Quantum Climate Changer QUANTUM XP Product Catalogue

0.5 - 31 m3/s (1000 - 65000 CFM)

CLCP-PRC001-EN

Contents

Introduction Model Nomenclature Features and Benefits Quick Select


50mm Casing Construction

3 4 5 6

General Data
Casing Fan and Drives Coils Filters Air Pressure Drop

Dimension Data
HDT HDT VDT VDT Unit Dimensions Unit Weight Unit Dimensions Unit Weight

23

Installation Consideration
Define Unit Left or Right Service Clearance Coil Connection Dimension Fan Outlet DImension

32

Mechanical Specification

37

Introduction
THE FOUNDATION GROWS DEEPER, THE QUANTUM XP ... LEADING THE WAY TO HIGH PERFORMANCE BUILDING CLIMATE CONTROL

TECHNOLOGICAL LEADERSHIP Tranes pioneering leadership in making building work better for life has seen many milestone in recent years. In 1989, Trane revolutionized the HVAC industry with the development of the Modular Climate ChangerTM Air Handler. Using a building block approach to air handler design, Trane dramatically increased the flexibility of cataloged air handlers and systems. The Quantum Climate Changer followed in 1992 with introduction of Alluminium-pentapost frames and double skin panels. This was superseded with the industry leading Performances certified CLCP Euro. As customer demand for even greater flexibility, performance and customization grows, Trane continues this innovative legacy. The Quantum XP, today marks the next milestone of performance which takes the Quantum line into performance driven applications. Trane global engineering is renowned for reliable, high quality, environmentally responsible designs. Critical performance applications require confidence in your flexible air-handling system. Trane experts provide testing, tools, and data to give precise and predictable performance. Trane engineered solutions tailored to your specific performance requirements include: Energy recovery Dehumidification Energy efficiency Demanding high static applications Meeting stringent IAQ standards.

SHARED KNOWLEDGE Trane custom application and design engineers work directly with you and Trane sales team help you create a safe, comfortable and efficient indoor environment for new and existing buildings, or develop stringently controlled conditions for process applications. Its almost like having your own custom design team. THE FIRST STEP Designing for a hospital? An Electronics plants? Pharmaceutical facility? A university R&D Lab? Trane has experts experienced in these vertical markets and others to help you design and deliver the greatest value. For a successful flexible air-handling Project, in these critical process environments, involve your local Trane sales team early - communication is key. Your Trane team includes factory application and design engineers with the expertise and systems knowledge to help you specify the optimal HVAC package for your new or existing building. CUSTOMIZED FLEXIBILITY The Quantum XP Air Handlers offers flexibility and performances demanded by process sensitive operations in the healthcare, electronics life-sciences and pharmaceutical markets. Whether your specific need is in specialized ventilation monitoring capabilities, a unique footprint, a high performance thermal and leakage casing, engineered dehumidification, Trane engineers will work closely with you to understand and meet your specifications, schedule, and budget. With Trane custom air handlers you can fine-tune your performance to exactly meet your specifications. Trane can make recommendations on component selection based on pre-tested performance data gathered in our labs, positioning you to make a more informed decision. Though you are not limited to components Trane has pre tested, Trane validated performance is available for many options, including:

Trane coils with: - A unique, high-efficient fin design,optimizing the coil to the nearest fin-per-foot - One of the highest moisture carryover limits in the industry Fans with precise vibration, balancing and performance standards. Traq airflow monitoring stations (outdoor air) Trane energy recovery wheels Unit sound data per partial ARI 260 covering, discharge, inlet and inlet + casing. Trane CDQ (Cool, Dry, Quiet) desiccant dehumidification - Breaks the dew-point barrier using standard equipment - Uses less energy than comparable systems

NO SURPRISES Data that we have gathered through years of testing in our research and development labs enables us to more accurately predict your specific unit performance. This data, used to engineer your custom air handler design, includes:

ARI Standard 410 coil performance Unit casings designed for: - comfort and process applications up to 10 inches w.g. of static pressure Unit air leakage rates that comply to Eurovent Class L1 [highest in its class], further improves IAQ. Eurovent Class D1 strength compliance. [Highest in its class] Unit thermal performance comply to Eurovent TB1. [Highest in its class] Unit acoustical performance

In addition to testing our designs in the laboratory, factory performance testing is also available for complete peace of mind. From running fans, to pressure testing our coils, to operating the controls, we provide you performance data in which you can be confident. You have enough to manage with your project. You dont need any last minute surprises with your Quantum XP Air Handler. The Quantum XP... Built For Performance.

QUANTUM XP Model Nomenclature


EG.: CLCP XP 00304
DIGIT 1,2,3 4 5,6 7,8 9,10,11 DESCRIPTION

04AMKAT 0560J3F 1FA028D38X 12002DNXWR12144YWR12144YWR12144XB

12,13,14,15

16 17 18,19,20 21,22,23,24

25 26 27,28

29 30 31,32,33 34 35,36 37 38,39,40,41 42 43 44 45

46 47 48,49 50,51,52 53 54 55 56,57 58,59,60 61 62 63 64, 65 66,67,68 69 70

CLC = Climate Changer P = Development sequence XP = Xtra Performance X, X = Future Use Casing size 003 008 014 025 040 060 080 095 120 004 010 016 030 045 065 085 100 006 012 020 035 050 070 090 110 Casing parametric dimension Std parametric (case size), Non standard to key in the parametric dimension 0404 (003) 1004 (008) 1206 (014) 1210 (025) 1612 (040) 2014 (060) 2614 (080) 3214 (095) 3218 (120) 0604 (004) 0806 (010) 1008 (016) 1212 (030) 1812 (045) 2214 (065) 2814 (085) 3216 (100) 0804 (006) 1006 (012) 1208 (020) 1412 (035) 2012 (050) 2414 (070) 3014 (090) 3217 (110) Insulation C = 50mm PU Insulation Country of Origin C = China M = Malaysia Fan Model FDA ADA BDB BNA ANA SSS = Special XXX = None Fan Size 0200 0280 0400 0560 0800 1120 XXXX = None 0225 0315 0450 0630 0900 1250 0250 0355 0500 0710 1000 1400 Fan / Bearing Type A=S C = S2 E = SM G = TM I = TX K = S2M M = T2M X = None B=C D = C2 F = CM H = XM J = XX L = C2M N = X2M Fan Arrangement 1 = ARR 1 3 = ARR 3 5 = ARR 5 7 = ARR 7 9 = ARR 9 B = ARR11 X = None 2 = ARR 2 4 = ARR 4 6 = ARR 6 8 = ARR 8 A = ARR 10 C = ARR 12 S = Special Motor Frame, KW & Pole XX = None H1 = D100L, 3.0KW, 4P P1 = D180L, 22.0KW, 4P A2 = D63, 0.18KW, 2P I2 = D112M, 3.7KW, 2P A1 = D63, 0.18KW, 4P I1 = D112M, 3.7KW, 4P Q1 = D200L, 30.0KW, 4P B2 = D71, 0.37KW, 2P J2 = D112M, 4.0KW, 2P B1 = D71, 0.37KW, 4P J1 = D112M, 4.0KW, 4P R1 = D225SC, 37.0KW, 4P C2 = D71, 0.55KW, 2P K2 = D132S, 5.5KW, 2P C1 = D80, 0.55KW, 4P K1 = D132S, 5.5KW, 4P T1 = D225MC, 45.0KW, 4P D2 = D80, 0.75KW, 2P L2 = D132S, 7.5KW, 2P D1 = D80, 0.75KW, 4P L1 = D132M, 7.5KW, 4P U1 = D250SC, 55.0KW, 4P E2 = D80,1.1KW, 2P SS = Special E1 = D90S, 1.1KW, 4P M1 = D160M, 11.0KW, 4P V1 = D250MC, 75.0KW, 4P F2 = D90S, 1.5KW, 2P F1 = D90L, 1.5KW, 4P N1 = D160L, 15.0KW, 4P W1 = D280SC, 90.0KW, 4P G2 = D90L, 2.2KW, 2P G1 = D100L, 2.2KW, 4P O1 = D180M, 18.5KW, 4P Y1 = D280MC, 110.0KW, 4P H2 = D100L, 3.0KW, 2P Electrical rating of motor : Volt/Phase/Hz. X = None E = 200V/ 3 Ph/ 50 Hz G = 380V/ 3 Ph/ 60 Hz J = 460V/ 3 Ph/ 60 Hz S = Special D = 380-415V/ 3 Ph/ 50 Hz F = 230V/ 3 Ph/ 60 Hz H = 440V/ 3 Ph/ 60 Hz K = 480V/ 3Ph/ 60 Hz Fan Pulley Size Fan shaft diameter Motor Pulley Size Motor shaft diameter Belt type X = None A = SPA B = SPB C = SPC Z = SPZ Belt length Grooves 1 = 1Groove 2 = 2Groove 3 = 3Groove 4 = 4Groove 5 = 5Groove X = None Pre-Filter Media A = 2 Pleated 30% B = 2 Washable 20% C = 2 Aluminum D = 4 Pleated 30% S = Special X = None Filter Media # 1 Filter Media # 2 A = 2 Pleated 30% F = Hepa 99.99% K = 4 Cartridge 85% P = 12 Cartridge 65% U = Biocell B = 2 Washable 20% G = 15 Bag 60 - 65% L = 4 Cartridge 95% Q = 12 Cartridge 85% V = PTFE C = 2 Aluminum H = 15 Bag 85% M = 21 Bag 60 - 65% R = 12 Cartridge 95% X = None D = 4 Pleated 30% I = 15 Bag 95% N = 21 Bag 85% S = Carbon E = Hepa 99.97% J = 4 Cartridge 65% O = 21 Bag 95% T = Special Media Coil # 1,Type X = None; W = WL(1/2Tube); L = LL(1/2Tube); D = DL(1/2Tube); F = FD (1/2 Tube); A = A (1/2 Tube); B = AA, (1/2 Tube); S = Special P = WL(5/8Tube); Q = LL(5/8Tube); R = DL(5/8Tube); S = FD(5/8Tube); T = A(5/8Tube); U = AA(5/8Tube); Coil # 1, Connection L = LH, R = RH, X = None Coil # 1, Row XX = without coil., 01 = 1row 2 = 2rows, 04 = 4rows, 06 = 6rows, 08 = 8rows, 10 = 10rows, 12 = 12rows Coil # 1, Fin Series (FPF) XXX = without coil, 100 - 168 Fins per Foot SSS = Special Coil # 1, Turbulator X = No Y = Yes Coil # 2,Type X = None; W = WL(1/2Tube); L = LL(1/2Tube); D = DL(1/2Tube); F = FD (1/2 Tube); A = A (1/2 Tube); B = AA, (1/2 Tube); S = Special P = WL(5/8Tube); Q = LL(5/8Tube); R = DL(5/8Tube); S = FD(5/8Tube); T = A(5/8Tube); U = AA(5/8Tube); Coil # 2, Connection L = LH, R = RH, X = None Coil # 2, Row XX = without coil., 01 = 1row 2 = 2rows, 04 = 4rows, 06 = 6rows, 08 = 8rows, 10 = 10rows, 12 = 12rows Coil # 2, Fin Series (FPF) XXX = without coil, 100 - 168 Fins per Foot SSS = Special Coil # 2, Turbulator X = No Y = Yes Coil # 3,Type X = None; W = WL(1/2Tube); L = LL(1/2Tube); D = DL(1/2Tube); F = FD (1/2 Tube); A = A (1/2 Tube); B = AA, (1/2 Tube); S = Special P = WL(5/8Tube); Q = LL(5/8Tube); R = DL(5/8Tube); S = FD(5/8Tube); T = A(5/8Tube); U = AA(5/8Tube); Coil # 3, Connection L = LH, R = RH, X = None Coil # 3, Row XX = without coil., 01 = 1row 2 = 2rows, 04 = 4rows, 06 = 6rows, 08 = 8rows, 10 = 10rows, 12 = 12rows Coil # 3, Fin Series (FPF) XXX = without coil, 100 - 168 Fins per Foot SSS = Special Coil # 3, Turbulator X = No Y = Yes Service digit A = present Model Nomenclature Revision, First Issue Oct 09

