Ingress protection

the Ingress Protection (IP) for all low voltage enclosures up to 1000 V a.c. and 1500 V d.c. is defined in identical fashion by the standards EN 60529 - IEC 529 it comprises the letters IP followed by two character numerals: The first character numeral indicates the degree of protection provided by the enclosure with respect to persons, also to the equipment inside the enclosure The first character numeral: protection against solid substances IP 0 1 dsignation non-protected protected against solid objects greater than 50 mm 1 IP The second character numeral: protection against liquid substances dsignation non-protected protected against dripping water The second character numeral indicates the degree of protection provided by the enclosure with respect to harmful ingress of water; a third character may be used to indicate mechanical strength. An x signifies that no test has been carried out

2 2 protected against solid objects greater than 12,5 mm 3

protected against dripping water when titled up to 15 protected against spraying water

protected against solid objects greater than 2,5 mm

protected against splashing water

protected against solid objects greater than 1,0 mm

protected against water jets

dust-protected

protected against heavy seas

7 6 dust-tight 8

15 cm

protected against the effect of immersion

protected against submersion

code IK: protection against mechanical shocks code IK according to EN 50-102 (new designation) additional letter (in option) protection of people against access to dangerous parts

code IK 00 01 02 03 04 05 06 07 08 09 10

shock energy non-protected 0,15 joule 0,2 joule 0,35 joule 0,5 joule 0,7 joule 1 joule 2 joules 5 joules 10 joules 20 joules H M S W A B C D

designation protected against access of the back of the hand protected against access of a finger protected against access of a tool - 2,5 mm protected against access of a tool - 1 mm additional letter (in option) specific information on the product designation high voltage material movements during water test stationary during water test bad weather

60

Type tested assemblies


Consumer Units & Distribution Boards As you might expect, consideration has been given to the design of the enclosure to accommodate the range of MCB and RCD devices which are suitable for use in domestic or similar installations, or generally in installations where unskilled persons have access to their use. This, as it happens, describes the European Standard covering the requirements of LV Distribution Boards suitabie for this application. The full title is: EN 60439-3 Specification for low voltage switchgear and control switchgear assemblies. Part 3. Particular requirements for low-voltage switchgear and control gear assemblies intended to be installed in places where unskilled persons have access to their use Distribution boards This standard covers the supplementary requirements for enclosure distribution boards suitable for indoor use containing protective devices and intended for use either in domestic applications or in other places where unskilled persons have access for their use, Control and/or signalling devices may aiso be included. They are for use on ac, with a nominal voltage to earth not exceeding 300V. The outgoing circuits contain short circuit protection devices, each having a rated current not exceeding 125A with a total incoming load current not exceeding 250A. Customer Distribution Boards which are generally known in Ireland as Consumer Units are aiso included in this Standard. The additional test requirements are set out in annex ZA which calls for the assembly to withstand a short-circuit fault of 16kA when protected by a 10OA specified fuse. By definition a customer distribution board or consumer unit is an integrated assembly, for the control and distribution of electrical energy, principally in domestic installations, incorporating manual means of double pole isolation in the incoming circuits, and are designed for use exclusively with one or more of the following outgoing circuit protective devices: fuses, MCBs and RCBOs. The units may aiso incorporate RCDs. Polarity must be observed throughout and the consumer unit is type tested when energised through a 100A type II fuse complying with BS1361. The rated current of a consumer unit is determined by the rated current of the incoming protective device, usually 63A, 80A or 100A, the rated current of the incoming device(s) is limited to 100A. As there are no diversity factors applied to consumer units, the incoming circuit and the bus-bar system must be able to carry their full rated current without exceeding the temperature rise limits. Panelboards The idea of group mounting MCCBs or MCBs on to a vertical three phase bus-bar system came from North America during the 1960s, where it had been used very effectively for a number of years. The design takes advantage of the modular dimensions of the circuit breakers which, together with the simple bus-bar system, proved to be very economical and safe. The basic design philosophy behind the panelboard is to provide a three phase distribution board capable of accommodating MCCBs, which is simple to specify, manufacture and install, and can be made available off the shelf or on a very short delivery cycle. Generally installed for commercial and light industrial application the panelboard is, however, used in many different types of applications. Panelboards are covered by the European Standard for Low-voltage Switchgear and Control Gear Assemblies EN 60439 Part 1, which is the specification for type-tested and partially type-tested assemblies (general requirements). Panelboards are usually type-tested assemblies but, unlike consumer units and distribution boards, they do not, as yet, have their own particular standard, so care must be taken in their selection and application, lt.is important that the system designer understands, and is able to use, the technical information that the manufacturer is required to publish regarding the panelboard. Most of the information is straightforward and presents little problem, except perhaps for internai separation ~Form numbers), degree of protection (IP rating) and short-circuit withstand strength. Internal Separation The internal separation of assemblies is described in the European Standard EN 60439 and is concemed with three requirements which can be met by the suitable arrangement of barriers or partitions. Protection against contact with live parts belonging to adjacent functional units. Limitation of the possibility of initiating and spreading of arcing faults. Prevention of the passage of solid foreign bodies from one unit of an assembly to an adjacent unit. Form numbers are given to some typical forms of separation Form 1 - no separation Form 2 - separation of bus-bars from the functional units Form 3 - separation of bus-bars from the functional units and separation of ail functional units from one another, but not their outgoing terminais. Form 4 - separation of bus-bars from the functional units and separation of all functional units from one another including their outgoing terminals.

