Tutorial
Conductor Fatigue
Louis Cloutier Cloutier, Convenor Andr Leblond, Secretary
CIGR WG B2.30 "Engineering Guidelines Relating to Fatigue Endurance Capability of Conductor/Clamp Systems" February F b 28 28, 2011 CIGR 2011
Outline of Presentation
Introduction Examples p of Conductor Fatigue g Typical Conductor Configurations Some Characteristics of Suspension Clamps CIGRE Technical Brochures Prediction of Aeolian Vibration Amplitudes
Laboratory Fatigue Tests Resonant Type Test Benches Fatigue Endurance Data
Vibration Measurement Analysis Case Study Conductor and Clamp Types Lacking Fatigue Data Conclusion
Study Committee B2 - Technical Advisory Group B2-AG-06 3
2011-02-28
Introduction (I)
Aeolian vibrations :
Small vibration amplitudes exceeding rarely the conductor diameter; frequency range : 3 to 150 Hz; winds : 1 to 7 m/s
Such failures are caused by dynamic stresses resulting from reverse bending Other wind-induced conductor motions such as wakeinduced oscillations and galloping may also be responsible for fatigue conductor strand failures
Study Committee B2 - Technical Advisory Group B2-AG-06 4
2011-02-28
Introduction (II)
2011-02-28
Conductor fatigue occurs when wind-induced vibration is not controlled Fretting fatigue has long been recognized as being the cause of strand failures in outer as well as inner layers of the conductors Steel core can fail by overheating after aluminum layers are separated Interstrand microslip amplitude increases, small cracks are generated t d and d some propagate t up to t complete l t strand t d failures f il
Study Committee B2 - Technical Advisory Group B2-AG-06 6
2011-02-28
Strand failures occur mainly at suspension p clamps p where such singular conditions are created To a lesser extent, a similar phenomenon can occur at damper damper, marker or spacer clamps Early detection of conductor failure or risk i k of ff failure il ( (attentiveness tt ti to t early warnings) Wear and failure of conductor strands due to spacer clamp loosening Fatigue usually takes many years to become apparent
Study Committee B2 - Technical Advisory Group B2-AG-06 7
2011-02-28
The conductor size is chosen to suit electrical and mechanical requirements The most common conductor type is ACSR (Aluminum Conductor Steel Reinforced) The ratio of steel to aluminum areas vary widely
2011-02-28
2011-02-28
Most of the conductor fatigue test results refer to those obtained bt i d when h th the conductor d t is supported in a short metallic clamp The ideal profile of the clamp body follows the natural curvature of the conductor The ends of the clamp body and the keeper must be rounded to avoid indenting the conductor The clamp should be able to rotate in a longitudinal vertical plane to accommodate asymmetrical ti ll loads d
2011-02-28 Study Committee B2 - Technical Advisory Group B2-AG-06 10
2011-02-28
11
Fretting behaviour in stranded conductor Determination of fatigue endurance capability Inner conductor mechanics Assessment of vibration severity on actual lines Evaluation of conductor residual life This TB covers the determination of possible damage and ways to predict remaining life of conductors as well as new methods to t t conductor/clamp test d t / l systems t
2011-02-28 Study Committee B2 - Technical Advisory Group B2-AG-06 12
This TB includes a review of those design g tools and g gives the transmission line engineer the limits to their application
2011-02-28 Study Committee B2 - Technical Advisory Group B2-AG-06 13
Many utilities have their own design rules (for number of dampers) based on past experience Vibration severity can also be measured on existing lines A useful analytical approach is the "Energy Balance Principle" (EBP) Principle The EBP leads to an estimate of conductor vibration amplitude based on equating the energy input from the wind with the energy absorption (damping) of the conductor and dampers The EBP can also be used for the direct design of the damping system for a new line The estimate of the expected vibratory motion from EBP is considered an upper bound and is therefore a safe value
