TABLA No.

5
DIMENSIONES DE LOS CONDUCTORES ELECTRICOS DESNUDOS
CALIBRE
AWG o MCM
20
18
16
14
12

SECCIN
CIRCULAR MIL
1 022
1 824
2 583
4 107
6 530

Mm2
0.518
0.823
1.309
2.080
3.310

DIMETRO
PULGADAS
MILIMETROS
0.032
0.812
0.040
1.024
0.051
1.291
0.064
1.628
0.081
2.053

10
8
6
4
2

10 380
16 510
26 250
41 740
66 370

5.260
8.370
13.300
21.150
33.630

0.102
0.129
0.162
0.204
0.258

2.588
3.264
4.115
5.189
6.543

1/0
2/0
3/0
4/0

105 400
133 100
167 800
211 600

53.480
67.420
85.030
107.230

0.325
0.365
0.410
0.460

8.252
9.266
10.403
11.684

250
300
350
400
500

250 000
300 000
350 000
400 000
500 000

126.640
152.000
177.350
202.710
253.350

0.575
0.630
0.681
0.728
0.814

14.605
16.000
17.300
18.490
20.680

600
700
750
800
900

600 000
700 000
750 000
800 000
900 000

304.000
354.710
379.840
405.160
455.810

0.893
0.964
0.998
1.031
1.093

22.680
24.690
25.350
26.190
27.760

1000
1250
1500
1750
2000

1 000 000
1 250 000
1 500 000
1 750 000
2 000 000

506.450
633.060
759.680
886.290
1 012.900

1.152
1.289
1.412
1.526
1.631

29.260
32.740
35.870
38.760
41.420

TABLA No. 6
CAPACIDAD DE CORRIENTE EN AMPERES PARA CONDUCTORES DE COBRE,
AISLADOS Y, PARA UNA TEMPERATURA AMBIENTE DE 30 C.
CALIBRE
TIPOS T, TW, UF (60 C)
THW, THWN, RHW, XHW (75 C)
AWG o MCM
TUBO o DUCTO
EN AIRE
TUBO o DUCTO
EN AIRE
14
15
20
15
20
12
20
25
20
25
10
30
30
30
40
8
40
60
50
70
6
55
80
65
95
4
70
105
85
125
2
95
140
115
170
1/0
125
195
150
230
2/0
145
225
175
265
3/0
165
260
200
310
4/0
195
300
230
360
250
215
340
255
405
300
240
375
285
445
350
260
420
310
505
400
280
455
335
545
500
320
515
380
620
600
355
575
420
690
700
385
630
460
755
750
400
655
475
785
800
410
680
490
815
900
435
730
520
870
1000
455
780
545
935
FACTORES DE CORRECCIN PARA TEMPERATURAS AMBIENTES
MAYORES DE 30 C
31 A 35 C
0.91
0.91
0.94
0.94
36 A 40 C
0.82
0.82
0.88
0.88
41 A 45 C
0.71
0.71
0.82
0.82
46 A 50 C
0.58
0.58
0.75
0.75
51 A 55 C
0.41
0.41
0.67
0.67
56 A 60 C
0.58
0.58
61 A 79 C
0.41
0.41
NOTAS: Para 4 a 6 conductores en un tubo, la ampacidad se reduce al 80% de las cifras
dadas, de 7 a 9 conductores, la ampacidad se reduce al 70% ; al 50% si hay de 10 a 20
conductores y, al 45% si hay de 21 a 30 conductores en un tubo. En un sistema balanceado,
el neutro no cuenta como conductor para los efectos de esta nota.

