A-Series

Features
Din sized enclosure for Track / Screw mounting Front terminal protective cover For A1DA : External potential free contacts (Zero Volt) for timing initiation of 150 mSecs. For A1DS : Star to Delta transfer time delay of 40msec / 100msec, user selectable. For A1DH-1 : Relay energizes on application of power and continues to remain 'ON' even after removal of power till completion of set time (set time starts on removal of power) : Minimum 2sec energization time required, else timer may malfunction.

Electronic Timers

Ordering Information
Model Function Source Voltage
9V to 30V DC

Time Range
0.3 Secs to 30 Mins. 18 Secs to 180 Secs. 3 Secs to 30 Secs. 0.3 Secs to 30 Mins. 0.6 Secs to 60 Secs. 18 Secs to 180 Secs.

Output
2 c/o Relay 2 c/o Relay 1 c/o Relay 1 c/o Relay 1 c/o star, 1c/o delta Relay 2 c/o Relay*

A1D1(9V to 30V DC) On-Delay A1D1 (SR) A1D1 (WB) A1DA A1DS A1DH-1 On Delay (Single Range) On Delay (Wide Band) Signal Off-Delay Star Delta Timer Power Off Delay

12V DC 266V to 456V AC 240V AC / 110V AC 240V AC / 110V AC 240V AC

* Contact rating 500mA @ 250V AC/28V DC

Timing Diagram
a) A1DA
Power A1-A2 Potential free Start NO NC 150msec 25-26 15-18 15-16 t1 t2

Specifications
Operating Voltage Range -20% to +10% of the rated voltage(A1DH-1,A1DS) -10% to +10% of the rated voltage for A1D1(SR) -30% to+20% of the rated voltage. for A1D1(WB)on 380V AC for A1D1( 9 to 30V DC) min. = 9V, max. = 30V DC Rated Frequency Control Output 50 Hz 5% , NA for DC operated Models 5A @ 250V AC / 28 V DC resistive load . 0.5A @ 250V AC / 28 V DC resistive load for A1DH-1 5A @ 250V AC / 28 V DC resistive load, 1A @ 415V AC resistive load for A1D1 (WB) Setting Accuracy Repeat Accuracy 10% max. w.r.t full scale 100mSec 1% max. 100mSec; 2% max. 100mSec for A1DH-1 100mSec minimum, 400mSec minimum for A1D1(WB); 150mSec minimum for A1DS, NA (A1DH-1) Rated Frequency of operation 1800 5% operations per hour max; 180 5% operations per hour max for A1DH-1 Variation due to voltage change
ts

t1+t2=ts:Set time

b) A1DS
Power A1-A2

Recovery Time

NO

15-18

Star contact

2%max 100mSec 5%max. 100mSec 2%max. 100mSec, NA for DC operated Models. Operation:-10 to +55C, Storage: -25 to +80C Max 85% RH @40C 106 operations minimum (under no load) 10 operations minimum (under full load) Screw type terminals with self lifting clamps AC approx. 10VA / 2W [A1DH-1, A1DA, A1DS(110V AC)] DC approx. 2W for A1D1(9 to 30V DC) & A1D1(SR)
5

Variation due to temp. change


td Delta Contact

NO

25-28

Variation due to freq. change Ambient temperature

ts: Star time td: Transfer time=40 or 100msec

Humidity Service Life

c) A1DH-1
Power A1-A2

Electrical Life Connections Power Consumption

NO 15-18 , 25-28 15-16 , 25-26 NC ts: Set Time

AC approx.15VA/3W A1DS(240V AC),20VA/4W for A1D1(WB) Insulation Resistance


ts

>100M ohms @ 500V DC 3% max for A1D1(9 to 30V DC), 2% max. for A1D1(SR) 0.5% max for every 1C only for A1DH-1 2 Sec minimum for A1DH-1 Refer Page Number 57 (non CSA product) Min 150msec (Potential free) for A1DA A1DS: 6s, 60s. Transfer time:40ms / 100ms 10ms A1D1(9 to 30V), A1DA: 3s, 30s, 3m. 30m A1DH-1, A1D1(SR):180s

Allowable Ripple Temperature Coefficient

d) A1D1(9-30VDC ), A1D1(SR) & A1D1(WB)*


Power A1-A2 NO NC 15-18, 25-28 15-16, 25-26 ts ts: Set time

Minimum Energization Time Dielectric strength Start Signal Time Range selection

A1D1(WB)NO-15-18,NC-15-16(Single C/o) Timer resets on power failure except A1DH-1

A1D1(WB):30s Dimensions 22.5 x 75 x 96.5mm [W x H x D]

Connections
A1D1, A1D1 (SR) (WB)

SS*

Start Signal*

Dimensions

Windows for Range set

Accessories
Protective Cover The protective cover shields the front panel, particularly the timer setting section from dust, dirt and as well as prevents the set value from being altered due to accidental contact with time setting knob.

Hints on correct use


Change the positions of range selector slide switches on the left hand side of the timer & rotate the pot to get desired time setting with the flat blade screw driver.

Caution
Do not change the time range & set time while the timer is in operation. Switch off the power while changing the time range & set time. Application of voltage other than the specified one will permanently damage the timer. Use 2.5mm2 U-type lugs with sleeve.

*Technical Specifications are subject to change without prior notice