plate

3 1/16" (78mm) 5 1/2" (140mm) Polyethylene Sheet or Concrete Release Surface. TYPE FSN RATINGS (1336 Housing)
EAFM Neoprene Element

1" (25mm)

AASHTO Specification Element 3/4"-10UNC Lifting & Adjusting Screw

FLOOR IN POURED POSITION

FLOOR RAISED TO OPERATING HEIGHT


Air Gap A Most Common 1" or 2" Floor ** Thickness B Overall Height C

Load Capacity

Duro0.2" 0.3" 5.0mm 8.0mm Casting Element Color meter Defl. Defl. Defl. Defl. Color Type Size No. Mark 5 [lbs] [lbs] [kg] [kg] Code 3" - Minimum Air Gap 335 500 152 227 Green 500 12530 Green 40 4" - Most plus 470 700 214 318 Red 700 12530 Red 50 (25mm or 50mm Common FSN *Floor 60 600 900 273 409 White 900 12530 White 5" Seldom Occasionally (3,4,5,6) Thickness 50 875 1300 398 591 Orange 1300 11901 Red 6" - Common 3" or 4" 1700 11901 White 60 1140 1700 518 773 Yellow (75mm or 100mm ** Thicker Floors or Fractional * FSN Housing Height matches floor thickness. Housing suffix indicates housing height, i.e. FSN4 indicates a 4" floor and housing; FSN6, a 6" floor and housing, etc. Dimensions as Required. Note : Castings can be modified for floors over 6" thick. Mounts are designed for 0.3" maximum deflection under constant load. BRIDGE-BEARING NEOPRENE SPECIFICATIONS Temporary loadings may greatly exceed these numbers without ORIGINAL PHYSICAL TESTING FOR AGING COMPRES- damage or permanent set. See graph below. PROPERTIES SION SET (c) (d) All mountings are molded to AASHTO specifications. Elastomer may be (a) (b) (b) Oven Aging(70hrs/212 F) Ozone (e) Neoprene or AASHTO equivalent. Duro- Tensile Elongat. Hard- Tensile Elongat. 1 ppm in air 22hrs/150 F The theoretical natural frequency of mounts without Dynamic Stiffness meter Strength at Break ness Strength at Break by Vol.20% Method B [min.] [min.] [max.] [max.] [min.] Strain 100 F correction: at 0.2" (5.0mm) - 7.0 Hz / at 0.3" (8.0mm) - 5.7 Hz 405 2000 psi 450% + 15% 15% - 40% No Cracks 30% (max) Actual frequencies may be read from the chart. 505 2500 psi 400% + 15% 15% - 40% No Cracks 25% (max)
605 2500 psi 350% + 15% 15% - 40% No Cracks 25% (max) (a)ASTM D-676 (b)ASTM D-412 (c)ASTM D-573 (d)ASTM D-1149 (e)ASTM D-395

LOAD - DEFLECTION CURVES


5000
STEADY LOAD ZONE

DYNAMIC STIFFNESS & FREQUENCY CURVES


50 3000

5000
MAXIMUM LOAD TEMPORARY OVERLOAD ZONE

DYNAMIC NATURAL FREQUENCY -Hertz

LOAD (lbs) PER MOUNTING

40 30 20

2400

DYNAMIC NATURAL FREQUENCY -CPM

70 Duro 60 Duro 50 Duro 40 Duro 30 Duro

1800 1200

4000

4000

3000 1700 2000 1300 900 700 500

3000

10 8 6 5 4 3 2

600 480

Test No. KAL-1391-1-72


Durometer Compound Stiffness 70 7072 2.32 60 6072 1.63 50 5072 1.50 40 4072 1.43 30 3072 1.25 Data based on Resonance Tests on Numbered Neoprene Compounds For EAFM mounts 0.02 0.04 0.06 0.10 0.20 0.40 0.60 1.00

360 300 240 180 120

2000

1000

1000

1 0. 01

60

0 0 0.1 0.2 0.3 0.4 0.5 0.6


DEFLECTION (inches)

STATIC DEFLECTION - inches


Note: Data does not apply to compounds other than those tested.