Академический Документы
Профессиональный Документы
Культура Документы
By J. A. Hanson
Reprint
from
of the
American
Proceedings
AND
DRYING
ON SPLITTING OF CONCRETE
By
J.
A.
Hanson
CEX4ENT
ASSOCIATION LABOK.+TOK1E3
lIEVEI.OPMENl
.5420 OId
The splitting
tensile
strengths
and
normal weight concretes were test series which clea 1+ with curing showed ing humidity strength. strength and that had for drying the prior While the to duration drying effect of
period
little
there
was
lightweight
concrete
drying periods, atmosphere led ting were levels ing from for strengths. subiected of relative 7 days.
In
the
second
for after
series, initial
concretes
moist of cur-
2 I days changes
minor
strength
were found
as the relative
humidity
75 to
I O percent. age-strength curing; humidity: Monfore (material): shale relation; drying; fine compressive drying shrinkaggremoist curhumidity tensile aggregates;
Keywords: strength; age; gravel gate ing: probe: strength; expanded concretes; moisture
concretes; (material):
aggregates;
aggregates;
research: testing.
W THE SPLITTING TENSILE TEST (ASTM C496-66) has been adopted as a convenient and relative measure of the tensile strength of concrete. In the test, a concrete cylinder is placed on its side in the testing machine and subjected to diametral compression. Such compression induces uniform tensile stresses normal to the loaded diameter, causing the specimen to fail by splitting along the diameter. Reference 1 provides a discussion of
early studies of this test and its concomitant advantages and disadvantages. Over the past few years, several investigational-~ have shown that some amount of drying of structural lightweight concrete may reduce the splitting tensile strength of concrete cylinders. Similar but more erratic results have been obtained from modulus of rupture tests of plain concrete beams. On the other hand, such drying of normal weight concrete appears to cause only a small reduction of the splitting strength, and some increase may even be evident. This same relative behavior has been found with concretes steam cured at atmospheric pressures and then allowed to cool and dry at room temperatures.~,~ The splitting strength of the steam-cured normal weight concrete at 28 days was about 98 percent of that of continuous moist-cured concrete, while the splitting strength of the steam-cured lightweight concrete dropped to about 75 percent. Close correlation Isg has been shown between the splitting tensile strength of lightweight concrete subjected tc~ a period of drying and the diagonal tension strength of reinforced beams and slabs containing the same concrete, though little or no correlation was found with concretes continuously moist cured. This relationship between splitting tensile strength and diagonal tension resistance was adopted by ACI 318-631) to compute the contribution of lightweight concrete to the shear resistance of reinforced beams and slabs. Section 505 of the Code provides that the splitting tensile strength of lightweight concrete be determined after 7 days moist curing followed by 21 days drying at 73 F (23 C) and 50 percent relative humidity. Since most research has been performed under these same curing and storage conditions, questions have arisen as to the minimum strength
ACI JOURNAL
may be encountered in practice with other curing periods, or with drying at other ambient relative humidities. A further question has been raised regarding the amount of tensile strength which may be recovered with additional age of drying concrete. The two somewhat limited test series reported herein provide some insight into these questions. Series I was planned to study the effects of various durations of initial moist curing on the splitting tensile strength of drying concretes at intervals of time up to 2 years. Series II concerned the effect of drying at relative humidities other than the generally prescribed value of 50 percent. Such a study is of importance to the humidity control required in commercial testing laboratories.
that
PROCEDURE mixes
The concretes used in both test series utilized a single lightweight aggregate and a single normal weight aggregate, both in their commercial gradings. The gradings of the fines of both aggregates fell within the limits of ASTM C-330-64T and ASTM C-33-67, respectively. The lightweight aggregate (No. 14 in the PCA series) was a rotary -kihi expanded shale. The
Long-time Research ACI member .). A. Hanson Methods
is manager,
Laboratory Portland
Section,
Construction
Department,
Cement Association Research and Development Division, Skokie, Ill. At PCA Mr. Hanson has beet? concerned with all types of concrete products, Iightweight concrete, concrete masonry, architectural concrete; and is the author of numerous a member of the prefabricated building elements. He papers and reports. Currently, he is Technical Activities Committee, Architectural Concrete, and a Lightweight Aggregates and and Committee 533, Precast the Federation International on Prestressed Lightweight Building Research Institute.
Institutes
chairman of AC! Committee 303, member of AC I Committee 213, Lightweight Aggrqaie Concrete, PaceIs. tie is also a member of de la Precontrainte Commission Concrete, and a member of the
JULY 1968
particles of this aggregate are generally rounded and coated as a result of presizing prior to expansion. The normal weight aggregate was sand and gravel obtained from Elgin, Illinois. Concretes containing this sand and gravel have been used for comparison purposes in all previous PCA studies of structural lightweight concrete under aggregate code No. 8. The all-lightweight concrete and normal weight concrete of Series I were proportioned to obtain a nominal compressive strength of 4500 psi (316 kg/cm) at 28 days. In Series II, three types of concretes were employed: all-lightweight, lightweight coarse aggregate with normal weight sand fines, and all normal weight aggregate. These were each proportioned for two nominal strength levels: 3000 and 5000 psi (211 and 352 kg/cm~) at .28 days. AH test specimens were 6 x 12-in. (15 x 30-cm) cylinders consolidated by internal vibration. Concrete placing and proportioning procedures were in accordance wi.thlACI 613A-5911 as modified by the recomrnenda.tions of Reference 12. The mix proportions, plastic properties, and 28-day compressive strengths of concretes in both test series are provided in Table 1. The Type I portland cement was a blend of four commercial brands.
