A simple and economical solution for resolving the problem of flooding

The CAREL flood prevention system is a device designed to quickly and reliably detect unwanted water leaks, to protect equipment or special environments (computer rooms, offices, laboratories, industrial facilities, boiler rooms). The advantages of the device include easy operation, with no configuration and maintenance required, and simple connection. Simply connect the power supply, the sensor, and the signal device. Typically, the detector is installed in the electrical panel, while the sensor is located in the area being controlled. When the sensor is wet by water, the signal system is activated. Two different types of probes are used, so as to respond to the different requirements of the applications. A network of sensors connected in parallel series can be created so as to control a group of points at the same time with the same detector. This system has an incomparable price/performance ratio, and represents a solution for a large variety of applications, guaranteeing the quality that CAREL has always stood out for.

Technology & Evolution

Detector technical specifications


Power supply: 24 Vac (10%) ~ 50/60 Hz Maximum power input: 1.5 VA Operating conditions: -10T60 C, 95% rH non-cond. Alarm relay output circuit: 250 Vac 2 A resistive, 2 A inductive, cosj= 0.4, 2 (2) A, according to EN60730-1 (100,000 cycles) Maximum length of the probe connection cable: 500 m, with single wire cable and double insulation Cross-section of the connection cable: 1.5 mm2 Standards compliance: CE EN 6000-6-2, EN 6000-6-4 (EMC), EN 61010-1 (safety) Dimensions: 2 DIN modules Index of protection: IP40

Operating status
The front panel has three LEDs that indicate the operating status of the device. Green LED ON power supply present; Yellow LED ON probe not connected to the detector, or line not terminated by 10 K resistor. Red LED ON water present alarm.

Codes and accessories


Flood detector 2 DIN modules Flood sensor Sensor strip L= 25 m
CAREL reserves the right to modify or change its products without prior notice
CAREL S.p.A. 2004 all rights reserved
Cod. +302240501 - rel. 1.0 - 01.10.04

Codes FLOE000010 FLOS000000 FLOR000000

Connection diagram
sonda probe 24 V~ 50/60Hz

A:
1 2 3 4

1 2 3 4
Flooding Sensor Detector

10 K

B:
1 2 3 4

5 6 7 8

FLOS000000 1 FLOE000010

FLOS000000 ...n

CAREL

CAREL

CAREL

CAREL

CAREL

CAREL

C:
1 2 3 4

5 6 7 8

10 K

5 6 7 8
non usato not used N.C. N.O.

FLOE000010

FLOR000000

CAREL

CAREL

10 K

5 6 7 8

FLOS000000 FLOE000010

FLOR000000

Dimensions (mm)
Montage on DIN rail
1 2 3 4
Flooding Sensor Detector

Dimensions of pinhole probe

32
22

80

87

Dimensions of CAREL sensor strip


5 6 7 8
15
CAREL
CAREL
CAREL CAREL CAREL CA

36

60

230

25000

CAREL S.p.A. Via dellIndustria, 11 - 35020 Brugine - Padova (Italy) Tel. (+39) 0499 716611 - Fax (+39) 0499 716600 e-mail: carel@carel.com - www.carel.com

30

Вам также может понравиться