Академический Документы
Профессиональный Документы
Культура Документы
Contents
Preface .................................................................................................................................. iv Acknowledgements ............................................................................................................................ v Handbook Contributors ...................................................................................................................... v Participating Systems ......................................................................................................................... v Outreach Events for Small Water Systems Energy Audit Program .................................................. vi I. Introduction ................................................................................................................... 1
Background ........................................................................................................................................ 1 Treatment Process ............................................................................................................................. 2 Surface Water Systems ................................................................................................................. 2 Groundwater Systems ................................................................................................................... 3 Benchmarking .................................................................................................................................... 3
II.
III. Electrical Power Cost ................................................................................................. 10 Reading Electric Bills ....................................................................................................................... 10 Energy Charges ............................................................................................................................... 11 Demand Charge (Capacity Charge) ................................................................................................ 11 Power Factor .................................................................................................................................... 12 Other Charges .................................................................................................................................. 12 Rebates and Incentives.................................................................................................................... 13 IV. Energy Consumption and Cost Savings ............................................................... 15
Energy Consumption ........................................................................................................................ 15 Pressure Reducing Valves ............................................................................................................... 16 Throttling Valves .............................................................................................................................. 16 Variable Frequency Drives ............................................................................................................... 16 Demand Management...................................................................................................................... 18 Time-of-Use Rate Schedules ....................................................................................................... 19 Electric Utility Load Management Programs................................................................................ 20 Motor Run Times ......................................................................................................................... 20 Pump Efficiency ............................................................................................................................... 21 Pump Efficiency Testing................................................................................................................... 21 Compressed Air Systems................................................................................................................. 23 Water Treatment Processes ............................................................................................................ 23 UV Disinfection ............................................................................................................................ 23 Filter Backwash ............................................................................................................................ 23 Lime Sludge Disposal .................................................................................................................. 24 Reducing Water Demand ................................................................................................................. 24 Water Loss ................................................................................................................................... 24 Water Conservation ..................................................................................................................... 24 SCADA ............................................................................................................................................. 25 HVAC ............................................................................................................................................... 25 Lighting ............................................................................................................................................. 26 Unnecessary Equipment .................................................................................................................. 27
V. VI.
SD DENR
Solar Power ...................................................................................................................................... 30 Photovoltaic ................................................................................................................................. 30 Wind Power ...................................................................................................................................... 32 Hydropower ...................................................................................................................................... 34 Alternative Energy Conclusion ......................................................................................................... 35
Figures
Figure 1. O&M Costs in a Typical Water Treatment Plant (Roberts, 2008) .......................................... 1 Figure 2. Process Flow Diagram for a Lime Softening Water Plant ...................................................... 3 Figure 3. Process Flow Diagram for a Treated Groundwater System .................................................. 3 Figure 4. Benchmarking of Specific Energy .......................................................................................... 4 Figure 5. Benchmarking of Electricity Cost ........................................................................................... 4 Figure 6. Example of Specific Energy Consumption for Five Wells within One System ....................... 8 Figure 7. Example Electric Bill ............................................................................................................. 13 Figure 8. Effect of Groundwater Level on Pump Curve ...................................................................... 17 Figure 9. Effect of Motor Speed on Pump Curve ................................................................................ 18 Figure 10. Effect of Run-Time on Production Cost.............................................................................. 21 Figure 11. Solar Resource Map............................................................................................................ 32 Figure 12. South Dakota Wind Resource Map ..................................................................................... 34
Equations
Equation 1. Equation 2. Equation 3. Equation 4. Equation 5. Equation 6. Equation 7. Pumping Horsepower ....................................................................................................... 11 Pumping Energy Use ....................................................................................................... 11 Pumping Energy Cost ...................................................................................................... 11 Kilowatt input (Demand) to motor ..................................................................................... 12 Demand Charge ............................................................................................................... 12 Wire-to-Water Efficiency................................................................................................... 22 Hydropower Capacity ....................................................................................................... 34
Tables
Table 1. Example of Equipment and Rate Schedule Inventory ........................................................... 10 Table 2. Example Rate Schedules ...................................................................................................... 10 Table 3. Example Annual Water Production and Energy Cost ........................................................... 15 Table 4. Example Demand Charge and Energy Use Comparison ...................................................... 19 Table 5. Example TOU Rate Schedule ............................................................................................... 19 Table 6. Example Load Management Statistics .................................................................................. 20 Table 7. Typical Water and Wastewater High-Use Energy Operations and Associated Potential Energy Saving Measures (EPA, 2008) ......................................................................... 28 Table 8. Energy Use and Costs at Nine Small Water Systems Evaluated ......................................... 37 Table 9. Estimated Energy Savings at Nine Small Water Systems Evaluated ................................... 38
SD DENR
ii
Appendices
Appendix A Example Rate Schedule Appendix B Example Calculations Appendix C Energy Audit Checklist
SD DENR
iii
PREFACE
Preface
In July 2009, HDR and South Dakota Rural Water were selected by the South Dakota Department of Environment and Natural Resources to provide technical assistance to community drinking water systems in South Dakota. This included training, select water system energy audits, information transfer, and associated activities to promote the long-term goal of maximizing energy conservation by drinking water systems in South Dakota. This project was funded under the American Resource Recovery Act (ARRA) and was applicable to small water systems, serving a population of less than 10,000 only. While the systems involved were small water systems, items evaluated in the energy audit process are applicable to larger water systems and wastewater systems. The project initially selected a representative cross section of small water systems across the state to conduct the energy audits. Criteria used in the selection of the facilities included: Met small system requirements Generally covered the state geographically Included surface and groundwater sources Included city, rural water and tribal water systems Include varied water treatment processes, such as direct pump and disinfect, iron and manganese removal, lime softening, and membrane technologies The system desired to participate
A total of nine systems were audited that included and a detailed report provided for each. In all cases energy conservation measures (ECMs) were identified and recommended for implementation. The magnitude of the savings varied widely due to water source, treatment processes, distribution coverage, topography of the service area, previous energy savings efforts, etc. Copies of the complete reports for the systems may be obtained from either the SD DENR in Pierre or HDRs offices in Sioux Falls or Rapid City, South Dakota. Training and dissemination of information was a primary goal of this project, to be able to benefit all water systems, not just the nine systems actually audited. This handbook presents a summary of procedures, results, and benchmarking for system managers, operators, boards, or councils to use as a tool to identify potential energy savings at their facilities and to determine if detailed evaluation and auditing is desired. Additionally the project, procedures and results have been, or are scheduled to be presented at several conferences and meetings across the state, and nationally. A partial listing of these events follows this Preface. Additionally, as part of this program, energy savings information is sent out via South Dakota Rural Waters monthly eNews to over 540 individuals in the water and wastewater industry and via Ergs Joules and Such, an energy newsletter provided by National Rural Water containing
SD DENR
iv
PREFACE
information regarding energy saving for rural water communities. Updates and information will continue to be distributed via these sources for the remainder of the program. South Dakota Association of Rural Water Systems training staff members attended several of the audits conducted by HDR to train the trainer. They will be incorporating the procedures and results of the energy auditing process in association with utilizing this Handbook as part of their formal training for systems across South Dakota. Thorough distribution of information through presentations, development of this handbook, and training of the trainers will allow for widespread awareness of potential energy savings available to water and wastewater systems statewide.
Acknowledgements
HDR would like to acknowledge the State and Federal agencies involved in planning, conducting and funding of this project, including: South Dakota Department of Environment and Natural Resources The Environmental Protection Agency, Region 8 South Dakota Board of Water and Natural Resources South Dakota Rural Water The auditing process, presentations, report, and handbook preparation and technical review required input from several HDR staff members. We acknowledge their efforts and the fact that this has resulted in ongoing energy savings for the systems involved and will be expanded to other systems in South Dakota and beyond. The major contributors are acknowledged below.
Handbook Contributors
Participating Systems
Brandon Dakota Dunes Lower Brule Clay Rural Water Rapid Valley Spearfish Clark Rural Water Lead Deadwood Sanitary District West River Lyman Jones
SD DENR
PREFACE
SD DENR
vi
INTRODUCTION
I. Introduction
Background
An energy audit is intended to evaluate how much energy is consumed and identify measures that can be taken to utilize energy more efficiently. The primary goal is reducing power consumption and cost through physical or operational changes. Each system will have unique opportunities to reduce energy use or cost depending on system specific changes and opportunities within the power providers rate schedules. An audit of an individual water treatment plant (WTP) is an attempt to pinpoint wasted or unneeded energy usage for that facility. With the cost of electricity on the rise, reducing energy use should be a priority for municipalities. Nationwide, about 4% of U.S. power generation is used for water supply and treatment (DOE, 2006). Water facilities are energy intensive, with energy typically second only to staffing as the largest operations and maintenance expense (Biehl, 2010). Electricity usage represents roughly 30-50% of a water treatment plants annual operating cost. Approximately 80% of municipal water processing and distribution costs are for electricity (EPRI, 2002).
Staffing,35%
A key part of energy audits is thorough analysis of the effects of overdesign on energy efficiency. Plants are designed to perform at maximum flow and loading conditions. Unfortunately, most plants are not efficient at average conditions. Aging infrastructure is another source of inefficient usage of energy in WTPs across the country. The basis for addressing aging infrastructure related energy waste is also included in the energy audit process.
SD DENR
INTRODUCTION
Customers often dont understand the electrical power utility bill and that simple changes in day to day operations can lead to significant savings. Secondly, it is typical that the power bill is not seen by the treatment and distribution staff, rather delivered directly to finance for payment. As such, water system management and operations staff members are often unaware of power costs. Finally, operation staff rarely has incentive to minimize usage as the primary focus is centered on the quality of the water produced. This handbook addresses these issues and provide guidance on how to develop an energy conservation program, identify and implement energy conservation measures (ECMs), and monitor the progress and success of the implementation program.
Treatment Process
Each water system is unique and will be presented with opportunities to reduce energy use and cost. Energy use by water systems also varies depending on several factors. The type of source water utilized by the system affects the amount of energy required to produce potable water. Groundwater systems require about 30% more electricity on a unit basis than surface water systems (EPRI, 2002). This is primarily due to a greater energy requirement for pumping groundwater to the surface. The treatment process employed also affects energy use. Membrane systems are generally more energy intensive to operate. Conventional plants require less energy, however, some processes can be energy intensive such as filter backwash or aeration.
SD DENR
INTRODUCTION
Groundwater Systems Groundwater quality can vary depending on the aquifer. Some groundwater systems operate a treatment plant while other sources do not require advanced treatment. Systems not requiring advanced treatment are able to simply pump groundwater to the surface, and typically chlorinate, then distribute to the system. A flow diagram for a treated groundwater system is presented in Figure 3.
Benchmarking
Energy requirements for water treatment and pumping can vary by water source. Data from the systems that participated in the Small Water Systems Energy Audit Project conducted for the South Dakota Department of Environment and Natural Resources (SD DENR) was used to determine a system benchmark. Figure 4 shows cost per million gallons ($/MG) and Figure 5
SD DENR
INTRODUCTION
illustrates specific energy use (kWh/MG) for the systems evaluated. The systems are listed by the water source utilized.
Specific Energy
8,000 7,000 6,000 5,000 4,000 3,000 2,000 1,000 -
kWh/MG
Electricity Cost
700 600 500 $/MG
SD DENR
INTRODUCTION
Benchmarking of the audit participants doesnt give a clear relationship between water source and energy use. Five groundwater systems were evaluated, four of which operate a treatment plant. Three surface water plants were evaluated, two of which use membrane systems and the other does not operate a distribution system. Another unique aspect in this particular study is that rural water systems were included, which have significant energy use associated with booster pumping. These benchmarking figures can be used to indicate how a system compares with respect to its specific energy and electricity costs for the evaluated systems, and more specifically a similar system. The US Environmental Protection Agency (EPA) has developed an Energy Star program for water and wastewater utilities. The program offers an online benchmarking tool as part of the Portfolio Manager. The goal of the program is to help eliminate energy waste and lower operating costs of water and wastewater utilities (EPA, 2010). The Portfolio Manager tool allows utilities to track energy use, energy cost, and carbon emissions. Information about the program can be found at http://www.energystar.gov by entering energy star for water systems in the search field.
SD DENR
SD DENR
Flow data and electricity consumption are used to determine the specific energy required (kWh/MG) for the various facilities within the system. This allows the facilities to be benchmarked and compared to similar facilities within the system or to other water systems. Determining specific energy also creates a baseline for energy use. This baseline can be used to identify changes in energy use and to track results of energy conservation measures. Creating graphical representations of energy use can help visualize trends and they can be useful for presenting information to others. Figure 6 presents specific energy for five well sites evaluated within a water system included in this study. The figure illustrates how an evaluation of flow data and energy use can be used to identify the sources of water that require the least energy input. Implementing this data into daily operations can significantly reduce energy use.
