Академический Документы
Профессиональный Документы
Культура Документы
Before operating any generator system, read the Operator's Manual to become familiar with your
equipment. Safe and efficient operation can only happen if the equipment is properly operated
and maintained.
No generator manufacturer or installation contractor can anticipate every potential hazard
involved with the installation and use of these type of systems. The warnings, decal and labels
attached to the equipment and used in this Manual can not cover all hazards. Use of methods or
procedures other than those recommended by the equipment manufacturer must satisfy you that
it is safe for you or others to follow.
The following symbols are highlighted to alert you of conditions that are potentially dangerous to
the operator, installation/service/repair personnel, or the equipment.
1-1. General Safety Precautions
• Keep equipment clean and properly maintained. Normal maintenance and servicing of
equipment is a prerequisite to a functional, safely operated machine.
• Use common sense, read the instructions and information in this manual carefully, and
check for other local safety rules that require compliance.
1-2. Installation Precautions
• Be safety conscious. Read all operational, safety and installation information before
attempting to install or operate any generator equipment.
• This equipment should be installed, operated, serviced, and repaired by qualified
personnel only. The installation and interconnection of this equipment to facility wiring
and other equipment must be done by a competent, qualified craftsperson who is familiar
with applicable standards and codes governing the installation.
• Installation methods, practices, or procedures that are unauthorized or done improperly
are dangerous and could result in serious personal injury or damage to property and
equipment.
• Installation, operation, servicing and repair of electrical power generators and their
related equipment must be done in accordance to applicable codes, standards, regulations
and laws. The National Fire Prevention Association (NFPA), National Electric Code
(NEC), Occupational Safety and Health Administration (OSHA) regulations, local
industrial codes and requirements must be complied with in the use and servicing of this
equipment.
• An open flame, smoking, or welding near a generator is a potential fire hazard. Internal
combustion engine fuels are flammable.
• Ensure all fuel fittings are properly connected and not leaking. Periodic inspection is
required to ensure no leaks develop over time.
• Fuel connection at the engine should be made with an approved flexible fuel line. Use of
copper piping for flexible lines is not recommended as copper work hardens and becomes
brittle.
• Never fill fuel tanks while the engine is running, unless tanks are outside the engine
room. When fuel comes in contact with a hot engine or exhaust system, there is
possibility of a fire or explosion.
• Under certain conditions storage batteries will expel explosive hydrogen gas. Do not
allow smoking, welding or sparks in the vicinity of any storage battery. Adequate
ventilation must be provided around batteries. Battery racks must also be grounded to
minimize static charges.
• Ensure the exhaust system is installed properly and adequate ventilation is provided.
Exhaust gases must be safely piped away from the unit to an area not used by people. The
engine consumes oxygen and the exhaust given off by the engine contains carbon
monoxide gas. Carbon Monoxide is a deadly, lethal gas.
• The installation must have adequate ventilation.
• Wire gauge sizes of electrical wiring, cables, and facility circuits must be of sufficient
size to handle the maximum electrical current (ampacity) of circuits. Refer to generator
system's User Manual to determine appropriate cable/wire size.
• Remove electrical power before removing any generator's protective panels or touching
any electrical components.
SECTION 2 - Locations
The location for a generator is dependent on applicable codes and associated support systems for
the generator such as ventilation, wiring, fuel, and exhaust.
The following factors should be considered:
• The ideal location for any generator is away from extreme ambient temperatures and
where the generator is protected from adverse weather conditions. It is recommended that
generator be as close to the load it is supporting as possible.
• The structure the Gen-Set (Generator Set) will be set upon must be strong enough to
support the weight of the Gen-Set, its' auxiliary equipment, and other equipment mounted
on the structure.
• The structure must meet a 1 hour non-combustion fire rating.
• The installation site must be clean, dry and not subject to flooding.
• Because of excessive ambient temperatures associated with the use of stand-alone metal
sheds from exposure to sunlight, a concrete pad with a supported roof and an outside
security enclosure (fence) to protect the unit from vandalism, birds, rodents, and other
small animals is recommended.
• The Gen-Set generates heat while running. Installing the Gen-Set in a tightly enclosed
building or shed is not recommended. The site must provide for adequate cooling and
ventilation with a minimum of duct work. Adequate ventilation for a generator is
specified in cubic feet per minute.
• The site must permit engine exhaust gases to be piped away to an area that is uninhabited
by people or animals. Care must be given to ensure that exhaust gases do not re-enter an
occupied area.
