Fire Dampers & Valves

FDC Nominal Size Fire Protection Standard Conformity Fire Classification Tightness of the casing Tightness Smoke Protection Class Operation range Application Masonry & concrete wall Lightweight plasterboard wall Masonry & concrete ceiling Power supply Other Information X X X 230 VAC 3100 Pa 15 m/s 160400 EN 1366-2 EN 13501-3 EIS 30 EIS 120 Class C EN 1751 Class S

FDE 100...500 EN 1366-2 EN 13501-3 EIS15,ES90 E120 Class C EN 1751

FDR 200x200 1000x1000*) EN 1366-2 EN 13501-3 EIS 30 EIS 120 Class C EN 1751 Class S

BSD 100500 BS 476 NT FIRE 010

SSA 150x150 1000x1000 *) BS 476 NT FIRE 010

FRH 100200 BS 476

Class C EN 1751

Class C EN 1751

3300 Pa

2800 Pa 15 m/s

X X X / 230 VAC

X X X 24 VAC/VDC / 230 VAC *) Circular ducts NS 630..1000 *) Modulated units for larger sizes Release at 50 C or 74 C

24 VAC/VDC / 24 VAC/VDC

Halton fire damper range


119

BSD
Fire Damper

Fire damper with non-insulated blade for circular ducts Available thermal fuses: 50, 74, 65, 100, 120, 150 or 200C Classification of casing leakage EN 1751 class C Inlet and outlet spigots include integral rubber gaskets Fire tested to BS 476:part 20:1987 at the Warrington Fire Research Centre, Report No. WARRES 45434. Fire tested to NORDTEST NT FIRE 010 standard, which is the subject of the PAL 2864 a and b Research Reports of the Fire Technology Laboratory of the Technical Research Centre of Finland.

Product model options and Accessories Model with stainless steel (AISI 316) design Model equipped with cleaning access panel Several automatic release and position indication options

MATERIAL AND FINISHING


PART Casing Blade Installation frame Closing springs Duct gaskets MATERIAL Galvanised steel Galvanised steel Galvanised steel Stainless steel MS-polymer NOTE Optional stainless steel AISI 316 Optional stainless steel AISI 316 Optional stainless steel AISI 316

BSD - Fire Damper


120

20/BSD/3500/0606/EN

DIMENSIONS
Sizes 100 - 400
L L1

NS 100 125 160 200 250 315 400 500

L 145 145 145 145 245 245 245 295

L1 110 110 110 110 210 210 210 260

D 99 124 159 199 249 314 399 499

A 160 180 215 255 300 365 450 600

Size 600

600

Product models and Accessories BSD -unit integrated with cleaning access panel RLA (BSD/R) enables removal of the fire damper and access to ductwork for cleaning. The fire damper can be equipped with a bipolar micro switch, which indicates the closing of the shut-off blade. The micro switch has potential free points (no=normally open and nc=normally closed), which can be used to control other fire dampers equipped with an electric release e.g. triggering an alarm in the fire suppression system. The maximum operating voltage and current is 400 V, 10A.
ACCESSORY Installation frame Mesh on one side Mesh on both sides Fuse Micro switch CODE GM N1 N2 FU MS Thermal release at 50, 65, 74, 100, 120, 150 or 200 C Closed position indication/enclosure class IP 65 DESCRIPTION

BSD - Fire Damper


121

20/BSD/3500/0606/EN

Release types The fire damper is always equipped with thermal release. Additional release systems available: Electric signal release, solenoid operation Electromagnetic operation Pneumatic operation with pressurised gas (e.g. CO2). Solenoid operation The fire damper can be released with an electric signal, which is initiated by a smoke detector, micro switch or pressure switch etc. When the circuit is closed, the operating voltage is switched to the magnet and the damper closes. Pneumatic operation The damper is connected to the fire suppression system. When the system is activated, pressure
OPTION Power supply Power consumption (design value) Enclosure IP class (minimum) ED S1 24 VDC 15 W IP 20 100 % S2 230 VAC 40 VA IP20 100 %

Electromagnetic operation The fire damper stays open, when the electric circuit is closed. The damper is shut by opening the circuit. Note: Interruption of power supply will close the damper. Uninterrupted power supply e.g. battery backup system is recommended.

OPTION Power supply Wattage (design value) Enclosure IP class (minimum) ED

EM 24 VDC 15 W IP20 100 %

acting on the pneumatic cylinder releases the spring, allowing the damper to close. The actuator is suitable for common pressure levels used in fire suppression systems. The lowest operating pressure of the actuator is 200 kPa.

Pressure drop data Damper open BSD

BSD - Fire Damper


122

20/BSD/3500/0606/EN

D+23

Function The BSD is a fire damper suitable for circular ducts. The device prevents the spread of fire and smoke in insulated ventilation ducts. In the case of a temperature rise in the ductwork, the thermal fuse releases allowing the springs to close the damper blades. The device can be set and test released, because the thermal fuse is reusable. The outer indicator handle also functions as a position indicator. The BSD is set from outside the device and can be installed in any direction. The nominal fuse release temperatures are +50C or +74C, but +65C, +100C, +120C, +150C or +200C are available for special cases.

Installation CODE DESCRIPTION 1 2 3 4 Fire damper Reusable fuse Installation frame Handle / position indicator

The fire damper is fixed on a compartment wall or in a duct from the installation flange, either directly or with the aid of the GM installation frame. There are no restrictions on the position of use. Check the function of the fire damper before installation. Clean the damper after installation. Set the fire damper by turning the shut-off blade to the desired position with the aid of the indicator handle. Lock the damper by turning the fuse manually.

Servicing A released damper can be reset once the fuse temperature is lower than the release temperature. If the shut-off blade does not lock, the fuse has be worn out and must be replaced.