SD DENR
Figure 6. Example of Specific Energy Consumption for Five Wells within One System
4,500 4,000 3,500 3,000 2,500 kWh/MG 2,000 1,500 1,000 500 0 Well #1
Well #2
Well #3
Well #4
Well #5
SD DENR
these will constitute a planning level analysis. Of the recommended improvements, some will require no further design. However, projects that involve construction or new equipment will require outside expertise for design. Examples of typical ECMs are described in Sections 4 and 5 of this handbook, and example ECM calculations are included in Appendix B.
SD DENR
Rate schedules may also include miscellaneous taxes, fees, and customer charges that are added to each months bill. These costs are generally pre-determined and are not otherwise affected by monthly energy use, except that some are based on kWh used and effectively increases the usage cost.
SD DENR
10
Energy Charges
Energy charges are directly associated with hours of use and equipment efficiency. The hours of operation can be reduced by minimizing use through water conservation and leak detection and correction. Improving pump and motor efficiency will reduce energy usage by reducing wasted energy. Electric utility rate schedules should be evaluated to determine how energy charges are applied. Some electric utilities offer tiered rates that change with the amount of energy consumed, others offer a straight energy charge that remains constant. Time-of-use (TOU) rate schedules may be available and should be evaluated as a way to reduce energy charges. TOU energy charges vary by time of day and are set up to encourage off-peak energy use. If adequate storage is available within the water system, pumps can remain idle during peak hours and operated off-peak and substantial cost savings can be realized. Energy use can be calculated using Equation 1 for pump horsepower, Equation 2 for energy use, and Equation 3 for energy cost.
Equation 1. Pumping Horsepower
Q x TDH 3960 x pump efficiency bhp = brake horsepower Pump bhp = Q = pump flow (gpm) TDH = total dynamic head (feet)
Equation 2. Pumping Energy Use
pump bhp x 0.746 kW/hp x hours/day x days/month = monthly kWh motor efficiency
Equation 3. Pumping Energy Cost
SD DENR
11
The maximum kilowatt load for a pump motor can be approximated using Equation 4. Multiplying the demand by the demand rate gives the monthly demand charge, as shown in Equation 5.
Equation 4. Kilowatt input (Demand) to motor
KW input to motor =
In some cases demand charges have a ratchet clause. Rather than charge for the actual peak demand in the billing period the highest demand over the past 6 or 12 months is charged. Any operation that results in a higher than normal demand will result in an increased demand charge during that billing period and for several future bills as well. Reducing the load on a pumps motor for the entire billing period would in turn reduce the monthly demand charge. For pumps the only way to reduce the load on the motor is through the use of a variable frequency drive (VFD). Reducing a pumps speed can be an effective way to reduce demand charges, especially during winter months when water demands are low.
Power Factor
A third charge that is less frequently levied is for low power factor. The power factor is the ratio of the true power capacity of the circuit (measured in kW) to the power the utility actually needs to provide (measured in volt-amperes, VA). Customers whose loads have low power factor require greater generation capacity than what is actually used. A low power factor is caused by inductive loads. The most common type of inductive load is a motor. If a power utility charges for low power factor the water system should evaluate equipment, such as capacitors, to correct power factor and reduce harmonics. Variable frequency drives also correct for power factor and can be a viable alternative for reducing charges for a low power factor. Low power factor does cause some energy loss through increased heat losses. However, power factor correction will rarely be cost-effective based on energy savings alone. Cost savings comes primarily from avoiding utility charges for low power factor. Power bills should be monitored to identify if the power utility begins charging for low power factor.
Other Charges
In addition to the typical power charges, many utilities also include other miscellaneous charges. The names and criteria for these charges vary. Some common charges include a customer charge, power cost adjustment, and transmission charges. The amount of the charges can be fixed or can
SD DENR
12
be based on energy use. Charges based on energy use should be considered when calculating payback on ECMs. By reducing energy use these charges will also be reduced. An example electric bill is provided in Figure 7. Key elements of the bill have been highlighted. The example bill shows the rate schedule that is being applied to the energy use, energy use for the billing period, energy cost, peak demand, and demand cost.
Figure 7. Example Electric Bill
SD DENR
13
Water systems should also monitor funding sources available through SD DENR, EPA, and the US Department of Energy. Several new programs have been implemented and the current regulatory environment is favorable for grants or State Revolving Fund (SRF) loans. The US Department of Energy has created an Energy Efficiency and Renewable Energy (EERE) program. Information about opportunities to participate in their programs can be found at: http://www.eere.energy.gov/. The Energy Efficiency and Conservation Block Grant (EECBG) is one such program that may provide funding to implement energy efficiency and conservation programs. Information can also be found on the Database of State Incentives for Renewables & Efficiency (DSIRE) at: http://www.dsireusa.org/. Additionally a tax deduction of up to $1.80 per square foot is available for new or existing commercial buildings that are constructed or reconstructed to save at least 50% of the heating, cooling, ventilation, water heating, and interior lighting energy cost of a building that meets ASHRAE Standard 90.1-2001. Partial deductions of $.60 per square foot can be taken for improvements to one of three building systems that reduce total heating, cooling, ventilation, water heating and interior lighting energy use by a certain percentage below ASHRAE 90.1-2001the building envelope (10%), lighting (20%), or heating and cooling system (20%). An interim system-specific goal for lighting is provided directly in the legislation and is valid until the IRS issues a final regulation. The interim lighting provision allows prorated deductions from 30 cents to 60 cents per square foot for lighting systems. Rebates, incentives and tax deductions are continuously changing and the rebates and incentives offered by the power providers vary widely between providers. These need to be monitored and current offers utilized as appropriate when evaluating, making or planning for improvements and funding of proposed improvements.
SD DENR
14
ENERGY CONSUMPTION
AND
COST SAVINGS
Energy Consumption
Understanding where energy is being consumed is critical to focusing resources where the greatest savings potential exists. The greatest opportunity for savings comes from equipment that is routinely operated or from large improvements in efficiency. Replacing a pump with a limited run time with one that is only slightly more efficient will not likely be cost-effective. The available energy use data should be compiled and summarized for the facilities being audited. A useful measure of performance is specific energy consumption. This measures energy use relative to water production and can be calculated where flow and energy use data is available. Energy cost per million gallons is another useful measure as it will include costs associated with demand and other miscellaneous charges. An example of specific energy and cost data for well facilities is provided in Table 3 for one of the systems included in the SD DENR Small Water Systems Energy Audit.
Table 3. Example Annual Water Production and Energy Cost Facility Name Well #1 Well #2 Well #3 Well #4 Well #5 Well #6 Pumping 173 MG 207 MG 86 MG 163 MG 65 MG 0.0 MG Specific Energy 1,254 kWh/MG 3,863 kWh/MG 1,387 kWh/MG 1,669 kWh/MG 3,261 kWh/MG NA 2,673 kWh/MG Annual Cost* $17,468 $44,639 $9,951 $17,577 $14,031 $676 $104,344 $/MG Produced $101 /MG $215 /MG $116 /MG $108 /MG $217 /MG NA $150 /MG Average Energy Cost 8.1 /kWh 5.6 /kWh 8.4 /kWh 6.5 /kWh 6.7 /kWh 30.7 /kWh 6.4 /kWh
The energy consumption of the well sites was determined using past energy bills. This data indicates which wells cost less to operate per million gallons produced. In this example, well #2 and well #5 are approximately twice as expensive to operate as the other wells. In this case the cause of increased energy use is due to the depth of the aquifer and drawdown. In comparison, well #3 and well #4 can be free flowing and the static water elevation in well #1 is near the surface. Relying more on these three wells would significantly reduce power costs.
SD DENR
15
ENERGY CONSUMPTION
AND
COST SAVINGS
Another factor to consider is the location of pressure zones within the water system. Simply operating the most efficient well may not be the most efficient option. The location of booster pumps and pressure reducing valves within the system must also be considered. If a booster pump is used then the cost of production will include the energy consumed by the well and booster pumps.
Throttling Valves
Controlling flow or pressure by throttling a valve is inefficient and presents a good opportunity for energy and cost savings. This is especially true where flow is constantly throttled on the discharge of a pump. Any valve that is not fully open is imparting losses to the system and wasting energy. Several options are available for increasing efficiency, such as; trim the pump impeller, install a new pump that is sized to fit operating conditions, or install a VFD. Each option should be evaluated separately in order to compare capital costs, cost savings, energy reduction, payback time, and operational impacts.
SD DENR
16
ENERGY CONSUMPTION
AND
COST SAVINGS
235 ft
225 ft
BEP
195 ft
Design Groundwater Level
185 ft
Higher Groundwater Level
175 ft 0 200 400 600 800 1,000 Flow (gpm) 1,200 1,400 1,600 1,800 2,000
A VFD can help improve a pumps efficiency when the operating conditions are to the right of the pumps BEP. By reducing the speed of a pump, the operating point will shift left, back to a more efficient range as seen in Figure 9.
SD DENR
17
ENERGY CONSUMPTION
AND
COST SAVINGS
235 ft
225 ft
Pump Curve at reduced speed
New BEP
195 ft
185 ft
Higher Groundwater Level
175 ft 0 200 400 600 800 1,000 Flow (gpm) 1,200 1,400 1,600 1,800 2,000
Water systems can also benefit from reduced demand charges while pumps are operated at less than full speed for an entire billing period. This can occur during off-peak months when the pumps are not required to run at 100% by extending the historical pumping period or in conditions when the pumps are oversized. Demand charges are decreased each month a pump is run at less than full speed. The cost to install a VFD in an outdoor, climate controlled enclosure increases with horsepower. The added load of an air conditioner detracts from the electrical savings obtained with a VFD and needs to be considered in conjunction with the internal VFD losses mentioned previously.
Demand Management
Demand charges are an often overlooked charge that can make up a significant portion of the monthly power bill. Operational changes can often be made to reduce these demand charges. Examples include changing rate schedules, backwashing filters when other equipment is idle, maximizing individual well use within a billing cycle, reducing the number of wells that are operated during a billing cycle, etc. An awareness of how demand charges are applied can help water systems avoid unnecessary charges. An example of energy charges and demand charges are presented in Table 4.
SD DENR
18
ENERGY CONSUMPTION
AND
COST SAVINGS
Table 4. Example Demand Charge and Energy Use Comparison Facility Name Well #1 Well #2 Well #3 Well #4 Well #5 Well #6 Booster #1 Booster #2 Energy Use 216,900 kWh 800,480 kWh 119,160 kWh 267,501 kWh 210,920 kWh 2,200 kWh 206,160 kWh 26,240 kWh Average Monthly Demand 126.0 kW 131.6 kW 75.7 kW 61.5 kW 52.3 kW 8.9 kW 71.4 kW 8.9 kW Demand $ $5,552 $7,106 $3,354 $2,617 $2,406 $373 $3,147 $396 Total* $ $17,468 $44,639 $9,951 $17,577 $14,031 $676 $14,447 $1,991 Demand/Total Cost 32% 16% 34% 15% 17% 55% 22% 20%
This example shows that demand charges can range from 15% to 55% of the total electrical bill. Measures to help manage demand charges are discussed further in the following sections.
SD DENR
19
ENERGY CONSUMPTION
AND
COST SAVINGS
Current regulations should be reviewed prior to making operational changes that will impact how generators are operated. Operating internal combustion generators for power generation rather than only for emergency backup may require additional provisions to meet air quality regulations.
SD DENR
20
ENERGY CONSUMPTION
AND
COST SAVINGS
$/MG
Pump Efficiency
Pump efficiency affects energy use. The more efficient a pump and motor are, the less energy they use to perform the same amount of work. Regular maintenance should be performed on pumps in order to keep them as efficient as possible. Daily observations such as operating pressure, flow rates, operating sound levels, and unusual sounds can give an early indication of pending pumping issues and potential less efficient operation. Also on a routine basis, proper lubrication is to be conducted along with evaluating seal condition, wear ring and impeller conditions, bearing running temperature and condition, amp draw, etc., and compared to historical observations. This can allow for repairs or adjustments to be made early to keep the system operating as efficiently as possible and reducing failures. As pumps near the end of their useful life, they should be replaced by high efficiency pumps and motors.