Curing Series and testing
IThe purpose of this series was to investigate the effect of the duration of the initial moist curing period on the splitting tensile strength. The four initial moist curing periods chosen were 3, 7, 14, and 28 days. After initial moist curing, all specimens were stored at 73 F (23 C) and 50 percent relative humidity. Consequently for each curing condition, sufficient alllightweight concrete specimens were produced to
ACI JOURNAL
TASLE I--MIX
PROPORTIONS OF CONCRETES*
All-lightweight 25 55 502 ) concrete ii376 E9F I Elan 454 Series II All-lightweight 10 Sand-lightweight 10 10 Elgin I 49 47 / I ( 290 274 10 10 351 457 sand and gravel / 1566 1 1480 ) concrete 1662 1679 (Aggregate 1 concrete 56 54 ;;; ( ( j 424 390 ~ ;;g concrete ;;; (Aggregate sand and- gravel I 1480 ; ; lC45 i 1 298 47 , 372 15 ~___. 64
concrete
(Aggregate
._~ ~~ (Aggregate j 14 with ;:; Elgin 14) ( sand fines) 100.1 97.7 ( ;3/4 ( ;;a;
8) 6.5 6.2 ( ( 143.3 144.0 I ( lb per 21/A z yd3 by I I 3310 4820 0.5933 to obtain
*Equivalent metric units may be obtained by using the following conversion factors: (a) multiply in. by 2.54 to obtain cm. kg/W, (b) multiply lb per ft3 by 16.0185 to obtain kg/r@, (c) multiply iGross water and floor-dry aggregate.
vl
obtain the compressive strength (two specimens per test) and the splitting tensile strength (four specimens per test) as a function of time to 2 years age of concrete. In addition, these properties were determined for continuously moist cured concretes. In the case of the Elgin normal weight concrete the same properties were determined only under continuous moist curing, and after 7 and 28 days of moist storage followed by drying. Four additional lightweight and two normal weight specimens, one from each of the initial moist storage conditions, were inst~umented to obtain relative humidity distribution, weight loss, and drying shrinkage. Brass tube wells, 5/32 in. (4 mm) inside diameter to receive the Monfore relative humidity probe,l:] were installed at distances of Y4, 3A, 13A, and 3 in. (6, 19, 44, and 75 mm) from the cylinder exterior surface. The wells allowed a gaging length of 1 in. which was centered at middepth of each 6 x 12-in. (15 x 30-cm) cylinder. The cylinder ends were sealed with an amide epoxy to force all drying of the concrete to occur in the lateral direction. Drying shrinkage was obtained witk a 10-in. (25-cm) Whittemore strain gage. Fig. 1 shows a typical installation of wells, gage points fo,r Whittemore gage, and direct reading relative humidity indicator. Series 11The purpose of this series was to study the effect of storage at various levels of relative humidity on the splitting tensile strength of concrete otherwise tested in strict accordance with Section 505 c)f ACI 318-63.1( Ten batches at each strength level of the three concretes provided four specimens for compressive strength and eight specimens for splitting tensile strength at the five levels of relative humidity storage of 100, 75, 50, 30, and 10 percent. The specimens were
ACI JOURNAL
placed in these atmospheres after 7 days of moist curing and were all tested at 28 days. The ambient temperatures accompanying each relative humidity level were controlled to 73 L 2 F (23 L- 1 C). Two control cylinders from each batch were tested for compressive strength after storage at the standard conditions (ASTM C330-64T) of 7 days moist curing followed by 21 days drying at 50 percent relative humidity. In both series of tests, with the exceptions noted above, compressive strength was determined according to the requirements of ASTM C39-66, and splitting tensile strength according to ASTM C496-66.
.4$-:
-L.
Fig.
iinstrumentation
for
relative
humidity cylinder.
measurements
in
6
J(JL <Y 1968
x 12-in. concrete
TEST Series I
RESULTS
AND
DISCUSSION
Relative humidity distributionTables 2a and 2b present results obtained on relative humidity distribution, drying shrinkage, and weight loss of the 6 x 12-in. (15 x 30 cm) cylinders over the 3 year storage period. Fig. 2 is a typical plot of these data for the particular condition of 7 days moist curing followed bydrying at 73 F and 50 percent relative humidity. Perhaps the most striking feature of the data is the long period of time indicated for 6 x 12-in. concrete cylinders to attain moisture equilibrium in the 50 percent relative humidity atmosphere. After 3 years of drying, the relative humidity at the center of the lightweight concrete cylinders varies from 57 to 64 percent, depending on the length of initial moist curing. The normal weight concretes dried somewhat faster than the lightweight but these too have not reached moisture equilibrium. It should be noted that, while considerable moisture gradients still exist in the concretes, after 1 year of drying the weight loss and drying shrinkage curves have nearly attained equilibrium. The low drying shrinkage indicated by this particular lightweight concrete, relative to that of the normal weight, has been found in other studies.~ Such indications with these relatively small concrete cylinders point toward the extreme slowness with which full-sized structural members lose moisture. The extremely slow rate of drying of large concrete sections leads to reduced creep and shrinkage relative to that found in usual laboratory sized specimens.5 Splitting tensile st~engthTable 3 presents the compressive and splitting tensile strengths of alllightweight and normal weight concretes after the various lengths of initial curing and during the
ACI JOURNAL
HUMIDITY ( 15X 30
IN
PERCENT
12-IN.
cove r,
in.
