Item Pt. no. Description Qty VA D.F Total Reference
1 6ES7414-5HM06-0AB0 SIMATIC S7-400H, CPU 414-5H 2 7.5 1 15 Page 6 2 6ES7960-1AA06-0XA0 SIMATIC S7-400H, SYNC SUBMODULE 4 0.77 1 3.08 Page 7 3 6ES7407-0KA02-0AA0 SIMATIC S7-400, POWER SUPPLY 2 20 1 40 Page 8 4 6GK5204-2BB10-2AA3 SCALANCE X204-2, MANAGED IE SWITCH 2 6.36 1 12.72 Page 9 5 6ES7153-2BA02-0XB0 SIMATIC DP, ET 200M INTERFACE IM 153-2 1 11 1 11 Page 10 6 6ES7331-1KF02-0AB0 SIMATIC S7-300, ANALOG INPUT SM 331 2 0.4 1 0.8 Page 11 7 6ES7321-1BL00-0AA0 SIMATIC S7-300, DIGITAL INPUT SM 321 5 6.5 1 32.5 Page 12 8 6ES7322-1BL00-0AA0 SIMATIC S7-300, DIGITAL OUTPUT SM 322 2 6.6 1 13.2 Page 13 9 6ES7197-1LA04 -0XA0 Y-Link for S7-400H SIMATIC S7-400H, Y-LINK 1 0 0 0 Page 14 10 46.52.9.024.0040 Relay 24VDC, 8A, 2 Pole,Lockable test button +mechanical 42 0.5 1 21 Page 25 14 FIT-201A/B Magnetic flow meters DN 500 2 15 1 30 Page 26 15 LSH-201A/B Level switch for hazarouds 2 2.5 1 5 Page 27 16 LIT-201A/B level indicator transmitter 2 23 1 46 Page 28 17 PIT-201A/B/C/D/E/F Pressure transmitter 6 0.4 1 2.4 Page 29 232.7 0 232.7 300 Al- Wefaq Control System TOTAL IN VA Summation Auxiliary Rate UPS Load Calculation for Industrial Area Pumping Station PLC panel Project: - Rev. 0 Page 1 of 43 Sheet 3,4 PLC-4 Item Pt. no. Description Qty VA D.F Total Reference 1 6ES7414-5HM06-0AB0 SIMATIC S7-400H, CPU 414-5H, CENTRAL UNIT 2 7.5 1 15 Page 6 2 6ES7960-1AA06-0XA0 SIMATIC S7-400H, SYNC SUBMODULE FOR 4 0.77 1 3.08 Page 7 3 6ES7407-0KA02-0AA0 SIMATIC S7-400, POWER SUPPLY PS407: 10A, WIDERANGE, 120/230V UC 2 20 1 40 Page 8 4 6GK5204-2BB10-2AA3 SCALANCE X204-2, MANAGED IE SWITCH 2 6.36 1 12.72 Page 9 5 6ES7153-2BA02-0XB0 SIMATIC DP, ET 200M INTERFACE IM 153-2 2 11 1 22 Page 10 6 6ES7331-1KF02-0AB0 SIMATIC S7-300, ANALOG INPUT SM 331,OPTICALLY ISOLATED, 8 AI, 13 BIT 2 0.4 1 0.8 Page 11 7 6ES7321-1BL00-0AA0 SIMATIC S7-300, DIGITAL INPUT SM 321,OPTICALLY ISOLATED 32DI 8 6.5 1 52 Page 12 8 6ES7322-1BL00-0AA0 SIMATIC S7-300, DIGITAL OUTPUT SM 322,OPTICALLY ISOLATED, 3 6.6 1 19.8 Page 13 9 46.52.9.024.0040 Relay 24VDC, 8A, 2 Pole,Lockable test button +mechanical indicator 74 0.5 1 37 Page 25 10 DLIT-301C Differential Level Indicator Transmitters 3 0.5 1 1.5 Page 30 11 AIT-401 Hydrocarbon Analyzer 1 0.6 1 0.6 Page 31 12 ASS-401 Auto Sampler 1 290 1 290 Page 32 13 FIT-401 FIT-401B Open Channel Ultrasonic level type flowmeter 2 23 1 46 Page 28 540.5 0 540.5 600 Al- Wefaq Control System TOTAL IN VA Summation Auxiliary Rate UPS Load Calculation Inlet Works panel Project: - Rev. 0 Page 2 of 43 Sheet 5,6,7 SBR-PLC Item Pt. no. Description Qty D.F Total Reference 1 6ES7414-5HM06-0AB0 SIMATIC S7-400H, CPU 414-5H, CENTRAL UNIT 2 7.5 1 15 Page 6 2 6ES7960-1AA06-0XA0 SIMATIC S7-400H, SYNC SUBMODULE FOR PATCH CABLES UP TO 10M 4 0.77 1 3.08 Page 7 3 6ES7407-0KA02-0AA0 SIMATIC S7-400, POWER SUPPLY PS407: 10A 2 20 1 40 Page 8 4 6GK5204-2BB10-2AA3 SCALANCE X204-2, MANAGED IE SWITCH 2 6.36 1 12.72 Page 9 5 6ES7153-2BA02-0XB0 SIMATIC DP, ET 200M INTERFACE IM 153-2 5 11 1 55 Page 10 6 6ES7331-1KF02-0AB0 SIMATIC S7-300, ANALOG INPUT SM 331 13 0.4 1 5.2 Page 11 7 6ES7332-5HF00-0AB0 SIMATIC S7-300, ANALOG OUTPUT SM 332 3 6 1 18 Page 15 8 6ES7321-1BH02-0AA0 SIMATIC S7-300, DIGITAL INPUT SM 321 25 3.5 1 87.5 Page 16 9 6ES7322-1BH01-0AA0 SIMATIC S7-300, DIGITAL OUTPUT SM 322 9 4.9 1 44.1 Page 17 10 6ES7197-1LA04 -0XA0 Y-Link for S7-400H SIMATIC S7-400H, Y-LIN 1 0 0 0 Page 14 11 46.52.9.024.0040 Relay 24VDC, 8A, 2 Pole,Lockable test button +mechanical indicator 104 0.5 1 52 Page 25 12 PIT-501A/B PIT601A/B Pressure Transmitter 4 0.5 1 2 Page 33 13 LIT-501A/B LIT-601A/B Level Indicator Transmitters 4 23 1 92 Page 28 14 Viberation Sensor 10 0.5 1 5 Page 34 15 FIT-701A/B Differential Pressure Type 2 0.5 1 1 Page 30 16 AIT-501A/B/C AIT-502A/B/C AIT-601A/B/C AIT-602A/B/C LIT-502A/B LIT-602A-B AIT-503 Analyzers 17 55 1 935 Page 35 1367.6 0 1367.6 1400 UPS Load Calculation SBR PLC panel Al- Wefaq Control System TOTAL IN VA Summation Auxiliary Rate Project: - Rev. 0 VA Page 3 of 43 Item Pt. no. Description Qty VA D.F Total Reference 1 6ES7214-1AG31-0XB0 SIMATIC S7-1200, CPU 1214C, COMPACT CPU, DC/DC/DC 1 12 1 12 Page 37 2 6ES7221-1BH30-0XB0 SIMATIC S7-1200, DIGITAL INPUTSM 1221 , 16DI, 24 V DC, S 5 2.5 1 12.5 Page 38 3 6ES7222-1BH30-0XB0 SIMATIC S7-1200, DIGITAL OUTPUT SM 1222, 16 DO, 2 2.5 1 5 Page 39 4 6ES7231-4HF30-0XB0 SIMATIC S7-1200, ANALOG INPUT, SM 1231, 5 1.5 1 7.5 Page 40 5 6AV6647-0AB11-3AX0 SIMATIC HMI ,KTP600 BASIC ,MONO PN 1 6 1 6 Page 41 6 6GK7242-5DX30-0XE0 COMMUNICATION MODULE CM 1242-5 1 0.75 1 0.75 Page 42 7 46.52.9.024.0040 Relay 24VDC, 8A, 2 Pole,Lockable test button +m. indicator 21 0.5 0.6 6.3 Page 25 8 55.34.9.024.0040 Relay 24 VDC, 7A ,4 Pole, Lockable test button 14 1 0.6 8.4 Page 43 9 - Loop Powered Signal 3 0.576 1 1.728 not avaliable 60.178 10 6ES7214-1AG31-0XB0 SIMATIC S7-1200, CPU 1214C, COMPACT CPU, DC/DC/DC 1 12 1 12 11 6ES7221-1BH30-0XB0 SIMATIC S7-1200, DIGITAL INPUTSM 1221 , 16DI, 24 V DC, S 5 2.5 1 12.5 12 6ES7222-1BH30-0XB0 SIMATIC S7-1200, DIGITAL OUTPUT SM 1222, 16 DO, 2 2.5 1 5 13 6ES7231-4HF30-0XB0 SIMATIC S7-1200, ANALOG INPUT, SM 1231, 5 1.5 1 7.5 14 6AV6647-0AB11-3AX0 SIMATIC HMI ,KTP600 BASIC ,MONO PN 1 6 1 6 15 6GK7242-5DX30-0XE0 COMMUNICATION MODULE CM 1242-5 1 0.75 1 0.75 16 46.52.9.024.0040 Relay 24VDC, 8A, 2 Pole,Lockable test button +m. indicator 21 0.5 0.6 6.3 17 55.34.9.024.0040 Relay 24 VDC, 7A ,4 Pole, Lockable test button 14 1 0.6 8.4 18 - Loop Powered Signal 3 0.576 1 1.728 60.178 120.356 0 120.356 200 Odor 1 PLC Panel Odor 2 PLC Panel The Same as Odor 1 PLC Panel UPS Load Calculation OCU PLC panel Al- Wefaq Control System TOTAL IN VA Summation Auxiliary Rate Project: - Rev. 0 Page 4 of 43 Item Pt. no. Description Qty VA D.F Total Reference 1 6ES7405-0KA02-0AA0 SIMATIC S7-400 , PS 405 2 95 1 190 Page 18 2 6ES7412-3HJ 14-0AB0 SIMATIC S7-400H, CPU412H 2 5.5 1 11 Page 19 3 6ES7960-1AA04-0XA0 SIMATIC S7-400H, SYNC SUB MODULE 2 