61

Consumer Units and enclosures

Mini Gamma and Vector IP65 enclosures


Mini Gamma enclosures GD102N

GD104N

GD106N

GD104N bis GD110N

GD108N

GD110N

Vector IP65 enclosures Dimensions References VE103L VE106L VE110L VE112L VE212L VE312L VE412L VE118L VE218L VE318L Enclosure sizes Wall box R A H 3T 1 6T 1 10 T 1 12 T 1 24 T 2 36 T 3 18 T 4 18 T 1 36 T 2 54 T 3 111 165 237 310 310 310 310 418 418 418 175 190 210 302 427 552 677 302 452 602

E 108 180 230 230 230 230 338 338 338

F 147 158 173 155 280 405 550 155 305 455

Connection assembly mounting on insulating support at both end of the chassis additional connection assembly: VZ403 or VZ428insulated terminal VZ743 enclosure reference VE103 VE106 VE110 VE112 VE118 VE212 VE218 VE312 VE318 VE412 62 knock outs 2xM20 1xM20+1xM25+1xM30/32 1xM20/32+1xM25+3xM20 supplied cable bushes 3xM20 2xM20+2xM25+1xM32 4xM20+2xM25+1xM32
2

2xM20/32/40+2xM25/32+3xM25+6xM20 10xM20+2xM25+1xM32 1xM20/40/50+2xM20/32+12xM25+2xM20 8xM20+10xM25+1xM32 2xM20/32/40+2xM25/32+3xM25+6xM20 14xM20+4xM25+1xM32 1xM20/40/50+2xM20/32+12xM25+2xM20 8xM20+14xM25+1xM32


1

2xM20/32/40+2xM25/32+3xM25+6xM20 14xM20+10xM25+2xM32 1xM20/40/50+2xM20/32+12xM25+2xM20 8xM20+18xM25+2xM32 2xM20/32/40+2xM25/32+3xM25+6xM20 14xM20+10xM25+1xM32

Volta flush enclosures


VU24B

Enclosure Volta R VU12B VU24B VU36B VU48B 12 T 24 T 36 T 48 T 1 2 3 4 Outside A 348 348 348 348 B 336 461 586 711 Inside E 330 330 330 330 F 317 442 567 692
Consumer Units and enclosures

Wall mounting bracket

Connecting two enclosures

Conduit entry

Cable entry plate

63

Gamma dimensions
Gamma dimensions GD106N- 1 row 5 T
145

GD110N - 1 row 10 T
250 45

140

140

125

235

65

GD113H - 1 row 13 T

GD26C - 1 row 26 T

GD413D - 4 row 52 T
250

GD313H - 3 row 39 T GD213H - 2 row 26 T


250

250
between rail 125

600

between rail 125

between rail 125

475

350

between rail 125

277

402

between rail 125

between rail 125

180

64

36,5

180

36,5

36,5

180

527

Golf dimensions
Flush mounting A D

dimension (mm) A B
between rail 125

fixing D 90 94 97 97 97 E 140 209 281 281 281 F 177 189 224 349 494
Consumer Units and enclosures