I
~ O I 3 days I 7 days I 14 days
Time I 28 days
100
100 100
88 97 100 100
80 94 99 100
70 88 95 97
60 70 84 86
58 63 74 79
56 61 69 72
52 58 62 64
50 53 55 57
100
7 days 100 100 100 100 14 days
100
Moist %
( 6 mm)
89 98 100 108
81 94 100 100
73 89 98 99
61 73 87 92
57 65 78 84
56 62 72 78
53 56 64 67
52 55 57 59
Moist
\~ (
l~g 3
Iljo 100
84 98 99 100
76 92 97 99
63 76 88 93
59 68 80 87
58 64 74 81
55 59 65 70
53 55 57 61
mm) ~100
cured, 28 days 100 100 100 100
Moist
86 99 100 100
71 91 99 99 weight
60 77 92 95 concrete
58 70 84 91
57 66 78 84
55 60 69 73
54 56 61 64
Moist % % 3
7 days 100 100 100 100 28 days 100 100 100 100 85 98 100 100 82 76 87 94 98 69 80 90 92 58 68 76 78 57 84 70 73 55 61 66 89 52 55 58 61 50 52 54 56 89 97 108 100 84 93 98 99 77 8a 94 96 68 81 89 92 59 67 76 78 57 61 69 72 56 59 63 65 52 55 57 59 50 52 53 55
Moist
94
97 99
JULY 1968
1}
TABLE
AND
WEIGHT
LOSS
CYLINDERS) -
I 180 days in. per in. ]
1 year
I 2 YearS ! 3 YearS
concrete 490 450 450 400 concrete 67o 550 lbconcrete 1 720 620 I 750 630 790 67o 810 690 i i 1 570 560 560 480 640 590 620 560 650 640 680 630 1 , 670 680 710 660
310 70 14 28 0 ,0
80 60 80 80 ,
210
170
70 28
160 150
260 220
1..1
370 290 0.74 0.58 0.48 0.46
1 loss,
1(
All-1 ightweight . 0.60 0.44 0.38 0.34 0.86 0.70 0.60 0.58
~;l:
28
lo
I M 1R
0.96 : 0.94 1.08 1.06 0.98 0.88 1 1.04 0.94
;$- ~ :,;;
1.24 1.18 ; 1.27 1.25
70 28
0.60 0.46
I :2 i :H /
l!b by 0.4536 to obtain kg.
1.08 ~
1.04
1.12 1.07
*Equivalent
multiply
TABLE
3COMPRESSIVE AFTER
3 days
ANID
SPLITTING
TENSILE OF MOIST
STRENGTHS
OF
CON1
CRETES
Moist cure, days
DIFFERENT
DURATIONS
Age
CURINGSERIES
7 days AH
I 14 days light-weight
I 28 d~ys concrete
1 year
I 2 years
strength,
+ psi 3500 4150 4130 4700 4850 4760 5120 5280 5320 5400 5970 5850 5480 5960 5720 6420 6620 5400 5800 5750 6530 6840 5500- 577C 5350 6460 6760 , 385 385 397 433 492
I tensiIe
2620
4320
strength,l
1-
1+ psi
313 315 .
276
407 and
strength,
4630 4560
I 19
;6. 0.0703
371
4!30 467
505
506523
I 2_L:L %Equivalent metric units: multiply $Average of two .specime Rs. $Average of four specimens.
506-
AU JOURNAL
11
100
90
80
=--7-7
.
I I
LIGHTWEIGHT
CONCRETE
70 g n 60
. ~%
I
Cover
i 1
60
50 c
E:
?K \ \>>_
J \ . . _-=-==.:__ ---- -
28 90D 180D 90D 180D
NORMAL WEIGHT
CONCRETE
. _ .
2YR
iyiE:7!??E5?
028 I YR 2 YR
TIME
OF DRYING
relative
humidity
distribution,
drying
shrinkage,
and
x [2-in.
cylinders
moist cured
JULY 1968
12
following 50 percent relative humidity storage. Fig, 3 provides curves of the tabulated data which have been augmented by auxiliary tests performed during the first few days after start of drying. The solid curves of these two diagrams indicate the continuous increase of splitting strength achieved with continuous moist curing. Comparison of the two curves also indicates the approximately equal splitting strength of both types of concrete when moist curing prevails. PfeiferL found this in his study of concretes containing seven different lightweight aggregates and at two levels of compressive strength. As would be expected from the previous studies, Fi g. 3 indicates that drying of the lightweight concrete brings about an early loss of splitting strength. Considering only initial moist curing periods of 7 to 28 days, the early splitting strength of this drying concrete, containing this particular aggregate and no natural sand fines, is approximately 75 percent of the 28-day splitting strength of the continuous moist cured concrete. The duration of initial moist curing appears to have little effect on the magnitude of this tensile strength loss. It is of interest to note that this reduction of splitting strength occurs during the period of greatest moisture gradient in the cylinders, as indicated by Table 2 and Fig. 3. Due to the moisture gradient, drying shrinkage will not be uniform across the concrete cross section, and the potential shrinkage near the exterior surface will be reduced through the restraint of the interior material. Tensile stresses will then be self-induced near the exterior surface and balancing compressive stresses in the interior. The induced tensile stresses will reduce the resistance to externally caused tensile stresses.
ACI JOURNAL
13
600 -
Go
400.
