23.5.2013/PK VAMPSET versions Latest public revision 2.2.122 (For firmware V210) Revision 2.2.1182.2.122 08.05.

2013 minor fix for devices with smaller logic left menu updating from device fixed communication settings: com port list updating fixed logic usage display has now three numbers, indicating inputs, memory and outputs mouse wheel support added help/homepage changed to www.schneider-electric.com Revision 2.2.117 04.04.2013 reading protection stages could fail in time stamps VEA tester removed faster group refresh after writing settings to device UL1y and UL1z scaling support added for virtual measurement Revision 2.2.116 15.03.2013 GOOSE Subscriber network input bit index now can be updated using SCL files. Revision 2.2.115 18.02.2013 ICD generation fix: BUG 571 - ICD-File Generation with Quick Connect (F11) and Connect Device (F5) Revision 2.2.1132.2.114 30.01.2013 ICD generation supports now edition 2 image Fixed problem with updating RptId from SCD file Revision 2.2.1112.2.112 18.12.2012 Fixes on closing password when disconnecting device Auto com port selection added to communication settings. When USB com port is added, Vampset selects it when user makes new connection. This can be used for VAMP5X and VAMP3XX devices Full group refreshing fixes Revision 2.2.1082.2.110 14.12.2012 Full group refresh from device after changing parameter values, changing the visible group and connecting to device BUG 544: active signal names in matrix fixed BUG 488: last window position is saved BUG 511: Select group(s) text fixed BUG 381: Boot pending text fixed BUG 365: active signals now updating also in block matrix view BUG 336: sublocation fixed BUG 206: text box fixed for large font scaling Reading available COM ports fixed

1 (11)

Revision 2.2.107 15.11.2012 IDE generation: variable array for harmonics and SDO->DO in datasets support Revision 2.2.106 09.11.2012 ICD file generation changes: support for NARI SCADA Revision 2.2.105 18.10.2012 Analog GOOSE values support added: creating ICD file updated Revision 2.2.104 10.10.2012 EDS file reading: line feed bug fixed Revision 2.2.103 8.10.2012 About & splash window fixed for Schneider version Revision 2.2.102 27.9.2012 2.2.102 WIMO firmware update: DB data buffer is allocated only once, not again when db data fails Revision 2.2.101 27.9.2012 More fixes to WIMO sw updating via ethernet netport can be given via command line Revision 2.2.99 25.9.2012 Update linked parameters when doing matrix connections from the logic editor, to prevent duplicated OMC_ parameters with inconsistent values. Avoid crash when trying to insert too many functions per block in the logic editor Revision 2.2.98 14.9.2012 run-scripts: if device outputs multiple lines, all are added to log Revision 2.2.97 5.9.2012 Supports logic output redirection. Logic output redirects are handled so that the logic outputs will stay with the logic function they were connected to when editing the logic configuration. Revision 2.2.96 4.9.2012 Wimo sw update via ethernet fixed Language packet for G5 devices are generated using only translated lines to get smaller filesize Virtual meas: support added for U12y, U12z, U31 Revision 2.2.95 24.7.2012 Arc matrix support (32bits outputs) Revision 2.2.94 31.5.2012 Since APPID in GOOSE Subscriber configuration is in Hex format configuration of NIs according to SCD file needed to be corrected Revision 2.2.93 19.4.2012 Dynamic datasets (persistent) can be created according to SCD file Revision 2.2.92 26.3.2012 Dynamic datasets (persistent) are added to ICD file

2 (11)

Revision 2.2.91 14.3.2012 Fixed problem with ProfiBus/EthernetIP/DeviceNet views caused by change made for IEC 61850 in version 2.2.90 Revision 2.2.90 21.2.2012 Visualization of faultlog2 list modified: list can become shorter (used in IEC 61850 dynamic datasets visualization) Revision 2.2.89 10.2.2012 Support for 3XX Revision 2.2.88 18.1.2012 Creation of ICD offline is supported Revision 2.2.87 18.1.2012 Firmware updating fixes: BUG 321: db data buffer size increased BUG 298: support for manufacturer DeviceID "new/old method" text renamed Revision 2.2.86 21.12.2011 BUG 311: speed changing fixed for firmware (USB file) updating for old devices, for example VAMP40 5.75->6.88 Revision 2.2.85 1.12.2011 ICD generation: LLN0 elements in DS, 16 RCBs Revision 2.2.802.2.84 24.11.2011 BUG 295: major fix for firmware updating of G5 devices. Older versions than 2.2.84 should not be used for updating G5 firmwares (V10.xx). Updating firmwares V6.xx (or older) are not affected. Only G5 devices are affected. Only small amount of G5 devices can have this problem, but because of the risk, version 2.2.84 should be used only. Fixed ICD file generation (no unused LN types, multipliers as text) Added visualization of line differential diagram LDP diagram changes Fixed problem with updating time server IP from SCD file Revision 2.2.772.2.79 17.6.2011 BUG 192: firmware update continues even if external flash is empty BUG 195: harmonic display bars cannot go too high BUG 196: waiting for boot message changed BUG 203: fix for SpaM reading problem BUG 204: closing com fixed BUG 205: virtual meas is set off before booting device and closing com BUG 207: protocol selections are written first and relay booted, before writing protocol specific data BUG 215: scandinavian characters in TestedBy fixed BUG 209: fix for VAMP321 firmware updating BUG 218: LCD contrast (and other items which are not sent by write all settings) are now sent also by write current view, if they have changed (red values). In case not changed, they are not sent. BUG 219: Online meas display fixes BUG 221: fix for using short device names (less than 3 characters) Terminal com port closing fixed Serial error dump file added
3 (11)

