Вы находитесь на странице: 1из 403

Fans | Air Handling Units | Air Distribution Products | Fire Safety | Air Curtains and Heating Products | Tunnel

Fans

Systemair Fans
Product catalogue

Disclose the secret of fresh air!


Systemair has been taking care of Indoor Air Quality (IAQ) as an essential resource since 1974. Today Systemair is one of the leading ventilation companies worldwide. A success story, which started in Skinnskatteberg, Sweden with the invention of the inline duct fan. This invention revolutionised the ventilation world. Since then the company has continuously advanced and now offers a comprehensive range of products for all ventilation requirements. The experts at Systemair have the required knowledge and understanding in finding solutions when considering the ventilation of shopping centres, domestic ventilation of a family home to the complex ventilation of tunnels and metro stations. With more than 2800 employees, and in excess of 60 subsidiaries in 41 countries, we remain globally available to our customers. With this catalogue which features fans and accessories, we give you as our customer a general overview of what Systemair can offer within this range. For further information about all the other Systemair products you can contact your local Systemair company or visit our on-line catalogue on www.systemair.com. Quality Systemair has been certified according to ISO 9001, ISO 14001 and ATEX. Our R&D centre remains one of the most modern facilities in Europe. We test in compliance with the international standards EN, ISO and AMCA.

Systemair 2012. Systemair reserves the right to make technical changes. For updated documentation, please refer to www.systemair.com.

Contents
Systemair..................................................................................4-5 Fans Overview........................................................................6-7 Product range...........................................................................8-9 A good indoor climate is vital................................................... 10 Selection tools........................................................................... 11

Technical data

Circular duct fans......................................................... 16-63 Rectangular duct fans............................................... 64-121 Roof fans................................................................. 122-165 Axial fans................................................................. 166-199 Explosion proof fans............................................... 200-235 Smoke extract fans................................................. 236-273 Fans for aggressive media...................................... 274-285 Centrifugal fans....................................................... 286-311 Domestic fans.......................................................... 312-317 Electrical accessories.............................................. 318-345

Accessories.............................................................. 346-390

Wiring diagrams.............................................................. 391-400

Systemair
The straight way
The straight way was our first production idea and led to the circular duct fan. Today it represents our ambition to simplify the life of our customers. Stocked products are delivered in Europe within 24 hours from local warehouses and within 72 hours from distribution centres. High product quality, correct technical data and fast deliveries are always our main focus.

Technical data
Our development centre in Skinnskatteberg is one of the most modern in Europe for airflow, acoustic, efficiency and low velocity measurements on air terminal devices, etc. All measurements are performed in compliance with applicable standards as set out in AMCA and ISO.

Dal, Eidsvoll Norway


In Eidsvoll, Norway we manufacture air handling units for the Norwegian market. The Norwegian warehouse for fans is also located here.

Quality and environment

Systemair
Systemair was established in Sweden in 1974 and is today the parent company in an international group with 60 subsidiaries and approximately 2800 employees. The Group's head office and largest production plant is located in Skinnskatteberg, Sweden with some 400 employees and a floor area of 50000 m2.

Production
We are proud of our production units. The aim has been to have both effective production of bulk products and, at the same time, an efficient and flexible approach to producing small volumes. This has steered our choice of machinery and how we plan our production, with focus on the working environment. Our premises are light and pleasant and we invest in tools that facilitate work and provide our employees with a safe and efficient workplace.

Systemair is certified according to ISO Bouctouche Canada 9001 and ISO 14001. Our quality system allows us to continuously improve our In Bouctouche, Canada we primarily products and our customer service. Certi- produce ventilation products for the fication means that we have undertaken North American market. to minimise our environmental impact. We always take the environment into consideration when choosing sub-suppliers, materials, production methods, etc. An important factor is that we continuously work to reduce our energy consumption and reduce waste. Through increased recovery and heightened awareness we have been able to reduce our waste by 90%. Quality and environment management systems are under continuous development. These are audited twice a year by the certification body BVQI (Bureau Veritas Quality International). Detailed product information can be found on our website, www.systemair.com.

Kansas City USA


In Kansas City we produce ventilation products for the North American market.

Production in Skinnskatteberg is virtually fully automated with modern machinery featuring advanced computer support. Also located here is the company's most advanced test facility for measuring.

Skinnskatteberg Sweden
Main plant The main plant in Skinnskatteberg houses one of the company's three central warehouses and the largest production facility as well as the group's head office. Fans and accessories are produced here as stock items. Klockargrden Systemair's compact air handling units are made at Klockargrden in Skinnskatteber g. Frico's central warehouse of approximately 8000 m2 is also located here.

Hssleholm - Sweden
VEAB VEAB in Hssleholm manufactures heating and cooling coils as well as fan heaters.

Ukmerge Lithuania
Production of air handling units.

Bratislava Slovakia
The factory in Bratislava manufactures air distribution products and fire dampers.

Maribor Slovenia
The factory in Maribor, Slovenia specialises in high temperature centrifugal fans for flue gas ventilation.

New Delhi India


The factories in New Delhi and Noida manufacture grilles and diffusers. Systemair Software is also based here. The combined factory area has a size of approximately 6500 m2 with a total of 290 employees.

Kuala Lumpur Malaysia


Production and central warehouse for the Asian market.

Madrid Spain
The factory in Madrid, Spain produces air handling units mainly for the southern European, Asian, and African market.

Hasselager Denmark
The factory in Hasselager, Denmark manufactures large air handling units to Eurovent standards.

Windischbuch Germany
In Windischbuch, Germany a broad assortment of fans are manufactured, of which the majority are stock items. One of Systemair's central warehouses is located here.

Fans Overview
Systemair has a wide range of fans for use in various applications from small office premises to larger industrial applications. Common to all items in the range is that components have been developed to satisfy stringent demands for low energy consumption. The fans have all undergone extensive testing, both in the laboratory and out in the field, in order to comply with current and future demands for low energy consumption. All products are also manufactured to comply with environmental requirements.

Circular duct fans up to 2.3 m3/s


Systemair offers different variants of circular duct fans. For systems with higher pressure losses we are offering the ranges K and RVK. The KV range can be installed directly on the wall. For higher air volumes we are offering the KD range with mixed flow impellers. Technical data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18-63

Rectangular and square duct fans up to 4.8 m3/s


Systemair rectangular and square duct fans have been developed for use in compact exhaust and supply air systems. This range is available in a wide performance spectrum. Technical data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66-121

Roof fans up to 15.2 m3/s


Systemair roof fans have been developed for use in effective exhaust air systems. Roof fans with circular or square connection and available for vertical discharge and for horizontal discharge.

Technical data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124-165

Axial fans up to 70 m3/s


Systemair axial fans have been developed for installation in effective supply and exhaust air systems. Axial fans for use in low and for medium/high pressure systems. For industrial buildings Systemair offers a wide area of axial fans to suit most building ventilation applications. Technical data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 168-189

Jet fans
Systemair jet fans for Car Park Ventilation, axial or centrifugal solutions, certified in accordance with EN 12101-3. Complete solutions including control systems and CFD. Technical data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 194-196
300C 120min

Explosion proof fans up to 12.36 m3/s


Systemair explosion proof fans have been developed to be used in effective supply and exhaust air systems allocated to category 2 (zone 1) and category 3 (zone 2) in explosion hazardous areas.

Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202-235

Smoke extract fans up to 70 m3/s


600C 120min

Systemair offers different types of smoke and heat extract fans: Centrifugal roof and box fans, centrifugal wall/ duct fans and axial fans. All fans are approved for dual purpose ventilation, i.e. for normal daily ventilation and for emergency ventilation in case of a fire.

400C 120min

300C 120min

Technical data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 238-272

Fans for aggressive media up to 2.11 m3/s


These sturdy plastic fans have been developed especially for applications where dirty or aggressive gases can contaminate the exhaust air. Typical applications are laboratories in medical or pharmaceutical institutions and in the food and chemical industry. Technical data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 276-285

Centrifugal fans up to 3 m3/s


Centrifugal fans for various applications, impellers with forward and backward curved blades. Also available with motors outside the airstream and EC motors.

Technical data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 288-310

Domestic fans up to 0.19 m3/s


Domestic fans for the ventilation of bathrooms, toilets, storage rooms, for installation on walls, in ceilings, in ducts and in windows. Technical data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 314-317

Other products from Systemair


Systemair has an extensive range of ventilation products: fans including smoke extract, tunnel and car park fans, explosion proof fans, air handling units from large central units to small residential units with energy recovery, air distribution products and fire dampers. These products are installed in a variety of locations, including homes, offices, healthcare premises, shops, industrial buildings, tunnels, parking garages, training facilities, sports centres etc.

Air handling units


Systemair produces a wide range of air handling units.

Compact air handling units


Compact supply air handling unit with heating battery and filter for use in petrol stations, schools, stores, offices and smaller premises. The units are compact in dimensions and are easy to install. Air flow: 20-1400 l/s

False ceiling units


Compact and easy to maintain air handling unit with heat recovery and control system. Mounted in a false ceiling or in the attic. Air flow: 20-1500 l/s

Horizontal units
A broad range of horizontal air handling units with or without heat recovery. Useable everywhere from minor premises to schools, stores and larger offices. Air flow: 20-1500 l/s

Vertical units
A broad range of vertical air handling units with or without heat recovery. Useable everywhere from minor premises to schools, stores and larger offices. Air flow: 20-1500 l/s

residential Ventilation
Complete energy-efficient air handling units with heat recovery and built-in control systems. Designed to be mounted over the cooker, on walls or horizontally in attics.

Residential units
For homes with living areas of 60-320 m .
2

Cooker hoods
Ideal for capturing odours even at low airflows.

Catalogues for other products


We have seperate catalogues for Air Handling Units and Air Distribution Products as well as leaflets and brochures for our entire product range. Contact us for printed versions or download on www.systemair.com.

Fire and smoke dampers


Systemair produces fans, dampers and control equipment for dual use, i.e. for normal operation and certified for use during normal operation and in the event of a fire.

Fire & smoke dampers


Dampers that reduce the spread of smoke and fire.

Air distribution products


Systemairs range also includes a wide selection of air distribution products suitable for a variety of applications and requirements. Development and manufacture take place in modern factories in Slovakia, Sweden and India.

Supply, extract & transfer devices


For mounting in ceilings or walls.

Nozzle diffusers
Optimum flexibility and comfort in air distribution for rooms

Supply & extract air valves


For mounting in ceilings and walls.

Volume control
Dampers, plenum boxes, VAV/CAV and duct accessories.

A good indoor climate is vital


We often take natural resources such as fresh air for granted. We must however remain frugal with this essential resource and mindful of maintaining a responsible balance between the designing of good ventilation systems and considering energy consumption and well thought out material usage and production methods. Systemair has recognized this need and has developed the "Green Ventilation" registered trade mark for labelling these products.

Heat recovery
In areas with a relatively low average annual temperature, ventilation systems employ effective heat recovery that returns energy from extract air to the supply air. A good rotating heat exchanger can recover up to 90% of the energy present.

Pressure
The design of the duct system and the unit has an impact on required system pressure. There are often tens, sometimes hundreds, of Pascals to be saved here. Systemair we are going one step further and working hard to ensure that our products maintain a high standard and are approved by various bodies. For units, this may mean Eurovent certification or other local certification for the country in question. To achieve this, you need resources and expertise. Within the Group, you will find, among other things, one of Europes most modern development centres, which is AMCA-certified. Systemair "sileo" ranges: The new generation of Systemair products with high efficiency and at the same time drastically reduced sound levels. A new impeller generation, introduced in our roof fans DVS/ DHS and our axial fans AW/AR. Read more in our online-catalogue.

Cool recovery
In warmer parts of the world, energy savings may be possible by drawing cool night-time supply air into premises, thus cooling the building structure.

Energy-efficient fans
Today, there is a new generation of fan motors that contribute to a dramatic reduction in energy consumption, as much as 50% in some cases. The new EC motors are better suited to speed control functions, which is where considerable energy savings can be made. Further benefits are of quieter operation as well as extended product life.

Quality-certified products
How can you choose the right solution and product when there are so many alternatives? Nowadays, most major suppliers are ISO-certified and have CEmarked products, but is that enough? At

One of Europe's most modern development centres


A room that is so quiet that the only thing youll hear is your heartbeat. The development centre in Skinnskatteberg, recently accredited by AMCA, signifies an investment of EUR 700,000 and is fitted with measurement and testing equipment, making it one of the most modern facilities of its kind in Europe. The quiet room is one of the test stations or a reverberation chamber, producing a background sound of less than 10 dBA. When measuring supply air terminals, a green laser is used to show how the air is expelled from wall-mounted or ceilingmounted devices. There is also a climate chamber that cools the air to -20C, which means we can use it all year round to develop our recovery units. In addition to the test centre in Skinnskatteberg, there are also test facilities in Germany and Denmark where we can measure air volumes of more than 400000 m3/h.

10

Selection tools
We have developed this overview to make it easier for you to get an idea of which product best suits your specific needs. More detailed analysis or planning usually requires additional information, which is where the following tools come in.

Product catalogue and specification data


More detailed technical information, sufficient to carry out complete planning, is available in separate catalogues and specification data. These describe all incorporated functions, available accessories, and additional technical data.

Online catalogue and computer software


For those who prefer to work online, it is possible to select and dimension most products (except DV and NB) using Systemairs online catalogue. In addition to complete product information, there is also a selection function that suggests alternative products to suit actual needs. For certain products, such as Topvex, medium pressure axial fans, air handling units DV and NB, there is computer software that you can download and install locally.

Personal support
Systemair aims to have local expertise close to the customer. You can find up-to-date information and contact details for each country on our website, www.systemair.com.

11

Efficiency classification IE2 New motor efficiency classification IE2


With the aim to reduce world-wide energy consumption, the International Electrotechnical Commission (IEC) has developed and published a new standard, IEC 60034-30:2008. This new worldwide standard defines efficiency classes of low voltage three phase motors for 50/60Hz supply with motor powers between 0,75 and 375 kW.

IE2
2009/640/EG

In the EEA (European Economic Area) this standard was the base for the guideline 2009/640/EU, which defines minimum efficiencies for motors being sold, installed and operated in this area. Since 16.6.2011 the minimum efficiency class for those motors is IE2. Those motors combine the benefits of a higher efficiency with a longer lifetime. This guideline has had an influence on the Systemair product range. All three phase IEC motors, used for example in Multibox MUB, roof fans DVN, axial fans AXC and other Systemair products, covered by the EU guideline have been replaced by high efficiency IE2 motors. IE2 motors cannot be speed controlled by voltage, i.e. voltage transformers.

Systemair is offering a newly developed range of frequency inverters, FRQ, to fill this gap, offering a real plug and play solution no need for time consuming configuration at site, and when choosing the FRQ-S models, no need to install expensive shielded cable. Read more on www. systemair.com. Another excellent alternative to IE2 high efficiency motors are Systemair fans with EC-motors, offering up to 50% energy saving. All EC fans are fully speed controllable by a simple 0-10V signal. Full technical details on www.systemair.com.

12

Product features and applications


Fans suitable for continous operation with 100C, 120C, 200C medium temperature

100C

120C

200C

Explosion proof fans certified in accordance with ATEX 94-9 EC

300C 120min

400C 120min

600C 120min

Smoke extract fans certified in accordance with EN 12101-3

Workshops/Industries

Warehouses/Storage facilitiies

Car parks

Laboratories

Battery rooms

Kitchens/Bakeries

13

EC-fans The challenge


Energy-saving
Everyones talking about climate protection, and calling for immediate action. But what needs to be done? The challenge has to be faced by individuals as well as by organisations. If companies are to take their corporate social responsibility seriously, and consumers are to adopt LOHAS (Lifestyle of Health and Sustainability), the focus will most definitely be on sustainable materials and efficiency. Avoiding the use of energy is one thing, but the true answer in this context is to use it more efficiently. Then it will be possible to maintain the function, comfort and convenience that are part of a modern lifestyle. Systemair, the ventilation company, offers you an opportunity to play an active part in this process. It has developed a simple, effective answer that creates a win-win situation; in other words you, your customer and the environment all benefit. Space-saving The control electronics are fully integrated and not visible. Low noise The reduction of noise emission is immediately evident. Energy-saving EC-motors consume an average of 30% less energy than standard alternating current motors. In some applications, the saving can be 50% or more. Flexible Suitable for use in 50 Hz and 60 Hz mains systems all over the world, so that fewer versions are needed. A reliable investment Long operating life and advanced technology with no unnecessary use of scarce natural resources. Payback-optimised Reduced energy consumption through high efficiency guarantees a drop in operating costs. EC-Vent offers a solution that provides: Lower energy usage then traditional systems. A ventilation rate that matches the requirements every time. Reduced operating costs. Ease of installation. Lower sound. Longer lifetime. The philosophy of EC-Vent is to provide a variable degree of ventilation that may be required to handle variable occupancy levels. EC-Vent responds to the exact ventilation requirements of a room at any time with the help of several sensor inputs; providing a ventilation rate that perfectly matches the required level of ventilation and therefore using as little energy as possible to achieve the desired indoor air quality. EC-Vent comprises a control unit located near the fan plus a remote room unit. Control unit and room unit ready for different sensors e.g. CO2, temp, humidity, pressure etc. Room unit has built in humidity and temperature sensors. Possibility to program a week schedule. Built in transformer with 24V feed to sensors, dampers etc. User friendly menu.

More than just hot air!


In Europe alone, ventilation fans consume about 197000 GWh. This puts them among the largest electricity users overall. Even a 12-15% improvment in efficiency could reduce CO2 emissions by 19 million tons. In other words, companies could cut annual operating costs by as much as 2.6 billion Euros by optimising the motor systems. And since the use of fans will increase in the years to come, there is an obvious need for innovative solutions in the motor area.

Advantages and benefits


Straightforward modern economical Convenient Easy to install. Demand-oriented Adjustment of fan performance by stepless speed control; excellent control features. Maintenance-free Guaranteed reliable operation and longterm value retention with a minimum of routine upkeep. Flexible 100% control technology for all control values. Makes efficient use of energy The proportion of energy used effectively is far higher than with an AC motor.

Energy efficient ventilation


Energy efficient ventilation is about designing the system in a smart way, using fans that have high efficiency and adjusting the ventilation rate to the actual need while keeping a good indoor air quality. Systemairs new EC-Vent greatly simplifies demand-controlled change of ventilation. EC-Vent is an intelligent controller that provides an effective and very efficient means of using variable speed ventilation solutions with the help of multiple sensor input that will offer a trickle and boost control and/or a proportional control. By controlling high efficiency, EC-driven exhaust and/or supply fans as well as other components of a ventilation system it promotes new levels of comfort and energy use in a wide variety of environments.

In combination with energy efficient ECdriven fans, EC-Vent offers an intelligent yet easy-to-install climate solution for new buildings as well as retrofit projects.

14 14

EC-fans

K EC. . . . . . . . . . . . . . . . . . . . 18

TFSK/TFSR EC. . . . . . . . . . . 124

KVKE EC. . . . . . . . . . . . . . . . . 56

DVC/DVCI . . . . . . . . . . . . . . 132

MUB EC. . . . . . . . . . . . . . . . . 94

KBR/KBT EC . . . . . . . . . . . . 300

15 15

Circular duct fans

IGC Intake grid IGK Intake grid

KVKE/KVO FFR Filter cassette

FK Fast clamp FGR Filter cassette KD K FK Fast clamp LDC Silencer KVK

VBF Water heating battery with filter

VBC Water heating battery CB/CBM Electrical heating FK battery Fast clamp SPI CWK cooling battery Iris damper water based

RVK

Sinus B Diffuser Sinus A Diffuser

Elegant Diffuser

General
Systemair circular duct fans have been developed for use in compact exhaust and supply air systems. The Systemair circular duct fan was the first in-line duct fan available on the market in this design. The availability of a comprehensive range of accessories, including heating and cooling coils, filters, silencers and more, offers solutions for complete systems for almost all applications. Our experience over the past 35 years and continuous research and development of new products and technologies has resulted in the Systemair circular duct fan system being a market leader. Our motto the straight way is revealed in the straight routing of the air in a ducted system.

Systemair range
Systemair offers different variants of circular duct fans. For systems with higher pressure losses we are offering the ranges K and RVK. The KV range can be installed directly on the wall. For higher air volumes we are offering the KD range with mixed flow impellers. When a low noise level is required, we are offering the ranges KVK, KVKE and KVO, all with sound absorbent insulation.

Motors

Systemair circular duct fans are all equipped with external rotor motors, speed controllable by voltage. All motors are equipped with thermal contacts (TK) for effective thermal motor protection. The TK is internally wired in the ranges K, KV, RVK and KVKE. Manual re-setting of the TK is in accordance with EN 60335-2-80. The KD, KVK and KVO ranges are partly equipped with internally wired TK, partly with TK with extended leads. The TK leads have to be connected to an external motor protection device. (See Electrical Accessories) NB! Failure to connect the TK provided will result in all warranties being null and void.

16

Circular duct fans

Circular duct fans

K EC. . . . . . . . . . . . . . . . . . . . 18 Circular metal duct fans with EC-motors: up to 0.48 m3/s, backward curved impeller, 1 phase.

KVK . . . . . . . . . . . . . . . . . . . . 46 Insulated box fans: up to 1.49 m3/s, forward curved impeller, 1 phase.

K/KV. . . . . . . . . . . . . . . . . . . 22 Circular metal duct fans: up to 0.45 m3/s, backward curved impeller, 1 phase.

KVK DUO. . . . . . . . . . . . . . . . 52 Insulated twin box fans: up to 1.49 m3/s, forward curved impeller, 1 phase.

RVK . . . . . . . . . . . . . . . . . . . . 28 Circular duct fan in plastic: up to 0.47 m3/s, backward curved impellers, 1 phase.

KVKE EC. . . . . . . . . . . . . . . . . 56 Insulated box fans with Ecmotors: up to 0.52 m3/s. With backward curved impeller, 1 phase.

KVO. . . . . . . . . . . . . . . . . . . . 34 Box fans: up to 0.8 m3/s. With backward curved impeller, 1 phase.

KVKE . . . . . . . . . . . . . . . . . . . 60 Insulated box fans: up to 0.6 m3/s. With backward curved impeller, 1 phase.

KD . . . . . . . . . . . . . . . . . . . . . 38 Circular mixflow duct fans: up to 2.3 m3/s, mixflow impeller, 1 and 3 phase.

17

Circular duct fans

Circular duct fans K EC


EC-motors, high level of efficiency 100% speed controllable Integrated motor protection Supplied with mounting bracket MTP 10 p. 341 Electrical accessories

EC technology is intelligent technology; using integral electronic control which eliminates the slip losses in the motor and ensures that the motor always runs at optimal load and guarantees that the proportion of energy utilised effectively is many times higher and that the energy usage is considerably lower compared to AC motors. Another special feature of EC fans is their energy-saving potential not only at full load, but especially at part-load. When operating at part-load, the energy used is much lower than with an asynchronous motor of equivalent output. Reduced energy usage guarantees a drop in operating costs. The K EC series is designed for installation in ducts. All the K fans have minimum 25 mm long spigot connections. The fans have backward-curved blades and external rotor motors (EC). The FK mounting clamp facilitates easy installation and removal, and prevents the transfer of vibration to the duct. The fans are delivered with a pre-wired potentiometer (0-10V) which allows you to easily set the desired working point. Motor protection is integrated in the electronics of the motor. The casing is manufactured from galvanised sheet steel with the seams folded to give the fan a close to air tight casing. Outdoor mounting and wet room applications are possible due to the fans air tight casing. By using an EC fan you eliminate the need for an electrical protection unit and speed controller. This should be considered when doing a cost comparison with a standard AC fan model. It also simplifies the process when commissioning.

EC-Vent p. 329-330

MTV 1/010 p. 341

Technical data
K Art no. Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Motor protection Speed control, stepless Wiring diagram p. 391-400 Electronic V/50 Hz W A m3/s min-1 C C dB(A) kg 160 EC 2580 230 1~ 79.4 0.628 0.151 3105 60 60 47 3 B IP 44 Integral MTP 10 41 200 EC 2581 230 1~ 78.6 0.626 0.215 2468 60 60 51 3.3 B IP 44 Integral MTP 10 41 250 EC 2583 230 1~ 120 0.921 0.287 2628 40 40 46 3.5 B IP 44 Integral MTP 10 41 315 M EC 2584 230 1~ 166 1.14 0.393 2113 40 40 50 6 B IP 44 Integral MTP 10 41 315 L EC 2585 230 1~ 340 2.08 0.481 2719 55 55 57 7.2 B IP 44 Integral MTP 10 41

18

Circular duct fans


Dimensions
B A E 40

Circular duct fans

Ventilation accessories

FK p. 355

(F)

88

SG p. 357
C

VK p. 356
A K 160 EC K 200 EC K 250 EC K 315 L EC 159 199 249 314 B 286 336 336 408 408 C 25 30 30.5 32.5 37.5 D 147 148 144.5 160.5 160.5 E 26 27 27 27 27 (F) 198 205 202 220 225

K 315 M EC 314

RSK p. 355

LDC p. 348

FFR p. 349

CB p. 350

Quick selection

1 2 3 4 5

19

Circular duct fans

Circular duct fans


Performance

dB(A) LwA Duct LwA Surrounding With LDC 160-900 LwA Duct

Tot 63 78 54 69 53 22 51 125 72 28 68

Frequency bands [Hz] 250 73 39 63 500 73 50 45 1k 69 48 27 2k 66 47 23 4k 56 40 36 8k 46 29 31

dB(A) LwA Duct LwA Surrounding With LDC 200-900 LwA Duct

Tot 63 77 58 67 51 24 49 125 70 38 66

Frequency bands [Hz] 250 68 45 60 500 73 57 49 1k 68 50 36 2k 63 45 29 4k 55 39 42 8k 47 29 37

Measurement point: 0,0717 m/s; 367 Pa

Measurement point: 0,108 m/s; 274 Pa

dB(A) LwA Duct LwA Surrounding With LDC 250-900 LwA Duct

Tot 63 74 53 52 16 125 65 36

Frequency bands [Hz] 250 68 40 500 68 50 1k 66 46 2k 61 44 4k 53 34 8k 43 23

dB(A) LwA Duct LwA Surrounding With LDC 315-900 LwA Duct

Tot 63 76 57 69 53 24 52 125 70 33 67

Frequency bands [Hz] 250 67 48 60 500 70 52 54 1k 69 49 47 2k 65 50 53 4k 65 48 59 8k 60 36 53

64

49

61

60

48

40

38

43

35

Measurement point: 0,119 m/s; 383 Pa

Measurement point: 0,181 m/s; 319 Pa

20

Circular duct fans

Circular duct fans

dB(A) LwA Duct LwA Surrounding With LDC 315-900 LwA Duct

Tot 63 82 64 74 67 47 66 125 74 45 71

Frequency bands [Hz] 250 74 58 67 500 78 61 62 1k 75 54 53 2k 71 54 59 4k 69 52 63 8k 67 44 60

Measurement point: 0,227 m/s; 591 Pa

21

Circular duct fans

Circular duct fans K/KV


Speed-controllable Integral thermal contacts Can be installed in any position Can be installed outdoors Maintenance-free and reliable Electrical accessories

RE p. 320

The K series is designed for installation in ducts and the KV is designed to be used as a wall mounted duct-connected extract fan. All the K/ KV-fans have a minimum 25 mm long spigot connections. The fans have backward-curved blades and external rotor motors. To simplify installation the K-fan has a fixing bracket together with screws for mounting the bracket included as standard. The FK mounting clamp facilitates easy installation and removal, and prevents the transfer of vibration to the duct. The fans can be speed-controlled via a stepless thyristor or a 5-step transformer. To protect the motor from overheating K/KV 100 M and 125 M is impedance protected, K/KV 100 XL-315 L has integral thermal contacts with electrical reset. The casing is manufactured from galvanised sheet steel and folded which gives the fan an air tight casing. Duct connected outdoor and wet room applications of the fan are possible due to the air tight casing. Quick selection

REU p. 320

REE p. 321

1 2 3 4 5 6 7 8

K/KV 100M K/KV 100XL K/KV 125M K/KV 125XL K/KV 150 M K/KV 150 XL K/KV 160M K/KV 160XL

5961, 4115, 5994, 4110, 4218, 4506, 3986, 4501

1 2 3 4 5 6

K/KV 200M K/KV 200L K/KV 250M K/KV 250L K/KV 315M K/KV 315L

4 3 1 2 5 6

3 1

Technical data
K/KV Art no. Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Capacitor Motor protection Speed control, five-step Speed control, five step high/low Speed control, stepless Wiring diagram p. 391-400 100 M 1001/1205 V/50 Hz 230 1~ W 29.9 A 0.171 m3/s 0.051 min-1 2443 C 70 C 70 dB(A) 38 kg 2.5 B IP 44 F Integral Transformer RE 1.5 Transformer REU 1.5 Thyristor REE 1 1 100 XL 1004/1207 230 1~ 58.6 0.253 0.074 2425 70 70 48 2.5 B IP 44 2 Integral RE 1.5 REU 1.5 REE 1 2 125 M 1002/1208 230 1~ 29.1 0.172 0.057 2483 70 70 34 2.5 B IP 44 Integral RE 1.5 REU 1.5 REE 1 1 125 XL 1003/1210 230 1~ 62 0.271 0.0978 2390 70 70 50 2.5 B IP 44 2 Integral RE 1.5 REU 1.5 REE 1 2 150 M 1017/1211 230 1~ 61 0.264 0.122 2412 70 70 42 3.5 B IP 44 2 Integral RE 1.5 REU 1.5 REE 1 2 150 XL 1018/1212 230 1~ 104 0.458 0.199 2567 70 70 55 4.5 B IP 44 3 Integral RE 1.5 REU 1.5 REE 1 2 160 M 1005/1213 230 1~ 59 0.259 0.136 2499 70 70 44 3 B IP 44 2 Integral RE 1.5 REU 1.5 REE 1 2

22

4401, 4398, 4427, 4453, 6112, 6121

Circular duct fans


Dimensions
B A E 40

Circular duct fans

Ventilation accessories
K 100 M 100 XL 125 M
88

A 99 99 124 124 149 149 159 159 199 199 249 249 314 314

B 218 246 218 246 286 336 286 336 336 336 336 336 408 408

C 26 26 27 26 25 29 25 29 30 30 30.5 30.5 32.5 37.5

D 166 161 142 151 152 171 147 166 148 174 119.5 144.5 160.5 160.5

E 26 26 27 26 25 26 26 26 27 27 27 27 27 27

F 218 213 196 203 202 226 198 221 205 231 177 202 220 225

FK p. 355

(F)

125 XL 150 M 150 XL

160 M 160 XL 200 M 200 L 250 M 250 L 315 M 315 L

SG p. 357

VK p. 356

40 5

KV 100 M 100 XL 125 M 125 XL 150 M 150 XL

A 99 99 124 124 149 149 159 159 199 199 249 249 314 314

B 218 246 218 246 286 336 286 336 336 336 336 336 408 408

C 26 26 27 26 25 29 25 29 30 30 30.5 30.5 32.5 37.5

D 143 125 131 127 113 147 113 147 134 158 135 159 145 145

E 254 304 254 304 344 394 344 394 394 394 394 394 458 458

F 284 334 284 334 374 425 374 425 425 425 425 425 489 489

RSK p. 355

LDC p. 348

A B E F

160 M 160 XL 200 M 200 L 250 M 250 L 315 M 315 L

FFR p. 349

CB p. 350

K/KV Art no. Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Capacitor Motor protection Speed control, five-step Speed control, five step high/low Speed control, stepless Wiring diagram p. 391-400

160 XL 1006/1214 V/50 Hz 230 1~ W 105 A 0.457 m3/s 0.214 min-1 2553 C 70 C 70 dB(A) 53 kg 4.5 B IP 44 F 3 Integral Transformer RE 1.5 Transformer REU 1.5 Thyristor REE 1 2

200 M 1007/1215 230 1~ 106 0.463 0.216 2551 70 70 51 4.5 B IP 44 3 Integral RE 1.5 REU 1.5 REE 1 2

200 L 1008/1216 230 1~ 158 0.709 0.269 2630 50 50 50 4.5 B IP 44 4 Integral RE 1.5 REU 1.5 REE 1 2

250 M 1009/1217 230 1~ 103 0.448 0.216 2579 70 70 49 4.5 B IP 44 3 Integral RE 3 REU 3 REE 1 2

250 L 1010/1218 230 1~ 157 0.699 0.267 2641 70 70 49 5 B IP 44 4 Integral RE 3 REU 3 REE 1 2

315 M 1011/1219 230 1~ 202 0.893 0.347 2578 51 51 47 6 F IP 44 5 Integral RE 1.5 REU 1.5 REE 2 2

315 L 1012/1220 230 1~ 318 1.39 0.48 2318 51 45 50 7 F IP 44 7 Integral RE 1.5 REU 1.5 REE 2 2

23

Circular duct fans

Circular duct fans


Performance

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 100-600 LwA Inlet LwA Outlet

Tot 63 63
60 45

Frequency bands [Hz] 125 59


54 14

dB(A) 4k 40
38 29

Tot 63 125 65 63 28 62 60 72 69 55 63 61 49 49 28 45 45

Frequency bands [Hz] 250 68 63 47 57 52 500 66 65 51 42 41 1k 62 60 48 26 24 2k 55 55 46 6 6 4k 52 54 44 18 20 8k 40 44 30 23 27

250 56
55 23

500 58
54 36

1k 50
49 41

2k 47
44 42

8k 28
27 17

50
35 21

LwA Inlet LwA Outlet LwA Surrounding With LDC 100-600 LwA Inlet LwA Outlet

57 52

46 31

56 51

45 44

34 30

14 13

0 0

6 4

11 10

Measurement point: 0,231 m/s; 105 Pa

Measurement point: 0,04 m/s; 201 Pa

dB(A)
LwA Inlet LwA Outlet LwA Surrounding

Tot 63 59 60 41 50 50 33 40 12 30 37 125 51 46 9 48 43

Frequency bands [Hz] 250 54 58 24 45 49 500 55 55 39 32 32 1k 48 47 32 18 17 2k 45 44 33 5 4 4k 36 38 25 14 16 8k 29 31 18 15 17

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 125-600 LwA Inlet LwA Outlet

Tot 63 73 73 57 64 64 56 55 35 53 52 125 65 64 31 62 61

Frequency bands [Hz] 250 68 68 46 59 59 500 69 68 53 46 45 1k 65 64 52 35 34 2k 61 61 48 21 21 4k 52 57 40 30 35 8k 41 50 29 27 36

With LDC 125-600


LwA Inlet LwA Outlet

Measurement point: 0,0267 m/s; 104 Pa

Measurement point: 0,0469 m/s; 190 Pa

24

Circular duct fans

Circular duct fans

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 150-600 LwA Inlet LwA Outlet

Tot 63 70 69 49 63 63 45 46 24 45 46 125 63 63 25 60 60

Frequency bands [Hz] 250 66 66 43 59 59 500 64 60 46 44 40 1k 58 56 40 31 29 2k 55 52 39 24 21 4k 51 50 36 35 34 8k 42 41 24 31 30

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 150-600 LwA Inlet LwA Outlet

Tot 63 78 76 62 70 68 56 51 26 56 51 125 67 67 28 64 64

Frequency bands [Hz] 250 75 73 43 68 66 500 74 70 61 54 50 1k 67 65 47 40 38 2k 62 61 49 31 30 4k 62 60 50 46 44 8k 54 49 36 43 38

Measurement point: 0,063 m/s; 202 Pa

Measurement point: 0,0869 m/s; 294 Pa

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 160-900 LwA Inlet LwA Outlet

Tot 63 70 68 51 62 60 43 44 13 41 42 125 65 62 23 61 58

Frequency bands [Hz] 250 64 64 35 54 54 500 65 61 47 37 33 1k 61 59 43 19 17 2k 59 56 46 16 13 4k 48 48 38 28 28 8k 37 37 23 22 22

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 160-900 LwA Inlet LwA Outlet

Tot 63 77 75 60 65 65 49 47 24 47 45 125 65 65 31 61 61

Frequency bands [Hz] 250 72 72 42 62 62 500 73 68 59 45 40 1k 67 65 46 25 23 2k 63 63 46 20 20 4k 63 62 49 43 42 8k 51 50 35 36 35

Measurement point: 0,0681 m/s; 201 Pa

Measurement point: 0,0956 m/s; 278 Pa

25

Circular duct fans

Circular duct fans

dB(A)
LwA Inlet LwA Outlet LwA Surrounding

Tot 63 75 74 58 65 64 47 45 16 45 43 125 67 65 40 63 61

Frequency bands [Hz] 250 67 69 39 59 61 500 72 68 54 48 44 1k 65 63 49 33 31 2k 61 62 52 27 28 4k 59 61 52 46 48 8k 50 50 37 40 40

dB(A)
LwA Inlet LwA Outlet LwA Surrounding

Tot 63 75 74 57 66 66 49 51 17 47 49 125 68 66 30 64 62

Frequency bands [Hz] 250 70 71 41 62 63 500 71 67 52 47 43 1k 65 64 49 33 32 2k 62 62 52 28 28 4k 58 60 48 45 47 8k 50 53 36 40 43

With LDC 200-900


LwA Inlet LwA Outlet

With LDC 200-900


LwA Inlet LwA Outlet

Measurement point: 0,108 m/s; 276 Pa

Measurement point: 0,136 m/s; 336 Pa

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 250-900 LwA Inlet LwA Outlet

Tot 63
70 70 56 45 46 18

Frequency bands [Hz] 125


59 58 31

dB(A) 4k
62 62 52

Tot 63 125 66 64 33 62 60 74 75 56 65 65 59 58 34 56 55

Frequency bands [Hz] 250 67 71 45 59 63 500 68 66 52 48 46 1k 67 68 47 41 42 2k 62 66 50 39 43 4k 55 58 46 45 48 8k 46 49 33 38 41

250
61 62 31

500
65 64 48

1k
62 61 44

2k
60 63 51

8k
53 51 39

LwA Inlet LwA Outlet LwA Surrounding With LDC 250-900 LwA Inlet LwA Outlet

59 59

42 43

55 54

53 54

45 44

36 35

37 40

52 52

45 43

Measurement point: 0,11 m/s; 241 Pa

Measurement point: 0,13 m/s; 366 Pa

26

Circular duct fans

Circular duct fans

dB(A)
LwA Inlet LwA Outlet LwA Surrounding

Tot 63 73 70 54 63 60 51 49 22 50 48 125 60 56 28 57 53

Frequency bands [Hz] 250 66 62 39 59 55 500 69 62 48 53 46 1k 67 65 45 45 43 2k 62 64 47 50 52 4k 58 58 43 52 52 8k 55 54 50 48 47

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 315-900 LwA Inlet LwA Outlet

Tot 63 76 77 57 68 69 55 63 24 54 62 125 67 67 37 64 64

Frequency bands [Hz] 250 70 71 45 63 64 500 71 69 52 55 53 1k 68 70 49 46 48 2k 66 69 50 54 57 4k 63 63 46 57 57 8k 58 57 46 51 50

With LDC 315-900


LwA Inlet LwA Outlet

Measurement point: 0,18 m/s; 357 Pa

Measurement point: 0,203 m/s; 438 Pa

27

Circular duct fans

Circular duct fans RVK


Speed-controllable Integral thermal contacts Can be installed in any position Inclusive mounting bracket Maintenance-free and reliable Electrical accessories

RE p. 320

The RVK series is designed for installation in ducts. The casing is manufactured from PA6 fibreglass reinforced plastic which gives the fan a low leakage casing. Duct connected wet room applications of the fan are possible due to a close to air tight casing and the IP 44 rated terminal box.The fans have backward-curved blades and external rotor motors. The FK mounting clamp facilitates easy installation and removal, and prevents the transfer of vibration to the duct. The fans can be speed-controlled via a stepless thyristor or a 5-step transformer. The RVK fans have integral thermal contacts with automatic reset.

REU p. 320

REE p. 321

Quick selection

5156, 5136, 5541, 5403, 5429, 5231, 5414

1 2 3 4 5 6 7

RVK 100E2-A1 RVK 125E2-A1 RVK 125E2-L1 RVK 150E2-A1 RVK 150E2-L1 RVK 160E2-A1 RVK 160E2-L1

1 2 3 4 5 6 7

RVK 200E2-A1 RVK 200E2-L1 RVK 250E2-A1 RVK 250E2-L1 RVK 250E2-XL RVK 315E2-A1 RVK 315E2-L1

1 2

5 6

2 4

Technical data
RVK Art no. Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Capacitor Motor protection Speed control, five-step Speed control, five step high/low Speed control, stepless Wiring diagram p. 391-400 100E2-A1 5755 V/50 Hz 230 1~ W 29.1 A 0.171 m3/s 0.0512 min-1 2482 C 70 C 70 dB(A) 35 kg 2 B IP 44 F Impedans Transformer RE 1.5 Transformer REU 1.5 Thyristor REE 1 1 125E2-A1 5756 230 1~ 29.2 0.172 0.0612 2469 70 70 38 2 B IP 44 Impedans RE 1.5 REU 1.5 REE 1 1 125E2-L1 9775 230 1~ 61.2 0.26 0.0947 2436 70 70 43 2 B IP 44 2 Integral RE 1.5 REU 1.5 REE 1 2 150E2-A1 5757 230 1~ 59.9 0.261 0.118 2418 70 70 48 3 B IP 44 2 Integral RE 1.5 REU 1.5 REE 1 2 150E2-L1 5758 230 1~ 115 0.5 0.185 2497 70 70 50 2.7 B IP 44 3 Integral RE 1.5 REU 1.5 REE 1 2 160E2-A1 5759 230 1~ 57.8 0.257 0.125 2429 70 70 43 3 B IP 44 2 Integral RE 1.5 REU 1.5 REE 1 2 160E2-L1 5760 230 1~ 112 0.485 0.202 2530 70 70 48 2.7 B IP 44 3 Integral RE 1.5 REU 1.5 REE 1 2

28

5602, 5607, 5618, 5640, 6694, 5648, 5458

Circular duct fans


Dimensions
C A

Circular duct fans

Ventilation accessories

FK p. 355
E

SG p. 357
I B J G F

RVK 100E2-A1 125E2-A1 125E2-L1 150E2-A1 150E2-L1 160E2-A1 160E2-L1 200E2-A1 200E2-L1 250E2-A1 250E2-L1 250E2-XL 315E2-A1 315E-L1

A 99 124 124 149 149 159 159 199 199 249 249 249 315 315

B 99 124 124 149 149 159 159 199 199 249 249 249 315 315

C 251 251 251 340.5 340.5 340.5 340.5 340.5 340.5 340.5 340.5 340.5 405 405

D 30 30 30 30 30 30 30 30 30 30 30 30 30 30

E 230 230 230 230 230 230 230 230 250 230 230 230 275 275

F 30 30 30 30 30 30 30 30 30 30 30 30 30 30

G 271.5 271.5 271.5 271.5 271.5 271.5 271.5 271.5 271.5 271.5 271.5 271.5 271.5 271.5

I 60 60 60 60 60 60 60 60 60 60 60 60 60 60

J 200 200 200 200 200 200 200 200 200 200 200 200 200 200

VK p. 356

RSK p. 355

LDC p. 348

FFR p. 349

CB p. 350

RVK Art no. Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Capacitor Motor protection Speed control, five-step Speed control, five step high/low Speed control, stepless Wiring diagram p. 391-400

200E2-A1 5761 V/50 Hz 230 1~ W 107 A 0.47 m3/s 0.216 min-1 2550 C 70 C 70 dB(A) 45 kg 3.3 B IP 44 F 3 Integral Transformer RE 1.5 Transformer REU 1.5 Thyristor REE 1 2

200E2-L1 5762 230 1~ 160 0.705 0.273 2581 70 55 46 3.7 B IP 44 4 Integral RE 1.5 REU 1.5 REE 1 2

250E2-A1 5763 230 1~ 109 0.476 0.234 2546 70 70 48 3.3 B IP 44 3 Integral RE 1.5 REU 1.5 REE 1 2

250E2-L1 5764 230 1~ 159 0.706 0.302 2595 57 57 44 4 B IP 44 4 Integral RE 3 REU 3 REE 1 2

250E2-XL 30901 230 1~ 213 0.935 0.341 2415 51 38 49 6 B IP 44 5 Integral RE 1.5 REU 1.5 REE 1 2

315E2-A1 5765 230 1~ 176 0.773 0.369 2387 70 70 40 5.0 F IP 44 5 Integral RE 1.5 REU 1.5 REE 1 2

315E2-L1 5766 230 1~ 318 1.39 0.51 2433 38 38 45 5.2 F IP 44 7 Integral RE 1.5 REU 1.5 REE 2 2

29

Circular duct fans

Circular duct fans


Performance

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 100-600 LwA Inlet LwA Outlet

Tot 63 62 57 41 39 42 1 125 57 52 11

Frequency bands [Hz] 250 57 51 30 500 57 51 37 1k 51 47 37 2k 44 43 34 4k 39 39 25 8k 27 28 14

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 125-600 LwA Inlet LwA Outlet

Tot 63 63 60 45 54 53 36 36 12 33 33 125 56 54 15 53 51

Frequency bands [Hz] 250 57 56 28 48 47 500 60 53 42 37 30 1k 52 50 37 22 20 2k 46 47 36 6 7 4k 41 42 27 19 20 8k 33 33 28 19 19

55 50

35 38

54 49

46 40

33 27

15 11

0 0

5 5

10 11

Measurement point: 0,0275 m/s; 93 Pa

Measurement point: 0,0347 m/s; 85 Pa

dB(A)
LwA Inlet LwA Outlet LwA Surrounding

Tot 63 70 69 50 64 62 49 50 23 46 47 125 66 64 37 63 61

Frequency bands [Hz] 250 64 64 36 55 55 500 65 64 48 42 41 1k 59 58 43 29 28 2k 55 55 43 15 15 4k 52 53 35 30 31 8k 42 44 23 28 30

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 150-600 LwA Inlet LwA Outlet

Tot 63 70 69 54 62 62 43 44 23 43 44 125 61 60 32 58 57

Frequency bands [Hz] 250 66 67 42 59 60 500 64 59 52 44 39 1k 58 57 47 31 30 2k 56 52 44 25 21 4k 53 51 38 37 35 8k 43 42 27 32 31

With LDC 125-600


LwA Inlet LwA Outlet

Measurement point: 0,0369 m/s; 226 Pa

Measurement point: 0,0606 m/s; 203 Pa

30

Circular duct fans

Circular duct fans

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 150-600 LwA Inlet LwA Outlet

Tot 63 74 73 57 66 67 42 43 19 42 43 125 67 68 35 64 65

Frequency bands [Hz] 250 68 69 39 61 62 500 71 68 56 51 48 1k 62 59 49 35 32 2k 57 55 45 26 24 4k 58 57 42 42 41 8k 48 48 29 37 37

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 160-900 LwA Inlet LwA Outlet

Tot 63 69 66 50 58 57 40 39 23 38 37 125 58 58 18 54 54

Frequency bands [Hz] 250 66 64 38 56 54 500 63 56 46 35 28 1k 60 58 45 18 16 2k 56 53 42 13 10 4k 54 53 37 34 33 8k 43 41 29 28 26

Measurement point: 0,0906 m/s; 284 Pa

Measurement point: 0,0731 m/s; 176 Pa

dB(A)
LwA Inlet LwA Outlet LwA Surrounding

Tot 63 71 70 55 59 61 41 42 18 39 40 125 62 63 35 58 59

Frequency bands [Hz] 250 63 65 31 53 55 500 68 64 53 40 36 1k 62 60 47 20 18 2k 59 58 45 16 15 4k 60 59 43 40 39 8k 50 49 33 35 34

dB(A)
LwA Inlet LwA Outlet LwA Surrounding

Tot 63 70 69 52 57 58 43 45 17 41 43 125 58 58 26 54 54

Frequency bands [Hz] 250 61 62 26 53 54 500 66 65 49 42 41 1k 62 59 44 30 27 2k 61 60 44 27 26 4k 59 60 42 46 47 8k 48 48 27 38 38

With LDC 160-900


LwA Inlet LwA Outlet

With LDC 200-900


LwA Inlet LwA Outlet

Measurement point: 0,107 m/s; 258 Pa

Measurement point: 0,122 m/s; 242 Pa

31

Circular duct fans

Circular duct fans

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 200-900 LwA Inlet LwA Outlet

Tot 63 73 73 53 49 48 14 125 64 64 27

Frequency bands [Hz] 250 67 69 36 500 68 65 51 1k 63 62 47 2k 61 63 45 4k 58 58 38 8k 49 49 28

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 250-900 LwA Inlet LwA Outlet

Tot 63 69 69 55 58 58 43 47 16 40 44 125 59 58 31 55 54

Frequency bands [Hz] 250 61 62 40 53 54 500 64 64 52 44 44 1k 61 59 51 35 33 2k 60 62 42 37 39 4k 59 61 40 49 51 8k 49 49 28 41 41

63 64

47 46

60 60

59 61

44 41

31 30

27 29

45 45

39 39

Measurement point: 0,141 m/s; 324 Pa

Measurement point: 0,118 m/s; 264 Pa

dB(A)
LwA Inlet LwA Outlet LwA Surrounding

Tot 63 71 73 51 63 65 49 52 19 46 49 125 65 64 41 61 60

Frequency bands [Hz] 250 66 71 37 58 63 500 65 62 48 45 42 1k 61 61 44 35 35 2k 59 61 42 36 38 4k 57 58 37 47 48 8k 49 50 26 41 42

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 250-900 LwA Inlet LwA Outlet

Tot 63 75 75 56 66 68 58 58 31 55 55 125 68 70 53 64 66

Frequency bands [Hz] 250 66 69 41 58 61 500 70 66 51 50 46 1k 67 68 44 41 42 2k 62 66 43 39 43 4k 59 61 34 49 51 8k 53 53 25 45 45

With LDC 250-900


LwA Inlet LwA Outlet

Measurement point: 0,144 m/s; 351 Pa

Measurement point: 0,145 m/s; 357 Pa

32

Circular duct fans

Circular duct fans

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 315-900 LwA Inlet LwA Outlet

Tot 63 69 70 47 60 61 43 46 12 42 45 125 57 59 25 54 56

Frequency bands [Hz] 250 62 62 38 55 55 500 62 64 45 46 48 1k 61 60 40 39 38 2k 59 61 38 47 49 4k 61 61 36 55 55 8k 54 54 26 47 47

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 315-900 LwA Inlet LwA Outlet

Tot 63 73 74 52 65 66 47 47 17 46 46 125 62 63 29 59 60

Frequency bands [Hz] 250 66 66 40 59 59 500 68 68 49 52 52 1k 64 66 44 42 44 2k 64 67 44 52 55 4k 66 67 44 60 61 8k 59 59 35 52 52

Measurement point: 0,181 m/s; 331 Pa

Measurement point: 0,254 m/s; 399 Pa

33

Circular duct fans

Circular duct fans KVO


Speed-controllable Integral thermal contacts Low sound level Compact construction S-ET p. 341 Electrical accessories

KVO has a single-inlet centrifugal fan (size 100-160 and size 355400 with forward curved blades, size 200-315 with backward curved blades) and a maintenance-free external rotor motor. In all KVO models, the motor and impeller are mounted on the cover for easy cleaning and maintenance. To protect the motor from overheating, the KVO 100-315 have integral thermal contacts with electrical reset, size 355-400 with integral thermal contact with external leads for connection to a motor protection device. The fans can be installed in any position, and are easy to connect to spiral ducts using FK mounting clamps. The lid is insulated with 40 mm rockwool. The casing is manufactured from galvanised sheet steel.

RTRE p. 320

RE p. 320

Quick selection REU p. 320


3103, 3009, 3023, 3913

1 2 3 4

KVO 100 KVO 125 KVO 160L KVO 200

1 2 3 4

KVO 250L KVO 315L KVO 355 KVO 400

3045, 8215, 8985, 9000

REE p. 321

Technical data
KVO Art no. Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Capacitor Motor protection Speed control, five-step Speed control, five step high/low Speed control, stepless Wiring diagram p. 391-400 100 2075 V/50 Hz 230 1~ W 77.9 A 0.346 m3/s 0.0778 min-1 2438 C 60 C 60 dB(A) 40 kg 6 B IP 44 F 2 Integral Transformer RE 1.5 Transformer REU 1.5 Thyristor REE 1 2 125 2020 230 1~ 89 0.393 0.101 2175 64 64 38 6 B IP 44 2 Integral RE 1.5 REU 1.5 REE 1 2 160 2024 230 1~ 135 0.59 0.138 2544 70 70 43 7 B IP 44 4 Integral RE 1.5 REU 1.5 REE 1 2 200 2025 230 1~ 151 0.681 0.244 2632 70 70 51 12.5 F IP 44 4 Integral RE 1.5 REU 1.5 REE 1 2 250 2027 230 1~ 301 1.33 0.417 2480 70 70 52 20 F IP 44 7 Integral RE 1.5 REU 1.5 REE 2 2 315 2029 230 1~ 549 2.38 0.592 2227 48 41 56 27.2 F IP 44 10 Integral RE 3 REU 5 REE 4 2

34

Circular duct fans


Dimensions Ventilation accessories
KVO 100 125 160 200 250
G H

Circular duct fans

A 100 125 160 200 250 315 355 400

B 329 329 329 419 527.5 535.5 572 572

C 367 367 367 466 568 580 661 653

D 69 84 99 123 151 186 209 221

E 76 72 90 109 133 166 231 209

F 300 300 300 435 558 580 640 640

G 150 150 185 220 270 340 425 425

H 150 150 185 220 270 550 600 600

FK p. 355

315
E

355 400
D A F

SG p. 357

VK p. 356

RSK p. 355

LDC p. 348

FGR p. 348

CB p. 350

KVO Art no. Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Capacitor Motor protection Speed control, five-step Speed control, five step high/low Speed control, stepless Wiring diagram p. 391-400 * + S-ET 10

355 2030 V/50 Hz 230 1~ W 1196 A 5.69 m3/s 0.882 min-1 1118 C 65 C 65 dB(A) 53 kg 38.6 F IP 54 F 20 S-ET 10 Transformer RTRE 7 Transformer REU 7* Thyristor 6

400 2031 230 1~ 1257 5.95 0.893 1075 58 58 56 38.6 F IP 54 20 Integral RTRE 7 REU 7* 6

35

Circular duct fans

Circular duct fans


pERFORMANCE

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 100-600 LwA Inlet LwA Outlet

Tot 63 63 68 47 47 55 21 125 60 61 36

Frequency bands [Hz] 250 57 58 41 500 55 60 39 1k 52 63 42 2k 47 58 37 4k 43 51 28 8k 38 45 22

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 125-600 LwA Inlet LwA Outlet

Tot 63 65 66 45 58 55 44 46 19 41 43 125 61 56 36 58 53

Frequency bands [Hz] 250 56 58 38 47 49 500 58 59 38 35 36 1k 57 61 39 27 31 2k 52 57 38 12 17 4k 49 50 33 27 28 8k 43 39 26 29 25

58 59

43 51

57 58

46 47

31 36

16 27

0 9

9 17

21 28

Measurement point: 0,0447 m/s; 105 Pa

Measurement point: 0,0475 m/s; 214 Pa

dB(A)
LwA Inlet LwA Outlet LwA Surrounding

Tot 63 68 75 50 52 55 31 125 62 63 39

Frequency bands [Hz] 250 63 69 45 500 61 67 42 1k 58 67 40 2k 57 69 41 4k 56 63 40 8k 53 59 39

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 200-900 LwA Inlet LwA Outlet

Tot 63 73 76 58 64 64 53 56 34 51 54 125 61 60 42 57 56

Frequency bands [Hz] 250 70 70 55 62 62 500 66 71 51 42 47 1k 66 71 50 34 39 2k 62 69 46 28 35 4k 56 60 37 43 47 8k 49 51 28 39 41

With LDC 160-900


LwA Inlet LwA Outlet

60 63

50 53

58 59

53 59

33 39

16 25

14 26

36 43

38 44

Measurement point: 0,0767 m/s; 272 Pa

Measurement point: 0,129 m/s; 349 Pa

36

Circular duct fans

Circular duct fans

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 250-900 LwA Inlet LwA Outlet

Tot 63 73 78 59 61 63 55 57 37 52 54 125 60 60 41 56 56

Frequency bands [Hz] 250 64 66 48 56 58 500 68 75 57 48 55 1k 66 71 51 40 45 2k 65 71 48 42 48 4k 61 64 42 51 54 8k 56 59 36 48 51

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 315-900 LwA Inlet LwA Outlet

Tot 63 78 86 63 72 79 56 64 42 55 63 125 73 75 53 70 72

Frequency bands [Hz] 250 73 84 59 66 77 500 67 79 59 51 63 1k 67 75 54 45 53 2k 68 72 50 56 60 4k 65 67 43 59 61 8k 57 61 35 50 54

Measurement point: 0,254 m/s; 388 Pa

Measurement point: 0,263 m/s; 640 Pa

KVO 355

KVO 400

dB(A)
LwA Inlet LwA Outlet LwA Surrounding

Tot 63 77 83 60 72 74 57 66 41 57 66 125 73 72 55 70 69

Frequency bands [Hz] 250 66 71 52 60 65 500 66 74 52 53 61 1k 69 78 53 51 60 2k 69 75 51 59 65 4k 68 74 46 62 68 8k 63 68 41 56 61

dB(A)
LwA Inlet LwA Outlet LwA Surrounding

Tot 63 80 84 63 75 77 61 68 39 60 67 125 75 73 56 72 70

Frequency bands [Hz] 250 71 74 57 66 69 500 69 75 54 59 65 1k 73 78 57 60 65 2k 72 76 54 65 69 4k 70 75 51 65 70 8k 65 69 45 59 63

With LDC 355-900


LwA Inlet LwA Outlet

With LDC 400-900


LwA Inlet LwA Outlet

Measurement point: 0,457 m/s; 404 Pa

Measurement point: 0,47 m/s; 381 Pa

37

Circular duct fans

Circular duct fans KD


High efficiency low noise Speed-controllable Integral thermal contacts Can be installed in any position Maintenance-free and reliable Electrical accessories

S-ET p. 341

The KD series have external rotor motors with a mixed flow impeller which reduces the external dimensions of the fans. These fans have high flow capacity in relation to their compact design. Brackets are supplied with the fans to make installation easier. The FK mounting clamp facilitates easy installation and removal and prevents the transfer of vibration to the duct. To protect the motor from overheating KD 200 L1, 250 M, 315 M1, 315 L1 and and 355 S1 have integral thermal contacts with electrical reset, and the remaining sizes have integral thermal contacts with leads to a motor protection device. The casing is manufactured from galvanised sheet steel.

RTRE p. 320

RE p. 320

Quick selection REU p. 320


1 2 3 4 5 6 7 8
1 2 3 4 5 6

REE p. 321

1 2

3 4 5

1 2

tECHNICAL DATA
KD Art no. Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Capacitor Motor protection Speed control, five-step Speed control, five step high/low Speed control, stepless Wiring diagram p. 391-400 *+ S-ET 10 200 L 1284 V/50 Hz 230 1~ W 257 A 1.14 m3/s 0.37 min-1 2562 C 55 C 46 dB(A) 53 kg 7 F IP 44 F 6 Integral Transformer RE 1.5 Transformer REU 1.5 Thyristor REE 2 2 250 M 1285 230 1~ 254 1.13 0.40 2572 55 46 54 6.5 F IP 44 6 Integral RE 1.5 REU 1.5 REE 2 2 250 L 1286 230 1~ 369 1.60 0.55 2604 70 70 55 9.5 F IP 44 10 Integral RE 3 REU 3 REE 2 2 315 M 1287 230 1~ 252 1.12 0.39 2573 55 46 59 5.5 F IP 44 6 Integral RE 1.5 REU 1.5 REE 2 2 315 L 1288 230 1~ 372 1.62 0.59 2595 70 70 54 9 F IP 44 10 Integral RE 3 REU 3 REE 2 2 315 XL 1289 230 1~ 276 1.29 0.77 1375 70 70 52 15.5 B IP 54 6 S-ET 10 RTRE 3 REU 1.5* REE 2* 6 355 S 1291 230 1~ 371 1.61 0.60 2597 70 70 54 8 F IP 44 10 Integral RE 3 REU 3 REE 2 2 355 M 1292 230 1~ 275 1.30 0.85 1375 70 70 50 15 B IP 54 6 S-ET 10 RTRE 1.5 REU 1.5* REE 2* 6 355 XL1 1294 230 1~ 431 1.90 1.10 1309 70 70 56 20.5 F IP 54 10 S-ET 10 RTRE 3 REU 3* REE 4* 6 355 XL3 1296 400 3~ 451 0.96 1.16 1399 70 70 58 18 F IP 54 STDT 16 RTRD 2 RTRDU 2 8

38

Circular duct fans


dIMENSIONS Ventilation accessories
0

Circular duct fans

155

25

D/2

102,5

180 310

10

25

C A

25

248 313

25

10 353 31

10

60 205

B D

30

FK p. 355

SG p. 357

VK p. 356

45

45

45

KD 250 L 315 L 355 M 400 M 450 M 500 M

A 353 353 455 503 560 717

B 205 205

C 248 313 315 355 355 400 400 450 450 500

D 385 305 484 435 516 480 602 559 742 699

KD 250 M

KD 355 S

RSK p. 355

315 XL 455 355 XL 503 400 XL 560 450 XL 560

LDC p. 348

FFR p. 349

CB p. 350

KD Art no. Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Capacitor Motor protection Speed control, five-step Speed control, five step high/low Speed control, stepless Wiring diagram p. 391-400 *+ S-ET 10

400 M1 1297 V/50 Hz 230 1~ W 432 A 1.90 m3/s 1.16 min-1 1307 C 70 C 70 dB(A) 54 kg 19.5 F IP 54 F 10 S-ET 10 Transformer RTRE 3 Transformer REU 3* Thyristor REE 4* 6

400 M3 1300 400 3~ 456 0.952 1.22 1397 70 70 57 17.5 F IP 54 STDT 16 RTRD 2 RTRDU 2 8

400 XL1 1301 230 1~ 855 4.24 1.62 1298 65 65 64 28.5 F IP 54 16 S-ET 10 RTRE 5 REU 5* 6

400 XL3 1302 400 3~ 792 1.53 1.65 1304 67 67 61 25.5 F IP 54 STDT 16 RTRD 2 RTRDU 2 8

450 M1 1303 230 1~ 857 4.21 1.60 1308 65 65 61 28 F IP 54 16 S-ET 10 RTRE 5 REU 5* REE 2* 6

450 M3 1304 400 3~ 778 1.53 1.64 1307 70 70 63 25.5 F IP 54 STDT 16 RTRD 2 RTRDU 2 8

450 XL1 1305 230 1~ 1392 6.16 2.35 1289 60 60 61 36.5 F IP 54 30 S-ET 10 RTRE 7 REU 7* 6

450 XL3 1307 400 3~ 1246 2.22 2.07 1325 61 30 61 35 F IP 54 STDT 16 RTRD 4 RTRDU 4 8

500 M1 1309 230 1~ 1386 6.12 2.37 1290 62 57 64 39 F IP 54 30 S-ET 10 RTRE 7 REU 7* 6

500 M3 1310 400 3~ 1243 2.20 2.18 1315 62 51 65 34.5 F IP 54 STDT 16 RTRD 4 RTRDU 4 8

39

Circular duct fans

Circular duct fans


pERFORMANCE

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 200-900 LwA Inlet LwA Outlet

Tot 63 79 84 60
68 72

Frequency bands [Hz] 125 70 71 27


66 67

dB(A) 4k 64 75 48
51 62

Tot 63 125 66 70 27 49 66 79 79 61 73 68 55 55 22 73 52

Frequency bands [Hz] 250 69 71 43 51 63 500 76 73 56 36 53 1k 73 73 56 33 47 2k 66 72 53 34 49 4k 65 65 50 48 55 8k 61 59 44 51 51

250 71 75 46
63 67

500 75 76 55
51 52

1k 71 76 56
39 44

2k 64 78 52
30 44

8k 57 73 39
47 63

60 57 27
58 55

LwA Inlet LwA Outlet LwA Surrounding With LDC 250-900 LwA Inlet LwA Outlet

Measurement point: 0,2 m/s; 255 Pa

Measurement point: 0,229 m/s; 260 Pa

dB(A)
LwA Inlet LwA Outlet LwA Surrounding

Tot 63
82 81 62 56 56 28

Frequency bands [Hz] 125


73 71 37

dB(A) 4k
71 71 49

Tot 63 125 64 69 33 61 66 79 81 66 67 70 54 58 32 53 57

Frequency bands [Hz] 250 68 70 41 61 63 500 76 76 65 60 60 1k 73 75 50 51 53 2k 68 74 46 56 62 4k 66 67 45 60 61 8k 62 60 40 55 53

250
75 71 46

500
78 75 61

1k
75 74 50

2k
71 76 48

8k
64 64 37

LwA Inlet LwA Outlet LwA Surrounding With LDC 315-900 LwA Inlet LwA Outlet

With LDC 250-900


LwA Inlet LwA Outlet

72 70

53 53

69 67

67 63

58 55

49 48

48 53

61 61

56 56

Measurement point: 0,341 m/s; 296 Pa

Measurement point: 0,23 m/s; 262 Pa

40

Circular duct fans

Circular duct fans

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 315-900 LwA Inlet LwA Outlet

Tot 63 80 81 61 71 71 58 54 32 57 53 125 69 68 36 66 65

Frequency bands [Hz] 250 71 70 44 64 63 500 75 73 60 59 57 1k 75 75 50 53 53 2k 71 76 47 59 64 4k 69 71 48 63 65 8k 67 65 40 60 58

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 315-900 LwA Inlet LwA Outlet

Tot 63 74 75 59 65 68 60 59 33 59 58 125 63 69 42 60 66

Frequency bands [Hz] 250 68 66 51 61 59 500 69 67 52 53 51 1k 68 69 55 46 47 2k 61 66 52 49 54 4k 56 56 38 50 50 8k 46 48 27 39 41

Measurement point: 0,358 m/s; 312 Pa

Measurement point: 0,481 m/s; 142 Pa

dB(A)
LwA Inlet LwA Outlet LwA Surrounding

Tot 63 80 83 61 71 73 57 58 32 57 58 125 68 68 35 65 65

Frequency bands [Hz] 250 69 68 43 63 62 500 75 76 60 62 63 1k 74 77 50 56 59 2k 72 78 48 62 68 4k 70 72 49 64 66 8k 68 67 41 61 60

dB(A)
LwA Inlet LwA Outlet LwA Surrounding

Tot 63 73 75 57 67 68 62 57 40 62 57 125 65 69 40 62 66

Frequency bands [Hz] 250 67 66 48 61 60 500 66 68 51 53 55 1k 65 70 52 47 52 2k 61 65 49 51 55 4k 56 56 38 50 50 8k 46 48 27 39 41

With LDC 355-900


LwA Inlet LwA Outlet

With LDC 355-900


LwA Inlet LwA Outlet

Measurement point: 0,367 m/s; 305 Pa

Measurement point: 0,52 m/s; 145 Pa

41

Circular duct fans

Circular duct fans

dB(A)
LwA Inlet LwA Outlet LwA Surrounding

Tot 63 78 78 63 73 73 55 50 26 55 50 125 75 75 48 72 72

Frequency bands [Hz] 250 72 70 60 66 64 500 69 70 59 56 57 1k 66 68 53 48 50 2k 62 65 47 52 55 4k 61 64 47 55 58 8k 56 59 42 49 52

dB(A)
LwA Inlet LwA Outlet LwA Surrounding

Tot 63 79 79 65 75 74 55 50 29 55 50 125 77 76 52 74 73

Frequency bands [Hz] 250 73 71 60 67 65 500 71 72 60 58 59 1k 67 70 57 49 52 2k 63 66 51 53 56 4k 63 66 51 57 60 8k 57 61 42 50 54

With LDC 355-900


LwA Inlet LwA Outlet

With LDC 355-900


LwA Inlet LwA Outlet

Measurement point: 0,577 m/s; 202 Pa

Measurement point: 0,639 m/s; 226 Pa

dB(A)
LwA Inlet LwA Outlet

Tot 63 77 77 60 72 72 52 48 27 51 47 125 73 73 45 70 70

Frequency bands [Hz] 250 71 70 56 66 65 500 69 71 57 59 61 1k 64 68 51 51 55 2k 61 65 46 54 58 4k 60 64 46 55 59 8k 54 59 39 48 53

dB(A)
LwA Inlet LwA Outlet LwA Surrounding

Tot 63 78 79 64 74 73 54 51 24 53 50 125 76 74 47 73 71

Frequency bands [Hz] 250 72 71 60 67 66 500 70 72 59 60 62 1k 67 71 56 54 58 2k 63 67 49 56 60 4k 62 65 49 57 60 8k 57 61 44 51 55

LwA Surrounding With LDC 400-900


LwA Inlet LwA Outlet

With LDC 400-900


LwA Inlet LwA Outlet

Measurement point: 0,65 m/s; 193 Pa

Measurement point: 0,615 m/s; 237 Pa

42

Circular duct fans

Circular duct fans

dB(A)
LwA Inlet LwA Outlet

Tot 63 84 85 71 78 79 55 55 21 54 54 125 79 79 62 76 76

Frequency bands [Hz] 250 78 80 64 73 75 500 78 79 68 68 69 1k 71 75 59 58 62 2k 68 71 54 61 64 4k 66 69 51 61 64 8k 58 61 41 52 55

dB(A)
LwA Inlet LwA Outlet

Tot 63 83 85 68 77 79 53 55 18 52 54 125 78 78 44 75 75

Frequency bands [Hz] 250 77 79 61 72 74 500 77 79 65 67 69 1k 71 75 61 58 62 2k 68 72 53 61 65 4k 66 70 51 61 65 8k 58 60 42 52 54

LwA Surrounding With LDC 400-900


LwA Inlet LwA Outlet

LwA Surrounding With LDC 400-900


LwA Inlet LwA Outlet

Measurement point: 0,798 m/s; 290 Pa

Measurement point: 0,818 m/s; 283 Pa

dB(A)
LwA Inlet LwA Outlet LwA Surrounding

Tot 63 83 83 68 57 51 25 125 77 75 47

Frequency bands [Hz] 250 79 76 67 500 77 79 61 1k 69 75 56 2k 68 69 55 4k 65 66 50 8k 58 61 43

dB(A)
LwA Inlet LwA Outlet LwA Surrounding

Tot 63 83 84 70 53 52 15 125 78 77 45

Frequency bands [Hz] 250 78 77 68 500 77 80 66 1k 68 75 59 2k 68 71 53 4k 66 69 50 8k 58 61 42

Measurement point: 0,854 m/s; 270 Pa

Measurement point: 0,865 m/s; 273 Pa

43

Circular duct fans

Circular duct fans

KD 450 XL3

dB(A)
LwA Inlet LwA Outlet LwA Surrounding

Tot 63 82 82 68 69 69 35 125 76 75 54

Frequency bands [Hz] 250 75 73 60 500 75 76 65 1k 73 76 61 2k 73 72 59 4k 66 66 46 8k 59 61 40

dB(A)
LwA Inlet LwA Outlet LwA Surrounding

Tot 63 84 86 68 64 61 34 125 76 76 48

Frequency bands [Hz] 250 78 78 60 500 78 82 61 1k 77 81 65 2k 73 75 60 4k 66 69 47 8k 60 63 40

Measurement point: 1,3 m/s; 342 Pa

Measurement point: 0,957 m/s; 365 Pa

KD 500 M3

dB(A)
LwA Inlet LwA Outlet LwA Surrounding

Tot 63 82 83 71 69 70 41 125 75 75 58

Frequency bands [Hz] 250 75 72 63 500 75 76 68 1k 73 78 64 2k 72 73 60 4k 65 67 48 8k 59 60 48

dB(A)
LwA Inlet LwA Outlet LwA Surrounding

Tot 63 84 86 71 66 62 26 125 77 78 47

Frequency bands [Hz] 250 78 77 63 500 78 82 67 1k 75 81 67 2k 73 75 63 4k 66 68 55 8k 60 63 51

Measurement point: 1,28 m/s; 355 Pa

Measurement point: 0,853 m/s; 393 Pa

44

Circular duct fans Reference

Circular duct fans

Project: EON Kharadi Type of Building: SEZ IT Park City/Country: Pune, India Products/ Solution: MUB, Inline (K, KD), Axial, Jet Nozzles, Grilles

45

Circular duct fans

Circular duct fans KVK


Speed-controllable Integral thermal contacts Low sound level Compact construction S-ET p. 341 Electrical accessories

The KVK 125-160 models have a single-inlet centrifugal fan, size 200500 have double-inlet centrifugal fans. All sizes have forward-curved blades and a maintenance-free external rotor motor. To protect the motor from overheating the KVK 125-160 has integral thermal contacts with electrical reset, and size 200-500 has leads for connection to a motor protection device. The fans can be installed in any position, and are easy to connect to spiral ducts using FK mounting clamps. The KVK models are manufactured from galvanised sheet steel and are thermally and acoustically insulated with a 50 mm layer of rockwool with a surface liner which prevents the migration of fibres into the airstream.

RTRE p. 320

RE p. 320

Quick selection REU p. 320


6663, 6683, 6687, 3115, 7657

1 2 3 4 5

KVK 125 KVK 160M KVK 160L KVK 200 KVK 250

1 2 3 4 2 3

KVK 315M KVK 315L, 355 KVK 400 KVK 500

733, 2228, 2218, 2229, 5010

REE p. 321

1
1 2 3 4 5

Technical data
KVK Art no. Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Capacitor Motor protection Speed control, five-step Speed control, five step high/low Speed control, stepless Wiring diagram p. 391-400 * + S-ET 10 125 2430 V/50 Hz 230 1~ W 92.7 A 0.409 m3/s 0.106 min-1 1978 C 68 C 68 dB(A) 38 kg 11 B IP 44 F 2 Integral Transformer RE 1.5 Transformer REU 1.5 Thyristor REE 1 2 160 M 2433 230 1~ 111 0.48 0.123 2062 70 70 39 11 B IP 44 2 Integral RE 1.5 REU 1.5 REE 1 2 160 L 2434 230 1~ 134 0.59 0.138 2519 70 70 39 11.8 B IP 44 4 Integral RE 1.5 REU 1.5 REE 1 2 200 1337 230 1~ 172 0.75 0.197 1807 57 57 40 12.9 B IP 44 4 S-ET 10 RTRE 1.5 REU 1.5* REE 1* 5 250 1347 230 1~ 308 1.34 0.311 1833 50 50 43.2 17 F IP 44 8 S-ET 10 RTRE 1.5 REU 1.5* REE 2* 5

46

Circular duct fans


dIMENSIONS
A

Circular duct fans

Ventilation accessories

FK p. 355

D E
KVK 125 160 A 230 230 B 266 266 C 151 134 D 114 132 E 367 367 F 415 415 G 464 464 H 125 160 I 40 40

SG p. 357

VK p. 356

IGK p. 357
I A H B

D E

RSK p. 355

LDC p. 348
I

KVK 200 250


G

A 340 380 540 540 540 750

B 345 385 545 545 545 680

C 191 198 328 328 328 400

D 193 228 256 256 256 355

E 395 460 520 520 520 710

F 395 400 570 570 570 718

G 440 490 655 655 680 850

H 200 250 315 355 400 500

I 20 40 40 40 50 80

315 355 400 500

FFR p. 349

CB p. 350
KVK Art no. Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Capacitor Motor protection Speed control, five-step Speed control, five step high/low Speed control, stepless Wiring diagram p. 391-400 * + S-ET 10 315 M 1357 V/50 Hz 230 1~ W 335 A 1.49 m3/s 0.542 min-1 1324 C 70 C 70 dB(A) 35 kg 30 B IP 54 F 10 S-ET 10 Transformer RTRE 3 Transformer REU 3* Thyristor REE 2* 5 315 L 1365 230 1~ 643 2.82 0.789 1201 53 53 36 32.2 B IP 54 20 S-ET 10 RTRE 3 REU 3* REE 4* 5 355 1370 230 1~ 614 2.69 0.72 1220 40 40 36 32.1 B IP 54 20 S-ET 10 RTRE 3 REU 3* REE 4* 5 400 1375 230 1~ 603 2.64 0.73 1186 40 40 39 32 B IP 54 20 S-ET 10 RTRE 3 REU 3* REE 4* 5 500 4506 230 1~ 1452 6.27 1.49 1235 68 68 56 66.9 F IP 54 25 S-ET 10 RTRE 7 REU 7* 3

47

Circular duct fans

Circular duct fans


pERFORMANCE

KVK 125

KVK 160 M

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 125-900 LwA Inlet LwA Outlet

Tot 63 57 70 45 51 58 37 50 17 33 46 125 55 61 33 51 57

Frequency bands [Hz] 250 50 58 40 38 46 500 44 60 41 11 27 1k 42 66 36 0 21 2k 41 62 36 0 12 4k 36 55 25 6 25 8k 30 48 16 13 31

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 160-900 LwA Inlet LwA Outlet

Tot 63 62 72 46 57 61 39 53 10 37 51 125 61 64 43 57 60

Frequency bands [Hz] 250 53 64 38 43 54 500 48 64 37 20 36 1k 44 68 38 2 26 2k 41 65 27 0 22 4k 38 57 24 18 37 8k 35 51 21 20 36

Measurement point: 0,0625 m/s; 229 Pa

Measurement point: 0,0678 m/s; 258 Pa

KVK 160 L

dB(A)
LwA Inlet LwA Outlet LwA Surrounding

Tot 63 63 75 46 58 64 48 56 25 46 54 125 62 66 43 58 62

Frequency bands [Hz] 250 53 66 39 43 56 500 49 67 38 21 39 1k 46 69 34 4 27 2k 44 69 30 1 26 4k 42 62 25 22 42 8k 38 57 18 23 42

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 200-900 LwA Inlet LwA Outlet

Tot 63 66 73 47 60 63 47 59 19 45 57 125 63 63 38 59 59

Frequency bands [Hz] 250 59 66 43 51 58 500 58 67 42 34 43 1k 55 66 35 23 34 2k 48 66 31 14 32 4k 41 61 26 28 48 8k 35 54 19 25 44

With LDC 160-900


LwA Inlet LwA Outlet

Measurement point: 0,0722 m/s; 286 Pa

Measurement point: 0,0983 m/s; 255 Pa

48

Circular duct fans

Circular duct fans

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 250-900 LwA Inlet LwA Outlet

Tot 63 67 76 50 46 61 27 125 66 68 46

Frequency bands [Hz] 250 60 68 45 500 56 69 43 1k 47 68 38 2k 49 69 37 4k 44 65 31 8k 36 58 21

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 315-900 LwA Inlet LwA Outlet

Tot 63 60 71 42 57 63 55 59 36 54 58 125 56 63 35 53 60

Frequency bands [Hz] 250 51 57 35 44 50 500 42 63 33 26 47 1k 42 66 30 20 44 2k 41 62 27 29 50 4k 39 59 22 33 53 8k 36 57 17 29 50

62 67

43 58

62 64

52 60

36 49

21 42

26 46

34 55

28 50

Measurement point: 0,166 m/s; 357 Pa

Measurement point: 0,284 m/s; 182 Pa

dB(A)
LwA Inlet LwA Outlet LwA Surrounding

Tot 63 63 73 43 61 64 61 59 31 60 58 125 55 61 35 52 58

Frequency bands [Hz] 250 51 61 36 44 54 500 45 64 37 29 48 1k 46 68 35 24 46 2k 43 66 33 31 54 4k 40 63 29 34 57 8k 38 59 26 31 52

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 355-900 LwA Inlet LwA Outlet

Tot 63 62 72 43 61 64 60 58 31 60 58 125 55 60 35 52 57

Frequency bands [Hz] 250 51 60 36 45 54 500 44 64 37 31 51 1k 46 68 35 28 50 2k 43 66 33 33 56 4k 40 63 29 34 57 8k 38 59 26 31 52

With LDC 315-900


LwA Inlet LwA Outlet

Measurement point: 0,463 m/s; 275 Pa

Measurement point: 0,531 m/s; 238 Pa

49

Circular duct fans

Circular duct fans

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 400-900 LwA Inlet LwA Outlet

Tot 63 63 73 46 60 62 33 125 58 61 37

Frequency bands [Hz] 250 54 63 38 500 51 64 41 1k 51 68 37 2k 47 66 36 4k 47 64 37 8k 46 60 27

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 71 78 63 53 64 31 125 68 68 59

Frequency bands [Hz] 250 66 68 59 500 54 69 48 1k 52 69 44 2k 53 69 38 4k 58 72 41 8k 57 66 41

Measurement point: 0,848 m/s; 396 Pa 61 67 59 61 55 58 49 58 41 54 38 55 40 59 42 59 40 54

Measurement point: 0,393 m/s; 296 Pa

50

Circular duct fans Reference

Circular duct fans

Project: Ukraine hotel complex Type of Building: The hotel Ukraine is not only one of the best hotels but also an integral part of the architectural and historical view in Moscow. City/Country: Moscow, Russia Products/Solution: 98 modular air handling units, type DV, including 15 DV Coolers 81 duct and roof fans; K, KD, KT, RSI, DVSI 4 Compact heat recovery units; Topvex 4 Compact supply units; TLP 2 Residential heat recovery units; VR

51

Circular duct fans

Circular duct fans KVK DUO


Speed-controllable Integral thermal contacts Low sound level Twin fan S-ET p. 341 Electrical accessories

KVK DUO models are designed for applications where a standby fan is required. The fans have double inlet centrifugal fans with forward-curved impellers and maintenance-free external rotor motors. To protect the motors from overheating the fans have integral thermal contacts with leads for connection to a motor protection device. The fans are easy to connect to spiral ducts using FK mounting clamps. The KVK DUO models are manufactured from galvanised sheet steel and are thermally and acoustically insulated with a 50 mm layer of mineral wool. Internal surfaces are protected with perforated galvanised sheet steel.

AWE-SK p. 342

RTRE p. 320

Quick selection REU p. 320


1 2 3 2 3

719, 3647, 3115, 1758

1 2 3 4

KVK DUO 125 KVK DUO 160 KVK DUO 200 KVK DUO 250

KVK DUO 315M KVK DUO 315L, 355 KVK DUO 400

733, 2228, 2218, 2229

REE p. 321

tECHNICAL DATA
KVK DUO Art no. Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Capacitor Motor protection Speed control, five-step Speed control, five step high/low Speed control, stepless Wiring diagram p. 391-400 * + AWE-SK, ** + S-ET 10 125 5341 V/50 Hz 230 1~ W 41.4 A 0.171 m3/s 0.0528 min-1 1724 C 69 C 69 dB(A) 29 kg 18.3 B IP 44 F 1.5 AWE-SK Transformer RTRE 1.5 Transformer REU 1.5* Thyristor REE 1* 5 160 5127 230 1~ 69.1 0.301 0.105 1943 35 35 37 19.5 B IP 22 2 AWE-SK RTRE 1.5 REU 1.5* REE 1* 5 200 5030 230 1~ 172 0.75 0.197 1807 56 56 40 27.9 B IP 44 4 S-ET 10 RTRE 1.5 REU 1.5** REE 1** 5 250 5031 230 1~ 304 1.31 0.316 1962 50 55 42 45 F IP 44 8 S-ET 10 RTRE 1.5 REU 1.5** REE 2** 5 315M 5032 230 1~ 335 1.49 0.542 1324 69 69 35 66 B IP 54 10 S-ET 10 RTRE 3 REU 3** REE 2* 5 315L 5773 230 1~ 643 2.82 0.789 1201 53 53 36 74 B IP 54 20 S-ET 10 RTRE 3 REU 3** REE 4** 5

52

Circular duct fans


dIMENSIONS
B

Circular duct fans

Ventilation accessories

D E

H A

FK p. 355

SG p. 357

VK p. 356

KVK DUO 125 160 200 250 315M 315L 355 400

A 333 333 386 460 505 505 505 505

B 275 275 325 400 450 450 450 450

C 165 165 190 207 250 250 250 250

D 255 255 300 360 473 473 473 473

E 510 510 600 720 946 946 946 946

F 350 350 400 500 565 565 565 565

G 425 425 475 615 680 680 680 680

H 125 160 200 250 315 315 355 400

RSK p. 355

LDC p. 348

FGR p. 348

CB p. 350

KVK DUO Art no. Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Capacitor Motor protection Speed control, five-step Speed control, five step high/low Speed control, stepless Wiring diagram p. 391-400 * + S-ET 10

355 5774 V/50 Hz 230 1~ W 614 A 2.69 m3/s 0.72 min-1 1220 C 40 C 40 dB(A) 36 kg 67 B IP 54 F 20 S-ET 10 Transformer RTRE 3 Transformer REU 3* Thyristor REE 4* 5

400 5775 230 1~ 603 2.64 0.73 1186 40 40 39 72 B IP 54 20 S-ET 10 RTRE 3 REU 3* REE 4* 5

53

Circular duct fans

Circular duct fans


pERFORMANCE

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 125-900 LwA Inlet LwA Outlet

Tot 63 52 61 36 47 50 49 46 30 45 42 125 47 53 32 43 49

Frequency bands [Hz] 250 41 53 24 29 41 500 40 54 25 7 21 1k 38 53 26 0 8 2k 33 53 17 0 3 4k 26 46 18 0 16 8k 25 38 19 8 21

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 160-900 LwA Inlet LwA Outlet

Tot 63 59 68 44 53 56 39 49 6 37 47 125 56 57 32 52 53

Frequency bands [Hz] 250 55 62 42 45 52 500 52 64 40 24 36 1k 45 60 30 3 18 2k 39 59 22 0 16 4k 33 54 20 13 34 8k 26 48 12 11 33

Measurement point: 0,0281 m/s; 114 Pa

Measurement point: 0,06 m/s; 148 Pa

dB(A)
LwA Inlet LwA Outlet LwA Surrounding

Tot 63 66 73 47 60 63 47 59 19 45 57 125 63 63 38 59 59

Frequency bands [Hz] 250 59 66 43 51 58 500 58 67 42 34 43 1k 55 66 35 23 34 2k 48 66 31 14 32 4k 41 61 26 28 48 8k 35 54 19 25 44

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 250-900 LwA Inlet LwA Outlet

Tot 63 69 77 49 64 67 50 62 22 47 59 125 67 68 42 63 64

Frequency bands [Hz] 250 62 67 45 54 59 500 59 69 45 39 49 1k 53 69 37 27 43 2k 50 71 32 27 48 4k 46 67 27 36 57 8k 40 62 23 32 54

With LDC 200-900


LwA Inlet LwA Outlet

Measurement point: 0,0983 m/s; 255 Pa

Measurement point: 0,152 m/s; 328 Pa

54

Circular duct fans

Circular duct fans

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 315-900 LwA Inlet LwA Outlet

Tot 63 60 71 42 55 59 36 125 56 63 35

Frequency bands [Hz] 250 51 57 35 500 42 63 33 1k 42 66 30 2k 41 62 27 4k 39 59 22 8k 36 57 17

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 315-900 LwA Inlet LwA Outlet

Tot 63 63 73 43 61 64 61 59 31 60 58 125 55 61 35 52 58

Frequency bands [Hz] 250 51 61 36 44 54 500 45 64 37 29 48 1k 46 68 35 24 46 2k 43 66 33 31 54 4k 40 63 29 34 57 8k 38 59 26 31 52

57 63

54 58

53 60

44 50

26 47

20 44

29 50

33 53

29 50

Measurement point: 0,284 m/s; 182 Pa

Measurement point: 0,463 m/s; 275 Pa

dB(A)
LwA Inlet LwA Outlet LwA Surrounding

Tot 63 62 72 43 61 64 60 58 31 60 58 125 55 60 35 52 57

Frequency bands [Hz] 250 51 60 36 45 54 500 44 64 37 31 51 1k 46 68 35 28 50 2k 43 66 33 33 56 4k 40 63 29 34 57 8k 38 59 26 31 52

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 400-900 LwA Inlet LwA Outlet

Tot 63 63 73 46 61 67 60 62 33 59 61 125 58 61 37 55 58

Frequency bands [Hz] 250 54 63 38 49 58 500 51 64 41 41 54 1k 51 68 37 38 55 2k 47 66 36 40 59 4k 47 64 37 42 59 8k 46 60 27 40 54

With LDC 355-900


LwA Inlet LwA Outlet

Measurement point: 0,531 m/s; 238 Pa

Measurement point: 0,393 m/s; 296 Pa

55

Circular duct fans

Circular duct fans KVKE EC


EC-motors, high level of efficiency 100% speed controllable Low sound level Integrated motor protection Potentiometer included for ease of commissioning EC technology is intelligent technology; using integral electronic control which eliminates the slip losses in the motor and ensures that the motor always runs at optimal load and guarantees that the proportion of energy utilised effectively is many times higher and that the energy usage is considerably lower compared to AC motors. Another special feature of EC fans is their energy-saving potential not only at full load, but especially at part-load. When operating at partload, the energy used is much lower than with an asynchronous motor of equivalent output. Reduced energy usage guarantees a drop in operating costs. The KVKE EC models have a single inlet centrifugal fan with backward-curved blades and a maintenance-free external rotor motor(EC). These fans develop relatively high static pressure and have a very high efficiency. The fans are delivered with a pre-wired potentiometer (010V) which allows you to easily set the desired working point. The KVKE motor and impeller are mounted on the access cover for ease of maintenance. The service cover can be easily removed by withdrawing the hinge pin. Motor protection is integrated in the electronics of the motor. The fans can be installed in any position and are easy to connect to spiral ducts using FK mounting clamps. The KVKE models are manufactured from galvanised sheet steel and are thermally and acoustically insulated with a 50 mm layer of rockwool with a surface liner which prevents the migration of fibres into the airstream. By using an EC fan you eliminate the need for an electrical protection unit and speed controller. This should be considered when doing a cost comparison with a standard AC fan model. It also simplifies the process when commissioning. Electrical accessories

MTP 10 p. 341

EC-Vent p. 329-330

MTV 1/010 p. 341

tECHNICAL DATA
KVKE Art no. Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Motor protection Speed control Wiring diagram p. 391-400 125 EC 2570 V/50 Hz 230 1~ W 68.7 A 0.536 m3/s 0.104 min-1 3339 C 60 C 60 dB(A) 41 kg 13.2 B IP 44 Integral Electronic MTP 42 160 EC 2571 230 1~ 67.7 0.531 0.151 2592 60 60 39 17 B IP 44 Integral MTP 42 200 EC 2575 230 1~ 156 1.10 0.24 3033 60 60 46 18.8 B IP 44 Integral MTP 42 250 EC 2577 230 1~ 265 1.64 0.321 2821 55 55 49 28.1 B IP 44 Integral MTP 42 315 EC 2578 230 1~ 308 1.89 0.492 2215 45 45 47 38.8 B IP 44 Integral MTP 42

56

Circular duct fans


dIMENSIONS Ventilation accessories

Circular duct fans

50 * C B *

FK p. 355

SG p. 357
F 27 A 47 D

VK p. 356
A KVKE 125 EC KVKE 160 EC KVKE 200 EC KVKE 250 EC KVKE 315 EC 125 160 200 250 315 B 433 482 482 578 680 C 479 528 534 700 802 D 125 145,5 150,5 176 208.5 E 128,5 132,5 149 174 207.5 F 442 505 505 596 705.5 G 246 266 303 359 430 H 470 530 530 620 730

IGK p. 357

* Handle 315M/L

RSK p. 355

LDC p. 348

FFR p. 349

CB p. 350 Quick selection

1 2 3 4 5

KVKE 125 EC KVKE 160 EC KVKE 200 EC KVKE 250 EC KVKE 315 EC

8166, 7721, 7755, 7788, 8159

57

Circular duct fans

Circular duct fans


pEFORMANCE

Do not select in this area

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 125-900 LwA Inlet LwA Outlet

Tot 63 60 76 48 54 61 46 54 18 42 50 125 57 63 40 53 59

Frequency bands [Hz] 250 56 69 41 44 57 500 50 71 43 17 38 1k 45 69 40 0 24 2k 40 66 38 0 16 4k 37 60 35 7 30 8k 35 46 32 18 29

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 160-900 LwA Inlet LwA Outlet

Tot 63 57 72 46 51 57 42 50 19 40 48 125 54 59 39 50 55

Frequency bands [Hz] 250 49 62 36 39 52 500 47 68 39 19 40 1k 44 65 34 2 23 2k 47 62 39 4 19 4k 40 55 36 20 35 8k 33 42 28 18 27

Measurement point: 0,0608 m/s; 384 Pa

Measurement point: 0,0753 m/s; 358 Pa

dB(A)
LwA Inlet LwA Outlet LwA Surrounding

Tot 63 64 80 53 58 66 52 57 27 50 55 125 59 64 43 55 60

Frequency bands [Hz] 250 60 72 49 52 64 500 56 76 49 32 52 1k 53 74 40 21 42 2k 50 71 39 16 37 4k 47 64 39 34 51 8k 45 53 35 35 43

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 250-900 LwA Inlet LwA Outlet

Tot 63 67 83 56 61 70 53 64 32 50 61 125 64 70 49 60 66

Frequency bands [Hz] 250 60 72 50 52 64 500 59 80 53 39 60 1k 54 76 42 28 50 2k 48 75 39 25 52 4k 46 66 35 36 56 8k 40 56 26 32 48

With LDC 200-900


LwA Inlet LwA Outlet

Measurement point: 0,144 m/s; 467 Pa

Measurement point: 0,188 m/s; 663 Pa

58

Circular duct fans

Circular duct fans

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 315-900 LwA Inlet LwA Outlet

Tot 63 66 85 54 53 62 36 125 64 71 48

Frequency bands [Hz] 250 61 83 52 500 51 75 44 1k 49 72 40 2k 45 67 36 4k 41 62 32 8k 36 54 26

62 77

52 61

61 68

54 76

35 59

27 50

33 55

35 56

29 47

Measurement point: 0,289 m/s; 530 Pa

59

Circular duct fans

Circular duct fans KVKE


Speed controllable Integral thermal contacts Low sound level Servicing cover Electrical accessories

RE p. 320

The KVKE models have a single inlet centrifugal fan with backwardcurved blades and a maintenance-free external rotor motor. These fans develop relatively high static pressure and have a high efficiency. The KVKE motor and impeller are mounted on the access cover for ease of maintenance. The service cover can be easily removed by withdrawing the hinge pin. To protect the motor from overheating, the fans have integral thermal contacts with automatic reset. The fans can be installed in any position and are easy to connect to spiral ducts using FK mounting clamps. The KVKE models are manufactured from galvanised sheet steel and are thermally and acoustically insulated with a 50 mm layer of rockwool with a surface liner which prevents the migration of fibres into the airstream.