0.0011 1 0.0022 Page 20 4 6EP1 333-3BA00 SITOP MODULAR 5A 2 18 1 36 Page 21 5 6ES7153-2AR03-0XA0 IM153-2 INTERFACE REDUND.BUNDLE 3 5.5 1 16.5 Page 22 6 6ES7321-1BL00-0AA0 32DI DIGITAL INPUT MODULE 9 6.5 1 58.5 Page 12 7 6ES7322-1BL00-0AA0 32DO DIGITAL OUTPUT MODULE 8 6.6 1 52.8 Page 13 8 6ES7331-1KF02-0AA0 8AI ANALOG INPUT MODULE, 4-20mA 4 0.4 1 1.6 Page 23 9 6GK1503-3CB00 OLM/G12 2 4.8 1 9.6 Page 24 10 6ES7197-1LA04-0XA0 Y-Link 1 0 0 0 Page 14 11 46.52.9.024.0040 2-CONTACT RELAY 24VDC 300 0.5 1 150 Page 25 12 SCADA system computer 1 535 1 535 not avaliable 13 Printer 1 70 1 70 not avaliable 14 FIT-1001A/B/C/D/E/F FIT- 1002 FIT-1003A/B Magnetic flow meters DN 200/400/500 9 15 1 135 Page 26 15 AIT-1002 TUT-1001 Nitrate/Turbidity analyzers 2 55 1 110 Page 35 16 AIT-1001 hydro-carbon analyzer 1 0.6 1 0.6 Page 31 17 flow switch low 19 10 1 190 Page 36 18 LIT-1001 level transmitter 1 23 1 23 Page 28 19 PIT-1001:6A/B PIT-1001:6C Pressure transmitter 20 0.5 1 10 Page 33 20 Solenoid valve of pneumatic 40 15 1 600 not avaliable 2199.6 0 2199.6 2200 UPS Load Calculation Ultrafilters PLC panel Al- Wefaq Control System TOTAL IN VA Summation Auxiliary Rate Project: - Rev. 0 Page 5 of 43 Power losses Power loss, typ. 7.5 W Backup battery Battery operation Backup current, typ. 180 A ; Valid up to 40C Backup current, max. 1000 A Backup time, max. Dealt with in the module data manual with the secondary conditions and the factors of influence Feeding of external backup voltage to CPU 5 to 15 VDC Feeding of external backup voltage to CPU 5 to 15 VDC Memory Work memory integrated 4 Mbyte integrated (for program) 2 Mbyte integrated (for data) 2 Mbyte expandable No Load memory expandable FEPROM Yes ; with Memory Card (FLASH) expandable FEPROM, max. 64 Mbyte integrated RAM, max. 512 kbyte expandable RAM Yes expandable RAM, max. 64 Mbyte Backup present Yes with battery Yes ; all data without battery No CPU processing times for bit operations, min. 18.75 ns for word operations, min. 18.75 ns for fixed point arithmetic, min. 18.75 ns for floating point arithmetic, min. 37.5 ns CPU-blocks DB Number, max. 6000 ; Number range: 1 - 16.000 6ES7414-5HM06-0AB0 Page 2 Date: 07/27/2012 subject to modifications Copyright Siemens AG 2012 32 Page 6 of 43
productdatablad 6ES7960-1AA06-0XA0 - SIMATIC S7-400H, SYNC SUBMODULE V6 FOR PATCH CABLES UP TO 10M Input current from CPU, max. 220mA Power losses Power loss, typ. 0,77W Dimensions Breedte 13mm Hoogte 14mm Diepte 58mm Weight Weight, approx. 14g Status 6-jul-2013 6ES7960-1AA06-0XA0 Page 1/ 20.07.2013 subject to modifications Copyright Siemens AG 2013 1 Page 7 of 43 Input current Rated value at 110 V DC 1 A ; at 120 V DC Rated value at 230 V DC 0.5 A Rated value at 120 V AC 0.9 A Rated value at 230 V AC 0.5 A Inrush current, max. 63 A ; Full width at half maximum 1 ms Output voltage Rated value, 5 V DC Yes Rated value, 24 V DC Yes Output current for backplane bus (5 V DC), max. 10 A ; no base load required for backplane bus (24 V DC), max. 1 A ; idling-proof Short-circuit protection Yes Power Power consumption, typ. 95 W Power losses Power loss, typ. 20 W Backup battery Backup battery Backup battery (optional) Yes ; 2 x lithium AA; 3.6 V/2.3 Ah Galvanic isolation primary/secondary Yes EMC Compliance with line harmonic distortion limits Observance of line harmonic distortion acc. to IEC 61000-3-2, IEC 61000-3-3 Yes Degree and class of protection Protection class 1 ; with protective conductor Standards, approvals, certificates FM approval Yes ; Ta: 0 C to 60 C T4 Connection method Connecting cables/cross sections 3 x 1.5 mm2, solid or stranded wire with end sleeve, external diameter 3 to 9 mm Dimensions 6ES7407-0KA02-0AA0 Page 2 Date: 06/28/2012 subject to modifications Copyright Siemens AG 2012 26 Page 8 of 43 Attenuation / of fiber-optic cable transmission link / minimum necessary 0 dB Range / at the optical interface / depending on the optical fiber used 0 5 km design of the removable storage / C-PLUG Yes Inputs/outputs Operating voltage / of signaling contacts / at DC / rated value 24 V Operating current / of signaling contacts / at DC / maximum 0.1 A Supply voltage, current consumption, power loss Type of voltage / of supply voltage DC Supply voltage / external 24 V minimum 18 V maximum 32 V Product component / fusing at power supply input Yes Type of fusing / at input for supply voltage 0,6 A / 60 V Consumed current / maximum 0.265 A Active power loss / at 24 V / for DC 6.36 W Permitted ambient conditions Ambient temperature during operating -40 +60 C during storage -40 +70 C during transport -40 +70 C Relative humidity / at 25 C / without condensation / during operating / maximum 95 % Protection class IP IP30 Design, dimensions and weight Design compact Width 60 mm Height 125 mm Depth 124 mm Net weight 0.78 kg Type of mounting 35 mm DIN rail mounting Yes wall mounting Yes S7-300 rail mounting Yes Product properties, functions, components / general Cascading in the case of a redundant ring / at reconfiguration time of <\~0.3\~s 50 Cascading in cases of star structuring Any (depending only on signal propagation time) Product function CLI Yes 6GK5204-2BB10-2AA3 Page 2/ 12/03/2012 subject to modifications Copyright Siemens AG 2012 4 108 Page 9 of 43 It 0.1 As Output voltage Rated value, 5 V DC Yes Output current for backplane bus (5 V DC), max. 1.5 A Power losses Power loss, typ. 5.5 W Address area Addressing volume Outputs 244 byte Inputs 244 byte Hardware configuration Number of modules per DP slave interface, max. 12 Time stamping Accuracy 1 ms ; 1ms at up to 8 modules; 10ms at up to 12 modules Number of message buffers 15 Messages per message buffer 20 Number of stampable digital inputs, max. 128 ; Max. 128 signals/station; max. 32 signals/slot Time format RFC 1119 Time resolution 0.466 ns Time interval for transmitting the message buffer if a message is present 1000 ms Time stamp on signal change rising / falling edge as signal entering or exiting Interfaces