• The site must provide adequate acoustical noise and vibration isolation.
• The outside site must provide access to the generator to allow for maintenance, service,
and repair. A three foot (.914 meter) service clearance around the unit is recommended.
• Fuel supply and ease of refueling must be taken into consideration.
• Adequate normal and emergency lighting must be provided in any installation.
• When mounting a generator outside on a roof or next to a building the generator must be
at least 3 feet from any combustible wall and 5 feet from any opening(i.e. doors,
windows, vents, & ducts).
2-1. Ground/Floor Loading
The foundation for the generator must support the total weight of the generator. This includes
fuel, oil, and the weight of any associated support systems.
Plan for 3 feet (1 Meters) of access around the generator for maintenance, service and repair.
When calculating the floor loading, ensure the fuel weight, cooling system fluids (where
applicable), piping, pumps, power cables/runways and supporting structures are included in the
calculations. Most user's manuals do not include the weight of the fuel tanks since most are sold
less tank.
SECTION 3 - Mounting
A concrete foundation with anchored mounting bolts, is recommended. Steel Beams are an
acceptable alternative. Foundations help in the servicing and repair of Gen-Set's and protect the
unit from moisture that could occur from seepage. The concrete base that the generator is
mounted to should be separate and independent from the surrounding structure.
The following applies to concrete bases:
• A Single (See Figure 1)or Double (See Figure 2) pedestal base may be used. A height of
at least 6 inches higher than floor level is recommended.
Roof mount radiators on liquid cooled units is sometimes done where the installation location of
the unit can not dissipate the heat generated by the unit during operation. Roof mount radiators
is beyond the scope of this publication.
4-5. Louvers, Screening And Expanded Metal
When louvers, screening or expanded metal are used to cover air openings in buildings housing
generators, consideration must be given that these materials do not restrict the free flow of
cooling air. Any restriction must be compensated for by making the actual opening size
proportionately larger.
Louvers: Either fixed or movable louvers may be installed on the air openings in a structure that
houses a generator. The installer must make sure that the total square inches of free air inlet
opening is sufficient to limit the heat rise in the room to prevent the room temperature from
exceeding the generator 's operating temperature.
Figure 8. Louver
To find the actual size of the air inlet opening needed, proceed as follows:
• Find the area of the generator's inlet air duct, by multiplying the air duct height by its
width.
• Divide the inlet air duct area by the percentage of free air inlet area for the particular
screening or expanded metal to be used. The result is the required size of the air inlet
opening in the building.
Example 1: If the required inlet air opening area on a particular generator is 400 square inches
and the building air opening is to be covered with screening having a 70% "free air inlet area":
Divide 400 square inches by 0.70, to obtain 576 square inches. Actual air inlet opening size in
the building should be equal to or greater than 576 square inches. (An opening that measures 24
X 24 inches (576 square inches) would be adequate in this case to achieve the required 1125 Cu.
ft/minute (31.86 Cubic Meters/Min.).
Example 2: The required inlet air opening area on a particular generator is 500 square inches and
the building air opening is to be covered with screening having a 70% "free air inlet area":
Divide 500 square inches by 0.70, to obtain 714 square inches. Actual air inlet opening size in
the building should be greater than 714 square inches. (An opening that measures 27 X 27 inches
(729 square inches) would be adequate in this case to achieve the required 2000 Cu. ft/Minute
(39 Cubic Meters/Min.).
SECTION 5 - Fuel
5-1. Gasoline
For gasoline egine generators, Unleaded or Regular gasoline with a lower octane rating than
85((RON/MON)/2) may cause pre-detonation (knocking) which can damage the engine. Regular
gasoline can be used, however, unleaded gasoline is preferred because it reduces pollution and
combustion chamber deposits. See the generator's engine owner's manual for fuel information or
contact the generator set's manufacturer.
CAUTION POOR QUALITY, LOW OCTANE FUEL can damage the engine.
IMPORTANT:
• Use clean, fresh, unleaded gasoline with at least 85 octane rating.
• Do not mix oil with the gasoline.
• Do not use gasohal or gasoline alcohol fuel blends.
Most A.C. Generators require the use of transfer switches. Refer to manufacturer's installation
instructions and recommendations.