2011-02-28
Parameters describing conductor vibration include: Bending amplitude Yb, Free loop amplitude ymax Bending angle , Wave length and Loop length This representation applies to metal clamps, not to elastomer lined clamps
2011-02-28 Study Committee B2 - Technical Advisory Group B2-AG-06 15
Several methods to measure the vibration intensity of a conductor have been employed The bending amplitude Yb method y comes out as the most finally practical It measures the differential displacement of the conductor at 89 point of contact with the clamp p mm from the last p The reverse bending amplitude was presented as an alternative to permit the installation of the vibration recorder directly onto the conductor The bending amplitude method must be properly interpreted when cushioned clamps are used Recommended by IEEE in 1966 (also in the 2007 revision) and CIGRE SC22 WG04 1979 and SC22 WG11 TF02 1995
2011-02-28 Study Committee B2 - Technical Advisory Group B2-AG-06 16
HILDA
TVM 90
Vibrec 400
Ribe LVR
Pavica
Scolar III
2011-02-28 Study Committee B2 - Technical Advisory Group B2-AG-06 17
a =
4 e px 1 + px
Ea d p 2
Yb
H p= EI
An idealized bending stress in the top-most outer-layer strand (in the plane of the last point of contact) is calculated from the bending amplitude (Poffenberger-Swart formula) Ea: modulus of elasticity of outer wire material (N/mm2) d: diameter of outer layer wire (mm) H: conductor tension at average temperature during test period (N) ( ) EI: sum of flexural rigidities of individual wires in the cable (Nmm2) x: distance from the point of measurement to the last point of contact between the clamp and the conductor
2011-02-28 Study Committee B2 - Technical Advisory Group B2-AG-06 18
a = d Ea
m fymax EI
The idealized bending stress can be derived from the free loop amplitude, ymax, which is the vibration parameter often measured in indoor test spans Ea: Youngs modulus for the outer-layer strand material (N/mm2) d: diameter of outer layer wire (mm) f: frequency of the motion (Hz) m: conductor mass per unit length (kg/m) g of individual wires in the cable ( (Nmm2) EI: sum of flexural rigidities
2011-02-28 Study Committee B2 - Technical Advisory Group B2-AG-06 19
The phenomenon is complex and its exact modelling has yet to be completed
Contact areas between round strands are elliptical Fretting and microslip occur in these contact areas Fatigue cracks develop out of these contact areas The knowledge on fatigue performance of conductors mostly relies on results of laboratory tests made on conductors in fixed short metallic clamps
It is not possible at the moment to determine the fatigue endurance of a conductor alone
Pneumatic tensioning system Dynamometer Amplitude measuring system Rubber dampers Wire break detection Slider 2m Vibrator Active length : 7 m 5.5 deg. 2m Suspension clamp End clamp Turnbuckle
Constant amplitude excitation Measurement of the bending g amplitude Yb and/or the free loop amplitude ymax Most tests done with conductors supported in short metallic clamps Clamps usually held in a fixed position on the test bench
2011-02-28
21
The results of fatigue tests ultimately lead to the presentation of a fatigue (S (S-N) N) curve Note scatter in the data The endurance limit is determined at 500 megacycles Idealized bending stress relative to Yb vs megacycles to failure Endurance limits
22.5 MPa for single-layer ACSR 8.5 MPa for multi-layer ACSR
2011-02-28
22
2011-02-28
23
