Вы находитесь на странице: 1из 3

If the air is not continuously and Dehumidification Run Time

adequately dehumidified, the moisture If the system cannot provide sufficient


added to the space might be greater dehumidification while it reacts to
than the HVAC system’s ability to temperature control alone, it must
remove it. This moisture source continue moisture removal without
normally results in moisture-related affecting interior temperatures and
mildew problems on the interior occupant comfort. This can be
Figure 2 - Effects of Positive surfaces of the building (that is, accomplished by reheating—a form of
Pressurization interior finishes and the surface of simultaneously cooling and heating to
An important consideration in achieving furnishings). continue dehumidification while not
positive pressurization is that interior overcooling the occupants.
building partitions not adversely affect the Airflow Dehumidification
distribution of air. To provide proper dehumidification, Methods of reheating include direct
an HVAC system must: or indirect gas-fired heating; hot-
The way buildings operate today is water heating; hot-gas reheating for
as a multitude of pressure vessels: • Fully dehumidify the air that flows refrigeration-based units; and for parts
interstitial spaces in an exterior wall; across the cooling coil. of the country that allow it—electric.
plenums; dropped ceilings; rooms that • Provide sufficient run time to
typically have doors closed between remove moisture from the interior Devices added to the equipment, such
them. These different pressure air despite the satisfaction of as wraparound coils, can also provide
relationships—some of which are very interior temperatures. a means of reheating. Wraparound
well connected to the supply air, some coils simply transfer energy from the
To fully dehumidify the airflow incoming cooling coil air stream to
that are not—include pressure-starved across the coil, cooling coils must be
areas and some pressure-excessive the exiting cooling coil air stream.
sized properly to meet the sensible These coils are available in a passive
areas. load (load associated with dry- refrigeration-based unit or as a water-
Ventilation bulb temperature) and latent load based system that uses pumps to move
Most building codes establish (moisture in air associated with wet- the water through the system.
minimum ventilation requirements bulb temperature). This includes the
in relation to occupancy or space combination of both outside air and In conventional HVAC systems, two
function. These requirements are return air. This air must be brought dehumidification methods are used.
usually based on ASHRAE Standard to a temperature that causes the The first is a cooling-based system
62-1989, “Ventilation for Acceptable moisture in the air to condense for cooling air below its dewpoint.
Indoor Air Quality.” This standard latent heat (or latent energy) removal. Moisture condenses on the cooling
specifies the minimum acceptable Simultaneously, the cooling coil is surface and is removed from the air.
outdoor air requirements for occupied reducing the sensible temperature of For example, a cooling-based system
spaces. the air to offset the sensible energy can cool an outside air stream from
generated in the space (lights, solar, 95°Fdb (55% RH) to 77°Fdb. At
Providing conditioned outside air not people, equipment, etc.). A common 77°Fdb the air is at 100 percent
only helps pressurize a building but range of temperature for the cooling RH. If it is cooled below 77°Fdb to
also dilutes chemicals or particulate of this air is between 50°F and 55°F. 55°Fdb, 68 grains of moisture per
pollutants generated in the space. At this temperature, most HVAC pound of dry air are condensed out of
Outside air can also be induced in system airflows will be at 100% the air and onto the cooling coil.
the space by the HVAC system as relative humidity (RH) and will
ventilation air. If the HVAC system effectively condense moisture from The second method involves the use
introduces air into the space, the of a desiccant that attracts moisture to
the air. Air provided to a space under its surface by introducing a low vapor
system must continuously dehumidify these conditions has the best chance
the air. Of course, adequate pressure at the desiccant surface. The
of maintaining interior conditions of vapor pressure of the moisture in the
dehumidification should not be 75°F dry-bulb (°Fdb) and 60% RH. air is higher, so moisture travels from
sacrificed for adequate ventilation. Continued on Page 14

Interaction Between the Building Envelope and the HVAC Systems

A/E Interaction Positive Building Pressurization Negative Building Pressurization