Dexter JobGe
Hansen
Publicati
Data Presenation
Software
nie
12,700 job
ons English Germa Descriptions
n on CD ROM
Amazon.com now has tools, tooling and gas powered generators in their Amazon.com's Home
Improvement Store. Click onAmazon.com's Home Improvement Store
SECTION 7 - Exhaust System
7-1. General (Exhaust System)
Generator engines give off deadly carbon monoxide gas through their exhaust systems.
Carbon monoxide gas, if breathed in sufficient concentrations, can cause unconsciousness or
death. Exhaust gases must be piped safely away from any room or enclosure that houses a
generator and to a well ventilated area where people will not be endangered.
Besides the possibility of carbon monoxide poisoning, exhaust piping becomes extremely hot
during operation and remains hot for a long time after shutdown. For that reason, the following
precautions are necessary:
• Avoid contact with hot engines, exhaust manifolds, exhaust piping and mufflers. Any of
these can cause severe burns.
• Where piping must pass through combustible walls or ceilings, special precautions must
be taken to prevent fire or heat damage such as using heat thimbles through walls and
ceilings.
7-2. General Rules for Exhaust Systems
When installing an exhaust system for a generator, the following rules should be considered:
• Exhaust piping should be of wrought iron or steel having adequate strength and
durability.
• Exhaust fittings may be of cast iron. A 9 inch spacing (10 inches (250mm) recommended)
from the exhaust pipe and walls is also required by most local codes.
• Low points in horizontal runs of piping should be provided with condensation traps, as
well as condensation drains.
• Piping and mufflers must be properly supported and connected.
• A flexible length of exhaust pipe is required between the engine exhaust manifold and
rigid exhaust piping.
• Exhaust piping must be terminated safely outside a structure that houses a generator, in
such a way that hot gases and sparks will be discharged harmlessly and will not blow
against any combustible surface or material.
• Exhaust piping must not terminate under loading platforms, structures, or near any
opening in a building.
• Where necessary, exhaust piping must be guarded and/or insulated to prevent burns.
• Provide a clearance of at least 9 inches (229mm)(10 inches (250mm) recommended)
between exhaust piping and any combustible material.
• Keep exhaust piping well clear of fuel tanks, fuel lines, etc.
7-3. Routing Exhaust Piping Through Combustible Walls
• Exhaust piping that passes through any combustible wall or partition must be guarded at
the point of passage by:
• A ventilated metal thimble that is at least 12 inches in diameter larger than the piping, or
• Metal or burned fire clay thimbles built in brickwork that provides not less than 8 inches
of insulation between the clay thimble and any combustible material.
• Thermal insulation or protective guards are typically required for exhaust pipes/system
by national and local codes to protect users from burns.
Figure 10. Wall Thimble
7-4. Routing Exhaust Piping Through Combustible Roofs
Exhaust piping that passes through any combustible roof must be separated from the roof by a
ventilated metal thimble that is at least 6 inches in diameter larger than the piping. The thimble
must extend at least 9 inches (229mm)(10 inches (250mm) recommended) above and below roof
construction.
Figure 11. Roof Thimble
Introduction
There are many people in the generator and UPS industries that have tried to operate engine
driven alternating current (A.C.) generator sets (gen-sets) and uninterruptible power systems
(UPS) together. Although some systems are successful, there are problems that can occur. This
article should provide insight into the problems of using a gen-set to power a UPS as well as
provide enough information to possibly save the reader from a problem installation.
Achieving and maintaining adequate control of frequency and line noise is a common issue in
generator design and use. Unless the gen-set is sized 2 to 3 times the size of the UPS, and the
UPS is about 75 percent loaded, the UPS may never switch from the inverter (battery power) to
generator power. Another factor is that there is a great deal of line noise from small generators
compared to utility line power. This can also cause the UPS to stay on inverter until the batteries
go dead. To address these problems, Best Power Technology, Inc., a fairly well known U.S. UPS
supplier, started a DC generator product line. They have since dropped that product line due to a
take over by a UPS competitor who did not want to be in the generator business.
When preparing to connect a gen-set to a UPS, first check with the UPS manufacturer for
recommendations on using their UPS with a generator. Sizing and compatibility issues should be
addressed before even considering hooking a gen-set to the UPS. Loading and the ability of the
generator to regulate the load, possibly the hardest issues to deal with, should be considered.