BSD - Fire Damper


123

20/BSD/3500/0606/EN

Suggested specifications The casing and blades of the fire damper shall be made of galvanised steel (or stainless steel AISI 316) The release spring shall be made of stainless steel. Thermal fuse release temperature shall be as specified, (+50C, +65C, +74C +100C, +120C, +150C or +200C). The fire damper shall have means for opening and triggering the release externally. The fire damper shall comprise a position indicator. Where indicated the damper shall be supplied with the following release option A. Electric signal release by closing circuit (initiated by e.g. smoke detector, micro- or pressure switch). Enclosure class of the electric release arrangement shall be IP 20 or better. B. Electromagnetic release by opening circuit C. Pneumatic release

Product code BSD/S-D S = Model N R Standard With access panel RLA

D = Diameter of duct connection 100, 125, 160, 200, 250, 315, 400, 500

Specifics and accessories FU = Fuse release temperature[C] 50 C, 70 C, 74 C, 100 C, 120 C, 150 C, 200 C

RE = Release type NA S1 S2 EM PN Not assigned Solenoid 24 VDC Solenoid 230 VAC Electromagnetic, 24 VDC Pneumatic

MA = Material CS AS Steel Stainless steel, AISI 316

AC = Accessories GM N1 N2 MS Installation frame Safety mesh 1 side Safety mesh 2 sides Micro switch

Code example BSD/N-100, FU=50,RE=NA,MA=CS

BSD - Fire Damper


124

20/BSD/3500/0606/EN

FDC
Fire Damper for Circular Ducts

Type-approved and compliant with the EN 1366-2 and EN 13501-3 standards For installation in separating concrete and masonry walls and ceilings of fire compartments with fire resistance class EIS 30 EIS 120 Also for installations on lightweight plasterboard walls with a fire resistance class of EIS 30 EIS 120 Manufactured in accordance with the ISO 9001 quality system VTT, the Technical Research Centre of Finland, is responsible for external quality control For installation in circular ducts with diameter 160500 mm Double sealing, ensuring that the blades are tight when the fire damper is closed before and during a fire

Fire damper casing complying with the tightness requirements for Class C, EN 1751 Fire damper tightness meeting smoke damper requirement S of standard EN 1366-2 Suitable for use in ducts with a maximum pressure of 3100 Pa Damper closing tests performed at 15 m/s duct velocity Product models and Accessories Models equipped with either manual or electric actuators Installation frame (GM) for lightweight plasterboard walls

FDC - Fire Damper for Circular Ducts


125

20/FDC/3500/0606/EN

DIMENSIONS
560

D = 160, 200, 250, 315, 400


218 D + 50

When the damper is installed on concrete and masonry walls or ceilings, the size of the installation
D-1

342

hole is D+50 mm When it is installed on lightweight walls, consult the Installation Instructions for the size of the installation holes.

143

D = 500

D 160 200 250 315 400 500

Material and finishing The FDC fire damper casing, installation flange and installation frame are made of galvanised steel. The closing blade is made of calcium silicate and equipped with a flexible silicone seal as well as a graphite mass seal.

Product options and Accessories Actuators Manual actuator, MA (spring return) Belimo BF 24-T2 HI, operating voltage AC/DC 24 V (72 C, contains a microswitch), B1 (Sizes D400D500) Belimo BF 230-T2 HI, operating voltage AC 230 V (72 C, contains a microswitch), B2 (Sizes D400D500) Belimo BLF24-T2 HI, operating voltage AC/DC 24 V (72 C, contains a microswitch), B3 (Sizes D160D315) Belimo BLF230-T2 HI, operating voltage AC 230 V (72 C, contains a microswitch), B4 (Sizes D160D315) Accessories Safety mesh on one side, N1 Safety mesh on both sides, N2 For lightweight wall installation (WT=L), the installation frame (GM) is included in the delivery. Manual actuator accessories Fuse release temperatures, FU = 50 C, 65 C, 72 C, 100 C Limit switches, open and closed position, MS

FDC - Fire Damper for Circular Ducts


126

20/FDC/3500/0606/EN

60 0

Function The FDC is a circular fire damper of fire resistance class EIS 30-EIS 120, which prevents fire and smoke from spreading in ventilation ducts The fire damper is equipped with either a motorised actuator or manual actuation arrangement. In both options, a fuse reacts to a rise in temperature, causing a spring-return blade to close. If the power in the motorised actuator system is switched off, the blade closes automatically. The fire damper is made of fireproof materials. Once the fire damper has closed, the double sealing closes the duct tightly, effectively preventing the spreading of flue gases in the ventilation ductwork. The flexible seal of the double sealing system operates at lower temperatures, while the graphite mass seal expands to insulate the system at temperatures above 150 C. The fire damper is delivered complete with a springreturn actuator and a fuse that is activated at 72 C. The fire damper can also be delivered as a manually operated unit. Both actuators have a visual position indicator. The FDC fire damper can be connected to the MSH control and testing system for fire dampers. The MSH enables the use of smoke detectors in the ductwork or rooms. The FDC fire damper can also be connected to other common building automation systems.

Pressure drop and sound data Sound power level Lw, in in each ocatve band is computed bu adding the corresponding correction factor, Kok, to the sound pressure level in the selection chart according to the following equation. Lw = LpA + Kok The corresponding factor Kok is the average of the FDC operating area.

f / [Hz] kok l / dB

125 13 +/- 2

250 7 +/- 2

500 1 +/- 2

1k -5 +/- 2

2k -7 +/- 2

4k -14 +/- 2

8k -27 +/- 2

FDC - Fire Damper for Circular Ducts


127

20/FDC/3500/0606/EN

Installation Installation on concrete and masonry walls When the fire damper is installed on concrete and masonry walls and ceilings between fire compartments, the blade shaft is always horizontal. An opening is always left in the separating element for the fire damper, and the product is subsequently grouted into this. To make installation easier, all products come with an installation flange, which is used to fasten the fire damper to the concrete surface with screws before grouting. During installation, the fire damper and actuator must be protected with, e.g., a plastic cover. The correct operation of the fire damper must be ensured before and after grouting. When the damper is installed on concrete and masonry walls or ceilings, the size of the installation hole is D+50 mm. Installation on lightweight plasterboard walls When the fire damper is installed on lightweight plasterboard walls between fire compartments, an opening for the fire damper must be left on the plasterboard in which the installation frame (accessory) is first mounted. The blade shaft must always be horizontal. To make installation easier, the fire damper comes with an installation flange, which is used to fasten the fire damper to, e.g., the steel frame of the panel wall. The space between the fire damper and the installation frame is filled with a fire prevention mastic. During installation, the fire damper and actuator must be protected with, e.g., a plastic cover. The correct operation of the fire damper must be ensured after application of the fire prevention mastic. For lightweight walls, the size of the installation hole varies according to the product in question. The size should be chosen on the basis of the size of the installation frame (accessory). Electric actuator wiring diagram
24 VAC / VDC 230 VAC (-) N 1 2 (+) L1 3 4 5 6 7 8 9 10

Detailed installation instructions, as well as an installers installation certificate form, are supplied with each product. See also the Installation Instructions.

