Вы находитесь на странице: 1из 4

GUJARAT STATE ELECTRICITY CORPORATION LIMITED, WANAKBORI TPS GUARANTEED TECHNICAL PERTICULARS DATA SHEETS

FOR 3 CORE 240 mm2 HT XLPE CABLES - 6.35/11 KV (E)


S.No. Description 1 GENERAL Name of Manufacture Place of Manufacturing Applicable Standards 1S/IEC Design Ambient Temperature C Cable particulars whether confirmed as per clause 1.5 of Section I of Technical Specification ( Yes/No) CABLES Voltage Grade (UO/U) Whether Suitable for neutral earthed/unearthed System Permissible voltage & frequency variation for satisfactory operation Voltage Frequency Combined No. of cores & Size Continuous Current carrying capacity a) For Standard Condition as per IS 1) In Air 2) In Ground 3) In Duct 4) In Trench b) For Site Condition 1) In Air ( at 40 Deg. C) 2) In Ground ( at 30 Deg C) 3) In Duct 4) In Trench CONDUCTOR Material & its applicable IS Unit

IS:7098(Part-2)1985,IS:58311984,IS:8130-1984,IS:3975 C 40

KV Earthed

6.35/11 Earthed

KV Hz

Between +10% to -15% Between 3% Between 10% 3C x 240 Sq.mm

Amp Amp Amp Amp Amp Amp Amp Amp

392 319 287 333 392 319 287 333

Stranded (Class-2) Aluminium Conductor as per IS: 8130

Shape of Conductor Nominal Cross Section Area Number of Wires per core Nominal diameter & cross Section area of each wire used in each core of the con ductor ( Before Stranding) CONDUCTOR SCREEN Type Material & its applicable IS Continuous Working Temperature Nominal Thickness INSULATION

Compacted Circular Sq. mm 240 No. 37 2.987mm/7.0Sq.mm

Extruded Non metalic Semi-conducting compound , IS 7098(Part-2)1985 C 90C mm 0.3 Cross Linked Polyethylene(XLPE)as pre IS:7098 Part-2 mm mm 3.6 NA

Material & its applicable IS Thickness of Insulation (Nom) a) Between Cores b) Between cores & Inner Sheath Tolerance in thickness ( Percent) of insulation Diameter of core over insulation ( Calculated) Specific insulation resistance at 90C INSULATION SCREEN

mm 1x1012

24.7 ohm-cm(Min) at 90C

Materail & its applicable IS Thickness 1) Semiconductor Part 2) Metallic Part ( Copper Tape) Whether overlapping provided for copper tape current carrying capacity a) Continuous b) S.C. current duration of 3 -sec Diameter of core over screening ( Calculated)

Semi-conducting compound, IS:7098(Part-2)1985 (NonMetallic) Copper Tape(Metallic) mm mm YES NA 0.6 (All 3 core combined) 27.7 0.3 0.045

KA mm

10

Whether insulation screen is removable without the applicable of heat FILLER Material & its applicable IS Whether suitable for operating temperature of cable No. fillers provided including central filler INNER SHEATH Material & its applicable IS Extruded or Wrapped Thickness ( Min) Diameter of Cable over innersheath( Calculated) ARMOURING Material & its applicable IS Type of Armoring No. of wires Diameter of Cable over Armoring ( Calculated) Current carrying capacity of Armour a) On continuous basis b) S.C. current duration of 1-Sec OUTER SHEATH Material & its applicable IS Thickness of Sheath ( Min) Tolerance on thickness of sheath Overall diameter of cable Scheme for identification (Cable)

YES

Non Hygroscopic PVC YES No 10

PVC Type ST-2 as per IS:5381 Extruded mm 0.7 mm 61.2

Galvanised Steel as per IS:3975 4x0.8mm Flate Strip No. 44(Approx.)


mm

62.8

NA KA 6.55

PVC Type ST-2 as per IS-5831 mm 2.52 As per IS:7098(Part-2) mm 70.70(Approx.) As per IS:7098(Part-2)1985 along with word 'GSECL'

11

CABLE CONSTANT AC resistance per core at operating temp DC resistance per core at 20C Reactance per core Capacitance per core Insulation resistance at 27C ohm/Km 0.160(Approx.) 0.125(Max.) ohm/Km ohm/Km 0.085(Approx.) fd/Km 0.43(Approx.) Shall be corresponding to min. volume resistivity of 1x10^ohm cm at 27C

Loss Talent Dielectric Constant

0.004(Max.)at Uo 2.35(Average)

12

13

14 15 16

Max Cable charging current at Amp/Km 0.86 normal operating voltage OTHER PARAMETERS Recommended minimum bending radius 15xD mm Safe pulling force 30 N/Sq.mm Approx. Cable Weight Kg/Km 6700(Approx.) CABLE DRUM Net weight of cable Kg 6700(Approx.) Drum weight( Empty) Kg 340(Approx.) Shipping weight ( Drum wt + cable wt) Kg 7040(Approx.) Whether ISI Mark shall be indicated on drum YES Length of cable per drum Mtrs 500+ 5% Whether details shall be embossed YES Whether type test reports submitted YES Whether drawing submitted YES