In addition, the type of power plant and alternator used in the gen-set can effect whether the
equipment will work together or not. For instance, Diesels/turbine engines work better than
gasoline/liquid propane (LP) and Natural gas (NG) engines. It has been noted on gen-sets that
single-phase alternators work better than three phase alternators. Turbo-charged engines work
better than normally aspirated engines, as well as being better at higher altitudes. Fuel injected
engines work better than engines with carburetors (Aspirated engines use carburetors). See
Figure 1 below for a block diagram of a typical gen-set/UPS installation.
Figure 1. A Typical Generator - UPS Installation
[Back to Index]
Sizing Considerations
Tables 1 and 2 provide generator sizing and loading recommendations for various sizes of UPSs.
These recommendations are based on UPSs and gen-sets from several manufacturers, and are
more rules of thumb based on experience with connecting gen-set and UPSs together than
absolute rules. The two tables differ in the fuel type of the gen-sets engines.
The reason that a background load is shown in the tables is two fold. First, the additional load
helps the generator regulate better. Second, in an emergency situation, it is always a wise move
to put in emergency lighting, and is an electrical code requirement. Caution is advised when
operating fluorescent lights from the UPS for emergency lighting. Preferably, power the
fluorescent lights from the generator and have some incandescent emergency lights running from
the UPS. Fluorescent lights will sometimes flicker, especially if the UPS is one that is a double
conversion unit that uses a Ferro-resonant transformer. As improvements in UPS and generator
technologies take place, these recommendations may become less relevant.
Gasoline/LP/NG Fuel
Gasoline/LP/NG Gasoline/LP/NG
Background Background
Single Phase Three Phase
UPS Load Load
Generator Generator
KVA KW KVA KW KW KVA KW
0.5 to 3.5 10 12 2 10 12 2
4 10 12 2 10 15 2
5 13 16 2 15 19 2
7 16 20 3 19 24 2
10 24 30 4 29 36 4
12 30 38 5 36 45 6
18 46 57 7 55 68 8
Table 1. Gasoline/LP/NG Fuel Gen-sets
Diesel Fuel
Diesel Diesel
Background Background
UPS Single Phase Three Phase
Load Load
Generator Generator
KVA KW KVA KW KW KVA KW
0.5 to 2 5 7 1.5 5 7 1.5
2.5 to 3.5 5 7 1.5 6 8 1.5
4 6 8 1.5 8 10 1.5
5 8 10 2 10 13 2
7 10 12 2 13 16 2
10 14 18 2.5 19 24 3
12 18 23 3 24 30 4
18 28 34 4 37 46 6
Table 2. Diesel Fuel Gen-sets
From Tables 1 and 2, note that the size of the gen-set is significantly larger than the UPS. There
are a number of reasons. Besides the obvious losses due to line loss, there are inefficiencies
involved every time another piece of equipment is brought into the equation. One of the biggest
factors is that the generator needs to be sized to handle the start up of the largest load, not just the
continuous load. Based on calculations and manufacturers specifications, the gen-set
recommendations look like they are larger than needed. However, if the generators engine can't
get up to speed and running, for any reason, the system will fail.
[Back to Index]
Start Up Load / In Rush Current
When a gen-set is being used to put power directly into the battery bank of the UPS, as shown in
Figure 3, the load can exceed the gen-sets ability to supply power. The UPS, in holding the load,
starts to deplete battery power immediately, at the start of the outage. By the time the gen-set is
up and running, and prepared to go on-line, the battery bank has lost a considerable amount of
power. At the instant power is provided to the battery charger, the charger is trying to power a
battery bank that acts like a very large capacitor and the in rush of current into the batteries takes
all the power available from the battery charger. This has been known to stop the engine on some
gen-sets. This has also been known to start a "stop-restart cycle" where the gen-set never gets
running to power the load and the UPS batteries finally run down and the UPS shuts down.
A work-around for the current in-rush problem is to limit the amount of current the batteries can
draw from the charger. Putting a Current Shunt in-line with one of the battery leads can do this.
Another option is, if the gen-set has the capability of auto-start from sensing the UPS battery
bank float voltage, set the float voltage on the battery bank at a higher voltage to get the gen-set
to start sooner also may help.
[Back to Index]
Other Generator Tips
Other gen-set related caveats that allow the gen-set to work with the UPS are as follows:
1. If installing a three-phase generator, install the UPS across the generator phase that is
monitored by the generator's voltage regulator.
2. Adjust the governor of the generator so that the line frequency doesn't deviate by more than
plus or minus 3 hertz.