200
DRYING I NITIAL
10
LI
3DA.
iDA
74DA
28DA
0
90DA I(30DAIYR 2YR
AGE
AFTER
CASTING CONCRETE
LIGHTWEIGHT
600
400
E o x
200
- 10
3Dli
7DA
14DA
28DA
90DA
180DA
IYR
2~-
AGE
AFTER
CASTING CONCRETE
NORMALWEIGHT
Fig. 3-Effect
and
drying l).
time
on splitting
tensile
(Series
.JIJLY 1968
114
The Initial loss of splitting strength of the drying lightweight concrete is followed by a gain as the concrete ages (Fig. 3). After one year the splitting strength is about 30 percent greater than the minimum, or about 80 percent of the potential strength indicated by continuous moist curing. In tests involving a number of all-lightweight concretes, Grieb and Wernerz found the average dry splitting tensile strength of such concretes to be about 90 percent of the moist cu:red strength at I year. With lightweight concrete containing quartz sand fines, Lewis and Blakey:] found the l-year splitting strength to be equal for dry and moist concrete. the increased splitting It is gratifying to note strength since this is evidence that the diagonal tension resistance of structures also increases with age of concrete. If these results are considered typical of lightweight concretes in general, the ACI 318-631) curing requirement, 7 days moist curing followed by 21 days of drying prior to tests for splitting strength, appears to provide a conservative (mini.mum) value of this property. As has been consistently found with Elgin gravel concrete, drying for 21 days apparently increases the splitting strength at 28 days over that found with continuous moist curing. Grieb and Werner,z studying a crushed limestone concrete, found that drying reduced the splitting strength by 10 to 15 percent. AS indicated by the lower diagram of Fig. 3, the splitting strength of the dry Elgin concrete at 2 years is about equal to that of the con.tinuosuly moist cured Elgin concrete.
Series II
Compressive strengtk-Table 4 presents the 28-day compressive and splitting tensile strengths of the three types of concrete, each at two
ACl JOURNAL
F 4
TABLE AT
AII-lightweigh.t Lightweight
1.
+28-DAY DIFFERENT
concrete f I
COMPRESSIVE
AND RELATIVE SPLITTING TENSILE
STRENGTHS
OF
CONCRETES II*
with sand Control, + .Nonixil
STORED
IN
AIR
HUMIDITIESSERIES
concrete
weight
f,>
f$r!
PSI F.,g psi
f,>
psi
f.,
psi 357 509 372 417 360 431 361 439, 360 427
fw!>
psl F,P p .si
100 302 452 6.18 I 4.95 281 380 296 351 7.5 2650 5200 2790 5280 50
2380 5070
365 424
6,47
30
I
5,C9
5.2, 5.14 psi x 0.0703
2770 5360
:%
294 354 multiply
I
to
2470 5340 2650 5310 2630 5160 2880 5200 7780 5280
obtain
3360 h620 34s0 5720 3450 5940 3580 .5840 3340 5920
kg/cm~,
3580 5840 3630 5810 3440 5910 3520 sg~o 3480 6000
3400 48oO 3220 4820 3340 5160 3300 4818 3300 4500
c yli:ders Section
after 7 days moist curing and with exception 505, ACI 318-63,
All
other
16
strength levels, which were subj ected to various levels of relative humidity storage after 7 days of moist curing. The aggregates in these concretes were all-lightweight, lightweight coarse with sand fines, and Elgin sand and gravel. Examination of the data discloses little effect of the relative humidity storage level on compressive strength. With the possible exception of the results from 100 percent relative humidity storage (continuous moist curing) only random variations of compressive strength from that of the standard 50 percent storage are noted. Under continuous moist curing the lightweight and normal weight concretes averaged 5 and 10 percent lower, respectively, than the drying concretes. Splitting tensile stnengthThe splitting tensile strengths of each of the concretes are shown in Fig. 4 as a function of the storage relative humidity. Each of these curves for the lightweight concretes indicates a drop of the splitting strength when the concretes are allowed to dry after 7 days moist curing. This effect is more pronounced for the higher strength concrete than for the lower, and is also greater for the all-] ightwelght concrete than for the sand lightweight. These indications agree with Pf eif erb who reported as follows: for 3000 psi all-lightweight concretes, the splitting strengths varied from 80 to 95 percent of the moist cured strength, and for 5000 psi, these percentages varied from 65 to 85; similar results for sandlightweight concrete were 95 to 105 and 80 to 100 percent. A most important observation from Fig. 4 is the minor change of splitting tensile strength as the 21-day drying storage changes from 173 F (23 C), 75 percent relative humidity to 73 F, 10 percent relative humidity. Ivey and ButhA found similar indications with other lightweight concretes, except
AH JOURNAL
17
500
r
~~
ALL
LTWT.
CONC.
35
400
500
400
300
F:,~
LTWT. CONC./SAND psi FINES f~ =5800 30; o f:= 3400 psi 25> x 20 _J~ 7 : 100 80 60 40 20 0
35
0+ F
:~:yo:;w::N;~,
RELATIVE
HUMIDITy,O/o
Fig. 4-28-Day splitting tensile strengths of concretes dried at different relative humidifies for 2 I days, temperature 73*2 F [Series II).
JULY 1968
18
that splitting strengths of concretes stored at 80 percent relative humidity were about equal to those of continuously moist cured concretes. Similar to the previous discussion of Series I, the splitting strength of the Series II Elgin normal weight concrete increased as the concrete dried. ASTM C496-66, Splitting Tensile Strength of Concrete Cylinders, requires that lightweight concrete, tested in accordance with ACI 318-63() shall be stored at 73 & 3 F (23 & 2 C) and 50 & 5 percent relative humidity for 21 days after 7 days moist curing. Commercial testing laboratories seldom have facilities sufficiently refined to control the relative humidity within these limits. From the results of this study and those of Reference 4, it would appear that wider limits, perhaps &15 percentage points, might be allowed without sacrifice of uniform splitting test results, although additional studies, incorporating other lightweight aggregates, may be advisable. Splitting ratio, F, PThe ACI 318-6310 defines the shear parameter of structural lightweight concrete FSPas the ratio of the splitting tensile strength to the square root of the compressive strength of the same concrete. Since Series II of this study satisfied other Code requirements, the variation of F,p vvith variation of relative humidity storage couldl be determined as indicated in Table 4. Small variations of the F.p of the dry concretes may be noted. The average F~P (excluding the moist cured) for the al.l-lightweight, sand-lightweight, and normal weight concretes, respectively, are 5.1, 5.8, and 6.9. Pf eif ers reported the following corresponding data: 4.8-6.4, 5.9-6.4, and 7.0; the range in each case covering the seven lightweight aggregates which he studied.