S1

S2

S3

S4

S5

S6

80

BF24 BLF24 BF230 BLF230

IP54

Manual actuator wiring diagram (limit switches, MS)

K1

K1

K1

Damper open

Damper driving

Damper closed

K1: 13/14 closed K1: 14/14 open K1:13/14 open K2: 21/22 open K2:21/22 closed K2:21/22 closed Limit switch K1 and K2: Pizzato, type FR 538-HO

FDC - Fire Damper for Circular Ducts


128

20/FDC/3500/0606/EN

Suggested specifications The fire damper of class EIS 30EIS 120 shall have a double sealing solution that ensures fire-gas resistance at all temperatures when the fire damper is closed. The fuse shall be located inside the damper, and it is possible to replace it from the outside. In motorised models, the fuse shall be activated at +72 C. In the manually operated system, the fuse activation temperature corresponds to the specifications (50, 65, 72, 100 C). The fire damper shall have means for external opening / triggering of the release and closing. The fire damper shall include a position indicator. The fire damper shall be suitable for vertical and horizontal installations on concrete and masonry walls and ceilings or lightweight plasterboard walls between fire compartments (EIS 30...EIS 120). The technical properties of the type-approved fire damper shall conform to the EN 1366-2 and EN 135013 standards. The internal quality control of the fire damper manufacturer shall be based on the ISO 9001 quality system. VTT, the Technical Research Centre of Finland, is responsible for external quality control.

Product code FDC/S-D S = Model E S R Europe Sweden Russia

D = Size of duct connection 160, 200, 250, 315, 400, 500

Specifics and Accessories WT = Wall type C L Concrete wall Lightweight wall (installation frame GM)

RE = Release type MA B1 B2 B3 Spring release BF-24-T2 HI fuse 72C (Belimo) (D400...D500) BF-230-T2 HI fuse 72C (Belimo) (D400...D500) Belimo BLF24-T2 HI, operating voltage AC/DC 24 V (72 C, contains a microswitch), (Sizes D160D315) Belimo BLF230-T2 HI, operating voltage AC 230 V (72 C, contains a microswitch), (Sizes D160D315)

B4

FU = Fuse release temperature [C ] 50 C, 65 C, 72 C, 100 C

AC = Accessories N1 N2 MS Safety mesh, 1 side Safety mesh, 2 sides Limit switches

Code example FDC/E-160, WT=C,RE=MA,FU=72

FDC - Fire Damper for Circular Ducts


129

20/FDC/3500/0606/EN

FDE
Fire Damper for Circular Ducts

Type-approved and compliant with the EN 1366-2 and EN 13501-3 standards Installation in separating concrete or masonry walls and ceilings Possibility of installation on lightweight plasterboard walls Fire resistance classes EIS 15, ES 90 and E120. External quality control management by VTT, the Technical Research Centre of Finland Installation in circular ducts with diameter 100500 mm Manufacture in accordance with the ISO 9001 quality standard Fire damper casing complying with the tightness requirements for Class C, EN 1751
MATERIAL AND FINISHING
PART Casing Blade Blade gaskets Installation frame Closing springs Duct gaskets MATERIAL Galvanised steel Galvanised steel Ceramic cloth Galvanised steel Stainless steel 1C-polyurethane hybrid

Inlet and outlet spigots that include integral rubber gaskets Suitability for use in ducts with a maximum pressure of 3300 Pa Product models and Accessories Several automatic release and position indication options Models equipped with either manual or electrical actuators (various types available) Manual fuses available (spring release): 50, 65, 72, 100, 120, 150 or 200 C

FDE - Fire Damper for Circular Ducts


130

20/FDE/3500/0606/EN

DIMENSIONS

When the damper is installed on a concrete or masonry wall or ceiling, the size of the installation
D

Detailed installation instructions, as well as an installers installation certificate form, are supplied with each product.
L1 L2 L3

NS 100 125 160 200 250 315 400 500

D 99 124 159 199 249 314 399 499

L 145 145 145 145 145 145 245 245

L1 105 105 105 105 105 105 135 135

L2 40 40 40 40 40 40 110 110

L3 180 205 240 280 330 395 550 630

Pressure drop and sound data Sound power level Lw, in in each ocatve band is computed bu adding the corresponding correction factor, Kok, to the sound pressure level in the selection chart according to the following equation. Lw = LpA + Kok The corresponding factor Kok is the average of the FDE operating area.

f / [Hz] kok l / dB

125 7 +/- 2

250 1 +/- 2

500 3 +/- 2

1k -3 +/- 2

2k -11 +/- 2

4k -20 +/- 2

8k -27 +/- 2

FDE - Fire Damper for Circular Ducts


131

L3

hole is about D + 50 mm.

20/FDE/3500/0606/EN

ACCESSORIES
ACCESSORY Mesh on one side Mesh on both sides Fuse Microswitch CODE N1 N2 FU MS Thermal release at 50, 65, 72, 100, 120, 150 or 200 C Closed position indication, enclosure class IP 65 DESCRIPTION

The fire damper can be equipped with a bipolar microswitch, which indicates the closing of the shutoff blade. The microswitch has potential-free contacts (no=normally open and nc=normally closed), which can be used to control other fire dampers equipped with an electric release (e.g., triggering an alarm in the fire suppression system). The maximum operating voltage and current is 400 V, 10 A.