Revision 2.2.742.2.76 19.4.2011 BUG 179: fix for English.lan BUG 180: device speed checking is run max three times when connecting to device BUG 187: even buffer reading fix 20s timeout for opening com port BUG 185: support for vector diagram with primary values BUG 194: max virtual meas voltage 500kV BUG 191: virtual meas view scrolling fixed with small resolutions Revision 2.2.612.2.73 17.3.2011 BUG 102: EDS file creation fixed for Vista and Windows 7 BUG 130: default paths fixed (for SetPointPS) BUG 132: changes log fixed BUG 134136 Reading menus without fast reading mode fixed BUG 164: virtual meas view scrolling fixed Virtual meas: peak mode for Io and harmonics controls added, support for VAMP265 ICD file generation: INT128 support added for energy counters Serial timeout is increased automatically for older devices Revision 2.2.502.2.59 22.11.2010 BUG 71 fixed (Converting to UTF8 message caused problems with device library) BUG 46 fixed (problem when changing from edit box to combo box without pressing enter) BUG 79 fixed (Auto DR reading doesnt come over boot request dialog) Wrong password message added to Device Setup window New record trig buttons added Vampset language selection changed. Now language can be selected from Program Settings. New language becomes valid after rebooting Vampset. Support added for new VAMP40 boot code (V5.11) Revision 2.2.462.2.49 25.8.2010 BUG 18 fixed (problem with matrix signals, max signal count was too low) BUG 47 fixed (NVRAM size is set to FFFFFFFF on boot code update) BUG 69 fixed (problem with new FTDI driver 2.8.2, could not communicate with VAMP50) ICD parser updated for firmware V10.58 Revision 2.2.422.2.45 10.6.2010 Font transfer function added (Chinese support) Remove language packets function removes also font files ICD parser: support for new control modes Bug fix: get ICD/IID file function could crash in quick connect mode Support for firmware updating in 9600 bps Revision 2.2.392.2.41 24.3.2010 Writing IEC-61850 configuration fixed (problem with writing settings automatically) Terminal changes and fixes, pressing CTRL+R runs last command again

4 (11)

Revision 2.2.322.2.38 10.3.2010 Supports V210 firmwares Terminal works now like any terminal, showing also device boot messages Online measurement display should not disappear any more VAMP50 firmware updating uses always 187500 bps speed Writing all settings fixed for VAMP 100-series (problems with writing voltage meas mode) Communication error handling improvements Writing IEC-103 configuration for 100-series fixed Reading event codes from old devices (firmware < V5) fixed SPBUS communication fixed, checksum added to all messages Auto-disconnecting timer fixed Fix for empty setting range problem Event buffer supports now more than 200 events Continuous updating reads maximum of 5 events at a time Continuous updating started also if booting device was cancelled Now continuous updating reads also values which were first changed by user, but refresh from device later without writing to device (bug fix) Communication error displaying in serial log fixed Protection status display crashing fixed Vector diagram display crashing fixed Revision 2.2.232.2.31 16.2.2010 UTF-8 character conversion for non-G5 firmwares (< V10) UTF-8 character conversion for older Vampset files IEC-103 config fixed (UTF-8) Reading disturbance recordings fixed for older devices (UTF-8 conversion) Profibus DB data accepts max 8 bytes long items Firmware update fixes Restore device DB: default file name added, speed checking removed (for 2-button start) Read all DB text from device: default file name added Convert ASCII file to language packet: message texts fixed Backup device DB always active, support for firmwares V510 added Language setup fixed on connecting to device Revision 2.2.162.2.22 4.2.2010 New info added to IID file Buffer fixes for DeviceNet/EthernetIP config view Firmware updating vie Ethernet fixed (WIMO & VEA3CG) Document types changed when exe is not named Vampset Continuous updating fixed for Network connection ICD & SCD parsers updated Better UTF-8 support Revision 2.2.72.2.15 2.10.2009 SPABUS transmit delay added Better UTF-8 support Misc bug fixes