AH JOURNAL
19 CONCLUSIONS
This somewhat limited study was planned to furnish insight into some of the effects of drying on the splitting tensile strength of lightweight aggregate concrete. Since only a single lightweight aggregate, a single natural sand, and a single normal weight gravel were used, the data reported may not be precisely applied to all lightweight and normal weight concretes. However, the observed effects of curing and drying environments on tlhe splitting strength should provide information on some little understood aspects of this property- of concrete, particularly since these observations are in general accord with previous findings. The long-time measurements of relative humidity distribution (Series I) have indicated the extreme slowness with which concrete dries. Normal weight concrete, with its lower aggregate absorption, may reach moisture equilibrium with the ambient atmosphere faster than lightweight concrete. However, the accompanying I;ests of drying shrinkage and weight loss show that these properties attain equilibrium much earlier than does the internal relative humidity. The tests have reconfirmed the initial loss of splitting strength that generally occurs with drying of lightweight concrete. This loss of splitting strength is little affected by prior moist curing periods varying between 7 and 28 days. The Series I tests have shown that the drying concretes regain splitting tensile strength as the concrete ages, reaching perhaps 80 percent of the potential obtainable under I to 2 years of moist curing. This regain of splitting strength points toward an increased shear resistance occurring with age of concrete structures, though it should be noted that large structural members dry much slower
JULY 1968
than 6 x 12-in. (15 x 30 cm) cylinders. This regain indicates curing requirements of AC-I 318-6310 and ASTM 496-66 provide conservative values of splitting strength for design purposes. The Series II tests have shown that any drying environment between 75 and 10 percent relative humidity has about the same effect on splitting tensile strength measured at 28 days. This would indicate that the current requirements of ASTM 496-66 for maintaining 50 +5 percent relative humidity during the 21-day storage period might be broadened to a tolerance of perhaps f 15 percentage points.
ACKNOWLEDGMENTS
This investigation was carried out in the Products and Applications Development Section of the Portland Cement Association Laboratories. Particular credit is due Emil Greinke, Senior Technician, for conduct of the Series I tests and to Albert Litvin, Senior Engineer, for those of Series II.
ACI JOURNAL
21
REFERENCES
1. Hanson, J. A., Tensile Strength and Diagonal Tension Resistance of Structural Lightweight Concrete, JOURNAL, Proceedings V. 58, No. .1, July 1961, ACI pp. 1-39. Also, P(2A Development Department Bulletin D50.
2. Grieb, W. E.t$and Werner, G., Comparison of the Splitting Tensile Strength of Concrete with Flexural and Compressive Strength, Public Roads, V. 32, No. 5, Dec. 1962, pp. 97-106. 3. Lewis, R. K., and Blakey, F. A., Moisture Conditions Influencing the Tensile Splitting Strength of Lightweight Concrete, Constructional. Review (Sydney), V. 38, No. 8, Aug. 1965, pp. 17-22. 4. Ivey, D. L., and Buth, E., Splitting Tension Test of Structural Lightweight Concrete, ASTM Journal of Materials, V. 1, No. 4, Dec. 1966, pp. 859-871,
5.
Pfeifer,
D.
Splitting Tensile Strength, ACI JOURNAL, Proceedings V. 64, No. 7, July 1967, pp. 384-392. Also, PCA Development Depc!rtment Bulletin .Dlzo. 6. Hanson, J. A., Optimum Steam Curing Procedure in Precasting Plants, ACI JOURNAL, Proceedings V. 60, No. 1, Jan. 1963, pp. 75-100. Also, PCA Development Department Bulletin D62. 7. Hanson, J. A,, Optimum Steam Curing Procedures for Structural Lightweight Concrete, ACI JOURNAL, Proceedings V. 62, No. 6, June 1965, pp. 661-672. Also, PCA Development Department Bulletin D92. 8. Ivey, D. L., and Buth, E., Shear Capacity of Lightweight Concrete Beams, ACI JOURNAL, Proceedings V. 64, No. 10, Oct. 1967, pp. 634-643. 9. Hognestad, E.; Elstner, R. C.; and Hanson, J. A., Shear Strength of Reinforced Structural Lightweight .Aggregate Concrete Slabs, ACI JOURNAL, Proceedings V. 61, No. 6, June 1964, pp. 643-656. Also, PCA Development Depa~tment Bulletin D78. 10. ACI Committee 318, Building Cocie Requirements for Reinforced Concrete (ACI 318-63) , American Concrete Institute, Detroit, 1963, 144 pp. 11. ACI Committee 613, Subcommittee on Proportioning Lightweight Aggregate Concrete, Recommended for Structural Practice for Selecting Proportions
Lightweight Concrete
22
12. Landgren, R.; Hanson, J. A.; and Pfeifer, D. W., An Improved Procedure for Proportioning Mixes of Structural Lightweight Concretes, Jou?maZ, PCA Research and Development Laboratories, V. 7, No. 2, May 1965, pp. 47-65. Also, PCA Resem-ch Department .Buttetin 183. 13. Monfore, G. E., A Small Probe-Type Gage for Measuring Relative Humidity, Journal,, PCA Research and Development Laboratories, V. 5, No. 2, May 1963, PP. 41-47. Also, PCA Research Department Bulletin 160. 14. Pfeifer, D, W., Sand Replacement in Structural Lightweight Concrete Creep and Shrinkage Studies, 2, Feb. 1968, ACI JOURNAL, Proceedings V. 65, No. pp. 131-140. Also, PCA Development Bulletin D128. 15. Hansen, T. C., and Mattock, A. H., Influence of Size and Shape of Member on the Shrinkage and Creep of Concrete, ACI JOURNAL, Proceedings V. 63, No. 2, Feb. 1966, pp. 267-290. Also, PCA Development Department Bulletin D103.