Actuators Manual actuator, MA (spring return) Belimo BLF24-T2 HI, operating voltage AC/DC 24 V (72 C, contains a microswitch), B1 Belimo BLF230-T2 HI, operating voltage AC 230 V (72 C, contains a microswitch), B2

Release types The fire damper always has thermal release operation (a fuse). Additional release systems available: Electric signal release, solenoid operation. Electromagnetic operation. Pneumatic operation with pressurised gas (e.g., CO2). Solenoid operation The fire damper can be released with an electrical signal, which is initiated by a smoke detector, microswitch / pressure switch or similar. When the circuit is closed, the operating voltage is switched to the magnet and the damper closes.
OPTION Power supply Wattage (design value) Enclosure IP class (minimum) ED EM 24 VDC 15 W IP20 100 %

Electromagnetic operation The fire damper stays open when the electrical circuit is closed. The damper is shut by opening the circuit. Note: Interruption of the power supply closes the damper. An uninterrupted power supply (e.g., a battery backup system) is recommended.

Pneumatic operation The damper is connected to the fire suppression system. When the system is activated, pressure acting on the pneumatic cylinder releases the spring,

OPTION Power supply Power consumption (design value) Enclosure IP class (minimum) ED

S1 24 VDC 15 W IP 20 100 %

S2 230 VAC 40 VA IP20 100 %

allowing the damper to close. The actuator is suited for common pressure levels used in fire suppression systems. The lowest operating pressure for the actuator is 200 kPa.

FDE - Fire Damper for Circular Ducts


132

20/FDE/3500/0606/EN

The FDE unit is a circular fire damper of fire resistance class EIS 15, ES 90 and E120, which prevents fire and smoke from spreading in ventilation ducts. The fire damper is equipped with either a motorised actuator or a manual actuation arrangement. Under both options, a fuse reacts to a rise in temperature, causing a spring-return blade to close. If the power in the motorised actuator system is switched off, the blade closes automatically. The FDE can be installed in any direction, and setting is performed from outside the device. The fire damper is made of fireproof materials. Once the fire damper has closed, the blade and sealing

close the duct tightly, effectively preventing the spreading of flue gases. The fire damper is delivered complete with a springreturn actuator and a fuse that is activated at 72 C. Alternatively, the fire damper can be delivered as a manually operated unit. The nominal fuse release temperature is 50 or 72 C, but 65, 100, 120, 150 and 200 C are available for special cases. The FDE fire damper can be connected to the MSH control and testing system. The MSH enables the use of smoke detectors in ductwork or in rooms. The FDE fire damper can also be connected to common building automation systems.

Installation There are no restrictions on the position of use.

D1

Product size + about 50 mm

When the fire damper is installed on a concrete or Check the functioning of the fire damper before installation. Clean the damper after installation. Set the fire damper by turning the shut-off blade to the desired position with the aid of the indicator handle. Lock the damper by turning the fuse manually. Installation on masonry walls 1 Screw and fixing plug masonry wall or ceiling between fire compartments, there are no restrictions on the position of use. An opening is always left in the separating element for the fire damper, and the product is subsequently grouted into this. To make installation easier, all products come with an installation flange, which is used to fasten the fire damper to the concrete surface with screws before grouting. During installation, the fire damper and actuator must be protected with, e.g., a plastic cover. The correct operation of the fire damper must be
1

ensured before and after grouting. When the damper is installed on a concrete or masonry wall or ceiling, the size of the installation

FDE - Fire Damper for Circular Ducts


133

20/FDE/3500/0606/EN

Function

hole is about D+50 mm. Installation on lightweight plasterboard walls D1 1 2 3 4 Product size + about 5 mm Fireproof sealing mass Steel frame Plasterboard Mineral wool

with each product. See also Installation Instructions.


~
AC 24 V + DC 24 V
Connect via safety isolating transformer!

S1 S2 S3 S4 S5 S6
1 2

< 5
Tf1 Tf2 Tf3

< 80

BLF24-HI

BAE72A-S

N L1 230 VAC

S1 S2 S3 S4 S5 S6
1 2

< 5
1 2 4 3
Tf1 Tf2 Tf3

< 80

BLF230-HI

BAE72A-S

Electric actuator wiring diagram 5 Screw Manual FDE actuator wiring diagram (limit switch,

When the fire damper is installed on a lightweight plasterboard wall between fire compartments, a small opening for the fire damper must be left in the plasterboard walls. There are no restrictions on the position of use. To make installation easier, the fire damper comes with an installation flange, which is used to fasten the fire damper to, e.g., the steel frame of the panel wall. The space between the fire damper and the plasterboard wall is grouted with fire prevention mastic. During installation, the fire damper and actuator must be protected with, e.g., a plastic cover. The correct operation of the fire damper must be ensured after application of the fire prevention mastic. Set the fire damper manually by turning the shutoff blade to the desired position with the aid of the indicator handle. Lock the damper by turning the fuse manually. If the shut-off blade does not lock, the fuse is worn out and must be replaced. Detailed installation instructions, as well as an installers installation certificate form, are supplied
Damper open Damper closed K1: 13/14 closed K1: 13/14 open 21/22 open 21/22 closed

K1

K1

MS)

FDE - Fire Damper for Circular Ducts


134

20/FDE/3500/0606/EN

Servicing A released damper can be reset after the fuse temperature has fallen below the release temperature. If the shut-off blade does not lock, the fuse is worn out and must be replaced.

Product code FDE-D D = Diameter of duct connection 100, 125, 160, 200, 250, 315, 400, 500

Suggested specifications The casing and blades of the fire damper shall be made of galvanised steel. The release spring shall be made of stainless steel. The thermal fuse release temperature shall be as specified, (50, 65, 72, 100, 120, 150 or 200 C). The fire damper shall have means for opening and triggering the release externally. The fire damper shall include a position indicator. Where indicated, the damper shall be supplied with the following release options: A. Electric signal release by closing circuit (initiated by, e.g., a smoke detector or a microswitch or pressure switch); the enclosure class of the electric release arrangement shall be IP 54 or better. B. Electromagnetic release by opening circuit. C. Pneumatic release.