B 220 230 265 390 535

C 73 77 80 80 80

VF04 VF08 VF12 VF24 VF36

1 row 4 T 1 row 8 T

180 250

1 row 12 T 322 2 row 24 T 322 3 row 36 T 322

Surface mounting
A 95

dimension (mm) A
F B

fixing E F

B 180 180 225 350 500

D 86 86 95 95 95

VS04 VS08 VS12 VS24

between rail 125

1 row 4 T 1 row 8 T

130 200

120 205 205 205

140 160 285 410

1 row 12 T 275 2 row 24 T 275 3 row 36 T 275

VS36

65

VL enclosure
VL enclosure VL 12T
A 70 75 H F

References

Enclosure dimensions A 250 324 445 H 186 186 208 B 27 27 28

Wall box E 200 272 360 F 170 170 170

VL 08.. VL 12.. VL 18..

12T 24T 36T

Vega enclosure VB 36W - 2 rows 36T


A 135

References

150

150

VB 18W VB 36W VB 54W

18T 36T 54T

Enclosure dimensions A H 370 300 370 450 370 600

Fixing E 300 300 300 F 236 386 536 G 32 32 32

66

Orion Plus- metal enclosures IP 65


Metal enclosure Orion Plus
A B 22

F F1 F2

B1 H

B2

E1 E E2

16

Dimensions references
plain door transp. door number of rows enclosure L A B B1 B2 C D external fixing E1 E2 F1 F2

FL101A FL102A FL103A FL104A FL105A FL106A FL107A FL108A FL109A FL110A FL111A FL112A FL113A FL114A FL115A FL116A FL117A FL118A FL119A FL120A FL121A FL122A FL123A FL124A FL125A FL126A FL127A FL128A FL129A FL130A

FL151A FL152A FL153A FL154A FL155A FL156A FL157A FL158A FL159A FL160A FL161A FL162A FL163A FL164A FL165A FL166A FL167A FL168A FL169A FL170A FL171A FL172A FL173A FL174A FL175A FL176A FL177A FL178A FL179A FL180A

2 2 3 3 3 3 4 4 4 4 5 5 5 5 6 6 6 6 8 8

200 250 300 300 300 300 300 400 300 300 400 400 500 400 400 600 400 400 500 500 500 500 600 600 600 600 800 800 600 800

250 300 300 350 350 400 400 400 500 500 500 500 500 600 600 600 650 650 650 650 800 800 800 800 950 950 950 950 1250 1250

160 160 160 160 200 160 200 200 160 200 160 200 200 200 250 250 200 250 200 250 200 250 250 300 250 300 250 300 250 300

145 195 245 245 245 245 245 345 245 245 345 345 445 345 345 545 345 345 445 445 445 445 545 545 545 545 745 745 545 745

80 80 80 80 120 80 120 120 80 120 80 120 120 120 170 170 120 170 120 170 120 170 170 220 170 220 170 220 170 220

150 200 250 250 250 250 250 350 250 250 350 350 450 350 350 550 350 350 450 450 450 450 550 550 550 550 750 750 550 750

200 250 250 300 300 350 350 350 450 450 450 450 450 550 550 550 600 600 600 600 750 750 750 750 900 900 900 900 1200 1200

160 210 260 260 260 260 260 360 260 260 360 360 460 360 360 560 360 360 460 460 460 460 560 560 560 560 760 760 560 760

270 320 370 370 370 370 370 470 370 370 470 470 570 470 470 670 470 470 570 570 570 570 670 670 670 670 870 870 670 870

170 220 220 270 270 320 320 320 420 420 420 420 420 520 520 520 570 570 570 570 720 720 720 720 870 870 870 870 1170 1170

282 332 332 382 382 432 432 432 532 532 532 532 532 632 632 632 682 682 682 682 832 832 832 832 982 982 982 982 1282 1282

67

Consumer Units and enclosures

Orion Plus - polyester enclosures IP 65


orion Plus polyester enclosures
A

235

F2 F F1

H1

C
C

D1

E E1 E2

note: plan for A + 25 mm for door opening

Dimensions references
plain door transp. door number enclosure of rows L A A1 A2 B C D D1 in.fixing E F external fixing E1 E2 F1 F2

FL204B FL209B FL213B FL216B FL221B FL229B FL300B FL301B FL302B FL305B FL306B FL307B FL310B FL311B FL312B FL320B FL321B FL322B FL325B FL326B FL327B FL330B FL331B FL332B FL340B FL342B FL344B FL346B FL348B FL350B FL352B FL354B FL356B FL358B FL360B FL362B FL364B FL366B FL368B 68