Interface physics, RS 485 Yes Interface physics, FOC No PROFIBUS DP Node addresses 1 to 125 permitted Automatic detection of transmission speed Yes PROFIBUS DP, output current, max. 70 mA Transmission procedure RS 485 Transmission rate, max. 12 Mbit/s SYNC capability Yes 6ES7153-2BA02-0XB0 Page 2 Date: 02/14/2012 subject to modifications Copyright Siemens AG 2012 60 Page 10 of 43 Product data sheet 6ES7331-1KF02-0AB0 SIMATIC S7-300, ANALOG INPUT SM 331, OPTICALLY ISOLATED, 8 AI, 13 BIT RESOLUTION, U/I/RESISTANCE/PT100, NI100, NI1000, LG-NI1000, PTC / KTY, 66 MS MODULE UPDATE, 1 X 40 PIN Input current from backplane bus 5 V DC, max. 90mA Power losses Power loss, typ. 0.4W Analog inputs Number of analog inputs 8 Number of analog inputs for resistance measurement 8 permissible input voltage for voltage input (destruction limit), max. 30V ; 12 V continuous, 30 V for max. 1 s permissible input current for current input (destruction limit), max. 40mA Input ranges Voltage Yes Current Yes Thermocouple No 6ES7331-1KF02-0AB0 Page 1 Date: 01/09/2012 subject to modifications Copyright Siemens AG 2012 73 6ES7331-1KF02-0AB0 Page 11 of 43 Product data sheet 6ES7321-1BL00-0AA0 SIMATIC S7-300, DIGITAL INPUT SM 321, OPTICALLY ISOLATED 32DI, 24 V DC, 1 X 40 PIN Supply voltage Load voltage L+ Rated value (DC) 24 V permissible range, lower limit (DC) 20.4 V permissible range, upper limit (DC) 28.8 V Input current from backplane bus 5 V DC, max. 15 mA Power losses Power loss, typ. 6.5 W Digital inputs Number/binary inputs 32 Input characteristic curve acc. to IEC 61131, Type 1 Yes Number of simultaneously controllable inputs horizontal installation up to 40 C, max. 32 6ES7321-1BL00-0AA0 Page 1 Date: 01/29/2012 subject to modifications Copyright Siemens AG 2012 65-1 6ES7321-1BL00-0AA0 Page 12 of 43 Product data sheet 6ES7322-1BL00-0AA0 SIMATIC S7-300, DIGITAL OUTPUT SM 322, OPTICALLY ISOLATED, 32DO, 24V DC, 0.5A, 1 X 40 PIN, SUM OF OUTPUT CURRENTS 4A/GROUP (16A/MODULE) Supply voltage Load voltage L+ Rated value (DC) 24V permissible range, lower limit (DC) 20.4V permissible range, upper limit (DC) 28.8V Input current from load voltage L+ (without load), max. 160mA from backplane bus 5 V DC, max. 110mA Power losses Power loss, typ. 6.6W Digital outputs Number/binary outputs 32 Limitation of inductive shutdown voltage to L+ (-53 V) Lamp load, max. 5W Load resistance range 6ES7322-1BL00-0AA0 Page 1 Date: 01/29/2012 subject to modifications Copyright Siemens AG 2012 69-1 6ES7322-1BL00-0AA AAA0 Page 13 of 43
Product data sheet 6ES7197-1LA04-0XA0 - SIMATIC S7-400H, Y-LINK FOR CONNECTING SINGLE-CHANNEL DP SLAVES TO S7-400H BASED ON IM153-BA02 (NOT FIT FOR PCS7 V6.1) Dimensions Width 40mm Height 125mm Depth 130mm Status Jul 1, 2013 6ES7197-1LA04-0XA0 Page 1/ 07/20/2013 subject to modifications Copyright Siemens AG 2013 1 Page 14 of 43 Product data sheet 6ES7332-5HF00-0AB0 SIMATIC S7-300, ANALOG OUTPUT SM 332, OPTICALLY ISOLATED, 8 AO, U/I; DIAGNOSTICS; RESOLUTION 11/12 BITS, 40 PIN, REMOVE/INSERT W. ACTIVE, BACKPLANE BUS Supply voltage Load voltage L+ Rated value (DC) 24V Input current from load voltage L+ (without load), max. 340mA from backplane bus 5 V DC, max. 100mA Power losses Power loss, typ. 6W Analog outputs Number of analog outputs 8 Voltage output, short-circuit protection Yes Voltage output, short-circuit current, max. 25mA Current output, no-load voltage, max. 18V Output ranges, voltage 0 to 10 V Yes 6ES7332-5HF00-0AB0 Page 1 Date: 02/09/2012 subject to modifications Copyright Siemens AG 2012 85 6ES7332-5HF00-0AB0 Page 15 of 43 Product data sheet 6ES7321-1BH02-0AA0 SIMATIC S7-300, DIGITAL INPUT SM 321, OPTICALLY ISOLATED, 16DI, 24 V DC, 1 X 20 PIN Supply voltage Load voltage L+ Rated value (DC) 24 V permissible range, lower limit (DC) 20.4 V permissible range, upper limit (DC) 28.8 V Input current from backplane bus 5 V DC, max. 10 mA Power losses Power loss, typ. 3.5 W Digital inputs Number/binary inputs 16 Input characteristic curve acc. to IEC 61131, Type 1 Yes Number of simultaneously controllable inputs horizontal installation up to 60 C, max. 16 6ES7321-1BH02-0AA0 Page 1 Date: 02/12/2012 subject to modifications Copyright Siemens AG 2012 66-1 6ES7321-1BH02-0AA0 Page 16 of 43 Product data sheet 6ES7322-1BH01-0AA0 SIMATIC S7-300, DIGITAL OUTPUT SM 322, OPTICALLY ISOLATED, 16 DO, 24V DC, 0.5A, 1 X 20 PIN SUM OF OUTPUT CURRENTS 4A/GROUP (8A/MODULE) Supply voltage Load voltage L+ Rated value (DC) 24V permissible range, lower limit (DC) 20.4V permissible range, upper limit (DC) 28.8V Input current from load voltage L+ (without load), max. 80mA from backplane bus 5 V DC, max. 80mA Power losses Power loss, typ. 4.9W Digital outputs Number/binary outputs 16 Limitation of inductive shutdown voltage to L+ (-53 V) Lamp load, max. 5W Load resistance range 6ES7322-1BH01-0AA0 Page 1 Date: 02/12/2012 subject to modifications Copyright Siemens AG 2012 70-1 6ES7322-1BH01-0AA AAA0 Page 17 of 43 for backplane bus (24 V DC), max. 1 A ; idling-proof Short-circuit protection Yes Power Power consumption, typ. 95 W Power losses Power loss, typ. 20 W Battery Backup battery Backup battery Backup battery (optional) Yes ; 2 x lithium AA; 3.6 V/2.3 Ah Galvanic isolation primary/secondary Yes Degree and class of protection Protection class 1 ; with protective conductor Standards, approvals, certificates FM approval Yes ; Ta: 0 C to 60 C T4 Connection method Connecting cables/cross sections 3 x 1.5 mm2, solid or stranded wire with end sleeve, external diameter 3 to 9 mm Dimensions Width 50 mm Height 290 mm Depth 217 mm Required slots 2 Weight Weight, approx. 