Specifics and accessories FU = Fuse release temperature 50 65 72 100 120 150 200 50 C 65 C 72 C 100 C 120 C 150 C 200 C

RE = Release type RS = Release type for spring release NA S1 S2 EM PN Not assigned Solenoid, 24 VDC Solenoid, 230 VAC Electromagnetic, 24 VDC Pneumatic MA B1 B2 Spring return BLF24-T2 HI fuse, 72 C (Belimo) BLF230-T2 HI fuse, 72 C (Belimo)

MA = Material AC = Accessories N1 N2 MS Safety mesh, 1 side Safety mesh, 2 sides Microswitch CS Galvanised steel

Code example FDE D-100, FU=50, RE=MA, MA=CS

FDE - Fire Damper for Circular Ducts


135

20/FDE/3500/0606/EN

FDR
Fire Damper for Circular and Rectangular Ducts

Type-approved and compliant with the EN 1366-2 and EN 13501-3 standards For installation in separating concrete and masonry walls and ceilings of fire compartments with fire resistance class EIS 30 EIS 120 For installations on lightweight plasterboard walls with a fire resistance class of EIS 30 EIS 120. Manufactured in accordance with the ISO 9001 quality system VTT, the Technical Research Centre of Finland, is responsible for external quality control For installation in rectangular and circular ducts with diameter 6301,000 mm Available with motorised or manual actuator Double sealing, ensuring that the blades are tight when the fire damper is closed before and during a fire

Fire damper casing complying with the tightness requirements for Class C, EN 1751 Fire damper tightness meeting smoke damper requirement S of standard EN 1366-2 Suitable for use in ducts with a maximum pressure of 2800 Pa Damper closing tests performed at 15 m/s duct velocity Product models and Accessories Models equipped with either manual or electric actuators Installation frame (GM) for lightweight plasterboard walls

FDR - Fire Damper for Circular and Rectangular Ducts


136

20/FDR/3500/0606/EN

DIMENSIONS

B/H: 200, 250, 300, 400, 500...1000 When the damper is installed on concrete and masonry walls or ceilings, the size of the installation hole is B/H + 100 mm When the damper is installed on lightweight walls, the size of the installation hole is B/H + 110 mm

FDR 630 800 1000

BxH 600x600 800x800 1000x1000

D-1 629 799 999

La 266 366 466

Lb 354 454 554

C 52 58 58

L 620 820 1020

L+2xC 724 936 1136

Pressure drop and sound data Sound power level Lw, in in each octave band is computed bu adding the corresponding correction factor, Kok, to the sound pressure level in the selection chart according to the following equation. Lw = LpA + Kok The corresponding factor Kok is the average of the FDR operating area.

f / [Hz] kok l / dB

125 10 +/- 2

250 5 +/- 2

500 0 +/- 2

1k -3 +/- 2

2k -3 +/- 2

4k -11 +/- 2

8k -20 +/- 3

FDR - Fire Damper for Circular and Rectangular Ducts


137

20/FDR/3500/0606/EN

Material and finishing The FDR fire damper casing, installation flange and installation frame are made of galvanised steel. The closing blade is made of calcium silicate and equipped with a flexible silicone seal as well as a graphite mass seal that expands at high temperatures.

Function The FDR is a fire damper of class EIS 30.EIS 120 for circular or rectangular ducts, which prevents fire and smoke from spreading in ventilation ducts. The fire damper is equipped with either a motorised actuator or manual actuation arrangement. In both options, a fuse reacts to a rise in temperature, causing a springreturn blade to close. If the power in the motorised actuator system is switched off, the blade closes automatically. The fire damper is made of fireproof materials. Once the fire damper has closed, the double sealing closes the duct tightly, effectively preventing the spreading of flue gases in the ventilation ductwork. The flexible seal of the double sealing system operates at lower temperatures, while the graphite mass seal expands to insulate the system at temperatures above 150 C. The fire damper is delivered complete with a springreturn actuator and a fuse that is activated at 72 C. The fire damper can also be delivered as a manually operated unit. Both actuators have a visual position indicator. The FDR fire damper can be connected to the MSH control and testing system for fire dampers. The MSH enables the use of smoke detectors in the ductwork or rooms. The FDR fire damper can also be connected to other common building automation systems.

Product options and Accessories Actuators Manual actuator, MA (spring return) Belimo BF 24-T2 HI, operating voltage AC/DC 24 V (72 C, contains a microswitch), B1 Belimo BF 230-T2 HI, operating voltage AC 230 V (72 C, contains a microswitch), B2 Accessories Safety mesh on one side, N1 Safety mesh on both sides, N2 For lightweight wall installation (WT=L), the installation frame (GM) is included in the delivery. Manual actuator accessories Fuse release temperatures, FU = 50 C, 65 C, 72 C, 100 C Limit switches, open and closed position, MS

FDR - Fire Damper for Circular and Rectangular Ducts


138

20/FDR/3500/0606/EN

Installation Installation on masonry walls When the fire damper is installed on concrete and masonry walls and ceilings between fire compartments, the blade shaft is always horizontal. An opening is always left in the separating element for the fire damper, and the product is subsequently grouted into this. To make installation easier, all products come with an installation flange, which is used to fasten the fire damper to the concrete surface with screws before grouting. During installation, the fire damper and actuator must be protected with, e.g., a plastic cover. The correct operation of the fire damper must be ensured before and after grouting. When the damper is installed concrete and masonry walls and ceilings, the size of the installation hole is B/H + 100 mm Installation on lightweight plasterboard walls When the fire damper is installed on lightweight plasterboard walls between fire compartments, an opening for the fire damper must be left on the plasterboard in which the installation frame (accessory) is first mounted. The blade shaft must always be horizontal. To make installation easier, the fire damper comes with an installation flange, which is used to fasten the fire damper to, e.g., the steel frame of the panel wall. The space between the fire damper and the installation frame is filled with a fire prevention mastic. During installation, the fire damper and actuator must be protected with. e.g.. a plastic cover. The correct operation of the fire damper must be ensured after application of the fire prevention mastic. For lightweight walls, the size of the installation hole is B/H+110 mm. The size should be chosen on the basis of the size of the installation frame (accessory). Detailed installation instructions, as well as an installers installation certificate form, are supplied with each product.

