BAY CONTROL UNIT

GBU100

GBU100
BAY CONTROL UNIT

FEATURES
Application
For control and monitoring of switchgear, transformers and other equipment or devices in EHV, HV, MV and LV substations Applicable to single, double and one- and a half breaker arrangements and to both GIS and AIS switchgear

Communication
Data Data

communication for station bus IEC 61850 communication for local setting and testing facility over RSM system

Redundancy
Redundant

DC/DC converter for reliable DC supply (option)

Functionality
Built-in

protection features (model 700) Synch. check and dead-line check function for single- or multi-breaker arrangements Analog measurement accuracy up to 0.5% for power, current and voltage Power quality measurement and monitoring Integrated disturbance and event recorder (model 700) Time synchronization over IEC 61850 Test mode for convenience of database maintenance and testing Self-supervision Parameters with password protection

Security
Password

protection

Flexibility
Various models and hardware options for exible application depending on system requirement and controlled object Programmable control, trip and alarm logic

Human Machine Interface


Graphical Single

LCD and LEDs for local human-machine interface line diagram indication and touch-type operation on LCD

GBU 100

BAY CONTROL UNIT

FUNCTIONS
Control
Circuit

HMI function
Graphic Status

breaker and disconnector control Switchgear interlock check Transformer tap change control Synchronism voltage check Programmable automatic sequence control

LCD with display of single line diagram and alarm LEDs Touch type screen for control and setting

Recording
Event

Monitoring
and condition monitoring of primary apparatus operation monitoring Plausibility check Measurement of I, V, P, Q, PF, f, Wh and varh Measurement and supervision of individual and total harmonic up to 15 th, sag, swell, interruption (option) DC analog input (Transducer input) Current and voltage circuit supervision
Switchgear Status

record with 1ms resolution record (model 700) Fault record (model 700)
Disturbance

Communication
IEC RSM

61850 Station bus local PC access

General functions
Self

Protection (for Model 700s)


Directional Directional

or non-directional overcurrent protection or non-directional earth fault protection Sensitive directional or non-directional earth fault protection Thermal overload protection Under- and over-voltage protection Under- and over-frequency protection

supervision synchronization 4 setting group (model 700) Test mode Password protection for settings and selection of local / remote control
Time

APPLICATIONS
GBU100 is used for the control, protection and monitoring of bay/feeder equipment in electrical substations. It is applicable to all types of busbar and switchgear arrangement in both GIS and AIS type substations. It is suitable for use in the highest voltage level substations in which very high reliability is required, but can also be applied for industrial substation and automation systems due to its exible settings and functionality. Control is performed remotely through the communication bus or locally from a graphical HMI on the front panel showing the single line diagram for the bay. GBU100 can be applied in a standard conguration of one unit per bay, or alternatively one unit can be applied as a common device for several bays. GBU100 has three models as shown in Table -1. GBU100 is connected to the station bus through Ethernet Switch devices in GBU100-700 provides protection features to be applied for MV and LV systems in which built-in protection features are required in the bay control unit. GBU100-800 provides bay control and monitoring functions for EHV and HV systems or MV/LV systems where the protection function is separated from the bay control functions. the same manner as protection relays and other bay level devices. GBU100 performs control and monitoring of the bay in accordance with commands or operation from the station level. An Ethernet LAN, 100BASE-TX/FX, is used for the Station Bus to interface station level equipment with GBU100 and other IEDs. IEC 61850 is applied for communication between the Station Computer (Server) and GBU100. GBU100-900 provides expanded binary inputs and/or transducer inputs/ outputs. It is applicable to bay or primary apparatus for which a large number of binary inputs or transducer inputs are required for monitoring and supervision.

Integration into GSC1000


GBU100 bay control unit is an integral component of the Substation Automation System Type GSC1000. A typical system conguration for GSC1000 is shown in Figure 1.

Table - 1 GBU100 Models and Features


Models Function Control functions - CB/DS/ES control - Transformer tap control - Synchronism check - CB/DS/ES status condition - CB contact wear - CB/DS/ES operation time - Analogue input supervision - Self supervision Model 700 4 4 10 78 10 2 5 1/2 x 19 GBU100 Model 800 4 7 10 117 10 5 1/2 x 19 Model 900 4 7 30 156 10 5 3/4 x 19

Monitoring functions

Protection functions HMI functions Recording functions Max. CT input Max. VT input Max. Analog DC input Max. Binary input Max. Binary output Case size - For control - For trip - For signal - Event record - Fault & Disturbance record

Remote Control Centre Remote Monitoring


Station Computer

IEC60870-5-101 or IEC60870-5-104

Operator Workstation GPS Receiver

Engineering Workstation

GSU100
Hard Copy Printer
On demand printing
Station Computer

GSU100
Station Computer
100BASE-TX Note; BCU: Bay Control Unit ESW: Ethernet Switch IFU: Interface Unit

ESW

ESW

IEC61850, Ring LAN, 100BASE-FX


ESW ESW ESW ESW

Relay IFU

Relay IFU

Relay IFU

BAY CONTROL UNIT

BAY CONTROL UNIT

BAY CONTROL UNIT

GBU100

GBU100

GBU100
Relay Relay Protection Relay Panels Relay

GIS Local Control Panels

Figure 1 - Typical System Conguration for Substation Automation System GSC1000

GBU 100

BAY CONTROL UNIT

FUNCTIONS

CONTROL
Switchgear Control
GBU100 provides functions for local control of switchgear from the HMI. Three-stepped operation (select-control-execute) is applied for the control of circuit breakers, disconnectors and earthing switches within a bay. Also, switchgear control commands from the station level can be performed through GBU100 within the application of a Substation Automation System.