TABLA No. 7
CAPACIDAD DE CORRIENTE EN AMPERES PARA CONDUCTORES DE COBRE,
AISLADOS Y, PARA UNA TEMPERATURA AMBIENTE DE 30 C
CALIBRE
THHW, RHH, THHN, XHHW (90 C)
VINICON, AVA, AVL (110 C)
AWG o MCM
TUBO o DUCTO
EN AIRE
TUBO o DUCTO
EN AIRE
14
25
35
30
40
12
30
40
35
50
10
40
55
45
65
8
55
80
60
85
6
75
105
80
120
4
95
140
105
160
2
130
190
135
210
1/0
170
260
190
285
2/0
195
300
215
330
3/0
225
350
245
380
4/0
260
405
275
445
250
290
455
315
495
300
320
505
345
555
350
350
570
390
610
400
380
615
420
665
500
430
700
470
765
600
475
780
525
855
700
500
850
560
940
750
535
885
580
980
800
550
900
600
1 020
1000
615
1 055
680
1 165
FACTORES DE CORRECCION PARA TEMPERATURAS AMBIENTES
MAYORES DE 30 C
31 A 35 C
0.96
0.96
0.97
0.97
36 A 40 C
0.91
0.91
0.94
0.94
41 A 45 C
0.87
0.87
0.90
0.90
46 A 50 C
0.82
0.82
0.87
0.87
51 A 55 C
0.76
0.76
0.83
0.83
56 A 60 C
0.71
0.71
0.79
0.79
NOTAS: Para 4 a 6 conductores en un tubo, la ampacidad se reduce al 80% de las cifras
dadas. De 7 a 9 conductores, la ampacidad se reduce al 70% ; de 10 a 20 al 50% y de 21 a
30 al 45%. En un sistema balanceado, el neutro no cuenta como conductor para los efectos
de esta nota.

TABLA No. 8
NUMERO MAXIMO DE CONDUCTORES TIPO T, TW, THW, THHW, XHHW QUE PUEDEN
INSTALARSE EN UN TUBO CONDUIT DE ACUERDO CON LOS FACTORES DE
RELLENO AUTORIZADOS POR LAS NORMAS OFICIALES NOM-001-SEDE.
CALIBRE
CONDUCTOR

13

DIAMETRO NOMINAL DEL TUBO EN MILMETROS


19
25
32
38
51
63
76
89
102 127

14
12
10
8

9
7
5
2

15
12
9
4

25
19
15
7

44
35
26
12

60
47
36
17

99
78
60
28

142
111 171
85 111
40
62

176
84

108

6
4
2

1
1
1

2
1
1

4
3
2

7
5
4

10
7
5

16
12
9

23
17
13

36
27
20

48
36
27

62
47
34

97
73
54

141
106
78

1/0
2/0
3/0
4/0

1
1
1
-

1
1
1
1

2
1
1
1

3
3
2
1

5
5
4
3

8
7
6
5

12
10
9
7

16
14
12
10

21
18
15
13

33
29
24
20

49
41
35
29

1
1

1
1
1
1
1

1
1
1
1
1

2
2
1
1
1

4
3
3
2
1

6
5
4
4
3

8
7
6
5
4

10
9
8
7
6

16
14
12
11
9

23
20
18
16
14

1
1
1

1
1
1
1
1

1
1
1
1
1

3
2
1
1
1

3
3
3
3
2

5
4
4
3
3

7
6
6
5
5

11
9
8
8
7

250
300
350
400
500
600
750
800
900
1000

152

TABLA No. 9
NUMERO MAXIMO DE CONDUCTORES TIPO THWN Y THHN QUE PUEDEN
INSTALARSE EN UN TUBO CONDUIT DE ACUERDO CON LOS FACTORES DE
RELLENO AUTORIZADOS POR LAS NORMAS OFICIALES NOM-001-SEDE.

