4250TEU-YZJ Seaspan Ship Management Local Protection Water Mist System Machinery Space _______________________________________________________________________ _

LOCAL PROTECTION WATER MIST SYSTEM MACHINERY SPACE LOCATION-ENGINE ROOM 3 RD DECK AFT, PORT SIDE

1. This system protects local hazardous area by water mist where fire most often occur. 2. Spaces protected by this system are: 1 2 3 4 5 6 MAIN ENGINE AE #1 & #2 AE#3 & #4 BOILER INCINERATOR PURIFIER

4250TEU-YZJ Seaspan Ship Management Local Protection Water Mist System Machinery Space _______________________________________________________________________ _

3. Require two signals from the detector of same area to release the system. NOTE: For CSAV Loncomilla two signals from FLAME DETECTOR as shown below is required to release the system.

AUTOMATIC RELEASE OF SYSTEM 1. A Fire starts in water mist system protected space. 2. Fire detection system on getting signal from one detector raises alarm locally & on Bridge to give initial warning.

4250TEU-YZJ Seaspan Ship Management Local Protection Water Mist System Machinery Space _______________________________________________________________________ _

Fire Control Panel 3. Seconds later another detector will activate & detector signal goes to FIRE CONTROL PANEL which activates the PUMP STARTER panel to start the pump & opens the section valve for the affected space automatically.

4. Water flow through section valve is indicated as WATER MIST SYSTEM RELEASED ON FIRE CONTROL PANEL. 5. Water in the form of mist will be released from the sprinkler nozzles in the affected area & suppress the fire.

Sprinkler Nozzle

4250TEU-YZJ Seaspan Ship Management Local Protection Water Mist System Machinery Space _______________________________________________________________________ _

6. Operation of this system is controlled by the water level float switch fitted in Distill water tank. Ensure distill water tank have sufficient water at all times.

MANUAL RELEASE OF SYSTEM IN CASE OF FAILURE OF AUTOMATIC RELEASE. 1. Go to FIRE CONTROL STATION OR EHQ for manual release.

2. Change over the mode of MANUAL RELEASE PANEL from AUTOMATIC to LOCAL by key. 3. Manually activate the starting signal for pump to START by changing the knob of affected space from AUTOMATIC to LOCAL. 4. This action will start the pump, opens the section valve for affected space/spaces & water mist releases to suppress the fire.

4250TEU-YZJ Seaspan Ship Management Local Protection Water Mist System Machinery Space _______________________________________________________________________ _

Note: Water mist system can also activate locally at the space protected. PRESS !!!! SPRINKLER RELEASE BUTTON

4250TEU-YZJ Seaspan Ship Management Local Protection Water Mist System Machinery Space _______________________________________________________________________ _

LOCAL RELEASE OF WATER MIST SYSTEM


IF SYSTEM STILL FAILS TO START THE PUMP 1. Go to local pump starter panel in Engine room.

2. Change over the pump mode selection switch from AUTOMATIC to LOCAL. 3. Pump will start, ensure the valve for the affected space/spaces is/are open. 4. Water mist releases through sprinkler nozzles to suppress the fire in space concerned.

4250TEU-YZJ Seaspan Ship Management Local Protection Water Mist System Machinery Space _______________________________________________________________________ _

NOTE !!!!! In case of electric failure of section valve it can be manually opened by turning the marked release button on the solenoid valve as shown below.

4250TEU-YZJ Seaspan Ship Management Local Protection Water Mist System Machinery Space _______________________________________________________________________ _

manually.

T urn

to open section valve

TESTING FOR MAINTENANCE OR OPERATION CHECK DURING PORT STATE INSPECTIONS /AUDITS
1. Testing to be done in rotation to ensure all sections are working satisfactorily. 2. Close all outlet valves. 3. Open all test valves.

4250TEU-YZJ Seaspan Ship Management Local Protection Water Mist System Machinery Space _______________________________________________________________________ _

Outlet valves

Test valves SHUT

Test valve OPEN 4. Release sections in one of following ways: - Activate two flame detectors of the one protected space for release. - Activate SPRINKLER RELEASE BUTTON locally in protected space. From Manual Release Panel at FCS/EHQ, manually release one section of protected space as explained earlier.

4250TEU-YZJ Seaspan Ship Management Local Protection Water Mist System Machinery Space _______________________________________________________________________ _

5. Check that pump starts, correct section valve opens, water being discharged through drain/test valves & display on fire control panel indicates WATER MIST SYSTEM RELEASED. 6. Reset the alarm on the FCP. 7. Check that section valve is closed & pump stopped. 8. Close test valve. 9. If required repeat test for other sections. 10.Open all outlet valves. 11. Log down all tests in Log book & NS5.

PREPARED BY : CE SUNIL JAIN