Split synchronism check


In case the circuit breaker closing command is received during an asynchronous network condition where frequencies are different between the line and bus sides, the split synchronism check mode automatically functions by detecting angle differences, instead of normal synchronism check mode.

Interlock check
The interlocking function blocks the operation of primary switching devices, for instance when a disconnector is under load, in order to prevent material damage and/or accidental human injury. Each switchgear control function has interlocking modules included for different switchyard arrangements, where each function handles interlocking for one bay. The interlocking function is distributed to each IED and is not dependent on any central function. For station-level interlocking scheme, GBU100 communicates via the station bus or by hard-wiring. The interlocking conditions depend on the circuit configuration and apparatus position status at any given time. For easy and safe implementation of the interlocking function, standard software interlocking logic is provided in GBU100. The interlocking logic and conditions can be modied to satisfy the specic requirements by means of the graphical conguration tool.

Characteristics of synchronism check


The synchronism check scheme is shown in Figure 2. The function includes a built-in voltage selection scheme for double bus and one- and a half or ring busbar arrangements.
Incoming voltage(V2) V Running voltage(V1) Synchronism check area

(a) Synchronism check zone


V2 ncoming voltage Vov

Synchronism and voltage check


When the circuit breaker closing selection command is received, the integrated synchronism and voltage check function is performed to check feeder synchronisation.

Vuv

C
0V Vuv Vov

V1 Running voltage

A, C, D: Voltage check

B: Synchronism check

(b) Voltage and synchronism check zone

Figure2 - Synchronism check characteristic

MONITORING
Status Monitoring
The open or closed status of each switchgear device and failure information concerning power apparatus and control equipment are monitored in GBU100. Both normally open and normally closed contacts are used to monitor the switchgear status. If an unusual status is detected, a switchgear abnormality alarm is generated.

Measuring
On the local HMI, the following on-line information is provided; Measured analog voltages, currents, frequency, active- and reactivepower Logical values of all binary inputs

The accuracy of analog measurement is 0.5% for I, V, P, Q at rated input and 0.03Hz for frequency measurement. In addition, energy values (Watt-hour, var-hour) are calculated and data storage is guaranteed for 24 hours if the DC power supply is interrupted. The accuracy of energy calculation is 1.0%.

Power Quality Measurement


GBU100 provides power quality measurement features for the supervision of power system values.
Individual Total

DC analog inputs
The DC analog inputs provide monitoring and supervision of measurement and process signals from measuring transducers. Many monitoring devices 2nd 15th used in substation apparatus represent various parameters such as temperature, gas pressure of GIS and DC battery voltage as low current values. This transducer inputs are also monitored on the local LCD or Substation Automation System. The status and failure data provided by these monitoring functions are transmitted to the station level control equipment.

harmonic distortion from to Harmonic Distortion (THD) and Total Demand Distortion (TDD) from 2nd to 15th Sag, Swell and Interruption

PROTECTION (model 700 only)


Directional or non-directional phase overcurrent protection (DOC/OC)
Three-phase overcurrent function has definite time or inverse time characteristics in which all IEC, ANSI and user-dened characteristics are available. The function can be set to be directional or non-directional.

Thermal overload protection (THM)


The thermal overload feature provides protection for cables and other plant against the effects of prolonged operation under excess load conditions. A thermal replica algorithm is applied to create a model for the thermal characteristics of the protected plant. Tripping times depend not only on the level of overload current, but also on the level of prior load current, the thermal replica providing memory of previous conditions.

Directional or non-directional earth fault protection (DEF/EF)


Earth fault protection has definite time or inverse time characteristics in which all IEC, ANSI and optional user-dened characteristics are available. The function can be set to be directional or non-directional independently.

Under and over voltage protection (UV/OV)


Both undervoltage and overvoltage protection schemes are provided. Each scheme can be programmed with denite or inverse time delay.

Frequency protection (FRQ) Sensitive directional or non-directional earth fault protection (DSEF/SEF)
This function provides earth fault protection with more sensitive settings for use in applications where the fault current magnitude may be very low. The sensitive earth fault quantity is measured directly, using a dedicated core balance earth fault CT. The function can be set to be directional or non-directional independently. 6 independent frequency stages are provided. Each is programmable for either under-frequency or over-frequency operation, and each has an associated DTL timer. The underfrequency function can be applied to implement load-shedding schemes.

HMI FUNCTION
The local human machine interface includes an LCD which can display the single line diagram for the bay. The local human machine interface is simple and easy to understand with the following facilities and indications.

Alarm indication LEDs with user printable card. Touch type screen for control and navigation purposes, switch for selection between local and remote control and reset.

Status indication LEDs (IN SERVICE, ALARM, TRIP, TEST, LAN CONN. FAIL, TIME SYNC. FAIL)

GBU 100

BAY CONTROL UNIT

LCD with key switch (option)


The function for local control from the LCD can be locked by the optional key switch.

Local PC Connection using RSM100


The user can communicate with GBU100 from a local PC via the RS232C port on the front panel. Using RSM100 software, the user can view and change settings and monitor real-time measuring. The following data can be viewed or analysed on the local PC with RSM100 software.
Setting Measuring

Figure 3 - HMI Panel

Event

record Fault & Disturbance Record

RECORDING
Event records
Continuous event-logging is useful for monitoring of the system from an overview perspective and is a complement to specic disturbance recorder functions. Up to 1,024 time-tagged events are stored with 1ms resolution.

Disturbance records (model 700 only)


The Disturbance Recorder function supplies fast, complete and reliable information for disturbances in the power system. It facilitates understanding of system behavior and performance of related primary and secondary equipment during and after a disturbance. The Disturbance Recorder acquires sampled data from all selected analogue input and binary signals. These records are available on the HMI and/or at a local PC using RSM100.