SD DENR
21
ENERGY CONSUMPTION
AND
COST SAVINGS
pump head. Newer wells may include an airline, which can provide rapid determination of water levels. In order to obtain flow rate, a means of measurement must be available or provided. In many instances, existing installed flow metering devices can be used. If an existing flow element is not available a flow meter may be installed in the discharge line or a strap-on Doppler type device may be used. The ideal location for flow measurement varies by manufacturer, but is commonly specified by stating an unobstructed length of the discharge pipe ahead of and downstream of the flow meter (for example no bends, valves, etc. in that unobstructed segment). This minimizes the impact of turbulence on the accuracy of the flow measurement. This unobstructed pipe length is typically in the range of eight times the discharge pipe diameter upstream and five times the pipe diameter downstream. Shorter lengths than recommended by the manufacturer may be used, although the accuracy may be affected. Ideally, a vertical turbine (VT) pump sized for the field conditions should operate at 76 percent total system efficiency. Submersible pumps are slightly less efficient, at 72 percent total system efficiency. Pumps driven with a VFD are also less efficient due to losses associated with the VFD. Equation 6 shows how pump efficiency factors into the wire-to-water efficiency and provides an example using efficiencies typical of each component in the pump system.
Equation 6. Wire-to-Water Efficiency Wire To Water Efficiency = VFD Efficiency Motor Efficiency Pump Efficiency Effic w t w = (0.95 0.96 0.8 ) 100% = 73%
Two causes of poor efficiency for well pumps are typically attributed to mechanical wear and changing groundwater level. Worn impellers, wear rings, and bearings decrease mechanical efficiency while a drop in groundwater level increases the discharge head, pushing the pump back and up on its curve and away from its best efficiency point. Sand is the typical cause of premature wear in a well pump. Worn impellers and wear rings allow water to recirculate in the pump. Manufacturers anticipate about a 20 year life from a well pump due to wear on the impellers, wear rings, and bowls. The cost to replace or rebuild impellers and wear rings can be up to 50 percent of the cost for a new pump. This is usually feasible if the pump is still a good match for the field conditions. Owners typically opt to replace a pump when the repair cost approaches 75 percent of the cost for a new pump. This is usually the case when the line shaft and/or the bowls also need to be replaced. Well pumps with low efficiency should be pulled and modified or replaced to better match head conditions. The flow rate can be changed and the motor can also be replaced where needed. Note that acceptable paybacks are only achievable on wells that are operated routinely or have an appreciable efficiency improvement. Provisions to perform pump efficiency testing should be considered during the design of new facilities. For example sounding tubes and flow meters should be installed with new wells.
SD DENR
22
ENERGY CONSUMPTION
AND
COST SAVINGS
Performing pump efficiency testing on existing facilities without these provisions can be difficult or impossible.
UV Disinfection
Disinfection using ultraviolet (UV) light is becoming increasingly popular in water systems. Current regulations for disinfection contact time and disinfection byproducts can favor the use of UV systems. However, UV systems can be energy intensive to operate. As the cost of electricity rises, the use of UV systems will become less favorable. Rather, construction of larger clearwells or process changes to reduce disinfection byproducts may prove to be more cost-effective alternates. UV system controls should be set up to limit use. The UV system should only be used when flow rate, temperature, or pH make it necessary.
Filter Backwash
Filters are typically backwashed by dedicated pumps. Setting up the plant controls to ensure filter backwash occurs during times of low electrical demand can reduce demand charges. For example the monthly demand charge will be based on the greatest electrical demand observed during the billing period. By backwashing filters when other energy intensive equipment, such as high service pumps, are idle, a reduction in demand charges can be achieved. A Supervisory Control and Data Acquisition Systems (SCADA) system can be programmed to delay filter backwash or to temporarily shut down high service pumps during the backwash process.
SD DENR
23
ENERGY CONSUMPTION
AND
COST SAVINGS
Water Loss
Reducing water loss may present the greatest opportunity to reduce energy costs. Reducing water loss can be challenging and may require significant capital investments. Systems with relatively high water loss (greater than 25%) have an opportunity to significantly reduce energy use and costs. All water systems should track water loss and set goals of reducing loss. Systems with high percentages of water loss should make reducing water loss a priority. The American Water Works Association (AWWA) has realized the importance of improving water management and has recently updated their manual Water Audits and Loss Control Programs. The third edition was published in 2009 and includes a major advancement in water audit methodology, giving water utilities greater guidance in improving accountability and economically controlling water and revenue losses (AWWA, 2009). A water loss control program can identify real losses, unbilled consumption, and apparent losses. In general real losses are the primary type of loss and include distribution system leakage. Unbilled consumption is typically authorized by the water system. This would include flushing hydrants, backwashing filters, or other forms of use by the water system. Apparent losses include accounting errors, meter inaccuracy, and unauthorized consumption. Identifying the source of water loss can be difficult. Implementing a water loss control program will help identify sources of water loss and lead to corrective actions being taken. Water systems typically strive to account for 90% or more of their water.
Water Conservation
Water conservation programs generally focus on educating the customer on efficient water use, environmentally friendly practices, water efficient products, and product rebates. As demand for natural resources increases, water conservation will become an increasingly important issue. Water systems are in a unique position of encouraging their customers to conserve. Successful implementation of water conservation measures may have a negative impact on revenue. Decreased revenue prompts the water system to increase rates and can lead to frustration among consumers who feel they are being punished for their conservation efforts. Implementing
SD DENR
24
ENERGY CONSUMPTION
AND
COST SAVINGS
conservation measures, such as structured rates, that protect the water system from lost revenue and encourages conservation will be difficult. Rate structures with high fixed costs provide stability to the water utilitys revenue but do little to encourage conservation. A rate structure with low fixed costs and tiered rate increases corresponding to water use provide the greatest incentive for conservation. However, such a rate structure leaves the water system vulnerable to volatile revenue. As water conservation becomes increasingly important, water systems in the state of South Dakota will need to find ways to encourage conservation while generating adequate revenue.
SCADA
SCADA systems are becoming the norm for control of most treatment facilities due to the affordability of robust computing systems, increased data transmission speed, open architecture design, flexibility, and more user friendly control software systems. A computer or computers in conjunction with programmable logic controllers (PLCs), remote telemetry units (RTUs) and other devices add significant flexibility in what data is monitored and collected as well as how equipment can be operated over hardwired relay and switch operated systems. SCADA systems can result in energy savings by optimizing the treatment and pumping operations via real-time monitoring and automated control of equipment and systems. Automated operation or SCADA assisted operation to adjust driver speeds, pump sequencing, elevated storage filling timing, backwash initiation and duration, and HVAC monitoring and control are just some of the potential areas where power use can be reduced. Additionally, the SCADA system can be beneficial in actually monitoring energy use, demand peaks, etc. This gives the operations staff members a means of visualizing what their operation decisions have on the energy consumption and demand. This could also be taken a step further to incorporate the power providers rate schedule into the system, such that an approximation of what the power costs are can be shown. As mentioned previously, it is common that the plant staff members do not see the power bills and therefore dont fully understand how their decisions may impact actual costs.
HVAC
HVAC systems can be gas or electric powered on the heating side and electrical on the cooling side. No matter what the power supply, a cost savings may be available by reducing power consumption by replacement with more efficient systems, however payback can be quite long. Additionally, geothermal heating system can be used to provide a much more efficient HVAC system. These can utilize a closed loop in which the ground (via a well or buried loop) is used as a heat source or in a water facility the water already being pumped can be used as the source. This is more feasible during initial construction due to the high capital costs, but with the availability of grants, rebates, tax incentives, etc., each application needs to be evaluated under its own conditions.
SD DENR
25
ENERGY CONSUMPTION
AND
COST SAVINGS
Check with the power provider for potential rebates on more efficient HVAC systems or components. Items that can be done to existing systems that can reduce power use at low to no cost include: Keep filters on forced air units clean to reduce pressure drop, Seal leaking areas around doors, Use programmable thermostats to automatically reduce temperature when unoccupied (check for rebate offers from power provider)
For areas that are typically unoccupied, reduce normal temperature on the thermostat in the winter and raise the temperature in the summer if applicable.
Lighting
Lighting at water treatment facilities can realize a power cost savings associated with lighting spaces. When compared to pumping this can be a much smaller savings, but not insignificant. The savings can be through installation of occupancy sensors, reducing lighting coverage or intensity, using compact fluorescent (CFL) or LED lighting, etc. Savings can be impacted by rebates from the electrical service provider or through grants, incentives, tax breaks, and so on that are quite prevalent at this time of renewed emphasis on energy conservation. Occupancy sensors turn the lights on when occupancy is detected and turn them off after an area has remained unoccupied for a set period of time. These sensors are most effective at reducing energy consumption from lighting in spaces where occupancy is intermittent or where lights are left on in spaces after occupants leave. Occupancy sensors use passive infrared sensors, ultrasonic sound waves, or both (called dual technology) to detect occupancy. These sensors can be installed either on walls or ceilings. Wall sensors are typically used in small rooms, such as private offices, whereas ceiling sensors are generally used in larger rooms. Each sensor manufacturer has its own style of occupancy sensors. In general, ultrasonic sensors are more sensitive and work in a lot of spaces but are also subject to false ons due to air movement and motion outside of doors. Infrared sensors have a more focused coverage range and are more appropriate for smaller rooms, such as private offices. Dual technology sensors use an infrared sensor to activate lights and use an ultrasonic sensor to keep lights on, thus reducing false ons and offs. We suggest consulting the manufacturers literature to select the sensor with the right coverage area and sensor technology for each particular space. Reducing lighting lamination is a consideration. Designers follow typical standards when lighting spaces and that may be more than needed or desired in certain areas. Reducing lamp wattages would directly reduce lighting energy usage. CLF and LED lights will significantly reduce the kW usage to provide the same lamination as incandescent lighting. CFLs currently consume less than 25% of the power of an incandescent
SD DENR
26
ENERGY CONSUMPTION
AND
COST SAVINGS
bulb, with a 23W CFL being essentially equivalent to a 100W incandescent bulb and the expected life of the bulbs are 8 to 15 times longer. The cost of CFLs have reduced significantly over recent years, making them cost-effective in many instances. LED lamps are even more efficient, at approximately 10% of the energy consumption of an incandescent bulb, and with a life that can exceed 25 years. The cost of these lamps are still quite high, such that CFLs currently are normally more cost-effective, but should be compared. The use of LEDs in inaccessible areas may be desirable due to their extremely long life, regardless of the cost savings.
Unnecessary Equipment
There are cases in which equipment or processes are installed in a water treatment facility or distribution system that are not necessary to provide safe, reliable drinking water in compliance with SDWA requirements. This may be due to construction in anticipation of future regulations, changes in source water characteristics, effectiveness of treatment, demand, and numerous other factors. In such cases, the system can reduce operation or eliminate such unnecessary processing to reduce power consumption. Just because the equipment exists, or that is the way it was always operated, doesnt mean that it needs to be operated or operated that way. Evaluate the process and operate as required to meet regulatory requirements in a safe and reliable manner without additional unnecessary steps.
SD DENR
27
Aeration
Dewatering
Lighting
SD DENR
28
Selected ECMs that were developed for the individual energy audit participants are provided in the Appendix. These ECMs have been provided so that the general ECM development process can be more easily understood. A payback period, or return on investment period, of 5 years was set as a limit for the ECMs provided.
SD DENR
29
RENEWABLE POWER
Solar Power
Solar energy technology has a number of different systems and variations of those systems. In addition, many of the technologies are advancing at this time with changes in the unit cost and development of larger and more efficient systems. In general, solar energy can be separated into systems that generate electrical energy and those that generate thermal energy. Solar electrical generation systems are photovoltaic (PV) and thermal energy generation systems are concentrating solar power (CSP). Both PV and CSP have a number of subsets or variations on the basic technology. Almost all of these systems are proprietary and have manufacturers that specialize and develop standard products. The following provides more detailed information regarding the PV electrical energy systems.
Photovoltaic
PV systems generate electricity as the light rays travel through a medium such as silicon crystals. The panels generate direct current power. Inverters are used to transform the power into alternating current (AC) power commonly provided by utilities. Each type of PV material will tend to capture the energy from a portion of the wave lengths or spectrum of the light source (e.g. red, yellow, or blue). Advances in PV material and systems are occurring and there has been a general improvement in the efficiency of the systems over time. The main components of the systems include: PV material a. Crystalline single and multi-junction b. Thin film Tracking a. Fixed flat or tilted generally facing south in the northern hemisphere. b. Single axis tracking generally rotating east to west as the sun rises in the morning and sets in the evening. c. Double axis tracking rotating east to west and up and down as the sun varies by day and season.
SD DENR
30
RENEWABLE POWER
Light Concentration a. Flat panels with no magnification or focusing. b. Concentrating PV with mirrors or lenses to concentrate the sunlight into a smaller area. Capacity or Size a. Size or capacity vary widely with larger systems currently in development. Installation capacities vary from small 10 watt panels to charge batteries, 500KW systems to provide a portion of the commercial buildings electrical needs, to a 10250MW utility grade solar power plant connected to the utilitys high voltage transmission system.
