Академический Документы
Профессиональный Документы
Культура Документы
O
s1
of the fundamental of the current link-
age of a poly-phase (m > 1) rotating-field stator winding (or a rotor winding), when the effective
value of the stator current is I
s
, we may write
s
s
I
p
N m
2
2
4
2
1
s1
O
t
= . (2.7)
For example in the case of Fig. 2.15, if N
s
= 200,
1
= 0.96 , m = 3, p = 1 and ( ) i t i
sU
A = =
1 (and
thus the effective value of the sinusoidal current is 2 / 1
s
= I A = 0.707 A), we obtain
O
s
= 183 A.
2.6 Voltage Vector Graph
Since the winding is spatially distributed in the slots on the stator surface, the flux penetrating the
winding does not intersect all windings simultaneously, but with a certain phase shift. Therefore the
electromotive force (emf) of the winding is not calculated directly with the number of turns N
s
, but
the winding factors
v
corresponding to harmonics are required. The emf of a fundamental harmonic
induced in the turn is calculated with the flux linkage + by applying Faradays induction law
.
d
d
d
d
t
N e = = (2.8)
Electrical drives 2.15 Juha Pyrhnen, LUT, Department of Electrical Engineering
Figure 2.17 illustrates the voltage vector graph of the two-pole winding of Fig. 2.15.
1
2
3
4
5
6
7
8
9
10
11
12
U
1
8
-U
Figure 2.17. The voltage vector graph for the winding of Fig. 2.15 Q
s
= 12, p = 1, q
s
= 2. The figure illustrates also the
calculation of the voltage in a single coil with the radii of the voltage vector graph.
When the flux rotates inside the stator bore, the maximum voltage is simultaneously induced to the
coil sides 1 and 7. If the flux rotates clockwise, a maximum voltage is induced to the coil sides 2 and
8 in a moment, etc.
The coils of the phase U travel from slot 1 to slot 8 and from slot 2 to slot 7. Thus a voltage, which
is the difference of the phasors
1
U and
8
U , is induced to the coil 1. The total voltage of the phase is
thus
U U U U U U = +
1 8 2 7
, (2.9)
and the winding factor
1
for the fundamental harmonic is calculated here as a ratio of the geometric
sum and the sum of absolute values:
1 966 . 0
7 2 8 1
7 2 8 1
1
s =
+ + +
+
=
U U U U
U U U U
. (2.10)
The winding factor is always 1. The value
1
= 1 can be reached when q = 1. In general, the wind-
ing factor for a harmonic v is calculated as
|
|
.
|
\
|
|
.
|
\
|
|
|
.
|
\
|
=
s
s
p
sin
2
sin
2
sin 2
Q
p
mp
Q
m
W
v
v
t
v
v . (2.11)
W is the coil width, v is the order of the harmonic, Q
s
is the number of stator slots, p is the number
of pole pairs, and m is the phase number.
Electrical drives 2.16 Juha Pyrhnen, LUT, Department of Electrical Engineering
2.7 Harmonics
Depending on the number of phases m, the slot winding develops the harmonics (k is a positive inte-
ger)
v = 1 2km. (2.12)
A symmetrical three-phase winding may develop the following harmonics listed in Table 1.
Table 1 Orders of the harmonics developed by a three-phase winding (m = 3)
K 0 1 2 3 4 5 6 7...
v +1 +7 +13 +19 +25 +31 +37 +43...
5 11 17 23 29 35 41...
We see that v = 1 and all harmonics divisible by three are missing. In other words, a symmetrical
poly-phase winding does not produce a harmonic propagating to an opposite direction at the fre-
quency of the fundamental harmonic. Instead, a single-phase winding m = 1 creates also a harmonic,
the ordinal of which is v = 1. This is a particularly harmful harmonic, and impedes the operation of
single-phase machines. For instance a single-phase induction motor, due to the field rotating to the
negative direction, does not start without assistance.
The winding factor may be also used to derive the relative magnitude of the magnetomotive force.
Fig. 2.18 depicts the current linkage distribution of a phase A of a short-pitch winding (Q = 24, m =
3, q = 2, W/t
p
= 5/6), as well as its fundamental harmonic and third harmonic at time t = 0, when
i i
A
= . The winding factors for the lowest harmonics and the amplitudes of the magnetomotive
forces are:
v = 1
1
= 0.965 0.965 = 0.933
O
1
= 1.188
O
max
v = 3
3
= 0.707 0.707 = 0.5
O
3
= 0.212
O
max
v = 5
5
= 0.258 0.258 = 0.067
O
5
= 0.017
O
max
Only the harmonics 1 and 3 are illustrated in Fig. 2.18.
1 2 3 4 5 6 7 8 9 10 11 12 24
+A -C +B -A +C -B +A
...
o
O(o)
0
t
O
max
max
F
Figure 2.18. A short-pitch winding and the analysis of its current linkage distribution of the phase A. The distribution
includes a notable amount of the third harmonic. In the figure, the first and third harmonics are illustrated with broken
lines.