Fault records (model 700 only)


Information about the pre-fault and fault values for currents and voltages are recorded and displayed for trip event conrmation. The most recent 8 time-tagged faults with 1ms resolution are stored.

COMMUNICATION
Station bus, IEC 61850 communication protocol
An Ethernet port for the substation communication standard IEC 61850 is provided for the station bus.

GENERAL FUNCTION
Self supervision
Automatic self-supervision of internal circuits and software is provided. In the event of a failure being detected, the ALARM LED on the front panel is illuminated, the UNIT FAILURE binary output operates, and the date and time of the failure is recorded in the event record.

Password protection
Password protection is available for the execution of setting changes, clearing records and switching of local/remote control.

Operation mode
GBU100 provides on-line mode and test mode. On-line mode is for normal operation. Test mode is selected to perform system testing after database modication in the case of bay extension. By means of test mode operation, bay-wise testing can be performed without disturbing other bays which are in-service (on-line mode).

Time synchronisation
Current time can be provided with time synchronisation via station bus by SNTP (Simple Network Time Protocol).

Setting groups (model 700 only)


4 settings groups are provided, allowing the user to set one group for normal conditions, while the other groups may be set to cover alternative operating conditions.

TOOLS & ACCESSORY

REMOTE SETTING AND MONITORING


The PC interface RSM100 allows users to access GBU100 and other Toshiba GR-series relays from a local personal computer (PC) to view online or stored data, and to change settings. RSM100 also supports functions to view and analyze fault and disturbance records stored in GBU100 (for model 700). Waveform data in the disturbance records can be displayed, edited, measured and analyzed in detail.

Figure 4 - PC Display of RSM100

LCD CONFIGURATION
The user can configure and customize the MIMIC data displayed on the LCD of GBU100 using LCD editor tool software.

PROGRAMMABLE LOGIC EDITOR


The programmable logic capability allows the user to configure flexible logic for customized application and operation. The logic can be prepared by graphical PC tool and allows special applications such as automatic disconnection of a feeder from a busbar, automatic busbar changeover and automatic Close/Open of a bus coupler/section.

Figure 5 - PC Display of SLD conguration

Figure - 6 PC display of PLC editor

GBU 100

BAY CONTROL UNIT

TECHNICAL DATA
HARDWARE
Analog Inputs Rated current In Rated voltage Vn Rated Frequency Current inputs Voitage inputs Phase current inputs Burden Earth current inputs Sensitive earth fault inputs Voltage inputs Measurement range Transducer inputs Power Supply Rated auxiliary voltage Superimposed AC ripple on DC supply Supply interruption Power consumption (GBU100-741) Binary Inputs Input circuit DC voltage Pick-up voltage Maximum permitted voltage Minimum impulse duration Power consumption Binary Outputs Switching capacity for trip and command relay Make and carry: 4A continuously Make and carry: 20A, 220Vdc for 0.5s (L/R5ms) Break: 0.1A, 220Vdc or 0.2A, 110Vdc (L/R=40ms) Make and carry: 4A continuously Make and carry: 10A, 220Vdc for 0.2s (L/R5ms) Break: 0.1A, 220Vdc (L/R=40ms) 12ms 8ms Flush mounting Approx. 10kg (Model 700s & 800s), 15kg (Model 900s) 2.5Y7.5/1 (approximation to Munsell value) 110/125Vdc, 220/250Vdc Typical 74Vdc (min. 70Vdc) for 110/125V rating Typical 138Vdc (min. 125Vdc) for 220/250V rating 150Vdc for 110/125V rating, 300Vdc for 220/250V rating 40ms 0.5W per input at 110Vdc 110/125Vdc (Operative range: 88 150Vdc), 220/250Vdc (Operative range: 176 300Vdc) 12% 50ms at 110V 20W (quiescent) 30W (maximum) Maximum permitted continuous current Input resistance 1A or 5A 100V to 120V 50Hz or 60Hz 3 times rated current continuous 3 times rated current continuous 100 times rated current for 1 second (for model 700s) 2 times rated voltage continuous 0.1VA at In = 1A, 0.3VA at In = 5A 0.3VA at In = 1A, 0.4VA at In = 5A 0.3VA at In = 1A, 0.4VA at In = 5A 0.1VA 4 20mA, 1mA 2 times for maximum measurement range 150(4 20mA), 3000(1mA )

Overload Rating

Switching capacity for signal output Maximum operating time Maximum break time Mechanical Design Installation Weight Case colour

HARDWARE
LED Number IN SERVICE (Green) ALARM, TRIP, SPARE (Red) TEST (Yellow) LAN CONN. FAIL (Yellow) TIME SYNC. FAIL (Yellow) SPARE (Yellow) 1Serial Interface for RSM100 Local RS232 (RSM) Connection Maximum length Cable type Station Bus Interface for IEC61850 100BASE-TX Physical medium 100BASE-FX Physical medium Terminal Block CT/VT input M3.5 Ring terminal Direct cable connection : AWG26 to AWG12 or 0.14 - 2.5 mm2 recommended. Cable ferrule : H2.5/18D from Weidmuller is recommended for AWG14 or cross-section 2.5mm2. stripping length is 14mm. H1.5/16 from Weidmuller is recommended for AWG16 or cross-section 1.5mm2. stripping length is 12mm. Fast Ethernet Twisted pair cable, RJ-45 connector Fast Ethernet 50/125 or 62.5/125m bre, SC connector 9-way D-type female Point to point 15m (max.) Multi-core (straight) 12 1 1 each 1 1 1 5