1200 g Status J ul 11, 2013 6ES7405-0KA02-0AA0 Page 2/ 07/16/2013 subject to modifications Copyright Siemens AG 2013 2 Page 18 of 43 Product data sheet 6ES7412-3HJ14-0AB0 - SIMATIC S7-400H, CPU 412-3H CENTRAL UNIT FOR S7-400H AND S7- 400F/FH, 3 INTERFACES: 1 MPI/DP AND 2 FOR SYNC MODULES 768 KB MEMORY (256 KB DATA/512 KB CODE) General information Hardware product version 1 Firmware version V4.5 Engineering with Programming package STEP7 V 5.3 SP2 or higher with HW update CiR - Configuration in RUN CiR synchronization time, basic load 150 ms CiR synchronization time, time per I/O slave 40 s Supply voltage 24 V DC No ; Power supply via system power supply Input current from backplane bus 5 V DC, typ. 1.2 A from backplane bus 5 V DC, max. 1.5 A from backplane bus 24 V DC, max. 150 mA ; Per DP interface from interface 5 V DC, max. 90 mA ; At each DP interface Power losses Power loss, typ. 5.5 W Memory 6ES7412-3HJ14-0AB0 Page 1/ 07/16/2013 subject to modifications Copyright Siemens AG 2013 10 Page 19 of 43 Product data sheet 6ES7960-1AA04-0XA0 - SIMATIC S7-400H, SYNC SUBMODULE V4 FOR PATCH CABLES UP TO 10M Input current from CPU, max. 210mA Power losses Power loss, typ. 1.1mW Dimensions Width 25mm Height 53mm Depth 140mm Weight Weight, approx. 65g Status Jul 6, 2013 6ES7960-1AA04-0XA0 Page 1/ 07/16/2013 subject to modifications Copyright Siemens AG 2013 1 Page 20 of 43 Note >60 C Derating delivered active power / typ. 120 W constant overload current / at short-circuit during run- up / typical 5.5 A short-term overload current / at short-circuit during operation / typical 15 A Duration of overloading ability for excess current / on short-circuiting during the operational phase 25 ms Parallel switching for enhanced performance Yes Note switchable characteristic Numbers of parallel switchable units for enhanced performance 2 Efficiency Efficiency at Vout rated, Iout rated, approx. 87 % Power loss at Vout rated, Iout rated, approx. 18 W Closed-loop control Dynamic mains compensation (Vin rated 15 %), max. 0.1 % Dynamic load smoothing (Iout: 50/100/50 %), Uout typ. 3 % Load step setting time 50 to 100%, typ. 2 ms Load step setting time 100 to 50%, typ. 2 ms Setting time / maximum 5 ms Protection and monitoring Output overvoltage protection <35 V Current limitation, typ. 5.5 A Characteristic feature of the output / short-circuit protected Yes Short-circuit protection Alternatively, constant current characteristic approx. 5.5 A or latching shutdown Enduring short circuit current / Effective level / typical 5.5 A Overload/short-circuit indicator LED yellow for "overload", LED red for "latching shutdown" Safety Primary/secondary isolation Yes Potential separation Safety extra low output voltage Vout according to EN 60950-1 and EN 50178 6EP1333-3BA00 Page 3 Date: 02/09/2012 subject to modifications Copyright Siemens AG 2012 12 Page 21 of 43 It 0.1 As Output voltage Rated value, 5 V DC Yes Output current for backplane bus (5 V DC), max. 1.5 A Power losses Power loss, typ. 5.5 W Address area Addressing volume Outputs 244 byte Inputs 244 byte Hardware configuration Number of modules per DP slave interface, max. 12 Time stamping Accuracy 1 ms ; 1ms at up to 8 modules; 10ms at up to 12 modules Number of message buffers 15 Messages per message buffer 20 Number of stampable digital inputs, max. 128 ; Max. 128 signals/station; max. 32 signals/slot Time format RFC 1119 Time resolution 0.466 ns Time interval for transmitting the message buffer if a message is present 1000 ms Time stamp on signal change rising / falling edge as signal entering or exiting Interfaces Interface physics, RS 485 Yes Interface physics, FOC No PROFIBUS DP Node addresses 1 to 125 permitted Automatic detection of transmission speed Yes PROFIBUS DP, output current, max. 70 mA Transmission procedure RS 485 Transmission rate, max. 12 Mbit/s SYNC capability Yes 6ES7153-2BA02-0XB0 Page 2 Date: 02/14/2012 subject to modifications Copyright Siemens AG 2012 60 Page 22 of 43 Product data sheet 6ES7331-1KF02-0AB0 SlMATlC S7-300, ANALOG lNPUT SM 331, OPTlCALLY lSOLATED, 8 Al, 13 BlT RESOLUTlON, U/l/RESlSTANCE/PT100, Nl100, Nl1000, LG-Nl1000, PTC / KTY, 66 MS MODULE UPDATE, 1 X 40 PlN lnput current from backplane bus 5 V DC, max. 90mA Power losses Power loss, typ. 0.4W Analog inputs Number of analog inputs 8 Number of analog inputs for resistance measurement 8 permissible input voltage for voltage input (destruction limit), max. 30V ; 12 V continuous, 30 V for max. 1 s permissible input current for current input (destruction limit), max. 40mA lnput ranges Voltage Yes Current Yes Thermocouple No 6ES7331-1KF02-0AB0 Page 1 Date: 01/09/2012 subject to modifications Copyright Siemens AG 2012 73 Page 23 of 43 for glass FOC with 50/125 m / at 3 dB/km / maximum 10 dB for glass FOC with 62.5/125 m at 3.5 dB/km / maximum 12 dB Signal delay time in bit time 6.5 bit Injectable optical power relating to 1 mW for glass FOC with 50/125 m / at 3 dB/km -16 dB for glass FOC with 62.5/125 m at 3.5 dB/km -13 dB Optical sensitivity relating to 1 mW for glass FOC with 50/125 m / at 3 dB/km -28 dB for glass FOC with 62.5/125 m at 3.5 dB/km -28 dB Wavelength for glass FOC with 50/125 m / compatible with interface / at 3 dB/km 860 nm for glass FOC with 62.5/125 m / compatible with interface at 3.5 dB/km 860 nm Cable length for glass FOC with 50/125 m / at 3 dB/km / maximum 3 km for glass FOC with 62.5/125 m at 3.5 dB/km maximum 3 km Inputs/outputs Operating voltage / of signaling contacts / at DC / rated value 24 V Operating current / of signaling contacts / at DC / maximum 0.1 A Supply voltage, current consumption, power loss Type of voltage / of supply voltage DC Supply voltage / for DC rated value 24 V minimum 18.8 V maximum 28.8 V Product component / fusing at power supply input Yes Consumed current / At 24 V / with DC / maximum 0.2 A Permitted ambient conditions Ambient temperature during operating 0 60 C during storage -40 +70 C during transport -40 +70 C Relative humidity at 25 C / without condensation / during operating / maximum 95 % Protection class IP IP40 6GK1503-3CB00 Page 2/ 07/16/2013 subject to modifications Copyright Siemens AG 2013 3 0.2 A At 24 V Page 24 of 43 3 2 . 8 29 12.4 2 0 4.75 0.5 4.75 6 . 