5 (11)

Revision 2.2.6.12.2.6.14 9.9.2009 UTF-8 character coding (only partial support) Not fully compatible with older devices (until 2.2.38) 61850 updated Revision 2.2.12.2.6 12.2.2009 Support for V10 firmware (new G5 platform) Support for EDS & SCD files New file selection window for language packet conversion New timeout settings Revision 2.1.332.1.40 29.7.2008 Event reading adds only unread events 61850: ICD file creation Net port setting added IP & port are resolved PQ-diagram fix for VAMP210 Automatic menu & view update for new device firmware (6.49) Matrix signals are read in fast mode also when quick connect is not used Revision 2.1.122.1.32 21.4.2008 Communication changes for new device firmware (6.43) Communication fix for external IO detection Fix for modem initialization Vamp257 FlexIO relay connections are also cleared with Clear Matrix Option for reading disturbance records automatically Revision 2.1.42.1.11 11.10.2007 Updates for new device firmware (6.23) Updates for VAMP 257 (6.23) Left menu fixes, grouping added Protection stages: if both setting groups use inverse delay, definite time setting is not visible. If both setting groups use definite delay, inverse time setting is not visible Misc communication fixes Public Revision 2.1.22.1.3 3.5.2007 Cursor vectors added to disturbance recorder Public Revision 1.4.262.1.1 19.4.2007 Updates for new device firmware (6.x) Writing old file (5.x) to relay running 6.x not allowed Fixes for booting device via Ethernet connection Clear all records menu command fixed Table columns are bit wider

6 (11)

Revision 1.4.11.4.25 28.2.2007 Updates for new device firmware (5.53 5.74) Several communication fixes Writing current view works now in Block & AR matrixes Parameter info box removed Revision 1.3.19 24.4.2006 Public Revision 1.3.6 12.12.2005 Disturbance recorder can open files with sample timestamps by forcing to fixed sampling rate. A warning message is given. Revision 1.3.5 8.12.2005 Writing logic group by Write Group command, writes also output matrix (This is needed because matrix signals carry the logic input connections) BUG FIX: matrix display reading fixed (affected also logic display) BUG FIX: parameters with clear only access are not written when writing all settings to device Revision 1.3.4 7.12.2005 Communication settings layout fixed for longer (French) texts Revision 1.3.3 5.12.2005 About menu: Version is visible only if Versions.pdf is found About menu: Help is visible only if Vampset.hlp is found Revision 1.3.2 7.11.2005 Support for VAMP 2xx firmware v5.32 Revision 1.3 17.10.2005 Logic editor displays input signal status (for VAMP 230/245/255 v5.21) Logic editor layout updated Spabus mode: slave address is requested when connecting to device Reduced CPU usage BUG FIX: instability problems with matrix displays fixed BUG FIX: problems with COM port >= 10 fixed BUG FIX: Scandinavian character fix for logic input & output selections Revision 1.2.53 2.6.2005 BUG FIX: network connection problems with fast PCs fixed Revision 1.2.50 27.5.2005 Online measurements display added (requires VAMP 230/245/255 v5.2). This can be enabled on program settings. Display is active only when continuous updating is on and one or more measured values are greater than zero.
7 (11)

Revision 1.2.47 4.5.2005 If modem doesnt respond to the first AT command, Vampset tries again with AT&F. This sets on the modem echo, if initially disabled Revision 1.2.46 21.4.2005 Fix for firmware updating: errors occuring while saving a tmp file doesnt stop the updating process Revision 1.2.44 4.4.2005 Table view type added (for VAMP 230/245/255 v5.2) New matrix display type added (for VAMP 230/245/255 v5.2) BUG FIX: clicking mouse above the first parameter on any screen doesnt cause illegal operation any more Revision 1.2.15 14.9.2004 New setting: inactive timeout. If communication has been inactive for set time, Vampset closes the communication port. This is useful for Ethernet connection, thus other applications can access the device after this timeout. Browsing log-files on Program Settings: Open dialog is used instead of Write (no more warnings about overwriting file) BUG FIX: password is now treated as integer value (not string) BUG FIX: check box items didnt update from the device correctly ! Revision 1.2.13 6.9.2004 BUG FIX (VAMP 265): selecting IL1..IL3 works now Revision 1.2.12 31.8.2004 SPABUS slave address setting added to communication settings Revision 1.2.11 27.8.2004 No need to open a document for using the Device Diagnostics function Revision 1.2.9 13.8.2004 Quick fix for Finnish language. If the document is in Finnish, the device is forced to Finnish when connecting to the device Fix for empty strings. Revision 1.2.6 10.6.2004 Device Setup dialog added: user can change language, application option, remote port protocol etc when connecting to new device. Revision 1.2.2 25.4.2004 BUG FIX: changes log works now correctly with automatic-writing