Binary input, Binary output

GBU 100

BAY CONTROL UNIT

FUNCTIONIONAL DATA
Synchronism Check Function Synchronism check angle: Frequency difference check: Voltage difference check: Voltage dead check: Voltage live check: Metering Function Current Voltage Power (P, Q) Energy (Wh, varh) Frequency Power Quality Measurement Current harmonic distortion (up to 15th) Voltage harmonic distortion (up to 15th) GPS Time Synchronisation Protocol SNTP 1.0% In, if Im < 10% In ; 10 % Im, if Im>10% In 0.3% Un, if Um<3 % In ; 10 % Um, if Um>3% Un Accuracy 0.5% (at rating) Accuracy 0.5% (at rating) Accuracy 0.5% (at rating) Accuracy 1.0% (at rating) Accuracy 0.03Hz 5 75 in 1 steps 0.01 0.50Hz in 0.01Hz steps 1.0 60.0V in 0.1V steps 5 50V in 1V steps 10 100V in 1V steps

PROTECTION RELAY (Model 700)


Directional Phase Overcurrent Protection (Model 700) Overcurrent threshold: Delay type: IDMTL Time Multiplier Setting TMS: DTL delay: Reset Type: Reset Denite Delay: Reset Time Multiplier Setting RTMS: DOC Characteristic Angle: Directional Earth Fault Protection (Model 700) Overcurrent threshold: Delay type: IDMTL Time Multiplier Setting TMS: DTL delay: Reset Type: Reset Denite Delay: Reset Time Multiplier Setting RTMS: DEF Characteristic angle: DEF Voltage threshold: Directional Sensitive Earth Fault Protection (Model 700) Overcurrent threshold: Delay Type: IDMTL Time Multiplier Setting TMS: OFF, 0.002 0.200A in 0.001A steps (1A rating) OFF, 0.01 1.00A in 0.01A steps (5A rating) DT, IEC NI, IEC VI, IEC EI, IEC LTI, IEEE MI, IEEE VI, IEEE EI, US CO8 I, US CO2 STI 0.010 1.500 in 0.001 steps OFF, 0.02 5.00A in 0.01A steps (1A rating) OFF, 0.1 25.0A in 0.1A steps (5A rating) DT, IEC NI, IEC VI, IEC EI, IEC LTI, IEEE MI, IEEE VI, IEEE EI, US CO8 I, US CO2 STI 0.010 1.500 in 0.001 steps Inst, 0.01 300.00s in 0.01s steps Denite Time or Dependent Time. Instantaneous, 0.1 300.0s in 0.1s steps 0.010 1.500 in 0.001 steps 95 to +95 in 1 steps 0.5 100.0V in 0.1V steps OFF, 0.02 5.00A in 0.01A steps (1A rating) OFF, 0.1 25.0A in 0.1A steps (5A rating) DT, IEC NI, IEC VI, IEC EI, IEC LTI, IEEE MI, IEEE VI, IEEE EI, US CO8 I, US CO2 STI 0.010 1.500 in 0.001 steps Inst, 0.01 300.00s in 0.01s steps Denite Time or Dependent Time. Instantaneous, 0.1 300.0s in 0.1s steps 0.010 1.500 in 0.001 steps 95 to +95 in 1 steps

10

PROTECTION RELAY (Model 700)


Directional Sensitive Earth Fault Protection (Model 700) DTL delay: Reset Type: Reset Denite Delay: Reset Time Multiplier Setting RTMS: DSEF Characteristic angle: DSEF Boundary of operation: DSEF Voltage threshold: Residual power threshold: Overvoltage Protection (Model 700) 1st and 2nd overvoltage (OV) thresholds: 1st OV delay type: 1st OV IDMTL Time Multiplier Setting TMS: 1st and 2nd OV DTL delay: DO/PU ratio: 1st OV Reset Delay: Undervoltage Protection (Model 700) 1st and 2nd Undervoltage (UV) thresholds: 1st UV delay type (1st threshold only): 1st UV IDMTL Time Multiplier Setting TMS: 1st and 2nd UV DTL delay: 1st UV Reset Delay: Under/Over Frequency Protection (Model 700) 1st - 4th under/over frequency threshold: DTL delay: Undervoltage block: Thermal Overload Protection (Model 700) I = k.I FLC (Thermal setting): Pre-load current setting: Time constant (): Thermal alarm: Accuracy IDMTL Overcurrent Pick-up: All Other Overcurrent Pick-ups: Overcurrent PU/DO ratio: Undercurrent Pick-up: Undercurrent PU/DO ratio: IDMTL Overvoltage Pick-up: All Other Overvoltage Pick-ups: Inverse Time Delays: Denite Time Delays: Transient Overreach for instant. elements: Setting value 5% Setting value 5% 95% Setting value 5% 105% Setting value 2% Setting value 2% 5% or 30ms (1.5 to 30 times setting) 1% (for more than 1s setting) or 10ms < 5% for X/R = 100. OFF, 0.20 2.00A in 0.01A steps (1A rating) OFF, 0.1 10.0A in 0.1A steps (5A rating) 0.00 1.00A in 0.01A steps (1A rating) 0.0 5.0A in 0.1A steps (5A rating) 0.5 - 300.0 mins in 0.1min steps OFF, 50% to 99% in 1% steps -10.00 +10.00Hz in 0.01Hz steps Inst, 0.01 300.00s in 0.01s steps 40.0 100.0V in 0.1V steps OFF, 5.0 130.0V in 0.1V steps DTL, IDMTL 0.05 100.00 in 0.01 steps Inst, 0.01 300.00s in 0.01s steps Instantaneous, 0.1 300.0s in 0.1s steps Inst, 0.01 300.00s in 0.01s steps Denite Time or Dependent Time Instantaneous, 0.1 300.0s in 0.1s steps 0.010 1.500 in 0.001 steps 95 to +95 in 1 steps 87.5 0.5 100.0V in 0.1V steps OFF, 0.00 20.00W in 0.05W (1A rating) OFF, 0.00 100.00W in 0.25W (5A rating) OFF, 10.0 200.0V in 0.1V steps DTL, IDMTL 0.05 100.00 in 0.01 steps Inst, 0.01 300.00s in 0.01s steps 10 98% in 1% steps Instantaneous, 0.1 300.0s in 0.1s steps