REU p. 320

REE p. 321

tECHNICAL DATA
KVKE Art no. Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Capacitor Motor protection Speed control, five-step Speed control, five step high/low Speed control, stepless Wiring diagram p. 391-400 125 1406 V/50 Hz 230 1~ W 55.1 A 0.244 m3/s 0.0854 min-1 2548 C 70 C 70 dB(A) 34 kg 14 B IP 44 F 2 Integral Transformer RE 1.5 Transformer REU 1,5 Thyristor REE 1 4 160 1409 230 1~ 97.6 0.422 0.148 2687 70 70 36 18 B IP 44 3 Integral RE 1.5 REU 1.5 REE 1 4 200 1412 230 1~ 152 0.67 0.211 2661 70 70 47 19.5 F IP 44 4 Integral RE 1.5 REU 1.5 REE 1 4 250 M 1416 230 1~ 186 0.841 0.27 2655 58 58 38 26.5 B IP 44 5 Integral RE 1.5 REU 1.5 REE 1 4 250 L 1419 230 1~ 258 1.10 0.317 2578 60 56 45 28.5 F IP 44 7 Integral RE 1.5 REU 1.5 REE 2 4 315 M 1421 230 1~ 285 1.23 0.44 2505 60 60 41 40.5 F IP 44 7 Integral RE 1.5 REU 1.5 REE 2 4 315 L 1423 230 1~ 496 2.15 0.61 2364 59 49 50 42 F IP 44 12 Integral RE 3 REU 3 REE 4 4

60

Circular duct fans


dIMENSIONS Ventilation accessories

Circular duct fans

Free area
H 50

FK p. 355

Handle
E

size 315M/L
D

C B

SG p. 357

F 60

VK p. 356

KVKE 125 160 200 250 315

A 125 160 200 250 315

B 433 482 482 578 680

C 479 528 534 700 802

D 125 145.5 150.5 176 208.5

E 128.5 132.5 149 174 207.5

F 442 505 505 596

G 246 266 303 359

H 470 530 530 620 730

IGK p. 357

705.5* 430

* + handle

RSK p. 355

LDC p. 348

FFR p. 349 Quick selection CB p. 350


3680, 662, 3877

1 2 3

KVKE 125 KVKE 160 KVKE 200

1 2 3 4

KVKE 250M KVKE 250L KVKE 315M KVKE 315L

3889, 1783, 1777, 1652

61

Circular duct fans

Circular duct fans


pERFORMANCE

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 125-900 LwA Inlet LwA Outlet

Tot 63 56 70 41 35 50 6 125 50 59 35

Frequency bands [Hz] 250 55 67 38 500 42 63 31 1k 40 63 32 2k 32 61 29 4k 21 56 20 8k 17 36 15

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 160-900 LwA Inlet LwA Outlet

Tot 63 57 71 43 54 57 55 53 32 53 51 125 48 58 30 44 54

Frequency bands [Hz] 250 49 62 33 39 52 500 48 68 37 20 40 1k 43 65 35 1 23 2k 38 61 33 0 18 4k 35 54 34 15 34 8k 38 40 35 23 25

48 58

31 46

46 55

43 55

9 30

0 18

0 11

0 26

0 19

Measurement point: 0,0489 m/s; 248 Pa

Measurement point: 0,0828 m/s; 333 Pa

dB(A)
LwA Inlet LwA Outlet LwA Surrounding

Tot 63 67 79 54 60 68 44 56 12 42 54 125 58 61 40 54 57

Frequency bands [Hz] 250 66 75 54 58 67 500 54 73 43 30 49 1k 52 71 38 20 39 2k 45 69 35 11 35 4k 36 59 31 23 46 8k 33 49 20 23 39

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 250-900 LwA Inlet LwA Outlet

Tot 63 60 73 45 52 59 44 56 17 41 53 125 54 56 37 50 52

Frequency bands [Hz] 250 54 62 37 46 54 500 53 70 42 33 50 1k 51 67 35 25 41 2k 49 65 31 26 42 4k 45 58 30 35 48 8k 37 48 23 29 40

With LDC 200-900


LwA Inlet LwA Outlet

Measurement point: 0,126 m/s; 371 Pa

Measurement point: 0,148 m/s; 415 Pa

62

Circular duct fans

Circular duct fans

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 250-900 LwA Inlet LwA Outlet

Tot 63 65 78 52 51 60 28 125 60 62 44

Frequency bands [Hz] 250 61 69 49 500 57 75 46 1k 52 71 36 2k 45 70 28 4k 45 62 31 8k 41 54 23

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 315-900 LwA Inlet LwA Outlet

Tot 63 61 76 47 56 65 46 60 21 45 59 125 57 59 38 54 56

Frequency bands [Hz] 250 55 65 43 48 58 500 52 73 43 36 57 1k 52 68 36 30 46 2k 46 66 29 34 54 4k 47 60 28 41 54 8k 45 55 26 38 48

58 65

48 57

56 58

53 61

37 55

26 45

22 47

35 52

33 46

Measurement point: 0,198 m/s; 475 Pa

Measurement point: 0,22 m/s; 517 Pa

dB(A)
LwA Inlet LwA Outlet LwA Surrounding

Tot 63 70 85 57 65 77 58 62 37 57 61 125 66 71 48 63 68

Frequency bands [Hz] 250 66 83 56 59 76 500 54 76 46 38 60 1k 55 74 40 33 52 2k 45 66 36 33 54 4k 43 60 34 37 54 8k 39 53 29 32 46

With LDC 315-900


LwA Inlet LwA Outlet

Measurement point: 0,318 m/s; 576 Pa

63

Rectangular duct fans

Rectangular & square duct fans

FFK Filter cassette

DS

RSI

DS SRK Damper RS DS Flexible connection DS

DS PGK Cooling coil

DS

VBR Heating coil LDR Silencer

SRKG Damper

WSD Weather roof RB Heating coil

WSG

UGS Flexible connections MUB UGS

SRKG

FGV Flexible connections

FGV

General
Systemair rectangular and square duct fans have been developed for use in compact exhaust and supply air systems. Covering a wide performance spectrum and availability of a comprehensive range of accessories, including heating and cooling coils, filters, silencers and more, offers solutions for complete systems for almost all applications. Our experience over the past 35 years and continuous research and development of new products and technology have made the Systemair duct fan a market leader. Our motto the straight way is revealed in the straight routing of airflow in a ducted system. For instance, the flexibility offered by removable panels allows the MUB Range to be adapted to all installation positions and airflow directions, which can still be decided during installation. The MUB Range is suited for outdoor applications (complete with Systemair weather protection accessories).

Systemair range
Systemair rectangular duct fans are available in 3 different versions. Where high pressure losses occur in a system we offer the KE/KT range. The RS and RSI Range is ideal for installing where the ease of maintenance or comfort is a requirement. The RSI Range is perfectly suited where low noise levels are a pre-requisite. The casings are manufactured from galvanized steel. The RSI Models have double skin with mineral wool insulation (40-60 kg/m). Systemair Multiboxes, MUB, are offered in four box sizes with varying capacities available within one size. The casing consists of a self supporting aluminium profiled frame, with either aluminium or PA6 plastic corner pieces. The double skin panels have 20 mm acoustic and thermal insulation, consisting of mineral wool with a density of 25 kg/m3. The MUB/T Therma Multibox has the motor out of the airstream which enables temperatures of up to 100C to be

exhausted. The bottom panel serves as a drain pan and is complete with a drain plug. The motor and impeller can easily be removed from the unit for cleaning and servicing.

Motors
All Systemair rectangular duct fans have external rotor motors which are suitable to control by means of voltage control. All motors have thermal motor protection embedded in the windings. The MUB Range of square duct fans is equipped with powerful external rotor motors up to size 499 and from size 500 with IEC standard motors. All MUB/T versions are equipped with IEC standard motors separated from the airstream. By combining a Systemair motor protection device optimum operational reliability is guaranteed.

64 64

Rectangular & square duct fans

KE, KE(I) . . . . . . . . . . . . . . . . 66 Rectangular duct fans: up to 0.81 m3/s, forward curved impeller, 1 phase. (I) insulated version.

MUB EC. . . . . . . . . . . . . . . . . 94 Multibox fan with EC-motor: up to 3.62 m3/s, 1 and 3 phase.

Rectangular duct fans

KT, KT(I) . . . . . . . . . . . . . . . . . 70 Rectangular duct fans: up to 2.47 m3/s, forward curved impeller, 3 phase. (I) insulated version.

MUB. . . . . . . . . . . . . . . . . . 102 Multibox fans: up to 4.80 m3/s, backward curved impeller, 1 and 3 phase.

IE2
2009/640/EG

RS . . . . . . . . . . . . . . . . . . . . . 78 Rectangular duct fans: up to 3.36 m3/s, backward-curved impeller, 1 and 3 phase.

KDRE/KDRD . . . . . . . . . . . . 114 Mixed flow square duct fans: up to 4.12 m3/s, mixed flow impeller, 1 and three phase.

IE2
2009/640/EG

RSI. . . . . . . . . . . . . . . . . . . . . 84 Insulated rectangular duct fans: up to 3.35 m3/s, backward-curved impeller, 1 and 3 phase.

MUB/T . . . . . . . . . . . . . . . . . 118 Thermo Multibox: up to 4.4 m3/s, backward curved impeller, 1 phase and 3 phase.
100C

KVD. . . . . . . . . . . . . . . . . . . . 90 Box fans: up to 2.0 m3/s, 1 and 3 phase, forward curved impeller, direct driven.

65 65

Rectangular duct fans KE, KE(I)


Swing-out Speed-controllable Integral thermal contacts Can be installed in any position Maintenance-free and reliable Electrical accessories

Rectangular duct fans

S-ET p. 341

Quick selection

The KE models have impellers with forward-curved blades and external rotor motors. The motor and impeller are mounted on the access cover to facilitate easy maintenance. The casing is manufactured from galvanised sheet steel. To protect the motor from overheating the fans have integral thermal contacts with external leads for connection to a motor protection device. The fans can be installed in any position and are simple to couple using DS flexible connections. The KE fans have a prewired, integral terminal box. KE(I) versions have double skin side panels, manufactured from galvanised steel with 25 mm mineral wool insulation.

RTRE p. 320

RE p. 320

1 2 3 4

KE 40-20-4 KE 50-25-4 KE 50-30-4 KE 50-30-6

3404, 501, 504, 1795

1 2 3

KE 60-30-4 KE 60-30-6 KE 60-35-6

8963, 1797, 1659

REU p. 320

REE p. 321
2 3 1

Technical data
KE 40-20-4 Art no. KE Art no. KE(I) Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Capacitor Motor protection Speed control, five-step Speed control, five step high/low Speed control, stepless Wiring diagram p. 391-400 * + S-ET 10 1463 68560 V/50 Hz 230 1~ W 248 A 1.08 m3/s 0.293 min-1 1059 C 45 C 45 dB(A) 55/49 kg 13.8/15 F IP 44 F 6 S-ET 10 Transformer RTRE 1,5 Transformer REU 1,5 Thyristor REE 2 * 5 KE 50-25-4 1467 68562 230 1~ 533 2.51 0.479 1298 70 69 55/51 19.8/33 F IP 54 8 S-ET 10 RTRE 3 REU 3 REE 4 6 KE 50-30-4 1473 68565 230 1~ 819 3.67 0.64 1193 70 70 59/55 24.8/39 F IP 54 14 S-ET 10 RTRE 5 REU 5 REE 4 6 KE 50-30-6 1471 230 1~ 294 1.48 0.404 676 70 70 49 23.3 F IP 54 6 S-ET 10 RTRE 3 REU 3 REE 2 6 KE 60-30-4 1478 68569 230 1~ 1261 5.93 0.847 1046 43 43 58/56 32/55 F IP 54 20 S-ET 10 RTRE 7 REU 7 6 KE 60-30-6 1476 68570 230 1~ 493 2.30 0.659 898 70 70 55/50 33/36 F IP 54 14 S-ET 10 RTRE 3 REU 3 REE 4 6 KE 60-35-6 1480 68573 230 1~ 554 2.63 0.68 565 41 41 51/44 34.5/54 F IP 54 8 S-ET 10 RTRE 3 REU 3 REE 4 6

66

Rectangular duct fans


DimensionS
E A H D 8,0

Ventilation accessories

DS p. 363

Rectangular duct fans

10,0(x8)

A KE 40-20-4 KE 50-25-4 KE 50-30-4/6 KE 60-30-4/6 KE 60-35-6


G

B 198 248 298 298 348

C 220 270 320 320 370

D 420 520 520 620 620

E 440 540 540 640 640

F 240 290 340 340 390

G 502 532 562 642 717

H 28 30 32 34 47

I 530 610 695 715 805

VK p. 368

398 498 498 598 598

LDR p. 358

FFK p. 355
C A D

RB p. 359

KE (I) 40-20 50-25 50-30-4 60-30-4

A 502 532 562 642

B 461 561 561 661

C 261 311 361 361

D 283.9 334.9 396 400.1

VBR p. 365

67

Rectangular duct fans


Performance

Rectangular duct fans

dB(A) LwA Inlet LwA Outlet LwA Surr. KE(I) With LDR 40-20 LwA Inlet LwA Outlet

Tot 63
69 72 54 55 42

Frequency bands [Hz] 125


66 63 49

dB(A) 4k
55 61 46

Tot 63 125 69 64 50 47 53 46 73 77 62 58 59 77 62 56 35 26 55 77

Frequency bands [Hz] 250 65 66 56 54 51 49 500 59 68 58 53 40 41 1k 63 73 55 48 41 43 2k 64 70 51 49 43 53 4k 62 68 46 46 46 55 8k 59 64 50 40 42 56

250
62 66 58

500
61 65 55

1k
57 66 55

2k
56 63 49

8k
49 54 41

LwA Inlet LwA Outlet LwA Surrounding


LwA Surr. KE(I)

LwA Surrounding 62 56 63 62

30 54 55

42 61 58

54 53 57

47 46 50

46 34 43

43 40 47

38 43 49

32 39 44

With LDR 50-25 LwA Inlet LwA Outlet

Measurement point: 0,17 m/s; 211 Pa

Measurement point: 0,269 m/s; 258 Pa

dB(A)
LwA Inlet LwA Outlet LwA Surrounding LwA Surr. KE(I)

Tot 63 76 80 66 62 77 66 66 60 38 33 77 60 125 71 68 57 54 48 60

Frequency bands [Hz] 250 66 67 62 56 49 52 500 63 71 58 55 46 51 1k 67 76 61 55 37 45 2k 68 73 55 54 56 56 4k 66 72 51 51 56 58 8k 62 66 47 47 57 55

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDR 50-30 LwA Inlet LwA Outlet

Tot 63 67 70 56 59 57 58 55 50 58 55 125 61 58 48 53 50

Frequency bands [Hz] 250 57 57 49 42 42 500 56 64 45 36 44 1k 59 65 49 28 34 2k 59 62 43 42 45 4k 56 61 38 42 47 8k 49 53 34 38 42

With LDR 50-30


LwA Inlet LwA Outlet

Measurement point: 0,343 m/s; 337 Pa

Measurement point: 0,259 m/s; 146 Pa

68

Rectangular duct fans

Rectangular duct fans

dB(A) LwA Inlet LwA Outlet LwA Surrounding LwA Surr. KE(I) With LDR 60-30 LwA Inlet LwA Outlet

Tot 63
77 82 65 63 63 46

Frequency bands [Hz] 125


73 71 60

dB(A) 4k
68 75 55

Tot 63 125 65 65 51 49 57 57 71 75 62 57 65 61 64 55 56 41 64 55

Frequency bands [Hz] 250 63 62 58 52 48 47 500 60 69 50 50 40 49 1k 62 69 51 49 31 38 2k 62 67 49 46 45 50 4k 59 65 44 40 45 51 8k 53 57 37 32 42 46

250
66 68 55

500
65 74 55

1k
70 77 59

2k
69 74 56

8k
63 69 49

LwA Inlet LwA Outlet LwA Surrounding


LwA Surr. KE(I)

63 68 68

28 63 63

51 65 63

53 51 53

55 45 54

57 39 46

57 52 57

54 54 61

44 52 58

With LDR 60-30 LwA Inlet LwA Outlet

Measurement point: 0,468 m/s; 454 Pa

Measurement point: 0,354 m/s; 180 Pa

dB(A)
LwA Inlet LwA Outlet LwA Surrounding LwA Surr. KE(I)

Tot 63 67 72 58 51 61 61 60 56 52 42 60 56 125 60 60 49 45 53 53

Frequency bands [Hz] 250 57 61 52 42 44 48 500 57 66 49 42 40 49 1k 59 65 51 42 41 47 2k 59 64 46 42 46 51 4k 58 64 45 38 48 54 8k 51 56 37 30 43 48

With LDR 60-35


LwA Inlet LwA Outlet

Measurement point: 0,353 m/s; 249 Pa

69

Rectangular duct fans KT, KT(I)


Swing-out Speed-controllable Integral thermal contacts Can be installed in any position Maintenance-free and reliable Electrical accessories

Rectangular duct fans

STDT p. 342

The KT models have impellers with forward-curved blades and external rotor motors. The motor and impeller are mounted on the access cover to facilitate easy maintenance. The casing is manufactured from galvanised sheet steel. To protect the motor from overheating the fans have integral thermal contacts with external leads for connection to a motor protection device. The fans can be installed in any position and are simple to couple using DS flexible connections. The KT fans have a prewired, integral terminal box. KT(I) versions have double skin side panels, manufactured from galvanised steel with 25 mm mineral wool insulation.

RTRD p. 321

RTRDU p. 321

Quick selection

493, 502, 533, 463, 483, 465, 478, 468, 466

1 2 3 4 5

6 4

6 7 8 9

2 1 5 3 7

KT 40-20-4 KT 50-25-4 KT 50-25-6 KT 50-30-4 KT 50-30-6 KT 60-30-4 KT 60-30-6 KT 60-35-4 KT 60-35-6

1 2 3 4 4 5 1 6 7 7 5 2 3 6 8 8

KT 70-40-4 KT 70-40-6 KT 70-40-8 KT 80-50-4 KT 80-50-6 KT 80-50-8 KT 100-50-6 KT 100-50-8

Technical data
KT Art no. KT Art no. KT(I) Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight KT/KT(I) Insulation class, motor Enclosure class, motor Motor protection Speed control, five-step Speed control, five step high/low Wiring diagram p. 391-400 40-20-4 1482 68561 V/50 Hz 400 3~ W 289 A 0.519 m3/s 0.368 min-1 1303 C 63.4 C 63.4 dB(A) 52/49 kg 13.5/25 B IP 44 STDT 16 Transformer RTRD 2 Transformer RTRDU 2 7 50-25-4 1487 68563 400 3~ 565 0.969 0.544 1287 66.3 51.3 55/50 18.5/32 F IP 54 STDT 16 RTRD 2 RTRDU 2 8 50-25-6 1485 400 3~ 220 0.44 0.381 826 70 70 44 17.5 B IP 54 STDT 16 RTRD 2 RTRDU 2 8 50-30-4 1489 68567 400 3~ 935 1.64 0.72 1223 41 41 57/53 23/23 F IP 54 STDT 16 RTRD 2 RTRDU 2 8 50-30-6 1491 68568 400 3~ 330 0.66 0.509 804 49.9 49.9 51/48 21.5/36 F IP 54 STDT 16 RTRD 2 RTRDU 2 8 60-30-4 1494 68571 400 3~ 1362 2.36 0.953 1279 62.5 62.5 58/55 33.2/36 F IP 54 STDT 16 RTRD 4 RTRDU 4 8 60-30-6 1493 68572 400 3~ 418 0.855 0.598 837 39.9 39.9 48/43 26.5/36 F IP 54 STDT 16 RTRD 2 RTRDU 2 8 60-35-4 1499 68575 400 3~ 2478 4.15 1.32 1244 42.3 42.3 61/58 40.5/61 F IP 54 STDT 16 RTRD 7 RTRDU 7 8 60-35-6 1497 68574 400 3~ 935 1.84 1.08 777 44.3 44.3 52.5/48 34.5/40 F IP 54 STDT 16 RTRD 2 RTRDU 2 8

70

479, 471, 515, 525, 516, 494, 520, 511

Rectangular duct fans


Dimensions
E A H D 8,0

Ventilation accessories

DS p. 363

Rectangular duct fans

10,0(x8)

KT 40-20-4 50-25-4/6 50-30-4/6 60-30-4/6 60-35-4/6 70-40-4 70-40-6/8 80-50-4/6/8 100-50-6/8

A 398 498 498 598 598 698 698 798 998

B 198 248 298 298 348 398 398 497 497

C 220 270 320 320 370 420 420 520 520

D 420 520 520 620 620 720 720 820 1020

E 440 540 540 640 640 740 740 840 1040

F 240 290 340 340 390 440 440 540 540

G 502 532 562 642 717 787 787 880 980

H 32 68 68 89 92 92 92 113 113

I* 530 610 695 715 805 900 900 1090 1140

VK p. 368

LDR p. 358

* Dimension with fully open hatch

FFK p. 355
KT (I) 50-30-4 60-30-4 60-30-6 60-35 70-40-4 70-40-6 80-50 100-50 A 562 642 642 717 787 787 880 980 B 561 661 661 661 761 761 861 1061 C 361 361 361 411 461 461 560 560 D 383.7 383.7 433.7 470.3 470.3 587.3 588.8 E 396 418.5 399 473.5 523.5 506.5 625 626.5 F 385.5 408 388.5 463 513 496 614.5 616

RB p. 359

VBR p. 365

KT Art no. KT Art no. KT(I) Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight KT/KT(I) Insulation class, motor Enclosure class, motor Motor protection Speed control, five-step Speed control, five step high/low Wiring diagram p. 391-400

70-40-4 1506 68576 V/50 Hz 400 3~ W 4186 A 7.15 m3/s 1.84 min-1 1250 C 48.5 C 48.5 dB(A) 66/60 kg 57.7/65 F IP 54 STDT 16 Transformer RTRD 14 Transformer 8

70-40-6 1504 68577 400 3~ 1628 3.02 1.46 805 60.8 60.8 57/51 46.7/72 F IP 54 STDT 16 RTRD 4 RTRDU 4 8

70-40-8 1502 68578 400 3~ 951 1.89 1.28 661 68.7 68.7 51/50 45.5/65 F IP 54 STDT 16 RTRD 4 RTRDU 4 8

80-50-4 1513 400 3~ 5639 9.22 2.15 1266 41 41 67 73.5 F IP 54 STDT 16 RTRD 14 8

80-50-6 1511 400 3~ 2799 5.12 2.1 828 70 70 59 67.5 F IP 54 STDT 16 RTRD 7 RTRDU 7 8

80-50-8 1509 400 3~ 1167 2.44 1.52 548 62 62 59 60.5 F IP 54 STDT 16 RTRD 4 RTRDU 4 8

100-50-6 1516 68582 400 3~ 4450 7.82 2.73 794 43 43 62/61 83.5/100 F IP 54 STDT 16 RTRD 14 8

100-50-8 1514 68583 400 3~ 2287 4.68 2.30 614 70 70 58/58 81.5/100 F IP 54 STDT 16 RTRD 7 RTRDU 7 8

71

Rectangular duct fans


Performance

Rectangular duct fans

dB(A) LwA Inlet LwA Outlet LwA Surrounding LwA Surr. KT(I) With LDR 40-20 LwA Inlet LwA Outlet

Tot 63 70 72 59 56 64 62 56 53 34 28 56 53 125 67 63 46 42 62 58

Frequency bands [Hz] 250 63 67 57 54 54 58 500 59 63 51 48 44 48 1k 56 65 49 43 33 42 2k 55 62 44 43 39 46 4k 53 59 40 39 41 47 8k 46 53 34 31 36 43

dB(A) LwA Inlet LwA Outlet LwA Surrounding LwA Surr. KT(I) With LDR 50-25 LwA Inlet LwA Outlet

Tot 63 72 76 62 57 58 61 60 56 39 32 53 56 125 67 63 50 46 53 53

Frequency bands [Hz] 250 64 64 53 49 52 49 500 59 67 54 47 38 42 1k 64 71 56 50 40 46 2k 64 69 52 51 42 49 4k 62 67 50 48 44 52 8k 58 65 55 42 41 53

Measurement point: 0,144 m/s; 236 Pa

Measurement point: 0,283 m/s; 282 Pa

Min. static back pressure: 110 Pa


dB(A)
LwA Inlet LwA Outlet LwA Surrounding

Tot 63 63 66 51 54 52 52 50 33 52 50 125 59 55 41 49 45

Frequency bands [Hz] 250 55 55 46 40 40 500 52 60 45 27 35 1k 53 59 43 28 34 2k 53 57 37 33 37 4k 50 54 33 35 39 8k 44 48 30 32 36

dB(A) LwA Inlet LwA Outlet LwA Surrounding


LwA Surr. KT(I)

Tot 63 75 79 64 60 68 66 66 62 45 36 66 62 125 70 68 55 53 62 60

Frequency bands [Hz] 250 64 67 59 53 49 52 500 63 70 55 50 43 50 1k 67 74 58 52 36 43 2k 67 72 54 51 50 55 4k 66 71 49 50 52 57 8k 62 66 48 44 51 55

With LDR 50-25


LwA Inlet LwA Outlet

With LDR 50-30 LwA Inlet LwA Outlet

Measurement point: 0,188 m/s; 133 Pa

Measurement point: 0,29 m/s; 351 Pa

72

Rectangular duct fans

Rectangular duct fans

dB(A) LwA Inlet LwA Outlet LwA Surrounding LwA Surr. KT(I) With LDR 50-30 LwA Inlet LwA Outlet

Tot 63 66 73 58
55

Frequency bands [Hz] 125 60 60 48 46 52 52 250 55 59 52 47 40 44 500 56 68 53 51 36 48 1k 58 67 50 46 27 36 2k 58 64 46 45 41 47 4k 56 63 44 43 42 49 8k 48 55 37 36 37 44 54 53 30 25 54 53

dB(A) LwA Inlet LwA Outlet LwA Surrounding LwA Surr. KT(I) With LDR 60-30 LwA Inlet LwA Outlet

Tot 63 78 81 65 61 72 67 71 59 39 33 71 59 125 71 70 59 55 63 62

Frequency bands [Hz] 250 67 68 60 52 52 53 500 66 73 59 55 46 53 1k 71 76 57 54 40 45 2k 71 73 54 53 54 56 4k 67 73 52 50 53 59 8k 63 68 48 43 52 57

57 58

Measurement point: 0,267 m/s; 153 Pa

Measurement point: 0,487 m/s; 422 Pa

Min. static back pressure: 75 Pa


dB(A)
LwA Inlet LwA Outlet LwA Surrounding

Min. static back pressure: 180 Pa


dB(A) 4k 54 59 40 35 40 45 8k 47 51 35 29 36 40 LwA Inlet LwA Outlet LwA Surrounding LwA Surr. KT(I) With LDR 60-35 LwA Inlet LwA Outlet 80 84 68 65 74 73 Tot 63 72 67 52 44 72 67 125 75 73 62 57 68 66 Frequency bands [Hz] 250 67 72 63 57 54 59 500 68 76 59 57 51 59 1k 73 79 60 59 55 61 2k 72 77 55 56 59 64 4k 69 75 52 52 59 65 8k 65 70 48 47 57 62 1k 58 62 45 42 27 31 2k 56 60 42 39 39 43

Tot 63 66 69 55 50 60 57 59 53 35 25 59 53 125 60 62 49 44 52 54

Frequency bands [Hz] 250 55 58 50 44 40 43 500 55 62 48 45 35 42

LwA Surr. KT(I) With LDR 60-30


LwA Inlet LwA Outlet

Measurement point: 0,256 m/s; 217 Pa

Measurement point: 0,508 m/s; 632 Pa

73

Rectangular duct fans

Rectangular duct fans

Min. static back pressure: 300 Pa


dB(A) LwA Inlet LwA Outlet LwA Surrounding LwA Surr. KT(I) With LDR 60-35 LwA Inlet LwA Outlet 66 63 65 58 58 56 44 49 43 51 43 49 47 52 48 54 46 50 Tot 63 70 73 59 55 65 58 41 34 125 65 63 52 47 Frequency bands [Hz] 250 57 62 56 48 500 60 68 52 47 1k 61 67 50 48 2k 60 65 46 47 4k 58 64 45 43 8k 54 58 41 37 LwA Inlet LwA Outlet LwA Surrounding
LwA Surr. KT(I)

dB(A)

Tot 63 84 86 73 67 81 78 80 73 55 52 80 73 125 77 75 64 60 70 68

Frequency bands [Hz] 250 70 75 67 61 59 64 500 69 79 65 58 55 65 1k 76 81 68 59 62 67 2k 74 79 63 58 64 69 4k 71 77 63 53 63 69 8k 68 72 59 48 62 66

With LDR 70-40 LwA Inlet LwA Outlet

Measurement point: 0,443 m/s; 279 Pa

Measurement point: 0,677 m/s; 820 Pa

dB(A)
LwA Inlet LwA Outlet LwA Surrounding LwA Surr. KT(I)

Tot 63 72 76 64 58 68 68 67 65 46 44 67 65 125 64 66 57 50 57 59

Frequency bands [Hz] 250 60 66 57 52 49 55 500 63 71 60 54 49 57 1k 65 70 54 48 51 56 2k 63 68 49 48 53 58 4k 61 67 46 43 53 59 8k 55 60 42 39 49 54

dB(A) LwA Inlet LwA Outlet LwA Surrounding


LwA Surr. KT(I)

Tot 63 69 73 58 57 63 63 62 56 35 35 62 56 125 60 59 49 48 53 52

Frequency bands [Hz] 250 59 63 52 50 48 52 500 59 68 53 54 45 54 1k 61 66 51 49 47 52 2k 60 65 45 47 50 55 4k 59 64 42 44 51 56 8k 52 56 37 41 46 50

With LDR 70-40


LwA Inlet LwA Outlet

With LDR 70-40 LwA Inlet LwA Outlet

Measurement point: 0,537 m/s; 397 Pa

Measurement point: 0,48 m/s; 208 Pa

74

Rectangular duct fans

Rectangular duct fans

Min. static back pressure: 720 Pa


dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDR 80-50 LwA Inlet LwA Outlet 76 82 71 72 68 71 66 69 61 72 65 75 67 76 65 74 64 73 Tot 63 82 90 74 71 72 61 125 74 77 68 Frequency bands [Hz] 250 74 77 67 500 71 82 66 1k 76 86 69 2k 75 84 64 4k 71 80 60 8k 67 76 58 LwA Inlet LwA Outlet dB(A)

Min. static back pressure: 70 Pa


Tot 63 77 82 66 70 74 64 62 51 64 62 125 66 66 57 60 60 Frequency bands [Hz] 250 65 69 58 57 61 500 69 77 62 59 67 1k 72 76 60 61 65 2k 71 75 55 63 67 4k 67 72 51 61 66 8k 62 66 50 59 63

LwA Surrounding With LDR 80-50 LwA Inlet LwA Outlet

Measurement point: 1,05 m/s; 1046 Pa

Measurement point: 0,976 m/s; 458 Pa

Min. static back pressure: 250 Pa


dB(A)
LwA Inlet LwA Outlet LwA Surrounding

Tot 63 68 73 66 63 65 59 55 50 59 55 125 59 59 51 53 53

Frequency bands [Hz] 250 59 64 57 51 56 500 59 68 54 49 58 1k 62 66 53 51 55 2k 62 66 54 54 58 4k 58 64 57 52 58 8k 50 54 63 47 51

dB(A) LwA Inlet LwA Outlet LwA Surrounding LwA Surr. KT(I) With LDR 100-50 LwA Inlet LwA Outlet

Tot 63 79 84 69 68 74 71 71 69 59 55 71 69 125 68 71 63 61 62 65

Frequency bands [Hz] 250 65 72 61 60 57 64 500 72 78 63 61 62 68 1k 72 78 61 60 61 67 2k 72 77 58 61 64 69 4k 69 74 53 53 63 68 8k 65 69 53 47 62 66

With LDR 100-50


LwA Inlet LwA Outlet

Measurement point: 0,709 m/s; 251 Pa

Measurement point: 1,14 m/s; 608 Pa

75

Rectangular duct fans

Rectangular duct fans

dB(A) LwA Inlet LwA Outlet LwA Surrounding LwA Surr. KT(I) With LDR 100-50 LwA Inlet LwA Outlet

Tot 63 73 78 65 65 67 70 64 62 52 47 64 62 125 61 63 55 53 55 57

Frequency bands [Hz] 250 61 68 59 59 53 60 500 66 73 60 58 56 63 1k 65 70 57 56 54 59 2k 66 71 56 59 58 63 4k 63 68 54 54 57 62 8k 56 61 46 41 53 58

Measurement point: 0,17 m/s; 211 Pa

76

Rectangular duct fans Reference

Rectangular duct fans

Project: Ice Hockey Stadium City/Country: Bratislava, Slovakia Products/Solutions: K, KD, KT to ventilate different premises at stadium + air distribution products (grilles, diffusers).

77

Rectangular duct fans RS


Speed-controllable Integral thermal contacts Can be installed in any position Maintenance-free and reliable S-ET/STDT p. 341-342 Electrical accessories

Rectangular duct fans

The RS models have impellers with backward-curved blades and external rotor motors. The motor and impeller are mounted on the access cover to facilitate easy maintenance. To protect the motor from overheating RS 30-15 to 50-25 have an integral thermal contact with electrical reset, RS 60-35 M to 100-50 have integral thermal contacts with external leads for connection to a motor protection device. The fans can be installed in any position and are simple to couple using DS flexibleconnections. The casing is manufactured from galvanised sheet steel.

RTRE p. 320

RE p. 320 Quick selection

1 2 3 4 5 6

RS 30-15 RS 40-20 M RS 40-20 L RS 50-25 RS 60-35 M1 RS 60-35 M3

1 2 3 4 5 6 7

RS 60-35 L1 RS 60-35 L3 RS 70-40 L1 RS 70-40 L3 RS 80-50M3 RS 80-50L3 RS 100-50L3

3099, 3085, 2486, 2483, 2487, 2488, 2492

3672, 644, 3891, 607, 3896, 2485

REU p. 320

REE p. 321

3 1 2 4 5 6 1 2 4 3 5 6 7

RTRD/RTRDU p. 321

Technical data
RS Art no. Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Capacitor Motor protection Speed control, five-step Speed control, five step high/low Speed control, stepless Wiring diagram p. 391-400 * + S-ET 10 30-15 1435 V/50 Hz 230 1~ W 59.9 A 0.264 m3/s 0.135 min-1 2431 C 70 C 70 dB(A) 48 kg 6.8 B IP 44 F 2 Integral Transformer RE 1.5 Transformer REU 1.5 Thyristor REE 1 2 40-20 M 1439 230 1~ 106 0.461 0.238 2597 70 70 52 11.8 B IP 44 3 Integral RE 1.5 REU 1.5 REE 1 2 40-20 L 1443 230 1~ 208 0.926 0.342 2556 65 65 53 12.8 F IP 44 5 Integral RE 1.5 REU 1.5 REE 1 2 50-25 1447 230 1~ 138 0.604 0.411 1362 53 53 46 17 B IP 44 5 Integral RE 1.5 REU 1.5 REE 1 2 60-35 M1 1795 230 1~ 401 1.91 0.941 1365 70 70 58 33.4 F IP 54 8 S-ET 10 RTRE 3* REU 3 REE 2* 6 60-35 M3 1796 400 3~ 399 0.795 0.974 1371 70 70 58 32.2 F IP 54 STDT 16 RTRD 2 RTRDU 2 8 60-35 L1 2046 230 1~ 626 2.80 1.12 1308 70 70 58 37.2 F IP 54 14 S-ET 10 RTRE 3* REU 3 REE 4* 6

78

Rectangular duct fans


Dimensions
10,0 (x8) I K

Ventilation accessories

DS p. 363
B D c/c F H

Rectangular duct fans

A L

G c/c E C 8,0
RS 30-15 40-20 M 40-20 L 50-25 A 402 502 502 532 B 217 267 267 317 C 340 440 440 540 D 190 240 240 290 E 320 420 420 520 F 170 220 220 270 G 298 398 398 498 H 148 198 198 248 I 79 99 99 125 J 120 125 125 85.5 K 230 310 366 L 254 352 423

VK p. 368

LDR p. 358

310.5 352.5

FFK p. 355
~1300

10,0 (x8)

I J

RB p. 359

B D c/c F H

VBR p. 365

G c/c E C 7,5

RS 70-40 L 80-50 L 100-50 L

A 787 882 982

B 402 452 573 583

C 640 740 840 1040

D 390 440 541 541

E 620 720 820 1020

F 370 420 520 520

G 598 698 798 998

H 348 398 498 498

I 128

J 145

K 490 490 614 614

L 524 524 644 644

60-35 M/L 717

189,5 215 182,5 190 298,5 290

RS Art no. Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Motor protection Speed control, five-step Speed control, five step high/low Speed control, stepless Wiring diagram p. 391-400

60-35 L3 2047 V/50 Hz 400 3~ W 667 A 1.59 m3/s 1.21 min-1 1408 C 70 C 70 dB(A) 61 kg 37 F IP 54 STDT 16 Transformer RTRD 2 Transformer RTRDU 2 Thyristor 8

70-40 L1 1797 230 1~ 623 2.84 1.59 1308 67 67 60 41.8 F IP 54 S-ET 10 RTRE 5 REU 5* REE 4* 6

70-40 L3 1798 400 3~ 704 1.70 1.39 1410 70 70 61 41.4 F IP 54 STDT 16 RTRD 2 RTRDU 2 8

80-50 M3 1799 400 3~ 1089 1.97 1.96 1335 70 55 60 59.5 F IP 54 STDT 16 RTRD 4 RTRDU 4 8

80-50 L3 1800 400 3~ 1893 3.60 2.60 1385 70 64 63 71.5 F IP 54 STDT 16 RTRD 7 RTRDU 7 8

100-50 L3 1801 400 3~ 2962 5.09 3.36 1361 70 51 65 96.5 F IP 54 STDT 16 RTDR 7 RTRDU 7 8

79

Rectangular duct fans


Performance

Rectangular duct fans

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDR 30-15 LwA Inlet LwA Outlet

Tot 63 69 72 55 47 51 29 125 59 56 36

Frequency bands [Hz] 250 67 69 53 500 59 66 48 1k 58 64 47 2k 56 61 44 4k 50 54 38 8k 41 46 30

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDR 40-20 LwA Inlet LwA Outlet

Tot 63 71 74 59 62 62 52 51 37 52 51 125 64 62 49 59 57

Frequency bands [Hz] 250 66 67 56 57 58 500 63 70 54 48 55 1k 64 67 49 41 44 2k 59 65 46 43 49 4k 54 60 41 42 48 8k 46 48 34 36 38

56 57

47 51

52 49

52 54

41 48

33 39

31 36

31 35

22 27

Measurement point: 0,0686 m/s; 224 Pa

Measurement point: 0,119 m/s; 246 Pa

dB(A)
LwA Inlet LwA Outlet LwA Surrounding

Tot 63 73 77 60 61 63 53 51 34 53 51 125 58 57 42 53 52

Frequency bands [Hz] 250 65 66 51 56 57 500 66 72 57 51 57 1k 68 71 53 45 48 2k 64 71 52 48 55 4k 61 64 47 49 52 8k 57 59 45 47 49

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDR 50-25 LwA Inlet LwA Outlet

Tot 63 68 69 53 61 58 59 54 40 59 54 125 66 65 48 56 55

Frequency bands [Hz] 250 60 63 49 45 48 500 55 62 44 30 37 1k 56 60 41 31 35 2k 50 57 37 30 37 4k 47 49 35 32 34 8k 45 42 37 33 30

With LDR 40-20


LwA Inlet LwA Outlet

Measurement point: 0,189 m/s; 386 Pa

Measurement point: 0,222 m/s; 190 Pa

80

Rectangular duct fans

RS 60-35 M1

RS 60-35 M3

Rectangular duct fans

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDR 60-35 LwA Inlet LwA Outlet

Tot 63 73 81 65 57 60 41 125 61 68 54

Frequency bands [Hz] 250 70 78 62 500 67 74 56 1k 64 73 56 2k 63 70 53 4k 56 61 46 8k 47 50 37

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDR 60-35 LwA Inlet LwA Outlet

Tot 63 74 79 65 63 66 59 57 44 59 57 125 62 65 54 55 58

Frequency bands [Hz] 250 69 74 63 56 61 500 68 72 55 51 55 1k 65 71 55 47 53 2k 64 70 53 51 57 4k 59 62 48 49 52 8k 52 53 38 44 45

62 68

57 60

54 61

57 65

50 57

46 55

50 57

46 51

39 42

Measurement point: 0,538 m/s; 285 Pa

Measurement point: 0,528 m/s; 306 Pa

RS 60-35 L3

dB(A)
LwA Inlet LwA Outlet LwA Surrounding

Tot 63 75 80 65 66 67 63 61 47 63 61 125 67 68 56 60 61

Frequency bands [Hz] 250 69 73 62 56 60 500 68 74 58 51 57 1k 66 74 57 48 56 2k 65 70 54 52 57 4k 59 65 49 49 55 8k 52 56 39 44 48

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDR 60-35 LwA Inlet LwA Outlet

Tot 63 78 82 68 68 69 64 60 50 64 60 125 68 70 57 61 63

Frequency bands [Hz] 250 72 77 64 59 64 500 72 77 60 55 60 1k 70 76 61 52 58 2k 69 73 57 56 60 4k 63 67 52 53 57 8k 56 59 43 48 51

With LDR 60-35


LwA Inlet LwA Outlet

Measurement point: 0,448 m/s; 404 Pa

Measurement point: 0,668 m/s; 363 Pa

81

Rectangular duct fans

Rectangular duct fans

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDR 70-40 LwA Inlet LwA Outlet

Tot 63 77 80 67 67 70 62 62 46 62 62 125 65 66 56 58 59

Frequency bands [Hz] 250 72 75 64 61 64 500 72 74 60 58 60 1k 68 74 57 54 60 2k 68 72 54 58 62 4k 62 65 47 54 57 8k 53 57 40 47 51

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDR 70-40 LwA Inlet LwA Outlet

Tot 63 78 81 68 68 70 60 63 44 60 63 125 67 66 59 60 59

Frequency bands [Hz] 250 73 76 64 62 65 500 72 75 59 58 61 1k 69 74 59 55 60 2k 70 72 58 60 62 4k 65 65 52 57 57 8k 57 57 45 51 51

Measurement point: 0,815 m/s; 355 Pa

Measurement point: 0,693 m/s; 429 Pa

dB(A)
LwA Inlet LwA Outlet LwA Surrounding

Tot 63 78 83 67 70 75 60 60 47 60 60 125 68 69 56 62 63

Frequency bands [Hz] 250 69 80 61 61 72 500 73 77 62 63 67 1k 71 76 59 60 65 2k 69 72 58 61 64 4k 64 65 51 58 59 8k 57 57 45 54 54

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDR 80-50 LwA Inlet LwA Outlet

Tot 63 82 88 70 73 79 64 70 51 64 70 125 73 74 62 67 68

Frequency bands [Hz] 250 73 81 64 65 73 500 77 82 66 67 72 1k 74 83 62 63 72 2k 72 79 60 64 71 4k 67 72 53 61 66 8k 60 64 47 57 61

With LDR 80-50


LwA Inlet LwA Outlet

Measurement point: 0,935 m/s; 482 Pa

Measurement point: 1,04 m/s; 672 Pa

82

Rectangular duct fans

Rectangular duct fans

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDR 100-50 LwA Inlet LwA Outlet

Tot 63 83 91 72 69 73 61 125 73 78 66

Frequency bands [Hz] 250 74 84 64 500 77 85 66 1k 77 87 65 2k 76 82 64 4k 72 75 59 8k 66 66 52

76 83

69 73

67 72

66 76

67 75

66 76

68 74

66 69

63 63

Measurement point: 1,77 m/s; 678 Pa

83

Rectangular duct fans RSI


Speed-controllable Integral thermal contacts Can be installed in any position Maintenance-free and reliable S-ET/STDT p. 341-342 Electrical accessories

Rectangular duct fans

The RSI models have impellers with backward-curved blades and external rotor motors. The motor and impeller are mounted on the access cover to facilitate easy maintenance. The RSI models are thermally and acoustically insulated with 50 mm mineral wool, with perforated sheet steel on the inner surface. To protect the motor from overheating the RSI fans have integral thermal contacts with external leads for connection to a motor protection device. The fans can be installed in any position and are simple to couple using DS flexible connections. The casing is manufactured from galvanised sheet steel.

RTRE p. 320

REU p. 320

Quick selection REE p. 321


3896, 2362, 3110, 3109, 2371

1 2 3 4 5

RSI 60-35 M1 RSI 60-35 M3 RSI 60-35 L1 RSI 60-35 L3 RSI 70-40 L1

1 2 3 4

RSI 70-40 L3 RSI 80-50 M3 RSI 80-50 L3 RSI 100-50 L3

2379, 2389, 2384, 2393

RTRD/RTRDU p. 321

3 1 2

Technical data
RSI Art no. Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Capacitor Motor protection Speed control, five-step Speed control, five step high/low Speed control, stepless Wiring diagram p. 391-400 * + S-ET 10 60-35 M1 1788 V/50 Hz 230 1~ W 401 A 1.91 m3/s 0.941 min-1 1365 C 70 C 70 dB(A) 50 kg 61 F IP 54 8 S-ET 10 Transformer RTRE 3 Transformer REU 3* Thyristor REE 2* 6 60-35 M3 1789 400 3~ 399 0.795 0.974 1371 70 70 48 60.5 F IP 54 STDT 16 RTRD 2 RTRDU 2 8 60-35 L1 2042 230 1~ 626 2.80 1.12 1308 70 70 52 65 F IP 54 14 S-ET 10 RTRE 3 REU 3* REE 4* 6 60-35 L3 2043 400 3~ 667 1.59 1.21 1408 70 70 57 65 F IP 54 STDT 16 RTRD 2 RTRDU 2 8 70-40 L1 1790 230 1~ 623 2.84 1.59 1308 67 67 51 82.5 F IP 54 14 S-ET 10 RTRE 2 REU 3* REE 4* 6 70-40 L3 1791 400 3~ 704 1.70 1.39 1410 70 70 51 81.2 F IP 54 STDT 16 RTRD 2 RTRDU 2 8

84

Rectangular duct fans


Dimensions
L 10,0 (x8) J M N

Ventilation accessories

~1200

DS p. 363

c/c F

Rectangular duct fans

D B

G c/c E C A

VK p. 368

RSI 60-35 70-40 80-50 100-50

A 708 808 908

B 492 542 662

C 741 841 1041

D 441 541 541

E 620 720 820

F 370 420 520

G 598 697 797 997

H 347.5 397 497 497

I 55

J 92.5

K 717 787 882 982

L 201 194 310

N 532

O 597 597 717 717

LDR p. 358

640.5 391

139.5 99.5

55.5 92.5 55.5 112.5 55.5 112.5

169.5 532 144.5 656 244.5 656

1108 662

1020 520

FFK p. 355

RB p. 359

VBR p. 365

RSI Art no. Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Motor protection Speed control, five-step Speed control, five step high/low Speed control, stepless Wiring diagram p. 391-400

80-50 M3 1792 V/50 Hz 400 3~ W 1089 A 1.97 m3/s 1.96 min-1 1335 C 70 C 55 dB(A) 53 kg 109 F IP 54 STDT 16 Transformer RTRD 4 Transformer RTRDU 4 Thyristor 8

80-50 L3 1793 400 3~ 1893 3.60 2.60 1385 70 64 56 122 F IP 54 STDT 16 RTRD 7 RTRDU 7 8

100-50 L3 1794 400 3~ 2962 5.09 3.36 1361 70 51 62 159 F IP 54 STDT 16 RTRD 7 RTRDU 7 8

85

Rectangular duct fans


Performance

RSI 60-35 M3

Rectangular duct fans

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDR 60-35 LwA Inlet LwA Outlet

Tot 63 65 79 57 52 65 43 48 29 43 48 125 53 61 47 46 54

Frequency bands [Hz] 250 61 74 54 48 61 500 59 73 47 42 56 1k 55 72 47 37 54 2k 55 70 44 42 57 4k 49 60 38 39 50 8k 42 50 29 34 42

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDR 60-35 LwA Inlet LwA Outlet

Tot 63 67 79 55 59 66 55 57 29 55 57 125 62 65 47 55 58

Frequency bands [Hz] 250 62 74 50 49 61 500 60 72 48 43 55 1k 55 71 47 37 53 2k 55 70 45 42 57 4k 51 62 37 41 52 8k 47 53 35 39 45

Measurement point: 0,538 m/s; 285 Pa

Measurement point: 0,528 m/s; 306 Pa

RSI 60-35 L1

RSI 60-35 L3

dB(A)
LwA Inlet LwA Outlet LwA Surrounding

Tot 63 71 82 59 63 70 60 66 40 60 66 125 66 69 54 59 62

Frequency bands [Hz] 250 65 74 54 52 61 500 63 74 52 46 57 1k 58 77 49 40 59 2k 57 74 47 44 61 4k 54 62 43 44 52 8k 47 53 39 39 45

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDR 60-35 LwA Inlet LwA Outlet

Tot 63 72 83 64 63 69 55 60 26 55 60 125 67 70 56 60 63

Frequency bands [Hz] 250 67 77 59 54 64 500 66 77 57 49 60 1k 58 76 52 40 58 2k 59 73 54 46 60 4k 59 67 55 49 57 8k 52 59 48 44 51

With LDR 60-35


LwA Inlet LwA Outlet

Measurement point: 0,448 m/s; 404 Pa

Measurement point: 0,668 m/s; 363 Pa

86

Rectangular duct fans

Rectangular duct fans

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDR 70-40 LwA Inlet LwA Outlet

Tot 63 67 80 58 57 62 41 125 61 66 46

Frequency bands [Hz] 250 62 75 52 500 60 74 51 1k 57 74 50 2k 56 72 48 4k 51 65 46 8k 46 57 44

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDR 70-40 LwA Inlet LwA Outlet

Tot 63 68 81 57 61 70 57 63 39 57 63 125 62 66 46 55 59

Frequency bands [Hz] 250 62 76 51 51 65 500 62 75 52 48 61 1k 57 74 50 43 60 2k 58 72 48 48 62 4k 55 65 44 47 57 8k 49 57 39 43 51

60 70

57 62

54 59

51 64

46 60

43 60

46 62

43 57

40 51

Measurement point: 0,815 m/s; 355 Pa

Measurement point: 0,693 m/s; 429 Pa

dB(A)
LwA Inlet LwA Outlet LwA Surrounding

Tot 63 71 83 60 64 75 58 59 40 58 59 125 64 68 51 58 62

Frequency bands [Hz] 250 62 80 53 54 72 500 64 77 53 54 67 1k 61 76 52 50 65 2k 61 72 49 53 64 4k 60 65 49 54 59 8k 56 57 50 53 54

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDR 80-50 LwA Inlet LwA Outlet

Tot 63 74 88 63 68 79 63 70 43 63 70 125 69 74 56 63 68

Frequency bands [Hz] 250 66 81 55 58 73 500 67 82 59 57 72 1k 65 83 54 54 72 2k 65 79 52 57 71 4k 61 72 46 55 66 8k 58 64 46 55 61

With LDR 80-50


LwA Inlet LwA Outlet

Measurement point: 0,935 m/s; 482 Pa

Measurement point: 1,04 m/s; 672 Pa

87

Rectangular duct fans

Rectangular duct fans

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDR 100-50 LwA Inlet LwA Outlet

Tot 63 79 91 69 72 83 68 73 53 68 73 125 73 78 62 67 72

Frequency bands [Hz] 250 71 84 61 63 76 500 72 85 61 62 75 1k 70 87 63 59 76 2k 68 82 61 60 74 4k 62 75 56 56 69 8k 59 66 54 56 63

Measurement point: 1,77 m/s; 678 Pa

88

Rectangular duct fans Reference

Rectangular duct fans

Project Bolshoi Ice Palace City/Country: Sochi, Russia The building has been constructed for the Olympic Games in 2014. It is located in Olympic Park near the sea. It will be a major hockey stadium during the Games in 2014. Arena is designed for 12,000 visitors. The architecture of Arena resembles the famous Faberg egg, based on the concept of the image of frozen droplets. The arena is equipped with 75 AXC fans for smoke pressurization. TA units and duct fans are used for supply and extract air. Completion date of construction is 2012. Total building area is around 55,000 m2.

89

Rectangular duct fans KVD


Double inlet direct driven range Easy to install Robust and quiet operation Electrical accessories

Rectangular duct fans

REV p. 340

Direct driven box fan for in-line operation and suitable for outdoor installation. The unit is fitted with a forward curve double inlet fan and IP54 F class motor.The casing is manufactured from 1mm galvanized steel.The fan is mounted on 4 anti-vibration rubber mounts and the outlet connected to the casing via an 18mm flexible connection. An IP 55 connection box is fitted on the casing for easy access. Belt driven box fan for in-line operation and suitable for outdoor installation. The units are fitted with either forward curved or backward curved belt driven centrifugal fans and IP 55 Class F IE2 motors. Selection programme available as a download from www.systemair.com

DTV p. 343

tECHNICAL DATA
KVD Art no. Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air Sound pressure level at 1 m Weight Insulation class, motor Enclosure class, motor Wiring diagram p. 391-400 7-7-E4 645348 V/50 Hz 230 1~ W 146 A 2.20 m3/s 0.47 min-1 1410 C 50 dB(A) 58 kg 20 F IP 54 1 7-7-E6 645327 230 1~ 73 1.10 0.47 960 50 54 20 F IP 54 1 9-7-E4 645329 230 1~ 370 4.00 0.76 1410 50 61 30 F IP 54 1 9-7-E6 645328 230 1~ 237 2.5 0.70 950 50 59 30 F IP 54 1 9-9-E4 645349 230 1~ 550 5.90 0.88 1450 50 64 32 F IP 54 1 9-9-E6 645330 230 1~ 237 2.40 0.72 950 50 61 31 F IP 54 1 10-8-E6 645332 230 1~ 237 3.00 0.71 950 50 63 35 F IP 54 1

90

Rectangular duct fans


dIMENSIONS Ventilation accessories
B

A'

LDC p. 348

Rectangular duct fans

A'' A

B'

FK p. 355

RSK p. 355

KVD 7-7 9-7 9-9 10-8 10-10 12-9 12-12

A 498 548 548 648 648 698 698

A 458 508 508 608 608 658 658

A 454 504 504 604 604 654 654

B 457 507 507 607 607 657 657

B 415 465 465 565 565 615 615

C 442 532 532 592 592 642 642

D 273 336 336 371 371 434 434

E 253 304 304 330 330 382 382

F 200 250 250 300 300 350 350

ORH p. 357

KVD Art no. Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Wiring diagram p. 391-400

10-10-E4 645351 V/50 Hz 230 1~ W 550 A 6.00 m3/s 0.90 min-1 1375 C 50 dB(A) 66 kg 37 F IP 54 1

10-10-E6 645333 230 1~ 237 3.10 0.75 950 50 63 36 F IP 54 1

12-9-E6 645334 230 1~ 765 8.50 1.34 950 50 62 50 F IP 54 1

12-12-E6 550W 645335 230 1~ 525 6.40 1.22 950 50 64 50 F IP 54 1

12-12-E6 736W 645352 230 1~ 736 9.80 1.60 910 50 67 52 F IP 54 1

12-12-E6 645347 400 3~ 1100 5.10 1.99 910 50 71 53.5 F IP 54 1

91

Rectangular duct fans

Rectangular duct fans

........do not operate in dotted area

........do not operate in dotted area

92

Rectangular duct fans

Rectangular duct fans

E6

E6 (525W) E6 (237W)

E6 (237W) E6 (525W)
E6

........do not operate in dotted area

E6 (1100W)

E6 (736W)

E6 (525W)

E6 (525W)

E6 (1100W) E6 (736W)

93

Square duct fans MUB EC


100% speed controllable Integrated electronic motor protection Modular system Low noise level Installation in any mounting position Safe and maintenance free operation Energy-saving Mini MUB has circular spigot connections Electrical accessories

Square duct fans

MTP 10 p. 341

The MUB-EC fans are driven by EC-external rotor motors. These are energy saving motors with high efficiency. The power electronics are integrated in the motor housing. All models have one potential-free terminal for error message. All motors are suitable to be used for 50/60Hz. The input voltage for single phase units can vary between 200 and 277V, for three phase units between 380 and 480V. Speed control by a 0-10V signal. From size 450 the motor has an output voltage of 10V and 20V for an external potentiometer. MUB-EC is equipped with impellers with backward curved blades, manufactured from aluminium. The Mini MUB 200EC box is equipped with impellers with backward curved blades, manufactured from plastic PA6 25GV. The casing consists of an aluminium frame with fibreglass reinforced plastic corners of PA6; highly shock-resistant. The double skin panels are manufactured from galvanized steel with 20 mm mineralwool insulation. To avoid condensation the profile is provided with a separate chamber to fix the screws. The

CXE/AVC p. 322

EC-Vent p. 329-330

panels are removable, any outlet side can be chosen, allowing flexible ventilation solutions. Installation in any mounting position is possible.

Mini MUB

Technical data
MUB Art no. Techn.data is relating to 90 outlet Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Speed control, electronic Speed control, electronic Wiring diagram p. 391-400 Mini MUB 33032 200 EC V/50/60 Hz 230 1~ W 89.1 A 0.701 m3/s 0.174 min-1 3965 C 40 C 40 dB(A) 47 kg 8.1 B IP 44 CXE/AVC MTP 10 23a 025 315 30676 EC-A2 230 1~ 180 1.40 0.685 1870 60 60 44 30 B IP 44 CXE/AVC MTP 10 23b 025 355 30670 EC-A2 230 1~ 388 2.37 0.884 1639 60 60 53 28 B IP 44 CXE/AVC MTP 10 23b 042 400 30209 EC-A2 230 1~ 378 2.26 1.08 1339 60 60 51 58 B IP 44 CXE/AVC MTP 10 23b 042 450 30610 EC-A2 400 3~ 1170 1.95 1.75 1560 60 60 56 65 B IP 54 CXE/AVC MTP 10 28 042 450 31380 EC-A2-K 230 1~ 597 2.71 1.41 1297 60 60 56 65 B IP 54 CXE/AVC MTP 10 28

94

Square duct fans


dIMENSIONs
MUB 025 315EC-A2 025 355EC-A2 042 400EC-A2
A F

Ventilation accessories
A 500 500 670 670 670 670 800 800 B 500 500 670 670 670 670 800 800 C 420 420 590 590 590 590 720 720 D 315 355 400 454 450 504 560 630 E 200 224 253 286 286 321 360 407 F 40 40 40 70 70 70 70 70

042 450EC-A2 042 450EC-A2-K 042 500EC-A2 062 560EC-A2 062 630EC-A2

FGV p. 370

Square duct fans

SRKG p. 370

E D C B

UGS p. 370

WSG p. 370 Quick selection

1 2 3 4 5

1 2 3 4

Mini MUB EC MUB 025 315EC-A2 MUB 025 355EC-A2 MUB 042 400EC-A2

MUB 042 450EC-A2 MUB 042 450EC-A2-K MUB 042 500EC-A2 MUB 062 560EC-A2 MUB 062 630EC-A2

1 3

MUB Art no. Techn.data is relating to 90 outlet Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Speed control, electronic Speed control, electronic Wiring diagram p. 391-400

042 500 30314 EC-A2 V/50/60 Hz 400 3~ W 1100 A 2.18 m3/s 2.07 min-1 1340 C 60 C 60 dB(A) 56 kg 70 B IP 54 CXE/AVC MTP 10 28

062 560 30235 EC-A2 400 3~ 2000 3.10 3.00 1360 60 60 57 90 F IP 54 CXE/AVC MTP 10 28

062 630 30207 EC-A2 400 3~ 2560 3.90 3.63 1210 60 60 67 95 F IP 54 CXE/AVC MTP 10 28

6845, 6658, 6714, 6740, 6827

33032, 6773, 6816, 6669

95

Square duct fans


pERFORMANCE

Square duct fans

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 75 80 54 55 59 32 125 65 65 43

Frequency bands [Hz] 250 69 71 46 500 71 78 51 1k 65 72 49 2k 64 68 42 4k 60 64 32 8k 53 56 24

Measurement point: 0,085 m/s; 359 Pa

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 68 72 54 35 48 22 125 62 70 51

Frequency bands [Hz] 250 57 61 45 500 63 65 48 1k 61 64 45 2k 56 59 44 4k 55 55 33 8k 47 46 23

Measurement point: 0,306 m/s; 252 Pa

96

Square duct fans

Square duct fans

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 75 77 60 43 43 35 125 64 69 53

Frequency bands [Hz] 250 65 66 53 500 70 70 54 1k 66 70 51 2k 68 69 53 4k 66 66 50 8k 57 58 35

Measurement point: 0,494 m/s; 377 Pa

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 70 74 59 41 49 31 125 60 67 51

Frequency bands [Hz] 250 61 64 52 500 64 67 49 1k 65 68 54 2k 62 65 51 4k 59 60 43 8k 51 53 29

Measurement point: 0,563 m/s; 337 Pa

97

Square duct fans

Square duct fans

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 78 83 70 46 68 29 125 68 76 67

Frequency bands [Hz] 250 70 71 62 500 73 76 61 1k 71 78 61 2k 70 75 59 4k 65 68 52 8k 61 63 44

Measurement point: 0,988 m/s; 595 Pa

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 78 77 64 42 47 33 125 60 63 51

Frequency bands [Hz] 250 63 62 52 500 68 68 52 1k 70 71 54 2k 75 73 61 4k 71 68 55 8k 60 58 38

Measurement point: 0,727 m/s; 421 Pa

98

Square duct fans

Square duct fans

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 77 80 65 46 49 35 125 71 70 55

Frequency bands [Hz] 250 69 71 61 500 71 75 59 1k 70 74 57 2k 69 72 56 4k 65 67 51 8k 60 64 39

Measurement point: 1,08 m/s; 501 Pa

MUB 062 560EC-A2

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 80 77 71 51 57 40 125 71 70 66

Frequency bands [Hz] 250 75 70 67 500 73 71 61 1k 74 70 60 2k 72 67 58 4k 67 64 48 8k 63 58 36

Measurement point: 1,64 m/s; 677 Pa

99

Square duct fans

Square duct fans

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 82 83 76 54 59 47 125 75 75 74

Frequency bands [Hz] 250 76 77 67 500 73 76 62 1k 74 74 60 2k 73 72 59 4k 69 68 49 8k 65 64 39

Measurement point: 1,91 m/s; 703 Pa

100

Square duct fans

Square duct fans

101

Square duct fans

IE2
2009/640/EG

MUB
The MUB fans have impellers with backward curved blades, manufactured from polyamide (size 355), aluminium (size 400-560), welded steel painted in RAL 5002 (size 100 630D4-L). The MUB 355-500 is equipped with external rotor motors, fully speed controllable. MUB 500-560DV, DS are driven by an IEC standard motor. For size 630D4-A2, 630D4-L and 710D6-A speed control is only possible by using a frequency converter. All single speed motors are in IE2 execution and possible to control via frequency converter. The three phase motors are D/Y connected for two speed operation. Motor protection is done by thermal contacts, which have to be connected to an external motor protection device. The casing consists of a corrosion-resistant aluminum frame with fiberglass reinforced plastic corners of PA6; highly shock resistant. The double skin panels are manufactured from galvanized steel with 20 mm mineral wool insulation. To avoid condensation the profile is provided with a separate chamber to fix screws. The Multibox fans are delivered for straight through airflow but can easily be rebuilt due to removable panels. This allows flexible ventilation solutions. The MUB can also be used as extract- or supply air unit in air handling units. Installation in any mounting position is possible.

Electrical accessories

Square duct fans

S-ET/STDT p. 341-342

RTRE p. 320

REU p. 320

Quick selection 90 airflow


1 2 3 4 5 6 7 8

REE p. 321
6726, 6734, 6739, 6748, 6751, 6755, 6777, 6779

MUB 025 355 E4-A2 MUB 025 355 DV-A2 MUB 042 400 E4-A2 MUB 042 400 DV-A2 MUB 042 450 E4-A2 MUB 042 450 DV-A2 MUB 042 499 E4-A2 MUB 042 499 DV-A2

1 2 3 4 5 6 7 8 9 1

MUB 042 500 E4-A2 MUB 042 500 D4-A2 IE2 MUB 062 560 D4-A2 IE2 MUB 062 560 D6-A2 IE2 MUB 062 630 D4-A2 IE2 MUB 062 630 D6-A2 IE2 MUB 062 630 DV-B2 MUB 100 630 D4-L IE2 MUB 100 710 D6-A2 IE2
7 9 5

6763, 9782, 9784, 9791, 9468, 9793, 6794, 9798, 9795

RTRD/RTRDU p. 321

1 2

FRQ p. 325

S-DT2 SKT p. 340

Technical data
MUB Art no. Techn.data is relating to 90 outlet Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Capacitor Motor protection Speed control, five-step Speed control, five step high/low Speed control, 2-step Speed control, stepless Wiring diagram p. 391-400 * + S-ET 10 025 355 2104 E4-A2 V/50 Hz 230 1~ W 264 A 1.19 m3/s 0.741 min-1 1399 C 40 dB(A) 55 kg 37 B IP 44 8 S-ET 10 Transformer RTRE 1.5 Transformer REU 1.5* Thyristor REE 2* 5 025 355 2775 DV-A2 400 3~ 243 0.541 0.731 1349 40 55 37 B IP 44 STDT 16 RTRD 2 RTRDU 2 S-D2SKT 16 042 400 2116 E4-A2 230 1~ 467 2.13 1.01 1358 40 49 58 F IP 54 10 S-ET 10 RTRE 3 REU 3* REE 4* 5 042 400 2112 DV-A2 400 3~ 430 0.826 1.08 1339 40 49 57 F IP 54 STDT 16 RTRD 2 RTRDU 2 S-D2SKT 16 042 450 2124 E4-A2 230 1~ 756 3.33 1.48 1249 60 52 60 F IP 54 16 S-ET 10 RTRE 5 REU 5* REE 4* 5 042 450 2123 DV-A2 400 3~ 726 1.32 1.52 1277 40 52 62 F IP 54 STDT 16 RTRD 2 RTRDU 2 S-D2SKT 18 042 499 2134 E4-A2 230 1~ 1023 4.72 1.87 1270 40 48 66 F IP 54 20 S-ET 10 RTRE 5 REU 5 6 042 499 2133 DV-A2 400 3~ 1457 1.64 1.76 1210 40 48 64 F IP 54 STDT 16 RTRD 2 RTRDU 2 S-D2SKT 18 042 500 2141 E4-A2 230 1~ 1310 5.78 2.13 1332 40 56 68 F IP 54 30 S-ET 10 RTRE 7 REU 7 6

102

Square duct fans


dIMENSIONs
A MUB025 355 MUB042 400 MUB042 450 MUB042 499 MUB042 500E4-A2
A

B 500 670 670 670 670 800

C 420 590 590 590 590 720

D 378 548 548 548 548 678

D 355 404 454 504 504 635

E 224 253 286 321 321 407

Ventilation accessories

500 670 670 670 670

FGV p. 370

MUB062 630DV-B2 800

Square duct fans

SRKG p. 370
E D D C B

UGS p. 370

A MUB042 500DS-A2 MUB042 500DV-A2 MUB062 560DS-A2 MUB062 560DV-A2 MUB062 630DV-B2 MUB062 630DS-B2 MUB062 630D4-L MUB062 710D6-A2
E D D C B A

B 670 670 800 800 800 800

C 590 590 720 720 720 720

D 548 548 676 676 678 678 878 878 878 878

D 504 504 570 570 635 635 630 715 630 715

E 321 321 361 361 407 407 389 460 389 460

WSG p. 370

670 670 800 800 800 800

1000 1000 920 1000 1000 920 1000 1000 920 1000 1000 920

MUB100 630D4-L MUB100 710D6-A2

MUB Art no. Techn.data is relating to 90 outlet Voltage/Frequency Power at shaft (P2) Current Max air flow R.p.m. Max temp. of transported air Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Motor protection Speed control, five-step Speed control, 2-step Speed control, stepless Wiring diagram p. 391-400

042 500 33542 D4-A2 IE2 V/50 Hz 400 3~ W 1500 A 3.39 m3/s 2.15 min-1 1400 C 40 dB(A) 55 kg 68 F IP 55 FRQ5(S)-4A FRQ(S)-4A 13b Y

062 560 33543 D4-A2 IE2 400 3~ 2200 4.64 3.25 1420 40 56 99 F IP 55 FRQ5(S)-10A FRQ(S)-10A 13b Y

062 560 33544 D6-A2 IE2 400 3~ 750 1.98 2.19 905 40 47 117 F IP 55 FRQ5(S)-4A FRQ(S)-4A 13b Y

062 630 33545 D4-A2 IE2 400 3~ 4000 8.12 3.89 1450 40 68 135 F IP 55 FRQ(S)-10A 13b D

062 630 33546 D6-A2 IE2 400 3~ 1500 3.61 2.76 940 40 53 130 F IP 55 FRQ(S)-4A 13b Y

062 630 2150 DV-B2 400 3~ 3890 6.4 4.17 1370 40 69 145 F IP 54 STDT 16 S-D2SKT 18

100 630 33549 D4-L IE2 400 3~ 4000 8.12 5.07 1450 40 74 160 F IP 55 FRQ5(S)-10A FRQ(S)-10A 13b D

100 710 33548 D6-A2 IE2 230D/400 3~ 2200 5.1 4.47 945 40 59 160 F IP 55 FRQ5(S)-10A FRQ(S)-10A 13b Y

FRQ5(S)-10A FRQ5(S)-4A RTRD 14

103

Square duct fans


pERFORMANCE

IE2
2009/640/EG

Square duct fans

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 68 70 62 55 57 49 125 57 59 51

Frequency bands [Hz] 250 61 63 55 500 63 65 57 1k 62 64 56 2k 59 61 53 4k 54 56 48 8k 47 49 41

Measurement point: 0,33 m/s; 270 Pa

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 68 70 62 55 57 49 125 57 59 51

Frequency bands [Hz] 250 61 63 55 500 63 65 57 1k 62 64 56 2k 59 61 53 4k 54 56 48 8k 47 49 41

Measurement point: 0,42 m/s; 250 Pa

104

Square duct fans

Square duct fans

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 72 74 56 59 61 43 125 61 63 45

Frequency bands [Hz] 250 65 67 49 500 67 69 51 1k 66 68 50 2k 63 65 47 4k 58 60 42 8k 51 53 53

Measurement point: 0,48 m/s; 365 Pa

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 72 74 56 59 61 43 125 61 63 45

Frequency bands [Hz] 250 65 67 49 500 67 69 51 1k 66 68 50 2k 63 65 47 4k 58 60 42 8k 51 53 35

Measurement point: 0,56 m/s; 323 Pa

105

Square duct fans

IE2
2009/640/EG

Square duct fans

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 75 77 59 62 64 46 125 64 66 48

Frequency bands [Hz] 250 68 70 52 500 70 72 54 1k 69 71 53 2k 66 68 50 4k 61 63 45 8k 54 56 38

Measurement point: 1,06 m/s; 250 Pa

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 74 76 59 61 63 46 125 63 65 48

Frequency bands [Hz] 250 67 69 52 500 69 71 54 1k 68 70 53 2k 65 67 50 4k 50 62 45 8k 53 55 38

Measurement point: 0,81 m/s; 325 Pa

106

Square duct fans

Square duct fans

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 78 80 55 65 67 42 125 67 69 44

Frequency bands [Hz] 250 71 73 48 500 73 75 50 1k 72 74 49 2k 69 71 46 4k 64 66 41 8k 57 59 34

Measurement point: 0,94 m/s; 451 Pa

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 76 78 55 63 65 42 125 65 67 44

Frequency bands [Hz] 250 69 71 48 500 71 73 50 1k 70 72 49 2k 67 69 46 4k 62 64 41 8k 55 57 34

Measurement point: 1,02 m/s; 370 Pa

107

Square duct fans

IE2
2009/640/EG

Square duct fans

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 79 81 63 66 68 50 125 68 70 52

Frequency bands [Hz] 250 72 74 56 500 74 76 58 1k 73 75 57 2k 70 72 54 4k 65 67 49 8k 58 60 42

Measurement point: 1,35 m/s; 380 Pa

MUB 042 500D4-A2 IE2

MUB 042 500D4-A2 IE2

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 77 79 62 64 66 49 125 66 68 51

Frequency bands [Hz] 250 70 72 55 500 72 74 57 1k 71 73 56 2k 68 70 53 4k 63 65 48 8k 56 68 41

Measurement point: 1,40 m/s; 400 Pa

108

Square duct fans

MUB 062 560D4-A2 IE2

MUB 062 560D4-A2 IE2

Square duct fans

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 78 80 63 65 67 50 125 67 69 52

Frequency bands [Hz] 250 71 73 56 500 73 75 58 1k 72 74 57 2k 69 71 54 4k 64 66 49 8k 57 59 42

Measurement point: 2,25 m/s; 565 Pa

MUB 062 560D6-A2 IE2

MUB 062 560D6-A2 IE2

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 69 71 54 56 58 51 125 58 60 43

Frequency bands [Hz] 250 63 65 48 500 64 66 49 1k 64 66 49 2k 60 62 45 4k 55 57 40 8k 47 49 32

Measurement point: 1,31 m/s; 283 Pa

109

Square duct fans

IE2
2009/640/EG

MUB 062 630D4-A2 IE2

MUB 062 630D4-A2 IE2

Square duct fans

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 86 88 75 73 75 62 125 75 77 64

Frequency bands [Hz] 250 79 81 68 500 81 83 70 1k 80 82 59 2k 77 79 66 4k 72 74 61 8k 65 67 54

Measurement point: 1,95 m/s; 911 Pa

MUB 062 630D6-A2 IE2

MUB 062 630D6-A2 IE2

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 73 75 60 60 62 47 125 62 64 49

Frequency bands [Hz] 250 67 69 54 500 68 70 55 1k 68 70 55 2k 64 66 51 4k 59 61 46 8k 51 53 38

Measurement point: 1,92 m/s; 395 Pa

110

Square duct fans

Square duct fans

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 87 89 76 74 76 63 125 76 78 65

Frequency bands [Hz] 250 80 82 69 500 82 84 71 1k 81 83 70 2k 78 80 67 4k 73 75 62 8k 66 68 55

Measurement point: 2,78 m/s; 761 Pa

MUB 100 630D4-L IE2

MUB 100 630D4-L IE2

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 87 89 81 58 60 52 125 76 78 70

Frequency bands [Hz] 250 80 82 74 500 82 84 76 1k 81 83 75 2k 78 80 72 4k 73 75 66 8k 65 67 59

Measurement point: 2,8 m/s; 928 Pa

111

Square duct fans

IE2
2009/640/EG

MUB 100 710D6-A2 IE2

MUB 100 710D6-A2 IE2

Square duct fans

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 78 80 66 65 67 53 125 67 69 55

Frequency bands [Hz] 250 72 74 60 500 73 75 61 1k 73 75 61 2k 69 71 57 4k 64 66 52 8k 56 58 44

Measurement point: 2,25 m/s; 565 Pa

112

Square duct fans Installation example

Square duct fans

Panels can be exchanged for different outlet positions.

113

Square duct fans KDRE/KDRD


Speed-controllable Integral thermal contacts Can be installed in any position Maintenance-free and reliable S-ET/STDT p. 341-342 Electrical accessories

KDRE/KDRD fans have external rotor motors and mixed flow impeller. The KDRE/KDRD series is notable for its relatively high static pressure and high level of efficiency. The casing is manufactured from galvanised sheet steel. To protect the motor from overheating, the KDRE/KDRD fans have integral thermal contacts with leads for connection to a motor protection device. The fans can be installed in any position and are simple to couple using DS flexible connections.

Square duct fans

RTRE p. 320

REU p. 320

Quick selection REE p. 321


586, 5182, 583, 581

1 2 3 4

KDRE 45 (586) KDRE 50 (5182) KDRE 55 (583) KDRE 65 (581)

1 2 3 4

KDRD 50 (4466) KDRD 55 (1646) KDRD 65 (3925) KDRD 70 (584)

4466,1646, 3925, 584

RTRD/RTRDU p. 321

Technical data
KDRE 45 Art no. Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Capacitor Motor protection Speed control, five-step Speed control, five step high/low Speed control, stepless Wiring diagram p. 391-400 * + S-ET 10 1311 V/50 Hz 230 1~ W 325 A 1.55 m3/s 1.00 min-1 1387 C 70 C 70 dB(A) 45 kg 23.5 F IP 54 8 S-ET 10 Transformer RTRE 3 Transformer REU 3* Thyristor REE 2* 6 KDRE 50 1313 230 1~ 442 1.94 1.27 1297 70 70 52 31 F IP 54 10 S-ET 10 RTRE 5 REU 5* REE 4* 6 KDRD 50 1314 400 3~ 462 0.962 1.34 1397 70 70 54 29 F IP 54 STDT 16 RTRD 2 RTRDU 2 8 KDRE 55 1315 230 1~ 861 4.10 1.94 1280 45 45 51 41 F IP 54 16 S-ET 10 RTRE 5 REU 5* 6 KDRD 55 1316 400 3~ 789 1.52 1.87 1315 49 40 55 38 F IP 54 STDT 16 RTRD 2 RTRDU 2 8 KDRE 65 1317 230 1~ 1501 6.61 3.07 1315 70 70 61 54 F IP 54 30 S-ET 10 RTRE 7 REU 7* 6

114

Square duct fans


DimensionS Ventilation accessories
10(4x)

DSK p. 370

Square duct fans

45

LDK p. 365

A* c/c B
c/c 470 520 573 680 720 B 492 547 595 707 740 C 400 450 485 510 530

FFS p. 368

A KDRE 45 KDRE/D 50 KDRE/D 55 KDRE/D 65 KDRE 447 502 550 661 696

RBK p. 368

VBK p. 367

KDRD 65 Art no. Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Motor protection Speed control, five-step Speed control, five step high/low Speed control, stepless Wiring diagram p. 391-400 1318 V/50 Hz 400 3~ W 1250 A 2.23 m3/s 2.72 min-1 1341 C 70 C 56 dB(A) 53 kg 50 F IP 54 STDT 16 Transformer RTRD 4 Transformer RTRDU 4 Thyristor 8

KDRD 70 6690 400 3~ 2489 4.67 4.12 1383 70 69 62 62 F IP 54 STDT 16 RTRD 7 RTRDU 7 8

115

Square duct fans


Performance

Square duct fans

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDK 45 LwA Inlet LwA Outlet

Tot 63 70 74 52 61 64 49 51 33 49 51 125 60 61 40 55 56

Frequency bands [Hz] 250 62 63 47 54 55 500 64 66 46 51 53 1k 64 71 47 52 59 2k 62 67 43 54 59 4k 57 58 35 50 51 8k 50 49 31 43 42

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDK 50 LwA Inlet LwA Outlet

Tot 63 71 74 59 61 64 46 47 27 46 47 125 58 62 45 51 55

Frequency bands [Hz] 250 64 64 57 56 56 500 68 68 52 55 55 1k 63 69 49 51 57 2k 60 65 47 51 56 4k 58 62 44 50 54 8k 50 54 40 43 47

Measurement point: 0,57 m/s; 140 Pa

Measurement point: 0,64 m/s; 200 Pa

dB(A)
LwA Inlet LwA Outlet LwA Surrounding

Tot 63 75 79 61 66 69 59 57 30 59 57 125 65 68 51 58 61

Frequency bands [Hz] 250 69 69 57 61 61 500 71 71 53 58 58 1k 68 75 56 56 63 2k 65 71 52 56 62 4k 58 63 44 50 55 8k 49 54 36 42 47

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDK 55 LwA Inlet LwA Outlet

Tot 63 75 80 58 65 69 58 58 43 58 58 125 62 64 48 53 55

Frequency bands [Hz] 250 68 69 56 59 60 500 70 72 46 57 59 1k 70 76 49 58 64 2k 67 72 44 57 62 4k 60 64 40 51 55 8k 54 57 34 46 49

With LDK 50
LwA Inlet LwA Outlet

Measurement point: 0,717 m/s; 224 Pa

Measurement point: 1,08 m/s; 233 Pa

116

Square duct fans

Square duct fans

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDK 55 LwA Inlet LwA Outlet

Tot 63 76 80 62 66 70 56 59 57 56 59 125 61 65 48 52 56

Frequency bands [Hz] 250 69 69 59 60 60 500 71 74 51 58 61 1k 70 77 50 58 65 2k 68 73 47 58 63 4k 61 65 44 52 56 8k 54 57 44 46 49

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDK 65 LwA Inlet LwA Outlet

Tot 63 78 86 68 69 76 56 55 36 56 55 125 65 67 53 59 61

Frequency bands [Hz] 250 71 74 63 64 67 500 72 78 60 58 64 1k 71 83 64 58 70 2k 70 79 58 61 70 4k 64 73 50 56 65 8k 65 75 54 58 68

Measurement point: 0,944 m/s; 273 Pa

Measurement point: 1,98 m/s; 244 Pa

dB(A)
LwA Inlet LwA Outlet LwA Surrounding

Tot 63 79 84 60 70 73 62 62 40 62 62 125 70 68 47 64 62

Frequency bands [Hz] 250 72 70 58 65 63 500 72 78 50 58 64 1k 72 81 50 59 68 2k 71 77 49 62 68 4k 64 69 37 56 61 8k 57 61 27 50 54

dB(A) LwA Inlet LwA Outlet With LDK 70 LwA Inlet LwA Outlet

Tot 63 84 89 75 74 44 75 74 125 74 76 54 69 71

Frequency bands [Hz] 250 77 79 63 70 72 500 77 82 62 58 63 1k 78 85 64 54 61 2k 76 80 60 53 57 4k 69 73 54 54 58 8k 65 67 49 55 57

LwA Surrounding 69 77 78

With LDK 65
LwA Inlet LwA Outlet

Measurement point: 1,3 m/s; 332 Pa

Measurement point: 2,33 m/s; 398 Pa

117

Square duct fans MUB/T


Motor outside of the air stream Integral cold conductors Low sound level Maintenance-free and reliable Pre-assembled isolator as standard Electrical accessories

FRQ p. 325

Square duct fans

100C

IE2
2009/640/EG

All MUB/T fans have impellers with backward curved blades, manufactured from aluminium, and IEC standard motors with efficiency class IE2 for all 400V three phase motors from 0.75 kW. Motors are outside the air stream. The casing consists of an aluminium frame with fiberglass reinforced plastic corners and double skin, galvanised steel panels with 20 mm mineral wool insulation. Panels are removable, allowing flexible ventilation solutions and including a quicklock access door. The MUB bottom panel is shaped as a grease tray and incorporates a premounted drain plug. An isolator switch is mounted on the casing. Motor protection by cold conductors or thermal contact, to be connected to an external motor protection device. Standard execution, seen in airflow direction: service door left, top outlet. NB! Outlet spigot to be ordered as an accessory.

S-ET/STDT p. 341-342

RTRE p. 320

REU p. 320

RTRD/RTRDU p. 321

Technical data
MUB/T Art no. Voltage/Frequency Power at shaft Current Max air flow R.p.m. Max temp. of transported air Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Capacitor Motor protection Speed control, five-step Speed control, five step high/low Speed control, stepless Speed control, electronic Wiring diagram p. 391-400 * + S-ET 10 042 400DV 33655 V/50 Hz 400 3~ W 370 A 1.4 m3/s 1.13 min-1 1370 C 100 dB(A) 47 kg 47 F IP 54 F STDT 16 RTRD 2 Transformer RTRDU 2 13b 042 400E4 33656 230 1~ 370 2.1 1.11 1370 100 47 62 F IP 54 12 S-ET 10 RTRE 3 REU 3* 21 042 450D4-IE2 33657 400 3~ 750 1.78 1.72 1400 100 49 64 F IP 55 U-EK 230E FRQ5(S)-4A FRQ(S)-4A 13b Y 042 450E4 33658 230 1~ 750 5.3 1.68 1430 100 50 62 F IP 54 30 S-ET 10 RTRE 7 REU 7* 21 042 500D4-IE2 33622 400 3~ 1500 3.39 2.23 1400 100 53 68 F IP 55 U-EK 230E FRQ5(S)-4A FRQ(S)-4A 13b Y FRQ(S)-10A FXDM 7 13b Y 062 560D4-IE2 33659 400 3~ 2200 4.2 3.25 1445 100 55 132 F IP 55 U-EK 230E FRQ5(S)-10A

U-EK230E p. 340
062 630D4-IE2 33660 400 3~ 4000 8.12 4.12 1450 100 67 137 F IP 55 U-EK 230E FRQ5(S)-10A FRQ(S)-10A FXDM 13 13b D

118

Square duct fans


Dimensions Ventilation accessories
A

FGV p. 370

Square duct fans

F E D

SRKG p. 370

1 inch

UGS p. 370
MUB/T MUB 042 400 MUB 042 450 MUB 042 500 MUB 062 560 MUB 062 630 A 670 670 670 800 800 B 670 670 670 800 800 C 590 590 590 720 720 D 548 548 548 678 678 E 404 454 504 564 635 F 253 286 321 361 407

WSD p. 370

WSG p. 370

CCM inlet p. 375

CCM outlet p. 375

Quick selection

CCMI outlet p. 375


9826, 9859, 9824, 9825
9823, 10950, 9821

1 2 3 4

MUB/T 042 400DV MUB/T 042 400E4 MUB/T 042 450D4-IE2 MUB/T 042 450E4

1 2 3

MUB/T 042 500D4-IE2 MUB/T 062 560D4-IE2 MUB/T 062 630D4-IE2

1 2

3 4
1 2 3

119

Square duct fans


pERFORMANCE

IE2
2009/640/EG

MUB/T 042 400DV

MUB/T 042 400E4

Square duct fans

dB(A) LwA Inlet LwA Outlet

Tot 63 70 72 57 59 41 125 59 61 43

Frequency bands [Hz] 250 63 65 47 500 65 67 49 1k 64 66 48 2k 61 63 45 4k 56 58 40 8k 51 51 33

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 70 72 54

Frequency bands [Hz] 63 57 59 41 125 59 61 43 250 63 65 47 500 65 67 59 1k 64 66 48 2k 61 63 45 4k 56 58 40 8k 49 51 33

LwA Surrounding 54

Measurement point: 0,6 m/s; 385 Pa

Measurement point: 0,59 m/s; 380 Pa

MUB/T 042 450D4-IE2

MUB/T 042 450E4

dB(A)
LwA Inlet LwA Outlet LwA Surrounding

Tot 71 73 56

Frequency bands [Hz] 63 58 60 43 125 60 62 45 250 64 66 49 500 66 68 51 1k 65 67 50 2k 62 64 47 4k 47 59 42 8k 50 52 35

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 72 74 57 59 61 44 125 61 63 46

Frequency bands [Hz] 250 65 67 50 500 67 69 52 1k 66 68 51 2k 63 65 48 4k 48 60 43 8k 51 53 36

Measurement point: 0,8 m/s; 400 Pa

Measurement point: 0,88 m/s; 470 Pa

120

Square duct fans

MUB/T 042 500D4-IE2

Square duct fans

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 75 77 60 62 64 47 125 64 66 49

Frequency bands [Hz] 250 68 70 53 500 70 72 55 1k 69 71 54 2k 66 68 51 4k 61 63 46 8k 54 56 39

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 78 80 63 65 67 50 125 67 69 51

Frequency bands [Hz] 250 71 73 56 500 73 75 58 1k 72 74 57 2k 69 71 54 4k 64 66 59 8k 57 59 42

Measurement point: 1,26 m/s; 470 Pa

Measurement point: 2,25 m/s; 565 Pa

MUB/T 062 630D4-IE2

dB(A)
LwA Inlet LwA Outlet LwA Surrounding

Tot 63 86 88 75 73 78 62 125 75 77 64

Frequency bands [Hz] 250 79 81 68 500 81 83 70 1k 80 82 69 2k 77 79 61 4k 72 74 66 8k 65 67 54

Measurement point: 1,95 m/s; 911 Pa

121

Roof fans
DHS Also possible for DVS, DVN and DVC VKS Automatic shutter DVS/DVSI Also possible for DHS, DVN and DVC DVS/DVSI Also possible for DHS, DVN and DVC

Roof fans

SSD Socket silencer

VKM Motor driven shutter ASS Flexible connection ASF Inlet flange

FTG Tilting device TDA Adapter frame VKS Automatic shutter ASS Flexible connection ASF Inlet flange FDS Flat roof socket

ASK Inflow chamber ASS Flexible connection DVN/DVNI ASF Inlet flange VKS Automatic shutter SSD Socket silencer

FDS Flat roof socket

FTG Tilting device TDA Adapter frame VKM Motor driven shutter

ASK Inflow chamber VKS Automatic shutter ASS Flexible connection ASF Inlet flange

FDS Flat roof socket

120C

200C

IE2
2009/640/EG

General
Systemair roof fans have been developed for the use in effective exhaust air systems. Ranges DVS/DVSI/DHS/DVN/ DVNI/DVC are equipped with a sea water resistant aluminium casing. The integrated bird screen is manufactured from galvanized and powder coated steel. The impellers are manufactured either from compound material or from aluminium. Range TFSR/TFSK has a casing manufactured from galvanized steel, powder coated in black. The units are supplied with cord and plug.

Systemair range
Systemair roof fans are available for vertical discharge (ranges DVS, DVSI, DVC, DVN and DVNI up to size 900) and for horizontal discharge (ranges TFSR/TFSK and DHS up to size 710). The vertical discharge units are also available with sound insulated casing, having a 50 mm insulation (density 60 kg/m3). All of Systemair roof fans are equipped with self-cleaning impellers with backward curved blades. A comprehensive range of easy to install accessories is available.

Motors
Systemair roof fans DVS/DVSI/DHS and TFSR/TFSK are equipped with external rotor motors, speed controllable by voltage. DVN is driven by IEC standard motors in efficiency class IE2 as per guideline 2009/640/EC. DVEX have ATEX-certified external rotor motors (see Explosion proof fans page 188-223). DVC is equipped with electronically commutated EC-motor, either with automatic speed control by pressure (integrated pressure sensor) or with manual speed control by an external 0-10V signal. Most of the roof fans are equipped with thermal contacts or cold conductors for motor protection. DVS/DHS/DVN from size 355 have to be connected to an external motor protection unit.

122 122

Roof fans

TFSR/TFSK EC. . . . . . . . . . . 124 Roof fan with EC-motor, swing out: up to 0.39 m3/s, 1 phase.

DHS/DVS/DVSI . . . . . . . . . . 146 Roof fans: up to 4.00 m3/s, backward curved impeller, 1 and 3 phase. DVSI insulated version.

TFSR/TFSK . . . . . . . . . . . . . 126 Roof fans, swing out: up to 0.39 m3/s, backward curved impeller, 1 phase.

DVN/DVNI. . . . . . . . . . . . . . 152 Roof fans: up to 8.75 m3/s, backward curved impeller, 1 and 3 phase. DVNI insulated version.

IE2
2009/640/EG

120C

Roof fans

DHA sileo . . . . . . . . . . . . . . 130 Supply air roof fan: up to 4.4 m3/s, 1 and 3 phase, axial impeller.

DVV. . . . . . . . . . . . . . . . . . . 158 Roof fans: up to 15.20 m3/s, backward curved impeller, 3 phase. DVVI insulated version.

IE2
2009/640/EG

120C

DVC/DVCI . . . . . . . . . . . . . . 132 Roof fan with EC-motor: up to 3.8 m3/s, 1 and 3 phase. DVCI insulated version.

ZRS . . . . . . . . . . . . . . . . . . . 164 Flue gas roof fans: up to 0.14 m3/s, 1 phase.

DHS/DVS/DVSI sileo. . . . . . 138 Roof fans: up to 4.00 m3/s, 1 and 3 phase. DVSI insulated version. New generation of backward curved sileo impellers with extremely low noise level from size 400 up to 630.