3. Install additional ballast loads such as emergency lighting that are equal to 15% of the KW
rating of the gen-set. The ballast loads share the generator with the UPS and stabilize the
generator so that the frequency is less erratic. The loads should be stable and continuous such as
lighting or electric heaters. In other words, do not use air conditioners or air compressors for a
background load. See Figure 2 below.
Click here to use the UPS/Power Conditioner Quote Request / Sizing - Applications Assistance
Contact Form to obtain help sizing a Uninterruptible Power Products or Best Power UPS for your
needs from Uninterruptible Power Products, Inc..
SWITCHGEAR OPTIONS
The benefit of Caterpillar's vast experience in power generation is fully realized in its generator switchgear offering. Available
from 600V through 15 kV, Cat® switchgear provides a harmonized system solution by being able to integrate all elements of
monitoring and control of a Caterpillar® generator set in a single-source package.
For integration of Caterpillar generator sets into a customer's facility, Caterpillar offers switchgear suitable for applications
ranging from single standby/load management to multi-unit utility paralleling installations. In any of these cases, Caterpillar
switchgear can offer remote communication capabilities for monitoring and control of your total system.
Caterpillar switchgear employs a feature rich microprocessor based control system that is combined with an easy to use
touchscreen operator interface panel. The entire system can be controlled from the switchgear-mounted touchscreen, or it
can be controlled/monitored from a remote site through a personal computer.
Caterpillar offers three standard switchgear products that can support a wide variety of applications or can provide a custom
designed system to meet your specific site's needs as required. Our XLM series products supports transfer between the
utility source and generator bus, as well as affording capability for parallel operation with the utility for load management
applications. The EGP series supports paralleling on an isolated generator bus and is commonly used in prime power or
emergency standby systems. Finally, our LM series supports single unit paralleling with utility for load management and
peak shaving applications.
English
Products & Applications › Power Generation › UPS
U
Full
Product P
Line
S
W
Agricultu h
re e
t
h
e
Demoliti r
on &
Scrap s
u
p
Landsca p
ping o
r
t
i
Forestry n
g
General c
Construction r
i
t
Government i
al c
a
l
Heavy p
Construction r
o
c
e
Industrial /
s
OEM
s
e
s
Marine
o
r
Mining d
e
f
Oil & Gas e
n
d
i
On-Highway n
Transportati g
on
s
e
r
Pipeline
v
e
r
Paving s
f
r
Power
o
Generation
m
h
» Generator a
Sets r
m
f
» Integrated u
Systems l
p
» Automatic o
Transfer w
Switches e
r
» Switchgear p
r
o
» UPS b
l
e
› Spec
m
Sheets
s
,
› Systems
Data Sheets C
a
t
› Brochures e
r
p
› White i
Papers l
l
a
» Rental r
Power '
s
» Literature U
P
S
» Customer
Testimonials
S
y
» News s
t
e
» Services m
s
» Application w
s i
l
l
Power
Plants p
r
o
Quarry, v
Aggregates i
and Cement d
e
y
Railway e
Power a
r
s
Waste
o
f
l
o
w
m
a
i
n
t
e
n
a
n
c
e
p
r
o
t
e
c
t
i
o
n
.
UNINTERRUPTIBLE POWER
SYSTEMS (UPS)
Caterpillar knows the importance of quality power to your operation. Whether
supporting critical processes or defending servers from harmful power problems,
Caterpillar's uninterruptible power supply systems will provide years of low maintenance
protection. Yielding the lowest operating costs in the industry, Caterpillar's UPS system
will provide the peace of mind that comes from knowing that Caterpillar is standing
beside you in your efforts to grow your business.
Currently offering uninterruptible power supply systems from 150kVA to multi-megawatt
solutions, Caterpillar integrates a battery free UPS with its market leading generator
sets, switchgear and automatic transfer switches to deliver a world class integrated
system.
Caterpillar's world wide dealer network makes service and support locally available and
timely. Click here to find a Caterpillar Dealer near you or use the left navigation to learn
more about the Cat UPS, the uninterruptible power supply with the highest power
density in the world.
Performance report
- Sales Updates
- Presentations
- Annual Reports
Product
- Buses
- Trucks
- Engines ENGINES DEFENCE & SPECIAL
- Defence & Special
Vehicles VEHICLES TRUCKS BUSES
Customer Center
Media Center
Leyparts
Aspiration » T.C
Electricals » 12 Volts DC
Voltage » 415 V
Frequency » 50 Hz
Conforming To » BS 5514
Sitemap ©Ashok Leyland. All rights
Change over switch allows switching between mains supply and standby generators for emergency services
and remote locations
Question : I have bought a generator, and would like to connect it to my house in case of
mains failure. What do I need to do?