11

GBU 100

BAY CONTROL UNIT

ENVIRONMENTAL PERFORMANCE
Test Atmospheric Environment Temperature Humidity Enclosure Protection Mechanical Environment Vibration IEC60255-21-1 Response - Class 1 Endurance - Class 1 Shock Response Class 1 Shock Withstand Class 1 Bump Class 1 Class 1 2kVrms for 1 minute between all terminals and earth. 2kVrms for 1 minute between independent circuits. 1kVrms for 1 minute across normally open contacts. Three positive and three negative impulses of 5kV(peak), 1.2/50s, 0.5J between all terminals and between all terminals and earth. 1MHz 2.5kV applied to all ports in common mode. 1MHz 1.0kV applied to all ports in differential mode. 6kV contact discharge, 8kV air discharge. Field strength 10V/m for frequency sweeps of 80MHz to 1GHz and 1.7GHz to 2.2GHz. Additional spot tests at 80, 160, 450, 900 and 1890MHz. 4kV, 2.5kHz, 5/50ns applied to all inputs. 1.2/50s surge in common/differential modes: HV ports: 2kV/1kV (peak) PSU and I/O ports: 2kV/1kV (peak) 10Vrms applied over frequency range 150kHz to 80MHz. Additional spot tests at 27 and 68MHz. 300V 50Hz for 10s applied to ports in common mode. 150V 50Hz for 10s applied to ports in differential mode. Not applicable to AC inputs. Conducted emissions: 0.15 to 0.50MHz: <79dB (peak) or <66dB (mean) 0.50 to 30MHz: <73dB (peak) or <60dB (mean) Radiated emissions (at 30m): 30 to 230MHz: <30dB 230 to 1000MHz: <37dB Compliance with the European Commission Electromagnetic Compatibility Directive is demonstrated according to EN 61000-6-2 and EN 61000-6-4. Compliance with the European Commission Low Voltage Directive is demonstrated according to EN 60255-27. IEC 60068-2-1/2 IEC 60068-2-3 IEC 60529 Operating range: -10C to +55C. Storage / Transit: -25C to +70C. 56 days at 40C and 93% relative humidity. IP51 (Rear : IP20 ) Standards Details

Shock and Bump Seismic Electrical Environment Dielectric Withstand

IEC60255-21-2 IEC60255-21-3

IEC60255-5

High Voltage Impulse Electromagnetic Environment High Frequency Disturbance / Damped Oscillatory Wave Electrostatic Discharge Radiated RF Electromagnetic Disturbance Fast Transient Disturbance Surge Immunity Conducted RF Electromagnetic Disturbance Power Frequency Disturbance

IEC60255-5

IEC60255-22-1, IEC61000-4-12 IEC 60255-22-2 Class 3, IEC61000-4-2 IEC60255-22-3, IEC61000-4-3 IEC60255-22-4, IEC61000-4-4 IEC60255-22-5, IEC61000-4-5 IEC60255-22-6, IEC61000-4-6

IEC60255-22-7, IEC61000-4-16

Conducted and Radiated Emissions

IEC60255-25, EN55022 Class A, IEC61000-6-4

89/336/EEC 73/23/EEC

12

ORDERING INFORMATION Model 700


1 2 3 4 5 6 7 8

Congurations
CT/VT Module

G B U

0 0 -

None VT x 4, CT x 4 VT x 4, CT x 4, Harmonic meas. VT x 4, CT x 3, CT for SEF x 1 VT x 4, CT x 3, CT for SEF x 1, Harmonic meas I/O Module BI x 39, BO x 15, Trip x 2, BI x 78, BO x 15, Trip x 2, BI x 117, BO x 15, Trip x 2, BI x 39, BO x 15, Trip x 2, DC analog input x 10 BI x 78, BO x 15, Trip x 2, DC analog input x 10 AC and DC Rating 1A, 50Hz, 110/125Vdc 1A, 60Hz, 110/125Vdc 5A, 50Hz, 110/125Vdc 5A, 60Hz, 110/125Vdc 1A, 50Hz, 220/250Vdc 1A, 60Hz, 220/250Vdc 5A, 50Hz, 220/250Vdc 5A, 60Hz, 220/250Vdc No AC input, 110/125Vdc No AC input, 220/250Vdc LCD (HMI) Option LCD panel LCD panel with key switch Communication option 100BASE-TX x 1 port 100BASE-FX x 1 port Further option None Redundant DC power supply

0 1 4 7 8

1 2 3 5 6

1 2 3 4 5 6 7 8 E F

1 2

A B

0 1

13

GBU 100

BAY CONTROL UNIT

ORDERING INFORMATION Model 800


1 2 3 4 5 6 7 8

Congurations
CT/VT Module

G B U

0 0 -

None VT x 5, CT x 4 VT x 7, CT x 4 VT x 5, CT x 4, Harmonic measurement VT x 7, CT x 4, Harmonic measurement I/O Module BI x 39, BO x 15 BI x 78, BO x 15 BI x 117, BO x 15 BI x 39, BO x 15, DC analog input x 10 BI x 78, BO x 15, DC analog input x 10

