Cabinet Type2.

1M+HX02&Natural-ventilation +Combination Rack


No.
1

Item
Base Information
Internal Dimensions (W x D x H) External Dimensions (W x D x H ) Base Dimensions (W x D x H ) Net Weight of the Cabinet Maximum Space Column Material Panel Material Panel Thickness Door Lock Protection Level Cable Hole on Bottom Shipping Storage Temperature Relative Humidity

Specification
800 mm (W) x 800 mm (D) x 1800 mm (H) 905 mm (W) x 1135 mm (D) x 2110 mm (H) 900 mm (W) x 900 mm (D) x 200 mm (H) 220KG Equipment cabinet capability 22U ;Battery cabinet capability 18U Aluminium Sandwich panel: prepainted galvanized steel sheet +EPS/PU 45mm Three points anti-theft locks; European standard DIN18152 lock, replaceable lock cylinder by different operators IP55 / IP34 8*50mm Integrated equipment shipping, spare parts shipping -40+70 5%95%

Homepag e

Power Specifications ETP48200 (Optional)


Power Supply Standard Output Voltage Frequency Surge Protection Performance Power Module Capability Power Module Number Power Module Efficiency AC Input Circuit Breaker AC Output Circuit Breaker DC Output Circuit Breaker Battery Breaker Output Load Surge Protection Single-phase, three-phase, dual-live-wire mains, 50/60Hz 220V/380V 45Hz65Hz Nominal discharge capacity (In): 30 kA (8/20 s) Maximum discharge capacity (Imax): 60 kA (8/20 s) 50A 2 4 0.94; 0.96Optional 63A/3P 20A/1P*2 LLVD: 100A x 2, 20A x 1; BLVD: 32A x 3, 16A x 3 125A x 2 Differential mode: 10 kA (8/20 s); Common mode: 20 kA (8/20 s)

EMUA Specifications (Optional)


Sensor Extended Input Dry Contact Output Communication Door status sensor, smoke sensor, water sensor, ambient temperature and humidity sensor and infrared 32 dry contact inputs and 4 analog parameter input Six dry contact outputs for high temperatures, high humidity, low temperatures, low humidity, smoke, and RS485

Cable Distribution Unit (Optional)


75ohm DDF 120ohm DDF ODF 20 E1 routes, 19inch 4U, routed out from the front 8 E1 routes, 19inch 1U, routed out from the front 12 pigtails, 19inch 1U, routed out from the front

Temperature Control Mode


Equipment compartment HX02 power HX02 Heat exchanger effect HX02 Typical power consumption: 50W(DC); Maximum power consumption: 68W(DC) 80W/K When Equipment heat output is 700 W: HEX air intake vent - ambient temperature9 When Equipment heat output is 1000 W: HEX air intake vent - ambient temperature11 Natural-ventilation Typical power consumption: 48W(DC); Maximum power consumption: 48W(DC) 300W Interior ambient temperature - Exterior ambient temperature3exterior ambient temperature 33 When 10exterior ambient temperature33, interior ambient temperature: 1535 When exterior ambient temperature10, interior ambient temperature: -515 500W (Optional)

Battery compartment Power Cooling Capacity Temperature control performance of the cabinet Natural-ventilation Heating box power

Battery (Optional)
Specification Capacity Battery string 150Ah, 12V AGM 300Ah 2 Groups

Others
Cabinet Lamp -48V Light emitting diode (LED)

Standard and Certification


Security Standard EMC Certification IEC/EN/UL 60 950 EN 300 386-2 CE, IC, ETL, FCC, C-tick, RoHS, NRTL(ELT)

NotesCabinet Type=Cabiner External Highness +Temperature Control Mode+Rack Type

19"
Cable Space (1U) EMUA (1U) Spare Space (3U) Socket (2U) ETP48200 Power System (8U) DCDU (1U) BBU (2U) Spare Space (4U)

12V 150A h

12V 150A h

2U

8U

12V 150Ah

12V 150A h

12V 150A h

8U

12V 150Ah

12V 150A h

12V 150A h

22U