FL254B FL259B FL263B FL266B FL271B FL279B FL500B FL501B FL502B FL505B FL506B FL507B FL510B FL511B FL512B FL520B FL521B FL522B FL525B FL526B FL527B FL530B FL531B FL532B -

2 3 3 4 4 5 3 5 7 3 5 7 3 5 7 3 5 7 3 5 7 3 5 7 3+3 5+3 7+3 5+5 7+5 3+3 5+3 7+3 5+5 7+5 3+3 5+3 7+3 5+5 7+5

300 300 400 400 500 600 600 600 600 850 850 850 1100 1100 1100 600 600 600 850 850 850 1100 1100 1100 600 600 600 600 600 850 850 850 850 850 1100 1100 1100 1100 1100

500 500 500 650 650 800 550 850 1150 550 850 1150 550 850 1150 600 900 1200 600 900 1200 600 900 1200 1150 1450 1750 1750 2050 1150 1450 1750 1750 2050 1500 1450 1750 1750 2050

550 850 1150 850 1150 550 850 1150 850 1150 550 850 1150 850 1150

550 550 550 850 850 550 550 550 850 850 550 550 550 850 550

160 200 200 200 250 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300

250 250 350 350 450 550 500 500 500 750 750 750 1000 1000 1000 500 500 500 750 750 750 1000 1000 1000 500 500 500 500 500 750 750 750 750 750 1000 1000 1000 1000 1000

300 450 450 600 600 750 450 750 1050 450 750 1050 450 750 1050 450 750 1050 450 750 1050 450 750 1050 450 750 1050 750 1050 450 750 1050 750 1050 450 750 1050 750 1050

450 450 750 750 450 450 450 750 750 450 450 450 750 750

219 219 319 319 419 519 -

258 408 408 558 558 708 -

339 339 439 439 539 639 -

339 339 439 439 539 639 -

269 419 419 569 569 719 -

389 539 539 689 689 839 -

Orion Plus - metal enclosures IP 65


Mounting plate
A1 E3

H1 F3

Dimensions plain plate perforated plate size


L1 A1

for enclosures

insulated

size
L1 A1

FL401A FL402A FL403A FL404A FL405A FL406A FL407A FL408A FL510E FL520E FL530E FL409A FL410A FL411A FL412A FL413A FL414A FL415A FL511E FL521E FL531E FL512E FL522E FL532E FL416A FL417A FL418A FL419A

FL472A FL473A FL474A FL475A FL476A FL477A FL478A FL479A FL480A FL481A FL482A FL483A

143 193 243 243 243 343 243 343 493 743 993 443 343 543 343 443 443 543 493 743 993 493 693 993 543 743 543 743

230 280 280 330 380 380 480 480 480 480 480 480 580 580 630 630 780 780 780 780 780 1080 1080 1080 930 930 1230 1230

FL101A,FL151A FL102A,FL152A FL103A,FL153A FL104A,FL105A,FL154A, FL155A,FL204B,FL254B FL106A,FL107A, FL156A,FL157A FL108A,FL158A FL109A,FL110A,FL159A, FL160A,FL209B,FL259B FL111A,FL112A,FL161A, FL162A,FL213B,FL263B FL300B,FL500B, FL320B,FL520B FL305B,FL505B, FL325B,FL525B FL310B,FL510B, FL330B,FL530B FL113A,FL163A FL114A,FL115A, FL164A,FL165A FL116A,FL166A FL117A,FL118A,FL167A, FL168A,FL216B,FL266B FL119A,FL120A,FL169A, FL170A,FL221B,FL271B FL121A,FL122A, FL171A,FL172A FL123A,FL124A,FL173A, FL174A,FL229B,FL279B FL301B,FL501B, FL321B,FL521B FL306B,FL506B, FL326B,FL526B FL311B,FL511B, FL331B,FL531B FL302B,FL502B, FL322B,FL522B FL307B,FL507B, FL327B,FL527B FL312B,FL512B, FL332B,FL532B FL125A,FL126A, FL175A,FL176A FL127A.FL128A, FL177A,FL178A FL129A,FL179A FL130A,FL180A

FL422A FL423A FL424A FL425A FL550E FL560E FL570E FL426A FL427A FL428A FL429A FL551E FL561E FL571E FL552E FL562E FL572E FL430A FL431A FL432A FL433A