0 2 3 5 6

1 2 3 A B Same as model 700 Refer to page 13

ORDERING INFORMATION Model 900


1 2 3 4 5 6 7 8

Congurations
CT/VT Module

G B U

0 0 -

None VT x 5, CT x 4 VT x 7, CT x 4 VT x 5, CT x 4, Harmonic measurement VT x 7, CT x 4, Harmonic measurement I/O Module BI x 78, BO x 15, DC analog input x 20 BI x 117, BO x 15, DC analog input x 10 BI x 156, BO x 15, DC analog input x 10 BI x 117, BO x 15, DC analog input x 20 BI x 156, BO x 15, DC analog input x 20 BI x 117, BO x 15, DC analog input x 30 BI x 156, BO x 15, DC analog input x 30 BI x 156, BO x 15

0 2 3 5 6

1 3 4 5 6 7 8 A Same as model 700 Refer to page 13

14

DIMENSION AND PANEL CUT-OUT (TYPE-A)


220 216

279

(a) Top view

TOSHIBA

266

258

A B 0V

254

28

73.4

183

22.6

(b) Front view


4 - 5.5
TB10
1 2 3 4 5 1

(c) Side view

TB8
1 2

TB6
1 2

TB4
1 2

TB2
1 2

T1 TB1
2

19 20

19 20

19 20

19 20 17 18

190.5
F1
R T

260

1 2

1 2

1 2

1 2

TB9

19 20

TB7

19 20

TB5

19 20

TB3

19 20

(d) Rear view

6.2

223 34.8 235.4

(e) Panel cut-out


Figure 7 - Dimension and Panel Cut-out Type A (1/2 case size) for model 700 and 800

15

GBU 100

BAY CONTROL UNIT

ORDERING INFORMATION Model 800


330 326

279

(a) Top view

TOSHIBA

266

258

A B 0V

364

28

73.4

183

22.6

(b) Front view


4 - 5.5
TB18
1 2 3 4 5 1

(c) Side view

TB16
1 2

TB14
1 2

TB12
1 2

TB10
1 2

TB8
1 2

TB6
1 2

TB4
1 2

TB2
1 2

T1 TB1
2

19 20 1 2

19 20 1 2

19 20 1 2

19 20 1 2

19 20 1 2

19 20

19 20 1 2

19 20 1 2 17 18

190.5

260

F1 E

R T

19 20

19 20

19 20

19 20

19 20

19 20

19 20

19 20

TB17

TB15

TB13

TB11

TB9

TB7

TB5

TB3

(d) Rear view

6.2

333 34.8 345.4

(e) Panel cut-out


Figure 8 - Dimension and Panel Cut-out Type B (3/4 case size) for model 900

16

CONNECTIONS DIAGRAM
CT/VT
TB1-1 TB1-2 TB1-3 TB1-4 TB1-5 TB1-6 TB1-7 TB1-8 Sef-CT IC1 IB1
P N E

DC/DC
IA1
DC/DC Converter

P N

TB10-1 TB10-2

TB6-1 TB6-2

Binary Input
TB7-1 BI1 BI2 BI21 TB7-2 BI22 TB7-3 BI3 BI23 TB7-4 BI4 BI24 TB7-5 BI5 BI25 TB7-6 BI26 TB7-7 BI7 BI27 TB7-8 BI8 BI28 TB7-9 BI9 BI29 TB7-10 BI10 BI30 TB7-11 BI11 BI31 TB7-12 BI32 TB7-13 BI13 BI33 TB7-14 BI14 BI34 TB7-15 BI15 BI35 TB7-16 BI16 BI36 TB7-17 BI17 BI37 TB7-18 BI18 BI38 TB7-19 BI19 BI39

DC/DC Converter (OPTION)

TB10-3 TB10-4 TB10-5 TB6-4 TB6-3

LAN
LAN-A

T1 or F1
100BASE-TX or 100BASE-FX (SC TYPE)

TB6-5 TB6-6 BI6 TB6-7

TB1-9 VA1 TB1-10 VB1 TB1-11 VC1 TB1-12 TB1-15 TB6-10 TB6-11 TB6-12

RS-232
Front Panel RS-232C

For Local PC

TB6-8 TB6-9

TB1-16

BI12 TB6-13

TB1-17 TB6-14 TB1-18 TB6-15 TB1-13 VS TB1-14 TB6-16 TB6-17 TB6-18 TB6-19 TB5-1 BI1 TB4-2 BI2 TB4-3 BI3 TB4-4 BI4 TB4-5 BI5 TB4-6 BI6 TB4-7 BI7 TB4-8 BI8 TB4-9 BI9 TB4-10 BI10 TB4-11 BI11 TB4-12 BI12 TB4-13 BI13 TB4-14 BI14 TB4-15 BI15 TB4-16 BI16 TB4-17 BI17 TB4-18 BI18 TB4-19 BI19 TB4-20 TB5-20
N

TB4-1

Binary Input #1
BI21 TB5-2 BI22 TB5-3 BI23 TB5-4 BI24 TB5-5 BI25 TB5-6 BI26 TB5-7 BI27 TB5-8 BI28 TB5-9 BI29 TB5-10 BI30 TB5-11 BI31 TB5-12 BI32 TB5-13 BI33 TB5-14 BI34 TB5-15 BI35 TB5-16 BI36 TB5-17 BI37 TB5-18 BI38 TB5-19 BI39

TB6-20 BI20 TB7-20


N

DC Analog Input #1
TB2-1 TB2-2 TB2-5 TB2-6 TB2-9 TB2-10 TB2-13 TB2-14 TB2-17 TB2-18 TB3-1 TB3-2 TB3-5 TB3-6 TB3-9 TB3-10 TB3-13 TB3-14 TB3-17 TB3-18 TB3-20
P N P N P N P N P N P N P N P N P N P N