200C

123 123

Roof fans TFSR/TFSK EC


High efficiency EC-motors 100% speed controllable Swing-out The TFSR EC and TFSK EC roof mounted fans are driven by EC motors and intended for use as extract fans in smaller premises such as self contained flats and apartments as well as storage areas, smaller workrooms etc. EC-technology is intelligent technology, using integral electronic control to ensure that the motor always runs at optimal load and guarantees that the energy utilized effectively is many times higher for EC motors compared with AC motors. The fans are delivered with a pre-wired potentiometer (0-10V) that allows you to easily find the desired working point. The isolation switch is integrated and there are several alternative roof curbs available as accessories. The tilting mechanism simplifies cleaning and maintenance. To protect the motor from overheating, the fans have integrated thermal contact with automatic reset. TFSR EC comes with circular connection whilst the TFSK EC is provided with a square connection. The horizontal discharge creates smaller internal pressure losses and prevents accumulation of ice on the roof. The protection guard prevents unintentional contact with the impeller. Both models are delivered with a connection box. TFSR is delivered with a spigot connection if the installation requires direct duct connection. TFSR 125-160 are delivered with a 160 spigot and TFSR 200-315 with a 200. The spigot is not pre-assembled to the fan. MTP 10 p. 341 Electrical accessories

CXE/AV p. 323

EC-vent p. 329-330

Roof fans

Technical data
TFSR/TFSK Art no Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 4m/10 m Weight Insulation class, motor Enclosure class, motor Speed control, electronic Wiring diagram p. 391-400 160 EC 1226/1223 V/50/60 Hz 230 1~ W 81.5 A 0.64 m3/s 0.161 min-1 3162 C 45 C 45 dB(A) 43 kg 4.2/4.6 B IP 44 MTP 10 41 200 EC 1227/1224 230 1~ 74.6 0.587 0.216 2501 45 45 43 5.4/6.2 B IP 44 MTP 10 41

124

Roof fans
Dimensions Ventilation accessories
C

TOB p. 372
A
A B

HC D

E c/c F

LDC p. 348

9(4x)

36

RSK p. 355

Roof fans

TFSR 160 EC 200 EC

A 147 150

B 172 187

C 334 364

D 380 439

HC 205 250

TFSK 160 EC 200 EC

A 147 150

B 172 187

C 334 364

E 421 421

c/cF 330 330

HC= Hole diameter for fixing, 6x4

Performance

dB(A) LwA Inlet LwA Outlet

Tot 63 79 74 52 37 125 77 61

Frequency bands [Hz] 250 72 58 500 70 68 1k 69 70 2k 66 68 4k 62 63 8k 50 54

dB(A) LwA Inlet LwA Outlet

Tot 63 74 74 49 27 125 66 61

Frequency bands [Hz] 250 66 62 500 68 69 1k 68 69 2k 61 67 4k 57 61 8k 46 49

Measurement point: 0,0511 m/s; 478 Pa

Measurement point: 0,0992 m/s; 294 Pa

125

Roof fans TFSR/TFSK


The TFSR/TFSK roof fans are fitted with a single-inlet centrifugal fan with backward-curved blades and external rotor motors. The motors can be tilted outwards to facilitate inspection and service. They have integral on/off switch and are supplied with 1 m cable. TFSR has circular connection. Cable for fast connection to the mains e.g. via the connection box on the roof curb TOB or TOS. TFSR is delivered with a spigot connection if the installation requires direct duct connection. TFSR 125-160 are delivered with a 160 spigot and TFSR 200315 with a 200. The spigot is not pre-assembled to the fan. TFSK has square connection, the cable is easily connected to our standard roof curbs TG, FDS and SSD. These fans are suitable for exhaust-air ventilation systems, e.g. single and multiple dwellings, offices and day nurseries. To protect the motors from overheating, all motors have an integral thermal contact with automatic reset. The fans are manufactured in powder-coated, galvanized sheet steel and are available in standard powder coat black finish. Electrical accessories

RE p. 320

REU p. 320

REE p. 321

Roof fans

Quick selection

1 2 3 4 5 6

TFSK 125M TFSK 125XL TFSK 160 TFSR 200 TFSR 315M TFSR 315L

2 3

Technical data
TFSR/TFSK Art no. TFSK 125M, 160, 200, 315M are suitable for 60Hz Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 4m/10m Weight Insulation class, motor Enclosure class, motor Capacitor Motor protection Speed control, five step Speed control, five step high/low Speed control, stepless Wiring diagram p. 391-400 V/50 Hz 230 1~ W 24.8 A 0.13 m3/s 0.086 min-1 1965 C 70 C 70 dB(A) 23 kg 2.5 B IP 44 F 1.5 Aut. th. cont. Transf. RE 1,5 Transf. REU 1,5 Thyristor REE 1 29 230 1~ 53.9 0.26 0.106 2531 40 40 33 2.5/3.3 F IP 44 1.5 Aut. th. cont. RE 1,5 REU 1,5 REE 1 29 230 1~ 58.3 0.26 0.121 2461 70 70 36 3.3 B IP 44 2 Aut. th. cont. RE 1,5 REU 1,5 REE 1 29 230 1~ 108 0.47 0.208 2537 62 62 40 4.2 B IP 44 3 Aut. th. cont. RE 1,5 REU 1,5 REE 1 29 230 1~ 195 0.87 0.313 2628 47 47 46 8.0/9.7 F IP 44 5 Aut. th. cont. RE 1,5 REU 1,5 REE 1 29 50 Hz 230 1~ 329 1.43 0.444 2401 42 38 53 9.1/10.7 F IP 44 8 Aut. th. cont. RE 1,5 REU 1,5 REE 2 29 125 M 1330/1344 125 XL 1332/1346 160 1333/1348 200 1334/1349 315 M 1336/1350 315 L 1343/1352

126

6526, 6558, 6427, 6424, 7696, 7691

Roof fans
Dimensions
c/c F

Ventilation G (4x) accessories

TOB p. 372

36

HC D

TG p. 373
c/c F C G (4x)

LDC p. 348

Roof fans

36 E

RSK p. 355

FDS p. 374
TFSR 125 M/XL 160 200 315 M/L A 119 120 123 160 B 144 145 160 206 C 284 334 364 404 D 315 380 439 485 HC 205 205 250 250 TFSK 125 M/XL 160 200 315 M/L A 119 120 123 160 B 144 145 160 206 C 284 334 364 404 E 321 421 421 521 c/cF 245 330 330 450 G 9 9 9 11

HC= Hole diameter for fixing, 6x4

SSD p. 374

127

Roof fans
Performance

Roof fans

dB(A)
LwA Inlet LwA Outlet

Tot 63 58 54 38 20 125 50 41

Frequency bands [Hz] 250 52 45 500 51 47 1k 50 50 2k 49 49 4k 32 37 8k 23 25

dB(A)
LwA Inlet LwA Outlet

Tot 63 68 64 47 27 125 60 46

Frequency bands [Hz] 250 63 51 500 58 53 1k 62 60 2k 57 60 4k 49 50 8k 37 37

Measurement point: 0,0458 m/s; 83,1 Pa

Measurement point: 0,0589 m/s; 151 Pa

dB(A)
LwA Inlet LwA Outlet

Tot 63 68 67 50 26 125 63 53

Frequency bands [Hz] 250 63 55 500 61 58 1k 61 62 2k 58 62 4k 49 54 8k 38 48

dB(A)
LwA Inlet LwA Outlet

Tot 63 71 71 50 31 125 62 52

Frequency bands [Hz] 250 64 56 500 64 61 1k 66 67 2k 63 67 4k 56 61 8k 47 49

Measurement point: 0,0556 m/s; 237 Pa

Measurement point: 0,105 m/s; 280 Pa

128

Roof fans

Roof fans

dB(A)
LwA Inlet LwA Outlet

Tot 63 74 77 49 29 125 65 57

Frequency bands [Hz] 250 64 61 500 70 71 1k 69 73 2k 62 70 4k 57 60 8k 46 48

dB(A)
LwA Inlet LwA Outlet

Tot 63 78 84 51 37 125 70 62

Frequency bands [Hz] 250 68 65 500 75 82 1k 71 79 2k 67 73 4k 63 64 8k 54 57

Measurement point: 0,176 m/s; 367 Pa

Measurement point: 0,219 m/s; 454 Pa

129

Roof fans DHA sileo


Roof fan for supply air Casing and base frame manufactured from galvanized steel, powder coated RAL 7010; cowl manufactured from seawater resistant aluminium. With external rotor motors, speed controllable by reducing voltage with thyristor or transformer. Three phase version to can be switched between D/Y connection for two speeds. Motor protection via integral thermal contacts with external leads for connection to a motor protection switch. Inlet protection guard Size 400: The axial impeller is manufactured from black high efficiency composite material. Size 500-630: The axial impeller is manufactured from pressure die cast aluminium and is powder coated in black. Dimensions DHA 400 DHA 500/630
830
C

Electrical accessories

S-ET/STDT p. 341-342

RTRE p. 320

REU p. 320

Roof fans

398,95 225

RTRD p. 321
4xG D E A

4x d10 450 595

216,5

RTRDU p. 321
E G

DHA 500 630 * inside

A 1100 1282

B 434 481.5

C 240 240

D 535 750

665* 4xd12 939* 4xd14

REE p. 321

S-DT2 SKT p. 340 Technical data


DHA sileo Art no. Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air Sound pressure level at 4 m/10 m Weight Insulation class, motor Enclosure class, motor Capacitor Motor protection Speed control, five step Speed control, five step high/low Speed control, two step, 400V D/Y Speed control, stepless Wiring diagram p. 391-400 ** + S-ET 10 400DV 34501 V/50/60 Hz 400 3~ W 230 A 0.44 m3/s 0.9 min-1 1370 C 70 dB(A) 40 kg 18 F IP 54 F STDT 16 Transformer RTRD 2 Transformer RTRDU 2 S-DT2 SKT Thyristor 18 400E4 34500 230 1~ 240 1.1 0.9 1350 65 40 18 F IP 54 5 S-ET 10 RTRE 1.5 REU 1.5** REE 1** 6a 500DV 34503 400 3~ 770 1.7 2.3 1300 70 50 35 F IP 54 STDT 16 RTRD 2 RTRDU 2 S-DT2 SKT 18 500E4 34502 230 1~ 750 3.35 2.3 1230 70 50 35 F IP 54 16 S-ET 10 RTRE 5 REU 5** REE 4** 6a 630DV 31492 400 3~ 1900 3.2 4.44 1320 60 67/59 39 F IP54 STDT 16 RTRD 4 RTRDU 4 S-DT2 SKT 18 630DS 34505 400 3~ 630 1.25 2.8 900 70 43 51 F IP 54 STDT 16 RTRD 2 RTRDU 2 S-DT2 SKT 18 630E6 34504 230 1~ 730 3.4 2.7 910 70 50 51 F IP 54 16 S-ET 10 RTRE 3 REU 3** 6a

130

Roof fans
Performance
1000 120 2000 3000

Ventilation accessories
2000 160 4000 6000 8000 10000 12000

DHA 400
100
75

DHA 500
130
81

FDS p. 374

80

104

60 5 4 3 20 1 0,28 0,56 0,83 2

78

40

52

26 1 0,55 1,10 2 1,7 3 4 5 2,22 2,78 3,3

dB(A) 400DV LwA Inlet LwA Outlet 400E4 LwA Inlet LwA Outlet

Tot 63 69 69 49 47 125 57 56

Frequency bands [Hz] 250 58 60 500 61 61 1k 63 65 2k 63 63 4k 58 58 8k

dB(A) 500DV 50 48 LwA Inlet LwA Outlet 500E4

Tot 63 71 70 43 45 125 53 53

Frequency bands [Hz] 250 55 59 500 60 62 1k 66 65 2k 67 66 4k 62 61 8k 53 52

Roof fans

Measurement point: 0.678 m/s; 95.8 Pa 68 69 48 46 56 56 59 60 60 61 63 65 62 63 57 57 50 48

Measurement point: 1,76 m/s; 122 Pa LwA Inlet LwA Outlet 72 72 45 45 59 60 59 60 60 61 67 67 69 68 62 61 51 51

Measurement point: 0.693 m/s; 90.4 Pa

Measurement point: 1.61 m/s; 123 Pa

81

dB(A)

Tot 63 125

Frequency bands [Hz] 250 500 1k 2k 4k 8k

dB(A)

Tot 63 125

Frequency bands [Hz] 250 500 1k 2k 4k 8k

630DV LwA Inlet/Outlet 90 81 82 83 83 82 80 76 72

630DV LwA Inlet LwA Outlet 71 71 50 50 54 54 58 58 63 63 67 67 66 65 60 60 53 52

Measurement point: 2,4 m/s; 150 Pa 630DS/E6 LwA Inlet/Outlet 81 72 73 74 74 73 71 67 63

Measurement point: 1.8 m/s; 111 Pa 630DS/E6 LwA Inlet LwA Outlet 73 74 48 49 55 56 65 67 65 68 68 70 68 65 61 60 53 53

Measurement point: 2,0 m/s; 60 Pa

Measurement point: 1.96 m/s; 102 Pa

131

Roof fans DVC/DVCI


100% speed controllable Integrated motor protection Low noise level Safe and maintenance free operation Energy-saving Electrical accessories

REV p. 340

Roof fans

The DVC roof fans are driven by EC-external rotor motors, so called energy saving motors with high efficiency. The input voltage for single phase units can vary between 200 and 277V, for three phase units between 380 and 480V. All motors are suitable for 50Hz and 60Hz and from size 355 up to 630 suspended on effective vibration dampers. Motor protection is integrated in the electronics of the motor, no additional external motor protection device is needed. The DVC-P versions have integrated pressure sensors and the electronics are programmed for a pressure constant operation. Two potentiometers in the electronics allow for 2 set values (day/night), one additional contact for an external setting. Casing from seawater-resistant aluminum. Backward curved impellers manufactured from polyamide PA 6 for size 190 and 315. From 355 up to 630 impellers manufactured from seawater resistant aluminium. Quick selection

MTP 10 p. 341

MTV 1/010 p. 341

EC-vent p. 329-330

6371, 5835, 5828, 5837, 7231

1 2 3 4 5

DVC/DVCI 225 DVC/DVCI 315 DVC/DVCI 355 DVC/DVCI 400 DVC/DVCI 450 PK/SK

1 2 3 4

DVC/DVCI 450 DVC/DVCI 500 DVC/DVCI 560 DVC/DVCI 630

3 4

1 2

Technical data
DVC/DVCI Art no. DVC-P/DVC-S Art no. DVC-P+REV/DVC-S +REV Art no. DVCI-P/DVCI-S Art no. DVC-P+REV/DVCI-S +REV Voltage/Frequency Fan power consumption (P1) Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 4 m/10 m, DVC Sound pressure level at 4 m/10 m, DVCI Weight, DVC/DVCI Insulation class, motor Enclosure class, motor Speed control, electronic Wiring diagram p. 391-400 225-P/225-S Tech. data is relating to DVC-S 30690/30667 30691/30725 30701/30693 30717/30709 V/50/60 Hz 230 1~ W 166 A 1.17 m3/s 0.261 min-1 3278 C 60 C 60 dB(A) 58/51 dB(A) 53/45 kg 8/13 B IP 44 MTP 10 23b/24 315-P/315-S 30634/30619 30684/30585 30702/30694 30718/30710 230 1~ 173 1.18 0.546 1867 60 60 47/39 41/33 11/16 B IP 44 MTP 10 23b/24 355-P/355-S 30635/30620 30692/30621 30703/30695 30719/30711 230 1~ 378 2.31 0.918 1657 60 60 50/42 46/38 25/30 B IP 44 MTP 10 23b/24 400-P/400-S 30682/30622 30685/30623 30704/30696 30720/30712 230 1~ 381 2.30 1.00 1348 60 60 49/41 43/35 29/34 B IP 44 MTP 10 23b/24 450-PK/450-SK 31327/31427 33195/32744 230 1~ 614 2.79 1.43 1300 60 60 53/45 40/32 45/38 B IP 54 MTP 10 28/25

132

5966, 5969, 5977, 5974

Roof fans
Dimensions
A B

Ventilation accessories
F G H M20x1,5

SSD p. 374
D

I(4x)
D E

FDS p. 374

ASK p. 380
DVC/DVCI 190-225 315 355-400 450-500 A B C 330 D 285 E 335 435 595 665 F 245 330 450 535 G 105 146 200 237 H 6xM6 6xM6 6xM8 6xM8 I 10(4x) 10(4x) 12(4x) 12(4x) 370/497 295 560/690 470 720/874 618 170/179 213 390/439 438

900/968 730/748 465/479 438

VKS p. 380

Roof fans

ASS p. 381 DVC 560-630


1150/1315 8xM8 560/600
05

750 293 M20x1,5

ASF p. 375

30

605 939

14(4x)

DVC Art no. DVC-P/DVC-S Art no. DVC-P + REV/DVC-S + REV Art no. DVCI-P/DVCI-S Art no. DVCI-P + REV/DVCI-S + REV Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 4/10 m, DVC Sound pressure level at 4/10 m, DVCI Weight, DVC/DVCI Insulation class, motor Enclosure class, motor Speed control, electronic Wiring diagram p. 391-400

450-P/450-S Tech. data is relating to DVC-S 30683/30626 30686/30627 30705/30697 30721/30713 V/50/60 Hz 400 3~ W 1048 A 1.79 m3/s 1.70 min-1 1558 C 60 C 60 dB(A) 51/48 dB(A) 50/42 kg 45/43 B IP 54 MTP 10 26/27

293

500-P/500-S 30679/30628 30687/30629 30706/30698 30722/30714 400 3~ 984 1.66 1.84 1339 60 60 55/47 51/43 49/57 B IP 54 MTP 10 26/27

560-P/560-S 30680/30630 30688/30631 30707/30699 30723/30715 400 3~ 1873 2.88 2.99 1359 60 60 63/55 55/47 58/70 F IP 54 MTP 10 26/27

630-P/630-S 30681/30632 30689/30633 30708/30700 30724/30716 400 3~ 2444 3.72 3.59 1209 60 60 64/56 57/49 85/65 F IP 54 MTP 10 26/27

133

Roof fans
Performance

Roof fans

----- = only S-version


dB(A) LwA Inlet With SSD LwA Inlet 70 41 59 63 65 64 61 56 49 Measurement point: 0,13 m/s; 448 Pa Tot 63 78 44 45 LwA Surrounding 82 125 58 58 Frequency bands [Hz] 250 64 62 500 74 77 1k 72 74 2k 72 77 4k 70 73 8k 60 63 LwA Inlet LwA Surrounding With SSD LwA Inlet 60 31 49 53 55 54 51 46 39 Measurement point: 0,28 m/s; 243 Pa 67 70 dB(A) Tot 63 41 42 125 56 57 Frequency bands [Hz] 250 59 60 500 63 67 1k 59 64 2k 55 59 4k 54 56 8k 49 49

----- = only S-version


dB(A) LwA Inlet LwA Surrounding With SSD LwA Inlet 64 35 53 57 59 58 55 50 43 Measurement point: 0,54 m/s; 378 Pa Tot 63 71 73 37 38 125 65 60 Frequency bands [Hz] 250 62 66 500 65 68 1k 63 67 2k 62 65 4k 60 62 8k 56 56 LwA Inlet LwA Outlet With SSD LwA Inlet 63 34 52 56 58 57 54 49 42 Measurement point: 0,748 m/s; 210 Pa 70 72 dB(A) Tot 63 40 40 125 59 56 Frequency bands [Hz] 250 67 67 500 67 67 1k 60 64 2k 59 62 4k 60 61 8k 59 56

134

Roof fans

Roof fans

----- = only S-version


dB(A) LwA Inlet LwA Surrounding With SSD LwA Inlet 64 58 58 58 56 48 40 38 36 Measurement point: 0,56 m/s; 450 Pa Tot 63 74 76 61 63 125 63 65 Frequency bands [Hz] 250 67 69 500 69 71 1k 68 70 2k 65 67 4k 60 62 8k 53 55 LwA Inlet With SSD LwA Inlet 70 41 59 63 65 64 61 56 49 Measurement point: 1,01 m/s; 566 Pa 77 LwA Surrounding 78 dB(A) Tot 63 43 47 125 63 64 Frequency bands [Hz] 250 70 71 500 70 73 1k 65 70 2k 67 69 4k 71 71 8k 69 68

----- = only S-version


dB(A) LwA Inlet LwA Surrounding With SSD LwA Inlet 70 41 59 63 65 64 61 56 49 Measurement point: 0,99 m/s; 503 Pa Tot 63 77 78 40 42 125 64 63 Frequency bands [Hz] 250 75 72 500 69 73 1k 66 70 2k 65 68 4k 64 67 8k 61 61 LwA Inlet dB(A)

----- = only S-version


Tot 63 81 86 75 48 53 46 LwA Surrounding With SSD LwA Inlet 64 68 70 69 66 61 54 Measurement point: 1,66 m/s; 630 Pa 125 70 74 Frequency bands [Hz] 250 71 78 500 73 80 1k 69 77 2k 75 78 4k 77 80 8k 69 71

135

Roof fans

Roof fans

----- = only S-version


dB(A) LwA Inlet LwA Surrounding With SSD LwA Inlet 76 47 65 69 71 70 67 62 55 Measurement point: 1,83 m/s; 713 Pa Tot 63 82 87 47 52 125 74 77 Frequency bands [Hz] 250 78 77 500 75 81 1k 69 78 2k 71 78 4k 74 80 8k 67 70

136

Roof fans Sileo version of roof fans DHS, DVS, DVSI

Roof fans

A completely new generation of modern Systemair roof fans which were developed and built consistently according to the companys set target: low noise level, high performance. Especially suited to all uses and areas of application sensitive to noise. You can see and hear the result: a reduction in sound of up to 50 % at the same system performance and an increased level of efficiency compared to its predecessors.

137

Roof fans DHS/DVS/DVSI sileo


DHS Available from sizes 400 up to 630 High efficiency Speed-controllable Integral thermal contacts Excellent sound level Extensive range of accessories Maintenance-free and reliable ElectrIcal accessories

S-ET/STDT p. 341-342

DVS

DVSI DHS with horizontal outlet. DVS with vertical outlet. DVSI has a 50 mm mineral wool insulation for lower noise levels.

The DVS/DHS/DVSI sileo, in sizes from 400 up to 630, is well suited for applications requiring high air volumes at medium pressure and very low noise levels. These models have 3D profiled impellers with backward curved blades and external rotor motors. All motors are speed controllable by voltage. For speed controlling of the DVS/DHS/DVSI sileo roof fans with a frequency converter,an all pole sine filter is required. The motors are suspended on effective vibration dampers. DVS/DHS/DVSI ...E4 / E6: 1~ motor DVS/DHS/DVSI ...DV / DS: 3~ with Y/D-connection for 2-speeds To protect the motors from overheating the sileo range motors are equipped with thermal contacts with external leads for connection to a motor protection device. The casing is made from aluminum and the base frame from hot-dip galvanized steel. Suitable for coastal applications. The impellers of the sileo types are manufactured from high-performance composite material with highly efficient 3D fan blade profile technology.

RTRE p. 320

Roof fans

RTRD/RTRDU p. 321

REU p. 320

REE p. 321

S2S 160 p. 340

Technical data
DHS/DVS/DVSI Art no. DHS Art no. DVS; tech. data is relating to DVS Art no. DVSI Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level DVS* Weight Insulation class, motor Enclosure class, motor Capacitor Wiring diagram p. 391-400 * at 4/10 m. DHS +2 dB, DVSI -9 dB 400DS 33348 33316 33332 V/50 Hz 400 3~ W 129 A 0.255 m3/s 0.684 min-1 797 C 60 C 60 dB(A) 33/25 kg 25/25/31 F IP 54 F 18 400DV 33347 33315 33331 400 3~ 209 0.564 1.11 1436 60 60 46/38 27/28/33 F IP 54 18 400E4 33349 33317 33333 230 1~ 466 2.25 1.1 1324 60 60 46/38 27/29/33 F IP 54 10 6 400E6 33350 33318 33334 230 1~ 169 0.84 0.739 890 60 60 37/29 27/27/33 F IP 54 5 6 450DV 33351 33319 33335 400 3~ 667 1.32 1.44 1238 60 60 49/41 39/39/45 F IP 54 18 450E4 33352 33320 33336 230 1~ 665 2.93 1.4 1259 60 60 49/41 39/41/45 F IP 54 16 6 450E6 33353 33321 33337 230 1~ 241 1.05 0.979 863 60 60 40/32 39/39/45 F IP 54 8 6

S-DT2 SKT p. 340


499DV 33354 33322 33338 400 3~ 907 1.7 1.82 1125 60 60 51/43 43/42/47 F IP 54 18

138

Roof fans
Dimensions DVS/DVSI
A B

DHS 400-499
J

DHS/DVS/DVSI bottom view


F G M20x1,5

Ventilation accessories

H G

SSD p. 374

D E

I(4x)

FDS p. 374

D E

DHS 560-630
J

ASK p. 380
K L

D E

Roof fans

DHS sileo 400E4/E6/DV/DS 450E4/499DV/500DV/DS/E6 560DV/DS/630DV/DS DVS sileo 400E4/E6/DV/DS 450E4/499DV/500DV/DS/E6 560DV/DS/630DV/DS DVSI sileo 400E4/E6/DV/DS 450E4/499DV/500DV/DS/E6 560DV/DS/630DV/DS

A A 720 900 1150 A 874 968 1315

B B 618 730 B 618 748

C C 390 465 560 C 439 479 600

D 438 438 605 D 438 438 605 D 438 438 605

E 595 665 939 E 595 665 939 E 595 665 939

F 450 535 750 F 450 535 750 F 450 535 750

G 200 237 293 G 200 237 293 G 200 237 293

H 6xM8 6xM8 8xM8 H 6xM8 6xM8 8xM8 H 6xM8 6xM8 8xM8

I 12 12 14 I 12 12 14 I 12 12 14

J 720 830 1100 J J

K 330 490 535 K K

L 30 30 30 L L

VKS p. 380

ASS p. 381

ASF p. 375

139

Roof fans
Quick selection

9487, 9467, 9515, 9504, 9316, 9204, 9326

1 2 3 4 5

DHS/DVS/DVSI sileo 400DS DHS/DVS/DVSI sileo 400DV,450E4 DHS/DVS/DVS sileo 400E6 DHS/DVS/DVS sileo 450DV DHS/DVS/DVS sileo 450E4

1 2 3 4 5

DHS/DVS/DVSI sileo 450E6 DHS/DVS/DVSI sileo 499DV DHS/DVS/DVSI sileo 500DV DHS/DVS/DVSI sileo 500DS DHS/DVS/DVSI sileo 500E6

5
5

Roof fans

1 2 3 4

DHS/DVS/DVSI sileo 560DV DHS/DVS/DVSI sileo 560DS DHS/DVS/DVSI sileo 630DV DHS/DVS/DVSI sileo 630DS

DHS/DVS/DVSI Art no. DHS Art no. DVS Tech. data is relating to DVS Art no. DVSI Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level DVS* Weight Insulation class, motor Enclosure class, motor Capacitor Wiring diagram p. 391-400 * at 4/10 m. DHS +2 dB, DVSI -9 dB

500DV 33356 33324 33340 V/50 Hz 400 3~ W 1241 A 2.24 m3/s 2.08 min-1 1337 C 60 C 60 dB(A) 53/45 kg 41/46/57 F IP 54 F 18

500DS 33357 33325 33341 400 3~ 428 0.931 1.34 860 60 60 42/34 41/49/57 F IP 54 18

10910, 10815, 10803, 10827

500E6 33358 33326 33342 230 1~ 380 1.67 1.32 841 60 60 40/32 41/41/57 F IP 54 12 6

560DV 33359 33327 33343 400 3~ 1767 3.29 2.82 1195 55 55 54/46 58/58/70 F IP 54 18

560DS 33360 33328 33344 400 3~ 597 1.03 1.91 820 40 40 52/44 47/47/59 F IP 54 18

630DV 33361 33329 33345 400 3~ 3870 6.47 3.98 1361 50 50 68/60 85/85/99 F IP 54 18

9326, 9528, 9538, 9462, 9544

630DS 33362 33330 33346 400 3~ 1110 2.2 3.00 846 60 60 56/48 65/65/79 F IP 54 18

140

Roof fans
sPEED CONTROL
DHS/DVS/DVSI sileo 400E4, 450E6, 500E6 400E6 450E4 400DV/DS, 499DV, 500DS, 560DS 500DV, 560DV 630DV + motor protection S-ET 10/STDT 16 Transformer Five step RTRE 3 RTRE 1.5 RTRE 5 RTRD 2 RTRD 4 RTRD 14 Transformer Five step high/low REU 3* REU 1.5* REU 5* RTRDU 2* RTRDU 4* Electronic Two step S-DT2SKT S-DT2SKT S-DT2SKT Thyristor Stepless REE 2 REE 1 REE 4

Roof fans

141

Roof fans
pERFORMANCE

DHS/DVS/DVSI sileo 400DS

DHS/DVS/DVSI sileo 400DV

Roof fans

dB(A) LwA Inlet LwA Surrounding DVSI LwA Surrounding With SSD LwA Inlet

Tot 63 56 56 47 45 45 35 26 35 125 49 43 34 39

Frequency bands [Hz] 250 48 53 44 38 500 50 49 40 40 1k 47 48 39 37 2k 42 43 34 32 4k 42 43 34 32 8k 27 28 19 17

dB(A) LwA Inlet LwA Surrounding DVSI LwA Surrounding With SSD LwA Inlet

Tot 63 73 73 64 62 49 50 41 39 125 69 71 62 59

Frequency bands [Hz] 250 68 65 56 58 500 64 65 56 54 1k 58 63 54 48 2k 55 58 49 45 4k 50 52 43 40 8k 48 50 41 38

Measurement point: 0,349 m/s; 112 Pa

Measurement point: 0,66 m/s; 286 Pa

DHS, DVS, DVSI sileo 400E4

DHS/DVS/DVSI sileo 400E6

dB(A) LwA Inlet LwA Surrounding DVSI LwA Surrounding With SSD LwA Inlet

Tot 63 67 69 60 57 37 38 29 27 125 59 58 49 49

Frequency bands [Hz] 250 63 62 53 53 500 62 64 55 52 1k 57 62 53 47 2k 55 58 49 45 4k 51 53 44 41 8k 52 51 42 42

dB(A) LwA Inlet LwA Surrounding DVSI LwA Surrounding With SSD LwA Inlet

Tot 63 57 61 52 47 37 45 36 27 125 51 54 45 41

Frequency bands [Hz] 250 51 55 46 41 500 53 55 46 43 1k 46 52 43 36 2k 42 47 38 32 4k 40 44 35 30 8k 29 34 25 19

Measurement point: 0,662 m/s; 279 Pa

Measurement point: 0,404 m/s; 137 Pa

142

Roof fans

DHS/DVS/DVSI sileo 450DV

DHS/DVS/DVSI sileo 450E4

Roof fans

dB(A) LwA Inlet LwA Surrounding DVSI LwA Surrounding With SSD LwA Inlet

Tot 63 67 71 62 57 41 41 32 31 125 58 56 47 48

Frequency bands [Hz] 250 61 63 54 51 500 62 67 58 52 1k 58 65 56 48 2k 56 60 51 46 4k 53 55 46 43 8k 53 52 43 43

dB(A) LwA Inlet LwA Surrounding DVSI LwA Surrounding With SSD LwA Inlet

Tot 63 70 73 64 60 43 48 39 33 125 57 59 50 47

Frequency bands [Hz] 250 65 68 59 55 500 64 68 59 54 1k 61 67 58 51 2k 59 62 53 49 4k 57 56 47 47 8k 54 51 42 44

Measurement point: 0,843 m/s; 311 Pa

Measurement point: 0,833 m/s; 308 Pa

DHS/DVS/DVSI sileo 450E6

DHS/DVS/DVSI sileo 499DV

dB(A) LwA Inlet LwA Surrounding DVSI LwA Surrounding With SSD LwA Inlet

Tot 63 58 63 54 48 38 39 30 28 125 46 50 41 36

Frequency bands [Hz] 250 54 59 50 44 500 54 60 51 44 1k 49 55 46 39 2k 47 50 41 37 4k 45 45 36 35 8k 36 34 25 26

dB(A) LwA Inlet LwA Surrounding DVSI LwA Surrounding With SSD LwA Inlet

Tot 63 70 73 64 58 43 49 40 38 125 60 61 51 46

Frequency bands [Hz] 250 65 67 60 54 500 67 69 61 54 1k 59 67 56 49 2k 58 62 51 47 4k 54 55 46 45 8k 52 50 35 35

Measurement point: 0,568 m/s; 150 Pa

Measurement point: 1,06 m/s; 314 Pa

143

Roof fans

DHS/DVS/DVSI sileo 500DV

DHS/DVS/DVSI sileo 500DS

Roof fans

dB(A) LwA Inlet LwA Surrounding DVSI LwA Surrounding With SSD LwA Inlet

Tot 63 76 77 73 71 48 47 52 50 125 62 64 64 62

Frequency bands [Hz] 250 73 69 67 65 500 69 73 67 65 1k 66 71 65 63 2k 62 67 61 59 4k 58 61 58 56 8k 56 57 57 55

dB(A) LwA Inlet LwA Surrounding DVSI LwA Surrounding With SSD LwA Inlet

Tot 63 63 65 62 60 47 42 45 43 125 56 51 52 50

Frequency bands [Hz] 250 58 61 59 57 500 57 60 55 53 1k 52 57 53 51 2k 50 53 44 42 4k 47 49 39 37 8k 39 41 35 33

Measurement point: 1,2 m/s; 467 Pa

Measurement point: 0,746 m/s; 195 Pa

DHS/DVS/DVSI 500E6 sileo

DHS/DVS/DVSI sileo 560DV

dB(A) LwA Inlet LwA Surrounding DVSI LwA Surrounding With SSD LwA Inlet

Tot 63 64 63 59 51 43 42 43 41 125 56 49 51 49

Frequency bands [Hz] 250 59 58 55 53 500 59 59 53 51 1k 52 56 49 47 2k 49 51 42 40 4k 45 45 37 35 8k 39 38 31 29

dB(A) LwA Inlet LwA Surrounding DVSI LwA Surrounding With SSD LwA Inlet

Tot 63 74 76 67 65 45 47 60 59 125 63 65 60 58

Frequency bands [Hz] 250 67 69 62 59 500 69 71 60 58 1k 68 70 54 51 2k 65 67 47 44 4k 60 62 45 41 8k 53 55 39 40

Measurement point: 0,696 m/s; 192 Pa

Measurement point: 1,82 m/s; 405 Pa

144

Roof fans

DHS/DVS/DVSI sileo 560DS

DHS/DVS/DVSI sileo 630DV

Roof fans

dB(A) LwA Inlet LwA Surrounding DVSI LwA Surrounding With SSD LwA Inlet

Tot 63 64 66 57 55 35 37 50 44 125 53 55 50 43

Frequency bands [Hz] 250 57 59 53 45 500 59 61 50 43 1k 58 60 45 37 2k 55 57 37 29 4k 50 52 35 26 8k 43 45 28 25

dB(A) LwA Inlet LwA Surrounding DVSI LwA Surrounding With SSD LwA Inlet

Tot 63 83 85 76 74 54 56 69 68 125 72 74 69 67

Frequency bands [Hz] 250 76 78 71 68 500 78 80 69 67 1k 77 79 63 60 2k 74 76 56 53 4k 69 71 54 50 8k 62 64 48 49

Measurement point: 1.18 m/s; 205 Pa

Measurement point: 2.2 m/s; 788 Pa

dB(A) LwA Inlet LwA Surrounding DVSI LwA Surrounding With SSD LwA Inlet

Tot 63 67 69 60 58 38 40 53 52 125 56 58 53 51

Frequency bands [Hz] 250 60 62 56 53 500 62 64 53 51 1k 61 63 48 45 2k 58 60 40 37 4k 53 55 38 34 8k 46 48 31 32

Measurement point: 1.74 m/s; 268 Pa

145

Roof fans DHS/DVS/DVSI


DHS DHS 710 Speed-controllable Integral thermal contacts Low sound level Maintenance-free and reliable S-ET/STDT p. 341-342 ElectrIcal accessories

The DVS/DHS/DVSI models have impellers with backward curved blades and external rotor motors. All motors are speed controllable by voltage. Frequency inverters must have an allpole sine filter. The motors are suspended on effective vibration dampers. DVS/DHS/DVSI...EZ/EV/ES: 1~ motor with connection for 2-speeds DVS/DHS/DVSI...E4:1-speed motor DVS/DHS/DVSI...DV/DS:3~ with Y/D-connection for 2-speeds To protect the motors from overheating the DVS/DHS/DVSI up to size 311 have integral thermal contacts, from size 355 with external leads for connection to a motor protection device. The casing is made from seawater resistant aluminum. Suitable for coastal applications. The impellers are manufactured from high-performance composite material. DVS with outlet vertical DHS with outlet horizontal DVSI with 50 mm mineral wool insulation for low noise level.

RTRE p. 320

DVS

RTRD/RTRDU p. 321

Roof fans

DVSI

REU p. 320 sPEED CONTROL


DHS/DVS/DVSI 190EZ-311ES 355E4 355DV 710DS + motor protection S-ET 10/STDT 16 Transformer Transformer Five step Five step high/low RE 1.5 REU 1.5 RTRE 1.5 REU 1.5* RTRD 2 RTRDU 2* RTRD 7 RTRDU 7* Electronic Two step S2S 160 S-DT2SKT S-DT2SKT Thyristor Stepless REE 1 REE 2

REE p. 321

S2S 160 p. 340

S-DT2 SKT p. 340

Technical data
DHS/DVS/DVSI Art no. DHS Art no. DVSI Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level DVS* Weight Insulation class, motor Enclosure class, motor Capacitor Wiring diagram p. 391-400 * at 4/10 m. DHS +2 dB, DVSI -9 dB 190EZ 5712 30273 V/50 Hz 230 1~ W 80 A 0.36 m3/s 0.155 min-1 2240 C 40 C 40 dB(A) 48/40 kg 5/5/12 B IP 44 F 2 20 225EZ 5713 5731 30275 230 1~ 113 0.5 0.228 2590 40 40 49/41 6/6/14 B IP 44 3 20 225EV 5714 5732 30274 230 1~ 48 0.227 0.142 1422 40 40 41/33 6/6/14 B IP 44 2 20 310EV 5703 5733 2347 230 1~ 116 0.53 0.406 1365 40 40 44/36 13/13/19 B IP 44 4 20 310ES 5704 5734 2350 230 1~ 70 0.30 0.369 1000 40 40 37/29 13/13/19 B IP 44 1.5 20 311EV 5705 5735 2352 230 1~ 135 0.6 0.46 1365 40 40 45/37 13/13/20 B IP 44 5 20 311ES 5715 5736 2381 230 1~ 100 0.38 0.439 940 40 40 38/30 13/13/16 B IP 44 2 20 355E4 5706 5737 2356 230 1~ 279 1.22 0.773 1401 40 40 47/39 25/25/38 B IP 44 8 5 355DV 5707 5710 2354 400 3~ 249 0.58 0.779 1350 40 40 47/39 25/25/37 B IP 44 16 710DS 5729 5752 2378 400 3~ 2475 4.0 4.58 883 40 40 58/50 88/88/104 F IP 54 18 65/57 88/88/104 F IP 54 18 Y 710D6-L 33181 33177 33179 Y400 3~ 2562 4.86 4.12 941 40

Art no. DVS Tech. data is relating to DVS 5730

146

Roof fans
Dimensions DVS/DVSI
A B

DHS 190-355
J

DHS/DVS/DVSI bottom view


F G M20x1,5

Ventilation accessories

H G

SSD p. 374

D E

I(4x)

FDS p. 374

D E

DHS 710
J

ASK p. 380
K L D E

Roof fans

DHS 190EZ, 225EZ/EV 310EV/ES, 311EV/ES 355E4/DV 710DS DVS 190EZ, 225EZ/EV 310EV/ES, 311EV/ES 355E4/DV 710DS DVSI 190EZ, 225EZ/EV 310EV/ES, 311EV/ES 355E4/DV 710DS

A A 370 560 720 1350 A 497 690 874 1483

B B 295 470 618 B 295 470 618

C C 170 330 390 660 C 179 369 439 729

D 213 285 438 647 D 213 285 438 647 D 213 285 438 674

E 335 435 595 1035 E 335 435 595 1035 E 335 435 595 1035

F 245 330 450 840 F 245 330 450 840 F 245 330 450 840

G 105 146 200 320 G 105 146 200 320 G 105 146 200 320

H 6xM6 6xM6 6xM8 8xM8 H 6xM6 6xM6 6xM8 8xM8 H 6xM6 6xM6 6xM8 8xM8

I 10 10 12 14 I 10 10 12 14 I 10 10 12 14

J 417 540 720 1282 J J _

K 150 250 330 580 K K

L 30 30 30 40 L L

VKS p. 380

ASS p. 381

ASF p. 375

Quick selection
5236, none, 5240, 5242, 6717, 8370

5212, 5214, 5218, 5220, 5229

1 2 3 4 5

DHS /DVS/DVSI 190EZ DHS /DVS/DVSI 225EZ DHS /DVS/DVSI 225EV DHS /DVS/DVSI 310EV DHS /DVS/DVSI 310ES

1 2 3 4 5 6

DHS/DVS/DVSI 311EV DHS/DVS/DVSI 311ES DHS/DVS/DVSI 355E4 DHS/DVS/DVSI 355DV DHS/DVS/DVSI 710DS DHS/DVS/DVSI 710DS-L

2 1

147

Roof fans
pERFORMANCE

Roof fans

dB(A) LwA Inlet LwA Surrounding DVSI LwA Surrounding With SSD LwA Inlet

Tot 63 71 72 67 60 42 43 54 40 125 60 61 56 55

Frequency bands [Hz] 250 64 65 60 56 500 66 67 62 55 1k 65 66 61 46 2k 62 63 58 42 4k 57 58 53 37 8k 50 51 46 32

dB(A) LwA Inlet LwA Surrounding DVSI LwA Surrounding With SSD LwA Inlet

Tot 63 71 72 67 60 42 43 54 40 125 60 61 56 55

Frequency bands [Hz] 250 64 65 60 56 500 66 67 62 55 1k 65 66 61 46 2k 62 63 58 42 4k 57 58 53 37 8k 50 51 46 32

Measurement point: 0,07 m/s; 172 Pa

Measurement point: 0,14 m/s; 240 Pa

dB(A) LwA Inlet LwA Surrounding DVSI LwA Surrounding With SSD LwA Inlet

Tot 63 63 64 58 52 34 35 51 32 125 52 53 51 47

Frequency bands [Hz] 250 56 57 53 48 500 58 59 51 47 1k 57 58 45 38 2k 54 55 38 34 4k 49 50 36 29 8k 42 43 30 24

dB(A) LwA Inlet LwA Surrounding DVSI LwA Surrounding With SSD LwA Inlet

Tot 63 65 67 58 55 52 54 51 49 125 54 56 51 49

Frequency bands [Hz] 250 58 60 53 50 500 60 62 51 48 1k 59 61 45 41 2k 56 58 38 35 4k 51 53 36 31 8k 44 46 30 29

Measurement point: 0,07 m/s; 87 Pa

Measurement point: 0,14 m/s; 220 Pa

148

Roof fans

Roof fans

dB(A) LwA Inlet LwA Surrounding DVSI LwA Surrounding With SSD LwA Inlet

Tot 63 58 60 51 49 45 47 44 42 125 47 49 44 42

Frequency bands [Hz] 250 53 54 47 44 500 53 55 44 41 1k 53 55 39 35 2k 49 51 31 28 4k 44 46 29 24 8k 36 38 22 21

dB(A) LwA Inlet LwA Surrounding DVSI LwA Surrounding With SSD LwA Inlet

Tot 63 66 68 59 56 53 55 52 50 125 55 57 52 50

Frequency bands [Hz] 250 59 61 54 51 500 61 63 52 49 1k 60 62 46 42 2k 57 59 39 36 4k 52 54 37 32 8k 45 47 31 30

Measurement point: 0,15 m/s; 84 Pa

Measurement point: 0,28 m/s; 169 Pa

dB(A) LwA Inlet LwA Surrounding DVSI LwA Surrounding With SSD LwA Inlet

Tot 63 59 61 52 50 46 48 45 43 125 48 50 45 48

Frequency bands [Hz] 250 53 55 48 45 500 54 56 45 42 1k 54 56 40 36 2k 50 52 32 29 4k 45 47 30 25 8k 37 39 23 22

dB(A) LwA Inlet LwA Surrounding DVSI LwA Surrounding With SSD LwA Inlet

Tot 63 68 70 61 58 55 57 54 52 125 57 59 54 52

Frequency bands [Hz] 250 61 63 55 53 500 63 65 54 49 1k 62 64 48 43 2k 59 61 41 37 4k 54 56 39 38 8k 47 49 33 32

Measurement point: 0,17 m/s; 137 Pa

Measurement point: 0,45 m/s; 240 Pa

149

Roof fans

DHS/DVS/DVSI 710DS

Roof fans

dB(A) LwA Inlet LwA Surrounding DVSI LwA Surrounding With SSD LwA Inlet

Tot 63 68 70 61 58 55 57 54 52 125 57 59 54 52

Frequency bands [Hz] 250 61 63 56 53 500 63 65 54 49 1k 62 64 48 43 2k 59 61 41 37 4k 54 56 39 38 8k 47 49 33 32

dB(A) LwA Inlet LwA Surrounding DVSI LwA Surrounding With SSD LwA Inlet

Tot 63 79 81 72 69 66 68 65 63 125 68 70 65 62

Frequency bands [Hz] 250 73 75 68 65 500 74 76 65 60 1k 74 76 60 54 2k 70 72 52 45 4k 65 67 50 42 8k 57 59 43 46

Measurement point: 0,45 m/s; 240 Pa

Measurement point: 2,1 m/s; 402 Pa

dB(A) LwA Inlet LwA Surrounding DVSI LwA Surrounding With SSD LwA Inlet

Tot 63 82 88 79 72 66 62 59 63 125 73 69 70 67

Frequency bands [Hz] 250 75 75 71 67 500 75 81 73 61 1k 78 83 71 58 2k 78 83 69 53 4k 75 78 68 52 8k 65 68 61 54

Measurement point: 2,1 m/s; 537 Pa

150

Roof fans Reference

Roof fans

North side

Project: Matrix Type of Building: Commercial office building City/Country: Pune, India Products/Solution: Jet Fans, Axial Fans, Roof Fans, Inline Fans (K) Motorized Fire Dampers with Actuators, Grilles, Louvres, Diffusers, VCDs.w

South side

151

Roof fans DVN/DVNI


Electrical accessories

IE2
2009/640/EG

120C

The casing and impeller with backward-curved blades is manufactured from seawater resistant aluminum. The base frame and the integrated protection guard consist of powder-coated galvanised steel. The motor is suspended on effective vibration dampers. The motors are speed-controllable via transformer or frequency converter. To protect the motor from overheating the fan has integral thermal contacts or PTC with external leads for connection to a motor protection device. The DVNI version has a 50 mm mineral wool insulation for lower sound level.

S-ET/STDT p. 341-342

REU p. 320

RTRDU p. 321

Roof fans

Quick selections

1 2

DVN/DVNI 355E4 DVN/DVNI 355DV

3 4 5 6 7

6803, 6804, 5222, 5226, 9775, 9776, 5307

DVN/DVNI 400E4 DVN/DVNI 400DV DVN/DVNI 450D4 IE2 DVN/DVNI 500D4 IE2 DVN/DVNI 500DS

1 2 3 4 5

DVN/DVNI 560D4 IE2 DVN/DVNI 560D6 IE2 DVN/DVNI 630D4 IE2 DVN/DVNI 630D6 IE2 DVN/DVNI 710D6 IE2

9777, 9778, 9860, 9779, 9780, 8296

FXDM p. 324

S-DT2 SKT p. 340

2 2 1 3 4 7 5 6

FRQ p. 325

Technical data

DVN/DVNI Art no. DVN Tech. data is relating to DVN Art no. DVNI Voltage/Frequency Power at shaft Current Max air flow R.p.m. Max temp. of transported air Sound pressure level at 4 m/10 m* Weight Insulation class, motor Enclosure class, motor Capacitor Motor protection Speed control, five-step Speed control, five step high/low Speed control, two step Speed control, stepless Wiring diagram p. 391-400 * DVNI -9 dB, ** + S-ET 10

355E4 30301 30446 V/50 Hz 230 1~ W 370 A 1.49 m3/s 0.846 min-1 1408 C 120 dB(A) 49/41 kg 27/33 F IP 54 F 12 S-ET 10 RTRE 3 Transformer REU 3** 21

355DV 30278 30313 400 3~ 370 1.20 0.839 1420 120 50/42 26/42 F IP 54 STDT 16 RTRD 2 RTRDU 2 S-DT2SKT FXDM 17

400E4 2630 3909 230 1~ 370 2.00 1.00 1420 120 52/44 33/39 F IP 54 12 S-ET 10 RTRE 3 REU 3** 21

400DV 2631 3396 400 3~ 370 1.37 1.1 1442 120 52/44 33/43 F IP 54 STDT 16 RTRD 2 RTRDU 2 S-DT2SKT FXDM 17

450D4 IE2 32184 33462 400 Y 3~ 750 1.78 1.85 1390 120 53/45 38/46 F IP 55 U-EK230E FRQ5(S)-4A FRQ(S)-4A 13 b Y

500D4 IE2 32185 33463 400 Y 3~ 1500 3.39 2.12 1400 120 56/48 49/57 F IP 55 FRQ5(S)-4A FRQ(S)-4A 13 b Y

500DS 9852 9857 400 3~ 550 1.86 1.41 936 120 47/39 48/55 F IP 54 STDT 16 RTRD 2 RTRDU 2 S-DT2SKT FXDM 20

152

Roof fans
Dimensions
A B

Ventilation accessories
DVN 355-400 450-500 560-630 710 A 720 900 B 618 730 C 600 675 900 936 D 390 465 560 660 E 438 438 605 674 F 595 665 939 1035 G 450 535 750 840 H I J 200 12(4x) 6xM8 237 12(4x) 6xM8 293 14(4x) 8xM8 320 14(4x) 8xM8

1150 955 1350 1178

SSD p. 374

E F G H M20x1,5 J

DVNI 355-400 450-500 560-630 710

A 874 970

B 648 730

C 600 675 900 936

D 439 479 600 729

E 438 438 605 674

F 595 665 939 1035

G 450 535 750 840

FDS p. 374

200 12(4x) 6xM8 237 12(4x) 6xM8 293 14(4x) 8xM8 320 14(4x) 8xM8

1315 1035 1483 1165

ASK p. 380

E
I

VKS p. 380

Roof fans

VKM p. 380

ASS p. 381

ASF p. 375

DVN/DVNI Art no. DVN, Techn. data is relating to DVN Art no. DVNI Voltage/Frequency Power at shaft Current Max air flow R.p.m. Max temp. of transported air Sound pressure level at 4/10 m Weight Insulation class, motor Enclosure class, motor Motor protection Speed control, five-step Speed control, stepless Wiring diagram p. 391-400

560D4 IE2 32187 33465 V/50 Hz 400 Y 3~ W 2200 A 4.64 m3/s 3.00 min-1 1420 C 120 dB(A) 64/56 kg 58/70 F IP 55 U-EK230E FRQ5(S)-10A FRQ(S)-10A 13 b Y

560D6 IE2 32188 33466 400 Y 3~ 750 1.98 2.08 905 120 49/41 57/69 F IP 55 U-EK230E FRQ5(S)-4A FRQ(S)-4A 13 b Y

630D4 IE2 33554 33468 400 D 3~ 4000 8.12 4.07 1450 120 66/58 65/79 F IP 55 U-EK230E FRQ5(S)-10A FRQ(S)-10A 13b D

630D6 IE2 32189 33467 400 Y 3~ 1500 3.61 2.60 940 120 52/45 65/79 F IP 55 U-EK230E FRQ5(S)-4A FRQ(S)-4A 13 b Y

710D6 IE2 33555 33469 400 Y 3~ 2200 5.1 4.01 945 120 58/50 210/102 F IP 55 U-EK230E FRQ5(S)-10A FRQ(S)-10A 13 b Y

153

Roof fans
Performance

Roof fans

dB(A) LwA Inlet LwA Surrounding DVNI LwA Surrounding With SSD 355/400 LwA Inlet

Tot 63 70 72 63 60 41 43 34 31 125 59 61 52 49

Frequency bands [Hz] 250 63 65 56 53 500 65 67 58 55 1k 64 66 57 54 2k 61 63 54 51 4k 56 58 49 46 8k 49 51 42 39

dB(A) LwA Inlet LwA Surrounding DVNI LwA Surrounding With SSD 355/400 LwA Inlet

Tot 63 70 72 63 60 41 43 34 31 125 59 61 52 49

Frequency bands [Hz] 250 63 65 56 53 500 65 67 58 55 1k 64 66 57 54 2k 61 63 54 51 4k 56 58 49 46 8k 49 51 42 39

Measurement point: 0,45 m/s; 315 Pa

Measurement point: 0,45 m/s; 315 Pa

dB(A) LwA Inlet LwA Surrounding DVNI LwA Surrounding With SSD 355/400 LwA Inlet

Tot 63 73 75 66 63 60 62 59 57 125 62 64 59 57

Frequency bands [Hz] 250 66 68 61 58 500 68 70 60 54 1k 67 69 56 48 2k 64 66 47 42 4k 59 61 45 43 8k 52 54 39 37

dB(A) LwA Inlet LwA Surrounding DVNI LwA Surrounding With SSD 355/400 LwA Inlet

Tot 63 73 75 66 63 60 62 59 57 125 62 64 59 57

Frequency bands [Hz] 250 66 68 61 58 500 68 70 60 54 1k 67 69 56 48 2k 64 66 47 42 4k 59 61 45 43 8k 52 54 39 37

Measurement point: 0,69 m/s; 249 Pa

Measurement point: 0,74 m/s; 285 Pa

154

Roof fans

DVN/DVNI 450D4 IE2

DVN/DVNI 500D4 IE2

Roof fans

dB(A) LwA Inlet LwA Surrounding DVNI LwA Surrounding With SSD 450/ 499/500 LwA Inlet

Tot 63 74 76 67 61 63 60 125 63 65 60

Frequency bands [Hz] 250 67 69 62 500 69 71 60 1k 68 70 54 2k 65 67 47 4k 60 62 45 8k 53 55 39

dB(A) LwA Inlet LwA Surrounding DVNI LwA Surrounding With SSD 450/ 499/500

Tot 63 78 80 71 65 67 64 125 67 69 64

Frequency bands [Hz] 250 71 73 66 500 73 75 64 1k 72 74 58 2k 69 71 51 4k 64 66 49 8k 57 59 43

64

56

56

57

53

47

41

42

36

LwA Inlet

68

62

62

62

60

52

44

42

40

Measurement point: 1,11 m/s; 489 Pa

Measurement point: 1,50 m/s; 400 Pa

DVN/DVNI 560D4 IE2

dB(A) LwA Inlet LwA Surrounding DVNI LwA Surrounding With SSD 450/ 499/500 LwA Inlet

Tot 63 68 70 61 55 57 54 125 57 59 54

Frequency bands [Hz] 250 62 64 57 500 63 65 54 1k 63 65 49 2k 59 61 41 4k 54 56 39 8k 46 48 32

dB(A) LwA Inlet LwA Surrounding DVNI LwA Surrounding With SSD 560/630 LwA Inlet

Tot 63 79 86 77 70 66 73 70 64 125 68 75 70 63

Frequency bands [Hz] 250 72 79 72 64 500 74 81 70 63 1k 73 80 64 56 2k 70 77 57 49 4k 65 72 55 46 8k 58 65 49 45

58

52

52

53

50

43

34

32

29

Measurement point: 1,5 m/s; 701 Pa

Measurement point: 0,69 m/s; 250 Pa

155

Roof fans

DVN/DVNI 560D6 IE2

DVN/DVNI 630D4 IE2

Roof fans

dB(A) LwA Inlet LwA Surrounding DVNI LwA Surrounding With SSD 560/630 LwA Inlet

Tot 63 70 72 63 61 57 59 56 55 125 59 61 56 54

Frequency bands [Hz] 250 64 66 59 56 500 65 67 56 54 1k 65 67 53 48 2k 61 63 44 40 4k 56 58 42 37 8k 48 50 34 35

dB(A) LwA Inlet LwA Surrounding DVNI LwA Surrounding With SSD 560/630 LwA Inlet

Tot 63 87 89 80 78 74 76 73 72 125 76 78 73 71

Frequency bands [Hz] 250 80 82 75 72 500 82 84 73 71 1k 81 83 69 64 2k 78 80 61 57 4k 73 75 59 54 8k 66 68 52 53

Measurement point: 1,1 m/s; 340 Pa

Measurement point: 3,06 m/s; 600 Pa

DVN/DVNI 630D6 IE2

DVN/DVNI 710D6 IE2

dB(A) LwA Inlet LwA Surrounding DVNI LwA Surrounding With SSD 560/630 LwA Inlet

Tot 63 74 76 67 65 61 63 60 59 125 63 65 60 58

Frequency bands [Hz] 250 68 70 63 60 500 69 71 60 58 1k 69 71 57 52 2k 65 67 48 44 4k 60 62 46 41 8k 52 54 38 39

dB(A) LwA Inlet LwA Surrounding DVNI LwA Surrounding With SSD 710 LwA Inlet

Tot 63 79 81 72 69 66 68 65 63 125 68 70 65 62

Frequency bands [Hz] 250 73 75 67 65 500 74 76 65 60 1k 74 76 62 54 2k 70 72 53 45 4k 65 67 51 42 8k 57 59 44 41

Measurement point: 3,06 m/s; 600 Pa

Measurement point: 2.93 m/s; 400 Pa

156

Roof fans Reference

Roof fans

Project: Staatstheater Darmstadt Type of Building: The theatre in Darmstadt is one of the biggest theatres in Germany. It was built in the 1970s and refurbished in 2002 and 2006 for about 90 million Euros. City/Country: Darmstadt/Germany Products/Solution: - 11 smoke extract medium pressure axial fans, type HA 500 - 1 smoke extract medium pressure axial fan, type AXC 500 B - 8 smoke extract roof fans DVV 800 - Roof fans DVS/DVN.

157

Roof fans DVV


Motor outside of the air stream Max temperature of transported air 120C Vertical exhaust Suitable for coastal applications Wide range of accessories Electrical accessories

REV DVV p. 340

120C

IE2
2009/640/EG

Note: article numbers in tables refer to items without PTC or thermal contact, with exception of items with IE2 motors, where PTC is serial built-in. Data related to motor and weight of delivered items can slightly vary from catalogue data. Technical data
DVV 120C Art no. Voltage/Frequency Power at shaft Current Starting current Max air flow R.p.m. Max temp. of transported air Sound pressure level at 4 m Sound pressure level at 10 m Weight Insulation class, motor Enclosure class, motor Wiring diagram p. 391-400

The octagonal casing is manufactured from seawater resistant aluminium (4 pole 1000-M and P from aluzinc steel sheet). The base frame is manufactured from galvanized steel. The impeller with backwardcurved blades is also manufactured from galvanised steel. The fan is equipped with IEC standard motors, according to 2009/640/EC guideline and IEC 60034-30, with protection class IP 54, insulation class F. Single speed or two speed Dahlander connected (4-8,6-12 pole) or with separate windings (6-8,4-6,8-12 pole). Motor cooling with fresh air via air duct. Thermal motor protection (PTC or thermal contact built-in) on request, in IE2 motors serial PTC built-in. For frequency controlled single speed units up to 0,55 kW PTC must be ordered (since IE1 motors built-in). Sizes 800 and 1000 with on/off switch, other sizes equipped with terminal box, on/off switch on request. The DVV fans can be factory fitted with sound attenuators at the outlet (DVVI). Sound attenuators are also available as HSDV accessories.

Roof fans

400D4-6 3506 V/50 Hz 400 3~ kW 0.55/0.18 A 1.7/0.8 A 6.8/2.4 m3/s 1.17/0.778 min-1 1420/940 C 120 dB(A) 62/53 dB(A) 52/43 kg 52/45 F IP 54 15a

450D4 IE2 95139 400 3~ 1.1 2.6 12.5 2.01 1435 120 66 56 65 F IP 54 15c

450D4-6 3530 400 3~ 1.1/0.37 3/1.4 10.8/5.9 2.01/1.35 1420/950 120 66/55 56/46 68 F IP 54 15a

560D4-6 3554 400 3~ 1.7/1.2 4.6/3.7 23.9/13.3 2.64/1.81 1450/940 120 69/60 59/52 75 F IP 54 15a

560 D4 IE2 95140 400 3~ 1.5 3.5 20.3 2.64 1420 120 69 59 69 F IP 54 15c

630 D4-K IE2 95141 400 3~ 3.0 6.6 36.7 3.5 1400 120 71 63 109 F IP 54 15c

630 D4-6-K 3582 400 3~ 3.0/0.9 6.9/3.3 38.0/13 3.5/2.28 1450/975 120 71/61 63/53 118 F IP 55 15a

630 D4 IE2 95142 400 3~ 5.5 11.6 95 5.36 1455 120 75 69 124 F IP 54 13b D

DVV 120C Art no. Voltage/Frequency Power at shaft Current Starting current Max air flow R.p.m. Max temp. of transported air Sound pressure level at 4 m Sound pressure level at 10 m Weight Insulation class, motor Enclosure class, motor Wiring diagram p. 391-400

630D4-6 3586 V/50 Hz 400 3~ kW 5.5/1.7 A 12/4.5 A 81.6/20.3 m3/s 5.36/3.36 min-1 1460/970 C 120 dB(A) 75/64 dB(A) 69/58 kg 124 F IP 55 15a

630D6 IE2 95143 400 3~ 2.2 5.5 25.3 3.36 935 120 64 58 114 F IP 54 15c

800D4-K IE2 95144 400 3~ 9.5 18 121 7.08 1445 120 76 70 224 F IP 55 13b D

800D6-K 95145 400 3~ 2.2 5.5 25.3 5 935 120 66 60 159 F IP 54 15c

800D4-8-K 3630 400 3~ 9.0/2.4 18.5/5.5 114/24 7.08/3.92 1420/720 120 76/55 70/48 243 F IP 55 14a

800D6 IE2 800D6-8 95146 400 3~ 5.5 12.6 76 7.08 960 120 72 64 179 F IP 55 13b D 3644 400 3~ 5.7/2.4 12.3/6.2 62.8/21.7 7.08/5.28 960/720 120 72/66 64/57 190 F IP 54 15a

800D4-M IE2 95148 400 3~ 15 29.8 265 9.58 1470 120 80 72 265 F IP 55 13b D

800D4-6-M 30040 400 3~ 15.0/5.0 33/13.5 198/76 9.58/6.22 1465/980 120 80/70 72/62 353 F IP 55 15a

158

Roof fans
Ventilation accessories

ASFV p. 384

ASK/F p. 380

ASSV p. 383

SSV p. 382

Roof fans

SSVE p. 377

FDV p. 381
DVV 120C Art no. Voltage/Frequency Power at shaft Current Starting current Max air flow R.p.m. Max temp. of transported air Sound pressure level at 4 m Sound pressure level at 10 m Weight Insulation class, motor Enclosure class, motor Wiring diagram p. 391-400 V/50 Hz kW A A m3/s min-1 C dB(A) dB(A) kg 800D4-8-M 800D4-P IE2 800D4-6-P 800D4-8-P 30044 400 3~ 16.2/3.7 36/13 290/64 9.58/4.79 1470/735 120 80/65 72/57 355 F IP 55 14a 95149 400 3~ 18.5 35 280 10.8 1465 120 83 75 353 F IP 55 13b D 30052 400 3~ 18.5/7.0 36/19 244/110 10.8/7.25 1460/985 120 83/71 75/64 335 F IP 55 15a 30056 400 3~ 18.5/4.5 40/15 335/75 10.8/5.42 1470/735 120 83/65 75/57 369 F IP 55 14a 1000D6 IE2 95147 400 3~ 11 22 156 12,4 955 120 74 66 333 F IP 55 13b D 1000D6-8 3663 400 3~ 11.0/5.0 22/15 154/82.5 12.4/9.44 970/730 120 74/66 66/58 400 F IP 55 15a 1000D8 3669 400 3~ 5.5 12.5 63.8 9.44 710 120 66 58 310 F IP 55 13a D

FDVE p. 382

VKV/F p. 383

VKVM p. 384

DVV 120C Art no. Voltage/Frequency Power at shaft Current Starting current Max air flow R.p.m. Max temp. of transported air Sound pressure level at 4 m Sound pressure level at 10 m Weight Insulation class, motor Enclosure class, motor Wiring diagram p. 391-400

1000D4-M IE2 1000D4-6-M 1000D4-8-M 95151 V/50 Hz 400 3~ kW 22 A 42 A 340 m3/s 14.2 min-1 1470 C 120 dB(A) 89 dB(A) 79 kg 469 F IP 55 13b D 32288 400 3~ 22.0/9.0 49/23 299/110 14.2/9.42 1460/985 120 89/77 79/67 495 F IP 55 15a 32289 400 3~ 22.0/5.5 45/17 338/85 14.2/7.08 1470/730 120 89/70 79/60 495 F IP 55 14a

1000D6-M IE2 1000D4-P IE2 95152 400 3~ 7.5 15.7 112 9.42 970 120 77 67 313 F IP 55 13b D 95150 400 3~ 28 56 420 15.2 1470 120 90 79 495 F IP 55 13b D

1000D4-6-P 31265 400 3~ 28.0/8.0 53.5/18 360/120 15.2/10.1 1470/980 120 90/78 79/67 595 F IP 54 15a

1000D6-P IE2 1000 D4-8-P 95212 400 3~ 8.5 18 126 10.1 965 120 78 67 313 F IP 54 13b D 31269 400 3~ 28.0/7.0 51/20 400/80 15.2/7.56 1470/730 120 90/71 79/60 595 F IP 55 14a

159

Roof fans
Dimensions

ds d

d1

nxM

Roof fans

H B C

G A

d2

DVV 400 450 560 630 800 800-M, P 1000 1000D4-M, P

A 560 710 710 995 995 995

B 460 600 600 880 880 880

C 557 706 706 990 990 990 1154 1154

d 315 355 400 500 630 630 710 710

d1 356 395 438 541 674 674 751 751

d2 14 14 14 18 18 18 18 18

ds 284 324 364 452 566 566 710 710

F 635 808 808

G 630 700 750

H 40 20 20 40 40 40 70 70

nxM 8xM8 8xM8 12xM8 12xM8 16xM10 16xM10 16xM10 16xM10

1100 958 1272 1165 1350 1280 1500 1350 1500 1479

1160 1040 1160 1040

160

Roof fans
Performance

81

71

84 75

dB(A) 4-pole LwA Inlet LwA Surrounding 6-pole LwA Inlet LwA Surrounding

Tot 63 81 83 54 56 125 66 68

Frequency bands [Hz] 250 74 76 500 75 77 1k 74 76 2k 72 74 4k 69 71 8k

dB(A) 4-pole 61 63 LwA Inlet LwA Surrounding 6-pole

Tot 63 84 86 57 59 125 69 71

Frequency bands [Hz] 250 77 79 500 78 80 1k 77 79 2k 75 77 4k 72 74 8k 64 66

Roof fans

Measurement point: 0,9 m/s; 200 Pa 71 73 48 50 57 59 63 65 67 69 62 64 60 62 58 60 46 48

Measurement point: 1,7 m/s; 200 Pa LwA Inlet LwA Surrounding 75 76 52 53 61 62 67 68 71 72 66 67 64 65 62 63 50 51

Measurement point: 0,4 m/s; 140 Pa

Measurement point: 1,15 m/s; 100 Pa

2000

4000

6000

8000

10000

88

92

82

81

dB(A) 4-pole LwA Inlet LwA Surrounding 6-pole LwA Inlet LwA Surrounding

Tot 63 88 90 61 63 125 73 75

Frequency bands [Hz] 250 81 83 500 82 84 1k 81 83 2k 79 81 4k 76 78 8k

dB(A) 4-pole 68 70 LwA Inlet LwA Surrounding 6-pole

Tot 63 92 94 65 67 125 77 79

Frequency bands [Hz] 250 85 87 500 86 88 1k 85 87 2k 83 85 4k 80 82 8k 72 74

Measurement point: 2,1 m/s; 310 Pa 81 83 58 60 67 69 73 75 77 79 72 74 70 72 68 70 56 58

Measurement point: 2,8 m/s; 400 Pa LwA Inlet LwA Surrounding 82 84 58 60 69 71 71 73 78 80 73 75 72 74 68 70 55 57

Measurement point: 1,5 m/s; 125 Pa

Measurement point: 1,38 m/s; 350 Pa

161

Roof fans

98

97 87

6-pole

75

dB(A) 4-pole LwA Inlet LwA Surrounding 6-pole LwA Inlet LwA Surrounding

Tot 63 125 79 87

Frequency bands [Hz] 250 91 88 500 90 91 1k 92 91 2k 87 91 4k 81 89 8k

dB(A) 4-pole

Tot 63 125 83 84

Frequency bands [Hz] 250 91 92 500 92 93 1k 91 92 2k 89 90 4k 86 87 8k 78 79

Roof fans

97 98

68 68

72 79

LwA Inlet LwA Surrounding 6-pole

98 99

71 72

Measurement point: 4,58 m/s; 370 Pa 87 88 64 65 73 74 79 80 83 84 78 79 76 77 74 75 62 63

Measurement point: 5,6 m/s; 700 Pa LwA Inlet LwA Surrounding 8-pole LwA Inlet LwA Surrounding 75 77 58 60 64 66 66 68 70 72 68 70 68 70 60 62 49 51 84 86 60 62 71 73 73 75 80 82 75 77 74 76 70 72 57 59

Measurement point: 2,3 m/s; 290 Pa

Measurement point: 4,0 m/s; 280 Pa

Measurement point: 3,1 m/s; 150 Pa

6-pole 8-pole
101
93 82

90 82

dB(A) 6-pole LwA Inlet LwA Surrounding 8-pole LwA Inlet LwA Surrounding

Tot 63 93 95 70 72 125 79 81

Frequency bands [Hz] 250 85 87 500 89 91 1k 84 86 2k 82 84 4k 80 82 8k

dB(A) 4-pole 68 70 LwA Inlet LwA Surrounding 6-pole

Tot 63 101 103 74 76 125 86 88

Frequency bands [Hz] 250 94 96 500 95 97 1k 94 96 2k 92 94 4k 89 91 8k 81 83

Measurement point: 6,1 m/s; 250 Pa 82 84 64 66 70 72 73 75 77 79 74 76 74 76 69 71 58 60

Measurement point: 8,1 m/s; 740 Pa LwA Inlet LwA Surrounding 8-pole LwA Inlet LwA Surrounding 82 84 65 67 71 73 73 75 77 79 75 77 75 77 67 69 56 58 90 92 67 69 78 80 80 82 87 89 82 84 81 83 77 79 64 66

Measurement point: 4,3 m/s; 200 Pa

Measurement point: 5,5 m/s; 250 Pa

Measurement point: 4,2 m/s; 150 Pa

162

Roof fans

92

104

84

85

91

dB(A) 4-pole LwA Inlet LwA Surrounding 6-pole LwA Inlet LwA Surrounding 8-pole LwA Inlet LwA Surrounding

Tot 63 104 106 77 79 125 89 91

Frequency bands [Hz] 250 97 99 500 98 100 1k 97 99 2k 95 97 4k 92 94 8k

dB(A) 6-pole 84 86 LwA Inlet LwA Surrounding 8-pole

Tot 63 92 94 69 71 125 78 80

Frequency bands [Hz] 250 84 86 500 88 90 1k 83 85 2k 81 83 4k 79 81 8k

Roof fans

67 69

Measurement point: 8,6 m/s; 740 Pa 91 93 67 69 78 80 80 82 87 89 82 84 81 83 77 79 64 66

Measurement point: 6,94 m/s; 650 Pa LwA Inlet LwA Surrounding 84 86 66 68 72 74 75 77 79 81 76 78 76 78 71 73 60 62

Measurement point: 5,6 m/s; 330 Pa 85 87 68 70 74 76 76 78 80 82 78 80 78 80 70 72 59 61

Measurement point: 6,11 m/s; 310 Pa

Measurement point: 4,3 m/s; 200 Pa

104

105

92 84 84

93

dB(A) 4-pole LwA Inlet LwA Surrounding 6-pole LwA Inlet LwA Surrounding 8-pole LwA Inlet LwA Surrounding

Tot 63 104 109 82 87 125 91 96

Frequency bands [Hz] 250 97 102 500 100 105 1k 96 101 2k 94 99 4k 92 97 8k

dB(A) 4-pole 80 85 LwA Inlet LwA Surrounding 6-pole

Tot 63 105 110 82 87 125 91 96

Frequency bands [Hz] 250 97 102 500 101 106 1k 96 101 2k 94 99 4k 92 97 8k 80 85

Measurement point: 7,3 m/s; 1600 Pa 92 97 75 80 81 86 83 88 87 92 85 90 85 90 80 85 69 74

Measurement point: 9,2 m/s; 1580 Pa LwA Inlet LwA Surrounding 8-pole 93 98 75 80 81 86 84 89 88 93 85 90 85 90 80 85 69 74

Measurement point: 4,8 m/s; 700 Pa 84 91 66 73 72 79 75 82 79 86 76 83 76 83 71 78 60 67

Measurement point: 7,1 m/s; 560 Pa LwA Inlet LwA Surrounding 84 91 66 73 72 79 75 82 79 86 76 83 76 83 71 78 60 67

Measurement point: 3,1 m/s; 430 Pa

Measurement point: 6,1 m/s; 220 Pa

163

Roof fans ZRS


200C

Electrical accessories

Fans are supplied with 1 m armoured cable and a junction box. Steel cables are provided to give extra support for the fan during chimney sweeping and similar operations. The flue-gas fans have a casing of cast aluminium alloy. The ZRS 170 impeller is made of silumin alloy, while the ZRS 180 impeller is made of stainless steel. The ZRS 170 is suitable for smaller fireplaces with an aperture of less than 0.35 m2, and the ZRS 180 is intended for fireplaces with an aperture between 0.35 and 0.80 m2. Systemair flue-gas fans counteract drafts caused by stoves, ovens and open fireplaces. Flue-gas fans are positioned on the top of the chimney and fixed with four adjustable locating rods which are inserted down the chimney. This means that no fixing into the chimney itself is required. The fan is a discreet and compact unit with a low profile.

REU p. 320

REE p. 321

RE p. 320

Roof fans

Dimensions

300

180

132

Technical data
ZRS Art no. Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 10 m Weight Insulation class, motor Enclosure class, motor Capacitor Speed control, five step Speed control, stepless Wiring diagram p. 391-400 170 1665 V/50 Hz 230 1~ W 42.9 A 0.19 m3/s 0.0861 min-1 2566 C 200 C 200 dB(A) 37 kg 7.6 F IP 44 F 1.5 Transformer RE 1,5 Thyristor REE 1 2 180 1667 230 1~ 55.5 0.26 0.144 2746 200 200 41 8.6 F IP 44 2 RE 1,5 REE 1 2

164

Roof fans
Performance

Roof fans

dB(A) LwA Inlet LwA Surrounding

Tot 63 72 68 54 38 125 66 64

Frequency bands [Hz] 250 66 59 500 67 60 1k 58 61 2k 55 57 4k 46 51 8k 37 41

dB(A) LwA Inlet LwA Surrounding

Tot 63 64 72 44 42 125 47 50

Frequency bands [Hz] 250 60 68 500 58 62 1k 58 66 2k 54 62 4k 48 58 8k 47 55

Measurement point: 0,0672 m/s; 47 Pa

Measurement point: 0,111 m/s; 75 Pa

165

Axial fans

VK Louvre shutter

SG-AW-D Protection guard

AW SG-AW (size 710-1000)

VK Louvre shutter

Axial fans

SG Protection guard AR

EV Flexible connection GFL Counterflange

MFA Mounting feet

SD Rubber mounts

SG Protection guard

RSA Silencer

MP (4x angle 90) Mounting brackets EV-AXC Flexible connection AXC

REV on/off switch

LRK Air operated damper

ESD-F Inlet cone

REV (F) on/off switch

GFL Counterflange MFA Mounting feet SD (4x) AV rubber mounts FSD (4x) AV spring mounts ZSD (4x) AV spring mounts for tensile load

166

Axial fans

AW sileo . . . . . . . . . . . . . . . 168 Axial wall fans: up to 9.70 m3/s, axial impeller, 1 and 3 phase.

AXCBF. . . . . . . . . . . . . . . . . 186 Thermo axial fans: up to 5.5 m3/s, axial impeller, 3 phase.

IE2
2009/640/EG

AR sileo. . . . . . . . . . . . . . . . 170 Axial duct fans: up to 9.70 m3/s, axial impeller, 1 and 3 phase.

Jet fans . . . . . . . . . . . . . . . . 190

IE2
2009/640/EG

AXC . . . . . . . . . . . . . . . . . . . 180 Axial fans: up to 19.16 m3/s, axial impeller, 3 phase.

IE2
2009/640/EG

Axial fans

General
Systemair axial fans have been developed for the installation in effective supply and exhaust air systems. Ranges AR and AW are designed for the use in low pressure systems. Sizes 200 up to 450 are equipped with an impeller made from black coloured high efficiency composite material. From size 450 up to 1000 the AR/AW series are equipped with profiled, pressure die-cast aluminium blades. The long casings for ducted installation as well as the wall plates for wall mounting are manufactured from galvanized, powder coated steel. The AXC range is designed for the use in medium/high pressure systems. Especially for industrial buildings the AXC range

offers a wide area of applications. AXC is equipped with profiled aluminium blades, hot dip galvanized casing. A comprehensive range of accessories is available.

Motors
The Systemair AR/AW range is equipped with external rotor motors, speed controllable by voltage. All external rotor motors have thermal contacts embedded in the motor windings. The TK-leads have to be connected to an external motor protection unit. Systemair also offers a range of explosion proof ATEX axial fans, (see chapter EX-fans). AXC is equipped with IEC standard motors, in IE2 according to the latest ENstandards with PTC thermistors for thermal motor protection. PTC thermistors have to be connected to an external motor protection unit.

Systemair range
The Systemair AR axial fan casings are designed for duct mounting, the AW fan casings for direct wall mounting. From sizes 200 up to 1000 mm. Due to adjustable fan blades and different motor options the Systemair AXC axial fans can be selected to match the exact duty points required for a project. Available from sizes 315 to 2000 mm.

167

Axial fans AW sileo


Speed controllable by voltage reduction, plus option of 2-step operation by D/Y switching for 400V versions Inlet protection guard up to size 630, for bigger sizes as accessory Safe and maintenance free operation Electric connection via terminal box mounted on the motor Single phase fans are supplied with capacitor Axial fans of the AW sileo range do have a bionic shape of the fan blade, which reduces the noise level and increases the efficiency of the fan. AW sileo fans are driven by external rotor motors. The AW range is equipped with a square wall plate, galvanized steel and powder coated in black (RAL9005). The protection guard at the inlet side is powder coated in black. The axial impeller is manufactured either from pressure die cast aluminum, powder coated in black, or from high efficiency composite material. The impeller is balanced dynamically in two levels in accordance with DIN ISO 1940 part 1, quality G6.3. The motors are equipped with thermal contacts for motor protection, with leads to be connected to a motor protection unit, for example Systemair unit S-ET. Electrical accessories

S-ET/STDT p. 341-342

RTRE/REU p. 320

RE p. 320

Quick selection
Quick selection also on page 170 REE p. 321
9736, 9735, 9740, 9738, 9741, 7004, 10906, 9742

1 2 3 4 5 6 7 8

Axial fans

AW/AR 200E4 AW/AR 200E2 AW/AR 250E4 AW/AR 250E2 AW/AR 300E4 AW/AR 300E2-K AW/AR 315DV AW/AR 315E4
6

1 2 3 4 5 6 7 8

AW/AR 350E4 AW/AR 350DV AW/AR 400E4 AW/AR 400DV AW/AR 450DV-K AW/AR 450E4-K AW/AR 450E4 AW/AR 450DV
3 4 5 6

10187, 9675, 9676, 9677, 9681, 9678, 9680, 9682

RTRD/RTRDU p. 321

4 2 3 1 5 7 8

S-DT2 SKT p. 340

Technical data
AW sileo Art no. Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 1 m Weight Insulation class, motor Enclosure class, motor Capacitor Wiring diagram p. 391-400 200 E4 34115 V/50 Hz 230 1~ W 30 A 0.15 m3/s 0.124 min-1 1425 C 70 C 70 dB(A) 46 kg 3.2 F IP 44 F 1 49 200 E2 34114 230 1~ 80 0.38 0.242 2550 60 60 59 3.2 F IP 44 1.5 49 250 E4 34117 230 1~ 50 0.24 0.273 1370 55 55 52 4 F IP 44 1.5 49 250 E2 34116 230 1~ 140 0.59 0.486 2240 70 70 64 4.2 F IP 44 3.5 49 300 E4 34119 230 1~ 100 0.41 0.584 1330 60 60 56 5.9 F IP 44 3 49 300 E2-K 5801 230 1~ 309 1.35 0.948 2730 50 50 72 6.6 B IP 44 8 5 315 DV 34120 400 3~ 120 0.616 0.39 1450 70 70 62 6.8 F IP 54 18 315 E4 34121 230 1~ 160 0.67 0.677 1300 50 50 59 6.7 F IP 44 5 49 350 E4 34123 230 1~ 170 0.75 0.91 1260 60 60 62 7.5 F IP 44 5 49 350 DV 34122 400 3~ 190 0.4 0.976 1390 70 70 64 7.6 F IP 54 18 400 E4 34125 230 1~ 240 1.1 1.07 1350 65 65 64 8.7 F IP 54 5 6a 400 DV 34124 400 3~ 230 0.44 1.08 1370 70 70 64 8.7 F IP 54 18 450 DV-K 34127 400 3~ 350 0.64 1.55 1250 70 70 66 10.1 F IP 44 18 450 E4-K 34129 230 1~ 390 1.75 1.59 1290 65 65 65 10.1 F IP 44 7 6a 450 E4 34128 230 1~ 550 2.5 1.98 1320 70 70 66 16.2 F IP 54 14 6a

Impeller material: put comp. in no. 1 to 14 put alu in no. 15 and full next page

168

Axial fans
Dimensions Ventilation accessories

Motor protection

Thyristor

AW

Transformer

VK p. 356

200E2 200E4 250E2 250E4 300E2 300E4 AW AW 200 AW 250E2 AW 250E4 AW 300E2 AW 300E4 AW 315DV AW 315E4 AW 350DV AW 350E4 AW 400 AW 450DV AW 450DV-K AW 450E4 AW 450E4-K AW 500 AW 560 AW 630 AW 710DV AW 710DS AW 710E6 AW 800DS AW 910DS AW 1000DS AW 1000DS-L A 260 320 320 380 380 380 380 435 435 490 535 535 535 535 615 675 750 810 810 810 910 B 46 50 50 65 69 69 63 68 68 88 96 96 96 96 104 119 130 150 150 150 193 B1 92 102 97 111 103 118 132 119 132 146 171 148 191 148 204 215 207 272 246 246 284 293 323 400 B2 6 6 6 12 11 11 11 12 12 12 14 14 14 14 16 16 20 20 20 20 17 20 20 20 B3 142 152 147 171 165 182 173 182 173 182 206 186 226 186 226 227 225 272 246 246 284 293 323 400 B4 30 30 30 46 28 19 48 22 49 54 47 40 47 40 62 96 52 37 37 37 34 40 40 47,5 D1 210 264 264 330 326 330 349 388 390 420 480 480 480 480 531 589 664 763 763 763 869 922 D4 7 7 7 9 9 9 9 9 9 9 11 11 11 11 11 11 11 L 312 370 370 430 430 430 430 485 485 540 575 575 575 575 655 725 805 315DV 315E4 350DV 350E4 400DV 400E4 450DV-K 450E4 450E4-K 500DV 500E4 560DV 560E4 630D4-2 630DS 630E6 710DV 710DS 710E6 800DS 910DS 1000DS 1000DS-L

S-ET S-ET S-ET S-ET S-ET S-ET STDT S-ET STDT S-ET STDT S-ET STDT S-ET S-ET STDT S-ET STDT S-ET STDT STDT S-ET STDT STDT S-ET STDT STDT STDT STDT

RTRE 1.5/REU 1.5 RTRE 1.5/REU 1.5 RTRE 1.5/REU 1.5 RTRE 1.5/REU 1.5 RTRE 1.5/REU 1.5 RTRE 1.5/REU 1.5 RTRD 2/RTRDU 2 RTRE 1,5/REU 1,5 RTRD 2/RTRDU 2 RTRE 1,5/REU 1,5 RTRD 2/RTRDU 2 RTRE 1,5/REU 1,5 RTRD 2/RTRDU 2 RTRE 3/REU 3 RTRE 3/REU 3 RTRD 2/RTRDU 2 RTRE 5/REU 5 RTRD 4/RTRDU 4 RTRE 7/REU 7 RTRD 4, RTRDU 4 RTRD 2, RTRDU 2 RTRE 5/REU 5 RTRD 7/RTRDU 7 RTRD 4/RTRDU 4 RTRE 5/REU 5 RTRD 4/RTRDU 4 RTRD 7/RTRDU 7 RTRD 7/RTRDU 7 RTRD 14

REE 1 REE1 REE 1 REE 1 REE 1 REE 1 REE 1 REE 1 REE 2 REE 4 REE 2 REE 4 REE 4 REE 4

SG AW p. 385

SG AW-D p. 386

Axial fans

14,5 850 14,5 850 14,5 850 14,5 970 14,5 1070

1010 220 1110 220 1110 220

1016 14,5 1170 1067 14,5 1170

AW sileo Art no. Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 1 m Weight Insulation class, motor Enclosure class, motor Capacitor Wiring diagram p. 391-400

450 DV 34126 V/50 Hz 400 3~ W 540 A 1.1 m3/s 2.0 min-1 1350 C 70 C 70 dB(A) 67 kg 14.6 F IP 54 F 18

500 E4 230 1~ 750 3.35 2.48 1230 70 70 68 20.1 F IP 54 16 6a

500 DV 400 3~ 770 1.7 2.54 1300 70 70 67 20.1 F IP 54 18

560 DV 400 3~ 1044 2.2 3.15 1280 70 70 74 23.5 F IP 54 18

560 E4 5816 230 1~ 1449 6.49 3.72 1287 50 50 77 31.7 F IP 54 30 6a

630 E6 230 1~ 730 3.4 3.1 910 70 70 67 27 F IP 54 16 6a

630 DS 400 3~ 630 1.25 3.12 900 70 70 64 24.5 F IP 54 18

630 DV 5818 400 3~ 1950 3.41 4.94 1353 60 60 80 34.2 F IP 54 18

710 E6 34142 230 1~ 950 4.4 3.86 850 65 65 67 35.1 F IP 54 16 6a

710 DS 34141 400 3~ 1000 2.5 4.05 910 70 70 66 35.1 F IP 54 18

710 DV 34140 400 3~ 2600 4.9 6.27 1330 60 60 76 36.9 F IP 54 18

800 DS 34143 400 3~ 1600 3.6 6.33 920 70 70 73 53 F IP 54 18

910 DS 34157 400 3~ 1950 4.4 7.66 880 70 70 72 58.1 F IP 54 18

1000 DS 34144 400 3~ 2700 5.3 10.1 820 70 70 72 69.5 F IP 54 18

1000 DS-L 4309 400 3~ 5701 10.30 13.40 891 60 60 91 84 F IP 54 18

34132 34131 34134

34139 34138

169

Axial fans AR sileo


Speed controllable by voltage reduction, plus option of 2-step operation by D/Y switching for 400V versions Inlet protection guard up to size 630, for bigger sizes as accessory Safe and maintenance free operation Electric connection via terminal box supplied with the fan Single phase fans are supplied with capacitor Axial fans of the AR sileo range do have a bionic shape of the fan blade, which reduces the noise level and increases the efficiency of the fan. AR sileo fans are driven by external rotor motors. The AR range is equipped with a short casing and flanges according to Eurovent 1/2, galvanized steel and powder coated in black (RAL9005). The protection guard at the inlet side is powder coated in black. The axial impeller is manufactured either from pressure die cast aluminum, powder coated in black, or from high efficiency composite material. The impeller is balanced dynamically in two levels in accordance with DIN ISO 1940 part 1, quality G6.3. The motors are equipped with thermal contacts for motor protection, with leads to be connected to a motor protection unit, for example Systemair unit S-ET. Quick selection Quick selection also on page 168 REE p. 321
1 2 3 4 5 6

Electrical accessories

S-ET/STDT p. 341-342

RTRE p. 320

REU p. 320

Axial fans

AW/AR 500E4 AW/AR 500DV AW/AR 560DV AW/AR 560E4 AW/AR 630E6,DS AW/AR 630DV

1 2 3 4 5 6 7 3

AW/AR 710E6 AW/AR 710DS AW/AR 710DV AW/AR 800DS AW/AR 910DS AW/AR 1000DS AW/AR 1000DS-L

9747, 9693, 9694, 10904, 10388, 10387, 11025

9684, 9685, 11019, 5339, 9687, 9688, 5343

RTRD/RTRDU p. 321

2 1

4 5

4 5 6 7

Technical data
AR sileo Art no. Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 1 m Weight Insulation class, motor Enclosure class, motor Capacitor Wiring diagram p. 391-400 200 E4 34458 V/50 Hz 230 1~ W 30 A 0.15 m3/s 0.124 min-1 1425 C 70 C 70 dB(A) 46 kg 3.2 F IP 44 F 1 49 200 E2 34457 230 1~ 80 0.38 0.242 2550 60 60 59 3.2 F IP 44 1.5 49 250 E4 34460 230 1~ 50 0.24 0.273 1370 55 55 52 4 F IP 44 1.5 49 250 E2 34459 230 1~ 140 0.59 0.486 2240 70 70 64 4.2 F IP 44 3.5 49 300 E4 34462 230 1~ 100 0.41 0.584 1330 60 60 56 5.9 F IP 44 3 49 300 E2-K 5772 230 1~ 309 1.35 0.948 2730 50 50 72 6.6 B IP 44 8 5 315 DV 34464 400 3~ 120 0.616 0.39 1450 70 70 62 6.8 F IP 54 18 315 E4 34463 230 1~ 160 0.67 0.677 1300 50 50 59 6.7 F IP 44 5 49 350 E4 230 1~ 170 0.75 0.91 1260 60 60 62 7.5 F IP 44 5 49 350 DV 400 3~ 190 0.4 0.976 1390 70 70 64 7.6 F IP 54 18 400 E4 34468 230 1~ 240 1.1 1.07 1350 65 65 64 8.7 F IP 54 5 6a 400 DV 34470 400 3~ 230 0.44 1.08 1370 70 70 64 8.7 F IP 54 18 450 DV-K 34474 400 3~ 350 0.64 1.55 1250 70 70 66 10.1 F IP 44 18 450 E4-K 34472 230 1~ 390 1.75 1.59 1290 65 65 65 10.1 F IP 44 7 6a 450 E4 34471 230 1~ 550 2.5 1.98 1320 70 70 66 16.2 F IP 54 14 6a

34465 34466

Impeller material: put comp. in no. 1 to 14 put alu in no. 15 and full next page

170

Axial fans
Dimensions
B E A I H
AR Motor protection

Ventilation accessories
Transformer

Thyristor

200E2 200E4 250E2 250E4 300E2 300E4 315DV 315E4 350DV G 4x90 4x90 8x45 8x45 8x45 8x45 8x45 8x45 8x45 12x30 12x30 12x30 H 10 10 10 10 12 12 12 12 12 12 12 12 I 225 280 355 395 450 500 500 500 500 560 620 690 770 860 970 1070 1070 350E4 400DV 400E4 450DV-K 450E4 450E4-K 500DV 500E4 560DV 560E4 630D4-2 630DS 630E6 710DV 710DS 710E6 800DS 910DS 1000DS 1000DS-L

S-ET S-ET S-ET S-ET S-ET S-ET STDT S-ET STDT S-ET STDT S-ET STDT S-ET S-ET STDT S-ET STDT S-ET STDT STDT S-ET STDT STDT S-ET STDT STDT STDT STDT

RTRE 1.5/REU 1.5 RTRE 1.5/REU 1.5 RTRE 1.5/REU 1.5 RTRE 1.5/REU 1.5 RTRE 1.5/REU 1.5 RTRE 1.5/REU 1.5 RTRD 2/RTRDU 2 RTRE 1,5/REU 1,5 RTRD 2/RTRDU 2 RTRE 1,5/REU 1,5 RTRD 2/RTRDU 2 RTRE 1,5/REU 1,5 RTRD 2/RTRDU 2 RTRE 3/REU 3 RTRE 3/REU 3 RTRD 2/RTRDU 2 RTRE 5/REU 5 RTRD 4/RTRDU 4 RTRE 7/REU 7 RTRD 4, RTRDU 4 RTRD 2, RTRDU 2 RTRE 5/REU 5 RTRD 7/RTRDU 7 RTRD 4/RTRDU 4 RTRE 5/REU 5 RTRD 4/RTRDU 4 RTRD 7/RTRDU 7 RTRD 7/RTRDU 7 RTRD 14

REE 1 REE1 REE 1 REE 1 REE 1 REE 1 REE 1 REE 1 REE 2 REE 4 REE 2 REE 4 REE 4 REE 4

VK p. 356

SG AR p. 385

AR 200 250 300-315 350 400 450DV 450DV-K 450E4 450E4-K 500 560 630 710 800 910 1000DS 1000DS-L

A 85 95

C 204 254 319 356 400 451 451 451 451 503 559 634 711 797 914 1001 1003

D 255 306 382 421 466 515 515 515 515 567 636 709 785 875 1005 1085 1079

130 135 155 160 25 160 175 25 160 174 6 210 220 260 33 280 33 330 376 44.5 330 44.5

Dimension subject to change

AR sileo Art no. Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 1 m Weight Insulation class, motor Enclosure class, motor Capacitor Wiring diagram p. 391-400

450 DV 34473 V/50 Hz 400 3~ W 540 A 1.1 m3/s 2.0 min-1 1350 C 70 C 70 dB(A) 67 kg 14.6 F IP 54 F 49

G
E 72 72 72 72 72 72 72 73 63 63 16x22.5 12 16x22.5 12 16x22.5 15 16x22.5 15 16x22.5 15 500 E4 34475 230 1~ 750 3.35 2.48 1230 70 70 68 20.1 F IP 54 16 49 500 DV 34476 400 3~ 770 1.7 2.54 1300 70 70 67 20.1 F IP 54 49 560 DV-2 5789 400 3~ 993 1.8 3.43 1216 60 60 74 23.5 F IP 54 16 560 E4 5790 230 1~ 1449 6.49 3.72 1287 50 50 77 31.7 F IP 54 30 6a 630 E6 730 3.4 3.1 910 70 70 67 27 F 16 49

EV-AR p. 387

GFL-AR p. 389

MFA-AR p. 386

Axial fans

630 DS 34481 400 3~ 630 1.25 3.12 900 70 70 64 24.5 F IP 54 49

630 DV 5792 400 3~ 1950 3.41 4.94 1353 60 60 80 34.2 F IP 54 18

710 E6 34482 230 1~ 950 4.4 3.86 850 65 65 67 35.1 F IP 54 16 49

710 DS 34484 400 3~ 1000 2.5 4.05 910 70 70 66 35.1 F IP 54 49

710 DV 34483 400 3~ 2600 4.9 6.27 1330 60 60 76 36.9 F IP 54 49

800 DS 34485 400 3~ 1600 3.6 6.33 920 70 70 73 53 F IP 54 49

910 DS 34486 400 3~ 1950 4.4 7.66 880 70 70 72 58.1 F IP 54 49

1000 DS 34487 400 3~ 2700 5.3 10.1 820 70 70 72 69.5 F IP 54 49

1000 D6-2 4308 400 3~ 5701 10.30 13.40 891 60 60 91 84 F IP 54 16

34479 230 1~

IP 54

171

Axial fans
Performance

AW/AR sileo 200E4

AW/AR sileo 200E2

4 3 1 2

5 2

dB(A) LwA Inlet LwA Outlet

Tot 63 51 51 28 26 125 39 38

Frequency bands [Hz] 250 40 41 500 43 43 1k 47 47 2k 44 44 4k 40 40 8k 30 29

dB(A) LwA Inlet LwA Outlet

Tot 63 66 65 36 34 125 47 46

Frequency bands [Hz] 250 54 54 500 56 56 1k 58 58 2k 61 61 4k 59 59 8k 53 52

Measurement point: 0,0894 m/s; 26,2 Pa

Measurement point: 0,158 m/s; 90,6 Pa

Axial fans

AW/AR sileo 250E4

AW/AR sileo 250E2

dB(A) LwA Inlet LwA Outlet

Tot 63 59 59 30 29 125 46 47

Frequency bands [Hz] 250 48 47 500 51 50 1k 53 53 2k 54 54 4k 50 49 8k 40 39

dB(A) LwA Inlet LwA Outlet

Tot 63 71 71 39 37 125 50 50

Frequency bands [Hz] 250 59 60 500 62 62 1k 64 65 2k 67 67 4k 64 63 8k 55 54

Measurement point: 0.196 m/s; 31,4 Pa

Measurement point: 0,305 m/s; 86,5 Pa

172

Axial fans

AW/AR sileo 300E4

dB(A) LwA Inlet LwA Outlet

Tot 63 63 62 39 37 125 48 48

Frequency bands [Hz] 250 51 52 500 54 53 1k 55 55 2k 59 59 4k 54 53 8k 42 41

dB(A)

Tot 63 125 71 70

Frequency bands [Hz] 250 72 500 72 1k 71 2k 69 4k 65 8k 61

LwA Inlet/Outlet 79

Measurement point: 0,6 m3/s; 150 Pa

Measurement point: 0,395 m/s; 54,4 Pa

Axial fans

AW/AR sileo 315DV

AW/AR sileo 315E4

dB(A) LwA Inlet LwA Outlet

Tot 63 68 68 49 47 125 54 53

Frequency bands [Hz] 250 53 55 500 57 58 1k 62 62 2k 64 64 4k 61 61 8k 52 50

dB(A) LwA Inlet LwA Outlet

Tot 63 66 66 39 39 125 55 55

Frequency bands [Hz] 250 58 58 500 59 58 1k 60 60 2k 60 60 4k 54 54 8k 44 44

Measurement point: 0,368 m/s; 73,5 Pa

Measurement point: 0,434 m/s; 71,8 Pa

173

Axial fans

AW/AR sileo 350E4

AW/AR silo 350DV

dB(A) LwA Inlet LwA IOutlet

Tot 63 65 65 40 39 125 52 51

Frequency bands [Hz] 250 53 55 500 60 58 1k 58 58 2k 60 60 4k 54 53 8k 46 45

dB(A) LwA Inlet LwA Outlet

Tot 63 69 70 50 49 125 53 52

Frequency bands [Hz] 250 55 56 500 61 62 1k 64 64 2k 65 65 4k 60 60 8k 53 51

Measurement point: 0,553 m/s; 79,8 Pa

Measurement point: 0,593 m/s; 87,8 Pa

Axial fans

AW/AR sileo 400E4

AW/AR sileo 400DV

dB(A) LwA Inlet LwA Outlet

Tot 63 68 69 48 46 125 56 56

Frequency bands [Hz] 250 59 60 500 60 61 1k 63 65 2k 62 63 4k 57 57 8k 50 48

dB(A) LwA Inlet LwA Outlet

Tot 63 69 69 49 47 125 57 56

Frequency bands [Hz] 250 58 60 500 61 61 1k 63 65 2k 63 63 4k 58 58 8k 50 48

Measurement point: 0,693 m/s; 90,4 Pa

Measurement point: 0,678 m/s; 95,8 Pa

174

Axial fans

AW/AR sileo 450E4-K

AW/AR sileo 450DV-K

dB(A) LwA Inlet LwA Outlet

Tot 63 73 73 52 50 125 64 63

Frequency bands [Hz] 250 64 64 500 65 66 1k 67 67 2k 67 66 4k 62 61 8k 54 52

dB(A) LwA Inlet LwA Outlet

Tot 63 71 71 53 51 125 61 60

Frequency bands [Hz] 250 62 63 500 64 64 1k 65 66 2k 64 65 4k 60 59 8k 51 52

Measurement point: 0,991 m/s; 95,9 Pa

Measurement point: 0,916 m/s; 104 Pa

Axial fans

AW/AR sileo 450E4

AW/AR sileo 450DV

dB(A) LwA Inlet LwA Outlet

Tot 63 70 69 42 46 125 53 54

Frequency bands [Hz] 250 63 62 500 61 62 1k 64 63 2k 64 63 4k 60 59 8k 52 51

dB(A) LwA Inlet LwA Outlet

Tot 63 70 70 47 49 125 54 55

Frequency bands [Hz] 250 57 59 500 62 63 1k 65 65 2k 65 65 4k 60 60 8k 52 51

Measurement point: 1,33 m/s; 120 Pa

Measurement point: 1,29 m/s; 133 Pa

175

Axial fans

AW/AR sileo 500DV

AW/AR sileo 500E4

dB(A) LwA Inlet LwA Outlet

Tot 63 72 72 45 45 125 59 60

Frequency bands [Hz] 250 59 60 500 60 61 1k 67 67 2k 69 68 4k 62 61 8k 51 51

dB(A) LwA Inlet LwA Outlet

Tot 63 71 70 43 45 125 53 53

Frequency bands [Hz] 250 55 59 500 60 62 1k 66 65 2k 67 66 4k 62 61 8k 53 52

Measurement point: 1,61 m/s; 123 Pa

Measurement point: 1,76 m/s; 122 Pa

Axial fans

AW/AR sileo 560DV

AW/AR 560E4

dB(A)

Tot 63 125 63 41

Frequency bands [Hz] 250 66 500 71 1k 74 2k 75 4k 72 8k 64

dB(A)

Tot 63 125 68 46

Frequency bands [Hz] 250 69 500 72 1k 77 2k 78 4k 76 8k 67

LwA Inlet/Outlet 80

LwA Inlet/Outlet 83

Measurement point: 2,19 m/s; 146 Pa

Measurement point: 2,22 m/s; 186 Pa

176

Axial fans

AW/AR sileo 630E6

AW/AR sileo 630DS

dB(A) LwA Inlet LwA Outlet

Tot 63 73 74 48 49 125 55 56

Frequency bands [Hz] 250 65 67 500 65 68 1k 68 70 2k 68 65 4k 61 60 8k 53 53

dB(A) LwA Inlet LwA Outlet

Tot 63 71 71 50 50 125 54 54

Frequency bands [Hz] 250 58 58 500 63 63 1k 67 67 2k 66 65 4k 60 60 8k 53 52

Measurement point: 1,96 m/s; 102 Pa

Measurement point: 1,8 m/s; 111 Pa

Axial fans

AW/AR sileo 710E6

dB(A)

Tot 63 125 65 54

Frequency bands [Hz] 250 73 500 79 1k 81 2k 80 4k 76 8k 70

dB(A) LwA Inlet LwA Outlet

Tot 63 74 74 52 52 125 62 62

Frequency bands [Hz] 250 65 65 500 67 67 1k 70 70 2k 68 65 4k 62 61 8k 57 55

LwA Inlet/Outlet 86

Measurement point: 4,8 m/s; 31 Pa

Measurement point: 2,49 m/s; 114 Pa

177

Axial fans

AW/AR sileo 710DS

AW/AR sileo 710DV

dB(A) LwA Inlet LwA Outlet

Tot 63 73 72 45 46 125 55 55

Frequency bands [Hz] 250 61 61 500 65 65 1k 69 68 2k 67 64 4k 61 59 8k 52 52

dB(A) LwA Inlet LwA Outlet

Tot 63 82 81 51 52 125 64 64

Frequency bands [Hz] 250 67 69 500 72 73 1k 77 76 2k 77 75 4k 73 72 8k 66 66

Measurement point: 2,83 m/s; 115 Pa

Measurement point: 4,41 m/s; 204 Pa

Axial fans

AW/AR sileo 800DS

AW/AR sileo 910DS

dB(A) LwA Inlet LwA Outlet

Tot 63 80 80 50 50 125 63 63

Frequency bands [Hz] 250 70 70 500 73 73 1k 75 75 2k 73 73 4k 68 69 8k 62 62

dB(A) LwA Inlet LwA Outlet

Tot 63 79 79 56 57 125 62 62

Frequency bands [Hz] 250 72 71 500 73 74 1k 73 73 2k 71 70 4k 69 68 8k 61 60

Measurement point: 4,68 m/s; 115 Pa

Measurement point: 5,01 m/s; 144 Pa

178

Axial fans

AW/AR 1000DS

AW sileo 1000DS-L AR sileo 1000D6-2

dB(A) LwA Inlet LwA Outlet

Tot 63 79 79 58 58 125 63 63

Frequency bands [Hz] 250 71 71 500 72 73 1k 74 74 2k 72 70 4k 68 67 8k 64 64

dB(A) LwA Inlet LwA Outlet

Tot 63 92 93 34 36 125 54 57

Frequency bands [Hz] 250 74 75 500 82 83 1k 87 88 2k 88 88 4k 86 87 8k 76 78

Measurement point: 6,5 m3/s; 150 Pa

Measurement point: 8.71 m3/s; 241 Pa

Axial fans

179

Axial fans, medium pressure AXC


Aerofoil impeller with adjustable pitch angle for maximum efficiency. Die cast aluminium hub and blades. Long casing, hot dip galvanized steel, to DIN EN ISO 1461. Spun flanges for high rigidity, according to Eurovent 1/2 Terminal box in IP65 mounted at the outside of the casing for easy wiring. Three-phase motors IP55, insulation class F, in accordance with EN 60034-5/IEC 85 and IEC 60034-30. Suitable for operating temperatures of up to 55C Inspection hole to verify correct direction of rotation Truly reversible version AXR on request 60 Hz range available Inspection hole to verify correct direction of rotation. The Systemair AXC range of long cased medium pressure axial fans is available in sizes from 315 up to 2000 mm impeller diameter. The adjustable pitch angle setting offers a wide performance and maximum flexibility to match precisely individual airflow requirements. This catalogue gives an overview up to size 1250. Other sizes and configurations are available from our selection software. The AXC axial fans have been performance tested in accordance with DIN ISO 5801, DIN 24163 and AMCA 210-99 on the Systemair fan test rig. The IE2 three phase motors are equipped with PTC thermistors for optimum motor protection. The motor is speed controllable by frequency converter. Electrical accessories

REV p. 340

IE2
2009/640/EG

FRQ p. 325

Axial fans

Dimensions

Zx D

Da

Di

s L

TK

Di AXC 315 AXC 355 AXC 400 AXC 450 AXC 500 AXC 560 AXC 630 AXC 710 AXC 800 AXC 900 AXC 1000 AXC 1120 AXC 1250 315 355 400 450 500 560 630 710 800 900 1000 1120 1250

Da 395 435 480 530 590 650 720 800 890 1005 1105 1260 1390

TK 355 395 450 500 560 620 690 770 860 970 1070 1190 1320

ZxD 8x10 8x10 8x12 8x12 12x12 12x12 12x12 16x12 16x12 16x15 16x15 20x15 20x15

L 375 375 450 500 540 500/750 500/750 500/700/800 500/700 640/850 640/850 700/1000 850/1050

s 2,5 2,5 2,5 2,5 3 3 3 3 3 4 4 4 5

Length depending on motor size

180

Axial fans, medium pressure Axial Fans AXC


High efficiency impellers
The AXC die cast aerofoil aluminium impellers can be offered with full or fractional solidities, maximum efficiencies can be obtained. Different impeller/hub configurations allow high pressure drops. AXR impellers are truly reversible. Ventilation accessories

Multi stage fans

For higher pressure drops two stage fans are offered. Two fans in series increase the available static pressure drop.