SinopsisResumeZusammenfassung
Se investigaron las resistencias a la tension por compression diametral de concreto ligero y de peso normal en dos series de ensayes que tratan con 10S efectos del curado y las condiciones de secado. La primers serie mostr6 que la duraci6n del periodo initial de curado htimedo, antes del secado a 50 por ciento de humedad relativa, tiene poco efecto en la resistencia compresi6n diametral. a la tensi6n por A pesar de que se produjo una perdida de resistencia a la tension por cortante para concreto ligero al iniciarse el periodo de secado, un almacenamiento i~ una ganancia continuo en atmosfera seca condujo considerable de resistencia a la tensibn. En la segunda serie, el concreto se sometio a secado durante 21 alias con diferentes niveles de humedad rela.tiva despu& de un curad.o iniciaI htimedo de 7 alias. Solamente se obtuvieron cambios menores en la resistencia a la tension cuando se vario la humedad relativa de 75 a 10 por ciento.
ACI JOURNAL
23
Les r&istances au dedoublement en tension de bktons I+gers et normaux ont &6 ~tudi~es lors de deux s6ries dessais clans lesquels linfluence de lambiance de ressuage et s&chage 6tait consid&-&e. Les premi&es s6ries ont montrh que la durke de ressuage initial &tat hurnide pr6c6dent un shchage ii 50 pourcent dhumidit6 relative avait peu dinfluence sur la resistance au dedoublement en tension. Tandis quon notait une diminution de r&istance au dedoublement pour le bkton 16ger tr$s t6t durant la p&iode de skchage; un stockage conti.nu clans Iatmosphere de s~chage conduisait ~ un gain consid&able dam la r&istance au d6doublement. Dans les secondes skries, les betons ont ete soumis a un sechage durant ~!1 jours a different niveaux dhumidite relative! apres ressuage initial etat humide de 7 j ours. Seulement des changements mineurs de r&istance au d6doublement ont W trouv% lorsque lhumidit6 relative varie de 75 ~ 10 pourcent. Der Einfluss der Lagerungsbedingungen Spaltzugfestigkeit von Beton auf die
Die Spaltzugfestigkeit von Leichtbeton und Normalbeton wurde im Rahmen von zwei Versuchsreihen studiert, wobei vor allern der Einfluss der Lagerungsbedingungen untersucht wurde. Die erste Versuchsreihe zeigte, class die Dauer einer Feuchtlagerung, die einer anschliessenden Austrocknungsperiode bei einer Luft feuchtigkeit von auf die Spaltzugfestigkeit wenig 50 ZO vorangeht, Einfluss hat. Zu Beginn der Austrocknungsperioden wurde zwar ein geringer Abfall der S,paltzugfestigkeit beobachtet; langere Austrocknung fflhrte jedoch zu einem merklichen Anstieg der Spaltzugfestigkeit. In der zweiten Versuchreihe wurden die Bet(mproben nach einer anfanglichen Feuchtlagerung von sieben Tagen einundzwanzig Tage lang verschiedenen relativen Luftfeuchtigkeiten ausgesetzt. Eine Variation der relativen Luftf euchte zwischen 10 uncl 75% hatte nur einen geringfiigigen Einfluss auf die Spaltzugfestigkeit.
JULY 1968
PCA,
R& D, Ser.1314-2
Bulletins
Published
by
the
Department Lak>oratories
Portland
DIOOIndex and of Development Index. Cement
Association
D1-D99. Annotated List with Author
Department
Subject
Association,
Research
and
Development
Laboratories,
Hinging
Regions
in
Reinforced
Concrete
Beams,
by
ALAN
Miami, Flu. (November 1964) pages national Symposium, Cop yrighted 1965 by American Society of Civil Eng {neers.
D102Tests of Partially Prestressed Concrete Girders, by HOCNESTAD. Reprinted Society
Reprinted
from
Of the
Inter-
DONALD
frprn the Jou?mat of the ,.St?wcturaIDivision, Proceedings of tize American of CtvZl Engineers, Proc. Paper 4685, 92, ST 1, 327-350 (February 1966).
D103Influence of Size and Shape of Member on the Shrinkage and Creep of Concrete. by TORBEN C. HANSEN and ALAN H, MATTOCK. of the American Concrete Institute (February 1966): Proc@edReprinted from Jownat irsgs 63, 267-290 ( 1966). DIOQCast-in-Place Concrete Residences With Insulated Walls, by HARRY L. SCOGCIN. Reprinted from Journal of the PCA Research and Development Laboratories, 8, No. 2, 21-29 (May 1966). D105TensiIe Testing of Concrete Reprinted from Jousma~of 42-52 (May 1966). Block and Wall Elements, by RICHARDO. HEDSTROM. PCA Research and Development Laboratories, 8, No. 2,
the
D106High Strength Bars as Concrete Reinforcement. Part 8. Similitude in Flexural Cracking of T-Beam Flanges, by PAUL H. KAAR. Reprinted from Journal of the PCA Research and Development Laboratories, 8, No. 2, 2-12 (May 1966). D107Sesmicic Resistance of Reinforced ConcreteA Laboratory Test Rig, by NORMAN W. HANSON and HAROLD W. CONNER. Reprinted from Joti?vsal of the PCA Research and D?veloprnent Laboratories, 8, No. 3, 2-9 (September 1986). D108Rotational Capacity of Reinforced Concrete Beams. by W. GENE CORLEY. Reprinted from Journal of the Structural Division, Proceedings of the Amertcan cietu of Civil Engineers, Proc. Paper 4939, 92, ST5, 121-146 (October 1966). D109Laboratory Studies B. E. COLLEY.