8 (11)

Revision 1.2 29.4.2004 Changes for VAMP 255 Motor option: blocking matrix supports now > 32 protections stages Supports faster reading method found on VAMP 255 rev 4.39 (2004/04/05) and VAMP 260 rev 5.83 (2004/04/14) XOR-function added to logic BUG FIX: communication problems with Windows NT fixed BUG FIX: mimic display was always sent to device after opening file and transmitting changes, even if the mimic was not changed at all Revision 1.1.70 19.1.2004 Boot window is not shown when Vampset is launched by clicking a file Vampset rev 1.1.69 didnt show the boot window at all. BUG FIX: If Vampset document is open, raw recordings could not be opened from Disturbance Record/Open with the default file extension filter Revision 1.1.69 7.1.2004 chanhes in "File/Open": - can open also raw disturbance recordings - "All VAMPSET Files" file extension filter added changes in "Disturbance Recorder/Open": - can open also raw disturbance recordings - "All Record Files" file extension filter added Time&Date button is not active on USER access level If Vampset is not started with "-locked" argument, USER can change user level parameters

9 (11)

Revision 1.1.68 19.12.2003 *.dri files are associated to VAMPSET (i.e. double clicking those files opens VAMPSET) in disturbance recorder view, only channels that contain data (any of the samples differs from zero) are displayed by default BUG FIX:baud rates below 9600 bps work now Revision 1.1.65 16.12.2003 support for raw distubance record files, that are read from VAMP relays via SPABUS menu:"Disturbance Record/Open Raw" added for opening raw recordings "Ignore Read Errors" setting added. Init reading doesn't stop in case of errors, if this parameter has been checked harmonics display added

Revision 1.1.62 3.12.2003 Response timeout setting for local port added Revision 1.1.57 26.11.2003 SGS Fimko uses this version on EMC testing BUG FIX: output matrix works now with new VAMP 230 firmware (version 4.x) Revision 1.1.54 19.11.2003 Response timeout setting for network port added BUG FIX: Removing communication cable if continous updating is on doesnt cause illegal operation. (since version 1.1.44) Revision 1.1.47 6.11.2003 Check box in the setting views is bigger now BUG FIX: Closing Vampset doesnt cause illegal operation, if Ethernet port is still open or serial port is open and the cable has been disconnected from the device BUG FIX: Opening new document while communication port is still open doesnt cause illegal operation BUG FIX: Disturbance record reading didnt work on version 1.1.46 Revision 1.1.46 31.10.2003 Parity setting removed from communication settings, because it's never used. Local port (on the device) works always in no parity mode, and SPABUS mode uses always EVEN parity. No setting is needed. Check box is used in setting views for Off/On and Disabled/Enabled type parameters Revision 1.1.44 9.10.2003 Save Log button added to the communication display. Homepage & Support added to the Help menu. BUG FIX: Sync time & date from computer works now correctly if the device language is finnish. Date was not changed if the date style was v-k-p or p.k.v

10 (11)

Revision 1.1.37 29.9.2003 simple SPABUS mode added. Communicates only with SPABUS slave number 1. This is implemented only for testing Get/Set/Spa software on the devices and has no real use yet (no slave address setting) changes in log view of the progress & communication display - Read all settings supported - Boot dialog supported - Stop & Close buttons added Revision 1.1.34 18.9.2003 support for VAMP scripts (.run files) support for SPABUS variable tables, Versions < 1.1.34 cause illegal operation log view added to progress & communication display, supports the following functions: - File/Open - File/Save - Communication/Run VAMP script - Disrutbance Record reading - Write All/Changed settings Revision 1.1.33 5.9.2003 Public on www.vamp.fi/software Revision 1.1.32 3.9.2003 Show only used matrix signals function added to View menu State of this setting is saved within the document file Changes in matrix printing: only signals, which have at least one connection are printed to paper Revision 1.1.26 10.7.2003 support for using Scandinavian characters in device strings (like main & sub location in Device Info view) Scandinavian character support in caption view & group view Revision 1.1.16 13.6.2003 support for IEC-103 data configurations Revision 1.1.10 27.5.2003 support for VAMP 255 fault logs support for setting groups changes in get/set & serial port handling new colour look CTRL + TAB can be used for switching between recorder and settings view CTRL + R reads the oldest disturbance record from device

11 (11)