ESD-F p. 388

Sturdy casing
AXC/AXR axial fan casings are heavy gauge, hot dip galvanized, with spun flanges for high rigidity. Long cased execution as standard stock range. Also available with short casing and with an acoustically insulated box.

Quality
Systemair is ISO 9001 approved. The Systemair quality is regularly monitored by TV Sd.

EV-AXC p. 387

Two stage fan

FSD p. 386

Warranty
Systemair offers a three year warranty on all AXC fan models. The Systemair warranty conditions apply. Performance curves and technical details for the required fan duties are available from our selection software, which can be downloaded or used online from our homepage: www.systemair.de. You can, of course, also order it directly from our customer support. GFL-AXC p. 389

Motors
The built-in motors are equipped with PTC thermistors for optimum motor protection. Single or two speed motors. Speed controllable by frequency converter. Efficiency class IE2 as per 2009/640/EC guidelines.

LRK(F) p. 385

MFA-AXC p. 386

Acoustic data of the AXC series


The human ear perceives tones and intensity based on sound pressure levels. To consider this fact frequency weighting curves were established. In technical acoustics the A-weighting is most common. The level values in the diagrams are A-weighted. They correspond to the sound power levels of a fan emitted on pressure side in a duct. According to EN 25136 = LW4 in dB(A). The catalogue values can be expected, if the flow conditions of the fan correspond to those which are adequate according to standard when installing the fan. When inadequately installed or operated incorrectly, the fan can produce much more noise than necessary for the ventilation task. The fan sound level which is emitted into the duct is important for the selection of the right duct silencers. The efficiency of silencers depends on the frequency. A division of the frequency into bands with the width of an octave is sufficient in ventilation technology. The following example shows how to calculate a spectrum from the total sound power level. Table 1 shows the correction values in the different frequencies of the mid octave band. Example Calculation of an octave band for: Operating point 6000 m/h at 115 Pa static Fan model: AXC 500-10 50 Hz 1440 rpm Result The calculation gives a duct emission level Lw4 of 78 dB(A). LWA oct = LWA4 - Lcorrection
AXC 500-10 50 Hz 1440 rpm
200 ps [Pa]

Axial fans

RSA p. 384

SD p. 385

MP p. 387

q [m/h]

2000
10 15

4000

6000

8000

10000

12000

SG p. 357

L W dB(A)
30 25 20 40 35

150
76

78

80

83

84 dB(A)

100
76 78 80 82 84 dB(A)

50
76
Pd

78

80

82

83 dB(A)

0 1 2 3 m/s

Mid octave band frequency Lcorrection

Hz dB

63 7

125 7

250 6

500 7

1k 10

2k 14

4k 18

8k 23

Table 1: Correction values dependent on the frequency Mid octave band frequency Lw oct Hz 63 125 72 250 73 500 72 1k 69 2k 65 4k 61 8k 56

dB(A) 72

Table 2: Level values of the fan in the octave band

181

Axial fans, medium pressure


300 250 200 150 100 200 50 0 1 1,2 1,0 0,8 0,6 0,4 0,2 0 Item no CAX3152001 CAX3152002 CAX3152003 Model AXC 315-10-2 (0.75 kW) AXC 315-10-2 (1.1 kW) AXC 315-10-2 (1.5 kW) 100 0 1 1,6 P [kW] 1,2 0,8 0,4 0 Item no CAX3552001 CAX3552002 CAX3552003 CAX3552004 Model AXC 355-10-2 (0.75 kW) AXC 355-10-2 (1.1 kW) AXC 355-10-2 (1.5 kW) AXC 355-10-2 (2.2 kW) 2 0 1000 2000 3000 4000 5000 6000 700 0 1000 2000 3000 4000 5000 6000 7000 8000 9000

AXC 315-10 2-pole

600 500 400 300

AXC 355-10 2-pole

Axial fans

P [kW]

700 600 500 400 300 200 100 0

2000

4000

6000

8000 10000 12000 14000 700

2000

6000

10000

14000

18000

AXC 400-10 2-pole

600 500 400 300 200 100 0 1 6,0 P [kW] 4,0 2,0 0 2

AXC 450-10 2-pole

4,0 P [kW] 3,0 2,0 1,0 0 Item no CAX4002001 CAX4002002 CAX4002003 CAX4002004 CAX4002005 Model AXC 400-10-2 (0.75 kW) AXC 400-10-2 (1.1 kW) AXC 400-10-2 (1.5 kW) AXC 400-10-2 (2.2 kW) AXC 400-10-2 (3.0 kW)

Item no CAX4502001 CAX4502002 CAX4502003 CAX4502004 CAX4502005

Model AXC 450-10-2 (1.1 kW) AXC 450-10-2 (1.5 kW) AXC 450-10-2 (2.2 kW) AXC 450-10-2 (3.0 kW) AXC 450-10-2 (4.0 kW)

182

Axial fans, medium pressure


900 800 700 600 500 400 300 200 100 0 1 2 3 4 5 6 7 8 0 5000 10000 15000 20000 25000 30000 5000 1000 900 800 700 600 500 400 300 200 100 0 2 3 4 5 6 7 8 10000 15000 20000 25000 30000

AXC 500-10 2-pole

AXC 560-9 2-pole

10,0 P [kW] P [kW] Item no CAX5002001 CAX5002002 CAX5002003 CAX5002004 CAX5002005 Model AXC 500-10-2 (1.1 kW) AXC 500-10-2 (1.5 kW) AXC 500-10-2 (2.2 kW) AXC 500-10-2 (3.0 kW) AXC 500-10-2 (4.0 kW)

12,0 8,0 4,0 0 Item no CAX5602019 CAX5602020 CAX5602021 CAX5602022 CAX5602023 CAX5602024 CAX5602025 CAX5602026 CAX5602027 Model AXC 560-9-2 (1.1 kW) AXC 560-9-2 (1.5 kW) AXC 560-9-2 (2.2 kW) AXC 560-9-2 (3.0 kW) AXC 560-9-2 (4.0 kW) AXC 560-9-2 (5.5 kW) AXC 560-9-2 (7.5 kW) AXC 560-9-2 (11 kW) AXC 560-9-2 (15 kW)

5,0

Axial fans

10000 1400 1200 1000 800

20000

30000

40000

4000 300 250 200 150

8000

12000

16000

20000

AXC 630-9 2-pole

AXC 630-9 4-pole

600 400 200 0 5 20,0 P [kW] 12,0 8,0 4,0 0 P [kW] 16,0 10 2,5 2,0 1,5 1,0 0,5 0 100 50 0 2 3 4 5 6

Item no CAX6302017 CAX6302018 CAX6302019 CAX6302020 CAX6302021 CAX6302022 CAX6302023 CAX6302024

Model AXC 630-9-2 (2.2 kW) AXC 630-9-2 (3 kW) AXC 630-9-2 (4 kW) AXC 630-9-2 (5.5 kW) AXC 630-9-2 (7.5 kW) AXC 630-9-2 (11 kW) AXC 630-9-2 (15 kW) AXC 630-9-2 (18.5 kW)

Item no CAX6304005 CAX6304006

Model AXC 630-9-4 (2.2 kW) AXC 630-9-4 (3 kW)

183

Axial fans, medium pressure


0 5000 10000 15000 20000 25000 30000 10000 20000 30000 40000

450 400 350 300 250 200 150 100 50 0

600 500 400 300 200 100 0

AXC 710-9 4-pole

AXC 800-9 4-pole

1 5,0 P [kW] 3,0 2,0 1,0 0 Item no

8 9,0 P [kW] 6,0 3,0 0

10

4,0

Model AXC 710-9-4 (2.2 kW) AXC 710-9-4 (3 kW) AXC 710-9-4 (4 kW) AXC 710-9-4 (5.5 kW)

Item no CAX8004011 CAX8004012 CAX8004013 CAX8004014 CAX8004015

Model AXC 800-9-4 (2.2 kW) AXC 800-9-4 (3 kW) AXC 800-9-4 (4 kW) AXC 800-9-4 (5.5 kW) AXC 800-9-4 (7.5 kW)

CAX7104007 CAX7104008 CAX7104008 CAX7104012

Axial fans

5000 700 600 500 400 300 200 100 0

15000

25000

35000

45000

55000

65000 900 800

20000

40000

60000

80000

AXC 1000-10 4-pole

AXC 900-10 4-pole

700 600 500 400 300 200 100

5 16,0 P [kW]

10

15

10

30,0 P [kW] Item no CAX9004008 CAX9004009 CAX9004010 CAX9004011 CAX9004012 CAX9004013 CAX9004014 Model AXC 900-10-4 (2.2 kW) AXC 900-10-4 (3 kW) AXC 900-10-4 (4 kW) AXC 900-10-4 (5.5 kW) AXC 900-10-4 (7.5 kW) AXC 900-10-4 (11 kW) AXC 900-10-4 (15 kW) 20,0 10,0 0 Item no CAX10004007 CAX10004008 CAX1000409 CAX10004010 CAX10004011 CAX10004012 CAX10004013 CAX10004014 Model AXC 1000-10-4 (4 kW) AXC 1000-10-4 (5.5 kW) AXC 1000-10-4 (7.7 kW) AXC 1000-10-4 (11 kW) AXC 1000-10-4 (15 kW) AXC 1000-10-4 (18.5 kW) AXC 1000-10-4 (22 kW) AXC 1000-10-4 (30 kW)

12,0 8,0 4,0 0

184

Axial fans, medium pressure


20000 1000 900 800 700 600 500 400 300 200 100 0 60 50 40 30 20 10 0 10 20 30
8 12 16 24 20

40000

60000

80000 100000 120000 140000

20000 1400 1200 1000 800 600 400 200 0

60000

10000

14000

180000

28

AXC 1120-10 4-pole 32


36

AXC 1250-12 4-pole

10

20

30

40

50

P [kW]

P [kW]

36 24 28 32

80,0 60,0 40,0 20,0 0

12

16

20

Item no CAX11204006 CAX11204007 CAX11204008 CAX11204009 CAX11204010

Model AXC 1120-10-4 (5.5 kW) AXC 1120-10-4 (7.5 kW) AXC 1120-10-4 (11 kW) AXC 1120-10-4 (15 kW) AXC 1120-10-4 (18.5 kW)

Item no CAX12504007 CAX12504008 CAX12504009 CAX12504010 CAX12504011 CAX12504012 CAX12504013 CAX12504014

Model AXC 1250-12-4 (11 kW) AXC 1250-12-4 (15 kW) AXC 1250-12-4 (18.5 kW) AXC 1250-12-4 (22 kW) AXC 1250-12-4 (30 kW) AXC 1250-12-4 (37 kW) AXC 1250-12-4 (45 kW) AXC 1250-12-4 (55 kW)

Axial fans

185

Axial fans, medium pressure AXCBF


200C

Aerofoil impeller with adjustable pitch angle. Die cast aluminium hub and blades. Bifurcated casing, hot dip galvanized steel, to EN ISO 1461 flange holes according Eurovent 1/2. Three phase motors, IP55, insulation class F, in accordance with EN 60034-5, IEC 85. Terminal box mounted directly onto the IE2 motor Suitable for operating temperatures of up to 200C continuously Inspection hole to verify correct direction of rotation. The Systemair AXCBF range of bifurcated medium pressure axial fans has been developed for applications with an atmosphere which would either require special motors or reduce the lifetime of a standard motor. The motors of AXCBF are outside of the airstream. Available in sizes from 250 up to 800 mm impeller diameter. AXCBF bifurcated axial fan casings are heavy gauge, hot dip galvanized. The motor compartment allows easy access to the motor terminal box for wiring. Three phase B3 foot mounted motors, totally enclosed and fan cooled. The three phase motors are equipped with PTC thermistors for optimum motor protection.

IE2
2009/640/EG

Quick selection

7561, 7571, 7574, 7576, 7579

1 2 3

AXCBF 250D2-32 AXCBF 250D4-32 AXCBF 315D2-30 AXCBF 315D4-32 AXCBF 400D2-22

1 2 3 4 5

AXCBF 400D4-32 AXCBF 500D2-20 AXCBF 500D4-32 AXCBF 630D4-26 AXCBF 800D4-18

Axial fans

4 5

4 2

Technical data
AXCBF Art no. Voltage/Frequency Power Rated current Max air flow R.p.m. Max temp. of transported air Weight Insulation class, motor Enclosure class, motor Wiring diagram p. 391-400 250D4-32 32458 V/50 Hz 400 3~ kW 0.25 A 0.80 m3/s 0.23 min-1 1400 C 200 kg 30 F IP 55 13b 250D2-32 32456 400 3~ 0.37 1.0 0.49 2690 200 30 F IP 55 13b 315D4-32 32462 400 3~ 0.25 0.8 0.54 1390 200 32 F IP 55 13b 315D2-30 IE2 34146 400 3~ 0.75 1.68 0.951 2875 200 35 F IP 55 13b 400D4-32 32483 400 3~ 0.55 1.5 1.00 1370 200 42 F IP 55 13b

186

7594, 7580, 7581, 7583, 7584

Axial fans, medium pressure


Dimensions
A G H

Ventilation accessories

LRK(F) p. 385

F
AXCBF 250 315 400 500 long version 500 short version A 535 535 625 710 660 B 448 452 585 695 695 C 328 385 480 590 590 D 250 315 400 500 500 F 302 355 450 560 560 G 22.5 22.5 22.5 15 15 H 10 10 10 12 12 I 8x45 8x45 8x45 12x30 12x30

MFA-AXCBF p. 388

ESD-F p. 388

G H

EVH p. 388

FSD p. 386

Axial fans

E
AXCBF 630 800 A 790 880 B 728 890 C 630 800 E 690 860 G 15 11.25 H 12 12 I 12x30 16x22,5

GFL-AR/AXC p. 389

SG AR/AXC p. 385

Note: Accessories LRK, ESD-F and SG not available for size 250

AXCBF Art no. Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air Weight Insulation class, motor Enclosure class, motor Wiring diagram p. 391-400

400D2-22 IE2 34147 V/50 Hz 400 3~ kW 2.20 A 4.48 m3/s 1.65 min-1 2890 C 200 kg 49 F IP 55 13b

500D2-20 IE2 34148 400 3~ 4.00 7.64 3.06 2914 200 87 F IP 55 13b

500D4-32 IE2 34152 400 3~ 1.10 2.53 1.91 1445 200 66 F IP 55 13b

630D4-26 IE2 34155 400 3~ 2.20 4.64 3.44 1440 200 106 F IP 55 13b

800D4-18 IE2 34156 400 3~ 4.00 8.12 5.63 1445 200 155 F IP 55 13b

34148 = long version 34152 = short version

187

Axial fans, medium pressure


Performance

AXCBF 315D2-30 IE2

Axial fans

AXCBF 400D2-22 IE2

188

Axial fans, medium pressure

AXCBF 500D4-32 IE2

AXCBF 500D2-20 IE2

Axial fans

189

Jet fans

Jet fans
Green ventilation Contemporary ventilation for underground car parks

Underground car park ventilation without compromise: Systemairs Green Ventilation jet fan system is the contemporary solution for energy efficiency and high safety standard requirements. The result is setting standards: 80% energy saving in Green Ventilation mode*, combined with a guaranteed safety promise of a worldwide acting system partner. The Green Ventilation jet fan system combines low operation cost and competitive initial investment by complying with legal requirements.

% 0 8
g avinn mode s y g tilatio n Ener
in G reen Ve

Jet fans

All Systemair products and systems, marked with the Green Ventilation label, meet highest requirements for energy and economic efficiency.

Components
The Green Ventilation jet fan system replaces the duct system of a car park. According to the ventilation concept, it may include exhaust fans as well as potential supply fans . In addition to jet fans, Systemair offers axial supply fans (AXC series) as well as temperature resistant exhaust fans as axial or roof fans (AXC (B), AXC (F) or DVV series) according to EN 12101-3. Systemair is able to supply all necessary dampers, flaps and other ventilation elements.

An effective system requires good planning, beginning with physical values such as the underground car parks dimensions, its occupancy, its usage profile and taking peak loads in consideration. The dimensioning of the ventilation is normally based on the air change rate (depending on air pollution) or an air volume load which is multiplied with the amount of parking places.

Application examples and planning


With an optimal planning, the Green Ventilation fan system avoids dead spaces in the garage. Systemair jet fans are used for everyday demand ventilation as well as smoke extraction in case of fire in underground car parks and closed parking garages.
*CO mode compared with nominal fan power of car park exhaust ventilation

190

Jet fans

Advantages and benefits of Systemair Green Ventilation jet fan systems For investors
Reduction of investment cost, because bulky and complex duct systems can be omitted. This is a great advantage in particular for renovation projects. The flexible positioning of the jet fans enables the creation of modern and aesthetic buildings. The whole design of the underground car park gets optically more attractivity, there is no line-of-sight obstruction coming from the ductwork.

For users
The Green Ventilation jet fan system provides an 80% reduced energy consumption. This leads to considerably reduced operational cost. The center-piece is an intelligent control unit for highest energy efficiency of demand controlled ventilation. Furthermore, no resistance for the duct system in the car park has to be overcome. Selective ventilation for specific areas in the underground car park. CO (carbon monoxide) car exhaust sensors make sure that only really needed fans will be activated. This, again, helps to lower the running cost. In comparison to conventional systems, the concentration of pollutants is lower, providing a better air quality. The air moves constantly all over the activated car park area which allows better air mixture. Jet fan ventilation systems for smoke extraction avoid costintensive secondary damages: building ceilings are exposed to lower heat, smoke will be quickly exhausted out of the building. Optimised safety in case of fire. Faster smoke and heat extraction, smoke spreading is avoided and a better smoke control is possible to facilitate the work of fire-services.

Jet fans

For planners
More flexible fan positioning, in particular for redesign or renovation of parking decks. Faster design of complete systems, because no complex duct system is needed inside the car park. Possibility to have functional demonstration of the installation by the Systemair CFD analysis and by a warm smoke test.

For installers
Easy and fast fan installation to the car park ceiling - therefore less mounting work. Less points of contact with other crafts, because the fans can be installed at the end. Flexible fan positioning.

191

Jet fans

Customized solutions
System description

Driveway, ramp or other fresh air openings can supply natural fresh air. The supply air is designed to guarantee an almost laminar air flow. If no natural supply air can be provided, a supply air fan is needed. The Green Ventilation jet fan system supports the natural air flow between supply and exhaust air and helps accelerate the airflow in areas where it is too low to guarantee a sufficient air change all over the car park. According to safety regulations, virtual smoke sectors are created by aerodynamic loads in case of fire. This allows the design of wide and spacious car parks which normally need to be separated by gates or other installation elements. This always includes the aspect of efficiency and energy efficiency without losing sight of investment costs. A project-related switching matrix ensures that legal requirements are observed and individual safety objectives are followed. These are e.g. maximum CO and smoke gas concentration, required sight distances for personal rescue and preparation of fire-fighting operations by fire services. In case of an exhaust air fan failure, it is important that the control detects and indicates this failure automatically and finally switches over to the second fan.

Jet fans

Different versions of axial, radial and roof fans are available, for standard temperature up to temperature class F600 (600 C/120 min.). An optimised operation is provided by the project designed Green Ventilation control system. It analyses measurements of CO exhaust sensors and/or fire/smoke detectors and controls single, virtual smoke and CO zones according to the requirements. Jet fans in not affected smoke and CO zones are controlled according to the stored control matrix. The system will be designed in accordance with the requirements given in the specifications. Complete documentation can be found within the control cabinet.

Exhaust air

Exhaust air

Supply air

Supply air

192

Jet fans

The space required by different ventilation systems has a direct impact on the investment cost of a project. Jet fans do only punctually reduce the available ceiling height and need often many other installation systems like electric wiring and water pipes less than 0.5% ceiling surface. The extra ceiling space can be used for technical appliances and/or allows to reduce the ceiling height during the planning stage already. Another advantage is a higher safety of an active system which, depending on the fire location, reacts in accordance with the defined fire scenario matrix and offers best possible protection to human beings and buildings. Systemair remains your partner from the car park's planning to the commissioning and designs Green Ventilation garage exhaust systems according to your requirements.

Green Ventilation and smoke extraction function Many systems provide an opportunity either to save energy or to extract smoke out of your garage. But why should you choose the one or the other? Systemair educated smoke extraction car park systems in energy saving.

Jet fans

Energy cost reduction

Reduction

% 100 80 60 40 20 0
Jet System EFF2 motor Jet System IE2 motor Green Ventilation mode

Case study

Power requirement for a 5000 m garage, 60.000 m/h; 13 jet fans

kW 40 20 0 Jet System EFF2 motor Jet System IE2 motor Green Ventilation mode

193

Jet fans Jet Fan AJR-TR


Dual use: For daily ventilation and smoke extraction in case of fire F300 (300C/120 min.); F400 (400/120 min.) Symmetrical blades; 100% reversible with low sound level Motors IP54, insulation class H (smoke extract); Motors IP55, insulation class F (CO-exhaust), according to EN 60045-5/IEC 85 60 Hz range available Tested inspection switch optional Casing manufactured from galvanized steel Certified to EN 12101-3, CE-certification by TV Sd Electrical accessories

IE2
2009/640/EG

FRQ p. 325

Technical data
Jet fan AJR-TR 400V/50Hz N AJR 315-2-TR AJR 315-2/4-TR AJR 355-2-TR AJR 355-2/4-TR AJR 400-2-TR 22 22/6 37 37/9 55 55/14 22 22/6 37 37/9 55 55/14 m/h 4400 4400/2200 6400 6400/3200 8700 8700/4350 4400 4400/2200 6400 6400/3200 8700 8700/4350 Thrust Air volume Motor rated power kW 0,75 0,75/0,17 1,5 1,4/0,3 1,5 1,9/0,4 0,75 0,75/0,12 1,5 1,5/0,25 1,5 1,5/0,25 Motor rated current A 1,8 1,74/0,63 3,3 3,13/1,11 3,3 4,18/1,47 1,65 1,8/0,4 3,6 3,6/0,7 3,6 3,6/0,7 rpm 2900 2860/1420 2840 2880/1440 2840 2885/1435 2880 2880/1440 2880 2880/1440 2880 2880/1440 Speed Sound level 3 m, from center of casing LpA dB 60 60/45 66 66/51 72 72/57 60 60/45 66 66/51 72 72/57 kg 50 52 65 67 83 85 50 52 65 67 83 85 55C 55C 55C 55C 55C 55C 300C/120 Min. 300C/120 Min. 300C/120 Min. 300C/120 Min. 300C/120 Min. 300C/120 Min. Weight Temperature

Jet fans

AJR 400-2/4-TR AJR 315-2 (B)-TR AJR 315-2/4 (B)-TR AJR 355-2 (B)-TR AJR 355-2/4 (B)-TR AJR 400-2 (B)-TR AJR 400-2/4 (B)-TR

Dimensions
F E C 344

400C/2h versions on request

Da

Size 315 355 400

Da 419 459 504

H 430 497 558

E 265 305 350

C 235 255 280

F 315 355 400

L 1660 1820 2000

All dimensions in mm.

194

Jet fans Jet Fan AJ8


Dual use: For daily ventilation and smoke extraction in case of fire F300 (300C/120 min.) and F400 (400C/120min). Aerodynamical impellers for maximum thrust and with low sound level (reversible impellers on request) Motors IP54, insulation class H (smoke extract); Motors IP55, insulation class F (CO-exhaust), according to EN 60045-5/IEC 85 Tested inspection switch optional Shapely, low design-casing Casing manufactured from galvanized steel Removable fan module also after installation for easy maintenance Certified to EN 12101-3, CE-certification by TV Sd

Technical data
Jet fan AJ8 400V/50Hz N AJ8 315-2 AJ8 315-2/4 AJ8 355-2 AJ8 355-2/4 AJ8 400-2
476

Thrust

Air volume

Motor rated power

Motor rated current A 1,99 2,14/0,75 2,5 3,13/1,11 3,3 4,18/1,47 1,8 1,6/0,4 2,5 3,1/0,68 3,2 3,9/0,95

Speed

Sound level 3 m, from center of casing

Weight

Temperature

m/h 4400 4400/2200 6300 6300/3150 7700 7700/3850 4400 4400/2200 6300 6300/3150 8700 8700/4350

kW 0,75 0,75/0,17 1,1 1,4/0,3 1,5 1,9/0,4 0,75 0,75/0,15 1,1 1,3/0,25 1,5 1,8/0,37

rpm 2900 2860/1420 2900 2880/1430 2840 2885/1435 2900 2880/1450 2870 2905/1460 2870 2880/1455

LpA dB 62 62 / 47 69 69 / 54 73 73 / 58 62 62 / 47 69 69 / 54 73 73 / 58

kg 82 84 88 90 97 99 82 84 88 90 97 99 55C 55C 55C 55C 55C

23 23/6 37 37/9 55 55/11 23 23/6 37 37/9 55 55/11

Jet fans

AJ8 400-2/4 AJ8 315-2 (B) AJ8 315-2/4 (B) AJ8 355-2 (B) AJ8 355-2/4 (B) AJ8 400-2 (B) AJ8 400-2/4 (B)

55C 300C/120 Min. 300C/120 Min. 300C/120 Min. 300C/120 Min. 300C/120 Min. 300C/120 Min.

2200 2213

Air volume related to air density 1,2 kg/m

400C/2h versions on request

Dimensions
F E C
476
476

2200 2213

2200 2213

F E

Size 315 C 355 400

H 365 395 445

B 550 550 600


F E

C 355 355 380

E 635
C

F 650 650 700

635 684

All dimensions in mm.

195

Jet fans Jet Fan IV


Dual use: For daily ventilation and smoke extraction in case of fire F300 (300C/120 min.); F400 (400/120 min.) on request Aerodynamical centrifugal impeller for maximum thrust and with low sound level Motors IP54, insulation class H (smoke extract); motors IP55, insulation class F (CO-exhaust), according to EN 60045-5/IEC 85 Tested inspection switch optional Compact design for low ceiling heights Casing manufactured from galvanized steel Integrated deflector (exhaust direction adjustable) Certified to EN 12101-3 CE-certification by TV Sd

Technical data
Centrifugal Jet fan IV Voltage/Frequency Motor rated power Current Thrust Max. air volume R.p.m. 50-4 (B) V/50 Hz 400 3~ kW 1,5 A 3,4 N 52 m/h 6196 min-1 1435 C 55 C 300 dB (A) 73 kg 105 H IP 55 50-4/6 (B) 400 3~ 1,5/0,7 3,5/1,9 52/20 6196/4190 1445/955 55 300 73/56 102 H 55 50-4/8 (B) 400 3~ 1,5/0,25 3,8/1,15 52/14 6138/3100 1430/715 55 300 73/52 105 H 55 85-4 (B) 400 3~ 2,2 4,7 85 9950 1435 55 300 78 140 H 55 85-4/6 (B) 400 3~ 2,2/0,75 4,9/2,6 85/28 9950/5875 1450/965 55 300 78/66 141 H 55 85-4/8 (B) 400 3~ 2,2/0,37 5,2/1,6 85/22 9950/5098 1425/715 55 300 78/62 142 H 55

Jet fans

Max. temp. of transported air Max. temp. of transported air 120 min. Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor

Dimensions
6x K

H F D

Size IV 50 IV 85

A 790 1140

B 834 1184

C 870 1220

D 1248 1900

E 300 340

F 370 420

H 185 210

I 210 230

6xK 13,5 13,5

All dimensions in mm.

196

Jet fans

Our control at your service!


Systemair control systems

Every building has individual requirements for ventilation and smoke extraction concepts. Safety and efficiency are not in contradiction. In case of a fire, the control disregards energy consumption. It is important to guarantee the safety of the people and the building, to enable the personal rescue and assist the fire brigade and other action forces in their work, which minimizes fire and smoke gas damages. However, the systems generally run 24/24 and 365 days a year. Therefore each kilowatt of electrical energy used by the system counts for the operator or owner of the building. Compared to conventional systems a Green Ventilation Car Park System considerably reduces the energy use. For an optimal function, the control system has to be designed individually to meet all requirements of the project. Ideally, this must be done in line with all other crafts during basic conception and coordinated with the ventilation system of the building. Air quality requirements for desk spaces are different from those for underground car parks. Because of the duration of stay and other factors, harmful substances influence the human health. The factor time/duration of stay in the car park is responsible for different legal demands to average time values concerning CO exposure (half-hourly average value, quarter-hourly average value, ). Therefore, you can specify some areas of your building with different air quality that allows to provide exhaust air from the air conditioning unit to other areas as supply air. Normally, the windows of energy optimised, modern buildings are not permanently in a tilted position. In fact, air quality in modern buildings is monitored and can be changed when preset maximum values are achieved. Systemair implements this concept also for underground car parks. On demand, the parameters can be changed and customised by the user. All legal requirements can be accomplished.

The Systemair control system


The Systemair control system provides active motor protection during normal ventilation mode with single and group error messages (only for standard temperature version).

Jet fans

The control system includes fan control for ventilation and smoke extraction of underground car parks, equipped with supply and exhaust fans, jet fans and sensors. Single- or double-speed fans and unidirectional or reversible fans can be controlled. Each jet fan can be separately switched on or off for maintenance and commissioning. In normal ventilation mode, the control system works either in accordance with the CO alarm system, or the timer, or the BMS system data. The fan will run either in high or low speed in the selected flow direction. In case of fire, the control system acts dependent on the fire alarm system. Virtual fire zones with different flow directions can be formed for smoke extraction. Being activated in the fire zone operate automatically in the selected speed and airflow direction. The built-in motor overload protection will be deactivated in the control cabinet. The fan permanently runs until mechanically demolished by the fire.

197

Jet fans

Safety requires individual planning


CFD simulations

A CFD simulation is needed to confirm that there is enough air movement in all areas of the car park to secure the required number of air exchanges, to confirm the proposed number of jet fans and to determine the location where the jet fans have to be installed. In order to be able to perform a CFD analysis, it is essential to have a 3-D model of the building site, giving all openings, slab height, surface of the ceiling (flat or with drop beams, dimensioning of the drop beams, etc.) and all other details required to carry out a simulation. A CFD analysis is used to simulate the airflows, to ensure that the distribution of the air is sufficient to effectively ventilate the cark park under normal conditions as well as in emergency situations. Systemair offers this service meaning everything from one source and firsthand truly tailored solutions.

Jet fans

Velocity vectors (without Jet fans) 2,35 m above the ground


velocity m/s

Smoke concentration 5 minutes after the fire has started

Smoke concentration (CO2) at 1,5 m height

Smoke concentration in different rooms on the same floor

198

Jet fans

Systemair as a system partner

Project handling
Electrical planning, commissioning, final approval test, handing over. Everyone knows the problems on the building site when ventilation crafts and electrical crafts meet with different requirements. Two crafts with different requirements for your team. Systemair helps you to handle the project successfully and on schedule. From the conception of the complete system with CFD analysis to the detailed technical planning of the ventilation system and the creation of cable lists and the delivery of components to the points of commissioning and supervised final approval test including warm smoke gas test. Thus, all planning phases and crafts are in our focus, we coordinate the interfaces and give you support according to your needs.

Jet fans

Commissioning
Systemair offers a smoke gas extraction test while commissioning your car park system. This simulates a case of emergency.

Smoke gas test preparation

Smoke gas test during commissioning

199

Explosion proof fans

General
Systemair explosion proof fans have been developed to be used in effective supply and exhaust air systems allocated to category 2 (zone 1) and category 3 (zone 2) in explosion hazardous areas. All fans are manufactured in accordance with ATEX guideline 94/9/EG certified for EC countries. Certificates can be downloaded from our homepage. The fans are suitable for mounting in above mentioned explosion hazardous zones, for extraction of gases.

II, allowing an application in zone 1 and zone 2. In the industry, explosion hazardous areas are classified in zones. ATEX classifies the fans in categories, corresponding to the zones. Categories are independent from the substance causing the explosion hazard. The classification in categories (or zones) is related to the temporal appearance (frequency of occurrence) of explosion hazard ous atmosphere (gas/vapour/ fog-air mixture in ignitable condition). The categories or zones do not define the concentration! Category 1 (zone 0) covers areas, where there is a permanent or long lasting occurrence of explosion hazardous atmosphere (more than 1000h/year). Example: inside a fuel tank. Category 2 (zone 1) covers areas, where there is a regular occurrence of explosion hazardous atmosphere (10-1000 h/year). Example: Filling machine Category 3 (zone 2) covers areas, where there is a non-regular or short time appearance of explosion hazardous atmosphere (up to 10h/year). Example: defective gas pipe, accidents. The categories show the occurrence of an explosion hazardous area as a probability. It is important to know: In all categories (zones) there is the same momentary hazard (same substance and same concentration) when explosion hazardous atmosphere occurs. Example: zone 0, empty and non-cleaned fuel tank, concentration 20Vol%; zone 2, leaked fuel, concentration 20Vol%. If an explosion hazardous atmosphere occurs, the hazard potential is the same in all zones! The last decision has to be made regarding the ignition protection class. All Systemair explosion proof fans correspond to ignition protection class Ex e = increased safety. The following table shows possible ignition protection classes.

Systemair ranges
The materials used in Systemair EX fans are in accordance with DIN EN 60079. The fans of series DVEX, DVV-Ex and RVK-Ex are equipped with self-cleaning impellers with backward curved blades. EX, KTEX and DKEX are equipped with impellers with forward curved blades. AW-EX is equipped with profiled steel axial impellers with additional painting.

AXC-EX and AXCBF-EX is equipped with either single or two speed motors in Ex d. This motor type can be speed controlled by frequency. All DVEX, KTEX, DKEX, AW-EX and RVK EX fan motors are equipped with a cold conductor for motor protection. The motor protection has to be connected with a motor protection device, described in the certificate and also certified. Motors of series DVV-Ex and EX do not have a thermal motor protection. Those motors have to be supervised by a suitable over-current device. The ignition temperature of the medium, but also the classification in explosion groups is important. Both classifications have to be considered when selecting a suitable fan.

Group (IEC)

Some examples of gas


acetone, ammonia, ethyl alcohol, fuel, benzene, methane, propane, carbon dioxide ethylene, diethyl ether, town gas hydrogen, carbon disulphide, acetylene.

Explosion proof fans

group II A

The selection of an ATEX-fan


Below Systemair provides you with helpful information for the selection of a suitable fan. We want to point out that we as manufacturers are responsible only for the appearance and workmanship of the fan. The system user is responsible for the correct system design for a proper operation. Pre-selection depends on the medium to be transported. Each medium has an individual ignition temperature. The fans supplied by Systemair comply with temperature classification T3, some units can also be used in T4. Regarding the ignition group units with external rotor motors, fans like DVEX, KTEX are suitable to transport gases with ignition group IIA and IIB. Fans like AXC-EX, AXCBF-EX are also suitable to transport gases with ignition group IIC. The next step is the selection of the correct zone resp. category. Basically the correct zone or category can only be given by the user of the system, after having conducted an analyse regarding the occurrence of explosion hazardous gases or gas mixtures in the project. All Systemair explosion proof fans are in unit category

group II B group II C

Ignition protection classes


i c* d* e* p o m q nA* intrinsic safety constructional safety flameproof enclosure increased safety pressurized oil immersion encapsulation powder filling non sparking

Motors
DVEX, AW-EX, KTEX, RVK and DKEX are equipped with speed controllable, certified external rotor motors in Ex e execution. EX is equipped with non speed controllable IEC motors, Exe execution. DVV-EX,

* in the Systemair range

200

Explosion proof fans


All Explosion proof fans according to (ATEX95 for EX Symbol) II 2G

RVK 315Y4. . . . . . . . . . . . . 202 ATEX certified circular duct fan: 0.28 m3/s, backward curved impeller, 3 phase. Ex e, T1-T3, IIA and IIB, Zone 1 and 2.

DVV-EX . . . . . . . . . . . . . . . . 220 ATEX certified roof fan: up to 11.9 m3/s, backward curved impeller. Motor Ex d, T1-T4, IIA and IIB, Zone 1 and 2.

EX . . . . . . . . . . . . . . . . . . . . 204 ATEX certified centrifugal fans: up to 0.33 m3/s, forward curved impeller, 1-3 phase. Ex e, T1-T3, IIA and IIB, Zone 1 and 2

AW-EX. . . . . . . . . . . . . . . . . 226 Axial wall fans: up to 3.19 m3/s, 3 phase. Ex e, T1-T4, IIA and IIB, Zone 1 and 2.

KTEX . . . . . . . . . . . . . . . . . . 208 ATEX certified rectangular fans: up to 1.375 m3/s, forward curved impeller, 3 phase. Ex e, T1-T3, IIA and IIB, Zone 1 and 2.

AXC-EX . . . . . . . . . . . . . . . . 230 ATEX certified axial fan, up to 12.36 m3/s, 3~ version. Motor Ex d, T1-T3, IIA, IIB and IIC, Zone 1 and 2.

DKEX. . . . . . . . . . . . . . . . . . 212 ATEX certified centrifugal fans: up to -1.39 m3/s, forward curved impeller, 3 phase. Ex e, T1-T3, IIA and IIB, Zone 1 and 2.

AXCBF-EX . . . . . . . . . . . . . . 234 ATEX certified axial fan, up to 5.88 m3/s, 3~ versions. Motor Ex d, T1-T3, IIA, IIB and IIC, Zone 1 and 2.

DVEX. . . . . . . . . . . . . . . . . . 216

Explosion proof fans

ATEX certified roof fan: 0.412.39 m3/s, backward curved impeller. Ex e, T1-T3, IIA and IIB, Zone 1 and 2.

Labelling of an ATEX approved fan:

CE labelling

Notified body Unit group (Quality assurance system)

Category Classification G=gas, D=dust

EPL = Equipment protection level

CE 0820

II 2G c Ex e IIB T3 Gb Sira 07ATEX 6341 X


Temperature class Group ATEX certification no.

Ignition protection class

201

Explosion proof circular duct fans RVK 315Y4


In accordance with ATEX directive 94-9 EC Speed controllable Can be installed in any position Motorprotection over cold conductor Electrical accessories

U-EK 230E EX p. 338

The RVK fans are designed for installation in ducts. The fans have backward curved blades and external rotor motors. The RVK 315 Y4 can be controlled by reducing voltage via 5-step controller in combination with the Systemair Standard tripping unit UEK230E EX. The fans is supplied with flying leads. The RVK 315Y4 fan complies with the ATEX regulation. The fans can be used for zone 1 and zone 2; Field of application II, for gases of groups IIA and IIB, temperature class T1, T2 and T3. The casing is made from conducting plastic. The fans are certified under the no ZELM 03 ATEX 0198x. Improved safety in accordance with Ex e II T3. Attention: Motor protection device U-EK230E EX must always be connected.

R-DK4 KT p. 323

EX e p. 339

The explosion proof terminal box is supplied as an accessory to the RVK 315Y4, ordered seperately.

Explosion proof fans

Technical data
RVK Art no. Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 4/10 m Weight Insulation class, motor Enclosure class, motor Motor protection Certificate Wiring diagram p. 391-400 315Y4 30271 V/50 Hz 400 3~ W 90 A 0.25 m3/s 0.311 min-1 1385 C 40 C 40 dB(A) 41.2 kg 6.7 B IP 44 U-EK230E EX ZELM 03 ATEX 0198X 43

202

Explosion proof circular duct fans


Dimensions
225

Ventilation accessories

FK p. 355

200

60

SG p. 357

314

405 264 30,5 314

Performance

Explosion proof fans

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 67 68 48 44 49 18 125 61 61 27

Frequency bands [Hz] 250 62 62 36 500 61 60 44 1k 58 60 44 2k 55 57 39 4k 54 55 34 8k 45 45 25

Measurement point: 0,172 m/s; 145 Pa

203

Explosion proof centrifugal fans EX


Certified according to ATEX 95 Suitable for use in battery-charging rooms, fume cupboards and similar environments Compact design EX fans can be installed in any position, and their compact design makes them easy to install. These fans are powered by specially manufactured EX motors, and have impellers with forward-curved blades. The fan casing is cast in silumin, and the impeller is manufactured from aluminium. The single-phase fans have a capacitor enclosed in sand, which is approved for EX certification. Explosion proof versions comply with EN 50014, EN 50017, EN 50019, EN 1127- and EN 13463-1. Improved safety in accordance with Ex e q IIB T3. NOTE! EX 140-180 fans are not speed controllable. Motorprotection type MSEX, has to be used in accordance to ATEX certificate. MSEX p. 342 Electrical accessories

Quick selection

1 2

EX 140-4C, 140-4 EX 140-2C


3 2

3 4 5

EX 140-2 EX 180-4C EX 180-4

Explosion proof fans

Technical data
EX Art no. Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Capacitor Motor protection Certificate Wiring diagram p. 391-400 9 9 10 140-4C 1557 V/50 Hz 230 1~ W 113 A 0.63 m3/s 0.154 min-1 1465 C -20... +40 C -20... +40 dB(A) 43 kg 8 F IP 54 8 MSEX 0.4-0.63 140-2C 1559 230 1~ 674 3.00 0.326 2885 -20... +40 -20... +40 49 9.8 F IP 54 25 MSEX 2.5-4.0 140-4 1560 400 3~ 131 0.38 0.162 1465 -20... +40 -20... +40 41 7.3 F IP 54 MSEX 0.25-0.4 140-2 1562 400 3~ 696 1.28 0.327 2890 -20... +40 -20... +40 47 9 F IP 54 MSEX 1.0-1.6 10 SP 03ATEX3103X 9 10 180-4C 1558 230 1~ 185 0.91 0.236 1415 -20... +40 -20... +40 41 8.3 F IP 54 8 MSEX 0.63-1.0 180-4 1561 400 3~ 188 0.43 0.217 1435 -20... +40 -20... +40 42 7.5 F IP 54 MSEX 0.4-1.0

204

3960, 3992, 3962, 3991, 3967, 3965

Explosion proof centrifugal fans


Dimensions
F C B G(4x) L K I

Ventilation accessories

FKX p. 355

E D

IS p. 371

8/ 11

49
/ 58

HC

94

US p. 371

EX 140-2 140-2C 140-4 140-4C 180-4 180-4C

A 92 92 92 92 109 109

B 94 94 94 94 86 86

C 115 115 115 115 110 110

D 105 105 105 105 120 120

E 120 120 120 120 140 140

F 130 130 130 130 125 125

G 6 6 6 6 7 7

H 261 261 261 261 294 294

I 50 50 50

K 103 103 103 103 120 120

L 226 226 226 226 261 261

M 285 285 255 255 255 255

Explosion proof fans

205

Explosion proof centrifugal fans


Performance

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 59 67 50 23 45 19 125 38 54 22

Frequency bands [Hz] 250 47 60 31 500 52 63 43 1k 55 61 43 2k 52 55 46 4k 46 49 41 8k 36 42 32

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 72 79 56 34 63 22 125 52 66 34

Frequency bands [Hz] 250 62 72 42 500 62 73 50 1k 66 72 48 2k 69 73 52 4k 63 65 47 8k 57 61 43

Measurement point: 0,0878 m/s; 135 Pa

Measurement point: 0,161 m/s; 645 Pa

Explosion proof fans

dB(A)
LwA Inlet LwA Outlet LwA Surrounding

Tot 63 60 65 48 23 43 13 125 42 57 23

Frequency bands [Hz] 250 50 58 37 500 50 59 40 1k 58 59 43 2k 50 52 43 4k 44 46 41 8k 35 39 32

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 72 78 54 32 63 21 125 50 67 31

Frequency bands [Hz] 250 62 72 42 500 62 73 47 1k 66 71 47 2k 67 70 50 4k 62 63 46 8k 57 59 42

Measurement point: 0,0786 m/s; 141 Pa

Measurement point: 0,15 m/s; 653 Pa

206

Explosion proof centrifugal fans

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 62 67 48 24 47 23 125 41 57 25

Frequency bands [Hz] 250 52 60 32 500 54 61 43 1k 58 64 44 2k 54 54 40 4k 50 50 37 8k 45 42 31

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 62 70 49 24 52 13 125 47 63 30

Frequency bands [Hz] 250 56 65 36 500 54 63 43 1k 58 61 45 2k 54 54 42 4k 49 48 37 8k 42 42 29

Measurement point: 0,104 m/s; 232 Pa

Measurement point: 0,102 m/s; 200 Pa

Explosion proof fans

207

Explosion proof rectangular duct fans KTEX


In accordance with ATEX directive 94-9 EC Speed controllable Motor protection via cold conductor KTEX fans can be installed in any position and are easy to connect using the DS flexible connections. These fans have impellers with forwardcurved blades and external rotor motors. The casing is manufactured from galvanised sheet steel, with a copper inlet cone. To protect the motor from overheating, these fans have cold conductor with external leads which must be connected to the U-EK230E EX motor protection relay. Explosion proof versions comply with EN 50014, EN 50019, EN 1127-1 and EN 13463-1. Improved safety in accordance with Ex e IIB T3. U-EK 230E EX p. 338 Electrical accessories

R-DK4 KT p. 323

Quick selection

RTRD p. 321

3750, 3752, 3756, 4234, 4245

1 2 3 4 5

KTEX 50-25-4 KTEX 50-30-4 KTEX 60-30-4 KTEX 60-35-4 KTEX 70-40-6

RTRDU p. 321

Ex e-Terminal box 32A p. 339

Explosion proof fans

Min. static pressure as per dotted line Technical data


KTEX Art no. Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Motor protection Certificate Speed control, five step Speed control, five step high/low Wiring diagram p. 391-400 * + U-EK230E EX 50-25-4 1564 V/50 Hz 400 3~ W 490 A 0.85 m3/s 0.467 min-1 1290 C -20... +40 C -20... +40 dB(A) 57 kg 18 F IP 44 U-EK230E EX SP 04ATEX3105X Transformer RTRD 2* Transformer RTRDU 2* 11 50-30-4 1566 400 3~ 900 1.80 0.66 1355 -20... +40 -20... +40 58 23.3 F IP 44 U-EK230E EX SP 03ATEX3103X RTRD 4* RTRDU 4* 11 60-30-4 1568 400 3~ 1300 2.20 0.82 1330 -20... +40 -20... +40 58 32 F IP 44 U-EK230E EX SP 04ATEX3107X RTRD 4* RTRDU 4* 11 60-35-4 1570 400 3~ 2100 3.90 1.01 1380 -20... +40 -20... +40 62 44 F IP 44 U-EK230E EX SP 04ATEX3109X RTRD 7* RTRDU 7* 11 70-40-6 1572 400 3~ 1800 3.70 1.38 840 -20... +40 -20... +40 55 51 F IP 44 U-EK230E EX SP 04ATEX3111X RTRD 4* RTRDU 4* 11

208

Explosion proof rectangular duct fans


Dimensions
E D A 8,0

Ventilation accessories

DS-EX p. 363

FFK p. 357

10,0(8x)

LDR p. 358

8,0
KTEX 50-25-4 50-30-4 60-30-4 60-35-4 70-40-6 A 498 498 598 598 698 B 248 298 298 348 398 C 270 320 320 370 420 D 520 520 620 620 721 E 540 540 640 640 740 F 290 340 340 390 440 G 299 351 366 421 466 H 532 562 642 717 787

Explosion proof fans

209

Explosion proof rectangular duct fans


Performance

Min. static pressure 85 Pa


dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDR 50-25 LwA Inlet 60 55 56 51 36 37 43 46 46 Tot 63 72 72 64 55 46 57 125 66 60 59 Frequency bands [Hz] 250 66 64 57 500 61 66 53 1k 62 67 53 2k 63 64 50 4k 61 62 46 8k 58 58 43 LwA Inlet LwA Outlet dB(A)

Min. static pressure 130 Pa


Tot 63 73 79 65 61 54 48 54 54 125 65 62 56 57 Frequency bands [Hz] 250 64 67 61 49 500 63 70 55 43 1k 67 74 58 36 2k 67 71 53 50 4k 65 70 49 51 8k 61 65 46 50

LwA Surrounding With LDR 50-30 LwA Inlet

Measurement point: 0,288 m/s; 258 Pa

Measurement point: 0,351 m/s; 374 Pa

Explosion proof fans

Min. static pressure 220 Pa


dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDR 60-30 LwA Inlet 62 57 58 48 44 37 51 52 52 Measurement point: 0,36 m/s; 495 Pa Tot 63 75 89 65 57 60 55 125 66 70 60 Frequency bands [Hz] 250 63 75 57 500 64 80 55 1k 68 84 56 2k 68 83 56 4k 66 82 51 8k 63 77 47 LwA Inlet LwA Outlet dB(A)

Min. static pressure 220 Pa


Tot 63 78 85 69 68 59 54 49 59 125 67 68 64 60 Frequency bands [Hz] 250 66 71 59 53 500 66 77 57 49 1k 69 78 60 51 2k 71 77 60 58 4k 74 80 62 64 8k 70 75 57 62

LwA Surrounding With LDR 60-35 LwA Inlet

Measurement point: 0,42 m/s; 586 Pa

210

Explosion proof rectangular duct fans

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDR 70-40 LwA Inlet

Tot 63 71 77 62 63 51 52 42 51 125 58 59 54 51

Frequency bands [Hz] 250 60 65 54 49 500 61 71 54 47 1k 63 69 54 49 2k 63 68 52 53 4k 67 71 54 59 8k 62 66 50 56

Measurement point: 0,582 m/s; 361 Pa

Explosion proof fans

211

Explosion proof centrifugal fans DKEX


In accordance with ATEX directive 94-9 EC Suitable for use in battery-charging rooms, fume cupboards and similar environments Motor protection via cold conductor Speed-controllable DKEX fans can be installed in any position, and their compact design makes them easy to install. These fans have impellers with forward-curved blades and external rotor motors. The casing is manufactured from galvanised sheet steel with a copper inlet cone. To protect the motor from overheating, cold conductor are fitted with external leads which must be connected to the U-EK230E EX motor protection relay. Explosion proof versions comply with EN 50014, 50019, EN 1127-1 and EN 13463-1. Improved safety in accordance with Ex e IIB T3. Electrical accessories

U-EK 230E EX p. 338

R-DK4 KT p. 323

RTRD p. 321

Quick selection RTRDU p. 321


1 2 3 4 5

DKEX 225-4 DKEX 250-4 DKEX 280-4 DKEX 315-4 DKEX 355-6

3734, 3733, 3731, 4231, 4232

Ex e-Terminal box 32A p. 339

Explosion proof fans

Min. static pressure as per dotted line Technical data


DKEX Art no. Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Motor protection Certificate Speed control, five step Speed control, five step high/low Wiring diagram p. 391-400 * + U-EK230E EX 225-4 3965 V/50 Hz 400 3~ W 490 A 0.85 m3/s 0.41 min-1 1305 C -20... +40 C -20... +40 dB(A) 54 kg 12.5 F IP 44 U-EK230E EX SP 04ATEX3106X Transformer RTRD 2* Transformer RTRDU 2* 11 250-4 3966 400 3~ 900 1.80 0.73 1355 -20... +40 -20... +40 59 17.3 F IP 44 U-EK230E EX SP 03ATEX3104X RTRD 4* RTRDU 4* 11 280-4 3967 400 3~ 1300 2.20 0.822 1330 -20... +40 -20... +40 61 24.2 F IP 44 U-EK230E EX SP 04ATEX3108X RTRD 4* RTRDU 4* 11 315-4 3968 400 3~ 2100 3.90 1.04 1380 -20... +40 -20... +40 64 35.2 F IP 44 U-EK230E EX SP 04ATEX3110X RTRD 7* RTRDU 7* 11 355-6 3969 400 3~ 1800 3.70 1.39 840 -20... +40 -20... +40 58 38.6 F IP 44 U-EK230E EX SP 04ATEX3112X RTRD 4* RTRDU 4* 11

212

Explosion proof centrifugal fans


Dimensions Ventilation accessories

USE p. 371
D C E

ISE p. 371
L A G B

DKEX 225-4 250-4 280-4 315-5 355-6

F
A 280 315 357 400 450

B 133 154 169 188 213

C 145 165 180 203 227

D 196 216 230 254 278

E 196 243 248 276 320

F 367 410 453 515 574

G 445 492 547 615 689

Explosion proof fans

213

Explosion proof centrifugal fans


Performance

Min. static pressure 130 Pa


dB(A) LwA Inlet LwA Outlet LwA Surrounding Tot 63 71 76 61 46 45 35 125 55 51 44 Frequency bands [Hz] 250 63 64 54 500 60 68 53 1k 65 72 56 2k 65 68 54 4k 62 67 48 8k 57 64 44 LwA Inlet LwA Outlet dB(A)

Min. static pressure 115 Pa


Tot 63 77 77 66 50 48 41 125 62 53 43 Frequency bands [Hz] 250 67 65 58 500 66 68 55 1k 72 72 62 2k 71 70 59 4k 69 69 56 8k 65 64 48

LwA Surrounding

Measurement point: 0,266 m/s; 290 Pa

Measurement point: 0,461 m/s; 339 Pa

Explosion proof fans

Min. static pressure 230 Pa


dB(A) LwA Inlet LwA Outlet Tot 63 77 79 51 49 48 125 63 57 52 Frequency bands [Hz] 250 66 67 59 500 65 71 55 1k 72 73 63 2k 71 72 62 4k 68 71 58 8k 64 66 57 LwA Inlet LwA Outlet dB(A)

Min. static pressure 250 Pa


Tot 63 80 83 71 52 51 48 125 69 65 52 Frequency bands [Hz] 250 67 71 58 500 68 76 59 1k 72 75 65 2k 73 74 64 4k 75 78 66 8k 71 72 60

LwA Surrounding 68

LwA Surrounding

Measurement point: 0,411 m/s; 500 Pa

Measurement point: 0,509 m/s; 595 Pa

214

Explosion proof centrifugal fans

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 76 78 65 49 47 37 125 62 60 47

Frequency bands [Hz] 250 62 65 53 500 67 71 59 1k 68 70 59 2k 68 69 58 4k 71 74 59 8k 66 68 51

Measurement point: 0,641 m/s; 358 Pa

Explosion proof fans

215

Explosion proof roof fans DVEX


In accordance with ATEX directive 94-9 EC Speed-controllable Motor protection via cold conductor The DVEX models have impellers with backward-curved blades and external rotor motors. The casing is made from aluminium and the base frame from galvanised steel, with a copper inlet cone. To protect the motor from overheating these fans have cold conductor with external leads which must be connected to the U-EK230E EX motor protection relay. Improved safety in accordance with Ex e IIB T3. Certified according to ATEX. U-EK 230E EX p. 338 Electrical accessories

R-DK4 KT p. 323

RTRD p. 321 Quick selection

4087, 4076, 4081, 3931

4063, 4089, 5584

1 2 3 4

DVEX 315D4 DVEX 355D4 DVEX 400D4 DVEX 450D4

1 2

DVEX 560D6 DVEX 630D6

RTRDU p. 321

Ex e-Terminal box 32A p. 339

Explosion proof fans

Technical data
DVEX Art no Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 4/10 m Weight Insulation class, motor Enclosure class, motor Motor protection Certificate Speed control, five step Speed control, five step high/low Wiring diagram p. 391-400 315D4 32813 V/50 Hz 400 3~ W 120 A 0.23 m3/s 0.411 min-1 1340 C -20... +40 C -20... +40 dB(A) 44/36 kg 18 F IP 44 U-EK230E EX SP 07ATEX3129X Transformer RTRD 2* Transformer RTRDU 2* 11 355D4 32814 400 3~ 260 0.47 0.689 1340 -20... +40 -20... +40 49/41 28 F IP 44 U-EK230E EX SP 07ATEX3130X RTRD 2* RTRDU 2* 11 400D4 32815 400 3~ 390 0.76 0.847 1350 -20... +40 -20... +40 54/46 29 F IP 44 U-EK230E EX SP 07ATEX3131X RTRD 2* RTRDU 2* 11 450D4 32816 400 3~ 720 1.42 1.26 1360 -20... +40 -20... +40 57/49 40 F IP 44 U-EK230E EX SP 07ATEX3132X RTRD 2* RTRDU 2* 11

* + U-EK230E EX. NB! When using the RTRD or RTRDU together with an EX motor protection type U-EK230E EX, the two terminals in the transformer marked TK must be bridged.

216

Explosion proof roof fans


dIMENSIONS
F A C
M 20

Ventilation accessories

ASF p. 375

ASK p. 380
E K I (4x)

ASS-EX p. 381
DVEX 315D4 355D4 400D4 450D4 560D6 630D6 A 560 720 720 900 B 382 442 442 517 C 470 618 618 730 955 955 D 192 226 255 289 364 410 E 330 450 450 535 750 750 F 146 199 199 237 293 293 I 12 12 12 12 12 12 K 406 566 566 636 939 939 L 304 466 466 490 M 330 390 390 465 560 560

BTG p. 374

1150 1150

Shadowed area not for sizes 560, 630

FDS p. 374

FTG p. 371

SSD p. 374

TDA p. 371

Explosion proof fans

VKS-EX p. 380
DVEX Art no Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Motor protection Certificate Speed control, five step Speed control, five step high/low Wiring diagram p. 391-400 560D6 32818 V/50 Hz 400 3~ W 620 A 1.23 m3/s 1.62 min-1 900 C -20... +40 C -20... +40 dB(A) 52/44 kg 62 F IP 44 U-EK230E EX SP 07ATEX3134X Transformer RTRD 2* Transformer RTRDU 2* 11 630D6 32819 400 3~ 1070 2.15 2.20 880 -20... +40 -20... +40 55/47 78 F IP 44 U-EK230E EX SP 07ATEX3135X RTRD 4* RTRDU 4* 11

* + U-EK230E EX. NB! When using the RTRD or RTRDU together with an EX motor protection type U-EK230E EX, the two terminals in the transformer marked TK must be briged.

217

Explosion proof roof fans


Performance

dB(A) LwA Inlet LwA Outlet

Tot 63 64 67 48 48 125 53 53

Frequency bands [Hz] 250 56 56 500 60 63 1k 55 63 2k 53 59 4k 49 52 8k 37 40

dB(A) LwA Inlet LwA Outlet With TG 540-800 LwA Inlet

Tot 63 68 72 61 50 51 50 125 58 58 55

Frequency bands [Hz] 250 61 64 55 500 63 67 54 1k 60 67 48 2k 58 63 50 4k 52 55 47 8k 43 48 38

Measurement point: 0,221 m/s; 162 Pa

Measurement point: 0,417 m/s; 220 Pa

Explosion proof fans

dB(A) LwA In let LwA Outlet With TG 640-800 LwA Inlet

Tot 63 72 77 67 58 57 57 125 62 62 60

Frequency bands [Hz] 250 66 69 62 500 67 72 60 1k 64 72 55 2k 62 67 56 4k 55 59 51 8k 47 50 43

dB(A) LwA Inlet LwA Outlet With TG 640-800 LwA Inlet

Tot 63 76 80 71 58 58 57 125 64 67 62

Frequency bands [Hz] 250 71 74 67 500 71 75 64 1k 68 75 59 2k 66 70 60 4k 58 62 54 8k 52 53 48

Measurement point: 0,448 m/s; 275 Pa

Measurement point: 0,699 m/s; 360 Pa

218

Explosion proof roof fans

dB(A) LwA Inlet LwA Outlet With TG 940-1230 LwA Inlet

Tot 63 70 75 66 58 57 58 125 59 61 57

Frequency bands [Hz] 250 66 69 62 500 63 71 55 1k 64 70 57 2k 59 63 54 4k 52 57 48 8k 45 55 41

dB(A) LwA Inlet LwA Outlet With TG 940-1230 LwA Inlet

Tot 63 73 78 68 53 53 53 125 64 65 62

Frequency bands [Hz] 250 69 71 65 500 66 74 58 1k 64 71 57 2k 61 65 56 4k 60 64 56 8k 54 57 50

Measurement point: 0,962 m/s; 224 Pa

Measurement point: 1,05 m/s; 318 Pa

Explosion proof fans

219

Explosion proof roof fans DVV-EX


In accordance with ATEX directive 94-9 EC Speed-controllable via frequency converter Roof fans DVV-Ex are designed to exhaust potentially explosive atmospheres (mixtures of air and inflammables such as gases and steam) from explosion hazardous areas. The DVV-Ex fans have impellers with backward-curved blades and IEC motor in explosion protection flameproof enclosure, Ex d. The casing is manufactured from seawaterresistant aluminium and the base frame from galvanised steel, with a copper inlet cone. Suitable for exhaust from zones 1 or 2, field of application II, for gases of groups IIA and IIB and temperature classes T1 to T4. The fans are classified to category 2G. Terminal box in explosion protection increased safety, Ex e is mounted on casing. To enable protection of motor from overheating these fans have serial built-in thermistors (PTC) with external leads (connection to U-EK230E EX motor protection relay as accessories possible). On request fan can be factory fitted with sound attenuator on outlet (as DVVI-Ex fan). Electrical accessories

U-EK 230E EX p. 338

Quick selection

8862,8863, 8864, 8417, 8865, 8448, 8867

1 2

DVV-EX 560D4 DVV-EX 560D6

3 4 5 6

DVV-EX 630D4 DVV-EX 630D4-K DVV-EX 630D6 DVV-EX 60D6-K

1 2 3 4 5 6

DVV-EX 800D6 DVV-EX 800D6-K DVV-EX 800D8 DVV-EX 800D8-K DVV-EX 1000D6 DVV-EX 1000D8

5 2 6

Explosion proof fans

Technical data
DVV-EX Art no Voltage/Frequency Power Current Starting current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 4/10 m Weight Insulation class, motor Enclosure class, motor Certificate Wiring diagram p. 391-400 560D4 30841 V/50 Hz 400 3~ W 1500 A 3.35 A 17.4 m3/s 2.64 min-1 1415 C 40 C 40 dB(A) 69/61 kg 72 F IP 55 Ex d 13b Y 560D6 30844 400 3~ 750 2.10 7.80 1.81 915 40 40 60/52 69 F IP 55 Ex d 13b Y 630D4 30852 400 3~ 5500 10.8 55.1 5.36 1435 40 40 75/69 161 F IP 55 Ex d 13b D 630D4-K 30847 400 3~ 3000 6.5 32.5 3.5 1415 40 40 71/63 120 F IP 55 Ex d 13b Y 630D6 30854 400 3~ 2200 5.0 30.5 3.36 960 40 40 64/58 133 F IP 55 Ex d 13b Y 630D6-K 30850 400 3~ 1100 3.0 12.3 2.28 915 40 40 61/53 107 F IP 55 Ex d 13b Y

SIQ 06 ATEX 236X(PPC 00-31780)

220

8413, 8300, 8412, 8308, 8200, 8201

Explosion proof roof fans


Dimensions
A

Ventilation accessories

VKSV-EX p. 380

ASFV p. 384

ASSV-EX p. 383

FDVE/F p. 382

E F
DVV-EX 560D4/D6 630D4/D4-K/D6/D6-K 800D6/D6-K/D8/D8-K 1000D6/D8 A 808 B 750 C 20 40 40 70 D 438 541 674 751 E 600 880 880 F 706 990 990 G 12XM8 12XM8 H 14 18

SSV/F p. 382

SSVE/F p. 377

1100 958 1272 1175 1500 1350

16xM10 18

1040 1154 16xM10 18

ASK/F p. 380

Explosion proof fans

DVV-EX Art no Voltage/Frequency Power Current Starting current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 4/10 m Weight Insulation class, motor Enclosure class, motor Certificate Wiring diagram p. 391-400

800D6 30856 V/50 Hz 400 3~ W 5500 A 11.80 A 72 m3/s 7.08 min-1 955 C 40 C 40 dB(A) 72/66 kg 205 F IP 55 Ex d 13b D

800D6-K 30859 400 3~ 2200 5.0 30.5 5.0 960 40 40 66/60 171 F IP 55 Ex d 13b Y

800D8 30858 400 3~ 2200 5.5 23.7 5.28 710 40 40 66/57 189 F IP 55 Ex d 13b Y

800D8-K 30861 400 3~ 1100 3.25 12.4 3.92 695 40 40 59/53 157 F IP 55 Ex d 13b Y

1000D6 30862 400 3~ 11000 23.5 141 12.4 965 40 40 73/66 370 F IP 55 Ex d 13b D

1000D8 30863 400 3~ 5500 13.4 64.3 9.44 715 40 40 66/58 348 F IP 55 Ex d 13b D

SIQ 06 ATEX 236X(PPC 00-31780)

221

Explosion proof roof fans


Performance

DVV-EX 560D4 dB(A) LwA Inlet Tot 88 Frequency bands [Hz] 63 61 63 LwA Surrounding 90 125 73 75 250 81 83 500 82 84 1k 81 83 2k 79 81 4k 76 78 8k 68 70

DVV-EX 630D4 dB(A) LwA Inlet LwA Surrounding Tot 97 98 Frequency bands [Hz] 63 68 68 125 79 87 250 91 88 500 90 91 1k 92 91 2k 87 91 4k 81 89 8k 72 79

Measurement point: 2,1m/s; 310 Pa

Measurement point: 4,58 m/s; 370 Pa

DVV-EX 560D6 dB(A) LwA Inlet LwA Surrounding Tot 81 83 Frequency bands [Hz] 63 58 60 125 67 69 250 73 75 500 77 79 1k 72 74 2k 70 72 4k 68 70 8k 56 58

DVV-EX 630D6 dB(A) LwA Inlet LwA Surrounding Tot 90 92 Frequency bands [Hz] 63 67 69 125 76 78 250 82 84 500 86 88 1k 81 83 2k 79 81 4k 77 79 8k 65 67

Measurement point: 1,50m/s; 125 Pa

Measurement point: 2,3 m/s; 290 Pa

DVV-EX 560D8 dB(A) Tot 76 78 Frequency bands [Hz] 63 LwA Inlet LwA Surrounding 58 60 125 64 66 250 67 69 500 71 73 1k 68 70 2k 68 70 4k 63 65 8k 52 54

Explosion proof fans

Measurement point: 1,20 m/s; 50 Pa

222

Explosion proof roof fans

DVV-EX 630D4-K dB(A) LwA Inlet LwA Surrounding Tot 92 94 Frequency bands [Hz] 63 65 67 125 77 79 250 85 87 500 86 88 1k 85 87 2k 83 85 4k 80 82 8k 72 74

DVV-EX 800D6 dB(A) LwA Inlet LwA Surrounding Tot 93 95 Frequency bands [Hz] 63 70 72 125 79 81 250 85 87 500 89 91 1k 84 86 2k 82 84 4k 80 82 8k 68 70

Measurement point: 2,80 m/s; 400 Pa

Measurement point: 4,2 m/s; 600 Pa

DVV-EX 630D6-K dB(A) LwA Inlet LwA Surrounding Tot 82 84 Frequency bands [Hz] 63 58 60 125 69 71 250 71 73 500 78 80 1k 73 75 2k 72 74 4k 68 70 8k 55 57

DVV-EX 800D8 dB(A) LwA Inlet LwA Surrounding Tot 82 84 Frequency bands [Hz] 63 64 66 125 70 72 250 73 75 500 77 79 1k 74 76 2k 74 76 4k 69 71 8k 58 60

Measurement point: 1,0 m/s; 350 Pa

Measurement point: 2,50 m/s; 330 Pa

Explosion proof fans

223

Explosion proof roof fans

DVV-EX 800D6-K dB(A) LwA Inlet LwA Surrounding Tot 84 86 Frequency bands [Hz] 63 60 62 125 71 73 250 73 75 500 80 82 1k 75 77 2k 74 76 4k 70 72 8k 57 59

DVV-EX 1000D6 dB(A) LwA Inlet LwA Surrounding Tot 92 94 Frequency bands [Hz] 63 69 71 125 78 80 250 84 86 500 88 90 1k 83 85 2k 81 83 4k 79 81 8k 67 69

Measurement point: 4,00 m/s; 280 Pa

Measurement point: 6,94 m/s; 650 Pa

DVV-EX 800D8-K dB(A) LwA Inlet LwA Surrounding Tot 75 77 Frequency bands [Hz] 63 58 60 125 64 66 250 66 68 500 70 72 1k 68 70 2k 68 70 4k 60 62 8k 49 51

DVV-EX 1000D8 dB(A) LwA Inlet LwA Surrounding Tot 84 86 Frequency bands [Hz] 63 66 68 125 72 74 250 75 77 500 79 81 1k 76 78 2k 76 78 4k 71 73 8k 60 62

Measurement point: 3,10 m/s; 150 Pa

Measurement point: 6,11 m/s; 310 Pa

Explosion proof fans

224

Explosion proof roof fans

Explosion proof fans

225

Explosion proof axial fans AW-EX


In accordance with ATEX directive 94-9 EC Speed-controllable Motor protection via cold conductor The AW-EX fans have speed controllable external rotor motors. The fans have a square plate for wall mounting and are painted in standard black. The casing and impeller is manufactured from sheet steel. To protect the motor from overheating, cold conductors are fitted with external leads which must be connected to the U-EK230E EX motor protection relay. The AW-Ex fan motor is approved according to ATEX. Improved safety in accordance with Ex e IIB T3 or T4. Accessories for Ex-fans only on request. U-EK 230E EX p. 338 Electrical accessories

R-DK4 KT p. 323

RTRD p. 321 Quick selection

1 2 3 4

AW 355D4-2-EX AW 420D4-2-EX AW 550D6-2-EX AW 650D6-2-EX

5398, 5401, 5408, 5409

RTRDU p. 321

Ex e-Terminal box 32A p. 339

Explosion proof fans

Technical data
AW Art no Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Motor protection Certificate Speed control, five step Speed control, five step high/low Wiring diagram p. 391-400 * + U-EK230E EX 355 D4-2-EX 5969 V/50 Hz 400 3~ W 286 A 0.27 m3/s 0.694 min-1 1420 C 40 C 40 dB(A) 62 kg 9 F IP 44 U-EK230E EX ZELM 05 ATEX0279X Transformer RTRD 2* Transformer RTRDU 2* 19 420 D4-2-EX 5970 400 3~ 536 0.943 1.23 1269 40 40 69 10 F IP 44 U-EK230E EX ZELM 05 ATEX0279X RTRD 2* RTRDU 2* 19 550 D6-2-EX 5971 400 3~ 579 1.15 1.84 697 40 40 67 13 F IP 44 U-EK230E EX ZELM 05 ATEX0279X RTRD 2* RTRDU 2* 19 650 D6-2-EX 5972 400 3~ 1077 1.78 3.04 790 40 40 72 20 F IP 44 U-EK230E EX ZELM 05 ATEX0279X RTRD 2* RTRDU 2* 19

226

Explosion proof axial fans


Dimensions

A B C D 1,5

AW 355 D4-2-EX 420 D4-2-EX 550 D6-2-EX 650 D6-2-EX

A 138 138 138 162

B 48 71 72 66

C 70 70 55 78

D 16 16 18 18

E 350.5 419 551 651

F 356 426 558 658

G 125 125 143 161

H 12 14.5 14.5 14.5

I 385 460 610 730

J 423 503 650 770

Explosion proof fans

227

Explosion proof plate axial fans


Performance

dB(A) LwA Inlet LwA Outlet

Tot 63 69 69 36 36 125 56 56

Frequency bands [Hz] 250 61 61 500 60 60 1k 64 64 2k 62 62 4k 55 55 8k 46 46

dB(A) LwA Inlet LwA Outlet

Tot 63 76 76 43 43 125 64 64

Frequency bands [Hz] 250 68 68 500 69 69 1k 71 71 2k 70 70 4k 63 63 8k 54 54

Measurement point: 0,47 m/s; 76 Pa

Measurement point: 0,84 m/s; 96 Pa

Explosion proof fans

4 3

dB(A) LwA Inlet LwA Outlet

Tot 63 74 74 58 58 125 59 59

Frequency bands [Hz] 250 66 66 500 66 66 1k 71 71 2k 67 67 4k 59 59 8k 50 50

dB(A) LwA Inlet LwA Outlet

Tot 79 79

Frequency bands [Hz] 63 63 63 125 66 66 250 69 69 500 72 72 1k 74 74 2k 73 73 4k 64 64 8k 57 57

Measurement point: 1,32 m/s; 56 Pa

Measurement point: 2,2 m/s; 73 Pa

228

Explosion proof plate axial fans Reference

Explosion proof fans

Project: Choren Industries Type of Building: Choren is an internationally leading supplier of technologies for the production of synthesis gas from carbonaceous solids. City/Country: Freiberg (Sachsen), Germany Products/Solution: Explosion proof roof fans, type DVV-EX 800 Explosion proof axial fans, AW 200-EX

229

Explosion proof axial fans AXC-EX


Aerofoil impeller with adjustable pitch angle. Die cast aluminium hub and blades. Casing, hot dip galvanized steel, to EN ISO 1641. Aluminium anti-spark ring. Spun flanges for high rigidity, to Eurovent 1/2. Three phase motors, IP55, insulation class F, in accordance with EN 60034, IEC 85. Supplied with terminal box Ex e mounted at the outer side of the casing. Admissible ambient temperatures from -20C to +40C, other temperatures on request. Inspection hole to verify correct direction of rotation. The AXC-EX range of long cased medium pressure axial fans is available in sizes 315 up to 900 mm impeller diameter. The possibility to set the pitch angles at the factory offers a wide performance and maximum flexibility to match precisely individual airflow requirements. Attention: it is not permissible to change the pitch angle at site, this would invalidate the certification. The stock range offers a standard selection with maximum airflow for the installed motor power. The fans can be used for zones 1 or 2, field of application II, for gases of groups IIA, IIB, and IIC and temperature classes T1 to T4. The fans are classified to category 2G. The fans are certified under Sira 07ATEX6341X. The Ex d motors are equipped with PTC thermistors for optimum motor protection. The motor is speed controllable by frequency converter. Electrical accessories

U-EK 230E EX p. 338

Explosion proof fans

Technical data
AXC-EX Art no Voltage/Frequency Max. power load Power Max current Current Max air flow R.p.m. Max temp. of transported air Weight Insulation class, motor Enclosure class, motor Certificate Wiring diagram p. 391-400 44 44 44 44 355-7 32-4 33007 V/50 Hz 400 3~ kW 0.37 W 225 A A 0.837 m3/s 0.92 min-1 1471 C 40 kg 40 F IP 55 400-7 32-4 33008 400 3~ 0.37 337 0.845 1.28 1461 40 75 F IP 55 450-7 24-2 33001 400 3~ 2.2 2532 4.8 4.81 2.81 2924 40 63 F IP 55 450-7 32-4 33009 400 3~ 0.55 473 1.6 1.16 1.8 1441 40 55 F IP 55 500-9 16-2 33002 400 3~ 3.0 3396 7.3 5.61 2.78 2905 40 82 F IP 55 44 500-9 22-4 33010 400 3~ 0.55 546 1.6 1.21 1.75 1428 40 65 F IP 55 44 SIRA 07ATEX6341X 44 44 44 44 500-9 26-2 33003 400 3~ 5.5 4753 12 7.87 4.03 2945 40 130 F IP 55 500-9 28-4 33011 400 3~ 0.75 662 2.0 1.55 2.23 1439 40 65 F IP 55 560-9 18-2 33004 400 3~ 5.5 5502 12 8.76 4.52 2932 40 155 F IP 55 560-9 20-4 33012 400 3~ 0.75 779 2 1.68 2.46 1428 40 90 F IP 55

230

Explosion proof axial fans


Dimensions
A

Ventilation accessories
I

ESD-F p. 388

C D

GFL-AR/AXC p. 389

E F
AXC-EX 355 400 450 500 560 630 710 800 900 A 400 400 480 480 700 700 540 700 700 B 438 484 534 584 664 734 812 904 1004 C 359 401 450 504 565 634 711 797 894 D 346 388 436 490 551 618 694 778 869 E 395 438 487 541 605 674 751 837 934 F 505 552 605 659 730 803 883 973 1075 H 9.5 9.5 9.5 9.5 12 12 12 12 12 I 8x45 12x30 12 x 30 12 x 30 16 x 22.5 16 x 22.5 16 x 22.5 24 x 15 24 x 15

EV-EX/AXC p. 387

FSD p. 386

MFA-AR/AXC p. 386

SG AR/AXC p. 385

Cable gland set p. 386

Explosion proof fans

AXC-EX Art no Voltage/Frequency Max. power load Power Max current Current Max air flow R.p.m. Max temp. of transported air Weight Insulation class, motor Enclosure class, motor Certificate Wiring diagram p. 391-400

560-9 24-2 33005 V/50 Hz 400 3~ kW 7.5 W 6977 A 15 A 11.5 m3/s 5.43 min-1 2944 C 40 kg 155 F IP 55 44

560-9 26-4 33013 400 3~ 1.1 1088 2.8 2.04 3.18 1434 40 93 F IP 55 44

630-9 16-2 33006 400 3~ 7.5 7862 15 12.6 6.18 2936 40 155 F IP 55 44

630-9 18-4 33014 400 3~ 1.1 1156 2.8 2.15 3.44 1429 40 95 F IP 55 44

630-9 30-4 33015 400 3~ 3.0 2181 6.83 4.69 5.14 1465 40 105 F IP 55 44

710-9 30-4 33016 400 3~ 4.0 3360 8.2 6.03 6.7 1457 40 130 F IP 55 44

800-9 18-4 33017 400 3~ 4.0 2716 8.2 5.27 6.57 1467 40 130 F IP 55 44

800-9 28-4 33018 400 3~ 7.5 5339 16.5 11.8 9.1 1480 40 158 F IP 55 44

900-10 18-4 33019 400 3~ 7.5 6212 16.5 12.5 10 1476 40 255 F IP 55 44

900-10 26-4 33020 400 3~ 11 11964 23 16.7 12.4 1479 40 330 F IP 55 44

SIRA 07ATEX6341X

231

Explosion proof axial fans


Quick selection

8106, 8040, 7858, 7977, 7984

1 2 3

AXC-EX 355-7/32-4 AXC-EX 400-7/32-4 AXC-EX 450-7/24-2

4 5

AXC-EX 450-7/32-4 AXC-EX 500-9/16-2

1 2 3 4 5

AXC-EX 500-9/22-4 AXC-EX 500-9/26-2 AXC-EX 500-9/28-4 AXC-EX 560-9/18-2 AXC-EX 560-9/20-4

5 3

1
1 2 4

dB(A) LwA Inlet/Outlet AXC-EX 355-7/32-4 400-7/32-4 450-7/24-2 450-7/32-4 500-9/16-2

Tot 63 74 77 96 82 100 69 72 91 77 95 125 68 71 86 76 90

Frequency bands [Hz] 250 69 72 89 77 93 500 68 71 91 76 95 1k 67 70 88 75 93 2k 64 67 88 72 92 4k 59 62 84 67 88 8k 53 56 78 61 82

dB(A) LwA Inlet/Outlet AXC-EX 500-9/22-4 500-9/26-2 500-9/28-4 560-9/18-2 560-9/20-4

Tot 63 86 102 87 106 91 81 97 82 101 86 125 80 92 81 96 85

Frequency bands [Hz] 250 81 95 82 99 86 500 80 97 81 101 85 1k 79 95 80 99 84 2k 76 94 77 98 81 4k 71 90 72 94 76 8k 65 84 66 88 70

7994, 7997, 8003, 8005, 8006

1 2

AXC-EX 560-9/24-2 AXC-EX 560-9/26-4 AXC-EX 630-9/16-2

4 5

AXC-EX 630-9/18-4 AXC-EX 630-9/30-4

1 2 3

AXC-EX 710-9/30-4 AXC-EX 800-9/18-4 AXC-EX 800-9/28-4

4 5

AXC-EX 900-10/18-4 AXC-EX 900-10/26-4

Explosion proof fans

2 1 2 4 5 3 1 3 4 5

dB(A) LwA Inlet/Outlet AXC-EX 560-9/24-2 560-9/26-4 630-9/16-2 630-9/18-4 630-9/30-4

Tot 63 108 93 111 96 99 103 88 106 91 94 125 98 87 101 90 93

Frequency bands [Hz] 250 101 88 104 91 94 500 103 87 106 90 93 1k 101 86 104 89 92 2k 100 83 103 86 89 4k 96 78 99 81 84 8k 90 72 93 75 78

dB(A) LwA Inlet/Outlet AXC-EX 710-9/30-4 800-9/18-4 800-9/28-4 900-10/18-4 900-10/26-4

Tot 63 93 97 100 101 104 88 92 95 91 94 125 87 91 94 89 97

Frequency bands [Hz] 250 88 92 95 95 99 500 87 91 94 96 97 1k 86 90 93 94 96 2k 83 87 90 91 92 4k 78 82 85 86 86 8k 72 76 79 80 80

232

8009, 8030, 8035, 8032, 8020

7987, 7978, 7985, 8004, 7986

Explosion proof axial fans

Explosion proof fans

233

Explosion proof bifurcated axial fans AXCBF-EX


Aerofoil impeller with adjustable pitch angle Die cast aluminium hub and blades Casing, hot dip galvanized steel, to EN ISO 1641 Aluminium anti-spark ring Spun flanges for high rigidity, to Eurovent 1/2 standard Single and three phase motors, IP55, insulation class F, in accordance with EN 60034, IEC 85. Admissible ambient temperatures from -20C to +40C, other temperatures on request With motor outside the airstream Electrical accessories

U-EK 230E EX p. 338

Ex e-Terminal box 32A p. 339

The Systemair AXCBF-EX range of bifurcated medium pressure axial fans has been developed for applications with an atmosphere which would either require special motors or reduce the lifetime of a standard motor. The Ex d motors of AXCBF-EX are out of the airstream. Available in sizes from 250 up to 800 mm impeller diameter. The stock range offers a stand-

ard selection with maximum airflow for the installed motor power. The fans can be used for zones 1 or 2, field of application II, for gases of groups IIA, IIB and IIC and for temperature classes T1 to T4. The fans are classified to category 2G. The fans are certified under Sira 07ATEX6341X. The Ex d motors are equipped with PTC thermistors for optimum motor protection. The motor

is speed controllable by frequency converter. AXCBF-EX bifurcated axial fan casings are heavy gauge, hot dip galvanized, with spun flanges for high rigidity. The motor compartment allows easy access to the motor terminal box for wiring. Single or three phase B3 foot mounted motors, totally enclosed and fan cooled.