5 46.52 46.61 2 Pole CO, 8 A Plug-in/Solder terminals 2 CO (DPDT) 8/15 250/440 2,000 350 0.37 6/0.5/0.15 300 (5/5) AgNi 1.2/0.5 (0.8...1.1)U N (0.73...1.1)U N 0.8U N /0.4U N 0.2U N /0.1U N 10 10 6 100 10 3 10/3 6 (8 mm) 1,000 40 ... +70 RT II Contact specification Contact configuration Rated current/Maximum peak current A Rated voltage/Maximum switching voltage V AC Rated load AC1 VA Rated load AC15 (230 V AC) VA Single phase motor rating (230 V AC) kW Breaking capacity DC1: 30/110/220 V A Minimum switching load mW (V/mA) Standard contact material Coil specification Nominal voltage (U N ) V AC (50/60 Hz) V DC Rated power VA/W Operating range AC DC Holding voltage AC/DC Must drop-out voltage AC/DC Technical data Mechanical life AC/DC cycles Electrical life at rated load AC1 cycles Operate/release time ms Insulation between coil and contacts (1.2/50 s)kV Dielectric strength between open contacts V AC Ambient temperature range C Environmental protection Approvals (according to type) Features 1 & 2 Pole relay range 46.52 - 2 Pole 8 A 46.61 - 1 Pole 16 A Socket mount or direct connection via Faston connectors AC coils & DC coils Available with: lockable test button, mechanical indicator & LED indicator 8 mm, 6 kV (1.2/50 s) isolation, coil-contacts Cadmium Free contacts 1 Pole CO, 16 A Plug-in/Faston 187 1 CO (SPDT) 16/25 250/440 4,000 750 0.55 12/0.5/0.15 300 (5/5) AgNi 1.2/0.5 (0.8...1.1)U N (0.73...1.1)U N 0.8U N /0.4U N 0.2U N /0.1U N 10 10 6 100 10 3 15/5 6 (8 mm) 1,000 40 ... +70 RT II 12 - 24 - 48 - 110 - 120 - 230 - 240 12 - 24 - 48 - 110 - 125 1 46.52 46.61 FOR UL HORSEPOWER AND PILOT DUTY RATINGS SEE General technical information page V 46 Series - Miniature industrial relays 8 - 16 A 138 46.52 2 Pole CO, 8 A Plug-in/Solder terminals /0.5 Page 25 of 43 Proline Promag 50W, 53W 10 Endress+Hauser A0003194 a Signal cable b Coil current cable 1 Core 2 Core insulation 3 Core shield 4 Core jacket 5 Core reinforcement 6 Cable shield 7 Outer jacket Operation in zones of severe electrical interference The measuring device complies with the general safety requirements in accordance with EN 61010 and the EMC requirements of IEC/EN 61326 and NAMUR recommendation NE 21. " Caution! Grounding is by means of the ground terminals provided for the purpose inside the connection housing. Ensure that the stripped and twisted lengths of cable shield to the ground terminal are as short as possible. Power consumption AC: < 15 VA (incl. sensor) DC: < 15 W (incl. sensor) Switch-on current: Max. 3 A (< 5 ms) for 260 V AC Max. 13.5 A (< 50 ms) for 24 V DC Power supply failure Lasting min. cycle frequency: EEPROM saves measuring system data EEPROM or T-DAT (Promag 53 only) retain the measuring system data in the event of a power supply failure S-DAT: exchangeable data storage chip which stores the data of the sensor (nominal diameter, serial number, calibration factor, zero point etc.) 1 2 3 4 5 6 7 a b Page 26 of 43 Nivotester FTL 325 N 8 Endress+Hauser Power supply Electrical connection Terminal blocks The removable terminal blocks are separated into intrinsically safe connections (at top of the instrument) and non-instrinsically safe connections (at bottom of the instrument). Also, the terminal blocks have different colours to make them more easily recognisable. Blue for the intrinsically safe section and grey for the non-intrinsically safe section. This difference helps to ensure safe wiring. Connecting the measuring sensor (at upper, blue terminal blocks) The two-wire connecting line between the Nivotester FTL 325 N and the Liquiphant, Nivopuls or Soliphant measuring sensor can be either a commercially available installation cable or wires in a multi-wire cable for measuring purposes. Line resistance may be a maximum of 25 per wire. If strong electromagnetic interference is expected, e.g. from machines or radio devices, a screened cable must be used. Only connect the screen to the ground connection, and not to the Nivotester. Using the measuring sensor in explosion hazardous areas Please observe all local regulations on explosion protection concerning the type and installation of intrinsically safe signal cabling. Please refer to the Safety Instructions XA 134F for maximum permissible values of capacitance and inductance. Connecting signal and control devices (at lower, grey terminal blocks) The relay function is dependent on the level and fail-safe circuit. If an instrument is connected at high inductance (e.g. contactor, solenoid valve etc.), a spark suppressor must be installed to protect the relay contact. Connecting the supply voltage (at lower, grey terminal blocks) For voltage variants, see the Ordering Information on page 14. A fuse is built into the supply current circuit. This obviates the need to connect a fine-wire fuse in series. The Nivotester is equipped with reverse polarity protection. Supply voltage AC version: Voltage ranges: 85...253 V AC, 50/60 Hz DC version: Voltage ranges: 20...30 V AC / 20...60 V DC DC supply: max. 60 mA (1-channel) DC supply: max. 115 mA (3-channel) Permissible residual ripple within tolerance: U ss = max. 2 V The Nivotester is equipped with reverse polarity protection. Power consumption AC 1-channel: max. 1.75 W 3-channel: max. 2.75 W DC 1-channel: max. 1.2 W (bei U min 20 V) 3-channel: max. 2.25 W (bei U min 20 V) Page 27 of 43 Prosonic S FMU90 10 Endress + Hauser PROFIBUS DP interface Auxiliary energy Supply voltage/ Power consumption/ Current consumption Galvanic isolation The following terminals are galvanically isolated from each other: auxiliary energy sensor inputs analogue output 1 analogue output 2 relay outputs bus connection (PROFIBUS DP) Fuse 2 A T /DC 400 mA T /AC accesible in the terminal compartment Profile 3.0 Transmittable values main value (level or flow, depending on the instrument version) distances counters temperatures average/difference/sum relay states rake control pump control Function blocks 10 Analog Input Blocks (AI) 10 Digital Input Blocks (DI) 10 Digital Output Blocks (DO) Supported baud rates 9.6 kbaud 19.2 kbaud 45,45 kbuad 93.75 kbaud 187.5 kbaud 500 kbaud 1.5 Mbaud 3 Mbaud 6 Mbaud 12 Mbaud Service Access Points (SAPs) 1 ID number 1540 (hex) 1540 (hex) = 5440 (dec) GSD file EH3x1540.gsd Addressing via dip switches at the instrument or via software (e.g. FieldCare) Default address: 126 per software Termination can be activated/deactivated in the instrument Locking The device can be locked by hardware or software. Instrument version Supply voltage Power consumption Current consumption AC voltage (FMU90 - ****A****) 90 ... 