Electric actuator wiring diagram


24 VAC / VDC 230 VAC (-) N 1 2 (+) L1 3 4 5 6 7 8 9 10

Manual actuator wiring diagram (limit switches, MS)

K1

K1

K1

S1

S2

S3

S4

S5

S6

Damper open

Damper driving

Damper closed

80

BF24 BF230

IP42

K1: 13/14 closed K1: 14/14 open K1:13/14 open K2: 21/22 open K2:21/22 closed K2:21/22 closed Limit switch K1 and K2: Pizzato, type FR 538-HO

FDR - Fire Damper for Circular and Rectangular Ducts


139

20/FDR/3500/0606/EN

Suggested specifications The fire damper of class EIS 30EIS 120 shall have a double sealing solution that ensures fire-gas resistance at all temperatures when the fire damper is closed. The fuse shall be located inside the damper, and it is possible to replace it from the outside. In motorised models, the fuse shall be activated at +72 C. In the manually operated system, the fuse activation temperature corresponds to the specifications (50, 65, 72, 100 C). The fire damper shall have means for external opening / triggering of the release and closing. The fire damper shall include a position indicator. The fire damper shall be suitable for vertical and horizontal installations on concrete and masonry walls and ceilings or lightweight plasterboard walls between fire compartments (EIS 30...EIS 120). The technical properties of the type-approved fire damper shall conform to the EN 1366-2 and EN 135013 standards. The internal quality control of the fire damper manufacturer shall be based on the ISO 9001 quality system. VTT, the Technical Research Centre of Finland, is responsible for external quality control.

Product code FDR/S-A-W-H S = Model E S R Europe Sweden Russia Specifics and Accessories WT = Wall type C L Concrete wall Lightweight wall (installation frame GM)

A = Type of duct connections R A B C Rectangular Duct connection 630 Duct connection 800 Duct connection 1000 RE = Release type MA B1 B2 Spring release BF-24-T2 HI fuse 72C (Belimo) BF-230-T2 HI fuse 72C (Belimo)

W = Width A=R: 200, 250, 300, 400, 500, 600, 700, 800, 900, 1000 A=A: 600 A=B: 800 A=C: 1000

FU = Fuse release temperature [C ] 50 C, 65 C, 72 C, 100 C

AC = Accessories N1 N2 MS Safety mesh, 1 side Safety mesh, 2 sides Limit switches

H = Height A=R: 200, 250, 300, 400, 500, 600, 700, 800, 900, 1000 A=A: 600 A=B: 800 A=C: 1000

Code example FDR/E-R-200-200, WT=C,RE=MA,FU=72

FDR - Fire Damper for Circular and Rectangular Ducts


140

20/FDR/3500/0606/EN

FRH
Fire Valve

Combined exhaust valve with adjustable pressure loss and fire damper for circular ducts Prevents the spread of fire and flue gases into ventilation ductwork Airflow rate adjustment and measurement facility Release temperature of the fuse is +50C or +74C Fire tested to BS 476:part 22:1987 by the Loss Prevention Council, the subject of FIRTO Technical Evaluation No. TE 6643

Research Reports PAL 3147 and PAL 2268 of the Fire Technology Laboratory of the Technical Research Centre of Finland.

Accessories Installation frame options Wall protection ring

MATERIAL AND FINISHING


PART Collar Central cone Gasket Installation frame Protection ring Finishing MATERIAL Steel Steel Polyurethane Galvanised steel Steel Epoxy-painted White RAL 9010 Special colour available Melting fuse NOTE

FRH - Fire Valve


141

20/FRH/3500/0606/EN

QUICK SELECTION
qv FRH-100 l/s m 3/h LpA D Ptot dP_t FRH-125 LpA D Ptot dP_t FRH-150 LpA D Ptot dP_t FRH-160 LpA D Ptot dP_t FRH-200 LpA D Ptot dP_t LpA values presented with room attenuation 4 dB (red 10m 2 sab). When using room attenuation 8 dB (red 10m 2 - sab): LpA - 4dB. 15 54 13 26 157 20 72 20 46 152 25 90 26 72 161 14 31 207 30 108 30 104 148 19 44 188 40 144 37 184 27 79 165 16 42 140 15 38 176 33 123 145 24 66 130 21 59 160 17 39 147 38 177 31 95 125 27 85 155 21 57 154 36 130 32 116 147 26 77 150 36 152 29 102 154 33 129 155 35 159 50 180 60 216 70 252 80 288 90 324 100 360

LpA A-weighted sound pressure level, reduced by total equivalent absorption surface of 10m 2, dB(A) red 10m 2 - sab D Ptot Total pressure drop, Pa dP_t Maximum D Ptot (Pa), when a-weighted sound pressure level (Lp) is 35 dB(A)

DIMENSIONS
NS 100 125 150 160 200 W 139 165 197 200 251 H 13 13 15 13 13 D 99 124 149 159 199

ACCESSORIES
ACCESSORY Installation frame Installation frame Installation frame Protection ring CODE LF GF DF CS DESCRIPTION Installation frame without gasket, height 50 mm Installation frame with gasket, height 50 mm Installation frame with duct dimensions, can be installed direct to duct parts (bend, T-branch, etc.) For protection of the installation surface from smudging

FRH - Fire Valve


142

77

20/FRH/3500/0606/EN

Function The valve throttles the exhaust airflow and attenuates the duct noise. The pressure drop is dependant on the position of the central cone. The desired exhaust airflow rate is adjusted during the balancing of the airflows in a ductwork system.