QUANTUM XP Features and Benefits


Ultra Low Leak Construction Unique casing design with panel attached to the frame through a external locking mechanism represented by a wedge (stopper) and frame, exerting pressure evenly onto the panel and the seal attached to the frame, and hence a better air tight cabinet construction. The casing is designed to meet Eurovent Casing Air Leakage Standard, L1 refer to Guide Specification. Excellent Condensate Management Dual pitched sloping drain pan allows for total condensate removal. A unique IAQ feature developed to prevent stagnant water in air handling units. Environmental Friendly Materials High-grade aluminium frame is noncorrosive and is easily clean-able. All these features will further enhance indoor air quality. Design for Routine Cleaning Double wall panel construction allows for easy cleaning and disinfecting of the interior surfaces. Panel and frame design allows for easy removal of side panels for maximum access to internal areas. Interior is mostly of a flushed, clean constrution. High Grade Aluminum Frame Frame is constructed of extruded aluminum channels for structural rigidity and lightness. The frame shall be a full thermal break design.

Injected Polyurethane Foam Panels. All panels are injected with high efficiency polyurethane foam insulation. Foamed panels provide superior thermal resistance properties, and have excellent accoustic and vibration absorption characteristics. In addition, polyurethane foam does not absorb moisture and will not promote fungus growth. High Efficiency Performance Patented Delta-Flo slit fin heat transfer technology gives maximum cooling and dehumidification. Trane engineered fan systems provide maximum airflow while minimizing vibration, acoustic levels and power consumption. Suitable for High Performance Application Addresses the needs of electronics, healthcare, life-sciences and pharmaceuticals. Sturdy Unit Construction The Quantum XP flexibility is contributed by the structural integrity pentapost and panel construction. The casing strength is designed to meet European Standard EN 1886; 2006, Class D1. Optimized Coils Flexibility characterizes the Quantum Climate Changers broad coil offering. The variety of types, sizes, arrangements and materials enables you to select a coil optimized for the application pressure drop and capacity requirements. Options include;

2 to 12 rows, inch OD chilled water coils and two separate cooling coil in series to meet high capacity requirement. 1 and 2 rows, inch OD hot water coils. 4 and 6 rows, inch OD refrigerant coils. 1 row inch OD, distributing type steam coils. Infinitely variable fin spacing (IVS). Stainless steel coil casing (option). Copper fins. Coated aluminum fin for corrosion resistance. Header drain and vent connections. Fully drain able coils at header 5/8 inch coil.

Performance Assurance and Commitment to Quality Trane combines compreshensive performance certifications with thorough laboratory testing and manufacturing methods. Together these elements help to ensure that each Quantum XP operates predictably and reliably throughout the life of the unit. All fans are tested as per ANSI/AMCA 210, ANSI/ASHRAE Standard 51 - Laboratory Method of Testing Fans Rating and AMCA 300 Reverberant Room Method for Sound Testing of Fans. All coil capacities, pressure drops and selection procedures are rated in accordance to ARI Standard 410. All coils are leak and proof tested to minimum 375 psig. Quantum XP is manufactured in a facility that is certified to MS ISO9001.

Quick Select 50mm Casing Construction QUANTUM XP

Quick Selection Procedure


Step 1: Determine what is the design airflow (m3/s) or total cooling capacity (KW) Step 2: Use the table below to determine the unit size by picking the closest airflow or total cooling capacity. Step 3: The unit width and height are the same for all selections. Unit length in Table A is based on basic fan + coil + flat filter sections only. For other combinations. Use Table B : Standard Section Length to determine the overall unit length. Step 4: Determine the nominal units details (unit weight, coil water pressure drop, water flow rate and motor installed power) using Table A

Table A: Quick Select Coil Face Area m2 0.23 0.40 0.56 0.73 0.89 1.15 1.42 1.58 1.94 2.41 2.88 3.42 3.95 4.48 5.01 5.92 6.55 7.18 7.81 8.44 9.07 9.70 11.04 11.64 12.23 Airflow At 2.5m/s Total Face Cooling Velocity Capacity m 3/ s kw 0.6 8.64 1.0 21.51 1.5 37.13 1.9 50.35 2.3 58.03 3.0 80.40 3.6 100.53 4.1 110.44 5.0 139.68 6.2 173.71 7.4 206.18 8.7 248.79 10.1 291.13 11.5 312.01 12.9 356.42 15.2 421.31 16.8 472.83 18.4 524.44 20.0 576.11 21.6 586.93 23.2 679.63 24.9 733.61 28.4 837.56 30.2 889.04 32.0 940.50 External Unit Dimension (mm) Unit Static (Fan + Coil + Pre & Bag + MB) Weight Pressure Pa Width Height Length Kg 500 780 900 2950 290 500 1090 900 2950 354 500 1400 900 2950 435 500 1710 900 2950 495 500 1400 1210 3105 553 500 1710 1210 3105 621 500 2020 1210 3105 704 500 1710 1520 3105 734 500 2020 1520 3260 891 500 2020 1830 3415 1045 500 2020 2140 3415 1204 500 2330 2140 3575 1465 500 2640 2140 3730 1771 500 2950 2140 3730 1924 500 3260 2140 3885 2102 500 3260 2450 4040 1079 500 3570 2450 4195 2670 500 3880 2450 4665 3055 500 4190 2450 4665 3417 500 4500 2450 4820 3575 500 4810 2450 4820 3838 500 5120 2450 4820 3991 500 5120 2760 5285 4656 500 5120 2915 5440 4991 500 5120 3070 5231 5231 Water Pressure Drop kPa 0.5 3.6 11.5 22.8 10.6 21.9 36.9 21.1 36.4 42.8 40.4 62.9 80.5 25.1 34.2 36.9 48.2 61.4 76.6 83.0 113.5 136.1 141.6 151.0 149.9 Water Flow Rate L/s 0.37 0.93 1.61 2.18 2.51 3.48 4.36 4.79 6.05 7.53 8.94 10.78 12.62 13.52 15.45 18.26 20.49 22.73 24.97 25.43 29.45 31.79 36.30 38.53 40.76 Motor Installed Power kw 1.10 2.20 3.70 3.70 5.50 5.50 7.50 7.50 11.0 11.0 15.0 15.0 18.5 22.0 22.0 30.0 30.0 30.0 37.0 37.0 45.0 45.0 55.0 55.0 55.0