Electrical drives 2.17 Juha Pyrhnen, LUT, Department of Electrical Engineering
The strength of harmonics is often expressed in per cents of the fundamental harmonic. In this case,
the amplitude of the third harmonic is about 22 % of the amplitude of the fundamental harmonic;
this, however, is not harmful, since the current linkage wave created together by the windings can-
cels the third harmonic. This is illustrated in Fig. 2.19, in which there are currents i
A
= 2i
B
= 2i
C
,
and i i
A
=
flowing in the winding of Fig. 2.18.
1 2 3 4 5 6 7 8 9 10 11 12 24
+A -C +B -A +C -B +A
...
A
B
C
Figure 2.19. The cancellation of the third harmonic in a three-phase winding. There are currents i
A
= -2i
B
= -2i
C
flowing
in the winding. We see that when we sum the third harmonics of the phases B and C with the harmonic of the phase A,
the harmonics cancel each other.
In single- and poly-phase machines, the number of slots is preferably selected higher than in three-
phase machines. Further, it is sometimes necessary to fit a different number of conductors in the
slots to make the fraction line O(o) approach sinusoidal form.
A poly-phase winding thus produces superharmonics, the orders of which are calculated by Eq.
(2.12). When the stator is fed at an angular frequency e
s
, the angular speed of the harmonicv with
respect to stator is
e
e
v
vs
s
= . (2.13)
When we take the sign of the harmonic into account, we see that the waves of the different harmon-
ics propagate in different directions in the air gap. This is illustrated already in Fig. 2.14, which
shows how the shape of the mmf wave changes as the wave propagates in the air gap. The deforma-
tion of the wave in particular is an indication of the fact that the harmonic amplitudes proceed at dif-
ferent speeds and to different directions. The harmonic induces a voltage of fundamental frequency
to the stator winding. The order of the harmonic indicates how many wavelengths of the harmonic
fit to the distance 2t
p
of a single pole pair of one fundamental harmonic. This yields the number of
pole pairs and the pole pitch of the harmonic
p p
v
v = , (2.14)
Electrical drives 2.18 Juha Pyrhnen, LUT, Department of Electrical Engineering
v
t
t
v
p
= . (2.15)
The amplitude of the v th harmonic is determined from the amplitude of the current linkage of the
fundamental harmonic by
O O
v
v
v
=
1
1
. (2.16)
Figure 2.20 shows clearly how an increase in the number of slots per pole and per phase improves
the form of the curve, now q
s
= 3. Figure shows that the magnetic axis of the phase A is in the direc-
tion of the arrow drawn in the middle of the figure. Since we have a three-phase machine, the direc-
tions of the currents of the phases B and C have to be such that the magnetic axes are at a distance of
120
o
of the magnetic axis of the phase A.
a)
+A
-A
-C
+B +C
-B
A
C
B
t
t
p
v
b)
2t
p
O
A
u
-A
Figure 2.20 a) A three-phase diamond winding p = 1, q
s
= 3, Q
s
= 18. Only the coil end of the phase A on the observer
side is visible. There are similar coils also in the other end of the machine, the only difference being that the transition
from one slot to another takes place at the other end only. Also the magnetic axes of the phase windings are indicated in
the illustration. The depicted current directions correspond to a situation in which the current of the windings B and C is
a negative half of the current of the phase A. The direction of the created flux distribution u and the flux linkage + is
thus at that moment the direction of the magnetic axis of the phase A. b) The current linkage of the winding.
A poly-phase stator winding in the stator of a rotating-field machine creates a flux wave, when a
symmetrical poly-phase current flows in the winding. The flux wave is created for instance when the
mmf of Fig. 2.20 propagates in side direction and the currents of the poly-phase winding are alter-
nating sinusoidally as a function of time. For instance in a three-phase winding, time-varying sinu-
soidal currents with a 120 phase shift create a temporally and positionally alternating flux in the
windings that are set at the distances of 120 electrical degrees. This flux propagates as a wave on the
inner stator surface.
Figure 2.21 illustrates some current linkage curves of the winding of Fig. 2.20 at different instants of
the three-phase current.
Electrical drives 2.19 Juha Pyrhnen, LUT, Department of Electrical Engineering
i
1
i
2
i
3
t
1
t
2
t
3
t
4
2t
p
O
A
u
-A
2t
p
O
u
2t
p
O
u
2t
p
O
u
2t
p
O
u
t
5
A
A
A
A
Figure 2.21. The current linkage created by the three-phase winding at different values of the three-phase current. We
see that the wave propagates to the right, when the currents vary as functions of time. The peak of the flux shifts to the
right as the time progresses.
In this kind of a winding, the current linkage wave propagating in the stator bore creates a field that
propagates along the periphery, that is, a rotating field. The winding of a rotating-field machine has
thus been created.