Servicing CODE DESCRIPTION 1 2 3 Central cone Locking nut Collar

Loosen the valve from the ductwork by turning antiThe fire damper contains a thermal fuse, which releases the cone to the closed position with the help of a spring. The thermal fuse is released at +50C or at +74C . clockwise. Note the adjusted opening position of the central cone. Wipe the parts with a damp cloth, instead of immersing in water. Reassemble valve in reverse order after cleaning. Adjustment The valve is adjusted by rotating the central cone. Measure the opening (A) position (in mm) of the central cone. Set a probe inside the valve and measure the differential pressure with a manometer. The airflow rate is calculated using the formula below. After the adjustment, lock the central cone with the locking nut. The exhaust valve is mounted with the aid of a separate installation frame LF , GF or DF . Push the installation frame into the duct and fix it. Push the valve into the installation frame and turn until it is firmly attached.
qv = k * $pm

Note: Do not use hot water or hot temperatures during cleaning as this may cause unnecessary release of the fuse.

Installation

Technical data Please refer to URH in the Halton Air Distribution brochure

FRH - Fire Valve


143

20/FRH/3500/0606/EN

Suggested specifications The fire valve shall have an adjustable central cone and collar made of epoxy-painted steel, with white (RAL 9010) as standard colour. The installation frame shall be equipped with a sealing gasket. The fire valve shall be equipped with a thermal fuse and release spring. The opening position of the central cone shall be adjusted during balancing in order to achieve required pressure loss and airflow rate. After balancing the central cone shall be locked into the selected adjustment position.

Product code FRH-D D = Diameter of duct connection 100, 125, 150, 160, 200

Specifics and accessories CO = Colour W X White Special colour

FU = Fuse release temperature[C] 50 C, 74 C

Code example

FRH-100, CO=W,FU=50

Sub products DF GF LF Installation frame for duct parts Installation frame Installation frame

FRH - Fire Valve


144

20/FRH/3500/0606/EN

SSA
Fire Damper

Rectangular curtain fire damper with non-insulated folding blades Available fuses: +50, +72, +65, +100, +150 or +200 C Classification of casing leakage EN 1751 Class C Hot galvanised steel design Fire tested to BS 476:part 20:1987 at the Warrington Fire Research centre, Report No. WRCSI 31470/A SSA-D2 and WRCSA 31470/B SSA Fire tested to NORDTEST NT FIRE 010 standard,

which is the subject of the PAL 2876/73, No PAL 3132 b, No PAL 3132 c Research Reports of the Fire Technology Laboratory of the Technical Research Centre of Finland. Product models and Accessories Several automatic release and position indication options Circular duct connections; inlet and outlet spigots include integral rubber gaskets Large sizes are available with modular design

MATERIAL
PART Casing Curtain blades Closing springs External gaskets Thermal release fuse MATERIAL Galvanised steel Galvanised steel Stainless steel EPDM rubber Brass Only with circular connections D1, D2 Different release temperature options NOTE

SSA - Fire Damper


145

20/SSA/3500/0606/EN

DIMENSIONS
W 100,150,...,1000 H 150,200,...,1000

W-7

75

Special dimensions

H+43

It is possible to have a continuous grille of modular design when the installation length is greater than 1000 mm. The maximum total length is 20 m. Models with circular duct connections SSA/C, CT=D1 & SSA/C CT=D2

W+43

NS 100 125 160 200 250 315 400 500 630 800 1000

W 193 193 243 243 293 443 443 543 643 843 1043

145

H-7

The maximum nominal size is 1000x1000 mm.

75

W1

ACCESSORIES AND PRODUCT MODELS


ACCESSORY Installation frame Mesh on one side Mesh on both sides Fuse Microswitch MS Position Indicator Fastening flange Fastening flanges, 2 pcs CODE GM N1 N2 FU MS PI FL 2FL One side Both sides Thermal release at 50, 65, 72, 100, 150 or 200 C Closed position indication/ enclosure class IP 65 DESCRIPTION

The SSA fire damper can be equipped with a bipolar microswitch (MS), which indicates the closing of the fire damper. The microswitch has potential-free contacts (no=normally open and nc=normally closed),

which can be used to control other fire dampers equipped with an electric release, e.g., triggering an alarm in the fire suppression system. The maximum operating voltage and current is 400 V, 10A.

SSA - Fire Damper


146

20/SSA/3500/0606/EN

145

Release types The fire damper always has a thermal release. Additional release arrangements available: Solenoid operation, electric signal release, contact; normally open (no) Electromagnetic operation, contact; normally closed (nc) Pneumatic operation with pressurised gas (e.g., CO2) Manual release (wire rope) Solenoid operation The fire damper can be released with an electric signal, which is initiated by a smoke detector, microswitch or pressure switch etc. When the circuit is closed, the operating voltage is switched to the solenoid and the damper closes. Pneumatic operation The damper is connected to the fire suppression system. When the system is activated, pressure acting on the pneumatic cylinder releases the spring, allowing the damper to close. The actuator is suitable for common pressure levels used in fire suppression
OPTION Power supply Power consumption (design value) Enclosure IP class (minimum) ED S1 24 VDC 15 W IP 20 100 % S2 230 VAC 40 VA IP20 100 % OPTION Power supply Wattage (design value) Enclosure IP class (minimum) ED EM 24 VDC 15 W IP20 100 %

Electromagnetic operation The fire damper stays open when the electric circuit is closed. The damper is shut by opening the circuit. Note: Interruption of the power supply will close the damper. An uninterrupted power supply - e.g., a battery backup system - is recommended.

systems. The lowest operating pressure of the actuator is 200 kPa. Manual operation Manual release, options for wire rope release.

SSA - Fire Damper


147

20/SSA/3500/0606/EN

Pressure drop data

The SSA is a fire damper suitable for rectangular and circular ducts. The damper prevents the spread of fire and smoke in insulated ventilation ducts. The SSA is suitable for installation either horizontally or vertically so that the blades close downwards. Various release mechanisms are possible. A temperature increase in a ventilation duct causes a thermal fuse release, allowing the springs to close the damper blades. The bottom blade is locked after the curtain has closed, preventing accidental reopening. The standard nominal fuse release temperatures are +50 and +72 C, but release temperatures of +65, +100, +150 and +200 C are available.