CALIBRE
CONDUCTOR

13

DIMETRO NOMINAL DEL TUBO EN MILMETROS


19
25
32
38
51
63
76
89
102 127

14
12
10
8

13
10
6
3

24
18
11
5

39
29
18
9

69
51
32
16

94
70
44
22

154
114
73
36

164
104
51

160
79

106

136

6
4
2

1
1
1

4
2
1

6
4
3

11
7
5

15
9
7

26
16
11

37
22
16

57
35
25

76
47
33

98
60
43

154
94
67

137
97

1
1
1
1

1
1
1
1

3
2
1
1

4
3
3
2

7
6
5
4

10
8
7
6

15
13
11
9

21
17
14
12

27
22
18
15

42
35
29
24

61
51
42
35

1
1

1
1
1

1
1
1

3
3
2

4
4
3

7
6
5

10
8
7

12
11
9

20
17
15

28
24
21

1
1

1
1
1

1
1
1

3
2
1

5
4
2

6
5
3

8
7
4

13
11
7

19
16
11

1/0
2/0
3/0
4/0
250
300
350
400
500
750

152

TABLA No. 10
CANTIDAD DE CONDUCTORES QUE PUEDEN ALOJARSE EN UN DUCTO DE LAMINA

CALIBRE
CONDUCTOR
AWG o MCM

SECCIN CONDUCTOR
CON AISLAMIENTO mm2
THWN,
TW, THW
THHN
XHW

14
12
10
8

5.80
7.90
12.30
21.10

8.30
10.64
13.99
26.70

6
4
2

34.20
55.15
77.00

49.29
65.61
89.42

1/0
2/0
3/0
4/0

123.50
147.60
176.70
211.20

143.99
169.72
201.06
239.98

250
300
350
400

261.30
302.60
346.19
384.30

298.65
343.07
386.88
430.05

500
600
750
1000

463.00
572.27
673.91
813.92

514.72
628.70
735.04
934.35

DUCTOS DE LMINA
SECCION TRANSVER. mm2
MEDIDAS
TOTAL
20% TOTAL
EN mm

60 x 60
100 x 100
150 x 150
200 x 200

3 600
10 000
22 500
40 000

720
2 000
4 500
8 000

PARA USAR ESTA TABLA:


1.- Determinar cantidad, tipo y calibre de
conductores a canalizar.
2.- Sumar sus secciones transversales.
3.- Escoger el ducto adecuado, utilizando
la columna del 20% de su seccin - transversal.

TABLA No. 11
RESISTENCIA DE CONDUCTORES CON CORRIENTE DIRECTA, FACTORES DE
CORRECCION AL OPERARLOS CON CORRIENTE ALTERNA POR EL EFECTO PIEL Y,
REACTANCIA AL NEUTRO PARA UNA FRECUENCIA DE 60 HERTZ.
CALIBRE
RESISTENCIA FACTOR DE CORRECCIN
CONDUCTOR C. DIRECTA
POR EFECTO PIEL
AWG o MCM OHMS / 1000
(1)
(2)
14
3.0000
1.000
1.000
12
1.8700
1.000
1.000
10
1.1800
1.000
1.000
8
0.7400
1.000
1.000
6
0.4650
1.000
1.000
4
0.2920
1.000
1.000
2
0.1850
1.000
1.010
1/0
0.1600
1.000
1.020
2/0
0.0920
1.000
1.030
3/0
0.0730
1.000
1.040
4/0
0.0580
1.000
1.050
250
0.0490
1.005
1.060
300
0.0408
1.006
1.070
350
0.0350
1.009
1.080
400
0.0306
1.011
1.100
500
0.0245
1.018
1.130
600
0.0204
1.025
1.160
750
0.0163
1.039
1.210
1000
0.0123
1.067
1.300
1250
0.0098
1.102
1.410
1500
0.0082
1.142
1.530
1750
0.0070
1.185
1.659
2000
0.0061
1.233
1.800

REACTANCIA EN
OHMS / 1000 PIES
MNIMA
MXIMA

0.041
0.040
0.037
0.035
0.034
0.032
0.031
0.030
0.030
0.029
0.029
0.029
0.028
0.028
0.028
0.028
0.028
0.028
0.027
0.027

0.045
0.045
0.050
0.048
0.048
0.044
0.044
0.045
0.044
0.045
0.044
0.043
0.038
0.038
0.035
0.038
0.038
0.038
0.037
0.038

NOTAS: ( 1 ) Conductor en aire o en tubo no magntico.


( 2 ) Conductor en tubo de acero.
Los valores de la reactancia mnima se aplican para conductores juntos dentro de un tubo
o de un ducto.
Los valores de la reactancia mxima se aplican para conductores separados en
instalaciones areas o en mnsulas en galeras de conductores.
Para conductores en ductos o tubos de acero o, con armadura de acero, la reactancia
aumenta en un 25%. Por lo tanto, multiplquense los valores por 1.25.

