fire protection

Orcades

air intake opening frame

Launching deviced : The facade wall opening frame Orcades is equipped with an electromagnetic magnet ensuring the launching by pulse or by break 24 Vcc or 48 Vcc (power 3,5 W or 1,6 W). The launching can also be done by pneumatic jack. It is equipped with a manual rearmament control.

advantages
Careful design (grille Cyclades for interior face option). Good thermal isolation for a maximum comfort. Good air and waterproofness (covering vanes). Installation possible on door (with kit). Motorizable by electrical jack (factory or on work site). Launching by pneumatic jack.

It can be equipped with a double launching by adding a thermal fuse calibrated at 70 C.

options
Electric rearmament jack. Bipolar contacts. Thermal fuse (double launching fuse and coil). Assembly kit for thin wall : door and exterior woodwork.

range
Air intake wall opening frames with free area, matching to the dampers for the corridors. Wall opening frames of 1m2 of free area or of SGO for stairwells. 2 versions : - Insulated. - Insulated : enabling to get a cfficient K = 1,55 W/m2/ C. Dimensions : range enabling free passing from 10 dm2 to 1 m2 (see selection chart). Launching by electromagnetic jack by pulse or break 24 or 48 Vcc or by pneumatic launching. Possibility of double launching by adding a thermal fuse calibrated at 70 C depending on implantation. Bipolar or unipolar contacts.

packaging
On pallet.

specifications
The facade wall opening frame will have articulated vanes in aluminium and will be perfectly air and water proof in closed position. The free area will be tested in factory.. Mechanism complying to NF S 61-937. Type Orcades, France Air brand.

technical description
Fire class
Launching mechanism complies to the NFS 61-937 according to the tests of the CNPP relative to the launching mechanisms for remote controlled opening in front.

application
Remote controlled grilles used on vertical face of building, for natural air intake, of smoke extraction process in ERP and collective housing (premises, stairwells, corridors).

construction / composition
Connection box Launching device OUTSIDE INSIDE

Dimensions

orcades

Opening springs

OUTSIDE

INSIDE
nominal overall reservation reservation dim. without frame Ln Hn Ln + 80 Hn + 80 Ln + 50 Hn + 50 dim. without frame Ln + 5 Hn + 5 dimensions dimensions

Free movement
depth grilles* Cyclades Extra 100 100 Ln + 136 Hn + 137 grilles Cyclades Light and Medium Ln + 110 Hn + 110

Grille with articulated vanes, made of aluminium frame in which aluminium blades pivot. The standard finish is anodised natural silver (paint option). The blades are synchronised by a linkage and opened by a spring. They will be kept closed in position. The water proofness and airtightness is ensured by the covering of the vanes. In the insulated version, the airtightness is reinforced by a gasket. In the insulated version, the blades are doubled with an expanded polystyrene M1 (K = 1,55 W/m2/C) of 23 mm, locked up in to a PVC case.

(dimensions in mm.) * The dimensions of the grilles are foreseen for an installation with frame.

The installation of Orcades with a frame is highly recommended to maintain the rigidity of the set.

Electric features - electric version


Power coil by pulse = 3,5 W. Power coil by break = 1,6 W.

810

www.france-air.com

Guide created by France Air 2010. All rights reserved.

fire protection

fitting and connection


 Functioning principle
 Assembled on a facade, in a low part of the premises, Orcades ensures fresh air intake.

 Installation advice
T  he facade wall dampers Orcades are attached to a concrete wall (mechanism interior side) with the help of sealing frame or in a metallic wall.  Caution, foresee the clearance of the blades (140 mm) towards the exterior of the building.  Caution, complying to 6 of the appendix A fiche VIII, all the elements contributing to the rearmament (handle to manipulate and hanging system by magnetic coil) have to be at an inferior height of 3m in regards to the floor.

 Connection electric version


T  wo compression glands are delivered to receive the remote control and signalling cables.  The wiring has to be done according to the opposite diagram.

 Connection pneumatic version


C  opper pipe 6 mm to link to the Orcades.  Service pressure 4 Ps 6 bars.