• Answer : When using a generator as an alternative supply to the mains, there are
several precautions that must be observed.
• It is vital that the generator is completely isolated from the mains supply. This
ensures that the generator is not attempting to power up the whole neighborhood,
but also ensures that it does not electrocute a utility worker trying to restore the
mains supply.
• Most buildings now have an RCD built into the consumer unit. This is configured to
operate from the mains supply with an earthed neutral, and not from a generator
with a floating earth. To utilize this protection device, it is necessary to modify the
generator so that it is configured in the same way as the mains supply.
• This is a simple modification for a qualified electrician, involving adding a link wire
from the neutral terminal to the earth terminal. It is recommended to make this
connection in the plug that is to be used to connect to the generator. This ensures
that the generator is unmodified when it is disconnected from the house, and
therefore remains safe.
• The plug should be labeled “Do not connect to mains: Neutral-Earth link fitted”. The
lead between the generator and the transfer switch is not protected by the RCD, it is
therefore recommended to use a steel armored cable for this connection. Finally a
local low-impedance earth spike needs to be installed
Back
Our Voltimum Experts answer your questions on a daily basis in our Technical Expertise area.
This first Question of the Day, on BS 7671 Section 551 - temporary genset earthing and
protection, is answered by SELECT:
Question: I've been asked whether it is possible to install a 5KVA backup generator to supply
emergency power during power outages.
The supply is single-phase PME taken from a three-phase service head in an outbuilding/workshop.
The supply then runs under the drive via 25mm two-core SWA (with earthed sheath) cable to a cellar. In
the cellar, the earth is not connected to the MET of the house, which has an earth rod and a 100mA
Type-S RCD. I believe that this is because the Ze reading at the house end of the SWA is over 1.5ohm.
My thinking was to connect the generator to a break before make switch, connect the neutral to an
earth rod installed beneath the SW and feed the SWA via an 30mA RCD and a fused isolator to the
house CU. Can you see any problems with this approach?
Answer: The arrangements you describe appear to be generally satisfactory provided you meet the
requirements of BS 7671 Section 551. The following are some particular points to note:
• Ensure the earth electrode resistance is satisfactory - It should be less than 200ohm where
possible.
• The changeover switching arrangement (double-pole) should meet the requirements of
Regulation 551-06-01.
• To prevent danger or damage to equipment, ensure that the requirements of Regulation 551-
02-03 are met.
To see many more Q & A in Voltimum UK's Experts Area, please click on the link:
http://www.voltimum.co.uk/consult.php?universe=consult.index.questions
Abstract:
A control system for controlling an alternator driven by an engine, for generating electric power, has a changeover
switch for selectively switching destination of electric power generated by the alternator to a plurality of electric loads
having respective different load voltage values. An ECU controls switching operation of the changeover switch and
controls the alternator electric power, according to a direction in which the changeover switch has been switched. The
ECU detects voltage of the alternator electric power when the destination of the alternator electric power is to be
switched from a first electric load having a higher load voltage value of the plurality of electric loads to a second
electric load having a lower load voltage value of the same, and causes the changeover switch to switch the
destination of the alternator electric power from the first electric load to the second electric load after it is determined
that the voltage of the alternator electric power has been changed from a predetermined higher voltage value to a
predetermined lower voltage value
Brushless alternator
Document Type and Number:
United States Patent 4647806
Abstract:
A brushless alternator consisting of interconnected stator coils disposed in stator plates and surrounding the main
winding of the rotor and including rectifiers coupled to the stator coils. The rotor is on a shaft supported within the
housing of the alternator, and includes an exciter with shaft-mounted rectifiers for supplying a DC voltage to the main
winding of the rotor. The exciter field coil is spool wound on a cylindrical core that is contained within the exciter
stator, that is attached to thealternator housing. The field coil has a concentric opening for slidably receiving the rotor
shaft. The exciter rotor armature does not rotate, but is affixed to the alternator housing and surrounds the outer
periphery of the exciter field coil. The main winding of the rotor has a cylindrical sleeve extending from one end to
engage and support the exciter rotor armature in alignment with the exciter stator.