Model Size 003 004 006 008 010 012 014 016 020 025 030 035 040 045 050 060 065 070 080 085 090 095 *100 *110 *120

Note: 1: Nominal cooling capacities are based on EDB 26.7 C / EWB 19.4C and EWT 6.7 C / LWT 12.2C 2: Unit dimension and weight includes Backward curved fan section (arrangement 1 and 2). 6 row 144fpf coil (1/2 inch cu tube) section and pre & Bag and mixing section (with media)

Fan Section, L1 (arrangement 1 and 2, motor installed power as per Table A)


Model Size 003 004 006 008 010 Motor kW 0.18 ~ 3 0.37 ~ 3 0.55 ~ 7.5 0.75 ~ 7.5 1.1 ~ 7.5 11 L1 775 775 775 775 930 1085 Model Size 012 / 014 016 020 Motor kW 1.1 ~ 7.5 11 ~ 15 1.5 ~ 7.5 11 ~ 18.5 2.2 ~ 7.5 11 ~ 18.5 L1 930 1085 930 1395 930 1085 Model Size 025 / 030 Motor kW 2.2 ~ 7.5 11 ~ 15 18.5 ~ 30 4 ~ 22 30 ~ 45 4 ~ 22 30 ~ 45 L1 1085 1240 1550 1240 1550 1395 1550 Model Size 050 / 060 065 / 070 080 ~ 095 100 110 / 120 Motor kW 5.5 ~ 22 30 ~ 45 7.5 ~ 22 30 ~ 45 7.5 ~ 75 15 ~ 75 15 ~ 75 L1 1550 1705 1550 1860 1860 2170 2325

035 040 / 045

Mixing Section, L2
Model Size 003 ~ 065 070 ~ 080 085 ~ 120 L2 775mm 930mm 1085mm

Coil Section, L3
Model Size 003 ~ 120 003 ~ 120 Coil Row 2, 4 and 6 row 8, 10 and 12 row L3 620mm 775mm

Note: 1: Total unit length shall be calculated based on total sum of the individual section lengths added together. 2: Add 160mm to overall unit length for end frame for all models. 3: Fan Section lengths are indicative only as the length varies according to the fan arrangement and motor KW range 4: Add another 155m section for unit with fan and coil sections only.

General Data Casing


Casing Type The extruded frame of engineering grade aluminium provides the Quantum XP with excellent rigidity. Casing Strength is designed to meet European standard EN 1886:1998, D1. The panel is attached to the frame though a external locking mechanism represented by a wedge (stopper) and frame exerting pressure evenly onto the and the seal attached to the frame,and hence a better air tight cabinet construction. This unique design requires no welding during assembly of the framework sections. The panel are of double wall construction and injected with foam insulation to provide a rigid sturdy and easily cleaned enclosure.

The Quantum XP is designed to suit the technical requirement of each application.Design is specially suitable forhealthcare, electronics, life-sciences and pharmaceuticals where condensation concerns exist, IAQ requirements abound and where cleanable-flush interiors are needed.

ponent closed cell, rigid polyurethane foam. A mechanical cam locking mechanism, between panels with the added reinforcement of internal rivets allows air tightness compliance to Eurovent Class L1. Insulating Material Specification: Thermal conductivity K Factor = 0.02 W/ mK. Panel Thickness: Overall average panel nominal thickness shall be 50mm. The exterior and inner walls panel coating comes with a variety of choice Standard offering: galvanized prepainted exterior wall and galvanized steel sheet on inner wall. Option: galvanized prepainted steel sheet on exterior and inner - wall.

Panel The panel are manufactured by injection of polyurethane foam insulation between two metal skins to produce a rigid and totally enclosed panel of 50mm nominal thickness. This double wall contruction keeps the insulation out of the air airstream and contributes towards improved indoor air quality. The panels are also easily cleanable. The insulating material is a two com-

3 Leg Corner

3 Leg Corner Unit

Stealth

General Data Fans and Drives


Fan
Types of Fans Quantum XP Air Handling units are designed to provide accurate performance in order to meet the sophisticated building air conditiong requirement. Quantum XP Air Handling units are supplied with double inlet, double width (DIDW) centrifugal blowers. Forward curved blade (FC) Backward curved blade (BC) Airfoil blade (AF) Direct/belt Drive plenum fan

Type of Fans Fan casing are constructed of galvanized steel with a series of punchedholes or nutserts allowing the fixing of accessories such as frames or support structure thus providing a variety of discharge positions The impeller (blade) is galvanized steel finish for FC and painted steel for BC and securely fixed to the solid straight shaft. All fan impellers are statically and dynamically balanced by the ISO 1940 and AMCA 204/3-G2.5 quality. Fan shaft are carbon steel (C45) grade and machined to tolerances ISO 286-2 Grade G6 standard.

Vibration Isolator
Two types of isolator are: 1 Deflection spring 2 Deflection spring The isolators selected shall have a minimum 80% isolation efficiency.

Standby Systems

Standby Motor

Direct Drive Fan

Starters

General Data Fan and Drives

Fan Size and Diameter


Model Size 003 004 006 008 010 012 014 016 020 025 030 035 040 045 050 060 065 070 080 085 090 095 100 110 120 Fan Size FC 200 BC 200 FC 225 BC 225 FC 250 BC 250 FC 280 BC 280 FC 315 BC 315 FC 400 BC 400 FC 400 BC 400 FC 450 BC 450 FC 500 BC 500 FC 560 BC 560 FC 630 BC 630 FC 710 BC 710 FC 710 BC 710 FC 800 BC 800 FC 800 BC 800 FC 900 BC 900 FC 900 BC 900 FC 1000 BC 1000 FC 1000 BC 1000 FC 1000 BC 1000 FC 1000 BC 1000 FC 1000 BC 1000 FC 1120 BC 1120 BC 1250 BC 1250 Fan Size Diameter (mm) 200 200 225 225 250 250 280 280 315 315 400 400 400 400 450 450 500 500 560 560 630 630 710 710 710 710 800 800 800 800 900 900 900 900 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1120 1120 1250 1250

Fan Discharge Arrangements

General Data Fans and Drives


Fan Series
FC & BC Series - Double Inlet Forward Curved and Backward Curved Centrifugal Fans. The FC and BC series is DIDW centrifugal fans with forward curved and backward curved impeller. The fans are suitable for supply or extract applications in commercial, process and HVAC systems. The FC and BC series is available in type S, C, T or X as shown in Fig 1.

Fig 1

10

General Data Coils

Coils General The cooling coil shall be mounted over the dual pitched slopping drain pan to ensure water condensate flowing. Coil performances are designed in accordance to ARI Standard 410. All coils shall be counter flow design. The Delta Flo coils design that shall have the following criteria as above. Availability
Water, Refrigerant and Steam Coil
Description Face Velocity; FPM (m/s) EDB; 0F (0C) EWB; 0F (0C) EWT; 0F (0C) Water Velocity; Ft/s (m/s) Salurated Suction Temperature; 0F (0C) Minimum Superheat; 0F (0C) Refrigerant (FD) 200 ~ 800 (1.0 ~ 4.1) 65 ~ 100 (18 ~ 38) 60 ~ 85 (15 ~ 29) 34 ~ 55 (11 ~ 12.8) 6 (14) Chilled Water Hot Water 200 ~ 800 (1.0 ~ 4.1) 200 ~ 1500 (1.0 ~ 457) 65 ~ 100 (18 ~ 38) 0 ~ 100 (18 ~ 38) 60 ~ 85 (15 ~ 29) 35 ~ 65 (2 ~ 38) 120 ~ 250 (49 ~ 121) 1 ~ 8 (0.31 ~ 2.4) 0.5 ~ 8 (0.15 ~ 24) -

Coil Tube

Description General Purpose Single Row Serpentine Water Coil Drainable Double-Row Serpentine Water Coil Drainable Double-Row Serpentine Water Coil Refrigerant Cooling Coil