TABLA No. 12
CAPACIDADES Y DIMENSIONES DE CARTUCHOS FUSIBLES
CAPACIDAD EN
AMPERES
10, 15, 20, 25 Y
30
3, 5, 6, 10, 15,
20, 25 Y 30
35, 40, 45, 50 Y
60
75, 90, 100
125, 150, 175,
200
225, 250, 300
500, 600

250 VOLTS
600 VOLTS
LARGO (mm) DIMETRO(mm) LARGO (mm) DIMETRO(mm)
FUSIBLES TIPO TAPN
---

----FUSIBLES TIPO CASQUILLO

---

53

14

125

19

76

139

26

151

21
FUSIBLES TIPO NAVAJA
30

200

35

181
219
263

42
56
67

244
295
340

47
65
76

TABLA No. 13
CAPACIDAD Y DIMENSIONES DE LOS INTERRUPTORES TERMOMAGNETICOS
MARCO

CAPACIDAD EN
AMPERES

CAPACIDAD
INTERRUPTIVA
240V
480V
600V

No.
DE
POLOS

QL

15, 20, 30, 40, 50,


70, 100

10000

---

---

FA

15, 20, 30, 40, 50,


70, 100

10000

---

---

FB

15, 20, 30, 40, 50,


70, 100, 125, 150

18000

14000

14000

2
3

15.3
15.3

7.0
10.5

8.6
8.6

HFB

15, 20, 30, 40, 50,


70, 100, 125, 150

65000

25000

18000

2
3

15.3
15.3

7.0
10.5

8.6
8.6

25000

22000

22000

25.7

14.0

10.3

42000

30000

22000

25.7

14.0

10.3

65000

35000

25000

25.7

14.0

10.3

42000

30000

22000

27.6

21.0

10.3

42000

30000

22000

41.2

21.0

14.0

125000

100000 100000

56.2

30.5

22.9

42000

30000

22000

125000

100000 100000

25000

22000

15.3

10.5

8.6

LB
LB
HLB
LA
NB
PB
NC (+)
PC (+)
MPC

125, 150, 175,


200, 225
250, 300, 350,
400
125, 150, 175,
200, 225, 250,
300, 350, 400
500, 600
700, 800, 1000,
1200
1400, 1600, 1800
2000, 2500, 3000
800, 900, 1000,
1200
1000, 1200, 1400
1600, 1800, 2000
2500, 3000
3, 7, 15, 30, 50,
100, 150

22000

NOTAS: (+) Interruptores con proteccin electrnica.


MPC: Interruptor magntico instantneo.