195 245 245 245 495 745 995 345 445 445 545 495 745 995 495 745 995 545 745 545 745

235 285 285 435 435 435 435 585 585 735 735 735 735 735 1035 1035 1035 885 885 1185 1185

69

Consumer Units and enclosures

Power dissipated by the enclosures according to Standards (CEI EN 60439-1)


Power dissipated IEC standard EN 60439-1 (IEC 17-13/1) standard in Table 7 shows the list of checks and tests to be carried out on BT panel types AS (series equipment subject to type testing) and ANS (series equipment partially subject to type testing). One of the characteristics to be monitored is the overtemperature limit check to ensure that the temperatures specified in Table 3 of the standard are not exceeded for the various parts of the panel. IEC standard EN 60439-1 requires that for ANS type panels the overtemperature limit check can be carried out by means of extrapolation of the series panels (AS) that have passed the type testing. The extrapolation method laid down by the standard is set out in the IEC 890 publication corresponding to IEC standard 17-43 Overtemperature determination method, by extrapolation, for non-standard (ANS) protection and control equipment assemblies for low tension (BT panels). To make the overtemperature limit check easier, Hager Lume have drawn up a series of tables where the maximum power values that can be dissipated P.Max (W) are shown for all the Lume panels. These values have been determined so as to obtain the overtemperature values specified in Table 3 of IEC standard EN 60439-1 for accessible external envelopes and coverings (30K for metal surfaces and 40K for insulating surfaces) for the upper part of the panel. The maximum power values shown in the tables that can be dissipated by the metalwork are valid for the mounting conditions of the panel considered and for the overtemperature values halfway up t 0.5 and in the upper part t 1.0 indicated.

IP 65 standard metal panels Article FL102A FL104A FL105A FL109A FL110A FL111A FL112A FL117A FL118A FL119A FL120A FL121A FL122A FL123A FL124A FL125A FL126A FL127A FL128A FL129A FL130A Dimensional data (mm) 300 x 250 x 160 350 x 300 x 160 350 x 300 x 200 500 x 300 x 160 500 x 300 x 200 500 x 400 x 160 500 x 400 x 200 650 x 400 x 200 650 x 400 x 250 650 x 500 x 200 650 x 500 x 250 800 x 500 x 200 800 x 500 x 250 800 x 600 x 250 800 x 600 x 300 950 x 600 x 250 950 x 600 x 300 950 x 800 x 250 950 x 800 x 300 1250 x 600 x 250 1250 x 800 x 300 Laid Walls Walls Walls Walls Walls Walls Walls Walls Walls Walls Walls Walls Walls Walls Walls Walls Walls Walls Walls Walls Walls T 0,5 (K) 25,0 25,0 24,9 24,3 24,3 24,7 24,9 24,3 24,5 24,8 24,9 24,4 24,5 22,0 22,7 21,4 21,8 22,1 22,8 20,0 21,3 T 1,0 (K) 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 P. max (W) 28 35 39 44 49 54 60 71 80 84 93 97 107 100 114 113 127 148 170 134,5 211

FL152A FL154A FL155A FL159A FL160A FL161A FL162A FL167A FL168A FL169A FL170A FL171A FL172A FL173A FL174A FL175A FL176A FL177A FL178A FL179A FL180A

70

Power dissipated by the enclosures (CEI EN 60439-1)


Polyester panels IP 65 series boxes Article FL204B FL209B FL213B FL216B FL221B FL229B Dimensional data (mm) 350 x 300 x 160 500 x 300 x 200 500 x 400 x 200 650 x 400 x 200 650 x 500 x 250 800 x 600 x 300 Laid Walls Walls Walls Walls Walls Walls T 0,5 (K) 33,4 32,4 33,0 32,6 33,0 29,9 T 1,0 (K) 40 40 40 40 40 40 P. max (W) 50 70 85 102 132 160

Polyester panels IP 65 series panels Article FL300B FL301B FL302B FL305B FL306B FL307B FL310B FL311B FL312B Dimensional data (mm) 550 x 600 x 300 850 x 600 x 300 1150 x 600 x 300 550 x 850 x 300 850 x 850 x 300 1150 x 850 x 300 550 x 1100 x 300 850 x 1100 x 300 1150 x 1100 x 300 Laid Walls Walls Walls Walls Walls Walls Walls Walls Walls T 0,5 (K) 34,3 29,7 27,8 32,5 30,7 29,2 32,8 31,8 30,4 T 1,0 (K) 40 40 40 40 40 40 40 40 40 P. max (W) 150 167 205 170 230 300 215 310 405