Rows

End Connection

Header Material

Fins Per Foot Aluminum 100 - 168 Htg 100 - 168 Clg Copper 120 - 168 Aluminum 100 -168 Htg copper 100 - 168 Clg Copper 120 - 168 Htg 120 - 168 Clg Aluminum 100 - 168 Clg Copper 120 - 168 Clg Aluminum 100 - 168 Clg Copper 120 - 168 Clg Aluminum 100 - 168

Tube Material

Max. Standard Operation Pressure (Tube Side) Pressure Temp 0 0 Psig kPa F C 250 1724 220 104

WL

2,4,6,8 10 & 12

Same Side

Steel Or Copper

OD Copper

DL

2,4,6,8 10 & 12

Same Side

Steel Or Copper

OD Copper

250

1724

220

104

LL

4,6,8 10 & 12

Same Side

Steel Or Copper

OD Copper

250

1724

220

104

FD

4,6

Same Side

Copper

OD Copper

250

1724

220

104

A or AA

Steam Coil

Opposite Side

Steel

OD Copper

250

1724

220

104

1. All coil length are available in 1 inch increments. 2. All fin spacing are available in 1 fin per foot increments

3. Turbulators are available for type WL and LL coils. This option is useful when water velocities are low (less than 4 ft/ sec) to obtain maximum tube side heat tranfer. The use of turbulators is equivalent to doubling the water velocity though the tubes.

4. All water coils can be used in cooling and heating applications. 5. Circuiting options for type FD coils are: Standard (Single Distributor), and Intertwined circuiting

11

General Data Coils

Chilled and Hot Water Coil


Dimensions
Model Size Ft 2 2.5 4.3 6.1 7.9 9.7 12.5 15.3 17.1 21.0 26.0 31.5 37.3 43.2 49.0 54.8 64.0 70.8 77.6 84.4 91.1 97.9 104.5 118.84 125.26 131.68 Coil Face Area M2 0.24 0.40 0.57 0.73 0.90 1.16 1.42 1.59 1.95 2.40 2.93 3.47 4.02 4.56 5.10 5.95 6.58 7.21 7.85 8.48 9.11 9.78 11.04 11.64 12.23 in 21 21 21 21 34 34 34 46 46 58 70 70 70 70 70 40 41 40 41 40 41 40 41 40 41 40 41 40 41 46 46 46 51 51 51 Actual Fin Height mm 533 533 533 533 864 864 864 1175 1175 1473 1778 1778 1778 1778 1778 1016 1041 1016 1041 1016 1041 1016 1041 1016 1041 1016 1041 1016 1041 1175 1175 1175 1302 1302 1302 in 17 29 41 53 41 53 65 53 65 65 65 77 89 101 113 113 113 125 125 137 137 149 149 161 161 173 173 185 185 185 185 185 185 185 185 Finned Length mm 432 737 1041 1346 1041 1346 1651 1346 1651 1651 1651 1956 2261 2565 2870 2870 2870 3175 3175 3480 3480 3785 3785 4089 4089 4394 4394 4699 4699 4699 4699 4699 4699 4699 4699

003 004 006 008 010 012 014 016 020 025 030 035 040 045 050 060 065 070 080 085 090 095 100 110 120

12

General Data Coils

Steam Coil Dimension (1/2 Delta Flo: Type A and AA Circuiting)


Dimensions
Model Size Ft 2 2.1 2.4 5.4 7.1 8.8 11.5 14.2 14.2 17.6 23.0 28.4 33.8 39.2 44.6 50.2 57.8 Coil Face Area M2 0.2 0.23 0.5 0.66 0.82 1.07 1.32 1.32 1.64 2.14 2.64 3.14 3.65 4.15 4.66 5.38 in 20 20 20 20 32.5 32.5 32.5 20 20 20 20 32.5 20 32.5 32.5 32.5 32.5 32.5 32.5 32.5 32.5 32.5 32.5 20 20 35 20 20 35 20 20 35 20 20 35 20 20 35 20 20 35 20 20 35 20 32.5 35 20 32.5 35 32.5 32.5 35 13 Actual Fin Height mm 508 508 508 508 826 826 826 508 508 508 508 826 508 826 826 826 826 826 826 826 826 826 826 508 508 889 508 508 889 508 508 889 508 508 889 508 508 889 508 508 889 508 508 889 508 826 889 508 826 889 826 826 889 in 15 17 39 51 39 51 63 51 51 63 63 63 63 63 63 75 75 87 87 99 99 111 111 111 111 111 123 123 123 135 135 135 147 147 147 159 159 159 171 171 171 183 183 183 183 183 183 183 183 183 183 183 183 Finned Length mm 381 432 991 1295 991 1295 1600 1295 1295 1600 1600 1600 1600 1600 1600 1905 1905 2210 2210 2515 2515 2819 2819 2819 2819 2819 3124 3124 3124 3429 3429 3429 3734 3734 3734 4039 4039 4039 4343 4343 4343 4648 4648 4648 4648 4648 4648 4648 4648 4648 4648 4648 4648

003 004 006 008 010 012 014 016 020 025 030 035 040 045 050 060

065

64.1

5.96

070

70.4

6.55

080

78.5

7.11

085

82.8

7.7

090

89.2

8.30

095

95.3

8.86

100

111.2

10.33

110

111.2

10.33

120

127.1

11.81

General Data Coils

Refrigerant Coil Circuits ( 1/2 Standard Refrigerant Coil Circuiting)


Dimensions
Model Size Coil Face Area Ft 2 2.5 4.3 6.1 7.9 9.7 12.5 15.3 31.5 37.3 43.2 49 54.8 M2 0.23 0.40 0.56 0.73 0.90 1.16 1.42 2.93 3.47 4.02 4.56 5.10 in 21 21 21 21 34 34 34 70 70 70 70 70 Actual Fin Height mm 533 533 533 533 864 864 864 1778 1778 1778 1778 1778 in 17 29 41 53 41 53 65 65 77 89 101 113 Finned Length mm 432 737 1041 1346 1041 1346 1651 1651 1956 2261 2565 2870 No of Dist Fin Height Piping Liquid 1/4 3/16 28.6 22.2 28.6 22.2 28.6 22.2 28.6 22.2 35 28.6 35 28.6 35 28.6 35 35 35 35 35 28.6 28.6 28.6 28.6 28.6 Suction O.D 41.2 41.2 41.2 41.2 41.2 41.2 41.2 41.2 41.2 41.2 41.2 41.2 -

003 004 006 008 010 012 014 016 020 025 030 035 040 045 050 060 065 070 080 085 090 095 100 110 120

1 1 1 1 1 1 1 2 2 2 2 2 -

70 70 70 70 70 -

14

General Data Coils

Refrigerant Coil Circuits ( 1/2 Interwined Refrigerant Coil Circuiting)


Dimensions
Model Size Coil Face Area Ft 2 2.5 4.3 6.1 7.9 9.7 12.5 15.3 17.1 21.0 26.0 31.5 37.3 43.2 49.0 54.8 64.0 70.8 77.6 84.4 91.1 97.9 104.5 M2 0.23 0.40 0.56 0.73 0.90 1.16 1.42 1.59 1.95 2.42 2.93 3.47 4.02 4.56 5.10 5.93 6.56 7.19 7.82 8.45 9.08 9.78 in 21 21 21 21 34 34 34 46 46 58 70 70 70 70 70 40 41 40 41 40 41 40 41 40 41 40 41 40 41 Actual Fin Height mm 533 533 533 533 864 864 864 1168 1168 1473 1778 1778 1778 1778 1778 1016 1041 1016 1041 1016 1041 1016 1041 1016 1041 1016 1041 1016 1041 in 17 29 41 53 41 53 65 53 65 65 65 77 89 101 113 113 113 125 125 137 137 149 149 161 161 173 173 185 185 Finned Length mm 432 737 1041 1346 1041 1346 1651 1346 1651 1651 1651 1956 2261 2565 2870 2870 2870 3157 3157 3480 3480 3785 3785 4089 4089 4394 4394 4699 4699 No of Distt Liquid 1/4 28.6 28.6 28.6 28.6 35 35 35 28.6 28.6 35 35 35 35 35 35 28.6 28.6 28.6 28.6 28.6 28.6 28.6 Piping 3/16 22.2 22.2 22.2 22.2 28.6 28.6 28.6 22.2 22.2 28.6 28.6 28.6 28.6 28.6 28.6 22.2 22.2 22.2 22.2 22.2 22.2 22.2 Suction O.D 41 41 41 41 41 41 41 41 41 41 41 41 41 41 41 41 41 41 41 41 41 41

003 004 006 008 010 012 014 016 020 025 030 035 040 045 050 060 065 070 080 085 090 095