DCAI1 DCAI2 DCAI3 DCAI4 DCAI5 DCAI6 DCAI7 DCAI8 DCAI9 DCAI10

BI20

Figure 9 - Connection Diagram GBU100-776

17

GBU 100

BAY CONTROL UNIT

Binary Output
TB8-20 TB8-5 TB8-6 TB8-7 TB8-8 TB8-9 TB8-10 TB8-11 TB8-12 TB8-13 TB8-14 TB8-1 TB8-2 TB8-3 TB8-4 TB8-17 TB8-15 TB8-16 Unit Failure B01 B02 B03 TB9-4 B04 Circuit2 TB9-3 B05 TB8-19 TRIP1 TRIP2 OPEN CLOSE TB9-6 Circuit3 TB9-5
OP

P N
OP

OPEN CLOSE

TB9-2 Circuit1 TB9-1

CL

Device1

OP

CL

Device2

CL

Device3

TB9-8 Circuit4 TB9-7

OP

CL

Device4

TB9-10 Circuit5 TB9-9

OP

CL

Device5

TB9-12 Circuit6 TB9-11

OP

CL

Device6

TB9-14 Circuit7 TB9-13

OP

CL

Device7

TB9-16 Circuit8 TB9-15

OP

CL

Device8

TB9-18 Circuit9 TB9-17

OP

CL

Device9

TB9-20 Circuit10 TB9-19

OP

CL

Device10

(NOTE) OP: Auxiliary relay for open control CL: Auxiliary relay for close control

Figure 9 - Connection Diagram GBU100-776 (Continured)

18

CT/VT with Ext.AI


IA1 TB1-2 TB1-3 TB1-4 TB1-5 TB1-6 TB1-7 TB1-8 I0 IC1 IB1

DC/DC
DC/DC Converter

P N

TB10-1 TB10-2

TB4-1 TB4-2

Binary Input #2
TB5-1 BI1 BI2 BI21 TB5-2 BI22 TB5-3 BI3 BI23 TB5-4 BI4 BI24 TB5-5 BI5 BI25 TB5-6 BI26 TB5-7 BI7 BI27 TB5-8 BI8 BI28 TB5-9 BI9 BI29 TB5-10 BI10 BI30 TB5-11 BI11 BI31 TB5-12 BI32 TB5-13 BI13 BI33 TB5-14 BI14 BI34 TB5-15 BI15 BI35 TB5-16 BI16 BI36 TB5-17 BI17 BI37 TB5-18 BI18 BI38 TB5-19 BI19 BI39

DC/DC Converter (OPTION)

P N E

TB10-3 TB10-4 TB10-5 TB4-4 TB4-3

LAN
LAN-A

T1 or F1
100BASE-TX or 100BASE-FX (SC TYPE)

TB4-5 TB4-6 BI6 TB4-7

TB1-9 VA1 TB1-10 VB1 TB1-11 VC1 TB1-12 TB1-15 VA2 TB1-16 VB2 TB1-17 VC2 TB1-18 TB4-15 TB1-13 VS TB1-14 TB4-16 TB4-17 TB4-18 TB4-19 TB3-1 BI1 TB2-2 BI2 TB2-3 BI3 TB2-4 BI4 TB2-5 BI5 TB2-6 BI6 TB2-7 BI7 TB2-8 BI8 TB2-9 BI9 TB2-10 BI10 TB2-11 BI11 TB2-12 BI12 TB2-13 BI13 TB2-14 BI14 TB2-15 BI15 TB2-16 BI16 TB2-17 BI17 TB2-18 BI18 TB2-19 BI19 TB2-20 TB3-21
N

RS-232
Front Panel RS-232C

For Local PC

TB4-8 TB4-9 TB4-10 TB4-11 TB4-12 BI12 TB4-13 TB4-14

TB2-1

Binary Input #1
BI21 TB3-2 BI22 TB3-3 BI23 TB3-4 BI24 TB3-5 BI25 TB3-6 BI26 TB3-7 BI27 TB3-8 BI28 TB3-9 BI29 TB3-10 BI30 TB3-11 BI31 TB3-12 BI32 TB3-13 BI33 TB3-14 BI34 TB3-15 BI35 TB3-16 BI36 TB3-17 BI37 TB3-18 BI38 TB3-19 BI39

TB4-20 BI20 TB5-20


N

BI20

Figure 10 - Connection Diagram GBU100-863

19

GBU 100

BAY CONTROL UNIT

TB6-1 TB6-2

Binary Input #3
BI1 BI2 BI21

TB7-1 TB7-2 BI22 TB7-3 BI23 TB7-4 BI24 TB7-5 BI25 TB7-6 TB8-11 TB8-12 TB8-13 TB8-14 TB7-8 BI26 TB7-7 BI27 BI28 TB7-9 BI29 TB7-10 TB8-1 TB8-2 TB8-3 TB8-4 BI30 TB7-11 BI31 TB7-12 BI32 TB7-13 BI33 TB7-14 TB8-17 TB8-15 TB7-15 TB8-16 BI34 BI35 TB7-16 BI36 TB7-17 BI37 TB7-18 BI38 TB7-19 BI39 TB8-5 TB8-6 TB8-7 TB8-8 TB8-9 TB8-10

Binary Output

TB6-3 BI3 TB6-4 BI4 TB6-5 BI5 TB6-6 BI6 TB6-7 BI7 TB6-8 BI8 TB6-9 BI9 TB6-10 BI10 TB6-11 BI11 TB6-12 BI12 TB6-13 BI13 TB6-14 BI14 TB6-15 BI15 TB6-16 BI16 TB6-17 BI17 TB6-18 BI18 TB6-19 BI19 TB6-20 BI20 TB7-20