 Selection of the Orcades


All the Orcades are with horizontal blades. Free area (rearmament manual / rearmament by jack) no difference of SLC between a standard Orcades and an insulated Orcades.

Hn indm2 350 475 600 725 850 975* 1100 1250 1350

number of blades 2 3 4 5 6 7 8 9 10

330

11,3 / 9,4 14,0 / 11,8 16,8 / 14,2 19,6 / 16,5 22,4 / 18,9 25,2 / 21,3 28,0 / 23,6

475 8,8 / i 13,1 / i 17,3 / 15,5 21,6 / 19,3 25,9 / 23,3 30,2 / 27,1 34,4 / 30,9 38,7 / 34,8 43,0 / 38,6

600 11,4 / i 16,9 / i 22,5 / 20,7 28,1 / 25,8 33,7 / 31,0 39,2 / 36,1 44,8 /41,3 50,4 / 46,4 55,9 / 51,6

725 14,0 / i 20,9 / i 27,7 / 25,9 34,6 / 32,3 41,4 / 38,8 48,3 / 45,2 55,2 / 51,6 62,0 / 58,1 68,9 / 64,5

Ln 850 16,7 / i 24,8 / i 32,9 / 31,1 41,1 / 38,8 49,2 / 46,6 57,4 / 54,3 65,5 / 62,0 73,7 / 69,7 81,8 / 77,5

975 19,3 / i 28,7 / i 38,2 / 36,3 47,6 / 45,3 57,0 / 54,3 66,5 / 63,4 75,9 / 72,4 85,3 / 81,4 94,8 / 90,4

1100 21,9 / i 32,6 / i 43,4 / 41,5 54,1 / 51,8 64,8 / 62,1 75,5 / 72,4

1225 24,6 / i 36,6 / i 48,6 / 46,7 60,6 / 58,3 72,6 / 69,9 84,6 / 81,5

1350 24,2 / i 40,5 / i 53,8 / 51,9 67,1 / 64,8 80,4 / 77,7 93,7 / 90,6

86,3 / 82,7 96,6 / 93,1 107,0 / 103,5 97,0 / 93,0 108,6 / 104,7 107,7 / 103,3 120,6 / 116,3
orcades

*: maximum height of product enabling the air passage surface to be 1m maximum from floor. i: closing motorization impossible on these dimensions

SGO
Hn indm2 350 475 600 725 850 975* 1100 1250 1350 number of blades 2 3 4 5 6 7 8 9 10 330 475 0,11 0,17 0,25 0,30 0,33 0,38 0,43 0,49 0,54 600 0,15 0,23 0,32 0,39 0,43 0,50 0,56 0,63 0,70 725 0,18 0,28 0,40 0,48 0,53 0,61 0,69 0,78 0,86 Ln 850 0,21 0,33 0,47 0,57 0,63 0,72 0,82 0,92 1,02 975 0,25 0,38 0,55 0,66 0,72 0,84 0,95 1,07 1,18 1100 0,28 0,43 0,62 0,75 0,82 0,95 1,08 1,21 1,34 1225 0,32 0,49 0,70 0,85 0,92 1,07 1,21 1,36 1,51 1350 0,35 0,54 0,77 0,94 1,02 1,18 1,34

0,16 0,20 0,21 0,25 0,28 0,32 0,35

*: maximum height of product enabling the air passage surface to be 1m maximum from floor. i: closing motorization impossible on these dimensions

Particular dimensions for air intake in stairwells 1m in SGO.

Dimensions for air intake in corridor or air intake in premises.

Non existing dimension.

Guide created by France Air 2010 All rights reserved.

www.france-air.com

811

fire protection

specific accessories
Sealing frame
The sealing frame is the linking element to fix the Orcades opening frame to the wall. Its use is recommanded for concrete wall assemblies. The frame is supplied in a kit with assembly instructions.

specific accessories
Assembly kit for door installations
It is a set of parts enabling to sandwich a 50 mm panel. Orcades fixing system on fixed wall.

Bracket

Screw for damper fixation Sealing feet

Covering grilles Cyclades


The grilles Cyclades Light/Medium/Extra will be fixed with 4 screws into the wall. These screws maintain the grilles frame against the wall. The grille Cyclades Light has a fixed core. The Cyclades Medium and Extra have opening cores.