1/1 1/1 1/1 1/1 1/1 1/1 1/1 1/1/1/1 1/1/1/1 1/1/1/1 1/1/1/1 1/1/1/1 1/1/1/1 1/1/1/1 1/1/1/1 1/1/1/1 1/1/1/1 1/1/1/1 1/1/1/1 1/1/1/1 1/1/1/1 1/1/1/1 1/1/1/1 1/1/1/1 1/1/1/1 1/1/1/1 1/1/1/1 1/1/1/1 1/1/1/1 -

100 110 120

15

General Data Filters

General Quantum XP air handling unit offers wide range of filters to meet air filtration requirement in various types of commercial and industrial air conditioning applications. Filter type offered are: (a) Washable and throwaway type flat filters (b) Bag and catridge type filters (c) Hepa filters (d) Carbon or gas filters, etc. Flat Filter

a) Washable Filter b) Throwaway Filter The filter media consist of selected synthetic fibers. An exclusive bonding technology provides the media with high numbers of fibers per square meter for a given weight. Its characteristics are relatively low resistance to air flow and a high dust holding capacity. The media can be cleaned. in warm water (300 - 400C) with addition of a household detergent if necessary. Drying should be done on a flat surface. by blowing with compressed air in the opposite direction of filter airflow. Unique pleat design assures total usage of the filter media, maximum dust holding capacity and extended service life. Its greater dust holding capacity not only extends replacement intervals, but considerably lengthens the service life of any other secondary filters in the systems. The media used is a lofted, high performance, nonwoven, reinforced cotton and synthetic fabric. Filter media shall be of high density glass mirco fibers laminated to all glass woven mesh backing. The filter media shall have an average arrestance of 90 - 92%. The filter is categorized as a 30% efficiency filter.
Throwaway Filter - Product Information Normal Sizes (inch) : 12 x 24 20 x 24, 24 x 24 Filter Depth (mm) : 50 Average Arrestance : 90 - 92% Average Efficiency : 25 - 30%

Washable Filter - Product Information Normal Sizes (inch) : 12 x 24 20 x 24, 24 x 24 Filter Depth (mm) : 50 Average Arrestance : 80 - 85%

Flexible and Varied Filter Offering for IAQ and process filteration.

16

General Data Filters

High Efficiency Filter Section a. Bag Filter The filter is an extended surface nonsupported pocket filter which offers high efficiency, low resistance, compactness and unusual dust-holdding capacity. When placed in ventilating system, the pockets of the filtering media inflate for maximum efficiency and dust holding capacity. Filter efficiency is determined by the size and quality of fibers per square inch in each efficiency category. The media is manufactured to rigid specifications that assure an extremely large amount of dirt-catching surface area to catch mircoscopic contaminants. The exclusive pocket design allows every channel to fully inflate while maintaining the amount of space between pockets. Clean air can freely exit from front to back. Some manufacturers design permit adjacent pockets to touch when inflated which signficantly reduces dust holding capacity. Each filter pocket is attached to a support frame that fits into a U-channel header. Each pocket support frame is then mechanically fastened to the adjacent frame forming a rigid construction. The positive locking arrangement forms an air tight seal and also virtually eliminates the possibility of pocket separation from the header as resistance increase. b. Cartridge Filter
Bag Filter - Product Information Normal Sizes (inch) Filter Depth (mm) Average Efficiency : 12 x 24 20 x 24, 24 x 24 : 381 : 60 - 65% 80 - 85% 90 - 95%

The filters are ideally suited to variable volume systems. Being totally rigid, performance is not affected by changes in air velocity or fan shutdown, and their configuration is not altered by accumulation of dirt. High loft glass fiber media is laminated to which provides positive support, optimizes dust holding capacity, and precludes fiber emission, as compared to flat glass media. All double wall fiber board contour stabilizers, diagonal support provide rigidity, durability, consistent integrity and performance reliability throughout the filters life. The lofted media and exclusive radial pleats provide a high dust holding capacity, extending the life of the filter. The filter will operate at air volumes considerably below rates velocity and capacity. Initial resistance is reduced, performance is improved and service life is extended.

Cartridge Filter - Product Information Normal Sizes (inch) Filter Depth (mm) Average Efficiency : 12 x 24 20 x 24, 24 x 24 : 100 : 60 - 65% 80 - 85% 90 - 95%

17

General Data Filters


Filter Quantity and Sizes (Nominal)
a. Flat, Bag and Cartridge Filters
Model Size 003 004 006 008 010 012 014 016 020 025 030 035 040 045 050 060 065 070 080 085 090 095 100 110 120 Filter Face Area Sq. Ft. 3.3 3.3 6.7 6.7 10.7 10.7 16.0 20.0 24.0 30.0 36.0 42.0 48.0 54.0 60.0 70.0 76.0 84.0 90.0 98.0 104.0 112.0 128.0 128.0 144.0 12 X 24 2 2 3 2 3 3 3 5 8 6 9 7 10 8 8 Filter Sizes (inch) 20 X 24 1 1 2 2 2 2 3 24 X 24 4 6 6 9 9 12 12 15 15 15 18 18 21 21 24 32 32 32

18

General Data Filters


Filter Dimension (Nominal) and Arrangement
Flat Filter, Bag Filter & Cartridge Filter

19

General Data Filters

XP Std. Model 003 (0404) 004 (0604) 006 (0804) 008 (1004) 010 (0806) 012 (1006) 014 (1206) 016 (1008) 020 (1208) 025 (1210) 030 (1212) 035 (1412) 040 (1612) 045 (1812) 050 (2012) 060 (2014) 065 (2214) 070 (2414) 080 (2614) 085 (2814) 090 (3014) 095 (3214) 100 (3216) 110 (3217) 120 (3218)

Final Filter (HEPA) Casing Size ( X 155 parametric) 0605 0605 0905 0905 0907 0907 1307 1109 1309 1311 1313 1513 1713 2013 2213 2215 2215 2615 2615 3015 3015 3215 3217 3217 3218 W 1090 1090 1555 1555 1555 1555 2175 1865 2175 2175 2175 2485 2795 3260 3570 3570 3570 4190 4190 4810 4810 5120 5120 5120 5120

50mm CASING DIMENSION H 1055 1055 1055 1055 1365 1365 1365 1675 1675 1985 2295 2295 2295 2295 2295 2605 2605 2605 2605 2605 2605 2605 2915 2915 3070 L 2640 2640 2640 2640 2485 2485 2485 2485 2485 2485 2485 2330 2330 2330 2330 2330 2330 2330 2330 2330 2485 2485 2485 2485 2485

OUTLET OPENING B XA 465 X 310 465 X 310 465 X 310 620 X 310 620 X 310 620 X 310 775 X 310 775 X 465 775 X 465 930 X 465 930 X 620 930 X 775 1085 X 775 1240 X 775 1240 X 775 1705 x 775 1860 X 775 2015 X 775 2170 X 775 2170 X 775 2325 X 930 2480 X 930 2480 X 930 2480 X 930 2480 X 930

Discharge Plenum Section L1 775 775 775 775 775 775 775 775 775 775 775 930 930 930 930 930 930 930 930 930 1085 1085 1085 1085 1085

20

General Data Filters


Filter Dimension (Nominal) and Arrangement
Final Filter

21

General Data Air Pressure Drop


Damper Torque (Inch-lbs) at 1 Air pressure drop across the damper
Dimensions
Intake Damper or Mixing Box (per damper) (Inch-Ibs) 7 10 13 16 19 24 28 28 28 28 38 44 50 56 56 84 84 98 98 112 112 112 112 112 112

Model Size 003 004 006 008 010 012 014 016 020 025 030 035 040 045 050 060 065 070 080 085 090 095 100 110 120

Face Damper (Inch-Ibs) 8 13 18 23 29 37 45 52 63 80 98 115 132 150 167 197 197 197 197 197 197 197 197 197 197

External Face & Bypass (Inch-Ibs) 12 20 27 34 38 48 59 70 85 111 129 152 174 197 220 265 265 265 265 265 265 265 265 265 265

22

Dimensional Data HDT (Single Motor) Unit Dimensions

23

Dimensional Data HDT (Dual Motor) Unit Dimensions

24

Dimensional Data HDT Unit Weight (kg)

Fan and Coil sections (without motor weight)


