Вы находитесь на странице: 1из 6

SL7000 Transformer Connected Version

Installation Guide

SL7000 Transformer Connected Version

Installation Guide

SL7000 TC Installation Guide

Mounting: The meter is intended to be mounted on a metering panel. Dimensions and mounting points (all in mm):

180

85

SL7000

150

The net weight is approximately 1.9kg.

Connection: Safety warning: switch off network supply before connecting the meter. Unscrew the terminal cover and connect the wires according to the following drawing.

Main connections: The terminals permit the connection of solid or stranded wires (terminal diameter 9.4mm, 2 x M6 screws per terminal. For aluminium cables (multi-strand), the use of a tin-plated copper sheath on each conductor is compulsory to avoid corrosion and terminal. The configurable parameter of the meter is able to define if it is connected to a three-wire system or a fourwire system.

SL7000 TC Installation Guide


OFF

BAT

ON

RS485 RJ45

RS232 RJ45

The type of connection hardware depends on the meter type

Installation on the network (four-wire systems)

option : APS*

S S P L1 L2 L3 P P S

Installation on the network (three-wire systems)

option : APS*

S S P L1 L2 L3 N P P P S S

If the meter is configured for a four-wire connection, Aaron connection is possible for usage with a three-wire system.

SL7000 TC Installation Guide

Inputs & Outputs (Flexible I/O board): Auxiliary terminal: cables up to 1.4mm2 for pulses, and up to 2.55mm2 for controls.

RJ45 Customer port

RJ45 Utility port

1 2 3

4 5

1 2 Control Inputs (1 to 2)

Control Outputs (1 to 4)

1 2 3 4 5 6 Pulse Outputs (1 to 6) 1 2 3 4 Pulse Inputs (1 to 4)

Inputs & Outputs (Intermediate I/O board):

RJ45 Customer port

RJ45 Utility port

1 2 3

4 5

1 2 Control Inputs (1)

Control Outputs (1 to 2)

1 2 3 4 5 6 Pulse Outputs (1 to 2) 1 2 3 4 Pulse Inputs (1 to 2)

Programming date and time: Press the display push button several times, until the date (respectively the time) is displayed. Press the reset button to allow programming, digit by digit, with the display button (the digit to be modified will blink), move to the next digit by pressing the reset button. When all the digits are set, press the reset button twice to activate the new date or time.

Actaris SAS ZI de Chasseneuil - Avenue des Temps Modernes 86361 Chasseneuil du Poitou cedex - France For more information, see www.actaris.com t e l +33 5 49 62 70 00 fax +33 5 49 62 70 89

EL-0041.0-GB-02.03 - Copyright 2002, Actaris. All Rights Reserved. - Actaris reserves the right to change these specifications without prior notice.