Proprietary Systems Wide arrays of proprietary systems are commercially available. Some systems are specially designed for residential, commercial/industrial, or utility installation. Building integrated systems for roofs, windows, light weight roof installation, flexible thin film membrane, mobile systems, emergency power, battery charging, and numerous other systems are available Solar PV Pros: Low land use when installed on available rooftop and above parking area square footage. No transmission requirements. Provide power during peak demand as solar intensity typically coincides with peak power uses such as air conditioning peaks on hot summer days. Ability to ramp up quickly.
Solar PV Cons: Without energy storage (such as a battery), it is a must take energy source. Storing large amounts of electricity can be difficult. Dollar per watt is expensive when compared to large-scale base-load units. Variable and uncertain energy source.
The National Renewable Energy Laboratory (NREL), U.S. Department of Energy map in Figure 11 illustrates the solar resource potential by region. Solar conversion is an inefficient process; typical PV cells have a conversion efficiency ranging from 10% to 16%. The solar resource potential is reported in units of kilowatt-hour per square meter produced over the course of one day.
SD DENR
31
RENEWABLE POWER
A typical 1-kW, 11% efficient PV array may range in size from 8 to 9 m2; however, a larger array requires access space as well as spacing between the rows of panels to avoid self-shading and will subsequently require a greater amount of space per installed kW.
Wind Power
The United States has the benefit of holding a vast wind power resource. Total wind power available in a region is calculated by multiplying the total kinetic energy per unit mass by the flow rate. Wind turbines are unable to extract the total power available as that would require reducing the wind speed to zero. Instead, the actual power extracted is found by the actual pressure and velocities before and after the turbine. However, the greater the total ideal power, the greater the actual power extracted. The method of multiplying total kinetic energy per unit mass results in the total ideal power being proportional to the cube of the wind velocity. Wind velocity is therefore critically important to feasible wind power generation. There are two classifications of wind energy technologies: large scale industrial and small scale distributed or commercial systems.
SD DENR
32
RENEWABLE POWER
Industrial wind energy referred to as wind farms consist of larger groups of horizontal axis wind turbines (HAWT) that are capable of producing in the range of 660 kW to 3 MW of power output each. Distributed or commercial systems consist of smaller HAWT or vertical axis wind turbines (VAWT) and are typically mounted on top of, or amongst, urban construction.
Industrial commercial system turbines are typically HAWT configuration and are capable of producing in the range of up to 50 to 250 kW of power output each. Residential and commercial distributed systems are capable of producing in the range of 400 watts to 50 kW. These systems have varying hub heights and turbine spacing requirements. Distributed Wind Power Pros: Low land use. No transmission requirements. Provide power during peak demand. Able to ramp up quickly.
Distributed Wind Power Cons: Without energy storage (such as a battery), it is a must take energy source. Variable and uncertain energy source. Storing large amounts of electricity can be difficult. Dollar per watt is expensive when compared to large-scale base-load units.
SD DENR
33
RENEWABLE POWER
Hydropower
Hydropower may be a viable option in situations where large amounts of head are currently being wasted such as large pressure reducing stations. Hydropower facilities could benefit water systems by providing power to operate equipment and reduce the amount of power purchased from the power utility. The general equation for hydropower capacity is:
Equation 7. Hydropower Capacity
Where : Pw = power produced in kilowatts (kW) Q = flow through turbine (cfs) H n = net head on turbine (ft) h = hydropower plant efficiency (0.8 typical) A substantial flow rate and net head must be available in order to generate a significant amount of power. The application of hydropower to small drinking water systems is not likely to occur in the near future. However the opportunity may be present in some systems. As electrical rates increase and funding for alternative energy sources becomes available, such systems may be costeffective.
SD DENR
34
RENEWABLE POWER
SD DENR
35
APPLICATION
TO
OTHER FACILITIES
SD DENR
36
CONCLUSION
Below, in Table 8, the nine systems evaluated are listed along with the effective power cost, power use, and costs on a per million gallons (MG) basis.
Table 8. Energy Use and Costs at Nine Small Water Systems Evaluated Facility Name City of Brandon Clark Rural Water System Clay Rural Water System Dakota Dunes Lead-Deadwood Sanitary District Lower Brule Rural Water System Rapid Valley Sanitary District City of Spearfish West River/Lyman Jones Rural Water Total/Average Served Population 8,400 2,700 2,100 2,850 5,700 2,000 9,000 9,300 8,300 50,350 Annual Water Treated / Distributed MG 302 301 233 212 207 111 290 693 784 3,133 Average Effective Power Cost ( /kWh) 9.62 8.9 6.1 6.25 6.8 8.1 8.8 6.5 11.6 8.07 Average Electrical Power Use kWh/MG 2,872 3,768 3,762 1,916 2,360 7,013 3,445 2,700 1,151 3,221 Average Electrical Power Cost $/MG $276 $336 $274 $120 $160 $572 $303 $173 $139 $261
Since this was a representative cross section, the information collected and results of the analysis can be used by other systems across the state to see how they compare currently and get a gross estimation of potential energy savings they could realize by implementing energy conservation measures. For the initial comparison the system will need to: 1. Collect a minimum of one year of electrical power used for the entire treatment and distribution system to arrive at: o The total annual kWh used
SD DENR
37
CONCLUSION
2. Calculate o The power usage/MG used in treatment and distribution by dividing the total annual kWh used by the annual water treated for that year in MG (kWh/MG). o The power cost/MG for treatment and distribution by dividing the total annual power cost by the annual water treated for that year in MG ($/MG). 3. Compare the range and average values calculated in Step 2 above with those in Table 8 to get an indication of how the facility compares to those evaluated. To be more specific, the comparison can be made with the values presented for the facilities with similar treatment and distribution conditions. Several ECMs were evaluated for these systems and desirable ECMs with a short payback were recommended to be implemented. Examples of ECM calculations are presented in Appendix B. The total estimated annual power and cost savings are presented, along with a savings per MG in Table 9. These can also be utilized for comparisons and an indication of potential energy savings.
Table 9. Estimated Energy Savings at Nine Small Water Systems Evaluated Facility Name City of Brandon Clark Rural Water System Clay Rural Water System Dakota Dunes Lead-Deadwood Sanitary District Lower Brule Rural Water System Rapid Valley Sanitary District City of Spearfish West River/Lyman Jones Rural Water Total/Average Annual Water Treated / Distributed MG 302 301 233 212 207 111 290 693 784 3,133 Estimated Annual Power Use Savings kWh 32,840 116,990 107,380 59,870 50,410 74,530 184,020 493,080 80,430 1,199,550 Estimated Annual Power Cost Savings $ $6,020 $24,550 $8,550 $3,500 $5,830 $5,570 $15,320 $46,480 $19,280 $135,100 Estimated Annual Power Use Savings kWh/MG 109 389 461 282 244 671 635 712 103 383 Estimated Annual Power Cost Savings $/MG $19.90 $81.60 $36.70 $16.50 $28.20 $50.20 $52.80 $67.10 $24.60 $43.10
An indication of what energy savings could be realized across the state of South Dakota for all community water system if feasible ECMs were implemented can be estimated using the average values presented in Table 9 and system annual treated water values from the SD DENR. In all, there are approximately 460 community water systems in South Dakota with an annual treated water production of approximately 45 billion gallons.
SD DENR
38
CONCLUSION
Assuming similar results and recommended ECMs are implemented, the annual power savings statewide for all public water systems could be approximately 17 million kWh and $2 million dollars.
SD DENR
39
CONCLUSION
IX. References
USDOE (US Department of Energy), 2006. Energy Demands on Water Resources: Report to Congress on the Interdependencies of Energy and Water. USDOE, Washington. Biehl, W.H. & Inman, J.A., 2010. Energy Optimization for Water Systems. Jour. AWWA, 102:6:50. EPRI (Electric Power Research Institute), 2002. Water and Sustainability (Volume 4): U.S. Electricity Consumption for Water Supply & Treatment The Next Half Century, EPRI, Palo Alto, CA: 2000. 1006787. EPA (US Environmental Protection Agency), 2010. Energy Star for Wastewater Plants and Drinking Water Systems. www.energystar.gov. EAP (US Environmental Protection Agency), 2008. Ensuring a Sustainable Future: An Energy Management Guidebook for Wastewater and Water Utilities. AWWA (American Water Works Association), 2009. Water Audits and Loss Control Programs, 3rd edition (Manual of water supply practices, M36). AWWA, Denver, CO. Roberts, D.W.; Kubel, D.; Carrie, A.; Schoeder, D.; & Sorenson, C., 2008. Cost and Benefits of Complete Water Treatment Plant Automation. AWWARF and IWA, London.
SD DENR
40
This rate applies to single-phase services with installed transformer capacity of 100 KVA or less. Type of Service: Single-phase, 60 cycles, at available secondary voltages. Rate: Facility Charge: Energy Charge: Tax Liability Clause: Billing charges calculated using rates in this schedule are subject to any taxes the Cooperative must pay or collect during the application of this rate schedule. Minimum Monthly Charge: The minimum monthly charge is $30.00 when installed transformer capacity is 15 KVA or less. When transformer capacity exceeds 15 KVA, the minimum monthly charge will increase at the rate of $0.75 for each additional KVA of capacity. If KVA capacity is not a whole number, KVA capacity is rounded to the next whole number before calculating minimum monthly charge. Purchased Power Adjustment Clause: If the wholesale cost for purchased power changes, the Cooperative may increase or decrease billing charges that are calculated by using the rates in this schedule. Adopted by board action: February 23, 2010 Effective: Billings on and after May 1, 2010 $30.00 per month 8.4 cents per kWh
This rate applies to single-phase services with installed transformer capacity greater than 100 KVA and to multi-phase services. Type of Service: Single-phase or multi-phase, 60 cycles, at Cooperatives standard voltages. Rate: Facility Charge: Demand Charge: Energy Charge: Tax Liability Clause: Billing charges calculated using rates in this schedule are subject to any taxes the Cooperative must pay or collect during the application of this rate schedule. Determination of Billing Demand: The maximum kilowatt demand that occurs during any period of fifteen (15) consecutive minutes within a billing cycle, as indicated or recorded by metering equipment installed by the Cooperative, determines billing demand. Minimum Monthly Charge: In some cases, a contract for service will specify the minimum monthly charge. If no contract exists, the minimum monthly charge is the monthly facility charge or an amount equal to $1.00 per KVA of installed transformer capacity, whichever is greater. If KVA capacity is not a whole number, KVA capacity is rounded to the next whole number before calculating minimum monthly charge. Interruptible Service: The demand charge portion of the rate is waived for any service site controlled by a Cooperative-approved load control device; provided, the member/consumer has paid in full any applicable fees or charges, and any device or seal remains intact throughout the billing cycle and exhibits no evidence of tampering. $50.00 per month $13.30 per kW of billing demand 6.2 cents per kWh
(more)
Page 2
If service is furnished at secondary voltage, the delivery point is the metering point, unless otherwise specified in a contract for service. The member/consumer owns and has maintenance responsibility for all wiring and other electrical equipment on the load side of the delivery point. If service is furnished at Cooperatives primary line voltage, the delivery point is the point of attachment of Cooperatives primary line to member/consumer's transformer structure, unless otherwise specified in a contract for service. The member/consumer owns and has maintenance responsibility for all wiring and other electrical equipment on the load side of the delivery point, except for metering equipment owned by the Cooperative. Purchased Power Adjustment Clause: If the wholesale cost for purchased power changes, the Cooperative may increase or decrease billing charges that are calculated by using the rates in this schedule. Adopted by board action: February 23, 2010 Effective: Billings on and after May 1, 2010
This rate applies to single-phase service with installed transformer capacity greater than 100 KVA and to multi-phase service, without regard to transformer size, when either type of service is equipped with a load control device, standby generation and control-time demand metering. Type of Service: Single-phase or multi-phase, 60 cycles, at Cooperatives standard voltages. Rate: Facility Charge: Demand Charge: Energy Charge: Tax Liability Clause: Billing charges calculated using rates in this schedule are subject to any taxes the Cooperative must pay or collect during the application of this rate schedule. Determination of Billing Demand: Billing demand does not apply during the months of March, April, May, September and October. The maximum kilowatt demand that occurs during load control periods within a billing cycle, as indicated or recorded by metering equipment installed by the Cooperative, determines billing demand during the months of January, February, June, July, August, November and December. Demand charges associated with this rate will apply to demand recorded in any two billing cycles during a 24-calendar month rolling period. On the third occurrence of demand recorded in a billing cycle during the rolling period, demand charges will increase to three (3) times the demand charges associated with this rate as penalty for not complying with the spirit and intent of the rate class. Minimum Monthly Charge: In some cases, a contract for service will specify the minimum monthly charge. If no contract exists, the minimum monthly charge is the monthly facility charge or an amount equal to $1.00 per KVA of installed transformer capacity, whichever is greater. If KVA capacity is not a whole number, KVA capacity is rounded to the next whole number before calculating minimum monthly charge. $50.00 per month $13.30 per kW of billing demand 6.3 cents per kWh
(more)
Electric Rate Schedule: LPG LP Service with Auto-start Generator Service Provisions:
Page 2
If service is furnished at secondary voltage, the delivery point is the metering point, unless otherwise specified in a contract for service. The member/consumer owns and has maintenance responsibility for all wiring and other electrical equipment on the load side of the delivery point. If service is furnished at Cooperatives primary line voltage, the delivery point is the point of attachment of Cooperatives primary line to member/consumer's transformer structure, unless otherwise specified in a contract for service. The member/consumer owns and has maintenance responsibility for all wiring and other electrical equipment on the load side of the delivery point, except for metering equipment owned by the Cooperative. Purchased Power Adjustment Clause: If the wholesale cost for purchased power changes, the Cooperative may increase or decrease billing charges that are calculated by using the rates in this schedule. Date adopted: February 23, 2010 Date effective: Billings on and after May 1, 2010
Rate Code 43
(T) (T)
(T) (T)
MUNICIPAL PUMPING AVAILABLE At points on the Companys existing distribution facilities supplied by its interconnected transmission system within Butte, Custer, Fall River, Lawrence, Meade, and Pennington Counties of South Dakota. APPLICABLE To incorporated municipalities for electric service which is needed for and used in connection with the year-round operation of water utility pumping and treatment and sewage disposal facilities. This schedule is not applicable to temporary, standby, supplementary, emergency, resale, shared, or incidental service. CHARACTER OF SERVICE Alternating current, 60 hertz, at the voltage and phase of the Companys established distribution system most available to the location of customer. NET MONTHLY RATE Rate Customer Charge Capacity Charge Summer Rate $16.50 $4.54 per kW of Billing Capacity All usage at 6.05 per kWh Winter Rate $16.50 $4.08 per kW of Billing Capacity All usage at 6.05 per kWh (R) (R)
Energy Charge
(R)
Minimum The Capacity Charge but not less than the applicable Customer Charge. BILLING CAPACITY Customers average kilowatt load during the fifteen-minute period of maximum use during the month. Power Factor Adjustment If the power factor for the month (determined at the Companys option by permanent measurement or by a test of not less than fifteen-minute duration under conditions which the Company determines to be normal) is less than eighty-five percent at the point of delivery, the Billing Capacity will be increased by multiplying the eighty-five percent and dividing the power factor expressed in percent. The power factor is defined to be the quotient obtained by dividing the kilowatthours used during the month by the square root of the sum of the squares of the kilowatts used and the lagging reactive kilovolt-ampere-hours supplied during the same period. Any leading kilovoltampere-hours supplied during the period will not be considered.