The main flux penetrating the winding varies almost sinusoidally as a function of time
( ) t t e u u sin
h h
= . (2.17)
According to Faradays induction law, the induced voltage is obtained by the flux linkage +
t N
t
N
t
e e u e
u
+
cos
d
d
d
d
h 1
h
1
1
smv1
= = = . (2.18)
Electrical drives 2.20 Juha Pyrhnen, LUT, Department of Electrical Engineering
If the induced voltage is assumed sinusoidal, the effective value becomes
h 1
2
1
2
1
u e N e E = = . (2.19)
To be able to calculate this value, the peak value of the flux related to the fundamental harmonic
has to be known. This peak value has to be calculated by integrating the flux density over the pole
pitch and the assumed machine length, Fig. 2.22.
} }
=
'
0 0
h
d )d (
p L
L B t u
o
t
. (2.20)
Assuming the flux density distribution to be sinusoidal with respect to x and constant with respect
to y, we obtain the peak value of flux by the integration (2.20)
' u
h i p
= o t
o
B L , (2.21)
where
i
o is a coefficient indicating the arithmetical average of the flux density in the x-direction,
which at a sinusoidal flux density distribution obtains the value t = / 2
i
o .
Figure 2.22. The flux density dis-
tribution extending over a pole
pitch, integrated over the surface,
yields the maximum flux of the
machine.
L'
B
o
t
p
x
y
2.8 Magnetizing Inductance of the Rotating-Field Winding
Poly-phase rotating-field machines have a central role in electrical drives. Next, we calculate the
magnetizing inductance for an unsaturated machine. As stated previously, the peak value of the
flux of the machine depends on the pole pitch t
p
, the machine length L, and the air gap flux den-
sity B
o
. The flux linkage of a single phase is obtained correspondingly by multiplying by the effec-
tive turns (of winding) N
p s h
'
B L N = t + (2.22)
Electrical drives 2.21 Juha Pyrhnen, LUT, Department of Electrical Engineering
On the other hand, the magnetic flux density of the air gap in the equivalent air gap o
de
can be de-
termined by using the current linkage O of the phase
de
s 0
o
O
=
o
B . (2.23)
Hence, we obtain for the flux linkage of the single phase
'
p
de
s 0
s h
L N
t
= t
o
O
+ (2.24)
The current linkage of the phase winding is
s
s
s
2
2
4
I
p
N
t
=
O . (2.25)
The substitution yields for the flux linkage
s p
1
de
0
s 1 h
2 '
2
4 2
I L
p
N
N
s
t
t
= t
+ , (2.26)
( )
s
2
s 1
de
p
0 h
2 '
4
2
1 2
I N L
p
t t
=
o
t
+ . (2.27)
By dividing by the peak value of the current, we obtain the main inductance of the single phase
( )
2
s 1
de
p
0 p
'
4
2
1 2
N L
p
L
o
t
t t
= . (2.28)
The magnetizing inductance of the machine can be determined by multiplying the main inductance
by m/2
( )
2
s 1
de
p
0 m
'
4
2
1 2
2
N L
p
m
L
o
t
t t
= (2.29)
If the machine runs at a constant frequency (for instance a network connected machine), reac-
tances can be employed in the calculation. The magnetizing inductance of Eq. (2.29) corresponds
with the magnetizing reactance X
m
m m
L X e = . (2.30)
If the machine is magnetized only by the rotating-field winding of the stator, the magnetizing cur-
rent of the stator is obtained by the air gap voltage U
so
ms s ms
/ X U I
o
= . (2.31)
Electrical drives 2.22 Juha Pyrhnen, LUT, Department of Electrical Engineering
2.9 Winding Systems
Next, different winding systems are discussed in brief. Table 2.4 introduces the winding systems
used in practice. In industrial motors, the most common winding type is the three-phase winding. In
large synchronous machines, a six-phase winding is used to some degree in the context of power
electronic drives. Single and double-phase windings occur chiefly in small induction motors that are
fed directly from a single-phase network.
In certain special cases, it is also possible to use several three-phase windings having different phase
shifts in the same machine. This is a potential solution for instance in quite large 690 V high-speed
machines, in which the selection of the winding solution is constrained by the lacking winding alter-
natives.
Table 2.4. The phase systems of the windings of electrical machines. The fourth column introduces the so-called radially
symmetric winding alternatives (Vogt 1996)
number of phases m normal system reduced system corresponding non-
reduced system
1
m' = 2
2
m' = 4
3
m' = 6
4
m' = 8
5
m' = 10
6
m' = 12
On a single magnetic axis of an electrical machine, there may be located only an axis of a single
phase winding. If another phase winding is located on the same axis, no genuine poly-phase system
is created, because both windings produce a collinear flux. Therefore, each phase system that in-
volves an even number of phases is reduced to involve only a half of the original number of phases
m' as illustrated in Table 2. If the reduction produces a system with an odd number of phases, we
obtain a so called radially symmetric poly-phase system, also called a normal system.