Caution : you have to foresee a rear covering box (Orcades will exceed the wall) to be able to add a covering grille.

Rearmament jack kit


The rearmament jack can be assembled in factory or delivered, on already installed Orcades. They enable an electric closing of the wall opening frame after an opening (all or none). Technical information : - supply voltage : 24 Vcc. - jack consumption : 1,25 A. - circuit : 80 mm. - power : 400 N. This jack must be ordered with a supply case that will be able to control several wall opening frames equipped with jack (case to choose according to the number of jack equipped Orcades on the work site).

Position contact
Inverter contact stand by position (closed) or security position (open), unipolar or bipolar.

orcades

Launching plunger
Launching plunger by pulse or break, 24 Vcc, 48 Vcc.

Additional contacts
Possibility of adding contacts on Orcades that have already been installed, or by way of polar contact, or by way of unipolar contacts (if the delivered Orcade possesses no contact).

Insulation kit
Possibility of insulating the Orcades blades not insulated on the work site.

812

www.france-air.com

Guide created by France Air 2010. All rights reserved.

fire protection

regulation reminders
 Sizing of a wall damper and a natural smoke and heat extraction device
Definitions :  Free area of a wall damper : interior geometric area (provided that the wall damper opens at at least 60).  Useful area of wall damper : the useful area of wall opening frame is equal to the free area of this wall damper affected of a coefficient of 0,5. UDP : Passage unit. QE = extract air flow. QI = insufflation air flow.

 Smoke extraction of corridors


selection smoke extraction position in the corridor mechanical/natural smoke extraction mechanical extraction natural insufflation IT 246 6.2 If the air intake is carried out by the wall opening frames, their free area taken into account has to be situated in the inferior half of the premises. Qe = 0,5 m3/s/UDP Nominal section : with VMAX = 5 m/s QE SN = VMAX Q I = QE mechanical/natural smoke extraction natural extraction natural insufflation

IT 246 - The air intakes and the smoke evacuations are distributed, taking into account the localisation of the risks. IT 246 6.1 A wall opening frame can count on air intake grille and/ or smoke extraction; the area taken into account has to be positioned in the superior half of the corridor and has to be at more that 1.8m of the floor, the free area taken into account for the air intake has to be outside of the previously defined evacuation zone. IT 246 6.1 Each air intake and each smoke evacuation has a free area of minimum 10 dm2 by passage circulation unit.

sizing wall opening frame

 S  moke extracton of premises


selection smoke extraction position in the premises mechanical/natural smoke extraction mechanical extraction natural insufflation IT 246 If the air intake is carried out by the wall dampers, their free area taken into account has to be situated in the inferior half of the premises mechanical/natural smoke extraction natural extraction IT 7.1.3. The outlets must be positioned in the zone filled with smoke. The smoke evacuations, for roof with a slope inferior to 10% have to be situated at a maximum distance of all premises contour points with d 4 x H and 30 m with H average height. For all roofs with a slope superior to 10 %, the smoke evacuations must be embedded at the highest possible, at a height to the average height under roof or ceiling. IT 246 The useful area of the wall dampers will be obtained affecting a coefficient of 0,5 of the free area. natural insuffation The air intake must be done in the free height of smoke HP (at low parts of the circulation).

sizing of wall dampers

Nominal section : with VMAX = 5 m/s QE S N = VMAX

QI = QE

The geometric area of the air entrances have to be at least equal to the geometric area of the outlets ensuring the extraction.

orcades

 S  moke extraction of stairs


T  o limit or avoid the stairwells filling up with smoke, they can be, depending on the case, smoke extracted by a natural flushing or a pressurising application in relation to the damaged premises. T  he DENFC will be placed on the high part of the stairwell, and an air intake, of equal surface, will be placed at the low part of the cage. The manual control of the smoke extraction system is placed on the stairwell, at the level of the building entrance.

commissioning and connection


 Maintenance
Maintenance : according to norm NF S 61-933  Cleaning of the set (dust) at the start of the installation. F  unctioning, foresee periodical trials, according to norm NF S 61-933.