Fan Section Weight Fan Arrangement Model Size 003 004 006 008 010 012 014 016 020 025 030 035 040 045 050 060 065 070 080 085 090 095 100 110 120 Front-Top and Front-Bottom 88 107 132 154 193 246 264 301 322 447 467 556 632 654 759 785 952 978 1113 1139 1165 1191 1650 2054 2092 Top-Front and Top-Back 88 107 144 166 206 261 280 317 356 467 489 580 656 679 788 815 986 1014 1148 1175 1202 1540 1745 2151 2193 1 126 156 186 215 217 245 268 302 339 375 428 472 517 569 615 678 746 795 842 905 953 1000 1213 1250 1293 2 130 163 194 226 234 267 296 330 373 418 482 534 590 653 709 789 873 933 992 1070 1128 1186 1450 1507 1571 4 138 175 211 246 263 306 345 386 440 502 592 663 735 817 892 1012 1125 1207 1287 1392 1471 1552 1915 2014 2111 Coil Section Weight Coil Row 6 146 187 227 267 293 347 396 437 502 582 694 783 873 976 1069 1225 1368 1472 1574 1708 1809 1910 2370 2511 2642 8 170 222 272 322 350 418 480 530 610 709 848 961 1077 1208 1326 1524 1705 1838 1970 2140 2271 2401 2981 3162 3328 10 178 234 289 343 380 459 531 581 673 789 950 1081 1215 1366 1503 1738 1948 2103 2257 2456 2608 2761 3437 3659 3859 12 186 247 305 364 411 500 582 633 735 868 1052 1201 1353 1525 1680 1951 2192 2369 3545 2771 2945 3118 3893 4155 4389

1: Coil weight is the operating weight

25

Dimensional Data HDT Unit Weight (kg)


Fan + Coil + Filter Sections (without motor weight)
Fan Section Weight Fan Arrangement Model Size Front-Top and Front-Bottom 88 107 132 154 193 246 264 301 322 447 467 556 632 654 759 785 952 978 1113 1139 1165 1191 1650 2054 2092 Top-Front and Top-Back 88 107 144 166 206 261 280 317 356 467 489 580 656 679 788 815 986 1014 1148 1175 1202 1540 1745 2151 2193 1 126 156 186 215 217 245 268 302 339 375 428 472 517 569 615 678 746 795 842 905 953 1000 1213 1250 1293 2 130 163 194 226 234 267 296 330 373 418 482 534 590 653 709 789 873 933 992 1070 1128 1186 1450 1507 1571 Coil Section Weight Coil Row 4 138 175 211 246 263 306 345 386 440 502 592 663 735 817 892 1012 1125 1207 1287 1392 1471 1552 1915 2014 2111 6 146 187 227 267 293 347 396 437 502 582 694 783 873 976 1069 1225 1368 1472 1574 1708 1809 1910 2370 2511 2642 8 170 222 272 322 350 418 480 530 610 709 848 961 1077 1208 1326 1524 1705 1838 1970 2140 2271 2401 2981 3162 3328 10 178 234 289 343 380 459 531 581 673 789 950 1081 1215 1366 1503 1738 1948 2103 2257 2456 2608 2761 3437 2659 3859 12 186 247 305 364 411 500 582 633 735 868 1052 1201 1353 1525 1680 1951 2192 2369 3545 2771 2945 3118 3893 4155 4389 Filter Section Length .L3

2 Flat Filter 9 10 12 14 15 16 18 19 21 24 27 29 32 35 37 41 44 47 50 53 56 59 63 64 69

2 Flat Filter + 15 Bag Filter 38 42 50 54 57 62 70 72 79 88 97 106 114 123 132 144 152 162 171 181 190 200 213 215 231

2 Flat Filter + 4 Cartridge Filter 21 23 29 32 36 38 46 50 56 65 73 82 90 99 107 120 128 139 147 158 166 177 194 195 214

003 004 006 008 010 012 014 016 020 025 030 035 040 045 050 060 065 070 080 085 090 095 100 110 120

1: Coil weight is the operating weight 2: Filter section weight includes filter media

26

Dimensional Data HDT Unit Weight (kg)

Fan + Coil + Filter and Mixing Sections (without motor weight)


Fan Section Weight Fan Arrangement Model Size Front-Top and Top-Front and Front-Bottom Top-Back 88 107 132 154 193 246 264 301 322 447 467 556 632 654 759 785 952 978 1113 1139 1165 1191 1650 2054 2092 88 107 144 166 206 261 280 317 356 467 489 580 656 679 788 815 986 1014 1148 1175 1202 1540 1745 2151 2193 1 126 156 186 215 217 245 268 302 339 375 428 472 517 569 615 678 746 795 842 905 953 1000 1213 1250 1293 2 130 163 194 226 234 267 296 330 373 418 482 534 590 653 709 789 873 933 992 1070 1128 1186 1450 1507 1571 Coil Section Weight Coil Row 4 138 175 211 246 263 306 345 386 440 502 592 663 735 817 892 1012 1125 1207 1287 1392 1471 1552 1915 2014 2111 6 146 187 227 267 293 347 396 437 502 582 694 783 873 976 1069 1225 1368 1472 1574 1708 1809 1910 2370 2511 2642 8 170 222 272 322 350 418 480 530 610 709 848 961 1077 1208 1326 1524 1705 1838 1970 2140 2271 2401 2981 3162 3328 10 178 234 289 343 380 459 531 581 673 789 950 1081 1215 1366 1503 1738 1948 2103 2257 2456 2608 2761 3437 2659 3859 12 186 247 305 364 411 500 582 633 735 868 1052 1201 1353 1525 1680 1951 2192 2369 3545 2771 2945 3118 3893 4155 4389
2 Flat Filter

Filter Section (kg)


Mixing 2 Flat Filter + Box / Rear 4 Cartridge or Top Inlet Filter Section Weight (kg)

2 Flat Filter + 15 Bag Filter

003 004 006 008 010 012 014 016 020 025 030 035 040 045 050 060 065 070 080 085 090 095 100 110 120

9 10 12 14 15 16 18 19 21 24 27 29 32 35 37 41 44 47 50 53 56 59 63 64 69

38 42 50 54 57 62 70 72 79 88 97 106 114 123 132 144 152 162 171 181 190 200 213 215 231

21 23 29 32 36 38 46 50 56 65 73 82 90 99 107 120 128 139 147 158 166 177 194 195 214

55 65 75 85 81 91 103 97 109 123 129 146 174 188 193 213 219 264 271 320 328 336 340 345 353

1: Coil weight is the operating weight 2: Filter section weight includes filter media

27

General Data VDT - Unit Dimensions

28

Dimensional Data VDT Unit Weight (kg)


Fan and Coil sections (without motor weight)
Fan Section Weight Fan Arrangement Model Size 003 004 006 008 010 012 014 016 020 025 030 035 040 045 Front-Top and Front-Bottom 103 132 162 190 229 288 313 350 378 510 540 638 722 755 Top-Front and Top-Back 103 132 174 202 242 302 329 366 412 531 561 662 746 780 1 153 190 227 262 289 327 361 424 442 541 610 669 731 800 2 158 197 236 273 306 349 389 452 476 584 664 733 804 884 4 165 209 252 293 335 388 438 508 543 668 774 860 949 1048 Coil Section Weight Coil Row 6 173 221 268 314 365 429 489 559 605 748 876 980 1087 1207 8 189 246 302 357 410 486 558 637 698 858 1012 1139 1270 1417 10 197 258 319 378 440 527 609 688 761 938 1114 1259 1408 1575 12 205 271 335 399 471 568 660 740 823 1017 1216 1379 1546 1734

1: Coil weight is the operating weight

29

Dimensional Data VDT Unit Weight (kg)

Fan + Coil + Filter Sections (without motor weight)


Fan Section Weight Fan Arrangement Model Size Front-Top and Front-Bottom 103 132 162 190 229 288 313 350 378 510 540 638 722 755 Top-Front and Top-Back 103 132 174 202 242 302 329 366 412 531 561 662 746 780 1 153 190 227 262 289 327 361 424 442 541 610 669 731 800 2 158 197 236 273 306 349 389 452 476 584 664 733 804 884 Coil Section Weight Coil Row 4 165 209 252 293 335 388 438 508 543 668 774 860 949 1048 6 173 221 268 314 365 429 489 559 605 748 876 980 1087 1207 8 189 246 302 357 410 486 558 637 698 858 1012 1139 1270 1417 10 197 258 319 378 440 527 609 688 761 938 1114 1259 1408 1575 12 205 271 335 399 471 568 660 740 823 1017 1216 1379 1546 1734 Filter Section Length .L3

2 Flat Filter 9 10 12 14 15 16 18 19 21 24 27 29 32 35

2 Flat Filter + 15 Bag Filter 38 42 50 54 57 62 70 72 79 88 97 106 114 123

2 Flat Filter + 4 Cartridge Filter 21 23 29 32 36 38 46 50 56 65 73 82 90 99

003 004 006 008 010 012 014 016 020 025 030 035 040 045

1: Coil weight is the operating weight 2: Filter section weight includes filter media

30

Dimensional Data VDT Unit Weight (kg)

Fan + Coil + Filter and Mixing Sections (without motor weight)


Fan Section Weight Fan Arrangement Model Size Front-Top and Top-Front and Front-Bottom Top-Back 103 132 162 190 229 288 313 350 378 510 540 638 722 755 103 132 174 202 242 302 329 366 412 531 561 662 746 780 1 153 190 227 262 289 327 361 424 442 541 610 669 731 800 2 158 197 236 273 306 349 389 452 476 584 664 733 804 884 Coil Section Weight Coil Row 4 165 209 252 293 335 388 438 508 543 668 774 860 949 1048 6 173 221 268 314 365 429 489 559 605 748 876 980 1087 1207 8 189 246 302 357 410 486 558 637 698 858 1012 1139 1270 1417 10 197 258 319 378 440 527 609 688 761 938 1114 1259 1408 1575 12 205 271 335 399 471 568 660 740 823 1017 1216 1379 1546 1734 Filter Section (kg)
Mixing 2 Flat Filter + Box / Rear 4 Cartridge or Top Inlet Filter Section Weight (kg)

2 Flat Filter

2 Flat Filter + 15 Bag Filter

003 004 006 008 010 012 014 016 020 025 030 035 040 045

9 10 12 14 15 16 18 19 21 24 27 29 32 35

38 42 50 54 57 62 70 72 79 88 97 106 114 123

21 23 29 32 36 38 46 50 56 65 73 82 90 99

55 65 75 85 81 91 103 97 109 123 129 146 174 188

1: Coil weight is the operating weight 2: Filter section weight includes filter media

31

Installation Consideration Define Unit Handling Left or Right

Unit handling, LEFT or Right for coil connectors, drain, door loction & etc. Is expresswd when facing the airflow through the coil.