Polyester panels IP 65 series cupboards Article FL320B FL321B FL322B FL325B FL326B FL327B FL330B FL331B FL332B Dimensional data (mm) 600 x 600 x 300 900 x 600 x 300 1200 x 600 x 300 600 x 850 x 300 900 x 850 x 300 1200 x 850 x 300 600 x 1100 x 300 900 x 1100 x 300 1200 x 1100 x 300 Laid Floor-Walls Floor-Walls Floor-Walls Floor-Walls Floor-Walls Floor-Walls Floor-Walls Floor-Walls Floor-Walls T 0,5 (K) 33,9 29,4 27,8 32,2 30,7 29,1 32,8 31,4 30,1 T 1,0 (K) 40 40 40 40 40 40 40 40 40 P. max (W) 15 17 215 180 245 315 230 325 420

71

Consumer Units and enclosures

FL254B FL259B FL263B FL266B FL271B FL279B

Power dissipated by the enclosures (CEI EN 60439-1)


Polyester panels IP 65 series cupboards Article FL340B FL342B FL344B FL346B FL348B FL350B FL352B FL354B FL356B FL358B FL360B FL362B FL364B FL366B FL368B Dimensional data (mm) 1150 x 600 x 300 1450 x 600 x 300 1750 x 600 x 300 1750 x 600 x 300 2050 x 600 x 300 1150 x 850 x 300 1450 x 850 x 300 1750 x 850 x 300 1750 x 850 x 300 2050 x 850 x 300 1150 x 1100 x 300 1450 x 1100 x 300 1750 x 1100 x 300 1750 x 1100 x 300 2050 x 1100 x 300 Laid Floor-Walls Floor-Walls Floor-Walls Floor-Walls Floor-Walls Floor-Walls Floor-Walls Floor-Walls Floor-Walls Floor-Walls Floor-Walls Floor-Walls Floor-Walls Floor-Walls Floor-Walls T 0,5 (K) 27,5 26,9 25,7 25,7 25,6 29,0 27,9 26,9 26,9 26,2 30,3 29,0 27,9 27,9 27,1 T 1,0 (K) 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 P. max (W) 190 240 285 285 340 280 345 400 400 450 380 455 505 505 535

72

FW Surface enclosures IP44, Protection Class II M


General Description: Surface mounting enclosures for domestic and commercial electrical distribution Included in delivery: Cabinet with door Carrier rails with complete board Device covers with 46mm slots, with complete board Complies with Standards: DIN VDE 0603, DIN43870, EN60529, Parts 500, 504 and 504/A 1 SN EN 60439-3 Nominal Voltage: AC230/400V, 50Hz Current Rating: for devices up to 125A Protection Class: II (insulation protected) IP Rating: IP 44 Protection details: Protection against direct contact: IP3X behind the door Protection with indirect contact: Insulation Protection Air & leakage distance: as per DIN VDE 0110, Part 1 and 2/1.80, according to electrical surge category IV, pollution Grade 3, Insulation material II and IIIa, nominal voltage AC400V, max incoming current 355A. Door: frontal fastening, with internal hinges, all adjustable, removable without tools, optionally attachable on right or left, width from 800mm double door, opening angle 110. Door lock: Twist release lock, exchangeable with other locks, 3 point bar locks on double door cabinet Colour: RAL 9010 (pure white) Cable entries: cable entry plates top and bottom made of plastic to feed in the cable from the front. Material Housing and door made of steel, powder coated Carrier Rails: Steel, powdercoted Supports: Plastic Device rails: steel, galvanised Covers and knockouts: plastic

Height (mm) FWB31 FWB32 FWB33 FWB34 FWB41 FWB42 FWB43 FWB44 FWB51 FWB52 FWB53 FWB54 FWB61 FWB62 FWB63 FWB64 FWB71 FWB72 FWB73 FWB74 1100 950 800 650 500

Width (mm) 300 550 800 1050 300 550 800 1050 300 550 800 1050 300 550 800 1050 300 550 800 1050

Depth (mm) 161 161 161 161 161 161 161 161 161 161 161 161 161 161 161 161 161 161 161 161