Correct Wall Mildew/moisture problems unlikely in wall systems Possible mildew/moisture problems in wall system
Construction* and occupied space and occupied space

Incorrect Wall Possible mildew/moisture unlikely problems in Probable mildew/moisture problems in wall system
Construction problems in wall system; occupied space and occupied space

* Wall construction refers to vapor retarders and air and rainwater barriers. Building envelope and HVAC system design must interact to reduce the
potential of moisture and mildew formation.
www.fleng.org Florida Engineering SOCIETY JOURNAL • NOVEMBER 2006 13
Avoiding Moisture and Mold Problems in and its RH increases to the room’s RH Engineers] ASHRAE Handbook:
Florida Buildings Continued level once the two air streams reach Fundamentals.” Its second aspect,
the air to the desiccant. The desiccant equilibrium. likened by Odom to a Windows-like
then must be recharged through a computer operating system, is to
heating process, allowing the moisture Behind the Book facilitate access and direct readers to
to be driven from the desiccant and In assembling his book, Commissioning other documents. The biggest gap the
discharged to another location besides Buildings in Hot, Humid Climates: firm feels it has identified is lack of
the cooling air stream. Design and Construction Guidelines, co- detail in prescriptive vs. performance
author J. David Odom and LBDG language. ASHRAE Fundamentals, for
One of the best strategies is a hoped to literally fill in key gaps
combination of desiccant and cooling example, talks in terms of performance
missing in many reference manuals. language he says. “It doesn’t say you
systems, particularly for 100% “It is not everything you need to
outside air streams such as makeup must have constant pressurization, it
know about designing buildings in says ‘infiltration must be minimized.’
air systems. Since air exits a cooling- hot, humid climates, but a pathway
based system at saturation, it only What does that mean?” says Odom.
to crystallizing key issues that are To an architect, it means take out a
moves to a lower RH once it mixes not picked up by other manuals like
with the room air and heat is added to caulk gun and fill up holes. “Using
[the American Society of Heating, performance language may work fine
it. The desiccant, on the other hand, Refrigerating and Air-Conditioning
enters the space with very low RH, in a more forgiving environment, but
there are some things that you need to
get into very prescriptive language—
Do this, don’t do that.” Q
About the Author: J. David Odom has been
a moisture and mold forensics specialist with
CH2M HILL since 1978 during which time
he has managed some of the largest and
most complex moisture and mold problems
in the country including the recent $60M
construction defect claim at the Hilton
Hawaiian Village in Honolulu and the $20M
claim at the Martin County (FL) Courthouse.
In 1998, he was named by IAQ Publications
as IAQ Person of the Year and in 1999 he was
recognized as one of the 50 Most Influential

Tricky
People in the IAQ field. He has published
3 manuals and over 50 technical articles,
including a recent monograph on moisture

Project?
and mold for the National Council of
Architectural Registration Boards (NCARB).
This article was reprinted by permission from
“Sealing the Cracks in IAQ” in the September

Our Treat. 1999 issue of Consulting-Specifying Engineer.


Commissioning Buildings in Hot, Humid
— Barbara Mulkey Climates: Design and Construction Guidelines,
which has been successfully field-tested in
over $2 billion in new construction since
1990 and is available by reaching David at
407-697-7227 or d.odom@lpdg.net.

There are the simple, straightforward projects.


And then there are the ones that become the
stuff of engineering lore.At Mulkey, we’re just as
excited to take on one as the other. So go ahead.
Throw a challenge our way. We can’t wait.

CHARLOTTE, NC / RALEIGH, NC / CARY, NC


COLUMBIA, SC / METRO-ATLANTA, GA / JACKSONVILLE, FL
W W W. M U L K E Y I N C . C O M

14 Florida Engineering SOCIETY JOURNAL • NOVEMBER 2006 www.fleng.org

Вам также может понравиться