Quick selection

8929, 7831, 7832, 7827, 7833

1 2 3 4 5

AXCBF-EX 250-6/28-2 AXCBF-EX 250-6/28-4 AXCBF-EX 315-7/30-2 AXCBF-EX 315-7/32-4 AXCBF-EX 400-7/22-2

1 2 3 4 5

AXCBF-EX 400-7/32-4 AXCBF-EX 500-9/18-2 AXCBF-EX 500-9/30-4 AXCBF-EX 630-9/26-4 AXCBF-EX 800-9/18-4

Explosion proof fans

Technical data
AXCBF-EX Art no Voltage/Frequency Max. power load Power Max current Current Max air flow R.p.m. Max temp. of transported air Weight Insulation class, motor Enclosure class, motor Certificate Wiring diagram p. 391-400 45 45 250-6/28-2 33021 V/50 Hz 400 3~ kW 0.37 W 309 A 1.1 A 0.79 m3/s 0.463 min-1 2916 C 40 kg 30 F IP 55 250-6/28-4 33025 400 3~ 0.25 93.4 0.8 0.563 0.225 1487 40 30 F IP 55 315-7/30-2 33022 400 3~ 0.75 693 1.9 1.43 0.911 2885 40 72 F IP 55 SIRA 07ATEX6341X 45 45 45 315-7/32-4 33026 400 3~ 0.25 155 0.8 0.609 0.459 1476 40 65 F IP 55 400-7/22-2 33023 400 3~ 2.20 1911 4.8 3.16 1.71 2918 40 64 F IP 54

234

7826, 8041, 7834, 7846, 8039

Explosion proof bifurcated axial fans


Dimensions Ventilation accessories

22.5

H
FSD p. 386

B C D E

MFA-AXCBF p. 388

F
AXCBF-EX 250 315 400 500 short version 500 long version A 535 535 625 660 710 B 448 452 585 695 695 C 328 385 480 590 590 D 250 320 401 504 504 E 238 308 388 490 490 F 302 355 450 560 560 H I 10 10 10 12 12 8 x 45 8 x 45 8 x 45 12 x 30 12 x 30

EV-EX/AXC p. 387

GFL-AR/AXC p. 389

B C D

Explosion proof fans

AXCBF-EX 630 800

A 790 880

B 728 890

C 634 797

D 618 778

E 690 860

H 12 12

I 12 x 30 16 x 22,5

AXCBF/EX Art no Voltage/Frequency Max. power load Power Max current Current Max air flow R.p.m. Max temp. of transported air Weight Insulation class, motor Enclosure class, motor Certificate Wiring diagram p. 391-400

400-7/32-4 33027 V/50 Hz 400 3~ kW 0.55 W 444 A 1.6 A 1.1 m3/s 1.08 min-1 1444 C 40 kg 58 F IP 55 45

500-7/18-2 33024 400 3~ 2.2 3054 4.8 4.78 2.71 2840 40 85 F IP 55 45

500-7/30-4 33028 400 3~ 1.1 863 2.8 1.85 1.85 1450 40 77 F IP 55 SIRA 07ATEX6341X 45

630-9/26-4 33029 400 3~ 2.2 2187 5.25 4.27 3.4 1459 40 112 F IP 55 45

800-9/18-4 33030 400 3~ 4.0 3403 8.2 6.02 5.88 1457 40 185 F IP 55 45

235

Smoke extract fans


Systemair is ISO 9001 approved. The Systemair quality is regularly monitored by TV Sd. Warranty Systemair offers a three year warranty on all AXC (B) and AXR (B) fan models. The Systemair warranty conditions apply. Accessories Adapting pieces and bends for duct connection, exhaust ducts for installation into the wall.

300C 120min

400C 120min

600C 120min

General
Fire develops smoke and heat. Within buildings these two factors represent a substantial danger for human beings, animals and the inventory. Constantly rising temperatures might lead to a so-called flash-over, where the fire spreads like an explosion. Buildings must be designed in a way that spreading of smoke and flames in case of a fire can be kept as small as possible. Escape routes have to be kept free of smoke to a largest possible extent, and fire fighting routes for the fire brigade have to be created. Contrary to natural smoke outlets (i.e. roof openings), mechanical smoke and heat extract systems immediately provide full capacity. Mechanical smoke and heat extract systems are particularly important for: High rooms without windows Underground floors and rooms Buildings with a constantly high wind load Large rooms with a high fire load Rooms with sprinkler systems, working against the thermal lift.

Centrifugal fans KBR/F


KBR/F is suitable for dual purpose installations (standard installations in ambient temperature and smoke extract). For standard applications up to 120C continuous operation. Casing Manufactured from galvanised steel. For installation outside the fire zone. Motor IEC motor in efficiency class IE2. Impellers Backward curved impellers manufactured from galvanized steel.

Roof fans DVV, F400-F600


Casing The base frame is manufactured from galvanized steel, the fan casing from aluminium (AlMg3) respectively alu zinc steel sheet. Motor and motor cooling Capsulated and insulated IEC standard motors outside the airstream, insulation class F, protection class IP54 resp IP55. Motor cooling through a cooling duct, in negative pressure system. Impellers Impellers with backward curved blades, F400 from galvanized steel, F600 from stainless steel. Dynamically balanced in accordance with DIN ISO 1940-1, grade Q6.3. Accessories Wide range of accessories for all types. Terminal box Mounted at the cooling duct. DVV fans are also available as DVV/120 fans for continuous exhaust of air up to 120C. The characteristics and data (with exception weight) are the same as for DVV/F range. Details are available in online catalogue.

Axial fans F300


Casing Casing manufactured from galvanized steel. Terminal box F600 in the cooling duct, F300/F400 at the outer side of the fan casing, mounted on a bracket. Motor IEC high temperature motor in F600 300 or 400C/120 min, insulation class F or H, single or two speeds. F600 version with capsulated motors. Impellers Statically and dynamically balanced in accordance with DIN ISO 1940-1, grade Q6.3.

Systemair range
Systemair offers different types of smoke and heat extract fans: Centrifugal roof fans, centrifugal wall/duct fans and axial fans. All fans are approved for dual purpose ventilation, i.e. for normal daily ventilation and for emergency ventilation in case of a fire.

Smoke extract fans

Multibox MUB/F
Casing Steel frame and double skin panels from galvanized steel, 20 mm rock wool insulation. Motor High temperature IEC motor for 400C/120 min. Impeller Impellers with backward curved blades.

Wall fans WVA/WVI


Casing Sturdy welded structure. Surface painted in RAL 7032. WVA for mounting outside fire zone, on facade of building, with motor downwards. WVI for mounting inside fire zone, on outer wall, with motor downwards. WVI needs cooling air supply through the wall. Motors and motor cooling IEC standard motor, insulation class F, protection class IP54 resp. IP55. Single or two speeds. WVI has connection for duct (available as accessory) for cooling air supply in negative pressure system. Impellers Impellers with backward curved blades, F400 from galvanized steel, F600 from stainless steel. Dynamically balanced in accordance with DIN ISO 1940-1; Q6.3.

Typical applications
In mechanical smoke and heat extract systems installed in shopping centres, airports, industrial buildings, big cinemas and theatres, warehouses etc. For industrial process air with increased temperatures. Car park ventilation.

Certified in accordance with EN 12101-3


Systemair smoke and heat extract fans have been certified in accordance with EN 12101-3. CE certification in accordance with EN 12101-3, 2002-06 by the TUV Sd, Munich.

236

Smoke extract fans

KBR/F . . . . . . . . . . . . . . . . . 238 Smoke extract fans: up to 1.97 m3/s, 3 phase.

DVG-V, H 400D4V/400 . . . . 256 Smoke extract fans: up to 3.82 m3/s, 3 phase.

400C 120min

400C 120min

DVV/F . . . . . . . . . . . . . . . . . 244 Smoke extract roof fans: up to 14.6 m3/s, 3 phase.

MUB/F. . . . . . . . . . . . . . . . . 260 Smoke extract axial fans: 300C/2h, up to 19.16 m3/s, 3 phase, EN12101-3.

DVG/F . . . . . . . . . . . . . . . . . 250 Smoke extract roof fans 400C/2h: up to 7,5 m3/s, 3 phase.

400C 120min

600C 120min

AXC(B) . . . . . . . . . . . . . . . . . 266 Smoke extract fan for wall mounting, up to 11.1 m3/s, 3 phase. (I) insulated version.

300C 120min

400C 120min

600C 120min

WVA/WVI. . . . . . . . . . . . . . 268

400C 120min

400C 120min

600C 120min

Smoke extract fans

237

Smoke extract centrifugal fans KBR/F


400/120 min (F400) Insulated casing Speed-controllable Integral thermal contacts Low sound level Tested acc. to EN 12101-3 at LGAI Barcelona CE-certified acc. to EN 12101-3, 2002-06 at TV Sd Electrical accessories

REV p. 340

400C 120min

200C

The KBR/F fans smoke extract unit are used in case of fire to extract smoke gases from rooms, and also during normal working conditions for standard temperature up to 200C. The KBR/F units have backward curved impellers made of galvanized steel except size 355 which is a steel impeller painted RAL 9005.The units have a swing out door for easy inspection and service. The direction of the door opening can easily be changed from left to right at site. The fans have a double isolated casing with 50 mm rockwool inside. To protect the motors from overheating the KBR fans have integral thermal contacts with external leads for connection to a motor protection device. (Except size KBR 280 D2 and D2-4 which have integral cold conductors). In case of fire all protective devices must be bridged to guarantee functional capability. Single speed three phase units can also be delivered with motors according to IE2 standard on request.

RTRD p. 321

RTRDU p. 321

S-DT2 p. 340

Quick selection

1 2 3 4 5

KBR/F 280D2 KBR/F 280D2-4 KBR/F 280DV KBR/F 315DV KBR/F 315D2 IE2

1 2 3 4 5 6

KBR/F 355E4 KBR/F 355E4/K KBR/F 355DV KBR/F 355DV/K KBR/F 355K D2 IE2 KBR/F 355D2 IE2

STDT p. 342

Technical data
KBR/F Art no. Voltage/Frequency Power at shaft Power Current Max air flow R.p.m. Max temp. of transported air Max temp. of transported air for 120 min Sound pressure level at 4 m Sound pressure level at 10 m Weight Insulation class, motor Enclosure class, motor Wiring diagram p. 391-400 280D2 31586 V/50 Hz 400 3~ W 550 W 730 A 1.24 m3/s 0.824 min-1 2820 C 200 C 400 dB(A) 44 dB(A) 36 kg 48 F IP 55 13b Y 280D2-4 31588 400 3~ 480/120 1.2/0.33 0.806/0.422 2800/1410 200 400 44/33 36/25 49 F IP 55 14b 280DV 31587 400 3~ 370 1.39 0.422 1360 200 400 33 25 49 F IP 54 17 315DV 31590 400 3~ 370 1.39 0.611 1360 200 400 36 28 77 F IP 54 17 315D2 IE2 34509 400 3~ 1500 1218 2.33 1.09 2928 200 400 50 42 57 F IP 54 17 355E4 31554 230 370 2.1 0.972 1330 200 400 44 33 81 F IP 54 21

Smoke extract fans

238

Smoke extract centrifugal fans


Dimensions
J 130

Ventilation accessories
A I 78

EVH p. 388
G B C

LRK(F) p. 385
E 38 E L 50 D 50

RSA p. 384

WBK p. 389

35 H

KBR/F 280 315 355

A 171,5 187,5 206,7

B 537 600 655

C 295 339 372

D 360 398 451

E 625 690 770

G 280 315 355

H 234 249 273

I 142,5 153,5

J 291 307 331

L 600 800 770

WSD-KBT p. 371

KBR/F Art no. Voltage/Frequency Power at shaft Current Max air flow R.p.m. Max temp. of transported air Max temp. of transported air for 120 min Sound pressure level at 4 m Sound pressure level at 10 m Weight Insulation class, motor Enclosure class, motor Wiring diagram p. 391-400

355E4/K 32891 V/50 Hz 230 1~ W 370 A 2.1 m3/s 0.778 min-1 1330 C 200 C 400 dB(A) 42 dB(A) 31 kg 80 F IP 54 21

355DV 31594 400 3~ 550 1.88 1.06 1360 200 400 41 33 81 F IP 54 17

355DV/K 31592 400 3~ 550 1.88 0.806 1360 200 400 41 33 81 F IP 54 17

355K D2 IE2 34511 400 3~ 2200 3.85 1.63 2909 200 400 53 45 75 F IP 55 17

355D2 IE2 34510 400 3~ 4000 5.95 2 2889 200 400 53 45 84 F IP 54 17

Smoke extract fans

239

Smoke extract centrifugal fans


Performance
qv [m3/h]
0 500 1000 1500 2000 2500 3000 3500
0 400 800 1200 1600

qv [m3/h]
2000 350 300 250

ps [Pa]

ps [Pa]

1400 1200 1000


86

KBR/F 280D2-4

KBR/F 280DV

74

800

200

2-pole
600 400 200 0 0 0 200 400 600 800 0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1
0 200 400 600 800 150 100

74

4-pole
72 84

50 0 0 0,1 0,2 0,3 0,4

72

0,5

qv [m3/s] p1 [W]
p1 [W]

qv [m3/s]

0,6

dB(A) 2-pole LwA Inlet LwA Outlet LwA Surrounding 4-pole LwA Inlet LwA Outlet LwA Surrounding

Tot 63 86 88 67 80 82 61 125 78 80 59

Frequency bands [Hz] 250 74 76 55 500 71 73 52 1k 69 71 50 2k 65 67 46 4k 61 61 42 8k

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 74 76 56 125 68 70 50

Frequency bands [Hz] 250 66 68 48 500 62 64 44 1k 59 61 41 2k 57 59 39 4k 53 55 35 8k 49 51 31

Measurement point: 0,22 m/s; 220 Pa

Measurement point: 0,42 m/s; 800 Pa 74 76 56 68 70 50 66 68 48 62 64 44 59 61 41 57 59 39 53 55 35 49 51 31

Measurement point: 0,22 m/s; 220 Pa


qv [m3/h] 0 450 ps [Pa] 400 350 300 250 200 150 100 50 400 800 1200 1600 2000 2400

KBR/F 315DV

KBR/F 315D2 IE2

Smoke extract fans

0 0 0 100 200 300 0,1 0,2 0,3 0,4 0,5 0,6 0,7 qv [m3/s]

dB(A) LwA Inlet LwA Outlet LwA Surrounding

p1 [W]

Tot 63 77 79 59 125 75 77 57

Frequency bands [Hz] 250 74 76 56 500 69 71 51 1k 67 68 49 2k 63 65 45 4k 57 59 39 8k 54 56 36

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 91 93 73 125 89 31 71

Frequency bands [Hz] 250 88 90 70 500 83 85 65 1k 81 83 63 2k 77 80 59 4k 71 73 53 8k 68 70 50

Measurement point: 0,38 m/s; 250 Pa

Measurement point: 0,46 m/s; 1276 Pa

240

Smoke extract centrifugal fans


qv [m3/h] 0 ps [Pa] 700 600 500 400 300 200 100 0 0 0 100 200 300 400 0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 qv [m3/s]
p1 [W] qv [m3/h] 0 ps [Pa] 500 450 400 350 300 250 200 150 100 50 0 0 0 100 200 300 400 0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 qv [m3/s] 400 800 1200 1600 2000 2400 2800

500

1000 1500 2000 2500 3000

3500

KBR/F 355E4

KBR/F 355E4/K

dB(A) LwA Inlet LwA Outlet LwA Surrounding

p1 [W]

Tot 63 82 84 64 125 80 82 62

Frequency bands [Hz] 250 79 81 61 500 74 76 56 1k 72 74 54 2k 68 70 50 4k 62 64 44 8k 59 61 41

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 80 82 62 125 78 80 60

Frequency bands [Hz] 250 74 76 56 500 71 73 53 1k 67 69 49 2k 65 67 47 4k 61 63 43 8k 57 59 39

Measurement point: 0,42 m/s; 465 Pa

Measurement point: 0,42 m/s; 320 Pa

qv [m3/h] 700 ps [Pa] 600 500 400 300 200 100 0 0 0


p1 [W] 400 300 200 100 0 0 0,1 0,2 0,3 0,4 0,5 0,6 0,7

1000

2000

3000

4000
600 ps [Pa]

qv [m3/h] 0 400 800 1200 1600 2000 2400 2800 3200

KBR/F 355DV

500

KBR/F 355DV/K

Smoke extract fans

0,2

0,4

0,6

0,8

1,0 1,2 qv [m3/s]

0,8

0,9

qv [m3/s] 0 100 200 300 400

p1 [W]

200 400 600

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 82 84 64 125 80 82 62

Frequency bands [Hz] 250 79 81 61 500 74 76 56 1k 72 74 54 2k 68 70 50 4k 62 64 44 8k 59 61 41

dB(A) LwA Inlet LwA Outlet

Tot 63 82 84 125 80 82 62

Frequency bands [Hz] 250 79 81 61 500 74 76 56 1k 72 74 54 2k 68 70 50 4k 62 64 44 8k 59 61 41

LwA Surrounding 64

Measurement point: 0,69 m/s; 320 Pa

Measurement point: 0,32 m/s; 398 Pa

241

Smoke extract centrifugal fans

KBR/F 355K D2 IE2

KBR/F 355D2 IE2

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 94 96 76 125 92 94 74

Frequency bands [Hz] 250 91 93 73 500 86 88 68 1k 84 86 66 2k 80 82 62 4k 74 76 56 8k 71 73 53

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 97 96 76 125 92 94 74

Frequency bands [Hz] 250 91 93 73 500 86 88 68 1k 84 86 66 2k 80 82 62 4k 74 76 56 8k 71 73 53

Measurement point: 0,72 m/s; 1431 Pa

Measurement point: 0,83 m/s; 1800 Pa

Smoke extract fans

242

Smoke extract centrifugal fans Reference

Installation of DVV smoke extract roof fans

Smoke extract fans

243

Smoke extract roof fans DVV/F


Smoke extract roof fan 400C/120 min (F400) resp. 600C/120 min (F600) Vertical exhaust Suitable for coastal applications Wide range of accessories Certified acc. to EN 12101-3 at TU Munich CE-certified acc. to EN 12101-3, 2002-06 at TV Sd Electrical accessories

REV DVV p. 340

The DVV/F smoke extract fans are used in case of fire to extract smoke gases from rooms, and also during normal working conditions for standard ventilation. For installation only over heated rooms. For non-heated buildings flaps FSL for classification snow load SL1000 is available as accessories for sizes 450 up. The casing is manufactured from seawater resistant aluminium (DVV/F 1000 M and P 4 pole from aluzinc steel sheet). The base frame consists of galvanised steel. The impeller with backward-curved blades is manufactured from galvanised steel (type F400) respectively from stainless steel (type F600). The fan is equipped with IEC standard motors according to the 2009/640/EC guideline and IEC 60034-30, with protection class IP 54 or 55, insulation class F. Motor cooling with fresh air via air duct. Thermal motor protection (PTC or thermal contact built-in) on request, in IE2 motors serial PTC built-in. For frequency controlled single speed units up to 0,55 kW PTC must be ordered (since IE1 motors built-in). For speed control use only combination of frequency inverter and appropriate filter to motor side (sine or du/dt), observing installation conditions (e.g. cable

type, lenght). Operating over 50Hz is not allowed. Service switch serial on cooling duct at sizes 800 and 1000. Other sizes equipped with terminal box, service switch on request. In case of fire any speed control, frequency inverter and all motor protective devices must be bridged to guarantee functional capability (connection directly to mains). Frequency controlled units can have additional EMC protection (available on request). For additional sound reduction an outlet silencer HSDV is available as an accessory for all DVV/F fans. If factory mounted, the item reference is DVVI (sound insulated) fan. FSL is not dimensionally suitable for DVVI. Available also as DVV/120 for continuous exhaust of medium up to 120C (see online catalogue). Note: article numbers in tables refer to items without PTC or thermal contact, with exception of items with IE2 motors, where PTC is serial built-in.

400C 120min

600C 120min

Technical data
DVV/F Art no. F400 Art no. F600 Voltage/Frequency Power at shaft Current Starting current Max air flow R.p.m. Max. temp. of transp. air Max. temp. of transp. air for 120 min Sound pressure level at 4 m Sound pressure level at 10 m Weight Enclosure class, motor efficiency Thermal prot. PTC serial built-in Wiring diagram p. 391-400 400D4 3501 3500 V/50 Hz 400 3~ kW 0.55 A 1.6 A 6.6 m3/s 1.17 min-1 1390 C 55 C 400/600 dB(A) 62 dB(A) 52 kg 49 IP 54 15b 400D4-6 3505 3504 400 3~ 0.55/0.18 1.7/0.8 6.8/2.4 1.17/0.78 1420/940 55 400/600 62/53 52/43 49 IP 54 15a 450D4 IE2 95176 95175 400 3~ 1.1 2.6 12.5 2.01 1435 55 400/600 66 56 69 IP 54 IE2 yes 15c 3529 3528 400 3~ 1.1/0.370 3/1.4 10.8/5.9 2.01/1.35 1420/950 55 400/600 66/55 56/46 72 IP 54 15a 450D4-6 560D4 IE2 95178 95177 400 3~ 1.5 3.5 20.3 2.64 1420 55 400/600 69 59 78 IP 54 IE2 yes 15c 560D6 IE2 95180 95179 400 3~ 0.75 2 5.8 1.81 880 55 400/600 60 52 78 IP 54 IE2 yes 15c 3553 3552 400 3~ 1.7/1.2 4.6/3.7 23.9/13.3 2.64/1.81 1450/940 55 400/600 69/60 59/52 84 IP 54 15a 560D4-6 630D4-K IE2 95182 95181 400 3~ 3.0 6.6 36.7 3.5 1400 55 400/600 71 63 129 IP 54 IE2 yes 15c 630D6-K IE2 95186 95185 400 3~ 1.1 2.9 10.8 2.28 910 55 400/600 61 53 121 IP 54 IE2 yes 15c 3589 3588 400 3~ 3.6/0.9 8.0/3.2 44/10 3.5/1.72 1430/710 55 400/600 71/55 63/47 138 IP 54 14a 630D4-8-K

Smoke extract fans

244

Smoke extract roof fans


Installation examples DVV fans
DVV DVV

Ventilation accessories

DVV

ASFV p. 384

VKV/F SSVE/F ASSV/F ASK/F FDVE/F VKV/F ASSV/F

VKV/F ASSV/F FDV/F

ASK/F p. 380

ASSV/F p. 383

FDV/F p. 381

DVV/F Art no. F400 Art no. F600 Voltage/Frequency Power at shaft Current Starting current Max air flow R.p.m. Max. temp. of transp. air Max. temp. of transp. air for 120 min Sound pressure level at 4 m Sound pressure level at 10 m Weight Enclosure class, motor efficiency Thermal prot. PTC serial built-in Wiring diagram p. 391-400
3

630D4 IE2 95184 95183 V/50 Hz 400 3~ kW 5.5 A 11.6 A 95 m /s 5.36 min-1 1455 C 55 C 400/600 dB(A) 75 dB(A) 69 kg 144 IP 54 IE2 yes 13b D

630D6 IE2 95188 95187 400 3~ 2.2 5.5 25.3 3.36 935 55 400/600 64 58 134 IP 54 IE2 yes 15c

630D4-6 3585 3584 400 3~ 5.5/1.7 12/4.5 81.6/20.3 5.36/3.36 1460/970 55 400/600 75/64 69/58 154 IP 55 15a

800D4-K 95199 95200 400 3~ 9.5 18 121 7.08 1445 55 400/600 76 70 262 IP 54 13b D

800D4-8-K 30064 30065 400 3~ 9.0/2.4 18.5/5.6 114/24 7.08/3.92 1420/720 55 400/600 76/55 70/48 281 IP 55 14a

800D6-K IE2 95190 95189 400 3~ 2.2 5.5 25.3 5.0 935 55 400/600 66 60 189 IP 54 IE2 yes 15c

800D6 IE2 95192 95191 400 3~ 5.5 12.6 76 7.08 950 55 400/600 72 64 213 IP 54 IE2 13b D

FDVE/F p. 382

FSL-DVV p. 379

VKV/F p. 383

VKVE/F p. 383

DVV/F Art no. F400 Art no. F600 Voltage/Frequency Power at shaft Current Starting current Max air flow R.p.m. Max. temp. of transp. air Max. temp. of transp. air for 120 min Sound pressure level at 4 m Sound pressure level at 10 m Weight Enclosure class, motor efficiency Thermal prot. PTC serial built-in Wiring diagram p. 391-400

800D6-8 3643 3642 V/50 Hz 400 3~ kW 5.7/2.4 A 12.3/6.2

800D4-M IE2 95195 95196 400 3~ 15 29.8

800D4-8-M 30045 30046 400 3~ 16.2/3.7 36/13 290/64 9.58/4.79 1470/735 55 400/600 80/65 72/57 399 IP 55 14a

800D6-M 800D4-P IE2 95209 95210 400 3~ 4.0 9 48.6 6.22 955 55 400/600 70 62 209 IP 55 IE2 yes 13b D IE2 95197 95198 400 3~ 18.5 35 280 10.8 1465 55 400/600 83 75 397 IP 55 IE2 yes 13b D

800D4-8-P 30057 30058 400 3~ 18.5/4.5 40/15 335/75 10.8/5.42 1470/735 55 400/600 83/65 75/57 413 IP 55 14a

1000D6 IE2 95194 95193 400 3~ 11.0 22 156 12.4 955 55 400/600 74 66 378 IP 55 IE2 yes 13b D

1000D6-8 3766 3765 400 3~ 11.0/5.0 22/15 154/82.5 12.4/9.44 970/730 55 400/600 74/66 66/58 445 IP 55 15a

1000D6-12 3768 3767 400 3~ 12.0/2.4 23/7.5 140/23.3 12.4/6.67 960/480 55 400/600 74/63 66/54 445 IP 55 14a

Smoke extract fans

A 62.8/21.7 265 m3/s 7.08/5.28 9.58 min-1 960/720 C 55 C 400/600 dB(A) 72/66 dB(A) 64/57 kg 224 IP 54 15a 1470 55 400/600 80 72 309 IP 55 IE2 yes 13b D

245

Smoke extract roof fans


Dimensions
F

Ventilation accessories
E

HSDV p. 379
G H

ESDV p. 384

Shadowed area only for size DVV/F 400-560


d2 nxM C
E

SSV/F p. 382

d1

d 35 B A

SSVE/F p. 377

DVV/F 400 450 560 630 800 800-M, P 1000 1000D4-M 1000D4-P

A 560 710 710 995 995 995 1160 1160 1160

B 460 600 600 880 880 880 1040 1040 1040 1040

C 557 706 706 990 990 990 1154 1154 1154 1154

d 315 355 400 500 630 630 710 710 710 710

d1 356 395 438 541 674 674 751 751 751 751

d2 14 14 14 18 18 18 18 18 18 18

E 250 270 270 225 310 280 325 325 394 394

F 635 808 808 1100 1272 1350 1500 1500 1500 1500

G 630 700 750 958 1165 1280 1350 1350 1479 1479

H 40 20 20 40 40 40 70 70 70 70

nxM 8xM8 8xM8 12xM8 12xM8 16xM10 16xM10 16xM10 16xM10 16xM10 16xM10

1000D6-M, P 1160

DVV/F Art no. F400 Art no. F600 Voltage/Frequency Power at shaft Current Starting current Max air flow R.p.m. Max. temp. of transp. air Max. temp. of transp. air for 120 min Sound pressure level at 4 m Sound pressure level at 10 m Weight Enclosure class, motor efficiency Thermal prot. PTC serial built-in Wiring diagram p. 391-400

1000D8 3668 3667 V/50 Hz 400 3~ kW 5.5 A 12.5 A 63.8 m3/s 9.44 min-1 710 C 55 C 400/600 dB(A) 66 dB(A) 58 kg 355 IP 55 13a D

1000D4-M IE2 95205 95206 400 3~ 22.0 42 340 14.2 1470 55 400/600 89 79 539 IP 55 IE2 yes 13b D

1000D6-M IE2 95207 95208 400 3~ 7.5 15.7 112 9.42 970 55 400/600 77 67 358 IP 55 IE2 yes 13b D

1000D4-8-M 33126 33127 400 3~ 22.0/5.5 45/17 338/85 14.2/7.08 1470/730 55 400/600 89/70 79/60 575 IP 55 14a

1000D4-P IE2 95203 95204 400 3~ 28 56 420 15.2 1470 55 400/600 90 79 565 IP 55 IE2 yes 13b D

1000D4-8-P 31270 31271 400 3~ 28.0/7.0 51/20 400/80 15.2/7.56 1470/730 55 400/600 90/71 79/60 590 IP 55 14a

1000D6-P IE2 95201 95213 400 3~ 8.5 18 126 10.1 965 55 400/600 78 67 358 IP 55 IE2 yes 13b D

Smoke extract fans

246

Smoke extract roof fans


Performance

DVV/F 400D4-6

DVV/F 450D4-6

81

71

84

75

dB(A) 4-pole LwA Inlet LwA Surrounding 6-pole LwA Inlet LwA Surrounding

Tot 63 81 83 54 56 125 66 68

Frequency bands [Hz] 250 74 76 500 75 77 1k 74 76 2k 72 74 4k 69 71 8k

dB(A) 4-pole 61 63 LwA Inlet LwA Surrounding 6-pole

Tot 63 84 86 57 59 125 69 71

Frequency bands [Hz] 250 77 79 500 78 80 1k 77 79 2k 75 77 4k 72 74 8k 64 66

Measurement point: 0,9 m/s; 200 Pa 71 73 48 50 57 59 63 65 67 69 62 64 60 62 58 60 46 48

Measurement point: 1,7 m/s; 200 Pa LwA Inlet LwA Surrounding 75 76 52 53 61 62 67 68 71 72 66 67 64 65 62 63 50 51

Measurement point: 0,4 m/s; 140 Pa

Measurement point: 1,15 m/s; 100 Pa

2000

4000

6000

8000

10000

DVV/F 560D4-6

DVV/F 630-K

88
82

92

81

76

dB(A) 4-pole LwA Inlet LwA Surrounding 6-pole LwA Inlet LwA Surrounding

Tot 63 88 90 61 63 125 73 75

Frequency bands [Hz] 250 81 83 500 82 84 1k 81 83 2k 79 81 4k 76 78 8k

dB(A) 4-pole 68 70 LwA Inlet LwA Surrounding 6-pole

Tot 63 92 94 65 67 125 77 79

Frequency bands [Hz] 250 85 87 500 86 88 1k 85 87 2k 83 85 4k 80 82 8k 72 74

Smoke extract fans

Measurement point: 2,1 m/s; 310 Pa 81 83 58 60 67 69 73 75 77 79 72 74 70 72 68 70 56 58

Measurement point: 2,8 m/s; 400 Pa LwA Inlet LwA Surrounding 8-pole LwA Inlet LwA Surrounding 76 78 59 61 65 67 67 69 71 73 69 71 69 71 61 63 50 52 82 84 58 60 69 71 71 73 78 80 73 75 72 74 68 70 55 57

Measurement point: 1,5 m/s; 125 Pa

Measurement point: 1,0 m/s; 350 Pa

Measurement point: 0,98 m/s; 200 Pa

247

Smoke extract roof fans

DVV/F 630

DVV/F 800-K

98

97 87 84

79

75

dB(A) 4-pole LwA Inlet LwA Surrounding 6-pole LwA Inlet LwA Surrounding 8-pole LwA Inlet LwA Surrounding

Tot 63 97 98 68 68 125 79 87

Frequency bands [Hz] 250 91 88 500 90 91 1k 92 91 2k 87 91 4k 81 89 8k

dB(A) 4-pole 72 79 LwA Inlet LwA Surrounding 6-pole

Tot 63 98 99 71 72 125 83 84

Frequency bands [Hz] 250 91 92 500 92 93 1k 91 92 2k 89 90 4k 86 87 8k 78 79

Measurement point: 4,58 m/s; 370 Pa 87 88 64 65 73 74 79 80 83 84 78 79 76 77 74 75 62 63

Measurement point: 5,6 m/s; 700 Pa LwA Inlet LwA Surrounding 8-pole 84 86 60 62 71 73 73 75 80 82 75 77 74 76 70 72 57 59

Measurement point: 2,3 m/s; 290 Pa 79 81 61 63 67 69 70 72 74 76 71 73 71 73 66 68 55 57

Measurement point: 4,0 m/s; 280 Pa LwA Inlet LwA Surrounding 75 77 58 60 64 66 66 68 70 72 68 70 68 70 60 62 49 51

Measurement point: 1,67 m/s; 170 Pa

Measurement point: 3,1 m/s; 150 Pa

DVV/F 800

DVV/F 800-M

6-pole 8-pole
101

93 82

12-pole
71
82

90

Smoke extract fans

dB(A) 6-pole LwA Inlet LwA Surrounding 8-pole LwA Inlet LwA Surrounding 12-pole LwA Inlet LwA Surrounding

Tot 63 93 95 70 72 125 79 81

Frequency bands [Hz] 250 85 87 500 89 91 1k 84 86 2k 82 84 4k 80 82 8k

dB(A) 4-pole 68 70 LwA Inlet LwA Surrounding 6-pole

Tot 63 101 103 74 76 125 86 88

Frequency bands [Hz] 250 94 96 500 95 97 1k 94 96 2k 92 94 4k 89 91 8k 81 83

Measurement point: 6,1 m/s; 250 Pa 82 84 64 66 70 72 73 75 77 79 74 76 74 76 69 71 58 60

Measurement point: 7,2 m/s; 740 Pa LwA Inlet LwA Surrounding 8-pole 90 92 67 69 78 80 80 82 87 89 82 84 81 83 77 79 64 66

Measurement point: 4,3 m/s; 200 Pa 71 73 53 55 59 61 62 64 66 68 63 65 63 65 58 60 47 49

Measurement point: 5,2 m/s; 250 Pa LwA Inlet LwA Surrounding 82 84 65 67 71 73 73 75 77 79 75 77 75 77 67 69 56 58

Measurement point: 2,8 m/s; 70 Pa

Measurement point: 4 m/s; 150 Pa

248

Smoke extract roof fans

DVV/F 800-P

DVV/F 1000

92

104

84

85

91

81

dB(A) 4-pole LwA Inlet LwA Surrounding 6-pole LwA Inlet LwA Surrounding 8-pole LwA Inlet LwA Surrounding

Tot 63 104 106 77 79 125 89 91

Frequency bands [Hz] 250 97 99 500 98 100 1k 97 99 2k 95 97 4k 92 94 8k

dB(A) 6-pole 84 86 LwA Inlet LwA Surrounding 8-pole

Tot 63 92 94 69 71 125 78 80

Frequency bands [Hz] 250 84 86 500 88 90 1k 83 85 2k 81 83 4k 79 81 8k 67 69

Measurement point: 8,6 m/s; 740 Pa 91 93 67 69 78 80 80 82 87 89 82 84 81 83 77 79 64 66

Measurement point: 6,94 m/s; 650 Pa LwA Inlet LwA Surrounding 12-pole 84 86 66 68 72 74 75 77 79 81 76 78 76 78 71 73 60 62

Measurement point: 5,6 m/s; 330 Pa 85 87 68 70 74 76 76 78 80 82 78 80 78 80 70 72 59 61

Measurement point: 6,11 m/s; 310 Pa LwA Inlet LwA Surrounding 81 83 63 65 69 71 72 74 76 78 73 75 73 75 68 70 57 59

Measurement point: 4,3 m/s; 200 Pa

Measurement point: 5,36 m/s; 85 Pa

DVV/F 1000-M
104

DVV/F 1000-P
105

92 84 84

93

dB(A) 4-pole LwA Inlet LwA Surrounding 6-pole LwA Inlet LwA Surrounding 8-pole LwA Inlet LwA Surrounding

Tot 63 104 82 109 87 125 91 96

Frequency bands [Hz] 250 97 102 500 100 105 1k 96 101 2k 94 99 4k 92 97 8k

dB(A) 4-pole 80 85 LwA Inlet LwA Surrounding 6-pole

Tot 63 105 110 82 87 125 91 96

Frequency bands [Hz] 250 97 102 500 101 106 1k 96 101 2k 94 99 4k 92 97 8k 80 85

Smoke extract fans

Measurement point: 7,3 m/s; 1600 Pa 92 97 75 80 81 86 83 88 87 92 85 90 85 90 80 85 69 74

Measurement point: 9,2 m/s; 1580 Pa LwA Inlet LwA Surrounding 8-pole 93 98 75 80 81 86 84 89 88 93 85 90 85 90 80 85 69 74

Measurement point: 4,8 m/s; 700 Pa 84 91 66 73 72 79 75 82 79 86 76 83 76 83 71 78 60 67

Measurement point: 7,1 m/s; 560 Pa LwA Inlet LwA Surrounding 84 91 66 73 72 79 75 82 79 86 76 83 76 83 71 78 60 67

Measurement point: 3,1 m/s; 430 Pa

Measurement point: 6,1 m/s; 220 Pa

249

Smoke extract roof fans DVG/F


400C 120min

Smoke and heat extract unit + normal ventilation Up to 400C/120 min (F400/120, F400/90, F300, F200) Normal ventilation up to 120C continuous operation Vertical exhaust DVG-V or horizontal DVG-H Includes pre-wired isolator Suitable for coastal applications Wide range of accessories Tested acc. to EN 12101-3 at LGAI, Barcelona CE-certified acc. to EN 12101-3, 2002-06 at TV Sd

The DVG/F smoke extract fans are used in case of fire to extract smoke gases from rooms, and also during normal working conditions for standard ventilation. Smoke-free escape ways increase the chances to rescue people in case of a fire. The casing is manufactured from seawater resistant aluminium. The base frame consists of galvanised steel. The impeller with backward-curved blades is manufactured from galvanised steel. Motor outside air stream is air cooled. The fan is equipped with IEC standard motors according to the 2009/640/EC guideline and IEC 60034-30, with protection class IP 54, insulation class F. Thermal motor protection (PTC or thermal contact built-in) on request, in IE2 motors serial PTC built-in, in DVG 400D4V serial thermal

contact built-in. For frequency controlled single speed units up to 0,55 kW PTC must be ordered (since IE1 motors built-in). For two speed fans (up to 4 kW) two speed switch, S-DT2 SKT/S-DT2 GKT is available as accessory (in this case thermal contact must be ordered; not suitable for PTC or without thermal contact). In case of fire two speed switch, eventual speed controller at DVG 400D4V and motor protective devices must be bridged to guarantee functional capability (connection direct to mains). For speed control use only combination of frequency inverter and appropriate all pole sine filter (hot tested at LGAI with inverter and sine filter). If frequency inverter used in case of fire, PTC must be bridged and switching on max. speed even after eventual short sup-

ply cut off assured. Operating over 50 Hz is not allowed. Frequency controlled units can have additional EMC protection (available on request). Note: article numbers in tables refer to items without PTC or thermal contact, with exception of items with IE2 motors, where PTC is serial built-in. Note: diagrams and data of max. airflow and sound level refer to items with vertical exhaust DVG-V; diagrams and data of DVG-H are available on-line. Data related to motor and weight of delivered items can vary from catalogue data due to different suppliers.

Technical data
DVG/F Art no. DVG-V (vertical) Art no. DVG-H (horizontal) Voltage/Frequency Power at shaft Current Starting current Max air flow R.p.m. Max. temp. of transp. air* Sound pressure level at 4 m Sound pressure level at 10 m Weight vertical/horizontal Enclosure class, motor PTC serial built-in motor S-DT2DKT, S-DT2GKT FXDM Wiring diagram p. 391-400 *for 120 min 15b 14a 15b 14a 15b 14a 15b 14a 15c ...DKT ...DKT ...DKT ...DKT 315D4 32306 95001 V/50 Hz 400 3~ kW 0.37 A 0.95 A 4.1 m3/s 0.71 min-1 1405 C 400 dB(A) 55 dB(A) 49 kg 41/39 IP 54 315D4-8 32307 95002 400 3~ 0.37/0.12 1.3/0.6 3.4/1.3 0.71/0.36 1350/680 400 55/39 49/33 41/39 IP 54 355D4 32308 95003 400 3~ 0.37 0.95 4.1 0.81 1405 400 56 50 43/41 IP 54 355D4-8 32309 95004 400 3~ 0.37/0.12 1.3/0.6 3.4/1.3 0.76/0.38 1350/680 400 56/41 50/35 43/41 IP 54 400D4-S 32310 95005 400 3~ 0.37 1.6 6.6 0.97 1390 400 59 53 45/41 IP 54 400D4-8-S 32311 95006 400 3~ 0.37/0.12 1.3/0.6 3.4/1.3 0.97/0.49 1350/680 400 59/43 53/37 45/41 IP 54 400D4 32312 95007 400 3~ 0.55 1.6 6.6 1.31 1390 400 62 55 46/44 IP 54 400D4-8 32313 95008 400 3~ 0.50/0.12 1.6/0.6 5.8/1.3 1.31/0.66 1410/670 400 62/46 55/40 46/44 IP 54 450D4 IE2 95164 95153 400 3~ 0.75 2.1 10.1 1.52 1425 400 65 58 56/52 IP 54 PTC

Smoke extract fans

250

Smoke extract roof fans


Quick selection Ventilation accessories
8178, 8284, 8180, 8177, 8181, 8176, 8182
8199, 8183, 8174, 8184, 8172, 8173, 8185, 8186

1 2 3 4

DVG/F 315D4 DVG/F 315D6 DVG/F 315D8 DVG/F 355D4

5 6 7

DVG/F 355D8 DVG/F 400D4-S DVG/F 400D8-S

1 2 3

DVG/F 400D4 DVG/F 400D8 DVG/F 450D4 IE2

4 5 6 7 8

DVG/F 450D8 DVG/F 500D4 IE2 DVG/F 500D4-S IE2 DVG/F 500D8-S DVG/F 500D8

ASFV p. 384

5 6 3 1

4 1 6

ASK/F p. 380

2 3 5 7
2 4 7 8

ASSG/F p. 383

FDGE/F p. 378
8171, 8187, 8191, 8161, 8170, 8194, 8195

1 2 3

DVG-F 560D4 IE2 DVG-F 560D8 DVG-F 560D6 IE2

4 5 6 7

DVG-F 630D4 IE2 DVG-F 630D4-S DVG-F 630D8-S DVG-F 630D6 IE2

1 2 3

DVG-F 630D6-S DVG-F 630D8-S DVG-F 630D8

4 5 6 7

DVG-F 800D6-S IE2 DVG-F 800D8-S DVG-F 800D6 IE2 DVG-F 800D8

8193, 8194, 8196, 9856, 9858, 9656, 9935

SSG/F p. 378

4 1 5

6 4

1
3 2 6 7

5 2 3

FDG/F p. 377

VKG/F p. 383

DVG/F Art no. V (vertical) Art no. H (horizontal ) Voltage/Frequency Power at shaft Current Starting current Max air flow R.p.m. Max. temp. of transp. air* Sound pressure level at 4 m Sound pressure level at 10 m Weight vertical/horizontal Enclosure class, motor PTC serial built-in motor S-DT2DKT, S-DT2GKT FXDM... Wiring diagram p. 391-400 *for 120 min

450D4-8 32315 95010 V/50 Hz 400 3~ kW 1.1/0.25 A 3.1/1.2 A 12.4/3 m3/s 1.52/0.76 min-1 1400/690 C 400 dB(A) 65/48 dB(A) 58/42 kg 58/55 IP 54 ...DKT

500D4 IE2 95165 95154 400 3~ 1.5 3.5 20.3 2.64 1420 400 70 63 86/82 IP 54 PTC ...5AM

500D4-S IE2 95166 95155 400 3~ 1.1 2.6 12.5 2 1435 400 66 60 87/83 IP 54 PTC

500D4-8-S 32317 95012 400 3~ 1.1/0.25 3.1/1.25 12.4/3.0 2.0/1.0 1400/690 400 66/49 60/44 87/83 IP 54 ...DKT

500D4-8 32319 95014 400 3~ 1.4/0.35 3.5/1.4 14.4/3.5 2.64/1.32 1400/680 400 70/52 63/45 86/82 IP 54 ...DKT

560D4 IE2 95169 95158 400 3~ 2.2 4.9 28.9 3.24 1425 400 72 67 104/99 IP 54 PTC

560D4-8 32323 95018 400 3~ 2.5/0.6 5.9/2.4 30.7/7.4 3.24/1.6 1430/710 400 72/51 67/46 107/102 IP 54 ...DKT

560D6 IE2 95170 95159 400 3~ 0.75 2 5.8 2.11 880 400 58 52 96/91 IP 54 PTC ...5AM

630D4 IE2 95171 95160 400 3~ 4 8.7 51 4.91 1445 400 75 69 128/123 IP 54 PTC ...14AM 15c

Smoke extract fans

...5AM 15c 14a 14a

...5AM 15c 14a

14a

15c

15c

251

Smoke extract roof fans


Dimensions DVG-V/F
B df (n x M)

DVG-H/F
Max 240 df (nxM)

E
Max 240

DVG/F 315
G

A 598 598 668 668 943 943 1039 1255

B 450 450 535 535 750 750 840 1050

G 594

df (n x M)

H1 H

12 891

438 (6xM8) 30 520 438 (6xM8) 30 567 438 (6xM8) 30 557 438 (6xM8) 30 637 605 (8xM8) 30 696

355 400 450 500 560 630 800

12 1003 704 12 1053 724 12 1261 854 14 1343 892

14 1540 1078 605 (8xM8) 30 773 14 1573 1072 674 (8xM8) 40 858 14 2024 1280 872 (8xM8) 40 999

H1

DVG/F Art no. DVG-V (vertical) Art no. DVG-H (horizontal Voltage/Frequency Power at shaft Current Starting current Max air flow R.p.m. Max. temp. of transp. air* Sound pressure level at 4 m Sound pressure level at 10 m Weight Enclosure class, motor PTC serial built-in motor S-DT2DKT, S-DT2GKT FXDM... Wiring diagram p. 391-400 * for 120 min DVG/F Art no. DVG-V (vertical) Art no. DVG-H (horizontal Voltage/Frequency Power at shaft

630D4-S IE2 95172 95161 V/50 Hz 400 3~ kW 3 A 6.6 A 36.7 m3/s 3.82 min-1 1400 C 400 dB(A) 71 dB(A) 65 kg 119/114 IP 54 PTC

630D4-8-S 32328 95023 400 3~ 3.6/0.9 8.0/3.2 44.0/10.0 3.82/1.89 1430/710 400 71/55 65/49 128/123 IP 54 ...DKT

630D6 IE2 95173 95162 400 3~ 1.5 3.8 18.6 3.19 945 400 66 60 115/110 IP 54 PTC ...5AM

H1

630D6-S IE2 95174 95163 400 3~ 1.1 2.9 10.8 2.45 890 400 62 56 111/106 IP 54 PTC

630D6-8-S 32326 95021 400 3~ 1.0/0.4 3.3/1.35 14.2/4.7 2.45/1.89 950/710 400 62/55 55/49 117/112 IP 54 ...GKT

630D4-8 32333 95028 400 3~ 4.6/1.1 9.5/3.5 57/12.3 4.91/2.47 1450/720 400 75/59 69/54 144/139 IP 54 ...DKT 14a

...8AM 15c 14a

15c

15c

15a

800D6-S IE2 95131 95126 V/50 Hz 400 3~ kW 3 A 6.8 A 34.7 m3/s 5.28 min-1 950 C 400 dB(A) 71 dB(A) 64 kg 202/195 IP 54 PTC

800D6-8-S 95132 95127 400 3~ 2.8/1.1 7.5/3.8 38.3/15.6 5.28/3.96 970/730 400 71/63 64/56 208/201 IP 54 ...GKT

800D6 IE2 95128 95122 400 3~ 5.5 12.6 76 7.03 960 400 74 66 212/205 IP 54 PTC

800D6-8 95130 95125 400 3~ 5.7/2.4 12.3/6.2 62.8/21.7 7.08/5.28 960/720 400 74/68 66/60 219/212 IP 54 ...GKT

Smoke extract fans

Current Starting current Max air flow R.p.m. Max. temp. of transp. air* Sound pressure level at 4 m Sound pressure level at 10 m Weight vertical/horizontal Enclosure class, motor PTC serial built-in motor S-DT2DKT, S-DT2GKT FXDM... Wiring diagram p. 391-400 *for 120 min

...8AM 15c 15a

...14AM 13b D 15a

252

Smoke extract roof fans


Performance
qv [m/h] qv [m/h]

DVG-V 315/F

DVG-V 355/F

4-pole

4-pole

8-pole

8-pole

qv [m/s]
dB(A) 4-pole LwA Inlet LwA Outlet 8-pole LwA Inlet LwA Outlet 62 60 40 44 58 52 54 53 54 53 53 55 53 50 45 42 36 33 78 76 51 54 72 65 72 72 69 67 71 69 69 67 64 61 61 51 Tot 63 125 Frequency bands [Hz] 250 500 1k 2k 4k 8k 4-pole LwA Inlet LwA Outlet 8-pole LwA Inlet LwA Outlet 65 62 43 46 61 54 57 55 57 55 81 77 55 55 75 67 75 74 73 69 dB(A) Tot 63 125 250 500

qv [m/s]
Frequency bands [Hz] 1k 74 71 2k 73 68 4k 67 62 8k 64 52

Measurement point: 0,6 m/s; 80 Pa

Measurement point: 0,6 m/s; 200 Pa 56 57 56 52 48 44 39 35

Measurement point: 0,2 m/s; 50 Pa

Measurement point: 0,3 m/s; 50 Pa

qv [m/h]

qv [m/h]

DVG-V 400-S/F

DVG-V 400/F

4-pole

4-pole

6-pole 8-pole

8-pole
qv [m/s]
dB(A) 4-pole LwA Inlet LwA Outlet 8-pole LwA Inlet LwA Outlet 66 66 44 50 62 58 58 59 58 59 57 61 57 56 49 48 40 39 82 82 55 60 76 71 76 78 73 73 75 75 73 73 68 67 65 57 Tot 63 125

qv [m/s] Frequency bands [Hz]


250 500 1k 2k 4k 8k

dB(A) 4-pole LwA Inlet LwA Outlet

Tot 63 85 85 58 63 125 79 74

Frequency bands [Hz] 250 79 81 500 76 76 1k 78 78 2k 76 76 4k 71 70 8k 68 60

Smoke extract fans

Measurement point: 0,7 m/s; 220 Pa

Measurement point: 1,1 m/s; 125 Pa 6-pole LwA Inlet LwA Outlet 8-pole LwA Inlet LwA Outlet 69 68 47 52 65 60 61 61 61 61 60 63 60 58 52 50 43 41 76 76 46 55 69 66 69 70 69 69 68 71 69 67 61 59 53 49

Measurement point: 0,4 m/s; 50 Pa

Measurement point: 0,6 m/s; 100 Pa

Measurement point: 0,5 m/s; 50 Pa

253

Smoke extract roof fans


qv [m/h]
qv [m/h]

DVG-V 450/F
4-pole
4-pole

DVG-V 500-S/F

8-pole

8-pole

qv [m/s]
dB(A) 4-pole LwA Inlet LwA Outlet 8-pole LwA Inlet LwA Outlet 71 69 50 52 61 58 63 63 61 62 67 63 62 59 62 56 50 39 88 87 56 57 71 73 73 77 78 81 86 84 74 73 67 67 63 60 Tot 63 125 Frequency bands [Hz] 250 500 1k 2k 4k 8k 4-pole LwA Inlet LwA Outlet 8-pole LwA Inlet LwA Outlet 72 69 53 52 62 59 64 62 63 63 88 88 61 63 81 76 81 81 79 80 dB(A) Tot 63 125 250 500

qv [m/s]
Frequency bands [Hz] 1k 81 84 2k 78 78 4k 79 73 8k 66 62

Measurement point: 1,2 m/s; 200 Pa

Measurement point: 1,2 m/s; 500 Pa 66 65 67 61 55 52 45 40

Measurement point: 0,6 m/s; 50 Pa

Measurement point: 0,6 m/s; 130 Pa

qv [m/h]

qv [m/h]

DVG-V 500/F
4-pole

DVG-V 560/F
4-pole

6-pole
8-pole

8-pole

qv [m/s]

qv [m/s]

dB(A)

Tot 63 125 74 75

Frequency bands [Hz] 250 84 86 500 83 83 1k 83 87 2k 84 82 4k 81 76 8k

dB(A) 4-pole

Tot 63 125 85 84

Frequency bands [Hz] 250 86 88 500 84 88 1k 85 89 2k 87 85 4k 84 77 8k 82 70

Smoke extract fans

4-pole LwA Inlet


LwA

90 91

61 64

74 65

LwA Inlet LwA Outlet 6-pole

94 94

59 67

Outlet

Measurement point: 2,1 m/s; 300 Pa 8-pole LwA Inlet LwA Outlet 72 73 50 57 68 65 64 66 64 66 63 68 63 63 55 55 46 46

Measurement point: 2,5 m/s; 400 Pa LwA Inlet LwA Outlet 8-pole LwA Inlet LwA Outlet 76 74 55 58 65 64 68 69 66 67 72 69 67 65 67 61 55 44 87 82 57 61 80 73 80 77 80 74 79 75 80 74 71 66 64 58

Measurement point: 1,1 m/s; 50 Pa

Measurement point: 1,8 m/s; 100 Pa

Measurement point: 1,5 m/s; 50 Pa

254

Smoke extract roof fans


qv [m/h]
qv [m/h]

DVG-V 630-S/F
4-pole

DVG-V 630/F

4-pole

6-pole

6-pole 8-pole qv [m/s]


dB(A) 4-pole LwA Inlet LwA Outlet 6-pole LwA Inlet LwA Outlet 8-pole LwA Inlet LwA Outlet 78 77 56 61 74 69 70 70 70 70 69 72 69 67 61 59 52 50 85 84 55 63 78 74 78 78 78 77 77 79 78 75 70 67 62 57 94 93 60 66 86 84 80 84 83 86 87 88 87 84 87 79 72 68 Tot 63 125 Frequency bands [Hz] 250 500 1k 2k 4k 8k 4-pole LwA Inlet LwA Outlet 6-pole LwA Inlet LwA Outlet 8-pole LwA Inlet LwA Outlet 81 82 59 66 77 74 73 75 73 75 72 77 72 72 64 64 55 55 87 89 57 69 80 79 80 83 80 82 79 84 80 80 71 72 64 62 97 96 68 66 79 85 91 86 90 89 92 89 87 89 81 87 72 77 dB(A) Tot 63 125
8-pole

qv [m/s]

Frequency bands [Hz] 250 500 1k 2k 4k 8k

Measurement point: 2,8 m/s; 500 Pa

Measurement point: 3,8 m/s; 500 Pa

Measurement point: 2,2 m/s; 100 Pa

Measurement point: 2,8 m/s; 120 Pa

Measurement point: 1,7 m/s; 60 Pa

Measurement point: 2,1 m/s; 80 Pa

DVG-V 800-S/F

DVG-V 800/F

6-pole

8-pole

dB(A) 6-pole LwA Inlet LwA Outlet

Tot 63 125

Frequency bands [Hz] 250 500 1k 2k 4k 8k

dB(A) 6-pole

Tot 63 125

Frequency bands [Hz]

Smoke extract fans

250

500

1k

2k

4k

8k

88 91

48 56

64 70

69 76

78 84

81 88

84 84

83 79

70 64

LwA Inlet LwA Outlet 8-pole

96 94

55 42

65 65

81 75

87 87

89 91

93 87

86 77

83 67

Measurement point: 4,2 m/s; 300 Pa 8-pole LwA Inlet LwA Outlet 82 83 34 45 58 61 64 68 70 77 76 79 79 75 70 68 67 69

Measurement point: 5,4 m/s; 400 Pa

LwA Inlet LwA Outlet

90 87

48 42

62 59

70 70

79 82

88 84

84 77

77 69

71 63

Measurement point: 3,6 m/s; 100 Pa

Measurement point: 3,9 m/s; 250 Pa

255

Smoke extract roof fans DVG-V, H 400D4V/400


Smoke and heat extract unit + normal ventilation Up to 400C/120 min (F400/120, F400/90, F300, F200) Normal ventilation up to 120C continuous operation Horizontal/Vertical exhaust Service switch serial Suitable for coastal applications Suitable for speed control with transformer Nominal motor power 0,55 kW (not affected by Commission regulation (EC) No 640/2009) Wide range of accessories Tested acc. to EN 12101-3 at LGAI, Barcelona CE-certification acc. to EN 12101-3, 2002-06 at TV Sd Electrical accessories

RTRD p. 321

STDT 16 p. 342

The DVG smoke extract fans are used in case of fire to extract smoke gases from rooms, and also during normal working conditions for standard ventilation. Smoke-free escape ways increase the chances to rescue people in case of a fire. For installation only on top of heated buildings. The casing is manufactured from seawater resistant aluminium.

The base frame consists of galvanised steel. The impeller with backward-curved blades is manufactured from galvanised steel. Motor outside air stream of IE1 standard efficiency is cooled with fresh air. Thermal contact built-in motor. In case of fire eventual transformer and all protective devices must be bridged to guarantee functional capability (connection direct to mains).

Technical data
DVG/F DVG-V 400D4V Art no. V (vertical) 95220 Voltage/Frequency V/50 Hz 400 3~ kW 0.55 A 1.5 A 5.4 m3/s 1.32 min
-1

DVG-H 400D4V Art no. H (horizonal) 95221 400 3~ 0.55 1.5 5.4 1.42 1290 120 400 63 56 44 F IP 55 7

Smoke extract fans

Power at shaft Current Starting current Max air flow R.p.m. Max. temp. of transp. air Max. temp. of transp. air* Sound pressure level at 4 m Sound pressure level at 10 m Weight Insulation class, motor Enclosure class, motor Wiring diagram p. 391-400 *for 120 min

1290

C 120 C 400 dB(A) 62 dB(A) 55 kg 46 F IP 55 7

256

Smoke extract roof fans


Dimensions DVG/F-V DVG/F-H Ventilation accessories

38

38

ASFV p. 384

12

6xM
535 724

12
535 724

6xM

ASK/F p. 380

557

557

ASSG/F p. 383
289 379 670

251

668 1053

668
240 max

289 379 670

240 max

FDG/F p. 377

FDGE/F p. 378

SSG/F p.378

SSGE/F p. 379

VKG/F p. 383

Smoke extract fans

dB(A) LwA Inlet LwA Outlet

Tot 63 82 82 55 60 125 76 71

Frequency bands [Hz] 250 75 78 500 73 73 1k 74 75 2k 73 73 4k 68 56 8k 65 82

dB(A) LwA Inlet LwA Outlet

Tot 63 82 83 55 61 125 76 72

Frequency bands [Hz] 250 76 78 500 73 74 1k 74 76 2k 73 75 4k 68 70 8k 65 60

Measurement point: 0.62 m/s; 315 Pa

Measurement point: 0.78 m/s; 290 Pa

257

Smoke extract roof fans

Installation example DVG


DVG-V DVG-V

SSG/F Silencer ASG/F Inlet chamber VKG/F Automatic shutter


ASSG/F Flexible connection

VKG/F Automatic shutter ASSG/F Flexible connection FDG/F Silencer

DVG-V

DVG-V

VKG/F Automatic shutter SSG/F Silencer ASG/F Inlet chamber ASSG/F Flexible connection

VKG/F Automatic shutter SSGE/F (FDGE/F) Silencer ASG/F Inlet chamber ASSG/F Flexible connection

Smoke extract fans

258

Smoke extract roof fans

Smoke extract fans

259

Smoke extract square duct fans MUB/F


Smoke extract unit 400/120 min. (F400) Insulated casing Low sound level For dual purpose operation Tested according to EN 12101-3 at LGAI Barcelona Electrical accessories

REV DVV p. 340

400C 120min

The smoke extract units MUB/F are used in case of fire to extract smoke gases from rooms, and also during normal working conditions for standard temperature up to 55C continuously. The MUB/F units have backward curved impellers made of galvanized steel. The outlet can be easily changed on site from straight to side outlet. The unit is made of a profiled steel frame design. All materials are galvanized and seawater resistant. Motors are high temperature motors for temperature classification F 400/120 min. The fan has a double skinned panel with smooth surface to protect against dust and dirt. Motor can be wired for either single speed or 2-speed execution.

Quick selection

1 2 3 4 5 6

MUB/F 042 400D4 MUB/F 042 400D6 MUB/F 042 450D4 MUB/F 042 450D6 MUB/F 062 500D4 MUB/F 062 500D6

1 2 3 4

MUB/F 062 560D4 MUB/F 062 560D6 MUB/F 062 630D4 MUB/F 062 630D6

Technical data
MUB/F Art no. Voltage/Frequency Power at shaft Current Max air flow R.p.m. Max temp. of transported air Max temp. of transported air for 120 min Sound pressure level at 3 m Sound pressure level at 4 m Sound pressure level at 10 m Weight Insulation class, motor Enclosure class, motor Wiring diagram p. 391-400 042 400D4 33290 V/50 Hz 400 3~ W 550 A 1.32 m3/s 1.49 min-1 1461 C 55 C 400 dB(A) 31 dB(A) 39 dB(A) 55 kg 98 HC IP 55 10 042 400D4-6 33292 400 3~ 550/180 1.32/0.80 1.49/0.99 1461/980 55 400 31/23 39/31 55/47 105 HC IP 55 15a 042 450D4 33293 400 3~ 750 1.63 1.58 1446 55 400 33 41 57 105 HC IP 55 10 042 450D4-6 33295 400 3~ 750/250 1.63/0.90 1.58/1.04 1446/971 55 400 33/25 41/33 57/49 111 HC IP 55 15a 062 500D4 33296 400 3~ 1500 3.26 2.27 1440 55 400 42 50 66 134 HC IP 55 10 062 500D4-6 33298 400 3~ 1500/550 3.26/1.76 2.27/1.53 1440/967 55 400 42/31 50/39 66/55 136 HC IP 55 15a

Smoke extract fans

260

Smoke extract square duct fans


Dimensions Ventilation accessories
MUB/F 42 400 42 450 62 500 62 560 62 630 A 670 670 800 800 800 B 670 670 800 800 800 C 590 590 720 720 720 D 548 548 676 676 676 E 410 454 520 570 650 H 400 400 560 560 630 I 289 289 364 364 456 J max. 783 783 915 915 915

FGV p. 370

A J

SDM p. 369

SRKG p. 370

I H E D C B

UGS p. 370

WSD p. 370

MUB/F Art no. Voltage/Frequency Power at shaft Current Max air flow R.p.m. Max temp. of transported air Max temp. of transported air for 120 min Sound pressure level at 3 m Sound pressure level at 4 m Sound pressure level at 10 m Weight Insulation class, motor Enclosure class, motor Wiring diagram p. 391-400

062 560D4 33299 V/50 Hz 400 3~ W 2200 A 4.58 m3/s 2.66 min-1 1440 C 55 C 400 dB(A) 45 dB(A) 53 dB(A) 69 kg 154 HC IP 55 10

062 560D4-6 33301 400 3~ 2200/750 4.58/2.47 2.66/1.77 1440/972 55 400 45/34 53/42 69/58 155 HC IP 55 15a

062 630D4 33302 400 3~ 4000 8.58 3.83 1459 55 400 51 59 75 163 HC IP 55 10

062 630D6 33303 400 3~ 1500 3.93 2.52 979 55 400 40 48 64 158 HC IP 55 10

062 630D4-6 33304 400 3~ 4000/1500 8.58/3.93 3.83/2.52 1459/979 55 400 51/40 59/48 75/64 190 HC IP 55 15a

Smoke extract fans

261

Smoke extract square duct fans

MUB 042 400D4/F

MUB 042 400D4/F

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 77 73 61 63 62 35 125 72 64 50

Frequency bands [Hz] 250 71 63 60 500 70 64 50 1k 69 66 50 2k 65 66 45 4k 62 61 40 8k 57 55 36

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 77 79 62 62 64 42 125 69 72 49

Frequency bands [Hz] 250 71 72 61 500 71 72 51 1k 69 73 50 2k 67 72 47 4k 64 67 42 8k 58 59 38

Measurement point: 0,67 m/s; 300 Pa

Measurement point: 0,769 m/s; 349 Pa

MUB 042 450D4/F

MUB 042 450D4/F

Smoke extract fans

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 81 76 65 63 42 49 125 69 60 56

Frequency bands [Hz] 250 69 62 61 500 71 67 54 1k 71 69 56 2k 75 71 55 4k 75 70 55 8k 67 61 49

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 80 79 64 45 53 31 125 69 67 58

Frequency bands [Hz] 250 68 68 58 500 71 72 54 1k 72 72 57 2k 74 72 53 4k 74 71 54 8k 65 61 47

Measurement point: 0,767 m/s; 400 Pa

Measurement point: 0,922 m/s; 465 Pa

262

Smoke extract square duct fans

MUB 062 500D4/F

MUB 062 500D4/F

dB(A) LwA Inlet LwA Outlet

Tot 63 84 79 68 55 50 125 77 64 65

Frequency bands [Hz] 250 78 65 70 500 78 71 61 1k 74 75 62 2k 75 73 64 4k 74 71 61 8k 65 61 46

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 85 80 73 69 57 51 125 78 68 65

Frequency bands [Hz] 250 78 70 70 500 78 72 62 1k 75 75 62 2k 75 73 65 4k 74 72 61 8k 65 63 46

LwA Surrounding 73

Measurement point: 1,25 m/s; 449 Pa

Measurement point: 1,16 m/s; 526 Pa

MUB 062 500D6/F

MUB 062 500D6/F

Smoke extract fans

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 75 71 62 62 59 42 125 69 61 57

Frequency bands [Hz] 250 65 58 56 500 67 62 52 1k 65 65 52 2k 67 65 55 4k 61 61 48 8k 50 52 32

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 74 71 62 60 55 41 125 69 65 57

Frequency bands [Hz] 250 65 60 55 500 67 63 51 1k 65 65 52 2k 68 65 55 4k 62 60 48 8k 51 48 33

Measurement point: 0,741 m/s; 216 Pa

Measurement point: 0,793 m/s; 235 Pa

263

Smoke extract square duct fans

MUB 062 560D4/F

MUB 062 560D4/F

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 85 82 76 71 72 52 125 80 74 74

Frequency bands [Hz] 250 79 72 68 500 76 75 64 1k 74 75 62 2k 74 74 61 4k 74 73 58 8k 68 67 49

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 85 86 76 75 65 55 125 81 84 74

Frequency bands [Hz] 250 78 75 68 500 76 76 64 1k 74 76 63 2k 75 75 62 4k 75 74 59 8k 69 67 50

Measurement point: 1,55 m/s; 562 Pa

Measurement point: 1,48 m/s; 676 Pa

MUB 062 560D6/F

MUB 062 560D6/F

Smoke extract fans

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 75 81 65 61 68 44 125 70 73 59

Frequency bands [Hz] 250 68 73 59 500 65 76 55 1k 65 73 55 2k 66 70 56 4k 65 65 55 8k 55 58 40

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 76 73 65 63 56 46 125 71 64 60

Frequency bands [Hz] 250 67 65 59 500 66 65 55 1k 66 66 56 2k 67 65 57 4k 64 63 54 8k 56 54 40

Measurement point: 1,05 m/s; 245 Pa

Measurement point: 0,99 m/s; 302 Pa

264

Smoke extract square duct fans

MUB 062 630D4/F

MUB 062 630D4/F

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 93 93 83 79 82 62 125 85 84 74

Frequency bands [Hz] 250 87 84 81 500 87 87 70 1k 85 87 70 2k 84 84 72 4k 79 80 67 8k 72 74 56

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 92 94 82 74 85 58 125 83 83 72

Frequency bands [Hz] 250 85 87 80 500 86 87 69 1k 85 87 69 2k 83 85 71 4k 79 80 66 8k 72 74 56

Measurement point: 1,48 m/s; 741 Pa

Measurement point: 1,91 m/s; 800 Pa

MUB 062 630D6/F

MUB 062 630D6/F

Smoke extract fans

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 83 80 71 67 63 48 125 76 68 68

Frequency bands [Hz] 250 75 71 64 500 76 75 61 1k 75 75 60 2k 72 71 61 4k 67 66 55 8k 65 60 46

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 82 81 71 65 68 46 125 76 74 67

Frequency bands [Hz] 250 75 72 64 500 76 75 60 1k 74 75 60 2k 72 72 61 4k 67 67 55 8k 64 62 45

Measurement point: 0,994 m/s; 265 Pa

Measurement point: 1,26 m/s; 352 Pa

265

Smoke extract axial fans AXC(B)


Smoke extract axial fans certified for 300C/120 min. in accordance with EN 12101-3. Standard features:
AXC with aerofoil impeller, adjustable pitch angle. Die cast aluminium hub and blades. Long casing, hot dip galvanized steel, to DIN EN ISO 1461. Spun flanges for high rigidity, to Eurovent 1/2. Terminal box in IP65 mounted at the outside of the casing for easy wiring. Motors IP54, insulation class H, in accordance with EN 60034-5/IEC 85. Suitable for operating temperatures of up to 55C continuous or once for 300C/120 min. Truly reversible version AXR (B) on request.

300C 120min

The Systemair AXC (B), AXR (B) range of long cased smoke extract axial fans is available in sizes from 315 up to 1600 mm impeller diameter. The adjustable pitch angle setting offers a wide performance and maximum flexibility to match precisely individual airflow requirements. The AXC (B) and AXR (B) axial fans have been performance tested in accordance with DIN ISO 5801, DIN 24163 and AMCA 210-99 on the Systemair fan test rig. High temperature testing at Technical University Munich, Germany. All AXC (B) fans are labeled with CE-mark and they are DIBt approved.

High efficiency impellers


The AXC die cast aerofoil aluminium impellers can be offered with full or fractional solidities, maximum efficiencies can be obtained. AXR impellers are truly reversible.

Multi stage fans


For higher pressure drops two stage fans are offered. Two fans in series increase the available static pressure drop.

Sturdy casing
AXC and AXR axial fan casings are heavy gauge, hot dip galvanized, with spun flanges for high rigidity. Long cased execution as standard stock range.

Motors
Motors are air stream mounted. Frequency converter controllable only for standard ventilation on request. Single or two speed motors.

Smoke extract fans

Ordering code AXR AXC 630 - 9 / 22 - 2 Box G B

Axial fan reversible Two stage, two fans in series Sound insulated 300/120 min. 2-pole motor Pitch angle Number of blades Nominal diameter Axial fan unidirectional

266

Smoke extract axial fans

Smoke extract fans

267

Smoke extract centrifugal fans WVA/WVI


Smoke extract unit for wall mounting 400C/120 min (type F400) resp. 600C/120 min (type F600) Wide range of accessories Certified acc. to EN 12101-3 at TU Munich CE-certified acc. to EN 12101-3, 2002-06 at TV Sd Electrical accessories

REV DVV p. 340

400C 120min

600C 120min

The WVI smoke extract fans are used in case of fire to extract smoke gases from rooms, and also for daily ventilation (dual purpose fans). Smoke-free escape ways increase the chances to rescue people in case of fire. The casing is manufactured from steel, powder coated RAL 7032. The base frame consists of galvanised steel. The impeller with backward-curved blades is manufactured from galvanised steel resp. stainless steel (type F600). Thermal motor protection on request (PTC or thermal contact). In case of fire all motor protective devices must be bridged to guarantee functional capability.

WVA For installation only outside the building. Fans are certified for horizontal installation on a wall, motor pointing downwards. WVI With insulated motor for installation inside the building and inside the fire zone. Cooling of motor via air duct (accessories). Fans are certified for horizontal installation on a outer wall, motor facing downwards. Note: Article numbers in tables refer to items without PTC or thermal contact. IE2 single speed motors are available with PTC built-in. Data related to motor and weight of delivered items can vary from catalogue data due to different suppliers.

Quick selection

1 2 3

WVA/WVI 630D4-K WVA/WVI 630D6-K WVA/WVI 630D8-K

4 5 6 7 8

WVA/WVI 630D4 WVA/WVI 630D6 WVA/WVI 800D6-K WVA/WVI 800D8-K WVA/WVI 800D12-K

1 2 3

WVA/WVI 630D4-K WVA/WVI 630D6-K WVA/WVI 630D8-K

4 5 6 7 8

WVA/WVI 630D4 WVA/WVI 630D6 WVA/WVI 800D6-K WVA/WVI 800D8-K WVA/WVI 800D12-K

3 8

3 5 7 6 8

Technical data
WVA/WVI Art no. WVA F400 Art no. WVA F600 Art no. WVI F400 Art no. WVI F600 Voltage/Frequency Power at shaft Current Starting current Max air flow R.p.m. Max. temp. of transported air Max. temp. of transported air* Sound pressure level 4 m Sound presssure level 10 m Weight Insulation class, motor Enclosure class, motor Wiring diagram p. 391-400 * for 120 min 400D4 30736 30789 30763 30815 V/50 Hz 400 3~ kW 0.55 A 1.6 A 6.6 m3/s 1.22 min-1 1390 C 55 C 400/600 dB(A) 68 dB(A) 57 kg 48 F IP 54 15b 400D4-6 30737 30790 30764 30816 400 3~ 0.55/0.18 1.7/0.8 6.8/2.4 1.22/0.778 1420/940 55 400/600 68/54 57/43 48 F IP 54 15a 400D4-8 95099 95100 95105 95106 400 3~ 0.5/0.12 1.6/0.6 5.8/1.3 1.22/0.61 1410/670 55 400/600 68/48 57/37 48 F IP 54 14a 450D4 30739 30792 30766 30818 400 3~ 1.1 2.7 11.8 1.81 1390 55 400/600 75 64 64 F IP 54 15b 450D4-6 30740 30793 30767 30819 400 3~ 1.1/0.37 3/1.4 10.8/5.9 1.81/1.15 1420/950 55 400/600 75/63 64/52 67 F IP 54 15a 450D4-8 95101 95102 95107 95108 400 3~ 1.1/0.25 3.1/1.2 12.4/3.0 1.81/0.89 1400/690 55 400/600 75/56 64/45 67 F IP 54 14a 560D4 30742 30795 30769 30821 400 3~ 1.5 3.6 17.3 2.5 1390 55 400/600 77 66 81 F IP 54 15b 560D4-6 30743 30796 30770 30882 400 3~ 1.7/1.2 4.6/3.7 23.9/13.3 2.5/1.56 1450/940 55 400/600 77/66 66/55 87 F IP 54 15a 560D4-8 95103 95104 95109 95110 400 3~ 2.0/0.5 5.0/2.0 22.5/6.0 2.5/1.19 1420/700 55 400/600 77/59 66/48 89 F IP 54 14a

Smoke extract fans

268

Smoke extract centrifugal fans


Dimensions WVA
A M8

WVI
A M8 D C B

Ventilation accessories

D C B

EPSN/EPIN p. 389

max. F

E R

IN p. 390
P G

SN p. 390

WBK-W p. 389

J K

J K

ZHZ p. 389

More detailed dimensions on www.systemair.com


WVA/WVI 400 450 560 630 800 1000 A 536 746 746 836 B 286 286 316 391 C 250 250 280 355 400 630 D 500 710 710 800 E 33 33 33 33 F 250 300 350 450 450 600 G 500 500 630 710 900 1180 H 536 536 666 746 936 1216 I 670 764 855 J 472 528 590 K 790 886 991 L 290 340 380

M 356 (8xM8) 395 (8xM8) 438 (12xM8) 541 (12xM8) 674 (16xM10) 751 (16xM10)

P 510 638 638 808 980 980

R 116 240 200 349 295 442

S 200 200 225 225 250 250

Inlet duct connection 315 355 400 500 630 710

1055 730 1300 930

1237 465 1545 560

1156 436 1446 666

1120 43 1400 43

1400 1010 1700 580

WVA/WVI Art no. WVA F400 Art no. WVA F600 Art no. WVI F400 Art no. WVI F600 Voltage/Frequency Power at shaft Current Starting current Max air flow R.p.m. Max. temp. of transported air Max. temp. of transported air* Sound pressure level 4 m Sound presssure level 10 m Weight Insulation class, motor Enclosure class, motor Wiring diagram p. 391-400 * for 120 min

630D4-K 30750 30802 30776 30828 V/50 Hz 400 3~ kW 3.0 A 6.9 A 38.0 m3/s 3.28 min-1 1400 C 55 C 400/600 dB(A) 78 dB(A) 67 kg 169 F IP 54 15b

630D4-6-K 30751 30803 30777 30829 400 3~ 3.0/0.9 6.9/3.3 38.0/13 3.28/2.17 1450/975 55 400/600 78/69 67/58 176 F IP 54 15a

630D4-8-K 30752 30804 30778 30830 400 3~ 3.6/0.9 8.0/3.2 44.0/10.0 3.28/1.61 1430/710 55 400/600 78/62 67/51 175 F IP 54 14a

630D4 30746 30798 30772 30824 400 3 ~ 5.5 11.0 75.5 4.75 1440 55 85 74 179 F IP 54 13a D

630D4-6 30747 30799 30773 30825 400 3~ 5.5/1.7 12.0/4.5 81.6/20.3 4.75/3.06 1460/970 55 85/77 74/66 183 F IP 54 15a

800D6-K 30757 30809 30783 30835 400 3~ 2.2 5.7 30.2 4.28 930 55 400/600 74 63 204 F IP 54 15b

800D6-8-K 30758 30810 30784 30836 400 3~ 2.2/0.9 6.0/3.3 27.7/11.7 4.28/3.31 965/730 55 400/600 74/65 63/54 220 F IP 54 15a

800D6-12-K 30759 30811 30785 30837 400 3~ 2.5/0.5 7.5/2.7 38.0/5.2 4.28/2.17 970/465 55 400/600 74/55 63/44 211 F IP 54 14a

800D6 30754 30806 30780 30832 400 3~ 5.5 13.0 75.4 6.19 950 55 400/600 78 67 231 F IP 54 13a D

Smoke extract fans

400/600 400/600

269

Smoke extract centrifugal fans

1 2 3 4 5 6

WVA/WVI 800D6 WVA/WVI 800D8 WVA/WVI 800D12 WVA/WVI 1000D6 WVA/WVI 1000D8 WVA/WVI 1000D12
4

2 6 3

Installation examples
Flexible connection EPSN Outer wall Inlet duct SN Air direction Inlet duct SN Outlet duct in Air direction Cooling duct ZHZ Cooling air Supports WBK-W Supports WBK-W
WVA/WVI Art no. WVA F400 Art no. WVA F600 Art no. WVI F400 Art no. WVI F600 Voltage/Frequency Power at shaft Current Starting current Max air flow R.p.m. Max. temp. of transported air Max. temp. of transported air* Sound pressure level 4 m Sound presssure level 10 m Weight Insulation class, motor Enclosure class, motor Wiring diagram p. 391-400 * for 120 min 800D6-8 30755 30807 30781 30833 V/50 Hz 400 3~ kW 5.7/2.4 A 12.3/6.2 A 62.8/21.7 m3/s 6.19/4.72 min-1 960/720 C 55 C 400/600 dB(A) 78/68 dB(A) 67/57 kg 231 F IP 54 15a 800D6-12 30756 30808 30782 30834 400 3~ 5.1/1.0 13.5/4.4 75.0/12.0 6.19/3.06 960/470 55 400/600 78/57 67/46 249 F IP 54 14a 1000D6 30760 30812 30786 30838 400 3~ 11.0 22.0 154 11.1 965 55 400/600 83 72 407 F IP 54 13a D 1000D6-8 30761 30813 30787 30839 400 3~ 11.0/5.0 22.0/15.0 154/82.5 11.1/8.11 970/730 55 400/600 83/75 72/64 472 F IP 54 15a 1000D6-12 30762 30814 30788 30840 400 3~ 12.0/2.4 23.0/7.5 140.0/23.3 11.1/5.42 960/480 55 400/600 83/67 72/56 472 F IP 54 14a

Outer wall

Environment

Environment

WVI

Fire zone

Fire zone WVA Outlet duct in Cooling air

Air direction

Smoke extract fans

270

Smoke extract centrifugal fans

4-pole

61

6-pole
62

8-pole

dB(A) 4-pole LwA Inlet LwA Outlet 6-pole LwA Inlet LwA Outlet 8-pole LwA Inlet LwA Outlet

Tot 63 125

Frequency bands [Hz] 250 500 1k 2k 4k 8k

dB(A) 4-pole

Tot 63 125 60 71

Frequency bands [Hz] 250 76 84 500 80 87 1k 78 86 2k 73 83 4k 73 79 8k 62 69

80 87

41 51

56 66

72 79

76 82

74 81

69 78

69 74

58 64

LwA Inlet LwA Outlet

84 92

45 56

Measurement point: 1,0 m/s; 210 Pa 70 74 31 39 49 55 63 66 67 69 63 68 58 65 60 62 46 50

Measurement point: 1,25 m/s; 400 Pa 6-pole LwA Inlet LwA Outlet 74 79 35 44 53 60 67 71 70 74 67 73 62 70 64 67 50 55

Measurement point: 0,53 m/s; 150 Pa 61 68 25 38 42 55 54 61 57 63 54 61 54 60 45 53 32 42

Measurement point: 0,8 m/s; 150 Pa 8-pole LwA Inlet LwA Outlet 67 72 31 42 48 59 60 65 63 67 60 65 60 64 51 57 38 46

Measurement point: 0,4 m/s; 75 Pa

Measurement point: 0,62 m/s; 100 Pa

4-pole

4-pole 6-pole 8-pole

6-pole 8-pole

dB(A) 4-pole LwA Inlet LwA Outlet 6-pole LwA Inlet LwA Outlet 8-pole LwA Inlet LwA Outlet

Tot 63 125

Frequency bands [Hz] 250 500 1k 2k 4k 8k

dB(A) 4-pole

Tot 63 125

Frequency bands [Hz] 250 500 1k 2k 4k 8k

Smoke extract fans

89 97

50 61

65 76

81 89

85 93

83 90

78 88

78 84

67 74

LwA Inlet LwA Outlet 6-pole

91 98

57 68

75 88

85 92

86 91

83 93

83 88

81 87

62 71

Measurement point: 1,53 m/s; 570 Pa 81 86 42 51 60 67 74 78 78 81 74 80 69 77 71 74 57 62

Measurement point: 2,0 m/s; 750 Pa LwA Inlet LwA Outlet 8-pole 82 89 49 60 66 79 77 83 77 83 74 82 73 78 71 77 52 61

Measurement point: 1 m/s; 220 Pa 71 75 35 45 52 62 64 68 67 70 64 68 64 67 55 60 42 49

Measurement point: 1,34 m/s; 330 Pa LwA Inlet LwA Outlet 76 82 47 60 62 71 70 77 71 76 68 75 69 72 63 67 46 53

Measurement point: 0,78 m/s; 130 Pa

Measurement point: 1,0 m/s; 185 Pa

271

Smoke extract centrifugal fans

4-pole

6-pole 8-pole

6-pole

12-pole

dB(A) 4-pole LwA Inlet LwA Outlet 6-pole LwA Inlet LwA Outlet

Tot 63 125

Frequency bands [Hz] 250 500 1k 2k 4k 8k

dB(A) 6-pole

Tot 63 125 69 84

Frequency bands [Hz] 250 80 87 500 80 88 1k 77 88 2k 76 83 4k 74 82 8k 55 66

97 102

59 68

74 83

89 94

93 98

92 96

87 95

87 91

76 81

LwA Inlet LwA Outlet 8-pole

85 94

52 65

Measurement point: 3,45 m/s; 700 Pa 90 95 51 60 69 76 83 87 87 90 83 89 78 86 80 83 66 71

Measurement point: 3,3 m/s; 350 Pa LwA Inlet LwA Outlet 12-pole LwA Inlet LwA Outlet 69 75 43 55 52 62 63 68 64 69 61 70 61 66 55 56 40 53 79 85 50 63 65 74 73 79 74 79 71 78 72 75 66 70 49 56

Measurement point: 2,22 m/s; 300 Pa

Measurement point: 2,23 m/s; 300 Pa

Measurement point: 1,4 m/s; 140 Pa

6-pole

6-pole 8-pole 12-pole


12-pole 8-pole

dB(A)

Tot 63 125 71 79

Frequency bands [Hz] 250 85 90 500 89 93 1k 85 92 2k 80 89 4k 82 86 8k

dB(A) 6-pole

Tot 63 125

Frequency bands [Hz] 250 500 1k 2k 4k 8k

Smoke extract fans

6-pole LwA Inlet LwA Outlet 8-pole LwA Inlet LwA Outlet 12-pole LwA Inlet LwA Outlet 70 77 40 49 53 61 63 68 64 71 59 72 67 70 57 64 36 47 81 88 45 58 62 75 74 81 77 83 74 81 74 80 65 73 52 62 92 98 53 63 68 74

LwA Inlet LwA Outlet 8-pole LwA Inlet LwA Outlet 12-pole LwA Inlet LwA Outlet

95 103

62 74

79 93

90 96

90 97

87 96

86 92

84 91

65 75

Measurement point: 4,28 m/s; 550 Pa

Measurement point: 8,0 m/s; 600 Pa 86 95 57 73 72 84 80 90 81 89 78 88 79 85 73 80 56 66

Measurement point: 3,26 m/s; 310 Pa

Measurement point: 5,6 m/s; 370 Pa 79 87 53 67 62 74 73 80 74 81 71 82 71 78 65 68 50 65

Measurement point: 2,13 m/s; 140 Pa

Measurement point: 3,9 m/s; 150 Pa

272

Smoke extract centrifugal fans Installation examples Axial fans

SG Protection guard

ESD-F Inlet cone

MP (4x angle 90) Mounting brackets RSA Silencer EV-AXC Flexible connection AXC

REV (60) on/off switch REV (F) suitable for high temperature

LRK Air operated damper

MFA Mounting feet FSD (4x) ZSD (4x) Tension load

GFL Counter flange

SD (4x)

Smoke extract fans

273

Fans for aggressive media

General

Single inlet centrifugal fan PRF


Casing Standard casing in PE, water tight, with connections from 125 to 250mm dia meter. Can be turned to have other outlet directions. Standard position LG270 (as per illustration). Motor pedestal Manufactured from steel, powder coated. Impellers Single inlet impellers manufactured from PP. Motors IEC standard motors, separated from the airstream, in ISO F, equipped with PTC cold conductors or with thermal contacts, to be connected to a motor protection device.

Roof fan DVP


Casing Vertical outlet casing and single inlet backward curved impeller manufactured from PP. Motors Motor speed controllable by frequency inverter. Connections from 200 to 400mm diameter.

Plastic fans for aggressive media


These sturdy plastic fans have been developed especially for applications where dirt or aggressive gases can contaminate the exhaust air. Typical applications are laboratories in medical or pharmaceutical institutions, food industry and chemical industry.

PRF . . . . . . . . . . . . . . . . . . . 276 Plastic fan: up to 1.83 m3/s, backward curved impeller, 1 phase and 3 phase.

DVP. . . . . . . . . . . . . . . . . . . 280 Plastic roof fan: up to 2.11 m3/s, backward curved impeller, 1 phase and 3 phase.

For aggressive media

274

Fans for aggressive media

Installation example
PRF VP Splinter protection

ASSP Flexible connection ASS-P Flexible connection VKA-P Adjustable damper SD Anti vibration mounts

VKS-P Automatic shutter

For aggressive media

275

Aggressive media centrifugal fans PRF


Temperature of transported air from -15C to +70C Single-inlet impellers from PP with effective blade geometry The powder painted pedestal is manufactured from galvanised steel Position of casing can be easily adapted Perfect fitting accessories: connections, dampers, splinter protection Electrical accessories

REU p. 320

The PRF fans have been developed especially for the exhaust of aggressive media. This is the right fan when corrosive gases, contaminated air or other aggressive components are part of the exhaust air. Typical applications are medical facilities, the food-, electrical- or chemical industry. The sintered casing from UV-resistant PE is absolutely waterproof and offers a variety of applications with its connectors from 125-250 mm. The casing can be easily adjusted through turning it (standard position is LG270, see picture).

RTRE p. 320

REV p. 340

Quick selection S-ET p. 341


1 2 3 4 5 6

3.000
1 2 3 4 5 6

PRF 125D2 PFR 160D2 PRF 160D4 PRF 160E4 PRF 180D2 PRF 180DV

2.500

PRF 180E4 PRF 200D2 PRF 200DV PRF 250D2 PRF 250D4 PRF 250D2-L

2.000

1.500
1 2 5
6

1.000
6

500
4 3

3 1

0 0 0,2 0,4 0,6 0,8 1 1,2 1,4 1,6 1,8 2,0 2,2

Technical data
PRF Art no. Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Capacitor Motor protection Speed control, five-step Speed control, five-step high/low Speed control, stepless Wiring diagram p. 391-400 125D2 31525 V/50 Hz 400 3~ W 250 A 0.579 m3/s 0.197 min-1 2806 C 70 C 70 dB(A) 59 kg 9 F IP 55 F Transformer Transformer 13b Y 160D2 IE2 33562 400 3~ 750 1.68 0.464 2825 70 70 67 13 F IP 55 FRQ5(S)-4A FRQ(S)-4A 13b Y 160D4 31495 400 3~ 142 0.571 0.228 1467 70 50 14 F IP 55 13b Y 160E4 31545 230 1~ 171 0.75 0.213 1427 70 46 14 F IP 54 6 S-ET 10 RTRE 1.5 REU 1.5 21 180D2 IE2 33563 400 3~ 1100 2.37 0.635 2825 70 70 68 19 F IP 55 FRQ5(S)-4A FRQ(S)-4A 13b Y 180DV 31497 400 3~ 229 1.01 0.32 1365 70 70 49 14 F IP 54 STDT 16 RTRD 2 RTRDU 2 13b D

For aggressive media

276

Aggressive media centrifugal fans


Dimensions
C

Ventilation accessories
L E

ASS-P p. 285
D

A H

SD-PRF p. 285
N P Q D

PRF 125D2 160D2 160D4/E4 180D2 180E4/DV 200D2 200DV 250D2 250D2-L 250DV

A 140 183 183 208 208 240 240 290 290 290

C 40 40 40 40 40 40 40 40 40 40

D 125 160 160 180 180 200 200 250 250 250

E 150 180 180 190 190 200 200 240 240 240

H 250 310 310 350 350 410 410 495 495 495

L 195 210 190 230 190 245 210 340 230

N 200 255 255 277 277 320 320 330 330 330

P 100 100 100 120 120 150 150 170 170 170

Q 140 140 140 190 190 230 230 250 250 250

R 235 290 290 320 320 355 355 370 370 370

VKA-P p. 285

VKS-P p. 285

VP p. 285

WSD PRF p. 285

PRF Art no. Voltage/Frequency Power Current Max air flow R.p.m. Min. back pressure Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Capacitor Motor protection Speed control, five step Speed control, five step high/low Wiring diagram p. 391-400

180E4 31564 V/50 Hz 230 1~ W 140 A 1.11 m3/s 0.32 min-1 1365 Pa C 70 C 70 dB(A) 49 kg 15 F IP 54 F 6 S-ET 10 Transformer RTRE 1.5 Transformer REU 1.5 21

200D2 IE2 33564 400 3~ 1500 3.16 0.937 2840 400 70 70 74 29 F IP 55 13b Y

200DV 31499 400 3~ 250 0.95 0.47 1413 70 70 60 19 F IP 54 STDT 16 RTRD 2 RTRDU 2 13b D

250D2 IE2 33566 400 3~ 4000 7.64 1.83 2890 2000 70 70 95 50 F IP 55 13b D

250D2-L IE2 34531 400 3~ 5500 10.4 1.87 2855 600 70 70 95 60 F IP 54 13b D

250D4 IE2 33565 400 3~ 750 1.78 0.911 1400 70 70 66 35 F IP 54 13b D

For aggressive media

277

Aggressive media centrifugal fans


pERFORMANCE
PRF 125D2
PRF 160D2 IE2

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 77 80 66 69 71 48 125 61 68 25

Frequency bands [Hz] 250 74 77 52 500 70 74 59 1k 68 69 64 2k 62 62 55 4k 55 58 48 8k 48 48 39

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 82 87 74 71 73 53 125 73 77 45

Frequency bands [Hz] 250 76 83 68 500 76 82 70 1k 75 78 67 2k 68 74 63 4k 60 68 53 8k 53 60 45

Measurement point: 0,0725 m/s; 589 Pa

Measurement point: 0,205 m/s; 877 Pa

PRF 160D4

PRF 160E4

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 67 70 57 57 58 17 125 59 64 25

Frequency bands [Hz] 250 63 66 53 500 59 62 52 1k 53 55 44 2k 51 51 48 4k 42 43 38 8k 33 34 29

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 67 67 53 63 55 32 125 62 59 40

Frequency bands [Hz] 250 58 64 43 500 57 62 48 1k 53 56 47 2k 49 51 45 4k 41 43 35 8k 33 34 31

Measurement point: 0,118 m/s; 196 Pa

Measurement point: 0,104 m/s; 195 Pa

PRF 180D2 IE2

PRF 180DV

Minimum back pressure 180 Pa


dB(A) Tot 63 LwA Inlet LwA Outlet LwA Surrounding 87 91 74 78 70 68 125 81 86 46 Frequency bands [Hz] 250 80 85 60 500 81 85 69 1k 80 83 69 2k 73 78 62 4k 67 71 53 8k 61 63 47 LwA Inlet LwA Outlet LwA Surrounding 70 73 56 dB(A) Tot 63 53 54 32 125 67 70 34 Frequency bands [Hz] 250 62 67 45 500 62 66 54 1k 58 60 49 2k 54 58 46 4k 48 49 37 8k 41 41 34

For aggressive media

Measurement point: 0,274 m/s; 1093 Pa

Measurement point: 0,17 m/s; 221 Pa

278

Aggressive media centrifugal fans

PRF 200D2 IE2

Minimum back pressure 400 Pa


dB(A) LwA Inlet LwA Outlet LwA Surrounding Tot 63 69 73 56 52 53 32 125 66 70 34 Frequency bands [Hz] 250 61 66 45 500 61 66 54 1k 58 60 49 2k 54 58 46 4k 47 49 37 8k 41 41 34 LwA Inlet LwA Outlet LwA Surrounding 90 93 81 dB(A) Tot 63 83 85 77 125 78 86 47 Frequency bands [Hz] 250 81 85 63 500 85 87 74 1k 84 85 75 2k 81 83 72 4k 74 74 63 8k 67 65 55

Measurement point: 0,17 m/s; 221 Pa

Measurement point: 0,345 m/s; 1576 Pa

PRF 200DV

PRF 250D2 IE2

Minimum back pressure 2000 Pa


dB(A) LwA Inlet LwA Outlet LwA Surrounding Tot 63 77 74 67 59 58 32 125 66 69 38 Frequency bands [Hz] 250 70 69 54 500 72 68 65 1k 70 63 58 2k 65 61 54 4k 58 51 48 8k 51 42 43 LwA Inlet LwA Outlet LwA Surrounding 102 102 95 dB(A) Tot 63 91 86 69 125 92 96 82 Frequency bands [Hz] 250 96 96 90 500 96 96 89 1k 93 94 88 2k 92 93 86 4k 87 85 83 8k 78 75 73

Measurement point: 0,383 m/s; 171 Pa

Measurement point: 0,824 m/s; 2002 Pa


0 2.000 4.000 6.000 8.000

PRF 250D4 IE2

3.000 2.500 2.000 1.500 1.000 500 0

PRF 250D2-L IE2

0,27 0,55 0,83 1,11

1,39 1,66 1,94 2,22

Minimum back pressure 550 Pa


dB(A) LwA Inlet LwA Outlet LwA Surrounding Tot 63 83 87 73 76 83 47 125 75 78 51 Frequency bands [Hz] 250 72 77 60 500 77 77 66 1k 76 77 71 2k 73 76 65 4k 65 64 58 8k 56 55 44 LwA Inlet LwA Outlet LwA Surrounding 102 102 95 dB(A) Tot 63 91 86 69 125 92 96 82 Frequency bands [Hz] 250 96 96 90 500 96 96 89 1k 93 94 88 2k 92 93 86 4k 87 85 83 8k 78 75 73

For aggressive media

Measurement point: 0,406 m/s; 548 Pa

Measurement point: 0,824 m/s; 2002 Pa

279

Aggressive media roof fans DVP


Temperature of transported air from -15C to +60C Single inlet impellers from PP with effective blade geometry Weather-resistant, sturdy casing made from PP Motor and terminal box in IP55 Capsulated motor, outside the airstream Electrical accessories

STDT p. 342

The DVP fans have been developed especially for the exhaust of aggressive media. This is the right fan when corrosive gases, contaminated air or other aggressive components are part of the exhaust air. Typical applications are medical facilities, the food-, electrical-or chemical industry. The casing from PP offers a variety of applications with its connectors from 200 - 400 mm. Motor protection by protection switch.