DIN-Rails (12mod) 3 3 3 3 4 4 4 4 5 5 5 5 6 6 6 6 7 7 7 7

Fields across 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4

number of mods 36 72 108 144 48 96 144 192 60 120 180 240 72 144 216 288 84 168 252 336

IP-Class (standard) IP44 IP44 IP44 IP44 IP44 IP44 IP44 IP44 IP44 IP44 IP44 IP44 IP44 IP44 IP44 IP44 IP44 IP44 IP44 IP44

IP-Class Special Order only IP54 (on request) IP54 (on request) IP54 (on request) IP54 (on request) IP54 (on request) IP54 (on request) IP54 (on request) IP54 (on request) IP54 (on request) IP54 (on request) IP54 (on request) IP54 (on request) IP54 (on request) IP54 (on request) IP54 (on request) IP54 (on request) IP54 (on request) IP54 (on request) IP54 (on request) IP54 (on request)

73

Consumer Units and enclosures

FW Flush enclosures IP30, Protection Class II M


General Description: Flush mounting enclosures for domestic and commercial electrical distribution Included in delivery: Cabinet with door Carrier rails with complete board Device covers with 46mm slots, with complete board Comes fitted with Quick Connect Terminals in complete boards Complies with Standards: DIN VDE 0660, Parts 500, 504 and 504/A 1 SN EN 60439-3 Nominal Voltage: AC 400 V / 50 Hz Current Rating: for devices up to 125A Protection Class: II (insulation protected) IP Rating: IP 30 Protection details: Protection against direct contact: IP3X behind the door Protection with indirect contact: Insulation Protection Air & leakage distance: as per DIN VDE 0110, Part 1 and 2/1.80, according to electrical surge category III, polution Grade 2, Insulation material II and IIIa, nominal voltage AC400V Door: frontal fastening, with internal hinges, all adjustable, removable without tools, optionally attachable on right or left, width from 800mm double door, opening angle 110. Door lock: Twist release lock, exchangeable with other locks, 3 point bar locks on double door cabinet Quick Connect Terminals, built in per field to every complete board Colour: RAL 9010 (pure white) Cable entries: cable entry plates top and bottom made of plastic to feed in the cable from the front. Material Housing and door made of steel, powder coated Carrier Rails: Steel, powdercoted Supports: Plastic Device rails: steel, galvanised Covers and knockouts: plastic

Height (mm) FW31U.. FW32U.. FW33U.. FW41U.. FW42U.. FW43U.. FW51U.. FW52U.. FW53U.. FW54U.. FW61U.. FW62U.. FW63U.. FW64U.. FW71U.. FW72U.. FW73U.. 1100 950 800 650 500

Width (mm) 300 550 1050 300 550 1050 300 550 800 1050 300 550 800 1050 300 550 1050

Depth (mm) 110 110 110 110 110 110 110 110 110 110 110 110 110 110 110 110 110

DIN-Rails (12mod) 3 3 3 4 4 4 5 5 5 5 6 6 6 6 7 7 7

Fields across 1 2 3 1 2 3 1 2 3 4 1 2 3 4 1 2 3

number of mods 36 72 108 48 96 144 60 120 180 240 72 144 216 288 84 168 252

IP-Class (standard) IP30 IP30 IP30 IP30 IP30 IP30 IP30 IP30 IP30 IP30 IP30 IP30 IP30 IP30 IP30 IP30 IP30

74

FW Flush enclosures IP30, Protection Class II M


110 A

FW Flush Cabinets, depth 110mm

Cat. ref.

Recess Dimensions A 305 555 805 305 555 805 305 555 805 1055 305 555 805 1055 305 555 805 B 502 502 502 652 652 652 802 802 802 802 952 952 952 952 1102 1102 1102

Dimension incl. trimming frame C 353 603 853 353 603 853 353 603 853 1103 353 603 853 1103 353 603 853 D 553 553 553 703 703 703 853 853 853 853 1003 1003 1003 1003 1153 1153 1153

B D

22 mm

FW31U.. FW32U.. FW33U.. FW41U.. FW42U.. FW43U.. FW51U.. FW52U.. FW53U.. FW54U.. FW61U.. FW62U.. FW63U.. FW64U.. FW71U.. FW72U.. FW73U..

Door Tr

X2

X2

X2

X1 max 70 mm X2 max 92,5 mm

53 mm

53 mm

75

Consumer Units and enclosures

Вам также может понравиться