253 V AC (50/60 Hz) max. 23 VA max. 100 mA at 230 V AC DC voltage (FMU90 - ****B****) 10,5 ... 32 V DC max. 14 W (typically 8 W) max. 580 mA at 24 V DC Page 28 of 43 Cerabar M PMC51, PMP51, PMP55 Endress+Hauser 19 FOUNDATION Fieldbus Version for non-hazardous areas: 9 to 32 V DC Start-up current HART 12 mA or 22 mA (selectable) Current consumption PROFIBUS PA: 11 mA 1 mA, switch-on current corresponds to IEC 61158-2, Clause 21 FOUNDATION Fieldbus: 16 mA 1 mA, switch-on current corresponds to IEC 61158-2, Clause 21 Cable entry o 75 ff, feature 50 "Electrical connection". Cable specification Endress+Hauser recommends using twisted, shielded two-wire cables. Terminals for wire cross-sections 0.5 to 2.5 mm 2 (20 to 14 AWG) Cable outer diameter: 5 to 9 mm (0.2 to 0.35 in) Residual ripple No influence on 4 to 20 mA signal up to r5 % residual ripple within the permitted voltage range [according to HART hardware specification HCF_SPEC-54 (DIN IEC 60381-1)] Influence of power supply d0.001% of URL/1 V Page 29 of 43 Deltabar S 18 Endress+Hauser Supply voltage Note! When using the measuring device in hazardous areas, installation must comply with the corresponding national standards and regulations and the Safety Instructions or Installation or Control Drawings. All explosion protection data are given in separate documentation which is available upon request. The Ex documentation is supplied as standard with all devices approved for use in explosion hazardous areas. o 85, "Safety Instructions" and "Installation/Control Drawings" sections. 4 to 20 mA HART Version for non-hazardous areas, jumper for 4 to 20 mA test signal in "Test" position (delivery status): 11.5 to 45 V DC Version for non-hazardous areas, jumper for 4 to 20 mA test signal in "Non-test" position: 10.5 to 45 V DC PROFIBUS PA Version for non-hazardous areas: 9 to 32 VDC FOUNDATION Fieldbus Version for non-hazardous areas: 9 to 32 V DC Current consumption PROFIBUS PA: 13 mA 1 mA, switch-on current corresponds to IEC 61158-2, Clause 21 FOUNDATION Fieldbus: 15 mA 1 mA, switch-on current corresponds to IEC 61158-2, Clause 21 Cable entry o 69 ff, feature 30 "Housing; Cable entry; Protection". Cable specification Endress+Hauser recommends using shielded, twisted-pair two-wire cables. Terminals for core cross-sections 0.5 to 2.5 mm 2 (20 to 14 AWG) Cable outer diameter: 5 to 9 mm (0.2 to 0.35 in) Residual ripple Without influence on 4 to 20 mA signal up to r5 % residual ripple within the permitted voltage range [according to HART hardware specification HCF_SPEC-54 (DIN IEC 60381-1)] Influence of power supply d0.0006% of URL/1 V Page 30 of 43 x Power requirement 220 VAC x Power consumption: 0.48 Watts x Analog outputs: 4-20mA isolated x Analog loop resistance: 500 Ohms, nominally @ 24V x Alarms: Optional x Certification: Available upon request Mechanical x Transmitter weight: 3 lbs. x Enclosure: Extruded aluminum (optional NEMA or purged enclosures) x 8" H x 3-7/8" W x 1-1/2" D UV Lamp x Type: Xenon flash lamp x Wavelength range: 200 - 650 nm x Lamp Life: Typically 3 years x Size: 2" H x 4" W x 1-1/2" D x Power requirements: 24 VDC (9-32 VDC) 6650 UVF Probe x Materials: 316SS x Max temperature rating: 315.5 C (600 F) x Max pressure rating: 5000 psig Sample Conditioning System x All wetted parts of SCS components will be SS316 x Ultrasonic Homogenizer for sample mix x Sample shut off valve x Sample and fast loop bypass x Pressure regulator with viewing gauge x Sample flow meter with precision needle valves x Extra Cuno filter Mounting: x NEMA 4 (IP65) free standing enclosure Area Class x Exd certified Enclosure for Class 1 Div 2 Page 31 of 43 Liquistation CSF34 22 Endress+Hauser Mains fuse Optional fuses on DIN rail T10A (for 24V power supply) T3.15A (for 230V power supply) T10A (fuse for battery backup) Power consumption Version with vacuum pump: 290 VA Version with peristaltic pump: 290 VA Power failure Power supply via battery (optional): 2 x 12 V, 7.2 Ah, with additional charge controller Replace batteries with battery type Panasonic LC-R127R2PG1. Real-time clock: lithium battery, type CR2032 Performance characteristics Sampling methods Vacuum pump / peristaltic pump: Event sampling Single and multiple samples Sampling table Vacuum pump: In proportion to time In proportion to volume Peristaltic pump: In proportion to time In proportion to volume In proportion to flow Dosing volume Vacuum pump: 20 to 350 ml (0.7 to 12 fl.oz.) Peristaltic pump: 10 to 10,000 ml (0.3 to 340 fl.oz.) A sample volume < 20 ml can vary in dosing accuracy and repeatability, depending on the application. Dosing accuracy Vacuum pump: 5 ml (0.17 fl.oz.) or 5 % of the set volume Peristaltic pump: 5 ml (0.17 fl.oz.) or 5 % of the set volume Repeatability Vacuum pump: 5 % Peristaltic pump: 5 % Intake speed > 0.5 m/s (> 1.6 ft/s) for 13 mm (1/2") ID, in accordance with EN 25667, ISO 5667 > 0.6 m/s (> 1.9 ft/s) for 10 mm (3/8") ID, in accordance with 5893 (Austrian standard); US EPA Suction height Max. 8 m (26 ft) Hose length Max. 30 m (98 ft) Page 32 of 43 Cerabar S 18 Endress+Hauser Supply voltage Note! When using the measuring device in hazardous areas, installation must comply with the corresponding national standards and regulations and the Safety Instructions or Installation or Control Drawings. All explosion protection data are given in separate documentation which is available upon request. The Ex documentation is supplied as standard with all devices approved for use in explosion hazardous areas. o 89 ff, "Safety Instructions" and "Installation/Control Drawings" sections. 