Figure 10 - Connection Diagram GBU100-863 (Continued)

20

CT/VT
TB1-1 TB1-2 TB1-3 TB1-4 TB1-5 TB1-6 TB1-7 TB1-8 I0 IC1 IB1 IA1

DC/DC
DC/DC Converter

P N

TB18-1 TB18-2

TB14-1 TB14-2

Binary Input #2
TB15-1 BI1 BI2 BI21 TB15-2 BI22 TB15-3 BI3 BI23 TB15-4 BI4 BI24 TB15-5 BI5 BI25 TB15-6 BI26 TB15-7 BI7 BI27 TB15-8 BI8 BI28 TB15-9 BI9 BI29 TB15-10 BI10 BI30 TB15-11 BI11 BI31 TB15-12 BI32 TB15-13 BI13 BI33 TB15-14 BI14 BI34 TB15-15 BI15 BI35 TB15-16 BI16 BI36 TB15-17 BI17 BI37 TB15-18 BI18 BI38 TB15-19 BI19 BI39

DC/DC Converter (OPTION)

P N E

TB18-3 TB18-4 TB18-5

TB14-3 TB14-4 TB14-5 TB14-6 BI6 TB14-7

LAN
LAN-A

T1 or F1
100BASE-TX or 100BASE-FX (SC TYPE)

TB1-9 VA1 TB1-10 VB1 TB1-11 VC1 TB1-12 TB1-15 VA2 TB1-16 VB2 TB1-17 VC2 TB1-18 TB1-13 VS TB1-14

RS-232
Front Panel RS-232C

TB14-8 For Local PC TB14-9 TB14-10 TB14-11 TB14-12 BI12 TB14-13 TB14-14 TB14-15 TB14-16 TB14-17 TB14-18 TB14-19

TB12-1 TB12-2

Binary Input #1
TB13-1 BI1 BI2 BI21 TB13-2 BI22 TB13-3 BI3 BI23 TB13-4 BI4 BI24 TB13-5 BI5 BI25 TB13-6 BI6 BI26 TB13-7 BI7 BI27 TB13-8 BI8 BI28 TB13-9 BI9 BI29 TB13-10 BI10 BI30 TB13-11 BI11 BI31 TB13-12 BI12 BI32 TB13-13 BI13 BI33 TB13-14 BI14 BI34 TB13-15 BI15 BI35 TB13-16 BI16 BI36 TB13-17 BI17 BI37 TB13-18 BI18 BI38 TB13-19 BI19 BI39

TB14-20 BI20 TB15-20


N

TB12-3 TB12-4 TB12-5 TB12-6 TB12-7 TB12-8 TB12-9 TB12-10 TB12-11 TB12-12 TB12-13 TB12-14 TB12-15 TB12-16 TB12-17 TB12-18 TB12-19 TB12-20 TB13-20
N

DC Analog Input #1
TB8-1 TB8-2 TB8-5 TB8-6 TB8-9 TB8-10 TB8-13 TB8-14 TB8-17 TB8-18 TB9-1 TB9-2 TB9-5 TB9-6 TB9-9 TB9-10 TB9-13 TB9-14 TB9-17 TB9-18 TB9-20
P N P N P N P N P N P N P N P N P N P N

DCAI1 DCAI2 DCAI3 DCAI4 DCAI5 DCAI6 DCAI7 DCAI8 DCAI9 DCAI10

BI20

Figure 11 - Connection Diagram GBU100-931

21

GBU 100

BAY CONTROL UNIT

DC Analog Input #2
TB10-1 TB10-2 TB10-5 TB10-6 TB10-9 TB10-10 TB10-13 TB10-14 TB10-17 TB10-18 TB11-1 TB11-2 TB11-5 TB11-6 TB11-9 TB11-10 TB11-13 TB11-14 TB11-17 TB11-18 TB11-20
P N P N P N P N P N P N P N P N P N P N

Binary Output
TB16-20 TB16-5 TB16-6 TB16-7 TB16-8 TB16-9 TB16-10 TB16-11 TB16-12 TB16-13 TB16-14 TB16-1 TB16-2 TB16-3 TB16-4 TB16-17 TB16-15 TB16-16 Unit Failure B01 B02 B03 TB17-4 B04 Circuit2 TB17-3 B05 TB16-19 TRIP1 TRIP2 OPEN CLOSE TB17-6 Circuit3 TB17-5
OP

DCAI1 DCAI2 DCAI3 DCAI4 DCAI5 DCAI6 DCAI7 DCAI8 DCAI9 DCAI10

P N
OP

OPEN CLOSE

TB17-2 Circuit1 TB17-1

CL

Device1

OP

CL

Device2

CL

Device3

TB17-8 Circuit4 TB17-7

OP

CL

Device4

TB17-10 Circuit5 TB17-9

OP

CL

Device5

TB17-12 Circuit6 TB17-11

OP

CL

Device6

TB17-14 Circuit7 TB17-13

OP

CL

Device7

TB17-16 Circuit8 TB17-15

OP

CL

Device8

TB17-18 Circuit9 TB17-17

OP

CL

Device9

TB17-20 Circuit10 TB17-19

OP

CL

Device10

(NOTE) OP: Auxiliary relay for open control CL : Auxiliary relay for close control

Figure 11 - Connection Diagram GBU100-931 (Continued)

22

TOSHIBA CORPORATION Transmission Distribution & Industrial Systems Company 1-1, Shibaura 1-Chome, Minato-Ku, Tokyo 105-8001, Japan Tel +81-3-3457-3644 Fax +81-3-5444-9166 http://www.toshiba-relays.com

The data given in this catalog are subject to change without notice.

Printed in Japan



"