1
2
3
1
2
3

DIMENSIONES EN
CENTIMETROS
ALTO
ANCHO FONDO
7.5
2.5
7.3
7.5
5.0
7.3
7.5
7.5
7.3
15.3
3.5
8.6
15.3
7.0
8.6
15.3
10.5
8.6

TABLA No. 14
CORRIENTE A PLENA CARGA DE MOTORES DE CORRIENTE DIRECTA
POTENCIA EN
HP

115 VOLTS

VOLTAJE
230 VOLTS

550 VOLTS

0.50
0.75
1.00
1.50
2.00
3.00

4.6
6.6
8.6
12.6
16.4
24.0

2.3
3.3
4.3
6.3
8.2
12.0

-1.4
1.8
2.5
3.4
5.0

5.0
7.5
10.0
15.0
20.0

40.0
58.0
76.0
112.0
148.0

20.0
29.0
38.0
56.0
74.0

8.3
12.0
16.0
23.0
31.0

25.0
30.0
40.0
50.0
60.0

184.0
220.0
292.0
360.0
430.0

92.0
110.0
146.0
180.0
215.0

38.0
46.0
61.0
75.0
90.0

75.0
100.0
125.0
150.0
200.0

536.0
---------

268.0
355.0
443.0
534.0
712.0

111.0
148.0
184.0
220.0
295.0

TABLA No. 15
CORRIENTE A PLENA CARGA DE MOTORES DE CORRIENTE ALTERNA
MONOFASICOS
POTENCIA EN
HP
1/6

115 VOLTS

VOLTAJES
230 VOLTS

440 VOLTS

3.2
4.6

1.6
2.3

-----

7.4

3.7

---

10.2

5.1

---

1.0

13.0

6.5

---

1.5
2.0
3.0
5.0
7.5
10.0

18.4
24.0
34.0
56.0
80.0
100.0

9.2
12.0
17.0
28.0
40.0
50.0

--------21.0
26.0

TABLA No. 16
CORRIENTE A PLENA CARGA DE MOTORES DE CORRIENTE ALTERNA TRIFASICOS
POTENCIA
HP

MOTORES DE INDUCCIN
220 V
440 V
550 V
2400 V

220 V

MOTORES SNCRONOS
440 V
550 V
2300 V

1/2
3/4
1.0
1.5
2.0

2.0
2.8
3.5
5.0
6.5

1.0
1.4
1.8
2.5
3.3

0.8
1.1
1.4
2.0
2.6

-----------

-----------

-----------

-----------

-----------

3.0
5.0
7.5
10.0
15.0

9.0
15.0
22.0
27.0
40.0

4.5
7.5
11.0
14.0
20.0

4.0
6.0
9.0
11.0
16.0

-----------

-----------

-----------

-----------

-----------

20.0
25.0
30.0
40.0
50.0

52.0
64.0
78.0
104.0
125.0

26.0
32.0
39.0
52.0
63.0

21.0
26.0
31.0
41.0
50.0

--7.0
8.5
10.5
13.0

--54.0
65.0
86.0
108.0

--27.0
33.0
43.0
54.0

--22.0
26.0
35.0
44.0

--5.4
6.5
8.0
10.0

60.0
75.0
100.0
125.0
150.0

150.0
185.0
246.0
310.0
360.0

75.0
93.0
123.0
155.0
180.0

60.0
74.0
98.0
124.0
144.0

16.9
19.0
25.0
31.0
37.0

128.0
161.0
211.0
264.0
---

64.0
81.0
106.0
132.0
158.0

51.0
65.0
85.0
106.0
127.0

12.0
15.0
20.0
25.0
30.0

200.0
250.0
300.0
350.0
400.0

480.0
---------

240.0
300.0
345.0
406.0
475.0

192.0

48.0

---

210.0

168.0

40.0

TABLA No. 17
CAPACIDAD O AJUSTE MAXIMO DEL DISPOSITIVO DE PROTECCION PARA LOS
CIRCUITOS DERIVADOS DE LOS MOTORES

TIPO DE MOTOR

POR CIENTO DE LA CORRIENTE A PLENA CARGA


FUSIBLES
INT. TERMOMAGNTICO
NORMAL
ACC. RET.
INSTANT. TIEMPO INV.

Todos los motores monofsicos o


trifsicos, jaula de ardilla, con
arranque a tensin plena o con
resistencias o reactancias:
LETRA DE CDIGO A
LETRA DE CDIGO B a E
LETRA DE CDIGO F a V
SIN LETRA CDIGO

150
250
300
300

150
175
175
175

700
700
700
700

150
200
250
250

Todos los motores jaula de ardilla y


sncronos
con
arranque
por
autotransformador:
LETRA DE CDIGO A
LETRA DE CDIGO B a E
LETRA DE CDIGO F a V
SIN LETRA DE CDIGO

150
200
250
250

150
175
175
175

700
700
700
700

150
200
200
200

Motores jaula de ardilla de alta


reactancia y no mayores de 30 A.

250

175

700

250

Motores jaula de ardilla de alta


reactancia y mayores de 30 A.

200

175

700

200

Motores de rotor devanado

150

150

700

150

TABLA No. 18
RELACION QUE MUESTRA ALGUNAS DE LAS CAPACIDADES DE LOS ELEMENTOS
TERMICOS UTILIZADOS PARA LA PROTECCION CONTRA SOBRECARGA DE LOS
MOTORES
CAPACIDAD EN AMPERES

CAPACIDAD EN AMPERES

CAPACIDAD EN AMPERES

TAMAOS 0 Y 1

TAMAOS 0 Y 1

TAMAOS 2 A 8

0.167 - 0.187
0.188 - 0.210
0.211 - 0.237
0.238 - 0.266
0.267 - 0.298
0.299 - 0.334
0.335 - 0.376
0.377 - 0.422
0.423 - 0.474
0.475 - 0.532
0.533 - 0.598
0.599 - 0.672
0.673 - 0.757
0.758 - 0.855
0.856 - 0.959
0.969 - 1.070
1.080 - 1.210
1.220 - 1.350
1.360 - 1.520
1.530 - 1.700
1.710 - 1.900
1.910 - 2.100
2.110 - 2.330
2.340 - 2.620
2.630 - 2.930
2.940 - 3.270
3.280 - 3.640
3.650 - 4.060
4.070 - 4.550
4.560 - 5.030

5.040 - 5.590
5.600 - 6.250
6.260 - 6.920
6.930 - 7.750
7.760 - 8.630
8.640 - 9.590
9.600 - 10.60
10.70 - 11.90
12.00 - 13.30
13.40 - 14.70
14.80 - 16.60
16.70 - 18.80
18.90 - 21.20
21.30 - 23.90
24.00 - 27.00