4 to 20 mA HART Version for non-hazardous areas, jumper for 4 to 20 mA test signal in "Test" position (delivery status): 11.5 to 45 V DC Version for non-hazardous areas, jumper for 4 to 20 mA test signal in "Non-test" position: 10.5 to 45 V DC PROFIBUS PA Version for non-hazardous areas: 9 to 32 V DC FOUNDATION Fieldbus Version for non-hazardous areas: 9 to 32 V DC Current consumption PROFIBUS PA: 13 mA 1 mA, switch-on current corresponds to IEC 61158-2, Clause 21 FOUNDATION Fieldbus: 15 mA 1 mA, switch-on current corresponds to IEC 61158-2, Clause 21 Cable entry o 76 ff, feature 30 "Housing; Cable entry; Protection". Cable specification Endress+Hauser recommends using shielded, twisted-pair two-wire cables. Terminals for core cross-sections 0.5 to 2.5 mm 2 (20 to 14 AWG) Cable outer diameter: 5 to 9 mm (0.2 to 0.35 in) Residual ripple Without influence on 4 to 20 mA signal up to r5 % residual ripple within the permitted voltage range [according to HART hardware specification HCF_SPEC-54 (DIN IEC 60381-1)] Influence of power supply d0.0006% of URL/1 V Page 33 of 43 Page 34 of 43 Liquiline CM442 10 Endress+Hauser Cable specification Power consumption Depending on supply voltage 100 to 230 V AC and 24 V AC: Max. 55 VA 24 V DC: Max. 22 W Fuse For all versions: 5x20 mm, 250 V, 4.0 A, slow-blow (T4.0A) Performance characteristics Response time Current outputs t 90 = max. 500 ms for an increase from 0 to 20 mA Reference temperature 25 C (77 F) Maximum measured error of inputs --> Documentation of the connected sensor Maximum measured error of current outputs < 20 A at 4 mA < 50 A at 20 mA at 25 C (77 F) each Additional measured error depending on the temperature: < 1.5 A/K Resolution of current output < 5 A Repeatability --> Documentation of the connected sensor Cable gland Permitted cable diameter M16x1.5 mm 4 to 8 mm (0.16 to 0.32") M12x1.5 mm 2 to 5 mm (0.08 to 0.20") M20x1.5 mm 6 to 12 mm (0.24 to 0.48") NPT3/8" 4 to 8 mm (0.16 to 0.32") G3/8 4 to 8 mm (0.16 to 0.32") NPT1/2" 6 to 12 mm (0.24 to 0.48") G1/2 7 to 12 mm (0.28 to 0.47") Page 35 of 43 Limit reed switch ZE 951 for DFM 165 - 350 bistable Advantage reliable limit value determination using reed switches direct power control of consumers with contact protection relay ZE 3061 2-point control for monostable switches with ZE 3060 freely adjustable flow limit value - fastened with a clamping piece to the measuring tube dovetail guide reliable, simple installation, easy to retrofit in existing plants Description The limit reed switch ZE 951 serves as signal transmitters of the flow values. They are clamped to the dovetail guides and signal when the magnetic float in the measuring tube has reached or exceeded the signal transmitter position. As soon as this happens, a contact in the signal transmitter, as the actual switching element (reed switch), opens or closes. Function Type ZE 951 bistable (normally open contact/normally closed contact) The contact is closed (normally open contact) or opened (normally closed contact), as soon as the magnetic float moves up from below or is at the direct height of the signal transmitter. If the float goes above the signal transmitter, the switching state remains unaffected. The switching state is only cancelled if the float goes below the signal transmitter. Body ABS Connector Plug according to DIN EN 175301-803 Voltage 2V 'C Switching Current max. 0,5 A Electric Switching Capacity max. 10 VA Resistance < 150 mOhm Insulation Resistance > 10 10 Ohm Ambient Temperature 0C to +55C Hysteresis 10 mm Type Of Protection IP 65 with mounted connector plug Connection Cable nominal cross-section: 1.5 mm cable outside diameter: 46 mm Pin Assignment the polarity of the connections has no influence on the function Colour anthracite grey Accessories 2-Point Control Unit ZE 3060 (Article number 136245, 1326244) Contact Protection Relay ZE 3061 (Article number 136240, 136239) 1 All rights for technical modifications withheld > data sheet no.: 330207 - 2010/05/05 ASVStbbe GmbH & Co. KG Hollwieser Str. 5 D-32602 Vlotho Tel. +49(0)5733. 799-0 Fax +49(0)5733. 799-5000 contact@asv-stuebbe.de www.asv-stuebbe.de 2 2VV ''C ZE 951 for DFM 165 - 350 Page 36 of 43 Current output to backplane bus (DC 5 V), max. 1600mA ; Max. 5 V DC for SM and CM Power losses Power loss, typ. 12W Memory Usable memory for user data 75kbyte Work memory integrated 75kbyte expandable No Load memory integrated 4Mbyte Backup present (maintenance-free) without battery Yes CPU processing times for bit operations, typ. 0.085s ; / instruction for word operations, typ. 1.7s ; / instruction for floating point arithmetic, typ. 2.5s ; / instruction CPU-blocks Number of blocks (total) DBs, FCs, FBs, counters and timers. The maximum number of addressable blocks ranges from 1 to 65535. There is no restriction, the entire working memory can be used OB Number, max. Limited only by RAM for code Data areas and their retentivity retentive data area in total (incl. times, counters, flags), max. 10kbyte Flag Number, max. 8kbyte ; Size of bit memory address area Address area I/O address area I/O address area, overall 1024 bytes for inputs / 1024 bytes for outputs Process image Inputs, adjustable 1kbyte Outputs, adjustable 1kbyte Hardware configuration Number of modules per system, max. 3 comm. modules, 1 signal board, 8 signal modules Time of day Clock Hardware clock (real-time clock) Yes 6ES7214-1AG31-0XB0 Page 2/ 07/20/2013 subject to modifications Copyright Siemens AG 2013 8 Page 37 of 43 Product data sheet 6ES7221-1BH30-0XB0 - SIMATIC S7-1200, DIGITAL INPUT SM 1221, 16 DI, 24VDC, SINK/SOURCE INPUT Supply voltage 24 V DC Yes permissible range, lower limit (DC) 20.4 V permissible range, upper limit (DC) 28.8 V Input current from backplane bus 5 V DC, max. 130 mA Digital inputs from load voltage L+ (without load), max. 