S-DT2 SKT p. 340

Quick selection

7964, 7955, 7967, 7965, 7969, 7971

1 2 3 4 5 6

DVP 200D 2-pole DVP 200D 4-pole DVP 250D 2-pole DVP 250D 4-pole DVP 315D 4-pole DVP 315D 8-pole

1 2 3 4

DVP 400D 4-pole DVP 400D 8-pole DVP 400D-L 4-pole DVP 400D-L 8-pole

2 6

Technical data
DVP Art no. Voltage/Frequency Power P2 Current Max air flow R.p.m. Max temp. of transported air Sound pressure level at 4 m/10 m Weight 200D2-4 2-pole 32295 V/50 Hz 400 3~ W 1500 A 3.4 m3/s 0.628 min-1 2885 C 60 dB(A) 62/54 kg 25 F IP 55 14a 400 3~ 370 0.84 0.316 1468 60 43/35 25 F IP 55 14a 200D2-4 4-pole 250D2-4 2-pole 32296 400 3~ 3600 7.7 1.27 2874 60 69/61 35 F IP 55 14a 400 3~ 900 2.0 0.649 1468 60 51/43 35 F IP 55 14a 250D2-4 4-pole 315D4-8 4-pole 32297 400 3~ 2200 4.8 1.28 1494 60 55/47 45 F IP 55 14a 400 3~ 500 1.98 0.647 732 60 40/32 45 F IP 55 14a 315D4-8 8-pole

For aggressive media

Insulation class, motor Enclosure class, motor Wiring diagram p. 391-400

280

7981, 7979, 7975, 7973

Aggressive media roof fans


Dimensions
F

Ventilation accessories

SSD p. 374

FDS p. 374
M
K D

C E

A DVP 200 DVP 250 DVP 315 DVP 400 435 595 665 939

B 330 450 535 750

C 200 250 315 400

D 355 400 560 601

E 662 768 810 976

F 200 250 315 400

G 119 119 218 218

H 1065 981 1161 1134

K 146 181 200 235

L 30 30 30 30

M 4x10 4x12 4x12 4x14 DVP 200 = SSD/FDS 310/311 DVP 250 = SSD/FDS 355/400 DVP 315 = SSD/FDS 450/500 DVP 400 = SSD/FDS 560/630

DVP Art no. Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air Sound pressure level at 4 m/10 m Weight Insulation class, motor Enclosure class, motor Wiring diagram p. 391-400

400D4-8 4-pole 32299 V/50 Hz 400 3~ W 2000 A 4.8 m3/s 1.31 min-1 1445 C 60 dB(A) 60/52 kg 55 F IP 55 14a

400D4-8 8-pole 400 3~ 500 1.98 0.661 732 60 44/36 55 F IP 55 14a

400D4-8-L 4-pole 32298 400 3~ 3600 7.9 2.11 1447 60 61/53 55 F IP 55 14a

400D4-8-L 8-pole 400 3~ 900 2.0 1.05 733 60 47/39 55 F IP 55 14a

For aggressive media

281

Aggressive media roof fans


Performance

DVP 200D2-4 2-pole

DVP 200D2-4 4-pole

dB(A) LwA Inlet LwA Surrounding

Tot 63 90 85 71 61 125 74 65

Frequency bands [Hz] 250 83 78 500 86 81 1k 83 77 2k 78 76 4k 69 69 8k 61 62

dB(A) LwA Inlet LwA Surrounding

Tot 63 73 66 57 46 125 64 54

Frequency bands [Hz] 250 69 61 500 65 61 1k 64 57 2k 58 55 4k 48 48 8k 39 39

Measurement point: 0,36 m/s; 755 Pa

Measurement point: 0,18 m/s; 190 Pa

dB(A) LwA Inlet LwA Surrounding

Tot 63 82 81 66 70 125 77 75

Frequency bands [Hz] 250 77 73 500 74 74 1k 74 73 2k 67 68 4k 64 64 8k 55 57

dB(A) LwA Inlet LwA Surrounding

Tot 63 68 63 55 45 125 65 52

Frequency bands [Hz] 250 61 53 500 61 61 1k 56 54 2k 47 49 4k 43 45 8k 33 37

Measurement point: 0,329 m/s; 507 Pa

Measurement point: 0,335 m/s; 84 Pa

For aggressive media

282

Aggressive media roof fans

DVP 250D2-4 4-pole

dB(A) LwA Inlet LwA Surrounding

Tot 63 98 95 78 83 125 81 80

Frequency bands [Hz] 250 93 86 500 94 91 1k 89 87 2k 84 85 4k 76 78 8k 69 71

dB(A) LwA Inlet LwA Surrounding

Tot 63 80 78 60 69 125 73 68

Frequency bands [Hz] 250 77 72 500 73 73 1k 71 70 2k 63 63 4k 56 56 8k 48 49

Measurement point: 0,543 m/s; 1218 Pa

Measurement point: 0,279 m/s; 312 Pa

DVP 400D4-8 4-pole

dB(A) LwA Inlet LwA Surrounding

Tot 63 89 87 65 72 125 86 81

Frequency bands [Hz] 250 85 83 500 79 78 1k 79 76 2k 72 72 4k 67 68 8k 59 60

dB(A) LwA Inlet LwA Surrounding

Tot 63 73 76 57 62 125 72 75

Frequency bands [Hz] 250 59 59 500 63 62 1k 62 56 2k 52 51 4k 46 46 8k 36 36

Measurement point: 0,669 m/s; 448 Pa

Measurement point: 0,388 m/s; 104 Pa

For aggressive media

283

Aggressive media roof fans

DVP 400D4-8-L 8-pole

dB(A) LwA Inlet LwA Surrounding

Tot 63 88 86 69 72 125 84 77

Frequency bands [Hz] 250 82 80 500 80 78 1k 80 79 2k 75 75 4k 72 71 8k 64 63

dB(A) LwA Inlet LwA Surrounding

Tot 63 78 76 62 63 125 78 75

Frequency bands [Hz] 250 65 63 500 64 65 1k 61 59 2k 54 54 4k 50 49 8k 40 40

Measurement point: 0,564 m/s; 594 Pa

Measurement point: 0,567 m/s; 103 Pa

For aggressive media

284

Aggressive media roof fans WSD PRF VKS-P ASS-P

Weather roof for motor

Additional weather protection for the motor, if the fan is outdoor mounted. Manufactured from seawater resistant aluminium. The WSD PRF is painted in RAL 5015.

Automatic shutter for PRF


The automatic shutter is manufactured from PP.

Flexible connections for PRF


The flexible connections is made of PVC.

2xM6

WSD-PRF 125 160 180 200 250

A 228 283 313 348 287

B 173,5 201 211 218,5 228,5

C 210 270 270 320 400

D 60 60 70 70 70 VKS-P 125 160 180 200 250 A 205 240 260 280 330 B 125 160 180 200 250 ASS-P 125 160 180 200 250 A 155 155 155 155 155 B 125 160 180 200 250

VP

Splinter protection PRF


The splinter protection is manufactured in PVC and the bracket consist of stainless steel The size of the splinter protection is based upon the size of the corresponding PRF size.
A B

VKA-P

SD-PRF

Adjustable shutter for PRF


The automatic shutter is manufactured from PP.

Vibration damper PRF (4 pcs)


Rubber-mount for active and passive vibration- and impact sound isolation.
G A F

D SW C

SD-PRF 125 160-250

A 45 70 F

B 35 50 G 60 90

C 30 45 SW 11 17

D 6 9

E 20 32

M6 M10

VKA-P 125 160 180 200 250

A 120 120 120 120 120

B 125 160

For aggressive media

180 200 250

285

Centrifugal fans

General
Motors
All fans in this series are equipped with speed controllable external rotor motors. To protect the motor from overheating, the fans have integral thermal contacts with external leads for connection to a motor protection device. The casings are manufactured from galvanised sheet steel.

CE/CT centrifugal fans


CE/CT with forward curved impeller blades. Electrical connection via a junction box.

KBT/KBR thermo fans


KBT with forward curved, KBR with backward curved impeller blades, for the extract of air up to a temperature of 120C. Casing manufactured from galvanised steel, IEC standard motors, in three phase from 750 W speed controllable via frequency inverter, smaller and single phase motors speed controllable by transformers. KBT/KBR EC thermo fans with highly efficient EC motor, speed control by 0-10V signal.

CKS centrifugal fans


CKS with backward curved impeller blades. Swing-out function of motor impeller assembly for easy cleaning and maintenance.

Centrifugal fans

286

Centrifugal fans

Centrifugal fans

CE . . . . . . . . . . . . . . . . . . . . . 288 Single-inlet centrifugal fan with forward-curved blades: up to 0.8 m/s, 1 phase.

CT . . . . . . . . . . . . . . . . . . . . . 292 Centrifugal fans: up to 2.56 m3/s, forward curved impeller, 3 phase.

CKS . . . . . . . . . . . . . . . . . . . 296 Centrifugal fans: up to 3.00 m3/s, backward curved impeller, 1-3 phase.

KBR/KBT EC. . . . . . . . . . . . 300 Thermo Box: up to 1.86 m3/s, KBT-EC with forward curved impeller, KBR-EC with backward curved impellers, 1 phase and 3 phase.

120C

KBT/KBR . . . . . . . . . . . . . . . 304 Thermo Box: up to 1.97 m3/s KBT with forward curved, KBR with backward curved impellers, 1 phase and 3 phase.

IE2
2009/640/EG

120C

287

Centrifugal fans

Centrifugal fans single inlet CE


Speed-controllable Integral thermal contacts Can be installed in any position Maintenance-free and reliable CE fans are easy to install. Fans in this series have impellers with forward-curved blades and external rotor motors. The casing is manufactured from galvanised sheet steel. To protect the motor from overheating, the CE 140 fans have integral thermal contacts with manual reset, CE 200-280 have integral thermal contacts with external leads for connection to a motor protection device. CE fans are electrically connected via a junction box. S-ET p. 341 Electrical accessories

RE p. 320

REU p. 320 Quick selection

3343, 3349, 3360, 3354, 3364, 3358

1 2 3 4 5 6

CE 140 S-125 CE 140 S-160 CE 140 M-125 CE 140 M-160 CE 140 L-125 CE 140 L-160

1 2 3 4

CE 200-4 CE 225-4 CE 250-4 CE 280-4

3 2 4 5 6

Technical data
CE Art. no Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Capacitor Motor protection Speed control, five-step Speed control, five-step high/low Speed control, stepless Wiring diagram p. 391-400 CE 140 S-125 1525 V/50 Hz 230 1~ W 104 A 0.45 m3/s 0.11 min-1 1633 C 50 C 50 dB(A) 43 kg 2.7 B IP 44 F 2 Integral Transformer RE 1.5 Transformer REU 1.5 Thyristor REE 1.5 2 CE 140 S-160 1528 230 1~ 105 0.451 0.114 1498 54 54 45 2.7 B IP 44 2 Integral RE 1.5 REU 1.5 REE 1.5 2 CE 140 M-125 1526 230 1~ 121 0.529 0.115 1833 68 68 44 3.1 B IP 44 4 Integral RE 1.5 REU 1.5 REE 1.5 2 CE 140 M-160 1529 230 1~ 125 0.54 0.121 1807 65 65 42 3.1 B IP 44 4 Integral RE 1.5 REU 1.5 REE 1.5 2 CE 140 L-125 1527 230 1~ 147 0.64 0.14 2459 70 70 44 3.5 B IP 44 4 Integral RE 1.5 REU 1.5 REE 1.5 2 CE 140 L-160 1530 230 1~ 153 0.661 0.151 2406 70 70 42 3.5 B IP 44 4 Integral RE 1.5 REU 1.5 REE 1.5 2

288

822, 807, 806, 8975

REE p. 321

Centrifugal fans single inlet


Dimensions CE 140 Ventilation accessories

Centrifugal fans

VK p. 356

RSK p. 355

CE/CT 200-280
A

LDC p. 348

K E

FFR p. 349

CWK p. 354

Only CE 280-4

VBR p. 365

A CE 200-4 CE 225-4 CE 250-4 CE 280-4 404 445 492 547

B 250 280 315 357

C 26 25 26 26

D 26 25 26 26

E 4 6 8 50

F 132 147 167 182

G 183 198 218 233

H 332 369 412 455

J 187 211 239 257

K 164 180 198 221

L 186 234 261 293

CE Art. no Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Capacitor Motor protection Speed control, five-step Speed control, five-step high/low Speed control, stepless Wiring diagram p. 391-400

CE 200-4 1577 V/50 Hz 230 1~ W 230 A 1.0 m3/s 0.302 min-1 1202 C 51 C 51 dB(A) 51 kg 8.5 F IP 44 F 6 S-ET 10 Transformer RTRE 1.5 Transformer REU 1.5 Thyristor REE 2 5

CE 225-4 1582 230 1~ 509 2.45 0.489 1301 70 70 61 13 F IP 54 8 S-ET 10 RTRE 3 REU 3 REE 4 6

CE 250-4 1585 230 1~ 836 3.75 0.693 1183 70 70 55 16.7 F IP 54 14 S-ET 10 RTRE 5 REU 5 REE 4 6

CE 280-4 1534 230 1~ 1259 5.96 0.828 1074 59 59 57 21.8 F IP 54 20 S-ET 10 RTRE 7 REU 7 6

289

Centrifugal fans

Centrifugal fans single inlet


Performance
Q [m3/h]

Q [m3/s]

dB(A) CE 140 S-125 LwA Inlet LwA Outlet LwA Surrounding CE 140 M-125 LwA Inlet LwA Outlet LwA Surrounding CE 140 L-125 LwA Inlet LwA Outlet LwA Surrounding

Tot 63 70 70 50 49 49 7 125 65 65 38

Frequency bands [Hz] 250 64 64 29 500 60 63 42 1k 61 63 47 2k 56 59 40 4k 53 53 34 8k

dB(A) CE 140 S-160 45 48 37 LwA Inlet LwA Outlet LwA Surrounding CE 140 M-160

Tot 63 69 69 52 49 50 39 125 64 64 37

Frequency bands [Hz] 250 64 64 30 500 60 61 47 1k 60 61 49 2k 58 57 39 4k 53 51 33 8k 46 47 29

Measurement point: 0,069 m/s; 242 Pa 71 72 51 56 48 17 64 65 37 67 67 36 63 66 46 62 64 48 58 60 41 56 56 36 48 51 29

Measurement point: 0,069 m/s; 255 Pa

LwA Inlet LwA Outlet LwA Surrounding CE 140 L-160

71 71 49

50 50 26

67 66 32

67 66 41

62 63 43

60 63 45

58 59 38

56 54 35

50 51 29

Measurement point: 0,071 m/s; 271 Pa 74 74 51 67 62 38 67 66 40 69 69 32 65 67 45 64 67 48 61 64 42 59 59 39 52 56 33

Measurement point: 0,076 m/s; 267 Pa LwA Inlet LwA Outlet LwA Surrounding 73 73 49 56 53 27 66 65 37 69 69 35 64 66 43 62 65 44 60 63 41 59 58 38 53 56 35

Measurement point: 0,079 m/s; 286 Pa

Measurement point: 0,082 m/s; 300 Pa

290

Centrifugal fans single inlet

Centrifugal fans

dB(A) CE 200-4 LwA Inlet LwA Outlet LwA Surrounding CE 225-4 LwA Inlet LwA Outlet LwA Surrounding

Tot 63 68 69 58 51 44 47 125 52 45 43

Frequency bands [Hz] 250 60 57 40 500 60 63 51 1k 62 65 55 2k 63 61 47 4k 60 59 44 8k

dB(A) CE 250-4 56 55 38 LwA Inlet LwA Outlet LwA Surrounding CE 280-4

Tot 63 73 76 62 51 49 45 125 58 53 50

Frequency bands [Hz] 250 63 63 58 500 62 68 50 1k 68 72 55 2k 68 69 53 4k 65 68 49 8k 61 63 49

Measurement point: 0,195 m/s; 222 Pa 75 75 68 46 46 54 50 51 49 63 63 52 66 66 60 70 70 65 69 68 61 68 67 57 64 64 52

Measurement point: 0,338 m/s; 332 Pa LwA Inlet LwA Outlet LwA Surrounding 78 80 64 52 50 40 66 60 50 70 66 60 66 72 52 72 75 57 72 73 56 69 73 53 64 66 41

Measurement point: 0,267 m/s; 272 Pa

Measurement point: 0,43 m/s; 456 Pa

291

Centrifugal fans

Centrifugal fans single inlet CT


Speed-controllable Integral thermal contacts Can be installed in any position Maintenance-free and reliable RTRD p. 321 Electrical accessories

CT fans are easy to install. Fans in this series have impellers with forward-curved blades and external rotor motors. The casing is manufactured from galvanised sheet steel. To protect the motor from overheating, the fans have integral thermal contacts with external leads for connection to a motor protection device. CT 200 fans are electrically connected via a junction box. CT 225 450 fans electrical cable is directly connected to the motor without junction box.

RTRDU p. 321

STDT p. 342

Quick selection

823, 819, 820, 827, 834, 918, 924

1 2 3 4 5 6 7

CT 200-4 CT 225-4 CT 225-6 CT 250-4 CT 250-6 CT 280-4 CT 280-6

1 2 3 4 5 6 7

CT 315-4 CT 315-6 CT 355-4 CT 355-6 CT 400-4 CT 400-6 CT 450-6

7 4 3 1 5 2 7 4 6 2 1 6 3

Technical data
CT Art. no Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Motor protection Speed control, five-step Speed control, five-step high/low Wiring diagram p. 391-400 200-4 1579 V/50 Hz 400 3~ W 310 A 0.551 m3/s 0.392 min-1 1304 C 61 C 61 dB(A) 44 kg 8.5 B IP 44 STDT 16 Transformer RTRD 2 Transformer RTRDU 2 7 225-4 1583 400 3~ 504 0.892 0.534 1319 70 56 53 11.5 F IP 54 STDT 16 RTRD 2 RTRDU 2 8 225-6 1581 400 3~ 198 0.42 0.386 857 70 70 45 10.6 F IP 54 STDT 16 RTRD 2 RTRDU 2 8 250-4 1574 400 3~ 788 1.4 0.68 1266 60 60 60 14.5 F IP 54 STDT 16 RTRD 2 RTRDU 2 8 250-6 1584 400 3~ 297 0.624 0.5 832 55 55 51 12.3 F IP 54 STDT 16 RTRD 2 RTRDU 2 8 280-4 1586 400 3~ 1333 2.35 0.906 1307 70 70 59 22.5 F IP 54 STDT 16 RTRD 4 RTRDU 4 8 280-6 1575 400 3~ 407 0.863 0.587 825 60 60 45 16 F IP 54 STDT 16 RTRD 2 RTRDU 2 8

292

906, 868, 874, 908, 879, 923, 909

Centrifugal fans single inlet


Dimensions
A

Centrifugal fans

Ventilation accessories

VK p. 356

K E

Not for CT 200-4, 225-4, 250-4

RSK p. 355

LDR p. 358

A CT 200-4 CT 225-4 CT 225-6 CT 250-4 CT 250-6 CT 280-4 CT 280-6 CT 315-4/6 CT 355-4 CT 355-6 CT 400-4/6 CT 450-6 404 445 445 492 492 547 547 615 689 689 768 859

B 250 280 280 315 315 357 357 400 450 450 500 560

C 26 25 25 26 26 26 26 26 26 26 26 26

D 26 25 25 26 26 26 26 26 26 26 26 26

E 4 6 40 8 42 50 46 58 70 53 72 76

F 132 147 147 167 167 182 182 203 227 227 252 283

G 183 198 198 218 218 233 233 254 278 278 304 335

H 332 369 369 412 412 455 455 517 574 574 643 721

J 187 211 211 239 239 257 257 298 325 325 365 412

K 164 180 180 198 198 221 221 247 287 287 310 348

L 186 234 234 261 261 293 293 326 367 367 413 463

FFR p. 349

CWK p. 354

VBR p. 365

CT Art. no Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Motor protection Speed control, five-step Speed control, five-step high/low Wiring diagram p. 391-400

315-4 1587 V/50 Hz 400 3~ W 2365 A 3.95 m3/s 1.21 min-1 1233 C 40 C 40 dB(A) 65 kg 28.4 F IP 54 STDT 16 Transformer RTRD 7 Transformer RTRDU 7 8

315-6 1576 400 3~ 843 1.69 0.98 782 55 55 55 22.6 F IP 54 STDT 16 RTRD 2 RTRDU 2 8

355-4 1589 400 3~ 3716 6.16 1.73 1291 70 70 63 42.4 F IP 54 STDT 16 RTRD 7 RTRDU 7 8

355-6 1588 400 3~ 1538 2.88 1.45 818 70 70 56 31 F IP 54 STDT 16 RTRD 4 RTRDU 4 8

400-4 1536 400 3~ 4984 8.12 2.01 1312 70 70 70 54.9 F IP 54 STDT 16 RTRD 14 8

400-6 1591 400 3~ 2624 4.84 2.07 843 70 70 58 51 F IP 54 STDT 16 RTRD 7 RTRDU 7 8

450-6 1593 400 3~ 3821 6.76 2.56 842 59 59 61 59.8 F IP 54 STDT 16 RTRD 7 RTRDU 7 8

293

Centrifugal fans

Centrifugal fans single inlet


Performance

dB(A) CT 200-4 LwA Inlet LwA Outlet LwA Surrounding CT 225-4 LwA Inlet LwA Outlet LwA Surrounding

Tot 63 67 69 51 44 44 37 125 50 46 31

Frequency bands [Hz] 250 62 59 44 500 56 62 43 1k 60 65 45 2k 60 62 45 4k 57 60 41 8k

dB(A) CT 225-6 52 55 34 LwA Inlet LwA Outlet LwA Surrounding CT 250-6

Tot 63 62 64 51 38 39 34 125 45 39 35

Frequency bands [Hz] 250 55 53 44 500 54 59 47 1k 55 57 44 2k 56 56 43 4k 53 54 41 8k 43 46 39

Measurement point: 0,181 m/s; 254 Pa 75 77 59 65 63 44 64 59 40 71 69 47 63 69 49 67 72 53 67 68 54 65 66 51 61 63 53

Measurement point: 0,194 m/s; 125 Pa LwA Inlet LwA Outlet LwA Surrounding 64 67 58 41 41 46 46 41 33 54 54 42 55 62 50 58 60 53 58 59 53 55 58 47 47 49 35

Measurement point: 0,291 m/s; 263 Pa

Measurement point: 0,29 m/s; 143 Pa

dB(A) CT 250-4 LwA Inlet LwA Outlet LwA Surrounding CT 280-4 LwA Inlet LwA Outlet LwA Surrounding

Tot 63 75 77 67 51 50 53 125 57 52 43

Frequency bands [Hz] 250 62 63 47 500 63 68 56 1k 71 74 64 2k 70 70 61 4k 68 69 56 8k

dB(A) CT 280-6 64 64 50 LwA Inlet LwA Outlet LwA Surrounding CT 315-6

Tot 63 67 70 52 44 42 41 125 51 46 31

Frequency bands [Hz] 250 56 56 40 500 59 66 44 1k 62 64 48 2k 60 61 45 4k 58 60 40 8k 51 52 31

Measurement point: 0,425 m/s; 319 Pa 79 81 66 55 54 49 62 58 42 66 66 52 67 72 53 74 77 62 75 74 61 70 72 57 66 67 53

Measurement point: 0,341 m/s; 205 Pa

LwA Inlet LwA Outlet LwA Surrounding

71 72 62

49 47 38

57 52 37

59 60 48

63 68 57

66 65 57

64 64 53

63 64 50

56 55 41

Measurement point: 0,399 m/s; 445 Pa

Measurement point: 0,479 m/s; 274 Pa

294

Centrifugal fans single inlet

Centrifugal fans

dB(A) CT 315-4 LwA Inlet LwA Outlet LwA Surrounding CT 355-4 LwA Inlet LwA Outlet LwA Surrounding CT 400-4 LwA Inlet LwA Outlet LwA Surrounding

Tot 63 81 83 72 59 56 51 125 68 64 49

Frequency bands [Hz] 250 66 69 55 500 68 74 61 1k 76 78 68 2k 76 76 66 4k 74 75 62 8k

dB(A) CT 355-6 69 71 55 LwA Inlet LwA Outlet LwA Surrounding CT 400-6

Tot 63 75 79 63 52 63 39 125 59 63 42

Frequency bands [Hz] 250 60 67 49 500 67 74 58 1k 70 74 59 2k 69 71 56 4k 66 70 50 8k 62 64 45

Measurement point: 0,615 m/s; 594 Pa 84 88 70 60 57 44 71 69 51 68 73 54 73 79 56 81 84 68 79 81 62 75 79 54 71 73 48

Measurement point: 0,688 m/s; 355 Pa LwA Inlet LwA Outlet LwA Surrounding CT 450-6 79 81 65 56 51 40 63 60 43 62 67 48 75 76 60 73 75 60 72 74 58 69 72 49 65 66 42

Measurement point: 0,922 m/s; 756 Pa 90 88 77 60 63 46 72 73 52 76 71 61 81 76 67 87 84 75 84 82 69 80 77 60 76 74 54

Measurement point: 1,0 m/s; 442 Pa LwA Inlet LwA Outlet LwA Surrounding 81 85 67 60 55 39 66 64 49 64 70 51 77 80 64 75 79 63 74 78 59 70 74 48 67 69 45

Measurement point: 1,16 m/s; 974 Pa

Measurement point: 1,35 m/s; 593 Pa

295

Centrifugal fans

Centrifugal fans single inlet CKS


Swing-out Speed-controllable Integral thermal contacts Can be mounted in any position S-ET p. 341 Electrical accessories

Swing-out cover for easy cleaning and servicing. Maintenance- free and reliable. CKS fans are easy to install. Fans in this series have impellers with backward-curved blades and external rotor motors. The casing is manufactured from galvanised sheet steel. To protect the motor from overheating, the fans have integral thermal contacts with external leads for connection to a motor protection device.

RTRE p. 320

REU p. 320 Quick selection


3695, 4059, 3424, 3423

1 2 3

CKS 355-1, 355-3 CKS 400-1 CKS 400-3

1 2 3

CKS 450-3 CKS 500-3 CKS 560-3

3421, 3576, 3575

REE p. 321

RTRD/RTRDU p. 321

STDT p. 342

Technical data
CKS Art. no Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Capacitor Motor protection Speed control, five-step Speed control, five-step high/low Speed control, stepless Wiring diagram p. 391-400 355-1 1518 V/50 Hz 230 1~ W 410 A 1.96 m3/s 0.868 min-1 1356 C 70 C 70 dB(A) 54 kg 26.4 F IP 54 F 8 S-ET 10 Transformer RTRE 3 Transformer REU 3 Thyrisor REE 4 6 355-3 1519 400 3~ 353 0.73 0.856 1380 70 70 50 25.2 F IP 54 STDT 16 RTRD 2 RTRDU 2 8 400-1 1520 230 1~ 611 2.77 1.18 1314 70 70 56 33 F IP 54 14 S-ET 10 RTRE 3 REU 3 REE 4 6 400-3 1521 400 3~ 687 1.6 1.27 1404 70 70 48 32.6 F IP 54 STDT 16 RTRD 2 RTRDU 2 8 450-3 1522 400 3~ 1048 1.88 1.75 1333 70 68 60 43.6 F IP 54 STDT 16 RTRD 4 RTRDU 4 8 500-3 1523 400 3~ 1726 3.34 2.32 1393 66 62 65 60.6 F IP 54 STDT 16 RTRD 4 RTRDU 4 8 560-3 1524 400 3~ 2801 4.86 2.98 1360 70 70 68 74.1 F IP 54 STDT 16 RTRD 7 RTRDU 7 8

296

Centrifugal fans single inlet


Dimensions Ventilation accessories
D E

Centrifugal fans

G B

ISE p. 371

LDC p. 348

K F

USE p. 371
C 283 317 355 393 440 D 243 266 294 317 342 E 193 216 244 267 292 F 590 658 734 810 900 G 530 530 650 650 650 H 668 748 837 926 J 196 219 247 270 K 250 283 312 343 380 L 329 370 415 469 515

CKS 355 400 450 500 560

A 135 148 160 180 197

B 342 383 432 482 542

1033 295

297

Centrifugal fans

Centrifugal fans single inlet


Performance

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 355-900 LwA Inlet LwA Outlet

Tot 63 71 72 61 62 63 45 46 32 45 46 125 60 58 46 57 55

Frequency bands [Hz] 250 65 66 58 59 60 500 65 66 52 52 53 1k 64 66 54 46 48 2k 61 63 50 51 53 4k 55 54 42 49 48 8k 52 49 33 45 42

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 355-900 LwA Inlet LwA Outlet

Tot 63 69 73 57 61 64 44 44 25 44 44 125 58 57 41 55 54

Frequency bands [Hz] 250 63 68 53 57 62 500 64 67 48 51 54 1k 62 66 51 44 48 2k 60 63 48 50 53 4k 58 54 41 52 48 8k 55 45 33 48 38

Measurement point: 0,399 m/s; 375 Pa

Measurement point: 0,435 m/s; 345 Pa

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 400-900 LwA Inlet LwA Outlet

Tot 63 72 76 63 66 69 49 45 38 48 44 125 63 65 47 60 62

Frequency bands [Hz] 250 66 71 59 61 66 500 67 71 55 57 61 1k 65 69 56 52 56 2k 64 65 54 57 58 4k 58 60 42 53 55 8k 54 58 37 48 52

dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 400-900 LwA Inlet LwA Outlet

Tot 63 71 77 55 64 70 41 48 15 40 47 125 60 61 37 57 58

Frequency bands [Hz] 250 65 72 50 60 67 500 66 72 50 56 62 1k 62 71 49 49 58 2k 60 67 46 53 60 4k 52 59 30 47 54 8k 42 52 12 36 46

Measurement point: 0,511 m/s; 438 Pa

Measurement point: 0,552 m/s; 491 Pa

298

Centrifugal fans single inlet

Centrifugal fans

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 72 79 67 42 51 28 125 62 64 48

Frequency bands [Hz] 250 65 72 64 500 67 74 60 1k 65 73 59 2k 64 69 56 4k 56 62 44 8k 46 57 33

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 82 87 72 55 56 33 125 69 68 56

Frequency bands [Hz] 250 74 81 61 500 78 83 68 1k 74 81 67 2k 73 76 63 4k 66 72 51 8k 58 61 41

Measurement point: 0,798 m/s; 548 Pa

Measurement point: 1,21 m/s; 672 Pa

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 86 89 75 61 65 37 125 72 72 58

Frequency bands [Hz] 250 80 83 71 500 81 83 67 1k 78 84 69 2k 77 79 65 4k 71 72 56 8k 63 63 48

Measurement point: 1,76 m/s; 761 Pa

299

Centrifugal fans

Centrifugal fans single inlet KBR/KBT EC


EC-motors, high level of efficiency 100% speed controllable Integrated motor protection Low noise level Max. temp. of continuously transported air 120C Electrical accessories

MTP 10 p. 341

120C

EC technology is intelligent technology; using integral electronic control which eliminates the slip losses in the motor and ensures that the motor always runs at optimal load and guarantees that the proportion of energy utilized effectively is many times higher and the energy usage considerably lower compared with AC motors. EC fans are notable for their economical use of energy and excellent ease of control. They can be varied in speed to match the airflow demand, and operate at high efficiency levels. For the same air volume, they consume distinctly less energy than AC fan drives. Another special feature of EC fans is their energy-saving potential not only at full load, but especially at part-load. When operating at partload, the energy used is much lower than with an asynchronous motor of equivalent output. Reduced energy usage guarantees a drop in operating costs. The power electronics are integrated in the motor housing. All models have one potential-free terminal for error message. All motors are suitable to be used for 50/60Hz. The input voltage for single phase units can vary between 200 and 277V. Speed control by a 0-10V signal. Every motor has an output voltage of 10V for an external potentiometer or sensor. The KBR-EC fans have impellers manufactured from aluminium with backward-curved blades. The casing is manufactured from double-skinned galvanized sheet steel and is insulated with 50 mm mineral wool. The KBR-EC fans have a swing-out door for easy inspection and service. The direction of the door opening can easily be changed from left to right at site. The fan is isolated from the casing via connectors and anti-vibration dampers are incorporated into the base frame.

MTV 1 p. 341

REV p. 340

EC-Vent p. 329-330

Technical data
KBR-EC KBT-EC Art. no Voltage/Frequency Fan power consumption (P1) Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 4/10 m Weight Insulation class, motor Enclosure class, motor Speed control, stepless Wiring diagram p. 391-400 33396 V/50/60 Hz 230 1~ W 107 A 0.502 m3/s 0.426 min-1 1512 C 120 C 120 dB(A) 31/23 kg 47 F IP 55 MTP 10 46 33397 230 1~ 173 0.771 0.579 1512 120 120 34/26 75 F IP 55 MTP 10 46 33653 230 1~ 1268 5.53 1.12 3025 120 120 49/41 75 F IP 55 MTP 10 48 33400 230 1~ 498 2.17 0.997 1495 120 120 39/31 81 F IP 55 MTP 10 48 33398 230 1~ 296 1.3 0.822 1514 120 120 39/31 81 F IP 55 MTP 10 46 33665 400 3~ 2567 3.92 1.86 2610 120 120 52/44 83 F IP 55 MTP 10 47 280 315 315-L 355 355-K 355-L 200 33231 230 1~ 535 2.43 0.554 1498 70 70 36/28 35.6 F IP 55 MTP 10 48 250 33259 400 3~ 1252 2.01 0.925 1370 120 120 37/29 52.5 F IP 55 MTP 10 47

300

Centrifugal fans single inlet


Dimensions
130 A J 78

Centrifugal fans

Ventilation accessories

ALS-KBT p. 371

33

50

50

ASF/KB p. 371

38

WBK p. 389
KBR-EC 280 315 355 A 171.5 187.5 206.7 B 537 600 655 C 295 339 372 D 360 398 451 E 625 690 770 G 280 315 355 H 234 249 273 J 291 307 331 L 600 800 770

WSD KBT p. 371

35

E 38

KBT-EC 200
G

A 142.7 160

B 445 500

50

50

C 249 285

D 292 333

E 510 576

F 130 130

G 200 250

H 174 213

J 232 272

K 78 78

L 450 600

M 35 35

250

Quick selection
9748, 9771, 10701, 10699, 10707, 9749

1 2 3 4 5 6

KBR 280 EC KBR 315 EC KBR 315 EC-L KBR 355 EC KBR 355 EC-K KBR 355EC-L

1 2

KBT 200EC KBT 250EC

8361, 8453

301

Centrifugal fans

Centrifugal fans single inlet


Performance

KBR 280EC

KBR 315EC

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 63 64 53 31 34 28 125 45 47 41

Frequency bands [Hz] 250 56 59 47 500 57 58 39 1k 55 56 43 2k 56 56 41 4k 53 47 50 8k 47 46 31

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 69 70 49 46 46 16 125 58 58 39

Frequency bands [Hz] 250 64 66 45 500 65 66 39 1k 58 61 44 2k 58 60 36 4k 54 53 34 8k 49 48 25

Measurement point: 0,204 m/s; 255 Pa

Measurement point: 0,293 m/s; 306 Pa

KBR 315EC-L

KBR 355EC

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 87 90 61 63 64 42 125 74 72 54

Frequency bands [Hz] 250 76 75 55 500 85 88 56 1k 74 81 51 2k 75 80 52 4k 72 71 48 8k 67 66 40

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 74 76 54 55 60 26 125 65 65 42

Frequency bands [Hz] 250 69 74 45 500 69 68 45 1k 64 66 45 2k 61 61 47 4k 60 59 49 8k 55 54 45

Measurement point: 0.567 m/s; 1238 Pa

Measurement point: 0,52 m/s; 534 Pa

302

Centrifugal fans single inlet

Centrifugal fans

KBR 355EC-K

KBR 355EC-L

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 71 71 47 60 56 31 125 62 59 35

Frequency bands [Hz] 250 63 65 36 500 67 66 36 1k 61 63 45 2k 61 59 38 4k 57 54 31 8k 51 49 24

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 90 92 72 125 88 90 70

Frequency bands [Hz] 250 87 89 69 500 82 84 64 1k 80 82 62 2k 76 78 58 4k 70 72 52 8k 67 69 49

Measurement point: 0,438 m/s; 374 Pa

Measurement point: 0,93 m/s, Ps = 1531 Pa

KBT 200EC

KBT 250EC

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 75 77 59 60 63 26 125 59 69 23

Frequency bands [Hz] 250 72 74 53 500 66 69 50 1k 68 68 49 2k 64 64 54 4k 62 62 52 8k 56 56 42

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 78 80 60 51 58 12 125 68 68 45

Frequency bands [Hz] 250 69 73 51 500 69 73 50 1k 73 75 54 2k 70 71 53 4k 69 70 55 8k 64 63 50

Measurement point: 0,304 m/s; 296 Pa

Measurement point: 0,493 m/s; 528 Pa

303

Centrifugal fans

Centrifugal fans single inlet KBT/KBR


Max temperature of transported air 120C Speed-controllable Integral thermal contacts Low sound level REV p. 340 Electrical accessories

IE2
2009/640/EG

120C

The fans have impellers manufactured from galvanised sheet steel, KBT with forward-curved blades, KBR with backward-curved blades. The casing is manufactured from double-skinned galvanised sheet steel and is insulated with 50 mm mineral wool. KBT/KBR fans have a swing-out door for easy inspection and service. The direction of the door opening can easily be changed from left to right at site. The fan is isolated from the casing via connectors and antivibration dampers are incorporated into the base frame. To protect the motors from overheating the fans have integral thermal contacts with external leads for connection to a motor protection device.

RTRD p. 321

RTRDU p. 321

Quick selection S-DT2 p. 340

1 2 3 4 5

KBT 160DV KBT 160E4 KBT 180E4 KBT 200DV KBT 200E4

6 7 8 9 10

KBT 225D4 IE2 KBT 225E4 KBT 250D4 IE2 KBT 250E4 KBT 280D4 IE2

5201, 5196, 5211, 5239, 6599, 9774, 5246, 9773, 5274, 9769

1 2

KBR 315DV KBR 315D2 IE2

3 4 5 6 7 8

KBR 355DV KBR 355DV/K KBR 355D2 IE2 KBR 355D2/K IE2 KBR 355E4 KBR 355E4/K

5290, 9767, none, 5310, 9766, 9765, 5311, 5302

STDT p. 342

1 4 5 6 7 9 8 10

3 3 1 8 4 7

FRQ p. 325

Technical data
KBT Art no. Voltage/Frequency Power at shaft Current Max air flow R.p.m. Max temp. of transported air Sound pressure level at 4/10 m Weight Insulation class, motor Enclosure class, motor Capacitor Motor protection Speed control, five step Speed control, five step high/low Speed control, D/Y two step 400V Speed control, stepless Wiring diagram p. 391-400 *+ S-ET 10 160DV 5823 V/50 Hz 400 3~ kW 0.16 A 0.57 m3/s 0.248 min-1 1120 C 120 dB(A) 31/23 kg 24 F IP 54 F STDT 16 RTRD 2 RTRDU 2 S-DT2 FXDM 17 160E4 5976 230 1~ 0.14 1.1 0.231 1476 120 31/23 25 F IP 54 6 S-ET 10 RTRE 1.5 REU 1.5* 21 180E4 5824 230 1~ 0.14 1.11 0.345 1490 120 34/26 29 F IP 54 6 S-ET 10 RTRE 1.5 REU 1.5* 21 200DV 5825 400 3~ 0.55 1.88 0.583 1360 120 37/29 35.6 F IP 54 STDT 16 RTRD 2 RTRDU 2 S-DT2 FXDM 17 200E4 5826 230 1~ 0.75 5.1 0.541 1370 120 37/29 40.2 F IP 54 30 S-ET 10 RTRE 7 REU 7* 21 225D4 IE2 33556 400 3~ 0.75 1.78 0.747 1390 120 39/31 40.3 F IP 55 U-EK 230E FRQ5(S)-4A FRQ(S)-4A 13b Y 225E4 5828 230 1~ 0.88 5.5 0.653 1417 120 38/30 43 F IP 54 30 S-ET 10 RTRE 7 REU 7* 21 250D4 IE2 33557 400 3~ 1.5 3.39 1.2 1400 120 44/36 52.5 F IP 55 U-EK 230E FRQ5(S)-4A FRQ(S)-4A 13b Y 250E4 5830 230 1~ 1.84 10.5 1.08 1400 120 45/37 52 F IP 54 50 S-ET 10 RTRE 12 21 280D4 IE2 33558 400 3~ 2.2 4.64 1.41w 1420 120 47/39 63 F IP 55 U-EK 230E FRQ5(S)-10A FRQ(S)-10A 13b Y

304

Centrifugal fans single inlet


Dimensions Ventilation accessories

Centrifugal fans

FK p. 355

LDC p. 348
L

RSK p. 355

SG p. 357

KBT 160 180 200 225 250 280 KBR 315 355

A 127.4 134.4 142.7 146.5 162 171.5

B 382 412 445 455 500 537

C 213 230 249 256 282 295

D 248 269 292 301 333 360

E 435 470 510 522 576 625

G 160 200 200 225 250 280

H 149 161 174 193 213 234

J 207 219 232 251 272 291

L 450 450 450 600 600 600

WSD-KBT p. 371

187.5 206.7

600 655

339 372

398 451

690 770

315 355

249 273

307 331

800 770

KBR Art no. Voltage/Frequency Power at shaft Current Max air flow R.p.m. Max temp. of transported air Sound pressure level at 4/10 m Weight Insulation class, motor Enclosure class, motor Capacitor Motor protection Speed control, five step Speed control, five step high/low Speed control, D/Y two step 400V Speed control, stepless Wiring diagram p. 391-400 * + S-ET 10

315DV 5833 V/50 Hz 400 3~ kW 0.37 A 1.39 m3/s 0.611 min-1 1360 C 120 dB(A) 36/28 kg 75 F IP 54 F STDT 16 RTRD 2 RTRDU 2 S-DT2 FXDM 17

315D2 IE2 33559 400 3~ 1.5 3.16 1.14 2840 120 50/42 67.1 F IP 55 U-EK 230E FRQ5(S)-4A FRQ(S)-4A 13b Y

355DV 5835 400 3~ 0.37 1.39 1.06 1360 120 41/33 81 F IP 54 STDT 16 RTRD 2 RTRDU 2 S-DT2 FXDM 17

355DV/K 5977 400 3~ 0.37 1.39 0.82 1434 120 41/33 81 F IP 54 STDT 16 RTRD 2 RTRDU 2 S-DT2 FXDM 17

355D2 IE2 33560 400 3~ 3.0 5.86 1.97 2890 120 53/45 83.3 F IP 55 U-EK 230E FRQ5(S)-10A FRQ5(S)-10A 13b Y

355D2/K IE2 33561 400 3~ 2.2 4.48 1.53 2880 120 53/45 78.3 F IP 55 U-EK 230E FRQ5(S)-10A FRQ5(S)-10A 13b Y

355E4 5980 230 1~ 0.37 2.1 0.972 1330 120 41/33 70.1 F IP 54 12 S-ET 10 RTRE 3 REU 3* 21

355E4/K 5978 230 1~ 0.37 2.1 0.778 1330 120 41/33 80 F IP 54 12 S-ET 10 RTRE 3 REU 3* 21

305

Centrifugal fans

Centrifugal fans single inlet


pERFORMANCE

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 72 74 54 125 70 72 52

Frequency bands [Hz] 250 66 68 48 500 63 65 45 1k 59 61 41 2k 57 59 39 4k 53 55 35 8k 49 51 31

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 72 74 54 125 70 72 52

Frequency bands [Hz] 250 66 68 48 500 63 65 45 1k 59 61 41 2k 57 59 39 4k 53 55 35 8k 49 51 31

Measurement point: 0,14 m/s; 134 Pa

Measurement point: 0,12 m/s; 120 Pa

dB(A) LwA Inlet LwA Outlet

Tot 63 75 77 125 73 75 55

Frequency bands [Hz] 250 69 71 51 500 66 68 48 1k 62 64 44 2k 60 62 42 4k 56 58 38 8k

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 78 80 60 125 76 78 58

Frequency bands [Hz] 250 72 74 54 500 69 71 51 1k 65 67 47 2k 63 65 45 4k 59 61 41 8k 55 57 37

LwA Surrounding 57

Measurement point: 0,21 m/s; 210 Pa

Measurement point: 0,29 m/s; 280 Pa

306

Centrifugal fans single inlet

Centrifugal fans

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 78 80 60 125 76 78 58

Frequency bands [Hz] 250 72 74 54 500 69 71 51 1k 65 67 47 2k 63 65 45 4k 59 61 41 8k 55 57 37

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 81 83 63 125 79 81 61

Frequency bands [Hz] 250 75 77 57 500 72 74 54 1k 68 70 50 2k 66 68 48 4k 62 64 44 8k 58 60 40

Measurement point: 0,29 m/s; 280 Pa

Measurement point: 0,37 m/s; 382 Pa

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 82 84 64 125 80 82 62

Frequency bands [Hz] 250 76 78 58 500 73 75 55 1k 69 71 51 2k 67 69 49 4k 63 65 45 8k 59 61 41

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 85 87 67 125 83 85 65

Frequency bands [Hz] 250 79 81 61 500 76 78 58 1k 72 74 54 2k 70 72 52 4k 66 68 48 8k 62 64 44

Measurement point: 0,49 m/s; 285 Pa

Measurement point: 0,67 m/s; 400 Pa

307

Centrifugal fans

Centrifugal fans single inlet

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63
86 88

Frequency bands [Hz] 125


84 86

dB(A) 4k
67 69

Tot 63 125 86 88 68 88 90 70 -

Frequency bands [Hz] 250 82 84 64 500 79 81 61 1k 75 77 57 2k 73 75 55 4k 69 71 51 8k 65 67 45

250
80 82

500
77 79

1k
73 75

2k
71 73

8k
63 65

LwA Inlet LwA Outlet LwA Surrounding

68

66

62

59

55

53

49

45

Measurement point: 0,56 m/s; 500 Pa

Measurement point: 0,60 m/s; 630 Pa

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 77 79 59 125 75 77 57

Frequency bands [Hz] 250 74 76 56 500 69 71 51 1k 67 68 49 2k 63 65 45 4k 57 59 39 8k 54 56 36

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 91 93 73 125 89 31 71

Frequency bands [Hz] 250 88 90 70 500 83 85 65 1k 81 83 63 2k 77 80 59 4k 71 73 53 8k 68 70 50

Measurement point: 0,38 m/s; 250 Pa

Measurement point: 0,46 m/s; 1276 Pa

308

Centrifugal fans single inlet

Centrifugal fans

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 82 84 64 125 80 82 62

Frequency bands [Hz] 250 79 81 61 500 74 76 56 1k 72 74 54 2k 68 70 50 4k 62 64 44 8k

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 82 84 64 125 80 82 62

Frequency bands [Hz] 250 79 81 61 500 74 76 56 1k 72 74 54 2k 68 70 50 4k 62 64 44 8k 59 61 41

Measurement point: 0,69 m/s; 320 Pa

Measurement point: 0,32 m3/s, Ps = 398 Pa

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 94 96 76 125 92 94 74

Frequency bands [Hz] 250 91 93 73 500 86 88 68 1k 84 86 66 2k 80 82 62 4k 74 76 56 8k 71 73 53

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 94 96 76 125 92 94 74

Frequency bands [Hz] 250 91 93 73 500 86 88 68 1k 84 86 66 2k 80 82 62 4k 74 76 56 8k 71 73 53

Measurement point: 0,83 m/s; 1800 Pa

Measurement point: 0,72 m/s; 1431 Pa

309

Centrifugal fans

Centrifugal fans single inlet

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 82 84 64 125 80 82 62

Frequency bands [Hz] 250 79 81 61 500 74 76 56 1k 72 74 54 2k 68 70 50 4k 62 64 44 8k 59 61 41

dB(A) LwA Inlet LwA Outlet LwA Surrounding

Tot 63 80 82 62 125 78 80 60

Frequency bands [Hz] 250 74 76 56 500 71 73 53 1k 67 69 49 2k 65 67 47 4k 61 63 43 8k 57 59 39

Measurement point: 0,42 m/s; 465 Pa

Measurement point: 0,42 m/s; 320 Pa

310

Centrifugal fans single inlet Reference

Centrifugal fans

Applications for KBT, Therme Erding, Germany

311

Domestic fans

Domestic fans

General
Domestic fans for the ventilation of bathrooms,toilets and storage rooms. Can be wall or window mounted and in some cases duct mounted.

BF axial fan, CBF centrifugal fan


Casing manufactured from sturdy ABS plastic. Available in standard exhaust fan version, with timer or with timer and humidity sensor.

BF-W axial fan


Casing manufactured from sturdy ABS plastic. For wall or window mounting. Back draught damper included.

IF inline axial fan


Booster fan for duct mounting, with single phase induction motors.

312

Domestic fans

BF-W. . . . . . . . . . . . . . . . . . 314 Fans for bathrooms, toilets and store rooms, up to 0.06 m3/s.

Domestic fans

IF. . . . . . . . . . . . . . . . . . . . . 316 Fans for bathrooms, toilets and store rooms. 0,03 m3/s.

BF . . . . . . . . . . . . . . . . . . . . 316 Fans for bathrooms, toilets and shower rooms, up to 0.07 m3/s.

CBF . . . . . . . . . . . . . . . . . . . 316 Window or wall mounted fans for bathrooms, toilets and store rooms, up to 0.19 m3/s.

313

Domestic fans BF-W


BF-W axial fan for window mounting. Suitable for a variety of domestic and commercial applications, the BF-W range has been designed for window or wall mounting. These extract fans are easy to install and manufactured from ABS plastic for durability, ease of cleaning and maintenance and cover a wide variety of domestic and commercial applications including kitchens, utility rooms, pubs, restaurant, offices shops and factories. They, can be connected either through the light switch, so that they start when the light is turned on, or through a separate switch. BF-W is equipped with external gravity backdraught shutters. Ventilation accessories

BVK p. 390

Domestic fans

BF-W 230A

BDS p. 390

BF-W 120A

BF-W

BF-W 100A 120A 150A 230A 300A

A 163 182 203 286 362

B 90 92 105 125 145

C 30 32 23 25 29

D 98 118 150 230 300

tECHNICAL DATA
BF-W Art no. Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Capacitor 100A 7200 V/50 Hz 230 1~ W 14.8 A 0.0899 m3/s 0.0191 min-1 2468 C 70 C 70 dB(A) 45 kg 1 B IP 44 F 120A 7202 230 1~ 13.9 0.0899 0.023 2198 57.4 57.4 48 1.2 B IP 44 150A 7204 230 1~ 30.8 0.19 0.0641 2253 63.9 63.9 54 1.5 B IP 44 230A 7206 230 1~ 41.7 0.197 0.124 1155 61.1 61.1 53 3.1 B IP 44 2 300A 7219 230 1~ 70.8 0.32 0.192 1035 70 70 55 5.2 B IP 44 3.15

314

Domestic fans
performance
BF-W 100 BF-W 120

Domestic fans

dB(A) LwA Inlet LwA Outlet

Tot 63 52 59 12 40 125 42 54

Frequency bands [Hz] 250 47 55 500 47 53 1k 43 44 2k 40 41 4k 36 36 8k 29 28

dB(A) LwA Inlet LwA Outlet

Tot 63 55 62 18 42 125 48 57

Frequency bands [Hz] 250 48 57 500 49 57 1k 48 50 2k 46 47 4k 38 36 8k 31 29

Measurement point: 0,0072 m/s; 7,3 Pa

Measurement point: 0,0094 m/s; 14,7 Pa

BF-W 150

BF-W 230

dB(A) LwA Inlet LwA Outlet

Tot 63 60 66 17 42 125 50 59

Frequency bands [Hz] 250 54 63 500 56 60 1k 54 50 2k 50 50 4k 43 42 8k 34 31

dB(A) LwA Inlet LwA Outlet

Tot 63 60 61 37 37 125 47 47

Frequency bands [Hz] 250 52 50 500 54 54 1k 56 58 2k 52 53 4k 47 47 8k 38 40

Measurement point: 0,0342 m/s; 25,9 Pa

Measurement point: 0,0603 m/s; 20 Pa

BF-W 300

dB(A) LwA Inlet LwA Outlet

Tot 63 65 66 55 54 125 59 61

Frequency bands [Hz] 250 58 59 500 58 58 1k 58 59 2k 55 55 4k 50 50 8k 40 43

Measurement point: 0,108 m/s; 19,3 Pa

315

Domestic fans BF CBF


The BF/CBF units are extraction fans manufactured from ABS plastic. These fans, can be connected either through the light switch, so that they start when the light is turned on, or to a separate switch. The CBF has a spring-loaded back draft damper. There are three models: standard model (S), a model with timer (T) and a model with timer and humidity sensor (TH). A time delay of between 1 and 20 minutes can be set by removing the units front cover. The humidity sensor can be set to a value between 40 and 95% relative humidity. The BF fan has an adjustment knob that is easily accessible at the bottom of the fan. To adjust the humidity sensor on the CBF fan, the front cover should be removed first. BF CBF

Domestic fans

BF 100 120 150

A 163 182 203

B 98 118 150

C 60 40 81

IF
IF in-line axial fan, suitable for bathrooms, toilets and shower rooms. The IF series are in-line extractor fans designed for the safe ventilation of bathrooms, toilets and shower rooms. Manufactured from high impact ABS thermoplastic. The series comprises of a fan unit only and is suitable for boosting a BF fan where a longer run of ducting is used. The IF fans have single-phase induction motors with sealed for life bearings.

IF

IF 100 120 150

A 100 118 150

B 90 99 110

tECHNICAL DATA
BF 100 Art no. standard Art no BF + timer Art no + timer and humidity sensor Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor
3

BF 120 5951 5954 5957 230 1~ 13.9 0.09 0.023 2198 57.4 57.4 48 0.8 B IP 44

BF 150 5952 5955 5958 230 1~ 30.8 0.19 0.0641 2253 63.9 63.9 54 1.0 B IP 54

CBF 100L 5959 5960 5961 230 1~ 29.1 0.19 0.0291 2403 57.3 57.3 52 1.2 B IP 54

IF 100 5962 230 1~ 14 0.0242 2432 IP 44

IF 120 5963 230 1~ 25 0.0361 2000 IP 44

IF 150 5964 230 1~ 25 0.0667 2400 IP 44

5950 5953 5956 V/50 Hz 230 1~ W 14.8 A 0.09 m /s 0.0191 min-1 2468 C 70 C 70 dB(A) 45 kg 0.7 B IP 44

316

Domestic fans

BF 100

BF 120

Domestic fans

dB(A) LwA Inlet LwA Outlet

Tot 63 52 59 12 40 125 42 54

Frequency bands [Hz] 250 47 55 500 47 53 1k 43 44 2k 40 41 4k 36 36 8k 29 28

dB(A) LwA Inlet LwA Outlet

Tot 63 55 62 18 42 125 48 57

Frequency bands [Hz] 250 48 57 500 49 57 1k 48 50 2k 46 47 4k 38 36 8k 31 29

Measurement point: 0,0072 m/s; 7,3 Pa

Measurement point: 0,0094 m/s; 14,7 Pa

BF 150

dB(A) LwA Inlet LwA Outlet

Tot 63 60 66 17 42 125 50 59

Frequency bands [Hz] 250 54 63 500 56 60 1k 54 50 2k 50 50 4k 43 42 8k 34 31

Measurement point: 0,0342 m/s; 25,9 Pa

CBF 100L

IF

15

IF

12

IF 0 10

dB(A) LwA Inlet LwA Outlet

Tot 63 59 61 17 40 125 40 54

Frequency bands [Hz] 250 50 57 500 55 55 1k 55 53 2k 49 43 4k 44 37 8k 35 27

dB(A) LwA Inlet LwA Outlet

Tot 63 55 62 18 42 125 48 57

Frequency bands [Hz] 250 48 57 500 49 57 1k 48 50 2k 46 47 4k 38 36 8k 31 29

Measurement point: 0,0139 m/s; 74 Pa

Measurement point: 0,0094 m/s; 14,7 Pa

317

Electrical accessories

Electrical accessories

Switching devices & isolators

Motor protection

Electrical actuators

Speed control, transformers

Other electrical accessories

Sensors and thermostats

Speed control, electronic Heat controls

318

Electrical accessories

Switching devices & isolators


EMC KIT REV. . . . . . . . . . . . . 340 REV . . . . . . . . . . . . . . . . . . . . 340 REV DVV . . . . . . . . . . . . . . . . 340 S-DT2 DKT. . . . . . . . . . . . . . . 340 S-DT2 GKT. . . . . . . . . . . . . . . 340 S-DT2 SKT. . . . . . . . . . . . . . . 340 S2S 160. . . . . . . . . . . . . . . . . 340 S5S 100T1 . . . . . . . . . . . . . . 340 S5S 100T3 . . . . . . . . . . . . . . 340

Electrical actuators
RVAZ4-24. . . . . . . . . . . . . . . 339 RVAZ4-24A . . . . . . . . . . . . . . 339 SF 24A . . . . . . . . . . . . . . . . . . 344 SF 24A-S2. . . . . . . . . . . . . . . 344 SF 24A-SR. . . . . . . . . . . . . . . 344 SF 230A. . . . . . . . . . . . . . . . . 344 SM 230A. . . . . . . . . . . . . . . . 344

Motor protection
AWE-SK. . . . . . . . . . . . . . . . . 342 MSEX. . . . . . . . . . . . . . . . . . . 342 S-ET 10, S-ET 10E. . . . . . . . . 341 STDT 16, STDT 16E. . . . . . . . 342 U-EK 230E EX. . . . . . . . . . . . 338

Other electrical accessories


EX connection box. . . . . . . . 339 HR1. . . . . . . . . . . . . . . . . . . . 343 IR24-P. . . . . . . . . . . . . . . . . . 343 MicroREX D21 . . . . . . . . . . . . 339 SC1/D . . . . . . . . . . . . . . . . . . 331 SC2/D . . . . . . . . . . . . . . . . . . 331 T 120. . . . . . . . . . . . . . . . . . . 339

Sensors and thermostats


CO2RT. . . . . . . . . . . . . . . . . . 330 CO2RT-R-D . . . . . . . . . . . . . . 330 DSG. . . . . . . . . . . . . . . . . . . . 330 DTV. . . . . . . . . . . . . . . . . . . . 343 K-FST1. . . . . . . . . . . . . . . . . . 339 RT 0-30. . . . . . . . . . . . . . . . . 337 TFR . . . . . . . . . . . . . . . . . . . . 343 TG-A 130 . . . . . . . . . . . . . . . . 338 TG-K330. . . . . . . . . . . . . . . . 338 TG-KH/PT1000. . . . . . . . . . . 338 TG-R4/R5/PT1000. . . . . . . . 338 TG-R430/530. . . . . . . . . . . . 338 TG-R600/630. . . . . . . . . . . . 338 TG-UH/PT1000. . . . . . . . . . . 338 TM 10. . . . . . . . . . . . . . . . . . 337

Speed control, transformers


FRQ(5), FRQ(5)S. . . . . . . . . . 325 RADT. . . . . . . . . . . . . . . . . . . 333 R-DK4 KT (EX) . . . . . . . . . . . . 323 RE . . . . . . . . . . . . . . . . . . . . . 320 REU . . . . . . . . . . . . . . . . . . . . 320 RTRD. . . . . . . . . . . . . . . . . . . 321 RTRDU. . . . . . . . . . . . . . . . . . 321 RTRE . . . . . . . . . . . . . . . . . . . 320 Trafo 15/D . . . . . . . . . . . . . . 339

Electrical accessories

Heat controls
AQUA 24TF. . . . . . . . . . . . . . 341 Pulser . . . . . . . . . . . . . . . . . . 334 Pulser M. . . . . . . . . . . . . . . . 334 TTC . . . . . . . . . . . . . . . . . . . . . 335 TT-S1. . . . . . . . . . . . . . . . . . . 335 TT-S4/D. . . . . . . . . . . . . . . . . 336

Speed control, electronic


CXE/AV . . . . . . . . . . . . . . . . . 323 CXE/AVC . . . . . . . . . . . . . . . . 322 EC-Vent control board . . . . . 329 EC-Vent room unit . . . . . . . . 330 FXDM . . . . . . . . . . . . . . . . . . . 324 MTP 10. . . . . . . . . . . . . . . . . 341 MTV 1/010. . . . . . . . . . . . . . 341 Optigo OP 5 . . . . . . . . . . . . . 336 Optigo OP 10 . . . . . . . . . . . . 336 PKDM12. . . . . . . . . . . . . . . . 324 PXDM5A. . . . . . . . . . . . . . . . 324 REE . . . . . . . . . . . . . . . . . . . . 321 REE S0. . . . . . . . . . . . . . . . . . 322 REE TR0. . . . . . . . . . . . . . . . . 322 REPT . . . . . . . . . . . . . . . . . . . 331 RETP . . . . . . . . . . . . . . . . . . . 331

319

Electrical accessories RE
Manual five-step transformer

RTRE

Manual five-step transformer


(with motor protection) A single-phase transformer which controls the fan speed by altering the supply voltage in five fixed steps. The steps are adjusted manually, using the control knob on the front of the unit. An integral motor protection device is included which cuts the supply voltage to the fan if the thermal contact in the fan motor is activated. The unit is reset by turning the knob to 0 for 10 seconds, after which the unit restarts. The unit has input terminals for room thermostat RT, which stops the supply voltage to the fan when the circuit is broken. These terminals are bridged before delivery. The transformer has 230V terminals for operating dampers, electric water-heater batteries or other external equipment. These terminals have no current when the transformer knob is in position 0, or when the TK or RT input is open. The indicator lamp on the front shows when the transformer is in operation. The fuse may be reset from outside. The RTRE has a self-extinguishing thermoplastic casing. Supply voltage: 230V 50/60Hz.
Output voltages for each of the 5 steps: Step Voltage 1 80 2 105 3 130 4 160 5 230

REU

Manual five-step transformer


A single-phase transformer which controls the fan speed by altering the supply voltage in five fixed steps. The steps are adjusted manually, using the control knob on the front of the unit. There are two control switches: one for higher fan speeds and one for lower fan speeds. Switching between the high and low settings is done by an external change-over contact, which could be a thermostat or a timer. The indicator lamp on the front shows when the transformer is in operation. The fuse may be reset from outside. The REU has a self-extinguishing thermoplastic casing. Supply voltage: 230V 50/60Hz. NOTE! Fans with external thermal contact leads (TK) must always be connected to a motor protection device.
Output voltages for each of the 5 steps: Step Voltage 1 80 2 105 3 130 4 160 5 230

Electrical accessories

A single-phase transformer which controls the fan speed by altering the supply voltage in five fixed steps. The steps are adjusted manually, using the control knob on the front of the unit. The transformer has 230V terminals for operating dampers, electric heater batteries or other external equipment. When the transformer knob is in position 0, the outlet has no current. The indicator lamp on the front shows that the transformer is in operation. The fuse may be reset from outside. The RE has a self extinguishing thermoplastic casing. NOTE! Fans with external contact leads (TK) must always be connected to a motor protection device.

Output voltages for each of the 5 steps: Step Voltage 1 80 2 105 3 130 4 160 5 230

RE 1.5 3 5 7

Current 1.5 3 5 7

Enclosure 54 54 54 54

REU 1.5 3 5 7

Current 1.5 3 5 7

Enclosure IP 54 IP 54 IP 54 IP 54

RTRE 1.5 3 RE 1.5 3 5 7 Width 105 105 105 147 Height 200 200 200 257 Depth 105 105 105 145 Weight, kg 1.5 2.5 4.1 7.5 RTRE 1.5 3 5 7 12
Transmisson Supply voltage Earth Fan

Current 1.5 3 5 7 12

Enclosure IP 54 IP 54 IP 54 IP 54 IP 54 REU 1.5 3 5 7 Width 105 105 105 105 Height 200 275 275 275 Depth 105 145 145 145 Weight, kg 2.0 4.05 4.9 7.05

5 7 12

Width 105 105 105 147 147

Height 203 203 203 278 278

Depth 106 106 106 140 140

Weight, kg 1.9 2.6 4.2 7.2 10.5


Fan Earth Supply voltage

Transmisson: between ~ and N is always 230V when the transformer handle is in pos. 1-5

1. Switching contact 2. Low speed contact 3. High speed contact

Supply voltage Transmission

Earth

Fan

Thermostat

Motor protection

NB! A switchning contact has to be connected

Transmisson

Supply voltage

Earth

Fan

Thermostat

Motor protection

320

Electrical accessories RTRD


Manual fivestep transformer
(With motor protection). A three-phase transformer which controls the fan speed by altering the supply voltage in five fixed steps. The steps are adjusted manually, using the control knob on the front of the unit. An integral motor protection device is included which cuts the supply voltage to the fan if the thermal contact in the fan motor is activated. The unit is reset by turning the knob to 0 for 10 seconds, after which the unit restarts. Input terminals for room thermostat RT and frost protection thermostat FS cut supply voltage to the fan when the circuit is broken. When the frost protection thermostat FS breaks the circuit, it is reset in the same way as when the TK is triggered. Terminals are linked before delivery. The indicator lamp on the front shows that the transformer is in operation. The transformer has 230V terminals for operating dampers, electric heater batteries or other external equipment. These terminals have no current when the transformer knob is in position 0, or when the TK or RT input is open. Supply voltage: 400V 50/60Hz.

RTRDU

REE

Manual five-step transformer


(With motor protection). A three-phase transformer which controls the fan speed by altering the supply voltage in five fixed steps. The steps are adjusted manually, using the control knobs on the front of the unit. There are two control knobs: one for higher fan speeds and one for lower fan speeds. Switching between the high and low settings is done by an external change-over contact, which could be a thermostat or a timer. An integral motor protection device is included which cuts the supply voltage to the fan if the thermal contact in the fan motor is activated. The unit is reset by turning the switch to 0 for 10 seconds, after which the unit restarts. Input terminals for room thermostat RT cuts supply voltage to the fan when the circuit is broken. Terminals are linked before delivery. The indicator lamp on the front shows when the transformer is in operation. The transformer has 230V terminals for operating dampers, electric heater batteries or other external equipment. These terminals have no current when the transformer switch is in position 0, or when the TK or RT input is open. Supply voltage: 400V 50/60Hz.

Thyristor speed controller

- only surface mounting For the manual control of speed and air flow of electrical fans, AC-induction motors of universal motorand permanent-capacitor type. The jetproof IP 54 enclosure is achieved with the included surface mounting case. (Flushmounting without the surfase mounting case, gives a splash proof IP 44 enclosure also suitable for highly demanding enviroments as bathrooms etc.) Several motors can be connected in parallel as long as the total current does not exceed current range. Starting currents must be considered when choosing speed controller type. Fans to be used with this controller require a built-in overheating protection and should be designed for thyristor speed control.

Electrical accessories

REE 1 Voltage Frequency Current Fuse Enclosure WxHxD V 230 ~ Hz 50 A 0.1-1.0 A 1.25 IP 54 kg 0.25

REE 2 230~ 50 0.1-2.0 2.5 54 0.25

REE 4 230~ 50 0.4-4.0 5 54 0.25

Output voltages for each of the 5 steps: Step Voltage RTRD 2 3 4 5.2 7 14 RTRD 2 3 4 5.2 7 14 Width 240 270 270 270 270 450 1 95 2 145 Current 2 3 4 5.2 7 14 Height 284 323 323 323 323 290 Depth 132 172 173 172 172 174 3 190 4 240 5 400

Output voltages for each of the 5 steps: Step Voltage RTRDU 2 4 7 RTRDU 2 4 7 Width 270 270 270 1 95 2 145 Current 2 4 7 Height 323 323 323 Depth 163 163 163 3 190 4 240 5 400

mm 82x82x65 82x82x65 82x82x65

Weight

Enclosure IP 54 IP 54 IP 21 IP 54 IP 21 IP 21 Weight, kg 7.4 11 11 15.6 16 32

Enclosure IP 21 IP 21 IP 21 Weight, kg 8 12 16.5

External change-over contact 2. 230V

Line L state connection with cutting function on the speed control. Broken line (L) state connection without cutting function.

321

Electrical accessories REE TR0


Thyristor speed controller
Stepless phase cutting controller for 1~230V/50Hz motors. It has a potentiometer to set the speed and control lamps for operation and alarm. Internal potentiometer to set a min speed. On/off switch with control lamp. Connection for on/off switch, alarm and thermal contacts. White plastic casing IP54. Several motors can be connected in parallel as long as the total current does not exceed the current range. Fans to be used with this controller must be designed for thyristor speed control. NOTE: phase cutting controller can cause electrical noise interference!

REE S0

Thyristor power unit

Stepless phase cutting contoller for 1~230V/50Hz motors. It has a connection for an external control signal 0...10V or 4...20mA. The control signal can be choosen by an internal switch. Internal potentiometer to set a min speed. On/off switch with control lamp. White plastic casing IP54. Several motors can be connected in parallel as long as the total current does not exceed the current range. Fans to be used with this controller require a build-in overheating protection and should be designed for thyristor speed control. NOTE: phase cutting controller can cause electrical noise interference!
REE Voltage Current Fuse Enclosure V A A IP 030S0 230 ~ 0.3-3.0 FF4 54 050S0 230~ 0.5-5.0 FF8 54 100S0 230~ 1.0-10.0 FF14 54
V. min ADJUST
0-10VDC 4-20mA

Electrical accessories

REE Voltage Current Fuse Enclosure

050TR0 V 230~ A 0.5-5.0 A FF8 IP 54

100TR0 230~ 1.0-10.0 FF14 54

Control signal

0...10VDC/4...20mA

L1

FT

FT

TK

TK

U1

N Pe

230 VAC 50/60 Hz

230 VAC output

Alarm out
T

L1-N: Input to bypass the on/off contact 230 V non-controlled output FT-FT Connection for thermostat, timer, frostprotection, on/off-switch at a distance N-A Alarm output in case of motor fault 230 VAC, 2A TK-TK Input thermal contacts of the motor

L Pe

L1

DIP switch Select

230 VAC 50/60 Hz

+ 0-10VDC 4-20mA

Analog In 4...20 mA (0...20 mA)..1

Analog In 4...20 mA (0...20 mA)..2

Analog Out 1

Digital In 1

Digital In 3

Digital In 2

Digital In 4

Digital In 5 31 32

Analog In 0...10 V..1

Analog In 0...10 V..2

Analog In TF..1

Analog In TF..2

Universal module with timer function. Controlled 0-10 V output e.g. for electronic speed controllers of fans. Applications: Pressure control, outdoor temperature control, outdoor temperature compensated pressure control, etc.
CXE/AVC Voltage Frequency Phase Output 0-10 V, Imax Enclosure class Weight Dimensions V 230 Hz 50/60 ~ 1 mA 10 IP 54 kg 1.3 mm 213x185x102

Contact rating max. AC 250 V 5 A

Analog Out 2

Regulator

CXE/AVC

Unicon CXE/AVC(E)

GND DD+ B A

7 PE N L1 1 2 K1 3 4 5 K2 + 6 8

9 10

11 12

13 14

15 16

17 18

19 20

21 22

23 24

25 26

27 28

29 30

+ 24 V DC 24 V DC Out Out + Input TF..(KTY) E2 + + Input 4...20 mA (0...20 mA) E2 Eingang Input 0...10 V E2
Data Data GND

PE N

L1

Line 1 ~ 110...277 V (208...415 V) 50/60 Hz

Input TF..(KTY) E1

+ RS-485

+ Output 0...10 V (Imax = 10 mA) A2 + D1 D2 D3 D4 D5

+ Input 0...10 V E1

Input 4...20 mA (0...20 mA) E1

Output 0...10 V (Imax = 10 mA) A1

MCRE09K4 22.04.2009

322

Electrical accessories R-DK4 KT (EX)


Manual five-step transformer
R-DK...KT(G)
(With motor protection) for RVK 315Y4, KTEX, DKEX and DVEX fans. An integral thermistor releasing unit type U-EK230E with ATEX-approval can be used for the temperature monitoring of motors in explosion protected range. A three-phase transformer which controls the fan speed by altering the supply voltage in five fixed steps. The steps are adjusted manually, using the control knob on the front of the unit. An integral motor protection device is included which cuts the supply voltage to the fan should the thermistor motor position trigger. The unit is reset by turning the knob to 0 for 1 minute. Input terminals for room thermostat RT cut supply voltage to the fan when the circuit is broken. NB. The transformer can not be placed in the EX zone.

T2

T1

12

11

14

RT 1*

RT

L1

L2

L3

250 V AC max. 2 A

230 V AC max. 1 A

230 V AC

PE
0 1

L1

L2

L3
U V M 3~
TP TP

PE

3 ~ 400 V 50/60 Hz

Y/

Electrical accessories

SR171K13 27.11.2007

On/off

3~ motor with internal thermistors

1* If function is not needed, terminals must be bridged

R-DK4 KT Voltage Frequency Current Max. ambient temp. Enclosure WxHxD Weight V 400 3~ Hz 50/60 A 4.0 C 40 IP 21 mm 270x323x163 kg 11.5

CXE/AV

CXE/AV
Switch or jumper
C mA V C V 24 V DC mA C V E1 E1 mA 11 14 K1 12 21 24 K2 22

Universal regulator
Digital Analog A1 A2 Analog

Regulator with multifunction display constant temperature or constant pressure in duct systems with 0...10V output signal to control external devices (power units, frequency inverters, EC-motors etc.). Two setpoints are possible. 3 digital inputs, 2 analogue inputs, 2 analogue outputs 0...10V and 2 relays with changeover contact. All in-/outputs are programable. With preprogram modes also for outdoor compensation for easy setup. Menu languages are English, German, Swedish,... 24VAC/ Imax 70mA power supply for sensors.

Out

In 1/2/3
24V D1 D2 D3

Out 1/2
GND GND

In 1/2
E1 E2

E2

E2

Contact rating max- AC 250 V 5 A

D+ L1 (+) N (-) PE D-

24V GND

Line
+
Data Data 24 V GND

+ RS-485

Output
0...10 V (Imax = 10 mA)

Input
0...10 V 0...20 mA 4...20 mA TF..(KTY)

CXE/AVC Voltage Frequency Phase Output 0-10 V, Imax Switching capacity Ambient temp. Enclosure class Weight Dimensions V 230 Hz 50/60 ~ 1 mA 10 5A/250VAC C 0...40 IP 54 kg 0.9 mm 166x160x87

Output
0...10 V (Imax = 10 mA)

Input
0...10 V 0...20 mA 4...20 mA TF..(KTY)

323

Electrical accessories FXDM


Frequency inverter

PXDM5A

Electrical accessories

Frequency inverter with integrated allpole sine filter. Frequency regulator with multifunction display for constant temperature or constant pressure in duct systems with integrated process controller (PID free programmable) or with 0...10V control signal. Two setpoints or manual mode is possible. 2 digital inputs, 2 analogue inputs, 1 analogue output 0...10V and 2 relays with change-over contact. All inputs and outputs are programmable. Total motor protection using thermocontact/ thermistor connection. Menu languages are English, German, Swedish,... +24VAC/Imax 120mA power supply for sensors. Masking up to three settable speed ranges. Min. and max. speed limitation. Integrated allpole sine filter for external rotor motors. NB! Absolute parallel operation of fans, no risk of damage to motor. Screened motor cables are not required! Wiring diagram on page 326.

Internal display
Universal regulator, three phase. Regulator with multifunction display constant temperature or constant pressure in duct systems for 3~400V motors. Connection for thermal contacts. Two setpoints are possible. 2 digital inputs, 2 analogue inputs, 1 analogue output 0...10V and 2 relays with change-over contact. All in-/outputs are programmable. With preprogram modes also for outdoor compensation for easy setup. Menu languages are English, German, Swedish,... 24VDC/Imax 70mA power supply for sensors. Permitted relative humidity, non condensating 85%. Wiring on page 326.

PKDM12

Thyristor power unit


Stepless phase cutting controller for 3~400V/50Hz motors with motor protection. It has a connection for a potentiometer or an external control signal 0...10V, 0...20mA or 4...20mA. The control signal can be chosen by an internal jumper. Internal potentiometer for setting set point, min. speed, max. speed and p-band. Digital input for on/off. Temperature control possible. Several motors can be connected in parallel as long as the total current does not exceed the current range. Fans to be used with this controller should be designed for thyristor speed control. Permitted relative humidity, non condensating 85%. NB! Phase cutting controller can cause electrical noise interference! Wiring diagram on page 326.

PXDM5A Voltage Phase Frequency Current Recommended fuse Output voltage approx. Max. power dissipation Perm. ambient temp. Enclosure class Weight WxHxD V 400 ~ 3 Hz 50/60 A 5 A 10 % 20...100 W 40 C 0...40 IP 54 kg 2.9 mm 240x284x131

PKDM12 Voltage Phase Frequency Current Min. motor current Output voltage appr. Max. power dissipation Control signal Recom. fuse Ambient temperature Enclosure class Weight WxHxD V 208...415 ~ 3 Hz 50/60 A 12 A 0,2 % 0...100 W 55 0...10V/4...20mA A FF30A 10x38mm C 40 IP 54 kg 3.4 mm 270x323x146

FXDM Voltage Phase Frequency Max. current Recom.fuse Ambient temp. Enclosure Weight Width Height Depth

5 V 208...480 ~ 3 Hz 50/60 A 5 max A 10 C 40 IP 54 kg 7.2 mm 252 mm 302 mm 195.5

8 208...480 3 50/60 8 10 40 54 7.9 252 302 195.5

FXDM Voltage Phase Frequency Max. current Recom.fuse Ambient temp. Enclosure Weight Width Height Depth

13 V 208...480 ~ 3 Hz 50/60 A 14 max A 16 C 40 IP 54 kg 8.7 mm 252 mm 302 mm 195.5

18 208...480 3 50/60 18 20 40 54 14.2 382 355 239

324

Electrical accessories FRQ(5)


Speed controller with 0-10V (or 5-step) Input for 3~ fan
Optimized frequency inverters for the control of one fan motor for frequency converter suitable isolation system and bearings e.g. IE2 - Analog input for external speed setting(0-10 V, 0-20 mA, PWM) - 10V DC output for external potentiometer - Alarm relay - Enable contact section - Motor protection by connecting thermo stats or thermistors - Interference emission EN 61000-6-3 - Interference immunity EN 61000-6-2 - Parallel operation of several motors is not allowed - Max. length of contoller(poti) cable 100m - Max. length of motor cable 10m (screened) - Please note: Not suitable for external rotor motors. Wiring diagram on page 327

FRQ(5)S

Speed controller with 0-10V(or 5-step) Input for 3~ fan with all pole sine filter
The FRQS/FRQ5S frequency inverters have integrated all pole sine filters as standard. Therfore there is no need for shielded cables for the installation. This makes the unit also perfectly suited to retrofit into existing systems. The sine filters enable existing non-shielded cables to be retained. This units also reliably control motors which, due to their design, are not usually considered suitable for frequency inverter operation i.e. external rotor motors. - Save and trouble free motor operation with integrated, all pole effective sine filter - Enable contact section for a stand-by switch or electronic reset - Motor protection by connecting thermostat or thermistors - Interference emission EN 61000-6-3 - Interference immunity EN 61000-6-2 - Complete range in IP54 - Trouble free parallel operation of motors - - No danger to the motors through voltage peaks, bearing current, etc. - No limit of motor cable length - Retrofit in installations with existing wiring (unshielded cables) - Operation without electromagnetic motor noise - Wide voltage range 3~ 208V-480V, 50/60Hz. Wiring diagram on page 328
FRQ5S Voltage Phase Frequency Max. current Max. power load Recom.fuse 4A V 208...480 ~ 3 Hz 50...60 A 4 kW 1.5 A 10 C 40 % 85 IP 54 kg 5.4 mm 250+2 mm 302 mm 212 4A V 208...480 ~ 3 Hz 50...60 A 4 kW 1.5 A 10 C 40 % 85 IP 54 kg 5.4 mm 250+2 mm 302 mm 195.5 10A 208...480 3 50...60 10 4 16 40 85 54 5.4 250+2 302 212 10A 208...480 3 50...60 10 4 16 40 85 54 5.4 250+2 302 195.5

Electrical accessories

FRQ Voltage Phase Frequency Max. current Max. power load Recom.fuse Ambient temp. Hum, non cond. Enclosure Weight Width Height Depth

4A V 208...480 ~ 3 Hz 50...60 A 4 kW 1.5 A 10 C 40 % 85 IP 54 kg 2.3 mm 240 mm 284 mm 115

10A 208...480 3 50...60 10 4 16 40 85 54 5.3 250+2 302 195.5

FRQ5 Voltage Phase Frequency Max. current Max. power load Recom.fuse Ambient temp. Hum, non cond. Enclosure Weight Width Height Depth

4A V 208...480 ~ 3 Hz 50...60 A 4 kW 1.5 A 10 C 40 % 85 IP 54 kg 2.4 mm 240 mm 284 mm 132

10A 208...480 3 50...60 10 4 16 40 85 54 5.4 250+2 302 212

Ambient temp. Hum, non cond. Enclosure Weight Width Height Depth FRQS Voltage Phase Frequency Max. current Max. power load Recom.fuse Ambient temp. Hum, non cond. Enclosure Weight Width Height Depth

325

Electrical accessories
Wiring diagram FXDM
Fcontrol FXDM(A)M
Switch or jumper
C V C V E2 mA E1.1 E1.2 E2.1 E2.2 C Analog In 1 Analog In 2 Digital In 2 D2 V

Addressing Normal
DD+ GND 24 V

Contact rating
max. 2 A / 250 V AC TB / TP In 11 14 K1 12 21 24 K2 22 GND Digital In 1 D1

E1 Analog Out 1

mA

24V DC Out

TK / PTC D1

A GND 24 V 24 V E1 GND E2 GND D2

mA

L1

L2

L3

Output
0 .. 10 V (Imax = 10 mA)
10 mm / 2x

Input
0 ..10 V 0 .. 20 mA 4 .. 20 mA TF.. (KTY) + 1

24 V GND Data Data + -

V M 3~

PE

TB

TB

Input
0..10 V 0 .. 20 mA 4 .. 20 mA TF.. (KTY) GND D+ D-

PE L1 L2 L3

Electrical accessories

3~ 208 .. 480 V 50/60 Hz

Line

Y/

Terminal
AXG-1A(E)

3~motor with internal thermostats


12.09.2007 UMPO02K1.VSD

Only in special version suitable for IT network!

Wiring diagram PKDM


Dcontrol PKDM
Switches

C V E2 mA C

Depending on version switches or jumpers for input signal


24V DC OUT 1 Analog OUT 1

Jumpers

E2.1 E2.2 Analog IN 1 Analog IN 2 Digital IN 2

Contact raiting
max. 5A/250VAC GND N L1 L2 L3 U V W 11 14 K1 12

mA E1 TK TK 1*

Digital IN 1

RS-485

E1.1 E1.2

mA

J2

D1 D1 1*

A GND

24V 24V

E1 GND

E2 GND

D2 D2

0 1

1 0

C/bar > set

U A + / C/bar < set

U A+

On/of

Output
0...10V TF..

Input

PE N

L1 L2 L3
U V M 3~ W PE

(Imax=10mA)

Line
3~ 208 .. 415 V 50/60 Hz (3~ 208 .. 500V 50/60 Hz)

0...10V 4...20mA TF..

Temp. sensor
4-20mA

bzw. Y or

Special version
3~ Motor

D TB TB

braun grn BN GN

With internal thermostats

Extern desired value

MBG..
10K

Pressure sensor

Input
0...10V (Ri>100k)

1* If function is not needed, terminals must be bridged

Wiring diagram PXDM


Ucontrol PXDM...
Analog OUT 1 24V DC OUT Analog IN 1 Analog IN 2 Digital IN 1 Digital IN 2
C V mA X5 GND DD+
E2.1 E2.2 E1.1 E1.2

Max. contact rating 5A/250VAC


GND TK TK

D1 D1

A GND

24V 24V

E1 GND

E2 GND

D2 D2

B A

N L1 L2 L3 U

11 14 12 21 24 22

K1

K2
+
NET_ A B DATA DATA GND optional + (LON) RS-485

PE N L1 L2 L3
Line

Output
0...10V (Imax=10mA)

3 ~ 208V...400V 50/60Hz
U1 V1 W1 TK TK

1
+ GND D+ D-

Input Terminal

bzw. or

0...10V 0...20mA 4...20mA TF...(KTY)

2
Input

AXG-1A(E)

3~ motor with Internal thermostats

0...10V 0...20mA 4...20mA TF...(KTY)

PDUN16K6

326

Electrical accessories
Wiring diagram FRQ 4/10A

Electrical accessories

Wiring diagram FRQ5 4/10A

327

Electrical accessories
Wiring diagram FRQ5S 4/10A

Electrical accessories

Wiring diagram FRQS 4/10A

328

Electrical accessories EC-Vent control board


Fitness centre

EC-Vent offers the option to simultaneously connect multiple sensors (Temp, Humidity, CO2, PIR etc) that will detect the actual ventilation requirements and in this way speed control the EC fan so that it ventilates exactly as much as is needed, not more, not less. This way an energy efficient ventilation solution is obtained while a good indoor climate is achieved. EC-Vent consists of two units, a central unit placed near the fan and a room unit that can be placed in the occupied zone. These two are connected to each other with a low voltage cable.
CB Voltage Phase Frequency Current Recommended fuse Supply to sensor, 24V DC Ambient temp. Enclosure class Weight V 230 ~ 1 Hz 50/60 A 6 A 10 mA 150 C -20...50 IP 44 kg 0.95

Electrical accessories

Restaurant

Wiring EC-Vent

Room unit

Control board

329

Electrical accessories EC-Vent room unit DSG


Pressure sensor
A membrane-type sensor for measuring the differential pressure in nonaggressive gases. The difference in pressure between the sensors plus (+) and minus (-) connections affects the membrane, which generates a voltage via a differential transformer. This voltage converts into a continuous DC voltage proportional to the membranes position. Cable length approx. 0.5 m.
DSG Voltage supply 200/500/1000 V 15V-30V DC/24V~ 15% IP 65 A 0.012 Pa 0...200 Pa 0...500 Pa 0...1000

EC-Vent room unit that can be placed in the occupied zone. Room unit are connected to EC-vent control board with a low voltage cable.
WC Voltage Phase Ambient temp. Enclosure class Weight V 24 DC = C 0...50 IP 20 kg 0.2

CO2RT CO2RT-R-D
CO2-sensor for wall mounting
CO2RT is a room sensor for measuring carbondioxide, CO2 concentration in indoor environments. Measuring range 0...2000ppm. Output signal 0...10 V for the full measuring range. CO2RT also has a temperature signal, 0...10 V DC for 0...50C. Apart from the above mentioned temperature signal CO2RT also has a PT1000 temperature sensor with separate terminals CO2RT is intended for wall mounting. The display models (D) have an LCD-display showing both actual values by regularly alternating.
CO2RT, CO2RT-R-D Voltage Frequency Power consumption V 24 Hz 50/60 W 3 C -5...+55 % 90 ppm 0...2000 IP 30 kg 0.1 mm 85x100x30

Outp. 0-10 V, Imax mA 2

Electrical accessories

Enclosure Current Press. range 200 Press. range 500 Press. range 1000 Brown Yellow White

Output

Voltage supply 15...30V DC 24V AC 15%

Ambient temperature Re. humidity, non condens. Working range Enclosure class Weight Dimension

Pressure connection 5 mm

Residential

CO2RT-R-D

1 2 3 4 5

Supply voltage 24 V AC System neutral 24 V AC Common Normally open Normally closed

CO2RT

Spa

1 2 3 4 5 6 7 8

Supply voltage 24 V AC System neutral 24 V AC Output 0...10 V (humidity) Output 0...10 V (temperature) Output 0...10 V (CO2) Signal neutral Output, PT1000-sensor Output, PT1000-sensor

330

Electrical accessories SC1/D


Step controller 1-stage
SC1/D is a one-stage signal converter which converts a 0...10V DC input signal to a change-over relay function with adjustable switching points. SC1/D can be set for direct or reverse action, i.e. relay activation on rising input voltage or relay activation on falling input voltage.
SC1/D Voltage supply Frequency Power consumption Control signal Circuit-breaking relay Max. ambient humidity Ambient temperature Enclosure class WxHxD
1 2 3 4 5 6 7 8 9 10 11 12

REPT

Digital voltage regulation, single phase


Thyristor-type digital regulation for single-phase motors with variable voltage control. Used, for example, for the pressure regulation of fans in systems where there is a risk of increased draught, and compensation is required for outdoor temperature conditions and other pressure conditions. An integral motor protection device is included which cuts the supply voltage to the fan if the thermal contact in the fan motor is activated. Radio interference suppression in accordance with EN 50081-1 and EN 50082-2. Regulated output voltage approx. 20-100%. Permitted relative humidity, non condensating 85%. Voltage supply +24 V 20%, Imax 70 mA. Wiring on page 332.
REPT 6/10 Voltage Frequency Current Min. motor current Output 0-10 V, Imax Max. power disspation Perm. ambient temp. Enclosure class WxHxD REPT 6 WxHxD REPT 10 V 230~ Hz 50-60 A 6/10 A 0.2 mA 10 W 16 C 0....40 IP 54 mm 223x200x131 mm 240x284x132 kg 2

RETP

Pressure/temperature regulation, single phase


Thyristor-type stepless pressure or temperature regulation (P-regulation) for single-phase motors with variable voltage control. Used, for example, for room temperature regulation where the heating is conducted by air. An integral motor protection device is included which switch off the supply voltage to the fan if the thermal contact in the fan motor is activated. Regulated output voltage approx. 20-100%. Permitted relative humidity, non condensating 85%. Voltage supply +24 V 20%, Imax 250 mA. Wiring on page 332.
RETP 6/10 Voltage Frequency Current Min. motor current Output 0-10 V, Imax Recommended fuse Max. power disspation Perm. ambient temp. Enclosure class WxHxD RETP 6 WxHxD RETP 10 Weight V 230~ Hz 50-60 A 6/10 A 0.2 mA 10 A 16 W 10/40 C 40 IP 54 mm 223x200x131 mm 240x284x132 kg 1.3/2.3

V 24 VAC Hz 50/60 2 VA 0...10 V A 230V AC, max. 10 %RH 90 C 0...50 IP 20 mm 53x85x74


Sys.neutral Supplyvoltage 24V AC in Not connected Relay 230V AC, 10A Signal neutral Input signal 0-10 V DC Not connected Not connected Not connected Not connected

Electrical accessories

SC2/D

Weight

Step controller 2-stage


Step controller suitable for heating/cooling or alarm applications. Converts 0...10 V input signal to relay output. The module is suitable for mounting on a DIN-rail in a cabinet or other enclosure and has adjustable switching points. SC2/D can be set for either binary or sequential control. Voltage supply 24 V AC +/- 15%, 24 V DC (18...35 V DC).
SC2/D Frequency Power consumption Perm. ambient temp. Max. ambient humidity Step distance Enclosure class WxHxD Hz 50/60 2 VA C 0...50 %RH 90 0...2 V IP 20 mm 53x85x74

R1 1 10A 230V ~ 2 3 Not connected 4 Not connected R2 5 10A 230V ~ 6 7 Input signal 0-10V DC 8 Signal neutral 9 Not connected 10 Not connected 11 Sys.neutral Supply voltage 12 24V ~ in

331

Electrical accessories
Wiring REPT 6/10
...6 F1=M10 A / ...10 F1=FF20 A

REPT6/10
Auto 0 100 %

mA

E2
Analog Out 1 Analog In 2 Didital In 1 Digital In 2

E1
Analog In 1

Contact rating max. AC 250 V 5 A

24V GND D+

D-

PE

PE

L1

L1

U1

U1

U2

U2

11

12
K1

14

21

22
K2

24

D3 D3 D1 D1 24V (TB) (TB) (E3) (GND) A1 GND

(D2) (D2)

A3 GND

E2 GND E1 GND GND

2
Input
24 V GND Data Data

PE

L1

0...10 V 0...20 mA 4...20 mA TF..(KTY) PE U1 M 1~


q

+ RS-485

Analog Out 1

PE

PE

L1

L1

U1

U1

U2

U2

11

12
K1

14

TB

TB

D1

Didital In 1

D1

A1 GND E1 GND 24V GND

+
Input

PE

L1

PE

U1 M 1~
q

U2

TB

TB

Line 1 ~ 230 V 50/60 Hz


1

0...10 V 0...20 mA 4...20 mA TF..(KTY) +


Output
4

1~motor with internal thermostats


2

0...10 V (Imax = 10 mA)


3
PEUN17K2 15.07.2009

332

Analog In 1

Electrical accessories

U2

TB

TB

+
Output

1
Input

Line 1 ~ 230 V 50/60 Hz


1

0...10 V (Imax = 10 mA)


3

1~motor with internal thermostats


2

0...10 V 0...20 mA 4...20 mA TF..(KTY)


5
PEUN16K5 15.07.2009

Wiring RETP 6/10


...6 F1=M10 A / ...10 F1=FF20 A

RETP6/10
Hand/auto 0 100 %

mA

E1

Contact rating max. AC 250 V 5 A

Electrical accessories
5-step-transformer with control input
A three-phase transformer which controls the fan speed by altering the supply voltage in five fixed steps. The steps are adjusted by an external 0..10V control signal or by a potentiometer. Supply voltage +10V. Main switch on the front of the unit. An integral motor protection device is included which cuts the supply voltage to the fan if the thermal contact in the fan motor is activated. The unit is reset by turning the knob to 0 for 10 seconds, after which the unit restarts. Input terminals for on/off cut supply voltage to the fan when the circuit is broken. The indicator lamp on the front shows that the transformer is in operation. The transformer has 230V terminals for operating dampers, electric heater batteries or other external equipment. These terminals have no current when the transformer knob is in position 0, or when the on/off input is open. Max. ambient temp 40C. Dimensions: W 270, H 323, D 163 mm.
Step

RADT

RADT

D1 2*

D1

TB 2*

TB

L1

L2

L3

230VAC max. 1A

Contact rating
SRE5 J1...J4 D 1 2 3 4 5 6

>
1*

N
5 step thermostat

L1 L2 L3 PE
Line
3~ 400V 50/60Hz

Output
+10V (Imax=10mA) J1...J4
10K

Input
0...10V (Ri>100k)
0 1

V M 3~

PE

E 1*

TB TB

Y bzw. or D

Extern desired value

On/off

RDNT07K1 21.06.2006

3~motor with internal thermostat

1* Function change by changing the position of the switch

2* If function is not needed, terminal must be bridged

RADT Voltage Frequency Current Control signal Enclosure Weight Dimensions

2V V 400 3~ Hz 50/60 A 2.0 IP 21 kg 7.6 mm

4V 400 3~ 50/60 4.0 0...10VDC 21 12.5

7V 400 3~ 50/60 7.0 21 18

270x323x163

333

Electrical accessories

Electrical accessories Pulser


Wiring of supply voltage and heater

Electronic heating controller


The Pulser is a single or twophase temperature regulator for controlling heater batteries. This device is connected in series between the mains and an electric heater. The Pulser has an integral regulator with an input terminal for a duct temperature sensor which is located in the supply air duct. The integral sensor can be used when regulating room temperature. The power regulation is completely stepless thanks to what is known as time-proportional control, which means that the relationship between the on and off times is determined by the set temperature requirement. The total on and off time, or pulse period, is approximately 1 minute.