Reprinted from
So-
of Concrete.
by
ASTM
Dl10Connections
LAFRAUGH Reprinted and
in Precast
D. D. from JoumaL
StructuresColumn
Base
Plates,
MAGURA.
cember 1966).
Prest~essed Conc?w!e Institute, 11, No. 6, 18-39 (Deby ALBERT LrrvlN and JosEpH J. sHID~L~~.
American Concrete Institute, Paper No.
DillLaboratory
Study
of Shotcrete.
Dl12Tests
on Soil-Cement
and Cement-Modified
of the PCA Research
Bases in Minnesota, by
and Development
!CORBJORN
J. 1,
Testing-Reinforced
PCA
and Prestressed
ReseaTctt and
Mortar
Beams.
by
9,
DONNo.
f2ewto~ment
Laboratories,
1,
by
of
Heat
Flow
Factors
to
the
Unit
Weight
of
Concrete,
BREWER. Joumat 1967). in W. of the PCA Research and De Vf?tOpmerzt .Labomtones, 9, No. 1,
ConcreteSintering
Grate
Aggre-
gate:; . by
Reprinted
Jouwtal
American
Institute
(March,
]967); Proceedings by
1967);
Dl16Fatigue Tests of Reinforcing BarsTack BURTONand EIVINDHocNmsrAm Reprinted from Journal of the American
64, 244-252 (1967)
Welding
Concrete
of Stirrups,
Institute (May,
KENNETH T.
Proceedings
Dl17Connections Shrinkage,
Reprinted
StructuresEffects
G. COEiLEY, and E. Coracmte
of
Institute,
Restrained
Creep
and
HOGNESrAD.
1967).
Pmstressed
Dl18CasiniPlacece Concrete Residences with Insulated WallsInfluence of Shear Connectors on Flexural Resistance, by HARRY L. SCOGGIN and DONALDW. PFEIEER. Reprinted from JOumaZ of the PCA Research and Dewtownent Laboratories, 9, No. 2, 2-7 (May 1967), Dl19Fatijgue of Soil-Cement. B:eprinted from Journat 37-59 (May 1967). by T. J.
of the PCA LARSEN Research
and
and
9, No 2,
Lightweight
Anwrican
Concret~;Splitting
Inst, tute (July
Strength,
64,
Concrete
Proceedings
Concrete
Beam-Column
Joints, 1967).
of the
by
NORMAN
Society
of
civiLEngineers,
from
Journal of the Structural Division. Proceedings PTOC. Paper 5537, 93, ST5, 533-560 (October
American
D122Precast
HAROLD
BuildingsTest
of the PCA
of Scarf Conn(?ctions,
ReseaTch and
Reprinted
Journa~
Rigid
KAAR.
Frame
BuildingsComponent
PCA Re=mch
Tests,
by HAROLD W.
CONNER
and
and
D=Ve~o~mQ~t
~aboratoties,
9,
No.
3,
D124Aggregate
Interlock at Joints in Concrete Pavements, by E. E. COLLEY and H. A. HUMPHREY. Reprintedfrom Highway Research RECORD, Number 189,1-18(196?).
CHILDS.
Repr,nted from Highway Research REcOm, Number 1~9. 1943 (1967). Lightweight Concrete-Freezing and Thawing
Proceed-
Amer+can
D127 U1tim ate Torque of Reinforced Rectangular Reprinted from Journal of the Structural
ciety of Civil Engineers, PTOC. PafwT 5814,
W THOMAS T. C. Hsu.
the American 1968). So-
i)128-Sand Replacement in Structural Lightweight Concrete-Creep and Shrinkage Studies, by DONALD W. PFEIFER. Reprinted from Journal of the A?ne~ican Corzc~ete Institute (February 1968); P~oceedings, 65, 131-140 (1968).
Concrete
Research
by NORMAN
10, No.
Laboratories,
Demands
Proceedings, 22-32 (1967 ). and Block
for New
Fall
Grades
of Reinforcing
Meeting, Concrete
Steel,
by EIVIND
Steel
Business
Reinforcing
on LITVIN,
Cracking HANSON.
of
Masonry
RICHARD
O.
HEDSTROM,
Reprinted from Journal of No. 1, 34-51 (January 1968). D132 Toward MCHENRY. Reprinted Engineering a Generalized Treatment
Research
Development
Laboratories.
10,
of
Delayed
Elasticity
in
Concrete,
by
DOUGLAa
Association (1966).
for
Bridge
and
Structural
D133 Torsion
of Structural
ConcreteA
Summary
STRUCIWIAL 165-176
of Pure
CONCRETE, (1968).
Torsion:
American
by
THOMAS
T.
C.
PUbliCatio~ SP-1!3,
ConcretePlain
TORSION
OF
Concrete
Institute,
Concrete
Reef angular
American
Sections,
Concrete
by THOMAS
Institute,
Reprinted from TORSION OF .%RUCWRAL SP 18-8 in Publication SP-18, 203-238 (1968). D135<Torsion of Structural ConcreteBehavior T. C.