32

Installation Consideration And Service Clearance

The purpose of this section is to provide the Quantum XP site installation consideration. Refer to Installation, Operation and Maintenance manual for detailed installation information. When selecting and preparing the unit site, follow these guidelines: 1. Ensure that the site can support the total weight of the unit. 2. Allow sufficient space for service access. The below figure give the recommended space allowances for filters, coil removal, fan shaft removal and motor starter maintenance. As unit configurations will vary, refer to unit submittals for specific location of access doors, accessories, motor starter, etc. 3. Confirm that the foundation of the

mounting platform is large enough to include the unit dimensions plus services access. Refer to unit submittals for specific dimension. Certain unit maybe suspended from the ceiling. The recommended method for ceiling suspending air handler is with structural channels that run the full length of the unit. The factory shall provide the support with an external support at the base. Do not suspend air handler from the top of the unit. Serious safety risks exist if the unit is not suspended in the proper manner. 4. The floor or foundation must be level for proper coil drainage and condensate flow. 5. Allow the proper height for coil pip-

ing and condensate drain requirements. It may be necessary to elevate the unit when piping the con densate drain. Insufficient height could inhibit condensate drainage and result in flooding the unit or equipment room. 6. Provide adequate lighting for maintenance personnel to perform maintenance duties. 7. Provide permanent power outlets in close proximity of the unit for installation and maintenance.

33

Installation Consideration Coil Connection Dimension


Casing Construction Horizontal / Vertical Draw Through - Chilled And Hot Water Coil Connection Dimension

34

Installation Consideration Fan Outlet Dimensions HDT

35

Installation Consideration Fan Outlet Dimensions VDT

36

Mechanical Specifications
posed gaps between panels and frame, to minimize potential air leaks. Drain Pans Coil, moisture eliminator and humidifier shall be provided with an insulated, galvanized or stainless steel (option), dual pitch sloping drain pan to allow for proper condensate removal. The galvanized drain pan shall be painted with a mastic compound (bitumen) for corrosion protection. Access and Inspection Doors Access doors shall be constructed with a double-wall panel that compresses evenly a durable seal onto a rigid frame. The seal around the full perimeter of the access doors frame shall be used to prevent air leakage. The doors shall be hinged and able to be lifted off or removed totally for easy access. View Window A view window shall be made of 5mm thick transparent Plexiglass type on inner and outer wall panel with a rubber grommet seal and fitted on double wall panel. The size shall be 150 x 150mm The mounting location shall be flexible and upon customers requirement. Special window size shall be an option.

General The units must be rigged and lifted in strict accordance with the installation. Operation and Maintenance manual. The units are to be installed in strict accordance with the specifications. Units may be shipped fully assembled or disassembled to the minimum module size in accordance with shipping or jobsite requirements. Units shall have break point if manufacturer found appropriate for easy handling and transporatation. Break points shall have full independent external thermal break frames. Unit Construction The casing shall have a perimeter thermal break frame with a modular system based on standardized double wall panels. Removal of side panels must not effect the structural intergrity of the unit. Casing strength shall be designed to meet European Standard EN 1886: 1998, Class D1 The framework shall be made from non-corrosive recyclable extruded aluminum channels fitted together nonmetal corner pieces. A thermal break construction is mondatory. The casing panel shall be attached to the frame through a self-locking mechanism represented by a wedge and frame, exerting pressure evenly onto the panel and seal attached to the frame, and hence a better air tight cabinet construction. The casing shall be designed to meet Eurovent air leakage requirement, Class C. The casing shall be able to with stand up to 10 inches of total static pressure.

Closed-cell foam gasketing shall be provided where modules where modules are joined. The floor panels shall have double wall construction to allow maintenance personnel access without damage to the isulation. The whole unit shall be mounted on a galvanized sheet steel base frame for case of shipment and handling. The minimum height of the floor-mounting base shall be 120mm and designed to ensure air circulation and avoid entrapment of moisture below the unit. The base frame is to be used in lieu of concrete plinths or other additional bases that are used on site. However for high static pressure application additional concrete plinths or other additional bases is required at site to raise the AHU for drain pans U-trap. Double-Wall Panel The outer panel wall shall be painted with Colorbend paint that and shall allow for easy cleaning. The inner wall shall be galvanized steel. The paint shall be ultra violet resistant, weather resistant for outdoor application, offering excellent weather resistance properties. The panels shall be 50mm thick double wall type with injected polyurethane foam insulation for a rigid non-vibration construction. The panel insulation shall not absorb moisture and must be not resistant. The insulation material shall be totally enclosed in the panel to avoid any possibility of insulation being exposed to air stream. The panel insulation shall have a heat transfer K value of 0.02 w/mK. Exposed Insulation system shall meet UL 94, standard for safety and flameability of plastic material for parts in devices and appliances. The panels shall be flush mounted, leaving no ex-

37

Mechanical Specifications

Service Light A factory-mounted, weather-resistant (enclosed and gasketed), vapor-tight, light fixture shall be provided. fixture shall be equipped with plastic switch box, single phase wiring, PL lamp comes with ballast and reflector. Fan Module The fan assembly shall be checked and dynamically balanced to ISO 1940 on equivalent. Fan shaft shall be properly size and protectively coated. Fan wheels shall be keyed to fan shaft to prevent slipping. Fan shafts shall be solid and designed so that fan shaft does not pass through its first critical speed as the unit comes up to its rated rpm. Fan modules shall be provided with an access door. Access side for both side of fan shall be an option. FC Fan Modules Fan shall be double-width, double-inlet, and multi-blade type as produced by the unit manufacturer. Fan shall be forward curved (FC) as required for stable operation, low noise and optimum energy efficiency. Fan shall be equipped with bearings with an L-50 life (average life) of up to 200,000 hours. The multi blade shall be made of galvanized steel and the solid shaft shall be made of carbon steel: C45, machined and polished to tolerance of standard ISO 286-2-Grade G6. Protective coat of anti rusting shall be applied to all bare surfaces of shafts at the factory. The fans shall be licensed to bear the AMCA Air and Sound Certified Ratings seal. The test standard used shall be ANSI/AMCA 210. ANSI/ ASHRAE Standard 51 Laboratory Method of Testing Fans for Rating and AMCA 300 Reverberant Room method for Sound Testing of fans.

BC Fan Modules Fan shall be double-width, double-inlet, and multiblade type as produced by the unit manufacturer. Fan shall be backward curve (BC) as required for stable operation, high static pressure and optimum energy efficiency. Fan shall be equipped with bearings with an L-50 life (average life) of up to 200,000 hours. The multiple blades shall be made of treated steel with paint for corrosion resistant. The solid shaft shall be made of carbon steel: C45, machined and polished to tolerance of standard ISO 286-2-Grade G6. Protective coat of anti rusting shall be applied to all bare surfaces of shafts at the factory. The fans shall be licensed to bear the AMCA Air and Sound Certified Ratings seal. The test standard used shall be ANSI/AMCA 210, ANSI/ ASHRAE Standard 51 Laboratory Method of Testing Fans for Rating and AMCA 300 Reverberant Room Method for Sound Testing of Fans. AF Fan Modules Shall be customized upon request. The fan shall be double-width, doubleinlet, multiple blade type as produced by the unit manufacturer. Fan shall be backward inclined airfoil (AF). Fan Modulation a) Inlet Guide Vanes (Option) For variable air volume applications, airflow of BC fan type fans shall be modulated by inlet guide vanes. Actuator shall be provided as an option. b) Variable Frequency Drive (Option) For variable air volume applications, airflow shall be modulated by a vari able frequency drive controlling fan speed.