Pulser M

Electronic heating controller


K 1 2 U 3 4 U K G G
The Pulser M is a single or twophase temperature regulator for controlling heater batteries. This device is connected in series between the mains and an electric heater. The Pulser M has an integral regulator with input terminals for a main sensor together with min. or max. limit sensors. The integral sensor can be used when regulating room temperature. The power regulation is completely stepless thanks to what is known as time-proportional control, which means that the relationship between the on and off times is determined by the set temperature requirement. The total on and off time, or pulse period, is approximately 1 minute.

Switch setting for internal set-point and sensor

G G
Switch setting and wiring for internal set-point and external sensor

Electrical accessories

Pulser Voltage Frequency Current Heating power Temp. range of adjustment Temp. reduction at night Ambient temperature Ambient humidity Enclosure WxHxD Weight V 230/400 Hz 50 A 16 W max 3600/6400 C 0...30 C 0...10 C 0...30 %RH 0...90 IP 20 mm 94x150x43 kg 0.3

Pulser M Voltage V 230/400 Hz 50/60 A 16 W max 3600/6400 C 0...30 C 0...10 C 0...30 %RH 0...90 IP 20 mm 94x150x43 kg 0.32 Frequency Current

G G TG-K3xx* TG-G1xx*

Heating power Temp. range of adjustment Temp. reduction at night Ambient temperature Ambient humidity Enclosure WxHxD

Switch setting and wiring for room control using TG-R430 as sensor and set-point

G G

TG-R430 1 3

Weight

Switch setting and wiring using external separate sensor and TG-R430 as set-point

Circuit diagram for supply voltage and adjustment of change-over switch with external sensor. See Pulser. Adjustment of change-over switch with min. limit sensor.

TG-K330

G G

TG-R430 2 3

Wiring of night set-back function

Adjustment of change-over switch with max. limit sensor.


C

*Various temp. ranges available, for example TG-G150 = 20...50C, TG-K370 = 40...70C etc.

334

Electrical accessories TTC


Heating controller
TTC-2000 is a 3-phase triac controller for controlling electric heating up to 25 A. It is made for wall mounting. TTC2000 is to be connected in series between power supply and an electric heater and can control both Y- and Delta- connected loads. TTC-2000 can control assymetrical Deltaloads. Function The controller pulses the entire power output ON/OFF and utilises time-proportional control, the ratio between On-time and Off-time is varied to fit the prevailing heating requirement. E.g. ON = 30 sec and OFF= 30 sec gives 50% output power. The cycle-time (the sum of on-time and off-time) is adjustable 6...120 sec.
TTC Voltage Frequency Current Max heating power Temp. range of adjustment Temp. reduction at night Ambient temperature Enclosure WxHxD Weight V 230/400 3~ Hz 50 A 25 kW 10/17 C 0...30 C 0...10 C 0....40 IP 30 mm 160x207x94 kg 1.8 Voltage supply Control signal Contact Max. heating power *together with TTC-2000 TT-S1 V Suppl. by TTC-2000 Suppl. by TTC-2000 max. 250V/2A kW 34

TTC-2000 automatically adapts control mode to suit the dynamics of the controlled object. Supply air temperature control For rapid temperature changes, TTC-2000 will work as a PI-controller with a fixed proportional band of 20K and a fixed reset time of 6 minutes. Room temperature control For slow temperature changes, TTC-2000 will work as a P-controller with a fixed proportional band of 1.5 K. When running room temperature control the supply air temperature can be maximum and/or minimum limited. Controlling larger electric heaters At larger loads TTC-2000 can be combined with ancillary board TT-S1.

TT-S1

Control board
TT-S1 is a control board for use when you need to control larger loads with a TTC-2000. TT-S1 is used to control a contactor that activates and deactivates a basic heating load. For best function the load connected to TT-S1 should be of equal size to the load connected to the TTC-2000. TT-S1 and TTC-2000 must have separate loads. Easy to install The TTC-2000 is prepared to plug-in the TTS1 module. TTC-2000 detects if a TT-S1 is installed and automatically adapts the control function accordingly. No settings are necessary. Connect in series with the control voltage for the heating load contactor. The supply should be wired via the fan stat, the high temperature limit switch etc. TTC-2000 and TT-S1 must have separate, equal-sized loads.

Electrical accessories

1 2 TT-S1

335

Electrical accessories TT-S4/D


Step switching unit
Step controller for DIN-rail mounting in a cabinet or other enclosure. The controller is intended for controlling electric heating batteries, 4 relay output. The step controller can be set to sequence or binary mode. Can be used together with any controller with 0...10 V output signal. The switch setting on the front of the controller determines the number of steps to be used. The input signal 0...10 V is divided up into the number of steps, thus setting the switch-on point for each step.

Optigo OP 5
Multi purpose controller
Temperature CO2 Pressure Humidity Domestic hot water

Optigo OP 10
Multi purpose controller
Temperature CO2 Pressure Humidity Domestic hot water

Electrical accessories

TT-S4/D Voltage supply Voltage Regulating ratio Working range Enclosure class WxHxD V 24 VAC V Out signal max 250V AC, 2A Outgoing 4 sequence steps 15 binary steps IP 20 mm 101x85x74

Language independent, simple configuration via the backlit display. Input for an external set point device. Optigo 5 is a preprogrammed, configurable controller for DIN-mounting that is intended to control temperature, CO2, pressure, humidity and domestic hot water in HVAC applications. The controller is extremely easy to install and use. It is mainly intended for small applications. Optigo has a knob with an encoder which makes the menu system very easy to use. You can read and set values shown in the back-lit display. A value is approved by pressing the knob. Optigo is suitable for DINrail or cabinet mounting. Since the terminals are detachable all connections can be made before Optigo is installed. Number of inputs/outputs OP5:

TTC25 TTC40F 7
8 9

13 19 21

TT-S4/D

1 analogue input, PT1000 1 SPI input for external set-point device 1 universal input, PT1000 or digital 1 digital input 2 analogue outputs, 0...10V DC
OP5 Voltage Frequency V 24 Hz 50...60 W 3 %RH 90 C 0...50 IP 20 mm 122x120x64 kg 0.215

OP10 has 10 inputs/outputs and can be configured to control temperature (ventilation control with heating and cooling), waterheated radiator heating with outdoor temperature dependent control-curve or domestic hot-water control. The controller is extremely easy to install and use. It is mainly intended for small applications. Optigo has a knob with an encoder which makes the menu system very easy to use. You can read and set values shown in the back-lit display. A value is approved by pressing the knob. Optigo is suitable for DINrail or cabinet mounting. Since the terminals are detachable all connections can be made before Optigo is installed. OP10 is available in two versions, OP10 with 24 V AC supply voltage and OP10-230 with 230 V AC supply voltage. Number of inputs/outputs OP10: AI 2 DI 2 UI 1 AO 2 DO 3
OP10 Voltage Frequency Power Perm. max. amb. humidity Perm. ambient temp. Enclosure class WxHxD Weight V 24 Hz 50...60 W 6 %RH 90 C 0...50 IP 20 mm 122x120x64 kg 0.215 OP10-230 Voltage supply Power consump. Perm. max. amb. humidity Perm. ambient temp. Enclosure class WxHxD Weight V 230V AC W 4 %RH 90 C -40...+50 IP 20 mm 122x120x64 kg 0.215

Fig 1

+ 0 - 10V DC in 0 8 9

TTC25X TTC40FX

13 15 19 21

TT-S4/D

Power Perm. max. amb. humidity Perm. ambient temp. Enclosure class WxHxD Weight

Fig 2

336

Electrical accessories RT 0-30


Room thermostat
The RT 0-30 is an electronic room thermostat for indoor wall mounting, with a change-over relay for regulating either heating or cooling. It has an integral sensor, but an external sensor such as the TG-K330 or TG-R630 can also be connected to the thermostat. The RT 0-30 can also be used with other external temperature sensors to achieve different temperature range.

TM 10

Mechanical thermostat

K-FST1

Mechanical thermostat with change contact to switch fans or for the connection to controllers with thermostat or release connection. The setpoint is at the rotary button from 0 to 40C adjustable.

Frost protection thermostat


Especially suited to ensure the protection of hot water coil heating systems against freezing. The frost protection thermostat models are equipped with two switching outputs that provide the option to act on the system already in advance of the attaining of the corresponding danger point. All devices are fail-safe and dispose of a lead-sealable set value setting facility. In each case, the capillary tubes are active over their entire length. Capillar length: 6.0 M. capillar is active on the whole length. The device responds if the adjusted scale value is attained over a length of approx. 30 cm 60 cm respectively. Specially suited for the measuring of temperatures in non-aggressive gases. The bracing of the capillary tubes in front of the coil heating system can be realised by means of installation clips.

TM 10 Temp. range Ambient temp. Differential Contact Switching capacity Enclosure class Weight WxHxD C 0...40 C -20...+50 1.5K 1 Wechler 250V/max 4A 54 IP kg 0.35 mm 86 (+27)x126x58 (+13)

RT 0-30 Voltage Phase Frequency Temp. range of adjustment Enclosure class Power consumption Perm. ambient temp. Perm. max. ambient humidity Circuit-breaking relay WxHxD V 230 ~ 1 Hz 50/60 C 0...30 IP 30 W 1 C 0...50 %RH 90 A 16, 250 VAC mm 86x86x30

Electrical accessories

K-FST1 Sensor Contact Curcuit-breaking Temp. range of adjustm. 1 change-over A 15(8)A, 24-250V~ C -10...+12 C 200 C -10...+55 IP 40 mm 112x105x55

3 2 1
Cooling Heating
L N PE

Max. temp. of transp. air Ambient temperature Enclosure class WxHxD

1 = Red 2 = White 4 = Blue

External sensor

External sensor Internal sensor

337

Electrical accessories TG-R600/630


External sensor
For sensor measurement in applications where a sensor with a higher enclosure rating is required. To be used with the TTC 2000, Pulser or RT 0-30.
TG-R600 Temp. of adjustment Enclosure class WxHxD C -30...+30 IP 65 TG-R630 0...30 65 Length Temp. range of adjustment Enclosure

TG-A 130
Surface sensor
Surface sensor TG-A 130 to be used together with AQUA 24TF when frost protection or shut down function is required. Cannot be used together with the PULSER series.
TG-A130 mm 1500 C 0...30 IP IP 65

U-EK 230E EX

Thermistor motor protection


The U-EK 230E is a thermistor motor protection device which is intended for use in conjunction with a contactor for the protection of the Ex fans in the DKEX, KTEX and TFDX series. This is an electronic unit designed for snap fitting on to a 35 mm instrument rail. Fan motors have six series-connected thermistors, two per phase winding, whose resistance is determined by the motor temperature. When the motor temperature exceeds the permitted limit, the resistance rises sharply and the motor protector is triggered. When the motor protector has been triggered, the warning light marked Strung (Fault) is illuminated. The device is reset manually, either by pressing the Reset button, or by interrupting the voltage supply to the motor protector (stopping supply to A2) for approximately 10 seconds. If a five-step transformer is used for regulating EX fans, the U-EK 230E should be connected to the transformer. A casing is available as an accessory. Do not place the U-EK 230E in the EX zone!

mm 85x90x35 85x90x35

Electrical accessories

TG-K330
Duct sensor
Duct sensor which is mounted inside the duct, with a sensor diameter of 9 mm, a circular flange 40 mm and adjustable length from 15 to 130 mm. The connecting cable is 1.5 m. To be used with the TTC, Pulser or RT 0-30.
TG-K Temp. range Enclosure 330 C 0...30 IP 20 350 20...50 20 360 0...60 20

TG-R4/R5/ PT1000
Room sensor
Room sensor with setpoint. For measuring room temperature, -R4 with setpoint adjustment, -R5 without setpoint adjustment.
TG-R4/PT1000 Temperature range Control signal Enclosure class WxHxD C 0...50 PT1000 IP 30 mm 86x86x30

U-EK 230E EX

TG-KH/ PT1000 TG-R430/530


Room sensor for wall mounting
TG-R430 room sensor with adjustment of desired value. The dial can be locked with a screw which is concealed behind the cover. The TG-R530 is a room sensor for measuring the room temperature. To be used with the TTC, Pulser or RT 0-30.
TG-R Temp. range of adjustment C Enclosure class WxHxD IP 430/530 0...30 30

Voltage Frequency Max. current Switching capacity Ambient temperature Enclosure class Weight WxHxD

V 230 Hz 50 A 6 250V AC/3A C -20...+50 IP 20 kg 0,1 mm 35x116x58

Duct sensor

Duct sensor for measuring air temperature in ventilation ducts.


TG-KH/PT1000 Temperature range Time constant Insert length Enclosure class C -30 +70C 16 s mm 60...205 IP 65

mm 86x86x30

TG-UH/PT1000
Outdoor sensor
For measuring outdoor temperature.

TG-UH/PT1000 Temperature range Enclosure class WxHxD C -40...+60 IP 65 mm 70x93x46

338

Electrical accessories EX connection box MicroREX D21


Time switch
The MicroREX D21 is a digital 7 day time switch with a circular segmented display for general rail mounting use or on walls in a box, included. Up to 8 program pictures can be set. A program picture incorporates both ON and OFF time. If no button is pressed for 60 seconds during programing the time switch goes back to the start position. The copying function enables program to be copied to other days. Minimum switching time is 1 minute. The switching times are protected but can be overlaid by other programs. Programs are displayed with a minimum segment size of 30 minutes. The time and the week days are presented digitally. The summer-/winter changeover can be programmed for hand or automatic operation.
MicroREX Voltage Frequency Max. current load Accuracy WxHxD V 230 Hz 50/60 A 16 1s/day mm 36x83x66

T 120
Timer
Timer with 120-minute operating time. Supplied with flange for fitting into equipment housing. Casing for surface mounting is available Frame for as an extra. A switch wallmounting for closing and breaking circuits. A link can be used to produce a change-over function. The timer makes a quiet ticking sound when connected. This timer is suitable for controlling the REU and RTRDU five step transformers.

The EX-connection box is of dark grey, glass fibre polyester resin and will be delivered with 2 cable connections and 1 stopping plug in Ex-execution. There are 8 clamps in the connection box.
EX connection box Explosion proof Certificate Voltage Max. current Enclosure, motor WxHxD Ambient temperature Ex II 2G EX e II T6 PTB 99 ATEX 3103 V 690 A 32 IP 66 mm 115x115x64 C -50...+55

T 120 Voltage Frequency Max. current load Connection time WxHxD V 230 Hz 50 A 10 (2) min 0...120 mm 80x80x25

Electrical accessories

RVAZ4-24 RVAZ4-24A
Valve actuator
RVAZ4 24A is a valve actuator for 0...10 V DC control signal. 24 V AC supply voltage. Suitable for controlling ZTV/ZTR valves, kvs <= 6,0. This product conforms with the EMC requirements of European harmonised standards EN60730-1:2000 and EN60730-28:2002 and carries the CE mark.

RVAZ4-24/24A Voltage supply Power consumption Frequency Max. stroke Full stroke time Stem force Max. ambient humidity Ambient temperature Enclosure class V 24 V AC +/- 15% max 6 W Hz 50/60 mm 5.5 121 sec Nm 400 %RH 95 C 0...50 IP 44

Trafo 15/D

Transformer 230/24
The transformer mounted in a 3-module casing for DIN-mounting in a cabinet or other tight enclosure.
Trafo 15/D Voltage supply Voltage output Enclosure class Power output WxHxD V 230 AC V 24 AC IP 20 VA 15 mm 53x85x74

339

Electrical accessories REV


ON-OFF f. EMC inl.
REV- Isolator mounted on a bracket, leads connected l max 16 A. -3POL/03 3-pole (closing/auxillary contact 1) lead 3x1.5 mm2 for 1 phase motor TK not lead out. -5POL/05 5-pole (closing/auxillary contact 1) lead 5x1.5 mm2 for 1 phase motors TK lead out and 3 phase motors TK not lead out. -5POL/07 5-pole (closing/auxillary contact 1) lead 7x1.5 mm2 for 3 phase motors TK lead out. -9POL/12 9-pole (closing/auxillary contact 1) lead 12x1.5 mm for 3 phase motors TK lead out and two speed (D/Y ).

S-DT2 SKT S-DT2 DKT S-DT2 GKT


2 speed switch
Switching and protecting unit star/triangle. For changing speed of three phase motors with 2 speed by star/delta switching. Automatic cut out of motor when thermal contact trip (overheating of motor). Reset by setting the main switch to 0 and restart. Plastic casing for surface mounting, assembly without casing is possible on a mounting rail.
S-DT2 Voltage Phase Max. power load Connection Enclosure class WxHxD mm SKT V 400 ~ 3 kW 4 Y/D IP 54 DKT 400 3 4 Y/YY 54 GKT 400 3 4 Y/Y 54

S5S 100T1 S5S 100T3


5-step switch
5-step switch for transformer TES. Imax=10A. To mount in a front door of a switch board. Contacts: 5 steps NO 1 auxiliary contact NO 1 auxiliary contact NO (impulse)
S5S 100 Voltage Phase Max. current Width Height Depth Weight T1 V 230 ~ 1 A 10 mm 48 mm 48 mm 103 kg 0.15 T3 400 3 10 48 48 128 0.15

Electrical accessories

166x230x129

S5S 100T1

EMC KIT REV


3-POL/5-POL
The EMC-KIT is an accessory for the REVswitch. The EMC-KIT fitts in the casing of our REV-switch (3Pol/3, 5Pol/5, 5Pol/7). Due to IE2/ecodesign directive the use of frequency converters will increase. For frequency converters without all pole sine filter a shielded connection is needed. We recommend to order the EMC-KIT mounted.

S2S 160

Two speed switch


This two speed switch is available with casing for surface mounting: 1~change between two speeds with changing the different windings (auxiliary and main windings). Casing, plastic. Note only for motors with wiring diagram no 20.
S2S 160 Voltage Current Enclosure class V 1-230 A 10 IP 54

S5S 100T3

REV DVV

ON-OFF service switch

For fans DVV/F400, F600 and DVV/120. Available on request for sizes 400 to 630 (serial at sizes 800 and 1000). The REV DVV is mounted outside on the cooling duct placed instead of terminal box outside on the cooling duct (DVV/F), while with DVV/120 it is mounted on the casing. Service switch is 8 pole with 1 x NC and 1 x NO. Locking in OFF position possible (lock not supplied). Connection of max. 7x2.5 mm2 silicon cable on the switch is possible. Equipped with cable gland max. M25x1.5, size depending on cable from electric motor to service switch. If electric motor ordered with PTC or thermal relay, service switch is supplied with additional cable gland M16x1.5.

340

Electrical accessories AQUA 24TF


Temperature controller
AQUA 24TF with room or supply air temperature control. The AQUA 24TF controls three-point actuators with a puls-pause signal where the ratio between on-time and off-time is proportional to the temperature offset. The controller has built-in sensor, external sensor can be connected. Use surface sensor TG-A 130 when frost protection or shut-down function is required. AQUA 24TF is suitable for control of valve actuator RVAZ4 24. Cascade factor (CF) must be set to 1 for single sensor control. Minimum limit (Min) not active in single sensor control.
Parameter Voltage supply Frequency Power consumption Permitted range for ambient temperature Permitted relative humidity, non condensating Temperature range of adjustment Cascade factor (CF) Enclosure class Weight WxHxD Unit Value V 24V AC +/-10% Hz 50/60 Max 5 VA C 0...50 % 90 C 0...30 1...15 IP 20 kg 0.25 mm 92x150x45

MTV 1/010
Controller
Speed controller with 0-10V input. Combined flush or surface mounting. For the manual control of speed and air flow of electrical fans with 0-10V input. The jetproof IP 54 enclosure is achieved with the included surface mounting case. (Flush-mounting without the surface mounting case, gives a splash proof IP 44 enclosure).

S-ET 10, S-ET 10E

Motor protection, 1~
The S-ET 10 (for wall mounting) and S-ET 10E (for rail mounting) switches off the supply voltage to the motor when the thermal contact in the motor windings is tripped. The motor protector is connected to a 230V supply and also to the thermal contact in the motor. The motor protector is reset by pressing the black button as soon as the motor windings have cooled sufficiently. The motor protector can also be used in conjunction with a transformer. The S-ET has an alarm contact as an accessory. The alarm contact has a built-in potentialfree contact for an external signal to indicate when the contact relay has been tripped.

MTV 1/010 Voltage supply Output 0-10 V, Imax Enclosure class Weight Colour V 230 V mA 8 IP 44 kg 0.2 white

Electrical accessories

S-ET Voltage Current range Rec. fuse Ambient temp. Enclosure class Weight Width Height Depth

10 V 60...250 A 0,4...10 A 25 C -25...+55 IP 55 kg 0.45 mm 79 mm 141 mm 80

10E 60...250 0,4...10 25 -25...+55 20 0.2 63 80 76

MTP 10
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 Alarm relay 1 2 A 240 V AC Alarm relay 2 2 A 24 V AC Sensor neutral Main sensor Sensor neutral Limiting sensor Sensor neutral Frost protection sensor Night setback Supply voltage 24 V AC System neutral Run mode indication Run mode indication Actuator, Common pole Actuator, Increase heat Actuator, Reduce heat

Controller

Potentiometer 10k. Combined flush or surface mounting. For the manual control of speed and air flow of electrical fans with 0-10V output. The jetproof IP 54 enclosure is achieved with the included surface mounting case. (Flush-mounting without the surface mounting case, gives a splash proof IP 44 enclosure). NB! EC only.
MTP 10 Voltage supply Control signal Working range Contact Switching capacity Enclosure class Weight V DC 10 k 0...10 V 0...10 1 NO 4A/250V IP 44 kg 0.2

Alarm contact must be ordered seperately!

1~ 60V...250V 50/60Hz
L N PE

max. 25A

S -E T 1 0 E
1 5

ZB *
24 12

ZK(2S) *
24 14

I> 2 4 6 23 11 23 13

TB

TB

U1 U2 M 1~

PE

Us 1 2 3

+ 4

Us = 0-10V + = 10V Supply Output signal - = GND

341

Electrical accessories STDT 16, STDT 16E MSEX


Motor protection
Protective motor switch intended for use in conjunction with EX 140 and EX 180 fans. The motor protector is set to the rated current of the connected fan. The motor protector is mounted on a rail, 356 mm wide. An MSEX-H auxiliary contact for the motor protector can be supplied, with an opening and closing switch. This auxiliary contact is fitted on to the front of the motor switch. Enclosure MSEX-K is available as an accessory. This will fit both with and without an auxiliary contact. The enclosure is for surface mounting. Two output apertures at the top and bottom. The MSEX must not be placed in the EX zone!

AWE-SK

Motor protection
Thermal contact motor protection device for placing on a control panel. The AWE-SK is connected to the motor relay control circuit.

Motor protection, 3~
The STDT 16 (for wall mounting) and the STDT 16E (for rail mounting) and switches off the supply voltage to the motor when the thermal contact in the motor windings is tripped. The motor protector is connected to a 400V supply and also to the thermal contact in the motor. The motor protector is reset by pressing the black button as soon as the motor windings have cooled sufficiently. The motor protector can also be used in conjunction with a transformer. An alarm contact (K) is available as an accessory. The alarm contact has an integral potential-free contact producing an external signal when the relay has been tripped.
STDT Voltage Phase Current range Rec. fuse Ambient temp. Enclosure class Weight Width Height Depth 16 V 60...400 ~ 3 A 10...16 A 80 C -25...+40 IP 55 kg 0.6 mm 80 mm 150 mm 98 16E 60...400 3 10...16 80 -25...+40 20 0.35 54 80 76

Electrical accessories

Function If the thermal contact in the motor is tripped, the AWE-SK contact relay breaks the control circuit connecting with the motor, the warning light illuminates and the fan stops. The motor will still be without current after the thermal contact in the motor is closed. The motor protector is reset by pressing the red button marked Reset on the front panel, or by closing an external contact connected to the Reset connection block. The AWE-SK does not trip in the event of a mains power supply interruption. The 14-11 connection block provides a potential-free alarm contact producing an external signal when the relay is tripped.

MSEX Max. power load Adjustm. range Ambient temp. Enclosure MSEX Max. power load Adjustm. range Ambient temp. Enclosure MSEX Max. power load Adjustm. range

0.25-0.4 kW 0,09 A 0.25...0,4 C -25...+55 IP 20 0.63-1.0 0.25 0.63-1.0 -25...+55 20 2.5-4.0 0.9 2.54 -25...+55 20

0.4-0.63 0.12 0.40.63 -25...+55 20 1.0-1.6 0.57 1.01.6 -25...+55 20 Voltage Recommended fuse Max. current Ambient temperature Enclosure class Weight WxHxD

AWE-SK V 0...230 A 4.0 A 2.0 C 0...40 IP 20 kg 0.15 mm 48x96x42

Alarm contact must be ordered seperately!

Ambient temp. Enclosure

Single phase

Alarm contact

Three phase
Fan

342

Electrical accessories HR1 TFR


Room humidistat
A humidistat for controlling exhaust air fans in response to the relative humidity. The humidistat uses human hair as the humidity sensor medium. The set-point can be anywhere between 10 and 95% RH. Base plate in black plastic and cover in white plastic. The HR1 is supplied with a sliding cover over the set-point dial, which can be locked. The humidistat should be mounted in a location with good air circulation and constant temperature and humidity. It should not be fitted on external walls, walls in direct sunlight, corners etc. The humidistats mounting holes make it suitable for fixing on to a terminal box with screws at 60 mm centres. The humidistat should be precision-calibrated after it has been mounted, and should be recalibrated regularly. Dust and other matter should be removed with a soft brush at regular intervals. Contacts 1 and 3 close when the air humidity exceeds the preset value.

Room temperature sensor


With PTC element. With over-voltage protection (R20C ca 1.9 k). The PTC element is supplied loose in the housing. The element is fitted in one of the cable conduits.
TFR Temp. range of adjustment Resistance at +20C Enclosure class WxHxD C -20...+60 1900 IP 54 mm 75x75x37

IR24-P

Presence detector
A detector that gives a signal when someone is present in the room under supervision. The detector has a pulse detecting function that minimizes the risk for false alarm. Settable output on/ off delay. Intended for wall or ceiling mounting. IR24-P is a presence detector designed for automatic ventilation control of HVAC systems.
IR24-P Voltage supply Ambient temperature Max. ambient humidity Enclosure class Circuit-breaking relay Switching capacity Dimensions V 24 V AC/DC C -20...+50 %RH 95 IP 40 A NC/NO 24V DC/0,2A mm 112x66x45

Electrical accessories

HR1 Setpoint Differential Switching capacity Max. operating temp. Enclosure class Weight WxHxD %RH 10...95 %RH 4% at 45 250V/5A C 40 IP 21 kg 0.1 mm 83x136x37

DTV

Pressure switch
Differential pressure switch for air and non-corrosive gasses.Relay contact data 250 V AC 5 A, change-over.

DTV Pressure range Media Air temperature Switch. diff. press. Max. current load Enclosure class WxHxD

200 Pa 20...300 Clean air C -20...+85 Pa 15Pa +/-5 IP 54

500 50500 Clean air -20...+85 25Pa +/-8 54

A 250V, 5A (0.8A) mm 88x81x60 88x81x60

DTV 1 2 3

343

Electrical accessories SM 230A


Actuator
The damper motor is made for the adjustment of dampers. The motor is for round and square shafts 10...20 mm. 1-wire-control (open/close) or 3-point-control. Direction of rotation reversible. Manual override with push-button. The max. torque is 20Nm for dampers up to 4 m2 and a max. angle of rotation of 95 with adjustable mechanical limitation.
SM 230A Voltage Frequency Power consumption Enclosure class V 100...240 Hz 50/60 W 2,5 IP 54 s 150 % -30...+50 kg 1.05 Voltage Frequency Power consump. Torque Full stroke time Enclosure class Ambient temp. Weight
0

Damper actuator

SF 230A SF 24A SF 24A-SR SF 24A-S2

SF 230A, SF 24A

For air dampers up to approx. 4 m2 Torque 20 Nm Nominal voltage AC 230 V Control: Open-close Spring return actuator with emergency function for adjusting air dampers in ventilation and air conditioning systems in buildings.

1 = black 2 = red

SF 24A-SR
+

Electrical accessories

Full stroke time Perm. rel. humidity, non condens. Weight

SF 230A V 230 Hz 50/60 W 6.5 Nm 20 75s/20s IP 54 C -30...+50 kg 2.1 SF24A-SR

SF 24A 24 50/60 5 20 75s/20s 54 -30...+50 2.1 SF24A-S2 24 50/60 5 20 75s/20s 54 -30...+50 2.3
1 2

L1

L1

3 0 1

2 0 1

Voltage Frequency Power consump. Torque Full stroke time Enclosure class Ambient temp. Weight

V 24 Hz 50/60 W 5 Nm 20 150s/20s IP 54 C -30...+50 kg 2.1

SF 230A, SF 24A
+

344

~
Y U Y 1 DC 0 10 V U DC 2 10 V 2 3 5
1 = black 2 = red 3 = white 5 = orange 1 = black 2 = red S1 = violet S2 = red S3 = white S4 = orange S5 = pink S6 = grey
S1 S2 S3 S4 S5 S6
A = 10% <A >A <B >B B = 10 ... 90%

Electrical accessories

Electrical accessories

345

Accessories

Flanges Anti-vibration mounts

Coolers

Accessories

Roof sockets Flexible connections Silencers

Mounting clamps/feet

Others Shutters, dampers

Grilles, louvres, guards

Filter boxes

Heaters

Roofs

346

Accessories Contents
Flanges
ASF . . . . . . . . . . . . . . . . . . . . . . . . . . . 375 ASFV . . . . . . . . . . . . . . . . . . . . . . . . . . 384 GFL . . . . . . . . . . . . . . . . . . . . . . . . . . . 364 GFL-AR/AXC . . . . . . . . . . . . . . . . . . . . 389 GFL-AR/AXCBF. . . . . . . . . . . . . . . . . . 389 IS/US. . . . . . . . . . . . . . . . . . . . . . . . . . 371 STG . . . . . . . . . . . . . . . . . . . . . . . . . . . 372 TDA DV . . . . . . . . . . . . . . . . . . . . . . . . 371 TUB/TUS. . . . . . . . . . . . . . . . . . . . . . . 372

Filter boxes
FFK . . . . . . . . . . . . . . . . . . . . . . . . . . . . 357 FFR . . . . . . . . . . . . . . . . . . . . . . . . . . . 349 FFS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 368 FGR. . . . . . . . . . . . . . . . . . . . . . . . . . . 348

Coolers
CWK . . . . . . . . . . . . . . . . . . . . . . . . . . . 354 DXRE. . . . . . . . . . . . . . . . . . . . . . . . . . 362 PGK. . . . . . . . . . . . . . . . . . . . . . . . . . . 360

Anti-vibration mounts
FSD . . . . . . . . . . . . . . . . . . . . . . . . . . . 386 SD . . . . . . . . . . . . . . . . . . . . . . . . . . . . 385 ZSD . . . . . . . . . . . . . . . . . . . . . . . . . . . 386

Roof sockets
FDG/F . . . . . . . . . . . . . . . . . . . . . . . . . 377 FDS . . . . . . . . . . . . . . . . . . . . . . . . . . . 374 FDGE/F . . . . . . . . . . . . . . . . . . . . . . . . 378 FDVE, FDVE/F. . . . . . . . . . . . . . . . . . . 382 FDV, FDV/F . . . . . . . . . . . . . . . . . . . . . 381 TG . . . . . . . . . . . . . . . . . . . . . . . . . . . . 373 TG 300-800, 400-800. . . . . . . . . . . . 372 THB. . . . . . . . . . . . . . . . . . . . . . . . . . . 373 THS . . . . . . . . . . . . . . . . . . . . . . . . . . . 373 TOB. . . . . . . . . . . . . . . . . . . . . . . . . . . 372 TOS . . . . . . . . . . . . . . . . . . . . . . . . . . . 372

Flexible connections
ASF/KB . . . . . . . . . . . . . . . . . . . . . . . . 371 ASS . . . . . . . . . . . . . . . . . . . . . . . . . . . 381 ASS-P . . . . . . . . . . . . . . . . . . . . . . . . . 380 ASSG/F . . . . . . . . . . . . . . . . . . . . . . . . 383 ASSV, ASSV/F, ASSV-EX . . . . . . . . . . . 383 CCM inlet comm. . . . . . . . . . . . . . . . . 375 CCM cirkular comm. outlet . . . . . . . . 375 CCMI comm. isolated outlet . . . . . . . . 375 DSK . . . . . . . . . . . . . . . . . . . . . . . . . . . 370 DS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 363 DS-EX . . . . . . . . . . . . . . . . . . . . . . . . . 363 EPSN/EPIN . . . . . . . . . . . . . . . . . . . . . 389 EV-AR/AXC, EV-EX/AXC. . . . . . . . . . . 387 EVH . . . . . . . . . . . . . . . . . . . . . . . . . . . 388 FGV . . . . . . . . . . . . . . . . . . . . . . . . . . . 370 ISE/USE. . . . . . . . . . . . . . . . . . . . . . . . 371 UGS. . . . . . . . . . . . . . . . . . . . . . . . . . . 370

Silencers
HSDV. . . . . . . . . . . . . . . . . . . . . . . . . . 379 LDC . . . . . . . . . . . . . . . . . . . . . . . . . . . 348 LDK . . . . . . . . . . . . . . . . . . . . . . . . . . . 365 LDR . . . . . . . . . . . . . . . . . . . . . . . . . . . 358 RSA (F). . . . . . . . . . . . . . . . . . . . . . . . 384 SSD . . . . . . . . . . . . . . . . . . . . . . . . . . . 374 SSG/F. . . . . . . . . . . . . . . . . . . . . . . . . .378 SSVE/SSVE-F. . . . . . . . . . . . . . . . . . . . 377 SSV, SSV/F. . . . . . . . . . . . . . . . . . . . . . 382 SSGE/F . . . . . . . . . . . . . . . . . . . . . . . . 379

Mounting clamps/feet
FK . . . . . . . . . . . . . . . . . . . . . . . . . . . . 355 FKX . . . . . . . . . . . . . . . . . . . . . . . . . . . 355 MFA-AR/AXC . . . . . . . . . . . . . . . . . . . . 386 MFA-AXCBF . . . . . . . . . . . . . . . . . . . . . 388 MP. . . . . . . . . . . . . . . . . . . . . . . . . . . . 387 WBK . . . . . . . . . . . . . . . . . . . . . . . . . . . 389 WBK-W . . . . . . . . . . . . . . . . . . . . . . . . 389

Accessories

Others
ALS-KBT . . . . . . . . . . . . . . . . . . . . . . . 371 ASK, ASK/F, ASG/F. . . . . . . . . . . . . . . 380 BVK. . . . . . . . . . . . . . . . . . . . . . . . . . . 390 Cable gland set . . . . . . . . . . . . . . . . . . 386 ESDV. . . . . . . . . . . . . . . . . . . . . . . . . . 384 ESD-F . . . . . . . . . . . . . . . . . . . . . . . . . . 388 FSL. . . . . . . . . . . . . . . . . . . . . . . . . . . . 379 FTG . . . . . . . . . . . . . . . . . . . . . . . . . . . 371 IN. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 390 LGV/LGH. . . . . . . . . . . . . . . . . . . . . . . 376 RED. . . . . . . . . . . . . . . . . . . . . . . . . . . 364 SN. . . . . . . . . . . . . . . . . . . . . . . . . . . . 390 ZHZ . . . . . . . . . . . . . . . . . . . . . . . . . . . 389 ZTV/ZTR . . . . . . . . . . . . . . . . . . . . . . . 390

Grilles, louvres, guards


IGC. . . . . . . . . . . . . . . . . . . . . . . . . . . . 356 IGK. . . . . . . . . . . . . . . . . . . . . . . . . . . . 357 ORH. . . . . . . . . . . . . . . . . . . . . . . . . . . 357 SDM. . . . . . . . . . . . . . . . . . . . . . . . . . . 369 SG . . . . . . . . . . . . . . . . . . . . . . . . . . . . 357 SG AR/AXC, SG-AW . . . . . . . . . . . . . . 385 SG AW-D. . . . . . . . . . . . . . . . . . . . . . . 386 WSG . . . . . . . . . . . . . . . . . . . . . . . . . . . 370

Shutters, dampers
BDS . . . . . . . . . . . . . . . . . . . . . . . . . . . 390 BTG . . . . . . . . . . . . . . . . . . . . . . . . . . . 374 EFD, circular . . . . . . . . . . . . . . . . . . . . 355 EFD, rectangular. . . . . . . . . . . . . . . . . 363 LRK(F). . . . . . . . . . . . . . . . . . . . . . . . . 385 RSK . . . . . . . . . . . . . . . . . . . . . . . . . . . 355 SRK . . . . . . . . . . . . . . . . . . . . . . . . . . . 364 SRKG . . . . . . . . . . . . . . . . . . . . . . . . . . 370 VK, square . . . . . . . . . . . . . . . . . . . . . 356 VK, rectangular . . . . . . . . . . . . . . . . . . 368 VKV/F, VKVE/F, VKG/F. . . . . . . . . . . . 383 VKK . . . . . . . . . . . . . . . . . . . . . . . . . . . 356 VKS, VKM, VKS-EX, VKSV-EX . . . . . . 380 VKVM . . . . . . . . . . . . . . . . . . . . . . . . . 384

Roofs
WSD . . . . . . . . . . . . . . . . . . . . . . . . . . . 370 WSD-KBT . . . . . . . . . . . . . . . . . . . . . . . 371

Heaters
CB . . . . . . . . . . . . . . . . . . . . . . . . . . . . 350 CBM. . . . . . . . . . . . . . . . . . . . . . . . . . . 351 RB. . . . . . . . . . . . . . . . . . . . . . . . . . . . 359 RBK. . . . . . . . . . . . . . . . . . . . . . . . . . . 368 RBM . . . . . . . . . . . . . . . . . . . . . . . . . . . 360 VBC. . . . . . . . . . . . . . . . . . . . . . . . . . . 352 VBF . . . . . . . . . . . . . . . . . . . . . . . . . . . 353 VBK. . . . . . . . . . . . . . . . . . . . . . . . . . . 367 VBR. . . . . . . . . . . . . . . . . . . . . . . . . . . 365

347

Accessories LDC
Silencer Filter cassette for circular ducts
The FGR filter cassette is fitted with a standard type G3 panel filter. The cassette housing is manufactured from galvanised sheet steel with rubber-sealed circular connections, toggle locks and disposable filters. Replacement PFR filters are sold in packs of five. The filter cassette is suitable for use as a supply-air filter in industrial workshops. The recommended final pressure drop is 170 Pa for the G3 filter.

FGR

Easily-fitted silencer for circular ducts, fitted with a connection that complies with the spiral duct standard. The LDC effectively reduces noise in the duct. Two silencers can be used together in installations where noise reduction is critical. For the most effective noise reduction, the silencer should be fitted immediately behind a fan or bend. The silencer should be used together with an insulated fan where there is a requirement for noise reduction both in the duct and in the surroundings as a whole. Insulation thickness 50 mm.

G3

Free area for filter change

G3

d0 di
LDC 100-300 100-600 100-900 100-1200 125-600 125-900 125-1200 150-600 160-600 160-900 200-600 200-900 250-600 250-900 315-600 315-900 355-900 400-900

L nom d1 300 600 900 1200 600 900 1200 600 600 900 600 900 600 900 600 900 900 900 100 100 100 100 125 125 125 150 160 160 200 200 250 250 315 315 355 400

d0 200 200 200 200 224 224 224 250 260 260 300 300 355 355 415 415 560 600

l 360 660 960 665 965 600 670 970 685 985 600 900 600 900 900 900

kg 2.28 4.09 5.18 4.39 6.2 5.37 5.37 7.48 6.9 9.74 8.55 11.7 11.8 16.3 25.2 24.3 Filter mounting

Accessories

1260 6.46

1265 7.47 FGR 100 125 150 160 200 250 315 355 400 100 125 150 160 200 250 315 355 400 A 123 123 123 123 123 123 123 123 123 B 199 199 199 199 199 239 239 239 259 C 205 205 205 205 302 302 350 454 454 D 201 201 201 201 297 297 345 450 450 E 190 190 190 190 280 280 330 435 435

Noise suppression dB (mid-frequency Hz) LDC 63 125 250 500 1k 2k 4k 100-300 2 2 6 14 21 25 20 100-600 4 100-900 5 100-1200 6 125-600 125-900 3 4 3 4 5 3 4 5 3 3 4 3 4 2 4 2 3 3 3 11 15 19 9 12 15 7 7 10 7 8 7 8 6 7 6 5 24 34 45 23 33 43 20 19 28 16 24 13 20 11 16 13 10 36 50 50 30 45 50 27 27 42 21 32 17 26 14 22 18 13 49 50 50 40 50 50 31 29 43 23 34 16 23 9 12 10 7 34 48 50 22 30 38 16 14 20 9 13 8 10 4 6 6 5

8k 11 17 23 29 14 17 21 11 11 15 8 10 6 8 5 7 7 6 Filter cassette FGR 100 FGR 125 FGR 150 FGR 160 FGR 200 FGR 250 FGR 315 FGR 355 FGR 400 Panel filter (incl. in FGR) PFR 100-160 PFR 100-160 PFR 100-160 PFR 100-160 PFR 200 PFR 250 PFR 315 PFR 355 PFR 400 Filter media G3 G3 G3 G3 G3 G3 G3 G3 G3

125-1200 5 150-600 160-600 160-900 200-600 200-900 250-600 250-900 315-600 315-900 355-900 400-900 2 2 2 2 3 3 0 1 1

348

Accessories
Filter cassette for circular ducts
The FFR filter cassette is designed for bag filters of the G3, F5 or F7 standard filter types. The cassette is manufactured from galvanised sheet steel with rubber-sealed circular connections and locks with toggle fasteners. The cassette is fitted with connections for connecting to a pressure sensor. The filters for FFR are BFR bag filters. Available in various filter classes and are ordered separately and supplied individually. The recommended final pressure drop is 170 Pa for the G3 filter, 200 Pa for the F5 filter and 250 Pa for the F7 filter.
Free area for filter change
B D

FFR

A 100 125 150 160 200 250 315 355 400

B 200 200 200 200 245 295 345 445 445

C 203 203 203 203 248 298 348 448 448 Bag filter

D 522 522 522 522 530 584 634 780 782

E 450 450 450 450 450 500 550 650 650 Filter media G3, F5, F7 G3, F5, F7 G3, F5, F8 G3, F5, F9 G3, F5, F10 G3, F5, F11 G3, F5, F12 G3, F5, F13 G3, F5, F14

Accessories

Filter cassette FFR 100 FFR 125 FFR 150 FFR 160 FFR 200 FFR 250 FFR 315 FFR 355 FFR 400

BFR 100-160 BFR 100-160 BFR 100-160 BFR 100-160 BFR 200 BFR 250 BFR 315 BFR 355 BFR 400

A B
Dimensions for filter classes G3/F5/F7 in mm: BFR A B No. of filter bags 2/2/3 2/2/3 2/2/4 3/3/6 3/3/6

100-160 187/187/188 250/250/235 200 250 315 315 400 232/232/233 250/250/235 282/282/283 300/300/285 432/432/433 450/450/420 432/432/433 450/450/420

232/232/233 350/350/330 3/3/5

349

Accessories CB
CB Connection mm Power [kW] Voltage [V] Current [A] Min. airflow [m3/h] Weight [kg] Controlled by Wiring diagram CB Connection mm Power [kW] Voltage [V] Current [A] Min. airflow [m3/h] Weight [kg] Controlled by Wiring diagram CB Connection mm Power [kW] Voltage [V] Current [A] Min. airflow [m3/h] Weight [kg] Controlled by Wiring diagram 100-0.4 100 0.4 230 1~ 1.7 45 2 Pulser CB-1 150-5.0 150 5.0 400 2~ 12.5 100 3.8 Pulser CB-2 250-3.0 250 3.0 230 1~ 13 280 4.8 Pulser CB-1 355-9.0 355 9 400 3~ 13 550 8.2 TTC CB-3 100-0.6 100 0.6 230 1~ 2.6 45 2 Pulser CB-1 160-1.2 160 1.2 230 1~ 5.2 115 3 Pulser CB-1 250-6.0 250 6 400 2~ 16 280 5.2 Pulser CB-2 355-12.0 355 12 400 3~ 17.3 550 8.5 TTC CB-4 125-0.6 125 0.6 230 1~ 2.6 70 2.5 Pulser CB-1 160-2.1 160 2.1 230 1~ 9.1 115 3.2 Pulser CB-1 250-9.0 250 9 400 3~ 13 280 6.2 TTC CB-3 400-6.0 400 6 400 2~ 15 700 8 Pulser CB-2 125-1.2 125 1.2 230 1~ 5.2 70 2.5 Pulser CB-1 160-2.7 160 2.7 230 1~ 11.7 115 3.5 Pulser CB-1 315-3.0 315 3 230 1~ 13 430 6 Pulser CB-1 400-9.0 400 9 400 3~ 13 700 8.5 TTC CB-3 125-1.8 125 1.8 230 1~ 7.8 65 2.5 Pulser CB-1 160-5.0 160 5.0 400 2~ 12.5 115 4.0 Pulser CB-2 315-6.0 315 6 400 2~ 15 430 6.3 Pulser CB-2 400-12.0 400 12 400 3~ 17.3 700 9.2 TTC CB-4 150-1.2 150 1.2 230 1~ 5.2 100 2.5 Pulser CB-1 200-2.1 200 2.1 230 1~ 9.1 180 3.9 Pulser CB-1 315-9.0 315 9 400 3~ 13 430 7.3 TTC CB-3 150-2.1 150 2.1 230 1~ 9.1 100 3.2 Pulser CB-1 200-3.0 200 3.0 230 1~ 13 180 4.0 Pulser CB-1 315-12.0 315 12 400 3~ 17.3 430 7.6 TTC CB-4 150-2.7 150 2.7 230 1~ 11.7 100 3.0 Pulser CB-1 200-5.0 200 5.0 400 2~ 12.5 180 4.5 Pulser CB-2 355-6.0 355 6 400 2~ 15 550 7 Pulser CB-2

Electrical duct heater

Duct heater with spigot connection for standard spiral ducts. Manufactured from alu-zinc coated sheet steel with a heating element in stainless steel. The heater has integral overheating protection with a manual reset function. The CB heater has rubber seals on the connecting spigots. Suitable for control by room thermostat or Pulser. The minimum air volume is based on a minimum air velocity of 1.5 m/s. These duct heaters are designed for a maximum output air temperature of 40C. The CB can be installed in a horizontal or vertical duct. In a horizontal duct, the connection box should be installed facing upwards, or rotated 90 to one side. Installation with the connection box facing downwards is not allowed.

Accessories

D = connection diameter A = Heating elements B = Overheat protection with automatic reset C = Overheat protection with manual reset E = Interlocking F = All phase breaker H = Thyristor type Pulser or TTC Pulser page 334 TTC page 335 Sensors 338 CB-1 230V~

CB Connection mm Power [kW] Voltage [V] Current [A] Min. airflow [m3/h] Weight [kg] Controlled by Wiring diagram

CB-2 400V 2~

CB-3 230V 3~ 400V 3~

CB-4 12kW, 400V 3~

350

Accessories CBM
CBM Connection mm Power [kW] Voltage [V] Current [A] Weight [kg] Wiring diagram CBM Connection mm Power [kW] Voltage [V] Current [A] Weight [kg] Wiring diagram 100-0.6 100 0.6 230 1~ 2.6 2.3 CBM-1 315-6.0 315 6 400 2~ 15 6.6 CBM-2 125-1.2 125 1.2 230 1~ 5.2 70 3 CBM-1 315-9.0 315 9 400 3~ 13 430 8 CBM-3 150-2.1 150 2.1 230 1~ 9.1 100 3.5 CBM-1 355-9.0 355 9 400 3~ 13 550 8.8 CBM-3 160-2.1 160 2.1 230 1~ 9.1 115 3.5 CBM-1 400-9.0 400 9 400 3~ 13 700 9.3 CBM-3 200-3.0 200 3.0 230 1~ 13.1 180 4.4 CBM-1 200-5.0 200 5.0 400 2~ 12.5 115 4.8 CBM-2 250-3.0 250 3.0 230 1~ 13.1 180 5 CBM-1 250-6.0 250 6.0 400 2~ 15 280 5.6 CBM-2

Duct heater with integral control equipment


Duct heater with spigot connection for standard spiral circular ducts. Manufactured from alu-zinc coated sheet steel with a heating element in stainless steel. The heater has integral overheating protection with a manual reset function. The CBM (except sizes 150 and 355) have rubber seals on the connecting spigots. The temperature is set on the cover of the duct heater. The unit is controlled by an integral electronic temperature regulator, using so-called time-proportional Pulse/Pause technology. This provides extremely precise temperature control. As a thyristor is used for adjusting the temperature, the unit has no moving parts. This means that it is silent and not susceptible to wear and tear. Terminals for interlocking the heater, via a pressureand airflow guard are available in the terminal box. The minimum air volume is based on a minimum air velocity of 1.5 m/s. These duct heaters are designed for a maximum output air temperature of 40C. All CBMs are delivered with duct sensor TG-K330 (0-30C) as standard.

Min. airflow [m3/h] 45

Min. airflow [m3/h] 421

CBM-1 230V~

CBM-2 400V 2~

Accessories

D = connection diameter

CBM-3 400V 3~ A = Heating elements B = Overheat protection with automatic reset C = Overheat protection with manual reset E = Interlocking F = All phase breaker H = Thyristor type Pulser or TTC J = Sensor T = Air flow switch/Pressure switch

351

Accessories VBC
dy

Water heating coil


D H+8 H F

Water-heating coil for heating air in ventilation systems with circular ducts. Aluzinc-coated casing, heat transmission element with copper tubes and aluminium fins. Removable cover for cleaning the unit. The water-heating coil can be installed in a horizontal duct. Max operating temperature 150C. Max operating pressure 1.6 MPa (16 Bar) 2- and 3-rows batteries.

K L

VBC 100-2 100-3 125-2 125-3 160-2 160-3 200-2 200-3 250-2 250-3 315-2 315-3 400-2 400-3 500-2

D 100 100 125 125 160 160 200 200 250 250 315 315 400 400 500

B 238 238 238 313 313 313 313 398 398 473 473 557 557 707 707

H 180 180 180 255 255 255 255 330 330 405 405 504 504 539 529

dy 10 10 10 10 10 10 10 22 22 22 22 22 22 22 22

F 137 100 137 175 212 175 212 250 250 325 325 400 400 425 425

G 40 40 40 40 40 40 40 40 40 40 40 40 65 65 65

K 276 276 276 276 276 276 276 276 276 276 276 276 276 330 330

L 356 356 356 356 356 356 356 356 356 356 356 356 406 460 460

kg 3.7 3.8 3.5 5.5 5.4 5.4 5.3 8.2 7.7 10.2 9.9 13.4 13.1 17.9 16.9

Water out

Water in

Accessories

Coil calculation 2 rows


VBC 100-2 Air flow (m3/s) Pressure drop (Pa) DT air at T water 60/40, C Water flow rate (l/s) Water speed (m/s) Pressure drop (kPa) Power (kW) DT air at T water 90/70, C Water flow rate (l/s) Water speed (m/s) Pressure drop (kPa) Power (kW) 0.04 35 16 0.01 0.15 0.1 0.85 32.5 0.02 0.3 1 1.7 VBC 125-2 0.06 72 13 0.01 0.2 0.1 1.0 28.3 0.03 0.4 1 2.2 VBC 160-2 0.1 40 19.9 0.03 0.4 3 2.6 35.8 0.06 0.8 8 4.6 VBC 200-2 0.15 73 17.3 0.04 0.6 5 3.5 30.4 0.07 1.1 13 6.1 VBC 250-2 0.25 68 17.5 0.07 0.5 3 5.7 31.7 0.13 0.9 7 10.3 VBC 315-2 0.39 69 18.1 0.11 0.5 3 9.2 32 0.2 1 8 16.3 VBC 400-2 0.63 77 17.7 0.18 0.6 4 14.6 31 0.31 1.1 10 25.5 VBC 500-2 0.9 45 19.4 0.28 0.7 6.6 22.7 31 0.31 1.1 10 25.5

Coil calculation 3 rows


VBC 100-3 Air flow (m3/s) Pressure drop (Pa) DT air at T water 60/40, C Water flow rate (l/s) Water speed (m/s) Pressure drop (kPa) Power (kW) DT air at T water 90/70, C Water flow rate (l/s) Water speed (m/s) Pressure drop (kPa) Power (kW) 0.04 39 25,9 0.02 0.24 0.85 1.35 47.4 0.03 0.45 2.65 2.46 VBC 125-3 0.06 17.2 33.4 0.03 0.47 5.33 2.6 56.2 0.05 0.8 14 4.38 VBC 160-3 0.1 41 29.3 0.05 0.68 11 3.8 49.7 0.08 1.17 29.5 6.46 VBC 200-3 0.15 29 30.7 0.07 0.54 5.36 6 52.1 0.13 0.92 14.1 10.17 VBC 250-3 0.25 31.2 30.5 0.12 0.59 6.23 9.93 51.6 0.21 1.02 16.2 16.8 VBC 315-3 0.39 35 30.2 0.19 0.69 8.28 15.3 51 0.32 1.17 21.4 25.87 VBC 400-3 0.63 36.3 30.3 0.3 0.74 10.10 24.74 50.8 0.51 1.26 26.1 41.6

352

Accessories VBF
Water heating coil
Water-heating coil with integral F5 bag filter for heating air in ventilation systems with circular ducts. Casing from galvanised sheet steel, with copper tubes and aluminium fins. Inspection cover which facilitates cleaning and replacing the filter. The water-heating coil must be installed in a horizontal duct. The bag filter must always be fitted vertically. The VBF is fitted with connections for connecting to a filter monitor. The Systemair fan selection programme includes a special selection programme for waterheating batteries. The recommended final pressure drop is 200 Pa.

VBF 100 125 160 200 250 315 355 400

D 100 125 160 200 250 315 355 400

A 665 665 665 665 795 895 920 920

B 254 254 254 254 354 454 454 454

H 266 266 266 266 366 466 466 466

L 599 599 599 599 699 799 799 799

dy 22 22 22 22 22 22 22 22

F 213 213 213 213 313 413 413 413

kg 8 8 8 8 12 17 17 17

Bag filter BFR 200 BFR 200 BFR 200 BFR 200 BFR 315 BFR 355 BFR 355 BFR 355

Filter class G3, F5, F7 G3, F5, F7 G3, F5, F7 G3, F5, F7 G3, F5, F7 G3, F5, F7 G3, F5, F7 G3, F5, F7

Accessories

Water out

Water in

Coil calculation 2 rows


VBF Air flow (m3/s) Air velocity, (m/s) DT air at T water 60/40, C Water flow rate (l/s) Water speed (m/s) Pressure drop (kPa) Power (kW) DT air at T water 90/70, C Water flow rate (l/s) Water speed (m/s) Pressure drop (kPa) Power (kW) Filter media 100 0.04 1.2 23.3 0.01 0.1 0.1 1.17 44 0.03 0.2 0.4 2.2 EU5 125 0.05 1.6 20.9 0.02 0.1 0.2 1.35 39.9 0.03 0.2 0.5 2.58 EU5 160 0.12 3.5 14.3 0.03 0.2 0.4 2.1 28.2 0.03 0.4 1.2 4.13 EU5 200 0.16 4.6 12.6 0.03 0.2 0.5 2.4 25 0.06 0.4 1.6 4.76 EU5 250 0.17 1.8 25.9 0.06 0.5 3.5 5.31 44.3 0.11 0.8 8.1 8.97 EU5 315 0.28 1.7 26.2 0.11 0.4 1.6 8.82 44.9 0.18 0.7 3.7 15.11 EU5 355/400 0.44 2.7 21.5 0.14 0.5 2.6 11.67 37.2 0.24 0.9 6.3 20.18 EU5

353

Accessories CWK
dy

Water-cooling coil for circular ducts


Casing of galvanised sheet steel with copper tubes and aluminium fins. Inspection covers for easy cleaning and maintenance. Connection sleeves with rubber seal. Max operating temperature 150C Max operating pressure 1.6 MPa (16Bar)
CWK 100-3-2.5 125-3-2.5 160-3-2,5 200-3-2.5 250-3-2.5 315-3-2.5 400-3-2.5 D 100 125 160 200 250 315 400 B 251 326 326 411 486 560 710 H 180 255 255 330 405 504 529 dy 10 10 10 22 22 22 22 F 100 175 175 250 325 400 425

F H+8

G" *

K L

* Condensate drain

G 40 40 40 40 40 40 65

K 276 276 276 276 276 276 330

L 356 356 356 356 356 356 460

kg 4.4 6.5 6.7 9.4 11 14.3 19.5

Coil calculation
Air flow CWK (m3/h) 100-3-2.5 54 54 100 100 145 145 125-3-2.5 85 85 150 150 215 215 160-3-2.5 145 145 250 250 355 355 200-3-2.5 225 225 390 390 555 555 250-3-2.5 360 360 630 630 900 900 315-3-2.5 560 560 985 985 1410 1410 400-3-2.5 900 900 1590 1590 2280 2280 Air velocity m/s 2 2 3.5 3.5 5 5 2 2 3 3 4.5 4.5 2 2 3.5 3.5 5 5 2 2 3.5 3.5 5 5 2 2 3.5 3.5 5 5 2 2 3.5 3.5 5 5 2 2 3.5 3.5 5 5 Air Pressure drop (Pa) 7 7 22 22 58 58 3 3 9 9 18 18 9 9 24 24 45 45 6 6 17 17 33 33 6 6 18 18 34 34 7 7 20 20 39 39 9 9 25 25 49 49 Air before (C) 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 Air before (% RH) 50 45 50 45 50 45 50 45 50 45 50 45 50 45 50 45 50 45 50 45 50 45 50 45 50 45 50 45 50 45 50 45 50 45 50 45 50 45 50 45 50 45 Air after (C) 14.3 15.8 16.4 18.5 17.5 20.0 12.6 13.5 14.5 15.7 15.6 17.0 14.4 15.6 16.1 17.4 17.0 18.4 14.1 15.3 15.9 17.3 16.9 18.4 14.2 15.4 16.0 17.3 17.0 18.2 14.5 15.4 16.1 17.2 17.0 18.1 15.2 16.3 16.8 17.8 17.6 18.6 Capacity (kW) 0.2 0.4 0.3 0.5 0.4 0.6 0.5 0.7 0.7 1.1 0.8 1.4 0.7 1.0 0.9 1.5 1.1 1.3 1.0 1.6 1.4 2.3 1.7 3.1 1.6 2.5 2.2 3.8 2.7 5.1 2.4 3.9 3.4 6.1 4.3 8.3 3.4 5.8 4.8 9.3 6.1 12.8 Water Flow (l/s) 0.01 0.01 0.01 0.02 0.02 0.02 0.02 0.03 0.03 0.04 0.03 0.05 0.03 0.04 0.04 0.06 0.04 0.08 0.05 0.06 0.06 0.09 0.07 0.12 0.06 0.10 0.09 0.15 0.11 0.20 0.10 0.16 0.13 0.24 0.17 0.33 0.14 0.23 0.19 0.37 0.24 0.51 Water Pressure drop (kPa) < 0.5 1 1 2 1 3 3 5 5 10 7 16 4 10 8 20 11 32 2 5 4 9 5 15 2 5 4 10 6 17 3 7 5 14 8 25 2 5 4 12 6 22

Accessories

VBF 355/400

VBF 355/400

VBF 355/400

354

Accessories FK
Fast clamps

RSK

EFD

Back draft damper

Mounting clips which facilitate the installation and removal of fans for service and cleaning. Made from galvanised sheet steel and fitted with an 8 mm neoprene lining which suppresses vibration and ensures a tight fit. The mounting clips are clamped together by two screws which allows for connecting ducts with a marginal difference in diameter.
Hanging strap

Back draft damper for circular ducts, manufactured from galvanised sheet steel. The two blades are spring-loaded, which means that the damper can also be mounted vertically.

Circular shutter damper

RSK 100 FK 100 125 150 160 200 250 315 355 400* 450* 500* D mm 100 125 150 160 200 250 315 355 400 450 500 125 150 160 200 250 315 355 400

A 100 125 150 160 200 250 315 355 400

D 80 100 100 120 140 140 140 197 197

B 24 33 34 42 55 54 50 75 75

C 33 44 43 55 62 62 65 75 75

Shutter damper EFD is a turn off damper. The damper is provided with 230 V motors with spring-return actuators. EFD are made in leakage performance class 3 according to EN 1751:1998 Annex C.2. Outdoor/exhaust air damper have the function to prevent the hot water coil to freeze. The EFD consists of a tubular housing equipped with a damper blade pivoting on an axle. The connection ends are equipped with silicon rubber sealing rings. The damper is made from hot-dip galvanised sheet steel. The EFD turn off damper is prepared for external insulation and has arrows showing the damper blade position. We recommend preventative maintenance of the damper twice a year for optimum performance. If the damper gets dirty, the blade should be cleaned. The gasket sealing should be checked and the blade axle lubricated as necessary.

95 25

210 130 73

170 100

Accessories

10

Pressure drop

45 175

45

EFD 160 200 250 315

A 160 200 250 315

FKX

Mounting feet
2 pcs mounting feet include plate and screw. For EX 140 and 180, manufactured in galvanised steel plate.
0 45 40 35 30 25 20 15 10 5 0 0 0,05 0,1 0,15 0,2 0,25 0,3 0,35 0,4 0,45 0,5 315 355/400 250 200 400 600 800 1000 1200 1400 1600 1800 200

Pressure drop
100
ps [Pa]

50 40 30 20 10 5 4 3 2 1 1

EFD

* Note! Without hanging straps

50 67

m/s

10

355

Accessories
Back draft damper
Back draft damper for installation in horizontal ducts. The profiled vanes produce a strong upward force which reduces the air resistance. This means that the vanes opens fully at low air velocities as well. The box is manufactured from galvanised sheet steel. The damper inside the box is manufactured in weather-resistant and shock-proof nylon material. The robust construction ensures that the vanes will not become deformed or loose. Air velocity should not exceed 12 m/s.

VKK

Louvre shutters for vertical mounting on a wall. The profiled vanes produce a strong upward force which reduces the air resistance. This means that the vanes opens fully at low air velocities as well. All the parts are manufactured in weatherresistant and shockproof nylon material (PVC containing special synthetic). The robust construction ensures that the vanes will not become deformed or loose. Above size 45, the vanes are fitted with a cast counterweight. Air velocity should not exceed 12 m/s. The louvre shutters are easy to install. Wall plugs and screws are included above size 15.
C
F

ps [Pa]

Gravity louvre shutter

VK

Pressure drop

Air velocity in duct m/s

C E

B A

Accessories

VK 10 12 15 VKK 100 125 160 200 250 315 400 100 125 160 200 250 315 400 A 123 123 123 123 123 123 123 B 199 199 199 199 239 239 259 C 205 205 205 302 302 350 454 D 200 200 200 300 300 345 450 E 201 201 201 297 297 345 450 20 25 30 35 40 45 50

A 142 164 178 245 299 347 397 460 501 549

B 15 12 20 20 25 26 26 26 31 31 30 31 31

C 103 115 130 190 235 274 310 364 395 445 530 626 663 972

D 96 117 152 210 260 310 360 423 460 510 530 660 710 -

E 5 5 4 5 5 5 5 5 5 5 5 5 5 -

F 46 38 50 50 70 70 70 65 70 95 80 85 90 -

G 3 4 5 6 5 6 7 8 6 7 14(2x7) 16(2x8) 18(2x9) -

IGC

Intake grid

56* 610 63* 701 71* 749

Intake grid for inside or outside installation. Connection diameters 100-315 mm, and is manufactured from die-cast aluminium and supplied with a wire mesh. D = outside diameter d = connection diameter

100 1040 40

Pressure drop
ps [Pa]

*side by side shutters. G = amount of vanes

VK 80
B A F

C D H E

G I

IGC 100 125 160 200 250 315

d 100 125 160 200 250 315

D 125 150 185 225 275 350

Air velocity in duct m/s

356

Accessories SG
Protection guard
Protection grille for duct fans, mounted with three screws.

Intake grid
Intake grid manufactured from galvanised sheet steel with wall flange and wire mesh. Connection sleeve with rubber seal.

IGK

30 7.2
+0.8 0

FFK 30-15 40-20 50-25 50-30 60-30 60-35 70-40 80-50

A 340 440 540 540 640 640 740 840

B 190 240 290 340 340 390 440 540

C 402 502 532 562 642 717 787 882 882

D 250 350 350 350 350 350 420 530 530

E 320 420 520 520 620 620 720 820

F 170 220 270 320 320 370 420 520

12

A
2.8 C

Wire mesh
IGK
D

100-50 1040 540

1020 520

A 100 125 160 200

B 37 37 37 41 Filter cassette FFK 30-15 FFK 40-20 FFK 50-25 FFK 50-30 FFK 60-30 FFK 60-35 FFK 70-40 FFK 80-50 FFK 100-50 Bag filter BFK 30-15 BFK 40-20 BFK 50-25 BFK 50-30 BFK 60-30 BFK 60-35 BFK 70-40 BFK 80-50 BFK 100-50 Filter media F5, F7 F5, F7 F5, F7 F5, F7 F5, F7 F5, F7 F5, F7 F5, F7 F5, F7

100 125 160 200

SG 100 125 150 160 200 250 315 355 400 450 500

A 100 125 150 160 200 250 315 355 400 450 500

B 90 110 150 150 190 250 310 350 390 450 490

C 3.4 3.4 3.4 3.4 3.4 3.4 3.8 3.8 3.8 3.8 3.8

D 11.8 11.8 11.8 11.8 11.8 11.8 12.6 12.6 12.6 12.6 12.6

E 24.3 24.3 24.3 24.3 24.3 24.3 24.7 24.7 24.7 24.7 24.7

Pressure drop

Accessories

ORH

BFK 30-15 40-20 50-25 50-30 60-30 60-35 70-40 80-50

I 300/280 400/360 430/370 490/355 540/520 590/515 700/625 600/600 600/600

No. of filer bags 2/5 3/5 4/7 4/7 4/8 4/8 5/9 6/10 7/14

Outlet hood
Outlet protection to avoid foreign objects to enter into the unit. It consists of a galvanized steel frame fitting into the outlet spigot with a grill of the same material covering the total outlet surface.
A C

286/287 142/143 386/387 192/193 486/487 242/243 486/487 292/293 586/587 292/293 586/587 342/343 686/687 392/393 785/785 490/490

Rectangular filter cassette


A filter cassette designed for bag filters standard type F5 or F7. The cassette housing is manufactured from galvanised sheet steel. It has a hinged cover underneath fitted with a quick release latch, which makes it easy to replace the filter. The filter cassette can be connected directly on to the duct and should always be fitted in a flat or vertical position. If fitted vertically, the direction of the air flow must be downwards so that the filter bags do not collapse. BFK filter, in the F5 or F7 filter classes, are to be ordered separately. The recommended final pressure drop is 200 Pa for the F5 filter and 250 Pa for the F7 filter. The cassette is fitted with connections for connecting to a pressure sensor.

FFK

100-50 985/985 490/490

Pos 1 2 3 4 5

KVD 7/7 9/7 & 9/9 10/8 & 10/10 12/9 & 12/12 5/8

A 273 339 367 427 290

B 249 305 330 382 124

C 52 52 52 52 52

357

Accessories
Pressure drop

Silencer for rectangular ducts


Easily-fitted silencer immediately before or after the KE, KT, RS and RSI rectangular duct fans. Effectively suppresses noise transmitted to the duct. The silencer should be used together with an insulated fan where there is a requirement for noise suppression both in the duct and in the surroundings as a whole. All silencers are supplied with a universal flange suitable for PG flange 20 mm wide or Metu profile. NB! Ensure that LDR silencer is mounted in the correct position. Failure to do this will result in air starvation and high pressure drop being experienced. Pressure drop calculation for rectangular silencers These calculations apply only if the silencer is connected to a duct at both ends. Example: Calculation of pressure drop for the LDR 60-35 (with fan model RSI 60-35 M3~) using the diagram to the right. 1. Start by defining the front area, see the table below. 2. Move horizontally to the right until you reach the designated air flow in diagram B. 3. Go up vertically to diagram A and the correct p value (see the table). 4. Then continue horizontally to the left and read off the pressure drop. In this example, the pressure drop is 27 Pa.
Front area m2 LDR 30-15 LDR 40-20 LDR 50-25 LDR 50-30 LDR 60-30 LDR 60-35 LDR 70-40 LDR 80-50 LDR 100-50 0.045 0.08 0.125 0.15 0.18 0.21 0.28 0.40 0.50 P 3.5 3.6 3.7 3.3 3.3 3.0 3.1 3.6 3.6
Pressure drop Duct area m2

LDR

Noise suppression dB (mid-frequency Hz) LDR 30-15 40-20 50-25 50-30 60-30 60-35 70-40 80-50 100-50 125 250 500 1k 7 5 10 8 8 7 7 6 6 15 9 15 15 15 13 11 8 8 18 15 25 20 20 17 14 10 10 25 23 25 31 31 18 14 11 11 2k 25 16 20 17 17 13 10 8 8 4k 19 12 15 14 14 10 8 6 6 8k 19 10 12 11 11 8 6 3 3

Accessories

c/c = B + 20
LDR 30-15 40-20 50-25 50-30 60-30 60-35 70-40 80-50 100-50 B 300 400 500 500 600 600 700 800 1000 H 150 200 250 300 300 350 400 500 500 kg 10 13 17 19 21 23 27 34 41

358

c/c = H + 20

Accessories
Duct heater for rectangular ducts
Manufactured from aluzinc coated sheet steel with a heating element in stainless steel. The heater has integral overheating protection with a manual reset function. Suitable for control by room thermostat or TTC. The minimum air volume is based on a minimum air velocity of 1.5 m/s. These duct heaters are designed for a maximum output air temperature of 40C.

RB

RB Power [kW] Voltage [V] Current [A] Weight [kg] RB Power [kW] Voltage [V] Current [A] Weight [kg] RB Power [kW] Voltage [V] Current [A] Weight [kg]

40-20/9 9 400 3~ 13 9.2 60-30/34 34 400 3~ 49.1 30.6 100-50/45 45 400 3~ 65 33.6

40-20/15 15 400 3~ 22 450 16 60-35/27 27 400 3~ 39 1000 23.1 100-50/68 68 400 3~ 98.2 2800 42.1

50-25/15 15 400 3~ 22 700 12.7 60-35/45 45 400 3~ 65 1000 30.6 100-50/80 80 400 3~ 116 2800 42.1

50-25/22 50-30/15 50-30/27 60-30/22 22 400 3~ 31.8 700 19.9 15 400 3~ 22 850 15.6 27 400 3~ 39 850 23.9 22 400 3~ 31.8 1000 24.9

Min. air flow [m3/h] 450

70-40/27 70-40/45 80-50/45 80-50/68 27 400 3~ 39 1600 23.1 45 400 3~ 65 1600 30.3 45 400 3~ 65 1600 30.5 68 400 3~ 98.2 2200 39

Min. air flow [m3/h] 1000

Min. air flow [m3/h] 2800

RB 40-20/9-1 40-20/15-1 50-25/15-1 50-25/22-2 50-30/15-1 50-30/27-2 60-30/22-2 60-30/34-2 60-35/27-2 60-35/45-3 70-40/27-2 70-40/45-3 80-50/45-3 RB 80-50/68-4 RB 80-50/68-4 RB 100-50/68-4 RB 100-50/80-5

B 400 400 500 500 500 500 600 600 600 600 700 700 800 800 1000 1000 1000

H 200 200 250 250 300 300 300 300 350 350 400 400 500 500 500 500 500

D 370 500 370 500 370 500 500 500 370 500 370 370 370 370 370 370 370

TTC page 335 Sensors page 338

Accessories

F1 Overheat protection, automatic (60C) F2 Overheat protection, manual (120C)


F2 F1

21 20 19

18 17 16

15 14 13

12 11 10

9 8 7

6 5 4 3 2 1

400V 3~
15 14 13

400V 3~
18 17 16

400V 3~
15 14 13

400V 3~
12 11 10

400V 3~
9 8 7 6 5 4 3 2 1

18,6 21,1 21,2 24,1 A

16 kW

18,6 21,1 21,2 24,1 A


18 17 16

16 kW

18,6 21,1 21,2 24,1 A


15 14 13

16 kW

18,6 21,1 21,2 24,1 A


12 11 10

16 kW

18,6 21,1 21,2 24,1 A


9 8 7 6 5 4 3 2 1

16 kW

RB 100-50/80-5

17,5 19,9 22,5 25,6 A

17 kW

17,5 19,9 22,5 25,6 A


15 14 13

17 kW

17,5 19,9 22,5 25,6 A


12 11 10

17 kW

17,5 19,9 22,5 25,6 A


9 8 7 6 5 4 3 2 1

17 kW

RB 100-50/68-4 RB 80-50/68-4

15 kW 19,9 22,6

19,9 22,6 A

15 kW 19,9 22,6

19,9 22,6 A
12 11 10

15 kW 19,9 22,6

19,9 22,6 A
9 8 7 6 5 4 3 2 1

RB 100-50/45-3 RB 80-50/45-3 RB 70-40/45-3 RB 60-35/45-3 RB 60-30/34-2

17,5 19,9 22,5 25,6 A


12 11 10

17 kW

17,5 19,9 22,5 25,6 A


9 8 7 6 5 4 3 2 1

17 kW

22,1 25,1 17,9 20,3 A


12 11 10

13,5 kW

22,1 25,1 17,9 20,3 A


9 8 7 6 5 4 3 2 1

13,5 kW

RB 70-40/27-2 RB 60-35/27-2 RB 50-30/27-2

27,1 30,8 14,6 16,5 A

11 kW

27,1 30,8 14,6 16,5 A


9 8 7 6 5 4 3 2 1

11 kW

RB 60-30/22-2 RB 50-25/22-2

19,9 22,6 19,9 22,6 A


9 8 7 6 5 4 3 2 1

15 kW

RB 50-30/15-1 RB 50-25/15-1 RB 40-20/15-1

33,1 37,6 11,9 13,5 A

9 kW

RB 40-20/9-1

359

Accessories
Duct heater for rectangular ducts
Duct heater with integral control equipment. Manufactured from alu-zinc coated sheet steel with a heating element in stainless steel. The heater has integral overheating protection with a manual reset function. The unit is controlled by an integral electronic temperature regulator, using so-called time-proportional Pulse/Pause technology. This provides extremely precise temperature control. As a thyristor is used for adjusting the temperature, the unit has no moving parts. This means that it is silent and not susceptible to wear and tear. The RBM is supplied with a complete and fully-connected control system including contactors and alarm relays. This minimises the installation cost. The external installation requirements are: mains power supply, control circuit, dial for setting required temperature, sensor and a possible alarm circuit. The minimum air volume is based on a minimum air velocity of 1.5 m/s. These duct heaters are designed for a maximum output air temperature of 40C. All RBM are delivered with a TG-R430 room sensor with adjustment of desired value.

RBM

RBM Power [kW] Voltage [V] Current [A] Min. air flow [m3/h] Weight [kg] RBM Power [kW] Voltage [V] Current [A] Min. air flow [m3/h] Weight [kg] RBM Power [kW] Voltage [V] Current [A] Min. air flow [m3/h] Weight [kg]

40-20/9 9 400 3~ 13 450 19 50-30/15 15 400 3~ 22 850 21 60-35/27 27 400 3~ 39 1200 27

50-25/15 15 400 3~ 22 700 20.2 60-30/27 27 400 3~ 39 1000 26.4 70-40/27 27 400 3~ 39 1600 29.7

Cold water coil for rectangular ducts


Casing from galvanised sheet steel. Watercoil from copper tubes and aluminium fins. Air vent and drain valve included. Drip pan from stainless steel and condensate connection (R"). Max working pressure 1.6 MPa (16 bar). For water connection left or right. Two inspection covers for cleaning and maintenance. Droplet separator DE as an accessory regardless of air direction. Recommended for air velocities from 2.5 m/s.
58 90 B

PGK

9 10 (8x)

9 9

R K M

Accessories

19

200

200 + B + 19 B

19

c/c = B + 20

H + 38

330 395
PGK 40-20-3 B 438 538 538 638 638 738 838 H I K 176 176 176 176 176 170 170 170 M 43 43 43 43 43 55 55 55 N R 3/4 R 3/4 R 3/4 R 3/4 R 3/4 R1 R1 R1

238 70 288 120 338 175 338 170 388 220 438 250 538 340

19

10 (8x)

c/c = B + 20 D 35

50-25-3 50-30-3 60-30-3

35

A = B =

RBM 40-20/9 50-25/15 50-30/15 60-30/27 60-35/27 70-40/27

B 400 500 500 600 600 700

H 200 250 300 300 350 400

D 500 500 500 500 500 500

Heating elements Overheat protection with automatic reset C = Overheat protection with manual reset E = Flow control H = Thyristor ( or TTC) J = Sensor K = Set value adjustment K/J = Combined room sensor and set value adjustment T = Air flow switch/Pressure switch Sensors page 338

60-35-3 70-40-3 80-50-3

100-50-3 1038 538 350

Calculation of required heating power P=qv x air density x delta t P = power in kW qv = air volume in m3/s air density = 1.2 kg/m3 at 20C delta T = temperature difference

NB! Droplet separator DE must be ordered extra. Recommended for air velocities from 2.5 m/s.

360

35

Accessories
Coil calculation, water temp 6/12C
PGK 40x20-3-2.0 Air flow [m3/h] 576 576 864 864 1152 1152 900 900 1350 1350 1800 1800 1080 1080 1620 1620 2160 2160 1296 1296 1944 1944 2592 2592 1512 1512 2268 2268 3024 3024 1920 1920 2880 2880 3840 3840 2743 2743 4115 4115 5486 5486 3429 3429 5144 5144 6858 6858 Air velocity m/s 2 2 3 3 4 4 2 2 3 3 4 4 2 2 3 3 4 4 2 2 3 3 4 4 2 2 3 3 4 4 2 2 3 3 4 4 2 2 3 3 4 4 2 2 3 3 4 4 Air pressure drop (Pa) 31 36 66 72 113 119 31 36 66 72 113 119 31 36 66 72 113 119 31 36 66 72 113 119 31 36 66 72 113 119 47 55 91 100 142 151 47 55 91 100 142 151 47 55 91 100 142 151 Air before (C) 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 Air before (% RH) 50 45 50 45 50 45 50 45 50 45 50 45 50 45 50 45 50 45 50 45 50 45 50 45 50 45 50 45 50 45 50 45 50 45 50 45 50 45 50 45 50 45 50 45 50 45 50 45 Air after (C) 17.0 19.0 18.4 20.2 19.2 20.8 17.0 18.6 18.2 19.4 18.9 19.8 17.1 18.8 18.4 19.7 19.1 20.1 17.3 19.0 18.6 19.8 19.3 20.1 17.3 19.0 18.6 19.8 19.3 20.1 17.1 18.1 18.5 18.8 19.3 19.0 17.1 17.6 18.4 18.0 19.0 18.6 17.5 17.9 18.7 18.0 19.3 18.6 Capacity (kW) 1.53 2.50 1.89 3.26 2.20 4.15 2.38 4.27 3.02 6.16 3.61 8.34 2.83 4.93 3.56 6.94 4.22 9.40 3.3 5.69 4.13 8.12 4.90 11.18 3.86 6.64 4.82 9.48 5.72 13.05 5.02 8.66 6.20 12.94 7.26 18.41 7.20 13.59 9.04 21.61 10.82 28.41 8.56 16.13 10.72 26.77 12.85 35.52 Water flow (l/s) 0.06 0.10 0.08 0.13 0.09 0.17 0.09 0.17 0.12 0.25 0.14 0.33 0.11 0.20 0.14 0.28 0.17 0.37 0.13 0.23 0.16 0.32 0.20 0.45 0.15 0.26 0.19 0.38 0.23 0.52 0.20 0.35 0.25 0.52 0.29 0.73 0.29 0.54 0.36 0.86 0.43 1.13 0.34 0.64 0.43 1.07 0.51 1.41 Water pressure drop (kPa) 1 3 2 5 2 7 2 5 3 9 4 15 1 4 2 7 3 12 1 3 2 6 3 11 1 3 2 6 3 11 1 3 1 4 2 8 1 3 1 6 2 10 1 2 1 6 2 10

50x25-3-2.0

50x30-3-2.0

60x30-3-2.0

60x35-3-2

70x40-3-2.0

Accessories

80x50-3-2.0

100x50-3-2.0

Pressure drop DE, droplet eliminator


pressure drop delta p in Pa

Air velocity in m2

361

Accessories
Rectangular duct cooling coil (DX)
Same model for left-hand or right-hand installation (reversible coil) Stainless steel condensate drip tray. A droplet eliminator can be fitted regardless of the direction of air flow Easily removable drip tray to simplify cleaning and inspection. DXRE is recommended for central or decentral (zones) cooling of individual rooms. The DXRE is intended for installation in a horizontal duct, with the air flow in either direction (reversible coil). We recommend that a DE droplet eliminator (accessory) should be installed on the outlet side of the coil if the air velocity is in excess of 2.5 m/s. This prevents water droplets being entrained by the air flow out into the duct system. Maximum operating pressure 2.4 MPa (24 Bar).
R S 9 10 (8x) B 9 9

DXRE

Coil calculation
Refrigerant R407C, 5 C Air flow DXRE 40x20-3-2.5 (m3/h) 575 575 865 865 1150 1150 900 900 1350 1350 1800 1800 1080 1080 1620 1620 2160 2160 1300 1300 1950 1950 2600 2600 1510 1510 2270 2270 3025 3025 2015 2015 3020 3020 4030 4030 2880 2880 4320 4320 5760 5760 3600 3600 5400 5400 7200 7200 Air pressure drop (Pa) 32 36 60 68 91 107 32 36 60 69 92 108 32 36 62 70 97 110 33 37 63 71 99 112 32 36 62 70 97 110 40 44 72 83 112 130 39 44 73 84 113 131 40 45 74 86 116 134 Air in Air in Air out Output Refrigerant flow (kW) 2,2 3,2 2,7 3,9 2,8 4,4 3,4 5 4,2 6,3 4,4 7,1 4,3 6,4 5,4 7,9 6,3 8,9 5,3 8,2 6,6 9,7 7,7 11 6 8,7 7,5 11 8,6 12,4 8,6 12,5 9,6 14,7 11,2 16,9 12,4 18,1 14,1 21,8 16,2 24,5 16,3 23,6 18,7 29,1 21,4 31,9 (kg/h) 51 75 63 90 65 104 80 118 99 147 103 165 101 149 126 186 147 208 116 180 145 213 170 241 131 192 164 242 189 272 188 274 211 323 246 370 272 398 309 477 356 538 356 517 411 638 470 699 Refrigerant Pressure drop (kPa) 3 6,1 4,3 8,7 4,9 11,3 3,2 6,6 5 9,8 5,2 12,1 6,1 11,9 8,8 17,6 11,6 21,7 8,4 18,5 12,6 25,2 16,7 31,5 7,5 12,8 10,1 18,6 12,5 22,6 7,6 13,3 9 17,4 11,3 20 8,8 15,7 10,6 21,2 13,2 25,9 15,1 28 19 40,2 23,8 47

50x25-3-2.5

50x30-3-2.5

60x30-3-2.5

60x35-3-2.5

Accessories

70x40-3-2.5

40

R"

K O

80x50-3-2.5

330 395

100x50-3-2.5

DXRE 400x200-3-2.5 500x250-3-2.5 500x300-3-2.5 600x300-3-2.5 600x350-3-2.5 700x400-3-2.5 800x500-3-2.5 1000x500-3-2.5 DXRE 400x200-3-2.5 500x250-3-2.5 500x300-3-2.5 600x300-3-2.5 600x350-3-2.5 700x400-3-2.5 800x500-3-2.5 1000x500-3-2.5

B 438 558 558 638 638 738 838

H 238 288 338 338 388 438 538

I 70 120 175 170 220 250 340 350 S 90 90 90 90 90 100 100 100

O 100 30 30 30 30 30 30 30 R 105 105 105 105 105 115 115 115

K 165 165 165 165 165 160 160 160 C 1/2" 1/2" 1/2" 5/8" 5/8" 5/8" 5/8" 5/8" Refrigerant Factor

(C) 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30

(% RH) 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50

(C) 15,8 18,8 16,9 20,4 17,5 21,2 15,8 18,7 16,9 20,1 18 21,2 15,5 18,3 16,6 19,8 17,3 20,9 15,4 17,8 16,5 19,6 17,3 20,8 15,5 18,4 16,7 19,8 17,4 21 14,7 17,4 16,3 19,3 16,5 20,2 14,6 17,3 16,2 19,1 16,4 20,2 14,3 16,9 15,9 18,6 16,7 19,9

35

R 410A R 134A R 404A R 507A 1.01 0.93 1.00 0.97

1038 538 M 60 60 60 60 60 75 75 75 N 19 22 22 22 22 35 35 35

Recalculation of the basic value with different refrigerants.

362

Accessories EFD
Shutter damper for rectangular ducts

DS

Rectangular flexible connections


Flexible lengths from 100 to 158 mm. Flange width 20 mm.

DS-EX

Rectangular flexible connections


Flexible connections for the KTEX. In accordance with ATEX guideline 94/9/EC, EX II 2/2 GD IIC TX. Fitted with flanges to match the fan. Flexible lengths from 100 to 158 mm. Flange width 20 mm.
DS-EX A 300 400 500 500 600 600 700 800 1000 B 150 200 250 300 300 350 400 500 500

120

60

EFD is a shut-off damper. The damper is provided with 24 V motors with spring-return actuators. EFD is manufactured to leakage performance class 3 according to EN 1751:1998 Annex C.2. Outdoor/exhaust air damper has the function to prevent the hot water coil from freezing and also prevent the cold air from cooling down the building if the unit stops. The EFD multi-leaf damper comprises a number of opposed blades, swivelling on nylon bearings in a sheet metal framework. The blades are connected via a system of linkages (protected) on the outside of the frame. Maximum air temperature is 100C.

B B+20 B+40

A A+20 A+40

30-15 40-20 50-25 50-30 60-30 60-35 70-40

20

DS 30-15 40-20 50-25

A 300 400 500 500 600 600 700 800 1000

B 150 200 250 300 350 400 500 500 300

80-50 100-50

60-30
50 70 140

60-35 70-40 80-50 100-50

A A+20 A+40

B B+20 B+40

50-30

Accessories

EFD 40-20 50-25 50-30 60-30 60-40 70-30 70-40 80-35 80-40 100-35

A 400 500 500 600 600 700 700 800 800 1000

B 200 250 300 300 400 300 400 350 400 350

120

Pressure drop

60

363

Accessories GFL
Counterflange
Used as a flange for mounting to the duct system. Manufactured from galvanised sheet steel. Suitable for rectangular ducts.

SRK

Volume control damper


A valve with the same flange system as rectangular duct fans. Air tightness class 2 or 3. The shutter valve consists of a number of blades which close towards each other. These are mounted inside a steel sleeve on bushes made of glass-fibre reinforced nylon. The blades are connected via a linkage on the outside of the steel-plate sleeve coupling. The linkage is protected so that the valve can be insulated together with the duct. The blades and sleeve coupling are manufactured from galvanised sheet steel.
L

GFL

A1

A2 200 250 300 300 350 400 500

B1 420 520 520 620 620 720 820

B2 220 270 320 320 370 420 520

C1 440 540 540 640 640 740 840

C2 240 290 340 340 390 440 540

50-25 500 50-30 500 60-30 600 60-35 600 70-40 700 80-50 800

20

20

B
140

40-20 400

15

SRK 40-20 50-25 50-30 60-30

L 400 500 500 600 600 700 800 1000

B 201 251 301 301 351 401 501 501

Accessories

60-35 70-40 80-50 100-50

RED

Pressure drop

Reduction
Pa

Pressed, concentric reducer with female coupling,with a 45 angle. This reducer is designed to meet demands for short installation length with low pressure drop and low internal noise generation.

500 50 30 20 10 5 2 150 200

1000

2000

3000

5000

10000 15000 m3/h

K SR

40

20

SR

50

25

5 35 -3 -35 060 80 10 K K K 0 50 0 0-30 SR 0-30 SR SR 0-4 0-5 8 50 10 8 7 K K K K K SR -30 SR -40 -40 SR SR SR 60 60 70 K K RK R R S S S

150

300

500

1000

2000

3000 4000 l/s

48

160

364

Accessories VBR
Water-heating coil
VBR XX-XX-2 = Two pipe rows VBR XX-XX-4 = Four pipe rows VBR XX-XX-3 = Three pipe rows

LDK

Silencer for square ducts


LDK is easily connected to our square duct fans type KDRE and KDRD. Noise suppression can be decided with use of the diagram.

Water-heating coil for heating air in ventilation systems with rectangular ducts. Hot dip galvanized casing, heat transmission element with copper tubes and aluminium fins. In cold conditions, a frost protection device with sensor should be fitted to reduce the risk of damage from freezing. The water-heating coil can be installed in a horizontal duct.

