CURRENT TRANSFORMERS

Copyright Siemens AG Energy / Transmission / High Voltage Products

Why review CTs Description of CB and CT Manufacturing Process Issues with CTs Suggestions for Improvements - CT Specifications - CT Mix - CT Ratings - Other

Page 2

Energy / Transmission / High Voltage Products

CT-adapted toto CT-according protection specification requirements

Page 3

Energy / Transmission / High Voltage Products

High-Voltage Circuit-Breaker Type 3AP1 DT 72.5 up to 245 kV


Product Characteristics One interrupter unit per pole Stored energy Spring Drive Mechanism Rated voltages up to 245 kV Rated short circuit breaking current up to 63 kA Type tested according to IEC 62271-100 Equipped with bushing type current transformers Ambient temperature range from -55 C up to +50 C with pure SF6

Page 4

Energy / Transmission / High Voltage Products

Current Transformer

Sealing ring

Cowl Cores with secondary winding

Housing

Connecting leads

Page 5

Energy / Transmission / High Voltage Products

CT Specifications and Consequences

Standard special very special

Page 6

Energy / Transmission / High Voltage Products

Page 7

Energy / Transmission / High Voltage Products

Cost Savings per CB


Very Special Small Housing [Complying Offer]
Ratio: Class: 1200-900/5 0.25PX300R0.45 on 900/5 tap [S1-S2] 0.15PX400R0.58 on 1200/5 tap [S1-S3] Special Small Housing [Alternative Offer] Ratio: Class: 1200-900/5 0.25PX250R0.4 on 900/5 tap [S1-S2]

Quantity 15

15
0.15PX325R0.55 on 1200/5 tap [S1-S3] TOTAL SAVINGS - (Estimated)

$
Page 8

Approx 10k per CB

Energy / Transmission / High Voltage Products

Weight Saving
Very Special Small Housing [Complying Offer]
Ratio: Class: 1200-900/5 0.25PX300R0.45 on 900/5 tap [S1-S2] 0.15PX400R0.58 on 1200/5 tap [S1-S3] Special Small Housing [Alternative Offer] Ratio: Class: 1200-900/5 0.25PX250R0.4 on 900/5 tap [S1-S2] 0.15PX325R0.55 on 1200/5 tap [S1-S3]

Weight 150kg per bushing Total 900kg

129kg per bushing Total 774kg

TOTAL SAVINGS -

SAVINGS 126kg per CB

Page 9

Energy / Transmission / High Voltage Products

What do we look at in CT specification

CT Dimension
Knee Point

Burden

Sec. Current

ALF

Accuracy

Page 10

Energy / Transmission / High Voltage Products

CURRENT TRANSFORMER CONSTRUCTION Current transformers can be constructed in a number of different ways: WOUND PRIMARY: with a fixed primary with a number of turns around the core;the winding is fully insulated and form an integral part of the assembly BAR PRIMARY: this has a fixed insulated primary conductor passing through the core and essentially the primary conductor is equal to 1 turn

Page 11

Energy / Transmission / High Voltage Products

CURRENT TRANSFORMER CONSTRUCTION( cont.)

BUSHING TYPE:this has no primary winding;it is for use with a fully insulated conductor acting as the primary winding. WINDOW TYPE:this has no primary winding but it normally has insulation in the window so that conductors can be passed through Other types are for HV applications.

Page 12

Energy / Transmission / High Voltage Products

BASIC FORMULAE

MAXIMUM SECONDARY WINDING VOLTAGE

Page 13

Energy / Transmission / High Voltage Products

BASIC DESIGN CONCEPTS (Cont.)

The more accurate the reflection in the secondary of the primary current the smaller the current and phase angle errors. These errors are dependant on : Excitation ampere turns Type of magnetic material used Configuration of the transformer;in general the smaller the ID and OD the more accurate the transformer for the same excitation Ampere - turns

Page 14

Energy / Transmission / High Voltage Products

CT 1A or 5A Secondary?
1250/5 0.15 PX 100 Rct = 0.5 5P20 20VA Rb = 0.8 SSC = 25kA 1250/1 0.025 PX 100 Rct = 2.5 5P20 4VA Rb = 4 SSC = 25kA

Page 15

Energy / Transmission / High Voltage Products

CT 1A or 5A Secondary?
1250/5 0.15 PX 300 Rct = 0.5 5P20 85VA Rb = 3.4 SSC = 25kA 1250/1 0.025 PX 250 Rct = 2.5 5P20 13.75VA Rb = 13.75 SSC = 25kA

Page 16

Energy / Transmission / High Voltage Products

CURRENT TRANSFORMER CHOICE

MEASUREMENT CTS
Require good accuracy up to 120% rated current Require low saturation levels to protect instruments

PROTECTION CTS
Require accuracy up to many times rated current Require definite voltage outputs at below saturation levels

Page 17

Energy / Transmission / High Voltage Products

CT Magnetising Curve

Page 18

Energy / Transmission / High Voltage Products

Page 19

Energy / Transmission / High Voltage Products

MARKET CONSIDERATIONS

THE SPECIFIER Should ensure that the appropriate class for each application is used;specifying a greater burden than actually required may not give you the accuracy you want!!! The protection class requirements should be accurately calculated as the specifying of voltages higher than require only result in higher prices

Page 20

Energy / Transmission / High Voltage Products

MARKET CONSIDERATIONS (Cont.) THE PURCHASER Consider carefully the implications of the specification! Do not use metering CTs for Protection applications:it will cost more later when the end user has problems with its protection system. Ensure that the CTs you use have the correct mechanical characteristics;ensure that the materials used are adequate to withstand the temperatures of your busbars!!!

Page 21

Energy / Transmission / High Voltage Products

TYPICAL EXAMPLES
METERING APPLICATION

Customer asks for low ratio with high burden and class Typical 15 VA 1M Result: Large and expensive CT using mumetal

ALTERNATIVE Determine what connected load is; Typical now is electronic with small VA burden typical 2.5 or 5VA

RECOMMEND ALTERNATIVE

Page 22

Energy / Transmission / High Voltage Products

TYPICAL EXAMPLE PROTECTION APPLICATION

Customer specifies differential CTs with large knee point voltage CT size is too large to fit in switchgear Check voltage requirement based on relay recommended formulas!!!! 90% of time customer specified knee point voltage is much higher than needed!! Result : a lower cost ct that can fit in your gear

Page 23

Energy / Transmission / High Voltage Products

TYPICAL SWITCHGEAR APPLICATIONS How are dimensions of CTs affected??? Remember the basic formula ,voltage is dependant on: turns; flux density in core and size of core If a customer wants a larger internal diameter then the price will go up due to: Increased weight of core to compensate for lower flux density; remember flux density is proportional to magnetising force and for a given number of turns the magnetizing force of ampere turns /metre is indirectly proportional to the mean length of core i.e, The larger the diameter of the core the lower magnetising ampere turns the lower the flux density!!!

Page 24

Energy / Transmission / High Voltage Products

CT-Requirements

Old Specification No Calculation Multi-Ratio CT interchangable High Burden

new adapted Data CT-stability calculation necesary ratios only project specific data adapted burden

Page 25

Energy / Transmission / High Voltage Products

What do we look at in CT specification


CT Dimension

CT Design Consideration :
Knee Point Burden Sec. Current ALF Accuracy

Dont re-use old specifications Do your studies to optimise CT considering:


Fault Levels X/R ratio Relay response times

Work with the manufacturer . . . .


Page 26 Energy / Transmission / High Voltage Products