Installation Install the damper with the blades in horizontal or vertical position in the ductwork. For vertical installation, note that the blades are to close downwards. Fasten the damper in the ductwork using slip joints or using fastening flanges. Use a seal between the flanges in order to tighten the seam. Fasten the circular connections by riveting or screwing. The damper is installed on a compartment wall or in a duct by use of the fastening flange (AC=FL) or in conjunction with an installation frame (AC=GM, AC =FL) and is set with the aid of the indicator handle (see details in drawing below). When the required dimension exceeds 1000 mm, the damper is constructed in modular form. Modular installations are constructed with a GM frame with the size of the duct opening and FL modules. See the drawing below. To enable checking, cleaning and setting, an inspection panel has to be positioned close to the fire damper. The fuse can be changed by opening the quick-release fastener and attaching the new fusible link in the fastener.

SSA - Fire Damper


148

20/SSA/3500/0606/EN

Function

Product code SSA/S-W-H-D S = Type of duct connection R C Rectangular connections Circular connections CT = Type of circular connection W = Width S=R: 100,+50,..,10000 S=C and D=100: 150 S=C and D=125: 150 S=C and D=160: 200 S=C and D=200: 200 S=C and D=250: 250 S=C and D=315: 400 S=C and D=400: 400 S=C and D=500: 500 S=C and D=630: 600 S=C and D=800: 800 S=C and D=1000: 1000 S=C: 150 MA = Material H = Height S=R: 150,+50,..,10000 S=C: W AC = Accessories D = Diameter of duct connection S=C: 100, 125, 160, 200, 250, 315, 400, 500, 630, 800, 1000 MS GM N1 N2 PI FL Micro switch Installation frame Safety mesh one side Safety mesh two sides Position indicator Fastening flange CS Steel RE = Release type NA MA S1 S2 EM PN Not assigned Manual S1=Solenoid 24 VDC Solenoid 230 VAC Electromagnetic 24 VDC Pneumatic FU = Fuse release temperature[C] 50 C, 65 C, 72 C, 100 C, 150 C, 200 C D1 D2 1 circular connection 2 circular connections Specifics and accessories

Code example SSA/R-150-150, FU=50,RE=NA,MA=CS

SSA - Fire Damper


149

20/SSA/3500/0606/EN

MSH
Fire Damper Management System

Smoke detector, room installation

Smoke detector, duct installation

Used with motorised fire dampers FDR, FDC and FDE (operating voltage: 24 V) Controls the shut-off operation of fire dampers when a fire breaks out Enables time-controlled, external or manual testing of fire damper operation Smoke detectors able to be directly connected to the MSH management units Locks the fan during testing of operation and in fire scenarios Outputs for remote fire and service alarm indication Local alarm indication for fire and service alarm conditions Easy implementation

Control unit models Control unit for eight (8) or sixteen (16) fire dampers Control unit with or without smoke detector operation Smoke detectors can be connected to models MSH/2 and MSH/4. Transformer and fire indication from fire alarm system of the buiding for power supply are included in the delivery.

Smoke sensors Smoke detectors for duct and room installation Smoke detectors equipped with optical or ionising function

Type MSH/1 MSH/2 MSH/3 MSH/4

Max. Number of dampers 8 8 16 16

Max. Number of smoke detectors 30 30

Code MSH/A MSH/B MSH/C MSH/D

Type Smoke detector: duct, optical Smoke detector: room, optical Smoke detector: duct, ionising Smoke detector: room, ionising

Manufacturer Calectro Calectro Calectro Calectro

Model ST-P-DA, L= 600 mm UG-2-O ST-I-DA, L = 600 mm UG-2-J

MSH - Fire Damper Management System


150

20/MSH/3500/0606/EN

The MSH fire damper management system has three important functions: 1. close the fire dampers when a fire breaks out 2. regularly test the fire dampers to ensure that they are in operational condition 3. ensure that the fire dampers are open in normal conditions and that ventilation can operate as planned Fire Each fire damper is equipped with a thermal fuse, which closes the damper when the temperature rises above 72 C. If any of the thermal fuses is released, all the fire dampers connected to the MSH unit are immediately closed. If the system is equipped with smoke detectors, all fire dampers connected to the MSH unit in question are immediately closed to the safety position when the smoke detector indicates an early fire.

The MSH system regularly tests the operation of the fire dampers to ensure that they operate correctly should a fire break out. The testing can be timecontrolled and set to take place at desired intervals (1 to 9 days) for example, every other day. To test the system, the MSH unit sends a switch-off command to the air handling unit control system. When the fan stops, the MSH unit closes the fire dampers to the safety position and ensures that all the fire dampers are closed. After that, all dampers are reopened and the fan is able to start again. If an error is detected in the operation of any of the dampers, the MSH system issues a service alarm.

Product codes MSH/S S = Construction / component 1 = Unit for eight (8) fire dampers, no smoke detector connection 2 = Unit for eight (8) fire dampers, smoke detector connection Calectro ABAV-S3 3 = Unit for sixteen (16) fire dampers, no smoke detector connection 4 = Unit for sixteen (16) fire dampers, smoke detector connection Calectro ABAV-S3 A = Smoke detector: duct, optical Calectro: ST-P-DA, L= 600 mm B = Smoke detector: room, optical Calectro: UG-2-O C = Smoke detector: duct, ionising Calectro: ST-I-DA, L = 600 mm D = Smoke detector: room, ionising Calectro: UG-2-J

User interface The operational status of the fire dampers and any alarms are visible on the MSH units operator panel at a single glance. The operator panel is also used to set the time-controlled testing parameters, start manual testing and acknowledge service notification as well as operation in the event of a fire.

MSH 1-8-8-MC
Test Total Fire Service Closed Open Fan Reset Set Hour Min Set Day

MSH - Fire Damper Management System


151

20/MSH/3500/0606/EN

Operation

Testing of fire dampers