Widely used set of empirical criteria (Guide for Aeolian Vibration Field Measurements of Overhead Conductors, IEEE P1368, 1368 200 2007) ) The bending amplitude may exceed the endurance limit during no more than 5% of total cycles No more than 1% of total cycles may exceed 1.5 time the endurance limit No cycle may exceed 2 times the fatigue endurance limit
2011-02-28
24
2011-02-28
25
Based on Cumulative d damage th theory (Mi (Miners rule) Total damage D at several stress levels i cumulates linearly: D = ni/Ni Failure is predicted when D = ni/Ni =1 1
The accuracy of the resulting estimate of lifetime is between 50% and d 200%
2011-02-28 Study Committee B2 - Technical Advisory Group B2-AG-06 26
First measurement at Last measurement at Duration of one measurement (s) Measurement cycle time (s) Total duration of measurement (s) Factor for extrapolation to one year Total number of measurements taken
2011-02-28
27
0 0 10 20 30 40 50
Frequency, (Hz)
2011-02-28
28
10
5% S-N curve 50% S-N curve 95% S-N curve Accumulated stress curve per year
2011-02-28
29
Evaluation of remaining lif ti lifetime, D D=1 1 There is a 86% probability that the remaining lifetime exceeds 20 years
2011-02-28
30
Frequency, (Hz) )
Assessment of the most t damaging d i frequencies Helpful for choosing the right damping system
60 55 50 45 40 35 30 25 20 15 10 5 0 0 4 8 12 16 20 24 28
2011-02-28
31
The extrapolation of fatigue data available to other types of conductors or to different types of support is not recommended Bending amplitude method is valid only for armored or unarmored conductors fitted with solid metal-to-metal clamps Not valid for cushioned clamps (armored or unarmored) Little test data for conductors except ACSR and aluminum alloys Some data for ACSR conductors with armor rods There is a need for more published data on conductor fatigue
2011-02-28
32
Guide for Aeolian Vibration Field Measurements of Overhead Conductors, , IEEE P1368, 3 , 2007 (a ( revision of IEEE 1966 Report) Transmission Line Reference Book, Wind Induced , Second Ed. EPRI 2007 ( (Chapter p 3, , Conductor Motion, Fatigue of Overhead Conductors), a revision of the 1979 Orange Book Fatigue g Endurance Capability p y of Conductor/Clamp p Systems Update of Present Knowledge, CIGRE TF B2.11.07, TB No. 332, October 2007 Engineering g g Guidelines Relating g to Fatigue g Endurance Capability of Conductor/Clamp Systems, CIGRE WG B2.30, TB No. 429, October 2010
2011-02-28
33
Conclusion
Fatigue endurance capability of conductors is a very useful parameter at the design stage as well as for a maintenance program
Aeolian vibrations and conductor fatigue are both highly complex phenomena
So far, design tools proposed are a good example of the engineering g g approach pp to solve a complex p p problem Adequate determination of the fatigue characteristics of a conductor/clamp system is very important in the design of a line
Acceptable level of conductor vibrations Determination of safe design tensions
Future work is needed to better understand the importance of many other parameters
Study Committee B2 - Technical Advisory Group B2-AG-06 34
2011-02-28
CIGRE WG B2.30 B2 30
Members : L. L Cloutier (Convenor) (Convenor), A A. Leblond (Secretary) (Secretary), U U. Cosmai, P. Dulhunty, M. Ervik, D.G. Havard, D. Hearnshaw, H.J. Krispin, M. Landeira, P. Mouchard, K. Papailiou, D. Sunkle, B. Wareing Corresponding p g Members : J.A. Arajo, j , H. Argasinska, g , J.M. Asselin, O. Cournil, G. Diana, K. Halsan, C.B. Rawlins, R. Stephen, P. Timbrell Associated Experts : T. Alderton, J. Duxbury, A. Goel, C. Hardy, A. Laneville, A. Manenti Diana, S. Pichot, T. Sepp, P. Van Dyke
35
2011-02-28
Andr Leblond, Ph.D., Eng. Tel: 1 1-514-879-4100 514 879 4100 ext. 5734 Fax: 1-514-879-4855 E-Mail: leblond.andre.2@hydro.qc.ca Address :
85, rue Ste-Catherine Ouest, 2nd floor Montreal Quebec Montreal, H2X 3P4 CANADA
2011-02-28
36
Thank you !
QUESTIONS