91.80 - 105.0
106.0 - 121.0
122.0 - 135.0
126.0 - 139.0
140.0 - 157.0
158.0 - 175.0
176.0 - 196.0
197.0 - 218.0
219.0 - 243.0
244.0 - 270.0
264.0 - 295.0
296.0 - 330.0
331.0 - 369.0
370.0 - 410.0
411.0 - 458.0
459.0 - 512.0
513.0 - 574.0
550.0 - 607.0
608.0 - 685.0
686.0 - 763.0
764.0 - 855.0
828.0 - 924.0
925.0 - 1 027
1 028 - 1 147
1 148 - 1 285

TAMAOS 2 A 8
24.60 - 27.90
28.00 - 32.00
32.10 - 36.60
36.70 - 41.80
41.90 - 45.00
42.90 - 48.50
48.60 - 55.10
55.20 - 62.30
62.40 - 69.50
69.60 - 79.10
79.20 - 90.00
80.00 - 91.70

TABLA 19
POTENCIA MAXIMA DEL BANCO DE CAPACITORES PARA COMPENSAR FACTORES
DE POTENCIA DE MOTORES TRIFASICOS DE INDUCCION, LIMITANDO EL
FENOMENO DE AUTOINDUCCION.
POTENCIA
MOTOR EN HP

VELOCIDAD DE SINCRONISMO DEL MOTOR EN R. P. M.


3 600
1 800
1 200
900
720
600

10
15
20
25

2.5
2.5
5.0
5.0

4.0
5.0
5.0
7.5

4.0
5.0
5.0
7.5

5.0
7.5
7.5
10.0

5.0
7.5
10.0
10.0

6.5
10.0
12.5
15.0

30
40
50
60
75

7.5
10.0
12.5
15.0
17.5

10.0
10.0
12.5
15.0
17.5

10.0
10.0
12.5
15.0
17.5

10.0
12.5
15.0
17.5
20.0

12.5
15.0
20.0
22.5
27.5

15.0
17.5
22.5
25.0
30.0

100
125
150
200

22.5
25.0
32.5
42.5

22.5
27.5
32.5
42.5

22.5
27.5
35.0
42.5

25.0
30.0
37.5
45.0

35.0
40.0
47.5
60.0

37.5
47.5
55.0
67.5

TABLA No. 20
MULTIPLICADORES DE KW PARA DETERMINAR LOS KVAR EN CAPACITORES, REQUERIDOS
PARA CORREGIR EL FACTOR DE POTENCIA
F. P.
ORIGINA
L