4 mA ; per channel Output voltage Power supply to the transmitters present Yes Power losses Power loss, typ. 2.5 W Digital inputs Number/binary inputs 16 In groups of 4 Input characteristic curve acc. to IEC 61131, Type 1 Yes Number of simultaneously controllable inputs 6ES7221-1BH30-0XB0 Page 1/ 07/20/2013 subject to modifications Copyright Siemens AG 2013 3 Page 38 of 43 Product data sheet 6ES7222-1BH30-0XB0 - SIMATIC S7-1200, DIGITAL OUTPUT SM 1222, 16 DO, 24V DC, TRANSISTOR 0.5A Supply voltage permissible range, lower limit (DC) 20.4 V permissible range, upper limit (DC) 28.8 V Input current from backplane bus 5 V DC, max. 140 mA Power losses Power loss, typ. 2.5 W Digital inputs Number/binary inputs 0 Digital outputs Number/binary outputs 16 In groups of 1 Functionality/short-circuit strength No ; to be provided externally Limitation of inductive shutdown voltage to typ. (L+) -48 V Switching capacity of the outputs with resistive load, max. 0.5 A on lamp load, max. 5 W Output voltage 6ES7222-1BH30-0XB0 Page 1/ 07/20/2013 subject to modifications Copyright Siemens AG 2013 3 Page 39 of 43 Product data sheet 6ES7231-4HF30-0XB0 - SIMATIC S7-1200, ANALOG INPUT, SM 1231, 8 AI, +/-10V, +/-5V, +/-2.5V, OR 0-20 MA 12 BIT + SIGN OR (13 BIT ADC) Supply voltage 24 V DC Yes Input current Current consumption, typ. 45mA from backplane bus 5 V DC, typ. 90mA Power losses Power loss, typ. 1.5W Analog inputs Number of analog inputs 8 ; Current or voltage differential inputs permissible input frequency for current input (destruction limit), max. 35 V permissible input voltage for voltage input (destruction limit), max. 35V permissible input current for voltage input (destruction limit), max. 40mA permissible input current for current input (destruction limit), max. 40mA Cycle time (all channels) max. 625s Input ranges Voltage Yes ; 10 V, 5 V, 2.5 V Current Yes ; 0 to 20 mA Thermocouple No 6ES7231-4HF30-0XB0 Page 1/ 07/20/2013 subject to modifications Copyright Siemens AG 2013 4 Page 40 of 43 Alphanumeric keyboard Yes ; Onscreen keyboard Touch operation Design as touch screen Yes Installation type/mounting Mounting in portrait format possible Yes Mounting in landscape format possible Yes Supply voltage Type of supply voltage DC Rated voltage/DC 24V permissible range, lower limit (DC) 19.2V permissible range, upper limit (DC) 28.8V Input current Current consumption (rated value) 0.24A Inrush current As 0.5As Power Power consumption, typ. 6W Processor Processor type X86 No ARM Yes ; RISC 32-bit Memory Flash Yes RAM Yes Usable memory for user data 1Mbyte Type of output Acoustics Buzzer Yes Speaker No Time of day Clock Hardware clock (real-time clock) No Software clock Yes Battery-backed No Synchronizable Yes Interfaces Number of RS 485 interfaces 0 Number of USB interfaces 0 Number of SD card slots 0 6AV6647-0AB11-3AX0 Page 2/ 07/20/2013 subject to modifications Copyright Siemens AG 2013 9 Page 41 of 43 Product data sheet 6GK7242-5DX30-0XE0 Product-type designation CM 1242-5 COMMUNICATION MODULE CM 1242-5; FOR CONNECTION OF SIMATIC S7-1200 TO PROFIBUS AS DP SLAVE MODULE Transmission rate Transmission rate / at interface 1 / in accordance with PROFIBUS 9.6kbit/s 12Mbit/s Interfaces Number of electrical connections at interface 1 / in accordance with PROFIBUS 1 for power supply 0 Design of electrical connection at interface 1 / in accordance with PROFIBUS 9-pin Sub-D socket (RS485) Supply voltage, current consumption, power loss Type of voltage / of supply voltage DC Supply voltage 1 / from backplane bus 5V Consumed current from backplane bus / at 5 V / for DC / Typical 0.15A Resistive loss 0.75W Permitted ambient conditions Ambient temperature for vertical installation / during operating phase 0 45C for horizontal installation / during operating phase 0 55C during storage -40 +70C 6GK7242-5DX30-0XE0 Page 1/ 07/20/2013 subject to modifications Copyright Siemens AG 2013 2 Page 42 of 43 55.32 55.33 55.34 2 CO (DPDT) 3 CO (3PDT) 4 CO (4PDT) 10/20 10/20 7/15 250/400 250/400 250/250 2,500 2,500 1,750 500 500 350 0.37 0.37 0.125 10/0.25/0.12 10/0.25/0.12 7/0.25/0.12 300 (5/5) 300 (5/5) 300 (5/5) AgNi AgNi AgNi 6 - 12 - 24 - 48 - 60 - 110 - 120 - 230 - 240 6 - 12 - 24 - 48 - 60 - 110 - 125 - 220 1.5/1 1.5/1 1.5/1 (0.81.1)U N (0.81.1)U N (0.81.1)U N (0.81.1)U N (0.81.1)U N (0.81.1)U N 0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 20 10 6 /50 10 6 20 10 6 /50 10 6 20 10 6 /50 10 6 200 10 3 200 10 3 150 10 3 10/5 10/5 11/3 4 4 4 1,000 1,000 1,000 40+85 40+85 40+85 RT I RT I RT I 2 Contact specification Contact configuration Rated current/Maximum peak current A Rated voltage/Maximum switching voltage V AC Rated load AC1 VA Rated load AC15 (230 V AC) VA Single phase motor rating (230 V AC) kW Breaking capacity DC1: 30/110/220 V A Minimum switching load mW (V/mA) Standard contact material Coil specification Nominal voltage (UN) V AC (50/60 Hz) V DC Rated power AC/DC VA (50 Hz)/W Operating range AC DC Holding voltage AC/DC Must drop-out voltage AC/DC Technical data Mechanical life AC/DC cycles Electrical life at rated load AC1 cycles Operate/release time ms Insulation between coil and contacts (1.2/50 s) kV Dielectric strength between open contacts V AC Ambient temperature range C Environmental protection Approvals (according to type) Features Plug-in mount, general purpose 2, 3 & 4 Pole relays 55.32 - 2 Pole 10 A 55.33 - 3 Pole 10 A 55.34 - 4 Pole 7 A Lockable test button and mechanical flag indicator as standard on 2 & 4 pole types AC coils & DC coils UL Listing (certain relay/socket combinations) Cadmium Free contacts (preferred version) Contact material options 94 series sockets Coil EMC suppression Timer accessories 86 series European Patent 2 pole, 10 A Plug-in 94 series sockets 3 pole, 10 A Plug-in 94 series sockets 4 pole, 7 A Plug-in 94 series sockets FOR UL RATINGS SEE: General technical information page V 55.32 55.33 55.34 55 Series - General purpose relays 7 - 10 A V I I - 2 0 1 2 ,