Rate Code 43
(T) (T)
(T) (T)
MUNICIPAL PUMPING ENERGY COST ADJUSTMENT The above schedule of charges shall be adjusted in accordance with: 1. The Fuel and Purchased Power Adjustment tariff. 2. The Transmission Cost Adjustment tariff. When the billing period includes a change in the charges of an above referenced Energy Cost Adjustment tariff, the customers bill shall be prorated accordingly. PAYMENT Net monthly bills are due and payable twenty days from the date of the bill, and after that date the account becomes delinquent. A late payment charge of 1.5% on the current unpaid balance shall be calculated and included as part of each monthly billing. A non-sufficient funds charge of $15.00 shall apply to process a payment from a customer that is returned to the Company by the bank as not payable. If a bill is not paid, the Company shall have the right to suspend service, providing ten (10) days written notice of such suspension has been given. When service is suspended for nonpayment of a bill, a Customer Service Charge will apply. TERMS AND CONDITIONS 1. This schedule is predicated on continuous service of twelve months per year. If the customer desires only seasonal service, such service will be provided under the Companys applicable General Service schedule. 2. This schedule is not applicable for the pumping of water from streams, ponds, or lakes and applied directly to public parks and grounds for irrigation purposes or for other similar projects. 3. The Summer Rate shall apply to usage between June 1 through October 31. The Winter Rate shall apply to usage between November 1 through May 31. The Company reserves the right to modify the months applicable to the summer-winter billing periods. 4. Service will be rendered under the Companys General Rules and Regulations. TAX ADJUSTMENT Bills computed under the above rate shall be adjusted by the applicable proportionate part of any impost, assessment or charge imposed or levied by any governmental authority as a result of laws or ordinances enacted, which is assessed or levied on the basis of revenue for electric energy or service sold, and/or the volume of energy generated and sold. (D) (N) (D)
Rate Code 25
(T) (T)
(T) (T)
ENERGY STORAGE SERVICE AVAILABLE To customers installing certain energy efficient electrical equipment that will increase off-peak electrical use and reduce the Companys On-Peak demand, at points on the Companys existing secondary distribution lines supplied by its interconnected transmission system. The rate has been developed as part of the Companys Demand-Side Management strategy. APPLICABLE At the customers election, to General Service customers who operate Company approved energy storage facilities for the purpose of utilizing off-peak electric energy for space conditioning, water heating, battery charging, water pumping, and/or snowmaking. Electric energy will be supplied through a separately metered circuit utilizing the same transformer and service used to serve the balance of the customers electrical load. CHARACTER OF SERVICE Alternating current, 60 hertz, at the voltage and phase of the Companys established distribution system most available to the location of the customer. Energy Storage Service will be provided on a Time-Of-Use schedule for qualified Partial Storage and Geothermal systems. The number of off-peak hours available will amount to eight hours each day during the winter season, twelve hours each day during the summer season, and 24 hours a day on weekends and major holidays during both summer and winter seasons. NET MONTHLY BILL Rate Customer Charge $11.50 per month Energy Charge Off-Peak: On-Peak:
(R)
(R) (R)
Capacity Charge Off-Peak: no charge On-Peak: $7.68 per kW of Billing Capacity Minimum The Customer Charge
(R) (R)
Rate Code 25
(T) (T)
(T) (T)
ENERGY STORAGE SERVICE BILLING CAPACITY Customers average kilowatt load during the fifteen minute period of maximum On-Peak use during the month. Power Factor Adjustment If the power factor for the month (determined at the Companys option by permanent measurement or by a test of not less than fifteen minute duration under conditions which the Company determines to be normal) is less than eighty-five percent (85%) at the point of delivery, the Billing Capacity will be increased by multiplying by eighty five percent (85%) and dividing by the power factor expressed in percent. Power factor is defined to be the quotient obtained by dividing the kilowatt-hours used during the month by the square root of the sum of the squares of the kilowatthours used and the lagging reactive kilovolt-ampere-hours supplied during the same period. Any leading kilovolt-ampere-hours supplied during the period will not be considered. Penalty for Non-compliance If a Partial Storage customer exceeds their partial storage Limit (expressed in kW) during peak time periods, a penalty of five (5) times the Capacity Charge per kW will be assessed for the difference in kW that the maximum billing capacity exceeds the partial storage limit. The partial storage limit will be determined using design day load profiles from standard industry load calculation methods. A conversion factor of 0.75 kW per ton will be used for Cool Storage applications. ENERGY COST ADJUSTMENT The above schedule of charges shall be adjusted in accordance with: 1. The Fuel and Purchased Power Adjustment tariff. 2. The Transmission Cost Adjustment tariff. When the billing period includes a change in the charges of an above referenced Energy Cost Adjustment tariff, the customers bill shall be prorated accordingly. PAYMENT Net monthly bills are due and payable twenty days from the date of the bill, and after that date the account becomes delinquent. A late payment charge of 1.5% on the current unpaid balance shall be calculated and included as part of each monthly billing. A non-sufficient funds charge of $15.00 shall apply to process a payment from a customer that is returned to the Company by the bank as not payable. If a bill is not paid, the Company shall have the right to suspend service, providing ten (10) days written notice of such suspension has been given. When service is suspended for nonpayment of a bill, a Customer Service Charge will apply. (D) (N) (D) (T)
Rate Code 25
(T) (T)
(T) (T)
ENERGY STORAGE SERVICE TERMS AND CONDITIONS 1. Service will be rendered under the Companys General Rules and Regulations where not inconsistent with any specific provisions of this rate schedule or the service contract. 2. Service will be provided under this rate schedule only to customers who have contracted for service for an initial term of not less than three years. The contract may be terminated at any time on or after the expiration date of the initial term by twelve months written notice. 3. The Company will supply and maintain Time-of-Use metering to provide Off-Peak energy to Full Storage systems and to provide On-Peak and Off-Peak energy for Partial Storage and Geothermal systems. 4. The Company shall have the right to inspect all wiring and equipment connected to the storage circuit. In the event the Company finds that the customers wiring has been altered or arranged in any manner so that energy is used in any equipment other than Company approved energy storage facilities, the contract for service under this rate schedule may be terminated. 5. The Company may, at its option, install in the energy storage circuit load limiting devices to limit the total load to be served through the energy storage circuit. 6. Off-Peak Hours: Summer Months (April 1 October 31) 10:00 p.m. 10:00 a.m. (November 1 March 31) 11:00 p.m. 7:00 a.m.
Winter Months
Both Seasons
The hours may be shifted one (1) hour in accordance with the recognized Daylight Savings Time (DST) in the local area and customers will be notified prior to such change.
Rate Code 25
(T) (T)
(T) (T)
ENERGY STORAGE SERVICE 7. MEANS OF CONTROL: On Full Storage and Partial Storage systems, Company will install time of use metering to monitor onpeak demand limits. If the On-Peak limit is exceeded the Penalty for Non-Compliance will be assessed. 8. QUALIFIED SYSTEMS: A. Full Storage Available to heating, water heating, cooling, battery storage and water pumping applications that are able to store energy during Off-Peak periods for use during On-Peak periods. B. Partial storage Cooling Partial storage equipment size must be at least 25% less than conventional equipment size during On-Peak time periods. Chiller equipment, cooling tower pumps and fans, and cool water circulating pumps qualify for the rate. Air handling equipment and hot water circulating pumps do not qualify. A penalty for non-compliance will be assessed if the partial storage limit is exceeded. C. Partial Storage Heating and Water Heating Electric heating and water heating equipment used with Off-Peak storage capability and a heat storage medium (sand, bricks, liquid, etc.) qualify for partial storage when used in the applications listed below. A penalty for noncompliance will be assessed if the partial storage limit is exceeded. 1. An Electric Boiler used in combination with water loop heat pumps qualifies for Partial Storage. The Electric Boiler size must be 25% less than conventional equipment during On-Peak periods. Water-loop heat pumps, air handling equipment, and circulating pumps do not qualify. 2. Resistance Heat and Water Heating qualify for Partial Storage when no more than 50% of the system capacity is allowed to operate during On-Peak periods. D. Geothermal Applications Geothermal heat pumps, associated air handling equipment and circulating pumps qualify for the rate. Supplementary resistance heat associated with each heat pump or supplementary electric boiler heat associated with the geothermal system also qualify for the rate.
Rate Code 25
(T) (T)
(T) (T)
8. QUALIFIED SYSTEMS: (continued) E. Partial Storage Snowmaking Partial storage equipment size must be at least 50% less than conventional equipment during On-Peak time periods. Primary snowmaking equipment eligible for the rate includes air compressors and water pumps. 9. DESIGN REVIEW: Detailed design information must accompany each Energy Storage Application including: A. A 24-hour design day cooling, heating, water pumping, and/or snowmaking load profile using standard industry load calculation methods. B. A system description with operating strategy. The Demand-Side Management Department shall review and approve the Energy Storage Application and proposed contract. TAX ADJUSTMENT Bills computed under the above rate shall be adjusted by the applicable proportionate part of any impost, assessment, or charge imposed or levied by any governmental authority as a result of laws or ordinances enacted, which is assessed or levied on the basis of revenue for electric energy or service sold, and/or the volume of energy generated and sold.
Sheet 1 of 2
HDR Computation
Subject: Task: Energy Savings and Cost Analysis Switch Nevin Well to Energy Storage Rate
Operational
Existing Condition: Nevin well is operated on municipal pumping rate. Demand charges are assessed for operating the well on this rate schedule. Proposed Change: Switch to the energy storage rate. Demand charges are not assessed during times of off-peak usage. Energy Savings:
There are no energy savings for this ECM. Cost savings is realized by avoiding demand charges.