CONCRETE,
of
Reinforced
Concrete
Rectangular Institute,
Members,
by
THOMAS
Hsu.
S. RUC,URAL CONCRETE, SP-18, 261-306 (1988). American Concrete
Reprinted Paper SP
D136Precast
PAUL H.
Rigid
KAAR
Frame
and
BuildingsSummary
W. of CONNER. the PCA Research
of
a Laboratory
Development
Investigation,
Laboratories, 10,
by
No.
HAROLD
and
D137 Clear
Coatings
for
Exposed
oj
Architectural
the PCA Research
Concrete,
and
by
ALBEK~
LITVIN. 10, No
Reprinted from Journal 2, 49-57 (May 1968). D138Torsion and of :Bending Reprinted ceedings, Structural in Beams
Development
Laboratories,
for T.
Combined C. HSU.
Torsion, 1968):
Shear. Pro-
Institute
(January
Properties
NOWLEN.
on Effectiveness
PCA Research and
of Interlock
Develom?zent
Joints
in Concrete
10, No.
Reprinted from Journal 2, 2-8 (May 1968). D 140Torsion Without of Web Reprinted 1968 ) Structural Reinforcement, from Jomnal
of
the
Laboratories,
Prest HSU.
ressed
Rectangular
Members
Concrete
Institute,
13,
No.
2, 34-44
(April
Environments Concrete
on
Splitting
(JU1Y
Tensile
Strength
of Con65, 535-543
Institute
1968);
proceedings,
Printed
in US. A
Effects
of Curing
and
Drying
Environments of Concrete u
on Splitting
KEYWORDS;
Tensile Strength
age-strength
relation; compressive strength; coucrctc$ curing; ttryin~ drying shrinkage; expanded shale aggregates; fine aggregates; gravel (material); humiclity; lightweight a~ywgate concretes; lightweight aggregates; moist curing; moisture content; research; sand (material); splitting tensile strength; testing.
SYNOPSIS:
/ , , I
wcigbt
concretes
were investigated in two test series which dtalt with the effects of the curing and drying environments. The first series showed that the [Iuration of the initial moist curing periuti prior to drying at 50 percent relative humidity had little effect on the splitting tensile strength. ~tbile there was a loss of splitting strength for the lightweight crmcrcte early in the drying pcriocts, continued storage in the drying atmosphere lcd 10 considerable gain in the splitting strengths. In the second series, ctsncrctcs
wmc subjected to drying for 2!1 c1ays at different levels of rela tivc humidity initial moist clu]ing for 7 days. Only minor changes of splitting strrmgth were as the relative hnmi(lity varied from 75 to 1(I percent. REFERENCE:
after found
Tensile
Hanson, J. A., Effect of Curiug and Drying Environmrmts ou Splitting V. 65, No. 7, Jn]y 1968. Strength of Concrete, ACI JC)URNA1. Procce[lings.
pp. 535-543.
Effects
of Curing
and
Drying
Environments of Concrete
on Splitting
Tensile Strength
KEYWORDS: age-strength relation; compressive strength; concretes; ctlring; drying; drying shrinkage; expanded shale aggregates; fine aggregate$ gravel (material); humidity; lightweight aggregate concretes; lightweight aggregates; moist curing: moisture content; research; sand (material); splitting tensile strength; testin~.
SYNOPSIS: The splitting tensile strengths of lightweight and normal weight concretes Irere hlVeSl@tted in two test series which dealt with the efTccts of the curing and drying environments. The first series showed that the duration of the initial moist curing period prior to drying at 50 percent relative humidity ba{l IittIe effect on the splitting ttmsile strength. While there was a loss of splitting strength for the lightcontinued storage in the drying atmoweight concrete early in the drying periods, sphere! led to cor]siderahle gain in the splitting strengths. In the second series, ccmcrctes for 21 days at different levels of relati~,c bumiditv after wmw subjected to [lrying initial moist curing for 7 days. Only minor chmges of splitting strength were found as the relati\c humidity varied from 75 to 10 percent, REFERENCE: H~IIS~JII> J. A., Effect of Curing ACI JOURN.!L Tensile Strcngth of Concrete, PP. 535-543 and Drying Environments Proceedings, V. 65, No. nn Splitting 7, July 1968,
1 1 I I
1
1
I I I I I i
Effects
of Curing
and Drying
Environments
of Concrete L! ] I I
I
on Splitting
Tensile Strength
KEYWORDS: age-strength relatiou; compressive strength: concretes; curing; drying; drying shrinkage; cxpandcrt shale aggregates; fine aggrwgatcs; gravel (material); humidity; lightweight aggreg~te concretes; lightweight aggregates moist curing; moisture com
tent; xcscal-ch; sand (material); tt!nsilc test splitting strengths series which tensile of strength; testing.
[
SYNOPSIS:
were drying curiug
The
splitting
in two
antf normal
the effects of
weight the
[ I 1 1
initial eflect
Wbile there was a loss of splitting strength for the lightsplitting tensile strength. nreight concrete early in the drying pcriocfs, continued storage in the drying atmosphere led to considerable gain in the splitting strengths. In the sccrmd series, ~oncrctes were subjected to thying for 21 days at different Ievcls of relative humidity after initial moist curing for 7 days. Only minor changes of splitting strength were found as the relatile humidity varied from 75 to 10 percent. REFERENCE: Hanson, J. A., Effect of Curing Tensile Strength of Concrctc, ACI JOURNAL pp.535-543. and Drying Environmcnrs on Splittin$ Proceedings, V. 65, RIO. 7, July 1~16~,
1 1 , I 1 I I I , I i