Fan Isolation Fan connection shall be isolated from unit casing by a flexible canvas duct mounted at fan discharge outlet. a) One-Inch Spring Isolators (Option) Fan and motor assembly shall be internally isolated from the unit cas ing with 1-inch deflection spring isolators, furnished and installed by the unit manufacturer. b) Two-inch Spring Isolators (Option) Fan and motor assembly shall be internally isolated from the unit casing. The isolation system shall be designed to take higher isolation efficiency than 1spring isolator. Drives The drive assembly shall consist of Vbelt taper-lock pulley and electric motor. The V-belt type shall be SPZ, SPA, SPB or SPC grades, oil and heat resistant, antistatic and avoiding electric discharges. The pulley and shaft assembly shall be using taperlock bush with Allen set screws for easy and quick assemble and dis-assemble process. Drive shall be selected at 1.5 service factor. a) Fixed Pitch Drives shall be constant speed with fixed pitch sheaves.

38

Mechanical Specifications

Motors Motor shall be mounted integral to an isolated fan assembly furnished by the unit manufacturer. Motor shall be mounted inside the unit casing on a sliding base to permit adjustment of drive belt tension. Standard motor shall be horizontal foot mounting, induction motor squirrel cage, totally enclosed fan-cooled with IP55 protection with class F insulation and suitable for operation at ambient temperature of 40 degree C. Motor Options a) 380-415 Volt /3 pH /50 Hz (Standard) b) 200 Volt /3 pH/ 50 Hz c) 200 Volt /3 pH/ 60 Hz d) 230 Volt /3 pH/ 60 Hz e) 380 Volt /3 pH/ 60 Hz f) 440 Volt /3 pH/ 60 Hz g) 460 Volt /3 pH/ 60 Hz h) High Efficiency Motors i) Premium Efficiency Motor j) Customer Selected Motor Sources k) Explosion Proof Motor l) Dual Speed Motor Fan Module Option Belt guard unit shall be provided with a painted metal sheet belt guard.

Coil Module Coil shall be installed such that unit casing enclose headers and return bends. Coil shall be designed to maximize the utilization of the available unit cross-section area. Coil connections shall be clearly labeled on outside of units. Coil shall be catridge type mounted on steel channel for easy removability. Coils shall have aluminum fins and seamless copper tubes. Coated aluminum (for corrosion protection used near the sea) and copper fins shall be an option. The fins shall be sine-wave design with slits for better heat transfer efficiency and moisture carry-over limit performance. Fins shall have collars drawn, belled and firmly bonded to tubes by mechanical expansion of the tubes. Capacities, pressure drops and selection procedure shall be designed in accordance with ARI Standard 410. The copper tube shall be 0.5 inch OD. Coil casing shall be 1.5mm thick galvanized steel (standard) or stainless steel (option) or with formed end supports and top and bottom channels. Coil casing shall be a series of drain holes at the bottom channels to insure condensate drainage. If stacked coil in the unit, intermediate drainpan shall be installed between coils to drain condensate to the main drain pans without flooding the lower coils or passing condensate through the airstream of the lower coil. The coil working pressure at site shall not exceed the leak test value on each coil type given below. Water Coils Supply and return headers shall be clearly labeled on the outside of the unit to ensure that direction of coil wa-

ter flow is counter to direction of unit airflow. Coils shall be tested to 375 psig. The headers shall be round steel pipe with threaded. All headers with air venting and plug. constructed of BSPT external shall be fitted water draining

Header connection option Unthreaded copper header connection Copper header with BSPT external threaded brass adaptor for quick job site connection. Steel header with steel flanges for quick job site connection. Refrigerant Cooling Coils Suction and liquid line connections plate fins and seamless copper tubes shall be clearly labeled on the outside of the unit. Coils shall be leak tested to 450 psig (17 Bar) air pressure under water. After testing, insides of coils are to be dried; all connections are to be sealed and coils shall be shipped with a charge of dry nitrogen. Suction headers shall be constructed of cooper tubing. Suction connections shall penetrate unit casings to allow for external connections to refrigerant lines. Coils shall have equqlizing vertical distributors sized according to the capacities of the coils. Steam Heating Coils Steam coils shall be pitched in the unit for proper drainage of steam condensate from coils. Coils shall be leak tested to 375 psig air pressure under water. Steam header and condensate header connections are to be constructed of round steel. Steam header connection shall be located opposite with condensate header.

Varied Coil Types and Material

39

Mechanical Specifications

Filter Modules Filter sections shall have filter racks, an access door for filter removal and block-offs as required to prevent air bypass around filters. Modules shall be supplied with 2-inch or 4-inch angled or high capacity, catridge, bag and final filters. Filter shall be sized so as not to exceed scheduled face velocities. Pleated Filter Media (Throwaway) Filters shall be 2-inch or 4-inch thick non-woven fabric, treated with adhesive and continuosly laminated to a supported steel wire grid. Filters shall have a rated average dust spot efficiency of not less than 25 to 30 percent when tested in accordance with ASHRAE 52-1-1992 atmospheric dust spot method. Filter access shall be accessed from either right or left hand side as standard. Back access shall be an option. Washable or Permanent Filters Filters shall be 2-inch synthetic fibers capable of operating up to 600 fpm face velocity. Filter media shall be layers of cleanable wire maze. Filter frame shall be constructed of galvanized steel. Filter access shall be accessed from either right or left hand side as standard. Back access shall be an option. Hi-Capacity Filters Filter shall be 2-inch throwaway as standard. Option for pleated media and washable. The filter shall be fixed in angular (Zig-zag) form for higher duct holding capacity. Filter frame shall be consrtucted of galvanized steel. Filter accessed from either right or left hand side a standard. Cartridge Filters Filter shall be constructed by pleating a continuous sheet of fine-fiber glass media into closely spaced pleats with safe-edged separators. This filter shall be sealed into a fiber boards frame as-

sembled in a rigid manner to prevent air leakage. All cartridge filters shall be furnished with a 2-inch prefilter to provide extended cartridge life. Filters shall have a rated average dust spot efficiency of not less than 60 percent when tested in accordance with ASHRAE 52-1-1992 atmospheric dust spot method Manufacturer shall supply back access filter rack support and holding clips that capable of holding cartridge filters and prefilters. Bag Filters Filters shall be synthetic fiber media with spun backing to keep synthetic fibers from eroding downstream. Stitching method shall permit bag to retain pleat shape and air pocket when in operation without the use of wire basket support. Filters shall have a rated average dust spot efficiency of not less than 60 percent when tested in accordance with ASHRAE 52-1-1992 atmospheric dust spot method.

tors shall be mounted with the out side air damper linked normally closed and the return air damper linked normally open b) Face/bypass Damper Actuators indicated on the order and control drawings. c) Inlet Guide Vane Actuators Actuators shall be mounted with the IGVs linked normally closed. d) Averaging Temperature Sensors Averaging (Thermistor type) sensor shall be serpentined with capillary clips across the unit as engineered by the air handling unit manufacturer. e) Low-Limit Switches A manual reset low limit switch shall be installed as an option. f) Airflow Switches A differential pressure switch piped to both sides of the filter shall indicate filter status. g) Dirty Filter Switches A differential pressure switch piped to both sides of the filter shall indicate filter status. h) Dirty Filter Switches A differential pressure switch pipe to the discharge and suction sides of the fan shall indicate fan status. i) Customer Interface Relays 5 amp DPDT relays shall be provided as required for each binary output of the controller for customer interface to; supply, return and exhaust fan motor starters; relief dampers; pumps; condensing units; etc. j) Electonic end devices

Factory-Mounted Direct Digital Control (DDC)


Factory-mounted DDC systems shall be engineered mounted, wired and tested by the air handling unit manufacturer to reduce installed costs, save time, and improve reliability. Each control system shall be fully functional in a standalone mode or can be tied to a building automation system with a simple pair of wires. Direct Digital Controller A dedicated programmable direct digital controller with the appropriate point capabilities shall be unit mounted on each air-handling unit. A screen and keypad shall be provided to facilitate local monitoring, trouble shooting and changing of set points. Factory-Mounted Control Options a) Mixing Box Damper Actuators Actua-

40

Mechanical Specifications

Field-Mounted Control Options Control Valves Control valves can be provided by the air handling unit manufacturer and field piped by the piping contractor. Power and signal wiring shall be by a simple quick connect.

Space Temperature Sensors Thermister type sensors shall be provided as required for field wiring.

Outside Air Sensors Thermister type sensors shall be provided as required for filed wiring. All factory-mounted controls shall be covered by the air handling manufacturers standard warranty.

The manufacturer has a policy of continuous product improvement, and reserves the right to alter any details of the products at any time without notice

41

Literature Order Number File Number Trane www.trane.com For more information, contact your local district office Supersedes Stocking Location

CLCP - PRC001-EN (November 2009)