Energy:
Existing Condition Energy Cost = energy use * energy charge = 216,900 kWh * $0.0605/kWh = $13,120 Capacity Cost = kW input * capacity charge * 12 months = 169 kW * $4.31/kW * 12 months = $8,740 Energy Storage Rate Energy Cost = energy use * energy charge = 216,900 kWh * $0.032/kWh = $6,940 Capacity Cost = No Charge
Savings:
Sheet 2 of 2
Comments: This is basic calculation of cost savings. Annual run times were assumed to be the same for both scenarios. To increase savings the Nevin well should be ran as much as possible during off peak hours. Additional savings would be realized be reducing the run times of the other wells.
Sheet 1 of 1
HDR Computation
Subject: Task: Energy Savings and Cost Analysis Reduce Water Loss to 10%
Existing Condition: Existing water loss is approximately 32% Proposed Change: Reduce water loss to 10% Energy Savings:
Yearly Energy Use = 1,871,000 kW-hr / yr Recommended 10% Water Loss Yearly Energy Use = Current Energy Use * (1 - percent improvement) = 1,871,000 * (1 - 0.22) = 1,459,380 kW-hr / yr Savings: kW-hr / yr = 1,871,000 - 1,459,380 = 411,620 kW-hr / yr
$ / yr = $0.0605 / kW-hr x 411,620 kW-hr / yr = $24,900 / yr Capital Cost: Reduce Water Loss Simple Payback: None - funded by existing O&M budget. = NA = NA Recommended: YES
Comments: A water audit and distribution system leak detection should be performed. A water audit will help identify any apparent losses that may be occuring due to items such as inaccurate meters or accounting errors. A distribution leak detection program could be performed on the entire distribution system. The potential savings justify making a significant effort to find and eliminate water loss.
Sheet 1 of 1
HDR Computation
Subject: Task: Energy Savings and Cost Analysis Install Varible Frequency Drives on Pump Motors
Existing Condition: None of the well pumps currently have VFDs installed. Proposed Change: Install VFDs on the 4 primary wells - Nevin, Dickey, College, and Vigna Energy Savings: Cost savings will be realized by gaining the ability to operate motors at reduced speeds. Reduced speed operation would be able to meet demands during winter months and would reduce demand charges. Cost savings were determined for operating wells at 60% speed from October 1st to March 31st. kW Average kW Reduction @ Demand 60% 89.6 76.7 73.9 131.7 35.8 30.7 30.0 52.7 149.2 Montly Savings @ $4.08 / kW $146 $125 $122 $215 $608
Capital Cost: VFDs Nevin College Dickey Vigna Total Simple Payback: $20,000 $10,000 $15,000 $15,000 $60,000 = $60,000 / $3,648 = Recommended: NO (>5 yrs) 16.4
Comments: Reduced demand charges do not provide the necessary savings for a payoff of 5 years. VFDs also reduce overall efficiency by approximately 4%. Increased energy use would be offset in this situation by eliminating the start-towaste cycles.
Sheet 1 of 1
HDR Computation
Subject: Task: Energy Savings and Cost Analysis Prioritize Wells to Operate Most Efficient Wells First
Existing Condition: Wells have varying specific energy requirements. Proposed Change: Operate wells with the least specific energy requirements more often. Energy Savings: Energy savings were calculated based on pumping records from June through August of 2009 for the Kyte and Dickey wells. Condition Kyte Well Dickey Well Production 6/09 - 8/09 65 MG 0 MG Specific Energy 3,261 kWh/MG 1,669 kWh/MG
Savings:
Energy Savings = 1,592 kWh/MG x 65 MG = 103,480 kWh Cost Savings = $0.0605 / kW-hr x 103,480 kW-hr = $6,260 Capital Cost: Operational Change Simple Payback: = = Recommended: YES (<5 yrs) $0
Comments: Cost savings were determined based on a specific example from 2009 pumping records. This ECM is an excellent example of how a simple operational change can provide cost savings to the water system.
Sheet 1 of 1
119142
HDR Computation
Subject: Task: Energy Savings and Cost Analysis Switch Main Plant, Well Field, and Kampeska Plant to Load Control
01 Operational
Existing Condition: Generators and switch gear are in place. Proposed Change: Standby power will be used during periods of load control. Energy Savings:
Savings Main Plant Well Field Kampeska Plant Total $16,190 $6,059 $5,181 $27,430
Savings:
Minimum Control Time: Maximum Control Time: Average Control Time: Total Hours of Control: Total Control Events:
$16,190.59
Estimated Generator Operation and Maintenance: Operating Costs for Load Control
-$5,261.89
$10,928.69
Current Rate, Generator Activated for Load Control Rate Usage Demand LPG Energy Max NonDuring Total Large Power Coincident Control kWh Service With AutokW kW Usage start Generator January 2010 February 2010 March 2010 April 2010 May 2010 June 2010 July 2009 August 2009 September 2009 October 2009 November 2009 December 2009 Totals 112 110 96 102 111 109 102 87 91 93 89 109 1,212 56,189 55,622 52,638 54,911 50,740 52,414 53,967 47,912 46,939 51,116 47,963 68,347 638,758
Charges Demand Non-CoMax Incident During Control $0.00 $13.10 $0.00 $13.30 per kW per kW $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00
Energy All Energy $0.054 $0.063 per kWh $3,034.21 $3,003.59 $2,842.45 $3,459.39 $3,196.62 $3,302.08 $2,914.22 $2,587.25 $2,534.71 $2,760.26 $2,590.00 $3,690.74 $35,915.52
Demand
Energy
Itemized Detail Facility Tax Facility Charge $50.00 $50.00 $50.00 $50.00 $50.00 $50.00 $50.00 $50.00 $50.00 $50.00 $50.00 $50.00 $50.00 $50.00 $600.00 Sales Tax 4%
$/kW Total Cost per kWh (Pre Tax) $0.05489 $0.05490 $0.05495 $0.06391 $0.06399 $0.06395 $0.05493 $0.05504 $0.05507 $0.05498 $0.05504 $0.05473 $0.05717
Demand Cost
Energy Cost
$0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00
$3,034.21 $3,003.59 $2,842.45 $3,459.39 $3,196.62 $3,302.08 $2,914.22 $2,587.25 $2,534.71 $2,760.26 $2,590.00 $3,690.74 $35,915.52
$123.37 $122.14 $115.70 $140.38 $129.86 $134.08 $118.57 $105.49 $103.39 $112.41 $105.60 $149.63 $1,460.62
$3,207.57 $3,175.73 $3,008.15 $3,649.77 $3,376.48 $3,486.17 $3,082.79 $2,742.74 $2,688.09 $2,922.67 $2,745.60 $3,890.37 $37,976.14
68% 75% 74% 75% 62% 67% 71% 74% 72% 74% 75% 84% 72%
Charges Demand Non-CoIncident $13.10 $13.30 per kW $1,465.37 $1,439.04 $1,256.42 $1,360.99 $1,473.77 $1,447.71 $1,342.62 $1,144.68 $1,190.27 $1,220.53 $1,169.31 $1,429.73 $15,940.42
Energy All Energy $0.050 $0.062 per kWh $2,893.89 $2,931.08 $2,631.90 $3,404.48 $3,145.88 $3,385.34 $2,718.63 $2,538.53 $2,346.95 $2,555.80 $2,553.44 $3,645.35 $34,751.27
Demand
Energy
Itemized Detail Facility Tax Facility Charge $50.00 $50.00 $50.00 $50.00 $50.00 $50.00 $50.00 $50.00 $50.00 $50.00 $50.00 $50.00 $50.00 $50.00 $600.00 Sales Tax 4%
$/kW Total Cost per kWh (Pre Tax) $0.07618 $0.07540 $0.07482 $0.08732 $0.09159 $0.08903 $0.07561 $0.07353 $0.07642 $0.07486 $0.07388 $0.07030 $0.07802 Load Control Savings
Demand Cost
Energy Cost
January 2010 February 2010 March 2010 April 2010 May 2010 June 2010 July 2009 August 2009 September 2009 October 2009 November 2009 December 2009 Totals
57,878 58,622 52,638 54,911 50,740 54,602 54,373 50,771 46,939 51,116 51,069 72,907 656,565
$1,465.37 $1,439.04 $1,256.42 $1,340.52 $1,451.61 $1,425.94 $1,342.62 $1,144.68 $1,190.27 $1,220.53 $1,169.31 $1,429.73 $15,876.02
$2,893.89 $2,931.08 $2,631.90 $3,404.48 $3,145.88 $3,385.34 $2,718.63 $2,538.53 $2,346.95 $2,555.80 $2,553.44 $3,645.35 $34,751.27
$176.37 $176.80 $157.53 $191.80 $185.90 $194.45 $164.45 $149.33 $143.49 $153.05 $150.91 $205.00 $2,049.09
$4,585.63 $4,596.92 $4,095.85 $4,986.81 $4,833.39 $5,055.72 $4,275.70 $3,882.54 $3,730.70 $3,979.38 $3,923.66 $5,330.08 $53,276.39
$1,378.05 $1,421.19 $1,087.70 $1,337.04 $1,456.91 $1,569.56 $1,192.91 $1,139.80 $1,042.61 $1,056.71 $1,178.05 $1,439.72 $15,300.25
Current Rate, Generator Activated for Load Control Generator Size in kW: 250 Electrical Rate Gross $ Run Time Controls LPG Uncontrolled 5 Controlled 7 January 2010 February 2010 March 2010 April 2010 May 2010 June 2010 July 2009 August 2009 September 2009 October 2009 November 2009 December 2009 Totals
Generator Operating Costs Estimate of Reduced kWh Purchases from Electric Co-op Due to Load Management Maintenance Total Gen $/kWh Usage Total Maintenance Operation & Total Hours In the Year: 8760:00 Gross Generator Interval In Hours: Maintenance Estimated Average Total Hours on Central: 8537:17 Run Time Total for Price Fuel 250 Cost Average Hourly Total Hours on Generator: 222:42 Load for Load Load Per Gallon Costs Maintenance $23.63 Cost for Usage Percentage on Generator: 2.5% Control Load Control Control @ For Due To Cost In Dollars: per Hour Energy from Average Hourly Usage in kWhs: 75 Savings Control Periods Diesel Load $500.00 of Control Produced Electric Expense Reduction per kWh @: $0.050 9 $500 00 $0 050 Estimated kWhs and Expense Reduction Gallons Fuel Control Maintenance $: Total O&M $ On Site Co-op Provided By Generator Due To LM: hrs:min Per Hour per Month per Month per kWh kW $1,378.05 21:42 4 195 $2.54 $496.27 $63.63 $559.90 $0.33154 78 1,689 $84.44 $1,421.19 34:23 12 309 $2.37 $733.44 $63.63 $797.08 $0.26573 87 3,000 $149.98 $1,087.70 71 $1,337.04 76 $1,456.91 68 $1,569.56 28:51 6 260 $2.51 $651.83 $63.63 $715.46 $0.32696 76 2,188 $109.41 $1,192.91 5:33 2 50 $1.99 $99.41 $63.63 $163.04 $0.40194 73 406 $20.28 $1,139.80 41:53 6 377 $2.26 $852.08 $63.63 $915.71 $0.32032 68 2,859 $142.93 $1,042.61 65 $1,056.71 69 $1,178.05 43:47 16 394 $2.44 $961.57 $63.63 $1,025.21 $0.33009 71 3,106 $155.29 $1,439.72 46:31 15 419 $2.44 $1,021.87 $63.63 $1,085.50 $0.23805 98 4,560 $228.00 $15,300.25 222:42 61 2,004 $2.36 $4,816.47 $445.42 $5,261.89 $0.31638 75 17,807 $890.34 Fuel Price
$902.59 $774.09 $1,087.70 $1,337.04 $1,456.91 $963.51 $1,050.15 $367.03 $1,042.61 $1,056.71 $308.14 $582.21 $10,928.69
Minimum Control Time: Maximum Control Time: Average Control Time: Total Hours of Control: Total Control Events:
$5,181.47
Estimated Generator Operation and Maintenance: Operating Costs for Load Control
-$2,318.50
$2,862.98
Current Rate, Generator Activated for Load Control Rate Usage Demand LPG Energy Max NonDuring Total Large Power Coincident Control kWh Service With AutokW kW Usage start Generator January 2010 February 2010 March 2010 April 2010 May 2010 June 2010 July 2009 August 2009 September 2009 October 2009 November 2009 December 2009 Totals 36 23 36 49 28 28 28 28 36 32 28 33 385 10,821 10,089 8,434 10,177 9,641 8,861 9,403 8,201 8,437 7,643 6,133 11,866 109,706