G H
F Thread G 1/4 G Airing H Water out I Connection for immersion sensor J Water in K Draining

LDK 45 50 55

b 450 502 550

B 490 546 594

C 50 50 50

D 100 150 200

I J K

VBR 40-20-2 50-25-2 50-30-2 60-30-2 60-35-2 70-40-2 80-50-2 100-50-2

A 438 538 538 638 638 738 838 1038 A

c/c A 420 520 520 620 620 720 820 1020 c/c A 420 520 520 620 620 c/c A 720 820 1020

B 238 288 338 338 388 438 538 538 B 238 288 338 338 388 B 438 538 538

c/c B 220 270 320 320 370 420 520 520 c/c B 220 270 320 320 370 c/c B 420 520 520

E R'' R'' R'' R'' R'' R 1'' R 1'' R 1'' E R'' R'' R 1'' R 1'' R 1'' E R 1'' R 1'' R 1''

kg 5.5 kg 7 kg 8 kg 9 kg 10 kg 12.5 kg 16 kg 18.5 kg kg 7 kg 9 kg 10.5 kg 11.5 kg 13 kg kg 15.5 kg 19 kg 22.5 kg Noise suppression dB frequency band Hz LDK 45 50 55 65 70 125 5 7 9 6 5 250 8 8 9 7 7 500 13 13 13 14 19 1k 12 12 12 13 24 2k 8 9 10 9 23 4k 7 8 9 8 15 8k 7 7 8 7 10 LDK 65 70 b 661 696 B 703 740 C 50 50 D 100 100 E 93 110 F 175 176

Accessories

40-20-4 50-25-4 50-30-4 60-30-4 60-35-4

438 538 538 638 638 A

70-40-3 80-50-3 100-50-3

738 838 1038

Pressure drop

Max. operating temperature Max. operating pressure, at water temp. 100C Max. operating pressure, at water temp. 150C Coil calculation on page 366

16 bar 10 bar

365

Accessories
Coil calculation
VBR 40-20-2 Air Flow (m3/h) 400 1000 40-20-4 400 1000 40-20-2 80/60C 400 1000 40-20-4 400 1000 50-25-2 60/40C 600 1200 50-25-4 600 1200 50-25-2 80/60C 600 1200 50-25-4 600 1200 50-30-2 60/40C 800 2000 50-30-4 800 2000 50-30-2 80/60C 800 2000 50-30-4 800 2000 60-30-2 60/40C 1000 2500 60-30-4 1000 2500 60-30-2 80/60C 1000 2500 60-30-4 1000 2500 60-35-2 60/40C 1200 3000 60-35-4 1200 3000 60-35-2 80/60C 1200 3000 60-35-4 1200 3000 70-40-2 60/40C 2000 4000 70-40-3 2000 4000 70-40-2 80/60C 2000 4000 70-40-3 2000 4000 80-50-2 60/40C 2500 5000 80-50-3 2500 5000 80-50-2 80/60C 2500 5000 80-50-3 2500 5000 100-50-2 60/40C 3000 6000 100-50-3 3000 6000 100-50-2 80/60C 3000 6000 100-50-3 3000 6000 Data based on supply air temperature of 0C. Water temp. (in/out) 60/40C Pressure drop (Pa) 9 48 18 96 9 48 18 96 8 29 16 59 8 29 16 59 10 54 20 109 10 54 20 109 11 58 22 117 11 58 22 117 11 61 23 123 11 61 23 123 31 94 46 139 31 94 46 139 25 77 37 113 25 77 37 113 23 72 35 106 23 72 35 106 T 18.5 12.7 29.5 19.5 32.8 24.5 46.3 38.9 21.7 18.2 33.1 28.4 36.5 28.6 54.5 45.9 18.2 13.5 32.5 27.2 33.6 24.3 53.8 41.7 19.2 15.4 34.1 28.2 34.3 24.4 53.9 41.8 18.7 15.0 34.2 28.1 33.9 24.1 53.6 41.5 20.1 16.0 24.7 21.1 34.7 25.1 45.4 34.4 21.1 17.2 28.0 24.0 36.8 26.9 48.4 37.1 24.8 18.4 32.3 25.6 38.4 28.2 50.1 38.7 Capacity (kW) 2.7 4.6 4.3 7.1 4.7 8.9 6.7 14.0 4.7 7.9 7.2 12.3 7.9 12.4 11.8 19.9 5.3 9.8 9.4 19.7 9.7 17.5 15.5 30.1 6.9 13.9 12.3 25.5 12.4 22.1 19.5 37.8 8.1 16.3 14.8 30.4 14.7 26.1 23.2 45.0 14.5 23.2 17.8 30.5 25.1 36.3 32.8 49.7 19.0 31.1 25.3 43.4 33.3 48.6 43.7 67.0 26.9 40.0 35.0 55.4 41.6 61.1 54.3 83.8 Water Flow (l/s) 0.03 0.06 0.05 0.09 0.06 0.11 0.08 0.17 0.06 0.10 0.09 0.15 0.10 0.15 0.14 0.24 0.06 0.12 0.11 0.24 0.12 0.21 0.19 0.37 0.08 0.17 0.15 0.31 0.15 0.27 0.24 0.46 0.10 0.20 0.18 0.37 0.18 0.32 0.28 0.55 0.18 0.28 0.22 0.37 0.31 0.44 0.40 0.61 0.23 0.38 0.31 0.52 0.41 0.59 0.53 0.82 0.32 0.48 0.42 0.67 0.51 0.75 0.66 1.02 Pressure drop (kPa) 0.5 1 0.5 0.5 1 2 0.5 1 1 2 0.5 1 2 4 1 3 0.5 1 1 2 1 2 1 4 1 2 1 4 1 4 2 7 0.5 2 1 4 1 3 3 8 1 1 0.5 1 1 3 1 2 0.5 1 0.5 1 1 2 1 2 1 2 1 2 2 4 2 4

Accessories

366

Accessories VBK
Water heating coil for square ducts
The casing is made of galvanised steel, the heat transmission elements are copper tubes with aluminium fins, and with copper pipes for connecting water inlet and outlet. If the VBK is to be used in very cold conditions it may be necessary to install a frost protection device. The VBK is designed for horizontal mounting with the water connection to the right. For best results the air and water must be going through the coil in opposite directions. The water must be flowing upwards in order to facilitate airing of the coil. Software for determining the required dimensions for the desired output is available.
Air

Connection for thermostat (frost protection device)

Draining

VBK 45 50 55 65

A 492 547 595 707

c/c 470 520 573 680

D 78 78 98 98

no. of rows 2 2 2 2

Air

Accessories

Water

The air flow should be going in the opposite direction of the water.

Coil calculation
VBK 45 Water temp in/out 60/40C Air flow m3/h Pressure drop Pa 10 38 57 11 38 58 10 35 53 10 36 54 18 64 96 18 65 98 27 99 150 28 101 152 DT C 30,1 23 20,9 44,7 34,5 31,5 31,5 24,2 22 46,1 35,8 32,7 26,1 19,5 17,7 39,5 29,9 27,2 24,6 18,2 16,5 36,8 27,7 25,1 Capacity kW 10,2 15,6 17,7 15,1 23,4 26,7 12,8 19,7 22,4 18,8 29,1 33,3 17,8 26,5 29,9 26,8 40,6 46,1 30 44,5 50,2 49 67,6 76,5 Water flow l/s 0,12 0,19 0,21 0,18 0,28 0,32 0,15 0,23 0,27 0,22 0,35 0,40 0,21 0,32 0,36 0,32 0,48 0,55 0,36 0,53 0,60 54 0,81 0,91 Pressure drop kPa 0,8 1,7 2,2 1,5 3,4 4,3 1,4 3,1 3,9 2,6 5,8 7,4 0,7 1,4 1,7 1,3 2,8 3,5 1,5 3 3,7 2,8 5,9 7,3

1000 2000 2500 80/60C 1000 2000 2500 50 60/40C 1200 2400 3000 80/60C 1200 2400 3000 55 60/40C 2000 4000 5000 80/60C 2000 4000 5000 65 60/40C 3600 7200 9000 80/60C 3600 7200 9000 Data based on supply air temperature of 0C

367

Accessories FFS
Filter cassette for square ducts

VK

Louvre shutter
Louvre shutters for vertical mounting on a wall. The profiled vanes produce a strong upward force which reduces the air resistance. This means that the vanes opens fully at low air velocities as well. All the parts are manufactured in weatherresistant and shockproof nylon material (PVC containing special synthetic). The robust construction ensures that the vanes will not become deformed or loose. Air velocity should not exceed 12 m/s. The louvre shutters are easy to install. Wall plugs and screws are included.

RBK

Electric duct heater for square ducts


Casing of alu-zink coated sheet metal with heating elements in stainless steel. The heater has built-in overheating protection with manual reset. Heat control by means of a controller TTC together with a TT-Slave (TT-S1) or TTC together with a TT-M Slave. Min.airflow is based on a min.air velocity of 1.5 m/s. The duct heater is dimensioned for a maximum outgoing temp. of 40C.

Filter cassette with a bag filter standard type F5 included. The cassette is made of galvanized steel with a hinged cover underneath fitted with a quick-release latch for easy change of filter. It can be connected directly to the duct. Connections for a pressure sensor are standard. The recommended final pressure drop is 200 Pa.

A F

C D E H

FFS 45 50 55 65 70

A 447 502 550 661 697

c/c 470 520 573 680 720

B 492 547 595 707 742

C 502 532 562 642 642 VK 40-20 50-25 50-30 60-30 60-35 70-40 80-50 100-50 A 455 555 555 655 655 755 846 1146 F 40-20 50-25 50-30 60-30 60-35 70-40 80-50 100-50 415 515 515 615 615 715 806 1097 B

G I

C 452 552 552

D 255 305 355

E 215 265 315 315 365 415 515 506 J* 44 44 44 44 44 44 44 42 RBK Power Voltage Phase Current Min. airflow 45/17 kW 17 V 400 ~ 3 A 24.5 m3/h 570 55/33 Power Voltage Phase Current Min. airflow kW 33 V 400 ~ 3 A 48 m3/h 890 50/21 21 400 3 30 910 66/39 39 400 3 56 1650 RBK 45 50 55 65 B 450 500 550 660 D 370 370 370 370

Accessories

15 15 15 15 15 15 15 15 G 30 30 30 30 28

Pressure drop

2x309 355 2x309 405 2x359 455 2x405 555 2x560 555 H 285 335 385 385 435 485 585 585 I 485 585 585 685 685 785 876 1176

*J = thickness of frame Filter cassette FFS 45 FFS 50 FFS 55 FFS 65 FFS 70 Bag filter (incl. in FFS) BFS 45 BFS 50 BFS 55 BFS 65 BFS 70 Filter media F5 F5 F5 F5 ps [Pa] F5

Pressure drop

Calculation of required power P = qv x air density x delta t P = power (kW) qv = air volume (m3/s) air density = 1.2 kg/m3 at 20C delta t= temperature difference
Air velocity in duct m/s

368

Accessories

Accessories

F1 = overheat protection, automatic reset (70C) F2 = overheat protection, manual reset (120C)

SDM

Service door
For Multibox (MUB) or Thermo-Box (MUB-T). The door consists of double skin galvanised steel panels with a 20mm mineral wool insulation inside.
b1 b2

h2

l2 l1
MUB 025 042 062 l1 417 587 717 l2 327 497 627 b1 417 587 717 b2 327 497 627 h1 40 40 40 h2 42 42 42

h1

369

Accessories DSK
Flexible connections
Flexible connections for KDRE and KDRD. The connections fit exactly to the fan and are easily bolted to fan and duct.

WSD

WSG

Wheather roof for Multiboxes


Made of seawater resistant aluminium. Edges are welded.
A B

Weather protection guard


Manufactured from galvanised steel. The protection guard includes a protection grille. Suitable for MUB Multiboxes.
B 40 A 40

8 .5 (

x4 )

38

DSK 45 50 55 65 70

A 492 547 595 707 742

B 447 502 550 661 696

C 120 120 120 120 120

WSD 025 042 062 100

A 560 730 860 1060

B 480 650 780 980

C 370 700 Protection grille 500


39

260

WSG 025 042 062 100

A 418 585 715 915

39 62

B 418 585 715 915

Accessories

FGV

UGS

Flexible connection
Manufactured from aluminium with neoprene coated fabric. For temperature up to 60C. On both sides there are holes for mounting to the duct system. Suitable for MUB.

Flexible adaptor, square to round


Reduction from square to round. Aluminium frame and neoprene coated fabric. For temperature up to 60C. The circular side has a locking ring for easy installation to the duct system. Suitable for MUB.

SRKG

Shutter for Multibox


SRKG is a cut-off shutter intended for use in ventilation systems. The shutter is designed with a number of blades which close towards each other, mounted in an aluminium frame. The blades are manufactured from aluminium.
20

12

90 B c/c D A c/c C

15

120

FGV 025/418-418 042/586-586 062/718-718 100/918-918

A 418 586 718 918

B 398 568 698 898

C 378 548 678 878

D 190 350 418 400

UGS

A/C

G/H 418 418 418 588 588 588 718 718

I 315 355 400 355 400 500 500 630

J 210 210 210 210 210 210 210 210

SRKG 016 025 030 042 062 100

A 548 378 678 548 678 878

B 236 378 236 548 678 878

c/c C 568 398 698 568 698 898

c/c D 256 398 256 568 698 898

025/315 378 025/355 378 025/400 378 042/355 548 042/400 548 042/500 548 062/500 678 062/630 678

370

Accessories WSD-KBT
Weather roof for motor

ISE/USE

Flexible connections

FTG

Tilting device for roof fans


For DVS/DVSI/DVC/DHS/ DVN. With the tilting device FTG the roof fan is easy to open for service options. The open fan can be secured against unintended closing. The framework consists of galvanised steel and the hinges are made of stainless steel. For the connection of inlet accessory the adapter framework TDA is needed, which has to be ordered separately. The delivery includes mounting material. The tilting device is available for the sizes 310 up to 630. Preferrably to be ordered together with the fan, fully assembled.

Additional weather protection for the motor of thermo fans KBT and KBR, if mounted outside. Manufactured from seawater resistant aluminium. WSD KBT-1 suitable for KBT 160 180, KBR 315/355 4-pole, WSD KBT-2 suitable for KBT 200 - 280, KBR 315/355 2-pole.
265/385

Flexible connections for the CE/CT, CKS and DKEX centrifugal radial fans. ISE supply connection is fixed with a strap to the spiral ducting. ISE: flex. length 100158mm. USE: flex. length 65-120mm.
CE/CT, DKEX Size 200 225 250 Supply ISE 200 Exhaust USE 200

ISE 225/250 USE 225 ISE 225/250 USE 250 ISE 280/315 USE 280 ISE 280/315 USE 315 ISE 355/400 USE 355 ISE 450 Supply ISE 500 ISE 500 ISE 500 ISE 560 USE 400 USE 450 Exhaust USE 400 CKS USE 355 USE 500 CKS

181,25

280 315 355 400 450 CKS

20

126

300

126

,2

(x7

Size 355 400 450

ISE 355/400 USE 280

200

500 560

FTG 400 540 640 940

A 420 580 650 924

B 330 450 535 750

C 304 466 490 654

for size 310/311 355/400 450/499/500 560/630

60 10

Accessories

Adapter

TDA DV

Drain for liquids that accumulate in the casing. For KBT/KBR. Accessory to be ordered together with the fan, to be assembled in the factory.

ALS-KBT

Flexible connection
The ASF/KB is manufactured from galvanized steel, with neoprene coated fabric. It can be used for temperatures up to 120C. The ASF/KB has double sealing on each side. Suitable for KBT/KBR.

ASF/KB

Adapter framework TDA for mounting of accessories together with tilting frame FTG. The framework consists of galvanized steel.

4xi

nx

IS/US

d1

F E D

Inlet/outlet flange
Flange for EX 140 including washers and screws. Manufactured from galvanized steel. Makes it possible to connect the fans to spiral duct.
Inlet 125 160 200 Outlet 125 160 EX 140 IS 1412 IS 1416 EX 140 US 1412 EX 180 IS 1816 IS 1820 EX 180 US 1816 ASF 200/KB 225/KB 250/KB 280/KB 315/KB 355/KB da 200 225 250 280 315 355 h 196 199 200 200 205 210 310/311 315 TFSK 355/400 450/500 560/630 i 10 12 12 12 14 nxd 6x6.5 6x6.5 6x9 6x9 8x9 de 256 256 405 405 570 d1 285 285 438 438 605 TDA DV 310/311 315 TFSK 355/400 450/500 560/630 D 300 362 450 486 650 E 330 450 464 535 750 F 373 474 543 619 793 h 19 35 20 35 15

371

Accessories
Profiled roof cover plate
The cover plate is shaped like a roof tile so that it can be fitted on to a standard double-lap concrete roof tile (type TOB 125-160) or on to two single-lap roof tiles (TOB 200-315). It is fitted at right angles to the roof cladding and can therefore be used on different roof pitches. The cover plate is manufactured from powder-coated galvanised sheet steel. They are available in the standard colours of black, brick red and also uncoated. The spiral duct connected to the cover is insulated with 30 mm mineral fibre. The roof fan TFSR is fastened to the profiling plate with 4 screws, these screws are included in TOB. 3 m cable is included, as well as the TUB sealing-plate which is fitted on to the inside of the roof. This sealing-plate prevents water-damage via the roof aperture if there is leakage on the outside of the roof. The sealing-plate should not be used if the roof is only covered with roofing felt.

TOB

TOS

Flat roof cover plate


The cover plate is fitted at right angles to the roof cladding and can therefore be used on different roof pitches. The cover plate is manufactured from powder-coated galvanised sheet steel. They are available in the standard colours of black, brick red and also uncoated. The spiral pipe connected to the cover is insulated with 30 mm mineral fibre. The roof fan TFSR is fastened to the profiling plate with 4 screws, these screws are included in TOS. 3 m cable is included, as well as the TUS sealing-plate which is fitted on to the inside of the roof. This sealing-plate prevents waterdamage via the roof aperture if there is leakage on the outside of the roof. The sealingplate should not be used if the roof is only covered with roofing felt.

TG 300-800, 400-800
Roof curb
The brackets make it easy to fit the roof curb to the roof pitch. TG also has a silencer function. Manufactured from galvanised sheet steel and insulated with a 50 mm rockwool sheet and a perforated inner plate. The roof curb is fitted with plastic piping and conduits for electric cables. Weight 24 kg.

Accessories

TG
E D

A 800 800

B 293 393

C 245 330

300-800 400-800

Hole measurement in roof = B+10 mm


D

STG
C D A A B

Roof base plate


Accessory for the TG 400-800. Adapter for connection with 125, 160 and 200mm.
E 323 326 F 230 138 D 160 200

TOS 125-160 D E F D 200-315

A 455 585

B 480 735

TOB

125-160 260 375

448 323 230 160

200-315 560 684 430 500 326 138 200

TUB/TUS

Roof sealing plate for TOB or TOS.

A
STG 125 160 200 A 125 160 200

372

Accessories THB
Profiled roof cowl
This cowl is shaped to fit over a standard double-lap concrete roof tile (THB 160), or over two tiles (THB 200). The cowl is fitted at right angles to the roof cladding and can therefore be used on different roof pitches. Manufactured from powder-coated, galvanised sheet steel, in the standard colours of black and brick red. The spiral pipe connected to the cover is insulated with 30 mm rockwool matting. The TUB sealing-plate, for fitting inside the roof, is included. This sealingplate prevents water-damage via the roof aperture if there is leakage on the outside of the roof. The sealing-plate should not be used if the roof is only covered with roofing felt.

THS

Flat roof cowl


The cowl is fitted at right angles to the roof cladding and can therefore be used on different roof pitches. Manufactured from powder-coated, galvanised sheet steel, in the standard colours of black and brick red. The spiral pipe connected to the cover is insulated with 30 mm rockwool. The TUS sealing-plate, for fitting inside the roof, is included. This sealing-plate prevents water-damage via the roof aperture if there is leakage on the outside of the roof. The sealing-plate should not be used if the roof is only covered with roofing felt.

TG

Roof curb
The brackets make it easy to fit the roof curb to the roof pitch, and also function as a silencer. Manufactured from galvanised sheet steel and insulated with a 50 mm rockwool sheet and a perforated inner plate. The roof curb is fitted with plastic piping and conduits for electric cables. A roof curb with 100 mm insulation (corresponding to A60 insulation) is available on request.

Accessories

A
C D

TG 540-800 E 323 326 F 230 138 G 72 76 D 160 200 640-800 540-1230 640-1230 1140-800

A 800 800 1230 1230 800

B 494 594 494 594 1094

D 450 535 450 535 1040

THS
A B

A 455 585

B 480 735

160 200

THB 160 200

A 260 560 E 323 326

B 375 684 F 230 138

C 448 430 G 72 76

D 448 500 D 160 200

Hole measurement in roof = B+10 mm

TG 740-1200 940-1200

A 1200 1200

B 694 894

C 655 840

D 590 750

Hole measurement in roof = B + 10 mm

373

Accessories BTG
Back draft damper
Back draft damper designed for the TG 300-800, TG 400500, TG 400-800 and TG roof curbs, which can be fitted as long as the roof curb is installed vertically. The frame and damper vanes are manufactured from galvanised sheet steel. The frame is screwed or riveted on to the roof curbs perforated inner casing.

FDS

Flat roof socket

SSD

FDS is manufactured from seawater resistant aluminium and is supplied ready for assembly with insulation up to 100C. Suitable for DVS/DHS, DVSI, DVN, DVNI, DVC, DVEX. Supplied with washers and screws.
F E

Roof unit socket silencer


For special low noise requirements at the inlet side. The sound absorption at 250 Hz is in average 8 dB. The SSD is manufactured from seawater resistant aluminium. The sound absorbing material is abrasion resistant up to a velocity of 20 m/s. The baffles can be removed for service options. Suitable for DVS/ DHS, DVSI, DVN, DVNI, DVC, TFSK and DVEX.

h6

5 10

H D

FDS 190/225 310/311

D 245 330 450 450

E 294 395 478,5 555 625 nut M M6 M6 M10 M10 M10

F 730 817 898 977 997 h6 300 300 300 300 300

G 258 345 430 505 565 SSD 190/225* 310/311** 315M/L*** 355/400 450/499/500 560/630 710 800/900 D 245 330 450 450 535 750 840 1050 nut M 190/225* 310/311** 315M/L*** 355/400 450/499/500 560/630 710 800/900 M6 M6 M10 M10 M10 M10 M10 M12 E 294 395 478 555 625 895 985 1205 h7 400 500 650 650 650 700 800 1000 F 571 710 797 874 900 1200 1300 1540 G 258 345 430 505 565 835 925 1145

Accessories

315M/L TFSK 355/400

450/499/500 535 H 190/225 310/311 315M/L TFSK 355/400 452 553 638 713

450/499/500 783

pressure drop no 1 2 3 3 4 5 6 7

* also suitable for TFSK 125 M/L ** also suitable for TFSK 160 and 200 *** suitable only for TFSK 315 M/L

FDS 560/630 710 800/900

D 750 840 1050 nut M

E 895 985 1205 h6 300 300 300

F 1147 1300 1540

G 835 925 1145

560/630 710 800/900

M10 M10 M12

374

Accessories
Pressure drop

ASF
SSD 190/225 SSD 310/311 SSD 315 TFSK SSD 355/400 SSD 450/499/500 SSD 560/630 SSD 710 SSD 800/900 1 2 3 3 4 5 6 7

Inlet flange
Counterflange for connection to a duct system. Manufactured from galvanized steel. Suitable for DVS/DVSI, DHS, DVN/ DVNI up to 120C.

SSD 190-500

Attenuation [dB]

SSD 560-900

ASF 190/225 310/311 355/500 560/630 710

da 235 306 464 639 708 910

e 213 285 438 605 674 872

di 183 256 402 569 634 797

h2 25 25 30 30 30 30

zxd 6 x 7 6 x 7 6 x 9 6 x 9 6 x 9 6 x 10

Frequency [Hz]

800/900

Accessories

CCM

Inlet connection MUB


Reduction from square to round for easy connection of accessories on the inlet side. The CCM is manufactured galvanized steel. The circular side has a double sealing for easy installation to the duct system. This accessory should already be pre-assembled ex factory to the fan.

CCM

Circular connection, outlet MUB


Reduction from square to round for easy connection of accessories on the outlet side. The CCM is manufactured galvanized steel. The circular side has a double sealing for easy installation to the duct system.

CCMI

Circular connection isolated, outlet MUB


Reduction from square to round for easy connection of accessories on the outlet side. The CCMI double skin panel with 20mm mineral wool insultion is from manufactured galvanized steel. The circular side has a double sealing for easy installation of the duct system.
n5

nx

n5

nx

n da

n di

nd

nd

1.5

ol

17.8

CCM MUB042 d400 MUB042 d500 MUB062 d560 MUB062 d630

di 400 500 560 630

da 440 540 600 670

h 75 75 75 75

CCM MUB042 d400 MUB042 d500 MUB062 d560 MUB062 d630

d 400 500 560 630

I 588 588 718 718

CCMI MUB042 d400 MUB042 d500 MUB062 d560 MUB062 d630

d 400 500 560 630

I 588 588 718 718

375

ol

Accessories LGV/LGH
Roof cowl
The roof cowl LGV/LGH as supply or exhaust cowl. Empty (no motor impeller) casing of model DVS/DHS/DVN roof fans. Dimensions are equivalent to the size of the roof fans.
Pressure drop characteristic curve no. LGV 190/225 LGV 310/311 LGV 355/400 LGV 450/499/500 LGV 560/630 LGV 710 LGV 800/900 1 2 3 4 5 6 7

1 2 3 4 5 6 7
1000 500 Pressure drop in Pa 300 200 100 50 20 200

500 1000 5000 10000 40000 Air volume in duct m/h

1 2 3 4 5 6 7
1000 Pressure drop in Pa 500 300 200 100 50 20 200

Accessories

500 1000 5000 10000 40000 Air volume in duct m/h

1 2 3 4 5 6
1000 500 Pressure drop in Pa 300 200 100 50 20 200

500 1000 5000 10000 40000 Air volume in duct m/h

1 2 3 4 5 6
1000 500 Pressure drop in Pa 300 200 100 50 20 200

500 1000 5000 10000 40000 Air volume in duct m/h

376

Accessories SSVE, SSVE/F


Roof socket silencer for DVV/120, DVV/F
The socket silencers SSVE/F are suitable for pitched roof constructions up to a max. angle of 20. Angle can be adjusted on the silencer. Casing manufactured from galvanized steel, insulation/baffles of mineral wool with a textile lining. For versions .../F (smoke extract) the baffles are secured with an additional metallic guard. The surface of the baffles is abrasion resistant. Silencers come complete with nuts at the bottom to fix further inlet-side accessories. Supplied with sealing between socket and fan. Attention! Automatic shutters VKVE/F, VKV/F cannot be installed into the silencer. Pressure drop

SSVE, SSVE/F 400 450/560 630/800 1000 SSVE, SSVE/F 400 450/560 630/800 1000

A1 535 685 975

A2 460 600 880

M 12 12 16 16

E 447 597 884

Noise reduction [dB]

Pressure drop dp [Pa]

Noise reduction

Accessories

496 646 936

Frequency [Hz]

1120 1040 H 750 800 900 950

1029 1079 SSVE-F, kg 43 59 108 133

SSVE, kg 35 48 90 111

FDG/F

h6

Flat roof socket FDG/F is made of aluzinc steel sheet supplied with 40 mm mineral wool insulation with coated fabric. Additional guard for insulation protection. For use up to 400C medium temperature. Inclusive sealing between fan and socket. Suitable for DVG-H, DVG-V.

h6

Flat roof socket for DVG

F E

F E

10

D M10

H D M10

FDG/F 315-355 400-450 500-560 630 800

D 450 535 750 840 1050

E 555 625 895 985 1210

F 977 997 1147 1300 1540

G 505 565 835 925 1120

H 713 783 -

nut M M10 M10 M10 M10 M12

h6 300 300 300 300 300

kg 17 20 35 39 45

377

Accessories FDGE/F
Roof socket for DVG
The roof sockets FDGE/F are suitable for pitched roof constructions up to a max. angle of 30. Angle of supports and height above roof can be adjusted on the socket - 3 positions to fasten and rotate the supports. Casing manufactured from aluzinc steel sheet, insulation of mineral wool with a textile lining. Insulation is secured with an additional metallic guard. The surface of insulation is abrasion resistant. Supplied with sealing between socket and fan.

SSG/F

F E

Roof socket silencer for DVG


The socket silencers SSG/F are suitable for mounting on flat roofs. Casing made from aluzinc steel sheet, insulation/ baffles of mineral wool with textile lining. Insulation 40 mm thick on side walls is secured with an additional metallic guard. The sound absorption at 250 Hz is in average 8 dB. Silencers come complete with nuts at the bottom to fix further inlet side accessories. Supplied with appropriate high-temperature sealing between socket and fan. Suitable for DVG-H, DVG-V fans.
h7

D M

SSG/F 315/355 400/450 500/560 630 800

D 450 535 750 840 1050 nut M

E 555 625 895 985 1210 h7 650 650 700 800 1010

F 874 900 1200 1300 1540 kg 41 46 72 90 115

G 472 538 808 898 1120

315/355 400/450 FDGE/F 315-355 400-450 500-560 630 800 A1 562 628 898 990 1210 A2 450 535 750 840 1050 A3 526 596 866 956 1174 H 1200 1200 1200 1200 1200 kg 43 48 68 74 92 500/560 630 800

M10 M10 M10 M10 M12

Pressure drop
100

Accessories

SSG/F - SSGE/F
Pressure drop (Pa)

315 - 355

400 - 450

500 - 560

630

800 Air volume (m3/h)

10 1000 10000

Sound attenuation

378

Accessories SSGE/F
Roof socket silencer for DVG
The socket silencers SSGE/F are suitable for pitched roof constructions up to a max. angle of 30. Angle of supports and height above roof can be adjusted on the silencer - 3 positions to fasten and rotate the supports. Casing manufactured from aluzinc steel sheet, insulation/baffles of mineral wool with a textile lining. The baffles are secured with an additional metallic guard. The surface of the baffles is abrasion resistant. Supplied with sealing between socket and fan. When ordered together with DVV fan, the marking of the fan is DVVI. Observe additional weight from table, when fitted to DVV. Fastened in the corners to the roof base (dimensions of roof base and position of bolts are the same as for DVV alone). HSDV can be mounted instead of ordinary casing afterwards too (exception: DVV-Ex), but connection box rsp. service switch should be dismounted to fit the casing to cooling duct. New labels are needed. Noise attenuating 7 to 8 dBA.

FSL

Flaps for snow load, DVV roof unit

Suitable for DVV smoke and heat extract fans. Smoke and heat extract unit DVV with FSL for buildings with snow load requirement SL 1000. Suitable for temperatures from ambient up to 600C/2h. SL 1000 according to EN 12101-3. Flaps made from hot-dip galvanized steel sheet. Vertical exhaust. Tested according to EN 12101-3 at TU Munich for temperatures up to 600C/2h. Recommended to order factory mounted on the fan.
B

HSDV SSGE/F A1 A2 450 535 750 840 A3 526 596 866 956 H1 370 370 390 490 600 H kg 400 450/560 630 800 800 M,P 4 pole 1000

A 573 723

G 730 830

m kg

m1 kg

closed

200 732 220 908

18 14 25 19

315-355 562 400-450 628 500-560 898 630 800 990

1200 50 1200 55 1200 86 1200 98 1200 135

1023 175 1200 1050 45 30 1023 230 1432 1163 66 44 1023 200 1516 1353 80 54 1183 245 1660 1480 96 68 FSL 450 560 A 800 800 910 1050 1050 1280 1420 B 550 550 550 700 700 927

HF

Accessories

1210 1050 1174

opened
HF* E 210 305 235 305 285 400 285 428 285 428 295 446 kg** 26 27 35 47 50 59 66 67 68

Pressure drop and sound attenuation on page 378

1000 M,P 4 pole 1183 314 1660 1480 96 40

HSDV 400 450/560 630 HSDV 800

Suitable for DVV/F400, F600, DVV/120, DVV-Ex DVV 400 DVV 450, 560, DVV-Ex 560 DVV 630-K, DVV 630, DVV-Ex 630-K, DVV-Ex 630 DVV 800-K, DVV 800, DVV 800 M, P 6 pole, DVV-Ex 800-K, DVV-Ex 800 DVV 800D4-M, P, 4-8-M, P, 4-6-M, P DVV 1000, DVV 1000D6-M, P, 6-8-M, P, DVV-Ex 1000 DVV 1000D4-M, P, 4-8-M, P, 4-6-M, P

630 800 K 4 pole 800 800 M, P 1000

1090 273 466 1090 273 466 1090 273 466

1000 M, P 6 pole 1420 1000 M, P 4 pole 1420

HSDV 800 M,P 4 pole HSDV 1000 HSDV 1000 M,P 4 pole

* HF - additional height of DVV ** Additional weight of DVV, when FSL mounted

FSL 450 560 630 800 K 4 pole 800 800 M, P 1000

Suitable for DVV/F400, F600 DVV 450 DVV 560 DVV 630, DVV 630-K DVV 800D4-K, 4-8-K, 4-6-K DVV 800D6, 6-8, 6-12, 6-K, 6-8-K, 6-12-K, 6-M DVV 800D4-M, P, 4-8-M, P, 4-6-M, P DVV 1000D6, 6-8, 6-12, 8, 8-12

HSDV

Octagonal discharge silencer for DVV roof unit


From AlMg3, built as silencer to outlet, vertical exhaust (photo: DVV/F). Suitable for DVV/120, DVV/F400 and DVV/F600. Certified together with DVV/F according to EN 12101-3. With some additional details suitable also for DVV-Ex (only factory mounted possible). Insulation of 50 to 80 mm mineral wool with glass mat, perforated steel sheet for protection of insulation, holes for water outlet.

Note 1: m (kg) - weight of HSDV alone, without fan. Note 2: m1 (kg) - additional weight of fan, when HSDV mounted instead of original casing. Note 3: E* for 1000-P 4 pole only (2 cooling ducts). Note 4: E** for DVV 400 - 630 (cooling duct 45 to axis). Note 5: FSL snow load flaps for HSDV resp. DVVI on request. Note 6: DVVI-Ex without cooling ducts, connection box on casing.

1000 M, P 6 pole DVV 1000D6-M, P, 6-8-M, P 1000 M, P 4 pole DVV 1000D4-M, P, 4-8-M, P, 4-6-M, P

379

Accessories ASK, ASK/F, ASG/F


ASG/F 315-355 400-450 500-560 630 800 A 545 615 885 975 1205 H 315-355 400-450 500-560 630 800 526 596 866 956 1174 D 438 438 605 674 872 I 214 241 471 508 600 E 402 402 569 634 800 K 235.5 254 300 F 6xM8 6xM8 6xM8 6xM8 8xM8 L 200 200 250 300 300 G 4x9 4x9 6x9 6x9 6x9 kg 5 5 13 17 22

Plenum box

ASK, for mounting on SSD socket silencers to fix inlet accessories and duct system. Made of seawater resistant aluminium. The plenum box ASK/F is used for connection of inlet accessories and duct system. The ASK/F is manufactured from galvanised steel. ASK/F can be used together with roof sockets (SSVE-SSVE/F, SSV-SSV/F, FDV-FDV/F), flexible connections (ASSV-ASSV/F, ASSV-EX) and shutters (VKV/F, VKVE/F, VKVM, VKSVEX). The plenum box ASG/F is used for connection of inlet accessories and duct system. The ASG/F is manufactured from aluzinc steel sheet. ASG/F can be used together with roof socket SSG/F, SSGE/F, FDGE/F, flexible connections ASSG/F and shutter VKG/F.

VKS/VKM da e 190/225 310/311 355-500


L

di

h4

l1

zxd 6x8x12

235 217 183 306 286 255 464 438 406 639 605 573 910 872 801 da e di

115

156 210 6x10 220 290 6x10 255 375 8x10 340 500 8x10 h4 l1 zxd 6x7 6x9 8x9 zxd 12x12 16x12 16x12

560/630 710 800/900 VKS-EX 315 355-500 560/630 VKSV-EX 630 800 1000

708 674 638.5 250 400 8x10

Accessories

ASK 190/225 310/311 315 TFSK 355/400 450/500 560/630 710

A 290 385 474 551 621 891 981 H

D 213 285 285 438 438 605 674 I 114 152 179 214 241 508

E 183 256 256 402 402 569 634 K 254

F 6x7 6xd7 6x8 6x9 6x9 8x9 8x9 L 110 110 110 110 110 110

G 4x7 4xd9 4x9 4x9 4x9 4x9 6x9 kg 0.9 1.2 2 2 2.2 3.9 5

306 285 256 464 438 402 639 605 569 da e di

156 220 255 h4 l1

190/225 310/311 315 TFSK 355/400 450/500 560/630 710

272 366 449 526 596 866 956

Automatic and motor driven shutter


The automatic shutter VKS consists of flanges manufactured from galvanized steel, and of shutter blades manufactured from seawater resistant aluminium. Suitable for DVS/DHS, DVSI, DVN. VKM motor driven shutter consists of flanges manufactured from galvanized steel, and of shutter blades manufactured from seawater resistant aluminium. Is equipped with a servo motor (230V/50Hz/25W), which can be operated manually as well as through the automatic controllers of the air conditioning unit. While the motor is energized the shutter stays open. When separated from the supply the shutter will close automatically. Temperature approx 70C. Suitable for DVS/DHS, DVSI, DVN. The automatic shutter VKS-EX/VKSV-EX consists of flanges manufactured from galvanized steel epoxy painted RAL 9005, and of shutter blades manufactured from painted galvanized steel RAL 9005.

VKS, VKM, VKS-EX, VKSV-EX

584 541 504.5 255 708 674 638 255 814 751 711.5 350

235.5 233.5 110

ASK/F 400 450 560 630 800 1000

A 522 672 672 962 962

D 356 395 438 541 674

E 322 360 404 507 636 713 L 200 250 250 300 350 350

F 8xM8 8xM8 12xM8 12xM8

G 10 10 10 10

H 496 646 646 936 936 1079

16xM10 10 16xM10 10 n 1 1 1 2 2 2 kg 6 10 10 19 19 24

1105 751 I K 125 160 160 160 160 180

400 450 560 630 800 1000

380

Accessories
Pressure drop VKS
VKV/VKM 190/225 VKV/VKM 310/311 VKV/VKM 355/400 VKV/VKM 560/630 VKV/VKM 710 VKV/VKM 800/900 1 2 3 4 5 6

ASS

Flexible connection

Manufactured from galvanised sheet steel, with neoprene coated fabric. For temperature up to 70C. Suitable for DVS/DHS, DVSI, DVN, DVNI, DVC, DVEX, DVV-EX.

Pressure drop VKS-EX


ASS/ASS-EX VKS-EX 310/311 VKS-EX 355/500 VKS-EX 560/630 2 3 4 190/225* 310/311* 355-500* 560/630* 710 800/900 ASSV-EX 630 800 1000 da 235 306 464 639 710 910 da 584 708 814 e 213 285 438 605 674 872 e 541 674 751 di 183 256 402 569 634 797 di 504 638 711 h3 155 155 155 155 155 155 h3 155 155 155 zxd 6x7 6x7 6x9 8x9 8x9 8x10 zxd 12x12 16x12 16x12

Accessories

*ASS and ASS-EX

FDV, FDV/F
Pressure drop VKSV-EX
VKSV-EX 630 VKSV-EX 800/1000 4 6

Flat roof socket for DVV/120, DVV/F


The flat roof socket FDV is manufactured from galvanized steel supplied with 40 mm mineral wool insulation with coated fabric. The sealing between fan and socket is provided.

A1 A2 M

E G B

4xM8

381

350

Accessories
FDV, FDV/F 400 450/560 630/800 1000 A1 535 685 975 1120 A2 460 600 880 1040 B 720 870 1160 1400 FDV kg 17 21 41 52 M 12 12 16 16 FDV/F kg 19 24 45 63

SSV, SSV/F

A1 A2

Socket silencer for DVV/120, DVV/F


The socket silencers SSV are suitable for mounting on flat roofs. Casing manufactured from galvanized steel, insulation/baffles of mineral wool with a textile lining. For versions .../F (smoke extract) the baffles are secured with an additional metallic guard. The surface of the baffles is abrasion resistant. Silencers come complete with nuts at the bottom to fix further inlet-side accessories. Supplied with sealing between socket and fan. Attention! Automatic shutters VKVE/F, VKV/F cannot be installed into the silencer.

400 450/560 630/800 1000

444 594 879 1023

496 646 936 1079

M8

SSV, SSV/F 400 450/560 630/800 1000

A1 535 685 975

A2 460 600 880

B 720 870

30

480

FDV, FDV/F

M 12 12

H 750 800 900 950

1160 16

1120 1040 1400 16 SSV SSV/F kg 39 55 107 136

SSV, SSV/F 400 450/560 630/800 1000

E 444 594 879 1023

G 496 646 936 1079

kg 35 48 95 123

Accessories

FDVE, FDVE/F
Roof socket for DVV/120, DVV/F
Flat or inclined roof socket up to 20 inclination. Manu factured from galvanized steel, supplied with insulation, mineral wool 40 mm with coated fabric. Sealing tape between fan and socket attached. Profiles adjustable up to 20, to be adjusted to inclination of the roof at site. Pressure drop

FDVE/FDVE/F 400 450/560 630/800 1000

A1 535 685 975

A2 460 600 880

E 447 597 884

G 496 936 1079 FDVE/F kg 37 47 86 105


Frequency [Hz] Noise reduction [dB]

646

1120 1040 1029 FDVE kg 32 41 73 92

FDVE/FDVE/F 400 450/560 630/800 1000

H 750 800 900 950

M 12 12 16 16

382

Pressure drop dp [Pa]

Noise reduction

Accessories ASSV, ASSV/F, ASSV-EX ASSG/F


VKV/F, VKG/F

Flexible connection for DVV/DVV-EX roof unit


The flexible connections prevent transmission of eventual vibrations to the duct system. The flanges consist of galvanized steel. The flexible connecting piece consists of resistant neoprene in the standard version ASSV. The smoke extract version ASSV/F consists of aluminium-foil coated high temperature resistant glass fibre. The smoke extract version was tested together with the DVV range in accordance with EN 12101-3. ASSV/EX is manufactured from galvanised sheet steel, with neoprene coated antistatic fabric. For temperature up to 70C. Suitable for DVV-EX.

Flexible connection for DVG roof unit

d2 e d

n x d3

The flexible connections prevent transmission of eventual vibrations to the duct system. The flanges consist of galvanized steel. The smoke extract version ASSG/F consists of aluminium-foil coated high temperature resistant glass fibre. Suitable for the DVG range in accordance with EN 12101-3 (F400 - 400C, 2 hours).

VKVE/F

d2 e d

n x d3

ASSG/F 315-450 500/560 630 800

d 402 569 638 797

e 438 605 674 872

d2 475 652 723 910

nxd3 6X9 8X9 8X9 8X10

kg 4 7.5 10.2 12

VKV/F, VKVE/F 400 450 560 630 800 1000 VKG/F

d2

nxd3

H kg 4.3 5 6 9 322 356 386 360 395 425 404 438 468 507 541 571 636 674 712 713 751 789 d e d2 160 8x9.5 175 8x9.5 180 12x9.5 250 12x9.5 290 16x11.5 15 350 16x11.5 20 H nxd3 kg 6 11 15 22

ASSV (/F) 400 450 560 630 800 1000

d 322 361 404 507 638 715

e 356 395 438 541 674 751

d2 382 421 464 567 712 795

nxd3 8X9.5 8X9.5 12X9.5 12X9.5

kg 2.9 3.1 3.5 4.5

VKV/F, VKVE/F, VKG/F

315-450 404 438 468 500-560 569 605 643 630 800 636 674 712 797 872 903

180 6x9 240 8x9 290 8x9 330 8X10

Accessories

Automatic shutter

16X11.5 10.2 16X11.5 11

VKV/F and VKVE/F for roof fans DVV F400, F600 and 120 (not DVV-Ex), VKG/F for roof fans DVG. The casing and blades are manufactured from galvanized steel. Pressure drop VKV/F - VKVE/F
Pressure drop (Pa)

VKV/F - VKVE/F

100

400 400

450

560

630 800
10000

1000

ASSV-EX 630 800 1000

da 584 708 814

di

h3 155 155 155

zxd 12x12 16x 12 16x12

Air volume (m3/h)

541 504 674 638 751 711

10

Pressure drop VKG/F


VKG/F
Pressure drop (Pa)

100

315 - 450

500 - 560

630

800 Air volume (m3/h)

10 1000 10000

383

Accessories VKVM
Motorized shutter
VKVM motor driven shutter. Suitable for roof fans DVV/120. Temperature of use up to app. 70C. The flap of VKVM is made of galvanised steel. With direct coupled 230V/50Hz ONOFF spring return actuator. The flap opens when applying supply voltage. If the power supply is interrupted, the flap closes. Manually operating possible.

ESDV

RSA (F)
Silencer
The RSA effectively reduces noise in the duct. For the most effective noise reduction, the silencer should be fitted immediately behind a fan or bend. For axial fans AXC.
F I

Inlet cone DVV


For use together with the roof fan DVV. To improve aerodynamic flow with free inlet. The inlet cone is manufactured from galvanised steel. Additional to VKV/F or to duct inlet.

d2 d1 B n x d3

ESDV 400 450


D d A

d 322 360 404 507 636 713

e 356 395 438 541 674 751

d2 369 407 451 586 716 811

H 160 175 180 250 290 350

nxd3 8x9,5 8x9,5 12x9,5 12x9,5 16x11,5 16x11,5

kg 4,3 5 5,7 9 15 19

RSA (F) I 315 355 400 450 500 560 630 710 800 900 1000 1120 1250 315 355 400 450 500 560 630 710 800 900

E 455 495 540 610 660 720 790 870

F 355 395 450 500 560 620 690 770

AxB 8xM8 8xM8 8xM10 8xM10

L 315, 472.5, 630 355, 532, 710 400, 600, 600 450, 675, 900

560 630 800 1000

12xM10 500, 750, 1000 12xM10 560, 840, 1120 12xM10 630, 945, 1260 16xM10 630, 945, 1260 16xM10 800, 1200, 1600 16xM12 900, 1350, 1800 1000, 1500, 2000 1120, 1680, 2240 1250, 1875, 2500

VKVM 400 450 560 630 800 1000

d 322 360 404 507 636 713 B

d1 356 395 438 541 674 751 C 190 190 190 250 250 250

d2 386 425 468 571 712 789 D 260 280 305 365 445 485

nxd3 8x9.5 8x9.5 12x9.5 12x9.5

A 100 120 140 105

1000 860 1100 970

Accessories

16x11.5 170 16x11.5 210 H 250 250 250 395 395 395 kg 5.8 6.5 7.2 10.3 22 25

1000 1200 1070 16xM12 1120 1320 1190 20xM12 1250 1450 1320 20xM12

400 450 560 630 800 1000

0 0 10 0 65 105

ASFV

Noise suppression dB frequency band Hz I/L 315/315 315/472.5 315/630 355/355 355/532 355/710 400/400 400/600 400/800 450/450 450/675 450/900 500/500 500/750 500/1000 560/560 560/840 560/1120 630/630 630/945 315-450 500-560 630 630/1260 710/710 710/1065 710/1420 800/800 800/1200 800/1600 125 250 500 1 k 1 2 6 0 0 2 0 1 2 1 1 1 0 1 2 0 2 1 1 2 2 1 2 4 3 5 6 3 5 6 3 5 6 4 5 7 4 6 7 4 6 8 4 7 9 5 7 9 5 7 9 7 10 13 8 12 16 9 12 15 10 14 18 12 17 21 13 18 23 14 20 24 14 20 25 12 18 24 9 13 22 14 19 26 14 21 25 13 19 24 12 17 21 11 17 21 11 15 19 10 14 17 9 11 14 8 12 14 2k 9 13 17 10 13 16 8 12 15 9 13 15 9 12 14 8 11 14 9 12 14 7 9 11 6 9 10 4k 8 11 13 8 11 12 8 10 12 6 9 10 6 9 11 5 8 10 5 8 10 5 6 8 5 7 9 8k 7 8 9 6 9 10 5 8 9 6 8 8 5 7 8 4 5 7 5 6 7 5 7 8 4 7 7

Inlet flange
Counter flange for connection to a duct system or to the accessories. Manufactured from galvanized steel. Suitable for DVV, DVG fans and accessories.

ASFV 400 450 630 G500-560 V800/G630 1000 ASFV 400 450 V560/G315-450 630 G500-560 V800/G630 1000

d 322 361 505 569 638 712 kg 0,8 0,9 1.3 1.8 2.1 2.4 2.8

e 356 395 438 541 605 674 751 for DVV 400 450 560 630 800 1000

d2 390 428 475 577 652 723 802 for DVG

nxd3 8X9,5 8X9,5 12X9,5 12X9,5 16X12 16X12 16X12

V560/G315-450 402

384

Accessories
Noise suppression dB frequency band Hz I/L 900/900 900/1350 900/1800 125 250 500 1 k 3 5 6 7 11 14 8 12 16 8 12 15 9 12 17 13 16 23 12 17 23 13 18 23 13 17 22 8 11 13 8 10 12 7 8 10 7 8 10 2k 6 7 9 4 6 7 5 6 7 4 5 6 4k 5 7 7 4 6 7 4 5 6 4 5 6 8k 4 5 6 4 5 6 3 4 6 3 4 5
D SW C B

SD

Vibration damper
Rubber-metal-bearing for active and passive vibration- and impact sound isolation. Suitable for temperatures from -40C up to 70C.
G A F E

1000/1000 3 1000/1500 5 1000/2000 6 1120/1120 3 1120/1680 5 1120/2240 6 1250/1250 3 1250/1875 6 1250/2500 8

Protection guard

SG AR/ AXC, SGAW

Finger protection guard for axial fans AR, AXC and sizes 710, 800 and 1000 for AW. Powder coated in black.

SD

A 45 70 105 E 15 27 45

B 35 50 80 F M6 M10 M16

C 30 45 70 G 60 90 140

D 6 9 13 SW 11 17 24 SG AR/AXC 315 355 400 450 500 560 630 710 800 900 1000 1120 1250 B 355 395 450 500 560 620 690 770 860 970 1070 1190 1250 45 45 45 45 30 30 30 22.5 22.5 22.5 22.5 18 18 kg 0.5 0.8 1.5 2 1.3 1.4 1.7 2.5 3 2.5 5 3 6

LRK(F)

315-450 500-630 710-1000 SD 315-450 500-630 710-1000

Automatic shutter
The casing and flaps are manufactured from galvanized steel. For axial fans AXC up to temperatures of 400C/2h.
LK L U

z x d

Da Di

Accessories

LRK(F) 315 355 400 450 500 560 630 710 800 900 1000 1120 1250 LRK(F) 315 355 400 450 500 560 630 710 800 900 1000 1120 1250

da 398 438 484 534 584 664 734 812 904 1004 1105 1242 1350 L 250 250 250 250 250 250 250 350 350 350 350 350 400

di 320.5 359.5 401.5 450.5 504.5 565.5 634.5 711 797.5 894 1122

LK 355 395 450 500 560 620 690 770 860 970 1190

zxd 8x10 8x10 8x12 8x12 12x12 12x12 12x12 16x12 16x12 16x15 16x15 20x15 20x15 SG AW 710 800 900 1000 A d1 d2 856 979 d3 9 9 9 9 E 835 960 1115 1140 4x90 782 4x90 901

1003.5 1070 1250.5 1320 U 13.6 35 64.8 101.2 39.3 83 134 180 245 249 W 0 5 5 5 15 15 15 15 15 15 15 15 15

4x90 1030 1134 4x90 1110 1161

LRK (F) Pressure drop


300 [Pa] 280 260 240 220 200 180 160 140 120 100 80 60 40 20 0 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 [m/s]

385

Accessories FSD
Spring-mount AXC/set

SG AW-D

Protection guard
For axial fans AW, to be mounted at the inlet side. Powder coated in black.
A B

D2

D1

D3

Spring damper for active and passive vibration- and impact sound isolation. Steel spring vibration isolators consist of two spring elements with M10 internal thread and a cylindrical screw spring designed according to DIN EN10270-1:2001. For the selection of FSD the weight-force (in N) at the point of support and the oscillation frequency (1/min) is needed.

Mounting feet

MFA-AR/ AXC

For axial fans of range AR sileo and AXC. The mounting feet MFA-AR/AXC are manufactured from hot dip galvanized steel. MFA 315-450

TK

2,5

hf

D1
D2

C A
D2

95

11

94

MFA AXC
120 150

A 315 355 400 450

B 60 60 60 60

C 265 305 350 400

D4

E 30 30 30 30

F 25 25 25 30

12

315 355 400 450


D 70 M10

Spring damper

D2

TK 355 395 450 500

D1 10 10 12 12

W 45 45 45 45

hf 235 250 280 315

High without load

SG AW-D
95 11

A 154 145 187 184


120 223

B 95 64 131 83 120 127 152 D3 444 522 582 637 680 742 857

E 422 500 560 615 658 720 835 D4 7 7 7 7 7 7 9.5

D1 380 431 487 539 597 682 743

315 355 400 450

14 14 16 16

350 400 450 500 560 630 710

Accessories

Base plate
12

94

231 295 D2

150

MFA 500-1250

hf

TK

s W

350 400 450 500

387 424 455 522 569 677 702

D1

D2

C A
D2

ZSD

560 630 710

Tension Load Spring damper


Spring damper for active and passive tensile vibration loads and sound insulation. Unit consists of a rectangular tube housing, a spring element and two connection nuts with M10 internal thread for threaded rods. The cylindrical screw spring is designed according to DIN EN10270-1:2001.
100 x 73 M10

MFA AXC 500 560 630 710 800 900 1000 1120 1250 s 500 560 630 710 800 900 1000 1120 1250

A 500 560 630 710 800 900 1000 1120 1250

B 70 70 70 70 80 80 80 80 100 TK 560 620 690 770 860 970 1070 1190 1320

C 440 500 570 650 730 830 930

E 35 35 35 35 40 40 40

F 45 35 35 35 40 40 40 50 50 hf

D2 16 16 16 18 18 18 18 18 18

1030 40 1180 50 D1 12 12 12 12 12 15 15 15 15 W 30 30 30 22.5 22.5 22.5 22.5 18 18

Cable gland set


A2F/25/M25 EXD Cable Glands Ex d and Ex e
190

3.0 3.0 3.0 5.0 5.0 5.0 5.0 5.0 5.0

335 375 425 450 530 560 670 710 800

120

M10

Suitable for use with normal unarmoured offshore and onshore cables. Included gasket and counter nut.

386

Accessories EV-AR/AXC EV-EX/AXC


L

W1
zxd2

W2

MP

zxd1

Mounting brackets
Da (auen) Di (innen)

Flexible connections
For axial fans of range AR/AXC. The flexible connections consist of 2 counter flanges made of galvanized steel with flexible neoprene coated fabric in between.
Tk2 Tk1

For vertical mounting of axial fans. Manufactured from hot dip galvanized steel. Four piece needed.

Tk

EV/EX 315 355 400

Da 390 428 475 524 577 652 723 802 890

Di 322 361 402 455 505 569 638 712 797

TK1 355 395 438 487 541 605 674 751 837 934 W2 22.5 22.5

zxd1 8x10 8x10 12x9.5 12x9.5 12x9.5 16x12 16x12 16x12 24x12 24x12 L 154 154 154 154 154 154 154 154 154 154

W1 45 30 30 30 22.5 22.5 22.5 15 15 s 1.5 1.5 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.5 MP 315-355 400-450 500 560-630 710-800 900-1000 1120 1250 560-800 710 900-1250 1120 L
d

bM

45

450 500 560 630 710 800 900

T 128 128 133 133 133 140 157 157 136 133 155 157

bM 70 75 80 120 120 130 120 150 120 120 120 120

d 17 17 17 17 17 17 17 17 17 17 17 17

369.5 444.5 535 743 693 629 695 1038 493 794 840 991

1000 894 TK2 zxd2 8x12 8x12

315 EV-AR 200 250 315 355 400 450 500 560 630 710 800 900 1000 1120 1250 Da 250 328 390 435 480 534 585 652 723 802 890 1005 1105 1225 1370 Di 201 251 322 361 402 455 505 569 638 712 797 903 1003 1122 1250 L 153 153 153 153 154 154 154 154 154 154 155 162 165 166 165 zxd 4x7 4x10 8x10 8x10 8x12 8x12 12x12 12x12 12x12 16x12 16x12 16x15 16x15 20x15 20x15 TK 225 280 355 395 450 500 560 620 690 770 860 970 1070 1190 1320 355 400 450 500 560 630 710 800 900

450 500 560 620 690 770 860 970

12x12 15 12x12 30 12x12 30 16x12 11.25 16x12 11.25 16x14 11.25

Depends on casing length of Axial fan AXC

Accessories

387

Accessories EVH
Flexible connection EVH 400C

ESD-F

Inlet cone
The inlet cone is manufactured from galvanised steel

MFA-AXCBF
Mounting feet
For axial fans range AXCBF. The mounting feet MFA-AXCBF are manufactured from galvanized steel.

Flexible connection for axial fans AXC, for temperatures up to 400C/2h.

F
TK

da4 d1
n x d3
hf

9,

D
W
de

A
m x d4

Da

K L d

d2 da3

ESD-F
30 154

d1 355 395 450 500 560 620 690 770 860 970 1070 1190 1320 da4 398 438 484 534 584 664 734 812 904 1004 1105 1242 1370

de 320 359 401 450 504 565 634 711 797 894 1003 1122 1250 H 160 160 160 160 160 160 160 160 160 160 160 160 160

d2 395 450 500 560 620 690 770 860 970 1070 1190 1320 1470 nxd3 8x10 8x10 8x12 8x12 12x12 12x12 12x12 16x12 16x12 16x15 16x15 20x15 20x15

da3 438 484 534 584 664 734 812 904 1004 1105 1242 1370 1533 nxd4 8x10 8x10 8x12 12x12 12x12 16x12 16x12 16x15 16x15 20x15 20x15 20x15 12x12

315 355 400 450 500 560


L

MFA-AXCBF A 250 315 400 500 250 315 400 500 F 250 315 400 500 3 3 3 3

hf 250 250 315 362 H 25 25 30 42

C 60 60 60 70 I 4x12 4x14 4x16 4x16

D 210 265 350 440 J 2x10 2x10 2x10 4x12

E 35 45 45 60 TK 149 355 450 560

EVH 315 355


W1
zxd2

Da 390 435

d 322 361

LK 355 395

W 45 45
S

630 710 800 900 1000 1120 1250 ESD-F 315 355 400

W2

zxd1

Accessories

Da (auen)

Di (innen)

Tk2

Tk1

MFA 630-800

EVH 250 400 450 500 560 630 710 800 900

Da 328 480 534 585 652 723 802 890 1005

Di 251 402 455 505 569 638 712 797 903 1003 1122 1250 zxd2 8x10 8x12 8x12 12x12 12x12 12x12 16x12 16x12 16x15 16x15 20x15 20x15

TK1 280 438 487 541 605 674 751 837 934 1043 1174 1311 W2 90 22.5 22.5 15 15 15 11.25 11.25 11.25 11.25 9 9

zxd1 8x10 12x9.5 12x9.5 12x9.5 16x12 16x12 16x12 24x12 24x12 24x12 24x12 24x12 L 154 154 154 154 154 154 154 154 154 154 154 154

W1 45 30 30 30 22.5 22.5 22.5 15 15 15 15 15 s 1.5 2 2 2 2 2 2 2 2.5 2.5 2.5 2.5

500 560 630 710 800 900 1000 1120 1250

hf

450

TK

s W

D1

D2
F C A

D2
E

1000 1105 1120 1225 1250 1370 EVH 250 400 450 500 560 630 710 800 900 TK2 302 450 500 560 620 690 770 860 970

MFA -AXCBF A 630 800 s 630 800 3.0 5.0 630 800 TK 690 860

B 70 80 D1 12 12

C 570 730

E 35 40 W 30 22.5

F 35 40 hf 425 530

D2 16 18

1000 1070 1120 1190 1250 1320

388

Accessories GFL-AR/AXC
Counterflange
For axial fans of type AR and AXC. The counterflange GFL-AXC is manufactured from galvanized sheet steel.

EPSN/EPIN
Flexible connection (600C/2h) for WVA/WVI. The EPIN is a rectangular flexible connection for the outside of WVA/WVI smoke and heat extract fans. Fit to outlet connection IN. To avoid vibrations from the fan to the duct system. Applicable up to +/- 1000 Pa in cold condition and up to 600C/2h. Exclusive sealing tape and fasteners.

Rectangular flexible connection

WBK

Wall mounting bracket


For KBT/KBR close to the wall. Manufactured from galvanised steel. The corners are welded. Available in pairs. Suitable for KBT/KBR.
60 45 400 25 250 25

nxd3

2 x (13 x 16)

GFL-AR/AXC Da 315 355 400 450 500 560 630 710 800 900 1000 1120 1250 390 435 480 534 577 652 723 802 890 1005 1105 1225 1370

Di 322 361 402 455 505 569 638 712 797 903

Tk 355 395 450 500 541 620 690 770 860 970

A 30 30 30 30 35 35 35 35 35 52

nxd3 8x10 8x10 8x12

9,5

180

Da Ea x250

12x12 12x12 12x12 16x12 16x12 16x15 16x15 20x15 20x15

Ca

GFL-AR/AXCBF
Counterflange
The counterflange is manufactured from galvanized steel.
s

1000

800 Db

1180 43 Ea 1 3 B 500 710 710 800 Eb 1 1 3 3 Ca 286 286 158 195,5

233 kg 6 7 8 9 14 23 Cb 268 248 248 43 203 98 kg 6 7 8 9 12 22

836
H

400 450 560 630 800 1000 EPIN 400 450 560

536 536 666 746 936 1216 A 250 250 280 355 400 630 Db

Da

Di

n x D1 L

560 630 800 1000


1

746 836 1156 1446

1 3 3 5

50

100

Da

Di

2 TK
W1

TK

50

n x D2
n x D1 L

40 200

L/2

WBK-W W1 45 s 1.5 400 450 560 630 800 1000

L 938 1014 1105 1305 1570 1650

H 450 500 500 600 600 650

d 14 14 18 18 18 18

B 80 80 80 80 80 100

kg 20 22 23 28 31 38

GFL-AR/ AXCBF 250 GFL-AR/ AXCBF 250

Da 328 Tk2 280

Di

Tk1

zxD1 8x10 L 30

251.5 302 zxD2 4x10 W2 22.5

389

A
8x12
B 30 Cb Eb x250 150 Db

Cooling duct for WVI


The cooling duct ZHZ is manufactured from galvanized steel insulated with mineral wool. Has to be connected through the outside wall of the building. With protective cover for the cable leading to the terminal box.
B

ZHZ

1003 1070 55 1122 1190 55 1250 1320 55

EPSN 400 450 560 630 800

A 315 355 355 450 630

B 500 500 630 710 900

Ca 175.5 195.5 195.5 243 208

Cb 268 268 208 248 93

Da 351 391 391 486 666

Accessories

600 L

ZHZ 400/450 560/630 800/1000 Da 286 286 316 391 436 666

A 200 225 250

B 240 265 290

L 700 712 725

H 365 390 460

TK

WBK-W

630 zxD1 s 800 1000

GFLAR/ AXCBF 200

Da Di

Tk1 nxD1

1120 218 1400 208 Ea Eb 1

Wall mounting bracket


For the smoke extract fan WVA/WVI. Manufactured from powder-coated steel, RAL 7032. The delivery is in pairs.
d L

250 201

225

4x7
s

30

1.5 400 450

536 746

W2

Accessories
Outlet connection for WVA/WVI
The outlet connection IN is manufactured from hot-dip galvanized steel, with a protection guard. For mounting on the outlet of the fan WVI, if the outlet leads directly through the outside wall. For the type WVA as rain protection. Exclusive sealing tape and fasteners.

IN

9,5 A 30 D2 D2 B

ZTV/ZTR

Water valve/heating water, 2/3way


ZTV/ZTR is a 2 and 3-way control valve to control the hot water to the heating coil. They are intended for use together with the RVAZ4 24A actuator.

E1 x250

C2

C1

E2 x250 D1

Cb

E2 x250 m n

D2 L

SN 400
9,5

A 315 355 355 450 630

B 500 500 630 710 900

C1 175.5 195.5 195.5 243 208

C2 268 268 208 248 93 233 m 300 300 300 400 500 700

D1 351 391 391 486 666 836 n 150 150 150 200 300 400

D2 536 536 666 746 936 1216 kg 20 22 27 35 55 72

Technical data Flow charac. Media temp. Media Stroke Leakage Pressure class Rangeability Mat. Body Spindle Seat O-ring Percental increase 1...+110C Hot, cold, glycol mixed (max. 30% glycol) 5 mm 0% in closed position PN16 (1.6MPa) 50:1 Brass Stainless steel Brass EPDM

450 560 630

D1 E1 x250

800
B 30

1000 800 E1 400 450 560 630 800 1

1180 43 E2 1 1 3 3 L 800 850 950 1100 1450 1500

C1 C2

E2 x250

D2

45

1000 3
500

ZTV
C2 268 248 248 43 203 98 kg 15 19 20 24 32 53 D1 286 286 316 391 436 666 BDS 100 120 150 Length 55 mm 62 mm 77 mm

IN

A 250 250 280 355 400 630 D2

B 500 710 710 800

C1 286 286 158 195.5

Accessories

400 450 560 630 800 1000

Back draught shutter


Back draught shutter for bathroom fans.

42

BDS

1120 218 1400 208 E1 1 E2 1 1 3 3 5

I 60

400 450 560 630 800 1000

536 746 746 836 1156 1446

ZTR

BVK

Wall vent kit


Wall lead-through BVK. Consist of a flexible duct manufactured in aluminium and a wallgrid.

SN

Inlet connection for WVA/ WVI


The inlet connection SN is manufactured from hot-dip galvanized steel. For mounting on the inlet of the fan. The inlet flange of the fan is rectangular. The inlet connection can be rotated by 90. Exclusive sealing tape and fasteners.

ZTV/ZTR Connection G 15-0.25 15-0.4 15-0.6 15-1.0 15-1.6 BVK 100 120 150 E 140 160 180 D 100 125 150 20-2.0 20-2.5 20-4.0 20-6.0 DN15 DN15 DN15 DN15 DN15 DN20 DN20 DN20 DN20

h (only ZTR) 40 40 40 40 40

1/2 9 1/2 9 1/2 9 1/2 9 1/2 9

3/4 12.5 40 3/4 12.5 40 3/4 11.5 50 3/4 11.5 50

390

9 1 6a
Blue Black/Brown Yellow/Green
Counter Clockwise rotation

TK TK Z2 Z1 U2 U1

N L PE

10
Brown Blue Blue Black Yellow/ green Brown Black Yellow/green

Brown Blue Black Yellow/Green

230V3~ (D)

Wiring diagram

Wiring diagram

391

Wiring diagram 11 12

White

13a
Delta connection

White

13b
Delta connection
W2 U1 U2 V1 V2 W1

L1

L2

L3

PE

PTC/TK

Star connection

Star connection

W2 U1

U2 V1

V2 W1

Wiring diagram

L1

L2

L3

PE

PTC/TK

14a
W2 U2 V1 V2 W1

14b

Low speed
U1

W2

U2 V1

V2 W1

Low speed
U1

PTC/TK PTC/TK
W2 U2 V1 V2 W1

High speed
U1

W2

U2 V1

V2 W1

High speed
U1

392

Wiring diagram 15a


W2 U2 V1 V2 W1

15b, c
Low speed connection
U1

L1

L2
Y

L3

PE

L1
W2 U1

L2
U2 V1

L3
V2 W1

PE

High speed connection

16

17

Delta connection

Delta connection Low speed connection

Star connection

Star connection High speed connection

Wiring diagram

18

19

Delta connection

Delta connection

Star connection

Star connection

393

Wiring diagram 20 21

High speed

Low speed

U1 = blue U2 = black Z = brown

23a

23b

Net voltage

L N

Black Blue Green/yellow

L N PE

Net voltage

L N

Black

1-200-277V PE

1-200-277V PE

Blue Green/yellow N White White

PE NC COM

White Red
+ 0-10V P1 10k

Tacho +10V Exit 0-10V Inlet GND + 0-10V -

Error signal relay, COMMON (2A, 250 VAC)

Red
P1

Yellow Blue Motor

Yellow Blue Motor

+10V Exit 0-10V Inlet GND

External signal

External signal

Potentiometer

Potentiometer

10k

Wiring diagram

394

Wiring diagram 24
Pressure control Operation

Fan EC-

PE N L

Fan EC-

motor

motor

200-277 VAC 50/60 Hz

Mains

Mains 1

1 2 3 1 2 3 1 2 1 2

PE N L

Input

mode

Night 9

GND 10

GND 8 Day 7 GND 6 0-10V in 5 +10V 4 GND 3 0-10V out 2 Tacho in 1 3 2 1 GND 2 1
Red Blue Yellow White1 White2 Blue Black Green/yellow

Fan EC-motor
074/084 +10V GND 0-10V NC COM L N PE

Alarm relay Normally closed contact

Alarm relay

+20V in

Error signal relay, COMMON (2A, 250 VAC)

25
Pressure control

1 2 3 1 2 3 1 2 1 2

PE N L PE N L

Fan EC-

motor

GND 10 9 GND 8 7 GND 6 5 +10V 4 GND 3 2 1 3 2 1 GND 2 1

Operation

Fan EC-motor
112

mode

Alarm relay Normally closed contact

Alarm relay

12 11 10 9 8 7 6 5 4 3 2 1

Input

RS A RS B RS A RS B GND 0-10V KL.3 4-20mA +20V +10V 0-10V GND OUT

Wiring diagram

Mains

Fan EC-

motor

3 NO 2 COM KL.2 1 NC 2 L 1 N PE

L N PE

KL.1

395

Wiring diagram 26
Pressure control GND 10 9 GND 8 7 GND 6 5 +10V 4 GND 3 2 1 3 2 1 GND 2 1
operation mode

fan (EC-motor)
112/150

1 2 3 1 2 3 1 2 1 2

PE N L PE N L

12 11 10 9 8 7 6 5 4 3 2 1

RS A RS B RS A RS B GND 0-10V 4-20mA +20V +10V 0-10V GND OUT


KL.3

alarm relay normally closed contact

fan (EC-motor)

Input
Mains fan (EC-motor) alarm relay

3 NO 2 COM KL.2 Error signal relay, COMMON 1 NC (2A, 250 VAC) L1 L2 L3 PE

L1 L2 L3 PE

3 2 1

KL.1

27
12 11 10 9 8 Kl. 3 / class 3 7 5 + 0-10V External signal

RS A RS B RS A RS B GND 0-10V +20V +10V 0-10V GND OUT NO COM NC L1 L2 L3 PE

Interface RS485 for ebmBUS Interface RS485 for ebmBUS Interface RS485 for ebmBUS Interface RS485 for ebmBUS GND Control-/Actual value inlet Supply ext. sensor 50mA Supply ext. potentiometer 10mA Control/Actual value inlet GND Master exit 0-10V max 3mA Error signal relay, closes in case of fire Error signal relay, COMMON (2A, 250 VAC) Error signal relay, error signal relay, closes in case of fire Net, L1 Net, L2 Net, L3 Protective conductor

Wiring diagram

6 4-20mA Control-/Actual value inlet 4

P1 10k Potentiometer

3 2 1 3

Kl. 2 / class 2 2 1 3 Kl. 1 / class 1 2 1

396

Wiring diagram 28
12 11 10 9 8 Kl. 3 / class 3 7 5 + 0-10V P1 10k 4 3 2 1 3 Kl. 2 / class 2 2 1 2 Kl. 1 / class 1 1 RS A RS B RS A RS B GND 0-10V +20V +10V 0-10V GND OUT NO COM NC L N PE

Interface RS485 for ebmBUS Interface RS485 for ebmBUS Interface RS485 for ebmBUS Interface RS485 for ebmBUS GND Control-/Actual value inlet Control-/Actual value inlet Supply ext. sensor 50mA Supply ext. potentiometer 10mA Control/Actual value inlet GND Master exit 0-10V max 3mA Error signal relay, closes in case of fire Error signal relay, COMMON (2A, 250 VAC) Error signal relay, closes in case of fire Net, L Net, N Protective conductor

6 4-20mA

29

Yellow/green
( ) ( (L) (N) (L) Black (N) Blue )

Wiring diagram

Brown

Art.-Nr.: 305386

397

Wiring diagram 41
230V 1~ N L
Internal potentiometer, default

42
Wiring power cable Internal potentiometer, default

Yellow C

White

Yellow

Blue

White

Red

Blue

2
1=Min

3 5

4
+

1=Min

10

43

44
U V W TP3/4 PE

X1
TP TP U V W

X2

Wiring diagram

L1

L2

L3

PE

L1

L2

L3

TP3/4 PTC

PE

45
U V W TP3 TP4 PE

R [L1

S L2

T TP3 TP4 PE L3 PTC PE]

398

Red
+

10

Wiring diagram 46
Line 1 Line 2

COM

+10V

Black
Line 1

Blue

Green/yellow

White1

White2
Line 2

Red
Connection +10V 0-10V/PWM GND

Yellow

0-10V PWM

Connection Colour L N PE NC COM Black Blue Green/yellow White1 White2

Assignment/function Mains 50/60 Hz, phase Mains 50/60 Hz, neutral Protective earth Alarm relay, break for failure Alarm relay, COMMON

Colour Assignment/function Red Yellow Blue Voltage output +10V max 1.1 mA Control input (Impendence 100 k W) Protective earth

47
KL3 KL2 KL1

Ain1 U Ain2 U

+20V

GND

Ain2 I

Din 2

Din 3

Ain1 I

Din 1

Aout

RS B

RS A

GND

+10V

COM

NC

PE

No

L1

L2

GND
Blue

NC

PE

Connector KL1

Connection L3 L2 L1

Assignment/function Mains, L3 Mains, L2 Mains, L1 Protective earth Alarm relay, break for failure Alarm relay, COMMON (2A, 250 VAC, AC1) Alarm relay, make for failure

Connector KL3

Connection Assignment/function Din1 Digital input (enabling/disabling of electronics). Enabling: Pin open or applied voltage 5...50 VDC. Disabling: Bridge to GND or applied voltage < 1 VDC. Analogue set value input, 4-20 mA (impedance 100 W) , only to be used as alternative to terminal Ain1 U Supply for external potentionmeter, 10 VDC (3%) max. 10 mA. Analogue set value input, 0-10V (impedance 100 k W) , only to be used as alternative to terminal Ain1 I. GND RS485 interface for MODBUS RTU; RS B RS485 interface for MODBUS RTU; RS A Analogue output 0-10V max 5 mA, reading of current motor speed/current motor control factor. Analogue actual value input, 4-20 mA (impedance 100 k W) , only to be used as alternative to terminal Ain2 U. Supply for external sensor, 20 VDC (+25%/10%) max 40 mA. Analogue actual valve input, 0-10 V (impedance 100k W), only to be used as alternative to terminal Ain2 I. GND Digital input 3 (switch normal/inverse). The preset effective direction of the integrated controller can be selected via BUS or via digital input normal//inverse. Normal: Pin open or applied voltage 5...50 VDC. Inverse: Bridge to GND or applied voltage < VDC. Digital input 2 (switch day/night). The preset set of parameters can be selected via BUS or digital input day/night. Day: Pin open or applied voltage 5...50 VDC. Night: Bridge to GND or applied voltage < 1 VDC.

PE KL2

PE NC COM NO

Ain1 I +10V Ain1 U GND RSB RSA Aout

L3

Wiring diagram

Ain2 I +20 V Ain2 U GND

Din3

Din2

399

Wiring diagram 48
KL3 KL2 KL1

4-20mA

0-10 V PWM

0-10 V PWM

+20 V

+10 V

RS B

RS B

RS A

RS A

GND

GND

OUT

COM

NO

NC

Connector KL3

Connection Assignment/function OUT GND 0-10V/PWM +10V +20V 4-20 mA 0-10V/PWM GND RSB RSA RSB RSA Master output 0-10 V max 3 mA. GND Control/Actual valve input (impedance 100 k W ). Supply for external potentiometer, 10 VDC (+10%) max 10 mA Supply for external sensor, 20 VDC (+20%/10%) max 50 mA Control/actual valve input Control/actual valve input GND RS485 interface for ebmBUS; RS B RS485 interface for ebmBUS; RS A RS485 interface for ebmBUS; RS B RS485 interface for ebmBUS; RS A

Connector PE KL1 KL2

Connection OE N L NC COM NO

Assignment/function Protective earth Mains 50/60Hz, neutral Mains 50/60Hz, phase Alarm relay, break for failure Alarm relay, COMMON (2A, 250 VAC, AC1) Alarm relay, make for failure

Wiring diagram

49

TB TB U1 Z U2

PE

400

PE

Index A
ALS-KBT . . . . . . . . . . . . . . . . . . . . . . . . 371 AQUA 24TF. . . . . . . . . . . . . . . . . . . . . . 341 AR sileo. . . . . . . . . . . . . . . . . . . . . . . . . 170 ASF . . . . . . . . . . . . . . . . . . . . . . . . . . . . 375 ASF/KB . . . . . . . . . . . . . . . . . . . . . . . . . 371 ASFV. . . . . . . . . . . . . . . . . . . . . . . . . . . 384 ASK, ASK/F, ASG/F. . . . . . . . . . . . . . . . 380 ASS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 381 ASSG/F . . . . . . . . . . . . . . . . . . . . . . . . . 383 ASS-P . . . . . . . . . . . . . . . . . . . . . . . . . . 285 ASSV, ASSV/F, . . . . . . . . . . . . . . . . . . . . 383 ASSV-EX . . . . . . . . . . . . . . . . . . . . . . . . 383 AWE-SK. . . . . . . . . . . . . . . . . . . . . . . . . 342 AW-EX. . . . . . . . . . . . . . . . . . . . . . . . . . 226 AW sileo . . . . . . . . . . . . . . . . . . . . . . . . 168 AXC . . . . . . . . . . . . . . . . . . . . . . . . . . . . 180 AXC(B) . . . . . . . . . . . . . . . . . . . . . . . . . . 266 AXCBF. . . . . . . . . . . . . . . . . . . . . . . . . . 186 AXCBF-EX . . . . . . . . . . . . . . . . . . . . . . . 234 AXC-EX . . . . . . . . . . . . . . . . . . . . . . . . . 230 DS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 363 DS-EX . . . . . . . . . . . . . . . . . . . . . . . . . . 363 DSG. . . . . . . . . . . . . . . . . . . . . . . . . . . . 330 DSK. . . . . . . . . . . . . . . . . . . . . . . . . . . . 370 DTV. . . . . . . . . . . . . . . . . . . . . . . . . . . . 343 DVC/DVCI . . . . . . . . . . . . . . . . . . . . . . . 132 DVEX. . . . . . . . . . . . . . . . . . . . . . . . . . . 216 DVG/F. . . . . . . . . . . . . . . . . . . . . . . . . . 250 DVG-V, H 400D4V/400 . . . . . . . . . . . . . 256 DVN/DVNI. . . . . . . . . . . . . . . . . . . . . . . 152 DVP. . . . . . . . . . . . . . . . . . . . . . . . . . . . 280 DVV. . . . . . . . . . . . . . . . . . . . . . . . . . . . 158 DVV-EX . . . . . . . . . . . . . . . . . . . . . . . . . 220 DVV/F . . . . . . . . . . . . . . . . . . . . . . . . . . 244 DXRE. . . . . . . . . . . . . . . . . . . . . . . . . . . 362

G
GFL . . . . . . . . . . . . . . . . . . . . . . . . . . . . 364 GFL-AR/AXC . . . . . . . . . . . . . . . . . . . . . 389 GFL-AR/AXCBF . . . . . . . . . . . . . . . . . . . 389

H
HR1. . . . . . . . . . . . . . . . . . . . . . . . . . . . 343 HSDV. . . . . . . . . . . . . . . . . . . . . . . . . . . 379

I
IF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 316 IGC. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 356 IGK. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 357 IN. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 390 IR24-P. . . . . . . . . . . . . . . . . . . . . . . . . . 343 ISE/USE. . . . . . . . . . . . . . . . . . . . . . . . . 371 IS/US. . . . . . . . . . . . . . . . . . . . . . . . . . . 371

E
EC-Vent control board . . . . . . . . . . . . . 329 EC-Vent room unit . . . . . . . . . . . . . . . . 330 EFD circular. . . . . . . . . . . . . . . . . . . . . . 355 EFD rectangular . . . . . . . . . . . . . . . . . . 363 EMC KIT REV. . . . . . . . . . . . . . . . . . . . . 340 EPSN/EPIN . . . . . . . . . . . . . . . . . . . . . . 389 ESD-F . . . . . . . . . . . . . . . . . . . . . . . . . . . 388 ESDV. . . . . . . . . . . . . . . . . . . . . . . . . . . 384 EV-AR/AXC . . . . . . . . . . . . . . . . . . . . . . 387 EV-EX/AXC . . . . . . . . . . . . . . . . . . . . . . 387 EVH. . . . . . . . . . . . . . . . . . . . . . . . . . . . 388 EX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 204 EX connection box. . . . . . . . . . . . . . . . 339

J
Jet Fan AJ8 . . . . . . . . . . . . . . . . . . . . . . 195 Jet Fan AJR-TR. . . . . . . . . . . . . . . . . . . . 194 Jet Fan IV. . . . . . . . . . . . . . . . . . . . . . . . 196

B
BDS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 390 BF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 316 BF-W. . . . . . . . . . . . . . . . . . . . . . . . . . . 314 BTG . . . . . . . . . . . . . . . . . . . . . . . . . . . . 374 BVK . . . . . . . . . . . . . . . . . . . . . . . . . . . . 390

K
KBR/F . . . . . . . . . . . . . . . . . . . . . . . . . . 238 KBR/KBT EC. . . . . . . . . . . . . . . . . . . . . . 300 KBT/KBR . . . . . . . . . . . . . . . . . . . . . . . . 304 KD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 KDRE/KDRD . . . . . . . . . . . . . . . . . . . . . 114 K EC. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 KE, KE(I) . . . . . . . . . . . . . . . . . . . . . . . . . 66 K-FST1. . . . . . . . . . . . . . . . . . . . . . . . . . 337 K/KV . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 KTEX . . . . . . . . . . . . . . . . . . . . . . . . . . . 208 KT, KT(I) . . . . . . . . . . . . . . . . . . . . . . . . . . 70 KVD. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90 KVK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 KVK DUO. . . . . . . . . . . . . . . . . . . . . . . . . 52 KVKE . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60 KVKE EC. . . . . . . . . . . . . . . . . . . . . . . . . . 56 KVO. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

C
Cable gland set . . . . . . . . . . . . . . . . . . . 386 CB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 350 CBF . . . . . . . . . . . . . . . . . . . . . . . . . . . . 316 CBM. . . . . . . . . . . . . . . . . . . . . . . . . . . . 351 CCM. . . . . . . . . . . . . . . . . . . . . . . . . . . . 375 CCM. . . . . . . . . . . . . . . . . . . . . . . . . . . . 375 CCMI . . . . . . . . . . . . . . . . . . . . . . . . . . . 375 CE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 288 CKS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 296 CO2RT. . . . . . . . . . . . . . . . . . . . . . . . . . 330 CO2RT-R-D . . . . . . . . . . . . . . . . . . . . . . 330 CT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 292 CWK . . . . . . . . . . . . . . . . . . . . . . . . . . . . 354 CXE/AV . . . . . . . . . . . . . . . . . . . . . . . . . 323 CXE/AVC . . . . . . . . . . . . . . . . . . . . . . . . 322

F
FDGE/F . . . . . . . . . . . . . . . . . . . . . . . . . 378 FDG/F . . . . . . . . . . . . . . . . . . . . . . . . . . 377 FDS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 374 FDVE, FDVE/F . . . . . . . . . . . . . . . . . . . . 382 FDV, FDV/F . . . . . . . . . . . . . . . . . . . . . . 381 FFK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 357 FFR . . . . . . . . . . . . . . . . . . . . . . . . . . . . 349 FFS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 368 FGR. . . . . . . . . . . . . . . . . . . . . . . . . . . . 348 FGV. . . . . . . . . . . . . . . . . . . . . . . . . . . . 370 FK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 355 FKX . . . . . . . . . . . . . . . . . . . . . . . . . . . . 355 FRQ(5) . . . . . . . . . . . . . . . . . . . . . . . . . . 325 FRQ(5)S . . . . . . . . . . . . . . . . . . . . . . . . . 325 FSD . . . . . . . . . . . . . . . . . . . . . . . . . . . . 386 FSL. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 379 FTG . . . . . . . . . . . . . . . . . . . . . . . . . . . . 371 FXDM . . . . . . . . . . . . . . . . . . . . . . . . . . . 324

L
LDC . . . . . . . . . . . . . . . . . . . . . . . . . . . . 348 LDK . . . . . . . . . . . . . . . . . . . . . . . . . . . . 365 LDR . . . . . . . . . . . . . . . . . . . . . . . . . . . . 358 LGV/LGH . . . . . . . . . . . . . . . . . . . . . . . . 376 LRK(F). . . . . . . . . . . . . . . . . . . . . . . . . . 385

Index

D
DHA sileo . . . . . . . . . . . . . . . . . . . . . . . 130 DHS/DVS/DVSI . . . . . . . . . . . . . . . . . . . 146 DHS/DVS/DVSI sileo. . . . . . . . . . . . . . . 138 DKEX. . . . . . . . . . . . . . . . . . . . . . . . . . . 212

M
MFA-AR/AXC . . . . . . . . . . . . . . . . . . . . . 386 . . . . . . . . . . . . . . . . . . . . . . 388 MFA-AXCBF

401

Index
MicroREX D21 . . . . . . . . . . . . . . . . . . . . 339 MP. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 387 MSEX. . . . . . . . . . . . . . . . . . . . . . . . . . . 342 MTP 10. . . . . . . . . . . . . . . . . . . . . . . . . 341 MTV 1/010. . . . . . . . . . . . . . . . . . . . . . 341 MUB. . . . . . . . . . . . . . . . . . . . . . . . . . . . 102 MUB EC. . . . . . . . . . . . . . . . . . . . . . . . . . 94 MUB/F. . . . . . . . . . . . . . . . . . . . . . . . . . 260 MUB/T . . . . . . . . . . . . . . . . . . . . . . . . . . 118

S
S2S 160. . . . . . . . . . . . . . . . . . . . . . . . . 340 S5S 100T1 . . . . . . . . . . . . . . . . . . . . . . 340 S5S 100T3 . . . . . . . . . . . . . . . . . . . . . . 340 SC1/D . . . . . . . . . . . . . . . . . . . . . . . . . . 331 SC2/D . . . . . . . . . . . . . . . . . . . . . . . . . . 331 SD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 385 SDM. . . . . . . . . . . . . . . . . . . . . . . . . . . . 369 SD-PRF . . . . . . . . . . . . . . . . . . . . . . . . . 285 S-DT2 DKT. . . . . . . . . . . . . . . . . . . . . . . 340 S-DT2 GKT. . . . . . . . . . . . . . . . . . . . . . . 340 S-DT2 SKT. . . . . . . . . . . . . . . . . . . . . . . 340 S-ET 10, . . . . . . . . . . . . . . . . . . . . . . . . 341 S-ET 10E. . . . . . . . . . . . . . . . . . . . . . . . 341 SF 24A . . . . . . . . . . . . . . . . . . . . . . . . . . 344 SF 24A-S2. . . . . . . . . . . . . . . . . . . . . . . 344 SF 24A-SR. . . . . . . . . . . . . . . . . . . . . . . 344 SF 230A. . . . . . . . . . . . . . . . . . . . . . . . . 344 SG . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 357 SG AR/AXC, SG-AW . . . . . . . . . . . . . . . 385 SG AW-D. . . . . . . . . . . . . . . . . . . . . . . . 386 SM 230A. . . . . . . . . . . . . . . . . . . . . . . . 344 SN. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 390 SRK . . . . . . . . . . . . . . . . . . . . . . . . . . . . 364 SRKG. . . . . . . . . . . . . . . . . . . . . . . . . . . 370 SSD . . . . . . . . . . . . . . . . . . . . . . . . . . . . 374 SSGE/F . . . . . . . . . . . . . . . . . . . . . . . . . 379 SSG/F. . . . . . . . . . . . . . . . . . . . . . . . . . . 378 SSVE, SSVE/F . . . . . . . . . . . . . . . . . . . . 377 SSV, SSV/F. . . . . . . . . . . . . . . . . . . . . . . 382 STDT 16, STDT 16E. . . . . . . . . . . . . . . . 342 STG . . . . . . . . . . . . . . . . . . . . . . . . . . . . 372

TM 10 . . . . . . . . . . . . . . . . . . . . . . . . . . 337 TOB . . . . . . . . . . . . . . . . . . . . . . . . . . . . 372 TOS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 372 Trafo 15/D . . . . . . . . . . . . . . . . . . . . . . 339 TTC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 335 TT-S1. . . . . . . . . . . . . . . . . . . . . . . . . . . 335 TT-S4/D. . . . . . . . . . . . . . . . . . . . . . . . . 336 TUB/TUS. . . . . . . . . . . . . . . . . . . . . . . . 372

O
Optigo OP 5 . . . . . . . . . . . . . . . . . . . . . 336 Optigo OP 10 . . . . . . . . . . . . . . . . . . . . 336 ORH. . . . . . . . . . . . . . . . . . . . . . . . . . . . 357

U
U-EK 230E EX. . . . . . . . . . . . . . . . . . . . 338 UGS. . . . . . . . . . . . . . . . . . . . . . . . . . . . 370

V
VBC . . . . . . . . . . . . . . . . . . . . . . . . . . . . 352 VBF . . . . . . . . . . . . . . . . . . . . . . . . . . . . 353 VBK. . . . . . . . . . . . . . . . . . . . . . . . . . . . 367 VBR. . . . . . . . . . . . . . . . . . . . . . . . . . . . 365 VK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 356 VK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 368 VKA-P . . . . . . . . . . . . . . . . . . . . . . . . . . 285 VKK . . . . . . . . . . . . . . . . . . . . . . . . . . . . 356 VKS-P . . . . . . . . . . . . . . . . . . . . . . . . . . 285 VKS, VKM, VKS-EX, VKSV-EX . . . . . . . . 380 VKV/F, VKVE/F, VKG/F . . . . . . . . . . . . . 383 VKVM . . . . . . . . . . . . . . . . . . . . . . . . . . 384 VP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 285

P
PGK . . . . . . . . . . . . . . . . . . . . . . . . . . . . 360 PKDM12 . . . . . . . . . . . . . . . . . . . . . . . . 324 PRF . . . . . . . . . . . . . . . . . . . . . . . . . . . . 276 Pulser . . . . . . . . . . . . . . . . . . . . . . . . . . 334 Pulser M . . . . . . . . . . . . . . . . . . . . . . . . 334 PXDM5A. . . . . . . . . . . . . . . . . . . . . . . . 324

R
RADT. . . . . . . . . . . . . . . . . . . . . . . . . . . 333 RB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 359 RBK . . . . . . . . . . . . . . . . . . . . . . . . . . . . 368 RBM . . . . . . . . . . . . . . . . . . . . . . . . . . . . 360 R-DK4 KT (EX) . . . . . . . . . . . . . . . . . . . . 323 RE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 320 RED . . . . . . . . . . . . . . . . . . . . . . . . . . . . 364 REE . . . . . . . . . . . . . . . . . . . . . . . . . . . . 321 REE S0. . . . . . . . . . . . . . . . . . . . . . . . . . 322 REE TR0. . . . . . . . . . . . . . . . . . . . . . . . . 322 REPT . . . . . . . . . . . . . . . . . . . . . . . . . . . 331 RETP . . . . . . . . . . . . . . . . . . . . . . . . . . . 331 REU . . . . . . . . . . . . . . . . . . . . . . . . . . . . 320 REV . . . . . . . . . . . . . . . . . . . . . . . . . . . . 340 REV DVV . . . . . . . . . . . . . . . . . . . . . . . . 340 RS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78 RSA (F) . . . . . . . . . . . . . . . . . . . . . . . . . 384 RSI. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84 RSK . . . . . . . . . . . . . . . . . . . . . . . . . . . . 355

W
WBK . . . . . . . . . . . . . . . . . . . . . . . . . . . . 389 WBK-W . . . . . . . . . . . . . . . . . . . . . . . . . 389 WSD . . . . . . . . . . . . . . . . . . . . . . . . . . . . 370 WSD-KBT . . . . . . . . . . . . . . . . . . . . . . . . 371 WSD PRF. . . . . . . . . . . . . . . . . . . . . . . . 285 WSG . . . . . . . . . . . . . . . . . . . . . . . . . . . . 370 WVA/WVI. . . . . . . . . . . . . . . . . . . . . . . 268

T
T 120. . . . . . . . . . . . . . . . . . . . . . . . . . . 339 TDA DV . . . . . . . . . . . . . . . . . . . . . . . . . 371 TFR . . . . . . . . . . . . . . . . . . . . . . . . . . . . 343 TFSR/TFSK . . . . . . . . . . . . . . . . . . . . . . 126 TFSR/TFSK EC. . . . . . . . . . . . . . . . . . . . 124 TG . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 373 TG 300-800, 400-800. . . . . . . . . . . . . 372 TG-A 130 . . . . . . . . . . . . . . . . . . . . . . . . 338 TG-K330. . . . . . . . . . . . . . . . . . . . . . . . 338 TG-KH/PT1000. . . . . . . . . . . . . . . . . . . 338 TG-R4/R5/PT1000. . . . . . . . . . . . . . . . 338 TG-R430/530. . . . . . . . . . . . . . . . . . . . 338 TG-R600/630. . . . . . . . . . . . . . . . . . . . 338 TG-UH/PT1000. . . . . . . . . . . . . . . . . . . 338 THB. . . . . . . . . . . . . . . . . . . . . . . . . . . . 373 THS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 373

Z
ZHZ . . . . . . . . . . . . . . . . . . . . . . . . . . . . 389 ZRS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 164 ZSD . . . . . . . . . . . . . . . . . . . . . . . . . . . . 386 ZTV/ZTR . . . . . . . . . . . . . . . . . . . . . . . . 390

Index

RT 0-30. . . . . . . . . . . . . . . . . . . . . . . . . 337 RTRD. . . . . . . . . . . . . . . . . . . . . . . . . . . 321 RTRDU. . . . . . . . . . . . . . . . . . . . . . . . . . 321 RTRE . . . . . . . . . . . . . . . . . . . . . . . . . . . 320 RVAZ4-24. . . . . . . . . . . . . . . . . . . . . . . 339 RVAZ4-24A . . . . . . . . . . . . . . . . . . . . . . 339 RVK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 RVK 315Y4. . . . . . . . . . . . . . . . . . . . . . 202

402

www.systemair.com

Systemair AB January 2012 E8095

Вам также может понравиться