0.91

FACTOR DE POTENCIA CORREGIDO


0.92
0.93
0.94
0.95
0.96

0.90

0.98

1.00

0.56
0.58
0.60
0.62
0.64
0.66
0.68
0.70

0.996
0.921
0.849
0.782
0.717
0.654
0.594
0.536

1.024
0.949
0.877
0.810
0.745
0.682
0.622
0.564

1.054
0.979
0.907
0.840
0.775
0.712
0.652
0.594

1.085
1.010
0.938
0.871
0.806
0.743
0.683
0.625

1.117
1.042
0.970
0.903
0.838
0.775
0.715
0.657

1.151
1.076
1.004
0.937
0.872
0.809
0.749
0.691

1.188
1.113
1.041
0.974
0.909
0.846
0.786
0.728

1.277
1.202
1.130
1.063
0.998
0.935
0.875
0.817

1.480
1.405
1.333
1.266
1.201
1.138
1.078
1.020

0.72
0.74
0.76
0.78
0.80
0.81
0.82
0.83
0.84
0.85

0.480
0.425
0.371
0.318
0.266
0.240
0.214
0.188
0.162
0.136

0.508
0.453
0.399
0.346
0.294
0.268
0.242
0.216
0.190
0.164

0.538
0.483
0.429
0.376
0.324
0.298
0.272
0.246
0.220
0.194

0.569
0.514
0.460
0.407
0.355
0.329
0.303
0.277
0.251
0.225

0.601
0.546
0.492
0.439
0.387
0.361
0.335
0.309
0.283
0.257

0.635
0.580
0.526
0.473
0.421
0.395
0.369
0.343
0.317
0.291

0.672
0.617
0.563
0.510
0.458
0.432
0.406
0.380
0.354
0.328

0.761
0.706
0.652
0.599
0.547
0.521
0.495
0.469
0.443
0.417

0.964
0.909
0.855
0.802
0.750
0.724
0.698
0.672
0.646
0.620

0.86
0.87
0.88
0.89
0.90

0.109
0.083
0.056
0.028

0.137
0.111
0.084
0.056
0.028

0.167
0.141
0.114
0.086
0.058

0.198
0.172
0.145
0.117
0.089

0.230
0.204
0.177
0.149
0.121

0.264
0.238
0.211
0.183
0.155

0.301
0.275
0.248
0.220
0.192

0.390
0.364
0.337
0.309
0.281

0.593
0.567
0.540
0.512
0.484

0.030

0.061
0.031

0.093
0.063
0.032

0.127
0.097
0.066
0.034

0.164
0.134
0.103
0.071
0.037

0.253
0.223
0.192
0.160
0.126

0.456
0.426
0.395
0.363
0.329

0.089
0.048

0.292
0.251
0.203
0.143

0.91
0.92
0.93
0.94
0.95
0.96
0.97
0.98
0.99

EJEMPLO:
Se tiene una carga de 600 kilowatts con un factor de potencia de 0.80, que se desea corregir
a 0.92. Se entra a la columna de factor de potencia original con el dato de 0.80 y, en el
mismo rengln , se busca la constante para corregir el factor de potencia a 0.92,
encontrndose que es 0.324, el cual se multiplica por los 600 kilowatts de demanda. Se
tendr as:
600 * 0.324 = 194.4
siendo el resultado as obtenido, la capacidad del banco de capacitores en KVAR.

TABLA No. 21
FACTORES DE DEMANDA PROMEDIO
TIPO DE SERVICIO
Alumbrado pblico
Apartamentos
Bancos
Bodegas
Casinos
Correos
Escuelas
Garages
Hospitales
Hoteles chicos
Hoteles grandes
Iglesias
Mercados
Multifamiliares
Oficinas
Restaurantes
Teatros
Tiendas
Fbricas de acetileno
Industria automotriz
Talleres de carpintera
Empacadoras de carne
Fbricas de cartn
Fbricas de cemento

F. DEMANDA TIPO DE SERVICIO


1.00
0.35
0.70
0.50
0.85
0.30
0.70
0.60
0.40
0.50
0.40
0.60
0.80
0.25
0.65
0.65
0.60
0.65
0.70
0.70
0.65
0.80
0.50
0.65

Fbricas de cigarros
Fbricas de dulces
Talleres de fundicin
Fbricas de galletas
Fbricas de hielo
Talleres de herrera
Imprentas
Fbricas de jabn
Fb. artculos de lmina
Talleres de niquelado
Madereras
Talleres de marmolera
Talleres mecnicos
Fbricas de muebles
Fbricas de pan
Fbricas de papel
Peridicos
Fbricas de pinturas
Industria qumica
Refineras
Fbricas de refrescos
Industria textil
Fbricas de ropa
Fbricas de zapatos

F. DEMANDA
0.60
0.45
0.70
0.55
0.90
0.50
0.60
0.60
0.70
0.75
0.65
0.70
0.75
0.65
0.55
0.75
0.75
0.70
0.50
0.60
0.55
0.65
0.45
0.45

TABLA NO. 22

TABLA 250-95 SECCIN TRANSVERSAL MNIMA DE LOS CONDUCTORES DE PUESTA


A TIERRA PARA CANALIZACIONES Y EQUIPOS
CAPACIDAD DEL DISPOSITIVO
AUTOMTICO DE SOBRE
CORRIENTE ANTES DEL EQUIPO

15
20
30
40
60
100
200
300
400
500
600
800
1000

SECCIN TRANSVERSAL SECCIN TRANSVERSAL


COBRE
ALUMINIO
mm2
AWG
mm2
AWG
2.082
14
3.307
12
3.307
12
5.260
10
5.260
10
8.367
8
5.260
10
8.367
8
5.260
10
8.367
8
8.367
8
13.300
6
13.300
6
21.150
4
21.150
4
33.620
2
27.670
3
42.410
1
33.620
2
53.480
1/0
42.410
1
67.430
2/0
53.480
1/0
85.010
3/0
67.430
2/0
107.200
4/0