Charges Demand Non-CoMax Incident During Control $0.00 $13.10 $0.00 $13.30 per kW per kW $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00
Energy All Energy $0.054 $0.063 per kWh $584.33 $544.81 $455.44 $641.15 $607.38 $558.24 $507.76 $442.85 $455.60 $412.72 $331.18 $640.76 $6,182.24
Demand
Energy
Itemized Detail Facility Tax Facility Charge $50.00 $50.00 $50.00 $50.00 $50.00 $50.00 $50.00 $50.00 $50.00 $50.00 $50.00 $50.00 $50.00 $50.00 $600.00 Sales Tax 4%
$/kW Total Cost per kWh (Pre Tax) $0.05862 $0.05896 $0.05993 $0.06791 $0.06819 $0.06864 $0.05932 $0.06010 $0.05993 $0.06054 $0.06215 $0.05821 $0.06182
Demand Cost
Energy Cost
$0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00
$584.33 $544.81 $455.44 $641.15 $607.38 $558.24 $507.76 $442.85 $455.60 $412.72 $331.18 $640.76 $6,182.24
$25.37 $23.79 $20.22 $27.65 $26.30 $24.33 $22.31 $19.71 $20.22 $18.51 $15.25 $27.63 $271.29
$659.71 $618.60 $525.65 $718.80 $683.68 $632.57 $580.07 $512.57 $525.82 $481.23 $396.43 $718.39 $7,053.52
40% 66% 31% 29% 47% 44% 45% 39% 33% 32% 31% 48% 40%
Charges Demand Non-CoIncident $13.10 $13.30 per kW $476.19 $296.45 $471.47 $649.44 $369.08 $371.34 $367.72 $366.93 $470.29 $424.44 $362.74 $432.30 $5,058.37
Energy All Energy $0.050 $0.062 per kWh $557.31 $531.65 $421.70 $630.97 $597.74 $572.32 $473.68 $434.52 $421.85 $382.15 $326.51 $632.88 $5,983.29
Demand
Energy
Itemized Detail Facility Tax Facility Charge $50.00 $50.00 $50.00 $50.00 $50.00 $50.00 $50.00 $50.00 $50.00 $50.00 $50.00 $50.00 $50.00 $50.00 $600.00 Sales Tax 4%
$/kW Total Cost per kWh (Pre Tax) $0.09721 $0.08258 $0.11183 $0.12977 $0.10489 $0.10704 $0.09409 $0.09798 $0.11167 $0.11208 $0.11321 $0.08810 $0.10312 Load Control Savings
Demand Cost
Energy Cost
January 2010 February 2010 March 2010 April 2010 May 2010 June 2010 July 2009 August 2009 September 2009 October 2009 November 2009 December 2009 Totals
36 23 36 49 28 28 28 28 36 32 28 33 385
11,146 10,633 8,434 10,177 9,641 9,231 9,474 8,690 8,437 7,643 6,530 12,658 112,694
$476.19 $296.45 $471.47 $639.67 $363.53 $365.75 $367.72 $366.93 $470.29 $424.44 $362.74 $432.30 $5,037.47
$557.31 $531.65 $421.70 $630.97 $597.74 $572.32 $473.68 $434.52 $421.85 $382.15 $326.51 $632.88 $5,983.29
$43.34 $35.12 $37.73 $52.83 $40.45 $39.52 $35.66 $34.06 $37.69 $34.26 $29.57 $44.61 $464.83
$1,126.84 $913.23 $980.90 $1,373.47 $1,051.72 $1,027.59 $927.06 $885.50 $979.83 $890.85 $768.82 $1,159.79 $12,085.59
$467.13 $294.63 $455.24 $654.68 $368.04 $395.02 $346.98 $372.94 $454.00 $409.62 $372.39 $441.40 $5,032.07
Current Rate, Generator Activated for Load Control Generator Size in kW: 75 Electrical Rate Gross $ Run Time Controls LPG Uncontrolled 5 Controlled 7 January 2010 February 2010 March 2010 April 2010 May 2010 June 2010 July 2009 August 2009 September 2009 October 2009 November 2009 December 2009 Totals Gross Load Control Savings
$467.13 $294.63 $455.24 $654.68 $368.04 $395.02 $346.98 $372.94 $454.00 $409.62 $372.39 $441.40 $5,032.07
Generator Operating Costs Estimate of Reduced kWh Purchases from Electric Co-op Due to Load Management Maintenance Total Gen $/kWh Usage Total Maintenance Operation & Total Hours In the Year: 8760:00 Generator Interval In Hours: Maintenance Estimated Average Total Hours on Central: 8537:17 Run Time Total for Price Fuel 250 Cost Average Hourly Total Hours on Generator: 222:42 for Load Load Per Gallon Costs Maintenance $10.41 Cost for Usage Percentage on Generator: 2.5% Load Control Control @ For Due To Cost In Dollars: per Hour Energy from Average Hourly Usage in kWhs: 13 Control Periods 3.5 Diesel Load $500.00 of Control Produced Electric Expense Reduction per kWh @: $0.050 3 5 $500 00 $0 050 Estimated kWhs and Expense Reduction Gallons Fuel Control Maintenance $: Total O&M $ On Site Co-op Provided By Generator Due To LM: hrs:min Per Hour per Month per Month per kWh kW 21:42 4 76 $2.54 $192.99 $63.63 $256.63 $0.78905 15 325 $16.26 34:23 12 120 $2.37 $285.23 $63.63 $348.86 $0.64119 16 544 $27.20 11 14 13 28:51 6 101 $2.51 $253.49 $63.63 $317.12 $0.85722 13 370 $18.50 5:33 2 19 $1.99 $38.66 $63.63 $102.29 $1.44730 13 71 $3.53 41:53 6 147 $2.26 $331.36 $63.63 $395.00 $0.80724 12 489 $24.47 12 10 43:47 16 153 $2.44 $373.95 $63.63 $437.58 $1.10183 9 397 $19.86 46:31 15 163 $2.44 $397.39 $63.63 $461.02 $0.58235 17 792 $39.58 222:42 61 779 $2.36 $1,873.07 $445.42 $2,318.50 $0.88945 13 2,988 $149.40 Fuel Price
$226.76 -$27.02 $455.24 $654.68 $368.04 $96.40 $248.23 $2.41 $454.00 $409.62 -$45.33 $19.96 $2,862.98
Minimum Control Time: Maximum Control Time: Average Control Time: Total Hours of Control: Total Control Events:
$6,059.44
Estimated Generator Operation and Maintenance: Operating Costs for Load Control
-$2,586.08
$3,473.36
Current Rate, Generator Activated for Load Control Rate Usage Demand LPG Energy Max NonDuring Total Large Power Coincident Control kWh Service With AutokW kW Usage start Generator January 2010 February 2010 March 2010 April 2010 May 2010 June 2010 July 2009 August 2009 September 2009 October 2009 November 2009 December 2009 Totals 38 38 40 36 39 32 40 39 40 40 36 37 454 15,344 14,811 15,385 16,212 16,920 12,945 18,051 14,885 17,073 14,612 15,676 17,122 189,036
Charges Demand Non-CoMax Incident During Control $0.00 $13.10 $0.00 $13.30 per kW per kW $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00
Energy All Energy $0.054 $0.063 per kWh $828.58 $799.79 $830.79 $1,021.36 $1,065.96 $815.54 $974.75 $803.79 $921.94 $789.05 $846.50 $924.59 $10,622.64
Demand
Energy
Itemized Detail Facility Tax Facility Charge $50.00 $50.00 $50.00 $50.00 $50.00 $50.00 $50.00 $50.00 $50.00 $50.00 $50.00 $50.00 $50.00 $50.00 $600.00 Sales Tax 4%
$/kW Total Cost per kWh (Pre Tax) $0.05726 $0.05738 $0.05725 $0.06608 $0.06596 $0.06686 $0.05677 $0.05736 $0.05693 $0.05742 $0.05719 $0.05692 $0.05937
Demand Cost
Energy Cost
$0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00
$828.58 $799.79 $830.79 $1,021.36 $1,065.96 $815.54 $974.75 $803.79 $921.94 $789.05 $846.50 $924.59 $10,622.64
$35.14 $33.99 $35.23 $42.85 $44.64 $34.62 $40.99 $34.15 $38.88 $33.56 $35.86 $38.98 $448.91
$913.72 $883.79 $916.02 $1,114.21 $1,160.60 $900.16 $1,065.74 $887.94 $1,010.82 $872.61 $932.36 $1,013.57 $11,671.54
54% 59% 52% 63% 59% 57% 60% 52% 59% 49% 60% 62% 57%
Charges Demand Non-CoIncident $13.10 $13.30 per kW $501.47 $491.51 $520.46 $473.88 $516.97 $423.07 $530.29 $504.48 $523.61 $520.59 $476.97 $487.19 $5,970.50
Energy All Energy $0.050 $0.062 per kWh $790.26 $780.49 $769.25 $1,005.14 $1,049.04 $836.10 $909.33 $788.66 $853.65 $730.60 $834.55 $913.22 $10,260.29
Demand
Energy
Itemized Detail Facility Tax Facility Charge $50.00 $50.00 $50.00 $50.00 $50.00 $50.00 $50.00 $50.00 $50.00 $50.00 $50.00 $50.00 $50.00 $50.00 $600.00 Sales Tax 4%
$/kW Total Cost per kWh (Pre Tax) $0.08489 $0.08469 $0.08708 $0.09387 $0.09505 $0.09661 $0.08191 $0.08515 $0.08360 $0.08905 $0.08157 $0.07941 $0.08664 Load Control Savings
Demand Cost
Energy Cost
January 2010 February 2010 March 2010 April 2010 May 2010 June 2010 July 2009 August 2009 September 2009 October 2009 November 2009 December 2009 Totals
38 38 40 36 39 32 40 39 40 40 36 37 454
15,805 15,610 15,385 16,212 16,920 13,485 18,187 15,773 17,073 14,612 16,691 18,264 194,018
$501.47 $491.51 $520.46 $466.75 $509.20 $416.71 $530.29 $504.48 $523.61 $520.59 $476.97 $487.19 $5,949.23
$790.26 $780.49 $769.25 $1,005.14 $1,049.04 $836.10 $909.33 $788.66 $853.65 $730.60 $834.55 $913.22 $10,260.29
$53.67 $52.88 $53.59 $60.88 $64.33 $52.11 $59.58 $53.73 $57.09 $52.05 $54.46 $58.02 $672.38
$1,395.40 $1,374.88 $1,393.30 $1,582.77 $1,672.57 $1,354.92 $1,549.21 $1,396.86 $1,484.35 $1,353.24 $1,415.99 $1,508.42 $17,481.90
$481.68 $491.09 $477.28 $468.56 $511.97 $454.76 $483.46 $508.92 $473.53 $480.63 $483.62 $494.85 $5,810.36
Current Rate, Generator Activated for Load Control Generator Size in kW: 100 Electrical Rate Gross $ Run Time Controls LPG Uncontrolled 5 Controlled 7 January 2010 February 2010 March 2010 April 2010 May 2010 June 2010 July 2009 August 2009 September 2009 October 2009 November 2009 December 2009 Totals Gross Load Control Savings
$481.68 $491.09 $477.28 $468.56 $511.97 $454.76 $483.46 $508.92 $473.53 $480.63 $483.62 $494.85 $5,810.36
Generator Operating Costs Estimate of Reduced kWh Purchases from Electric Co-op Due to Load Management Maintenance Total Gen $/kWh Usage Total Maintenance Operation & Total Hours In the Year: 8760:00 Generator Interval In Hours: Maintenance Estimated Average Total Hours on Central: 8537:17 Run Time Total for Price Fuel 250 Cost Average Hourly Total Hours on Generator: 222:42 for Load Load Per Gallon Costs Maintenance $11.61 Cost for Usage Percentage on Generator: 2.5% Load Control Control @ For Due To Cost In Dollars: per Hour Energy from Average Hourly Usage in kWhs: 22 Control Periods 4.0 Diesel Load $500.00 of Control Produced Electric Expense Reduction per kWh @: $0.050 4 0 $500 00 $0 050 Estimated kWhs and Expense Reduction Gallons Fuel Control Maintenance $: Total O&M $ On Site Co-op Provided By Generator Due To LM: hrs:min Per Hour per Month per Month per kWh kW 21:42 4 87 $2.54 $220.57 $63.63 $284.20 $0.61624 21 461 $23.06 34:23 12 138 $2.37 $325.98 $63.63 $389.61 $0.48778 23 799 $39.94 21 23 23 28:51 6 115 $2.51 $289.70 $63.63 $353.33 $0.65379 19 540 $27.02 5:33 2 22 $1.99 $44.18 $63.63 $107.81 $0.79462 24 136 $6.78 41:53 6 168 $2.26 $378.70 $63.63 $442.33 $0.49805 21 888 $44.41 24 20 43:47 16 175 $2.44 $427.37 $63.63 $491.00 $0.48370 23 1,015 $50.75 46:31 15 186 $2.44 $454.16 $63.63 $517.79 $0.45328 25 1,142 $57.12 222:42 61 891 $2.36 $2,140.65 $445.42 $2,586.08 $0.56964 22 4,982 $249.08 Fuel Price
$220.54 $141.42 $477.28 $468.56 $511.97 $128.45 $382.43 $110.99 $473.53 $480.63 $43.38 $34.17 $3,473.36
Sheet 1 of 1
HDR Computation
Subject: Task: Energy Savings and Cost Analysis Install Varible Frequency Drives on Hanna Pump Motors
Physical
Proposed Change: Install a VFD on pump motors. Energy Savings: Cost savings will be realized by gaining the ability to operate motors at reduced speeds. Reduced speed operation would reduce energy and demand charges. Energy savings calculated using Fuji Electric Energy Savings Estimator.
Savings:
kW-hr / yr = 62,376 - 34,470 = 27,906 kW-hr / yr $ / yr = $0.0605 / kW-hr x 27,906 kW-hr / yr = $1,688 / yr
Simple Payback:
Recommended:
Comments: Reduced energy charges do not provide the necessary savings for a payoff of 5 years. Additional savings would likely be realized by reducing capacity charges. We recommend considering this ECM. In addition to energy and capacity savings, a VFD would provide increased operational flexibility. Fuji Electric savings report is attached.
Sheet 1 of 2
HDR Computation
Subject: Task: Energy Savings and Cost Analysis Evaluate Energy Use at Hanna Pump Station
Existing Condition: Substantial energy use year round. Pumps are operated during summer months only. Proposed Change: To be determined. Energy Savings: We assumed energy use could be reduced to 1,000 kWh per month during off peak months. Also assumed is that capacity charges could be reduced during off peak months. Recent Hanna pump station data is provided below. Month Jan-09 Feb-09 Mar-09 Apr-09 May-09 Jun-09 Jul-09 Aug-09 Sep-09 Oct-09 Nov-09 Dec-08 Total Energy kWh 7,200 6,000 6,000 6,300 6,300 , 6,600 7,800 55,500 21,600 600 6,300 5,400 135,600 Energy $ 383.42 322.10 322.10 337.43 337.43 352.76 414.08 2,836.05 1,103.76 306.60 321.93 291.44 7,329 Capacity kW 12.0 12.0 12.0 12.0 12.0 93.0 90.0 96.2 94.6 26.0 159.0 12.0 Capacity $ 83.84 89.70 91.43 97.29 95.57 725.11 667.78 369.41 363.26 99.84 548.55 89.36 3,321 Cost Adj $ 3.52 2.94 12.57 20.79 20.79 21.78 25.73 198.66 86.78 35.30 36.29 2.65 468 Total Cost $ 470.78 414.74 426.10 455.51 453.79 , 1,099.65 1,107.59 3,404.12 1,553.80 441.74 906.77 383.45 11,118
Sheet 1 of 1
HDR Computation
Subject: Task: Energy Savings and Cost Analysis Eliminate Grand Avenue Booster Station (Lead)
Existing Condition: Grand Avenue Booster Station is used to fill the 75,000 gallon Peak Street Reservoir. Proposed Change: Modify distribution system to fill the Peak Street Reservoir from a nearby main that is fed from a higher pressure zone. Energy Savings:
The Grand Avenue Booster Station can be eliminated. Energy: Current Energy Use
Yearly Energy Use = 24,624 kW-hr / yr Cost: Current Energy Cost Yearly Energy Cost = $3,372 / yr
Savings:
$ / yr = $3,372 - (12,312 x $0.0605) = $2,627 / yr Capital Cost: Altitude valve and minor distribution changes Simple Payback: $10,000 = $10,000 / $2,627 = Recommended: YES (<5 yrs) 3.8
Comments: Eliminating the Grand Avenue Booster Station is recommended. Additional costs will be associated with demolishion of the building. However these costs should be more than offset by a reduction in operation and maintenance costs.
Sheet 1 of 9
119142
HDR Computation
Subject: Task: Energy Savings and Cost Analysis Decommission Country Club Booster
01 Physical
Existing Condition: Booster is no longer used. Area is now served by Redwood Booster. Proposed Change: Decommission Country Club Booster so heating and electrical service are no longer needed. Energy Savings: Energy will be saved due to elimination of heating and lighting and service charges will also be eliminated. Annual kWhr savings is estimated to be 6,258.
Expenses $0 $0
Savings:
Capital Cost: None Simple Payback: $1,500 = Annual Savings/Capital Cost = $1,263/$1,500 = Recommended: Comments: YES (< 5 yrs) 1.2 years
Sheet 3 of 9
119142
HDR Computation
Subject: Task: Energy Savings and Cost Analysis Set Maximum Pump Speed on Well 3 to Limit kW Demand to < 75 kW
03 Operational
Existing Condition: Well 3 is used only when treated water from the WTP cannot maintain the water level in the elevated storage at a specific set point. This is not conveyed to or treated at the plant. Its use imparts significant costs on a per gallon basis when used. Proposed Change: Set existing VFD such that the demand does not exceed 75 kW. If 75 kW is reached at any time in a 12 month period, it places the facility into the Large Power rate category, subject to demand charges and a higher facility charge. The maximum experienced when pumping full speed has been 77 kW. Only a slight speed reduction will be required to keep this below 75 kW. Energy Savings: There will be no power savings based on kW-hrs used, but the electrical bills will be reduced due to elimination of demand charges and a reduced facility charge. The kW-hr rate would be higher but the additional energy charges are much lower than the savings for demand and facility charges.
Savings g Facility Charge Demand Charge Power Total $440 $2,180 $0 $2,620
Savings:
NA NA
Recommended:
YES
(< 5 yrs)
Comments: This is recommended over ECM 02 since it saves additional money on the net power bill and allows Well 3 to stay in service.
Sheet 1 of 1
HDR Computation
Subject: Task: Energy Savings and Cost Analysis Repair Compressed Air System
Existing Condition: Compressed air piping leaks causing the compressors to run nearly nonstop. Proposed Change: Repair leaks in order to reduce compressor run time. Energy Savings:
Energy: Energy Lost = power loss due to leak x annual time leak occurs x conversion factor = 0.35 x 15 hp x 8,760 hr/year x 0.7457 kW/hp = 34,295 kWh / year Savings: Energy = 34,295 kWh/yr x $0.075/kWh = $2,572 Capital Cost: Repair Air Line Simple Payback: $2,500 = $2,500 / $2,572 = 1.0 years Recommended: YES (< 5 yrs)
Sheet 1 of 1
HDR Computation
Subject: Task: Energy Savings and Cost Analysis Limit Use of UV Disinfection
Operational
Existing Condition: UV disinfection will be used in conjunction with chlorine disinfection. Proposed Change: Do not operate UV system unless adequate chlorine contact time is not being provided. Energy Savings:
Energy savings is realized by reducing the amount of energy required for disinfection.
Condition Size
UV System 10 kW system
Energy:
Existing Condition
Energy Consumption = UV demand x % of capacity x hours of operation x annual run time = 10 kW x 50% x 8,760 hours/year x 0.5 = 21,900 kWh/year
Cost Savings = energy use * energy charge = 21,900 kWh * $0.075/kWh = $1,643 Capital Cost: None Simple Payback: $0 = NA = NA Recommended: YES (< 5 yrs)
Comments: This ECM illustrates the energy savings of operating the UV system half of the year compared to year round. The UV system should be programmed to operate only when the plant output exceeds the flow rate for which adequate CT time can be provided.
Sheet 1 of 1
HDR Computation
Subject: Task: Energy Savings and Cost Analysis Replumb Air Burst Piping at Inlet
Existing Condition: Air burst piping is plumbed above ground at the inlet structure. Air line enters into Rapid Creek and freezes during winter months. Electric heat elements are used to keep the inlet functioning. Proposed Change: Replumb the air line to enter the inlet structure below grade. This will prevent icing at the water surface. Energy Savings:
Cost savings are realized by eliminating the need for the element style heaters.
Energy:
Existing Condition Energy Cost = energy use * energy charge = 18,000 kWh * $0.065/kWh = $1,170 Increased Compressor Run Time kW-hr / air burst = 5 Hp x 0.7457 kW/Hp x 0.08 hr = 0.311 kWh / year = 0.311 kWh x 6 air burst / hour x 732 hours / month x 4 months / year = 5,460 Energy Cost = 5,460 kWh x $0.065/kWh = $355
Savings:
Capital Cost: Replumb Air Line Simple Payback: $2,500 = $2,500 / $815 = 3.1 years Recommended: Comments: YES (< 5 yrs)
Sheet 1 of 1
HDR Computation
Subject: Task: Energy Savings and Cost Analysis Insulate CIP hot water tank
Physical
Existing Condition: Hot water for CIP cylce is stored in a tank. The tank is not insulated and is placed directly on the concrete floor. Proposed Change: Insulate tank and place on a layer of rigid insulation. Energy Savings:
Energy savings are realized be reducing the volume of water that must be reheated.
Energy:
Existing Condition Energy Savings = energy use * energy charge = 350 therms * $0.7034 / therm = $246
Capital Cost: Insulate Tank Simple Payback: $1,000 = $1,000 / $246 = 4.0 years Recommended: YES (< 5 yrs)
Comments: Annual reduction in natural gas consumption was estimated based increasing the R value of the tank.
Sheet 1 of 1
HDR Computation
Subject: Task: Energy Savings and Cost Analysis Install Occupancy Sensors
Physical
Existing Condition: Occupancy sensors are not currently used to turn off lights. Proposed Change: Install occupancy sensors so that lights are automatically shut off if a room is empty. Energy Savings:
Savings:
Capital Cost: Occupancy Sensors Simple Payback: $500 = $500 / $130 = 3.8 years Recommended: YES (< 5 yrs)
Comments: Energy savings were estimated. Actual energy savings will depend on the number of light fixtures controlled by occupancy sensors, energy used by lighting, and reduction of time lights are on.
WaterSystemEnergyAuditApproachChecklist Determinetypeofaudit Pumping,HVAC,lighting,and/orprocess Determineauditteammembers,everyonewillhavedifferentgoals Engineersreduceenergycost Plantstaffreducedisruptiontosystem Electricutilityreducepeakdemand Collectdata Powerbillsgetactualbillsthatshowenergyuse,demandcharges,costadjustments,etc Electricrateschedulesgetcurrentrateschedules Alternativerateschedulesarealternateratesavailablethatwillbenefitthewatersystem? Flowdataincludeboosterstations, pumps, ,wells, ,high g servicep p ,anything y gwithaflowmeter Meterdatasoldvsproduced,bulkpurchasesorsales,waterlossdata Pumpcurvescollectpumpcurvestoverifypumpsareoperatingneartheirdesignpoint Processflowdiagrams,designsummaryusefultohelpunderstandoperationofthesystem Waterqualitystandardsanyuniqueprocessesrequired? Previousauditfindingshaveenergyauditsbeenperformedinthepast? Systempressureoperatingpressureswithdistributionsystem Press rezones Pressure onesho howaredifferentzones onesoperated operated,ho howiswater atermo moved edaro around ndthes system? stem? PRVsamountofheadremoved,numberinthesystem,anywaytolimitwastinghead? Reservoirsstoragecapacity,elevation,headrange Compressedairsystemshorsepower,receivertanksize,devicesconsumingcompressedair HVACefficiencyandperformanceofexistingequipment GasbillsHVACaudit Lighting efficiencyandperformanceofexistinglights ConductSiteVisit Meetwithstaffandoperators Q&Asessiondiscussoperations,gainunderstandingofhowsystemisoperated Seekinputfromoperatorsandthosefamiliarwiththesytem Walkthroughtourfacilities,moreQ&A Ob i anymissing Obtain i i info, i f check h kmotorsizes, i observe b valve l positions ii Focusonbigpowerconsumers,theywillofferbestpaybackopportunity Rawwaterpumping,wells,HSP,aircompressorstypicallylargestpowerconsumers Seekenergyefficiencyideasfromplantstaff DevelopEnergyConservationMeasures Estimateenergyorcostsavings Determinecapitalcost Consideroperationalimpactstotheplant Lookforrebatesorincentives